Technical Questions - Milwaukee EHRM 3-14-22.pdf

PDF 233 KB Posted

Attached to
Y1DZ--EHRM Training and Admin Space Support Construction - Milwaukee, WI 695-21-703 Federal contract opportunity
Solicitation number
36C77622B0017
Issued by
Department of Veterans Affairs Technology Acquisition Center Austin

About this file

This document contains technical questions and responses related to a solicitation for the EHRM Training and Admin Space Support Construction project in Milwaukee, WI. The solicitation seeks a contractor to perform construction work including HVAC, electrical, and plumbing installation and repairs, as well as flooring replacement and painting, at the Milwaukee VA Medical Center. The questions and answers provide clarification on project requirements such as commissioning responsibilities, testing scopes, environmental remediation needs, and controls integration responsibilities. The responses indicate the awarded contractor will be responsible for disposing of contaminated soils, testing and balancing air distribution systems, and connecting new fire detection devices to the existing panel. The work must meet historic preservation standards and be conducted in phases to minimize disruptions.

View the file

Other files for this federal contract opportunity

Other files attached to Y1DZ--EHRM Training and Admin Space Support Construction - Milwaukee, WI 695-21-703, newest first.
File Type Posted
Technical Questions - Milwaukee EHRM 3-28-22.pdf PDF
36C77622B0017 0005.pdf PDF
MH100 - BASEMENT - C WING - MECHANICAL HVAC PLAN.pdf PDF
Attachment 13 - Construction Wage Rates - Milwaukee County - 03-18-22.pdf PDF
Technical Questions - Milwaukee EHRM 3-23-22.pdf PDF
MP104 - SECOND AND THIRD FLOOR - C WING - MECHANICAL PIPING PLAN.pdf PDF
MH102 - FIRST FLOOR - C WING - MECHANICAL HVAC PLAN.pdf PDF
MM500 - MECHANICAL DETAILS.pdf PDF
MP103 - FIRST FLOOR - C WING - MECHANICAL PIPING PLAN.pdf PDF
36C77622B0017 0004.pdf PDF
Drawing Changes 3-23-22.pdf PDF
MH103 - SECOND AND THIRD FLOOR - C WING - MECHANICAL HVAC PLAN.pdf PDF
MM600 - MECHANICAL SCHEDULES.pdf PDF
MM700 - MECHANICAL CONTROL SYSTEMS.pdf PDF
Question 93 C-wing north roof.JPG JPG image
36C77622B0017 0003.pdf PDF
Question 64 Third Floor Structural.pdf PDF
Question 69 Section Through A Wing North.pdf PDF
Question 74 Porch Detail.pdf PDF
36C77622B0017 0002.pdf PDF
Attachment 13 - Construction Wage Rates - Milwaukee County - 02-25-22.pdf PDF
Attachment 13 - Construction Wage Rates - Milwaukee County - 02-18-22.pdf PDF
Site Visit Sign-in Sheet - Milwaukee 2-23-22.pdf PDF
36C77622B0017 0001.pdf PDF
Attachment 2 - Specifications Volume 2.pdf PDF
Attachment 9 - COVID-19 Safety Protocols 12-14-21.pdf PDF
Attachment 4 - Drawings 1 of 4.pdf PDF
Attachment 7 - Drawings 4 of 4.pdf PDF
Attachment 10 - Limitations on Subcontracting - Construction.docx DOCX document
Attachment 13 - Construction Wage Rates - Milwaukee County - 02-04-22.pdf PDF
Attachment 15 - Milwaukee VAMC Map - EHRM Site Visit.pdf PDF
Attachment 5 - Drawings 2 of 4.pdf PDF
Attachment 8 - Contractor Core Work Hours.pdf PDF
Attachment 11 - Brand Name Justification - Milwaukee.pdf PDF
IFB - 36C77622B0017 - 2-10-22.pdf PDF
Attachment 3 - Final SOW - 1-27-22.pdf PDF
Attachment 14 - Contractor Safety - Environmental Form.docx DOCX document
Attachment 1 - Specifications Volume 1.pdf PDF
Attachment 6 - Drawings 3 of 4.pdf PDF
Attachment 12 - NESHAP Asbestos Survey.pdf PDF
Show all 40

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

TECHNICAL QUESTIONS AND

RESPONSES TRACKING SHEET

SOLICITATION #

36C77622B0017

PROJECT TITLE

Milwaukee EHRM Training and Admin Space Support Construction Project

# RECEIVED

DATE

ANSWERED

DATE

CONTRACTOR QUESTIONS VA RESPONSES TO QUESTIONS

1 2/28/22 3/14/22 There is no commissioning specification except for the reference on page 25 of specification section 01 00 24, paragraph 1.24 that commissioning is to be completed per specification section 23 05 93 which is the Test and Balancing contractor. Is this correct or will the government be hiring an independent 3rd party commission agent for Division 23 HVAC work? There are no commissioning specifications for any other trade craft work. We ask that you clarify the commissioning requirements for the project and provide specification sections describing the scope of work required.

