Attachment 4 - EHRM Columbus Drawings Part 2.pdf

PDF 7 MB Posted

Attached to
Y1DA--757-22-705 EHRM Infrastructure Upgrades - Columbus, OH - Tier 2 Construction (VA-22-00108764)
Solicitation number
36C77623R0150
Issued by

About this file

This document package includes construction drawings and specifications for infrastructure upgrades at the Chalmers P. Wylie VA Medical Center in Columbus, Ohio. The project involves replacing aging HVAC systems in several buildings with new ductless split systems, mini-split heat pumps, Liebert computer room air conditioners, and associated controls. Upgrades are also planned for the main computer room, including installation of a temporary cooling system, new raised floor supply air diffusers, reinforced return air ducts, fire dampers, and backdraft dampers. The scope of work entails demolition of existing equipment, installation of new indoor and outdoor units, routing of refrigerant lines, and integration with the existing JCI Metasys control system. Construction is scheduled to take place from May 2023 to June 2023.

View the file

Other files

File Type Posted
Amd 11 Att - RFI Responses_3.12.24.pdf PDF
36C77623R0150 0011.docx DOCX document
36C77623R0150 0010.docx DOCX document
Amd 10_1791.19 - RFI Responses_3.11.24.pdf PDF
Amd 10 23 07 11 HVAC and Boiler Plant Insulation2.pdf PDF
36C77623R0150 0009.docx DOCX document
36C77623R0150 0008.docx DOCX document
OIT Infrastructure Standard for Telecommunications Spaces - Version 3.1.pdf PDF
36C77623R0150 0007.docx DOCX document
Amendment 6 All Files.zip ZIP file
36C77623R0150 0006.docx DOCX document
36C77623R0150 0005.docx DOCX document
36C77623R0150 0004.docx DOCX document
757-22-705 Pre-Bid Site Visit Sign In.pdf PDF
04_Architectural.pdf PDF
36C77623R0150 0003.docx DOCX document
02_Hazardous Materials.pdf PDF
01_General.pdf PDF
06_Mechanical_Drawings.pdf PDF
07_Electrical.pdf PDF
03_Structural.pdf PDF
08_Telecom.pdf PDF
05_Fire Protection.pdf PDF
Columbus EHRM FINAL SPECS VOL 1.pdf PDF
Columbus EHRM FINAL SPECS VOL 2.pdf PDF
36C77623R0150 0002.docx DOCX document
36C77623R0150 0001.docx DOCX document
Attachment 15 -Site Visit Instructions Revised.docx DOCX document
Attachment 11 - 07_Narrative_Electrical.pdf PDF
Attachment 9 - 05_Narrative_Fire Protection.pdf PDF
Attachment 6 - 01_Narrative_Architectural.pdf PDF
Attachment 2 - Contractor Safety - Environmental Form.docx DOCX document
Attachment 13- Wage Rates.pdf PDF
Attachment 8 - 03_Narrative_Structural (1).pdf PDF
Attachment 15 -Site Visit Instructions.docx DOCX document
36C77623R0150_1.docx DOCX document
Attachment 14 - EHRM FULL SET 07122023.pdf PDF
Attachment 12 - 09_Narrative_Telecom.pdf PDF
Attachment 16- VA Engineering Map.pdf PDF
Attachment 3 - EHRM Columbus Drawings Part 1.pdf PDF
Attachment 10 - 06_Narrative_Mechanical.pdf PDF
Attachment 1- Limitations on Subcontracting - Construction.docx DOCX document
Attachment 5 - EHRM Columbus Drawings Part 3.pdf PDF
Attachment 7 - 02_Narrative_Environmental.pdf PDF
Show all 44

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

TELECOM

3A0041

TELECOM

3A0151

TELECOM

3A0631

4A041

TELECOM

4A0411

SERVER/MAIN

TELECOM

4A201 2

BREAKDOWN

AREA

4A200

STORAGE

E-4A202

HAZARD CLASSIFICATION LEGEND

LIGHT HAZARD

(0.10 GPM/FT² OVER 1,500 FT² WITH

100 GPM EXTERIOR HOSE DEMAND)

ORDINARY HAZARD 1

(0.15 GPM/FT² OVER 1,500 FT² WITH

250 GPM EXTERIOR HOSE DEMAND)

ORDINARY HAZARD 2

(0.20 GPM/FT² OVER 1,500 FT² WITH

250 GPM EXTERIOR HOSE DEMAND)

TELECOM

TELECOM

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project NumberCONSULTANTS:

Drawing #

VA Health Care System Approval:

ARCHITECT:

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

ARCH FIRM REG. NO. 20314270 EXP. 06/30/2023

ENGR FIRM REG. NO. 06253 EXP. 06/30/2024

FIRE PROTECTION ENGR

POOLE FIRE PROTECTION

19910 WEST 161ST ST.

OLATHE, KANSAS 66062

(913) 829-8690

FULLY SPRINKLERED

INDUSTRIAL HYGENIST

RIVERFRONT (RSH)

1139 OLIVE ST, SUITE 300

ST. LOUIS, MO 63101

(713) 864-2900

STRUCT ENGR

STAND (SEI)

8234 ROBINSON ST

OVERLAND PARK, KS 66204

(913) 214-2169

COMMISSIONING

ES2

13401 N SANTE FE AVE

OKLAHOMA CITY, OK

(405) 528-4500

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

STAMP:

Drawing Number

Building Number

TELECOMMUNICATION

ASPEN COMMUNICATIONS

7 KIJI-DAVA CIRCLE, STE A

PRESCOTT, AZ 86301

(928) 774-0992

MECH / ELEC / PLUMB ENGR

SPUR DESIGN

2519 MADISON AVENUE, STE 100

KANSAS CITY, MO 64108

(913) 369-7200

FORCE PROTECT

10901 FRONT BEACH RD, UNIT 1415

PANAMA CITY BEACH, FL 32407

(502) 836-4232

PHYSICAL SECURITY

/1

/2

:1 :4

P

M

ENLARGED FIRE SUPPRESION HAZARD

CLASSIFICATION PLAN

SAB 29 OF 78BLS

FINAL BID DOCUMENTS

EHRM INFRASTRUCTURE

UPGRADE - TIER 2

06/02/2023

757-22-705

CHALMERS P. WYLIE VA

420 NORTH JAMES ROAD

COLUMBUS, OHIO 43219-1834

FX403

SPUR #: 1791.19

N

1/4" = 1'-0"

LEVEL 3 - HAZARD CLASSIFICATION PLAN - 3A0045

N

1/4" = 1'-0"

LEVEL 3 - HAZARD CLASSIFICATION PLAN - 3A0154

N

1/4" = 1'-0"

LEVEL 3 - HAZARD CLASSIFICATION PLAN - 3A0633

N

1/4" = 1'-0"

LEVEL 4 - HAZARD CLASSIFICATION PLAN - 4A0412

N

1/4" = 1'-0"

LEVEL 4 - HAZARD CLASSIFICATION PLAN - 4A2011

SHEET KEYNOTES

MARK KEYNOTE

1 THIS TELECOMMUNICATION SPACE HAS BEEN DESIGNATED

AS AN ANSI/TIA-942-B RATING 1 SPACE/NON-MISSION

CRITICAL IN ACCORDANCE WITH VA FIRE PROTECTION

DESIGN MANUAL SECTION 3.7.C. A QUICK-RESPONSE TYPE

SPRINKLER IS REQUIRED TO BE INSTALLED TO PROTECT

THIS SPACE. THE SPACE IS CURRENTLY PROTECTED WITH

A QUICK-RESPONSE SPRINKLER. CONTRACTOR TO FIELD

VERIFY SPIRNKLER LOCATION DOES NOT CONFLICT WITH

NFPA 13 OBSTRUCTION REQUIREMENTS WITH NEW ROOM

LAYOUT.

2 CONTRACTOR TO PROVIDE NEW ISOLATION VALVE

ASSEMBLY TO DESIGNATE ROOM 4A201 AS SINGLE FIRE

SPRINKLER ZONE. CONTRACTOR TO COORDINATE THE

LOCATION OF THE FLOW AND TAMPER SWITCHES WITH THE

FIRE ALARM CONTRACTOR. VALVE ASSEMBLY SHALL BE

INSTALLED IN AN ACESSIBLE LOCATION OUTSIDE OF THE

SPACE. CONTRACTOR TO COORDINATE WITH VA

PERSONNEL ON LOCATION OF CONTROL VALVE FOR THIS

ZONE BEFORE WORK BEGINS. CONTRACTOR TO

COORDINATE WITH VA ON IMPAIRMENT OF FIRE SPRINKLER

SYSTEM DURING CONTRUCTION.

3 THIS TELECOMMUNICATION SPACE IS TO BE PROTECTED IN

ACCORDANCE WITH THE VA FIRE PROTECTION DESIGN

MANUAL 8TH EDITION. THIS SPACE HAS BEEN DESIGNATED

A ANSI/TIA-942-B RATING 1/NON-MISSION CRITICAL IN

ACCORDANCE WITH THE OI&T DESIGN GUIDE VERSION 3.1.

SPRINKLERS IN THIS SPACE ARE TO BE STANDARD

RESPONSE TYPE, FUSIBLE-LINK WITH PROTECTIVE CAGES.

N

1/4" = 1'-0"

ENGINEERING BUILDING - HAZARD CLASSIFICATION PLAN - 1066

N

1/4" = 1'-0"

BOILER PLANT - HAZARD CLASSIFICATION PLAN - 1047

No. REVISION DESCRIPTION DATE

06/02/2023

The information on this document is preliminary or incomplete, not for construction, recording purposes, or implementation.

SERVER/MAIN

TELECOM

4A201

P S

R S

F A

C U c d

B c d

R

K M

V S

S O

V

C A c d

B c d

R

A S

D

CA FCA

F

15cd

B

15cd

R

F

15cd

B

15cd

R

CAF CA

15 ASD DETECTOR - DISABLE • • • •

• PERFORM OPERATION/REPORT DEVICE STATUS

A B C D E F G H I J K L M N N O P Q R S T U

9 MAINTENANCE SWITCH • • • •

10 SOLENOID SUPERVISORY SWITCH • • • •

11 ACTUATOR PLACEMENT INDICATOR • • • •

12 DISCHARGE PRESSURE SWITCH • • • • • • • •

13 LOW PRESSURE SWITCH • • • •

11 SCP AC POWER FAILURE • • •

12 SCP SYSTEM LOW BATTERY • • •

13 OPEN CIRCUIT OR GROUND FAULT • • •

14 CLASS B NOTIFICATION CIRCUIT (NAC) - SHORT • • •

15 LOCAL MANUAL ACTUATOR ON TANK • • • • • • • • • •

13 ASD DETECTOR - URGENT FAULT • •

14 ASD DETECTOR - MINOR FAULT • •

3 ASD DETECTOR - FIRE 1 - 1.0% OBS/FT (w/ 15 SECOND DELAY) • • • • • • • • 4 ASD DETECTOR - FIRE 2 - 3.0% OBS/FT (w/ 30 SECOND DELAY) • • • • • • • • •

