About this file

This document outlines electrical plans and specifications for infrastructure upgrades at the Chalmers P. Wylie VA Medical Center in Columbus, Ohio. The project involves upgrading electrical systems in Building 1 as well as the Energy Building and Engineering Building on the campus. Work includes replacing electrical panels and switchgear, upgrading UPS systems and emergency power supplies, installing new lighting and power circuits, and reconfiguring electrical distribution throughout the medical center. The solicitation number for the construction contract is 36C77623R0150 and is being procured by the VA Technology Acquisition Center in Austin, Texas on behalf of the Chalmers P. Wylie VA Medical Center. The contract award date is not specified but response dates and other details are not provided.

View the file

Other files

File Type Posted
Amd 11 Att - RFI Responses_3.12.24.pdf PDF
36C77623R0150 0011.docx DOCX document
36C77623R0150 0010.docx DOCX document
Amd 10_1791.19 - RFI Responses_3.11.24.pdf PDF
Amd 10 23 07 11 HVAC and Boiler Plant Insulation2.pdf PDF
36C77623R0150 0009.docx DOCX document
36C77623R0150 0008.docx DOCX document
OIT Infrastructure Standard for Telecommunications Spaces - Version 3.1.pdf PDF
36C77623R0150 0007.docx DOCX document
Amendment 6 All Files.zip ZIP file
36C77623R0150 0006.docx DOCX document
36C77623R0150 0005.docx DOCX document
36C77623R0150 0004.docx DOCX document
757-22-705 Pre-Bid Site Visit Sign In.pdf PDF
04_Architectural.pdf PDF
36C77623R0150 0003.docx DOCX document
02_Hazardous Materials.pdf PDF
01_General.pdf PDF
06_Mechanical_Drawings.pdf PDF
03_Structural.pdf PDF
08_Telecom.pdf PDF
05_Fire Protection.pdf PDF
Columbus EHRM FINAL SPECS VOL 1.pdf PDF
Columbus EHRM FINAL SPECS VOL 2.pdf PDF
36C77623R0150 0002.docx DOCX document
36C77623R0150 0001.docx DOCX document
Attachment 15 -Site Visit Instructions Revised.docx DOCX document
Attachment 11 - 07_Narrative_Electrical.pdf PDF
Attachment 9 - 05_Narrative_Fire Protection.pdf PDF
Attachment 6 - 01_Narrative_Architectural.pdf PDF
Attachment 2 - Contractor Safety - Environmental Form.docx DOCX document
Attachment 13- Wage Rates.pdf PDF
Attachment 8 - 03_Narrative_Structural (1).pdf PDF
Attachment 15 -Site Visit Instructions.docx DOCX document
36C77623R0150_1.docx DOCX document
Attachment 14 - EHRM FULL SET 07122023.pdf PDF
Attachment 4 - EHRM Columbus Drawings Part 2.pdf PDF
Attachment 12 - 09_Narrative_Telecom.pdf PDF
Attachment 16- VA Engineering Map.pdf PDF
Attachment 3 - EHRM Columbus Drawings Part 1.pdf PDF
Attachment 10 - 06_Narrative_Mechanical.pdf PDF
Attachment 1- Limitations on Subcontracting - Construction.docx DOCX document
Attachment 5 - EHRM Columbus Drawings Part 3.pdf PDF
Attachment 7 - 02_Narrative_Environmental.pdf PDF
Show all 44

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

UE

OE

M/G 400A/3P

M/G 400A/3P

C

PC

R

TS

T

100/3

100/3/70

100/3/70/1

100/3/CB

PP

J

GF

OR

OR

OR

EPO

AM

VM

DM

ST

KK

GFR

M

SPD

R

LP1

1,3,5

A1

LIGHT FIXTURE, CEILING MOUNTED

A1 = LIGHT FIXTURE TYPE "A1E" REFER TO LIGHT

FIXTURE SCHEDULE

a = SWITCHED BY SWITCH "a"

NL = NIGHT LIGHT

= ARROW INDICATES AIMING DIRECTION

a

LIGHTING TRACK WITH TRACK LIGHT FIXTURES

A1E = LIGHT FIXTURE TYPE "A1E" REFER TO LIGHT

FIXTURE SCHEDULE

a = SWITCHED BY SWITCH "a"

LIGHT FIXTURE, POLE MOUNTED

A1 = LIGHT FIXTURE TYPE "A1" REFER TO LIGHT

FIXTURE SCHEDULE

LIGHT FIXTURE, WALL MOUNTED

A1 = LIGHT FIXTURE TYPE "A1" REFER TO LIGHT

FIXTURE SCHEDULE

EMERGENCY BATTERY PACK LIGHT FIXTURE,

WALL MOUNTED

Y1E = LIGHT FIXTURE TYPE "Y1E" REFER TO LIGHT

FIXTURE SCHEDULe

EMERGENCY BATTERY PACK LIGHT FIXTURE,

CEILING MOUNTED

Y1E = LIGHT FIXTURE TYPE "Y1E" REFER TO LIGHT

FIXTURE SCHEDULE

EXIT SIGN, WALL MOUNTED, FACE/ARROWS AS INDICATED

X1E = LIGHT FIXTURE TYPE "X1E" REFER TO LIGHT

FIXTURE SCHEDULE

EXIT SIGN, CEILING MOUNTED, FACE/ARROWS AS INDICATED

X1E = LIGHT FIXTURE TYPE "X1E" REFER TO LIGHT

FIXTURE SCHEDULE

EMERGENCY LIGHT FIXTURE, CEILING MOUNTED

A1E = LIGHT FIXTURE TYPE "A1E" REFER TO LIGHT

FIXTURE SCHEDULE

a = SWITCHED BY SWITCH "a"

NL = NIGHT LIGHT

A1E a

A1 a

A1

A1

X1E

X1E

Y1E

Y1E

HOMERUN TO PANELBOARD

TICK MARKS INDICATE NUMBER OF CONDUCTORS.

DESIGNATIONS ARE PANELBOARD AND

CIRCUIT NUMBERS.

UNSWITCHED HOT CONDUCTORS SHOWN LEADING

NEUTRAL CONDUCTOR

NEUTRAL CONDUCTOR

SWITCHED HOT CONDUCTORS SHOWN TRAILING

GROUND CONDUCTOR

EQUIPMENT GROUNDING CONDUCTOR IN RACEWAY

ISOLATED GROUNDING CONDUCTOR IN RACEWAY

CONCEALED RACEWAY

EXPOSED RACEWAY

RACEWAY TURNING DOWN

RACEWAY TURNING UP

EQUIPMENT TERMINATION

LOW VOLTAGE CABLE (NOT ROUTED IN CONDUIT)

LIGHT FIXTURE, BOLLARD

A1 = LIGHT FIXTURE TYPE "A1" REFER TO LIGHT

FIXTURE SCHEDULE

A1

RECEPTACLE, SIMPLEX, NEMA 5-20R, UNO

RECEPTACLE, DUPLEX, NEMA 5-20R, UNO

RECEPTACLE, DOUBLE-DUPLEX, NEMA 5-20R, UNO

RECEPTACLE, DUPLEX, CEILING MOUNTED, NEMA 5-20R, UNO

RECEPTACLE, SPECIAL PURPOSE

RECEPTACLE, TWIST-LOCK

RECEPTACLE, DUPLEX, FLOOR MOUNTED, NEMA 5-20R, UNO

RECEPTACLE, DUPLEX, DROP CORD, NEMA 5-20R, UNO

RECEPTACLE, MOUNTED 6" ABOVE COUNTER,

TYPE AS INDICATED ABOVE

RECEPTACLE DESIGNATIONS AS FOLLOWS:

C = CLOCK HANGER

E = EMERGENCY POWER

GF = GROUND FAULT CIRCUIT INTERRUPTER

IG = ISOLATED GROUND

S = SWITCHED

TR = TAMPER RESITANT

WP = WEATHER PROOF COVER

WR = WEATHER RESISTANT

XP = EXPLOSION PROOF

SWITCH, SINGLE POLE

SWITCH DESIGNATIONS AS FOLLOWS:

2 = TWO-POLE WALL SWITCH

3 = THREE-WAY WALL SWITCH

4 = FOUR-WAY WALL SWITCH

D = DIMMER SWITCH

OS# = OCCUPANCY SENSOR WALL SWITCH, REFER

TO OCCUPANCY SENSOR AND SWITCH SCHEDULE

P = SINGLE-POLE, SINGLE-THROW PILOT LIGHT

WALL SWITCH

K = KEYED WALL SWITCH

M = MOTOR RATED SWITCH

WP = WEATHER PROOF SWITCH AND COVER

OCCUPANCY SENSOR, CEILING MOUNTED

OS# = CEILING MOUNTED OCCUPANCY SENSOR, REFER

TO OCCUPANCY SENSOR AND SWITCH SCHEDULE

POWER PACK FOR LIGHTING CONTROL

JUNCTION BOX

RECEPTACLE ON EMERGENCY POWER

RECEPTACLE, ISOLATED GROUND TYPE

MULTI-OUTLET, SURFACE RACEWAY, 24" ON CENTER,

NEMA 5-20R, UNO

SWITCHBOARD, MOTOR CONTROL CENTER OR DISTRIBUTION

PANELBOARD ON HOUSEKEEPING PAD

PANELBOARD, RECESS MOUNTED

PANELBOARD, SURFACE MOUNTED

TRANSFORMER

DISCONNECT SWITCH, NON-FUSED, 100/3 INDICATES

AMPERES/POLES, CB = CIRCUIT BREAKER TYPE

DISCONNECT SWITCH, FUSED, 100/3/70 INDICATES

AMPERES/POLES/FUSE, CB = CIRCUIT BREAKER TYPE

COMBINATION DISCONNECT SWITCH WITH MOTOR STARTER

100/3/70/1 INDICATES AMPERES/POLES/FUSE/ NEMA STARTER

SIZE, NF = NON-FUSED, CB = CIRCUIT BREAKER TYPE

MAGNETIC MOTOR STARTER, NEMA SIZE AS NOTED,

3-POLE, UNO

CONTACTOR

PHOTOCELL

RELAY

TIME SWITCH

LOW-VOLTAGE TRANSFORMER

PUSH BUTTON, TYPE AS NOTED

VARIABLE FREQUENCY DRIVE WITH DISCONNECT SWITCH

100/3/70 INDICATES AMPERES/POLES/FUSE SIZE,

NF = NON-FUSED, CB = CIRCUIT BREAKER TYPE

UNDERGROUND ELECTRIC LINE

MULTI-SERVICE FLOOR BOX/POKE-THRU WITH POWER/DATA,

TYPE AS NOTED AND/OR SCHEDULED

CABINET, RECESS MOUNTED

CABINET, SURFACE MOUNTED

RECEPTACLE, DUPLEX, GROUND-FAULT CIRCUIT

INTERRUPTER, NEMA 5-20R, UNO

MULTI-SERVICE POWER POLE WITH POWER/DATA,

TYPE AS NOTED AND/OR SCHEDULED

OVERHEAD ELECTRIC LINE

MUSHROOM TYPE PUSH BUTTON, TYPE AS NOTED

TRANSFER SWITCH, RATINGS AS INDICATED

ATS = AUTOMATIC TRANSFER SWITCH

MTS = MANUAL TRANSFER SWITCH

TX#

600AF

500AT

3P

400AS

3P

225AF

LPS-R

275KW STANDBY

480Y/277V, 3PH, 4W

GENERATOR, SEPARATELY DERIVED

SOURCE, TYPE AND RATINGS AS INDICATED

275KW STANDBY

480Y/277V, 3PH, 4W

GENERATOR, NON-SEPARATELY DERIVED

SOURCE, TYPE AND RATINGS AS INDICATED

DRAWOUT CIRCUIT

BREAKER, RATINGS

AS INDICATED

600AF

500AT

3P

CIRCUIT BREAKER,

RATINGS AS

INDICATED

FUSED DISCONNECT

SWITCH, RATINGS

AS INDICATED

400AS

3P

225AF

LPS-R

NEMA 1

COMBINATION FUSED

SWITCH AND STARTER,

RATINGS AS

INDICATED

PANELBOARD,

SINGLE-SECTION,

RATINGS PER

SCHEDULES

PANELBOARD,

MULTI-SECTION,

RATINGS PER

SCHEDULES

AMMETER

VOLTMETER

COMBINATION DIGITAL

AMMETER/VOLTMETER

SHUNT-TRIP RELAY

KIRK-KEY INTERLOCK

GROUND-FAULT RELAY

UTILITY METER

RELAY

SURGE PROTECTION

DEVICE

AUTOMATIC TRANSFER SWITCH WITH BYPASS

TYPE AND RATINGS AS INDICATED

VARIABLE FREQUENCY

DRIVE WITH

DISCONNECT, RATINGS

AS INDICATED

GROUND CONNECTION

POTENTIAL TRANSFORMER

CURRENT TRANSFORMER

GROUND CONNECTION

WITH TEST WELL

CONTACT, OPEN

CONTACT, CLOSED

MOTOR

FEEDER TAGCAPACITOR

SURGE ARRESTER

HEATER

225A 3P

NEMA 1

COMBINATION CIRCUIT

BREAKER AND

STARTER, RATINGS AS

INDICATED

225A 3P

200A 3P

ATS#

200A 3P

ATS#

TRANSFORMER

TX#

TRANSFORMER,

SHIELDED

200A DEAD-FRONT ELBOW

600A DEAD-FRONT ELBOW

DEAD-FRONT SPLITTER

FAULT INDICATOR

LIGHTNING PROTECTION AIR TERMINAL

LIGHTNING PROTECTION CABLE CONNECTION

LIGHTNING PROTECTION GROUND ROD

LIGHTNING PROTECTION CONDUCTOR

LIGHTNING PROTECTION SYMBOLS

ELECTRICAL ONE-LINE DIAGRAM SYMBOLS

LIGHTING SYMBOLS

POWER EQUIPMENT SYMBOLS

WIRING DEVICE SYMBOLS

CIRCUITING SYMBOLS

ES EMERGENCY SHUNT RELAY

MECHANICAL OR FIRE SPRINKLER PLAN NOTE CALL OUT

PLUMBING PLAN NOTE CALL OUT

ELECTRICAL, TECHNOLOGY, OR FIRE ALARM

PLAN NOTE CALL OUT

PLUMBING EQUIPMENT DESIGNATION

EQUIPMENT DESIGNATION TAG

OWNER FURNISHED, CONTRACTOR INSTALLED

EQUIPMENT DESIGNATION

NEW WORK TO EXISTING WORK CONNECTION POINT

DETAIL REFERENCE

SECTION CUT DESIGNATION

ELECTRICAL: (AFF, AFG UNLESS NOTED OTHERWISE)

EP-101

EP-101

AUDIBLE APPLIANCES (CENTERLINE)

ALARMS (TOP)

ANNUNCIATOR PANELS (TOP)

CLOCK OUTLETS (CENTERLINE)

CONTROLS (TOP)

EXIT SIGNS (WALL-MOUNTED, BOTTOM)

FIRE ALARM ANNUNCIATOR PANEL (DISPLAY)

FIRE ALARM BELL (EXTERIOR)

FIRE ALARM CONTROL PANEL/UNIT (DISPLAY)

GROUND BAR

INTERCOM (AFEA ONLY)

INTERCOMS (TOP)

PANELS & PANELBOARDS (TOP)

PULL STATIONS (TOP)

PHOTOCELLS

RECEPTACLES (BOTTOM)

RECEPTACLES, EXTERIOR (BOTTOM)

RECEPTACLES, GARAGES (BOTTOM)

RECEPTACLES IN EQUIPMENT ROOMS (TOP)

RECEPTACLES ABOVE COUNTERTOPS (TOP)

REMOTE INDICATING LIGHT, EQUIPMENT ROOMS (TOP)

REMOTE INDICATING LIGHT, FINISHED AREAS (TOP)

SAFETY SWITCHES & STARTERS

SWITCHES (TOP)

TELEPHONE/DATA/TV OUTLETS (BOTTOM)

VISIBLE APPLIANCES (CENTERLINE)

