About this file

This federal contract opportunity notice is for infrastructure upgrades at a Veterans Affairs medical center in Columbus, Ohio. The Department of Veterans Affairs Technology Acquisition Center Austin is soliciting proposals under solicitation number 36C77623R0150 for tier 2 construction services to upgrade the enterprise human resources management infrastructure at the Columbus medical center. Proposals are due by February 15, 2023, and the contract is set to be awarded by April 30, 2023. The notice specifies the location but does not provide further details on the required products, services, pricing terms, or other salient information.

View the file

Other files

File Type Posted
Amd 11 Att - RFI Responses_3.12.24.pdf PDF
36C77623R0150 0011.docx DOCX document
36C77623R0150 0010.docx DOCX document
Amd 10_1791.19 - RFI Responses_3.11.24.pdf PDF
Amd 10 23 07 11 HVAC and Boiler Plant Insulation2.pdf PDF
36C77623R0150 0009.docx DOCX document
36C77623R0150 0008.docx DOCX document
OIT Infrastructure Standard for Telecommunications Spaces - Version 3.1.pdf PDF
36C77623R0150 0007.docx DOCX document
Amendment 6 All Files.zip ZIP file
36C77623R0150 0006.docx DOCX document
36C77623R0150 0005.docx DOCX document
36C77623R0150 0004.docx DOCX document
757-22-705 Pre-Bid Site Visit Sign In.pdf PDF
04_Architectural.pdf PDF
36C77623R0150 0003.docx DOCX document
02_Hazardous Materials.pdf PDF
01_General.pdf PDF
06_Mechanical_Drawings.pdf PDF
07_Electrical.pdf PDF
03_Structural.pdf PDF
05_Fire Protection.pdf PDF
Columbus EHRM FINAL SPECS VOL 1.pdf PDF
Columbus EHRM FINAL SPECS VOL 2.pdf PDF
36C77623R0150 0002.docx DOCX document
36C77623R0150 0001.docx DOCX document
Attachment 15 -Site Visit Instructions Revised.docx DOCX document
Attachment 11 - 07_Narrative_Electrical.pdf PDF
Attachment 9 - 05_Narrative_Fire Protection.pdf PDF
Attachment 6 - 01_Narrative_Architectural.pdf PDF
Attachment 2 - Contractor Safety - Environmental Form.docx DOCX document
Attachment 13- Wage Rates.pdf PDF
Attachment 8 - 03_Narrative_Structural (1).pdf PDF
Attachment 15 -Site Visit Instructions.docx DOCX document
36C77623R0150_1.docx DOCX document
Attachment 14 - EHRM FULL SET 07122023.pdf PDF
Attachment 4 - EHRM Columbus Drawings Part 2.pdf PDF
Attachment 12 - 09_Narrative_Telecom.pdf PDF
Attachment 16- VA Engineering Map.pdf PDF
Attachment 3 - EHRM Columbus Drawings Part 1.pdf PDF
Attachment 10 - 06_Narrative_Mechanical.pdf PDF
Attachment 1- Limitations on Subcontracting - Construction.docx DOCX document
Attachment 5 - EHRM Columbus Drawings Part 3.pdf PDF
Attachment 7 - 02_Narrative_Environmental.pdf PDF
Show all 44

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

ABBREVIATIONS

STANDARD MOUNTING HEIGHTSANNOTATION

ELECTRICAL: (AFF, AFG UNLESS NOTED OTHERWISE)

CU

TELECOMMUNICATION PLAN NOTE CALL OUT

EQUIPMENT DESIGNATION TAG

NEW WORK TO EXISTING WORK CONNECTION POINT

IC

CATV

FO

D

S

IC

S

WAP

# / #TV

M

S

V

COMMUNICATIONS OUTLET, TYPE AS NOTED

COMMUNICATIONS OUTLET, FLOOR BOX, TYPE AS NOTED

WIRELESS ACCESS POINT, CEILING MOUNTED

COMMUNICATIONS OUTLET, CEILING MTD, TYPE AS NOTED

SPEAKER, WALL MOUNTED

SPEAKER, CEILING MOUNTED

TELECOMMUNICATIONS RACK, TWO-POST, FLOOR MOUNTED

TELECOMMUNICATIONS ENCLOSURE, WALL MOUNTED

WIRE BASKET TRAY, TYPE AS NOTED

CABLE TELEVISION LINE

FIBEROPTIC LINE

COMMUNICATION CABLE PATHWAY

FIBER OPTIC BACKBONE PATHWAY "A"

DATA LINE

SPEAKER LINE

INTERCOM LINE

INTERCOM, "M" DENOTES MASTER STATION

VOLUME CONTROL, WALL MOUNTED

MULTI-SERVICE POWER POLE WITH POWER/DATA,

TYPE AS NOTED AND/OR SCHEDULED

MULTI-SERVICE FLOOR BOX/POKE-THRU WITH POWER/DATA,

TYPE AS NOTED AND/OR SCHEDULED

TELECOMMUNICATIONS CHANNEL RACK, 7'H x 19"W x 30"D, 4-POST, OPEN FRAME TYPE

SERVER CABINET, VENTED HOOD, FLOOR MOUNTED

# = DATA, # = QUANTITY OF CABLES

#TV = CABLE TELEVISION, # = QUANTITY OF CABLES

= DATA, 2 CABLES

#TV = CABLE TELEVISION, # = QUANTITY OF CABLES

#V = VOICE, # = QUANTITY OF CABLES

= DATA, 2 CABLES

# = DATA, # = QUANTITY OF CABLES

TELECOMMUNICATIONS SYMBOLS

#TV = CABLE TELEVISION, # = QUANTITY OF CABLES

#V = VOICE, # = QUANTITY OF CABLES

M (CONT'D)

MV MEDIUM VOLTAGE

MVA MEGAVOLT-AMPERE

MW MEGAWATT

X

W

V

U

T

S

R

P

O

N

M

L

K

J

I

H

FA FIRE ALARM

FAAP FIRE ALARM ANNUNCIATOR PANEL

FABL FIRE ALARM BELL

FABX FIRE ALARM BOX

FACP FIRE ALARM CONTROL PANEL

FC FOOTCANDLE

FI FILM ILLUMINATOR

FIXT FIXTURE

FLA FULL LOAD AMPS

FLEX FLEXIBLE METALLIC CONDUIT

FLUOR FLUORESCENT

FO FIBER-OPTIC

FP FIRE PROTECTION

FT FEET OR FOOT

FVNR FULL VOLTAGE NON-REVERSING

FVR FULL VOLTAGE REVERSING

G

F

E

D

EC EMPTY CONDUIT

EG EQUIPMENT GROUND

EL ELEVATION

ELEC ELECTRIC OR ELECTRICAL

ELEV ELEVATOR

EMCP EMER. MONITORING CONTROL PANEL

EMER EMERGENCY

EMI ELECTROMAGNETIC INTERFERENCE

EMT ELECTRICAL METALLIC TUBING

ENCL ENCLOSURE

EPO EMERGENCY POWER OFF

ESMT EASEMENT

ETD EXISTING TO BE DEMOLISHED

ETR EXISTING TO REMAIN

EWC ELECTRIC WATER COOLER

EWH ELECTRIC WATER HEATER

EXIST EXISTING

DB DECIBEL OR DIRECT BURIAL

DC DIRECT CURRENT

DCP DIMMER CONTROL PANEL

DEG C DEGREES CELSIUS

DEG F DEGREES FAHRENHEIT

DEMO DEMOLITION

DIAG DIAGRAM

DISC DISCONNECT

DISTR DISTRIBUTION

DISTR PNL DISTRIBUTION PANEL

DN DOWN

DPDT DOUBLE POLE, DOUBLE THROW

DPST DOUBLE POLE, SINGLE THROW

DRSW DOOR SWITCH

DS DISCONNECT SWITCH

DWG DRAWING

C CONDUIT

CAP CAPACITY

CAT CATALOG

CATV COMMUNITY ANTENNA TELEVISION

CCR CONTROL CONTACTOR

CCTV CLOSED CIRCUIT TELEVISION

cd CANDELA

CD CONSTRUCTION DOCUMENTS

CF CONTRACTOR FURNISHED

CF/CI CONTRACTOR FURNISHED/

CONTRACTOR INSTALLED

CF/OI CONTRACTOR FURNISHED/OWNER

INSTALLED

CFE CONTRACTOR FURNISHED

EQUIPMENT

CHW CHILLED WATER

CHWP CHILLED WATER PUMP

CKT CIRCUIT

CKT BRKR CIRCUIT BREAKER

CLF CURRENT LIMITING FUSE

CLG CEILING

CMU CONCRETE MASONRY UNIT

COAX COAX CABLE

COMM COMMUNICATION

CONC CONCRETE

CONT CONTINUE

CONTR CONTRACTOR

COORD COORDINATE

CPT CONTROL POWER TRANSFORMER

CRI COLOR RENDERING INDEX

CT CURRENT TRANSFORMER

CTV CABLE TELEVISION

CU COPPER

CU FT CUBIC FEET

C

B

A

UFD UNDERFLOOR DUCT

UGND UNDERGROUND

UL UNDERWRITERS LABORATORY

UNO UNLESS NOTED OTHERWISE

UPS UNINTERRUPTIBLE POWER SUPPLY

UTIL UTILITY

V VOLT

VA VOLT AMPERE

VAR VOLT AMPERE REACTIVE

VCM VERTICAL CABLE MANAGER

VFD VARIABLE FREQUENCY DRIVE

VOLT VOLTAGE

TC TIME CLOCK

TEL TELEPHONE

TO TELECOMMUNICATIONS OUTLET

TR TELECOMMUNICATIONS ROOM

TV TELEVISION

TYP TYPICAL

RCP REFLECTED CEILING PLAN

RCPT RECEPTACLE

REC RECESSED

REQD REQUIRED

RGS RIGID GALVANIZED STEEL

RM ROOM

RMS ROOT MEAN SQUARE

RU RACK UNIT

N NEUTRAL

NA NOT APPLICABLE

NEC NATIONAL ELECTRICAL CODE

NEMA NATIONAL ELECTRICAL

MANUFACTURERS ASSOCIATION

NFPA NATIONAL FIRE PROTECTION

ASSOCIATION

NIC NOT IN CONTRACT

NL NIGHT LIGHT

NO NORMALLY OPEN

NS NO SCALE

NTS NOT TO SCALE

OC ON CENTER

OD OUTSIDE DIAMETER

OL OVERLOAD

MATV MASTER ANTENNA TELEVISION SYSTEM

MAX MAXIMUM

MC METAL-CLAD

MCA MINIMUM CIRCUIT AMPS

MCB MAIN CIRCUIT BREAKER

MCC MOTOR CONTROL CENTER

MDP MAIN DISTRIBUTION PANEL

MECH MECHANICAL

MG MOTOR GENERATOR

MH MANHOLE

MIN MINIMUM

MOCP MAXIMUM OVERCURRENT PROTECTION

MLO MAIN LUGS ONLY

MT MOUNT

MTD MOUNTED

MTG MOUNTING

KV KILOVOLT

KVA KILOVOLT AMPERE

KVAH KILOVOLT AMPERE PER HOUR

KVAR KILOVOLT AMPERE REACTIVE

KW KILOWATT

KWH KILOWATT HOUR

KWHM KILOWATT HOUR METER

JB JUNCTION BOX

J-BOX JUNCTION BOX

XFER TRANSFER

XFMR TRANSFORMER

XP EXPLOSION PROOF

LED LIGHT EMITTING DIODE

LF LINEAR FEET (FOOT)