Contractors to commission, test and certify their respective systems. Also responsible for training of VA staff. The VA will contract separately for independent commissioning.

2 2/28/22 3/14/22 Please confirm that non-destructive examination of the piping welds as described in specification section 23 22 13, section 3.2, item “H” is a requirement for this project for the steam and condensate piping.

Yes, this requirement shall be followed for the steam and condensate piping.

3 2/28/22 3/14/22 Has the VA tested the ductwork and mechanical systems scheduled for demolition or relocation for biohazards? If the ductwork or equipment are contaminated, remediation will be required by a subcontractor.

The VA has not performed biohazard testing of the ductwork scheduled to be removed. The ductwork scheduled for demolition do not serve laboratories or isolation rooms that would have biohazards.

4 2/28/22 3/14/22 Specification Section 23 31 00: Confirm all ductwork to be sealed to Class A and tested to 2” WG pressure classes.

Please confirm that HVAC boxes and ductwork after the VAV do not need to be tested.

All ductwork shall be tested per pressure class and SMACNA as stated in Paragraph 1.6. All ductwork shall be tested per Paragraph 3.2, unless reduced by Owner/COR.

5 2/28/22 3/14/22 Clarify who is responsible for motor controllers for HVAC equipment.

The contractor is responsible for supplying and installing all motor controllers as per the construction documents.

# RECEIVED

DATE

ANSWERED

DATE

CONTRACTOR QUESTIONS VA RESPONSES TO QUESTIONS

6 2/28/22 3/14/22 Is a third-party scheduling consultant required on this project, or can the contractor develop and manage the schedule with its own staff?

Yes, as per specification section 01 32 16.15, paragraph1.3

7 2/28/22 3/14/22 Will a commissioning agent be appointed by the VA and are all associated costs being paid by the VA?

The contractor is responsible for startup, manufacturer commissioning, and training as per the specifications. The VA may hire an external commissioning agent for 3rd party services.

8 2/28/22 3/14/22 Please clarify the scope of work associated with duct testing.

Please be specific what the VA needs tested.

Duct leakage testing is required for newly installed portions of the air distribution system.

9 2/28/22 3/14/22 Does the sustainable project apply? LEED? No, LEED does not apply.

10 2/28/22 3/14/22 If after uncovering existing conditions there is a need for subgrade soil repairs, will the work have to stop until an approved Supplemental Agreement is in place, or will there be pre-determined unit rates/costs established so the work can proceed accordingly?

If this is determined, an RFI shall be submitted to the Post Award CO and then a determination of how to proceed will be made at that point.

11 2/28/22 3/14/22 Per Section 31 20 11 Part 3.6-D contaminated soils are not allowed to be stockpiled on site. Please confirm this is the case. If not, will a designated area for stockpiling contaminated soils be located with the project boundaries? Is all the soil considered contaminated or is there only isolated areas?

Section 31 20 11 Part 3.6D is not part of this project.

Section 31 20 00 Earthwork is part of this project. It states that contaminated soil (containing asbestos) cannot be stockpiled on site. Contaminated soils to be disposed of properly offsite. Soil not containing asbestos is considered historical fill material and can be reused at the project site.

All soil not reused must be hauled off-site per Specification 31 20 00 Paragraph 3.6.D.

12 2/28/22 3/14/22 Can any of the contaminated soils designated by the Resident Engineer be used as backfill?

Per Section 31 20 00, any disturbed contaminated soil is to be removed from the site. Contaminated soil cannot be stored on site. Contaminated soils to be disposed of properly offsite.

ANSWERED

DATE

CONTRACTOR QUESTIONS VA RESPONSES TO QUESTIONS

13 2/28/22 3/14/22 Will the VA provide direction as to when the stockpiled contaminated soil is to be removed and where it is to be taken to?

Per Section 31 20 00, contractor is responsible for properly disposing contaminated soil offsite. Contaminated soil cannot be stockpiled on site. Contaminated soils to be disposed of properly offsite.

14 2/28/22 3/14/22 Is there a Soil Profile showing the levels of contaminates for this project and will it be provided? If not, where should we figure the contaminated soils need to and will the VA be providing that paperwork showing compliance with all State and Local requirements?

The VA has a soil profile for historical fill materials from our entire campus, which is primarily low levels of PAH.

As agreed with the DNR, the VA sends any unusable soil to licensed landfill as it is assumed the same historical fill is present throughout the campus. It is acceptable to re-use the historical fill material on the site – the VA only uses their profile in the case that disposal of the soil is required. Milwaukee VA GEMS department has documentation to show the DNR guidance given to the VA on this process from 2017. The VA will not be providing soil profile or compliance documentation pre-bid, however, awarded contractor shall work with the COR to establish a disposal profile for the project.

15 2/28/22 3/14/22 Will the contractor be responsible to carry in their bid and pay for the tipping fees associated with the disposal of the contaminated soils?

Contractor will be required to pay for tipping fees associated with the disposal of contaminated soils.

16 2/28/22 3/14/22 Confirm all work can done during normal daytime work shifts?

Except major outages, which should be figured for off shift hours.

