04_Architectural.pdf
PDF 3 MB Posted
- Attached to
- Y1DA--757-22-705 EHRM Infrastructure Upgrades - Columbus, OH - Tier 2 Construction (VA-22-00108764)
- Solicitation number
- 36C77623R0150
About this file
This set of architectural drawings and specifications outlines renovations and infrastructure upgrades to telecommunications rooms in Building 1 at the Chalmers P. Wylie VA Medical Center in Columbus, Ohio. The project involves demolishing and upgrading electrical, mechanical, and network equipment in 14 telecom rooms across four levels of the building. Renovations will include installing new flooring, walls, doors, and ceiling finishes. Mechanical upgrades include adding ductless split units and relocating air diffusers. Electrical work consists of moving panels and equipment. The server room will be reconfigured and temporarily relocated in phases to minimize network downtime. The contract also involves roof repairs and replacing rooftop HVAC units. Specifications cover door schedules, finishes, and general construction notes.
View the file
Other files
Show all 44
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
BASE
PLAN
HEAD
METAL STUD U-TRACK (TOP AND BOTTOM)
LINE OF CEILING
(REF: RCP FOR HEIGHT & TYPE)
WALL FINISH
(REF: ROOM FINISH SCHEDULE)
WIDTH
ACTUAL
5/8"
WIDTH
STUD 5/8"
BASE
PLAN
HEAD
LINE OF CEILING
(REF: RCP FOR HEIGHT & TYPE)
WALL FINISH
(REF: ROOM FINISH SCHEDULE)
5/8" GYPSUM BOARD EACH SIDE
FIN FLOOR (REF: ROOM FINISH SCHEDULE)
BASE - (REF: ROOM FINISH SCHEDULE)
FIN FLOOR (REF: ROOM FINISH SCHEDULE)
BASE (REF: ROOM FINISH SCHEDULE)
BATT INSULATION WHERE
SPECIFIED IN SCHEDULE
BASE
PLAN
HEAD
UNDERSIDE OF STRUCTURE
METAL RUNNER (FASTENED 24" O.C. MAX)
WALL FINISH (REF: ROOM FINISH SCHEDULE)
WIDTH
ACTUAL
5/8"TYPE X
5/8"TYPE X
2 LAYERS "TYPE X" GYPSUM BOARD
METAL RUNNER "J"
(FASTENED 24" O.C. MAX)
FIN FLOOR (REF: ROOM FINISH SCHEDULE)
BASE (REF: ROOM FINISH SCHEDULE)
CH STUD PER SCHEDULE
ROOM SIDE SHAFT SIDE
1" TYPE X GYPSUM BOARD LINER PANEL
BASE
PLAN
HEAD
UNDERSIDE OF STRUCTURE
LINE OF CEILING
(REF: RCP FOR HEIGHT & TYPE)
WALL FINISH
(REF: ROOM FINISH SCHEDULE)
WIDTH
ACTUAL
5/8"TYPE X
WIDTH
STUD 5/8"TYPE X
5/8" "TYPE X" GYPSUM
BOARD EACH SIDE
FINISH FLOOR
(REF: ROOM FINISH SCHEDULE)
BASE (REF: ROOM FINISH SCHEDULE)
METAL STUD PER SCHEDULE
BASE
PLAN
HEAD
UNDERSIDE OF STRUCTURE
WALL FINISH
(REF: ROOM FINISH SCHEDULE)
WIDTH
ACTUAL
1"TYPE X
FIN FLOOR- (REF: ROOM FINISH SCHEDULE)
BASE - (REF: ROOM FINISH SCHEDULE)
ROOM SIDE SHAFT SIDE
BASE
PLAN
HEAD
UNDERSIDE OF STRUCTURE
LINE OF CEILING
(REF: RCP FOR HEIGHT & TYPE)
WALL FINISH
(REF: ROOM FINISH SCHEDULE)
ACTUAL
5/8"TYPE X
5/8"TYPE X
WIDTH
STUD
5/8"TYPE X
5/8"TYPE X
2 LAYERS "TYPE X" GYPSUM
BOARD EACH SIDE
FINISH FLOOR
(REF: ROOM FINISH SCHEDULE)
BASE (REF: ROOM FINISH SCHEDULE)
BATT INSULATION
BASE
PLAN
HEAD
UNDERSIDE OF STRUCTURE
LINE OF CEILING (REF: RCP FOR HEIGHT & TYPE)
WALL FINISH (REF: ROOM FINISH SCHEDULE)
WIDTH
ACTUAL
5/8"
WIDTH
STUD VARIES
WIDTH
STUD 5/8"
5/8" GYPSUM BOARD EACH SIDE
FIN FLOOR (REF: ROOM FINISH SCHEDULE)
BASE - (REF: ROOM FINISH SCHEDULE)
METAL STUD PER SCHEDULE
BATT INSULATION WHERE SPECIFIED
IN SCHEDULE
METAL STUD PER SCHEDULE
FIRE RATED SEALANT AROUND PERIMETER
FIRE RATED SEALANT AROUND PERIMETER
FIRE RATED SEALANT AROUND PERIMETER
FIRE RATED SEALANT AROUND PERIMETER
BATT INSULATION
FIRE RATED SEALANT
AROUND PERIMETER
FIRE RATED SEALANT AROUND PERIMETER
FIRE RATED SEALANT AROUND PERIMETER
ACOUSTICAL SEALANT AROUND
PERIMETER (INSULATED WALLS)
ACOUSTICAL SEALANT AROUND
PERIMETER (INSULATED WALLS)
NOTE: INSULATED WALLS AROUND
RESTROOMS EXTEND OUTSIDE LAYER
OF GYPSUM BOARD TO DECK
ACOUSTICAL SEALANT AROUND
PERIMETER (INSULATED WALLS)
WIDTH
STUD5/8"
WIDTH
ACTUAL
BATT INSULATION WHERE
SPECIFIED IN SCHEDULE
DIM DIMDIM DIMDIM DIM
DIM DIMDIM DIM
LINE OF CEILING
(REF: RCP FOR HEIGHT & TYPE)
DIM DIM DIM DIM
BASE
PLAN
HEAD
DIM DIM
WIDTH
ACTUAL
5/8"
WIDTH
STUD 5/8"
1"TYPE XWIDTH
STUD
3/4"TYPE X
WIDTH
STUD
CH STUD PER SCHEDULE
METAL STUD PER SCHEDULE METAL STUD PER SCHEDULE
5/8" GYPSUM WALLBOARD
METAL STUD U-TRACK (TOP AND BOTTOM)
METAL STUD U-TRACK (TOP AND BOTTOM)
METAL STUD U-TRACK (TOP AND BOTTOM)
1" GYPSUM SHAFT LINER
METAL STUD U-TRACK (TOP AND BOTTOM)
UNDERSIDE OF STRUCTURE
LINE OF CEILING (REF: RCP FOR HEIGHT & TYPE)
WALL FINISH (REF: ROOM FINISH SCHEDULE)
5/8" GYPSUM BOARD EACH SIDE
FIN FLOOR (REF: ROOM FINISH SCHEDULE)
BASE (REF: ROOM FINISH SCHEDULE)
METAL STUD PER SCHEDULE
FIRE-RATED SEALANT AROUND PERIMETER
METAL STUD U-TRACK (TOP AND BOTTOM)
1. NOT ALL WALL TYPES MAY BE USED.
2. PAINT CONTINUOUS 4" TALL, STENCILED LETTERS, ABOVE CEILING, ON BOTH SIDES OF ALL FIRE AND SMOKE WALLS DESIGNATING THE PARTITION RATING INDICATED ON THE LIFE SAFETY PLAN.
3. REFER TO FINISH SCHEDULE AND INTERIOR ELEVATIONS FOR LOCATIONS OF ALL WALL TILE.
PROVIDE AND INSTALL CEMENTITIOUS BACKER BOARD IN LIEU OF GYP. BD. AT ALL SCHEDULED TILE LOCATIONS. UNLESS NOTED OTHERWISE, TILE SHALL BE INSTALLED PER TILE COUNCIL OF
AMERICA LATEST STANDARDS FOR EACH TYPE OF BACKING MATERIAL REPRESENTED IN
WALL/PARTITION.
4. ALL SUSPENDED WALLS AND PARTITIONS SHALL HAVE GYP. BD. WHICH EXTENDS A MINIMUM OF
6" ABOVE THE SUSPENDED CEILING UNLESS SHOWN AND/OR NOTED OTHERWISE BY THE
ARCHITECT.
5. "ALIGN" MEANS SIMILAR COMPONENTS OF CONSTRUCTION, E.G. WALLS, JAMBS, ETC. SHALL
ALIGN ACROSS VOIDS AND JOINTS.
6. PARTITIONS SHALL BE CONTINUOUS OVER DOORS SAME ADJACENT WALLS (UNLESS NOTED
OTHERWISE) WHERE GYP. BD. CONTINUES ABOVE CEILING AND ABOVE THE CEILING LEVEL UP
TO THE STRUCTURE ABOVE. ALL GYPSUM BOARD RETURNS SHALL HAVE CORNER BEADS
MINIMUM FLOOR TO CEILING. ALL PENETRATIONS IN GYP. BD. CONSTRUCTION ABOVE FINISHED
CEILING SHALL BE EFFECTIVELY SEALED TO PREVENT SOUND LEAKAGE AND FIRE STOPPING
TAPE/CAULK AT ALL RATED PARTITIONS.
7. ALL MECHANICAL CHASES AND OTHER NOTED CHASES ARE TO EXTEND UP TO THE UNDERSIDE
OF THE DECK STRUCTURE ABOVE. ALL PLUMBING CHASES UNLESS NOTED OTHERWISE, SHALL
EXTEND ABOVE THE HIGHEST ADJOINING CEILING AND BE BRACED TO STRUCTURE.
8. ALL CONSTRUCTION DESIGNATED TO BE SUPPORTED BY ROOF STRUCTURE SHALL BE
SUPPORTED BY TOP CHORD OF STRUCTURAL JOISTS AND NOT FROM THE METAL DECK.
9. COORDINATE WITH MILLWORK DRAWINGS FOR PLACEMENT OF BLOCKING IN WALLS/PARTITIONS.
ALL WOOD BLOCKING IS TO BE FIRE RETARDANT TREATED.