5 COMPLETION OF 30 SECOND COUNTDOWN TIMER AFTER FIRE 2 • • •

6 ABORT SWITCH - CONTINUOUSLY HELD DOWN • • • •

7 MANUAL RELEASING PULL STATION • • • • • • • • •

8 AFTER 10 SECOND AGENT RELEASE DELAY • • •

AT 4007ES SCP NOTIFICATION AND FIRE SAFETY CONTROLS

S Y

S T

E M

O U

T P

U T

S

A C

T U

A T

E C

O M

M O

N A

L A

R M

S

IG

N A

L I

N D

IC

A

T O

R

A C

T U

A T

E A

U D

IB

L E

A L A

R M

S

IG

N A

L

A C

T U

A T

E C

O M

M O

N S

U P

E R

V

IS

O R

Y S

IG

N

A L I

N D

IC

A

T O

R

A C

T U

A T

E A

U D

IB

L E

S U

P E

R V

IS

O

R Y

S

IG

N A

L

A C

T U

A T

E C

O M

M O

N T

R O

U B

L E

S

IG

N A

L I

N D

IC

A

T O

R

A C

T U

A T

E A

U D

IB

L E

T R

O U

B L E

S

IG

N A

L

D

IS

P L A

Y C

H A

N G

E O

F S

T A

T U

S

T R

A N

S M

IT

A

L A

R M

S

IG

N A

L T

O M

A

IN

F A

C

IL

IT

Y

F A

C P

T R

A N

S M

IT

S

U P

E R

V

IS

O R

Y S

IG

N

A L T

O M

A

IN

I F

A C

IL

IT

Y F

A C

P

T R

A N

S M

IT

T

R O

U B

L E

S

IG

N A

L T

O M

A

IN

F A

C

IL

IT

Y

F A

C P

A C

T U

A T

E S

U P

P R

E S

S

IO

N B

E L L

A C

T U

A T

E S

U P

P R

E S

S

IO

N H

O R

N A

T

B

P M

A C

T U

A T

E S

U P

P R

E S

S

IO

N H

O R

N A

T S

T E

A D

Y T

O N

E

A C

T U

A T

E P

R E

-D

IS

C H

A R

G E

S T

R O

B E

A C

T U

A T

E S

U P

P R

E S

S

IO

N S

T R

O B

E

B E

G

IN

S

E C

O N

D C

O U

N T

D O

W N

A G

E N

T R

E L E

A S

E I

N T

O A

L L H

A Z

A R

D S

P A

C E

S

B E

G

IN

S

E C

O N

D A

G E

N T

R E

L E

A S

E D

E L A

Y

H V

A C

S H

U T

D O

W N

D A

M P

E R

C L O

S U

R E

S

IL

E N

C E

S S

U P

P R

E S

S

IO

N B

E L L

S T

O P

S F

IR

E

-S

E C

O N

D C

O U

N T

D O

W N

T

IM

E R

SYSTEM INPUTS A B C D E F G H I J K L M N N O P Q R S T U

1 ASD DETECTOR - ALERT - 0.2% OBS/FT (w/ 30 SECOND DELAY) • • • • 2 ASD DETECTOR - ACTION - 0.6% OBS/FT (w/ 30 SECOND DELAY) • • • •

AIM AIM

PS VS

AIM

CT

AIM

CT

AIM

CT

RSFACU

S U

P E

R V

IS

O

R Y

T R

O U

B L E

A L A

R M

SPD

120VAC DEDICATED

BRANCH CIRCUIT

s CA CA

B R

KM

SOV

CA

AIM

CT

AIM

CT

AIM

CT

A L E

R T

T R

O U

B L E

A L A

R M

AIM

CT

A L A

R M

ASD

s

ASD

ASPIRATING SMOKE

DETECTION SYSTEM

TO PRIMARY

POWER SUPPLY

SEE SHEET

FA-001 FOR

CONTINUATION

F

WARNING!

LEAVE AREA IMMEDIATELY

WHEN ALARM SOUNDS

NOVEC 1230

BEING RELEASED

WARNING!

THIS AREA IS PROTECTED BY A

NOVEC 1230 EXTINGUISHING

SYSTEM. DO NOT ENTER

WITHOUT AUTHORIZATION

DURING OR AFTER DISCHARGE.

PUSH

PULL

PUSH/HOLD

SUPPRESSION SYSTEM ABORT

FIRE

SUPPRESSION

MANUAL

RELEASE

FIRE

SUPPRESSION

ABORT

PUSH BUTTON

AND HOLD

CLEAN AGENT LEGEND

SYMBOL DESCRIPTION

F FIRE ALARM MANUAL PULL STATION

FIRE ALARM HORN/STROBE COMBINATION DEVICE

SUPPRESSION HORN

VS VALVE SUPERVISORY SWITCH

WF WATER FLOW SWITCH

AIM ADDRESSABLE INPUT MODULE

AOM ADDRESSABLE OUTPUT MODULE

SYMBOL MODIFIERS

WP

nCD

C

WEATHERPROOF

CANDELA RATING

CEILING MOUNTED

CA CLEAN AGENT MANUAL PULL STATION

CA CLEAN AGENT ABORT STATION

KM KEYED MAINTENANCE SWITCH

CLEAN AGENT DISCHARGE STROBEB

CLEAN AGENT PRE-DISCHARGE STROBER

s

ASD

ASPIRATING SMOKE DETECTOR

SOV

CA

CLEAN AGENT ACTUATOR

DISCRETE OUTPUT - DRY CONTACTCT

PS PRESSURE SWITCH

FACU FIRE ALARM CONTROL UNIT

ASPIRATING SMOKE DETECTOR CONTROL PANEL

SURGE PROTECTIVE DEVICE

ASD

SPD

RSFACU RELEASING SERVICE FIRE ALARM CONTROL UNIT

F

SUPPRESSION BELL

CLEAN AGENT TANK

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project NumberCONSULTANTS:

Drawing #

VA Health Care System Approval:

ARCHITECT:

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

ARCH FIRM REG. NO. 20314270 EXP. 06/30/2023

ENGR FIRM REG. NO. 06253 EXP. 06/30/2024

FIRE PROTECTION ENGR

POOLE FIRE PROTECTION

19910 WEST 161ST ST.

OLATHE, KANSAS 66062

(913) 829-8690

FULLY SPRINKLERED

INDUSTRIAL HYGENIST

RIVERFRONT (RSH)

1139 OLIVE ST, SUITE 300

ST. LOUIS, MO 63101

(713) 864-2900

STRUCT ENGR

STAND (SEI)

8234 ROBINSON ST

OVERLAND PARK, KS 66204

(913) 214-2169

COMMISSIONING

ES2

13401 N SANTE FE AVE

OKLAHOMA CITY, OK

(405) 528-4500

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

STAMP:

Drawing Number

Building Number

TELECOMMUNICATION

ASPEN COMMUNICATIONS

7 KIJI-DAVA CIRCLE, STE A

PRESCOTT, AZ 86301

(928) 774-0992

MECH / ELEC / PLUMB ENGR

SPUR DESIGN

2519 MADISON AVENUE, STE 100

KANSAS CITY, MO 64108

(913) 369-7200

FORCE PROTECT

10901 FRONT BEACH RD, UNIT 1415

PANAMA CITY BEACH, FL 32407

(502) 836-4232

PHYSICAL SECURITY

/1

/2

:1 :4

P

M

CLEAN AGENT NOTES, DETAILS, AND

PLAN

SAB 30 OF 78BLS

FINAL BID DOCUMENTS

EHRM INFRASTRUCTURE

UPGRADE - TIER 2

06/02/2023

757-22-705

CHALMERS P. WYLIE VA

420 NORTH JAMES ROAD

COLUMBUS, OHIO 43219-1834

SH001

SPUR #: 1791.19

N

1/4" = 1'-0"

LEVEL 4 - CLEAN AGENT PLAN - 4A2011

SCALE: NONE

CLEAN AGENT INPUT/OUTPUT MATRIX5

CLEAN AGENT GENERAL NOTES:

1. PROVIDE A NEW CLEAN AGENT (NOVEC 1230) FIRE EXTINGUISHING

SYSTEM THAT IS DESIGNED AND INSTALLED IN ACCORDANCE WITH

NFPA 2001, 2022 EDITION.

2. CLEAN AGENT TO BE USED IS NOVEC 1230 (FK-5-1-12) AT MINIMUM

DESIGN CONCENTRATION OF 6.1%. MINIMUM 4.5% TO BE INCREASED

TO 6.1% WITH 1.25 SAFETY FACTOR IN ACCORDANCE WITH NFPA 2001.

3. ALL PIPE AND FITTINGS SHALL BE IN ACCORDANCE WITH THE

REQUIREMENTS OF NFPA 2001.

4. ALL PIPE AN FITTINGS SHALL BE BLACK SCALE FREE STEEL

CONFORMING TO ONE OF THE FOLLOWING REQUIREMENTS:

A. ASTM A-106, SEAMLESS, GRADE A OR B SCHEDULE 40 THROUGH

8 INCHES

B. ASTM A-53, SEAMLESS, GRADE A OR B SCHEDULE 40 THROUGH 8

INCHES

C. ASTM A-53 ERW, GRADE A OR B SHALL NOT BE USED WITHOUT

PRIOR WRITTEN APPROVAL FROM AHJ.

D. ASTM A-53, CLASS F AND ASTM A-120 SHALL NOT BE USED.

5. STENCILED PIPE IDENTIFICATION SHALL NOT BE PAINTED OVER,

CONCEALED OR REMOVED PRIOR TO APPROVAL BY AHJ.

6. ALL FITTINGS SHALL BE BLACK MALLEABLE IRON OR FORGED STEEL

CONFORMING TO THE FOLLOWING REQUIREMENTS:

A. CLASS 300 MALLEABLE IRON THROUGH 3 INCHES

B. 1000# RATED FORGED STEEL GREATER THAN 3 INCHES

C. ALL GROOVED FITTINGS MUST BE UL LISTED AND CONFORM TO

THE PRESSURE REQUIREMENTS OUTLINED IN NFPA 2001

D. CAST IRON FITTINGS ARE NOT ACCEPTABLE.

7. ALL PIPE ENDS SHALL BE REAMED AFTER CUTTING.

8. EACH PIPE SECTION SHALL BE CLEANED INTERNALLY AFTER

PREPARATION AND BEFORE ASSEMBLY BY SWABBING WITH A

SUITABLE NONFLAMMABLE CLEANER.

9. TEFLON THREAD SEAL TAPE SHALL BE USED ON ALL MALE THREADED

JOINTS ONLY. ALL GROOVED COUPLING GASKETS SHALL BE

LUBRICATED PER THE MANUFACTURER'S SPECIFICATIONS.

10. ALL PIPING SHALL BE RIGIDLY AND SECURELY ANCHORED TO

BUILDING STRUCTURE USING U.L. APPROVED HANGERS. CONTRACTOR

TO PROVIDE SESIMIC BRACING, SITE IS CLASSIFIED AS SEISMIC

DESIGN CATEGORY "C". REFER TO STRUCTURAL DRAWINGS FOR

ADDITIONAL INFORMATION.

11. ALL STORAGE CONTAINERS SHALL BE MOUNTED PLUMB AND LEVEL

AND SECURELY ANCHORED TO BUILDING STRUCTURE.

12. REFER TO ARCHITECTURAL SIGNAGE DETAILS FOR MATERIAL, FINISH

COLOR, ETC. OF CLEAN AGENT SIGNAGE AND START/STOP STATIONS.

