03_Structural.pdf
PDF 745 KB Posted
- Attached to
- Y1DA--757-22-705 EHRM Infrastructure Upgrades - Columbus, OH - Tier 2 Construction (VA-22-00108764)
- Solicitation number
- 36C77623R0150
About this file
This document package includes structural engineering plans and notes for infrastructure upgrades at a Department of Veterans Affairs medical center in Columbus, Ohio. The plans call for roof repairs, equipment anchoring and bracing, as well as structural reinforcement for added loads. Contractors must verify dimensions and conditions before proceeding. Special inspections will be required for steel installation, concrete work, and earthwork. The related solicitation is for the tier 2 construction work associated with these infrastructure upgrades, issued by the VA Technology Acquisition Center with an opportunity number of 36C77623R0150 and solicitation number VA-22-00108764. The award date was not provided.
View the file
Other files
Show all 44
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
NOTES:
ROOF STRUCTURE, RE: PLAN.
POST-INSTALLED ANCHOR TO ROOF STRUCTURE.
STRUT CHANNEL BRACE
ATTACHMENT TO EQUIPMENT / CABINET.
POST-INSTALLED ANCHOR INTO FLOOR SLAB, TYP
CONCRETE FLOOR SLAB, RE: PLAN. AVOID
DAMAGING REINFORCEMENT.
ANCHORAGE BRACKET PER EQUIPMENT
MANUFACTURER
EQUIPMENT / CABINET
1 2
5 6
CONTRACTOR SHALL PROVIDE
FINAL DESIGN IN COMPLIANCE
WITH SEISMIC REQUIREMENTS
OUTLINED IN THE SPECIFICATIONS
NOTES:
CONCRETE ANCHOR (TYP)
CONCRETE TOPPED METAL
DECK, RE: PLAN
STEEL ANGLE
THREADED ROD HANGER
NOTE: SUSPENDED LOADS AT EACH HANGER
SHALL NOT EXCEED 350 LBS.
1 2 th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project NumberCONSULTANTS:
Drawing #
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
ARCH FIRM REG. NO. 20314270 EXP. 06/30/2023
ENGR FIRM REG. NO. 06253 EXP. 06/30/2024
FIRE PROTECTION ENGR
POOLE FIRE PROTECTION
19910 WEST 161ST ST.
OLATHE, KANSAS 66062
(913) 829-8690
FULLY SPRINKLERED
INDUSTRIAL HYGENIST
RIVERFRONT (RSH)
1139 OLIVE ST, SUITE 300
ST. LOUIS, MO 63101
(713) 864-2900
STRUCT ENGR
STAND (SEI)
8234 ROBINSON ST
OVERLAND PARK, KS 66204
(913) 214-2169
COMMISSIONING
ES2
13401 N SANTE FE AVE
OKLAHOMA CITY, OK
(405) 528-4500
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
Drawing Number
Building Number
TELECOMMUNICATION
ASPEN COMMUNICATIONS
7 KIJI-DAVA CIRCLE, STE A
PRESCOTT, AZ 86301
(928) 774-0992
MECH / ELEC / PLUMB ENGR
SPUR DESIGN
2519 MADISON AVENUE, STE 100
KANSAS CITY, MO 64108
FORCE PROTECT
