05_Fire Protection.pdf
PDF 4 MB Posted
- Attached to
- Y1DA--757-22-705 EHRM Infrastructure Upgrades - Columbus, OH - Tier 2 Construction (VA-22-00108764)
- Solicitation number
- 36C77623R0150
About this file
This document package includes construction drawings and specifications for fire alarm, fire suppression, and clean agent fire suppression system upgrades at the Chalmers P. Wylie VA Medical Center in Columbus, Ohio. The scope of work includes expanding and upgrading the existing fire alarm system, adding sprinklers and reclassifying hazard areas, and installing a clean agent fire suppression system in the server room. Drawings show layouts, equipment details, riser diagrams, and input/output matrices. Specifications require designing systems according to NFPA standards and coordinating work with the existing Simplex fire alarm panel. The related solicitation is for tier 2 construction services under opportunity number 36C77623R0150, with an estimated value over $5 million. The work will be awarded through full and open competition to support infrastructure upgrades at the Columbus VAMC.
View the file
Other files
Show all 44
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
FIRE ALARM LEGEND
S NEW SMOKE DETECTOR - SPOT TYPE
OUT OF SCOPE AREA
SPD EXISTING SURGE PROTECTIVE DEVICE
FACU EXISTING FIRE ALARM CONTROL UNIT
WF NEW WATERFLOW DEVICE
VS NEW VALVE SUPERVISORY SWITCH
AIM NEW ADDRESSABLE INPUT MODULE
AOM NEW ADDRESSABLE OUTPUT MODULE
AIR HANDLING UNIT CONTROLLERAHU
FA EXISTING FIRE ALARM EQUIPMENT
FA RELOCATED FIRE ALARM EQUIPMENT
WF EXISTING WATERFLOW DEVICE
VS EXISTING VALVE SUPERVISORY SWITCH
AOM EXISTING ADDRESSABLE OUTPUT MODULE
AIM EXISTING ADDRESSABLE INPUT MODULE
S EXISTING SMOKE DETECTOR - SPOT TYPE
S
NEW SMOKE DETECTOR - DUCT TYPE
EXISTING STROBE - WAL MOUNT
SYMBOL MODIFIERS
C
W ncd
CEILING MOUNTED
WALL MOUNTED
CANDELA RATING
1. EXPANSION OF THE EXISTING FIRE ALARM SYSTEM
SHALL BE DESIGNED AND INSTALLED IN
ACCORDANCE WITH THE VA FIRE PROTECTION
DESIGN MANUAL-EIGHTH EDITION, NFPA 70-2020,
AND NFPA 72-2022. FIRE ALARM CONTRACTOR IS
RESPONSIBLE FOR DEVELOPING CALCULATIONS
AND SHOP DRAWINGS.
2. SYSTEM MODIFICATION SHALL BE CONSIDERED
WITH RESPECT TO FLOOR PLAN CHANGES.
3. NOTIFICATION APPLIANCES SHALL MATCH
EXISTING MANUFACTURER AND MODEL OR BE
COMPATIBLE WITH THE EXISTING SYSTEM.
SPEAKERS AND STROBES SHALL BE WHITE FINISH
TO MATCH EXISTING DEVICES. EXISTING PANEL
MANUFACTURE IS SIMPLEX.
4. CONTRACTOR SHALL COORDINATE AND VERIFY
DEMOLITION OR RELOCATION OF ITEMS WITH
OWNER PRIOR TO COMMENCING WORK TO
PREVENT INTERRUPTION OF SERVICE.
5. FIRE ALARM INPUT/OUTPUT MATRIX IS PROVIDED
FOR DEVICES LOCATED IN THE PROJECT AREA. ALL
OTHER INPUTS SHALL MATCH EXISTING PANEL.
6. BEFORE WORK BEGINS, THE CONTRACTOR IS
RESPONSIBLE FOR DETERMINING THE AVAILABLE
CAPACITY OF THE EXISTING FIRE ALARM PANEL. IF
AVAILABLE CAPACITY IS NOT ADEQUATE FOR THE
SCOPE OF WORK THE CONTRACTOR SHALL ALERT
THE COR FOR FURTHER DIRECTION.
FIRE ALARM GENERAL NOTES:
FACU
SPD
LEVEL 2
NOTES:
1. TO DEDICATED 120VAC BRANCH CIRCUIT (EXISTING)
2. EXISTING SIMPLEX FIRE ALARM CONTROL PANEL. THE AVAILABLE CAPACITY IS ASSUMED TO
BE ADEQUATE FOR THE PROPOSED NEW WORK, CONTRACTOR IS RESPONSIBLE FOR
DETERMINING ACTUAL AVAILABLE CAPACITY.
3. THIS RISER DIAGRAM IS INTENDED ONLY TO CAPTURE THE SYSTEM DESIGN INTENT, PANEL
CONNECTIONS, AND GENERAL CIRCUIT ROUTING REQUIREMENTS. EXACT QUANTITIES AND
TYPES OF DEVICES NECESSARY TO ACCOMPLISH THE DESIGN GOALS ARE NOT INDICATED.
THE INTENT OF THIS RISER DIAGRAM IS TO INDICATE THE GENERAL SYSTEM CONFIGURATION
AFTER SUCCESSFUL COMPLETION OF THE PROJECT.
2 3
LEVEL 3
LEVEL 4
LEVEL 1
WF VS
AIM AIMS
S
S
S
WF VS
AIM AIMAIM
ASD
AOM
AHU
AOM
SEE SHEET SH001
FOR CONTINUATION
AIM
CT
AIM
CT
AIM
CT
S U
P E
R V
IS
O
R Y
T R
O U
B L E
A L A
R M
RSFACU
SEE SHEET SH001
FOR CONTINUATION
S
1 WATERFLOW/PRESSURE SWITCH X X X X X X X X 1
4 RSFACU - CLEAN AGENT COMMON SUPERVISORY X X X 4
5 CONTROL VALVE SUPERVISORY SWITCH X X X 5
12 RSFACU - CLEAN AGENT COMMON TROUBLE X X X 12
13 ANY OTHER SYSTEM TROUBLE X X X 13
SYSTEM OUTPUTS
SYSTEM INPUTS
F A
C U
A N
N U
N C
IA
T
IO
N
A C
T
IV
A T
E C
O M
M O
N A
L A
R M
S
IG
N A
L I
N D
IC
A
T O
R
A C
T
IV
A T
E A
U D
IB
L E
A L A
R M
S
IG
N A
L
A C
T
IV
A T
E C
O M
M O
N S
U P
E R
V
IS
O R
Y S
IG
N
A L I
N D
IC
A
T O
R
A C
T
IV
A T
E A
U D
IB
L E
S U
P E
R V
IS
O
R Y
S
IG
N A
L
A C
T
IV
A T
E C
O M
M O
N T
R O
U B
L E
S
IG
N A
L I
N D
IC
A
T O
R
A C
T
IV
A T
E A
U D
IB
L E
T R
O U
B L E
S
IG
N A
L
D
IS
P L A
Y /P
R
IN
T C
H A
N G
E O
F S
T A
T U
S
N O
T
IF
IC
A
T
IO
N
A C
T
IV
A T
E T
E M
P O
R A
L
A L E
R T
T O
N E
A N
D P
R E
-R E
C O
R D
E D
F
IR
E
V
A C
U A
T
IO
N M
E S
S A
G E
T H
R O
U G
H O
U T
T H
E A
S S
O C
IA
T
E D
Z O
N E
A C
T
IV
A T
E S
T R
O B
E S
T H
R O
U G
H O
U T
T H
E A
S S
O C
IA
T
E D
Z O
N E
A C
T
IV
A T
E P
R E
-R E
C O
R D
E D
S T
A F
F A
L E
R T
M E
S S
A G
E T
H R
O U
G H
O U
T T
H
B
U
IL
D
IN
G
N O
T
IF
Y S
U P
E R
V
IS
IN
G
S T
A T
IO
N
/F
IR
E D
E P
A R
T M
E N
T
A U
X
IL
IA
R
Y F
U N
C T
IO
N
S
S H
U T
D O
W N
A S
S O
C
IA
T E
D A
IR
H
A N
D L
IN
G U
N
IT
A C
T
IV
A T
E E
L E
C T
R
IC
A L D
IS
C
O N
N E
C T
O F
E Q
U
IP
M E
N T
I N
I T
E S
P A
C E
S
ALARM CONDITIONS A B C D E F G H I J K L M
2 RSFACU - CLEAN AGENT SYSTEM ACTIVATION X X X X X X 2
SUPERVISORY CONDITIONS A B C D E F G H I J K L M
3 SMOKE DETECTOR - DUCT TYPE X X X X 3
A B C D E F G H I J K L M
X PERFORM OPERATION/REPORT DEVICE STATUS
TROUBLE CONDITIONS A B C D E F G H I J K L M
6 AC POWER FAILURE X X X 6
7 LOW BATTERY X X X 7
8 OPEN CIRCUIT X X X 8
9 GROUND FAULT X X X 9
10 NOTIFICATION APPLIANCE CIRCUIT SHORT X X X 10
11 REMOTE POWER SUPPLY COMMON TROUBLE X X X 11
NOTES:
1. THIS INPUT/OUTPUT MATRIX IS REPRENTATIVE OF THE SCOPE OF WORK OF THIS PROJECT. ALL EXISTING
PROGRAMMING FOR THE BUILDING TO NOT BE MODIFIED UNLESS REQUIRED BY SOW FOR THIS PROJECT.