10. IMPACT RESISTANT GYP. BD., WHERE NOTED, IS OPTIONAL ABOVE 8' AFF AND BEHIND LOCKERS.
11. USE DEFLECTION TRACKS WHERE STUD WALLS ATTACH DIRECTLY TO METAL DECK.
GENERAL PARTITION NOTES
BASIC PARTITION
ASSEMBLY CATEGORY
FRAMING UNIT
SIZE CATEGORY
PARTITION TAG
PARTITION
PER PLAN
TYPICAL PARTITION TAG A3
UNDERSIDE OF STRUCTURE
FIRE RATED SEALANT
AROUND PERIMETER
DIM DIM
DEFLECTION TRACK
WHERE NEEDED
DEFLECTION TRACK AS REQUIRED
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project NumberCONSULTANTS:
Drawing #
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
ARCH FIRM REG. NO. 20314270 EXP. 06/30/2023
ENGR FIRM REG. NO. 06253 EXP. 06/30/2024
FIRE PROTECTION ENGR
POOLE FIRE PROTECTION
19910 WEST 161ST ST.
OLATHE, KANSAS 66062
(913) 829-8690
FULLY SPRINKLERED
INDUSTRIAL HYGENIST
RIVERFRONT (RSH)
1139 OLIVE ST, SUITE 300
ST. LOUIS, MO 63101
(713) 864-2900
STRUCT ENGR
STAND (SEI)
8234 ROBINSON ST
OVERLAND PARK, KS 66204
(913) 214-2169
COMMISSIONING
ES2
13401 N SANTE FE AVE
OKLAHOMA CITY, OK
(405) 528-4500
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
Drawing Number
Building Number
TELECOMMUNICATION
ASPEN COMMUNICATIONS
7 KIJI-DAVA CIRCLE, STE A
PRESCOTT, AZ 86301
(928) 774-0992
MECH / ELEC / PLUMB ENGR
SPUR DESIGN
2519 MADISON AVE, STE 100
KANSAS CITY, MO 64108
(913) 369-7200
FORCE PROTECT
10901 FRONT BEACH RD, UNIT 1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
PHYSICAL SECURITY
/3
/2
:1 :1
P
M
PARTITION TYPES
ZDL 7 OF 78BKM
FINAL BID DOCUMENTS
EHRM INFRASTRUCTURE
UPGRADES - TIER 2
06/02/2023
757-22-705
CHALMERS P. WYLIE VA
420 NORTH JAMES ROAD
COLUMBUS, OHIO 43219-1834
AE001
BLDG 1, ENERGY BLDG, & ENGR. BLDG
SPUR #: 1791.19
TYPE
MARK
WALL
TYPE
WALL
DESCRIPTION
WALL
WIDTH
MIN.
STC
K2 2 HR (U415/U438)
2 LAYERS 1/2" TYPE X GYPSUM BOARD ONE SIDE & 1" TYPE X
GYPSUM BOARD ONE SIDE OF 2 1/2" CH METAL STUD AT 16" O.C.
3 1/2" 47 STC
K4 2 HR (U415/U438)
2 LAYERS 1/2" TYPE X GYPSUM BOARD EACH SIDE OF 4" CH METAL
STUD AT 16" O.C.
5" 47 STC
K6 2 HR (U415)
2 LAYERS 5/8" TYPE X GYPSUM BOARD EACH SIDE OF 4" CH METAL
STUD AT 16" O.C.
7 1/4" 47 STC
TYPE
MARK
WALL
TYPE
WALL
DESCRIPTION
WALL
WIDTH
MIN.
STC
J2 2 HR (U411)
2 LAYERS 5/8" TYPE X GYPSUM BOARD EACH SIDE OF 2 1/2" METAL
STUD AT 16" O.C.
5" 51 STC
J3 2 HR (U404)
2 LAYERS 5/8" TYPE X GYPSUM BOARD EACH SIDE OF 3 5/8" METAL
STUD AT 16" O.C.
6 1/8" 51 STC
J6 2 HR (U404)
2 LAYERS 5/8" TYPE X GYPSUM BOARD EACH SIDE OF 6" METAL
STUD AT 16" O.C.
8 1/2" 51 STC
TYPE
MARK
WALL
TYPE
WALL
DESCRIPTION
WALL
WIDTH
MIN.
STC
H3 1 HR / SMOKE
5/8" TYPE X GYPSUM BOARD ON EACH SIDE OF 3 5/8" METAL STUD
AT 16" O.C.
4 7/8" 45 STC
H6 1 HR / SMOKE
5/8" TYPE X GYPSUM BOARD ON EACH SIDE OF 6" METAL STUD AT
16" O.C.
7 1/4" 45 STC
TYPE
MARK
WALL
TYPE
WALL
DESCRIPTION
WALL
WIDTH
MIN.
STC
G2 1 HR (U415/U469)
5/8" TYPE X GYPSUM BOARD ONE SIDE & 1" TYPE X GYPSUM
BOARD OPPOSITE SIDE OF 2 1/2" CH METAL STUD AT 16" O.C. W/
BATT INSULATION
3 1/8" 45 STC
G4 1HR (U415/U438)
5/8" TYPE X GYPSUM BOARD ONE SIDE & 1" TYPE X GYPSUM
BOARD OPPOSITE SIDE OF 4" CH METAL STUD AT 16" O.C. W/ BATT
INSULATION
4 5/8" 45 STC
G6 1 HR (U415/U469)
5/8" TYPE X GYPSUM BOARD ONE SIDE & 1" TYPE X GYPSUM
BOARD OPPOSITE SIDE OF 6" CH METAL STUD SPACED AT 16" O.C.
W/ BATT INSULATION
6 5/8" 45 STC
TYPE
MARK
WALL
TYPE
WALL
DESCRIPTION
WALL
WIDTH
MIN.
STC
F3 1 HR (U419)
5/8" TYPE X GYPSUM BOARD EACH SIDE OF 3 5/8" METAL STUD AT
16" O.C.
4 7/8" 48 STC
F6 1 HR (U419)
5/8" TYPE X GYPSUM BOARD EACH SIDE OF 6" METAL STUD AT 16"
O.C.
7 1/4" 48 STC
TYPE
MARK
WALL
TYPE
WALL
DESCRIPTION
WALL
WIDTH
MIN.
STC
E3 CARRIER
5/8" GYPSUM BOARD ONE SIDE OF (2) 3 5/8" METAL STUD AT 16"
O.C. WALLS W/ BATT INSULATION ONE SIDE
1'-8" --
E6 CARRIER
5/8" GYPSUM BOARD ONE SIDE OF (2) 6" METAL STUD AT 16" O.C.
WALLS W/ BATT INSULATION
2'-0 3/4" --
TYPE
MARK
WALL
TYPE
WALL
DESCRIPTION
WALL
WIDTH
MIN.
STC
C2 NON-INSULATED 5/8" GYPSUM BOARD EACH SIDE OF 2 1/2" METAL STUD AT 16" O.C. 3 3/4" --
C3 NON-INSULATED 5/8" GYPSUM BOARD EACH SIDE OF 3 5/8" METAL STUD AT 16" O.C. 4 7/8" --
C6 NON-INSULATED 5/8" GYPSUM BOARD EACH SIDE OF 6" METAL STUD AT 16" O.C. 7 1/4" --
D2 INSULATED
5/8" GYPSUM BOARD EACH SIDE OF 2 1/2" METAL STUD AT 16" O.C.
W/ BATT INSULATION
3 3/4" --
D3 INSULATED
5/8" GYPSUM BOARD EACH SIDE OF 3 5/8" METAL STUD AT 16" O.C.
W/ BATT INSULATION
4 7/8" --
D6 INSULATED
5/8" GYPSUM BOARD EACH SIDE OF 6" METAL STUD AT 16" O.C. W/
BATT INSULATION
7 1/4" --
TYPE
MARK
WALL
TYPE
WALL
DESCRIPTION
WALL
WIDTH
MIN.
STC
A1 NON-INSULATED
5/8" GYPSUM BOARD ONE SIDE 7/8" HAT CHANNEL SPACED AT 16"
O.C.
1 1/2" --
A2 NON-INSULATED 5/8" GYPSUM BOARD ONE SIDE OF 2 1/2" METAL STUD AT 16" O.C. 3 1/8" --
A3 NON-INSULATED 5/8" GYPSUM BOARD ONE SIDE OF 3 5/8" METAL STUD AT 16" O.C. 4 1/4" --
A6 NON- INSULATED 5/8" GYPSUM BOARD ONE SIDE OF 6" METAL STUD AT 16" O.C. 6 5/8" --
B2 INSULATED
5/8" GYPSUM BOARD ONE SIDE OF 2 1/2" METAL STUD AT 16" O.C.
W/ BATT INSULATION
3 1/8" --
B3 INSULATED
5/8" GYPSUM BOARD ONE SIDE OF 3 5/8" METAL STUD AT 16" O.C.
W/ BATT INSULATION
4 1/4" --
B6 INSULATED
5/8" GYPSUM BOARD ONE SIDE OF 6" METAL STUD AT 16" O.C. W/
BATT INSULATION
6 5/8" --
No. REVISION DESCRIPTION DATE
AE401
AE401
AE401
AE402
AE401
AE402
AE402
AE401
AE401
AE401
AE402
AE402
AE402
AE401
157 SF
TELECOM
1A457
101 SF
TELECOM
1A024
103 SF
TELECOM
1A014
104 SF
TELECOM
1B006
91 SF
TELECOM
1B002
120 SF
TELECOM
1A106 96 SF
TELECOM
1B609
AE402
AE403
AE403
AE403
AE404
AE403
AE402
AE403
AE403
AE404
AE403
AE403
103 SF
TELECOM
2A018
101 SF
TELECOM
2B003
100 SF
TELECOM
2B310
91 SF
TELECOM
2B102
101 SF
TELECOM
2A004
120 SF
TELECOM
2A143
1. OVERALL PLANS ARE ONLY INCLUDED TO SHOW GENERAL LOCATION OF IN-SCOPE SPACES ON
EACH FLOOR WITHIN EACH BUILDING.
2. REFER TO ENLARGED PLANS FOR ADDITIONAL INFORMATION REGARDING DEMOLITION AND NEW
CONSTRUCTION WITHIN AND ADJACENT TO EACH IN-SCOPE ROOM.
GENERAL OVERALL PLAN NOTES
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project NumberCONSULTANTS:
Drawing #
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
ARCH FIRM REG. NO. 20314270 EXP. 06/30/2023
ENGR FIRM REG. NO. 06253 EXP. 06/30/2024
FIRE PROTECTION ENGR
POOLE FIRE PROTECTION
19910 WEST 161ST ST.
OLATHE, KANSAS 66062
(913) 829-8690
FULLY SPRINKLERED
INDUSTRIAL HYGENIST
RIVERFRONT (RSH)
1139 OLIVE ST, SUITE 300
ST. LOUIS, MO 63101
(713) 864-2900
STRUCT ENGR
STAND (SEI)
8234 ROBINSON ST
OVERLAND PARK, KS 66204
(913) 214-2169
COMMISSIONING
ES2
13401 N SANTE FE AVE
OKLAHOMA CITY, OK
(405) 528-4500
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
Drawing Number
Building Number
TELECOMMUNICATION
ASPEN COMMUNICATIONS
7 KIJI-DAVA CIRCLE, STE A
PRESCOTT, AZ 86301
(928) 774-0992
MECH / ELEC / PLUMB ENGR
SPUR DESIGN
2519 MADISON AVE, STE 100
KANSAS CITY, MO 64108
(913) 369-7200
FORCE PROTECT
10901 FRONT BEACH RD, UNIT 1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
PHYSICAL SECURITY
/3
/2
:1 :2
P
M
REFERENCE PLANS - BUILDING 1
ZDL 8 OF 78BKM
FINAL BID DOCUMENTS
EHRM INFRASTRUCTURE
UPGRADES - TIER 2
06/02/2023
757-22-705
CHALMERS P. WYLIE VA
420 NORTH JAMES ROAD
COLUMBUS, OHIO 43219-1834
AE101
BLDG 1, ENERGY BLDG, & ENGR. BLDG
SPUR #: 1791.19
N
1" = 40'-0"
BLDG 1 - LEVEL 1 - REFERENCE PLAN1
N
1" = 40'-0"
BLDG 1 - LEVEL 2 - REFERENCE PLAN4
AE404
AE404
AE404
AE404
AE404
AE404
100 SF
TELECOM
3A004
102 SF
TELECOM
3A015
115 SF
TELECOM
3A063
AE407
AE406
1067 SF
SERVER/MAIN
TELECOM
4A201
119 SF
TELECOM
4A041
AE405
AE405
AE405
AE405
105 SF
TELECOM
AE405
10AE405
56 SF
TELECOM
1. OVERALL PLANS ARE ONLY INCLUDED TO SHOW GENERAL LOCATION OF IN-SCOPE SPACES ON
EACH FLOOR WITHIN EACH BUILDING.
