MM600 - MECHANICAL SCHEDULES.pdf
PDF 188 KB Posted
- Attached to
- Y1DZ--EHRM Training and Admin Space Support Construction - Milwaukee, WI 695-21-703 Federal contract opportunity
- Solicitation number
- 36C77622B0017
About this file
This mechanical schedule document provides specifications for various HVAC systems and components for the EHRM Training and Admin Space Support project located in Milwaukee, Wisconsin. It includes schedules for air handling units, condensing units, diffusers and grilles, exhaust fans, cabinet unit heaters, electric heaters, ductless split systems, VAV boxes, return fans, hoods, hot water coils, and other mechanical equipment. Key details covered include manufacturers and models, operating weights, airflow and pressure drop data, heating and cooling capacities, electrical requirements, and relevant notes for each item.
The related federal contract opportunity is a solicitation for the construction project to support the specified renovations. Solicitation number 36C77622B0017 has a description matching the mechanical schedule documents and lists the Department of Veterans Affairs Technology Acquisition Center in Austin as the contracting agency. The opportunity type is noted as a solicitation and additional supporting documentation is referenced but not included here.
View the file
Other files for this federal contract opportunity
Show all 40
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Consultant:
C U s e rs \c h a w k \D o c u m e n ts
\1 .1
.2
M E
P v c h a w k D
D
W
.r v t
/2
/2
:1
:2
A
M
MM600
MECHANICAL SCHEDULES
GUIDON
1221 N. PENNSYLVANIA STREET
INDIANAPOLIS, IN 46202
317.800.6388
EHRM TRAINING AND ADMIN
SPACE SUPPORT
5000 West National Avenue, Milwaukee, WI 53295
695-21-703
11/12/2021 CDH AJS
100% BID DOCUMENTS
FULLY SPRINKLERED
AIR HANDLING UNIT SCHEDULE
IDENTITY DATA AIRFLOW DATA PREHEATING DATA COOLING DATA HUMIDIFIER GRID DATA ELECTRICAL DATA
REMARKSMARK MANUFACTURER MODEL
OPERATING
WEIGHT (LBS)
SUPPLY
AIRFLOW (CFM)
OUTDOOR
AIRFLOW (CFM) ESP (IN WC) TSP (IN WC) EAT (°F) LAT (°F)
CAPACITY
(BTUH) EWT (°F) LWT (°F)
FLOWRATE
(GPM) WPD (FT WG)
EAT (°F) [DB /
WB]
LAT (°F) [DB /
WB]
TOTAL CAPACITY
(BTUH)
SENSIBLE
CAPACITY
(BTUH)
REFRIGERANT
TYPE SST (°F)
ENTERING AIR
CONDITIONS [DB (°F) /
RH (%)]
LEAVING AIR
CONDITIONS [DB (°F)
/ RH (%)] LOAD (LB/HR)
VOLTAGE /
PHASE FLA MCA / MOCP
AHU-A121 YORK XTI-45x66 3400 6000 1500 1.75 4.75 50 78 181,000 160 140 18.5 1.3 80 / 67 52.1 / 51.9 265,000 176,000 R-410A 46 55 / 30 55 / 41 27 208 / 3 12.0 15.0 / 25.0 1 - 3
AHU-C126 YORK XTI-60x48 2900 6000 1500 2.25 5.30 50 78 181,000 160 140 18.5 1.3 80 / 67 52.5 / 52.1 261,000 174,000 R-410A 45 55 / 30 55 / 41 27 208 / 3 12.0 15.6 / 25.0 1 - 3
AHU-CB42 YORK XTI-48x54 2600 5000 1250 2.00 4.95 50 78 151,200 160 140 15.0 1.2 80 / 67 51.4 / 51.1 229,000 150,000 R-410A 45 55 / 30 55 / 41 23 208 / 3 8.7 10.9 / 17.5 1 - 3
REMARKS:
1. MANUFACTURER AND MODEL INFORMATION FOR BASIS OF DESIGN ONLY.
2. COORDINATE WITH ARCHITECTURAL PLANS FOR CEILING TYPE.
3. PROVIDE WITH (2) 3/4" SLOTS. DIFFUSER TO BE INSTALLED IN LAY-IN CEILING.
4. PROVIDE WITH SINGLE 0° DEFLECTION BLADES AT 0.75" SPACING.
5. PROVIDE WITH DOUBLE DEFLECTION BLADES AT 0.75" SPACING
REMARKS:
1. MANUFACTURER AND MODEL INFORMATION FOR BASIS OF DESIGN ONLY.
2. PROVIDE WITH LIGHTING AND OUTLETS FOR 120V/1P CONNECTION.
3. PROVIDE WITH 2" MERV 8 AND 4" MERV 11 COMBINATION PREFILTERS.
REMARKS:
1. MANUFACTURER AND MODEL INFORMATION FOR BASIS OF DESIGN ONLY.
2. UNIT SHALL OPERATE DOWN TO 32°F WITH FULL COOLING. PROVIDE WIND BAFFLES/LOW AMBIENT KIT.
CONDENSING UNIT SCHEDULE
IDENTITY DATA COOLING DATA ELECTRICAL DATA
REMARKSMARK MANUFACTURER MODEL
OPERATING
WEIGHT (LBS)
TOTAL
CAPACITY(BTUH)
SENSIBLE
CAPACITY (BTUH)
AMBIENT TEMP
(°F) VOLTAGE / PHASE MCA / MOCP
CU-A121 YORK J25YCC00A2JLB4 1000 265,00 176,000 95 208 / 3 113.8 / 150 1 - 2
CU-C121 LG LSU180HSV5 200 18,000 12,600 95 208 / 1 13 / 20 1 - 2
CU-C126 YORK J25YCC00A2JLB4 1000 265,000 176,000 95 208 / 3 113.8 / 150 1 - 2
CU-CB42 YORK J20YCC00A2JLB4 1000 200,250 140,175 95 208 / 3 73.3 / 100 1 - 2
DIFFUSERS, REGISTERS, AND GRILLES SCHEDULE
IDENTITY DATA
SYSTEM STYLE / TYPE PANELSIZE (IN) NECK SIZE (IN) MATERIAL COLOR REMARKSMARK MANUFACTURER MODEL
EG24 PRICE 80 EXHAUST AIR EGGCRATE 24x24 22x22 ALUMINUM WHITE 1 - 2
LSD24-6 PRICE SDS SUPPLY AIR LINEAR SLOT DIFFUSER 24x4 6ø ALUMINUM WHITE 1 - 3
LSD24-6 PRICE SDS SUPPLY AIR LINEAR SLOT DIFFUSER 24x4 8ø ALUMINUM WHITE 1 - 3
LSD24-8 PRICE SDS SUPPLY AIR LINEAR SLOT DIFFUSER 24x4 8ø ALUMINUM WHITE 1 - 3
LSD36-6 PRICE SDS SUPPLY AIR LINEAR SLOT DIFFUSER 24x4 6ø ALUMINUM WHITE 1 - 3
LSD36-8 PRICE SDS SUPPLY AIR LINEAR SLOT DIFFUSER 36x8 8ø ALUMINUM WHITE 1 - 3
LSD72-8 PRICE SDS SUPPLY AIR LINEAR SLOT DIFFUSER 72x8 8ø ALUMINUM WHITE 1 - 3
RG12/8 PRICE 510Z RETURN AIR SIDEWALL RETURN GRILLE 10x8 12x8 STEEL WHITE 1,4
RG16/6 PRICE 510Z Undefined SIDEWALL TRANSFER GRILLE 10x8 16x6 STEEL WHITE 1,4
RG24 PRICE 80 RETURN AIR EGGCRATE 24x24 22x22 STEEL WHITE 1 - 2
RG24/14 PRICE 510Z RETURN AIR SIDEWALL RETURN GRILLE 24x14 24x14 STEEL WHITE 1,4
RG30/8 PRICE 510Z Undefined SIDEWALL TRANSFER GRILLE 10x8 30x8 STEEL WHITE 1,4
RG30/10 PRICE 510Z RETURN AIR SIDEWALL RETURN GRILLE 10x8 30x10 STEEL WHITE 1,4