2. ELECTRICAL DISCONNECT SHALL ONLY BE INTIATED FOR ALARM CONDITIONS DETECTED IN THE SERVER ROOM.
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project NumberCONSULTANTS:
Drawing #
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
ARCH FIRM REG. NO. 20314270 EXP. 06/30/2023
ENGR FIRM REG. NO. 06253 EXP. 06/30/2024
FIRE PROTECTION ENGR
POOLE FIRE PROTECTION
19910 WEST 161ST ST.
OLATHE, KANSAS 66062
(913) 829-8690
FULLY SPRINKLERED
INDUSTRIAL HYGENIST
RIVERFRONT (RSH)
1139 OLIVE ST, SUITE 300
ST. LOUIS, MO 63101
(713) 864-2900
STRUCT ENGR
STAND (SEI)
8234 ROBINSON ST
OVERLAND PARK, KS 66204
(913) 214-2169
COMMISSIONING
ES2
13401 N SANTE FE AVE
OKLAHOMA CITY, OK
(405) 528-4500
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
Drawing Number
Building Number
TELECOMMUNICATION
ASPEN COMMUNICATIONS
7 KIJI-DAVA CIRCLE, STE A
PRESCOTT, AZ 86301
(928) 774-0992
MECH / ELEC / PLUMB ENGR
SPUR DESIGN
2519 MADISON AVENUE, STE 100
KANSAS CITY, MO 64108
(913) 369-7200
FORCE PROTECT
10901 FRONT BEACH RD, UNIT 1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
PHYSICAL SECURITY
/1
/2
:1 :1
P
M
FIRE ALARM GENERAL NOTES, LEGEND,
AND DIAGRAMS
SAB 19 OF 78BLS
FINAL BID DOCUMENTS
EHRM INFRASTRUCTURE
UPGRADE - TIER 2
06/02/2023
757-22-705
CHALMERS P. WYLIE VA
420 NORTH JAMES ROAD
COLUMBUS, OHIO 43219-1834
FA001
SPUR #: 1791.19
SCALE: NONE
FIRE ALARM RISER DIAGRAM2 SCALE: NONE
FACU MATRIX INPUT/OUTPUT MATRIX1
No. REVISION DESCRIPTION DATE
06/02/2023
103 SF
TELECOM
2A018
101 SF
TELECOM
2B003
100 SF
TELECOM
2B310
91 SF
TELECOM
2B102
101 SF
TELECOM
2A004
120 SF
TELECOM
2A143
FA402
FA402
FA402
FA402
FA402
FA402
157 SF
TELECOM
1A457
101 SF
TELECOM
1A024
103 SF
TELECOM
1A014
104 SF
TELECOM
1B006
96 SF
TELECOM
1B609
91 SF
TELECOM
1B002
120 SF
TELECOM
1A106 96 SF
TELECOM
1B609
FA401
FA401
FA401
FA401
FA401
FA401
FA401
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project NumberCONSULTANTS:
Drawing #
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
ARCH FIRM REG. NO. 20314270 EXP. 06/30/2023
ENGR FIRM REG. NO. 06253 EXP. 06/30/2024
FIRE PROTECTION ENGR
POOLE FIRE PROTECTION
19910 WEST 161ST ST.
OLATHE, KANSAS 66062
(913) 829-8690
FULLY SPRINKLERED
INDUSTRIAL HYGENIST
RIVERFRONT (RSH)
1139 OLIVE ST, SUITE 300
ST. LOUIS, MO 63101
(713) 864-2900
STRUCT ENGR
STAND (SEI)
8234 ROBINSON ST
OVERLAND PARK, KS 66204
(913) 214-2169
COMMISSIONING
ES2
13401 N SANTE FE AVE
OKLAHOMA CITY, OK
(405) 528-4500
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
Drawing Number
Building Number
TELECOMMUNICATION
ASPEN COMMUNICATIONS
7 KIJI-DAVA CIRCLE, STE A
PRESCOTT, AZ 86301
(928) 774-0992
MECH / ELEC / PLUMB ENGR
SPUR DESIGN
2519 MADISON AVENUE, STE 100
KANSAS CITY, MO 64108
(913) 369-7200
FORCE PROTECT
10901 FRONT BEACH RD, UNIT 1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
PHYSICAL SECURITY
/1
/2
:1 :1
P
M
FIRE ALARM OVERALL PLANS
SAB 20 OF 78BLS
FINAL BID DOCUMENTS
EHRM INFRASTRUCTURE
UPGRADE - TIER 2
06/02/2023
757-22-705
CHALMERS P. WYLIE VA
420 NORTH JAMES ROAD
COLUMBUS, OHIO 43219-1834
FA101
SPUR #: 1791.19
N
1" = 40'-0"
BLDG 1 - LEVEL 2 - OVERALL FIRE ALARM PLAN2
N
1" = 40'-0"
BLDG 1 - LEVEL 1 - OVERALL FIRE ALARM PLAN1
1067 SF
SERVER/MAIN
TELECOM
4A201
119 SF
TELECOM
4A041
FA403
FA403
SH001
100 SF
TELECOM
3A004
102 SF
TELECOM
3A015
115 SF
TELECOM
3A063
FA403
FA403
FA403
105 SF
TELECOM
FA403
56 SF
TELECOM
FA403
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project NumberCONSULTANTS:
Drawing #
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
ARCH FIRM REG. NO. 20314270 EXP. 06/30/2023
ENGR FIRM REG. NO. 06253 EXP. 06/30/2024
FIRE PROTECTION ENGR
POOLE FIRE PROTECTION
19910 WEST 161ST ST.
OLATHE, KANSAS 66062
(913) 829-8690
FULLY SPRINKLERED
INDUSTRIAL HYGENIST
RIVERFRONT (RSH)
1139 OLIVE ST, SUITE 300
ST. LOUIS, MO 63101
(713) 864-2900
STRUCT ENGR
STAND (SEI)
8234 ROBINSON ST
OVERLAND PARK, KS 66204
(913) 214-2169
COMMISSIONING
ES2
13401 N SANTE FE AVE
OKLAHOMA CITY, OK
(405) 528-4500
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
Drawing Number
Building Number
TELECOMMUNICATION
ASPEN COMMUNICATIONS
7 KIJI-DAVA CIRCLE, STE A
PRESCOTT, AZ 86301
(928) 774-0992
MECH / ELEC / PLUMB ENGR
SPUR DESIGN
2519 MADISON AVENUE, STE 100
KANSAS CITY, MO 64108
(913) 369-7200
FORCE PROTECT
10901 FRONT BEACH RD, UNIT 1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
PHYSICAL SECURITY
/1
/2
:1 :2
P
M
FIRE ALARM OVERALL PLANS
SAB 21 OF 78BLS
FINAL BID DOCUMENTS
EHRM INFRASTRUCTURE
UPGRADE - TIER 2
06/02/2023
757-22-705
CHALMERS P. WYLIE VA
420 NORTH JAMES ROAD
COLUMBUS, OHIO 43219-1834
FA102
SPUR #: 1791.19
N
1" = 40'-0"
BLDG 1 - LEVEL 4 - OVERALL FIRE ALARM PLAN3
N
1" = 40'-0"
BLDG -1 LEVEL 3 - OVERALL FIRE ALARM PLAN1
N
1" = 40'-0"
BOILER PLANT - LEVEL 1 - OVERALL FIRE ALARM PLAN2
N
1" = 40'-0"
ENGINEERING BUILDING - LEVEL 1 - OVERALL FIRE ALARM PLAN4
1A0141
TELECOM
1A0241
TELECOM
1A106
75cd
TELECOM
1A4571
S C
F A
F A
TELECOM
1B0022
TELECOM
1B006
75cd
TELECOM
1B6091 th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project NumberCONSULTANTS:
Drawing #
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
ARCH FIRM REG. NO. 20314270 EXP. 06/30/2023
ENGR FIRM REG. NO. 06253 EXP. 06/30/2024
FIRE PROTECTION ENGR
POOLE FIRE PROTECTION
19910 WEST 161ST ST.
OLATHE, KANSAS 66062
(913) 829-8690
FULLY SPRINKLERED
INDUSTRIAL HYGENIST
RIVERFRONT (RSH)
1139 OLIVE ST, SUITE 300
ST. LOUIS, MO 63101
(713) 864-2900
STRUCT ENGR
STAND (SEI)
8234 ROBINSON ST
OVERLAND PARK, KS 66204
(913) 214-2169
COMMISSIONING
ES2
13401 N SANTE FE AVE
OKLAHOMA CITY, OK
(405) 528-4500
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
Drawing Number
Building Number
TELECOMMUNICATION
ASPEN COMMUNICATIONS
7 KIJI-DAVA CIRCLE, STE A
PRESCOTT, AZ 86301
(928) 774-0992
MECH / ELEC / PLUMB ENGR
SPUR DESIGN
2519 MADISON AVENUE, STE 100
KANSAS CITY, MO 64108
(913) 369-7200
FORCE PROTECT
10901 FRONT BEACH RD, UNIT 1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
PHYSICAL SECURITY
/1
/2
:1 :2
P
M
ENLARGED FIRE ALARM PLAN
SAB 22 OF 78BLS
FINAL BID DOCUMENTS
EHRM INFRASTRUCTURE
UPGRADE - TIER 2
06/02/2023
757-22-705
CHALMERS P. WYLIE VA
420 NORTH JAMES ROAD
COLUMBUS, OHIO 43219-1834
FA401
SPUR #: 1791.19
N
1/4" = 1'-0"
LEVEL 1 - FIRE ALARM PLAN - 1A0147
N
1/4" = 1'-0"
LEVEL 1 - FIRE ALARM PLAN - 1A0246
N
1/4" = 1'-0"
LEVEL 1 - FIRE ALARM PLAN - 1A1065
N
1/4" = 1'-0"
LEVEL 1 - FIRE ALARM PLAN - 1A4574
N
1/4" = 1'-0"
LEVEL 1 - FIRE ALARM PLAN - 1B0023
N
1/4" = 1'-0"
LEVEL 1 - FIRE ALARM PLAN - 1B0062
N
1/4" = 1'-0"
LEVEL 1 - FIRE ALARM PLAN - 1B6091
GENERAL SHEET NOTES:
1. FIRE ALARM EQUIPMENT LOCATIONS SHOWN ARE APPROXIMATE.
CONTRACTOR TO FIELD VERIFY EXACT EQUIPMENT LOCATIONS PRIOR
TO ANY WORK.
SHEET KEYNOTES
MARK KEYNOTE
1 THIS TELECOMMUNICATION SPACE HAS BEEN
DESIGNATED AS AN ANSI/TIA-942-B RATING 1
SPACE/NON-MISSION CRITICAL AND WILL THEREFORE
NOT REQUIRE SMOKE DETECTION IN ACCORDANCE WITH
VA FIRE PROTECTION DESIGN MANUAL SECTION 3.7.C.
2 THIS TELECOMMUNICATION SPACE HAS BEEN
DESIGNATED AS AN ANSI/TIA-942-B RATING 1
SPACE/NON-MISSION CRITICAL IN ACCORDANCE WITH VA
FIRE PROTECTION DESIGN MANUAL SECTION 3.7.C.
EXISTING SMOKE DETECTOR TO REMAIN IN
ACCORDANCE WITH NFPA 72 SECTION 10.4.5.
2A0181 S
C
F A
F A
TELECOM
2A1432
TELECOM
2B0031
TELECOM
2A004 1
S W
F A
F A
TELECOM
2B102 2
TELECOM
2B3101 th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project NumberCONSULTANTS:
Drawing #
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
ARCH FIRM REG. NO. 20314270 EXP. 06/30/2023
ENGR FIRM REG. NO. 06253 EXP. 06/30/2024
FIRE PROTECTION ENGR
POOLE FIRE PROTECTION
19910 WEST 161ST ST.
OLATHE, KANSAS 66062
(913) 829-8690
FULLY SPRINKLERED
INDUSTRIAL HYGENIST
RIVERFRONT (RSH)
1139 OLIVE ST, SUITE 300
ST. LOUIS, MO 63101
(713) 864-2900
STRUCT ENGR
STAND (SEI)
8234 ROBINSON ST
OVERLAND PARK, KS 66204
(913) 214-2169
COMMISSIONING
ES2
13401 N SANTE FE AVE
OKLAHOMA CITY, OK
(405) 528-4500
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
Drawing Number
Building Number
TELECOMMUNICATION
ASPEN COMMUNICATIONS
7 KIJI-DAVA CIRCLE, STE A
PRESCOTT, AZ 86301
(928) 774-0992
MECH / ELEC / PLUMB ENGR
SPUR DESIGN
2519 MADISON AVENUE, STE 100
KANSAS CITY, MO 64108
(913) 369-7200
FORCE PROTECT
10901 FRONT BEACH RD, UNIT 1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
PHYSICAL SECURITY
/1
/2
:1 :2
P
M
ENLARGED FIRE ALARM PLAN
SAB 23 OF 78BLS
FINAL BID DOCUMENTS
EHRM INFRASTRUCTURE
UPGRADE - TIER 2
06/02/2023
757-22-705
CHALMERS P. WYLIE VA
420 NORTH JAMES ROAD
COLUMBUS, OHIO 43219-1834
FA402
SPUR #: 1791.19
N
1/4" = 1'-0"
LEVEL 2 - FIRE ALARM PLAN - 2A1086
N
1/4" = 1'-0"
LEVEL 2 - FIRE ALARM PLAN - 2A1435
N
1/4" = 1'-0"
LEVEL 2 - FIRE ALARM PLAN - 2B0034
N
1/4" = 1'-0"
LEVEL 2 - FIRE ALARM PLAN - 2B0043
N
1/4" = 1'-0"
LEVEL 2 - FIRE ALARM PLAN - 2B1022
N
1/4" = 1'-0"
LEVEL 2 - FIRE ALARM PLAN - 2B3101
GENERAL SHEET NOTES:
1. FIRE ALARM EQUIPMENT LOCATIONS SHOWN ARE APPROXIMATE.
CONTRACTOR TO FIELD VERIFY EXACT EQUIPMENT LOCATIONS PRIOR
TO ANY WORK.
SHEET KEYNOTES
MARK KEYNOTE
1 THIS TELECOMMUNICATION SPACE HAS BEEN
DESIGNATED AS AN ANSI/TIA-942-B RATING 1
SPACE/NON-MISSION CRITICAL AND WILL THEREFORE
NOT REQUIRE SMOKE DETECTION IN ACCORDANCE WITH
VA FIRE PROTECTION DESIGN MANUAL SECTION 3.7.C.
2 THIS TELECOMMUNICATION SPACE HAS BEEN
DESIGNATED AS AN ANSI/TIA-942-B RATING 1
SPACE/NON-MISSION CRITICAL IN ACCORDANCE WITH VA
FIRE PROTECTION DESIGN MANUAL SECTION 3.7.C.
EXISTING SMOKE DETECTOR TO REMAIN IN
ACCORDANCE WITH NFPA 72 SECTION 10.4.5.
FAFA FA
S C
TELECOM
3A004
TELECOM
3A0151
3A063
TELECOM
3A0631 1 4A041
TELECOM
4A041
S
4A-201-CRU-B
S
4A-201-CRU-A
AOM ITE SPACE ELECTRICAL
DISCONNECT
VS
WF R
S
F A
C U
4A201
SERVER/MAIN
TELECOM
4A201
3 4 5 6
REFER TO SHEET SH001 FOR
ADDITIONAL FIRE ALARM
DETAIL IN THIS SPACE.
AOM ITE SPACE MECHANICAL
DISCONNECT
A S
D
BREAKDOWN
AREA
4A200
STORAGE
E-4A202
STORAGE
E-4A202
AOM ITE SPACE ELECTRICAL
DISCONNECT
AOM ITE SPACE MECHANICAL
DISCONNECT
TELECOM
TELECOM
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project NumberCONSULTANTS:
Drawing #
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
ARCH FIRM REG. NO. 20314270 EXP. 06/30/2023
ENGR FIRM REG. NO. 06253 EXP. 06/30/2024
FIRE PROTECTION ENGR
POOLE FIRE PROTECTION
19910 WEST 161ST ST.
OLATHE, KANSAS 66062
(913) 829-8690
FULLY SPRINKLERED
INDUSTRIAL HYGENIST
RIVERFRONT (RSH)
1139 OLIVE ST, SUITE 300
ST. LOUIS, MO 63101
(713) 864-2900
STRUCT ENGR
STAND (SEI)
8234 ROBINSON ST
OVERLAND PARK, KS 66204
(913) 214-2169
COMMISSIONING
ES2
13401 N SANTE FE AVE
OKLAHOMA CITY, OK
(405) 528-4500
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
Drawing Number
Building Number
TELECOMMUNICATION
ASPEN COMMUNICATIONS
7 KIJI-DAVA CIRCLE, STE A
PRESCOTT, AZ 86301
(928) 774-0992
MECH / ELEC / PLUMB ENGR
SPUR DESIGN
2519 MADISON AVENUE, STE 100
KANSAS CITY, MO 64108
(913) 369-7200
FORCE PROTECT
10901 FRONT BEACH RD, UNIT 1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
PHYSICAL SECURITY
/1
/2
:1 :2
P
M
ENLARGED FIRE ALARM PLAN
SAB 24 OF 78BLS
FINAL BID DOCUMENTS
EHRM INFRASTRUCTURE
UPGRADE - TIER 2
06/02/2023
757-22-705
CHALMERS P. WYLIE VA
420 NORTH JAMES ROAD
COLUMBUS, OHIO 43219-1834
FA403
SPUR #: 1791.19
N
1/4" = 1'-0"
LEVEL 3 - FIRE ALARM PLAN - 3A0044
N
1/4" = 1'-0"
LEVEL 3 - FIRE ALARM PLAN - 3A0156
N
1/4" = 1'-0"
LEVEL 3 - FIRE ALARM PLAN - 3A0633
N
1/4" = 1'-0"
LEVEL 4 - FIRE ALARM PLAN - 4A0412
N
1/4" = 1'-0"
LEVEL 4 - FIRE ALARM PLAN - 4A2011
GENERAL SHEET NOTES:
1. FIRE ALARM EQUIPMENT LOCATIONS SHOWN ARE APPROXIMATE.
CONTRACTOR TO FIELD VERIFY EXACT EQUIPMENT LOCATIONS PRIOR
TO ANY WORK.