LM LUMEN

LP LIGHT POLE

LPS LOW PRESSURE SODIUM

LRA LOCKED ROTOR AMPS

LTCP LOCAL TEMPERATURE CONTROL PANEL

LT LIGHT

LTG LIGHTING

LTG PNL LIGHTING PANEL

LTNG LIGHTNING

LV LOW VOLTAGE

W WATT

WAO WORK AREA OUTLET

WP WEATHERPROOF

IESNA ILLUMINATION ENGINEERING SOCIETY

OF NORTH AMERICA

IG ISOLATED GROUND

IMC INTERMEDIATE METAL CONDUIT

INCAND INCANDESCENT

IR INFRARED

IWH INSTANTANEOUS WATER HEATER

G OR GND GROUND OR GENERATOR

GEN GENERATOR

GFCI GROUND FAULT CIRCUIT INTERRUPTER

GTB GROUND TERMINAL BOX

SCC SHORT CIRCUIT CAPACITY

SES SERVICE ENTRANCE SECTION

SD SMOKE DETECTOR

SF SQUARE FOOT (FEET)

SHT SHEET

SI INTERNATIONAL SYSTEM OF UNITS

SPEC SPECIFICATION

SPST SINGLE POLE, SINGLE THROW

SURF SURFACE

SW SWITCH

SWBD SWITCHBOARD

SWGR SWITCHGEAR

P POLE

PA PUBLIC ADDRESS

PB PANELBOARD, PULL BOX, OR

PUSHBUTTON

PBPU PREFABRICATED BEDSIDE PATIENT UNIT

PCB POLYCHLORINATED BIPHENYL

PEC PHOTOELECTRIC CELL

PED PEDESTAL

PEND PENDANT

PF POWER FACTOR

PH PHASE

PNL PANEL

POD POWER OPERATED DAMPER

POE POWER OVER ETHERNET

PP PATCH PANEL

PT POTENTIAL TRANSFORMER

PTRV POWER TYPE ROOF VENTILATION

PVC POLYVINYL CHLORIDE (PLASTIC)

PWR POWER

1P SINGLE POLE

1PH SINGLE-PHASE

3P THREE POLE

3PH THREE-PHASE

3W THREE WIRE

4W FOUR WIRE

A/C AIR CONDITIONING

A/E ARCHITECT/ENGINEER

AAP ALARM ANNUNCIATOR PANEL

AC ALTERNATING CURRENT OR ARMORED

ACC ACCESSIBLE

ADDL ADDITIONAL

ADJ ADJACENT, ADJOINING

ADO AUTOMATIC DOOR OPENER

AF AMPERE FRAME OR AMP FUSE

AFC ABOVE FINISHED COUNTER, AUTOMATIC

FREQUENCY CONTROL, OR

AVAILABLE FAULT CURRENT

AFF ABOVE FINISHED FLOOR

AFG ABOVE FINISHED GRADE

AH AMPERE HOUR

AHJ AUTHORITY HAVING JURISDICTION

AIC AMPERE INTERRUPTING CAPACITY

ALT ALTERNATE

AMB OR A AMBIENT

AMP AMPERE

ARCH ARCHITECT

ASC AMPS SHORT CIRCUIT

AT AMPERE TRIP

ATS AUTOMATIC TRANSFER SWITCH

AUTO AUTOMATIC

AV AUDIO VISUAL

HCM HORIZONTAL CABLE MANAGER

HID HIGH INTENSITY DISCHARGE

HOA HAND-OFF-AUTOMATIC

HP HORSEPOWER

HT HEIGHT

HZ HERTZ

BAT BATTERY

BC BARE COPPER

BD BOARD

BFF BELOW FINISH FLOOR

BIL BASIC INSULATION LEVEL

BLDG BUILDING

BLK BLOCK

BPIP BOILER PLANT

INSTRUMENTATION PANEL

BRKR BREAKER

BYP BY PASS

DETAIL REFERENCE

SECTION CUT DESIGNATION

EP-101

EP-101

FIBER OPTIC BACKBONE PATHWAY "B"

84" 48" 48" 84" 48" 80" 60"

120" 60" 36" 48" 72" 48"

144" 18" 24" 26" 48" 48"

CEILING

48" 48" 18" 84"

AUDIBLE APPLIANCES (CENTERLINE)

ALARMS

ANNUNCIATOR PANELS

CLOCK OUTLETS (CENTERLINE)

CONTROLS (TOP)

EXIT SIGNS (WALL-MOUNTED, BOTTOM)

FIRE ALARM ANNUNCIATOR PANEL (DISPLAY)

FIRE ALARM BELL (EXTERIOR)

FIRE ALARM CONTROL PANEL/UNIT (DISPLAY)

INTERCOM (AFEA ONLY)

INTERCOMS (TOP)

PANELS & PANELBOARDS (TOP)

PULL STATIONS (HANDLE)

PHOTOCELLS

RECEPTACLES (BOTTOM)

RECEPTACLES (EXTERIOR)

RECEPTACLES (GARAGES) RECEPTACLES IN

EQUIPMENT ROOMS (TOP) REMOTE INDICATING

LIGHT (EQUIPMENT ROOMS) REMOTE INDICATING

LIGHT (FINISHED AREAS) SAFETY SWITCHES &

STARTERS SWITCHES (TOP)

TELEPHONE/DATA/TV OUTLETS (BOTTOM)

VISIBLE APPLIANCES (CENTERLINE)

#W = WALL PHONE, 1 CABLE, # = QUANTITY OF CABLES

TE TELECOMMUNICATIONS ENCLOSURE

VERTICAL CABLE MANAGER, 6" WIDE, WITH DOORS

COMM

PATH-A

PATH-B

LADDER TRAY, TYPE AS NOTED

SC

OF

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project NumberCONSULTANTS:

Drawing #

VA Health Care System Approval:

ARCHITECT:

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

ARCH FIRM REG. NO. 20314270 EXP. 06/30/2023

MECH FIRM REG. NO. 06253 EXP. 06/30/2024

FIRE PROTECTION ENGR

POOLE FIRE PROTECTION

19910 WEST 161ST ST.

OLATHE, KANSAS 66062

(913) 829-8690

FULLY SPRINKLERED

o n e e ig h th in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e in c h o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t th re e in c h e s o n e fo o t

No. REVISION DESCRIPTION DATE

INDUSTRIAL HYGENIST

RIVERFRONT (RSH)

1139 OLIVE ST, SUITE 300

ST. LOUIS, MO 63101

(713) 864-2900

STRUCT ENGR

STAND (SEI)

8234 ROBINSON ST

OVERLAND PARK, KS 66204

(913) 214-2169

COMMISSIONING

ES2

13401 N SANTE FE AVE

OKLAHOMA CITY, OK

(405) 528-4500

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

STAMP:

Drawing Number

Building Number

CONTROLLED UNCLASSIFED INFORMATION (CUI)

CONTROLLED UNCLASSIFED INFORMATION (CUI)

C O

N

TR

O

LL

ED

U

N C

LA

SS

IF

ED

IN

FO

R M

A

TI

O N

(C U

I)

TELECOMMUNICATION

ASPEN COMMUNICATIONS

7 KIJI-DAVA CIRCLE, STE A

PRESCOTT, AZ 86301

(928) 774-0992

MECH / ELEC / PLUMB ENGR

SPUR DESIGN

2519 MADISON AVENUE, STE 100

KANSAS CITY, MO 64108

(913) 369-7200

CHALMERS P. WYLIE VA

420 NORTH JAMES ROAD

COLUMBUS, OHIO 43219-1834FORCE PROTECT

10901 FRONT BEACH RD, UNIT 1415

PANAMA CITY BEACH, FL 32407

(502) 836-4232

PHYSICAL SECURITY

1791.19

TECHNOLOGY SYMBOLS & ABBREVIATIONS

FINAL BID DOCUMENTS

757-22-705

06/02/2023 7866

EHRM INFRASTRUCTURE

UPGRADES - TIER 2

ASPEN NER

N/A

T-000

Refer to included Telecom Narrative for additional information regarding telecommunications equipment installation.

AutoCAD SHX Text

FRONT

AutoCAD SHX Text

FRONT

AutoCAD SHX Text

FRONT

AutoCAD SHX Text

FRONT

157 SF

TELECOM

1A457

101 SF

TELECOM

1A024

103 SF

TELECOM

1A014

104 SF

TELECOM

1B006

96 SF

TELECOM

1B609

91 SF

TELECOM

1B002

120 SF

TELECOM

1A106

AREA WITHIN DASHED LINE

SERVED BY ROOM 1B002

AREA WITHIN DASHED LINE

SERVED BY ROOM 1B006

AREA WITHIN DASHED LINE

SERVED BY ROOM 1A014

AREA WITHIN DASHED LINE

SERVED BY ROOM 1A024

AREA WITHIN DASHED LINE

SERVED BY ROOM 1A106

T-300

T-300

T-300

T-301

T-300

T-301

T-301

T-300

T-300

T-300

T-301

T-301

T-301

T-300

160 WAO's

173 WAO's

248 WAO's

144 WAO's

241 WAO's

207 WAO's

287 WAO's

103 SF

TELECOM

2A018

101 SF

TELECOM

2B003

100 SF

TELECOM

2B310

91 SF

TELECOM

2B102

101 SF

TELECOM

2A004

120 SF

TELECOM

2A143

AREA WITHIN DASHED LINE

SERVED BY ROOM 2A143

AREA WITHIN DASHED LINE

SERVED BY ROOM 2A004

AREA WITHIN DASHED LINE

SERVED BY ROOM 2A018

AREA WITHIN DASHED LINE

SERVED BY ROOM 2B003

AREA WITHIN DASHED LINE

SERVED BY ROOM 2B102

T-301

T-302 1 T-302

T-302

T-303

T-302

T-301

T-302

T-302

T-303

T-302

T-302

NO CAT6A CABLING

NEEDED IN THIS AREA

220 WAO's

203 WAO's

266 WAO's

390 WAO's

178 WAO's

TECHNOLOGY GENERAL NOTES

A. CONTRACTOR SHALL INCLUDE AN ADDITIONAL 10% OF CABLE DROPS IN THEIR BID FOR ADDS

FOUND DURING INSTALLATION.

B. ADDITIONAL PATCH PANEL CAPACITY SHALL BE PROVIDED TO ACCOUNT FOR 15% GROWTH OF

ADDITIONAL CABLE DROPS.

C. ALL EXISTING DATA CABLES AND CIRCUITS MUST REMAIN IN PLACE AND OPERATIONAL UNTIL

FINAL CUT-OVER TO THE NEW CABLING.

D. EACH NEW WORK AREA OUTLET (WAO) LOCATION WILL CONSIST OF THE QUANTITY OF (2) CAT6A

CABLES. EACH CABLE WILL BE TERMINATED ON A 48-PORT CAT6A PATCH PANEL IN IT'S

DESIGNATED TR.