SAMPLING PIPE NETWORK REQUIREMENTS (ASD):

1. ALL PIPING SHALL BE CPVC.

2. ATTACH PIPES TO STRUCTURE AS APPLICABLE, USING STANDARD

PIPE SECURING HARDWARE AT INTERVALS OF NO MORE THAN 5 FEET.

3. ALL CONNECTIONS AND JOINTS SHALL BE MADE WITH STANDARD

CONNECTIONS DESIGNED TO BE COMPATIBLE WITH PIPE MATERIAL.

4. ALL JOINTS SHALL BE AIR TIGHT TO PREVENT INFILTRATION AT OTHER

THAN SAMPLING PORT LOCATIONS.

5. COORDINATE THE LOCATION OF PIPING AND SAMPLING PORTS WITH

OTHER TRADES TO PERMIT PROPER ACCESS TO ALL EQUIPMENT.

6. THE SAMPLING PIPE NETWORK SHALL BE CLEARED OF ALL DIRT AND

DEBRIS BY RUNNING AIR THROUGH THE PIPE NETWORK FOR A

MINIMUM OF 30 MINUTES PRIOR TO CONNECTION AND OPERATION OF

THE SYSTEM.

7. ALL PIPING SHALL BE LABELED AT EACH SAMPLING PORT AND AT 20

FOOT INTERVALS USING MANUFACTURERS IDENTIFICATION LABELS.

8. DO NOT GLUE PIPE(S) INTO SOCKET(S) OF INLET MANIFOLD. PIPES

MUST BE INSERTED INTO THE SOCKET(S) AT A MINIMUM OF 1/2 INCH.

9. SENSITIVITY SETTINGS SHOWN IN THE MATRIX SHALL BE ACHIEVED AT

EACH SAMPLING PORT.

SCALE: NONE

CLEAN AGENT TYPICAL RISER DIAGRAM4

SCALE: NONE

CLEAN AGENT SIGNAGE3

SCALE: NONE

CLEAN AGENT START/STOP STATIONS2

SHEET KEYNOTES

MARK KEYNOTE

1 SPACE TO BE PROTECTED WITH A CLEAN AGENT

FIRE EXTINGUISHMENT SYSTEM. AIR-ASPIRATING

SMOKE DETECTION SAMPLING PORTS TO BE

PROVIDED THROUGHOUT SCOPE OF WORK AREA.

CALCULATION AND SYSTEM DESIGN ARE BASED ON F-K-5-1-12.

THE SYSTEM IS DESIGNED TO EXTINGUISH A SINGLE FIRE.

THE SYSTEM IS DESIGNED FOR TOTAL FLOODING.

HAZARD CLASSIFICATION: CLASS C

MINIMUM DESIGN CONCENTRATION: 4.5% (NFPA 2001, TABLE A.7.2.2.3(b))

MINIMUM ANTICIPATED TEMPERATURE: 70F

ELEVATION: APPROX. 31FT.

EQUIVALENT ALTITUDE: 0 FT.

(C) AGENT REQUIRED AT 70F: 0.04075 LBS/FT3 (NFPA 2001, TABLE A.7.3.1(a))

(A) ATMOSPHERIC CORRECTION FACTOR 1.00

**ALL AGENT QUANTITIES ARE ESTIMATED MINIMUM QUANTITIES AND ASSUME ROOM

INTEGRITY WITH NEGLIGIBLE AGENT LEAKAGE.**

PROTECTED SPACE: SERVER/MAIN TELECOM ROOM 4A201

RAISED FLOOR: NONE

AREA (A): 1066.96 SQ. FT.

HEIGHT (H): 8'-10 5/16"

(V) SPACE VOLUME

V=(A)(H)

V=9452 CU. FT.

(W) TOTAL DESIGN QUANTITY:

W=(V)(C)(A) W=(9452)(.04075)(1.00)

TOTAL DESIGN QUANTITY:385.2 LBS.

No. REVISION DESCRIPTION DATE

06/02/2023

The information on this document is preliminary or incomplete, not for construction, recording purposes, or implementation.

ABBREVIATIONS

HVAC PIPING TYPES

GENERAL DUCT SYMBOLS

A/E ARCHITECT / ENGINEER

AAHX AIR TO AIR HEAT EXCHANGER

AB AIR BLENDER

AAV AUTOMATIC AIR VENT

ACC AIR COOLED CONDENSER

ACU AIR CONDITIONING UNIT

AF AFTER FILTER

AFCV AIR FLOW CONTROL VALVE

AFF ABOVE FINISHED FLOOR

AFW AIR FOIL WHEEL (FAN)

AHU AIR-HANDLING UNIT

AMP AMPERAGE

AP ACCESS PANEL

APD AIR PRESSURE DROP

ARI AIR CONDITIONING AND REFRIGERATION

INSTITUTE

AS AIR SEPARATOR

ASME AMERICAN SOCIETY OF MECHANICAL

ENGINEERS

AW AIR WASHER

AXF AXIAL FLOW

B

B BOILER

BD BUTTERFLY DAMPER

BDD BACKDRAFT DAMPER

BFP BACKFLOW PREVENTER

BHP BRAKE HORSEPOWER

BHX BOILER BLOWDOWN HEAT EXCHANGER

BIW BACKWARD INCLINED WHEEL (FAN)

BSC BIOLOGICAL SAFETY CABINETS

BT BLOWOFF TANK

BTU BRITISH THERMAL UNIT

BTUH BRITISH THERMAL UNIT PER HOUR

C

C CENTIGRADE (CELSIUS)

CC COOLING COIL

CCD COOLING COIL CONDENSATE DRAIN

CENT CENTRIFUGAL

CFH CUBIC FEET PER HOUR

CFM CUBIC FEET PER MINUTE

CFT CUBIC FEET

CFP CHEMICAL FEED PUMP

CH CHILLER

CHP CHILLED WATER PUMP

CHW CHILLER WATER

CHR CHILLED WATER RETURN

CHS CHILLED WATER SUPPLY

CI CAST IRON

CM CUBIC METER

CM/S CUBIC METER PER SECOND

CO CARBON MONOXIDE

CO2 CARBON DIOXIDE

COMP COMPRESSOR UNIT

COP COEFFICIENT OF PERFORMANCE

CP CONDENSATE PUMP

CS CONDENSATE STORAGE TANK

CSG CLEAN STEAM GENERATOR

CT COOLING TOWER

CU CONDENSING UNIT

CUH CABINET UNIT HEATER

CV CONSTANT VOLUME

CW COLD WATER (POTABLE)

CC CHILLED WATER COOLING COIL

CWP CONDENSER WATER PUMP

CWR CONDENSER WATER RETURN

CWS CONDENSER WATER SUPPLY

A

F

F FAHRENHEIT

F&T FLOAT AND THERMOSTATIC

FA FREE AREA

FC FLEXIBLE CONNECTION

FCU FAN COIL UNIT

FCUC FAN COIL UNIT COOLING ONLY

FCUH FAN COIL UNIT HEATING ONLY

FCW FORWARD CURVED WHEEL (FAN)

E

EA EXHAUST AIR

EAT ENTERING AIR TEMPERATURE

EC EVAPORATIVE COOLER

ECC ENGINEERING CONTROL CENTER

ECU EVAPORATIVE CONDENSER UNIT

EDH ELECTRIC DUCT HEATER

EER ENERGY EFFICIENCY RATIO

EF EXHAUST FAN

EGS EMERGENCY GAS SHUTOFF

EGT ENTERING GLYCOL TEMPERATURE

EH EXHAUST HOOD

EJ EXPANSION JOINT

EMD END OF MAIN DRIP (STEAM)

ENT ENTERING

ERC ELECTRIC REHEAT COIL

ERP ELECTRIC RADIANT PANEL

ESP EXTERNAL STATIC PRESSURE

ET EXPANSION TANK

ETO ETHYLENE OXIDE

ETR EXISTING TO REMAIN

EUH ELECTRIC UNIT HEATER

EWC EVAPORATIVE WATER COOLER

EWT ENTERING WATER TEMPERATURE

EX. EXISTING

D

DB DECIBELS

Db DRY-BULB TEMPERATURE

DDC DIRECT DIGITAL CONTROLS

DEG DEGREE

DIA DIAMETER

DIW DEIONIZED WATER

DP DEW POINT TEMPERATURE

DPA DIFFERENTIAL PRESSURE ASSEMBLY

DPS DIFFERENTIAL PRESSURE SENSOR

DX DIRECT EXPANSION

FD FIRE DAMPER

FF FINAL FILTER

FHX FLUE GAS/FEEDWATER HEAT EXCHANGER

FM FLOW METER

FOP FUEL OIL PUMP

FOT FUEL OIL TANK

FOHX FUEL OIL HEAT EXCHANGER

FPM FEET PER MINUTE

FPS FEET PER SECOND

FPTU FAN POWERED TERMINAL UNIT

FRP FIBER REINFORCED POLYESTER

FS FLOW SWITCH

FSTAT FREEZESTAT

FT FEET

FT-LB FOOT-POUND

FTR FIN TUBE RADIATION

FV FACE VELOCITY

FSD COMBINATION FIRE / SMOKE DAMPER

G

GA GAUGE

GAL GALLONS

GH GRAVITY HOOD

GPD GALLONS PER DAY

GPH GALLONS PER HOUR

GPM GALLONS PER MINUTE

GPR GAS PRESSURE REGULATOR

GS GALVANIZED STEEL

K kg KILOGRAM kg/HR KILOGRAM PER HOUR kPa KILOPASCAL kW KILOWATT kWh KILOWATT HOUR

J

J INTENTIONALLY LEFT BLANK

I/O INPUT/OUTPUT

IAQ INDOOR AIR QUALITY

IBT INVERTED BUCKET TRAP

ICF IN-LINE CENTRIFUGAL FAN

ID INSIDE DIAMETER

IFB INTEGRAL FACE AND BYPASS

IN INCHES

IN HG INCHES OF MERCURY

IN WC INCH WATER COLUMN

IN WG INCH WATER GAUGE

IN-LB INCH-POUND

IPLV INTEGRATED PART LOAD VALUE

IRH INFRARED HEATER

IS INSECT SCREEN

IU INDUCTION UNIT

IV INLET VANES

H

HU HUMIDIFIER

H&CW HOT & COLD WATER

HAC HOUSEKEEPING AID CLOSET

HB HOSE BIBB

HC HEATING COIL

HD HEAD

HOA HAND/OFF/AUTOMATIC

HP HEAT PUMP

HP HORSEPOWER

HPDT HIGH PRESSURE DRIP TRAP

HPC HIGH PRESSURE STEAM CONDENSATE RETURN

HPS HIGH PRESSURE STEAM (61-300 PSIG)

HRC HEAT RECOVERY COIL

HRD HEAT RECOVERY DEVICE

HRP HYDRONIC RADIANT (CEILING) PANEL

HRW HEAT RECOVERY WHEEL

HSTAT HUMIDISTAT

HTM HUMIDIFIER TERMINAL

HUM HUMIDIFIER UNIT MOUNTED

HVU HEATING AND VENTILATING UNIT

HW HOT WATER

HC HOT WATER HEATING COIL

HHP HEATING HOT WATER PUMP

HHR HEATING HOT WATER RETURN

HHS HEATING HOT WATER SUPPLY

HHUH HOT WATER UNIT HEATER

HX HEAT EXCHANGER

HZ HERTZ

I

L

L LITER

L/h LITERS PER HOUR (OR LITERS/HOUR) L/m LITERS PER MINUTE (OR LITERS/MINUTE) L/s LITERS PER SECOND (OR LITERS/SECOND)

