MM600 - MECHANICAL SCHEDULES.pdf

PDF 188 KB Posted

Attached to
Y1DZ--EHRM Training and Admin Space Support Construction - Milwaukee, WI 695-21-703 Federal contract opportunity
Solicitation number
36C77622B0017
Issued by
Department of Veterans Affairs Technology Acquisition Center Austin

About this file

This mechanical schedule document provides specifications for various HVAC systems and components for the EHRM Training and Admin Space Support project located in Milwaukee, Wisconsin. It includes schedules for air handling units, condensing units, diffusers and grilles, exhaust fans, cabinet unit heaters, electric heaters, ductless split systems, VAV boxes, return fans, hoods, hot water coils, and other mechanical equipment. Key details covered include manufacturers and models, operating weights, airflow and pressure drop data, heating and cooling capacities, electrical requirements, and relevant notes for each item.

The related federal contract opportunity is a solicitation for the construction project to support the specified renovations. Solicitation number 36C77622B0017 has a description matching the mechanical schedule documents and lists the Department of Veterans Affairs Technology Acquisition Center in Austin as the contracting agency. The opportunity type is noted as a solicitation and additional supporting documentation is referenced but not included here.

View the file

Other files for this federal contract opportunity

Other files attached to Y1DZ--EHRM Training and Admin Space Support Construction - Milwaukee, WI 695-21-703, newest first.
File Type Posted
36C77622B0017 0005.pdf PDF
Technical Questions - Milwaukee EHRM 3-28-22.pdf PDF
Attachment 13 - Construction Wage Rates - Milwaukee County - 03-18-22.pdf PDF
Technical Questions - Milwaukee EHRM 3-23-22.pdf PDF
MP104 - SECOND AND THIRD FLOOR - C WING - MECHANICAL PIPING PLAN.pdf PDF
MH102 - FIRST FLOOR - C WING - MECHANICAL HVAC PLAN.pdf PDF
MM500 - MECHANICAL DETAILS.pdf PDF
MP103 - FIRST FLOOR - C WING - MECHANICAL PIPING PLAN.pdf PDF
36C77622B0017 0004.pdf PDF
Drawing Changes 3-23-22.pdf PDF
MH103 - SECOND AND THIRD FLOOR - C WING - MECHANICAL HVAC PLAN.pdf PDF
MM700 - MECHANICAL CONTROL SYSTEMS.pdf PDF
MH100 - BASEMENT - C WING - MECHANICAL HVAC PLAN.pdf PDF
36C77622B0017 0003.pdf PDF
Question 64 Third Floor Structural.pdf PDF
Question 69 Section Through A Wing North.pdf PDF
Question 74 Porch Detail.pdf PDF
Technical Questions - Milwaukee EHRM 3-14-22.pdf PDF
Question 93 C-wing north roof.JPG JPG image
36C77622B0017 0002.pdf PDF
Attachment 13 - Construction Wage Rates - Milwaukee County - 02-25-22.pdf PDF
36C77622B0017 0001.pdf PDF
Attachment 13 - Construction Wage Rates - Milwaukee County - 02-18-22.pdf PDF
Site Visit Sign-in Sheet - Milwaukee 2-23-22.pdf PDF
Attachment 5 - Drawings 2 of 4.pdf PDF
Attachment 8 - Contractor Core Work Hours.pdf PDF
Attachment 11 - Brand Name Justification - Milwaukee.pdf PDF
IFB - 36C77622B0017 - 2-10-22.pdf PDF
Attachment 3 - Final SOW - 1-27-22.pdf PDF
Attachment 14 - Contractor Safety - Environmental Form.docx DOCX document
Attachment 1 - Specifications Volume 1.pdf PDF
Attachment 6 - Drawings 3 of 4.pdf PDF
Attachment 12 - NESHAP Asbestos Survey.pdf PDF
Attachment 2 - Specifications Volume 2.pdf PDF
Attachment 9 - COVID-19 Safety Protocols 12-14-21.pdf PDF
Attachment 4 - Drawings 1 of 4.pdf PDF
Attachment 7 - Drawings 4 of 4.pdf PDF
Attachment 10 - Limitations on Subcontracting - Construction.docx DOCX document
Attachment 13 - Construction Wage Rates - Milwaukee County - 02-04-22.pdf PDF
Attachment 15 - Milwaukee VAMC Map - EHRM Site Visit.pdf PDF
Show all 40