E. EXISTING WAO LOCATIONS SHALL BE RE-USED WHEREVER POSSIBLE.

F. PROVIDE (1) EACH SMALL DIAMETER CAT6A PATCH CORD FOR EACH NEW DATA PORT. PROVIDE

VARIOUS LENGTHS AS REQUIRED FOR A NEAT AND ORDERLY INSTALLATION, UTILIZING THE

VERTICAL AND HORIZONTAL WIRE MANAGERS AS APPLICABLE. (SEE SPECIFICATIONS)

G. NEW FIRE-RATED SLEEVES SHALL BE INSTALLED LEAVING THE TR AND IN ALL FIRE-RATED WALLS ALONG THE CABLE PATHWAYS. IN HALLWAYS NEAR TRs; 1A014, 1A106, 2B102 & 2A143

ABOVE CEILINGS ARE CROWDED WITH OTHER UTILITIES. FIRE-RATED SLEEVES CANNOT BE

INSTALLED IN THESE AREA. PHASE INSTALLATION AND REMOVAL OF CABLES.

H. EXISTING CONDUITS TO REMAIN.

I. EXISTING DATA RACK/RACKS TO REMAIN UNTIL AFTER CUT-OVER.

J. ENSURE THAT ALL GROUNDING AND BONDING IS COMPLETE. TWO SCREW BONDING LUGS NEED

TO BE INSTALLED TO BOND ALL METALLIC COMPONENTS OF THE RACK AND CABLE TRAY

SYSTEM, TO THE TELECOMMUNICATIONS SECONDARY BONDING BUSBAR.

K. AFTER CUT-OVER TO THE NEW CABLING, DEMOLISH ALL OLD DATA CABLING ALL THE WAY TO THE STATION END. ENSURE THAT ANY CABLES IN THE CEILING AREAS THAT ARE FOR SYSTEMS

OTHER THAN THE IT DATA AND TELEPHONE, ARE NOT DISTURBED. BLANK OFF ANY UNUSED

OLD DATA LOCATIONS. DEMOLISH ALL OLD PATCH PANELS AND ASSOCIATED HARDWARE. ALL

OTHER ANCILLARY RACK-MOUNTED EQUIPMENT, NOT RELATED TO IT DATA AND TELEPHONE, TO

BE RELOCATED TO A NEW RACK BY OIT PERSONNEL. FIRE-STOP ALL EXISTING SLEEVES WHERE

CABLING WAS REMOVED.

L. AFTER CUT-OVER, REMOVE ALL OLD IT FIBER OPTIC CABLING FROM THE TR ALL THE WAY BACK

TO THE SERVER DEMOLISH ALL ASSOCIATED HARDWARE AND TERMINATION EQUIPMENT.

ENSURE THAT ANY CABLING IN THE CEILING AREA THAT IS FOR OTHER SYSTEMS, IS NOT

DISTURBED.

M. ALL CATEGORY 6A STATION CABLING SHALL BE SUPPORTED USING A COMBINATION OF J-HOOKS

AND CABLE TRAYS (IF POSSIBLE) IN GENERAL PATHWAYS.

TECHNOLOGY LEGEND

WALL PHONE OUTLET CONTAINING (1) CATEGORY 6A UTP CABLE TERMINATED ONTO (1)

CATEGORY 6A RJ-45 TYPE (8P-8C) JACK. UTP CABLE JACKET COLOR TO BE BLUE.

TERMINATION SCHEME TO BE T568B.

WIRELESS ACCESS POINT CONTAINING (2) CATEGORY 6A UTP, GREEN, CABLE TERMINATED

ONTO (1) CATEGORY 6A RJ-45 TYPE (8P-8C) JACK. UTP CABLE JACKET COLOR TO BE BLUE.

TERMINATION SCHEME TO BE T568B.

4-PORT WORK AREA OUTLET FACEPLATE CONTAINING (2) CATEGORY 6A UTP CABLES

TERMINATED ONTO (2) CATEGORY 6A RJ-45 TYPE (8P-8C) JACKS. UTP CABLE JACKET COLOR

TO BE BLUE. TERMINATION SCHEME TO BE T568B.

AREA DEPICTED WITHIN THE HATCHED BOUNDARIES IS UNDER CONSTRUCTION, AND NOT

PART OF THIS CONTRACT.

WAP

W

N

1" = 40'-0"

BLDG 1 - LEVEL 1 - REFERENCE PLAN1

N

1" = 40'-0"

BLDG 1 - LEVEL 2 - REFERENCE PLAN4

OF

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project NumberCONSULTANTS:

Drawing #

VA Health Care System Approval:

ARCHITECT:

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

ARCH FIRM REG. NO. 20314270 EXP. 06/30/2023

MECH FIRM REG. NO. 06253 EXP. 06/30/2024

FIRE PROTECTION ENGR

POOLE FIRE PROTECTION

19910 WEST 161ST ST.

OLATHE, KANSAS 66062

(913) 829-8690

FULLY SPRINKLERED

o n e e ig h th in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e in c h o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t th re e in c h e s o n e fo o t

No. REVISION DESCRIPTION DATE

INDUSTRIAL HYGENIST

RIVERFRONT (RSH)

1139 OLIVE ST, SUITE 300

ST. LOUIS, MO 63101

(713) 864-2900

STRUCT ENGR

STAND (SEI)

8234 ROBINSON ST

OVERLAND PARK, KS 66204

(913) 214-2169

COMMISSIONING

ES2

13401 N SANTE FE AVE

OKLAHOMA CITY, OK

(405) 528-4500

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

STAMP:

Drawing Number

Building Number

CONTROLLED UNCLASSIFED INFORMATION (CUI)

CONTROLLED UNCLASSIFED INFORMATION (CUI)

C O

N

TR

O

LL

ED

U

N C

LA

SS

IF

ED

IN

FO

R M

A

TI

O N

(C U

I)

TELECOMMUNICATION

ASPEN COMMUNICATIONS

7 KIJI-DAVA CIRCLE, STE A

PRESCOTT, AZ 86301

(928) 774-0992

MECH / ELEC / PLUMB ENGR

SPUR DESIGN

2519 MADISON AVENUE, STE 100

KANSAS CITY, MO 64108

(913) 369-7200

CHALMERS P. WYLIE VA

420 NORTH JAMES ROAD

COLUMBUS, OHIO 43219-1834FORCE PROTECT

10901 FRONT BEACH RD, UNIT 1415

PANAMA CITY BEACH, FL 32407

(502) 836-4232

PHYSICAL SECURITY

1791.19

TECHNOLOGY FLOOR PLANS - BLDG 1A -

LVL 1 & 2

FINAL BID DOCUMENTS

757-22-705

06/02/2023 7867

EHRM INFRASTRUCTURE

UPGRADES - TIER 2

ASPEN NER

1A

T-100

100 SF

TELECOM

3A004

101 SF

TELECOM

3A015

116 SF

TELECOM

3A063

AREA WITHIN DASHED LINE

SERVED BY ROOM 3A063

AREA WITHIN DASHED LINE

SERVED BY ROOM 3A004

AREA WITHIN DASHED LINE

SERVED BY ROOM 3A015

AREA WITHIN DASHED LINE

SERVED BY ROOM 2B003

STUB 1" CONDUITS TO 2ND

FLOOR BELOW

AREA WITHIN DASHED LINE

SERVED BY ROOM 1B002

STUB 1" CONDUITS TO 1ST

FLOOR BELOW

T-303

T-303

T-303

T-303

T-303

T-303

204 WAO's

177 WAO's

286 WAO's

DN

119 SF

TELECOM

4A041

810 SF

SERVER/MAIN

TELECOM

4A201

95 SF

ELEC ROOM

4A012

AREA WITHIN DASHED LINE

SERVED BY ROOM 4A041

AREA WITHIN DASHED LINE

SERVED BY ROOM 4A201

T-304

T-304

T-305

T-305

T-305

188 WAO's

155 WAO's

105 SF

TELECOM

T-304

T-304

24 WAO's

56 SF

TELECOM

T-304 8T-304

46 WAO's

TECHNOLOGY GENERAL NOTES

A. CONTRACTOR SHALL INCLUDE AN ADDITIONAL 10% OF CABLE DROPS IN THEIR BID FOR ADDS

FOUND DURING INSTALLATION.

B. ADDITIONAL PATCH PANEL CAPACITY SHALL BE PROVIDED TO ACCOUNT FOR 15% GROWTH OF

ADDITIONAL CABLE DROPS.

C. ALL EXISTING DATA CABLES AND CIRCUITS MUST REMAIN IN PLACE AND OPERATIONAL UNTIL

FINAL CUT-OVER TO THE NEW CABLING.

D. EACH NEW WORK AREA OUTLET (WAO) LOCATION WILL CONSIST OF THE QUANTITY OF (2) CAT6A

CABLES. EACH CABLE WILL BE TERMINATED ON A 48-PORT CAT6A PATCH PANEL IN IT'S

DESIGNATED TR.

E. EXISTING WAO LOCATIONS SHALL BE RE-USED WHEREVER POSSIBLE.

F. PROVIDE (1) EACH SMALL DIAMETER CAT6A PATCH CORD FOR EACH NEW DATA PORT. PROVIDE

VARIOUS LENGTHS AS REQUIRED FOR A NEAT AND ORDERLY INSTALLATION, UTILIZING THE

VERTICAL AND HORIZONTAL WIRE MANAGERS AS APPLICABLE. (SEE SPECIFICATIONS)

G. NEW FIRE-RATED SLEEVES SHALL BE INSTALLED LEAVING THE TR AND IN ALL FIRE-RATED WALLS ALONG THE CABLE PATHWAYS. IN HALLWAYS NEAR TRs; 1A014, 1A106, 2B102 & 2A143

ABOVE CEILINGS ARE CROWDED WITH OTHER UTILITIES. FIRE-RATED SLEEVES CANNOT BE

INSTALLED IN THESE AREA. PHASE INSTALLATION AND REMOVAL OF CABLES.

H. EXISTING CONDUITS TO REMAIN.

I. EXISTING DATA RACK/RACKS TO REMAIN UNTIL AFTER CUT-OVER.

J. ENSURE THAT ALL GROUNDING AND BONDING IS COMPLETE. TWO SCREW BONDING LUGS NEED

TO BE INSTALLED TO BOND ALL METALLIC COMPONENTS OF THE RACK AND CABLE TRAY

SYSTEM, TO THE TELECOMMUNICATIONS SECONDARY BONDING BUSBAR.

K. AFTER CUT-OVER TO THE NEW CABLING, DEMOLISH ALL OLD DATA CABLING ALL THE WAY TO THE STATION END. ENSURE THAT ANY CABLES IN THE CEILING AREAS THAT ARE FOR SYSTEMS

OTHER THAN THE IT DATA AND TELEPHONE, ARE NOT DISTURBED. BLANK OFF ANY UNUSED

OLD DATA LOCATIONS. DEMOLISH ALL OLD PATCH PANELS AND ASSOCIATED HARDWARE. ALL

OTHER ANCILLARY RACK-MOUNTED EQUIPMENT, NOT RELATED TO IT DATA AND TELEPHONE, TO

BE RELOCATED TO A NEW RACK BY OIT PERSONNEL. FIRE-STOP ALL EXISTING SLEEVES WHERE

CABLING WAS REMOVED.