ANNOTATION STANDARD MOUNTING HEIGHTS

ABBREVIATIONS

1P SINGLE-POLE

1PH SINGLE-PHASE

3P THREE-POLE

3PH THREE-PHASE

3W THREE-WIRE

4W FOUR-WIRE

A OR AMP AMPERE

A/C AIR CONDITIONING

A/E ARCHITECT/ENGINEER

AAP ALARM ANNUNCIATOR PANEL

AC ALTERNATING CURRENT OR ARMORED

CABLE

ACC ACCESSIBLE

ADDL ADDITIONAL

ADJ ADJACENT, ADJOINING

ADO AUTOMATIC DOOR OPENER

AF AMPERE FRAME OR AMP FUSE

AFC ABOVE FINISHED COUNTER, OR

AUTOMATIC FREQUENCY CONTROL,

OR AVAILABLE FAULT CURRENT

AFF ABOVE FINISHED FLOOR

AFG ABOVE FINISHED GRADE

AH AMPERE HOUR

AHJ AUTHORITY HAVING JURISDICTION

AIC AMPERE INTERRUPTING CAPACITY

AIP ABANDONED IN PLACE

ALT ALTERNATE

AMB AMBIENT

ARCH ARCHITECT

ASC AMPS SHORT CIRCUIT

AT AMPERE TRIP

ATS AUTOMATIC TRANSFER SWITCH

AUTO AUTOMATIC

AV AUDIO VISUAL

BAT BATTERY

BC BARE COPPER

BD BOARD

BFF BELOW FINISH FLOOR

BIL BASIC INSULATION LEVEL

BLDG BUILDING

BLK BLOCK

BPIP BOILER PLANT INSTRUMENTATION PANEL

BRKR BREAKER

BYP BY-PASS

C CONDUIT

CAP CAPACITY

CAT CATALOG

CATV COMMUNITY ANTENNA TELEVISION

CCR CONTROL CONTACTOR

CCTV CLOSED CIRCUIT TELEVISION

CD CONSTRUCTION DOCUMENTS OR

CANDELA

CF CONTRACTOR FURNISHED

CF/CI CONTRACTOR FURNISHED /

CONTRACTOR INSTALLED

CF/OI CONTRACTOR FURNISHED /

OWNER INSTALLED

CFE CONTRACTOR FURNISHED EQUIPMENT

CHW CHILLED WATER

CHWP CHILLED WATER PUMP

CKT CIRCUIT

CLF CURRENT LIMITING FUSE

CLG CEILING

CMU CONCRETE MASONRY UNIT

COAX COAXIAL CABLE

COMM COMMUNICATION

CONC CONCRETE

CONT CONTINUED

CONTR CONTRACTOR

COORD COORDINATE

CPT CONTROL POWER TRANSFORMER

CRI COLOR RENDERING INDEX

CT CURRENT TRANSFORMER

CTV CABLE TELEVISION

CU COPPER

CU FT CUBIC FEET

DB DECIBEL OR DIRECT BURIAL

DC DIRECT CURRENT

DCP DIMMER CONTROL PANEL

DEG C DEGREES CELSIUS

DEG F DEGREES FAHRENHEIT

DEMO DEMOLITION

DIAG DIAGRAM

DISC DISCONNECT

DISTR DISTRIBUTION

DN DOWN

DPDT DOUBLE POLE, DOUBLE THROW

DPST DOUBLE POLE, SINGLE THROW

DRSW DOOR SWITCH

DS DISCONNECT SWITCH

DWG DRAWING

E EXISTING TO REMAIN

EC EMPTY CONDUIT

EG EQUIPMENT GROUND

EL ELEVATION

ELEC ELECTRIC OR ELECTRICAL

ELEV ELEVATOR

EMCP EMER. MONITORING CONTROL PANEL

EMER EMERGENCY

EMI ELECTROMAGNETIC INTERFERENCE

EMT ELECTRICAL METALLIC TUBING

ENCL ENCLOSURE

EPO EMERGENCY POWER OFF

ESMT EASEMENT

ETD EXISTING TO BE DEMOLISHED

ETR EXISTING TO REMAIN

ETL EXISTING TO BE RELOCATED

EWC ELECTRIC WATER COOLER

EWH ELECTRIC WATER HEATER

EXIST EXISTING

FA FIRE ALARM

FAAP FIRE ALARM ANNUNCIATOR PANEL

FABL FIRE ALARM BELL

FABX FIRE ALARM BOX

FACP FIRE ALARM CONTROL PANEL

FC FOOTCANDLE

FI FILM ILLUMINATOR

FIXT FIXTURE

FLA FULL LOAD AMPS

FLEX FLEXIBLE METALLIC CONDUIT

FLUOR FLUORESCENT

FO FIBER-OPTIC

FP FIRE PROTECTION

FT FEET OR FOOT

FVNR FULL VOLTAGE NON-REVERSING

FVR FULL VOLTAGE REVERSING

G GROUND OR GENERATOR

GND GROUND

GEN GENERATOR

GFCI GROUND FAULT CIRCUIT INTERRUPTER

GTB GROUND TERMINAL BOX

HCM HORIZONTAL CABLE MANAGER

HID HIGH INTENSITY DISCHARGE

HOA HAND-OFF-AUTOMATIC

HP HORSEPOWER

HT HEIGHT

HZ HERTZ

IC INSULATION CONTACT

IESNA ILLUMINATION ENGINEERING SOCIETY

OF NORTH AMERICA

IG ISOLATED GROUND

IMC INTERMEDIATE METAL CONDUIT

INCAND INCANDESCENT

IR INFRARED

IWH INSTANTANEOUS WATER HEATER

JB OR J-BOX JUNCTION BOX

KV KILOVOLT

KVA KILOVOLT-AMPERE

KVAH KILOVOLT-AMPERE-HOUR

KVAR KILOVOLT-AMPERE-REACTIVE

KW KILOWATT

KWH KILOWATT-HOUR

KWHM KILOWATT-HOUR METER

LED LIGHT EMITTING DIODE

LF LINEAR FEET (FOOT)

LM LUMEN

LP LIGHT POLE

LPS LOW PRESSURE SODIUM

LRA LOCKED ROTOR AMPS

LT LIGHT

LTCP LOCAL TEMPERATURE CONTROL PANEL

LTG LIGHTING

LTNG LIGHTNING

LV LOW VOLTAGE

MATV MASTER ANTENNA TELEVISION SYSTEM

MAX MAXIMUM

MC METAL-CLAD

MCA MINIMUM CIRCUIT AMPACITY

MCB MAIN CIRCUIT BREAKER

MCC MOTOR CONTROL CENTER

MDP MAIN DISTRIBUTION PANEL

MECH MECHANICAL

MG MOTOR GENERATOR

MH MANHOLE

MIN MINIMUM

MLO MAIN LUGS ONLY

MOCP MAXIMUM OVERCURRENT PROTECTION

MT MOUNT

MTD MOUNTED

MTD MOUNTED

MTG MOUNTING

MTS MANUAL TRANSFER SWITCH

MV MEDIUM VOLTAGE

MVA MEGAVOLT-AMPERE

MW MEGAWATT

N NEUTRAL

NA NOT APPLICABLE

NEC NATIONAL ELECTRICAL CODE

NEMA NATIONAL ELECTRICAL MANUFACTURERS

ASSOCIATION

NFPA NATIONAL FIRE PROTECTION

ASSOCIATION

NIC NOT IN CONTRACT

NL NIGHT LIGHT

NC NORMALLY CLOSED

NO NORMALLY OPEN

NS NO SCALE

NTS NOT TO SCALE

OC ON CENTER

OD OUTSIDE DIAMETER

OL OVERLOAD

P POLE

PA PUBLIC ADDRESS

PB PANELBOARD, OR PULL BOX, OR

PUSHBUTTON

PBPU PREFABRICATED BEDSIDE PATIENT UNIT

PCB POLYCHLORINATED BIPHENYL

PEC PHOTOELECTRIC CELL

PED PEDESTAL

PEND PENDANT

PF POWER FACTOR

PH PHASE

PNL PANEL

PNLBD PANELBOARD

POD POWER OPERATED DAMPER

POE POWER OVER ETHERNET

PP PATCH PANEL

PT POTENTIAL TRANSFORMER

PTRV POWER TYPE ROOF VENTILATION

PVC POLYVINYL CHLORIDE (PLASTIC)

PWR POWER

RCP REFLECTED CEILING PLAN

RCPT RECEPTACLE

REC RECESSED

RELO RELOCATED

REQD REQUIRED

RGS RIGID GALVANIZED STEEL

RM ROOM

RMS ROOT MEAN SQUARE

RU RACK UNIT

SCC SHORT CIRCUIT CAPACITY

SD SMOKE DETECTOR

SES SERVICE ENTRANCE SECTION

SF SQUARE FEET (FOOT)

SHT SHEET

SI INTERNATIONAL SYSTEM OF UNITS

SPEC SPECIFICATION

SPST SINGLE POLE, SINGLE THROW

SURF SURFACE

SW SWITCH

SWBD SWITCHBOARD

SWGR SWITCHGEAR

TC TIME CLOCK

TEL TELEPHONE

TP TWISTED PAIR

TPS TWISTED PAIR SHIELDED

TTB TELEPHONE TERMINAL BOARD

TV TELEVISION

TYP TYPICAL

UFD UNDERFLOOR DUCT

UGND UNDERGROUND

UL UNDERWRITERS LABORATORY

UNO UNLESS NOTED OTHERWISE

UPS UNINTERRUPTIBLE POWER SUPPLY

UTIL UTILITY

V VOLT

VA VOLT-AMPERE

VAR VOLT-AMPERE-REACTIVE

VCM VERTICAL CABLE MANAGER

VFD VARIABLE FREQUENCY DRIVE

W WATT

WH WATER HEATER

WP WEATHERPROOF

XFER TRANSFER

XFMR TRANSFORMER

XP EXPLOSION PROOF

84" 48" 48" 84" 48" 80" 60"

120" 60" 72" 36" 48" 72" 48"

144" 18" 24" 26" 48" 44" 48"

CEILING

48" 48" 18" 84"

A

# E (CONTINUED) M (CONTINUED)

B

C

D

E

F

N

G

H

I

J

K

L

M

O

P

R

S

T

U

V

W

X

A. ELECTRICAL PLANS AND SECTIONS ARE INTENDED TO

ACCURATELY ILLUSTRATE THE SCOPE OF WORK, BUT ARE STILL

DIAGRAMMATIC IN NATURE.