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Consultant:

C U s e rs \c h a w k \D o c u m e n ts

\1 .1

.2

M E

P v c h a w k D

D

W

.r v t

/2

/2

:1

:2

A

M

MM600

MECHANICAL SCHEDULES

GUIDON

1221 N. PENNSYLVANIA STREET

INDIANAPOLIS, IN 46202

317.800.6388

EHRM TRAINING AND ADMIN

SPACE SUPPORT

5000 West National Avenue, Milwaukee, WI 53295

695-21-703

11/12/2021 CDH AJS

100% BID DOCUMENTS

FULLY SPRINKLERED

AIR HANDLING UNIT SCHEDULE

IDENTITY DATA AIRFLOW DATA PREHEATING DATA COOLING DATA HUMIDIFIER GRID DATA ELECTRICAL DATA

REMARKSMARK MANUFACTURER MODEL

OPERATING

WEIGHT (LBS)

SUPPLY

AIRFLOW (CFM)

OUTDOOR

AIRFLOW (CFM) ESP (IN WC) TSP (IN WC) EAT (°F) LAT (°F)

CAPACITY

(BTUH) EWT (°F) LWT (°F)

FLOWRATE

(GPM) WPD (FT WG)

EAT (°F) [DB /

WB]

LAT (°F) [DB /

WB]

TOTAL CAPACITY

(BTUH)

SENSIBLE

CAPACITY

(BTUH)

REFRIGERANT

TYPE SST (°F)

ENTERING AIR

CONDITIONS [DB (°F) /

RH (%)]

LEAVING AIR

CONDITIONS [DB (°F)

/ RH (%)] LOAD (LB/HR)

VOLTAGE /

PHASE FLA MCA / MOCP

AHU-A121 YORK XTI-45x66 3400 6000 1500 1.75 4.75 50 78 181,000 160 140 18.5 1.3 80 / 67 52.1 / 51.9 265,000 176,000 R-410A 46 55 / 30 55 / 41 27 208 / 3 12.0 15.0 / 25.0 1 - 3

AHU-C126 YORK XTI-60x48 2900 6000 1500 2.25 5.30 50 78 181,000 160 140 18.5 1.3 80 / 67 52.5 / 52.1 261,000 174,000 R-410A 45 55 / 30 55 / 41 27 208 / 3 12.0 15.6 / 25.0 1 - 3

AHU-CB42 YORK XTI-48x54 2600 5000 1250 2.00 4.95 50 78 151,200 160 140 15.0 1.2 80 / 67 51.4 / 51.1 229,000 150,000 R-410A 45 55 / 30 55 / 41 23 208 / 3 8.7 10.9 / 17.5 1 - 3

REMARKS:

1. MANUFACTURER AND MODEL INFORMATION FOR BASIS OF DESIGN ONLY.

2. COORDINATE WITH ARCHITECTURAL PLANS FOR CEILING TYPE.

3. PROVIDE WITH (2) 3/4" SLOTS. DIFFUSER TO BE INSTALLED IN LAY-IN CEILING.

4. PROVIDE WITH SINGLE 0° DEFLECTION BLADES AT 0.75" SPACING.

5. PROVIDE WITH DOUBLE DEFLECTION BLADES AT 0.75" SPACING

REMARKS:

1. MANUFACTURER AND MODEL INFORMATION FOR BASIS OF DESIGN ONLY.

2. PROVIDE WITH LIGHTING AND OUTLETS FOR 120V/1P CONNECTION.

3. PROVIDE WITH 2" MERV 8 AND 4" MERV 11 COMBINATION PREFILTERS.

REMARKS:

1. MANUFACTURER AND MODEL INFORMATION FOR BASIS OF DESIGN ONLY.

2. UNIT SHALL OPERATE DOWN TO 32°F WITH FULL COOLING. PROVIDE WIND BAFFLES/LOW AMBIENT KIT.

CONDENSING UNIT SCHEDULE

IDENTITY DATA COOLING DATA ELECTRICAL DATA

REMARKSMARK MANUFACTURER MODEL

OPERATING

WEIGHT (LBS)

TOTAL

CAPACITY(BTUH)

SENSIBLE

CAPACITY (BTUH)

AMBIENT TEMP

(°F) VOLTAGE / PHASE MCA / MOCP

CU-A121 YORK J25YCC00A2JLB4 1000 265,00 176,000 95 208 / 3 113.8 / 150 1 - 2

CU-C121 LG LSU180HSV5 200 18,000 12,600 95 208 / 1 13 / 20 1 - 2

CU-C126 YORK J25YCC00A2JLB4 1000 265,000 176,000 95 208 / 3 113.8 / 150 1 - 2

CU-CB42 YORK J20YCC00A2JLB4 1000 200,250 140,175 95 208 / 3 73.3 / 100 1 - 2

DIFFUSERS, REGISTERS, AND GRILLES SCHEDULE

IDENTITY DATA

SYSTEM STYLE / TYPE PANELSIZE (IN) NECK SIZE (IN) MATERIAL COLOR REMARKSMARK MANUFACTURER MODEL

EG24 PRICE 80 EXHAUST AIR EGGCRATE 24x24 22x22 ALUMINUM WHITE 1 - 2

LSD24-6 PRICE SDS SUPPLY AIR LINEAR SLOT DIFFUSER 24x4 6ø ALUMINUM WHITE 1 - 3

LSD24-6 PRICE SDS SUPPLY AIR LINEAR SLOT DIFFUSER 24x4 8ø ALUMINUM WHITE 1 - 3

LSD24-8 PRICE SDS SUPPLY AIR LINEAR SLOT DIFFUSER 24x4 8ø ALUMINUM WHITE 1 - 3

LSD36-6 PRICE SDS SUPPLY AIR LINEAR SLOT DIFFUSER 24x4 6ø ALUMINUM WHITE 1 - 3

LSD36-8 PRICE SDS SUPPLY AIR LINEAR SLOT DIFFUSER 36x8 8ø ALUMINUM WHITE 1 - 3

LSD72-8 PRICE SDS SUPPLY AIR LINEAR SLOT DIFFUSER 72x8 8ø ALUMINUM WHITE 1 - 3

RG12/8 PRICE 510Z RETURN AIR SIDEWALL RETURN GRILLE 10x8 12x8 STEEL WHITE 1,4

RG16/6 PRICE 510Z Undefined SIDEWALL TRANSFER GRILLE 10x8 16x6 STEEL WHITE 1,4

RG24 PRICE 80 RETURN AIR EGGCRATE 24x24 22x22 STEEL WHITE 1 - 2

RG24/14 PRICE 510Z RETURN AIR SIDEWALL RETURN GRILLE 24x14 24x14 STEEL WHITE 1,4

RG30/8 PRICE 510Z Undefined SIDEWALL TRANSFER GRILLE 10x8 30x8 STEEL WHITE 1,4

RG30/10 PRICE 510Z RETURN AIR SIDEWALL RETURN GRILLE 10x8 30x10 STEEL WHITE 1,4

RG36/10 PRICE 510Z RETURN AIR SIDEWALL RETURN GRILLE 36x10 36x10 STEEL WHITE 1,4

SD6 PRICE SCD SUPPLY AIR SQUARE CONE DIFFUSER 24x24 6ø STEEL WHITE 1 - 2

SD8 PRICE SCD SUPPLY AIR SQUARE CONE DIFFUSER 24x24 8ø STEEL WHITE 1 - 2