L. AFTER CUT-OVER, REMOVE ALL OLD IT FIBER OPTIC CABLING FROM THE TR ALL THE WAY BACK

TO THE SERVER DEMOLISH ALL ASSOCIATED HARDWARE AND TERMINATION EQUIPMENT.

ENSURE THAT ANY CABLING IN THE CEILING AREA THAT IS FOR OTHER SYSTEMS, IS NOT

DISTURBED.

M. ALL CATEGORY 6A STATION CABLING SHALL BE SUPPORTED USING A COMBINATION OF J-HOOKS

AND CABLE TRAYS (IF POSSIBLE) IN GENERAL PATHWAYS.

TECHNOLOGY LEGEND

WALL PHONE OUTLET CONTAINING (1) CATEGORY 6A UTP CABLE TERMINATED ONTO (1)

CATEGORY 6A RJ-45 TYPE (8P-8C) JACK. UTP CABLE JACKET COLOR TO BE BLUE.

TERMINATION SCHEME TO BE T568B.

WIRELESS ACCESS POINT CONTAINING (2) CATEGORY 6A UTP, GREEN, CABLE TERMINATED

ONTO (1) CATEGORY 6A RJ-45 TYPE (8P-8C) JACK. UTP CABLE JACKET COLOR TO BE BLUE.

TERMINATION SCHEME TO BE T568B.

4-PORT WORK AREA OUTLET FACEPLATE CONTAINING (2) CATEGORY 6A UTP CABLES

TERMINATED ONTO (2) CATEGORY 6A RJ-45 TYPE (8P-8C) JACKS. UTP CABLE JACKET COLOR

TO BE BLUE. TERMINATION SCHEME TO BE T568B.

AREA DEPICTED WITHIN THE HATCHED BOUNDARIES IS UNDER CONSTRUCTION, AND NOT

PART OF THIS CONTRACT.

WAP

W

N

1" = 40'-0"

BLDG 1 - LEVEL 3 - REFERENCE PLAN1

N

1" = 40'-0"

BLDG 1 - LEVEL 4 - REFERENCE PLAN2

N

1" = 40'-0"

BOILER PLANT - LEVEL 1 - REFERENCE PLAN3

1" = 40'-0"

ENGINEERING BUILDING - LEVEL 1 - REFERENCE PLAN4

N

OF

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project NumberCONSULTANTS:

Drawing #

VA Health Care System Approval:

ARCHITECT:

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

ARCH FIRM REG. NO. 20314270 EXP. 06/30/2023

MECH FIRM REG. NO. 06253 EXP. 06/30/2024

FIRE PROTECTION ENGR

POOLE FIRE PROTECTION

19910 WEST 161ST ST.

OLATHE, KANSAS 66062

(913) 829-8690

FULLY SPRINKLERED

o n e e ig h th in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e in c h o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t th re e in c h e s o n e fo o t

No. REVISION DESCRIPTION DATE

INDUSTRIAL HYGENIST

RIVERFRONT (RSH)

1139 OLIVE ST, SUITE 300

ST. LOUIS, MO 63101

(713) 864-2900

STRUCT ENGR

STAND (SEI)

8234 ROBINSON ST

OVERLAND PARK, KS 66204

(913) 214-2169

COMMISSIONING

ES2

13401 N SANTE FE AVE

OKLAHOMA CITY, OK

(405) 528-4500

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

STAMP:

Drawing Number

Building Number

CONTROLLED UNCLASSIFED INFORMATION (CUI)

CONTROLLED UNCLASSIFED INFORMATION (CUI)

C O

N

TR

O

LL

ED

U

N C

LA

SS

IF

ED

IN

FO

R M

A

TI

O N

(C U

I)

TELECOMMUNICATION

ASPEN COMMUNICATIONS

7 KIJI-DAVA CIRCLE, STE A

PRESCOTT, AZ 86301

(928) 774-0992

MECH / ELEC / PLUMB ENGR

SPUR DESIGN

2519 MADISON AVENUE, STE 100

KANSAS CITY, MO 64108

(913) 369-7200

CHALMERS P. WYLIE VA

420 NORTH JAMES ROAD

COLUMBUS, OHIO 43219-1834FORCE PROTECT

10901 FRONT BEACH RD, UNIT 1415

PANAMA CITY BEACH, FL 32407

(502) 836-4232

PHYSICAL SECURITY

1791.19

TECHNOLOGY FLOOR PLANS - BLDG 1A -

LVL 3 & 4, BLDG ENG & EC

FINAL BID DOCUMENTS

757-22-705

06/02/2023 7868

EHRM INFRASTRUCTURE

UPGRADES - TIER 2

ASPEN NER

1A, ENG, EC

T-101

157 SF

1A457

'-8

1/ 2"

12'-5 1/2"

TR

101 SF

1A024

8'- 3 1

/2"

12'-2"

TR

CONDUITS

103 SF

1A014

8'-9"

'-8

1/ 2"

TR

T-MOBILE

EQUIPMENT

FOTP

157 SF

1A457

1A

TR

3 3

3'-0"3'-0"

3'- 0"

3'- 0"

101 SF

1A024 1A

4TR

CONDUIT

CHASE 3

3'-0"

1'- 0"

3'-0"

3'-0"

103 SF

1A014

1A014

TR

T-MOBILE

EQUIPMENT

FOTP

3 3

4 4

PHASE NEW CABLE. PULL IN CABLES FOR ALL

'ACTIVE' LINES FIRST. TERMINATE, TEST, LABEL,

CUT-OVER. REMOVE OLD 'ACTIVE' CABLES TO

MAKE ROOM FOR ADDITIONAL CABLES.

1'-0"3'-0"

3'- 0"

3'- 0"

38-123C-2 38-123C-1

GFGI DATA SWITCHES

GFGI DATA SWITCHES

GFGI DATA SWITCHES

GFGI DATA SWITCHES

GFGI DATA SWITCHES

SPECIFIED BY DIVISION 26

CFCI RACK-MOUNT UPS

SPECIFIED BY DIVISION 26

CFCI RACK-MOUNT UPS

GFGI DATA SWITCHES

GFGI DATA SWITCHES

TR 1A014 (LOOKING NORTH)

B C D E F G H

A

I J K L

M N O P Q R

GFGI DATA SWITCHES

3 4

4 3

GFGI DATA SWITCHES

GFGI DATA SWITCHES

GFGI DATA SWITCHES

GFGI DATA SWITCHES

GFGI DATA SWITCHES

SPECIFIED BY DIVISION 26

CFCI RACK-MOUNT UPS

GFGI DATA SWITCHES

GFGI DATA SWITCHES

B C D E F G H

A

I J K L

TR 1A024 (LOOKING EAST)

SPECIFIED BY DIVISION 26

CFCI RACK-MOUNT UPS

M N O P Q R

GFGI DATA SWITCHES

3 4

4 3

GFGI DATA SWITCHES

GFGI DATA SWITCHES

GFGI DATA SWITCHES

GFGI DATA SWITCHES

GFGI DATA SWITCHES

SPECIFIED BY DIVISION 26

CFCI RACK-MOUNT UPS

SPECIFIED BY DIVISION 26

CFCI RACK-MOUNT UPS

GFGI DATA SWITCHES

GFGI DATA SWITCHES

TR 1A457 (LOOKING NORTH)

B C D E F G H

A

I J K L

M N O P Q R

GFGI DATA SWITCHES

3 4

4 3

TECHNOLOGY KEYNOTES

DEMO EXISTING ITEM AFTER SYSTEMS CUTOVER.

LEAVE EXISTING ITEM IN PLACE AFTER SYSTEMS CUTOVER UNLESS OTHERWISE DIRECTED (UOD).

INSTALL TELECOMMUNICATIONS CHANNEL RACK, 7'H x 24"W x 30"D, 45RU, 4-POST, OPEN FRAME TYPE.

INSTALL VERTICAL CABLE MANAGER, 6"W x 6"D, W/DOOR.

INSTALL WIRE-MESH (WIRE BASKET) CABLE TRAY - 18"W x 4"D (TYPICAL).

INSTALL TELECOMMUNICATIONS ENCLOSURE, 48" H x 24"W x 30"D, 26RU, WALL-MOUNT CABINET

INSTALL WALL-MOUNTED CABLE SUPPORTS (J-HOOKS) AT 3', OR LESS, INTERVALS

INSTALL VERTICAL RBB IN REAR OF NETWORK CHANNEL RACK.

INSTALL 48 PORT ANGLED MODULAR PATCH PANELS WITH REAR CABLE SUPPORT.

INSTALL 1 RU OR 2 RU FIBER OPTIC TERMINATION PANEL, 144 STRAND CAPACITY AT TOP OF ONE RACK

PER TR.

INSTALL 1 RU FLAT HORIZONTAL CABLE MANAGERS BETWEEN ALL VA PROVIDED SWITCHES.

INSTALL 2 RU FLAT BLANK PANELS BETWEEN PATCH PANELS AND SWITCHES.

CHANNEL RACK CLEARANCE.

TECHNOLOGY GENERAL PLAN NOTES

1. CONTRACTOR TO PROVIDE PROTECTION TO ALL EQUIPMENT IN THE EXISTING RACKS WHILE TR

CONSTRUCTION IS OCCURRING.

2. ALL EXISTING DATA CABLES AND CIRCUITS MUST REMAIN IN PLACE AND OPERATIONAL UNTIL FINAL

CUT-OVER TO THE NEW CABLING SYSTEM.

3. REMOVE ALL EXISTING CABLE RUNWAY. TEMPORARILY SUPPORT EXISTING CABLES DURING TR

CONSTRUCTION IN ORDER TO KEEP EXISTING DATA AND OTHER SYSTEMS OPERATIONAL.

4. EXISTING DATA RACK/RACKS TO REMAIN UNTIL AFTER CUT-OVER.

5. EXISTING CONDUITS TO REMAIN.

6. NEW FIRE-RATED CONDUIT SLEEVES SHALL BE INSTALLED EXITING THE TR AND IN ALL FIRE-RATED WALLS ALONG THE CABLE PATHWAYS. CABLING PASSING THROUGH SLLEVES SHOULD NOT EXCEED

40% FILL RATIO.

7. INSTALL A RACK-MOUNTED HORIZONTAL BUSBAR AT THE TOP OF EACH RACK ON THE BACK RAIL.

8. ENSURE THAT ALL GROUNDING AND BONDING IS COMPLETE. TWO SCREW BONDING LUGS NEED TO BE INSTALLED TO BOND ALL METALLIC COMPONENTS OF THE RACK AND CABLE TRAY SYSTEM, TO THE

TELECOMMUNICATIONS SECONDARY BONDING BUSBAR.

9. BUILD AND POPULATE THE NEW CHANNEL RACKS. AFTER CUT-OVER, REMOVE ALL OLD DATA RACKS

AND MOVE CHANNEL RACKS INTO PLACE AS SHOWN ON TR KEYNOTES. ENSURE THAT ALL OTHER

EXISTING SYSTEMS IN THE OLD RACKS ARE MOVED TO THE NEW RACKS AND REMAIN OPERATIONAL.

COORDINATE WITH OIT AND FACILITIES. EQUIPMENT SHOULD BE SHARED BETWEEN THE RACKS, THERE SHOULD NOT BE PASSIVE RACKS IN TR's.