10901 FRONT BEACH RD, UNIT 1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
PHYSICAL SECURITY
OF 75
/1
/2
:0
:1
A
M
STRUCTURAL GENERAL NOTES
TJSPWS
FINAL BID DOCUMENTS
EHRM INFRASTRUCTURE
UPGRADE - TIER 2
06/02/2023
22325
CHALMERS P. WYLIE VA
420 NORTH JAMES ROAD
COLUMBUS, OHIO 43219-1834
S-001
BLDG 1, ENERGY BLDG, & ENGR BLDG
03_Abbreviation Schedule
Abbreviation Abbreviation Name
+/- PLUS OR MINUS
ADDNL ADDITIONAL
ADJ ADJACENT
AESS ARCHITECTURALLY EXPOSED
STRUCTURAL STEEL
AFF ABOVE FINISHED FLOOR
ALT ALTERNATE
AR ANCHOR ROD
ARCH ARCHITECT OR ARCHITECTURAL
B/ BOTTOM OF
B/W BETWEEN
BLDG BUILDING
BLKG BLOCKING
BM BEAM
BOT BOTTOM
BRG BEARING
BWP BRACED WALL PANEL
CFS COLD FORMED STEEL
CHKD CHECKED
CIP CAST IN PLACE
CJ CONTROL JOINT
CJP COMPLETE JOINT PENETRATION
CL CENTERLINE
CLR CLEAR
COL COLUMN
CONC CONCRETE
CONN CONNECTION
CONT CONTINUOUS
CTR CENTER
db DIA OF REINF BAR, DIA OF BOLT
DBA DEFORMED BAR ANCHOR
DIA or Ø DIAMETER
DIAG DIAGONAL
DIR DIRECTION
DWL DOWEL
EA EACH
EE EXTENDED END
EJ EXPANSION JOINT
ELEV ELEVATION
EN EDGE NAILING
ENGR ENGINEER
EOD EDGE OF DECK
EOS EDGE OF SLAB
EQ EQUAL
EW EACH WAY
EXIST EXISTING
EXT EXTERIOR
FDN FOUNDATION
FLG FLANGE
FLR FLOOR
FS FAR SIDE
FTG FOOTING
FV FIELD VERIFY
GA GAUGE
GALV GALVANIZED
GB GRADE BEAM
GC GENERAL CONTRACTOR
HORIZ HORIZONTAL
HSA HEADED STUD ANCHOR
HSS HOLLOW STRUCTURAL SECTION
IF INSIDE FACE
INT INTERIOR
JST JOIST
K KIPS (1000 LBS)
LCE COMPRESSION EMBEDMENT LENGTH
LCS COMPRESSION LAP SPLICE LENGTH
LLH LONG LEG HORIZONTAL
LLV LONG LEG VERTICAL
LSH LONG SLOTTED HOLE
LTE TENSION EMBEDMENT LENGTH
LTS TENSION LAP SLICE LENGTH
LW LIGHTWEIGHT
MFCR MANUFACTURER
MTL METAL
NIC NOT IN CONTRACT
NS NEAR SIDE
NTS NOT TO SCALE
OC ON CENTER
OF OUTSIDE FACE
OPP OPPOSITE
OVS OVERSIZED
P/C PRECAST
PAF POWDER ACTUATED FASTENER
PAR PARALLEL
PEMB PRE-ENGINEERED METAL BUILDING
PEN PENETRATION
PERP PERPENDICULAR
PL PLATE
PLF POUNDS PER LINEAR FOOT
PREFAB PREFABRICATED
PRELIM PRELIMINARY
PSF POUNDS PER SQUARE FOOT
PSI POUNDS PER SQUARE INCH
RC REINFORCED CONCRETE
RE: REFER TO
REINF REINFORCING
REQD REQUIRED
RF RIGID FRAME
SC SLIP CRITICAL
SDS SELF DRILLING SCREW
SIM SIMILAR
SLV SHORT LEG VERTICAL
SOG SLAB ON GRADE
SQ SQUARE
SS STAINLESS STEEL
STD STANDARD
STIR STIRRUPS
STL STEEL
SW SHEAR WALL
SYM SYMMETRIC
T&B TOP AND BOTTOM
T/ TOP OF
TRANS TRANSVERSE
TYP TYPICAL
UNO UNLESS NOTED OTHERWISE
VERT VERTICAL
W/ WITH
W/O WITHOUT
WF WIDE FLANGE
WP WORK POINT
WWR WELDED WIRE REINFORCEMENT
STRUCTURAL DESIGN CRITERIA (2021 IBC AND ASCE 7-16):