N
1/4" = 1'-0"
BOILER PLANT - FIRE ALARM PLAN - 1045
N
1/4" = 1'-0"
ENGINEERING BUILDING - FIRE ALARM PLAN - 1067
SHEET KEYNOTES
MARK KEYNOTE
1 THIS TELECOMMUNICATION SPACE HAS BEEN
DESIGNATED AS AN ANSI/TIA-942-B RATING 1
SPACE/NON-MISSION CRITICAL AND WILL
THEREFORE NOT REQUIRE SMOKE DETECTION IN
ACCORDANCE WITH VA FIRE PROTECTION DESIGN
MANUAL SECTION 3.7.C.
2 THIS TELECOMMUNICATION SPACE HAS BEEN
DESIGNATED AS AN ANSI/TIA-942-B RATING 1
SPACE/NON-MISSION CRITICAL IN ACCORDANCE
WITH VA FIRE PROTECTION DESIGN MANUAL
SECTION 3.7.C. EXISTING SMOKE DETECTOR TO
REMAIN IN ACCORDANCE WITH NFPA 72 SECTION
10.4.5.
3 THIS TELECOMMUNICATION SPACE IS TO BE
PROTECTED IN ACCORDANCE WITH THE VA FIRE
PROTECTION DESIGN MANUAL 8TH EDITION AND
HEFP SEP DESIGN ALERT 5 DATED 17 AUGUST 2021.
THIS SPACE HAS BEEN DESIGNATED A
ANSI/TIA-942-B RATING 3/MISSION CRITICAL IN
ACCORDANCE WITH THE OI&T DESIGN GUIDE
VERSION 3.1.
4 AN ASPIRATING SMOKE DETECTION SYSTEM SHALL
BE INSTALLED IN THE SERVER ROOM TO PROVIDE
EARLY WARNING OF A POTENTIAL FIRE EVENT.
SAMPLING PORTS FOR THE ASPIRATING SMOKE
DETECTION SHALL BE INSTALLED AND LOCATED IN
ACCORDANCE WITH NFPA 72. ASPIRATING SMOKE
DETECTION CONTROL UNIT SHALL BE UL LISTED
AND FM APPROVED. THE SYSTEM SHALL MEET THE
REQUIREMENTS OF NFPA 75. REFER TO
INPUT/OUTPUT MATRIX ON SHEET SH001 FOR
SENSITIVITY SETTINGS. SAMPLING PORTS ARE
ONLY TO BE INSTALLED AT THE CEILING. THIS
SPACE DOES NOT HAVE A RAISED FLOOR.
5 ASPIRATING SMOKE DETECTION CONTROL PANEL
SHALL BE POWERED FROM THE CLEAN AGENT
RSFACU OR BY A REMOTE POWER SUPPLY.
6 THIS SPACE WILL BE PROTECTED BY A CLEAN
AGENT FIRE EXTINGUISHMENT SYSTEM TO BE
MONITORED BY THE RSFACU SHOWN ON SHEET
SH001.
HAZARD CLASSIFICATION LEGEND
LIGHT HAZARD
(0.10 GPM/FT² OVER 1,500 FT² WITH
100 GPM EXTERIOR HOSE DEMAND)
ORDINARY HAZARD 1
(0.15 GPM/FT² OVER 1,500 FT² WITH
250 GPM EXTERIOR HOSE DEMAND)
ORDINARY HAZARD 2
(0.20 GPM/FT² OVER 1,500 FT² WITH
250 GPM EXTERIOR HOSE DEMAND)
1. ADDITIONS TO EXISTING FIRE PROTECTION WET PIPE
SYSTEM SHALL BE DESIGNED AND INSTALLED IN
ACCORDANCE WITH THE VA FIRE PROTECTION DESIGN
MANUAL - EIGHT EDITION AND NFPA 13-2022.
2. SPRINKLERS AND SPRINKLER PIPING ARE PERMITTED TO
BE INSTALLED IN TELECOMMUNICATION SPACES.
SPRINKLER AND SPRINKLER PIPING ARE REQUIRED TO BE
INSTALLED OUTSIDE OF THE DEDICATED ELECTRICAL
ZONE AS DEFINED BY NFPA 13 SECTION 26.30.2 AND NFPA
70 SECTIONS 110.26 (E) (1) (B) AND 110.26 (E) (1) (C).
3. SPRINKLERS INSTALLED IN TELECOMMUNCIATION SPACES
DESIGNATED AS ANSI/TIA-942-B RATING 1 SPACES/NON-
MISSION CRITICAL SHALL BE QUICK RESPONSE TYPE.
4. SPRINKLERS INSTALLED IN TELECOMMUNCIATION SPACES
DESIGNATED AS ANSI/TIA-942-B RATING 3
SPACES/MISSION CRITICAL SHALL BE FUSIBLE-LINK,
STANDARD-RESPONSE TYPE. THESE SPRINKLERS ARE
REQUIRED TO BE INSTALLED WITH PROTECTIVE CAGES AS
REQUIRED BY THE VA FIRE PROTECTION DESIGN MANUAL
SECTION 3.7.B.
5. ALL HANGERS MUST BE PROVIDED AND INSTALLED IN
ACCORDANCE WITH NFPA 13 AND PROJECT
SPECIFICATIONS. REFER TO STRUCTURAL DRAWINGS FOR
ADDITIONAL INFORMATION.
A. SEISMIC DESIGN CATEGORY: C
FIRE SUPPRESSION GENERAL NOTES:
157 SF
TELECOM
1A457
101 SF
TELECOM
1A024
103 SF
TELECOM
1A014
104 SF
TELECOM
1B006
96 SF
TELECOM
1B609
91 SF
TELECOM
1B002
120 SF
TELECOM
1A106 96 SF
TELECOM
1B609
FX401
FX401
FX401
FX401
FX401
FX401
FX401
103 SF
TELECOM
2A018
101 SF
TELECOM
2B003
100 SF
TELECOM
2B310
91 SF
TELECOM
2B102
101 SF
TELECOM
2A004
120 SF
TELECOM
2A143
FX402
FX402
FX402
FX402
FX402
FX402
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project NumberCONSULTANTS:
Drawing #
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
ARCH FIRM REG. NO. 20314270 EXP. 06/30/2023
ENGR FIRM REG. NO. 06253 EXP. 06/30/2024
FIRE PROTECTION ENGR
POOLE FIRE PROTECTION
19910 WEST 161ST ST.
OLATHE, KANSAS 66062
(913) 829-8690
FULLY SPRINKLERED
INDUSTRIAL HYGENIST
RIVERFRONT (RSH)
1139 OLIVE ST, SUITE 300
ST. LOUIS, MO 63101
(713) 864-2900
STRUCT ENGR
STAND (SEI)
8234 ROBINSON ST
OVERLAND PARK, KS 66204
(913) 214-2169
COMMISSIONING
ES2
13401 N SANTE FE AVE
OKLAHOMA CITY, OK
(405) 528-4500
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
Drawing Number
Building Number
TELECOMMUNICATION
ASPEN COMMUNICATIONS
7 KIJI-DAVA CIRCLE, STE A
PRESCOTT, AZ 86301
(928) 774-0992
MECH / ELEC / PLUMB ENGR
SPUR DESIGN
2519 MADISON AVENUE, STE 100
KANSAS CITY, MO 64108
(913) 369-7200
FORCE PROTECT
10901 FRONT BEACH RD, UNIT 1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
PHYSICAL SECURITY
/1
/2
:1 :3
P
M
FIRE SUPPRESSION HAZARD
CLASSIFICATION OVERALL PLANS
SAB 25 OF 78BLS
FINAL BID DOCUMENTS
EHRM INFRASTRUCTURE
UPGRADE - TIER 2
06/02/2023
757-22-705
CHALMERS P. WYLIE VA
420 NORTH JAMES ROAD
COLUMBUS, OHIO 43219-1834
FX101
SPUR #: 1791.19
N
1" = 40'-0"
BLDG - LEVEL 1 - OVERALL HAZARD CLASSIFICATION PLAN1
N
1" = 40'-0"
BLDG - LEVEL 2 - OVERALL HAZARD CLASSIFICATION PLAN2
100 SF
3A004
102 SF
TELECOM
3A015
115 SF
TELECOM
3A063
FX403
FX403
FX403
1067 SF
SERVER/MAIN
TELECOM
4A201
119 SF
TELECOM
4A041
FX403
FX403
HAZARD CLASSIFICATION LEGEND
LIGHT HAZARD
(0.10 GPM/FT² OVER 1,500 FT² WITH
100 GPM EXTERIOR HOSE DEMAND)
ORDINARY HAZARD 1
(0.15 GPM/FT² OVER 1,500 FT² WITH
250 GPM EXTERIOR HOSE DEMAND)
ORDINARY HAZARD 2
(0.20 GPM/FT² OVER 1,500 FT² WITH
250 GPM EXTERIOR HOSE DEMAND)
1. ADDITIONS TO EXISTING FIRE PROTECTION WET PIPE
SYSTEM SHALL BE DESIGNED AND INSTALLED IN
ACCORDANCE WITH THE VA FIRE PROTECTION DESIGN
MANUAL - EIGHT EDITION AND NFPA 13-2022.