B. ELECTRICAL DRAWINGS DO NOT SHOW ALL ACCESSORIES TO BE

INSTALLED. THE CONTRACTOR IS RESPONSIBLE FOR ENSURING

THAT ALL SYSTEMS ARE FULLY FUNCTIONAL AND COMPLIANT

WITH APPLICABLE CODES.

C. ELECTRICAL DRAWINGS REFLECT COORDINATION EFFORTS

WITH BUILDING DISCIPLINES. HOWEVER, COORDINATION WITH

OTHER TRADES IS REQUIRED.

D. REFERENCE ARCHITECTURAL DRAWINGS FOR ADDITIONAL

INFORMATION REGARDING SCHEDULE AND PHASING

REQUIREMENTS. SCHEDULE WORK TO MINIMIZE DISRUPTION OF

SERVICES.

E. COORDINATE WITH SCHEDULE WITH THE CONTRACTING

OFFICER'S REPRESENTATIVE BEFORE THE START OF WORK.

F. PANELBOARDS AND OTHER ELECTRICAL EQUIPMENT REQUIRE

SHUTDOWN. COORDINATE SERVICE SHUTDOWN FOR ALL

EQUIPMENT WITH THE CONTRACTING OFFICER'S

REPRESENTATIVE.

G. MULTI-GANG BACKBOXES FOR DIFFERENT VOLTAGES AND

TYPES OF EMERGENCY AND NORMAL BRANCH WIRING DEVICES

SHALL HAVE DIVIDERS BETWEEN DEVICES.

H. UPDATE ALL PANELBOARD SCHEDULES AFFECTED AT THE

COMPLETION OF THE PROJECT.

I. HATCHES ON PLAN VIEWS INDICATE AREAS OUTSIDE OF SCOPE.

J. CONTRACTOR SHALL SUBMIT A REQUEST, IN WRITING, TO

INTERRUPT ANY ELECTRICAL SERVICES TO COR (CONTRACTING

OFFICER’S REPRESENTATIVE) 48 HOURS IN ADVANCE OF

PROPOSED INTERRUPTION. REQUEST SHALL STATE REASON,

DATE, EXACT TIME OF, AND APPROXIMATE DURATION OF SUCH

INTERRUPTION. MAJOR INTERRUPTIONS OF THE ELECTRICAL

SYSTEM MUST BE REQUESTED, IN WRITING, AT LEAST 45

CALENDAR DAYS PRIOR TO THE DESIRED TIME AND SHALL BE

PERFORMED IN OFF HOURS (7PM - 7AM) IN MOST INSTANCES

AND AS DIRECTED BY THE COR. MAJOR INTERRUPTIONS SHALL

BE COORDINATED WITH OTHER MAJOR INTERRUPTIONS AND

MAY NOT BE SCHEDULED FOR ONE DISCIPLINE MORE THAN

TWICE THROUGHOUT THE OVERALL CONSTRUCTION SCHEDULE

UNLESS REQUESTED IN WRITING AND APPROVED BY THE COR.

CONTRACTOR WILL BE ADVISED, IN WRITING, OF APPROVAL OF

REQUEST, OR OF WHICH OTHER DATE AND/OR TIME. SUCH

INTERRUPTION WILL CAUSE THE LEAST INCONVENIENCE TO

OPERATIONS OF THE MEDICAL CENTER. INTERRUPTION TIME

APPROVED BY THE MEDICAL CENTER MAY OCCUR AT TIMES

OTHER THAN CONTRACTOR'S NORMAL WORKING HOURS.

SCHEDULE INTERRUPTION MAY BE ON WEEKENDS OR LATE

HOURS AND MAY NOT BE AN ADDITIONAL COST TO THE

GOVERNMENT. COORDINATE ALL INTERRUPTIONS THAT MAY

AFFECT THE NORMAL OPERATION OF THE FACILITY WITH THE

COR WHEN SUBMITTING THE CONSTRUCTION SCHEDULE OR

UPDATES TO THE CONSTRUCTION SCHEDULE.

K. IF FIELD CONDITIONS VARY FROM THE DRAWINGS, THE

CONTRACTOR SHALL DOCUMENT THE VARIATION AND REPORT

IT TO THE GENERAL CONTRACTOR FOR RESOLUTION WITH THE

ENGINEER OF RECORD.

GENERAL NOTES

PROJECT CODES AND STANDARDS

A. ARCHITECTURAL BARRIERS ACT (ABA) STANDARDS 2015

B. VA PG-18-13 VA BARRIER FREE DESIGN STANDARD 2018

(SUPPLEMENT TO ABA STANDARDS)

C. ASHRAE STANDARD 90.1-2019 – ENERGY STANDARD FOR

BUILDINGS EXCEPT LOW RISE RESIDENTIAL BUILDINGS

D. IBC 2021 – INTERNATIONAL BUILDING CODE

E. IEBC 2021 – INTERNATIONAL EXISTING BUILDING CODE

F. IECC 2021 – INTERNATIONAL ENERGY CONSERVATION CODE

G. JCAHO EC 7.40 – EMERGENCY ELECTRICAL POWER SYSTEM

INSPECTION, MAINTENANCE, AND TESTING

H. NFPA 70-2023 - NATIONAL ELECTRICAL CODE (NEC)

I. NFPA 99-2021 – HEALTH CARE FACILITIES CODE

J. NFPA 101-2021 – LIFE SAFETY CODE

K. NFPA 110-2022 – STANDARD FOR EMERGENCY AND STANDBY

POWER SYSTEMS

L. VA PG-18-10 ELECTRICAL DESIGN MANUAL, DECEMBER 2019

M. VA H-18-8 SEISMIC DESIGN REQUIREMENTS

N. VA PG-18-10 LIGHTING DESIGN MANUAL, JANUARY 2022

O. VA PHYSICAL SECURITY & RESILIENCY DESIGN MANUAL 2020

(1 JUL 22 REVISION)

P. VA OFFICE OF INFORMATION & TECHNOLOGY (OIT)

INFRASTRUCTURE STANDARDS FOR TELECOMMUNICATION

SPACES, JULY 2021

Q. VA PG-18-10 TELECOMMUNICATIONS AND SPECIAL

TELECOMMUNICATIONS SYSTEMS DESIGN MANUAL, FEBRUARY

R. BICSI AND EIA/TIA STANDARDS AS DEFINED IN VA PG-18-10

S. NFPA 780-2020 - STANDARD FOR THE INSTALLATION OF

LIGHTNING PROTECTION SYSTEMS

T. ILLUMINATION ENGINEERING SOCIETY (IES) HANDBOOK, 10TH

EDITION

CCTV

CR

DB

DB

DM

EL

GB

KP

MD

PB

RE

EC

KT

GO

C

CLOSED CIRCUIT TELEVISION LINE, MIN. 1" RACEWAY

CARD READER, PROXIMITY TYPE

DOOR BELL PUSHBUTTON

DOOR BELL CHIME

DOOR POSITION MONITOR

ELECTRIFIED LOCKING DEVICE

GLASS BREAK DETECTOR

INTRUSION DETECTION KEYPAD

INTRUSION DETECTION MOTION DETECTOR

DURESS PUSHBUTTON

REQUEST TO EXIT BUTTON

SINGLE VIEW SECURITY CAMERA

EMERGENCY CALL STATION

RFID KEY TAG READER

GATE OPENER

DUAL VIEW SECURITY CAMERA

180-DEGREE PANORAMIC VIEW SECURITY CAMERA

270-DEGREE PANORAMIC/MULTI-IMAGE VIEW

SECURITY CAMERA

360-DEGREE PANORAMIC/MULTI-IMAGE VIEW

SECURITY CAMERA

SECURITY SYMBOLS

AS KEY CONTROLLED ALARM SHUNT

PANIC DURESS PUSH-BUTTON

ML MAGNETIC LOCK

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project NumberCONSULTANTS:

Drawing #

VA Health Care System Approval:

ARCHITECT:

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

ARCH FIRM REG. NO. 20314270 EXP. 06/30/2023

ENGR FIRM REG. NO. 06253 EXP. 06/30/2024

The information on this document is preliminary or incomplete, not for construction, recording purposes, or implementation.

