Attachment 7 - Drawings 4 of 4.pdf

PDF 5 MB Posted

Attached to
Y1DZ--EHRM Training and Admin Space Support Construction - Milwaukee, WI 695-21-703 Federal contract opportunity
Solicitation number
36C77622B0017
Issued by
Department of Veterans Affairs Technology Acquisition Center Austin

About this file

This Invitation for Bid (IFB) solicits proposals for the construction of an EHRM Training and Administrative Space Support project located in Milwaukee, Wisconsin. Key details include:

  • The scope of work includes construction services for renovating approximately 5,000 square feet of existing office and training space to support EHRM programs. Specific requirements include interior demolition, new walls, doors, flooring, ceilings, mechanical and electrical systems.

  • The estimated cost of construction is between $1-5 million. The contract will be a firm-fixed-price award with a one year period of performance.

  • The solicitation was issued by the Department of Veterans Affairs Technology Acquisition Center located in Austin, Texas. Proposals are due by February 24th, 2022 and the contract is expected to be awarded by April 2022.

  • The solicitation is set aside for Service-Disabled Veteran Owned Small Businesses. The incumbent contractor was not identified.

  • The supporting documents include plans, specifications and other requirements applicable to the construction work.

View the file

Other files for this federal contract opportunity

Other files attached to Y1DZ--EHRM Training and Admin Space Support Construction - Milwaukee, WI 695-21-703, newest first.
File Type Posted
36C77622B0017 0005.pdf PDF
Technical Questions - Milwaukee EHRM 3-28-22.pdf PDF
Attachment 13 - Construction Wage Rates - Milwaukee County - 03-18-22.pdf PDF
Technical Questions - Milwaukee EHRM 3-23-22.pdf PDF
MP104 - SECOND AND THIRD FLOOR - C WING - MECHANICAL PIPING PLAN.pdf PDF
MH102 - FIRST FLOOR - C WING - MECHANICAL HVAC PLAN.pdf PDF
MM500 - MECHANICAL DETAILS.pdf PDF
MP103 - FIRST FLOOR - C WING - MECHANICAL PIPING PLAN.pdf PDF
MH100 - BASEMENT - C WING - MECHANICAL HVAC PLAN.pdf PDF
36C77622B0017 0004.pdf PDF
Drawing Changes 3-23-22.pdf PDF
MH103 - SECOND AND THIRD FLOOR - C WING - MECHANICAL HVAC PLAN.pdf PDF
MM600 - MECHANICAL SCHEDULES.pdf PDF
MM700 - MECHANICAL CONTROL SYSTEMS.pdf PDF
36C77622B0017 0003.pdf PDF
Question 64 Third Floor Structural.pdf PDF
Question 69 Section Through A Wing North.pdf PDF
Technical Questions - Milwaukee EHRM 3-14-22.pdf PDF
Question 93 C-wing north roof.JPG JPG image
Question 74 Porch Detail.pdf PDF
36C77622B0017 0002.pdf PDF
Attachment 13 - Construction Wage Rates - Milwaukee County - 02-25-22.pdf PDF
36C77622B0017 0001.pdf PDF
Attachment 13 - Construction Wage Rates - Milwaukee County - 02-18-22.pdf PDF
Site Visit Sign-in Sheet - Milwaukee 2-23-22.pdf PDF
Attachment 5 - Drawings 2 of 4.pdf PDF
Attachment 8 - Contractor Core Work Hours.pdf PDF
Attachment 11 - Brand Name Justification - Milwaukee.pdf PDF
IFB - 36C77622B0017 - 2-10-22.pdf PDF
Attachment 3 - Final SOW - 1-27-22.pdf PDF
Attachment 14 - Contractor Safety - Environmental Form.docx DOCX document
Attachment 2 - Specifications Volume 2.pdf PDF
Attachment 9 - COVID-19 Safety Protocols 12-14-21.pdf PDF
Attachment 4 - Drawings 1 of 4.pdf PDF
Attachment 10 - Limitations on Subcontracting - Construction.docx DOCX document
Attachment 13 - Construction Wage Rates - Milwaukee County - 02-04-22.pdf PDF
Attachment 15 - Milwaukee VAMC Map - EHRM Site Visit.pdf PDF
Attachment 1 - Specifications Volume 1.pdf PDF
Attachment 6 - Drawings 3 of 4.pdf PDF
Attachment 12 - NESHAP Asbestos Survey.pdf PDF
Show all 40

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

D

D D

OS

OS

D

DL

DL

DL

DL

D

D

DL

DL

D D

OS

OS

OS

S

3S

OS

S

D D

D D

OS

S

OS

D

D

OS

OS

OS

OS

OS

D D

D

D

OS

DL

OS

OS

OS

OS

OS

OS

D D

OS

OS

OS

B D

BUILDING 6 FIRST FLOOR KEY PLAN

N

SHADE INDICATES AREA

NOT IN SCOPE, TYP

NO SHADE INDICATES

LOCATION OF PROJECT,

TYP

A

SOUTH

C

SOUTH

C

NORTH

A

NORTH

LIGHTING GENERAL NOTES

A. REFER TO SHEET E000 FOR ELECTRICAL SYMBOL LEGENDS AND

ABBREVIATIONS.

B. REFER TO SHEET EP602 FOR LIGHT FIXTURE SCHEDULE AND PANEL

SCHEDULES.

C. ELECTRICAL ITEMS SHOWN LIGHT WITH A SOLID LINETYPE AND LABELED (E)

ARE EXISTING TO REMAIN UNLESS NOTED OTHERWISE.

D. ELECTRICAL ITEMS SHOWN BOLD WITH A SOLID LINETYPE ARE NEW UNLESS

NOTED OTHERWISE.

E. CONNECT NIGHT LIGHTS "NL", EXIT SIGNS AND EMERGENCY LIGHTS "EM"

AHEAD OF ALL SWITCHING, UNLESS NOTED OTHERWISE. PARTIAL SHADING OF

A LIGHT FIXTURE DESIGNATION INDICATES EMERGENCY / EGRESS

LIGHTING OR NIGHT LIGHTING.

F. ALL AREAS WHERE AN OCCUPANCY SENSOR IS SHOWN ON THE DRAWINGS

SHALL BE PROVIDED WITH 100% COVERAGE OF THAT AREA WITH

OCCUPANCY SENSING OF THE TECHNOLOGY TYPE SHOWN OR NOTED.

G. MULTIPLE LIGHT SWITCHES/DIMMERS SHALL BE GANGED IN A SINGLE NEMA

RATED BOX UNLESS NOTED OTHERWISE.

H. ALL WALL DEVICES AND COVER PLATE COLORS TO BE SELECTED BY

ARCHITECT.

I. ALL AFFECTED PANELS SHALL HAVE UPDATED TYPED, COMPLETED

DIRECTORIES INDICATING EQUIPMENT SERVED AND ROOM NUMBER (AS

INDICATED ON FINAL BUILDING ROOM SIGNAGE) OF EQUIPMENT LOCATION,

OR SPARE, OR SPACE. HAND WRITTEN DIRECTORIES WILL "NOT" BE

ACCEPTED.

J. RE-SUPPORT EXISTING SYSEM COMPONENTS NOT PROPERLY SUPPORTED

AFTER DEMOLITION AND NOT SCHEDULED FOR WORK.

LIGHTING PLAN NOTES

1. ALL LIGHTING AND LIGHTING CONTROLS IN THIS ROOM ARE EXISTING TO

REMAIN UNLESS OTHERWISE NOTED. ALL LIGHTING THAT REMAINS TO BE

CLEANED AND FLUORESCENTS TO BE RELAMPED.

2. PROVIDE RECESSED LED LIGHTING AND CONNECT TO THE CIRCUIT AND

LIGHTING CONTROLS SHOWN.

3. PROVIDE RECESSED LED DOWNLIGHT AND CONNECT TO THE CIRCUIT AND

LIGHTING CONTROLS SHOWN.

4. PROVIDE COMPATIBLE 0-10V LED WALL DIMMER FOR CONTROL OF THE

"NORMAL" LED LIGHTING IN THIS ROOM.

5. PROVIDE CEILING MOUNTED DUAL-TECHNOLOGY OCCUPANCY SENSOR TO

CONTROL ALL "NORMAL" LIGHTING IN THIS SPACE. PROVIDE 100%

COVERAGE. SET TO MAX TIME DELAY AND MAX SENSITIVITY. PROVIDE

(POWER PACK) FOR OCCUPANCY SENSOR ABOVE NEAREST ACCESSIBLE

CEILING. PENDANT MOUNT IN AREAS WHERE REQUIRED, COORDINATE FINAL

LOCATION WITH OTHER TRADES.

6. PROVIDE LED EXIT SIGNAGE AND CONNECT TO CIRCUIT SHOWN.

7. PROVIDE 3-WAY TOGGLE TO CONTROL OF THE "NORMAL" LED LIGHTING IN

THIS ROOM OR AREA.

8. PROVIDE A VACANCY WALL SWITCH SENSOR WITH DUAL-TECHNOLOGY, EQUAL

TO NLIGHT BRAND, TO CONTROL THE "NORMAL" LED LIGHTING IN THIS ROOM

OR AREA. SET TO 30 MINUTE TIME DELAY, MANUAL "ON" / AUTO OFF.

9. PROVIDE LINEAR LED LIGHT AND MOUNT BOTTOM OF LIGHT 9'-0" A.F.F.

PROVIDE ALL MOUNTING ACCESSORIES REQUIRED. COORDINATE FINAL

LOCATION WITH ALL TRADES PRIOR INSTALL. CONNECT TO CIRCUIT AND

LIGHTING CONTROLS SHOWN. ROUTE 0-10V DIMMING WIRES IN CONDUIT WITH

600V CONDUCTORS.

10. PROVIDE LINEAR LED STAIR LIGHT AND MOUNT 7'-6" A.F.F. TO CENTER OF

LIGHT FROM STAIR LANDING.

11. PROVIDE A CEILING MOUNTED DAYLIGHT HARVESTING SENSOR, NLIGHT

#NCM=ADCX OR EQUAL, FOR DIMMING THE DESIGNATED LIGHTING ON A

"NORMAL" CIRCUIT PER ASHRAE 90.1. PENDANT MOUNT TO SAME HEIGHT

AS BOTTOM OF LIGHTING IN SPACES WHERE APPLICABLE.

12. PROVIDE A LINEAR LED LIGHT AND WALL MOUNT 6-INCHES CENTER ABOVE

MIRROR. CONNECT TO CIRCUIT AND LIGHTING CONTROLS SHOWN.

13. PROVIDE EMERGENCY LIGHT AND WALL MOUNT 7'-6" A.F.F. TO BOTTOM OF

LIGHT AND CONNECT TO CIRCUIT SHOWN.

14. PROVIDE LED UNDERCOUNTER LIGHTING, CONTROLLED VIA INTEGRAL ROCKER

SWITCH, AND MOUNT CENTERED UNDER CABINET.

15. PROVIDE A SURFACE MOUNT EMERGENCY / SECURITY LED LIGHT CENTERED 6-

INCHES ABOVE DOOR FRAME OR GLASS HEADER. CONNECT TO CIRCUIT

SHOWN. LIGHT CONTROLLED BY INTEGRAL PHOTOCELL.

B -W

IN

G

C -W

IN

G

C -W

IN

G

D -W

IN

G

TRAINING

C148

TRAINING

C145

TRAINING

C143

TRAINING

C146

CORRIDOR

C140

TRAINING

C144

TRAINING

C141

WAITING

C142

WAITING

C124

ELEV. LOBBY

C120

ELEV.

C2-P

WOMENS RR

C119-A

MENS RR

C119-B

BREAK AREA

C118

TRAINING

C106-C

IT ROOM

C118-B

STAIR C2

C2

CIRC.