RG36/10 PRICE 510Z RETURN AIR SIDEWALL RETURN GRILLE 36x10 36x10 STEEL WHITE 1,4
SD6 PRICE SCD SUPPLY AIR SQUARE CONE DIFFUSER 24x24 6ø STEEL WHITE 1 - 2
SD8 PRICE SCD SUPPLY AIR SQUARE CONE DIFFUSER 24x24 8ø STEEL WHITE 1 - 2
SD10 PRICE SCD SUPPLY AIR SQUARE CONE DIFFUSER 24x24 10ø STEEL WHITE 1 - 2
SG10/4 PRICE 510 SUPPLY AIR SIDEWALL SUPPLY GRILLE 24x24 10x4 STEEL WHITE 1,5
SG10/6 PRICE 510 SUPPLY AIR SIDEWALL SUPPLY GRILLE 10x8 10x6 STEEL WHITE 1,5
SG12/4 PRICE 510 SUPPLY AIR SIDEWALL SUPPLY GRILLE 12x4 12x4 STEEL WHITE 1,5
SG16/4 PRICE 510 SUPPLY AIR SIDEWALL SUPPLY GRILLE 10x8 16x4 STEEL WHITE 1,5
SG24/6 PRICE 510 SUPPLY AIR SIDEWALL SUPPLY GRILLE 10x8 24x6 STEEL WHITE 1,5
EXHAUST FAN SCHEDULE
IDENTITY DATA AIR DATA SOUND DATA ELECTRICAL DATA
REMARKSMARK MANUFACTURER MODEL TYPE DRIVE WEIGHT (LBS) AIRFLOW (CFM) ESP (IN WG) RPM INLET (SONES) RADIATED (SONES) VOLTAGE / PHASE BHP NOM HP
EF-C119C GREENHECK SQ-140-VG INLINE DIRECT 100 2200 1.00 1566 15.0 10.5 120 / 1 0.67 1 1 - 5
REMARKS:
1. PROVIDE LISTED MANUFACTURER AND MODEL OR EQUAL.
2. PROVIDE WITH EC MOTOR WITH DIAL ON EXRACTOR HOUSING (MOUNTED AND WIRED).
3. PROVIDE WITH INTEGRAL NEMA-1, TOGGLE DISCONNECT SWITCH (MOUNTED AND WIRED).
4. PROVIDE WITH 120/1 MOTORIZED BACKDRAFT DAMPER (SHIPPED LOOSE).
5. PROVIDE WITH NEOPRENE ISOLATORS AND HANGING BRACKETS FOR INSTALLATION (SHIPPED LOOSE).
CABINET UNIT HEATER SCHEDULE
IDENTITY DATA AIRFLOW DATA HEATING DATA ELECTRICAL DATA
REMARKSMARK MANUFACTURER MODEL
OPERATING WEIGHT
(LBS) AIRFLOW (CFM) ESP (IN WG) EAT (°F) LAT (°F)
CAPACITY
(BTUH) EWT (°F) LWT (°F) FLOWRATE (GPM WPD (FT WG)
VOLTAGE /
PHASE FLA MCA / MOCP
CUH-A121 TRANE FF080 250 800 0.30 65 95 25,920 160 140 2.75 1.5 120 / 1 3.2 2 / 15 1 - 2
CUH-C4 TRANE FF080 250 800 0.30 65 95 25,920 160 140 2.75 1.5 120 / 1 3.2 2 / 15 1 - 2
CUH-C126 TRANE FF080 250 800 0.30 65 95 25,920 160 140 2.75 1.5 120 / 1 3.2 2 / 15 1 - 2
CUH-CB4 TRANE FF080 250 800 0.30 65 95 25,920 160 140 2.75 1.5 120 / 1 3.2 2 / 15 1 - 2
CUH-CB22A TRANE FF040 200 400 0.25 65 95 12,960 160 140 1.50 1.3 120 / 1 2.5 1.3 / 15 1 - 2
CUH-CB24 TRANE FF040 200 400 0.25 65 95 12,960 160 140 1.50 1.3 120 / 1 2.5 1.3 / 15 1 - 2
CUH-CB50 TRANE FF080 250 800 0.30 65 95 25,920 160 140 2.75 1.5 120 / 1 3.2 2 / 15 1 - 2
REMARKS:
1. MANUFACTURER AND MODEL INFORMATION FOR BASIS OF DESIGN ONLY.
2. PROVIDE WITH LOUVERED CEILING ADAPTER. COORDINATE WITH ARCHITECTURAL PLANS FOR CEILING TYPE.
ELECTRIC HEATER SCHEDULE
MARK
IDENTITY DATA AIRFLOW DATA ELECTRICAL DATA
REMARKSMANUFACTURER MODEL
OPERATING
WEIGHT (LBS) TYPE AIRFLOW (CFM) EAT (°F) LAT (°F)
VOLTAGE /
PHASE KW AMPS
ECH-CB42 QMARK EFF4008 45 CEILING 300 65 95 208 / 1 4 19.2 1,2,3
ECH-CB49 QMARK EFF4008 45 CEILING 300 65 95 208 / 1 4 19.2 1,2,3
EWH-C119C QMARK AWH4408F 35 WALL 300 65 95 208 / 1 4 19.2 1,2,4
EWH-CB21 QMARK AWH4408F 35 WALL 300 65 95 208 / 1 4 19.2 1,2,4
REMARKS:
1. MANUFACTURER AND MODEL INFORMATION FOR BASIS OF DESIGN ONLY.
2. PROVIDE WITH INTEGRAL DISCONNECT AND THERMOSTAT.
3. PROVIDE WITH HANGER/BRACKETS FOR CEILING/STRUCTURAL INSTALLATION.
4. PROVIDE WITH HANGER/BRACKETS FOR WALL INSTALLATION.
DUCTLESS SPLIT SYSTEM SCHEDULE
MARK MANUFACTURER MODEL
OPERATING
WEIGHT (LBS) AIRFLOW (CFM)
COOLING DATA
HEATING CAPACITY
(BTUH)
VOLTAGE /
PHASE MCA / MOCP REMARKS
COOLING
TONNAGE
TOTAL CAPACITY
(BTUH)
SENSIBLE
CAPACITY (BTUH)
DSS-C121 LG LSN180HSV5 220 600 1.5 18,000 12,600 21,000 208 / 1 2 / 15 1 - 2
REMARKS:
1. MANUFACTURER AND MODEL INFORMATION FOR BASIS OF DESIGN ONLY.
2. PROVIDE WITH HEAT PUMP CYCLE. PROVIDE WITH SHIPPED-LOOSE CONDENSATE PUMP.
VAV BOX SCHEDULE
IDENTITY DATA
COOLING
DESIGN
AIRFLOW (CFM)
MINIMUM
SETPOINT
AIRFLOW (CFM)
AIR DATA
CAPACITY
(MBH)
WATER DATA SOUND DATA
REMARKSMARK MANUFACTURER MODEL BOX / INLET SIZE (IN)
MIN BOX
AIRFLOW (CFM)
MAX BOX
AIRFLOW (CFM)
HEATING
AIRFLOW (CFM) EAT (°F) LAT (°F)
MAX APD (IN
WG)
MIN BOX STATIC
(IN WG) EWT (°F) LWT (°F)
FLOWRATE
(GPM)
MAX WATER
PD (FT WG)
RADIATED
SOUND POWER
(DB) [@ 3RD
OCTAVE BAND]
DISCHARGE
SOUND POWER
(DB) [@ 3RD
OCTAVE BAND]
VAV-A118-A PRICE SDV 12 300 2600 2150 1615 1615 55 95 0.50 0.75 68.0 160 140 7.0 3 52 63 1 - 2
VAV-A118-B PRICE SDV 10 210 1800 1600 1050 1050 55 95 0.50 0.75 51.8 160 140 4.5 3 47 60 1 - 2
VAV-A122 PRICE SDV 10 210 1800 1675 750 750 55 95 0.50 0.75 54.2 160 140 3.2 3 47 60 1 - 2