2. REFER TO ENLARGED PLANS FOR ADDITIONAL INFORMATION REGARDING DEMOLITION AND NEW
CONSTRUCTION WITHIN AND ADJACENT TO EACH IN-SCOPE ROOM.
GENERAL OVERALL PLAN NOTES
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project NumberCONSULTANTS:
Drawing #
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
ARCH FIRM REG. NO. 20314270 EXP. 06/30/2023
ENGR FIRM REG. NO. 06253 EXP. 06/30/2024
FIRE PROTECTION ENGR
POOLE FIRE PROTECTION
19910 WEST 161ST ST.
OLATHE, KANSAS 66062
(913) 829-8690
FULLY SPRINKLERED
INDUSTRIAL HYGENIST
RIVERFRONT (RSH)
1139 OLIVE ST, SUITE 300
ST. LOUIS, MO 63101
(713) 864-2900
STRUCT ENGR
STAND (SEI)
8234 ROBINSON ST
OVERLAND PARK, KS 66204
(913) 214-2169
COMMISSIONING
ES2
13401 N SANTE FE AVE
OKLAHOMA CITY, OK
(405) 528-4500
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
Drawing Number
Building Number
TELECOMMUNICATION
ASPEN COMMUNICATIONS
7 KIJI-DAVA CIRCLE, STE A
PRESCOTT, AZ 86301
(928) 774-0992
MECH / ELEC / PLUMB ENGR
SPUR DESIGN
2519 MADISON AVE, STE 100
KANSAS CITY, MO 64108
(913) 369-7200
FORCE PROTECT
10901 FRONT BEACH RD, UNIT 1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
PHYSICAL SECURITY
/3
/2
:1 :2
P
M
REFERENCE PLANS - BLDG 1, ENERGY
BLDG, & ENGINEERING BLDG
ZDL 9 OF 78BKM
FINAL BID DOCUMENTS
EHRM INFRASTRUCTURE
UPGRADES - TIER 2
06/02/2023
757-22-705
CHALMERS P. WYLIE VA
420 NORTH JAMES ROAD
COLUMBUS, OHIO 43219-1834
AE102
BLDG 1, ENERGY BLDG, & ENGR. BLDG
SPUR #: 1791.19
N
1" = 40'-0"
BLDG 1 - LEVEL 3 - REFERENCE PLAN1
N
1" = 40'-0"
BLDG 1 - LEVEL 4 - REFERENCE PLAN3
N
1" = 40'-0"
BOILER PLANT - LEVEL 1 - REFERENCE PLAN2
N
1" = 40'-0"
ENGINEERING BUILDING - LEVEL 1 - REFERENCE PLAN4
157 SF
TELECOM
1A457
2'
-8
/2
F V
+/- 12'-5 1/2" FV
2.05 2.13
2.15
2.17
+/- 1'-2 3/4" FV
3/ 4"
F V
+/- 4" FV
+/- 3'-4" FV
2.18
101 SF
TELECOM
1A024
'-3
/2
F
V
+/- 12'-2" FV
2.05
2.13
2.15
2.17
+/- 3'-4" FV +/- 4'-5" FV
2.18
103 SF
TELECOM
1A014
+/- 8'-9" FV
1'
-8
/4
F V
2.05
2.13
2.15
2.17
'-4
F
V
'-2
/2
F V
2.18
157 SF
TELECOM
1A457
1A
2.17
26.04
TYP.
27.01
4"
9.87
4'-1" 4'-2 1/2"
5' -1
5'
-1
101 SF
TELECOM
1A024
1A
2.17
27.01
26.04
26.04
4'-5"
9.87
3'-0"
1' -0
3'
-1
/2
103 SF
TELECOM
1A014
1A014
26.04
27.01
TYP.
2.17
9.87
1'-0"
3' -0
6'
-3
3'-7"
103 SF
TELECOM
1A014
2.16
2.16
103 SF
TELECOM
1A014
23.05
23.05
E Q
3'
-0
3' -0
3'
-0
E Q
EQ. EQ.
101 SF
TELECOM
1A024
2.16 2.16
101 SF
TELECOM
1A02423.05
23.05
2'-0" 3'-0" 3'-0" 3'-0" 1'-2"
E Q
E
Q
157 SF
TELECOM
1A457
2.16
157 SF
TELECOM
1A457
EQ. 4'-0" EQ.
E Q
7'
-0
E Q
23.05
23.05
120 SF
TELECOM
1A106
EQ. 6'-0" EQ.
E Q
5'
-4
E Q
23.05
23.05
120 SF
TELECOM
1A106
2.16
2.16
120 SF
TELECOM
1A106
+/- 13'-3 1/2" FV
'-0
F
V
2.05
2.13
2.17
+/- 3'-4" FV
+/- 1'-0" FV
2.15
2.18
120 SF
TELECOM
1A106
1A
27.01
26.04
TYP.
2.17
1'-0"
9.8726.04
TYP.
1' -1
0" 3'
-0
3'-0" 7'-9 1/2"
SPOT ELEVATION HEIGHT,
ABOVE FINISH FLOOR
00'-00"
EXISTING 2' x 2' ACOUSTICAL
CEILING TO BE REMOVED
AND SALVAGED FOR
REINSTALLATION
EXISTING GYPSUM BOARD
CEILING
EXISTING 2 x 2 LIGHT FIXTURE
TO BE DEMOLISHED; REF
ELECTRICAL
EXISTING 2 x 4 LIGHT FIXTURE
TO BE DEMOLISHED; REF
ELECTRICAL
DEMOLITION REFELCTED CEILING PLAN LEGEND
EXISTING 2' x 4' ACOUSTICAL
CEILING TO BE REMOVED AND
SALVAGED FOR
REINSTALLATION
EXISTING RETURN AIR GRILLE
TO BE DEMOLISHED; REF
MECHANICAL
EXISTING SUPPLY AIR
DIFFUSER TO BE DEMOLISHED;
REF MECHANICAL
EXISTING EXHAUST AIR
GRILLE TO BE DEMOLISHED;
REF MECHANICAL
AREA NOT IN SCOPE
NOTE: ALL SYMBOLS MAY NOT BE USED.
EXISTING 2 x 2 LIGHT FIXTURE
TO BE REMOVED AND
RELOCATED; REF ELECTRICAL
EXISTING 2 x 4 LIGHT FIXTURE
TO BE REMOVED AND
RELOCATED; REF ELECTRICAL
EXISTING DIFFUSER TO
REMAIN; REF MECHANICAL
EXISTING 2' x 2' ACOUSTICAL
CEILING TO BE REMOVED
1. ALL DOOR FRAMES TO BE LOCATED 4" FROM OUTSIDE OF FRAME TO FINISH FACE OF ADJACENT
WALL UNLESS NOTED OTHERWISE.
2. REFER TO DOOR SCHEDULE & DETAILS SHEET (AE601) FOR DOOR INFORMATION.
3. ALL WALLS ARE DIMENSIONED TO CENTERLINE OF METAL STUD, UNLESS NOTED OTHERWISE.
4. BLOCK OUT SLAB FOR PENETRATIONS SHALL BE 2" LARGER THAN DUCT SIZE TO ALLOW
TOLERANCE FOR DUCT PASSAGE AND FIRE SAFING. COORDINATE WITH MEP FOR DUCT SIZES.
5. FURR AROUND ALL COLUMN PROTRUSIONS AS NEEDED UNLESS NOTED OTHERWISE.
6. EACH TELECOM ROOM TO HAVE NO CEILING. CONTRACTOR TO PRESERVE EXISTING FIRE
SUPPRESSION SYSTEMS.
GENERAL PLAN NOTES
2' x 2' ACOUSTICAL CEILING
GYPSUM BOARD CEILING OR
SOFFIT
2 x 2 LIGHT FIXTURE; REF
ELECTRICAL
CEILING HEIGHT, ABOVE
FINISH FLOOR
2 x 4 LIGHT FIXTURE; REF
ELECTRICAL
00'-00"
REFLECTED CEILING PLAN LEGEND
2' x 4' ACOUSTICAL CEILING
NEW RETURN AIR GRILLE;
REF MECHANICAL
NEW SUPPLY AIR DIFFUSER;
REF MECHANICAL
NEW EXHAUST AIR GRILLE;
REF MECHANICAL
SUSPENDED LIGHT FIXTURE;
REF ELECTRICAL
NOTE: ALL SYMBOLS MAY NOT BE USED.
EXISTING DIFFUSER; REF
MECHANICAL
EXISTING DOOR, FRAME AND
HARDWARE TO BE
DEMOLISHED
DEMOLITION FLOOR PLAN LEGEND
AREA NOT IN CONTRACT
EXISTING PARTITION TO BE
DEMOLISHED
EXISTING PARTITION TO
REMAIN
NOTE: ALL SYMBOLS MAY NOT BE USED.
EXISTING DOOR & FRAME TO
REMAIN
EXISTING WINDOW & FRAME
TO REMAIN
EXISTING WINDOW & FRAME
TO BE DEMOLISHED
ICRA CONSTRUCTION
BARRIER AND
CONSTRUCTION ACCESS
EXISTING 1 HR PARTITION
TO REMAIN
DEMOLISH EXISTING
FLOORING TO EXTENT
INDICATED
1. ALL EXISTING WALL DIMENSIONS ARE TO FINISH FACE, UNLESS NOTED OTHERWISE.
2. THE CONTRACTOR SHALL VERIFY DIMENSIONS OF AS-BUILT CONDITIONS, AND NOTIFY THE
ARCHITECT IN WRITING OF ANY DISCREPANCIES. ALL INFORMATION SHOWN ON THE
CONSTRUCTION DOCUMENTS IS BASED ON FIELD OBSERVATIONS AND/OR THE ORIGINAL
CONSTRUCTION DOCUMENTS OF THE FACILITY.
3. DO NOT REMOVE BARRIERS FROM WORK AREA UNTIL COMPLETED PROJECT AREA HAS BEEN
INSPECTED BY THE VA SAFETY OFFICER AND INFECTION CONTROL COORDINATOR AND
THOROUGHLY CLEANED BY ENVIRONMENTAL MANAGEMENT SERVICES
4. THE CONTRACTOR SHALL PROVIDE PROTECTIVE COVERING FOR EXISTING FLOOR, WALL AND
CEILING FINISHES IN EXISTING AREAS NOT DESIGNATED FOR DEMOLITION OR NEW
CONSTRUCTION. THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE REPAIR OF ANY DAMAGE
CAUSED BY HIS WORK OR ANY SUBCONTRACTOR.