10. AFTER CUT-OVER TO THE NEW CABLING SYSTEM, DEMOLISH ALL OLD DATA CABLING ALL THE WAY TO THE WAO END. ENSURE THAT ANY CABLES IN THE CEILING AREAS THAT ARE FOR SYSTEMS OTHER

THAN THE IT DATA CABLES ARE NOT DISTURBED. DEMOLISH ALL OLD PATCH PANELS AND

ASSOCIATED HARDWARE. ALL OTHER ANCILLARY RACK-MOUNTED EQUIPMENT, NOT RELATED TO IT DATA, TO BE RELOCATED TO A NEW CHANNEL RACK BY OIT PERSONNEL. FIRE-STOP ALL EXISTING

CONDUIT SLEEVES WHERE CABLING WAS REMOVED.

11. PROVIDE 18" W x 4"D WIRE BASKET TYPE CABLE TRAY. MOUNT ALL NEW CABLE TRAY APPROXIMATELY 6" ABOVE CHANNEL RACK HEIGHT. SUPPORT TRAY USING VERTICAL THREADED ROD AND ASSOCIATED HARDWARE. USE CABLE TRAY EXITS AND DROP OUTS FOR SMOOTH TRANSITION OF CABLE OUT OF

THE CABLE TRAYS AND INTO THE CHANNEL RACKS FOR TERMINATION.

12. THERE ARE NUMEROUS ADDITIONAL CABLES IN THE TR FOR OTHER SERVICES SUCH AS WIRELESS

ACCESS POINTS, CAMERAS, FIRE ALARM, ACCESS CONTROL, MATV, NURSE CALL AND BIOMED.

CONTRACTOR NEEDS TO BE DILIGENT TO DEMOLISH ONLY WHAT IS BEING REPLACED AND ANY OTHER ITEMS SPECIFICALLY NOTED. ENSURE THAT ALL OTHER SERVICES IN THE TR REMAIN IN PLACE AND

AND OPERATIONAL.

13. ENSURE PROPER FIRE STOPPING (CAULKING, ETC.) IN ALL EXISTING AND ABANDONED CONDUIT

PATHWAYS/SLEEVES.

14. GROUNDING/BONDING: INSTALL RBB IN ALL RACKS AND CABINETS. IN TRs; BOND ALL RBBs AND CABLE TRAY TO SBB. IN MCR; BOND ALL RBBs AND CABLE TRAY TO MCR PBB/SBB

38-123C-2 38-123C-1

GFGI DATA SWITCHES

GFGI DATA SWITCHES

GFGI DATA SWITCHES

GFGI DATA SWITCHES

GFGI DATA SWITCHES

SPECIFIED BY DIVISION 26

CFCI RACK-MOUNT UPS

SPECIFIED BY DIVISION 26

CFCI RACK-MOUNT UPS

GFGI DATA SWITCHES

GFGI DATA SWITCHES

TR 1A106 (LOOKING WEST)

B C D E F G H

A

I J K L

M N O P Q R

GFGI DATA SWITCHES

3 4

4 3

120 SF

1A106

13'-3 1/2"

9'- 0"

TR

WALL-MOUNT

RACK

120 SF

1A106

1A

TR

WALL-MOUNT

RACK

CAT6A CABLES ENTER 1A106 FROM

1A110. INSTALL (1) 4" FIRE RATED

SLEEVE IF NEEDED.

1'-

1/ 4"

3'- 0"

3'-0"

3'-0"

N

1/4" = 1'-0"

BLDG 1 - LEVEL 1 - 1A457 - DEMO10

N

1/4" = 1'-0"

BLDG 1 - LEVEL 1 - 1A024 - DEMO4

N

1/4" = 1'-0"

BLDG 1 - LEVEL 1 - 1A014 - DEMO1

N

1/4" = 1'-0"

BLDG 1 - LEVEL 1 - 1A457 - NEW11

N

1/4" = 1'-0"

BLDG 1 - LEVEL 1 - 1A024 - NEW5

N

1/4" = 1'-0"

BLDG 1 - LEVEL 1 - 1A014 - NEW2

N

1/4" = 1'-0"

BLDG 1 - LEVEL 1 - 1A014 - RACK ELEVATION3

N

1/4" = 1'-0"

BLDG 1 - LEVEL 1 - 1A024 - RACK ELEVATION6

N

1/4" = 1'-0"

BLDG 1 - LEVEL 1 - 1A457 - RACK ELEVATION12

N

1/4" = 1'-0"

BLDG 1 - LEVEL 1 - 1A106 - RACK ELEVATION9

N

1/4" = 1'-0"

BLDG 1 - LEVEL 1 - 1A106 - DEMO7

N

1/4" = 1'-0"

BLDG 1 - LEVEL 1 - 1A106 - NEW8

OF

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project NumberCONSULTANTS:

Drawing #

VA Health Care System Approval:

ARCHITECT:

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

ARCH FIRM REG. NO. 20314270 EXP. 06/30/2023

MECH FIRM REG. NO. 06253 EXP. 06/30/2024

FIRE PROTECTION ENGR

POOLE FIRE PROTECTION

19910 WEST 161ST ST.

OLATHE, KANSAS 66062

(913) 829-8690

FULLY SPRINKLERED

o n e e ig h th in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e in c h o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t th re e in c h e s o n e fo o t

No. REVISION DESCRIPTION DATE

INDUSTRIAL HYGENIST

RIVERFRONT (RSH)

1139 OLIVE ST, SUITE 300

ST. LOUIS, MO 63101

(713) 864-2900

STRUCT ENGR

STAND (SEI)

8234 ROBINSON ST

OVERLAND PARK, KS 66204

(913) 214-2169

COMMISSIONING

ES2

13401 N SANTE FE AVE

OKLAHOMA CITY, OK

(405) 528-4500

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

STAMP:

Drawing Number

Building Number

CONTROLLED UNCLASSIFED INFORMATION (CUI)

CONTROLLED UNCLASSIFED INFORMATION (CUI)

C O

N

TR

O

LL

ED

U

N C

LA

SS

IF

ED

IN

FO

R M

A

TI

O N

(C U

I)

TELECOMMUNICATION

ASPEN COMMUNICATIONS

7 KIJI-DAVA CIRCLE, STE A

PRESCOTT, AZ 86301

(928) 774-0992

MECH / ELEC / PLUMB ENGR

SPUR DESIGN

2519 MADISON AVENUE, STE 100

KANSAS CITY, MO 64108

(913) 369-7200

CHALMERS P. WYLIE VA

420 NORTH JAMES ROAD

COLUMBUS, OHIO 43219-1834FORCE PROTECT

10901 FRONT BEACH RD, UNIT 1415

PANAMA CITY BEACH, FL 32407

(502) 836-4232

PHYSICAL SECURITY

1791.19

TECHNOLOGY ENLARGED PLANS - BLDG 1A

- LVL 1

FINAL BID DOCUMENTS

757-22-705

06/02/2023 7869

EHRM INFRASTRUCTURE

UPGRADES - TIER 2

ASPEN NER

1A

T-300

96 SF

1B609

TR

FO

TP

EL

EC

TR

IC

AL

PA

NE

L

96 SF

1B609

1B

TR

FO

TP

EL

EC

TR

IC

AL

PA

NE

L

1'-0"

3'- 0"

3'-0"

3'-0"

38-123C-2 38-123C-1

GFGI DATA SWITCHES

GFGI DATA SWITCHES

GFGI DATA SWITCHES

GFGI DATA SWITCHES

GFGI DATA SWITCHES

SPECIFIED BY DIVISION 26

CFCI RACK-MOUNT UPS

SPECIFIED BY DIVISION 26

CFCI RACK-MOUNT UPS

GFGI DATA SWITCHES

GFGI DATA SWITCHES

TR 1B609 (LOOKING EAST)

B C D E F G H

A

I J K L

M N O P Q R

GFGI DATA SWITCHES

3 4

4 3

91 SF

1B002

1B

TR

GROUNDING

BAR

4 4

PHASE CABLE INSTALL

INSTALL (1) 4"

SLEEVES FOR CAT6A

3'-0"

1'-10 1/4"

3'- 0"

3'- 0"

91 SF

1B002

TR

GROUNDING

BAR

104 SF

1B006

'-3

1/ 2"

8'-5 1/2"

TR

GROUNDING

BAR

T-MOBILE

FO

TP

W

AL

L

MO

UN

T

RA

CK

104 SF

1B006

1B

6 TR

GROUNDING

BAR

T-MOBILE

FO

TP

W

AL

L

MO

UN

T

RA

CK

4 4 4

PHASE CABLE INSTALL

INSTALL (1) 4"

SLEEVES FOR CAT6A

3'-0" 1'-0"

3'- 0"

3'- 0"

38-123C-2 38-123C-1

GFGI DATA SWITCHES

GFGI DATA SWITCHES

GFGI DATA SWITCHES

GFGI DATA SWITCHES

GFGI DATA SWITCHES

SPECIFIED BY DIVISION 26

CFCI RACK-MOUNT UPS

SPECIFIED BY DIVISION 26

CFCI RACK-MOUNT UPS

GFGI DATA SWITCHES

GFGI DATA SWITCHES

TR 1B006 (LOOKING SOUTH)

B C D E F G H

A

I J K L

M N O P Q R

GFGI DATA SWITCHES

3 4

4 3

38-123C-2 38-123C-1

GFGI DATA SWITCHES

GFGI DATA SWITCHES

GFGI DATA SWITCHES

GFGI DATA SWITCHES

GFGI DATA SWITCHES

SPECIFIED BY DIVISION 26

CFCI RACK-MOUNT UPS

SPECIFIED BY DIVISION 26

CFCI RACK-MOUNT UPS

GFGI DATA SWITCHES

GFGI DATA SWITCHES

TR 1B002 (LOOKING SOUTH)

B C D E F G H

A

I J K L

M N O P Q R

GFGI DATA SWITCHES

3 4

4 3

101 SF

2B004

12'-1 1/2"

8'- 3 1

/2"

TR

101 SF

2B004

2B

4 TR

3'-0"

1'- 0"

3'-0"

3'-0"

38-123C-2 38-123C-1

GFGI DATA SWITCHES

GFGI DATA SWITCHES

GFGI DATA SWITCHES

GFGI DATA SWITCHES

GFGI DATA SWITCHES

SPECIFIED BY DIVISION 26

CFCI RACK-MOUNT UPS

SPECIFIED BY DIVISION 26

CFCI RACK-MOUNT UPS

GFGI DATA SWITCHES

GFGI DATA SWITCHES

TR 2B004 (LOOKING EAST)

B C D E F G H

A

I J K L

M N O P Q R

GFGI DATA SWITCHES

3 4

4 3

TECHNOLOGY KEYNOTES

DEMO EXISTING ITEM AFTER SYSTEMS CUTOVER.

LEAVE EXISTING ITEM IN PLACE AFTER SYSTEMS CUTOVER UNLESS OTHERWISE DIRECTED (UOD).

INSTALL TELECOMMUNICATIONS CHANNEL RACK, 7'H x 24"W x 30"D, 45RU, 4-POST, OPEN FRAME TYPE.

INSTALL VERTICAL CABLE MANAGER, 6"W x 6"D, W/DOOR.

INSTALL WIRE-MESH (WIRE BASKET) CABLE TRAY - 18"W x 4"D (TYPICAL).