FIRE PROTECTION ENGR

POOLE FIRE PROTECTION

19910 WEST 161ST ST.

OLATHE, KANSAS 66062

(913) 829-8690

FULLY SPRINKLERED

INDUSTRIAL HYGENIST

RIVERFRONT (RSH)

1139 OLIVE ST, SUITE 300

ST. LOUIS, MO 63101

(713) 864-2900

STRUCT ENGR

STAND (SEI)

8234 ROBINSON ST

OVERLAND PARK, KS 66204

(913) 214-2169

COMMISSIONING

ES2

13401 N SANTE FE AVE

OKLAHOMA CITY, OK

(405) 528-4500

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

STAMP:

Drawing Number

Building Number

TELECOMMUNICATION

ASPEN COMMUNICATIONS

7 KIJI-DAVA CIRCLE, STE A

PRESCOTT, AZ 86301

(928) 774-0992

MECH / ELEC / PLUMB ENGR

SPUR DESIGN

11020 KING STREET, STE 350

OVERLAND PARK, KS 66210

(913) 369-7200

FORCE PROTECT

10901 FRONT BEACH RD, UNIT 1415

PANAMA CITY BEACH, FL 32407

(502) 836-4232

PHYSICAL SECURITY

/3

/2

:2 :0

P

M

ELECTRICAL AND SECURITY LEGEND

MIJ 43 OF 78ES

BID DOCUMENTS

EHRM INFRASTRUCTURE

UPGRADES - TIER 2

06/02/2023

757-22-705

CHALMERS P. WYLIE VA

420 NORTH JAMES ROAD

COLUMBUS, OHIO 43219-1834

E-001

BLDG 1, ENERGY BLDG, & ENGR. BLDG

SPUR #: 1791.19No. REVISION DESCRIPTION DATE

E-401

E-401

E-401

E-401

E-402

E-402

E-402

E-402

E-402

E-402

E-401

E-401

E-401

E-401

E-401

E-401

E-401

E-401

E-401

E-401

E-401

E-402

E-402

E-402

E-402

E-402

E-402

EXISTING CONDUIT FEEDING DISCONNECT IN MCR.

REUSE EXISTING CONDUIT FOR NEW CONDUCTORS

TO NEW UPS-B. VERIFY EXACT LOCATION AND SIZE

OF CONDUIT IN FIELD BEFORE BID.TELECOM

1A457

ELEC

1A025

TELECOM

1A024

TELECOM

1A014

ELEC

1A015

TELECOM

1A106

ELEC

1A105

TELECOM

1B002

ELEC

1B031

TELECOM

1B609

TELECOM

1B006

ELEC

1B007

E-403

E-403

E-403

E-404

E-403

E-404

E-404

E-404

E-404

E-403

E-403

E-403

E-403

E-403

E-403

E-403

E-403

E-403

E-404

E-404

E-404

E-403

E-403

E-403

EXISTING CONDUIT FEEDING DISCONNECT IN MCR.

REUSE EXISTING CONDUIT FOR NEW CONDUCTORS

TO NEW UPS-B. VERIFY EXACT LOCATION AND SIZE

OF CONDUIT IN FIELD BEFORE BID.

TELECOM

2A004

ELEC

2A145

TELECOM

2A143

TELECOM

2B102

ELEC

2B103

TELECOM

2B310

TELECOM

2B003

ELEC

2B004

ELEC

2A005

TELECOM

2A018

ELEC

2A017 th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project NumberCONSULTANTS:

Drawing #

VA Health Care System Approval:

ARCHITECT:

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

ARCH FIRM REG. NO. 20314270 EXP. 06/30/2023

ENGR FIRM REG. NO. 06253 EXP. 06/30/2024

The information on this document is preliminary or incomplete, not for construction, recording purposes, or implementation.

FIRE PROTECTION ENGR

POOLE FIRE PROTECTION

19910 WEST 161ST ST.

OLATHE, KANSAS 66062

(913) 829-8690

FULLY SPRINKLERED

INDUSTRIAL HYGENIST

RIVERFRONT (RSH)

1139 OLIVE ST, SUITE 300

ST. LOUIS, MO 63101

(713) 864-2900

STRUCT ENGR

STAND (SEI)

8234 ROBINSON ST

OVERLAND PARK, KS 66204

(913) 214-2169

COMMISSIONING

ES2

13401 N SANTE FE AVE

OKLAHOMA CITY, OK

(405) 528-4500

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

STAMP:

Drawing Number

Building Number

TELECOMMUNICATION

ASPEN COMMUNICATIONS

7 KIJI-DAVA CIRCLE, STE A

PRESCOTT, AZ 86301

(928) 774-0992

MECH / ELEC / PLUMB ENGR

SPUR DESIGN

11020 KING STREET, STE 350

OVERLAND PARK, KS 66210

(913) 369-7200

FORCE PROTECT

10901 FRONT BEACH RD, UNIT 1415

PANAMA CITY BEACH, FL 32407

(502) 836-4232

PHYSICAL SECURITY

/3

/2

:2 :0

P

M

REFERENCE PLANS

MIJ 44 OF 78ES

BID DOCUMENTS

EHRM INFRASTRUCTURE

UPGRADES - TIER 2

06/02/2023

757-22-705

CHALMERS P. WYLIE VA

420 NORTH JAMES ROAD

COLUMBUS, OHIO 43219-1834

E-101

BLDG 1, ENERGY BLDG, & ENGR. BLDG

SPUR #: 1791.19

N

1" = 40'-0"

BLDG 1 - LEVEL 1 - REFERENCE PLAN1

N

1" = 40'-0"

BLDG 1 - LEVEL 2 - REFERENCE PLAN2

No. REVISION DESCRIPTION DATE

DN

0"

8"

T S R Q P O N M L J

H G F E

K

D C B A

T.2

4.3

9.2

6.2

4.9

7.3

0.6

E-411

E-411

E-411

E-411

TELECOM

E-411

E-411

E-411

E-411

ELEC

TELECOM

E-404

E-405

E-405

E-405

E-405

E-405

E-405

E-405

E-405

E-405

E-405

E-405

E-404

E-404

E-404

EXISTING CONDUIT FEEDING DISCONNECT IN MCR.

REUSE EXISTING CONDUIT FOR NEW CONDUCTORS

TO NEW UPS-B. VERIFY EXACT LOCATION AND SIZE

OF CONDUIT IN FIELD BEFORE BID.

TELECOM

3A004

ELEC

3A005

TELECOM

3A015

ELEC

3A016

TELECOM

3A063

ELEC

3A065

E-411

UPS

4A008 E-406

E-406

E-406

E-409

E-408

E-408

E-408

E-407

E-407

E-407

E-406

E-406

E-406

E-411

E-411

E-411

E-409

E-409

E-409

E-409

ROUTE NEW CONDUCTORS IN

EXISTING CONDUIT DOWN HALLWAY

ABOVE CEILING ALONG ROUTE

SHOWN. COORDINATE LOCATION

WITH EXISTING CONDITIONS.

VERIFY EXACT LOCATION AND SIZE

OF CONDUIT IN FIELD BEFORE BID.

EXISTING CONDUIT FEEDING DISCONNECT IN MCR.

REUSE EXISTING CONDUIT FOR NEW CONDUCTORS

TO NEW UPS-B. VERIFY EXACT LOCATION AND SIZE

OF CONDUIT IN FIELD BEFORE BID.

ROUTE NEW CONDUCTORS AND

CONDUIT DOWN HALLWAY ABOVE

CEILING ALONG ROUTE SHOWN.

COORDINATE LOCATION WITH

EXISTING CONDITIONS. VERIFY

EXACT LOCATION BEFORE BID.

TELECOM

4A041

SERVER/MAIN TELECOM

4A201

SERVER/MAIN TELECOM

4A202

E-410

E-410 th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project NumberCONSULTANTS:

Drawing #

VA Health Care System Approval:

ARCHITECT:

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

ARCH FIRM REG. NO. 20314270 EXP. 06/30/2023

ENGR FIRM REG. NO. 06253 EXP. 06/30/2024

The information on this document is preliminary or incomplete, not for construction, recording purposes, or implementation.