C116

STORAGE

C119-C

STAIR

C4

P18 P18

P24 P24

(TYPICAL)

9(TYPICAL)

P20

P18 P18

4 (TYPICAL)

W4

X1B X1B

EM2 EM2

D2

D2

D2

D2

Z4 Z4

10(TYPICAL)

11 (TYPICAL)

a b a,bc a a,b a,b a b a a b a a,b a,b

EM2

A4 A4

D2

D2

D2

D2

D2

D2

D2

D2

D2

D2

D2

D2 a

A3 a a a,b

A4

A4

A4 A4 a b

A4 A4 a a a

D1

EM2

D1 D1

EM2

MECHANICAL

C126

D1

D1

D1

D1

D1

D1

D1

D1

X1B

X1B

(TYPICAL)

(TYPICAL)

6(TYPICAL)

7 (TYPICAL)

D1

EM2

J4 J4

J4 J4

X1B

EM2

EM2

EM2

a b a b

SECURITY

C118-A

CONFERENCE ROOM

C124-A

LIGHTWELL

C----

D1 D1

D1 D1

D1

A3 a a b b D1 a

J4

J4

ELEV. MACHINE.

C121

D1

UL-C1-6-4

UL-C1-6-2

13(TYPICAL)

D1D1 D1

D1D1D1D1

D1D1D1D1

D1D1D1

D1

D1D1

D1

A2

A2

A2

A2

A2

A2

A2

A2

A2

UL-C1-6-3

X1B

D1

EM2

D1 D1 D1 D1

D1 D1 D1 D1

EM2

EM2

NL

14 (TYPICAL)

UC2

UC2

a b

W4

X1B C1-4:6C1-4:6

C1-4:6

P20 a

C1-4:6

C1-4:2

C1-4:2

C1-4:2 C1-4:2

C1-4:2

C1-4:2

C1-4:2

C1-4:2

C1-4:2

C1-4:2

C1-4:2

C1-4:2

C1-4:2

C1-4:2

C1-4:2

C1-4:2

C1-4:2 C1-4:2

C1-4:2

C1-4:2 C1-4:2

C1-4:2

EM2

C1-4:2

C1-4:2 C1-4:2 C1-4:2 C1-4:2

C1-4:2C1-4:2C1-4:2C1-4:2

C1-4:2 C1-4:2

C1-4:2 C1-4:2

C1-4:2

C1-4:2

C1-4:2

C1-4:2

C1-4:2

C1-4:2 C1-4:2 C1-4:2

C1-4:2

C1-4:2C1-4:2C1-4:2C1-4:2C1-4:2

C1-4:2 C1-4:2 C1-4:2 C1-4:2 C1-4:2

C1-4:2C1-4:2C1-4:2

C1-4:2 C1-4:2 C1-4:2

C1-4:2

C1-4:2

C1-4:2

C1-4:2 cc c c c c c c c

C1-4:4C1-4:4

C1-4:4 C1-4:4 c

C1-4:2

C1-4:2

C1-4:8

C1-4:8

C1-4:8

C1-4:8 C1-4:8 C1-4:8

C1-4:8C1-4:8

C1-4:8

C1-4:8 C1-4:8

C1-4:8 C1-4:8

C1-4:8C1-4:8

C1-4:8 C1-4:8

C1-4:8C1-4:8

C1-4:8 C1-4:8

C1-4:8

C1-4:8 C1-4:8

C1-4:8C1-4:8

C1-4:8 C1-4:8

C1-4:8

C1-4:8

C1-4:8C1-4:8

C1-4:8C1-4:8

C1-4:8

C1-4:8 C1-4:8

C1-4:8C1-4:8 C1-4:8 C1-4:8

C1-4:8C1-4:8

C1-4:8 C1-4:8 C1-4:8 c c c c c c c ddd d d d d dd d d d d e e e e e ee e e e e e ee e e e e

(TYPICAL)

d

CORRIDOR

C140

D1

D1

NL

C1-4:2

C1-4:2

NL

EP300

J4 J4 C1-4:8 C1-4:8

X1B C1-4:2 a,b A4

A4

A4 b,c C1-4:8

C1-4:8

C1-4:8 c a a a a,b c b,c c b,c c c b,c c b,c b,c b,c

XW1

CB4:2

P18 P18 a

C1-4:4 C1-4:4 b,c

P18 P18 a

C1-4:6C1-4:6 b,c a b c c c d d e e e

B -W

IN

G

C -W

IN

G

C -W

IN

G

D -W

IN

G

CIRC.

C116

CORRIDOR

C115B

CORRIDOR

C115A

CORRIDOR

B/C

STAIR

C106

ELEV. EQUIP.

CB11

W4

EM2

EM2

W4

C3-2:1

C3-2:1

C3-2:1

C3-2:1

X1B C3-2:1

PANELBOARD NAMEPLATE ABBREVIATION LIST

NOTE: THE FOLLOWING PANELBOARDS ARE ABBREVIATED FOR CIRCUITING PURPOSES.

FULL PANEL NAME TO BE PUT ON FRONT OF PANEL "NOT" ABBREVIATED NAME.

BUILDING 6 BASEMENT FLOOR PANELS

1. CBA = CBA

2. UL-CB-6-2 = CB2:

3. UL-CB-6-3 = CB3:

4. UL-CB-6-4 = CB4:

5. UL-CB-6-5 = CB5:

BUILDING 6 FIRST FLOOR PANELS

1. UL-A1-6-1 = A1-1:

2. UL-A1-6-2 = A1-2:

3. UL-A1-6-3 = A1-3:

4. UL-B1-6-1 = B1-1:

5. UL-B1-6-2 = B1-2:

6. UL-C1-6-2 = C1-2:

7. UL-C1-6-3 = C1-3:

8. UL-C1-6-4 = C1-4:

BUILDING 6 THIRD FLOOR PANELS

1. UL-C3-6-2 = C3-2:

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Consultant:

C

U s e rs \c b a n k s \D o c u m e n ts \1

.1

.2

M

E P v c b a n k s S

H U

G

.r v t

/1 /2

:2

:2

A M

EL103

FIRST FLOOR - C-WING - LIGHTING

PLANSGUIDON

1221 N. PENNSYLVANIA STREET

INDIANAPOLIS, IN 46202

317.800.6388

EHRM TRAINING AND ADMIN

SPACE SUPPORT

5000 West National Avenue, Milwaukee, WI 53295

695-21-703

11/12/2021 JDF CMB

100% BID DOCUMENTS

FULLY SPRINKLERED

NN

SCALE: 1/8" = 1'-0"EL103

1 FIRST FLOOR - C WING NORTH LIGHTING PLAN

SCALE: 1/8" = 1'-0"EL103

2 FIRST FLOOR - C WING SOUTH - LIGHTING PLAN

Revisions: Date:

D

D

OS

OS

OS

OS

OS

D

OS

OS

OS

OS

LIGHTING GENERAL NOTES

A. REFER TO SHEET E000 FOR ELECTRICAL SYMBOL LEGENDS AND

ABBREVIATIONS.

B. REFER TO SHEET EP602 FOR LIGHT FIXTURE SCHEDULE AND PANEL

SCHEDULES.

C. ELECTRICAL ITEMS SHOWN LIGHT WITH A SOLID LINETYPE AND LABELED (E)

ARE EXISTING TO REMAIN UNLESS NOTED OTHERWISE.

D. ELECTRICAL ITEMS SHOWN BOLD WITH A SOLID LINETYPE ARE NEW UNLESS

NOTED OTHERWISE.

E. CONNECT NIGHT LIGHTS "NL", EXIT SIGNS AND EMERGENCY LIGHTS "EM"

AHEAD OF ALL SWITCHING, UNLESS NOTED OTHERWISE. PARTIAL SHADING OF

A LIGHT FIXTURE DESIGNATION INDICATES EMERGENCY / EGRESS

LIGHTING OR NIGHT LIGHTING.

F. ALL AREAS WHERE AN OCCUPANCY SENSOR IS SHOWN ON THE DRAWINGS

SHALL BE PROVIDED WITH 100% COVERAGE OF THAT AREA WITH

OCCUPANCY SENSING OF THE TECHNOLOGY TYPE SHOWN OR NOTED.

G. MULTIPLE LIGHT SWITCHES/DIMMERS SHALL BE GANGED IN A SINGLE NEMA

RATED BOX UNLESS NOTED OTHERWISE.

H. ALL WALL DEVICES AND COVER PLATE COLORS TO BE SELECTED BY

ARCHITECT.

I. ALL AFFECTED PANELS SHALL HAVE UPDATED TYPED, COMPLETED

DIRECTORIES INDICATING EQUIPMENT SERVED AND ROOM NUMBER (AS

INDICATED ON FINAL BUILDING ROOM SIGNAGE) OF EQUIPMENT LOCATION,

OR SPARE, OR SPACE. HAND WRITTEN DIRECTORIES WILL "NOT" BE

ACCEPTED.

J. RE-SUPPORT EXISTING SYSEM COMPONENTS NOT PROPERLY SUPPORTED

AFTER DEMOLITION AND NOT SCHEDULED FOR WORK.

LIGHTING PLAN NOTES

1. ALL LIGHTING AND LIGHTING CONTROLS IN THIS ROOM ARE EXISTING TO

REMAIN UNLESS OTHERWISE NOTED. ALL LIGHTING THAT REMAINS TO BE

CLEANED AND FLUORESCENTS TO BE RELAMPED.

2. PROVIDE RECESSED LED LIGHTING AND CONNECT TO THE CIRCUIT AND

LIGHTING CONTROLS SHOWN.

3. PROVIDE RECESSED LED DOWNLIGHT AND CONNECT TO THE CIRCUIT AND

LIGHTING CONTROLS SHOWN.

4. PROVIDE COMPATIBLE 0-10V LED WALL DIMMER FOR CONTROL OF THE

"NORMAL" LED LIGHTING IN THIS ROOM.

5. PROVIDE CEILING MOUNTED DUAL-TECHNOLOGY OCCUPANCY SENSOR TO

CONTROL ALL "NORMAL" LIGHTING IN THIS SPACE. PROVIDE 100%

COVERAGE. SET TO MAX TIME DELAY AND MAX SENSITIVITY. PROVIDE

(POWER PACK) FOR OCCUPANCY SENSOR ABOVE NEAREST ACCESSIBLE

CEILING. PENDANT MOUNT IN AREAS WHERE REQUIRED, COORDINATE FINAL

LOCATION WITH OTHER TRADES.

6. PROVIDE LED EXIT SIGNAGE AND CONNECT TO CIRCUIT SHOWN.

7. PROVIDE 3-WAY COMPATIBLE 0-10V LED WALL DIMMER FOR CONTROL OF THE

"NORMAL" LED LIGHTING IN THIS ROOM.

8. PROVIDE LINEAR LED STAIR LIGHT AND MOUNT 7'-6" A.F.F. TO CENTER OF

LIGHT FROM STAIR LANDING.

9. PROVIDE EMERGENCY LIGHT AND WALL MOUNT 7'-6" A.F.F. TO BOTTOM OF

LIGHT AND CONNECT TO CIRCUIT SHOWN.

10. PROVIDE A LINEAR LED LIGHT AND WALL MOUNT 6-INCHES CENTER ABOVE

MIRROR. CONNECT TO CIRCUIT AND LIGHTING CONTROLS SHOWN.

A

SOUTH

B D

BUILDING 6 SECOND FLOOR KEY PLAN

N

SHADE INDICATES

AREA NOT IN

SCOPE, TYP

NO SHADE

INDICATES

LOCATION OF

PROJECT, TYP

C SOUTH

C

NORTHA

NORTH

2ND FLR PORCH NIC

D

BUILDING 6 THIRD FLOOR KEY PLAN

N

HATCH INDICATES

ROOF AREA

BELOW, NIC

NO SHADE

INDICATES

LOCATION OF

PROJECT, TYP

C SOUTH

C

NORTH

(ROOF

ONLY)

SHADE INDICATES

AREA NOT IN

SCOPE, TYP

C207

C208

C209

C204

C203

C202

C212

C224

C225

C226

C227

C221

C228

VACO

C229

C231

C217

STAIR

STAIR

ELEV.