INSTALL TELECOMMUNICATIONS ENCLOSURE, 48" H x 24"W x 30"D, 26RU, WALL-MOUNT CABINET

INSTALL WALL-MOUNTED CABLE SUPPORTS (J-HOOKS) AT 3', OR LESS, INTERVALS

INSTALL VERTICAL RBB IN REAR OF NETWORK CHANNEL RACK.

INSTALL 48 PORT ANGLED MODULAR PATCH PANELS WITH REAR CABLE SUPPORT.

INSTALL 1 RU OR 2 RU FIBER OPTIC TERMINATION PANEL, 144 STRAND CAPACITY AT TOP OF ONE RACK

PER TR.

INSTALL 1 RU FLAT HORIZONTAL CABLE MANAGERS BETWEEN ALL VA PROVIDED SWITCHES.

INSTALL 2 RU FLAT BLANK PANELS BETWEEN PATCH PANELS AND SWITCHES.

CHANNEL RACK CLEARANCE.

TECHNOLOGY GENERAL PLAN NOTES

1. CONTRACTOR TO PROVIDE PROTECTION TO ALL EQUIPMENT IN THE EXISTING RACKS WHILE TR

CONSTRUCTION IS OCCURRING.

2. ALL EXISTING DATA CABLES AND CIRCUITS MUST REMAIN IN PLACE AND OPERATIONAL UNTIL FINAL

CUT-OVER TO THE NEW CABLING SYSTEM.

3. REMOVE ALL EXISTING CABLE RUNWAY. TEMPORARILY SUPPORT EXISTING CABLES DURING TR

CONSTRUCTION IN ORDER TO KEEP EXISTING DATA AND OTHER SYSTEMS OPERATIONAL.

4. EXISTING DATA RACK/RACKS TO REMAIN UNTIL AFTER CUT-OVER.

5. EXISTING CONDUITS TO REMAIN.

6. NEW FIRE-RATED CONDUIT SLEEVES SHALL BE INSTALLED EXITING THE TR AND IN ALL FIRE-RATED WALLS ALONG THE CABLE PATHWAYS. CABLING PASSING THROUGH SLLEVES SHOULD NOT EXCEED

40% FILL RATIO.

7. INSTALL A RACK-MOUNTED HORIZONTAL BUSBAR AT THE TOP OF EACH RACK ON THE BACK RAIL.

8. ENSURE THAT ALL GROUNDING AND BONDING IS COMPLETE. TWO SCREW BONDING LUGS NEED TO BE INSTALLED TO BOND ALL METALLIC COMPONENTS OF THE RACK AND CABLE TRAY SYSTEM, TO THE

TELECOMMUNICATIONS SECONDARY BONDING BUSBAR.

9. BUILD AND POPULATE THE NEW CHANNEL RACKS. AFTER CUT-OVER, REMOVE ALL OLD DATA RACKS

AND MOVE CHANNEL RACKS INTO PLACE AS SHOWN ON TR KEYNOTES. ENSURE THAT ALL OTHER

EXISTING SYSTEMS IN THE OLD RACKS ARE MOVED TO THE NEW RACKS AND REMAIN OPERATIONAL.

COORDINATE WITH OIT AND FACILITIES. EQUIPMENT SHOULD BE SHARED BETWEEN THE RACKS, THERE SHOULD NOT BE PASSIVE RACKS IN TR's.

10. AFTER CUT-OVER TO THE NEW CABLING SYSTEM, DEMOLISH ALL OLD DATA CABLING ALL THE WAY TO THE WAO END. ENSURE THAT ANY CABLES IN THE CEILING AREAS THAT ARE FOR SYSTEMS OTHER

THAN THE IT DATA CABLES ARE NOT DISTURBED. DEMOLISH ALL OLD PATCH PANELS AND

ASSOCIATED HARDWARE. ALL OTHER ANCILLARY RACK-MOUNTED EQUIPMENT, NOT RELATED TO IT DATA, TO BE RELOCATED TO A NEW CHANNEL RACK BY OIT PERSONNEL. FIRE-STOP ALL EXISTING

CONDUIT SLEEVES WHERE CABLING WAS REMOVED.

11. PROVIDE 18" W x 4"D WIRE BASKET TYPE CABLE TRAY. MOUNT ALL NEW CABLE TRAY APPROXIMATELY 6" ABOVE CHANNEL RACK HEIGHT. SUPPORT TRAY USING VERTICAL THREADED ROD AND ASSOCIATED HARDWARE. USE CABLE TRAY EXITS AND DROP OUTS FOR SMOOTH TRANSITION OF CABLE OUT OF

THE CABLE TRAYS AND INTO THE CHANNEL RACKS FOR TERMINATION.

12. THERE ARE NUMEROUS ADDITIONAL CABLES IN THE TR FOR OTHER SERVICES SUCH AS WIRELESS

ACCESS POINTS, CAMERAS, FIRE ALARM, ACCESS CONTROL, MATV, NURSE CALL AND BIOMED.

CONTRACTOR NEEDS TO BE DILIGENT TO DEMOLISH ONLY WHAT IS BEING REPLACED AND ANY OTHER ITEMS SPECIFICALLY NOTED. ENSURE THAT ALL OTHER SERVICES IN THE TR REMAIN IN PLACE AND

AND OPERATIONAL.

13. ENSURE PROPER FIRE STOPPING (CAULKING, ETC.) IN ALL EXISTING AND ABANDONED CONDUIT

PATHWAYS/SLEEVES.

14. GROUNDING/BONDING: INSTALL RBB IN ALL RACKS AND CABINETS. IN TRs; BOND ALL RBBs AND CABLE TRAY TO SBB. IN MCR; BOND ALL RBBs AND CABLE TRAY TO MCR PBB/SBB

OF

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project NumberCONSULTANTS:

Drawing #

VA Health Care System Approval:

ARCHITECT:

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

ARCH FIRM REG. NO. 20314270 EXP. 06/30/2023

MECH FIRM REG. NO. 06253 EXP. 06/30/2024

FIRE PROTECTION ENGR

POOLE FIRE PROTECTION

19910 WEST 161ST ST.

OLATHE, KANSAS 66062

(913) 829-8690

FULLY SPRINKLERED

o n e e ig h th in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e in c h o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t th re e in c h e s o n e fo o t

No. REVISION DESCRIPTION DATE

INDUSTRIAL HYGENIST

RIVERFRONT (RSH)

1139 OLIVE ST, SUITE 300

ST. LOUIS, MO 63101

(713) 864-2900

STRUCT ENGR

STAND (SEI)

8234 ROBINSON ST

OVERLAND PARK, KS 66204

(913) 214-2169

COMMISSIONING

ES2

13401 N SANTE FE AVE

OKLAHOMA CITY, OK

(405) 528-4500

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

STAMP:

Drawing Number

Building Number

CONTROLLED UNCLASSIFED INFORMATION (CUI)

CONTROLLED UNCLASSIFED INFORMATION (CUI)

C O

N

TR

O

LL

ED

U

N C

LA

SS

IF

ED

IN

FO

R M

A

TI

O N

(C U

I)

TELECOMMUNICATION

ASPEN COMMUNICATIONS

7 KIJI-DAVA CIRCLE, STE A

PRESCOTT, AZ 86301

(928) 774-0992

MECH / ELEC / PLUMB ENGR

SPUR DESIGN

2519 MADISON AVENUE, STE 100

KANSAS CITY, MO 64108

(913) 369-7200

CHALMERS P. WYLIE VA

420 NORTH JAMES ROAD

COLUMBUS, OHIO 43219-1834FORCE PROTECT

10901 FRONT BEACH RD, UNIT 1415

PANAMA CITY BEACH, FL 32407

(502) 836-4232

PHYSICAL SECURITY

1791.19

TECHNOLOGY ENLARGED PLANS - BLDG 1A

- LVL 1 & 2

FINAL BID DOCUMENTS

757-22-705

06/02/2023 7870

EHRM INFRASTRUCTURE

UPGRADES - TIER 2

ASPEN NER

1A

T-301

N

1/4" = 1'-0"

BLDG 1 - LEVEL 1 - 1B609 - DEMO

N

1/4" = 1'-0"

BLDG 1 - LEVEL 1 - 1B609 - NEW

N

1/4" = 1'-0"

BLDG 1 - LEVEL 1 - 1B609 - RACK ELEVATION

N

1/4" = 1'-0"

BLDG 1 - LEVEL 1 - 1B002 - NEW2

N

1/4" = 1'-0"

BLDG 1 - LEVEL 1 - 1B002 - DEMO1

N

1/4" = 1'-0"

BLDG 1 - LEVEL 1 - 1B006 - DEMO4

N

1/4" = 1'-0"

BLDG 1 - LEVEL 1 - 1B006 - NEW

N

1/4" = 1'-0"

BLDG 1 - LEVEL 1 - 1B006 - RACK ELEVATION

N

1/4" = 1'-0"

BLDG 1 - LEVEL 1 - 1B002 - RACK ELEVATION3

N

1/4" = 1'-0"

BLDG 1 - LEVEL 2 - 2A004 - DEMO

N

1/4" = 1'-0"

BLDG 1 - LEVEL 2 - 2A004 - NEW

N

1/4" = 1'-0"

BLDG 1 - LEVEL 2 - 2A004 - RACK ELEVATION

101 SF

2B003

'-1

0 1 /2"

8'-6"

TR

SBBCONDUITS

WALL

MOUNT

RACK

101 SF

2B003

2B

3 TR

PHASE CABLE INSTALL

INSTALL (2) 4" SLEEVES AND SADDLE

OR J-HOOK FOR CAT6A. KEEP CABLE

OFF WATER PIPES.