FIRE PROTECTION ENGR

POOLE FIRE PROTECTION

19910 WEST 161ST ST.

OLATHE, KANSAS 66062

(913) 829-8690

FULLY SPRINKLERED

INDUSTRIAL HYGENIST

RIVERFRONT (RSH)

1139 OLIVE ST, SUITE 300

ST. LOUIS, MO 63101

(713) 864-2900

STRUCT ENGR

STAND (SEI)

8234 ROBINSON ST

OVERLAND PARK, KS 66204

(913) 214-2169

COMMISSIONING

ES2

13401 N SANTE FE AVE

OKLAHOMA CITY, OK

(405) 528-4500

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

STAMP:

Drawing Number

Building Number

TELECOMMUNICATION

ASPEN COMMUNICATIONS

7 KIJI-DAVA CIRCLE, STE A

PRESCOTT, AZ 86301

(928) 774-0992

MECH / ELEC / PLUMB ENGR

SPUR DESIGN

11020 KING STREET, STE 350

OVERLAND PARK, KS 66210

(913) 369-7200

FORCE PROTECT

10901 FRONT BEACH RD, UNIT 1415

PANAMA CITY BEACH, FL 32407

(502) 836-4232

PHYSICAL SECURITY

/3

/2

:2 :0

P

M

REFERENCE PLANS

MIJ 45 OF 78ES

BID DOCUMENTS

EHRM INFRASTRUCTURE

UPGRADES - TIER 2

06/02/2023

757-22-705

CHALMERS P. WYLIE VA

420 NORTH JAMES ROAD

COLUMBUS, OHIO 43219-1834

E-102

BLDG 1, ENERGY BLDG, & ENGR. BLDG

SPUR #: 1791.19

N

1" = 40'-0"

BOILER PLANT - LEVEL 1 - REFERENCE PLAN4

N

1" = 40'-0"

ENGINEERING BUILDING - LEVEL 1 - REFERENCE PLAN5

N

1" = 40'-0"

BLDG 1 - LEVEL 3 - REFERENCE PLAN1

N

1" = 40'-0"

BLDG 1 - LEVEL 4 - REFERENCE PLAN2

No. REVISION DESCRIPTION DATE

N

1" = 40'-0"

BLDG 1 - ROOF - REFERENCE PLAN3

CR

DM

EL

RE AS

CR

DM

EL

RE ASCR

DM

EL

RE AS

CR

DM

EL

RE

AS

CR

DM

EL

RE

AS

CR

DM

EL

RE

ASCR

DM

EL

RE AS

J1EA (ETR)

GROUND BAR (ETR)

TELECOM

1A457

ETR

ETR

ETR

ETR

ETR

FIRE

ALARM

PANEL

(ETR)

DATA

PANELS

DATA

PANELS

ETR

ETR

ETR

ETR

ETR ETR

ETR ETR

ETLETL

J1EA (ETR) GROUND BAR (ETR)

DATA

PANELS

DATA

PANELS

FIRE

ALARM

PANEL

(ETR)

M,2

M,2ETR

ETR

ETR

ETR

ETR ETR

ETR ETR

ETR

ETR

ETR

ETR

ETR

1A-DS-457-B

1A-DS-457-A

6,8

J1EA

6,8

J1EA

ETLETL

(NEW)

NEW

TELECOM

1A457

TELECOM

1A024

ELEC

1A025

GROUND BAR (ETR)

A1C1 (ETR)

A1E1 (ETR)

A1N3 (ETR)

A1N2 (ETR)

A1N1 (ETR)

A1DN1 (ETR)

ETRETRETR

ETR

ETR

ETR ETR

ETR

ETR

ETLETL

GROUND BAR (ETR)

A1C1 (ETR)

A1N3 (ETR)

A1E1 (ETR)

A1N2 (ETR)

A1N1 (ETR)

A1DN1 (ETR)

ETR

ETR

ETR

ETR

ETR

ETR ETR

ETR

ETR

M,2

M,2

1A-DS-024-B

1A-DS-024-A

TELECOM

1A024ELEC

1A025

2,4

A1C1

2,4

A1C1

NEW

ETL

ETL

ELEC

1A015

TELECOM

1A014

LCP (ETR)

C1S1 (ETR) C1SA (ETR) C1E1 (ETR)

C1N3 (ETR)

C1N2 (ETR)

C1N1 (ETR)

C1NA (ETR)

C1DN3 (ETR)C1CA (ETR)

C1C1 (ETR)

T-C1C1 (ETR)

T-C1C1 (ETR)

GROUND BAR (ETR)

ETR

ETR

ETD

ETR

ETRETR

ETR

ACCESS

CONTROL

PANEL

DATA

PANEL

ETL

ETL

GROUND BAR (ETR)

T-C1C1 (ETR)

T-C1C1 (ETR)

LCP (ETR)

C1SA (ETR)C1S1 (ETR) C1E1 (ETR)

C1N2 (ETR)

C1N3 (ETR)

C1N1 (ETR)

C1DN3 (ETR)

C1C1 (ETR)

C1NA (ETR)

C1CA (ETR)

ETR

ETR

ETR

ETR

ETR

ETR

1A-DS-014-A

1A-DS-014-B

M,2

M,2

TELECOM

1A014

ELEC

1A015

36,38

C1C1

36,38

C1C1

ETL

ETL

NEW

E1E1 (ETR)

E1N2 (ETR)

E1N1 (ETR)

E1N3 (ETR)

E1NA (ETR)

E1C1 (ETR)

E1S1 (ETR)

E1CA (ETR)

T-E1C1 (ETR)

ELEC

1B007

TELECOM

1B006

GROUND BAR (ETR)

ETR ETR

ETR

ETR

ETRETRETR

ETR

ETR

PACS

SECURITY

PANELS

(ETR)

SECURITY

PANEL

(ETL)

ETLETL

E1E1 (ETR)

E1N2 (ETR)

E1N1 (ETR)

E1N3 (ETR)

E1NA (ETR)

E1C1 (ETR)

E1S1 (ETR)

T-E1C1 (ETR)

E1CA (ETR)

GROUND BAR (ETR)

ETR

ETR

ETR

ETR

ETR

ETR

ETR

ETR

ETR

1B-DS-006-A

1B-DS-006-B

M,2

M,2

TELECOM

1B006

ELEC

1B007

1,3

E1C-OIT

1,3

E1C-OIT

ETR

ETLETL

SECURITY

PANELS

(ETR)

SECURITY

PANEL

(ETL)

E1C-OIT

(NEW)

TELECOM

1A457

ETD

ETD

ETD

DATA

PANELS

DATA

PANELS

FIRE

ALARM

PANEL

(ETR)

J1EA (ETR)

TELECOM

1A457

J1EA (ETR) S2 S2

S2 S2

DATA

PANELS

DATA

PANELS

FIRE

ALARM

PANEL

(ETR)

J1EA

ETD

ETD ETD

A1E1 (ETR)

A1N3 (ETR)

A1N2 (ETR)

A1N1 (ETR)

A1DN1 (ETR)

A1C1 (ETR)

TELECOM

1A024

ELEC

1A025

A1E1 (ETR)

A1N3 (ETR)

A1N2 (ETR)

A1N1 (ETR)

A1DN1 (ETR)

A1C1 (ETR)

ELEC

1A025

TELECOM

1A024

S1 S1S1 S1

A1C1

TELECOM

1A014

ETD

ETD

ETD

ELEC

1A015

C1N1 (ETR)C1C1 (ETR)

C1CA (ETR)

C1NA (ETR)

LCP (ETR)

C1S1 (ETR)

C1SA (ETR)

C1E1 (ETR)

C1N3 (ETR)

C1N2 (ETR)

C1DN3 (ETR)

TELECOM

1A014

ELEC

1A015

C1N1 (ETR)C1C1 (ETR)

C1CA (ETR)

C1NA (ETR)

LCP (ETR)

C1S1 (ETR)

C1SA (ETR)

C1E1 (ETR)

C1N3 (ETR)

C1N2 (ETR)

C1DN3 (ETR)

S2

S2

S2

S2

C1C1

TELECOM

1B006

ETD

ETD

ETD

ELEC

1B007

E1N2 (ETR)

E1E1 (ETR)

E1N1 (ETR)

E1N3 (ETR)

E1NA (ETR)

E1C1 (ETR)

E1S1 (ETR)

E1CA (ETR)

ELEC

1B007

E1N2 (ETR)

E1E1 (ETR)

E1N1 (ETR)

E1N3 (ETR)

E1NA (ETR)

E1C1 (ETR)

E1S1 (ETR)

E1CA (ETR)

TELECOM

1B006

S1

S1

S1

S1

E1C-OIT

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project NumberCONSULTANTS:

Drawing #

VA Health Care System Approval:

ARCHITECT:

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

ARCH FIRM REG. NO. 20314270 EXP. 06/30/2023

ENGR FIRM REG. NO. 06253 EXP. 06/30/2024

The information on this document is preliminary or incomplete, not for construction, recording purposes, or implementation.