2. SPRINKLERS AND SPRINKLER PIPING ARE PERMITTED TO
BE INSTALLED IN TELECOMMUNICATION SPACES.
SPRINKLER AND SPRINKLER PIPING ARE REQUIRED TO BE
INSTALLED OUTSIDE OF THE DEDICATED ELECTRICAL
ZONE AS DEFINED BY NFPA 13 SECTION 26.30.2 AND NFPA
70 SECTIONS 110.26 (E) (1) (B) AND 110.26 (E) (1) (C).
3. SPRINKLERS INSTALLED IN TELECOMMUNCIATION SPACES
DESIGNATED AS ANSI/TIA-942-B RATING 1 SPACES/NON-
MISSION CRITICAL SHALL BE QUICK RESPONSE TYPE.
4. SPRINKLERS INSTALLED IN TELECOMMUNCIATION SPACES
DESIGNATED AS ANSI/TIA-942-B RATING 3
SPACES/MISSION CRITICAL SHALL BE FUSIBLE-LINK,
STANDARD-RESPONSE TYPE. THESE SPRINKLERS ARE
REQUIRED TO BE INSTALLED WITH PROTECTIVE CAGES AS
REQUIRED BY THE VA FIRE PROTECTION DESIGN MANUAL
SECTION 3.7.B.
5. ALL HANGERS MUST BE PROVIDED AND INSTALLED IN
ACCORDANCE WITH NFPA 13 AND PROJECT
SPECIFICATIONS. REFER TO STRUCTURAL DRAWINGS FOR
ADDITIONAL INFORMATION.
A. SEISMIC DESIGN CATEGORY: C
FIRE SUPPRESSION GENERAL NOTES:
105 SF
TELECOM
FX403
56 SF
TELECOM
FX403
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project NumberCONSULTANTS:
Drawing #
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
ARCH FIRM REG. NO. 20314270 EXP. 06/30/2023
ENGR FIRM REG. NO. 06253 EXP. 06/30/2024
FIRE PROTECTION ENGR
POOLE FIRE PROTECTION
19910 WEST 161ST ST.
OLATHE, KANSAS 66062
(913) 829-8690
FULLY SPRINKLERED
INDUSTRIAL HYGENIST
RIVERFRONT (RSH)
1139 OLIVE ST, SUITE 300
ST. LOUIS, MO 63101
(713) 864-2900
STRUCT ENGR
STAND (SEI)
8234 ROBINSON ST
OVERLAND PARK, KS 66204
(913) 214-2169
COMMISSIONING
ES2
13401 N SANTE FE AVE
OKLAHOMA CITY, OK
(405) 528-4500
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
Drawing Number
Building Number
TELECOMMUNICATION
ASPEN COMMUNICATIONS
7 KIJI-DAVA CIRCLE, STE A
PRESCOTT, AZ 86301
(928) 774-0992
MECH / ELEC / PLUMB ENGR
SPUR DESIGN
2519 MADISON AVENUE, STE 100
KANSAS CITY, MO 64108
(913) 369-7200
FORCE PROTECT
10901 FRONT BEACH RD, UNIT 1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
PHYSICAL SECURITY
/1
/2
:1 :3
P
M
FIRE SUPPRESSION HAZARD
CLASSIFICATION OVERALL PLANS
SAB 26 OF 78BLS
FINAL BID DOCUMENTS
EHRM INFRASTRUCTURE
UPGRADE - TIER 2
06/02/2023
757-22-705
CHALMERS P. WYLIE VA
420 NORTH JAMES ROAD
COLUMBUS, OHIO 43219-1834
FX102
SPUR #: 1791.19
N
1" = 40'-0"
BLDG 1 - LEVEL 3 - OVERALL HAZARD CLASSIFICATION PLAN1
N
1" = 40'-0"
BLDG 1 - LEVEL 4 - OVERALL HAZARD CLASSIFICATION PLAN3
N
1" = 40'-0"
BOILER PLANT - LEVEL 1 - OVERALL HAZARD CLASSIFICATION PLAN2
N
1" = 40'-0"
ENGINEERING BUILDING - LEVEL 1 - OVERALL HAZARD CLASSIFICATION PLAN4
1A0141
TELECOM
1A1061
TELECOM
1A0241
TELECOM
1A4571
TELECOM
1B0021
TELECOM
1B0061
TELECOM
1B6091
HAZARD CLASSIFICATION LEGEND
LIGHT HAZARD
(0.10 GPM/FT² OVER 1,500 FT² WITH
100 GPM EXTERIOR HOSE DEMAND)
ORDINARY HAZARD 1
(0.15 GPM/FT² OVER 1,500 FT² WITH
250 GPM EXTERIOR HOSE DEMAND)
ORDINARY HAZARD 2
(0.20 GPM/FT² OVER 1,500 FT² WITH
250 GPM EXTERIOR HOSE DEMAND)
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project NumberCONSULTANTS:
Drawing #
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
ARCH FIRM REG. NO. 20314270 EXP. 06/30/2023
ENGR FIRM REG. NO. 06253 EXP. 06/30/2024
FIRE PROTECTION ENGR
POOLE FIRE PROTECTION
19910 WEST 161ST ST.
OLATHE, KANSAS 66062
(913) 829-8690
FULLY SPRINKLERED
INDUSTRIAL HYGENIST
RIVERFRONT (RSH)
1139 OLIVE ST, SUITE 300
ST. LOUIS, MO 63101
(713) 864-2900
STRUCT ENGR
STAND (SEI)
8234 ROBINSON ST
OVERLAND PARK, KS 66204
(913) 214-2169
COMMISSIONING
ES2
13401 N SANTE FE AVE
OKLAHOMA CITY, OK
(405) 528-4500
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
Drawing Number
Building Number
TELECOMMUNICATION
ASPEN COMMUNICATIONS
7 KIJI-DAVA CIRCLE, STE A
PRESCOTT, AZ 86301
(928) 774-0992
MECH / ELEC / PLUMB ENGR
SPUR DESIGN
2519 MADISON AVENUE, STE 100
KANSAS CITY, MO 64108
(913) 369-7200
FORCE PROTECT
10901 FRONT BEACH RD, UNIT 1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
PHYSICAL SECURITY
/1
/2
:1 :3
P
M
ENLARGED FIRE SUPPRESSION HAZARD
CLASSIFCATION PLAN
SAB 27 OF 78BLS
FINAL BID DOCUMENTS
EHRM INFRASTRUCTURE
UPGRADE - TIER 2
06/02/2023
757-22-705
CHALMERS P. WYLIE VA
420 NORTH JAMES ROAD
COLUMBUS, OHIO 43219-1834
FX401
SPUR #: 1791.19
N
1/4" = 1'-0"
LEVEL 1 - HAZARD CLASSIFICATION PLAN - 1A0147
N
1/4" = 1'-0"
LEVEL 1 - HAZARD CLASSIFICATION PLAN - 1A1066
N
1/4" = 1'-0"
LEVEL 1 - HAZARD CLASSIFICATION PLAN - 1A0245
N
1/4" = 1'-0"
LEVEL 1 - HAZARD CLASSIFICATION PLAN - 1A4574
N
1/4" = 1'-0"
LEVEL 1 - HAZARD CLASSIFICATION PLAN - 1B0023
N
1/4" = 1'-0"
LEVEL 1 - HAZARD CLASSIFICATION PLAN - 1B0062
N
1/4" = 1'-0"
LEVEL 1 - HAZARD CLASSIFICATION PLAN - 1B6091
SHEET KEYNOTES
MARK KEYNOTE
1 THIS TELECOMMUNICATION SPACE HAS BEEN DESIGNATED
AS AN ANSI/TIA-942-B RATING 1 SPACE/NON-MISSION
CRITICAL IN ACCORDANCE WITH VA FIRE PROTECTION
DESIGN MANUAL SECTION 3.7.C. A QUICK-RESPONSE TYPE
SPRINKLER IS REQUIRED TO BE INSTALLED TO PROTECT
THIS SPACE. THE SPACE IS CURRENTLY PROTECTED WITH A
QUICK-RESPONSE SPRINKLER. CONTRACTOR TO FIELD
VERIFY SPIRNKLER LOCATION DOES NOT CONFLICT WITH
NFPA 13 OBSTRUCTION REQUIREMENTS WITH NEW ROOM
LAYOUT.