1. BUILDING OCCUPANCY RISK CATEGORY IV.
2. LIVE LOADS [UNIFORM (PSF) / POINT LOADS (KIPS)]:
-- ROOF:………………………………………...............20 PSF / 300#
-- OFFICES:………………….…..…............................50 PSF + 15 PSF PARTITIONS / 2.0 K
-- UPPER LEVEL CORRIDORS................................80 PSF / 2.0 K
-- GROUND LEVEL SLAB ........................................100 PSF / 2.0 K
-- STAIRS ................................................................100 PSF / 300# -- LOBBIES ..............................................................100 PSF / 2.0 K
-- ACCESS FLOOR / SERVER ROOM.....................100 PSF / 2.0 K
3. ROOF SNOW LOAD:
-- GROUND SNOW LOAD (Pg):……………………....20 PSF -- FLAT ROOF SNOW LOAD (Pf): ...........................18.5 PSF + DRIFT -- MIN UNIFORM ROOF SNOW LOAD (Pm):…...….24 PSF (NO DRIFT OR RAIN) -- RAIN ON SNOW SURCHARGE (Prs) ...................0 PSF -- SNOW EXPOSURE FACTOR (Ce):………………..1.0, EXPOSURE B & C -- SNOW LOAD IMPORTANCE FACTOR (Is):….......1.2 -- THERMAL FACTOR (Ct):……………………….......1.1 (just above freezing)
4. WIND DESIGN DATA:
-- BASIC WIND SPEED (3 SEC GUST):……………..119 MPH
-- WIND EXPOSURE:…………………………………..C
-- DIRECTIONALITY FACTOR (Kd) .........................0.85
5. EARTHQUAKE DESIGN DATA:
-- SEISMIC IMPORTANCE FACTOR (Ie):………......1.5
-- NONSTRUCTURAL COMPONENT IMPORTANCE
FACTOR (Ip):…….....................................…...1.5 -- MAPPED SPECTRAL RESP ACCEL (Ss / S1):…..0.118 / 0.06
-- SITE CLASS:………………………………………….D
-- SPECTRAL RESPONSE COEFF (Sds / Sd1):……0.126 / 0.095
-- SEISMIC DESIGN CATEGORY:……………………C
-- SEISMIC FORCE RESISTING SYSTEM:…………NON-BUILDING STRUCTURE
(ASCE 7-16 TABLE 15.4-2)
6. GUARD RAILS:.........................................................50 PLF, AND/OR 200#
CONCENTRATED LOAD APPLIED IN ANY DIRECTION.
STRUCTURAL GENERAL NOTES:
1. DESIGN AND CONSTRUCTION SHALL CONFORM TO THE "INTERNATIONAL
BUILDING CODE, 2021 EDITION" AND ALL APPLICABLE VA DOCUMENTS,
INCLUDING HANDBOOK 18-8. REFER TO THE SPECIAL STRUCTURAL
INSPECTION NOTES FOR ADDITIONAL REQUIREMENTS.
2. CONTRACTOR TO VERIFY ALL DIMENSIONS, ELEVATIONS AND EXISTING
CONDITIONS AND REPORT ANY DISCREPANCIES TO THE ARCHITECT
IMMEDIATELY.
3. IF DISCREPANCIES EXIST BETWEEN STRUCTURAL PLANS, ARCHITECTURAL
PLANS, OTHER PLANS, OR SPECIFICATIONS, THE CONTRACTOR OR
SUBCONTRACTOR SHALL PROVIDE A WRITTEN REQUEST FOR CLARIFICATION
FROM THE ARCHITECT AND/OR ENGINEER PRIOR TO PROCEEDING WITH THE
WORK
4. THE STRUCTURE IS DESIGNED TO BE SELF-SUPPORTING AND STABLE
AFTER THE BUILDING IS FULLY COMPLETED. IT IS SOLELY THE
CONTRACTOR'S RESPONSIBILITY TO EXECUTE AND DETERMINE FINAL
ERECTION PROCEDURES, SEQUENCING AND TO INSURE THE SAFETY OF THE
BUILDING AND ITS COMPONENT PARTS DURING ERECTION. THIS INCLUDES
WHATEVER SHORING, SHEETING, TEMPORARY BRACING, GUYING OR TIE
DOWNS WHICH MIGHT BE NECESSARY.
5. THE STRUCTURE AND FOUNDATIONS ARE DESIGNED FOR A ONE-STORY
ADDITION.
6. FABRICATORS AND SUPPLIERS SHALL CLEARLY NOTE AND HIGHLIGHT
CHANGES MADE IN SHOP DRAWINGS, WHICH DO NOT COMPLY WITH THE
CONTRACT DOCUMENTS.