C -W

IN

G

D -W

IN

G

STAIR

C205

EM2

EM2

W4

NL

C3-2:1

C3-2:1

C3-2:1

C -W

IN

G

D -W

IN

G

STAIR

C306

CORRIDOR

C3A

OFFICE

C304

OFFICE

C302

OFFICE

C307

OPEN OFFICE

C305

X1B

A3

A3

A3

A3

A3

A3

A3

A3

A2

A2

A2

A2

A3 A3

A3 A3

EM2

EM2

D1

D1

D1

D1

5(TYPICAL) 4 (TYPICAL)

A2

A2

A2

A2

A2

A2

A2A2

A2A2

A2A2

2 (TYPICAL)

(TYPICAL)

(TYPICAL)

EM2

EM2

A3

A3

ETR

C303

STAIR C1

C1

RESTROOM

C301-A

UTILITY

C301-B

ELEVATOR C1

C1

X1B

C3-2:1 C3-2:1

C3-2:1

C3-2:1

C3-2:1

C3-2:1 a

C3-2:2

C3-2:2

C3-2:2 C3-2:2 C3-2:2

C3-2:2C3-2:2

C3-2:2

C3-2:2 C3-2:2

C3-2:2C3-2:2

C3-2:2

C3-2:2 C3-2:2 C3-2:2 C3-2:2

C3-2:2C3-2:2

C3-2:2 C3-2:2

C3-2:2C3-2:2

C3-2:4

C3-2:4 C3-2:4

C3-2:2

C3-2:2C3-2:2

C3-2:2C3-2:2

C3-2:2

C3-2:2 a a

C3-2:2

D1D1D1

EM2

B2

Z3

C3-2:4

C3-2:4C3-2:4C3-2:4

C3-2:4

C3-2:4 a a aa a aa a a a a a a a

UL-C3-6-2

(C3-1)

X1B

A2

C3-2:2 a A2

C3-2:2 a A2

C3-2:2 a

C3-2:2

EM2

C3-2:4

EM2

C3-2:2

9 (TYPICAL)

a a

PANELBOARD NAMEPLATE ABBREVIATION LIST

NOTE: THE FOLLOWING PANELBOARDS ARE ABBREVIATED FOR CIRCUITING PURPOSES.

FULL PANEL NAME TO BE PUT ON FRONT OF PANEL "NOT" ABBREVIATED NAME.

BUILDING 6 BASEMENT FLOOR PANELS

1. CBA = CBA

2. UL-CB-6-2 = CB2:

3. UL-CB-6-3 = CB3:

4. UL-CB-6-4 = CB4:

5. UL-CB-6-5 = CB5:

BUILDING 6 FIRST FLOOR PANELS

1. UL-A1-6-1 = A1-1:

2. UL-A1-6-2 = A1-2:

3. UL-A1-6-3 = A1-3:

4. UL-B1-6-1 = B1-1:

5. UL-B1-6-2 = B1-2:

6. UL-C1-6-2 = C1-2:

7. UL-C1-6-3 = C1-3:

8. UL-C1-6-4 = C1-4:

BUILDING 6 THIRD FLOOR PANELS

1. UL-C3-6-2 = C3-2:

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Consultant:

C

U s e rs \c b a n k s \D o c u m e n ts \1

.1

.2

M

E P v c b a n k s S

H U

G

.r v t

/1 /2

:2

:2

A M

EL104

SECOND & THIRD FLOOR - C-WING

LIGHTING PLANSGUIDON

1221 N. PENNSYLVANIA STREET

INDIANAPOLIS, IN 46202

317.800.6388

EHRM TRAINING AND ADMIN

SPACE SUPPORT

5000 West National Avenue, Milwaukee, WI 53295

695-21-703

11/12/2021 JDF CMB

100% BID DOCUMENTS

FULLY SPRINKLERED

N N

SCALE: 1/8" = 1'-0"EL104

1 SECOND FLOOR - C-WING - LIGHTING PLAN

SCALE: 1/8" = 1'-0"EL104

2 THIRD FLOOR - C-WING - LIGHTING PLAN

G

FI G

FI

M

M

M

M

D E

D G

FI

GFIGFI

M J

M

M

M

M

M

M

M

S M

SM

SM

SM

SM

T M M

M

M

M

M

POWER GENERAL NOTES

A. REFER TO SHEET E000 FOR ELECTRICAL SYMBOL LEGENDS AND

ABBREVIATIONS.

B. REFER TO EP600 SERIES DRAWINGS FOR PANEL SCHEDULES.

C. REFER TO THE ELECTRICAL FEEDER SCHEDULE ON SHEET EP400 FOR

CONDUIT AND WIRE SIZES AND ELECTRICAL ONE-LINE DIAGRAM.

D. ELECTRICAL ITEMS SHOWN LIGHT WITH A SOLID LINETYPE AND LABELED (E)

ARE EXISTING TO REMAIN UNLESS NOTED OTHERWISE.

E. ELECTRICAL ITEMS SHOWN BOLD WITH A SOLID LINETYPE ARE NEW UNLESS

NOTED OTHERWISE.

F. ELECTRICAL CONTRACTOR SHALL COORDINATE ANY REQUIRED ADDITIONAL

WORK, MOUNTING LOCATIONS AND HEIGHTS OF DEVICES RELATED TO

COMMUNICATION, A/V, DOOR CONTROL, FIRE ALARM, SECURITY, ETC WITH

THE ASSOCIATED CONTRACTOR’S CONSTRUCTION DOCUMENTS AND/OR

APPROVED SHOP DRAWINGS.

G. ALL DEVICES ARE TO BE MOUNTED PER ADA REQUIREMENTS.

H. COORDINATE LOCATIONS AND MOUNTING HEIGHTS OF ALL DEVICES

MOUNTED IN OR ABOVE CASEWORK AND MILLWORK WITH

ARCHITECTURAL INTERIOR DETAILS AND ELEVATIONS.

I. ELECTRICAL CONTRACTOR SHALL VERIFY PRE-WIRED SYSTEMS

FURNITURE WIRING CONFIGURATION. IF SEPARATE NEUTRALS ARE

UTILIZED FOR EACH CIRCUIT THEN 20A/1-POLE CIRCUIT BREAKERS SHALL BE

USED TO FEED EACH CIRCUIT. IF A SHARED NEUTRAL IS USED, PROVIDE AN

APPROPRIATE MULTI-POLE CIRCUIT BREAKER FOR THE FURNITURE FEED

PER N.E.C. 210.4.

J. PANELBOARDS ARE ABBREVIATED FOR CIRCUITING PURPOSES. REFER TO

PANELBOARD ABBREVIATION LIST.

K. VERIFY RECEPTACLE OR JUNCTION BOX MOUNTING HEIGHT AND

CONNECTION TYPE WITH APPROVED EQUIPMENT VENDOR SHOP

DRAWINGS PRIOR TO ROUGH-IN.

L. ALL RECEPTACLES WITHIN 6 FEET OF A SINK SHALL BE GFCI PROTECTED.

M. ALL JUNCTION AND PULL BOXES SHALL BE SIZED PER NEC ARTICLE 314.16

AND 314.28.

N. CONTRACTOR SHALL PROVIDE NAMEPLATES FOR ALL NEW AND EXISTING

ELECTRICAL PANELS AND SWITCHBOARDS IN BUILDING 6 AFFECTED IN THIS

PROJECT SCOPE ONLY.

O. ALL AFFECTED PANELS SHALL HAVE UPDATED TYPED, COMPLETED

DIRECTORIES INDICATING EQUIPMENT SERVED AND ROOM NUMBER (AS

INDICATED ON FINAL BUILDING ROOM SIGNAGE) OF EQUIPMENT LOCATION,

OR SPARE, OR SPACE. HAND WRITTEN DIRECTORIES WILL "NOT" BE

ACCEPTED.

J. RE-SUPPORT EXISTING SYSEM COMPONENTS NOT PROPERLY SUPPORTED

AFTER DEMOLITION AND NOT SCHEDULED FOR WORK.

POWER PLAN NOTES

1. ALL ELECTRICAL PANELS AND EQUIPMENT IN THIS ROOM TO REMAIN

UNLESS NOTED OTHERWISE.

2. ALL POWER DEVICES TO REMAIN IN THIS ROOM UNLESS OTHERWISE NOTED.

3. PROVIDE A RECESSED MOUNTED 120V, 20A DUPLEX RECEPTACLE AND

CONNECT TO CIRCUIT SHOWN.

4. PROVIDE A RECESSED MOUNTED 120V, QUAD RECEPTACLE AND CONNNECT

TO CIRCUIT SHOWN.

5. PROVIDE NEW ELECTRICAL PANEL IN SAME LOCATION AS PANEL THAT WAS

REMOVED. PROVIDE ALL LABOR AND MATERIALS AS REQUIRED TO EXTEND

EXISTING ASSOCIATED FEEDER AND BRANCH CIRCUIT CONDUCTORS AND

CONDUIT TO NEW PANEL. RECONNECT ALL EXISTING BRANCH CIRCUITS TO

REMAIN TO NEW CIRCUIT BREAKERS IN NEW PANEL, FIELD VERIFY ALL

CIRCUITS TO REMAIN. REFER TO ELECTRICAL ONE-LINE DIAGRAM ON

SHEET EP400 AND ELECTRICAL PANELS ON EP600 SERIES SHEETS FOR

ADDITIONAL INFORMATION. PROVIDE NEW NAMEPLATE STANDARD AS

REQUIRED TO RENAME NEW PANEL TO NEW SITE STANDARD. OLD PANEL

NAME SHOWN IN ( ) FOR REFERENCE ONLY.

6. CONTRACTOR SHALL ONLY PROVIDE NEW STANDARD NAMEPLATES AND

DIRECTORIES FOR EXISTING ELECTRICAL PANELS AFFECTED IN THIS

PROJECT SCOPE. REFER TO ONE-LINE DIAGRAM ON SHEET EP400 FOR

ADDITIONAL INFORMATION.

7. PROVIDE DISCONNECT SWITCH AND CONNECT TO UNIT SHOWN.

COORDINATE FINAL LOCATION WITH ALL DISCIPLINES AND CODE CLEARANCES

IN FIELD PRIOR TO INSTALL.

8. PROVIDE A NEMA 3R DISCONNECT AND CONNECT TO UNIT SHOWN.

COORDINATE FINAL LOCATION WITH ALL DISCIPLINES AND CODE CLEARANCES

IN FIELD PRIOR TO INSTALL. REFER TO MECHANICAL DRAWINGS FOR

ADDITIONAL INFORMATION.

9. PROVIDE A DEDICATED DUPLEX GFI RECEPTACLE FOR DRINKING FOUNTAIN.

10. PROVIDE A DUPLEX GFI RECEPTACLE FOR AUTOMATIC FAUCET POWER

SUPPLY FOR SINKS AND MOUNT BELOW VANITY. COORDINATE WITH

PLUMBING DRAWINGS FOR ADDITIONAL INFORMATION.

11. CONNECT 208V-1PH. ELECTRIC HEATER TO CIRCUIT SHOWN. UNIT PROVIDED

WITH INTEGRAL SWITCH DISCONNECT. REFER TO MECHANICAL DRAWINGS

FOR ELECTRICAL COORDINATION AND ADDITIONAL INFORMATION.

12. PROVIDE A 120V JUNCTION BOX FOR LIGHTING AND RECEPTACLES WITHIN AIR

HANDLING UNIT AND CONNECT CIRCUIT SHOWN. REFER TO MECHANICAL

DRAWINGS FOR ELECTRICAL COORDINATION AND ADDITIONAL INFORMATION.

13. CONNECT CABINET UNIT HEATER TO 120V CIRCUIT SHOWN. REFER TO

MECHANICAL DRAWINGS FOR ELECTRICAL COORDINATION AND ADDITIONAL

INFORMATION.

14. CONNECT HOT WATER RECIRC PUMP TO 120V CIRCUIT SHOWN. REFER TO

MECHANICAL DRAWINGS FOR ELECTRICAL COORDINATION AND ADDITIONAL

INFORMATION.

15. PROJECTOR MOUNTING: PROVIDE A FSR #CB-22P (2' x 2' x 6") RECESSED

CEILING ENCLOSURE AND DUPLEX RECEPTACLE FOR PROJECTOR. PROJECT

PROVIDED AND INSTALLED BY VA. FIELD VERIFY LOCATION WITH

PROJECTOR SCREEN LOCATION PRIOR TO INSTALL. REFER TO DETAIL ON

SHEET EP501 FOR ADDITIONAL INFORMATION.