Refer to Construction Phasing Notes on GC101 for parameters on when work should happen. Most work can happen during normal daytime hours, however there is corridor work and A-Wing north work that will require after hours work.

17 2/28/22 3/14/22 Is the contractor required to clean all existing ductwork? Contractor is to clean ductwork in accordance with Specification 23 31 00 Paragraph 3.1.H

18 2/28/22 3/14/22 Is an offer guarantee (Bid Bond) required? Yes. Please review the RFP for the specific requirements.

ANSWERED

DATE

CONTRACTOR QUESTIONS VA RESPONSES TO QUESTIONS

19 2/28/22 3/14/22 What percent of SDVOSB labor is required? For construction it is 15%. See VAAR 852.219-77.

20 2/28/22 3/14/22 Confirm that the fabricator and install are not required to be AISC certified?

AISC certification not required. Copy of relevant work experience IS required.

21 2/28/22 3/14/22 Is a 3rd party Fire penetration inspector required for this project and is that inspector to be hired by contractor?

Per Specification 07 84 00 Paragraph 1.5.C, the contractor is to engage a qualified inspector to perform inspections and final reports.

22 2/28/22 3/14/22 Do the MEPF contractors need to include an allowance for _____ hours for training as specified?

General Contractor will provide the training as identified in the specifications.

23 2/28/22 3/14/22 How many copies of the O&M do you require? Per Specification 01 00 00 Paragraph 1.25.A and B, the contractor is required to upload one copy of the O&M manual for initial review and provide four hardcopies after approval.

24 2/28/22 3/14/22 Specs say all OSHA cards and AHAs need to be submitted with APP. This is not feasible. Is it acceptable to submit OSHA cards and AHAs during the project, but 2 weeks prior to related work starting?

General Contractor to submit OSHA cards of Competent Persons listed in the Accident Prevention Plan (APP) concurrently with the APP submission. Remaining OSHA cards can be submitted with Activity Hazard Analysis (AHA) 14 days prior to start of related work for approval.

25 2/28/22 3/14/22 Has any of the existing paint and plaster been tested? Is the paint consider lead and need to abated? Or can all materials be disposed of Construction Debris?

All tested materials identified in the Abatement report, Attachment 12, that is part of the solicitation.

26 2/28/22 3/14/22 Is a painting sample panel required, or can traditional “drawdowns” be provided for approval?

Traditional drawdowns may be provided for approval.

COR will use drawdown to confirm correct paint on finished walls. Any discrepancy will require the paint on the walls to be corrected.

ANSWERED

DATE

CONTRACTOR QUESTIONS VA RESPONSES TO QUESTIONS

27 2/28/22 3/14/22 Please confirm that the “Mockup Panel” for painting can be done in the field at the start of the painting operations. This can be done on the finished walls in place during the painting operations.

Mockup Panel may be done on the finished walls in place during the painting operations.

28 2/28/22 3/14/22 Can paint be applied with a HVLP sprayer? The specifications state “spray application with approval of COR”

No, HVLP sprayers may not be used on the VA campus.

29 2/28/22 3/14/22 Please confirm the new Hollow Metal Frames are to be grouted solid ONLY at CMU walls per the details on plan page AE601?

All new Hollow Metal Frames will be grouted solid, not just those in CMU walls. Detail 1, AE601 and Detail 2, AE601 should show grout solid door frame. This is also specified in specification 08 11 13, paragraph 2.5d.

30 2/28/22 3/14/22 Does the SSHO need to be a separate individual from the prime contractor’s superintendent?

Per specification 01 35 26 Paragraph 1.7, the SSHO is required to be a separate individual from the prime contractor’s superintendent.

31 2/28/22 3/14/22 Can flexible conduit be used in casework/Millwork? Yes.

32 2/28/22 3/14/22 Please clarify if the intent of BLDG 20, 3rd floor is to achieve a flat / Level floor. Current scope is to install 2x12” and new floor approximately 1.5” above the exiting floor. The existing floor is not flat and level. Please advise.

The new floor is to be flat and level.

33 2/28/22 3/14/22 In Building 20, 3rd floor. Plan page SF101, detail 4 calls out for new 5/8” Plywood Sheathing. BUT Plan page AE105, Plan Note #1 calls for new 2X Hardwood Flooring. Please clarify what is required.

Use hardwood plank flooring per 2/SF103 and AE105.

34 2/28/22 3/14/22 Are any finishes (Painting, flooring, etc.) to be provided in BLDG 20, 3rd Floor?

No, just replacement of the flooring as shown.

ANSWERED

DATE

CONTRACTOR QUESTIONS VA RESPONSES TO QUESTIONS

35 2/28/22 3/14/22 Per specification 23 09 23 1.1.D.1: “The General Contractor of this project shall directly hire the Control System Integrator in a contract separate from the contract procuring the controls contractor administered by this Section of the technical specifications.” Please confirm the DDC contractor shall be a direct sub to the GC and cannot be incorporated into the HVAC contract.

Either the General Contractor or the Mechanical Contractor may hire the Control System Integrator.