FIRE PROTECTION ENGR

POOLE FIRE PROTECTION

19910 WEST 161ST ST.

OLATHE, KANSAS 66062

(913) 829-8690

FULLY SPRINKLERED

INDUSTRIAL HYGENIST

RIVERFRONT (RSH)

1139 OLIVE ST, SUITE 300

ST. LOUIS, MO 63101

(713) 864-2900

STRUCT ENGR

STAND (SEI)

8234 ROBINSON ST

OVERLAND PARK, KS 66204

(913) 214-2169

COMMISSIONING

ES2

13401 N SANTE FE AVE

OKLAHOMA CITY, OK

(405) 528-4500

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

STAMP:

Drawing Number

Building Number

TELECOMMUNICATION

ASPEN COMMUNICATIONS

7 KIJI-DAVA CIRCLE, STE A

PRESCOTT, AZ 86301

(928) 774-0992

MECH / ELEC / PLUMB ENGR

SPUR DESIGN

11020 KING STREET, STE 350

OVERLAND PARK, KS 66210

(913) 369-7200

FORCE PROTECT

10901 FRONT BEACH RD, UNIT 1415

PANAMA CITY BEACH, FL 32407

(502) 836-4232

PHYSICAL SECURITY

/3

/2

:2 :1

P

M

ENLARGED PLANS

MIJ 46 OF 78ES

BID DOCUMENTS

EHRM INFRASTRUCTURE

UPGRADES - TIER 2

06/02/2023

757-22-705

CHALMERS P. WYLIE VA

420 NORTH JAMES ROAD

COLUMBUS, OHIO 43219-1834

E-401

BLDG 1, ENERGY BLDG, & ENGR. BLDG

SPUR #: 1791.19

N

1/4" = 1'-0"

BLDG 1 - LEVEL 1 - 1A457 - DEMO PWR1

N

1/4" = 1'-0" REFERENCING DETAIL: 1/ E-101

BLDG 1 - LEVEL 1 - 1A457 - NEW PWR2

N

1/4" = 1'-0" REFERENCING DETAIL: 1/ E-101

BLDG 1 - LEVEL 1 - 1A024 - DEMO PWR5

N

1/4" = 1'-0" REFERENCING DETAIL: 1/ E-101

BLDG 1 - LEVEL 1 - 1A024 - NEW PWR6

N

1/4" = 1'-0" REFERENCING DETAIL: 1/ E-101

BLDG 1 - LEVEL 1 - 1A014 - DEMO PWR9

N

1/4" = 1'-0" REFERENCING DETAIL: 1/ E-101

BLDG 1 - LEVEL 1 - 1A014 - NEW PWR10

N

1/4" = 1'-0" REFERENCING DETAIL: 1/ E-101

BLDG 1 - LEVEL 1 - 1B006 - EXISTING PWR13

N

1/4" = 1'-0" REFERENCING DETAIL: 1/ E-101

BLDG 1 - LEVEL 1 - 1B006 - NEW PWR14

ELECTRICAL KEYNOTES

3 DEMOLISH EXISTING LIGHT FIXTURE AND ASSOCIATED CIRCUIT AND CONTROLS BACK TO THE

NEAREST JUNCTION BOX.

39 PROVIDE NEW 208V, 30A, 3-PHASE L21-30R RECEPTACLE TO SERVE POWER TO RACK MOUNTED

UPS AND ZONE PDU. REFER TO DETAIL 2/E-502 FOR PDU ARRANGEMENT IN

TELECOMMUNICATION RACK.

50 REMOVE, RETAIN AND KEEP EXISTING ELECTRIFIED DOOR HARDWARE (INCLUDING

KEY-CONTROLLED ALARM SHUNT) IN GOOD WORKING CONDITION. EXISTING BACKBOXES,

PATHWAYS, AND CABLING TO REMAIN. INSTALL ADDITIONAL DOOR CONTROLLERS AND POWER

SUPLIES AS REQUIRED. COORDINATE SYSTEM INTEGRATION INTO FACILITY SCC.

51 INSTALL PREVIOUSLY REMOVED ELECTRIFIED DOOR HARDWARE (INCLUDING

KEY-CONTROLLED ALARM SHUNT) IN EXISTING BACKBOXES. EXTEND CIRCUITING AS

NECESSARY TO ENSURE CIRCUIT CONTINUITY. ANY DEVICES THAT ARE LOST OR DAMAGED

DURING CONSTRUCTION SHALL BE REPLACED WITH MATCHING AT CONTRACTOR'S EXPENSE.

52 DISCONNECT CONDUIT AND ENSURE ADEQUATE SLACK IN CABLING TO ENSURE FOR

TEMPORARY REMOVAL OF PACS ENCLOSURE. ENSURING TO SUPPORT PACS ENCLOSURE

DURING INSTALLATION OF FIRE TREATED PLYWOOD.

53 INSTALL 4'X8' 3/4" FIRE RATED PLYWOOD BACKBOARD PAINTED WITH TWO COATS OF

HIGH-GLOSS WHITE INTUMESCENT PAINT ON ALL SIDES WITH FIRE STAMP VISIBLE.

54 INSTALL PACS ENCLOSURE TO FIRE TREATED PLYWOOD. EXTEND CIRCUITS AS NECESSARY TO

ENSURE CIRCUIT CONTINUITY AND RECONNECT CONDUIT(S).

55 INSTALL NEW PANIC/DURESS PUSH BUTTON. VERIFY AND MATCH EXISTING CONDITIONS TO

ENSURE INTEGRATION INTO EXISTING SYSTEM.

56 INSTALL NEW ELECTRIFIED DOOR HARDWARE (INCLUDING KEY-CONTROLLED ALARM SHUNT).

CONNECT TO EXISTING PACS ENCLOSURE. FIELD VERIFY EXISTING SPARE CAPACITY AND

EXPAND AS NECESSARY TO ENSURE FULLY FUNCTIONAL SYSTEM. INSTALL ADDITIONAL DOOR

CONTROLLERS AND POWER SUPLIES AS REQUIRED. COORDINATE SYSTEM INTEGRATION INTO

FACILITY SCC.

58 INDOOR UNIT IS POWERED BY OUTDOOR UNIT. SEE MECHANICAL DRAWINGS FOR MORE

INFORMATION. COORDINATE WORK WITH MECHANICAL CONTRACTOR.

66 EXISTING 208V THREE PHASE RECEPTACLES TO BE RELOCATED. REMOVE AND PRESERVE FOR

REUSE. REFER TO NEW POWER PLAN FOR MORE INFORMATION.

67 RELOCATE EXISTING 208V THREE PHASE RECEPTACLE AS SHOWN. REFER TO DEMO POWER

PLAN FOR MORE INFORMATION.

68 TR ROOM RECEPTACLES TO BE REFED FROM CRITICAL PANEL E1C-OIT. RELABEL ALL

RECEPTACLES TO CIRCUITS FED FROM IN CRITICAL PANEL E1C-OIT.

69 TR ROOM RECEPTACLES TO BE REFED FROM CRITICAL PANEL C1C1. RELABEL ALL

RECEPTACLES TO CIRCUITS FED FROM IN CRITICAL PANEL C1C1.

70 TR ROOM RECEPTACLES TO BE REFED FROM CRITICAL PANEL A1C1. RELABEL ALL

RECEPTACLES TO CIRCUITS FED FROM IN CRITICAL PANEL A1C1.

71 TR ROOM RECEPTACLES TO BE REFED FROM CRITICAL PANEL J1C-OIT. RELABEL ALL

RECEPTACLES TO CIRCUITS FED FROM IN CRITICAL PANEL J1C-OIT.