16. LECTERN A/V BACK BOX: PROVIDE A FSR #PWB-250 (14.25” x 7”x 4”) RECESSED

WALL ENCLOSURE WITH RECEPTACLE FOR CEILING PROJECTOR CONTROLS

AND MOUNT 48" A.F.F. TO CENTER OF ENCLOSURE. PROVIDE 1-1/2" CONDUIT

AND ROUTE ABOVE ACCESSIBLE CEILING TO CEILING ENCLOSURE,

NOTE 16, AND CONNECT TO CIRCUIT SHOWN. COORDINATE LOCATION WITH

TEACHERS DESK. REFER TO DETAIL ON SHEET EP501 FOR ADDITIONAL

INFORMATION.

17. PROVIDE A 120V CIRCUIT TO AUTOMATIC DOOR CONTROLS. REFER TO

ARCHITECTURAL DRAWINGS FOR DOOR HARDWARE SCHEDULES AND

SYSTEMS DRAWINGS FOR ADDITIONAL INFORMATION. COORDINATE

INSTALL AND CONTROLS WITH DOOR HARDWARE CONTRACTOR.

A

SOUTH

B D

BUILDING 6 BASEMENT KEY PLAN

N

SHADE INDICATES

AREA NOT IN

SCOPE, TYP

NO SHADE INDICATES

LOCATION OF PROJECT,

TYP

C

SOUTH

C

NORTH

A

NORTH

B -W

IN

G

C -W

IN

G

STORAGE

CB15

ELEC. ROOM

CB16

CIRC.

CB17

ELEV. LOBBY

CB22

ELEV.

C2-P

DHW / UTILITY

CB21

IT ROOM

CB18-C

STAIR C2

C2

MECHANICAL

CB42

VESTIBULE

CB50

CORRIDOR

CB40

TRAINING

CB45

TRAINING

CB43

TRAINING

CB41

VESTIBULE

CB24

TRAINING

CB48

TRAINING

CB46

TRAINING

CB44

STAIR

CB4

STORAGE

CB49

VESTIBULE

CB22A

CIRC.

CB23

STORAGE

CB18

80"

208/120V-3PH.-4W,600A

PANEL CBA (EXIST.)

(E)

CORRIDOR C

CB12

C -W

IN

G

D -W

IN

G

DIST. PANEL MD-6A(EXIST.)

208/120V-3PH.-4W,1200A44"

44"

3 (TYPICAL)

4 (TYPICAL)

5 UL-CB-6-4

UL-CB-6-3

UL-CB-6-5

UL-CB-6-2

(CB-5)

CB2:1

CB2:1

CB2:1

CB2:1

CB3:18

CB3:18

CB3:18

CB3:8CB3:10

CB4:5 CB3:12

CB3:11

CB3:15

CB3:15

CB3:15

CB3:15

CB4:8

CB3:9

CB3:5

CB3:7

CB3:9

CB3:9

CB3:9 CB4:6

CB3:6

CB3:2 CB3:2 CB3:4

CB3:6

CB3:6CB3:6

CB3:6

CB3:21

CB4:7

CB4:1

CB4:1

CB3:17

CB3:21

CB3:21

CB3:21

CB3:14

CB3:18

CB4:3

CB5:2

CB4:1

CB4:1

CB4:1

CB4:1

CB3:23

CB3:12

CB3:12

CB4:3

CB5:3

CB5:3

CB5:2

CB5:2

CB5:2

CB2:2 CB2:2

CB2:2

CB2:2

CB5:2

CB3:17CB3:19

CB3:14CB3:16

CB3:11 CB3:13

CB3:5

CB3:9

CB3:18

CB3:15

CB3:8

CB3:12

CB3:12

CB4:4

CB3:6

MENS RR

CB19-B

WOMENS RR

CB19-A

(CB-3)

(CB)

(CB-2)

EP300

AHU-CB42

EP300

CB4:3

EX. CU

RF-CB42

EX. CU

CU-CB42

CU-C126

CU-C121

VFD

CBA:20,22,24

CBA:26,28,30

VFD

CBA:32,34,36

CBA:31,33,35

CB5:6

CB5:5CB5:5

EWH-CB21

DWH-CB21

HWCP-CB21

ECH-CB42

CB5:7,9

CUH-CB24

CB5:11

CB5:13 13

CUH-CB22A

CB5:15

CUH-CB50

CB5:17

CUH-CB4

CB5:19

ECH-CB49

CB5:14,16

CB2:4,6

C1-3:25,27

CB4:10

(2)#10,(1)#10GND.,3/4"C.

CB4:4

CB4:4

CB4:6

CB4:6

CB4:5

CB4:7 15

CB4:8

CB4:8

CB4:10

CB4:10

CB4:5

CB4:7

(3)#1/0, (1)#6 GND, 1-1/2"C.

(3)#1/0, (1)#6 GND, 1-1/2"C.

(2)#10, (1)#10 GND,

3/4"C.

(2)#10, (1)#10 GND,

3/4"C.

(2)#10, (1)#10 GND,

3/4"C.

CB2:3,5

(2)#10, (1)#10 GND,

3/4"C. CB2:7

(3)#8, (1)#10 GND,

3/4"C.

(3)#12, (1)#12 GND,

3/4"C.

TCP-CB42

CB2:8

ADO ADO

CB5:18

CB5:18

ADO

CB5:18

17 ADO

CB5:18

ADO

CB5:18

ADO

CB5:18

M A

T C

H L

IN

E

B -W

IN

G

C -W

IN

G

CORRIDOR C

CB12

ELEV.

C1-P

ELEV. EQUIP.

CB11

RR-MENS

CB06

CIRC.

CB08

ELECTRICAL CLOSET

CB09

RR-WOMEN'S

CB10

CIRC.

CB07

STAIR C1

C1

FM OFFICE

CB05

C -W

IN

G

D -W

IN

G

2 2

EXIST. DIST. PANEL MD-6

208/120V-3PH.-4W-3,000A

EP300

PANELBOARD NAMEPLATE ABBREVIATION LIST

NOTE: THE FOLLOWING PANELBOARDS ARE ABBREVIATED FOR CIRCUITING PURPOSES.

FULL PANEL NAME TO BE PUT ON FRONT OF PANEL "NOT" ABBREVIATED NAME.

BUILDING 6 BASEMENT FLOOR PANELS

1. CBA = CBA

2. UL-CB-6-2 = CB2:

3. UL-CB-6-3 = CB3:

4. UL-CB-6-4 = CB4:

5. UL-CB-6-5 = CB5:

BUILDING 6 FIRST FLOOR PANELS

1. UL-A1-6-1 = A1-1:

2. UL-A1-6-2 = A1-2:

3. UL-A1-6-3 = A1-3:

4. UL-B1-6-1 = B1-1:

5. UL-B1-6-2 = B1-2:

6. UL-C1-6-2 = C1-2:

7. UL-C1-6-3 = C1-3:

8. UL-C1-6-4 = C1-4:

BUILDING 6 THIRD FLOOR PANELS

1. UL-C3-6-2 = C3-2:

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Consultant:

C

U s e rs \c b a n k s \D o c u m e n ts \1

.1

.2

M

E P v c b a n k s S

H U

G

.r v t

/1 /2

:2

:2

A M

EP100

BASEMENT - C-WING - POWER

PLANSGUIDON

1221 N. PENNSYLVANIA STREET

INDIANAPOLIS, IN 46202

317.800.6388

EHRM TRAINING AND ADMIN

SPACE SUPPORT

5000 West National Avenue, Milwaukee, WI 53295

695-21-703

11/12/2021 JDF CMB

100% BID DOCUMENTS

FULLY SPRINKLERED

NN

SCALE: 1/8" = 1'-0"EP100

1 BASEMENT - C WING NORTH - POWER PLAN

SCALE: 1/8" = 1'-0"EP100

2 BASEMENT - C WING SOUTH - POWER PLAN

UP

DN

M

M

M

J

M

S M

M M

UP

DN

M M

POWER GENERAL NOTES

A. REFER TO SHEET E000 FOR ELECTRICAL SYMBOL LEGENDS AND

ABBREVIATIONS.

B. REFER TO EP600 SERIES DRAWINGS FOR PANEL SCHEDULES.

C. REFER TO THE ELECTRICAL FEEDER SCHEDULE ON SHEET EP400 FOR

CONDUIT AND WIRE SIZES AND ELECTRICAL ONE-LINE DIAGRAM.

D. ELECTRICAL ITEMS SHOWN LIGHT WITH A SOLID LINETYPE AND LABELED (E)

ARE EXISTING TO REMAIN UNLESS NOTED OTHERWISE.

E. ELECTRICAL ITEMS SHOWN BOLD WITH A SOLID LINETYPE ARE NEW UNLESS

NOTED OTHERWISE.

F. ELECTRICAL CONTRACTOR SHALL COORDINATE ANY REQUIRED ADDITIONAL

WORK, MOUNTING LOCATIONS AND HEIGHTS OF DEVICES RELATED TO

COMMUNICATION, A/V, DOOR CONTROL, FIRE ALARM, SECURITY, ETC WITH

THE ASSOCIATED CONTRACTOR’S CONSTRUCTION DOCUMENTS AND/OR

APPROVED SHOP DRAWINGS.

G. ALL DEVICES ARE TO BE MOUNTED PER ADA REQUIREMENTS.

H. COORDINATE LOCATIONS AND MOUNTING HEIGHTS OF ALL DEVICES

MOUNTED IN OR ABOVE CASEWORK AND MILLWORK WITH

ARCHITECTURAL INTERIOR DETAILS AND ELEVATIONS.

I. ELECTRICAL CONTRACTOR SHALL VERIFY PRE-WIRED SYSTEMS

FURNITURE WIRING CONFIGURATION. IF SEPARATE NEUTRALS ARE

UTILIZED FOR EACH CIRCUIT THEN 20A/1-POLE CIRCUIT BREAKERS SHALL BE

USED TO FEED EACH CIRCUIT. IF A SHARED NEUTRAL IS USED, PROVIDE AN

APPROPRIATE MULTI-POLE CIRCUIT BREAKER FOR THE FURNITURE FEED

PER N.E.C. 210.4.

J. PANELBOARDS ARE ABBREVIATED FOR CIRCUITING PURPOSES. REFER TO

PANELBOARD ABBREVIATION LIST.

K. VERIFY RECEPTACLE OR JUNCTION BOX MOUNTING HEIGHT AND

CONNECTION TYPE WITH APPROVED EQUIPMENT VENDOR SHOP

DRAWINGS PRIOR TO ROUGH-IN.

L. ALL RECEPTACLES WITHIN 6 FEET OF A SINK SHALL BE GFCI PROTECTED.

M. ALL JUNCTION AND PULL BOXES SHALL BE SIZED PER NEC ARTICLE 314.16

AND 314.28.

N. CONTRACTOR SHALL PROVIDE NAMEPLATES FOR ALL NEW AND EXISTING

ELECTRICAL PANELS AND SWITCHBOARDS IN BUILDING 6 AFFECTED IN THIS

PROJECT SCOPE ONLY.

O. ALL AFFECTED PANELS SHALL HAVE UPDATED TYPED, COMPLETED

DIRECTORIES INDICATING EQUIPMENT SERVED AND ROOM NUMBER (AS

INDICATED ON FINAL BUILDING ROOM SIGNAGE) OF EQUIPMENT LOCATION,

OR SPARE, OR SPACE. HAND WRITTEN DIRECTORIES WILL "NOT" BE

ACCEPTED.

J. RE-SUPPORT EXISTING SYSEM COMPONENTS NOT PROPERLY SUPPORTED

AFTER DEMOLITION AND NOT SCHEDULED FOR WORK.

POWER PLAN NOTES

1. ALL ELECTRICAL PANELS AND EQUIPMENT IN THIS ROOM TO REMAIN

UNLESS NOTED OTHERWISE.