5. THE CONTRACTOR SHALL VERIFY THAT NEW MECHANICAL SYSTEMS CAN BE INSTALLED IN
EXISTING SPACES TO CLEAR EXISTING CEILING AND OTHER CONSTRUCTED ITEMS AND
MAINTAIN FLOOR TO CEILING HEIGHTS INDICATED ON DRAWINGS. IF DISCREPANCIES OCCUR
DUE TO EXISTING CONDITIONS, CONSULT WITH THE ARCHITECT BEFORE PROCEEDING.
6. THE FINISH FACE OF MATERIAL OF NEW PARTITIONS SHALL ALIGN ON BOTH SIDES OF THE PARTITION WITH THE FACE OF THE MATERIALS ON EXISTING COLUMNS, WALLS, OR PARTITIONS, UNLESS NOTED OTHERWISE.
7. NO WORK TO BE DONE IN AREAS HATCHED GRAY IN PLANS, HOWEVER WORK MIGHT NEED TO
BE PERFORMED IN CEILING OR EXISTING CHASES THROUGHOUT BUILDING. REFERENCE
MECHANICAL AND ELECTRICAL DRAWINGS FOR EXTENT OF WORK. COORDINATE ACCESS TO
ROOMS OUTSIDE OF SCOPE WITH OWNER
GENERAL DEMOLITION NOTES
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project NumberCONSULTANTS:
Drawing #
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
ARCH FIRM REG. NO. 20314270 EXP. 06/30/2023
ENGR FIRM REG. NO. 06253 EXP. 06/30/2024
FIRE PROTECTION ENGR
POOLE FIRE PROTECTION
19910 WEST 161ST ST.
OLATHE, KANSAS 66062
(913) 829-8690
FULLY SPRINKLERED
INDUSTRIAL HYGENIST
RIVERFRONT (RSH)
1139 OLIVE ST, SUITE 300
ST. LOUIS, MO 63101
(713) 864-2900
STRUCT ENGR
STAND (SEI)
8234 ROBINSON ST
OVERLAND PARK, KS 66204
(913) 214-2169
COMMISSIONING
ES2
13401 N SANTE FE AVE
OKLAHOMA CITY, OK
(405) 528-4500
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
Drawing Number
Building Number
CONTROLLED UNCLASSIFED INFORMATION (CUI)
CONTROLLED UNCLASSIFED INFORMATION (CUI)
C O
N T
R O
L L
E D
U N
C L
A S
S
IF
E D
I N
F O
R M
A T
IO
N
C
U I)
TELECOMMUNICATION
ASPEN COMMUNICATIONS
7 KIJI-DAVA CIRCLE, STE A
PRESCOTT, AZ 86301
(928) 774-0992
MECH / ELEC / PLUMB ENGR
SPUR DESIGN
2519 MADISON AVE, STE 100
KANSAS CITY, MO 64108
(913) 369-7200
FORCE PROTECT
10901 FRONT BEACH RD, UNIT 1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
PHYSICAL SECURITY
/3
/2
:1 :3
P
M
ENLARGED PLANS - BLDG 1 - LEVEL 1
ZDL 10 OF 78BKM
FINAL BID DOCUMENTS
EHRM INFRASTRUCTURE
UPGRADES - TIER 2
06/02/2023
757-22-705
CHALMERS P. WYLIE VA
420 NORTH JAMES ROAD
COLUMBUS, OHIO 43219-1834
AE401
BLDG 1, ENERGY BLDG, & ENGR. BLDG
SPUR #: 1791.19
N
1/4" = 1'-0" 1/ AE101
BLDG 1 - LEVEL 1 - 1A457 - DEMO13
N
1/4" = 1'-0" 1/ AE101
BLDG 1 - LEVEL 1 - 1A024 - DEMO5
N
1/4" = 1'-0" 1/ AE101
BLDG 1 - LEVEL 1 - 1A014 - DEMO1
N
1/4" = 1'-0" 1/ AE101
BLDG 1 - LEVEL 1 - 1A457 - NEW14
N
1/4" = 1'-0" 1/ AE101
BLDG 1 - LEVEL 1 - 1A024 - NEW6
N
1/4" = 1'-0" 1/ AE101
BLDG 1 - LEVEL 1 - 1A014 - NEW2
N
1/4" = 1'-0"
BLDG 1 - LEVEL 1 - 1A014 - DEMO RCP3
N
1/4" = 1'-0"
BLDG 1 - LEVEL 1 - 1A014 - RCP4
N
1/4" = 1'-0"
BLDG 1 - LEVEL 1 - 1A024 - DEMO RCP7
N
1/4" = 1'-0"
BLDG 1 - LEVEL 1 - 1A024 - RCP8
N
1/4" = 1'-0"
BLDG 1 - LEVEL 1 - 1A457 - DEMO RCP15
N
1/4" = 1'-0"
BLDG 1 - LEVEL 1 - 1A457 - RCP16
N
1/4" = 1'-0"
BLDG 1 - LEVEL 1 - 1A106 - RCP12
N
1/4" = 1'-0"
BLDG 1 - LEVEL 1 - 1A106 - DEMO RCP11
N
1/4" = 1'-0" 1/ AE101
BLDG 1 - LEVEL 1 - 1A106 - DEMO9
N
1/4" = 1'-0" 1/ AE101
BLDG 1 - LEVEL 1 - 1A106 - NEW10
KEYNOTE LEGEND
2.05 DEMOLISH EXISTING DOOR AND FRAME IN ITS ENTIRETY
2.13 DEMOLISH EXISTING FLOORING AND BASE AND PREPARE SUBSURFACE FLOORING FOR NEW
TILE INSTALLATION
2.15 REMOVE EXISTING TELECOM AND ELECTRICAL EQUIPMENT PER ELECTRICAL AND TELECOM
DRAWINGS.
2.16 REMOVE EXISTING MECHANICAL EQUIPMENT PER MECHANICAL DRAWINGS.
2.17 EXISTING GROUND BAR TO REMAIN; SEE ELECTRICAL DRAWINGS.
2.18 PATCH AND REPAIR WALLS FOR PREPARATION OF NEW FINISH AFTER REMOVAL OF
EXISTING EQUIPMENT.
9.87 FLOOR FINISH AS SCHEDULED.
23.05 WALL-MOUNTED DUCTLESS SPLIT UNIT, SEE MECHANICAL DRAWINGS
26.04 PANEL LOCATION, SEE ELECTRICAL DRAWINGS
96 SF
1B609
2.05
2.13
2.15
2.17
+/- 9'-11 1/2" FV
0'
-0
F V
+/- 2'-1" FV
+/- 1'-3 1/4" FV
'-7
/2
F
V
+/- 1 3/4" FV
+/- 3'-4" FV
2.18
96 SF
TELECOM
1B609
1B
27.01
TYP
2.17
26.04
26.04
1 3/4"
9.87
3'-0"4'-5"
1' -0
3'
-2
96 SF
TELECOM
1B609
96 SF
TELECOM
1B609 23.05
23.05
3'-1" 5'-8" 1'-3"
2' -3
4'
-1
3' -8
91 SF
TELECOM
1B002
1B
27.01
2.17
26.04
TYP
2'-4"
9.87
1'-10 1/2"3'-0"
3' -1
1/
2" 3'
-1
1/ 2"
91 SF
TELECOM
1B002
2.05
2.13
2.15
2.17
+/- 9'-0 1/4" FV
'-9
/2
F
V
0' -4
F
V
+/- 1'-3 1/2" FV
+/- 3'-4" FV +/- 2'-4" FV
2.18
104 SF
TELECOM
1B006
2'
-3
/2
F V
+/- 8'-5 1/2" FV
2.05
2.13
2.15
2.17
+/- 3'-4" FV
+/- 2'-6 3/4" FV
2.18
104 SF
TELECOM
1B006
1B
2.17
27.01
TYP
26.04
TYP
9.87
1'-1"3'-2 1/2"
3' -8
6'
-1
104 SF
TELECOM
1B006
104 SF
TELECOM
1B006
E Q
3'
-0
3' -0
3'
-0
E Q
EQ. EQ.
23.05
23.05
91 SF
TELECOM
1B002
E Q
4'
-6
E Q
EQ. 4'-0" EQ.
23.05
23.05
91 SF
TELECOM
1B002
101 SF
TELECOM
2A004
+/- 12'-1 1/2" FV
'-3
/2
F
V
2.05
2.13
2.15
2.17
+/- 4'-4 3/4" FV +/- 3'-4" FV
2.18
101 SF
TELECOM
2A004
2A
2.17
26.04
27.01
TYP
9.87
1' -0
3'
-1
/2
3'-0"6'-7 1/2"
101 SF
TELECOM
2A004
2.162.16
101 SF
TELECOM
2A004
EQ. 3'-0" 3'-0" 3'-0" EQ.
23.05
23.05
4' -2
E
Q
SPOT ELEVATION HEIGHT,
ABOVE FINISH FLOOR
00'-00"
EXISTING 2' x 2' ACOUSTICAL
CEILING TO BE REMOVED
AND SALVAGED FOR
REINSTALLATION
EXISTING GYPSUM BOARD
CEILING
EXISTING 2 x 2 LIGHT FIXTURE
TO BE DEMOLISHED; REF
ELECTRICAL
EXISTING 2 x 4 LIGHT FIXTURE
TO BE DEMOLISHED; REF
ELECTRICAL
DEMOLITION REFELCTED CEILING PLAN LEGEND
EXISTING 2' x 4' ACOUSTICAL
CEILING TO BE REMOVED AND
SALVAGED FOR
REINSTALLATION
EXISTING RETURN AIR GRILLE
TO BE DEMOLISHED; REF
MECHANICAL
EXISTING SUPPLY AIR
DIFFUSER TO BE DEMOLISHED;
REF MECHANICAL
EXISTING EXHAUST AIR
GRILLE TO BE DEMOLISHED;
REF MECHANICAL
AREA NOT IN SCOPE
NOTE: ALL SYMBOLS MAY NOT BE USED.
EXISTING 2 x 2 LIGHT FIXTURE
TO BE REMOVED AND
RELOCATED; REF ELECTRICAL
EXISTING 2 x 4 LIGHT FIXTURE
TO BE REMOVED AND
RELOCATED; REF ELECTRICAL
EXISTING DIFFUSER TO
REMAIN; REF MECHANICAL
EXISTING 2' x 2' ACOUSTICAL
CEILING TO BE REMOVED
1. ALL DOOR FRAMES TO BE LOCATED 4" FROM OUTSIDE OF FRAME TO FINISH FACE OF ADJACENT
WALL UNLESS NOTED OTHERWISE.
2. REFER TO DOOR SCHEDULE & DETAILS SHEET (AE601) FOR DOOR INFORMATION.
3. ALL WALLS ARE DIMENSIONED TO CENTERLINE OF METAL STUD, UNLESS NOTED OTHERWISE.
4. BLOCK OUT SLAB FOR PENETRATIONS SHALL BE 2" LARGER THAN DUCT SIZE TO ALLOW
TOLERANCE FOR DUCT PASSAGE AND FIRE SAFING. COORDINATE WITH MEP FOR DUCT SIZES.