36 2/28/22 VAVs C106-C thru C124-A are listed on the VAV schedule but not shown on the plans. Associated thermostat locations reference hot water coils and not VAVs. Are VAVs 106-C, C118, C118-A, C118-B, C124, and C124-A required? If yes, please identify locations on the plans.

It appears that they might have been scheduled as VAVs and not HWCs. These VAVs are not required as they are covered in the HWC schedule. Updated drawings will be included in a future amendment.

37 2/28/22 Specification 23 09 23 Low temperature protection devices (freeze stats) are not shown on the AHU Schematic. Are freeze stats required?

Freeze stats are required for each AHU. This shall match the existing Station standard with the existing BAS.

Updated information will be included in a future amendment.

38 2/28/22 Specification section 23 09 23 - The VAV schematic shows a SA-T before the VAV box. Supply temperature is measured at each AHU. Can this point be used globally as the supply air temperature to each VAV box, or are individual supply air temperature sensors required at every VAV?

The SA-T sensor at the main AHU is only required, and not at each VAV. This shall match the existing Station standard with the existing BMS. Updated information will be included in a future amendment.

39 2/28/22 3/14/22 Specification Section 23 09 23 - Are all associated BAS graphics/user views to be updated for any existing equipment serving new terminal units (ex// update all associated VAV and AHU graphics for existing AHU serving new boxes)?

Yes, that is correct. All existing and new equipment shall be as part of the BAS graphics/user views.

ANSWERED

DATE

CONTRACTOR QUESTIONS VA RESPONSES TO QUESTIONS

40 2/28/22 3/14/22 Specification 22 14 29 2.1.H calls for the sump pump to have a provision of alarm monitoring and BACnet capabilities for the BAS. There is nothing in the plans or specs calling for the controls contractor to communicate with or pick up an alarm from the sump pump(s). Are the sump pumps to be monitored by the BAS? Which points are to be monitored?

Yes, the sump pumps are to be monitored. The BAS shall accept an alarm signal from the sump pump control panel for output to the BAS alarm notification system.

41 2/28/22 3/14/22 Specification 09 23 3.1.B.1 – 4 Calls for controls wiring to be in conduit. Can controls wiring be ran free air (with appropriate J-Hooks, etc.) above removeable ceilings? This would provide an installation cost savings.

Control wiring may be run free air as long as they are properly supported with J-Hooks and labeled.

42 2/28/22 3/14/22 Is the DDC contractor to provide a laptop as specified in section 23 09 23 1.1.D.3?

No, monitoring is conducted at a centralized location on campus.

43 2/28/22 Can a DDC points list/schedule be provided? There is an AHU Points list on MM700; however, more lists will be provided for all other equipment in a future amendment.

44 2/28/22 3/14/22 There are some remaining desks on the 3rd floor of BLDG 6.

Will these be removed prior to the project, or should these be figure for the GC to remove?

The furniture currently located on the 3rd floor of building 6 will be removed prior to the start of work by VA.

45 2/28/22 3/14/22 Question #: 1 Sheet: N/A Spec: 23 09 23 Topic: BAS Question: Does prime contractor need to hire 23 09 23 controls directly? Does prime contractor have hire third-party DIV 25 integration contractors?

See answer to question number 35.

ANSWERED

DATE

CONTRACTOR QUESTIONS VA RESPONSES TO QUESTIONS

46 2/28/22 3/14/22 Question #: 2 Sheet: AE104 Spec: 07 Topic: Roofing Warranty Question: Please confirm who has the roofing warranty and provide point of contact for the facility.

Referencing 07 01 50, paragraph 1.8B, “perform work to maintain existing roofing warranty in effect.” There is no active roofing warranty to maintain on the roofs located on building 6, C wing north.

47 2/28/22 3/14/22 Question #: 3 Sheet: N/A Spec: General Conditions Topic: Material Staging Question: Please confirm if contract has material staging location at facility. If so, where is it? Is prime contractor responsible for any costs associated with staging?

Material Staging location identified on drawing sheet, CS101. Secure storage is the responsibility of the contractor.

48 2/28/22 3/14/22 Question #: 4 Sheet: N/A Spec: N/A Topic: SOW Question: Please confirm order of precedence for the contract documents. Does SOW prevail over all documents?

Refer to VAAR 852.236-71 on pages 56 and 57 of the RFP. The SOW is only an overview of the Statement of Bid Items, the schedule, and phasing.

49 2/28/22 3/14/22 Question #: 5 Sheet: N/A Spec: N/A Topic: Submittal Exchange Question: Is the contractor responsible for cost associated with submittal exchange software?

We use OPCENTER. VA will provide access to contractor after award.

50 2/28/22 3/14/22 Question #: 6 Sheet: N/A Spec: N/A Topic: Historical Preservation Question: Are Building 6 and / or Building 20 considered to be historical buildings? If so, are there any work requirements regarding the historical preservation of the buildings that the contractor should be aware of?

Yes, building 6 and building 20 are both historical buildings. Work requirements are covered by Section 106 of the National Historic Preservation Act and meet the Secretary of the Interior’s standards in preserving the standards for historic buildings. Oversight is maintained by the required concurrence from the National Park Service and the Wisconsin State Preservation Office, that any work on the buildings will not cause an adverse effect on the historic property itself.