2. ALL POWER DEVICES TO REMAIN IN THIS ROOM UNLESS OTHERWISE NOTED.

3. PROVIDE A RECESSED MOUNTED 120V, 20A DUPLEX RECEPTACLE AND

CONNECT TO CIRCUIT SHOWN.

4. PROVIDE A RECESSED MOUNTED 120V, QUAD RECEPTACLE AND CONNNECT

TO CIRCUIT SHOWN.

5. PROVIDE NEW ELECTRICAL PANEL IN SAME LOCATION AS PANEL THAT WAS

REMOVED. PROVIDE ALL LABOR AND MATERIALS AS REQUIRED TO EXTEND

EXISTING ASSOCIATED FEEDER AND BRANCH CIRCUIT CONDUCTORS AND

CONDUIT TO NEW PANEL. RECONNECT ALL EXISTING BRANCH CIRCUITS TO

REMAIN TO NEW CIRCUIT BREAKERS IN NEW PANEL, FIELD VERIFY ALL

CIRCUITS TO REMAIN. REFER TO ELECTRICAL ONE-LINE DIAGRAM ON

SHEET EP400 AND ELECTRICAL PANELS ON EP600 SERIES SHEETS FOR

ADDITIONAL INFORMATION. PROVIDE NEW NAMEPLATE STANDARD AS

REQUIRED TO RENAME NEW PANEL TO NEW SITE STANDARD. OLD PANEL

NAME SHOWN IN ( ) FOR REFERENCE ONLY.

6. PROVIDE VARIABLE FREQUENCY DRIVE AND CONNECT TO UNIT SHOWN.

COORDINATE FINAL LOCATION WITH ALL DISCIPLINES AND CODE CLEARANCES

IN FIELD PRIOR TO INSTALL. REFER TO MECHANICAL DRAWINGS FOR

ELECTRICAL COORDINATION AND ADDITIONAL INFORMATION.

7. PROVIDE A NEMA 3R DISCONNECT AND CONNECT TO UNIT SHOWN.

COORDINATE FINAL LOCATION WITH ALL DISCIPLINES AND CODE CLEARANCES

IN FIELD PRIOR TO INSTALL. REFER TO MECHANICAL DRAWINGS FOR

ELECTRICAL COORDINATION AND ADDITIONAL INFORMATION.

8. PROVIDE A 120V JUNCTION BOX FOR LIGHTING AND RECEPTACLES WITHIN AIR

HANDLING UNIT AND CONNECT CIRCUIT SHOWN. REFER TO MECHANICAL

DRAWINGS FOR ELECTRICAL COORDINATION AND ADDITIONAL INFORMATION.

9. PROVIDE A 120V, DUPLEX RECEPACLE FOR LCD SCREEN. COORDINATE WITH

AV CONTRACTOR FOR LOCATION AND MOUNTING HEIGHT PRIOR TO

INSTALL.

10. PROVIDE A 120V CIRCUIT TO AUTOMATIC DOOR CONTROLS. REFER TO

ARCHITECTURAL DRAWINGS FOR DOOR HARDWARE SCHEDULES AND

SYSTEMS DRAWINGS FOR ADDITIONAL INFORMATION. COORDINATE

INSTALL AND CONTROLS WITH DOOR HARDWARE CONTRACTOR.

B D

BUILDING 6 FIRST FLOOR KEY PLAN

N

SHADE INDICATES AREA

NOT IN SCOPE, TYP

NO SHADE INDICATES

LOCATION OF PROJECT,

TYP

A

SOUTH

C

SOUTH

C

NORTH

A

NORTH

HAC

FILES/SCANNING

A115

STAIR

RESTROOM

ELEVATOR

P8

PB PCPA

P7

P6

P5

P4

P3

P2

P1

PH

CORRIDOR

A101

BREAKOUT

A122

TRAINING

A124

OIT CLOSET

A104

TRAINING

A118-A

MECHANICAL

A121

3 (TYPICAL)

4 (TYPICAL)

A -W

IN

G

B -W

IN

G

UL-A1-6-1

UL-A1-6-2

UL-A1-6-3

CIRC.

A117

STORAGE

A116-C

A1-3:17

A1-3:15

A1-3:11 A1-3:9 A1-3:9

A1-3:3

A1-3:8

A1-3:4

A1-3:4A1-3:6

A1-3:6

A1-3:2 A1-3:2

A1-3:8

A1-3:10

A1-3:5A1-3:1

A1-3:10

A1-3:17

A1-3:7

A1-3:5

A1-3:5 A1-3:10

A1-3:12

A1-3:12

A1-3:12

A1-3:10

A1-3:10

A1-3:7

A1-3:7

A1-3:5

A1-3:13

A1-3:13

A1-3:13

A1-3:2

A1-3:11

A1-3:1

A1-3:3

TRAINING

A118-B

(A1-2)

(A1-3)

(A1-1)

AHU-A121

CU-A121

EX. CU

RF-A121

V F

D V

F D

CBA:37,39,41

CBA:14,16,18

CBA:38,40,42

A1-3:14

72"

72"

A1-3:7

72" 9

A1-3:17

72"

(3)#1/0,(1)#6

GND.,1-1/2"C

TCP-A121

(3)#8,(1)#10

GND.,3/4"C

(3)#12,(1)#12

GND.,3/4"C

CUH-A121

A1-2:6

ADO

ADO

A1-1:1 A1-1:1

HAC

FILES/SCANNING

A115

CONFERENCE

A114

SCANNING

A113

A112

A109

NON-VA CARE

A108

MECHANICAL

STAIR

RESTROOM

ELEVATOR

P8

P9

P10

P12

P11

P13

P14

P18

P19

P20 PE PF

P21

P22

P23

P24

PB

P16

P.ZZ

P.AA

P17

PC

P15

PD PG

PA

P7

P6

P5

P4

P3

P2

P1

PH

A -W

IN

G

B -W

IN

G

UL-A1-6-2

UL-A1-6-3

UL-A1-6-1

CORRIDOR

A101

STORAGE

A116-C

CORRIDOR

A/B

(A-12)

(A-13)

(A-11)

A1-3:7

A1-3:5

A1-3:10

A1-3:10

PANELBOARD NAMEPLATE ABBREVIATION LIST

NOTE: THE FOLLOWING PANELBOARDS ARE ABBREVIATED FOR CIRCUITING PURPOSES.

FULL PANEL NAME TO BE PUT ON FRONT OF PANEL "NOT" ABBREVIATED NAME.

BUILDING 6 BASEMENT FLOOR PANELS

1. CBA = CBA

2. UL-CB-6-2 = CB2:

3. UL-CB-6-3 = CB3:

4. UL-CB-6-4 = CB4:

5. UL-CB-6-5 = CB5:

BUILDING 6 FIRST FLOOR PANELS

1. UL-A1-6-1 = A1-1:

2. UL-A1-6-2 = A1-2:

3. UL-A1-6-3 = A1-3:

4. UL-B1-6-1 = B1-1:

5. UL-B1-6-2 = B1-2:

6. UL-C1-6-2 = C1-2:

7. UL-C1-6-3 = C1-3:

8. UL-C1-6-4 = C1-4:

BUILDING 6 THIRD FLOOR PANELS

1. UL-C3-6-2 = C3-2:

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Consultant:

C

U s e rs \c b a n k s \D o c u m e n ts \1

.1

.2

M

E P v c b a n k s S

H U

G

.r v t

/1 /2

:2

:2

A M

EP101

FIRST FLOOR - A-WING - POWER

PLANSGUIDON

1221 N. PENNSYLVANIA STREET

INDIANAPOLIS, IN 46202

317.800.6388

EHRM TRAINING AND ADMIN

SPACE SUPPORT

5000 West National Avenue, Milwaukee, WI 53295

695-21-703

11/12/2021 JDF CMB

100% BID DOCUMENTS

FULLY SPRINKLERED

NN

SCALE: 1/8" = 1'-0"EP101

1 FIRST FLOOR - A WING NORTH - POWER PLAN

SCALE: 1/8" = 1'-0"EP101

2 FIRST FLOOR - A WING SOUTH - POWER PLAN

B D

BUILDING 6 FIRST FLOOR KEY PLAN

N

SHADE INDICATES AREA

NOT IN SCOPE, TYP

NO SHADE INDICATES

LOCATION OF PROJECT,

TYP

A

SOUTH

C

SOUTH

C

NORTH

A

NORTH

POWER GENERAL NOTES

A. REFER TO SHEET E000 FOR ELECTRICAL SYMBOL LEGENDS AND

ABBREVIATIONS.

B. REFER TO EP600 SERIES DRAWINGS FOR PANEL SCHEDULES.

C. REFER TO THE ELECTRICAL FEEDER SCHEDULE ON SHEET EP400 FOR

CONDUIT AND WIRE SIZES AND ELECTRICAL ONE-LINE DIAGRAM.

D. ELECTRICAL ITEMS SHOWN LIGHT WITH A SOLID LINETYPE AND LABELED (E)

ARE EXISTING TO REMAIN UNLESS NOTED OTHERWISE.

E. ELECTRICAL ITEMS SHOWN BOLD WITH A SOLID LINETYPE ARE NEW UNLESS

NOTED OTHERWISE.

F. ELECTRICAL CONTRACTOR SHALL COORDINATE ANY REQUIRED ADDITIONAL

WORK, MOUNTING LOCATIONS AND HEIGHTS OF DEVICES RELATED TO

COMMUNICATION, A/V, DOOR CONTROL, FIRE ALARM, SECURITY, ETC WITH

THE ASSOCIATED CONTRACTOR’S CONSTRUCTION DOCUMENTS AND/OR

APPROVED SHOP DRAWINGS.

G. ALL DEVICES ARE TO BE MOUNTED PER ADA REQUIREMENTS.

H. COORDINATE LOCATIONS AND MOUNTING HEIGHTS OF ALL DEVICES

MOUNTED IN OR ABOVE CASEWORK AND MILLWORK WITH

ARCHITECTURAL INTERIOR DETAILS AND ELEVATIONS.

I. ELECTRICAL CONTRACTOR SHALL VERIFY PRE-WIRED SYSTEMS

FURNITURE WIRING CONFIGURATION. IF SEPARATE NEUTRALS ARE

UTILIZED FOR EACH CIRCUIT THEN 20A/1-POLE CIRCUIT BREAKERS SHALL BE

USED TO FEED EACH CIRCUIT. IF A SHARED NEUTRAL IS USED, PROVIDE AN

APPROPRIATE MULTI-POLE CIRCUIT BREAKER FOR THE FURNITURE FEED

PER N.E.C. 210.4.

J. PANELBOARDS ARE ABBREVIATED FOR CIRCUITING PURPOSES. REFER TO

PANELBOARD ABBREVIATION LIST.

K. VERIFY RECEPTACLE OR JUNCTION BOX MOUNTING HEIGHT AND

CONNECTION TYPE WITH APPROVED EQUIPMENT VENDOR SHOP

DRAWINGS PRIOR TO ROUGH-IN.

L. ALL RECEPTACLES WITHIN 6 FEET OF A SINK SHALL BE GFCI PROTECTED.

M. ALL JUNCTION AND PULL BOXES SHALL BE SIZED PER NEC ARTICLE 314.16

AND 314.28.

N. CONTRACTOR SHALL PROVIDE NAMEPLATES FOR ALL NEW AND EXISTING

ELECTRICAL PANELS AND SWITCHBOARDS IN BUILDING 6 AFFECTED IN THIS

PROJECT SCOPE ONLY.

O. ALL AFFECTED PANELS SHALL HAVE UPDATED TYPED, COMPLETED

DIRECTORIES INDICATING EQUIPMENT SERVED AND ROOM NUMBER (AS

INDICATED ON FINAL BUILDING ROOM SIGNAGE) OF EQUIPMENT LOCATION,

OR SPARE, OR SPACE. HAND WRITTEN DIRECTORIES WILL "NOT" BE

ACCEPTED.

P. RE-SUPPORT EXISTING SYSEM COMPONENTS NOT PROPERLY SUPPORTED

AFTER DEMOLITION AND NOT SCHEDULED FOR WORK.