5. FURR AROUND ALL COLUMN PROTRUSIONS AS NEEDED UNLESS NOTED OTHERWISE.
6. EACH TELECOM ROOM TO HAVE NO CEILING. CONTRACTOR TO PRESERVE EXISTING FIRE
SUPPRESSION SYSTEMS.
GENERAL PLAN NOTES
2' x 2' ACOUSTICAL CEILING
GYPSUM BOARD CEILING OR
SOFFIT
2 x 2 LIGHT FIXTURE; REF
ELECTRICAL
CEILING HEIGHT, ABOVE
FINISH FLOOR
2 x 4 LIGHT FIXTURE; REF
ELECTRICAL
00'-00"
REFLECTED CEILING PLAN LEGEND
2' x 4' ACOUSTICAL CEILING
NEW RETURN AIR GRILLE;
REF MECHANICAL
NEW SUPPLY AIR DIFFUSER;
REF MECHANICAL
NEW EXHAUST AIR GRILLE;
REF MECHANICAL
SUSPENDED LIGHT FIXTURE;
REF ELECTRICAL
NOTE: ALL SYMBOLS MAY NOT BE USED.
EXISTING DIFFUSER; REF
MECHANICAL
EXISTING DOOR, FRAME AND
HARDWARE TO BE
DEMOLISHED
DEMOLITION FLOOR PLAN LEGEND
AREA NOT IN CONTRACT
EXISTING PARTITION TO BE
DEMOLISHED
EXISTING PARTITION TO
REMAIN
NOTE: ALL SYMBOLS MAY NOT BE USED.
EXISTING DOOR & FRAME TO
REMAIN
EXISTING WINDOW & FRAME
TO REMAIN
EXISTING WINDOW & FRAME
TO BE DEMOLISHED
ICRA CONSTRUCTION
BARRIER AND
CONSTRUCTION ACCESS
EXISTING 1 HR PARTITION
TO REMAIN
DEMOLISH EXISTING
FLOORING TO EXTENT
INDICATED
1. ALL EXISTING WALL DIMENSIONS ARE TO FINISH FACE, UNLESS NOTED OTHERWISE.
2. THE CONTRACTOR SHALL VERIFY DIMENSIONS OF AS-BUILT CONDITIONS, AND NOTIFY THE
ARCHITECT IN WRITING OF ANY DISCREPANCIES. ALL INFORMATION SHOWN ON THE
CONSTRUCTION DOCUMENTS IS BASED ON FIELD OBSERVATIONS AND/OR THE ORIGINAL
CONSTRUCTION DOCUMENTS OF THE FACILITY.
3. DO NOT REMOVE BARRIERS FROM WORK AREA UNTIL COMPLETED PROJECT AREA HAS BEEN
INSPECTED BY THE VA SAFETY OFFICER AND INFECTION CONTROL COORDINATOR AND
THOROUGHLY CLEANED BY ENVIRONMENTAL MANAGEMENT SERVICES
4. THE CONTRACTOR SHALL PROVIDE PROTECTIVE COVERING FOR EXISTING FLOOR, WALL AND
CEILING FINISHES IN EXISTING AREAS NOT DESIGNATED FOR DEMOLITION OR NEW
CONSTRUCTION. THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE REPAIR OF ANY DAMAGE
CAUSED BY HIS WORK OR ANY SUBCONTRACTOR.
5. THE CONTRACTOR SHALL VERIFY THAT NEW MECHANICAL SYSTEMS CAN BE INSTALLED IN
EXISTING SPACES TO CLEAR EXISTING CEILING AND OTHER CONSTRUCTED ITEMS AND
MAINTAIN FLOOR TO CEILING HEIGHTS INDICATED ON DRAWINGS. IF DISCREPANCIES OCCUR
DUE TO EXISTING CONDITIONS, CONSULT WITH THE ARCHITECT BEFORE PROCEEDING.
6. THE FINISH FACE OF MATERIAL OF NEW PARTITIONS SHALL ALIGN ON BOTH SIDES OF THE PARTITION WITH THE FACE OF THE MATERIALS ON EXISTING COLUMNS, WALLS, OR PARTITIONS, UNLESS NOTED OTHERWISE.
7. NO WORK TO BE DONE IN AREAS HATCHED GRAY IN PLANS, HOWEVER WORK MIGHT NEED TO
BE PERFORMED IN CEILING OR EXISTING CHASES THROUGHOUT BUILDING. REFERENCE
MECHANICAL AND ELECTRICAL DRAWINGS FOR EXTENT OF WORK. COORDINATE ACCESS TO
ROOMS OUTSIDE OF SCOPE WITH OWNER
GENERAL DEMOLITION NOTES
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project NumberCONSULTANTS:
Drawing #
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
ARCH FIRM REG. NO. 20314270 EXP. 06/30/2023
ENGR FIRM REG. NO. 06253 EXP. 06/30/2024
FIRE PROTECTION ENGR
POOLE FIRE PROTECTION
19910 WEST 161ST ST.
OLATHE, KANSAS 66062
(913) 829-8690
FULLY SPRINKLERED
INDUSTRIAL HYGENIST
RIVERFRONT (RSH)
1139 OLIVE ST, SUITE 300
ST. LOUIS, MO 63101
(713) 864-2900
STRUCT ENGR
STAND (SEI)
8234 ROBINSON ST
OVERLAND PARK, KS 66204
(913) 214-2169
COMMISSIONING
ES2
13401 N SANTE FE AVE
OKLAHOMA CITY, OK
(405) 528-4500
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
Drawing Number
Building Number
CONTROLLED UNCLASSIFED INFORMATION (CUI)
CONTROLLED UNCLASSIFED INFORMATION (CUI)
C O
N T
R O
L L
E D
U N
C L
A S
S
IF
E D
I N
F O
R M
A T
IO
N
C
U I)
TELECOMMUNICATION
ASPEN COMMUNICATIONS
7 KIJI-DAVA CIRCLE, STE A
PRESCOTT, AZ 86301
(928) 774-0992
MECH / ELEC / PLUMB ENGR
SPUR DESIGN
2519 MADISON AVE, STE 100
KANSAS CITY, MO 64108
(913) 369-7200
FORCE PROTECT
10901 FRONT BEACH RD, UNIT 1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
PHYSICAL SECURITY
/3
/2
:1 :4
P
M
ENLARGED PLANS - BLDG 1 - LEVEL 1 &
ZDL 11 OF 78BKM
FINAL BID DOCUMENTS
EHRM INFRASTRUCTURE
UPGRADES - TIER 2
06/02/2023
757-22-705
CHALMERS P. WYLIE VA
420 NORTH JAMES ROAD
COLUMBUS, OHIO 43219-1834
AE402
BLDG 1, ENERGY BLDG, & ENGR. BLDG
SPUR #: 1791.19
N
1/4" = 1'-0" 1/ AE101
BLDG 1 - LEVEL 1 - 1B609 - DEMO9
N
1/4" = 1'-0" 1/ AE101
BLDG 1 - LEVEL 1 - 1B609 - NEW10
N
1/4" = 1'-0"
BLDG 1 - LEVEL 1 - 1B609 - DEMO RCP11
N
1/4" = 1'-0"
BLDG 1 - LEVEL 1 - 1B609 - RCP12
N
1/4" = 1'-0" 1/ AE101
BLDG 1 - LEVEL 1 - 1B002 - NEW2
N
1/4" = 1'-0" 1/ AE101
BLDG 1 - LEVEL 1 - 1B002 - DEMO1
N
1/4" = 1'-0" 1/ AE101
BLDG 1 - LEVEL 1 - 1B006 - DEMO5
N
1/4" = 1'-0" 1/ AE101
BLDG 1 - LEVEL 1 - 1B006 - NEW6
N
1/4" = 1'-0"
BLDG 1 - LEVEL 1 - 1B006 - DEMO RCP7
N
1/4" = 1'-0"
BLDG 1 - LEVEL 1 - 1B006 - RCP8
N
1/4" = 1'-0"
BLDG 1 - LEVEL 1 - 1B002 - RCP4
N
1/4" = 1'-0"
BLDG 1 - LEVEL 1 - 1B002 - DEMO RCP3
N
1/4" = 1'-0" 4/ AE101
BLDG 1 - LEVEL 2 - 2A004 - DEMO13
N
1/4" = 1'-0" 4/ AE101
BLDG 1 - LEVEL 2 - 2A004 - NEW14
N
1/4" = 1'-0"
BLDG 1 - LEVEL 2 - 2A004 - DEMO RCP15
N
1/4" = 1'-0"
BLDG 1 - LEVEL 2 - 2A004 - RCP16
KEYNOTE LEGEND
2.05 DEMOLISH EXISTING DOOR AND FRAME IN ITS ENTIRETY
2.13 DEMOLISH EXISTING FLOORING AND BASE AND PREPARE SUBSURFACE FLOORING FOR NEW
TILE INSTALLATION
2.15 REMOVE EXISTING TELECOM AND ELECTRICAL EQUIPMENT PER ELECTRICAL AND TELECOM
DRAWINGS.
2.16 REMOVE EXISTING MECHANICAL EQUIPMENT PER MECHANICAL DRAWINGS.
2.17 EXISTING GROUND BAR TO REMAIN; SEE ELECTRICAL DRAWINGS.
2.18 PATCH AND REPAIR WALLS FOR PREPARATION OF NEW FINISH AFTER REMOVAL OF
EXISTING EQUIPMENT.
9.87 FLOOR FINISH AS SCHEDULED.
23.05 WALL-MOUNTED DUCTLESS SPLIT UNIT, SEE MECHANICAL DRAWINGS
101 SF
2B003
1'
-1
1/ 2"
F V
+/- 8'-5 3/4" FV
2.05
2.13
2.15
+/- 3'-4" FV
+/- 2'-6 3/4" FV
2.17
2.18
101 SF
TELECOM
2B003
2B
2'-7"
26.04 2.17
27.01
TYP
9.87
3'-4"1'-0"
6' -4
/2
3'
-0
91 SF
TELECOM
2B102
+/- 8'-11" FV
0'
-6
/4
F V
2.13
2.15
'-1
F
V
+/- 1'-4 1/2" FV
2.18
91 SF
TELECOM
2B102
26.0426.04
TYP
27.01
9.87
3'-5"1'-4"
5' -1
3'
-0
101 SF
TELECOM
2B003
EQ. EQ.
2.20
23.05
23.05
E Q
3'
-0
3' -0
3'
-0
E Q
101 SF
TELECOM
2B003
91 SF
TELECOM
2B102
TELECOM
2B102
EQ. EQ.
E Q
2'
-6
2' -6
2'
-6
E Q
23.05
23.05
120 SF
TELECOM
2A143
2.16
120 SF
TELECOM
2A143
E Q
E
Q
EQ. 3'-0" 3'-0" 3'-0" EQ.