LAT LEAVING AIR TEMPERATURE

LBS/HR POUNDS PER HOUR

LF LINEAR FOOT (FEET)

LGT LEAVING GLYCOL TEMPERATURE

LH LATENT HEAT

LPG LIQUID PROPANE GAS

LPC LOW PRESSURE STEAM CONDENSATE RETURN

CLPC LOW PRESSURE STEAM CONDENSATE (CLEAN)

LLHX LIQUID TO LIQUID HEAT EXCHANGER

LPS LOW PRESSURE STEAM (0-15 PSIG)

CLPS LOW PRESSURE STEAM (CLEAN)

LSD LINEAR SLOT DIFFUSER

LTCP LOCAL TEMPERATURE CONTROL PANEL

LVG LEAVING

LVR LOUVER

LWT LEAVING WATER TEMPERATURE

NOM NOMINAL

NPLV NON-STANDARD PART LOAD VALUE

NPSH NET POSITIVE SUCTION HEAD

NTS NOT TO SCALE

N

NA NOT APPLICABLE

NC NOISE CRITERIA

NG NATURAL GAS

NGFM NATURAL GAS FLOWMETER

NOAA NATIONAL OCEANIC & ATMOSPHERIC

ADMINISTRATION

M

M METER, SI UNIT

M/s METERS PER SECOND

(OR METERS/SECOND)

MA MIXED AIR

MAT MIXED AIR TEMPERATURE

MAU MAKE-UP AIR UNIT

MAV MANUAL AIR VENT

MAX MAXIMUM

MB MIXING BOX

MBH 1000 BTUH

MCA MINIMUM BRANCH CIRCUIT AMPACITY

MERV MINIMUM EFFICIENCY REPORTING VALUE

MH MANHOLE

MHP MOTOR HORSEPOWER

MIN MINIMUM

MM MILLIMETER

MOV MOTOR OPERATED VALVE

MPC MEDIUM PRESSURE STEAM CONDENSATE

RETURN

MPS MEDIUM PRESSURE STEAM (16-60 PSIG)

MTD MEAN TEMPERATURE DIFFERENCE

MVD MANUAL VOLUME DAMPER

MZ MULTI-ZONE

P

P PUMP

PA PASCAL

PC PUMPED CONDENSATE

PCF POUNDS PER CUBIC FOOT (FEET)

PD PRESSURE DROP

PF PRE-FILTER

PG PRESSURE GAGE

PGW PROPYLENE GLYCOL-WATER (SOLUTION)

PHC PREHEAT COIL

PPM PARTS PER MILLION

PRS PRESSURE REGULATING (VALVE) STATION

PRV PRESSURE REGULATING VALVE

PSI POUNDS PER SQUARE INCH

PSIA POUNDS PER SQUARE INCH – ABSOLUTE

PSIG POUNDS PER SQUARE INCH – GAGE

PSS PRIMARY SECONDARY SYSTEM

PSV PRESSURE SAFETY VALVE

PTAC PACKAGED TERMINAL AIR CONDITIONER

O

OA OUTSIDE AIR

OAI OUTSIDE AIR INTAKE

OD OUTSIDE DIAMETER

OFM OIL FLOWMETER

OSD ORGANIC SOIL FILTER

Q

Q INTENTIONALLY LEFT BLANK

T&PCV TEMPERATURE AND PRESSURE

CONTROL VALVE

TAB TESTING, ADJUSTING, BALANCE

TD TEMPERATURE DIFFERENCE

TDH TOTAL DYNAMIC HEAD

TDS TOTAL DISSOLVED SOLIDS

TG TRANSFER GRILLE

TP TRAP

TSP TOTAL STATIC PRESSURE

TSTAT THERMOSTAT

TU TERMINAL UNIT

TWU THRU-WALL UNIT

SA SUPPLY AIR

SAD SOUND ATTENUATING DEVICE

SAT SUPPLY AIR TEMPERATURE

SC SHADING COEFFICIENT

SCFM STANDARD CUBIC FEET PER MINUTE

SCR SILICON CONTROLLED RECTIFIER

DSD DUCT SMOKE DETECTOR

SD SMOKE DAMPER

SEN SENSIBLE HEAT

SF SUPPLY FAN

SH STEAM HUMIDIFIER

SHC STEAM HEATING COIL

SI SQUARE INCHES

SP STATIC PRESSURE

SP GR SPECIFIC GRAVITY

SPS STATIC PRESSURE SENSOR

SQ FT SQUARE FOOT (FEET)

SS STAINLESS STEEL

SSHX STEAM TO STEAM HEAT EXCHANGER

SSR SOLID SEPARATOR

ST STEAM TRAP

SUH STEAM UNIT HEATER

SVS STEAM VENT SILENCER

SWHX STEAM TO WATER HEAT EXCHANGER

R

R/E RETURN OR EXHAUST

RA RETURN AIR

RAD REFRIGERANT AIR DRYER

RAF RADIO FREQUENCY

RAHX ROTARY AIR HEAT EXCHANGER

RAT RETURN AIR TEMPERATURE

RCCH REMOTE CONDENSER CHILLER

RCU RECIPROCATING CHILLER UNIT

RD REFRIGERANT DISCHARGE

REA RELIEF AIR

RF RETURN FAN

RH RELATIVE HUMIDITY

RHC REHEAT COIL

RHG REFRIGERANT HOT GAS

RL REFRIGERANT LIQUID LINE

RLA RUN LOAD AMPERE

RO REVERSE OSMOSIS

RPM REVOLUTIONS PER MINUTE

RS REFRIGERANT SUCTION

RTU ROOF TOP UNIT

RV RELIEF VALVE

T

UC UNDER CUT

UH UNIT HEATER

UL UNDERWRITERS LABORATORY

URV UPBLAST UNIT VENTILATOR

U

X INTENTIONALLY LEFT BLANK

W

W WATTS

WAG WASTE ANESTHESIA GAS

Wb WET-BULB (TEMPERATURE)

WC WATER COOLED

WCCH WATER COOLED CHILLER

WCCU WATER COOLED CONDENSING UNIT

WCHP WATER COOLED HEAT PUMPS

WCPU WATER COOLED PACKAGED UNIT

WF WATER FILTER

WFM WATER FLOWMETER

WG WATER GAGE

WPD WATER SIDE PRESSURE DROP

V VALVE

VAF VANE-AXIAL FAN

VAV VARIABLE AIR VOLUME

VD VOLUME DAMPER (MANUAL OPPOSED BLADE)

VFD VARIABLE FREQUENCY DRIVE

VI VIBRATION ISOLATOR

VIV VARIABLE INLET VANES

VP VACUUM PUMP

VPS VARIABLE PRIMARY SYSTEM

VR VACUUM (STEAM CONDENSATE) RETURN

VSD VARIABLE SPEED DRIVE

VUH VERTICAL UNIT HEATER

X

V

GENERAL NOTES:

A. MECHANICAL PLANS AND SECTIONS ARE INTENDED TO ACCURATELY ILLUSTRATE THE

SCOPE OF WORK BUT ARE STILL DIAGRAMMATIC IN NATURE.

B. MECHANICAL DRAWINGS DO NOT SHOW ALL ACCESSORIES TO BE INSTALLED. THE

CONTRACTOR IS RESPONSIBLE FOR ENSURING THAT ALL SYSTEMS ARE FULLY

FUNCTIONAL AND COMPLIANT WITH APPLICABLE CODES.

C. THE EXISTING CONDITIONS DEPICTED IN THESE PLANS ARE BASED ON AS-BUILT

DOCUMENTATION AND INFORMATION OBTAINED FROM FIELD SURVEYS AND ARE AS

ACCURATE AS POSSIBLE. DUE TO OBSTRUCTIONS, CEILINGS, ETC., NOT ALL CONDITIONS

COULD BE VERIFIED. THE CONTRACTOR SHALL SURVEY THE SITE PRIOR TO BID AND

NOTIFY THE ARCHITECT/ENGINEER OF ANY CONFLICTS, OBSTRUCTIONS, OR

INCONSISTENCIES PREVENTING INSTALLATION OF THE MECHANICAL SYSTEM.

D. ALL EXPOSED UNINSULATED PIPING SHALL BE PAINTED PER THE SPECIFICATION SECTION

"PAINTING".

E. COORDINATE FAN COIL (FCU) AND TERMINAL UNIT (TU/VAV/CV) REHEAT COIL RIGHT OR

LEFT HAND COIL CONNECTIONS WITH PIPING PLANS.

F. ALL FLUE AND COMBUSTION AIR PIPING FROM GAS-FIRED EQUIPMENT SHALL BE SIZED BY

THE GAS-FIRED EQUIPMENT MANUFACTURER BASED ON THE SPECIFIC PIPE ROUTING AND

ELEVATIONS FOR THIS PROJECT. REFER TO MANUFACTURERS INSTALLATION MANUAL AND

LOCAL CODE REQUIREMENTS FOR REQUIRED FLUE AND COMBUSTION AIR PIPING

MATERIALS.

G. PROVIDE VIBRATION ISOLATION FOR ALL MECHANICAL EQUIPMENT TO PREVENT

TRANSMISSION OF VIBRATION TO BUILDING STRUCTURE.

H. PROVIDE VIBRATION ISOLATORS FOR ALL PIPING SUPPORTS CONNECTED TO AND WITHIN

50' OF ISOLATED EQUIPMENT (EXCEPT AT BASE ELBOW SUPPORTS AND ANCHOR POINTS)

THROUGHOUT MECHANICAL EQUIPMENT ROOMS. DO THE SAME FOR SUPPORTS OF STEAM

MAINS WITHIN 50' OF BOILER OR PRESSURE REDUCING VALVES.

I. COORDINATE CONSTRUCTION OF ALL MECHANICAL WORK WITH ARCHITECTURAL,

STRUCTURAL, CIVIL, ELECTRICAL WORK, ETC., SHOWN ON OTHER CONTRACT DOCUMENT

DRAWINGS.

J. MAINTAIN A MINIMUM OF 6′-8″ CLEARANCE TO UNDERSIDE OF PIPES, DUCTS, CONDUITS,

SUSPENDED EQUIPMENT, ETC., THROUGHOUT ACCESS ROUTES IN MECHANICAL ROOMS.

K. ALL TESTS SHALL BE COMPLETED BEFORE ANY MECHANICAL EQUIPMENT OR PIPING

INSULATION IS APPLIED.

L. LOCATE ALL TEMPERATURE, PRESSURE, AND FLOW MEASURING DEVICES IN ACCESSIBLE

LOCATIONS WITH STRAIGHT SECTION OF PIPE OR DUCT UP AND DOWNSTREAM AS

RECOMMENDED BY THE MANUFACTURER FOR GOOD ACCURACY.

M. COORDINATE ALL EQUIPMENT CONNECTIONS WITH MANUFACTURERS CERTIFIED

DRAWINGS. COORDINATE AND PROVIDE ALL DUCT AND PIPING TRANSITIONS REQUIRED

FOR FINAL EQUIPMENT CONNECTIONS TO FURNISHED EQUIPMENT. FIELD VERIFY AND

COORDINATE ALL DUCT AND PIPING DIMENSIONS BEFORE FABRICATION.