2A0181
TELECOM
2A1431
TELECOM
2B0031
TELECOM
2A0041
TELECOM
2B1021 TELECOM
2B3101
HAZARD CLASSIFICATION LEGEND
LIGHT HAZARD
(0.10 GPM/FT² OVER 1,500 FT² WITH
100 GPM EXTERIOR HOSE DEMAND)
ORDINARY HAZARD 1
(0.15 GPM/FT² OVER 1,500 FT² WITH
250 GPM EXTERIOR HOSE DEMAND)
ORDINARY HAZARD 2
(0.20 GPM/FT² OVER 1,500 FT² WITH
250 GPM EXTERIOR HOSE DEMAND)
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project NumberCONSULTANTS:
Drawing #
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
ARCH FIRM REG. NO. 20314270 EXP. 06/30/2023
ENGR FIRM REG. NO. 06253 EXP. 06/30/2024
FIRE PROTECTION ENGR
POOLE FIRE PROTECTION
19910 WEST 161ST ST.
OLATHE, KANSAS 66062
(913) 829-8690
FULLY SPRINKLERED
INDUSTRIAL HYGENIST
RIVERFRONT (RSH)
1139 OLIVE ST, SUITE 300
ST. LOUIS, MO 63101
(713) 864-2900
STRUCT ENGR
STAND (SEI)
8234 ROBINSON ST
OVERLAND PARK, KS 66204
(913) 214-2169
COMMISSIONING
ES2
13401 N SANTE FE AVE
OKLAHOMA CITY, OK
(405) 528-4500
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
Drawing Number
Building Number
TELECOMMUNICATION
ASPEN COMMUNICATIONS
7 KIJI-DAVA CIRCLE, STE A
PRESCOTT, AZ 86301
(928) 774-0992
MECH / ELEC / PLUMB ENGR
SPUR DESIGN
2519 MADISON AVENUE, STE 100
KANSAS CITY, MO 64108
(913) 369-7200
FORCE PROTECT
10901 FRONT BEACH RD, UNIT 1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
PHYSICAL SECURITY
/1
/2
:1 :4
P
M
ENLARGED FIRE SUPPRESSION HAZARD
CLASSIFICATION PLAN
SAB 26 OF 78BLS
FINAL BID DOCUMENTS
EHRM INFRASTRUCTURE
UPGRADE - TIER 2
06/02/2023
757-22-705
CHALMERS P. WYLIE VA
420 NORTH JAMES ROAD
COLUMBUS, OHIO 43219-1834
FX402
SPUR #: 1791.19
N
1/4" = 1'-0"
LEVEL 2 - HAZARD CLASSIFICATION PLAN - 2A0186
N
1/4" = 1'-0"
LEVEL 2 - HAZARD CLASSIFICATION PLAN - 2A1435
N
1/4" = 1'-0"
LEVEL 2 - HAZARD CLASSIFICATION PLAN - 2B0034
N
1/4" = 1'-0"
LEVEL 2 - HAZARD CLASSIFICATION PLAN - 2A0043
N
1/4" = 1'-0"
LEVEL 2 - HAZARD CLASSIFICATION PLAN - 2B1022
N
1/4" = 1'-0"
LEVEL 2 - HAZARD CLASSIFICATION PLAN - 2B3101
SHEET KEYNOTES
MARK KEYNOTE
1 THIS TELECOMMUNICATION SPACE HAS BEEN
DESIGNATED AS AN ANSI/TIA-942-B RATING 1
SPACE/NON-MISSION CRITICAL IN ACCORDANCE WITH VA
FIRE PROTECTION DESIGN MANUAL SECTION 3.7.C. A
QUICK-RESPONSE TYPE SPRINKLER IS REQUIRED TO BE
INSTALLED TO PROTECT THIS SPACE. THE SPACE IS
CURRENTLY PROTECTED WITH A QUICK-RESPONSE
SPRINKLER. CONTRACTOR TO FIELD VERIFY SPIRNKLER
LOCATION DOES NOT CONFLICT WITH NFPA 13
OBSTRUCTION REQUIREMENTS WITH NEW ROOM LAYOUT.
3A0041
TELECOM
3A0151
TELECOM
3A0631
4A041
TELECOM
4A0411
SERVER/MAIN
TELECOM
4A201 2
BREAKDOWN
AREA
4A200
STORAGE
E-4A202
HAZARD CLASSIFICATION LEGEND
LIGHT HAZARD
(0.10 GPM/FT² OVER 1,500 FT² WITH
100 GPM EXTERIOR HOSE DEMAND)
ORDINARY HAZARD 1
(0.15 GPM/FT² OVER 1,500 FT² WITH
250 GPM EXTERIOR HOSE DEMAND)
ORDINARY HAZARD 2
(0.20 GPM/FT² OVER 1,500 FT² WITH
250 GPM EXTERIOR HOSE DEMAND)
TELECOM
TELECOM
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project NumberCONSULTANTS:
Drawing #
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
ARCH FIRM REG. NO. 20314270 EXP. 06/30/2023
ENGR FIRM REG. NO. 06253 EXP. 06/30/2024
FIRE PROTECTION ENGR
POOLE FIRE PROTECTION
19910 WEST 161ST ST.
OLATHE, KANSAS 66062
(913) 829-8690
FULLY SPRINKLERED
INDUSTRIAL HYGENIST
RIVERFRONT (RSH)
1139 OLIVE ST, SUITE 300
ST. LOUIS, MO 63101
(713) 864-2900
STRUCT ENGR
STAND (SEI)
8234 ROBINSON ST
OVERLAND PARK, KS 66204
(913) 214-2169
COMMISSIONING
ES2
13401 N SANTE FE AVE
OKLAHOMA CITY, OK
(405) 528-4500
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
Drawing Number
Building Number
TELECOMMUNICATION
ASPEN COMMUNICATIONS
7 KIJI-DAVA CIRCLE, STE A
PRESCOTT, AZ 86301
(928) 774-0992
MECH / ELEC / PLUMB ENGR
SPUR DESIGN
2519 MADISON AVENUE, STE 100
KANSAS CITY, MO 64108
(913) 369-7200
FORCE PROTECT
10901 FRONT BEACH RD, UNIT 1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
PHYSICAL SECURITY
/1
/2
:1 :4
P
M
ENLARGED FIRE SUPPRESION HAZARD
CLASSIFICATION PLAN
SAB 29 OF 78BLS
FINAL BID DOCUMENTS
EHRM INFRASTRUCTURE
UPGRADE - TIER 2
06/02/2023
757-22-705
CHALMERS P. WYLIE VA
420 NORTH JAMES ROAD
COLUMBUS, OHIO 43219-1834
FX403
SPUR #: 1791.19
N
1/4" = 1'-0"
LEVEL 3 - HAZARD CLASSIFICATION PLAN - 3A0045
N
1/4" = 1'-0"
LEVEL 3 - HAZARD CLASSIFICATION PLAN - 3A0154
N
1/4" = 1'-0"
LEVEL 3 - HAZARD CLASSIFICATION PLAN - 3A0633
N
1/4" = 1'-0"
LEVEL 4 - HAZARD CLASSIFICATION PLAN - 4A0412
N
1/4" = 1'-0"
LEVEL 4 - HAZARD CLASSIFICATION PLAN - 4A2011
SHEET KEYNOTES
MARK KEYNOTE
1 THIS TELECOMMUNICATION SPACE HAS BEEN DESIGNATED
AS AN ANSI/TIA-942-B RATING 1 SPACE/NON-MISSION
CRITICAL IN ACCORDANCE WITH VA FIRE PROTECTION
DESIGN MANUAL SECTION 3.7.C. A QUICK-RESPONSE TYPE
SPRINKLER IS REQUIRED TO BE INSTALLED TO PROTECT
THIS SPACE. THE SPACE IS CURRENTLY PROTECTED WITH
A QUICK-RESPONSE SPRINKLER. CONTRACTOR TO FIELD
VERIFY SPIRNKLER LOCATION DOES NOT CONFLICT WITH
NFPA 13 OBSTRUCTION REQUIREMENTS WITH NEW ROOM
LAYOUT.
2 CONTRACTOR TO PROVIDE NEW ISOLATION VALVE
ASSEMBLY TO DESIGNATE ROOM 4A201 AS SINGLE FIRE
SPRINKLER ZONE. CONTRACTOR TO COORDINATE THE
LOCATION OF THE FLOW AND TAMPER SWITCHES WITH THE
FIRE ALARM CONTRACTOR. VALVE ASSEMBLY SHALL BE
INSTALLED IN AN ACESSIBLE LOCATION OUTSIDE OF THE
SPACE. CONTRACTOR TO COORDINATE WITH VA
PERSONNEL ON LOCATION OF CONTROL VALVE FOR THIS
ZONE BEFORE WORK BEGINS. CONTRACTOR TO
COORDINATE WITH VA ON IMPAIRMENT OF FIRE SPRINKLER
SYSTEM DURING CONTRUCTION.
3 THIS TELECOMMUNICATION SPACE IS TO BE PROTECTED IN
ACCORDANCE WITH THE VA FIRE PROTECTION DESIGN
MANUAL 8TH EDITION. THIS SPACE HAS BEEN DESIGNATED
A ANSI/TIA-942-B RATING 1/NON-MISSION CRITICAL IN
ACCORDANCE WITH THE OI&T DESIGN GUIDE VERSION 3.1.