23.05
23.05
120 SF
TELECOM
2A143
+/- 13'-3 1/4" FV
'-0
/4
F
V
2.05
2.13
2.15
2.17
+/- 3'-4" FV
+/- 2'-9 3/4" FV
2.18
120 SF
TELECOM
2A143
2A
2.17
27.01
9.87
3' -1
1/
2" 1'
-0
7'-9 1/2"3'-0"
103 SF
TELECOM
2A018
+/- 8'-9" FV
1'
-8
/4
F V
2.05 2.13
2.15
2.17
'-4
F
V
'-2
/2
F V
2.18
103 SF
TELECOM
2A018
2A018
26.04
27.01
TYP
TYP
2'-2" 2'-2 3/4"
9.87
1'-0"3'-7"
6' -3
3'
-0
103 SF
TELECOM
2A018
2.16
2.16
103 SF
TELECOM
2A018
E Q
3'
-0
3' -0
3'
-0
E Q
23.05
23.05
2.20
EQ. EQ.
SPOT ELEVATION HEIGHT,
ABOVE FINISH FLOOR
00'-00"
EXISTING 2' x 2' ACOUSTICAL
CEILING TO BE REMOVED
AND SALVAGED FOR
REINSTALLATION
EXISTING GYPSUM BOARD
CEILING
EXISTING 2 x 2 LIGHT FIXTURE
TO BE DEMOLISHED; REF
ELECTRICAL
EXISTING 2 x 4 LIGHT FIXTURE
TO BE DEMOLISHED; REF
ELECTRICAL
DEMOLITION REFELCTED CEILING PLAN LEGEND
EXISTING 2' x 4' ACOUSTICAL
CEILING TO BE REMOVED AND
SALVAGED FOR
REINSTALLATION
EXISTING RETURN AIR GRILLE
TO BE DEMOLISHED; REF
MECHANICAL
EXISTING SUPPLY AIR
DIFFUSER TO BE DEMOLISHED;
REF MECHANICAL
EXISTING EXHAUST AIR
GRILLE TO BE DEMOLISHED;
REF MECHANICAL
AREA NOT IN SCOPE
NOTE: ALL SYMBOLS MAY NOT BE USED.
EXISTING 2 x 2 LIGHT FIXTURE
TO BE REMOVED AND
RELOCATED; REF ELECTRICAL
EXISTING 2 x 4 LIGHT FIXTURE
TO BE REMOVED AND
RELOCATED; REF ELECTRICAL
EXISTING DIFFUSER TO
REMAIN; REF MECHANICAL
EXISTING 2' x 2' ACOUSTICAL
CEILING TO BE REMOVED
1. ALL DOOR FRAMES TO BE LOCATED 4" FROM OUTSIDE OF FRAME TO FINISH FACE OF ADJACENT
WALL UNLESS NOTED OTHERWISE.
2. REFER TO DOOR SCHEDULE & DETAILS SHEET (AE601) FOR DOOR INFORMATION.
3. ALL WALLS ARE DIMENSIONED TO CENTERLINE OF METAL STUD, UNLESS NOTED OTHERWISE.
4. BLOCK OUT SLAB FOR PENETRATIONS SHALL BE 2" LARGER THAN DUCT SIZE TO ALLOW
TOLERANCE FOR DUCT PASSAGE AND FIRE SAFING. COORDINATE WITH MEP FOR DUCT SIZES.
5. FURR AROUND ALL COLUMN PROTRUSIONS AS NEEDED UNLESS NOTED OTHERWISE.
6. EACH TELECOM ROOM TO HAVE NO CEILING. CONTRACTOR TO PRESERVE EXISTING FIRE
SUPPRESSION SYSTEMS.
GENERAL PLAN NOTES
2' x 2' ACOUSTICAL CEILING
GYPSUM BOARD CEILING OR
SOFFIT
2 x 2 LIGHT FIXTURE; REF
ELECTRICAL
CEILING HEIGHT, ABOVE
FINISH FLOOR
2 x 4 LIGHT FIXTURE; REF
ELECTRICAL
00'-00"
REFLECTED CEILING PLAN LEGEND
2' x 4' ACOUSTICAL CEILING
NEW RETURN AIR GRILLE;
REF MECHANICAL
NEW SUPPLY AIR DIFFUSER;
REF MECHANICAL
NEW EXHAUST AIR GRILLE;
REF MECHANICAL
SUSPENDED LIGHT FIXTURE;
REF ELECTRICAL
NOTE: ALL SYMBOLS MAY NOT BE USED.
EXISTING DIFFUSER; REF
MECHANICAL
EXISTING DOOR, FRAME AND
HARDWARE TO BE
DEMOLISHED
DEMOLITION FLOOR PLAN LEGEND
AREA NOT IN CONTRACT
EXISTING PARTITION TO BE
DEMOLISHED
EXISTING PARTITION TO
REMAIN
NOTE: ALL SYMBOLS MAY NOT BE USED.
EXISTING DOOR & FRAME TO
REMAIN
EXISTING WINDOW & FRAME
TO REMAIN
EXISTING WINDOW & FRAME
TO BE DEMOLISHED
ICRA CONSTRUCTION
BARRIER AND
CONSTRUCTION ACCESS
EXISTING 1 HR PARTITION
TO REMAIN
DEMOLISH EXISTING
FLOORING TO EXTENT
INDICATED
1. ALL EXISTING WALL DIMENSIONS ARE TO FINISH FACE, UNLESS NOTED OTHERWISE.
2. THE CONTRACTOR SHALL VERIFY DIMENSIONS OF AS-BUILT CONDITIONS, AND NOTIFY THE
ARCHITECT IN WRITING OF ANY DISCREPANCIES. ALL INFORMATION SHOWN ON THE
CONSTRUCTION DOCUMENTS IS BASED ON FIELD OBSERVATIONS AND/OR THE ORIGINAL
CONSTRUCTION DOCUMENTS OF THE FACILITY.
3. DO NOT REMOVE BARRIERS FROM WORK AREA UNTIL COMPLETED PROJECT AREA HAS BEEN
INSPECTED BY THE VA SAFETY OFFICER AND INFECTION CONTROL COORDINATOR AND
THOROUGHLY CLEANED BY ENVIRONMENTAL MANAGEMENT SERVICES
4. THE CONTRACTOR SHALL PROVIDE PROTECTIVE COVERING FOR EXISTING FLOOR, WALL AND
CEILING FINISHES IN EXISTING AREAS NOT DESIGNATED FOR DEMOLITION OR NEW
CONSTRUCTION. THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE REPAIR OF ANY DAMAGE
CAUSED BY HIS WORK OR ANY SUBCONTRACTOR.
5. THE CONTRACTOR SHALL VERIFY THAT NEW MECHANICAL SYSTEMS CAN BE INSTALLED IN
EXISTING SPACES TO CLEAR EXISTING CEILING AND OTHER CONSTRUCTED ITEMS AND
MAINTAIN FLOOR TO CEILING HEIGHTS INDICATED ON DRAWINGS. IF DISCREPANCIES OCCUR
DUE TO EXISTING CONDITIONS, CONSULT WITH THE ARCHITECT BEFORE PROCEEDING.
6. THE FINISH FACE OF MATERIAL OF NEW PARTITIONS SHALL ALIGN ON BOTH SIDES OF THE PARTITION WITH THE FACE OF THE MATERIALS ON EXISTING COLUMNS, WALLS, OR PARTITIONS, UNLESS NOTED OTHERWISE.
7. NO WORK TO BE DONE IN AREAS HATCHED GRAY IN PLANS, HOWEVER WORK MIGHT NEED TO
BE PERFORMED IN CEILING OR EXISTING CHASES THROUGHOUT BUILDING. REFERENCE
MECHANICAL AND ELECTRICAL DRAWINGS FOR EXTENT OF WORK. COORDINATE ACCESS TO
ROOMS OUTSIDE OF SCOPE WITH OWNER
GENERAL DEMOLITION NOTES
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project NumberCONSULTANTS:
Drawing #
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
ARCH FIRM REG. NO. 20314270 EXP. 06/30/2023
ENGR FIRM REG. NO. 06253 EXP. 06/30/2024
FIRE PROTECTION ENGR
POOLE FIRE PROTECTION
19910 WEST 161ST ST.
OLATHE, KANSAS 66062
(913) 829-8690
FULLY SPRINKLERED
INDUSTRIAL HYGENIST
RIVERFRONT (RSH)
1139 OLIVE ST, SUITE 300
ST. LOUIS, MO 63101
(713) 864-2900
STRUCT ENGR
STAND (SEI)
8234 ROBINSON ST
OVERLAND PARK, KS 66204
(913) 214-2169
COMMISSIONING
ES2
13401 N SANTE FE AVE
OKLAHOMA CITY, OK
(405) 528-4500
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
Drawing Number
Building Number
CONTROLLED UNCLASSIFED INFORMATION (CUI)
CONTROLLED UNCLASSIFED INFORMATION (CUI)
C O
N T
R O
L L
E D
U N
C L
A S
S
IF
E D
I N
F O
R M
A T
IO
N
C
U I)
TELECOMMUNICATION
ASPEN COMMUNICATIONS
7 KIJI-DAVA CIRCLE, STE A
PRESCOTT, AZ 86301
(928) 774-0992
MECH / ELEC / PLUMB ENGR
SPUR DESIGN
2519 MADISON AVE, STE 100
KANSAS CITY, MO 64108
(913) 369-7200
FORCE PROTECT
10901 FRONT BEACH RD, UNIT 1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
PHYSICAL SECURITY
/3
/2
:1 :5
P
M
ENLARGED PLANS - BLDG 1 - LEVEL 2
ZDL 12 OF 78BKM
FINAL BID DOCUMENTS
EHRM INFRASTRUCTURE
UPGRADES - TIER 2
06/02/2023
757-22-705
CHALMERS P. WYLIE VA
420 NORTH JAMES ROAD
COLUMBUS, OHIO 43219-1834
AE403
BLDG 1, ENERGY BLDG, & ENGR. BLDG
SPUR #: 1791.19
N
1/4" = 1'-0" 4/ AE101
BLDG 1 - LEVEL 2 - 2B003 - DEMO9
N
1/4" = 1'-0" 4/ AE101
BLDG 1 - LEVEL 2 - 2B003 - NEW10
N
1/4" = 1'-0" 4/ AE101
BLDG 1 - LEVEL 2 - 2B102 - DEMO13
N
1/4" = 1'-0" 4/ AE101
BLDG 1 - LEVEL 2 - 2B102 - NEW14
N
1/4" = 1'-0"
BLDG 1 - LEVEL 2 - 2B003 - RCP12
N
1/4" = 1'-0"
BLDG 1 - LEVEL 2 - 2B003 - DEMO RCP11
N
1/4" = 1'-0"
BLDG 1 - LEVEL 2 - 2B102 - DEMO RCP15
N
1/4" = 1'-0"
BLDG 1 - LEVEL 2 - 2B102 - RCP16
N
1/4" = 1'-0"
BLDG 1 - LEVEL 2 - 2A143 - DEMO RCP7
N
1/4" = 1'-0"
BLDG 1 - LEVEL 2 - 2A143 - RCP8
N
1/4" = 1'-0" 4/ AE101
BLDG 1 - LEVEL 2 - 2A143 - DEMO5
N
1/4" = 1'-0" 4/ AE101
BLDG 1 - LEVEL 2 - 2A143 - NEW6
N
1/4" = 1'-0" 4/ AE101
BLDG 1 - LEVEL 2 - 2A018 - DEMO1
N
1/4" = 1'-0" 4/ AE101
BLDG 1 - LEVEL 2 - 2A018 - NEW2
N
1/4" = 1'-0"
BLDG 1 - LEVEL 2 - 2A018 - DEMO RCP3
N
1/4" = 1'-0"
BLDG 1 - LEVEL 2 - 2A018 - RCP4
KEYNOTE LEGEND
2.05 DEMOLISH EXISTING DOOR AND FRAME IN ITS ENTIRETY
2.13 DEMOLISH EXISTING FLOORING AND BASE AND PREPARE SUBSURFACE FLOORING FOR NEW
TILE INSTALLATION
2.15 REMOVE EXISTING TELECOM AND ELECTRICAL EQUIPMENT PER ELECTRICAL AND TELECOM
DRAWINGS.