7. COLUMNS, BEAMS, JOISTS, OR TRUSSES SHALL NOT BE FIELD CUT OR
TRIMMED FOR ANY REASON WITHOUT THE WRITTEN APPROVAL OF THE
ARCHITECT/ENGINEER.
8. HOLES, PIPES, SLEEVES, ETC. NOT SHOWN ON THE DRAWINGS MUST BE
REVIEWED BY THE ARCHITECT BEFORE PLACEMENT THROUGH STRUCTURAL
MEMBERS.
9. IF MECHANICAL AND ELECTRICAL EQUIPMENT SIZES, WEIGHTS, OR
LOCATIONS DO NOT COINCIDE WITH EQUIPMENT SHOWN ON THE PLANS,
COORDINATE ADJUSTMENTS WITH THE ARCHITECT.
10. NO AREA OF THE STRUCTURE SHALL BE LOADED WITH CONSTRUCTION
MATERIALS OR EQUIPMENT THAT EXCEEDS FINAL DESIGN CRITERIA.
11. BEAMS, COLUMNS, WALLS AND FOOTING CENTERS SHALL BE CENTERED
UNDER SUPPORTING MEMBERS (TYPICAL UNLESS NOTED).
12. FOR DEFERRED SUBMITTALS (E.G. HELICAL PILES AND SEISMIC BRACING),
SHOP DRAWINGS AND CALCULATIONS SEALED BY A STRUCTURAL ENGINEER
LICENSED TO PRACTICE IN THE JURISDICTION OF THE PROJECT SHALL BE
FURNISHED TO THE ENGINEER OF RECORD FOR REIVEW.
13. TYPICAL DETAILS ARE SHOWN ON SHEETS DESIGNATED "S0XX". THE
INCLUDED TYPICAL DETAILS MAY OR MAY NOT BE CUT / REFERENCED ON
PLANS OR SECTIONS, BUT ARE TO BE USED AS APPLICABLE.
STRUCTURAL STEEL:
1. SUBMIT SHOP DRAWINGS FOR STEEL.
STRUCTURAL STEEL SHAPES AND PLATE MATERIAL REQUIREMENTS (TYPICAL
UNLESS NOTED OTHERWISE):
a. WIDE FLANGE SHAPES - ASTM A992 (FY = 50 KSI MIN.)
b. CHANNELS, ANGLES, AND PLATES: - ASTM A36 (FY = 36 KSI MIN)
c. ROUND HSS - ASTM A500, GR B (FY = 42 KSI)
d. RECTANGULAR HSS - ASTM A500, GR B (FY = 46 KSI)
e. PIPE - ASTM A53, GR B (FY = 35 KSI)
f. ANCHOR RODS - ASTM F1554 (FY = 36 KSI MIN.),
2. STRUCTURAL STEEL SHALL BE NEW AND MEET THE 13TH EDITION A.I.S.C.
“SPECIFICATIONS FOR STRUCTURAL STEEL BUILDINGS AND BRIDGES”, AND THE
“CODE OF STANDARD PRACTICES FOR STEEL BUILDINGS AND BRIDGES”,
EXCLUDING SECTION 4.4.1.B.
3. THE STRUCTURAL STEEL FABRICATOR SHALL BE AN AISC QUALITY CERTIFIED
COMPANY FOR THE CATEGORY OF WORK IN THIS PROJECT OR PROVIDE A
QUALITY ASSURANCE PLAN AND SPECIAL INSPECTIONS AS DEFINED IN THE CODE.
4. USE STANDARD AISC FRAMING CONNECTIONS WITH A325-N BOLTS, F436
WASHERS, AND A563 HEAVY-HEX NUTS AS REQUIRED, UNLESS NOTED
OTHERWISE.
5. BOLTS IN MOMENT AND BRACED FRAME CONNECTIONS SHALL BE PRE-
TENSIONED. ALL A490 BOLTS SHALL BE PRE-TENSIONED. OTHER BOLTED
CONNECTIONS USING A325 BOLTS MAY BE SNUG-TIGHTENED, UNLESS NOTED
OTHERWISE.