SPRINKLERS IN THIS SPACE ARE TO BE STANDARD
RESPONSE TYPE, FUSIBLE-LINK WITH PROTECTIVE CAGES.
N
1/4" = 1'-0"
ENGINEERING BUILDING - HAZARD CLASSIFICATION PLAN - 1066
N
1/4" = 1'-0"
BOILER PLANT - HAZARD CLASSIFICATION PLAN - 1047
SERVER/MAIN
4A201
P S
R S
F A
C U c d
B c d
R
K M
V S
S O
V
C A c d
B c d
R
A S
D
CA FCA
F
15cd
B
15cd
R
F
15cd
B
15cd
R
CAF CA
15 ASD DETECTOR - DISABLE • • • •
• PERFORM OPERATION/REPORT DEVICE STATUS
A B C D E F G H I J K L M N N O P Q R S T U
9 MAINTENANCE SWITCH • • • •
10 SOLENOID SUPERVISORY SWITCH • • • •
11 ACTUATOR PLACEMENT INDICATOR • • • •
12 DISCHARGE PRESSURE SWITCH • • • • • • • •
13 LOW PRESSURE SWITCH • • • •
11 SCP AC POWER FAILURE • • •
12 SCP SYSTEM LOW BATTERY • • •
13 OPEN CIRCUIT OR GROUND FAULT • • •
14 CLASS B NOTIFICATION CIRCUIT (NAC) - SHORT • • •
15 LOCAL MANUAL ACTUATOR ON TANK • • • • • • • • • •
13 ASD DETECTOR - URGENT FAULT • •
14 ASD DETECTOR - MINOR FAULT • •
3 ASD DETECTOR - FIRE 1 - 1.0% OBS/FT (w/ 15 SECOND DELAY) • • • • • • • • 4 ASD DETECTOR - FIRE 2 - 3.0% OBS/FT (w/ 30 SECOND DELAY) • • • • • • • • •
5 COMPLETION OF 30 SECOND COUNTDOWN TIMER AFTER FIRE 2 • • •
6 ABORT SWITCH - CONTINUOUSLY HELD DOWN • • • •
7 MANUAL RELEASING PULL STATION • • • • • • • • •
8 AFTER 10 SECOND AGENT RELEASE DELAY • • •
AT 4007ES SCP NOTIFICATION AND FIRE SAFETY CONTROLS
S Y
S T
E M
O U
T P
U T
S
A C
T U
A T
E C
O M
M O
N A
L A
R M
S
IG
N A
L I
N D
IC
A
T O
R
A C
T U
A T
E A
U D
IB
L E
A L A
R M
S
IG
N A
L
A C
T U
A T
E C
O M
M O
N S
U P
E R
V
IS
O R
Y S
IG
N
A L I
N D
IC
A
T O
R
A C
T U
A T
E A
U D
IB
L E
S U
P E
R V
IS
O
R Y
S
IG
N A
L
A C
T U
A T
E C
O M
M O
N T
R O
U B
L E
S
IG
N A
L I
N D
IC
A
T O
R
A C
T U
A T
E A
U D
IB
L E
T R
O U
B L E
S
IG
N A
L
D
IS
P L A
Y C
H A
N G
E O
F S
T A
T U
S
T R
A N
S M
IT
A
L A
R M
S
IG
N A
L T
O M
A
IN
F A
C
IL
IT
Y
F A
C P
T R
A N
S M
IT
S
U P
E R
V
IS
O R
Y S
IG
N
A L T
O M
A
IN
I F
A C
IL
IT
Y F
A C
P
T R
A N
S M
IT
T
R O
U B
L E
S
IG
N A
L T
O M
A
IN
F A
C
IL
IT
Y
F A
C P
A C
T U
A T
E S
U P
P R
E S
S
IO
N B
E L L
A C
T U
A T
E S
U P
P R
E S
S
IO
N H
O R
N A
T
B
P M
A C
T U
A T
E S
U P
P R
E S
S
IO
N H
O R
N A
T S
T E
A D
Y T
O N
E
A C
T U
A T
E P
R E
-D
IS
C H
A R
G E
S T
R O
B E
A C
T U
A T
E S
U P
P R
E S
S
IO
N S
T R
O B
E
B E
G
IN
S
E C
O N
D C
O U
N T
D O
W N
A G
E N
T R
E L E
A S
E I
N T
O A
L L H
A Z
A R
D S
P A
C E
S
B E
G
IN
S
E C
O N
D A
G E
N T
R E
L E
A S
E D
E L A
Y
H V
A C
S H
U T
D O
W N
D A
M P
E R
C L O
S U
R E
S
IL
E N
C E
S S
U P
P R
E S
S
IO
N B
E L L
S T
O P
S F
IR
E
-S
E C
O N
D C
O U
N T
D O
W N
T
IM
E R
SYSTEM INPUTS A B C D E F G H I J K L M N N O P Q R S T U
1 ASD DETECTOR - ALERT - 0.2% OBS/FT (w/ 30 SECOND DELAY) • • • • 2 ASD DETECTOR - ACTION - 0.6% OBS/FT (w/ 30 SECOND DELAY) • • • •
AIM AIM
PS VS
AIM
CT
AIM
CT
AIM
CT
RSFACU
S U
P E
R V
IS
O
R Y
T R
O U
B L E
A L A
R M
SPD
120VAC DEDICATED
BRANCH CIRCUIT
s CA CA
B R
KM
SOV
CA
AIM
CT
AIM
CT
AIM
CT
A L E
R T
T R
O U
B L E
A L A
R M
AIM
CT
A L A
R M
ASD
s
ASD
ASPIRATING SMOKE
DETECTION SYSTEM
TO PRIMARY
POWER SUPPLY
SEE SHEET
FA-001 FOR
CONTINUATION
F
WARNING!
LEAVE AREA IMMEDIATELY
WHEN ALARM SOUNDS
NOVEC 1230
BEING RELEASED
WARNING!
THIS AREA IS PROTECTED BY A
NOVEC 1230 EXTINGUISHING
SYSTEM. DO NOT ENTER
WITHOUT AUTHORIZATION
DURING OR AFTER DISCHARGE.
PUSH
PULL
PUSH/HOLD
SUPPRESSION SYSTEM ABORT
FIRE
SUPPRESSION
MANUAL
RELEASE
FIRE
SUPPRESSION
ABORT
PUSH BUTTON
AND HOLD
CLEAN AGENT LEGEND
SYMBOL DESCRIPTION
F FIRE ALARM MANUAL PULL STATION
FIRE ALARM HORN/STROBE COMBINATION DEVICE
SUPPRESSION HORN
VS VALVE SUPERVISORY SWITCH
WF WATER FLOW SWITCH
AIM ADDRESSABLE INPUT MODULE
AOM ADDRESSABLE OUTPUT MODULE
SYMBOL MODIFIERS
WP
nCD
C
WEATHERPROOF
CANDELA RATING
CEILING MOUNTED
CA CLEAN AGENT MANUAL PULL STATION
CA CLEAN AGENT ABORT STATION
KM KEYED MAINTENANCE SWITCH
CLEAN AGENT DISCHARGE STROBEB
CLEAN AGENT PRE-DISCHARGE STROBER
s
ASD
ASPIRATING SMOKE DETECTOR
SOV
CA
CLEAN AGENT ACTUATOR
DISCRETE OUTPUT - DRY CONTACTCT
PS PRESSURE SWITCH
FACU FIRE ALARM CONTROL UNIT
ASPIRATING SMOKE DETECTOR CONTROL PANEL
SURGE PROTECTIVE DEVICE
ASD
SPD
RSFACU RELEASING SERVICE FIRE ALARM CONTROL UNIT
F
SUPPRESSION BELL
CLEAN AGENT TANK
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project NumberCONSULTANTS:
Drawing #
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
ARCH FIRM REG. NO. 20314270 EXP. 06/30/2023
ENGR FIRM REG. NO. 06253 EXP. 06/30/2024
FIRE PROTECTION ENGR
POOLE FIRE PROTECTION
19910 WEST 161ST ST.
OLATHE, KANSAS 66062
(913) 829-8690
FULLY SPRINKLERED
INDUSTRIAL HYGENIST
RIVERFRONT (RSH)
1139 OLIVE ST, SUITE 300
ST. LOUIS, MO 63101
(713) 864-2900
STRUCT ENGR
STAND (SEI)
8234 ROBINSON ST
OVERLAND PARK, KS 66204
(913) 214-2169
COMMISSIONING
ES2
13401 N SANTE FE AVE
OKLAHOMA CITY, OK
(405) 528-4500
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
Drawing Number
Building Number
TELECOMMUNICATION
ASPEN COMMUNICATIONS
7 KIJI-DAVA CIRCLE, STE A
PRESCOTT, AZ 86301
(928) 774-0992
MECH / ELEC / PLUMB ENGR
SPUR DESIGN
2519 MADISON AVENUE, STE 100
KANSAS CITY, MO 64108
(913) 369-7200
FORCE PROTECT
10901 FRONT BEACH RD, UNIT 1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
PHYSICAL SECURITY
/1
/2
:1 :4
P
M
CLEAN AGENT NOTES, DETAILS, AND
PLAN
SAB 30 OF 78BLS
FINAL BID DOCUMENTS
EHRM INFRASTRUCTURE
UPGRADE - TIER 2
06/02/2023
757-22-705
CHALMERS P. WYLIE VA
420 NORTH JAMES ROAD
COLUMBUS, OHIO 43219-1834
SH001
SPUR #: 1791.19
N
1/4" = 1'-0"
LEVEL 4 - CLEAN AGENT PLAN - 4A2011
SCALE: NONE
CLEAN AGENT INPUT/OUTPUT MATRIX5
CLEAN AGENT GENERAL NOTES:
1. PROVIDE A NEW CLEAN AGENT (NOVEC 1230) FIRE EXTINGUISHING
SYSTEM THAT IS DESIGNED AND INSTALLED IN ACCORDANCE WITH
NFPA 2001, 2022 EDITION.