SD10 PRICE SCD SUPPLY AIR SQUARE CONE DIFFUSER 24x24 10ø STEEL WHITE 1 - 2

SG10/4 PRICE 510 SUPPLY AIR SIDEWALL SUPPLY GRILLE 24x24 10x4 STEEL WHITE 1,5

SG10/6 PRICE 510 SUPPLY AIR SIDEWALL SUPPLY GRILLE 10x8 10x6 STEEL WHITE 1,5

SG12/4 PRICE 510 SUPPLY AIR SIDEWALL SUPPLY GRILLE 12x4 12x4 STEEL WHITE 1,5

SG16/4 PRICE 510 SUPPLY AIR SIDEWALL SUPPLY GRILLE 10x8 16x4 STEEL WHITE 1,5

SG24/6 PRICE 510 SUPPLY AIR SIDEWALL SUPPLY GRILLE 10x8 24x6 STEEL WHITE 1,5

EXHAUST FAN SCHEDULE

IDENTITY DATA AIR DATA SOUND DATA ELECTRICAL DATA

REMARKSMARK MANUFACTURER MODEL TYPE DRIVE WEIGHT (LBS) AIRFLOW (CFM) ESP (IN WG) RPM INLET (SONES) RADIATED (SONES) VOLTAGE / PHASE BHP NOM HP

EF-C119C GREENHECK SQ-140-VG INLINE DIRECT 100 2200 1.00 1566 15.0 10.5 120 / 1 0.67 1 1 - 5

REMARKS:

1. PROVIDE LISTED MANUFACTURER AND MODEL OR EQUAL.

2. PROVIDE WITH EC MOTOR WITH DIAL ON EXRACTOR HOUSING (MOUNTED AND WIRED).

3. PROVIDE WITH INTEGRAL NEMA-1, TOGGLE DISCONNECT SWITCH (MOUNTED AND WIRED).

4. PROVIDE WITH 120/1 MOTORIZED BACKDRAFT DAMPER (SHIPPED LOOSE).

5. PROVIDE WITH NEOPRENE ISOLATORS AND HANGING BRACKETS FOR INSTALLATION (SHIPPED LOOSE).

CABINET UNIT HEATER SCHEDULE

IDENTITY DATA AIRFLOW DATA HEATING DATA ELECTRICAL DATA

REMARKSMARK MANUFACTURER MODEL

OPERATING WEIGHT

(LBS) AIRFLOW (CFM) ESP (IN WG) EAT (°F) LAT (°F)

CAPACITY

(BTUH) EWT (°F) LWT (°F) FLOWRATE (GPM WPD (FT WG)

VOLTAGE /

PHASE FLA MCA / MOCP

CUH-A121 TRANE FF080 250 800 0.30 65 95 25,920 160 140 2.75 1.5 120 / 1 3.2 2 / 15 1 - 2

CUH-C4 TRANE FF080 250 800 0.30 65 95 25,920 160 140 2.75 1.5 120 / 1 3.2 2 / 15 1 - 2

CUH-C126 TRANE FF080 250 800 0.30 65 95 25,920 160 140 2.75 1.5 120 / 1 3.2 2 / 15 1 - 2

CUH-CB4 TRANE FF080 250 800 0.30 65 95 25,920 160 140 2.75 1.5 120 / 1 3.2 2 / 15 1 - 2

CUH-CB22A TRANE FF040 200 400 0.25 65 95 12,960 160 140 1.50 1.3 120 / 1 2.5 1.3 / 15 1 - 2

CUH-CB24 TRANE FF040 200 400 0.25 65 95 12,960 160 140 1.50 1.3 120 / 1 2.5 1.3 / 15 1 - 2

CUH-CB50 TRANE FF080 250 800 0.30 65 95 25,920 160 140 2.75 1.5 120 / 1 3.2 2 / 15 1 - 2

REMARKS:

1. MANUFACTURER AND MODEL INFORMATION FOR BASIS OF DESIGN ONLY.

2. PROVIDE WITH LOUVERED CEILING ADAPTER. COORDINATE WITH ARCHITECTURAL PLANS FOR CEILING TYPE.

ELECTRIC HEATER SCHEDULE

MARK

IDENTITY DATA AIRFLOW DATA ELECTRICAL DATA

REMARKSMANUFACTURER MODEL

OPERATING

WEIGHT (LBS) TYPE AIRFLOW (CFM) EAT (°F) LAT (°F)

VOLTAGE /

PHASE KW AMPS

ECH-CB42 QMARK EFF4008 45 CEILING 300 65 95 208 / 1 4 19.2 1,2,3

ECH-CB49 QMARK EFF4008 45 CEILING 300 65 95 208 / 1 4 19.2 1,2,3

EWH-C119C QMARK AWH4408F 35 WALL 300 65 95 208 / 1 4 19.2 1,2,4

EWH-CB21 QMARK AWH4408F 35 WALL 300 65 95 208 / 1 4 19.2 1,2,4

REMARKS:

1. MANUFACTURER AND MODEL INFORMATION FOR BASIS OF DESIGN ONLY.

2. PROVIDE WITH INTEGRAL DISCONNECT AND THERMOSTAT.

3. PROVIDE WITH HANGER/BRACKETS FOR CEILING/STRUCTURAL INSTALLATION.

4. PROVIDE WITH HANGER/BRACKETS FOR WALL INSTALLATION.

DUCTLESS SPLIT SYSTEM SCHEDULE

MARK MANUFACTURER MODEL

OPERATING

WEIGHT (LBS) AIRFLOW (CFM)

COOLING DATA

HEATING CAPACITY

(BTUH)

VOLTAGE /

PHASE MCA / MOCP REMARKS

COOLING

TONNAGE

TOTAL CAPACITY

(BTUH)

SENSIBLE

CAPACITY (BTUH)

DSS-C121 LG LSN180HSV5 220 600 1.5 18,000 12,600 21,000 208 / 1 2 / 15 1 - 2

REMARKS:

1. MANUFACTURER AND MODEL INFORMATION FOR BASIS OF DESIGN ONLY.

2. PROVIDE WITH HEAT PUMP CYCLE. PROVIDE WITH SHIPPED-LOOSE CONDENSATE PUMP.

VAV BOX SCHEDULE

IDENTITY DATA

COOLING

DESIGN

AIRFLOW (CFM)

MINIMUM

SETPOINT

AIRFLOW (CFM)

AIR DATA

CAPACITY

(MBH)

WATER DATA SOUND DATA

REMARKSMARK MANUFACTURER MODEL BOX / INLET SIZE (IN)

MIN BOX

AIRFLOW (CFM)

MAX BOX

AIRFLOW (CFM)

HEATING

AIRFLOW (CFM) EAT (°F) LAT (°F)

MAX APD (IN

WG)

MIN BOX STATIC

(IN WG) EWT (°F) LWT (°F)

FLOWRATE

(GPM)

MAX WATER

PD (FT WG)

RADIATED

SOUND POWER

(DB) [@ 3RD

OCTAVE BAND]

DISCHARGE

SOUND POWER

(DB) [@ 3RD

OCTAVE BAND]