ANSWERED

DATE

CONTRACTOR QUESTIONS VA RESPONSES TO QUESTIONS

51 2/28/22 3/14/22 Question #: 7 Sheet: N/A Spec: N/A Topic: Dumpsters Question: Will the VA be providing dumpsters? If so, at what locations will dumpsters be provided?

No, contractor is responsible for dumpsters for this construction project.

52 2/28/22 3/14/22 Question #: 8 Sheet: N/A Spec: 05 12 00 Topic: AISC Certification Question: Is the steel fabricator and / or erector required to have an AISC Certification?

No, AISC certification is not required, but a list of relevant project experience must be provided.

53 2/28/22 3/14/22 Question #: 9 Sheet: CI001 Spec: N/A Topic: Site Work Question: Does the site work correspond with any specific phase of this job? Are there any phasing constraints limiting when site work can be performed relative to the rest of the project?

Refer to GC101 for phasing requirements. Porch/ramp work is identified in a phase, however parking lot work is not constrained to a phase.

54 2/28/22 3/14/22 Question #: 10 Sheet: SF501, SF102 Spec: N/A Topic: Ledger Question: SF102 says to remove and replace ledger, while SF501 refers to ledger as “existing”. Please confirm whether the contractor is responsible for replacing the existing ledger, or if the existing ledger is to remain.

SF102 specifies “as required”. Ledger to remain unless current condition of ledgers do not allow for construction to exist as shown. Assume replacement of 30% of ledgers along the perimeter.

ANSWERED

DATE

CONTRACTOR QUESTIONS VA RESPONSES TO QUESTIONS

55 2/28/22 3/14/22 Question #: 11 Sheet: AD100 Spec: N/A Topic: Entrance Security Question: While removing and replacing the door, frame, and hardware at the Building 6 C-Wing entrance per drawing page AD100, is the contractor responsible for securing this entrance to the building? If so, please provide clarity on what security measures are required at this location.

Contractor is responsible for the security of the building while exterior walls/doors are open. Contractor to construct a temporary fully enclosed vestibule with door during the replacement. The door shall have keyed entry hardware on the exterior, keyed to contractor/FM keyway.

The door should be temporarily tied into the P2000.

56 2/28/22 3/14/22 Question #: 12 Sheet: N/A Spec: N/A Topic: Furniture / Equipment Relocation Question: Who is responsible for moving furniture / equipment / miscellaneous items to and from work areas during construction? Is this to be done by the VA or by the contractor as part of this contract?

The furniture/ equipment and miscellaneous items will be removed prior to the start of work by VA. The remaining furniture currently located in building 6, C wing, first floor will be moved by VA following the completion of the building 20 floor work.

57 2/28/22 3/14/22 Question #: 13 Sheet: N/A Spec: N/A Topic: X-ray Question: Is contractor responsible for x-ray scanning for existing MEP components prior to saw cutting floor slab?

Yes, the contractor is responsible.

58 2/28/22 3/14/22 Question #: 14 Sheet: N/A Spec: 02 82 11 Topic: Asbestos Question: Have all work areas been tested for asbestos and lead? Please provide an asbestos report

Asbestos report was part of the solicitation, Attachment 12.

ANSWERED

DATE

CONTRACTOR QUESTIONS VA RESPONSES TO QUESTIONS

59 2/28/22 3/14/22 Question #: 15 Sheet: N/A Spec: N/A Topic: Subfloor Replacement Question: Per the site visit, subflooring and underlayment was damaged or missing. For bidding purposes, should prime contractor assume a certain amount of removal and replacement of subflooring. If so, please provide an estimated quantity to be assumed during bid.

Provide 25% of subflooring removal / replacement for bidding purposes.

60 2/28/22 3/14/22 Question #: 16 Sheet: N/A Spec: 09 06 00 Topic: Schedule for Finishes Question: The schedule for finishes in the specifications is completely blank. Please provide a schedule of finishes.

Finish Schedule is on Construction Drawing sheet AI601.

61 2/28/22 3/14/22 Question #: 17 Sheet: N/A Spec: N/A Topic: Window Removal Question: Is it acceptable for the contractor to temporarily remove a window on the 3rd floor as a means of loading in materials?

Yes, the window may be removed temporarily. The contractor will be responsible to remove, protect and reinstall at completion of work. Contractor will also be responsible for any damage to the window, casing, and building.

62 2/28/22 3/14/22 Question #: 18 Sheet: N/A Spec: N/A Topic: Elevator Usage Question: Will the contractor be permitted to utilize the elevators in Buildings 6 and 20?

The contractor will be allowed to use the elevators in building 6 and 20 but will not have exclusive access to the elevators. Contractor will need to coordinate with COR prior to commencement of work. Contractor will also have to provide protection to elevator cab in building 6 since these are passenger elevators and will be shared with the occupants of the building. Movement of large quantities of materials will need to be done before or after regular work hours and coordinated with the COR.