CWR

CWS

CD

LPC

LPS

MPC

MPS

HPC

HPS

CONDENSATE DRAIN

CONDENSER WATER SUPPLY

CONDENSER WATER RETURN

HIGH PRESSURE STEAM CONDENSATE

HIGH PRESSURE STEAM SUPPLY

MEDIUM PRESSURE STEAM CONDENSATE

MEDIUM PRESSURE STEAM SUPPLY

LOW PRESSURE STEAM CONDENSATE

LOW PRESSURE STEAM SUPPLY

VACUUM RETURN

FEEDWATER PUMP DISCHARGE

FEEDWATER PUMP SUCTION

VR

CONTINUOUS BLOWDOWN

CHEMICAL FEED

BOILER BLOWOFF BO

CF

CBD

FWPD

FWPS

A. PROVIDE ALL MATERIALS AND EQUIPMENT AND PERFORM ALL LABOR REQUIRED TO

INSTALL COMPLETE AND OPERABLE PIPING SYSTEMS AS INDICATED ON THE DRAWINGS, AS

SPECIFIED AND AS REQUIRED BY CODE.

B. ELEVATIONS AS SHOWN ON THE DRAWINGS ARE TO THE CENTERLINE OF ALL PRESSURE

PIPING AND TO THE INVERT OF ALL GRAVITY PIPING.

C. MAINTAIN A MINIMUM OF 3′-6″ OF GROUND COVER OVER ALL UNDERGROUND HVAC PIPING

(EDIT DEPTH OF GROUND COVER TO SUIT FROST LINE DEPTH AND PROJECT

REQUIREMENTS).

D. UNLESS OTHERWISE NOTED, ALL CHILLED WATER AND HEATING WATER PIPING SHALL BE

3/4" SIZE (EDIT SYSTEM TYPE OR PIPE SIZE TO SUIT PROJECT REQUIREMENTS).

E. PROVIDE AN AIR VENT AT THE HIGH POINT OF EACH DROP IN THE HEATING WATER, CHILLED

WATER, AND OTHER CLOSED WATER PIPING SYSTEMS (EDIT SYSTEM TYPES TO SUIT

PROJECT REQUIREMENTS). ALL PIPING SHALL GRADE TO LOW POINTS. PROVIDE HOSE END

DRAIN VALVES AT THE BOTTOM OF ALL RISERS AND LOW POINTS.

F. UNLESS OTHERWISE NOTED, ALL PIPING IS OVERHEAD, TIGHT TO UNDERSIDE OF

STRUCTURE OR SLAB, WITH SPACE FOR INSULATION IF REQUIRED.

G. INSTALL PIPING SO THAT ALL VALVES, STRAINERS, UNIONS, TRAPS, FLANGES, AND OTHER

APPURTENANCES REQUIRING ACCESS ARE ACCESSIBLE.

H. ALL VALVES SHALL BE INSTALLED SO THAT VALVE REMAINS IN SERVICE WHEN EQUIPMENT

OR PIPING ON EQUIPMENT SIDE OF VALVE IS REMOVED.

I. ALL BALANCING VALVES AND BUTTERFLY VALVES SHALL BE PROVIDED WITH POSITION

INDICATORS AND MAXIMUM ADJUSTABLE STOPS (MEMORY STOPS).

J. PROVIDE CHAINWHEEL OPERATORS FOR ALL VALVES IN EQUIPMENT ROOMS MOUNTED

GREATER THAN 7′-0″ ABOVE FLOOR LEVEL; CHAIN SHALL EXTEND TO 7′-0″ ABOVE FLOOR

LEVEL.

K. ALL VALVES (EXCEPT CONTROL VALVES) AND STRAINERS SHALL BE FULL SIZE OF PIPE

BEFORE REDUCING SIZE TO MAKE CONNECTIONS TO EQUIPMENT AND CONTROLS.

L. UNIONS AND/OR FLANGES SHALL BE INSTALLED AT EACH PIECE OF EQUIPMENT, IN

BYPASSES, AND IN LONG PIPING RUNS (100' OR MORE) TO PERMIT DISASSEMBLY FOR

ALTERATION AND REPAIRS.

M. PITCH STEAM PIPING DOWNWARD IN THE DIRECTION OF FLOW 1/4" IN 10' (1" IN 40') MINIMUM.

PITCH ALL STEAM RETURN LINES DOWNWARD IN THE DIRECTION OF CONDENSATE FLOW

1/2" PER 10' (1" IN 20') MINIMUM. WHERE LENGTH OF BRANCH LINES ARE LESS THAN 8', PITCH

BRANCH LINES TOWARD MAINS 1/2" PER FOOT MINIMUM.

N. PITCH UP ALL STEAM AND CONDENSATE RUNOUTS TO RISERS AND EQUIPMENT 1/2" PER

FOOT. WHERE THIS PITCH CANNOT BE OBTAINED, RUNOUTS OVER 8' IN LENGTH SHALL BE

ONE SIZE LARGER THAN NOTED.

O. TAP ALL BRANCH LINES FROM TOP OF STEAM MAINS (45° PREFERRED, 90° ACCEPTABLE).

A. PROVIDE ALL MATERIALS AND EQUIPMENT AND PERFORM ALL LABOR REQUIRED TO

INSTALL COMPLETE AND OPERABLE HVAC SYSTEMS AS INDICATED ON THE DRAWINGS, AS

SPECIFIED AND AS REQUIRED BY CODE.

B. CERTAIN ITEMS SUCH AS RISES AND DROPS IN DUCTWORK, ACCESS DOORS, VOLUME

DAMPERS, ETC., ARE INDICATED ON THE CONTRACT DOCUMENT DRAWINGS FOR CLARITY

FOR A SPECIFIC LOCATION REQUIREMENT AND SHALL NOT BE INTERPRETED AS THE

EXTENT OF THE REQUIREMENTS FOR THESE ITEMS.

C. IN CORRIDORS WHERE CEILING SPEAKERS AND AIR DIFFUSERS ARE INDICATED BETWEEN

THE SAME LIGHT FIXTURES, INSTALL BOTH DEVICES AT THE QUARTER POINTS BETWEEN

THE SAME FIXTURE.

D. UNLESS OTHERWISE SHOWN, LOCATE ALL ROOM THERMOSTATS AND HUMIDISTATS 4′-0″

(CENTERLINE) ABOVE FINISHED FLOOR.

E. ALL DUCTWORK SHALL CLEAR DOORS AND WINDOWS.

F. ALL DUCTWORK DIMENSIONS, AS SHOWN ON THE DRAWINGS, ARE INTERNAL CLEAR

DIMENSIONS AND DUCT SIZE SHALL BE INCREASED TO COMPENSATE FOR DUCT LINING

THICKNESS.

G. PROVIDE ALL 90° SQUARE ELBOWS WITH DOUBLE RADIUS TURNING VANES UNLESS

OTHERWISE INDICATED. ELBOWS IN DISHWASHER, KITCHEN, AND LAUNDRY EXHAUST

SHALL BE UNVANED SMOOTH RADIUS CONSTRUCTION WITH A RADIUS EQUAL TO 1.5 TIMES

THE WIDTH OF THE DUCT. PROVIDE ACCESS DOORS UPSTREAM OF ALL ELBOWS WITH

TURNING VANES.

H. COORDINATE DIFFUSER, REGISTER, AND GRILLE LOCATIONS WITH ARCHITECTURAL

REFLECTED CEILING PLANS, LIGHTING, AND OTHER CEILING ITEMS AND MAKE MINOR DUCT

MODIFICATIONS TO SUIT.

I. FIELD ERECTED AND FACTORY ASSEMBLED AIR HANDLING UNIT COILS SHALL BE

ARRANGED FOR REMOVAL FROM THE UPSTREAM SIDE WITHOUT DISMANTLING SUPPORTS.

PROVIDE GALVANIZED STRUCTURAL STEEL SUPPORTS FOR ALL COILS (EXCEPT LOWEST

COIL) IN BANKS OVER TWO COILS HIGH TO PERMIT INDEPENDENT REMOVAL OF ANY COIL.

J. ALL AIR HANDLING UNITS SHALL OPERATE WITHOUT MOISTURE CARRYOVER.

K. LOCATE ALL MECHANICAL EQUIPMENT (SINGLE DUCT, DUAL DUCT, VARIABLE VOLUME,

CONSTANT VOLUME AND FAN POWERED BOXES, FAN COIL UNITS, CABINET HEATERS, UNIT

HEATERS, UNIT VENTILATORS, COILS, STEAM HUMIDIFIERS, ETC.) FOR UNOBSTRUCTED

ACCESS TO UNIT ACCESS PANELS, CONTROLS AND VALVING.

L. FINNED TUBE RADIATION ENCLOSURES SHALL BE WALL TO WALL UNLESS OTHERWISE

INDICATED.

M. PROVIDE FLEXIBLE CONNECTIONS IN ALL DUCTWORK SYSTEMS (SUPPLY, RETURN, AND

EXHAUST) CONNECTED TO AIR HANDLING UNITS, FANS, AND OTHER EQUIPMENT WHICH

REQUIRE VIBRATION ISOLATION. FLEXIBLE CONNECTIONS SHALL BE PROVIDED AT THE

POINT OF CONNECTION TO THE EQUIPMENT UNLESS OTHERWISE INDICATED.

PIPING GENERAL NOTES: HVAC/SHEET METAL GENERAL NOTES:

EXISTING TO BE DEMOLISHED

LIMIT OF DEMOLITION

CONNECT NEW TO EXISTINGEXISTING TO REMAIN

NEW DUCT (INSIDE DIMENSIONS: W" X D")

RS

RL

REFRIGERANT SUCTION

REFRIGERANT LIQUID

SUPPLY AIR DUCT UP

SUPPLY AIR DUCT DOWN

H

T

H

T

26-P-3

MH-100

PUMP NO. 3 IN BUILDING NO. 26

EQUIPMENT ABBREVIATION (PUMP)

DETAIL NUMBER

SHEET NUMBER

SHEET NUMBER

SECTION NUMBER

THERMOSTAT

HUMIDISTAT

TEMPERATURE SENSOR

HUMIDITY SENSOR

BUILDING NUMBER WHERE EQUIPMENT

IS LOCATED

26-DS-100-A

ROOM NUMBER (ROOM NO. 100)

ITEM (DUCTLESS SPLIT)

BUILDING NUMBER WHERE EQUIPMENT

IS LOCATED

UNIT IDENTIFIER

DUCTLESS SPLIT UNIT TAG

MECHANICAL EQUIPMENT TAG

1 OWNER FURNISHED, CONTRACTOR

INSTALLED EQUIPMENT DESIGNATION

EXISTING TO BE DEMOLISHED

EXISTING TO REMAIN

NEW PIPE

CONNECT NEW TO EXISTING

LIMIT OF DEMOLITION

GENERAL PIPING SYMBOLS

GENERAL ANNOTATIONS

AV

STRAINERFLOAT & THERMOSTATIC

STEAM TRAP

INVERTED BUCKET

STEAM TRAP

FLANGE CONNECTION PIPE DROP

PIPE RISER TEE DOWN

TEE UP

UNION

PRESSURE REDUCING

VALVE

BALL VALVE

ANGLE GLOBE VALVE

SAFETY RELIEF VALVE

GLOBE VALVE

MANUAL OR

AUTOMATIC AIR VENT

EXPANSION JOINT

EJ

PRESSURE AND

TEMPERATURE TEST PLUG

QUICK-COUPLE HOSE

CONNECTOR

FLOW METER

HVAC PIPING SYMBOLS

CHILLED WATER RETURN

CHILLED WATER SUPPLY

CHR

CHS

HEATING HOT WATER RETURN

HEATING HOT WATER SUPPLY

HHR

HHS QV CRYOGEN VENT

DR DRIP RETURN

CAP

REDUCER (ECCENTRIC)