VAV-A124 PRICE SDV 10 210 1800 1425 1070 1070 55 95 0.50 0.75 50.3 160 140 4.6 3 47 60 1 - 2
VAV-C141 PRICE SDV 6 65 550 610 460 460 55 95 0.50 0.75 19.9 160 140 2.0 3 49 63 1 - 2
VAV-C142 PRICE SDV 4 45 400 300 225 225 55 95 0.50 0.75 9.7 160 140 1.0 3 41 56 1 - 2
VAV-C143 PRICE SDV 8 125 1100 950 715 715 55 95 0.50 0.75 30.9 160 140 3.3 3 46 61 1 - 2
VAV-C144 PRICE SDV 8 125 1100 760 570 570 55 95 0.50 0.75 24.6 160 140 2.5 3 46 61 1 - 2
VAV-C145 PRICE SDV 9 160 1400 1140 835 835 55 95 0.50 0.75 36.9 160 140 3.8 3 49 61 1 - 2
VAV-C146 PRICE SDV 8 125 1100 960 720 720 55 95 0.50 0.75 31.1 160 140 3.3 3 46 61 1 - 2
VAV-C148 PRICE SDV 8 125 1100 940 700 700 55 95 0.50 0.75 30.2 160 140 3.0 3 46 61 1 - 2
VAV-CB41 PRICE SDV 9 160 1400 950 715 715 55 95 0.50 0.75 30.9 160 140 3.1 3 49 61 1 - 2
VAV-CB43 PRICE SDV 9 160 1400 950 715 715 55 95 0.50 0.75 30.9 160 140 3.1 3 49 61 1 - 2
VAV-CB44 PRICE SDV 9 160 1400 950 715 715 55 95 0.50 0.75 30.9 160 140 3.1 3 49 61 1 - 2
VAV-CB45 PRICE SDV 9 160 1400 950 715 715 55 95 0.50 0.75 30.9 160 140 3.1 3 49 61 1 - 2
VAV-CB46 PRICE SDV 9 160 1400 950 715 715 55 95 0.50 0.75 30.9 160 140 3.1 3 49 61 1 - 2
VAV-CB48 PRICE SDV 9 160 1400 950 715 715 55 95 0.50 0.75 30.9 160 140 3.1 3 49 61 1 - 2
REMARKS:
1. MANUFACTURER AND MODEL INFORMATION FOR BASIS OF DESIGN ONLY.
2. PROVIDE WITH MINIMUM 2-ROW COILS ON BOXES WITH COILS.
RETURN FAN SCHEDULE
IDENTITY DATA AIR DATA SOUND DATA ELECTRICAL DATA
REMARKSMARK MANUFACTURER MODEL TYPE DRIVE WEIGHT (LBS) AIRFLOW (CFM) ESP (IN WG) RPM INLET (SONES) OUTLET (SONES) VOLTAGE / PHASE BHP NOM HP
RF-A121 GREENHECK QEID-22 MIXED FLOW DIRECT 400 6000 1.00 1044 17.2 21 208 / 3 2.11 3 1 - 2
RF-C126 GREENHECK QEID-18 MIXED FLOW DIRECT 250 6000 1.50 1747 22 24 208 / 3 2.66 3 1 - 2
RF-CB42 GREENHECK QEID-18 MIXED FLOW DIRECT 250 5000 1.00 1444 17.1 18.7 208 / 3 2.64 3 1 - 2
REMARKS:
1. MANUFACTURER AND MODEL INFORMATION FOR BASIS OF DESIGN ONLY.
2. PROVIDE WITH GALVANIZED FINISH, BOLTED ACCESS DOOR, EXTENDED MOTOR WIRING, PUNCHED INLET AND OUTLET FLANGES, AND UL/CUL-705 LISTING.