6. STEEL BEAMS SHALL BE FABRICATED WITH MILL CAMBER UP.
7. WELDING SHALL CONFORM TO THE CURRENT AND APPLICABLE AWS
STANDARDS AND BE COMPLETED BY AN AWS CERTIFIED WELDER. ALL WELDS
SHALL UTILIZE E70xx ELECTRODES. SHOP DRAWINGS SHALL SHOW FIELD WELDS, AS APPROPRIATE.
a. AWS D1.1 - STRUCTURAL WELDING CODE - STEEL
b. AWS D1.3 - STRUCTURAL WELDING CODE - SHEET STEEL
c. AWS D1.6 - STRUCTURAL WELDING CODE - STAINLESS STEEL
8. WELD SIZES SHALL BE INCREASED TO MEET THE REQUIRED EFFECTIVE
THROAT WIDTH IF GAPS EXIST AT THE FAYING SURFACE
9. NO COLUMN OR BEAM SPLICES, UNLESS CLEARLY INDICATED ON THE
STRUCTURAL DRAWINGS, WILL BE ALLOWED WITHOUT WRITTEN APPROVAL OF
THE STRUCTURAL ENGINEER.
10. SEE ARCHITECTURAL PLANS FOR FIREPROOFING & FINISHING
REQUIREMENTS, AND COORDINATE STEEL PRIMING & COATINGS ACCORDINGLY.
11. GROUT WHERE INDICATED ON PLANS AT BASE PLATES SHALL BE NON-
METALLIC NON-SHRINK WITH A MINIMUM COMPRESSIVE STRENGTH OF 6000 PSI AT
28 DAYS CONFORMING TO ASTM C1107
12. ALL POST-INSTALLED ANCHORS WHERE NOTED SHALL BE MANUFACTURED BY
SIMPSON STRONG-TIE OR HILTI, INC. AND INSTALLED PER MANUFACTURER'S
SPECIFICATIONS. SUBSTITUTIONS SHALL BE SUBMITTED FOR REVIEW AND
APPROVAL WITH APPROPRIATE IC-ES EVALUATION REPORTS.
13. ALL STEEL NOT PROTECTED FROM WEATHER AND WHOLLY WITHIN A
CONDITIONED SPACE (INCLUDING ALL MASONRY LINTELS) SHALL BE HOT DIPPED
GALVANIZED PER ASTM A123.
SPECIAL INSPECTIONS
1. PROVIDE SPECIAL STRUCTURAL INSPECTIONS AND VERIFICATIONS BY A
THIRD PARTY MEETING THE REQUIRMENTS OF CHAPTER 17 OF THE
BUILDING CODE AND THE BUILDING OFFICAL.
2. SPECIAL INSPECTORS SHALL BE QUALIFIED AND FURNISH THEIR
REPORTS IN A TIMELY MANNER TO THE CONTRACTOR, BUILDING OFFICALS,
ARCHITECT, AND/R ENGINEER
3. SHOULD INSPECTOR IDENTIFY ANY DISCREPANCY, THEY SHAL NOTIFY
CONTRACTOR FIRST, AND THEN ARCHT/ ENGINEER IMMEDIATELY
THEREAFTER IF CORRECTIVE ACTION IS NEEDED.
4. SPECIAL INSPECTIONS AS REQUIRED BY CODE:
A. STEEL: SECTION 1705.2, AISC 360, AND TABLE 1705.2.2. PERIODIC
OBSERVATIONS OF CONNECTION, ALL BRACED-FRAME CONNECTIONS,
WELDERS & FIELD WELDING.
B. CONCRETE: SECTION 1705.3 AND TABLE 1705.3 CONCRETE MATERIAL
SAMPLING AND TESTING, REBAR OBSERVATIONS. TAKE SET OF (3)
CYLINDERS FOR EVERY 50 C.Y., BUT NOT LESS THAN ONE SET OF
SAMPLES PER DAY'S WORK AND PER MIX.