2.16 REMOVE EXISTING MECHANICAL EQUIPMENT PER MECHANICAL DRAWINGS.
2.17 EXISTING GROUND BAR TO REMAIN; SEE ELECTRICAL DRAWINGS.
2.18 PATCH AND REPAIR WALLS FOR PREPARATION OF NEW FINISH AFTER REMOVAL OF
EXISTING EQUIPMENT.
2.20 EXISTING MECHANICAL EQUIPMENT TO REMAIN, SEE MECHANICAL DRAWINGS.
9.87 FLOOR FINISH AS SCHEDULED.
23.05 WALL-MOUNTED DUCTLESS SPLIT UNIT, SEE MECHANICAL DRAWINGS
115 SF
3A063
8' -8
/2
F
V
13'-3" FV
2.05
2.13
2.15
+/- 3'-4" FV +/- 2'-10" FV
2.17
2.18
115 SF
TELECOM
3A063
3A
2'-10"2.17
9.87
3'-0" 7'-9"
3' -0
1'
-6
/2
TELECOM
3A004
+/- 12'-2" FV
'-2
/4
F
V
2.05
2.13
2.15
+/- 2'-2" FV +/- 3'-8" FV
2.17
2.18
100 SF
TELECOM
3A004
3A
2.17
26.04
27.01
2'-2"
9.87
26.04 26.04
1' -0
3'-0"6'-8"
3' -0
/2
102 SF
TELECOM
3A015
1'
-7
/2
F V
+/- 8'-9 1/4" FV
2.05 2.13
2.15+
'-4
F
V
'-0
/4
F V
2.17
2.18
102 SF
TELECOM
3A015
3A015
26.04 2.17
27.01
9.87
1'-0"3'-7"
6' -1
/2
3'
-0
100 SF
TELECOM
3A004 2.16
2.16
100 SF
TELECOM
3A004
EQ. 3'-0" 3'-0" 3'-0" EQ.
E Q
E
Q
2.20
23.05
23.05
102 SF
TELECOM
3A015
2.16
2.16
102 SF
TELECOM
3A015
EQ. EQ.
E Q
3'
-0
3' -0
3'
-0
E Q
23.05
23.05
115 SF
TELECOM
3A063
EQ. 3'-0" 3'-0" 3'-0" EQ.
E Q
E
Q
23.05 23.05
115 SF
TELECOM
3A063
2.16
100 SF
TELECOM
2B310
EQ. 5'-6" EQ.
E Q
4'
-0
E Q
.23.05
100 SF
TELECOM
2B310
100 SF
TELECOM
2B310
2'
-7
F V
+/- 8'-0" FV
2.13
2.15
2.17
2.18
100 SF
TELECOM
2B310
2.17
26.04
27.01
9.87
23.04
1'-0" 2'-10"3' -0
SPOT ELEVATION HEIGHT,
ABOVE FINISH FLOOR
00'-00"
EXISTING 2' x 2' ACOUSTICAL
CEILING TO BE REMOVED
AND SALVAGED FOR
REINSTALLATION
EXISTING GYPSUM BOARD
CEILING
EXISTING 2 x 2 LIGHT FIXTURE
TO BE DEMOLISHED; REF
ELECTRICAL
EXISTING 2 x 4 LIGHT FIXTURE
TO BE DEMOLISHED; REF
ELECTRICAL
DEMOLITION REFELCTED CEILING PLAN LEGEND
EXISTING 2' x 4' ACOUSTICAL
CEILING TO BE REMOVED AND
SALVAGED FOR
REINSTALLATION
EXISTING RETURN AIR GRILLE
TO BE DEMOLISHED; REF
MECHANICAL
EXISTING SUPPLY AIR
DIFFUSER TO BE DEMOLISHED;
REF MECHANICAL
EXISTING EXHAUST AIR
GRILLE TO BE DEMOLISHED;
REF MECHANICAL
AREA NOT IN SCOPE
NOTE: ALL SYMBOLS MAY NOT BE USED.
EXISTING 2 x 2 LIGHT FIXTURE
TO BE REMOVED AND
RELOCATED; REF ELECTRICAL
EXISTING 2 x 4 LIGHT FIXTURE
TO BE REMOVED AND
RELOCATED; REF ELECTRICAL
EXISTING DIFFUSER TO
REMAIN; REF MECHANICAL
EXISTING 2' x 2' ACOUSTICAL
CEILING TO BE REMOVED
1. ALL DOOR FRAMES TO BE LOCATED 4" FROM OUTSIDE OF FRAME TO FINISH FACE OF ADJACENT
WALL UNLESS NOTED OTHERWISE.
2. REFER TO DOOR SCHEDULE & DETAILS SHEET (AE601) FOR DOOR INFORMATION.
3. ALL WALLS ARE DIMENSIONED TO CENTERLINE OF METAL STUD, UNLESS NOTED OTHERWISE.
4. BLOCK OUT SLAB FOR PENETRATIONS SHALL BE 2" LARGER THAN DUCT SIZE TO ALLOW
TOLERANCE FOR DUCT PASSAGE AND FIRE SAFING. COORDINATE WITH MEP FOR DUCT SIZES.
5. FURR AROUND ALL COLUMN PROTRUSIONS AS NEEDED UNLESS NOTED OTHERWISE.
6. EACH TELECOM ROOM TO HAVE NO CEILING. CONTRACTOR TO PRESERVE EXISTING FIRE
SUPPRESSION SYSTEMS.
GENERAL PLAN NOTES
2' x 2' ACOUSTICAL CEILING
GYPSUM BOARD CEILING OR
SOFFIT
2 x 2 LIGHT FIXTURE; REF
ELECTRICAL
CEILING HEIGHT, ABOVE
FINISH FLOOR
2 x 4 LIGHT FIXTURE; REF
ELECTRICAL
00'-00"
REFLECTED CEILING PLAN LEGEND
2' x 4' ACOUSTICAL CEILING
NEW RETURN AIR GRILLE;
REF MECHANICAL
NEW SUPPLY AIR DIFFUSER;
REF MECHANICAL
NEW EXHAUST AIR GRILLE;
REF MECHANICAL
SUSPENDED LIGHT FIXTURE;
REF ELECTRICAL
NOTE: ALL SYMBOLS MAY NOT BE USED.
EXISTING DIFFUSER; REF
MECHANICAL
EXISTING DOOR, FRAME AND
HARDWARE TO BE
DEMOLISHED
DEMOLITION FLOOR PLAN LEGEND
AREA NOT IN CONTRACT
EXISTING PARTITION TO BE
DEMOLISHED
EXISTING PARTITION TO
REMAIN
NOTE: ALL SYMBOLS MAY NOT BE USED.
EXISTING DOOR & FRAME TO
REMAIN
EXISTING WINDOW & FRAME
TO REMAIN
EXISTING WINDOW & FRAME
TO BE DEMOLISHED
ICRA CONSTRUCTION
BARRIER AND
CONSTRUCTION ACCESS
EXISTING 1 HR PARTITION
TO REMAIN
DEMOLISH EXISTING
FLOORING TO EXTENT
INDICATED
1. ALL EXISTING WALL DIMENSIONS ARE TO FINISH FACE, UNLESS NOTED OTHERWISE.
2. THE CONTRACTOR SHALL VERIFY DIMENSIONS OF AS-BUILT CONDITIONS, AND NOTIFY THE
ARCHITECT IN WRITING OF ANY DISCREPANCIES. ALL INFORMATION SHOWN ON THE
CONSTRUCTION DOCUMENTS IS BASED ON FIELD OBSERVATIONS AND/OR THE ORIGINAL
CONSTRUCTION DOCUMENTS OF THE FACILITY.
3. DO NOT REMOVE BARRIERS FROM WORK AREA UNTIL COMPLETED PROJECT AREA HAS BEEN
INSPECTED BY THE VA SAFETY OFFICER AND INFECTION CONTROL COORDINATOR AND
THOROUGHLY CLEANED BY ENVIRONMENTAL MANAGEMENT SERVICES
4. THE CONTRACTOR SHALL PROVIDE PROTECTIVE COVERING FOR EXISTING FLOOR, WALL AND
CEILING FINISHES IN EXISTING AREAS NOT DESIGNATED FOR DEMOLITION OR NEW
CONSTRUCTION. THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE REPAIR OF ANY DAMAGE
CAUSED BY HIS WORK OR ANY SUBCONTRACTOR.
5. THE CONTRACTOR SHALL VERIFY THAT NEW MECHANICAL SYSTEMS CAN BE INSTALLED IN
EXISTING SPACES TO CLEAR EXISTING CEILING AND OTHER CONSTRUCTED ITEMS AND
MAINTAIN FLOOR TO CEILING HEIGHTS INDICATED ON DRAWINGS. IF DISCREPANCIES OCCUR
DUE TO EXISTING CONDITIONS, CONSULT WITH THE ARCHITECT BEFORE PROCEEDING.
6. THE FINISH FACE OF MATERIAL OF NEW PARTITIONS SHALL ALIGN ON BOTH SIDES OF THE PARTITION WITH THE FACE OF THE MATERIALS ON EXISTING COLUMNS, WALLS, OR PARTITIONS, UNLESS NOTED OTHERWISE.