1'-0"

3'-0"

3'- 0"

3'- 0"

SB

B

CO

ND

UI

TS

91 SF

2B102

8'-11"

'-6

1/ 2"

TR

SBB CONDUITS

FP

91 SF

TR

2B102

2B

3 3

PHASE CABLE INSTALL

INSTALL (1)

HILTI-MDM400A OR

EQUIVALENT SLEEVE

FOR CAT6A

1'-4 5/16" 3'-0"

3'- 0"

3'- 0"

SBB CONDUITS

FP

38-123C-2 38-123C-1

GFGI DATA SWITCHES

GFGI DATA SWITCHES

GFGI DATA SWITCHES

GFGI DATA SWITCHES

GFGI DATA SWITCHES

SPECIFIED BY DIVISION 26

CFCI RACK-MOUNT UPS

SPECIFIED BY DIVISION 26

CFCI RACK-MOUNT UPS

GFGI DATA SWITCHES

GFGI DATA SWITCHES

TR 2B003 (LOOKING SOUTH)

B C D E F G H

A

I J K L

M N O P Q R

GFGI DATA SWITCHES

3 4

4 3

38-123C-2 38-123C-1

GFGI DATA SWITCHES

GFGI DATA SWITCHES

GFGI DATA SWITCHES

GFGI DATA SWITCHES

GFGI DATA SWITCHES

SPECIFIED BY DIVISION 26

CFCI RACK-MOUNT UPS

SPECIFIED BY DIVISION 26

CFCI RACK-MOUNT UPS

GFGI DATA SWITCHES

GFGI DATA SWITCHES

TR 2B102 (LOOKING SOUTH)

B C D E F G H

A

I J K L

M N O P Q R

GFGI DATA SWITCHES

3 4

4 3

38-123C-2 38-123C-1

GFGI DATA SWITCHES

GFGI DATA SWITCHES

GFGI DATA SWITCHES

GFGI DATA SWITCHES

GFGI DATA SWITCHES

SPECIFIED BY DIVISION 26

CFCI RACK-MOUNT UPS

SPECIFIED BY DIVISION 26

CFCI RACK-MOUNT UPS

GFGI DATA SWITCHES

GFGI DATA SWITCHES

TR 2A143 (LOOKING WEST)

B C D E F G H

A

I J K L

M N O P Q R

GFGI DATA SWITCHES

3 4

4 3

120 SF

2A143

13'-3"

9'- 0"

TR

CONDUITS

SBB

2 2

120 SF

2A1432A

3 TR

3'-0"

1'- 0"

3'-0"

3'-0"

CONDUITS SBB

103 SF

2A018

8'-9"

'-8

1/

2"TR

CONDUITS

SBB2

103 SF

2A018

2A018

TR

4 4 4

3 3

3'-0"

1'-0"

3'- 0"

3'- 0"

CONDUITS

SBB

38-123C-2 38-123C-1

GFGI DATA SWITCHES

GFGI DATA SWITCHES

GFGI DATA SWITCHES

GFGI DATA SWITCHES

GFGI DATA SWITCHES

SPECIFIED BY DIVISION 26

CFCI RACK-MOUNT UPS

SPECIFIED BY DIVISION 26

CFCI RACK-MOUNT UPS

GFGI DATA SWITCHES

GFGI DATA SWITCHES

TR 2A018 (LOOKING SOUTH)

B C D E F G H

A

I J K L

M N O P Q R

GFGI DATA SWITCHES

3 4

4 3

TECHNOLOGY KEYNOTES

DEMO EXISTING ITEM AFTER SYSTEMS CUTOVER.

LEAVE EXISTING ITEM IN PLACE AFTER SYSTEMS CUTOVER UNLESS OTHERWISE DIRECTED (UOD).

INSTALL TELECOMMUNICATIONS CHANNEL RACK, 7'H x 24"W x 30"D, 45RU, 4-POST, OPEN FRAME TYPE.

INSTALL VERTICAL CABLE MANAGER, 6"W x 6"D, W/DOOR.

INSTALL WIRE-MESH (WIRE BASKET) CABLE TRAY - 18"W x 4"D (TYPICAL).

INSTALL TELECOMMUNICATIONS ENCLOSURE, 48" H x 24"W x 30"D, 26RU, WALL-MOUNT CABINET

INSTALL WALL-MOUNTED CABLE SUPPORTS (J-HOOKS) AT 3', OR LESS, INTERVALS

INSTALL VERTICAL RBB IN REAR OF NETWORK CHANNEL RACK.

INSTALL 48 PORT ANGLED MODULAR PATCH PANELS WITH REAR CABLE SUPPORT.

INSTALL 1 RU OR 2 RU FIBER OPTIC TERMINATION PANEL, 144 STRAND CAPACITY AT TOP OF ONE RACK

PER TR.

INSTALL 1 RU FLAT HORIZONTAL CABLE MANAGERS BETWEEN ALL VA PROVIDED SWITCHES.

INSTALL 2 RU FLAT BLANK PANELS BETWEEN PATCH PANELS AND SWITCHES.

CHANNEL RACK CLEARANCE.

TECHNOLOGY GENERAL PLAN NOTES

1. CONTRACTOR TO PROVIDE PROTECTION TO ALL EQUIPMENT IN THE EXISTING RACKS WHILE TR

CONSTRUCTION IS OCCURRING.

2. ALL EXISTING DATA CABLES AND CIRCUITS MUST REMAIN IN PLACE AND OPERATIONAL UNTIL FINAL

CUT-OVER TO THE NEW CABLING SYSTEM.

3. REMOVE ALL EXISTING CABLE RUNWAY. TEMPORARILY SUPPORT EXISTING CABLES DURING TR

CONSTRUCTION IN ORDER TO KEEP EXISTING DATA AND OTHER SYSTEMS OPERATIONAL.

4. EXISTING DATA RACK/RACKS TO REMAIN UNTIL AFTER CUT-OVER.

5. EXISTING CONDUITS TO REMAIN.

6. NEW FIRE-RATED CONDUIT SLEEVES SHALL BE INSTALLED EXITING THE TR AND IN ALL FIRE-RATED WALLS ALONG THE CABLE PATHWAYS. CABLING PASSING THROUGH SLLEVES SHOULD NOT EXCEED

40% FILL RATIO.

7. INSTALL A RACK-MOUNTED HORIZONTAL BUSBAR AT THE TOP OF EACH RACK ON THE BACK RAIL.

8. ENSURE THAT ALL GROUNDING AND BONDING IS COMPLETE. TWO SCREW BONDING LUGS NEED TO BE INSTALLED TO BOND ALL METALLIC COMPONENTS OF THE RACK AND CABLE TRAY SYSTEM, TO THE

TELECOMMUNICATIONS SECONDARY BONDING BUSBAR.

9. BUILD AND POPULATE THE NEW CHANNEL RACKS. AFTER CUT-OVER, REMOVE ALL OLD DATA RACKS

AND MOVE CHANNEL RACKS INTO PLACE AS SHOWN ON TR KEYNOTES. ENSURE THAT ALL OTHER

EXISTING SYSTEMS IN THE OLD RACKS ARE MOVED TO THE NEW RACKS AND REMAIN OPERATIONAL.

COORDINATE WITH OIT AND FACILITIES. EQUIPMENT SHOULD BE SHARED BETWEEN THE RACKS, THERE SHOULD NOT BE PASSIVE RACKS IN TR's.

10. AFTER CUT-OVER TO THE NEW CABLING SYSTEM, DEMOLISH ALL OLD DATA CABLING ALL THE WAY TO THE WAO END. ENSURE THAT ANY CABLES IN THE CEILING AREAS THAT ARE FOR SYSTEMS OTHER

THAN THE IT DATA CABLES ARE NOT DISTURBED. DEMOLISH ALL OLD PATCH PANELS AND

ASSOCIATED HARDWARE. ALL OTHER ANCILLARY RACK-MOUNTED EQUIPMENT, NOT RELATED TO IT DATA, TO BE RELOCATED TO A NEW CHANNEL RACK BY OIT PERSONNEL. FIRE-STOP ALL EXISTING

CONDUIT SLEEVES WHERE CABLING WAS REMOVED.

11. PROVIDE 18" W x 4"D WIRE BASKET TYPE CABLE TRAY. MOUNT ALL NEW CABLE TRAY APPROXIMATELY 6" ABOVE CHANNEL RACK HEIGHT. SUPPORT TRAY USING VERTICAL THREADED ROD AND ASSOCIATED HARDWARE. USE CABLE TRAY EXITS AND DROP OUTS FOR SMOOTH TRANSITION OF CABLE OUT OF

THE CABLE TRAYS AND INTO THE CHANNEL RACKS FOR TERMINATION.

12. THERE ARE NUMEROUS ADDITIONAL CABLES IN THE TR FOR OTHER SERVICES SUCH AS WIRELESS

ACCESS POINTS, CAMERAS, FIRE ALARM, ACCESS CONTROL, MATV, NURSE CALL AND BIOMED.

CONTRACTOR NEEDS TO BE DILIGENT TO DEMOLISH ONLY WHAT IS BEING REPLACED AND ANY OTHER ITEMS SPECIFICALLY NOTED. ENSURE THAT ALL OTHER SERVICES IN THE TR REMAIN IN PLACE AND

AND OPERATIONAL.

13. ENSURE PROPER FIRE STOPPING (CAULKING, ETC.) IN ALL EXISTING AND ABANDONED CONDUIT

PATHWAYS/SLEEVES.

14. GROUNDING/BONDING: INSTALL RBB IN ALL RACKS AND CABINETS. IN TRs; BOND ALL RBBs AND CABLE TRAY TO SBB. IN MCR; BOND ALL RBBs AND CABLE TRAY TO MCR PBB/SBB

OF

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project NumberCONSULTANTS:

Drawing #

VA Health Care System Approval:

ARCHITECT:

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

ARCH FIRM REG. NO. 20314270 EXP. 06/30/2023

MECH FIRM REG. NO. 06253 EXP. 06/30/2024

FIRE PROTECTION ENGR

POOLE FIRE PROTECTION

19910 WEST 161ST ST.

OLATHE, KANSAS 66062

(913) 829-8690

FULLY SPRINKLERED

o n e e ig h th in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e in c h o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t th re e in c h e s o n e fo o t

No. REVISION DESCRIPTION DATE

INDUSTRIAL HYGENIST

RIVERFRONT (RSH)

1139 OLIVE ST, SUITE 300

ST. LOUIS, MO 63101

(713) 864-2900

STRUCT ENGR

STAND (SEI)

8234 ROBINSON ST

OVERLAND PARK, KS 66204

(913) 214-2169

COMMISSIONING

ES2

13401 N SANTE FE AVE

OKLAHOMA CITY, OK

(405) 528-4500

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

STAMP:

Drawing Number

Building Number

CONTROLLED UNCLASSIFED INFORMATION (CUI)

CONTROLLED UNCLASSIFED INFORMATION (CUI)

C O

N

TR

O

LL

ED

U

N C

LA

SS

IF

ED

IN

FO

R M

A

TI

O N

(C U

I)

TELECOMMUNICATION

ASPEN COMMUNICATIONS

7 KIJI-DAVA CIRCLE, STE A

PRESCOTT, AZ 86301

(928) 774-0992

MECH / ELEC / PLUMB ENGR

SPUR DESIGN

2519 MADISON AVENUE, STE 100

KANSAS CITY, MO 64108

(913) 369-7200

CHALMERS P. WYLIE VA

420 NORTH JAMES ROAD

COLUMBUS, OHIO 43219-1834FORCE PROTECT

10901 FRONT BEACH RD, UNIT 1415

PANAMA CITY BEACH, FL 32407

(502) 836-4232

PHYSICAL SECURITY

1791.19

TECHNOLOGY ENLARGED PLANS - BLDG 1A

- LVL 2

FINAL BID DOCUMENTS

757-22-705

06/02/2023 7871

EHRM INFRASTRUCTURE

UPGRADES - TIER 2

ASPEN NER

1A

T-302

N

1/4" = 1'-0" 4/ A-101

BLDG 1 - LEVEL 2 - 2B003 - DEMO

N

1/4" = 1'-0" 4/ A-101

BLDG 1 - LEVEL 2 - 2B003 - NEW

N

1/4" = 1'-0" 4/ A-101

BLDG 1 - LEVEL 2 - 2B102 - DEMO

N

1/4" = 1'-0" 4/ A-101

BLDG 1 - LEVEL 2 - 2B102 - NEW

N

1/4" = 1'-0"

BLDG 1 - LEVEL 2 - 2B003 - RACK ELEVATIONN

1/4" = 1'-0"

BLDG 1 - LEVEL 2 - 2B102 - RACK ELEVATION

N

1/4" = 1'-0"