C. EARTHWORK: FOUNDATION BEARING, EXCAVATION, FILL PLACEMENT.
3/4" = 1'-0"
CONCEPTUAL EQUIPMENT BRACING AND ANCHORAGE DETAILS1
1 1/2" = 1'-0"
CONCEPTUAL HANGER ATTACHMENT DETAIL2
No. REVISION DESCRIPTION DATE
04/20/202306/02/2023
DN
VD
DN
PLAN NOTES:
EXISTING ROOF DECK SPAN DIRECTION
ROOF STRUCTURE IS 1.5" 20 GA TYPE BE DECK. MAX SPAN BETWEEN SUPPORTS
IS 6'-4" CLEAR. ANCHOR EQUIPMENT RAILS TO METAL DECK WITH #12 SCREWS @
6" OC AROUND PERIMETER OF RAILS. RAIL LENGTH SHALL BE "AS REQD" TO
PROVIDE SUPPORT FOR THE UNITS, BUT SHALL BE 2'-0" LONG MIN.
ROOF STRUCTURE IS 6.5" THICK COMPOSITE SLAB (3.5" CONC OVER 3" 20 GA
DECK. ANCHOR EQUIPMENT RAILS TO CONCRETE W/ 1/4" X 1.5" LONG TAPCON
SCREWS @ 12" OC AROUND PERIMETER OF RAILS.
ROOF STRUCTURE IS UNKNOWN. CONTRACTOR TO COORDINATE EXISTING ROOF
STRUCTURE W/ STRUCTURAL ENGINEER DURING CONSTRUCTION
SHEET NOTES:
A. REFERENCE SHEET S00x FOR STRUCTURAL GENERAL NOTES. REVIEW NOTES & DETAILS
FOR APPLICABILITY.
B. SEE ARCHITECTURAL DRAWING FOR DETAILS & DIMENSIONS NOT SHOWN.
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project NumberCONSULTANTS:
Drawing #
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
ARCH FIRM REG. NO. 20314270 EXP. 06/30/2023
ENGR FIRM REG. NO. 06253 EXP. 06/30/2024
FIRE PROTECTION ENGR
POOLE FIRE PROTECTION
19910 WEST 161ST ST.
OLATHE, KANSAS 66062
(913) 829-8690
FULLY SPRINKLERED
INDUSTRIAL HYGENIST
RIVERFRONT (RSH)
1139 OLIVE ST, SUITE 300
ST. LOUIS, MO 63101
(713) 864-2900
STRUCT ENGR
STAND (SEI)
8234 ROBINSON ST
OVERLAND PARK, KS 66204
(913) 214-2169
COMMISSIONING
ES2
13401 N SANTE FE AVE
OKLAHOMA CITY, OK
(405) 528-4500
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
Drawing Number
Building Number
TELECOMMUNICATION
ASPEN COMMUNICATIONS
7 KIJI-DAVA CIRCLE, STE A
PRESCOTT, AZ 86301
(928) 774-0992
MECH / ELEC / PLUMB ENGR
SPUR DESIGN
2519 MADISON AVENUE, STE 100
KANSAS CITY, MO 64108
FORCE PROTECT
10901 FRONT BEACH RD, UNIT 1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
PHYSICAL SECURITY
OF 75
/1
/2
:0
:1
A
M
REFERENCE PLANS - BLDG 1 - LEVELS 3
& 4, ENERGY, & ENGINEERING
TJSPWS
FINAL BID DOCUMENTS
EHRM INFRASTRUCTURE
UPGRADE - TIER 2
06/02/2023
22325
CHALMERS P. WYLIE VA
420 NORTH JAMES ROAD
COLUMBUS, OHIO 43219-1834
S-102
BLDG 1, ENERGY BLDG, & ENGR BLDG
N
1" = 40'-0"
BLDG 1 - LEVEL 3 - REFERENCE PLAN1
N
1" = 40'-0"
BLDG 1 - LEVEL 4 - REFERENCE PLAN2
N
1" = 40'-0"
ENERGY BLDG - LEVEL 2 - REFERENCE PLAN4
N
1" = 40'-0"
BLDG 1 - LEVEL 4 - REFERENCE PLAN3
No. REVISION DESCRIPTION DATE
04/20/202306/02/2023
| Sheets |
| S-001 - STRUCTURAL GENERAL NOTES |
| S-102 - REFERENCE PLANS - BLDG 1 - LEVELS 3 & 4, ENERGY, & ENGINEERING |
File details come from the government source that posted it. Updated .