POWER PLAN NOTES

1. ALL POWER DEVICES TO REMAIN IN THIS ROOM UNLESS OTHERWISE NOTED.

2. PROVIDE NEW ELECTRICAL PANEL IN SAME LOCATION AS PANEL THAT WAS

REMOVED. PROVIDE ALL LABOR AND MATERIALS AS REQUIRED TO EXTEND

EXISTING ASSOCIATED FEEDER AND BRANCH CIRCUIT CONDUCTORS AND

CONDUIT TO NEW PANEL. RECONNECT ALL EXISTING BRANCH CIRCUITS TO

REMAIN TO NEW CIRCUIT BREAKERS IN NEW PANEL, FIELD VERIFY ALL

CIRCUITS TO REMAIN. REFER TO ELECTRICAL ONE-LINE DIAGRAM ON

SHEET EP400 AND ELECTRICAL PANELS ON EP600 SERIES SHEETS FOR

ADDITIONAL INFORMATION. PROVIDE NEW NAMEPLATE STANDARD AS

REQUIRED TO RENAME NEW PANEL TO NEW SITE STANDARD. OLD PANEL

NAME SHOWN IN ( ) FOR REFERENCE ONLY.

HAC

B109

B108

B103

HAC

MENS

WOMENS

STAIR

A -W

IN

G

B -W

IN

G

M A

T C

H L

IN

E

M A

T C

H L

IN

E

B -W

IN

G

C -W

IN

G

CORRIDOR

B/CCORRIDOR

A/B

UL-B1-6-1

UL-B1-6-2

(B1-2)

(B-1)

PANELBOARD NAMEPLATE ABBREVIATION LIST

NOTE: THE FOLLOWING PANELBOARDS ARE ABBREVIATED FOR CIRCUITING PURPOSES.

FULL PANEL NAME TO BE PUT ON FRONT OF PANEL "NOT" ABBREVIATED NAME.

BUILDING 6 BASEMENT FLOOR PANELS

1. CBA = CBA

2. UL-CB-6-2 = CB2:

3. UL-CB-6-3 = CB3:

4. UL-CB-6-4 = CB4:

5. UL-CB-6-5 = CB5:

BUILDING 6 FIRST FLOOR PANELS

1. UL-A1-6-1 = A1-1:

2. UL-A1-6-2 = A1-2:

3. UL-A1-6-3 = A1-3:

4. UL-B1-6-1 = B1-1:

5. UL-B1-6-2 = B1-2:

6. UL-C1-6-2 = C1-2:

7. UL-C1-6-3 = C1-3:

8. UL-C1-6-4 = C1-4:

BUILDING 6 THIRD FLOOR PANELS

1. UL-C3-6-2 = C3-2:

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Consultant:

C

U s e rs \c b a n k s \D o c u m e n ts \1

.1

.2

M

E P v c b a n k s S

H U

G

.r v t

/1 /2

:2

:2

A M

EP102

FIRST FLOOR - B-WING - POWER

PLANSGUIDON

1221 N. PENNSYLVANIA STREET

INDIANAPOLIS, IN 46202

317.800.6388

EHRM TRAINING AND ADMIN

SPACE SUPPORT

5000 West National Avenue, Milwaukee, WI 53295

695-21-703

11/12/2021 JDF CMB

100% BID DOCUMENTS

FULLY SPRINKLERED

N

SCALE: 1/8" = 1'-0"EP102

1 FIRST FLOOR - B WING - POWER PLAN

E

D G

FI

G

FI

G

FI

D E

D G

FI

DED

GFI

GFIGFI

M

J

M

M

M

M

SM

T

M

SM

T

M

B D

BUILDING 6 FIRST FLOOR KEY PLAN

N

SHADE INDICATES AREA

NOT IN SCOPE, TYP

NO SHADE INDICATES

LOCATION OF PROJECT,

TYP

A

SOUTH

C

SOUTH

C

NORTH

A

NORTH

TRAINING

C148

TRAINING

C145

TRAINING

C146

TRAINING

C144

TRAINING

C143

STAIR

C4

TRAINING

C141

WAITING

C142

LIGHTWELL

C----

WOMENS RR

C119-A

ELEV.

C2-P

ELEV. LOBBY

C120

TRAINING

C106-C

STORAGE

C119-C

IT ROOM

C118-B

CIRC.

C116

STAIR C2

C2

SECURITY

C118-A

BREAK AREA

C118 44"

B -W

IN

G

C -W

IN

G

C -W

IN

G

D -W

IN

G

3 (TYPICAL)

4 (TYPICAL)

44"44"

MENS RR

C119-B

63" (MICRO.)

(REFRIG.)

44"

EX. CU

UL-C1-6-3

UL-C1-6-2

UL-C1-6-4

CONFERENCE ROOM

C124-AWAITING

C124

MECHANICAL

C126

ELEV. MACHINE.

C121

CORRIDOR

C140

C1-3:15

C1-3:13

C1-3:13

C1-3:18

C1-3:9

C1-3:7

C1-3:7

C1-3:3

C1-3:1

C1-3:1

C1-3:15

C1-3:11

C1-3:9

C1-3:18

C1-3:8

C1-3:17

C1-3:20

C1-3:20

C1-2:6

C1-3:6

C1-3:16

C1-3:14

C1-3:14

C1-3:5

C1-3:3

C1-3:12

C1-3:4

C1-3:8

C1-3:10

C1-3:10

C1-3:4

C1-3:2

C1-3:2 C1-3:6 C1-4:16C1-4:16

C1-4:16

C1-4:16

C1-3:20

C1-4:17

C1-4:15 C1-4:15

C1-4:15

C1-4:15

C1-4:5

C1-4:9

C1-4:3 C1-2:4

C1-4:12

C1-4:10

C1-4:10

C1-4:14

C1-4:14

C1-4:14

C1-4:14

C1-4:14

C1-2:1C1-2:1

C1-4:7 C1-4:7

C1-4:7

C1-4:9

C1-4:1

C1-4:3

C1-4:9

C1-4:9

C1-4:11

C1-4:11

C1-4:11

C1-4:11

C1-2:12

C1-2:14

C1-3:12

C1-3:5

C1-3:17C1-2:10

C1-3:18

C1-4:17

C1-3:16

C1-2:16

C1-2:8

C1-3:11

C1-4:13

CORRIDOR

C140

(C1-2)

(C1-4)

(6-C-14)

EP300

C1-3:20

C1-3:19 C1-3:19

C1-3:19

C1-3:19

C1-3:19

C1-2:5

C1-2:3C1-2:3

V F

D

CBA:25,27,29

EWH-C119C

EF-C119C

AHU-C126

9C1-2:2

C1-3:22,24,26

C1-3:21,23

RF-C126

V F

D

CBA:2,4,6

C1-2:4

C1-2:4

C1-2:6

C1-2:8 11

C1-2:16

C1-2:10

C1-2:14

C1-2:12

C1-2:16

C1-2:8

C1-2:6

C1-2:10

C1-2:14

C1-2:12

(3)#12,(1)#12GND,

3/4"C.

(3)#6,(1)#10GND.,

3/4"C.

(3)#12,(1)#12GND.,

3/4"C.

TCP-C126

C1-2:7

CUH-C126

C1-2:9

CUH-C4

C1-2:11

ADO

C1-3:28

STAIR

C106

CORRIDOR

C115A

CORRIDOR

C115B

CORRIDOR

B/C

ELEV. EQUIP.

CB11

CEMETERY SCHED. OFFICE

C113

HAC

C109

C108

C107

C105

C104

C103

LACTATION

VENDING

STAIR

B -W

IN

G

C -W

IN

G

C -W

IN

G

D -W

IN

G

C3-2:9

POWER GENERAL NOTES

A. REFER TO SHEET E000 FOR ELECTRICAL SYMBOL LEGENDS AND

ABBREVIATIONS.

B. REFER TO EP600 SERIES DRAWINGS FOR PANEL SCHEDULES.

C. REFER TO THE ELECTRICAL FEEDER SCHEDULE ON SHEET EP400 FOR

CONDUIT AND WIRE SIZES AND ELECTRICAL ONE-LINE DIAGRAM.

D. ELECTRICAL ITEMS SHOWN LIGHT WITH A SOLID LINETYPE AND LABELED (E)

ARE EXISTING TO REMAIN UNLESS NOTED OTHERWISE.

E. ELECTRICAL ITEMS SHOWN BOLD WITH A SOLID LINETYPE ARE NEW UNLESS

NOTED OTHERWISE.

F. ELECTRICAL CONTRACTOR SHALL COORDINATE ANY REQUIRED ADDITIONAL

WORK, MOUNTING LOCATIONS AND HEIGHTS OF DEVICES RELATED TO

COMMUNICATION, A/V, DOOR CONTROL, FIRE ALARM, SECURITY, ETC WITH

THE ASSOCIATED CONTRACTOR’S CONSTRUCTION DOCUMENTS AND/OR

APPROVED SHOP DRAWINGS.

G. ALL DEVICES ARE TO BE MOUNTED PER ADA REQUIREMENTS.

H. COORDINATE LOCATIONS AND MOUNTING HEIGHTS OF ALL DEVICES

MOUNTED IN OR ABOVE CASEWORK AND MILLWORK WITH

ARCHITECTURAL INTERIOR DETAILS AND ELEVATIONS.

I. ELECTRICAL CONTRACTOR SHALL VERIFY PRE-WIRED SYSTEMS

FURNITURE WIRING CONFIGURATION. IF SEPARATE NEUTRALS ARE

UTILIZED FOR EACH CIRCUIT THEN 20A/1-POLE CIRCUIT BREAKERS SHALL BE

USED TO FEED EACH CIRCUIT. IF A SHARED NEUTRAL IS USED, PROVIDE AN

APPROPRIATE MULTI-POLE CIRCUIT BREAKER FOR THE FURNITURE FEED

PER N.E.C. 210.4.

J. PANELBOARDS ARE ABBREVIATED FOR CIRCUITING PURPOSES. REFER TO

PANELBOARD ABBREVIATION LIST.

K. VERIFY RECEPTACLE OR JUNCTION BOX MOUNTING HEIGHT AND

CONNECTION TYPE WITH APPROVED EQUIPMENT VENDOR SHOP

DRAWINGS PRIOR TO ROUGH-IN.

L. ALL RECEPTACLES WITHIN 6 FEET OF A SINK SHALL BE GFCI PROTECTED.

M. ALL JUNCTION AND PULL BOXES SHALL BE SIZED PER NEC ARTICLE 314.16

AND 314.28.

N. CONTRACTOR SHALL PROVIDE NAMEPLATES FOR ALL NEW AND EXISTING

ELECTRICAL PANELS AND SWITCHBOARDS IN BUILDING 6 AFFECTED IN THIS

PROJECT SCOPE ONLY.

O. ALL AFFECTED PANELS SHALL HAVE UPDATED TYPED, COMPLETED

DIRECTORIES INDICATING EQUIPMENT SERVED AND ROOM NUMBER (AS

INDICATED ON FINAL BUILDING ROOM SIGNAGE) OF EQUIPMENT LOCATION,

OR SPARE, OR SPACE. HAND WRITTEN DIRECTORIES WILL "NOT" BE

ACCEPTED.

P. RE-SUPPORT EXISTING SYSEM COMPONENTS NOT PROPERLY SUPPORTED

AFTER DEMOLITION AND NOT SCHEDULED FOR WORK.

POWER PLAN NOTES

1. ALL ELECTRICAL PANELS AND EQUIPMENT IN THIS ROOM TO REMAIN

UNLESS NOTED OTHERWISE.

2. ALL POWER DEVICES TO REMAIN IN THIS ROOM UNLESS OTHERWISE NOTED.

3. PROVIDE A RECESSED MOUNTED 120V, 20A DUPLEX RECEPTACLE AND

CONNECT TO CIRCUIT SHOWN.

4. PROVIDE A RECESSED MOUNTED 120V, QUAD RECEPTACLE AND CONNNECT

TO CIRCUIT SHOWN.