TYPE

AIRFLOW (CFM)

SD-1

TYPE

AIRFLOW (CFM)

RG-1

TYPE

AIRFLOW (CFM)

EG-1

SQUARE TO ROUND TRANSITION

ELBOW WITH TURNING

VANES

ROUND ELBOW

EXHAUST, RELIEF, MAKE UP, OR

OUTSIDE AIR DUCT DOWN

EXHAUST, RELIEF, MAKE UP, OR

OUTSIDE AIR DUCT UP

RETURN DUCT DOWN

RETURN DUCT UP

BRANCH DUCT WITH HIGH EFFICIENCY

TAKE-OFF (HETO) BRANCH FITTING &

MANUAL VOLUME DAMPER

BRANCH DUCT WITH CONICAL

FITTING & MANUAL VOLUME

DAMPER

DAMPERS: (BD, FD, FSD, MD, SD, VD)

BD

XX-XX

ANCHOR

TEEDIRECTION OF FLOW

S

N. CONCRETE HOUSEKEEPING PADS TO SUIT MECHANICAL EQUIPMENT SHALL BE SIZED AND

LOCATED BY THE MECHANICAL CONTRACTOR. MINIMUM CONCRETE PAD THICKNESS SHALL

BE 4". PAD SHALL EXTEND BEYOND THE EQUIPMENT A MINIMUM OF 4" ON EACH SIDE.

CONCRETE HOUSEKEEPING PADS SHALL BE PROVIDED BY THE GENERAL CONTRACTOR. IT

SHALL BE THE RESPONSIBILITY OF THE MECHANICAL CONTRACTOR TO COORDINATE SIZE

AND LOCATION OF CONCRETE HOUSEKEEPING PADS.

O. WHEN MECHANICAL WORK (HVAC, PLUMBING, SHEET METAL, ETC.) IS SUB-CONTRACTED, IT

SHALL BE THE MECHANICAL CONTRACTOR’S RESPONSIBILITY TO COORDINATE

SUBCONTRACTORS AND THE ASSOCIATED CONTRACTS. WHEN DISCREPANCIES ARISE

PERTAINING TO WHICH CONTRACTOR PROVIDES A PARTICULAR ITEM OF THE MECHANICAL

CONTRACT OR WHICH CONTRACTOR PROVIDES FINAL CONNECTIONS FOR A PARTICULAR

ITEM OF THE MECHANICAL CONTRACT, IT SHALL BE BROUGHT TO THE ATTENTION OF THE

MECHANICAL CONTRACTOR, WHOSE DECISION SHALL BE FINAL.

P. THE LOCATIONS OF ALL ITEMS SHOWN ON THE DRAWINGS OR CALLED FOR IN THE

SPECIFICATIONS THAT ARE NOT DEFINITELY FIXED BY DIMENSIONS ARE APPROXIMATE

ONLY. THE EXACT LOCATIONS NECESSARY TO SECURE THE BEST CONDITIONS AND

RESULTS MUST BE DETERMINED BY THE PROJECT SITE CONDITIONS AND SHALL HAVE THE

APPROVAL OF THE ENGINEER BEFORE BEING INSTALLED. DO NOT SCALE DRAWINGS.

Q. ALL MISCELLANEOUS STEEL REQUIRED TO ENSURE PROPER INSTALLATION AND AS SHOWN

IN DETAILS FOR PIPING, DUCTWORK, AND EQUIPMENT (UNLESS OTHERWISE NOTED) SHALL

BE FURNISHED AND INSTALLED BY THE MECHANICAL CONTRACTOR.

R. PROVIDE ACCESS PANELS FOR INSTALLATION IN WALLS AND CEILINGS WHERE REQUIRED

TO SERVICE DAMPERS, VALVES, SMOKE DETECTORS, AND OTHER CONCEALED

MECHANICAL EQUIPMENT.

S. ALL DUCTWORK, PIPING AND EQUIPMENT SUPPORTED FROM STRUCTURAL STEEL SHALL

BE COORDINATED WITH GENERAL CONTRACTOR. ALL ATTACHMENTS TO STEEL BAR

JOISTS, TRUSSES, OR JOIST GIRDERS SHALL BE AT PANEL POINTS. PROVIDE BEAM CLAMPS

MEETING MSS STANDARDS.WELDING TO STRUCTURAL MEMBERS SHALL NOT BE

PERMITTED. THE USE OF C-CLAMPS SHALL NOT BE PERMITTED.

T. ALL ROOF MOUNTED EQUIPMENT CURBS FOR EQUIPMENT PROVIDED BY THE MECHANICAL

CONTRACTOR SHALL BE FURNISHED BY THE MECHANICAL CONTRACTOR. COORDINATE

INSTALLATION WITH GENERAL CONTRACTOR.

U. LOCATIONS AND SIZES OF ALL FLOOR, WALL, AND ROOF OPENINGS SHALL BE

COORDINATED WITH ALL OTHER TRADES INVOLVED.

V. ALL OPENINGS IN FIRE WALLS DUE TO DUCTWORK, PIPING, CONDUIT, ETC., SHALL BE FIRE

STOPPED WITH AN APPROVED FIRE STOPPING MATERIAL.

W. ALL AIR CONDITIONING CONDENSATE DRAIN LINES FROM EACH AIR HANDLING UNIT AND

ROOFTOP UNIT SHALL BE PIPED FULL SIZE OF THE UNIT DRAIN OUTLET, WITH P-TRAP, AND

PIPED TO NEAREST DRAIN. SEE DETAILS AND SPECIFICATIONS FOR DEPTH OF AIR

CONDITIONING CONDENSATE TRAP.

X. REFER TO TYPICAL DETAILS FOR DUCTWORK, PIPING, AND EQUIPMENT INSTALLATION.

P. PROVIDE AN END OF MAIN DRIP AT EACH RISE IN THE STEAM MAIN. PROVIDE CONDENSATE

DRIPS AT THE BOTTOM OF ALL STEAM RISERS, DOWNFED RUNOUTS TO EQUIPMENT,

RADIATORS, ETC., AT END OF MAINS AND LOW POINTS, AND AHEAD OF ALL PRESSURE

REGULATORS, CONTROL VALVES, ISOLATION VALVES, AND EXPANSION JOINTS.

Q. ON STRAIGHT STEAM PIPING RUNS WITH NO NATURAL DRAINAGE POINTS, INSTALL DRIP

LEGS AT INTERVALS NOT EXCEEDING 200' WHERE PIPE IS PITCHED DOWNWARD IN THE

DIRECTION OF STEAM FLOW AND A MAXIMUM OF 100' WHERE THE PIPE IS PITCHED UP SO

THAT CONDENSATE FLOW IS OPPOSITE OF STEAM FLOW.

R. STEAM TRAPS SHALL BE MINIMUM 3/4″ IN SIZE.

S. INSTALL ALL PIPING WITHOUT FORCING OR SPRINGING.

T. ALL PIPING SHALL CLEAR DOORS AND WINDOWS.

U. ALL VALVES SHALL BE ADJUSTED FOR SMOOTH AND EASY OPERATION.

V. ALL PIPING WORK SHALL BE COORDINATED WITH ALL TRADES INVOLVED. OFFSETS IN

PIPING AROUND OBSTRUCTIONS SHALL BE PROVIDED AT NO ADDITIONAL COST TO THE

OWNER.

W. PROVIDE FLEXIBLE CONNECTIONS IN ALL PIPING SYSTEMS CONNECTED TO PUMPS,

CHILLERS, COOLING TOWERS, AND OTHER EQUIPMENT WHICH REQUIRE VIBRATION

ISOLATION EXCEPT WATER COILS. FLEXIBLE CONNECTIONS SHALL BE PROVIDED AS CLOSE

TO THE EQUIPMENT AS POSSIBLE OR AS INDICATED ON THE DRAWINGS.

X. SLOPE REFRIGERANT PIPING ONE PERCENT IN THE DIRECTION OF OIL RETURN. LIQUID

LINES MAY BE INSTALLED LEVEL.

Y. INSTALL HORIZONTAL REFRIGERANT HOT GAS DISCHARGE PIPING WITH 1/2″ PER 10'

DOWNWARD SLOPE AWAY FROM THE COMPRESSOR.

Z. INSTALL HORIZONTAL REFRIGERANT SUCTION LINES WITH 1/2″ PER 10' DOWNWARD SLOPE

TO THE COMPRESSOR, WITH NO LONG TRAPS OR DEAD ENDS WHICH MAY CAUSE OIL TO

SEPARATE FROM THE SUCTION GAS AND RETURN TO THE COMPRESSOR IN DAMAGING

SLUGS.

AA. PROVIDE LINE SIZE LIQUID INDICATORS IN MAIN LIQUID LINE LEAVING CONDENSER OR

RECEIVER. INSTALL MOISTURE LIQUID INDICATORS IN LIQUID LINES BETWEEN FILTER

DRYERS AND THERMOSTATIC EXPANSION VALVES AND IN LIQUID LINE TO RECEIVER.

BB. PROVIDE LINE SIZE STRAINER UPSTREAM OF EACH AUTOMATIC VALVE. PROVIDE SHUTOFF

VALVE ON EACH SIDE OF STRAINER.

CC. PROVIDE PERMANENT FILTER DRYERS IN LOW TEMPERATURE SYSTEMS AND SYSTEMS

USING HERMETIC COMPRESSORS.

DD. PROVIDE REPLACEABLE CARTRIDGE FILTER DRYERS WITH THREE-WAY VALVE BYPASS A

ASSEMBLY FOR SOLENOID VALVES, ADJACENT TO RECEIVERS.

EE. PROVIDE REFRIGERANT CHARGING VALVE CONNECTIONS IN LIQUID LINE BETWEEN

RECEIVER SHUTOFF VALVE AND EXPANSION VALVE.

N. UNLESS OTHERWISE NOTED, ALL DUCTWORK IS OVERHEAD, TIGHT TO THE UNDERSIDE OF

THE STRUCTURE, WITH SPACE FOR INSULATION IF REQUIRED.

M. RUNS OF FLEXIBLE DUCT SHALL NOT EXCEED 5' MAXIMUM LENGTH.

O. ALL DUCTWORK SHALL BE COORDINATED WITH ALL TRADES INVOLVED. OFFSETS IN

DUCTS, INCLUDING DIVIDED DUCTS AND TRANSITIONS AROUND OBSTRUCTIONS, SHALL BE

PROVIDED AT NO ADDITIONAL COST TO THE OWNER.