VAV-A118-A PRICE SDV 12 300 2600 2150 1615 1615 55 95 0.50 0.75 68.0 160 140 7.0 3 52 63 1 - 2

VAV-A118-B PRICE SDV 10 210 1800 1600 1050 1050 55 95 0.50 0.75 51.8 160 140 4.5 3 47 60 1 - 2

VAV-A122 PRICE SDV 10 210 1800 1675 750 750 55 95 0.50 0.75 54.2 160 140 3.2 3 47 60 1 - 2

VAV-A124 PRICE SDV 10 210 1800 1425 1070 1070 55 95 0.50 0.75 50.3 160 140 4.6 3 47 60 1 - 2

VAV-C141 PRICE SDV 6 65 550 610 460 460 55 95 0.50 0.75 19.9 160 140 2.0 3 49 63 1 - 2

VAV-C142 PRICE SDV 4 45 400 300 225 225 55 95 0.50 0.75 9.7 160 140 1.0 3 41 56 1 - 2

VAV-C143 PRICE SDV 8 125 1100 950 715 715 55 95 0.50 0.75 30.9 160 140 3.3 3 46 61 1 - 2

VAV-C144 PRICE SDV 8 125 1100 760 570 570 55 95 0.50 0.75 24.6 160 140 2.5 3 46 61 1 - 2

VAV-C145 PRICE SDV 9 160 1400 1140 835 835 55 95 0.50 0.75 36.9 160 140 3.8 3 49 61 1 - 2

VAV-C146 PRICE SDV 8 125 1100 960 720 720 55 95 0.50 0.75 31.1 160 140 3.3 3 46 61 1 - 2

VAV-C148 PRICE SDV 8 125 1100 940 700 700 55 95 0.50 0.75 30.2 160 140 3.0 3 46 61 1 - 2

VAV-CB41 PRICE SDV 9 160 1400 950 715 715 55 95 0.50 0.75 30.9 160 140 3.1 3 49 61 1 - 2

VAV-CB43 PRICE SDV 9 160 1400 950 715 715 55 95 0.50 0.75 30.9 160 140 3.1 3 49 61 1 - 2

VAV-CB44 PRICE SDV 9 160 1400 950 715 715 55 95 0.50 0.75 30.9 160 140 3.1 3 49 61 1 - 2

VAV-CB45 PRICE SDV 9 160 1400 950 715 715 55 95 0.50 0.75 30.9 160 140 3.1 3 49 61 1 - 2

VAV-CB46 PRICE SDV 9 160 1400 950 715 715 55 95 0.50 0.75 30.9 160 140 3.1 3 49 61 1 - 2

VAV-CB48 PRICE SDV 9 160 1400 950 715 715 55 95 0.50 0.75 30.9 160 140 3.1 3 49 61 1 - 2

REMARKS:

1. MANUFACTURER AND MODEL INFORMATION FOR BASIS OF DESIGN ONLY.

2. PROVIDE WITH MINIMUM 2-ROW COILS ON BOXES WITH COILS.

RETURN FAN SCHEDULE

IDENTITY DATA AIR DATA SOUND DATA ELECTRICAL DATA

REMARKSMARK MANUFACTURER MODEL TYPE DRIVE WEIGHT (LBS) AIRFLOW (CFM) ESP (IN WG) RPM INLET (SONES) OUTLET (SONES) VOLTAGE / PHASE BHP NOM HP

RF-A121 GREENHECK QEID-22 MIXED FLOW DIRECT 400 6000 1.00 1044 17.2 21 208 / 3 2.11 3 1 - 2

RF-C126 GREENHECK QEID-18 MIXED FLOW DIRECT 250 6000 1.50 1747 22 24 208 / 3 2.66 3 1 - 2

RF-CB42 GREENHECK QEID-18 MIXED FLOW DIRECT 250 5000 1.00 1444 17.1 18.7 208 / 3 2.64 3 1 - 2

REMARKS:

1. MANUFACTURER AND MODEL INFORMATION FOR BASIS OF DESIGN ONLY.

2. PROVIDE WITH GALVANIZED FINISH, BOLTED ACCESS DOOR, EXTENDED MOTOR WIRING, PUNCHED INLET AND OUTLET FLANGES, AND UL/CUL-705 LISTING.