5. PROVIDE NEW ELECTRICAL PANEL IN SAME LOCATION AS PANEL THAT WAS

REMOVED. PROVIDE ALL LABOR AND MATERIALS AS REQUIRED TO EXTEND

EXISTING ASSOCIATED FEEDER AND BRANCH CIRCUIT CONDUCTORS AND

CONDUIT TO NEW PANEL. RECONNECT ALL EXISTING BRANCH CIRCUITS TO

REMAIN TO NEW CIRCUIT BREAKERS IN NEW PANEL, FIELD VERIFY ALL

CIRCUITS TO REMAIN. REFER TO ELECTRICAL ONE-LINE DIAGRAM ON

SHEET EP400 AND ELECTRICAL PANELS ON EP600 SERIES SHEETS FOR

ADDITIONAL INFORMATION. PROVIDE NEW NAMEPLATE STANDARD AS

REQUIRED TO RENAME NEW PANEL TO NEW SITE STANDARD. OLD PANEL

NAME SHOWN IN ( ) FOR REFERENCE ONLY.

6. PROVIDE A DUPLEX GFI RECEPTACLE FOR AUTOMATIC FAUCET POWER

SUPPLY FOR SINKS AND MOUNT BELOW VANITY. COORDINATE WITH

PLUMBING DRAWINGS FOR ADDITIONAL INFORMATION.

7. PROVIDE A DEDICATED DUPLEX GFI RECEPTACLE FOR DRINKING FOUNTAIN.

8. PROVIDE VARIABLE FREQUENCY DRIVE AND CONNECT TO UNIT SHOWN.

COORDINATE FINAL LOCATION WITH ALL DISCIPLINES AND CODE CLEARANCES

IN FIELD PRIOR TO INSTALL.

9. PROVIDE A 120V JUNCTION BOX FOR LIGHTING AND RECEPTACLES WITHIN AIR

HANDLING UNIT AND CONNECT CIRCUIT SHOWN. REFER TO MECHANICAL

DRAWINGS FOR ELECTRICAL COORDINATION AND ADDITIONAL INFORMATION.

10. CONNECT 120V EXHAUST FAN TO CIRCUIT SHOWN. UNIT PROVIDED WITH

MOTOR RATED TOGGLE SWITCH DISCONNECT. REFER TO MECHANICAL

DRAWINGS FOR ELECTRICAL COORDINATION AND ADDITIONAL INFORMATION.

11. CONNECT 208V-1PH. ELECTRIC HEATER TO CIRCUIT SHOWN. UNIT PROVIDED

WITH INTEGRAL SWITCH DISCONNECT. REFER TO MECHANICAL DRAWINGS

FOR ELECTRICAL COORDINATION AND ADDITIONAL INFORMATION.

12. PROJECTOR MOUNTING: PROVIDE A FSR #CB-22P (2' x 2' x 6") RECESSED

CEILING ENCLOSURE AND DUPLEX RECEPTACLE FOR PROJECTOR. PROJECT

PROVIDED AND INSTALLED BY VA. FIELD VERIFY LOCATION WITH

PROJECTOR SCREEN LOCATION PRIOR TO INSTALL. REFER TO DETAIL ON

SHEET EP501 FOR ADDITIONAL INFORMATION.

13. LECTERN A/V BACK BOX: PROVIDE A FSR #PWB-250 (14.25” x 7”x 4”) RECESSED

WALL ENCLOSURE WITH RECEPTACLE FOR CEILING PROJECTOR CONTROLS

AND MOUNT 48" A.F.F. TO CENTER OF ENCLOSURE. PROVIDE 1-1/2" CONDUIT

AND ROUTE ABOVE ACCESSIBLE CEILING TO CEILING ENCLOSURE,

NOTE 16, AND CONNECT TO CIRCUIT SHOWN. COORDINATE LOCATION WITH

TEACHERS DESK. REFER TO DETAIL ON SHEET EP501 FOR ADDITIONAL

INFORMATION.

14. PROVIDE A 120V CIRCUIT TO AUTOMATIC DOOR CONTROLS. REFER TO

ARCHITECTURAL DRAWINGS FOR DOOR HARDWARE SCHEDULES AND

SYSTEMS DRAWINGS FOR ADDITIONAL INFORMATION. COORDINATE

INSTALL AND CONTROLS WITH DOOR HARDWARE CONTRACTOR.

PANELBOARD NAMEPLATE ABBREVIATION LIST

NOTE: THE FOLLOWING PANELBOARDS ARE ABBREVIATED FOR CIRCUITING PURPOSES.

FULL PANEL NAME TO BE PUT ON FRONT OF PANEL "NOT" ABBREVIATED NAME.

BUILDING 6 BASEMENT FLOOR PANELS

1. CBA = CBA

2. UL-CB-6-2 = CB2:

3. UL-CB-6-3 = CB3:

4. UL-CB-6-4 = CB4:

5. UL-CB-6-5 = CB5:

BUILDING 6 FIRST FLOOR PANELS

1. UL-A1-6-1 = A1-1:

2. UL-A1-6-2 = A1-2:

3. UL-A1-6-3 = A1-3:

4. UL-B1-6-1 = B1-1:

5. UL-B1-6-2 = B1-2:

6. UL-C1-6-2 = C1-2:

7. UL-C1-6-3 = C1-3:

8. UL-C1-6-4 = C1-4:

BUILDING 6 THIRD FLOOR PANELS

1. UL-C3-6-2 = C3-2:

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Consultant:

C

U s e rs \c b a n k s \D o c u m e n ts \1

.1

.2

M

E P v c b a n k s S

H U

G

.r v t

/1 /2

:2

:2

A M

EP103

FIRST FLOOR - C-WING - POWER

PLANSGUIDON

1221 N. PENNSYLVANIA STREET

INDIANAPOLIS, IN 46202

317.800.6388

EHRM TRAINING AND ADMIN

SPACE SUPPORT

5000 West National Avenue, Milwaukee, WI 53295

695-21-703

11/12/2021 JDF CMB

100% BID DOCUMENTS

FULLY SPRINKLERED

NN

SCALE: 1/8" = 1'-0"EP103

1 FIRST FLOOR - C WING NORTH - POWER PLAN

SCALE: 1/8" = 1'-0"EP103

2 FIRST FLOOR - C WING SOUTH - POWER PLAN

A

SOUTH

B D

BUILDING 6 SECOND FLOOR KEY PLAN

N

SHADE INDICATES

AREA NOT IN

SCOPE, TYP

NO SHADE

INDICATES

LOCATION OF

PROJECT, TYP

C SOUTH

C

NORTHA

NORTH

2ND FLR PORCH NIC

D

BUILDING 6 THIRD FLOOR KEY PLAN

N

HATCH INDICATES

ROOF AREA

BELOW, NIC

NO SHADE

INDICATES

LOCATION OF

PROJECT, TYP

C SOUTH

C

NORTH

(ROOF

ONLY)

SHADE INDICATES

AREA NOT IN

SCOPE, TYP

ELEV.

C -W

IN

G

D -W

IN

G

STAIR

C205

C207

C208

C209

C204

C203

C202

C212

C217

STAIR

C3-2:9

OFFICE

C304

OFFICE

C307

OFFICE

C302

STAIR C1

C1

ETR

C303

OPEN OFFICE

C305

STAIR

C306

CORRIDOR

C3A

ELEVATOR C1

C1

RESTROOM

C301-A

UTILITY

C301-B

2 (TYPICAL)

3 (TYPICAL)

C -W

IN

G

D -W

IN

G

UL-C3-6-2

4C3-2:3

C3-2:3

C3-2:3

C3-2:3

C3-2:5

C3-2:5

C3-2:5

C3-2:5

C3-2:7

C3-2:7

C3-2:7

C3-2:7

C3-2:6

C3-2:8C3-2:8

C3-2:10

C3-2:14

C3-2:14

C3-2:12

C3-2:12C3-2:12

(C3-1)

C3-2:9

PANELBOARD NAMEPLATE ABBREVIATION LIST

NOTE: THE FOLLOWING PANELBOARDS ARE ABBREVIATED FOR CIRCUITING PURPOSES.

FULL PANEL NAME TO BE PUT ON FRONT OF PANEL "NOT" ABBREVIATED NAME.

BUILDING 6 BASEMENT FLOOR PANELS

1. CBA = CBA

2. UL-CB-6-2 = CB2:

3. UL-CB-6-3 = CB3:

4. UL-CB-6-4 = CB4:

5. UL-CB-6-5 = CB5:

BUILDING 6 FIRST FLOOR PANELS

1. UL-A1-6-1 = A1-1:

2. UL-A1-6-2 = A1-2:

3. UL-A1-6-3 = A1-3:

4. UL-B1-6-1 = B1-1:

5. UL-B1-6-2 = B1-2:

6. UL-C1-6-2 = C1-2:

7. UL-C1-6-3 = C1-3:

8. UL-C1-6-4 = C1-4:

BUILDING 6 THIRD FLOOR PANELS

1. UL-C3-6-2 = C3-2:

POWER GENERAL NOTES

A. REFER TO SHEET E000 FOR ELECTRICAL SYMBOL LEGENDS AND

ABBREVIATIONS.

B. REFER TO EP600 SERIES DRAWINGS FOR PANEL SCHEDULES.

C. REFER TO THE ELECTRICAL FEEDER SCHEDULE ON SHEET EP400 FOR

CONDUIT AND WIRE SIZES AND ELECTRICAL ONE-LINE DIAGRAM.

D. ELECTRICAL ITEMS SHOWN LIGHT WITH A SOLID LINETYPE AND LABELED (E)

ARE EXISTING TO REMAIN UNLESS NOTED OTHERWISE.

E. ELECTRICAL ITEMS SHOWN BOLD WITH A SOLID LINETYPE ARE NEW UNLESS

NOTED OTHERWISE.

F. ELECTRICAL CONTRACTOR SHALL COORDINATE ANY REQUIRED ADDITIONAL

WORK, MOUNTING LOCATIONS AND HEIGHTS OF DEVICES RELATED TO

COMMUNICATION, A/V, DOOR CONTROL, FIRE ALARM, SECURITY, ETC WITH

THE ASSOCIATED CONTRACTOR’S CONSTRUCTION DOCUMENTS AND/OR

APPROVED SHOP DRAWINGS.

G. ALL DEVICES ARE TO BE MOUNTED PER ADA REQUIREMENTS.

H. COORDINATE LOCATIONS AND MOUNTING HEIGHTS OF ALL DEVICES

MOUNTED IN OR ABOVE CASEWORK AND MILLWORK WITH

ARCHITECTURAL INTERIOR DETAILS AND ELEVATIONS.

I. ELECTRICAL CONTRACTOR SHALL VERIFY PRE-WIRED SYSTEMS

FURNITURE WIRING CONFIGURATION. IF SEPARATE NEUTRALS ARE

UTILIZED FOR EACH CIRCUIT THEN 20A/1-POLE CIRCUIT BREAKERS SHALL BE

USED TO FEED EACH CIRCUIT. IF A SHARED NEUTRAL IS USED, PROVIDE AN

APPROPRIATE MULTI-POLE CIRCUIT BREAKER FOR THE FURNITURE FEED

PER N.E.C. 210.4.

J. PANELBOARDS ARE ABBREVIATED FOR CIRCUITING PURPOSES. REFER TO

PANELBOARD ABBREVIATION LIST.

K. VERIFY RECEPTACLE OR JUNCTION BOX MOUNTING HEIGHT AND

CONNECTION TYPE WITH APPROVED EQUIPMENT VENDOR SHOP

DRAWINGS PRIOR TO ROUGH-IN.

L. ALL RECEPTACLES WITHIN 6 FEET OF A SINK SHALL BE GFCI PROTECTED.

M. ALL JUNCTION AND PULL BOXES SHALL BE SIZED PER NEC ARTICLE 314.16

AND 314.28.

N. CONTRACTOR SHALL PROVIDE NAMEPLATES FOR ALL NEW AND EXISTING

ELECTRICAL PANELS AND SWITCHBOARDS IN BUILDING 6 AFFECTED IN THIS

PROJECT SCOPE ONLY.

O. ALL AFFECTED PANELS SHALL HAVE UPDATED TYPED, COMPLETED

DIRECTORIES INDICATING EQUIPMENT SERVED AND ROOM NUMBER (AS

INDICATED ON FINAL BUILDING ROOM SIGNAGE) OF EQUIPMENT LOCATION,

OR SPARE, OR SPACE. HAND WRITTEN DIRECTORIES WILL "NOT" BE

ACCEPTED.