P. PROVIDE ACCESS DOORS IN DUCTWORK TO PROVIDE ACCESS FOR ALL SMOKE

DETECTORS, FIRE DAMPERS, SMOKE DAMPERS, VOLUME DAMPERS, HUMIDIFIERS, COILS,

AND OTHER ITEMS LOCATED IN THE DUCTWORK WHICH REQUIRE SERVICE AND/OR

INSPECTION.

Q. PROVIDE ACCESS DOORS IN DUCTWORK FOR OPERATION, ADJUSTMENT, AND

MAINTENANCE OF ALL FANS, VALVES, AND MECHANICAL EQUIPMENT.

R. ALL DUCTS SHALL BE GROUNDED ACROSS FLEXIBLE CONNECTIONS WITH FLEXIBLE

COPPER GROUNDING STRAPS. GROUNDING STRAPS SHALL BE BOLTED OR SOLDERED TO

BOTH THE EQUIPMENT AND THE DUCT.

S. SMOKE DETECTORS SHALL BE FURNISHED AND WIRED BY THE ELECTRICAL CONTRACTOR.

THE MECHANICAL CONTRACTOR SHALL BE RESPONSIBLE FOR MOUNTING THE SMOKE

DETECTOR IN DUCTWORK AS SHOWN ON THE DRAWINGS AND IN ACCORDANCE WITH

MANUFACTURER’S PRINTED INSTRUCTIONS.

T. TERMINATE GAS VENTS FOR UNIT HEATERS, WATER HEATERS, HIGH PRESSURE PARTS

WASHER, HIGH PRESSURE CLEANER, AND OTHER GAS APPLIANCES A MINIMUM OF 3′-0″

ABOVE ROOF WITH RAIN CAP (NOTE TO DESIGNER: EDIT APPLIANCES AND HEIGHT ABOVE

ROOF TO MEET CODE AND TO SUIT PROJECT REQUIREMENTS).

U. SEE SPECIFICATIONS FOR DUCTWORK GAUGES, BRACING, HANGERS, AND OTHER

REQUIREMENTS.

V. LOUVER SIZES, LOCATIONS, MOUNTING, AND DETAILS SHALL BE COORDINATED WITH

OTHER TRADES INVOLVED. REFER TO ARCHITECTURAL SPECIFICATIONS FOR DETAILED

DESCRIPTIONS.

DIRECTION OF PIPE

PITCH (DOWN)

FM

MV

HVAC VALVE SYMBOLS

PC PUMPED CONDENSATE

ROOM TAG

FLEXIBLE CONNECTOR

PUMP

REDUCER (CONCENTRIC)

GATE VALVE

BUTTERFLY VALVE

CHECK VALVE

THERMOMETER

PRESSURE GAUGE

STRAINER WITH BLOWOFF

AND HOSE CONNECTION

YR YEAR

Y

Z INTENTIONALLY LEFT BLANK

Z

M

CONTROL VALVE

CONTROL VALVE, THREE WAY

MOTOR CONTROLLED

VALVE

M

M

NOTE: NOT ALL ABBREVIATIONS OR SYMBOLS WILL BE UTILIZED FOR THIS PROJECT.

A. MECHANICAL TRADES BIDDING DEMOLITION WORK SHALL ALLOW FOR A FULL DAY ON SITE TO REVIEW EXISTING MECHANICAL SERVICES AND EQUIPMENT IN DEMOLITION AND REMOVED AREAS. ACCESS WILL BE GIVEN TO ROOF AND EXISTING MECHANICAL AND ELECTRICAL ROOMS AS REQUIRED. VERIFY ALL EXISTING CONDITIONS PRIOR TO BEGINNING WORK. BRING ANY DISCREPANCIES FROM THE DRAWINGS AND NOTES TO THE ENGINEER OF RECORD IMMEDIATELY. MINOR CHANGES IN THE SCOPE OF THE

DEMOLITION WORK SHALL NOT JUSTIFY AN ADDITIONAL COST.

B. DEMOLISHED WORK SHALL INCLUDE FOR TEMPORARY AND PERMANENT WORK REQUIRED TO KEEP

NON-SCOPE AREAS IN OPERATION. COORDINATE UTILITY SHUT-OFFS AND TEMPORARY POWER,

STORAGE, AND ACCESS NEEDED TO COMPLETE WORK WITH GENERAL CONTRACTOR AND COR.

C. REMOVAL OF EXISTING FIXTURES AND EQUIPMENT WILL REQUIRE ISOLATION OF EXISTING PIPING BRANCHES AND/OR MAINS USING SHUTOFF VALVES. INSTALL NEW ISOLATION VALVES AS REQUIRED TO

COMPLETION DEMOLITION WORK.

D. REMOVAL OF EXISTING PLUMBING FIXTURES AND EQUIPMENT WILL REQUIRE CAPPING AND SEALING EXISTING MAINS OR BRANCHES, WITHOUT LEAVING DEAD LEGS, TO KEEP REMAINING SYSTEMS IN OPERATION. THE CONTRACTOR SHALL PROVIDE PROTECTIVE MEASURES TO PROTECT THE EXISTING

OCCUPIED AREAS AND EQUIPMENT DURING THE CONSTRUCTION WORK. THE CONTRACTOR SHALL

CLEAN THE AREAS OF ALL CONSTRUCTION DIRT DAILY, AND UPON COMPLETION OF THE WORK.

E. ALL DRAINED PIPING RISERS AND MAINS SHALL BE REFILLED AND PROPERLY VENTED BY THE

CONTRACTOR ONCE NEW WORK HAS BEEN COMPLETED.

F. COORDINATE REMOVAL, REPLACEMENT, AND/OR REPAIRS OF ANY EXISTING WALLS, CEILING, ETC.

REQUIRED FOR MECHANICAL DEMOLITION WORK WITH GENERAL CONTRACTOR.

G. PROVIDE TIGHTLY SEALED AND INSULATED TERMINATIONS FOR ALL PIPING, DUCTWORK, AND EQUIPMENT REMOVED FROM THE PROJECT. THERE SHALL BE NO "DEAD LEG" SECTIONS OF PIPING

WHERE WATER CAN SIT AND BECOME STAGNANT.

H. REFER TO THE CONTRACTING OFFICER'S REPRESENTATIVE (COR) FOR INSTRUCTIONS REGARDING THE

REMOVAL AND RETURN OR DEMOLITION OF EXISTING EQUIPMENT AND FIXTURES.

I. PORTIONS OF EXISTING SYSTEMS ARE SHOWN FOR CLARITY AND MAY NOT BE NECESSARY TO MODIFY OR REVISE THEM. ALL EXISTING SYSTEMS ARE SHOWN BASED ON AVAILABLE AS-BUILT DRAWINGS AND SITE SURVEYS OF ACCESSIBLE AREAS. THE CONTRACTOR SHALL VERIFY ALL EXISTING CONDITIONS.

J. ALL WORK MUST BE COORDINATED AND SCHEDULED WITH THE CONTRACTING OFFICER'S

REPRESENTATIVE TO ENSURE THE LEAST AMOUNT OF DISRUPTION OF BUILDING ACTIVITIES AS

POSSIBLE.

K. ALL ACCESSIBLE ABANDONED PIPING AND DUCTWORK SHALL BE REMOVED AND PROPERLY DISPOSED

OF.

L. SUPPLY AIR DUCTWORK AND PIPING NOT SHOWN HATCHED IS TO BE RETAINED, ANY DAMAGE TO

EXISTING INSULATION AND DUCTS TO BE REPAIRED TO MATCH EXISTING.

GENERAL DEMOLITION NOTES:

DS DUCTLESS SPLIT UNIT

ROOM NAME

000A

150 SF

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project NumberCONSULTANTS:

Drawing #

VA Health Care System Approval:

ARCHITECT:

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

ARCH FIRM REG. NO. 20314270 EXP. 06/30/2023

ENGR FIRM REG. NO. 06253 EXP. 06/30/2024

FIRE PROTECTION ENGR

POOLE FIRE PROTECTION

19910 WEST 161ST ST.

OLATHE, KANSAS 66062

(913) 829-8690

FULLY SPRINKLERED

INDUSTRIAL HYGENIST

RIVERFRONT (RSH)

1139 OLIVE ST, SUITE 300

ST. LOUIS, MO 63101

(713) 864-2900

STRUCT ENGR

STAND (SEI)

8234 ROBINSON ST

OVERLAND PARK, KS 66204

(913) 214-2169

COMMISSIONING

ES2

13401 N SANTE FE AVE

OKLAHOMA CITY, OK

(405) 528-4500

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

STAMP:

Drawing Number

Building Number

CONTROLLED UNCLASSIFED INFORMATION (CUI)

CONTROLLED UNCLASSIFED INFORMATION (CUI)

C O

N T

R O

L L

E D

U N

C L

A S

S

IF

E D

I N

F O

R M

A T

IO

N

C

U I)

TELECOMMUNICATION

ASPEN COMMUNICATIONS

7 KIJI-DAVA CIRCLE, STE A

PRESCOTT, AZ 86301

(928) 774-0992

MECH / ELEC / PLUMB ENGR

SPUR DESIGN

2519 MADISON AVENUE, STE 100

KANSAS CITY, MO 64108

(913) 369-7200

FORCE PROTECT

10901 FRONT BEACH RD, UNIT 1415

PANAMA CITY BEACH, FL 32407

(502) 836-4232

PHYSICAL SECURITY

/1

/2

:3 :2

P

M

LEGEND AND ABBREVIATIONS

BAJ 31 OF 78JRM

FINAL BID DOCUMENTS

EHRM INFRASTRUCTURE

UPGRADE - TIER 2

05/19/2023

757-22-705

CHALMERS P. WYLIE VA

420 NORTH JAMES ROAD

COLUMBUS, OHIO 43219-1834

M-000

1, ENERGY, & ENGINEERING

No. REVISION DESCRIPTION DATE

M-401

M-401

M-401

M-401

M-401

M-401

M-401

M-401

M-402

M-402

M-401

M-401

M-401

M-401

TELECOM

1A014

TELECOM

1A457

TELECOM

1A024

TELECOM

1A106

TELECOM

1B002

TELECOM

1B609

TELECOM

1B006

M-403

M-403

M-402

M-402

M-402

M-402

M-402

M-402

M-402

M-402

M-402

M-402

TELECOM

2A004

TELECOM

2A143

TELECOM

2A018

TELECOM

2B102

TELECOM

2B310

TELECOM

2B003 th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project NumberCONSULTANTS:

Drawing #

VA Health Care System Approval:

ARCHITECT:

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

ARCH FIRM REG. NO. 20314270 EXP. 06/30/2023

ENGR FIRM REG. NO. 06253 EXP. 06/30/2024

FIRE PROTECTION ENGR

POOLE FIRE PROTECTION

19910 WEST 161ST ST.

OLATHE, KANSAS 66062

(913) 829-8690

FULLY SPRINKLERED

INDUSTRIAL HYGENIST

RIVERFRONT (RSH)

1139 OLIVE ST, SUITE 300

ST. LOUIS, MO 63101

(713) 864-2900

STRUCT ENGR

STAND (SEI)

8234 ROBINSON ST

OVERLAND PARK, KS 66204

(913) 214-2169

COMMISSIONING

ES2

13401 N SANTE FE AVE

OKLAHOMA CITY, OK

(405) 528-4500

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

STAMP:

Drawing Number

Building Number

CONTROLLED UNCLASSIFED INFORMATION (CUI)

CONTROLLED UNCLASSIFED INFORMATION (CUI)

C O

N T

R O

L L

E D

U N

C L

A S

S

IF

E D

I N

F O

R M

A T

IO

N

C

U I)

TELECOMMUNICATION

ASPEN COMMUNICATIONS

7 KIJI-DAVA CIRCLE, STE A

PRESCOTT, AZ 86301

(928) 774-0992

MECH / ELEC / PLUMB ENGR

SPUR DESIGN

2519 MADISON AVENUE, STE 100

KANSAS CITY, MO 64108

(913) 369-7200

FORCE PROTECT

10901 FRONT BEACH RD, UNIT 1415

PANAMA CITY BEACH, FL 32407

(502) 836-4232

PHYSICAL SECURITY

/1

/2

:3 :2

P

M

REFERENCE PLANS - BLDG 1 - LEVELS 1

& 2

BAJ 32 OF 78JRM

FINAL BID DOCUMENTS

EHRM INFRASTRUCTURE

UPGRADE - TIER 2

05/19/2023

757-22-705

CHALMERS P. WYLIE VA

420 NORTH JAMES ROAD

COLUMBUS, OHIO 43219-1834

M-101

1, ENERGY, & ENGINEERING

N

1" = 40'-0"

BLDG 1 - LEVEL 1 - REFERENCE PLAN1

N

1" = 40'-0"

BLDG 1 - LEVEL 2 - REFERENCE PLAN2

KEYNOTES

1 EXISTING MECHANICAL SYSTEMS TO BE DEMOLISHED AND REPLACED WITH NEW COOLING ONLY DUCTLESS SPLIT-SYSTEM.

REFER TO ENLARGED PLANS FOR MORE INFORMATION.

DN

VD

M-403

M-403

M-403

M-403

M-403

M-403

2B-CU-003

1B-CU-006

1B-CU-609

2B-CU-3101A-CU-106

2A-CU-143

3A-CU-063

4A-CU-041

TELECOM

3A004

TELECOM

3A063

TELECOM

3A015

2B-CU-102

1B-CU-002

M-403

M-403

M-406

2 1A-CU-014

2A-CU-018

3A-CU-0153A-CU-004

2A-CU-004

1A-CU-024

1A-CU-457 8

M-406

M-404

M-404

M-404

SERVER/MAIN TELECOM

4A201

TELECOM

4A041

M-406

M-406

TELECOM

M-406

M-406

TELECOM

ENE-CU-104 8

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project NumberCONSULTANTS:

Drawing #

VA Health Care System Approval:

ARCHITECT:

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

ARCH FIRM REG. NO. 20314270 EXP. 06/30/2023

ENGR FIRM REG. NO. 06253 EXP. 06/30/2024

FIRE PROTECTION ENGR

POOLE FIRE PROTECTION

19910 WEST 161ST ST.

OLATHE, KANSAS 66062

(913) 829-8690

FULLY SPRINKLERED

INDUSTRIAL HYGENIST

RIVERFRONT (RSH)

1139 OLIVE ST, SUITE 300

ST. LOUIS, MO 63101

(713) 864-2900

STRUCT ENGR

STAND (SEI)

8234 ROBINSON ST

OVERLAND PARK, KS 66204

(913) 214-2169

COMMISSIONING

ES2

13401 N SANTE FE AVE

OKLAHOMA CITY, OK

(405) 528-4500

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

STAMP:

Drawing Number

Building Number

CONTROLLED UNCLASSIFED INFORMATION (CUI)

CONTROLLED UNCLASSIFED INFORMATION (CUI)

C O

N T

R O

L L

E D

U N

C L

A S

S

IF

E D

I N

F O

R M

A T

IO

N

C

U I)

TELECOMMUNICATION

ASPEN COMMUNICATIONS

7 KIJI-DAVA CIRCLE, STE A

PRESCOTT, AZ 86301

(928) 774-0992

MECH / ELEC / PLUMB ENGR

SPUR DESIGN

2519 MADISON AVENUE, STE 100

KANSAS CITY, MO 64108

(913) 369-7200

FORCE PROTECT

10901 FRONT BEACH RD, UNIT 1415

PANAMA CITY BEACH, FL 32407

(502) 836-4232

PHYSICAL SECURITY

/1

/2

:3 :2

P

M

REFERENCE PLANS - BLDG 1 - LEVELS 3

& 4, ENERGY, & ENGINEERING

BAJ 33 OF 78JRM

FINAL BID DOCUMENTS

EHRM INFRASTRUCTURE

UPGRADE - TIER 2

05/19/2023

757-22-705

CHALMERS P. WYLIE VA

420 NORTH JAMES ROAD

COLUMBUS, OHIO 43219-1834

M-102

1, ENERGY, & ENGINEERING

N

1" = 40'-0"

BLDG 1 - LEVEL 3 - REFERENCE PLAN1

N

1" = 40'-0"

BLDG 1 - LEVEL 4 - REFERENCE PLAN4

KEYNOTES

1 EXISTING MECHANICAL SYSTEMS TO BE DEMOLISHED AND REPLACED WITH NEW COOLING ONLY DUCTLESS SPLIT-SYSTEM.

REFER TO ENLARGED PLANS FOR MORE INFORMATION.

4 EXISTING MECHANICAL SYSTEMS TO REMAIN IN PLACE AND BE REUSED.

8 CONTRACTOR SHALL INSTALL NEW OUTDOOR CONDENSING UNIT IN THE LOCATION SHOWN. ENSURE THE UNIT HAS SUFFICIENT CLEARANCE SPACE, IS MOUNTED PROPERLY, AND IS PROTECTED AS NECESSARY. ROUTE AND CONNECT REFRIGERANT PIPING

TO THE ASSOCIATED INDOOR UNIT(S) AS SHOWN AND PER MANUFACTURER INSTRUCTIONS.

N

1" = 40'-0"

ENERGY BLDG - LEVEL 1 - REFERENCE PLAN2

N

1" = 40'-0"

ENGINEERING BLDG - LEVEL 1 - REFERENCE PLAN5

N

1" = 40'-0"

ENERGY BLDG - LEVEL 2 - REFERENCE PLAN3

D1

D3

D6

CD RL

RS

TELECOM

1A014

1A-DS-014-B2

1A-DS-014-A2

TELECOM

1A014

RS

RL

RL

RS Y-BRANCH

SELECTOR

D1

D3

D6

D4

VAV TSTAT

8"x8" SA

RL

RS

TELECOM

1A024

1A-DS-024-A

1A-DS-024-B

8"x8" SA

VAV TSTAT

TELECOM

1A024

Y-BRANCH

SELECTOR

3/4" RL

3/4" RS

RS

RL

D6

D1

D3

12"x10" SA

D4

VAV TSTAT

VAV

12"ø SA

TELECOM

1A106

3/4" RS

3/4" RL

12"x10" SA

VAV

VAV TSTAT

1A-DS-106-A

1A-DS-106-B

12"ø SA

TELECOM

1A106

Y-BRANCH

SELECTOR

"x

S A

10"x10" SA

RS

RL

FCU

FCU TSTAT

D2

D4

D6

TELECOM

1A457

10"x10" SA

"x

S A

1A-DS-457-B

1A-DS-457-A2

TELECOM

1A457

Y-BRANCH

SELECTOR

18"x8" RA

12"x10" SA

8"ø SA

VAV

VAV TSTAT

D812"ø SA

TELECOM

1B002

18"x8" RA

1B-DS-002-B

1B-DS-002-A

12"x10" SA

8"ø SA

VAV

VAV TSTAT

12"ø SA

TELECOM

1B002

Y-BRANCH

SELECTOR

20"x14" SA

VAV TSTAT

10"ø SA

TELECOM

1B006

20"x14" SA

VAV TSTAT1B-DS-006-A

1B-DS-006-B2

TELECOM

1B006

Y-BRANCH

SELECTOR

RS

RL

RS

RL

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project NumberCONSULTANTS:

Drawing #

VA Health Care System Approval:

ARCHITECT:

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

ARCH FIRM REG. NO. 20314270 EXP. 06/30/2023

ENGR FIRM REG. NO. 06253 EXP. 06/30/2024

FIRE PROTECTION ENGR

POOLE FIRE PROTECTION

19910 WEST 161ST ST.

OLATHE, KANSAS 66062

(913) 829-8690

FULLY SPRINKLERED

INDUSTRIAL HYGENIST

RIVERFRONT (RSH)

1139 OLIVE ST, SUITE 300

ST. LOUIS, MO 63101

(713) 864-2900

STRUCT ENGR

STAND (SEI)

8234 ROBINSON ST

OVERLAND PARK, KS 66204

(913) 214-2169

COMMISSIONING

ES2

13401 N SANTE FE AVE

OKLAHOMA CITY, OK

(405) 528-4500

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

STAMP:

Drawing Number

Building Number

CONTROLLED UNCLASSIFED INFORMATION (CUI)

CONTROLLED UNCLASSIFED INFORMATION (CUI)

C O

N T

R O

L L

E D

U N

C L

A S

S

IF

E D

I N

F O

R M

A T

IO

N

C

U I)

TELECOMMUNICATION

ASPEN COMMUNICATIONS

7 KIJI-DAVA CIRCLE, STE A

PRESCOTT, AZ 86301

(928) 774-0992

MECH / ELEC / PLUMB ENGR

SPUR DESIGN

2519 MADISON AVENUE, STE 100

KANSAS CITY, MO 64108

(913) 369-7200

FORCE PROTECT

10901 FRONT BEACH RD, UNIT 1415

PANAMA CITY BEACH, FL 32407

(502) 836-4232

PHYSICAL SECURITY

/1

/2

:3 :2

P

M

ENLARGED PLANS - BLDG 1 - LEVEL 1

BAJ 34 OF 78JRM

FINAL BID DOCUMENTS

EHRM INFRASTRUCTURE

UPGRADE - TIER 2

05/19/2023

757-22-705

CHALMERS P. WYLIE VA

420 NORTH JAMES ROAD

COLUMBUS, OHIO 43219-1834

M-401

1, ENERGY, & ENGINEERING

1/4" = 1'-0"

BLDG 1 - LEVEL 1 - 1A014 - DEMO11/4" = 1'-0"

BLDG 1 - LEVEL 1 - 1A014 - NEW21/4" = 1'-0"

BLDG 1 - LEVEL 1 - 1A024 - DEMO31/4" = 1'-0"

BLDG 1 - LEVEL 1 - 1A024 - NEW4

1/4" = 1'-0"

BLDG 1 - LEVEL 1 - 1A106 - DEMO51/4" = 1'-0"

BLDG 1 - LEVEL 1 - 1A106 - NEW61/4" = 1'-0"

BLDG 1 - LEVEL 1 - 1A457 - DEMO71/4" = 1'-0"

BLDG 1 - LEVEL 1 - 1A457 - NEW8

1/4" = 1'-0"

BLDG 1 - LEVEL 1 - 1B002 - DEMO91/4" = 1'-0"

BLDG 1 - LEVEL 1 - 1B002 - NEW101/4" = 1'-0"

BLDG 1 - LEVEL 1 - 1B006 - DEMO111/4" = 1'-0"

BLDG 1 -…

This is the start of the file's text. The full file is on GovTribe.