BLDG 1 - LEVEL 2 - 2A143 - RACK ELEVATION

N

1/4" = 1'-0" 4/ A-101

BLDG 1 - LEVEL 2 - 2A143 - DEMO4

N

1/4" = 1'-0" 4/ A-101

BLDG 1 - LEVEL 2 - 2A143 - NEW

N

1/4" = 1'-0" 4/ A-101

BLDG 1 - LEVEL 2 - 2A018 - DEMO1

N

1/4" = 1'-0" 4/ A-101

BLDG 1 - LEVEL 2 - 2A018 - NEW2

N

1/4" = 1'-0"3

N

1/4" = 1'-0" 4/ A-101

BLDG 1 - LEVEL 2 - 2A018 - DEMO1

N

1/4" = 1'-0" 4/ A-101

BLDG 1 - LEVEL 2 - 2A018 - NEW2

N

1/4" = 1'-0"

BLDG 1 - LEVEL 2 - 2A018 - RACK ELEVATION3

81011

116 SF

3A063

8'- 9"

13'-3 1/2"

TR

CONDUITS SBB

2 2

116 SF

3A063

3A

3 TR

1'- 6 7

/8"

3'- 0"

3'-0"

3'-0"

CONDUITS SBB

3A004

12'-2"

8'- 2"

TR

FPs

SB

B

CO

ND

UI

TS

CO

ND

UI

TS

3A004

3A

TR

INSTALL CAT6A PATIENTS SIDE FIRST. CABLE CAN BE

STORED IN THESE AREAS. WORK TO BE PREFORMED

ON WEEKENDS. DEMO ONE RACK AT A TIME OR BOTH,

MUST FINISH BEFORE MONDAY BY 6:00AM

3'-0"

1'- 0"

3'-0"

3'-0"

FPs

SB

B

CO

ND

UI

TS

CO

ND

UI

TS

101 SF

3A015

TR

CONDUITS SBB

2 2

101 SF

3A015

3A015

TR

4 4 4

3'-0"

1'-0"

3'- 0"

3'- 0"

CONDUITS SBB

38-123C-2 38-123C-1

GFGI DATA SWITCHES

GFGI DATA SWITCHES

GFGI DATA SWITCHES

GFGI DATA SWITCHES

GFGI DATA SWITCHES

SPECIFIED BY DIVISION 26

CFCI RACK-MOUNT UPS

SPECIFIED BY DIVISION 26

CFCI RACK-MOUNT UPS

GFGI DATA SWITCHES

GFGI DATA SWITCHES

TR 3A004 (LOOKING EAST)

B C D E F G H

A

I J K L

M N O P Q R

GFGI DATA SWITCHES

3 4

4 3

38-123C-2 38-123C-1

GFGI DATA SWITCHES

GFGI DATA SWITCHES

GFGI DATA SWITCHES

GFGI DATA SWITCHES

GFGI DATA SWITCHES

SPECIFIED BY DIVISION 26

CFCI RACK-MOUNT UPS

SPECIFIED BY DIVISION 26

CFCI RACK-MOUNT UPS

GFGI DATA SWITCHES

GFGI DATA SWITCHES

TR 3A015 (LOOKING SOUTH)

B C D E F G H

A

I J K L

M N O P Q R

GFGI DATA SWITCHES

3 4

4 3

38-123C-2 38-123C-1

GFGI DATA SWITCHES

GFGI DATA SWITCHES

GFGI DATA SWITCHES

GFGI DATA SWITCHES

GFGI DATA SWITCHES

SPECIFIED BY DIVISION 26

CFCI RACK-MOUNT UPS

SPECIFIED BY DIVISION 26

CFCI RACK-MOUNT UPS

GFGI DATA SWITCHES

GFGI DATA SWITCHES

TR 3A063 (LOOKING WEST)

B C D E F G H

A

I J K L

M N O P Q R

GFGI DATA SWITCHES

3 4

4 3

38-123C-2 38-123C-1

GFGI DATA SWITCHES

GFGI DATA SWITCHES

GFGI DATA SWITCHES

GFGI DATA SWITCHES

GFGI DATA SWITCHES

SPECIFIED BY DIVISION 26

CFCI RACK-MOUNT UPS

SPECIFIED BY DIVISION 26

CFCI RACK-MOUNT UPS

GFGI DATA SWITCHES

GFGI DATA SWITCHES

TR 2B310 (LOOKING NORTH)

B C D E F G H

A

I J K L

M N O P Q R

GFGI DATA SWITCHES

3 4

4 3

100 SF

2B310

'-7

7'-11 1/2"

TR 1

EP 2

2B310

2B310

TR

1'-0" 2'-9 3/4"

3'- 0"

3'- 0"

EP

TECHNOLOGY KEYNOTES

DEMO EXISTING ITEM AFTER SYSTEMS CUTOVER.

LEAVE EXISTING ITEM IN PLACE AFTER SYSTEMS CUTOVER UNLESS OTHERWISE DIRECTED (UOD).

INSTALL TELECOMMUNICATIONS CHANNEL RACK, 7'H x 24"W x 30"D, 45RU, 4-POST, OPEN FRAME TYPE.

INSTALL VERTICAL CABLE MANAGER, 6"W x 6"D, W/DOOR.

INSTALL WIRE-MESH (WIRE BASKET) CABLE TRAY - 18"W x 4"D (TYPICAL).

INSTALL TELECOMMUNICATIONS ENCLOSURE, 48" H x 24"W x 30"D, 26RU, WALL-MOUNT CABINET

INSTALL WALL-MOUNTED CABLE SUPPORTS (J-HOOKS) AT 3', OR LESS, INTERVALS

INSTALL VERTICAL RBB IN REAR OF NETWORK CHANNEL RACK.

INSTALL 48 PORT ANGLED MODULAR PATCH PANELS WITH REAR CABLE SUPPORT.

INSTALL 1 RU OR 2 RU FIBER OPTIC TERMINATION PANEL, 144 STRAND CAPACITY AT TOP OF ONE RACK

PER TR.

INSTALL 1 RU FLAT HORIZONTAL CABLE MANAGERS BETWEEN ALL VA PROVIDED SWITCHES.

INSTALL 2 RU FLAT BLANK PANELS BETWEEN PATCH PANELS AND SWITCHES.

CHANNEL RACK CLEARANCE.

TECHNOLOGY GENERAL PLAN NOTES

1. CONTRACTOR TO PROVIDE PROTECTION TO ALL EQUIPMENT IN THE EXISTING RACKS WHILE TR

CONSTRUCTION IS OCCURRING.

2. ALL EXISTING DATA CABLES AND CIRCUITS MUST REMAIN IN PLACE AND OPERATIONAL UNTIL FINAL

CUT-OVER TO THE NEW CABLING SYSTEM.

3. REMOVE ALL EXISTING CABLE RUNWAY. TEMPORARILY SUPPORT EXISTING CABLES DURING TR

CONSTRUCTION IN ORDER TO KEEP EXISTING DATA AND OTHER SYSTEMS OPERATIONAL.

4. EXISTING DATA RACK/RACKS TO REMAIN UNTIL AFTER CUT-OVER.

5. EXISTING CONDUITS TO REMAIN.

6. NEW FIRE-RATED CONDUIT SLEEVES SHALL BE INSTALLED EXITING THE TR AND IN ALL FIRE-RATED WALLS ALONG THE CABLE PATHWAYS. CABLING PASSING THROUGH SLLEVES SHOULD NOT EXCEED

40% FILL RATIO.

7. INSTALL A RACK-MOUNTED HORIZONTAL BUSBAR AT THE TOP OF EACH RACK ON THE BACK RAIL.

8. ENSURE THAT ALL GROUNDING AND BONDING IS COMPLETE. TWO SCREW BONDING LUGS NEED TO BE INSTALLED TO BOND ALL METALLIC COMPONENTS OF THE RACK AND CABLE TRAY SYSTEM, TO THE

TELECOMMUNICATIONS SECONDARY BONDING BUSBAR.

9. BUILD AND POPULATE THE NEW CHANNEL RACKS. AFTER CUT-OVER, REMOVE ALL OLD DATA RACKS

AND MOVE CHANNEL RACKS INTO PLACE AS SHOWN ON TR KEYNOTES. ENSURE THAT ALL OTHER

EXISTING SYSTEMS IN THE OLD RACKS ARE MOVED TO THE NEW RACKS AND REMAIN OPERATIONAL.

COORDINATE WITH OIT AND FACILITIES. EQUIPMENT SHOULD BE SHARED BETWEEN THE RACKS, THERE SHOULD NOT BE PASSIVE RACKS IN TR's.

10. AFTER CUT-OVER TO THE NEW CABLING SYSTEM, DEMOLISH ALL OLD DATA CABLING ALL THE WAY TO THE WAO END. ENSURE THAT ANY CABLES IN THE CEILING AREAS THAT ARE FOR SYSTEMS OTHER

THAN THE IT DATA CABLES ARE NOT DISTURBED. DEMOLISH ALL OLD PATCH PANELS AND

ASSOCIATED HARDWARE. ALL OTHER ANCILLARY RACK-MOUNTED EQUIPMENT, NOT RELATED TO IT DATA, TO BE RELOCATED TO A NEW CHANNEL RACK BY OIT PERSONNEL. FIRE-STOP ALL EXISTING

CONDUIT SLEEVES WHERE CABLING WAS REMOVED.

11. PROVIDE 18" W x 4"D WIRE BASKET TYPE CABLE TRAY. MOUNT ALL NEW CABLE TRAY APPROXIMATELY 6" ABOVE CHANNEL RACK HEIGHT. SUPPORT TRAY USING VERTICAL THREADED ROD AND ASSOCIATED HARDWARE. USE CABLE TRAY EXITS AND DROP OUTS FOR SMOOTH TRANSITION OF CABLE OUT OF

THE CABLE TRAYS AND INTO THE CHANNEL RACKS FOR TERMINATION.

12. THERE ARE NUMEROUS ADDITIONAL CABLES IN THE TR FOR OTHER SERVICES SUCH AS WIRELESS

ACCESS POINTS, CAMERAS, FIRE ALARM, ACCESS CONTROL, MATV, NURSE CALL AND BIOMED.

CONTRACTOR NEEDS TO BE DILIGENT TO DEMOLISH ONLY WHAT IS BEING REPLACED AND ANY OTHER ITEMS SPECIFICALLY NOTED. ENSURE THAT ALL OTHER SERVICES IN THE TR REMAIN IN PLACE AND

AND OPERATIONAL.

13. ENSURE PROPER FIRE STOPPING (CAULKING, ETC.) IN ALL EXISTING AND ABANDONED CONDUIT

PATHWAYS/SLEEVES.

14. GROUNDING/BONDING: INSTALL RBB IN ALL RACKS AND CABINETS. IN TRs; BOND ALL RBBs AND CABLE TRAY TO SBB. IN MCR; BOND ALL RBBs AND CABLE TRAY TO MCR PBB/SBB

OF

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project NumberCONSULTANTS:

Drawing #

VA Health Care System Approval:

ARCHITECT:

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

ARCH FIRM REG. NO. 20314270 EXP. 06/30/2023

MECH FIRM REG. NO. 06253 EXP. 06/30/2024

FIRE PROTECTION ENGR

POOLE FIRE PROTECTION

19910 WEST 161ST ST.

OLATHE, KANSAS 66062

(913) 829-8690

FULLY SPRINKLERED