HOOD SCHEDULE
IDENTITY DATA AIRFLOW DATA
REMARKSMARK MANUFACTURER MODEL
OPERATING
WEIGHT (LBS) LOCATION AIRFLOW (CFM) THROAT SIZE (IN) SERVICE PRESSURE DROP (IN WC)
EH-C119C GREENHECK GRSR-24 100 C119C ROOF 2200 24Ø EXHAUST 0.10 1 - 2
REMARKS:
1. MANUFACTURER AND MODEL INFORMATION FOR BASIS OF DESIGN ONLY.
2. PROVIDE WITH INSECT SCREEN AND 18 INCH ROOF CURB.
Revisions: Date:
Revision 1 03/21/2022
HOT WATER COIL SCHEDULE
IDENTITY DATA AIR DATA
CAPACITY (MBH)
WATER DATA
REMARKSMARK MANUFACTURER MODEL DUCT SIZE (IN)
AIRFLOW
(CFM) EAT (°F) LAT (°F)
MAX AIR PD
(IN WG) EWT (°F) LWT (°F)
FLOWRATE
(GPM)
MAX WATER
PD (FT WG)
HWC-C106C GREENHECK CUSTOM HW 24 x 12 1100 55 95 0.5 47.5 160 140 4.8 3 1 - 2
HWC-C118 GREENHECK CUSTOM HW 16 x 12 750 55 95 0.5 32.4 160 140 3.3 3 1 - 2
HWC-C118A GREENHECK CUSTOM HW 8 x 8 150 55 95 0.5 6.5 160 140 0.8 3 1 - 2
HWC-C119A GREENHECK CUSTOM HW 16 x 8 450 55 95 0.5 19.4 160 140 2.0 3 1 - 2
HWC-C119B GREENHECK CUSTOM HW 16 x 8 450 55 95 0.5 19.4 160 140 2.0 3 1 - 2
HWC-C124 GREENHECK CUSTOM HW 16 x 12 700 55 95 0.5 30.2 160 140 3.0 3 1 - 2
HWC-C124A GREENHECK CUSTOM HW 10 x 10 300 55 95 0.5 13.0 160 140 1.5 3 1 - 2
HWC-C302 GREENHECK CUSTOM HW 12 x 12 600 55 95 0.5 25.9 160 140 2.8 3 1 - 2
HWC-C304 GREENHECK CUSTOM HW 10 x 10 450 55 95 0.5 19.4 160 140 2.0 3 1 - 2
HWC-C305 GREENHECK CUSTOM HW 20 x 10 1100 55 95 0.5 47.5 160 140 4.8 3 1 - 2
HWC-CB16 GREENHECK CUSTOM HW 24 x 6 500 55 95 0.5 21.6 160 140 2.3 3 1 - 2
HWC-CB17 GREENHECK CUSTOM HW 24 x 8 650 55 95 0.5 28.1 160 140 2.8 3 1 - 2
HWC-CB19A GREENHECK CUSTOM HW 16 x 8 450 55 95 0.5 19.4 160 140 2.0 3 1 - 2
HWC-CB19B GREENHECK CUSTOM HW 16 x 8 450 55 95 0.5 19.4 160 140 2.0 3 1 - 2
HWC-CB23 GREENHECK CUSTOM HW 18 x 6 350 55 95 0.5 15.1 160 140 1.5 3 1 - 2
REMARKS:
1. MANUFACTURER AND MODEL INFORMATION FOR BASIS OF DESIGN ONLY.
2. PROVIDE WITH MINIMUM 2-ROW COILS.
| Sheets |
| MH100 - BASEMENT - C WING - MECHANICAL HVAC PLAN |
| MH102 - FIRST FLOOR - C WING - MECHANICAL HVAC PLAN |
| MH103 - SECOND AND THIRD FLOOR - C WING - MECHANICAL HVAC PLAN |
| MM500 - MECHANICAL DETAILS |
| MM600 - MECHANICAL SCHEDULES |
| MP103 - FIRST FLOOR - C WING - MECHANICAL PIPING PLAN |
| MP104 - SECOND AND THIRD FLOOR - C WING - MECHANICAL PIPING PLAN |