ANSWERED

DATE

CONTRACTOR QUESTIONS VA RESPONSES TO QUESTIONS

63 2/28/22 3/14/22 Question #: 19 Sheet: HA-100, HA101 Spec: 02 82 11 Topic: Asbestos Abatement Question: Keynote 3 on pages HA-100 and HA-101 is not shown on the drawings. Please advise on the locations of 9’’ x 9’’ checkerboard floor tile to be abated per HA-100 and HA- 101 keynote 3

Location of 9x9 checkerboard tile is in A Wing North 1st floor. Approximately 5700 sf. Same location of Keynote 2.

64 2/28/22 3/14/22 Question #: 20 Sheet: SF103 Spec: N/A Topic: Joist Terminations Question: Please provide a detail showing how joists shown on drawing page SF103 terminate into masonry at floor perimeter.

The design team was unable to observe conditions, but per drawings dated 10/23/52, joists at the perimeter rest on 4x4s (see attached plan)

65 2/28/22 3/14/22 Question #: 21 Sheet: N/A Spec: N/A Topic: Miscellaneous Hangers Question: Are Miscellaneous hangers on ceilings intended to be removed or abandoned in place?

Miscellaneous hangers on ceilings that are not being used should be removed.

66 2/28/22 3/14/22 Question #: 22 Sheet: N/A Spec: N/A Topic: Final Clean Question: Is the contractor responsible for final cleaning upon completion of work?

Yes, the contractor is responsible for a final cleaning prior to turning over the space to the VA.

67 2/28/22 3/14/22 Question #: 23 Sheet: N/A Spec: 01 45 29 Topic: Testing Quantities Question: Testing specification does not give approximate test quantities. Please provide the testing quantities anticipated for each activity.

Specification 01 45 29 is not required for this contract.

ANSWERED

DATE

CONTRACTOR QUESTIONS VA RESPONSES TO QUESTIONS

68 2/28/22 3/14/22 Question #: 24 Sheet: AD102, AD103 Spec: N/A Topic: Structural Details Question: AD102 KN 12 and AD103 KN 5 say “cut existing slab to accommodate new stair, refer to structural.” There are no structural details for this provided. Please provide this detail to quantify accurately for bid purposes.

The existing structural conditions were not available during design or in existing documents. Assume two W12 supports at plan north and east borders of the opening with masonry anchors for pricing.

69 2/28/22 3/14/22 Question #: 25 Sheet: SF-102 Spec: N/A Topic: Columns Question: Please provide a detail showing the columns indicated on page SF-102.

See attached drawing.

70 2/28/22 3/14/22 Question #: 26 Sheet: FX-101, FX-102, FX-103, FX-104, FX- 105 Spec: N/A Topic: Fire Protection Question: If the fire protection system to remain live during construction?

The fire protection system in A Wing 1st Floor, C Wing Basement/1st floor is not operational. Installation of Heat Detectors and connection to the fire panel is required by the contractor. This system needs to remain in place during the duration of the construction. See Specification 01 01 10SN, paragraph 3.

71 2/28/22 3/14/22 Question #: 27 Sheet: N/A Spec: N/A Topic: Heat Detectors Question: Is the contractor responsible for providing heat detectors during construction?

Heat detectors are required. The contractor is responsible for providing and maintaining the heat detectors throughout construction. The heat detectors must be tied to the Building Siemen Pyrotronics system. See Specification 01 01 10SN, paragraph 3.

ANSWERED

DATE

CONTRACTOR QUESTIONS VA RESPONSES TO QUESTIONS

72 2/28/22 3/14/22 Question #: 28 Sheet: N/A Spec: N/A Topic: Steel Channels Question: It was noted during the site visit walk through that there were new steel channels bolted to the old beams. Will the contractor be responsible for completing the remaining sections with the new steel on both sides of the old beams to support the new load?

Steel was placed in a previous project to repair deteriorated wood. It is not within the scope of this project to add more steel to beams.

73 2/28/22 3/14/22 Question #: 29 Sheet: N/A Spec: N/A Topic: Load Capacity – 3rd floor Question: Please provide the load capacity for staging of the new materials on the 3rd floor.

In building 20, Guidon does not recommend loads higher than 30 psf before the new structure has been placed, 50 psf after.

74 2/28/22 3/14/22 Question #: 30 Sheet: SF-501 Spec: N/A Topic: Porch Post Question: Please provide a full detail of the porch post “top to bottom” called out on the plan page SF- 501

See attached existing detail of porch. Posts are 7 ½ x 7 ½ wood, approx. 12’ high. Connect into architectural elements above.

75 2/28/22 3/14/22 Question #: 31 Sheet: N/A Spec: N/A Topic:

Question: It was noted at the site visit that the existing basement floor is pitched. What is the new finish floor grade in the basement to be?

Multiple options for the finish floor grade are not anticipated. Final flooring to be level in newly constructed areas.

76 2/28/22 3/14/22 Question #: 32 Sheet: Plumbing drawings Spec: N/A Topic: Vent Pipe Question: Drawings show a vent pipe to be routed from 1st floor up to and through roof. Is this pipe run to be exposed?