2. CLEAN AGENT TO BE USED IS NOVEC 1230 (FK-5-1-12) AT MINIMUM
DESIGN CONCENTRATION OF 6.1%. MINIMUM 4.5% TO BE INCREASED
TO 6.1% WITH 1.25 SAFETY FACTOR IN ACCORDANCE WITH NFPA 2001.
3. ALL PIPE AND FITTINGS SHALL BE IN ACCORDANCE WITH THE
REQUIREMENTS OF NFPA 2001.
4. ALL PIPE AN FITTINGS SHALL BE BLACK SCALE FREE STEEL
CONFORMING TO ONE OF THE FOLLOWING REQUIREMENTS:
A. ASTM A-106, SEAMLESS, GRADE A OR B SCHEDULE 40 THROUGH
8 INCHES
B. ASTM A-53, SEAMLESS, GRADE A OR B SCHEDULE 40 THROUGH 8
INCHES
C. ASTM A-53 ERW, GRADE A OR B SHALL NOT BE USED WITHOUT
PRIOR WRITTEN APPROVAL FROM AHJ.
D. ASTM A-53, CLASS F AND ASTM A-120 SHALL NOT BE USED.
5. STENCILED PIPE IDENTIFICATION SHALL NOT BE PAINTED OVER,
CONCEALED OR REMOVED PRIOR TO APPROVAL BY AHJ.
6. ALL FITTINGS SHALL BE BLACK MALLEABLE IRON OR FORGED STEEL
CONFORMING TO THE FOLLOWING REQUIREMENTS:
A. CLASS 300 MALLEABLE IRON THROUGH 3 INCHES
B. 1000# RATED FORGED STEEL GREATER THAN 3 INCHES
C. ALL GROOVED FITTINGS MUST BE UL LISTED AND CONFORM TO
THE PRESSURE REQUIREMENTS OUTLINED IN NFPA 2001
D. CAST IRON FITTINGS ARE NOT ACCEPTABLE.
7. ALL PIPE ENDS SHALL BE REAMED AFTER CUTTING.
8. EACH PIPE SECTION SHALL BE CLEANED INTERNALLY AFTER
PREPARATION AND BEFORE ASSEMBLY BY SWABBING WITH A
SUITABLE NONFLAMMABLE CLEANER.
9. TEFLON THREAD SEAL TAPE SHALL BE USED ON ALL MALE THREADED
JOINTS ONLY. ALL GROOVED COUPLING GASKETS SHALL BE
LUBRICATED PER THE MANUFACTURER'S SPECIFICATIONS.
10. ALL PIPING SHALL BE RIGIDLY AND SECURELY ANCHORED TO
BUILDING STRUCTURE USING U.L. APPROVED HANGERS. CONTRACTOR
TO PROVIDE SESIMIC BRACING, SITE IS CLASSIFIED AS SEISMIC
DESIGN CATEGORY "C". REFER TO STRUCTURAL DRAWINGS FOR
ADDITIONAL INFORMATION.
11. ALL STORAGE CONTAINERS SHALL BE MOUNTED PLUMB AND LEVEL
AND SECURELY ANCHORED TO BUILDING STRUCTURE.
12. REFER TO ARCHITECTURAL SIGNAGE DETAILS FOR MATERIAL, FINISH
COLOR, ETC. OF CLEAN AGENT SIGNAGE AND START/STOP STATIONS.
SAMPLING PIPE NETWORK REQUIREMENTS (ASD):
1. ALL PIPING SHALL BE CPVC.
2. ATTACH PIPES TO STRUCTURE AS APPLICABLE, USING STANDARD
PIPE SECURING HARDWARE AT INTERVALS OF NO MORE THAN 5 FEET.
3. ALL CONNECTIONS AND JOINTS SHALL BE MADE WITH STANDARD
CONNECTIONS DESIGNED TO BE COMPATIBLE WITH PIPE MATERIAL.
4. ALL JOINTS SHALL BE AIR TIGHT TO PREVENT INFILTRATION AT OTHER
THAN SAMPLING PORT LOCATIONS.
5. COORDINATE THE LOCATION OF PIPING AND SAMPLING PORTS WITH
OTHER TRADES TO PERMIT PROPER ACCESS TO ALL EQUIPMENT.
6. THE SAMPLING PIPE NETWORK SHALL BE CLEARED OF ALL DIRT AND
DEBRIS BY RUNNING AIR THROUGH THE PIPE NETWORK FOR A
MINIMUM OF 30 MINUTES PRIOR TO CONNECTION AND OPERATION OF
THE SYSTEM.
7. ALL PIPING SHALL BE LABELED AT EACH SAMPLING PORT AND AT 20
FOOT INTERVALS USING MANUFACTURERS IDENTIFICATION LABELS.
8. DO NOT GLUE PIPE(S) INTO SOCKET(S) OF INLET MANIFOLD. PIPES
MUST BE INSERTED INTO THE SOCKET(S) AT A MINIMUM OF 1/2 INCH.
9. SENSITIVITY SETTINGS SHOWN IN THE MATRIX SHALL BE ACHIEVED AT
EACH SAMPLING PORT.
SCALE: NONE
CLEAN AGENT TYPICAL RISER DIAGRAM4
SCALE: NONE
CLEAN AGENT SIGNAGE3
SCALE: NONE
CLEAN AGENT START/STOP STATIONS2
SHEET KEYNOTES
MARK KEYNOTE
1 SPACE TO BE PROTECTED WITH A CLEAN AGENT
FIRE EXTINGUISHMENT SYSTEM. AIR-ASPIRATING
SMOKE DETECTION SAMPLING PORTS TO BE
PROVIDED THROUGHOUT SCOPE OF WORK AREA.
CALCULATION AND SYSTEM DESIGN ARE BASED ON F-K-5-1-12.
THE SYSTEM IS DESIGNED TO EXTINGUISH A SINGLE FIRE.
THE SYSTEM IS DESIGNED FOR TOTAL FLOODING.
HAZARD CLASSIFICATION: CLASS C
MINIMUM DESIGN CONCENTRATION: 4.5% (NFPA 2001, TABLE A.7.2.2.3(b))
MINIMUM ANTICIPATED TEMPERATURE: 70F
ELEVATION: APPROX. 31FT.
EQUIVALENT ALTITUDE: 0 FT.
(C) AGENT REQUIRED AT 70F: 0.04075 LBS/FT3 (NFPA 2001, TABLE A.7.3.1(a))
(A) ATMOSPHERIC CORRECTION FACTOR 1.00
**ALL AGENT QUANTITIES ARE ESTIMATED MINIMUM QUANTITIES AND ASSUME ROOM
INTEGRITY WITH NEGLIGIBLE AGENT LEAKAGE.**
PROTECTED SPACE: SERVER/MAIN TELECOM ROOM 4A201
RAISED FLOOR: NONE
AREA (A): 1066.96 SQ. FT.
HEIGHT (H): 8'-10 5/16"
(V) SPACE VOLUME
V=(A)(H)
V=9452 CU. FT.
(W) TOTAL DESIGN QUANTITY:
W=(V)(C)(A) W=(9452)(.04075)(1.00)
TOTAL DESIGN QUANTITY:385.2 LBS.
| Sheets |
| FA001 - FIRE ALARM GENERAL NOTES, LEGEND, AND DIAGRAMS |
| FA101 - FIRE ALARM OVERALL PLANS |
| FA102 - FIRE ALARM OVERALL PLANS |
| FA401 - ENLARGED FIRE ALARM PLAN |
| FA402 - ENLARGED FIRE ALARM PLAN |
| FA403 - ENLARGED FIRE ALARM PLAN |
| FX101 - FIRE SUPPRESSION HAZARD CLASSIFICATION OVERALL PLANS |
| FX102 - FIRE SUPPRESSION HAZARD CLASSIFICATION OVERALL PLANS |
| FX401 - ENLARGED FIRE SUPPRESSION HAZARD CLASSIFCATION PLAN |
| FX402 - ENLARGED FIRE SUPPRESSION HAZARD CLASSIFICATION PLAN |
| FX403 - ENLARGED FIRE SUPPRESION HAZARD CLASSIFICATION PLAN |
| SH001 - CLEAN AGENT NOTES, DETAILS, AND PLAN |
File details come from the government source that posted it. Updated .