7. NO WORK TO BE DONE IN AREAS HATCHED GRAY IN PLANS, HOWEVER WORK MIGHT NEED TO
BE PERFORMED IN CEILING OR EXISTING CHASES THROUGHOUT BUILDING. REFERENCE
MECHANICAL AND ELECTRICAL DRAWINGS FOR EXTENT OF WORK. COORDINATE ACCESS TO
ROOMS OUTSIDE OF SCOPE WITH OWNER
GENERAL DEMOLITION NOTES
th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project NumberCONSULTANTS:
Drawing #
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
ARCH FIRM REG. NO. 20314270 EXP. 06/30/2023
ENGR FIRM REG. NO. 06253 EXP. 06/30/2024
FIRE PROTECTION ENGR
POOLE FIRE PROTECTION
19910 WEST 161ST ST.
OLATHE, KANSAS 66062
(913) 829-8690
FULLY SPRINKLERED
INDUSTRIAL HYGENIST
RIVERFRONT (RSH)
1139 OLIVE ST, SUITE 300
ST. LOUIS, MO 63101
(713) 864-2900
STRUCT ENGR
STAND (SEI)
8234 ROBINSON ST
OVERLAND PARK, KS 66204
(913) 214-2169
COMMISSIONING
ES2
13401 N SANTE FE AVE
OKLAHOMA CITY, OK
(405) 528-4500
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
Drawing Number
Building Number
CONTROLLED UNCLASSIFED INFORMATION (CUI)
CONTROLLED UNCLASSIFED INFORMATION (CUI)
C O
N T
R O
L L
E D
U N
C L
A S
S
IF
E D
I N
F O
R M
A T
IO
N
C
U I)
TELECOMMUNICATION
ASPEN COMMUNICATIONS
7 KIJI-DAVA CIRCLE, STE A
PRESCOTT, AZ 86301
(928) 774-0992
MECH / ELEC / PLUMB ENGR
SPUR DESIGN
2519 MADISON AVE, STE 100
KANSAS CITY, MO 64108
(913) 369-7200
FORCE PROTECT
10901 FRONT BEACH RD, UNIT 1415
PANAMA CITY BEACH, FL 32407
(502) 836-4232
PHYSICAL SECURITY
/3
/2
:1 :5
P
M
ENLARGED PLANS - BLDG 1 - LEVEL 2 &
ZDL 13 OF 78BKM
FINAL BID DOCUMENTS
EHRM INFRASTRUCTURE
UPGRADES - TIER 2
06/02/2023
757-22-705
CHALMERS P. WYLIE VA
420 NORTH JAMES ROAD
COLUMBUS, OHIO 43219-1834
AE404
BLDG 1, ENERGY BLDG, & ENGR. BLDG
SPUR #: 1791.19
N
1/4" = 1'-0" 1/ AE102
BLDG 1 - LEVEL 3 - 3A063 - DEMO13
N
1/4" = 1'-0" 1/ AE102
BLDG 1 - LEVEL 3 - 3A063 - NEW14
N
1/4" = 1'-0" 1/ AE102
BLDG 1 - LEVEL 3 - 3A004 - DEMO5
N
1/4" = 1'-0" 1/ AE102
BLDG 1 - LEVEL 3 - 3A004 - NEW6
N
1/4" = 1'-0" 1/ AE102
BLDG 1 - LEVEL 3 - 3A015 - DEMO9
N
1/4" = 1'-0" 1/ AE102
BLDG 1 - LEVEL 3 - 3A015 - NEW10
N
1/4" = 1'-0"
BLDG 1 - LEVEL 3 - 3A004 - DEMO RCP7
N
1/4" = 1'-0"
BLDG 1 - LEVEL 3 - 3A004 - RCP8
N
1/4" = 1'-0"
BLDG 1 - LEVEL 3 - 3A015 - DEMO RCP11
N
1/4" = 1'-0"
BLDG 1 - LEVEL 3 - 3A015 - RCP12
N
1/4" = 1'-0"
BLDG 1 - LEVEL 3 - 3A063 - RCP16
N
1/4" = 1'-0"
BLDG 1 - LEVEL 3 - 3A063 - DEMO RCP15
N
1/4" = 1'-0"
BLDG 1 - LEVEL 2 - 2B310 - RCP4
N
1/4" = 1'-0"
BLDG 1 - LEVEL 2 - 2B310 - DEMO RCP3
N
1/4" = 1'-0" 4/ AE101
BLDG 1 - LEVEL 2 - 2B310 - DEMO1
N
1/4" = 1'-0" 4/ AE101
BLDG 1 - LEVEL 2 - 2B310 - NEW2
KEYNOTE LEGEND
2.05 DEMOLISH EXISTING DOOR AND FRAME IN ITS ENTIRETY
2.13 DEMOLISH EXISTING FLOORING AND BASE AND PREPARE SUBSURFACE FLOORING FOR NEW
TILE INSTALLATION
2.15 REMOVE EXISTING TELECOM AND ELECTRICAL EQUIPMENT PER ELECTRICAL AND TELECOM
DRAWINGS.
2.16 REMOVE EXISTING MECHANICAL EQUIPMENT PER MECHANICAL DRAWINGS.
2.17 EXISTING GROUND BAR TO REMAIN; SEE ELECTRICAL DRAWINGS.
2.18 PATCH AND REPAIR WALLS FOR PREPARATION OF NEW FINISH AFTER REMOVAL OF
EXISTING EQUIPMENT.
2.20 EXISTING MECHANICAL EQUIPMENT TO REMAIN, SEE MECHANICAL DRAWINGS.
9.87 FLOOR FINISH AS SCHEDULED.
23.04 MECHANICAL EQUIPMENT, SEE MECHANICAL DRAWINGS
23.05 WALL-MOUNTED DUCTLESS SPLIT UNIT, SEE MECHANICAL DRAWINGS
119 SF
4A041
+/- 13'-3 1/2" FV
'-0
/4
F
V
2.05
2.13
2.15
+/- 3'-4" FV
+/- 1'-0" FV
2.17
2.18
119 SF
TELECOM
4A041
4A
2.17
27.01
9.87 1'
-0
3' -1
0"
3'-0" 7'-9 1/2"
119 SF
TELECOM
4A041
2.162.16
119 SF
TELECOM
4A041
E Q
E
Q
EQ. 3'-0" 3'-0" 3'-0" EQ.
2.20
23.05
23.05
2.20
105 SF
TELECOM
'-8
F
V
+/- 13'-8" FV
2.05
2.13
2.15
'-4
F
V
/2
F V
2.18
105 SF
TELECOM
1/
2"
27.01
TYP26.04
9.87
1' -0
4'
-8
/2
5'-8"5'-6 1/2"
105 SF
TELECOM
EQ. 8'-6" EQ.
E Q
E
Q
23.05
23.05
105 SF
TELECOM
104 2.16
56 SF
TELECOM
- 7
'-0
/4
F V
+/- 7'-11 1/2" FV
2.05 2.13
2.15
+/- 3'-4" FV
2.18
56 SF
TELECOM
26.04
27.02
9.87
4' -6
56 SF
TELECOM
EQ.
EQ.
E Q
3'
-9
E Q
23.05
56 SF
TELECOM
2.16
SPOT ELEVATION HEIGHT,
ABOVE FINISH FLOOR
00'-00"
EXISTING 2' x 2' ACOUSTICAL
CEILING TO BE REMOVED
AND SALVAGED FOR
REINSTALLATION
EXISTING GYPSUM BOARD
CEILING
EXISTING 2 x 2 LIGHT FIXTURE
TO BE DEMOLISHED; REF
ELECTRICAL
EXISTING 2 x 4 LIGHT FIXTURE
TO BE DEMOLISHED; REF
ELECTRICAL
DEMOLITION REFELCTED CEILING PLAN LEGEND
EXISTING 2' x 4' ACOUSTICAL
CEILING TO BE REMOVED AND
SALVAGED FOR
REINSTALLATION
EXISTING RETURN AIR GRILLE
TO BE DEMOLISHED; REF
MECHANICAL
EXISTING SUPPLY AIR
DIFFUSER TO BE DEMOLISHED;
REF MECHANICAL
EXISTING EXHAUST AIR
GRILLE TO BE DEMOLISHED;
REF MECHANICAL
AREA NOT IN SCOPE
NOTE: ALL SYMBOLS MAY NOT BE USED.
EXISTING 2 x 2 LIGHT FIXTURE
TO BE REMOVED AND
RELOCATED; REF ELECTRICAL
EXISTING 2 x 4 LIGHT FIXTURE
TO BE REMOVED AND
RELOCATED; REF ELECTRICAL
EXISTING DIFFUSER TO
REMAIN; REF MECHANICAL
EXISTING 2' x 2' ACOUSTICAL
CEILING TO BE REMOVED
1. ALL DOOR FRAMES TO BE LOCATED 4" FROM OUTSIDE OF FRAME TO FINISH FACE OF ADJACENT
WALL UNLESS NOTED OTHERWISE.
2. REFER TO DOOR SCHEDULE & DETAILS SHEET (AE601) FOR DOOR INFORMATION.
3. ALL WALLS ARE DIMENSIONED TO CENTERLINE OF METAL STUD, UNLESS NOTED OTHERWISE.
4. BLOCK OUT SLAB FOR PENETRATIONS SHALL BE 2" LARGER THAN DUCT SIZE TO ALLOW
TOLERANCE FOR DUCT PASSAGE AND FIRE SAFING. COORDINATE WITH MEP FOR DUCT SIZES.
5. FURR AROUND ALL COLUMN PROTRUSIONS AS NEEDED UNLESS NOTED OTHERWISE.
6. EACH TELECOM ROOM TO HAVE NO CEILING. CONTRACTOR TO PRESERVE EXISTING FIRE
SUPPRESSION SYSTEMS.
GENERAL PLAN NOTES
2' x 2' ACOUSTICAL CEILING
GYPSUM BOARD CEILING OR
SOFFIT
2 x 2 LIGHT FIXTURE; REF
ELECTRICAL
CEILING HEIGHT, ABOVE
FINISH FLOOR
2 x 4 LIGHT FIXTURE; REF
ELECTRICAL
00'-00"
REFLECTED CEILING PLAN LEGEND
2' x 4' ACOUSTICAL CEILING
NEW RETURN AIR GRILLE;
REF MECHANICAL
NEW SUPPLY AIR DIFFUSER;
REF MECHANICAL
NEW EXHAUST AIR GRILLE;
REF MECHANICAL
SUSPENDED LIGHT FIXTURE;
REF ELECTRICAL
NOTE: ALL SYMBOLS MAY NOT BE USED.
EXISTING DIFFUSER; REF
MECHANICAL
EXISTING DOOR, FRAME AND
HARDWARE TO BE
DEMOLISHED
DEMOLITION FLOOR PLAN LEGEND
AREA NOT IN CONTRACT
EXISTING PARTITION TO BE
DEMOLISHED
EXISTING PARTITION TO
REMAIN
NOTE: ALL SYMBOLS MAY NOT BE USED.
EXISTING DOOR & FRAME TO
REMAIN
EXISTING WINDOW & FRAME
TO REMAIN
EXISTING WINDOW & FRAME
TO BE DEMOLISHED
ICRA CONSTRUCTION
BARRIER AND
CONSTRUCTION ACCESS
EXISTING 1 HR PARTITION
TO REMAIN
DEMOLISH EXISTING
FLOORING TO EXTENT
INDICATED
1. ALL EXISTING WALL DIMENSIONS ARE TO FINISH FACE, UNLESS NOTED OTHERWISE.
2. THE CONTRACTOR SHALL VERIFY DIMENSIONS OF AS-BUILT CONDITIONS, AND NOTIFY THE
ARCHITECT IN WRITING OF ANY DISCREPANCIES. ALL INFORMATION SHOWN ON THE
CONSTRUCTION DOCUMENTS IS BASED ON FIELD OBSERVATIONS AND/OR THE ORIGINAL
CONSTRUCTION DOCUMENTS OF THE FACILITY.
3. DO NOT REMOVE BARRIERS FROM WORK AREA UNTIL COMPLETED PROJECT AREA HAS BEEN
INSPECTED BY THE VA SAFETY…