If this is referring to the piping exposed in CB21 DHW/Utility, the piping can be exposed and protected per specifications. A chase or shaft is not required for this pipe.

ANSWERED

DATE

CONTRACTOR QUESTIONS VA RESPONSES TO QUESTIONS

77 2/28/22 Question #: 33 Sheet: N/A Spec: N/A Topic: Slab thickness Question: Please provide a floor slab thickness to be assumed for all floor slabs within the work area of this project.

Do not assume existing slab thickness. Field Verify. More information to come in a future amendment.

78 2/28/22 3/14/22 Question #: 34 Sheet: N/A Spec: N/A Topic: Deck height Question: Please provide the deck height to be assumed for all areas within this project.

See AE323 for preliminary floor to floor heights. Field verify.

79 2/28/22 3/14/22 Question #: 35 Sheet: CS101, CS102 Spec: 31 20 00 Topic: Contaminated Soil Question: Is soil within the work area considered to be contaminated? If so, can contaminated soil be used as backfill?

The VA has a soil profile for historical fill materials from our entire campus, which is primarily low levels of PAH.

As agreed with the DNR, the VA sends any unusable soil to licensed landfill as it is assumed the same historical fill is present throughout the campus. It is acceptable to re-use the historical fill material on the site – the VA only uses their profile in the case that disposal of the soil is required. Milwaukee VA GEMS department has documentation to show the DNR guidance given to the VA on this process from 2017. The VA will not be providing soil profile or compliance documentation pre-bid, however, awarded contractor shall work with the COR to establish a disposal profile for the project. Any disturbed contaminated soil is to be removed from the site.

Contaminated soil cannot be stored on site. Contaminated soils to be disposed of properly offsite.

ANSWERED

DATE

CONTRACTOR QUESTIONS VA RESPONSES TO QUESTIONS

80 2/28/22 3/14/22 Question #: 36 Sheet: Civil Drawings Spec: 31 20 00 Topic: Stockpiling Question: Is the contractor allowed to stockpile and reuse existing subgrade material?

Section 31 20 00 Earthwork is part of this project. It states that contaminated soil (containing asbestos) cannot be stockpiled on site. Contaminated soils to be disposed of properly offsite. Soil not containing asbestos is considered historical fill material and can be reused at the project site.

All soil not reused must be hauled off-site per Specification 31 20 00 Paragraph 3.6.D.

81 2/28/22 3/14/22 Question #: 37 Sheet: Civil Drawings Spec: N/A Topic: Survey Question: Is the contractor responsible for performing and reporting a topographic survey of exterior area prior to construction?

Topographic survey was performed for design and drawings were created utilizing survey data. Contractor shall confirm existing conditions shown.

82 2/28/22 3/14/22 Question #: 38 Sheet: N/A Spec: N/A Topic: Utility Locate Question: Is the contractor responsible for performing a utility locate to identify underground utilities prior to performing civil work?

Yes, the contractor is responsible for performing a utility locate to identify underground utilities prior to performing civil work.

83 2/28/22 3/14/22 Question #: 39 Sheet: N/A Spec: N/A Topic: Landscape Restoration Question: Are grass areas disturbed by construction to be restored with seed or sod?

Landscape restoration will be accomplished using sod.

84 2/28/22 3/14/22 Question #: 40 Sheet: N/A Spec: N/A Topic: Geotechnical Report Question: Is a geotechnical report of the exterior work area available? If so, please provide.

Geotech report is not available.

ANSWERED

DATE

CONTRACTOR QUESTIONS VA RESPONSES TO QUESTIONS

85 2/28/22 3/14/22 Question #: 41 Sheet: N/A Spec: 01 45 29 Topic: Geotechnical Engineer Question: Please confirm that the contractor is responsible for hiring a third-party geotechnical engineer for inspection and observation of civil work.

Inspection and observation must be performed by accredited testing laboratory in accordance with Specification 01 45 29 and provided by the contractor.

86 2/28/22 3/14/22 Question #: 42 Sheet: SF103 Spec: N/A Topic: Joist Hangers Question: Are new hangers required at every piece of blocking for new joists?

Yes.

87 2/28/22 3/14/22 Question #: 43 Sheet: SF103 Spec: N/A Topic: Floor details Question: Details on SF103 show new plank floor, and then also show new 5/8’’ sheet flooring. Please confirm new floor type in Building 20.

Plank floor to be used per 2/SF103 and sheet AE105.

88 2/28/22 3/14/22 Question #: 44 Sheet: N/A Spec: N/A Topic: Plaster Finish Question: At areas where plaster finish is to be removed, is gypsum feathering acceptable as a new finish, or must plaster be replaced to match existing?

See finish drawings for information on finishes.

89 2/28/22 3/14/22 Question #: 45 Sheet: N/A Spec: N/A Topic: Drywall finish Question: Please clarify what level of drywall finishing is acceptable for areas in which drywall is to be replaced or repaired.

See 09 29 00 specification for level of finish.