HOOD SCHEDULE

IDENTITY DATA AIRFLOW DATA

REMARKSMARK MANUFACTURER MODEL

OPERATING

WEIGHT (LBS) LOCATION AIRFLOW (CFM) THROAT SIZE (IN) SERVICE PRESSURE DROP (IN WC)

EH-C119C GREENHECK GRSR-24 100 C119C ROOF 2200 24Ø EXHAUST 0.10 1 - 2

REMARKS:

1. MANUFACTURER AND MODEL INFORMATION FOR BASIS OF DESIGN ONLY.

2. PROVIDE WITH INSECT SCREEN AND 18 INCH ROOF CURB.

Revisions: Date:

Revision 1 03/21/2022

HOT WATER COIL SCHEDULE

IDENTITY DATA AIR DATA

CAPACITY (MBH)

WATER DATA

REMARKSMARK MANUFACTURER MODEL DUCT SIZE (IN)

AIRFLOW

(CFM) EAT (°F) LAT (°F)

MAX AIR PD

(IN WG) EWT (°F) LWT (°F)

FLOWRATE

(GPM)

MAX WATER

PD (FT WG)

HWC-C106C GREENHECK CUSTOM HW 24 x 12 1100 55 95 0.5 47.5 160 140 4.8 3 1 - 2

HWC-C118 GREENHECK CUSTOM HW 16 x 12 750 55 95 0.5 32.4 160 140 3.3 3 1 - 2

HWC-C118A GREENHECK CUSTOM HW 8 x 8 150 55 95 0.5 6.5 160 140 0.8 3 1 - 2

HWC-C119A GREENHECK CUSTOM HW 16 x 8 450 55 95 0.5 19.4 160 140 2.0 3 1 - 2

HWC-C119B GREENHECK CUSTOM HW 16 x 8 450 55 95 0.5 19.4 160 140 2.0 3 1 - 2

HWC-C124 GREENHECK CUSTOM HW 16 x 12 700 55 95 0.5 30.2 160 140 3.0 3 1 - 2

HWC-C124A GREENHECK CUSTOM HW 10 x 10 300 55 95 0.5 13.0 160 140 1.5 3 1 - 2

HWC-C302 GREENHECK CUSTOM HW 12 x 12 600 55 95 0.5 25.9 160 140 2.8 3 1 - 2

HWC-C304 GREENHECK CUSTOM HW 10 x 10 450 55 95 0.5 19.4 160 140 2.0 3 1 - 2

HWC-C305 GREENHECK CUSTOM HW 20 x 10 1100 55 95 0.5 47.5 160 140 4.8 3 1 - 2

HWC-CB16 GREENHECK CUSTOM HW 24 x 6 500 55 95 0.5 21.6 160 140 2.3 3 1 - 2

HWC-CB17 GREENHECK CUSTOM HW 24 x 8 650 55 95 0.5 28.1 160 140 2.8 3 1 - 2

HWC-CB19A GREENHECK CUSTOM HW 16 x 8 450 55 95 0.5 19.4 160 140 2.0 3 1 - 2

HWC-CB19B GREENHECK CUSTOM HW 16 x 8 450 55 95 0.5 19.4 160 140 2.0 3 1 - 2

HWC-CB23 GREENHECK CUSTOM HW 18 x 6 350 55 95 0.5 15.1 160 140 1.5 3 1 - 2

REMARKS:

1. MANUFACTURER AND MODEL INFORMATION FOR BASIS OF DESIGN ONLY.

2. PROVIDE WITH MINIMUM 2-ROW COILS.

Sheets
MH100 - BASEMENT - C WING - MECHANICAL HVAC PLAN
MH102 - FIRST FLOOR - C WING - MECHANICAL HVAC PLAN
MH103 - SECOND AND THIRD FLOOR - C WING - MECHANICAL HVAC PLAN
MM500 - MECHANICAL DETAILS
MM600 - MECHANICAL SCHEDULES
MP103 - FIRST FLOOR - C WING - MECHANICAL PIPING PLAN
MP104 - SECOND AND THIRD FLOOR - C WING - MECHANICAL PIPING PLAN

File details come from the government source that posted it. Updated .