P. RE-SUPPORT EXISTING SYSEM COMPONENTS NOT PROPERLY SUPPORTED

AFTER DEMOLITION AND NOT SCHEDULED FOR WORK.

POWER PLAN NOTES

1. ALL POWER DEVICES TO REMAIN IN THIS ROOM UNLESS OTHERWISE NOTED.

2. PROVIDE A RECESSED MOUNTED 120V, 20A DUPLEX RECEPTACLE AND

CONNECT TO CIRCUIT SHOWN.

3. PROVIDE A RECESSED MOUNTED 120V, QUAD RECEPTACLE AND CONNNECT

TO CIRCUIT SHOWN.

4. PROVIDE NEW ELECTRICAL PANEL IN SAME LOCATION AS PANEL THAT WAS

REMOVED. PROVIDE ALL LABOR AND MATERIALS AS REQUIRED TO EXTEND

EXISTING ASSOCIATED FEEDER AND BRANCH CIRCUIT CONDUCTORS AND

CONDUIT TO NEW PANEL. RECONNECT ALL EXISTING BRANCH CIRCUITS TO

REMAIN TO NEW CIRCUIT BREAKERS IN NEW PANEL, FIELD VERIFY ALL

CIRCUITS TO REMAIN. REFER TO ELECTRICAL ONE-LINE DIAGRAM ON

SHEET EP400 AND ELECTRICAL PANELS ON EP600 SERIES SHEETS FOR

ADDITIONAL INFORMATION. PROVIDE NEW NAMEPLATE STANDARD AS

REQUIRED TO RENAME NEW PANEL TO NEW SITE STANDARD. OLD PANEL

NAME SHOWN IN ( ) FOR REFERENCE ONLY.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Consultant:

C

U s e rs \c b a n k s \D o c u m e n ts \1

.1

.2

M

E P v c b a n k s S

H U

G

.r v t

/1 /2

:2

:2

A M

EP104

SECOND & THIRD FLOOR - C-WING

POWER PLANSGUIDON

1221 N. PENNSYLVANIA STREET

INDIANAPOLIS, IN 46202

317.800.6388

EHRM TRAINING AND ADMIN

SPACE SUPPORT

5000 West National Avenue, Milwaukee, WI 53295

695-21-703

11/12/2021 JDF CMB

100% BID DOCUMENTS

FULLY SPRINKLERED

N N

SCALE: 1/8" = 1'-0"EP104

1 SECOND FLOOR - C-WING - POWER PLAN

SCALE: 1/8" = 1'-0"EP104

2 THIRD FLOOR - C-WING - POWER PLAN

T

DED

GFI

S

G

FI

S M M

S

G

ELEC. ROOM

CB16

80"

208/120V-3PH.-4W,600A

PANEL CBA (EXIST.)

(E)

DIST. PANEL MD-6A(EXIST.)

208/120V-3PH.-4W,1200A

1 2

POWER GENERAL NOTES

A. REFER TO SHEET E000 FOR ELECTRICAL SYMBOL LEGENDS AND

ABBREVIATIONS.

B. REFER TO EP600 SERIES DRAWINGS FOR PANEL SCHEDULES.

C. REFER TO SHEET EP400 FOR THE ELECTRICAL ONE-LINE DIAGRAM.

D. ELECTRICAL ITEMS SHOWN LIGHT WITH A SOLID LINETYPE AND LABELED (E)

ARE EXISTING TO REMAIN UNLESS NOTED OTHERWISE.

E. ELECTRICAL ITEMS SHOWN BOLD WITH A SOLID LINETYPE ARE NEW UNLESS

NOTED OTHERWISE.

F. ALL AFFECTED PANELS SHALL HAVE UPDATED TYPED, COMPLETED

DIRECTORIES INDICATING EQUIPMENT SERVED AND ROOM NUMBER (AS

INDICATED ON FINAL BUILDING ROOM SIGNAGE) OF EQUIPMENT LOCATION,

OR SPARE, OR SPACE. HAND WRITTEN DIRECTORIES WILL "NOT" BE

ACCEPTED.

POWER PLAN NOTES

1. ALL ELECTRICAL PANELS AND EQUIPMENT IN THIS ROOM TO REMAIN

UNLESS NOTED OTHERWISE.

2. ALL POWER DEVICES TO REMAIN IN THIS ROOM UNLESS OTHERWISE NOTED.

3. PROVIDE A DEDICATED DUPLEX RECEPTACLE (NON-GFI) FOR ELEVATOR PIT

SUMP PUMP. MOUNT 54" A.F.F. ABOVE THE PIT FLOOR. COORDINATE LOCATON

WITH ELEVATOR CONTRACTOR.

4. PROVIDE 120V SINGLE-POLE TOGGLE SWITCH AND MOUNT IN ELEVATOR PIT.

COORDINATE MOUNTING HEIGHT AND LOCATIONS WITH ELEVATOR SHOP

DRAWINGS. CONNECT TO LINE SIDE OF GFI RECEPTACLE.

5. MAINTENANCE RECEPTACLE IN ELEVATOR PIT. COORDINATE LOCATION WITH

ELEVATOR CONTRACTOR. CONNECT THE ELEVATOR PIT LIGHT TO THE LINE

SIDE OF THIS RECEPTACLE.

6. PROVIDE LOCAL DISCONNECT SWITCH FOR ELEVATOR CONTROLLER AND

UTILIZE EXISTING ELEVATOR CIRCUIT. PROVIDE SHUNT TRIP IF REQUIRED BY

ELEVATOR SPECIFICATIONS. REWORK EXISTING FEEDER AS REQUIRED.

COORDINATE WITH ELEVATOR SPECIFICATIONS PRIOR TO INSTALL.

7. PROVIDE A 30AMP LOCAL DISCONNECT SWITCH FOR ELEVATOR CAB LIGHTS.

PROVIDE A LOCKABLE 120 VOLT SWITCH WITH 20AMP TYPE RK1 FUSES FOR

THE CAB LIGHTING. COORDINATE WITH ELEVATOR CONTRACTOR. UTILIZE

EXISTING ELEVATOR CAB CIRCUIT.

8. PROVIDE A 120V LINEAR LED LIGHT AND MOUNT BOTTOM OF LIGHT 9'-0" A.F.F.

PROVIDE ALL MOUNTING ACCESSORIES REQUIRED. COORDINATE FINAL

LOCATION WITH ALL TRADES PRIOR INSTALL. PROVIDE A DEDICATED

120V/20A/1P CIRCUIT FOR LIGHT AND GFI RECEPTACLE IN THIS ROOM.

CONNECT LIGHT TO CONTROLS SHOWN. REFER TO POWER PLAN ON THIS

SHEET FOR GFI RECEPTACLE LOCATION.

9. PROVIDE 120V, 20A SINGLE-POLE TOGGLE SWITCH TO CONTROL THE TYPE J4

LIGHT IN THIS ROOM.

10. PROVIDE EMERGENCY LIGHT AND WALL MOUNT 7'-6" A.F.F. TO BOTTOM OF

LIGHT AND CONNECT TO CIRCUIT SHOWN.

11. PROVIDE A 120V, 20A, GFI RECEPTACLE AND UTILIZE THE EXISTING

DEDICATED 120V/20A/1P CIRCUIT FOR GFI RECEPTACLE AND LIGHT IN THIS

ROOM. REFER TO LIGHTING PLAN ON THIS SHEET FOR LIGHT LOCATION.

12. PROVIDE NEMA 4, WALL MOUNTED LED LIGHTS IN ELEVATOR PIT MOUNTED

APPROX. 54" A.F.F. PROVIDE A SWITCH (NOTE 4) FOR ELEVATOR PIT LIGHTS

ON SIDE OF SHAFT (ACCESSIBLE FROM THE PIT ACCESS DOOR). MOUNT

SWITCH AT 54" ABOVE PIT FLOOR TO CENTER OF BOX, WITH NEMA 4 FLEXIBLE

SEAL-TIGHT CONDUIT/WIRING CONNECTION FROM THE SWITCH TO THE NEMA

4 LIGHTS. ALL NEMA 4 ELECTRICAL WORK SHALL BE IDENTIFIED FOR USE IN

WET LOCATIONS IN ACCORDANCE WITH NFPA 70.

13. PROVIDE A 208V-1PH. MOTOR RATED DISCONNNECT FOR INDOOR UNIT UNIT

AND CONNECT TO CIRCUIT SHOWN. REFER TO MECHANICAL DRAWINGS FOR

ADDITIONAL INFORMATION.

O

ELECTRICAL CLOSET

CB09

EXIST. DIST. PANEL MD-6

208/120V-3PH.-4W-3,000A

1 2

F

ELEV.

C2-P

EP300

EP300

EV1 EV1

EV1EV1

CB5:8 CB5:8

CB5:8CB5:8

12 (TYPICAL OF 4)

CB5:4

3 (SP-C2-P)

SP-C2-P

CB5:8

F

ELEV.

C2-P

ELEV. MACHINE.

C121

CB5:12

MD-6A

CB5:10

DSS-C121

TO OUTDOOR

UNIT CU-C121

F

ELEV.

C2-P

ELEV. MACHINE.

C121

J4

CB5:12

CB5:12

EM2

FIRST FLOOR

100' - 0"

FIRST FLOOR

100' - 0"

SECOND FLOOR

112' - 0"

BASEMENT

90' - 0"

BASEMENT

90' - 0"

GFI

EV1EV1

12(TYPICAL OF 4)

CB5:4

(SUMP PUMP)

CB5:8 CB5:8

CB5:8

FIRST FLOOR

100' - 0"

FIRST FLOOR

100' - 0"

SECOND FLOOR

112' - 0"

BASEMENT

90' - 0"

BASEMENT

90' - 0"

EV1

EV1

CB5:8

CB5:8

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Consultant:

C

U s e rs \c b a n k s \D o c u m e n ts \1

.1

.2

M

E P v c b a n k s S

H U

G

.r v t

/1 /2

:2

:3

A M

EP300

ELECTRICAL ENLARGED PLANS

GUIDON

1221 N. PENNSYLVANIA STREET

INDIANAPOLIS, IN 46202

317.800.6388

EHRM TRAINING AND ADMIN

SPACE SUPPORT

5000 West National Avenue, Milwaukee, WI 53295

695-21-703

11/12/2021 JDF CMB

100% BID DOCUMENTS

FULLY SPRINKLERED

SCALE: 1/4" = 1'-0"EP300

1 BASEMENT - C WING NORTH - ENLARGED ELECTRICAL ROOM CB16

N

SCALE: 1/4" = 1'-0"EP300

2 BASEMENT - C WING SOUTH - ENLARGED ELECTRICAL ROOM CB09

N

SCALE: 1/4" = 1'-0"EP300

3 BASEMENT - C WING NORTH - ELEVATOR POWER & LIGHTING PLAN

N

SCALE: 1/4" = 1'-0"EP300

4 FIRST FLOOR - C WING NORTH - ELEVATOR POWER PLAN

N

SCALE: 1/4" = 1'-0"EP300

5 FIRST FLOOR - C WING NORTH ELEVATOR LIGHTING PLAN

N

SCALE: 1/4" = 1'-0"EP300

6 C-WING - ELEVATOR SOUTH POWER & LIGHTING SECTION

SCALE: 1/4" = 1'-0"EP300

7 C-WING - ELEVATOR NORTH POWER & LIGHTING SECTION

FIRST FLR.

B1-2 208/120V

150A

MCB

3PH.,4W

FIRST FLR.

C1-4 208/120V

225A

MCB

3PH.,4W

THIRD FLR.

C3-1 208/120V

100A

MCB

3PH.,4W

CB-5

208/120V

150A

MCB

3PH.,4W

CBA

208/120V

600A

MCB

3PH.,4W

A1-3 208/120V

225A

MCB

3PH.,4W

CB-2

208/120V

100A

MLO

3PH.,4W

FIRST FLR.

B-1 208/120V

100A

MLO

3PH.,4W

C1-…