ANSWERED

DATE

CONTRACTOR QUESTIONS VA RESPONSES TO QUESTIONS

90 2/28/22 Question #: 46 Sheet: N/A Spec: N/A Topic: Saw Cutting Question: Please provide a detail showing areas of floor slab to be saw cut for new removal and replacement of in-slab piping.

See plumbing drawings for locations of in slab piping.

Additional information to be provided in a future amendment.

91 2/28/22 3/14/22 Question #: 47 Sheet: Plumbing Drawings Spec: 22 00 00 Topic: Plumbing Demolition Question: Plumbing drawings show existing pipe in floor slab to removed. In order to limit saw cutting and potential structural complications, would it be acceptable to abandon-in-place existing pipe within slab rather than remove? If so, please provide direction on what is required for pipes to be abandoned- in-place, such as flowable fill, etc.

All piping shall be removed per drawings.

92 3/1/22 3/14/22 Glass/Glazing:

Where is floor #CB25 listed on the door schedule (AE601) located? According to the door schedule, it should be in the elevator lobby CB22, but it is not seen on floor plan AE100.

Please disregard CB25. This door is not required in the project.

93 3/1/22 3/14/22 Roofing:

Due to inaccessibility during the site visit, does the owner have photos or other documentation of the roof areas to be worked on? Un-accessibility will be detrimental to determining the best price for thru roof repairs and EPDM roofing installation.

Photographs of the roof are part of the amendment.

ANSWERED

DATE

CONTRACTOR QUESTIONS VA RESPONSES TO QUESTIONS

94 3/1/22 3/14/22 Furniture:

Will all of the furniture in the various spaces be moved by the owner prior to work commencing based on proposed phasing plan and scheduled work activities? If not, has then been factored into the IGE?

The furniture will be removed prior to the start of work by VA. The remaining furniture currently located in building 6, C wing, first floor will be moved by VA following the completion of the building 20 floor work.

95 3/1/22 3/14/22 Flooring:

Flooring in Building 20 is described as a maximum bearing weight of 50lbs/sf. Who/what agency determined the existing flooring capacity? This impacts the ability to utilize mechanical lifts or scaffolding to access the work areas.

Please advise.

Load capacity was done by a 3rd party structural engineer and is the driving force behind floor replacement. It is not advised for higher loads than the 45 psf prescribed to be placed on new structure, 28 on existing.

96 3/1/22 3/14/22 Waste:

Will waste chutes be considered as feasible in logistics/refuse planning?

Yes, waste chutes will be allowed with COR coordination and limiting impact to staff using the buildings. The contractor will be responsible to remove, protect and reinstall the windows at completion of work. Contractor will also be responsible for any damage to the window, casing, and building due to the use of the chute.

97 3/1/22 3/14/22 Per specification 23 09 23 1.1.D.1: “The General Contractor of this project shall directly hire the Control System Integrator in a contract separate from the contract procuring the controls contractor administered by this Section of the technical specifications.”

Please confirm the DDC contractor will be working directly for the GC.

See answer to question number 35.

98 3/1/22 3/14/22 VAVs C106-C thru C124-A are listed on the VAV schedule but not shown on the plans. Associated thermostat locations reference hot water coils and not VAVs. Are VAVs 106-C, C118, C118-A, C118-B, C124, and C124-A required? If yes, please identify locations on the plans.

See answer to question number 36.

ANSWERED

DATE

CONTRACTOR QUESTIONS VA RESPONSES TO QUESTIONS

99 3/1/22 3/14/22 Specification 23 09 23 o Low temperature protection devices (freeze stats) are not shown on the AHU Schematic.

Are freeze stats required?

o The VAV schematic shows a SA-T before the VAV box.

Supply temperature is measured at each AHU. Can this point be used globally as the supply air temperature to each VAV box, or are individual supply air temperature sensors required at every VAV?

o Are all associated BAS graphics/user views to be updated for any existing equipment serving new terminal units (ex// update all associated VAV and AHU graphics for existing AHU serving new boxes)?

o Specification 22 14 29 2.1.H calls for the sump pump to have a provision of alarm monitoring and BACnet capabilities for the BAS. There is nothing in the plans or specs calling for the controls contractor to communicate with or pick up an alarm from the sump pump(s). Are the sump pumps to be monitored by the BAS? Which points are to be monitored?

o Specification 09 23 3.1.B.1 – 4 Calls for controls wiring to be in conduit. Can controls wiring be ran free air (with appropriate J-Hooks, etc.) above removeable ceilings?

This would provide an installation cost savings.

o Is the DDC contractor to provide a laptop as specified in section 23 09 23 1.1.D.3?

o Can a DDC points list/schedule be provided?

See answers to question numbers 37, 38, 39, 40, 41, 42 and 43 respectively.

3/4/22 3/14/22 Door #CB27 I cannot find its location on the plan sheets For the other aluminum doors I found these on the plan sheet and there it gave me the frame type to show the elevation for same. Thus I need an elevation view to see if it has sidelites or transom glazing.

I believe you meant to type CB25 as there is no CB27 on the door schedule and drawings. Door CB25 is not required on this project.