85 RENAME EXISTING PANELBOARD TO J1C-OIT.

N

1/4" = 1'-0" REFERENCING DETAIL: 1/ E-101

BLDG 1 - LEVEL 1 - 1A457 - DEMO LTG3

N

1/4" = 1'-0" REFERENCING DETAIL: 1/ E-101

BLDG 1 - LEVEL 1 - 1A457 - NEW LTG4

N

1/4" = 1'-0" REFERENCING DETAIL: 1/ E-101

BLDG 1 - LEVEL 1 - 1A024 - DEMO LTG7

N

1/4" = 1'-0" REFERENCING DETAIL: 1/ E-101

BLDG 1 - LEVEL 1 - 1A024 - NEW LTG8

N

1/4" = 1'-0" REFERENCING DETAIL: 1/ E-101

BLDG 1 - LEVEL 1 - 1A014 - DEMO LTG11

N

1/4" = 1'-0" REFERENCING DETAIL: 1/ E-101

BLDG 1 - LEVEL 1 - 1A014 - NEW LTG12

N

1/4" = 1'-0" REFERENCING DETAIL: 1/ E-101

BLDG 1 - LEVEL 1 - 1B006 - DEMO LTG15

N

1/4" = 1'-0" REFERENCING DETAIL: 1/ E-101

BLDG 1 - LEVEL 1 - 1B006 - NEW LTG16

EL

RE

AS

CR

DM

EL

RE

AS

CR

DM

EL

RE

ASCR

DM

EL

RE

AS

CR

DM

EL

RE

ASCR

DM

EL

RE

AS

TELECOM

1B609

F1E2 (ETR)

GROUND BAR (ETR)

ETR

ETRETR

ETR

ETR

DATA

PANEL

ETR

ETL

ETL

GROUND

BAR (ETR)

F1E2 (ETR)

M,2

M,2

1B-DS-609-A

1B-DS-609-B

ETR

ETR

ETR

ETR

ETR

ETR

TELECOM

1B609

2,4

F1E2

2,4

F1E2

NEW

ETL

ETL

TELECOM

1B002

GROUND BAR (ETR)

ETRETRETR

ETR

ETR

ETR

ETR

FIRE

ALARM

PANEL

DATA

PANEL

FIRE

ALARM

PANEL

D1NA (E)

D1E2 (ETR)

D1CA (ETR)

D1F1 (ETR)

D1N2 (ETR)

D1N1 (ETR)

D1SA (ETR)

D1NA (ETR)

D1C1 (ETR)

D1S1 (ETR)

D1N3 (ETR)

ETR

ELEC

1B031

ETL ETL

GROUND BAR (ETR)

D1F1 (ETR)

D1CA (ETR)

D1E2 (ETR)

D1NA (E)

D1N3 (ETR)

D1N2 (ETR)

D1N1 (ETR)

D1S1 (ETR)

D1SA (ETR)

D1C1 (ETR)

D1NA (ETR)

FIRE

ALARM

PANEL

DATA

PANEL

FIRE

ALARM

PANEL

ETRETRETR

ETR

ETR

ETR

ETR

ETR

1B-DS-002-A

1B-DS-002-B

M,2

M,2

ELEC

1B031

TELECOM

1B002

1,3

D1C-OIT

1,3

D1C-OIT

ETLETL

NEW

D1C2 (NEW)

D1C-OIT

(NEW)

TELECOM

1A106

ELEC

1A105

B1CA

B1E1

B1NA

LCP

B1DN1

B1C1

B1N1

B1N2

B1N3

GROUND BAR (ETR)

DATA

PANELS

DATA

BOXES

ACCESS

CONTROL

PANEL

PULL

BOX

DATA

PANELS

ETR

ETR

ETR

ETR

ETR ETR ETR ETR

ETL

ETL

GROUND BAR (ETR)

B1NA (ETR)

LCP (ETR)

B1DN1 (ETR)

B1E1 (ETR)

B1CA (ETR)

B1C1 (ETR)

B1N1 (ETR)

B1N2 (ETR)

B1N3 (ETR)

ETR

ETR

ETR

ETR

ETR ETR ETR ETR

1A-DS-106-A

1A-DS-106-B

M,2

M,2

TELECOM

1A106

ELEC

1A105

ETL

ETL

2,4

B1C1

2,4

B1C1

NEW

NEW

F1E2 (ETR)

TELECOM

1B609

ETD3

ETD

F1E2 (ETR)

TELECOM

1B609

S1

S1S1

S1

F1E2

TELECOM

1A106

ELEC

1A105

33 ETD ETD

ETD

B1N3 (ETR)

B1N2 (ETR)

B1N1 (ETR)

B1C1 (ETR)

B1E1 (ETR)

B1CA (ETR)

B1NA (ETR)

LCP (ETR)

B1DN1 (ETR)

TELECOM

1A106

ELEC

1A105

S2 S2

S2S2

B1C1

B1N3 (ETR)

B1N2 (ETR)

B1N1 (ETR)

B1C1 (ETR)

B1E1 (ETR)

B1CA (ETR)

B1NA (ETR)

LCP (ETR)

B1DN1 (ETR)

TELECOM

1B002

ETDETD3 3

ETD

ELEC

1B031

D1S1 (ETR)

D1SA (ETR)

D1NA (ETR)

D1C1 (ETR)

D1F1 (ETR)

D1CA (ETR)

D1E2 (ETR)

D1NA (E)

D1N2 (ETR)

D1N1 (ETR)D1N3 (ETR)

TELECOM

1B002

ELEC

1B031

D1S1 (ETR)

D1SA (ETR)

D1NA (ETR)

D1C1 (ETR)

D1F1 (ETR)

D1CA (ETR)

D1E2 (ETR)

D1NA (E)

D1N2 (ETR)

D1N1 (ETR)D1N3 (ETR)

S1S1

S1 S1 2

D1C-OIT

D1C2 (NEW)

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project NumberCONSULTANTS:

Drawing #

VA Health Care System Approval:

ARCHITECT:

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

ARCH FIRM REG. NO. 20314270 EXP. 06/30/2023

ENGR FIRM REG. NO. 06253 EXP. 06/30/2024

The information on this document is preliminary or incomplete, not for construction, recording purposes, or implementation.

FIRE PROTECTION ENGR

POOLE FIRE PROTECTION

19910 WEST 161ST ST.

OLATHE, KANSAS 66062

(913) 829-8690

FULLY SPRINKLERED

INDUSTRIAL HYGENIST

RIVERFRONT (RSH)

1139 OLIVE ST, SUITE 300

ST. LOUIS, MO 63101

(713) 864-2900

STRUCT ENGR

STAND (SEI)

8234 ROBINSON ST

OVERLAND PARK, KS 66204

(913) 214-2169

COMMISSIONING

ES2

13401 N SANTE FE AVE

OKLAHOMA CITY, OK

(405) 528-4500

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

STAMP:

Drawing Number

Building Number

TELECOMMUNICATION

ASPEN COMMUNICATIONS

7 KIJI-DAVA CIRCLE, STE A

PRESCOTT, AZ 86301

(928) 774-0992

MECH / ELEC / PLUMB ENGR

SPUR DESIGN

11020 KING STREET, STE 350

OVERLAND PARK, KS 66210

(913) 369-7200

FORCE PROTECT

10901 FRONT BEACH RD, UNIT 1415

PANAMA CITY BEACH, FL 32407

(502) 836-4232

PHYSICAL SECURITY

/3

/2

:2 :1

P

M

ENLARGED PLANS

MIJ 47 OF 78ES

BID DOCUMENTS

EHRM INFRASTRUCTURE

UPGRADES - TIER 2

06/02/2023

757-22-705

CHALMERS P. WYLIE VA

420 NORTH JAMES ROAD

COLUMBUS, OHIO 43219-1834

E-402

BLDG 1, ENERGY BLDG, & ENGR. BLDG

SPUR #: 1791.19

N

1/4" = 1'-0" REFERENCING DETAIL: 1/ E-101

BLDG 1 - LEVEL 1 - 1B609 - DEMO PWR1

N

1/4" = 1'-0" REFERENCING DETAIL: 1/ E-101

BLDG 1 - LEVEL 1 - 1B609 - NEW PWR2

N

1/4" = 1'-0" REFERENCING DETAIL: 1/ E-101

BLDG 1 - LEVEL 1 - 1B002 - DEMO PWR9

N

1/4" = 1'-0" REFERENCING DETAIL: 1/ E-101

BLDG 1 - LEVEL 1 - 1B002 - NEW PWR10

N

1/4" = 1'-0" REFERENCING DETAIL: 1/ E-101

BLDG 1 - LEVEL 1 - 1A106 - DEMO PWR5

N

1/4" = 1'-0" REFERENCING DETAIL: 1/ E-101

BLDG 1 - LEVEL 1 - 1A106 - NEW PWR6

ELECTRICAL KEYNOTES

3 DEMOLISH EXISTING LIGHT FIXTURE AND ASSOCIATED CIRCUIT AND CONTROLS BACK TO THE

NEAREST JUNCTION BOX.

50 REMOVE, RETAIN AND KEEP EXISTING ELECTRIFIED DOOR HARDWARE (INCLUDING

KEY-CONTROLLED ALARM SHUNT) IN GOOD WORKING CONDITION. EXISTING BACKBOXES,

PATHWAYS, AND CABLING TO REMAIN. INSTALL ADDITIONAL DOOR CONTROLLERS AND POWER

SUPLIES AS REQUIRED. COORDINATE SYSTEM INTEGRATION INTO FACILITY SCC.

51 INSTALL PREVIOUSLY REMOVED ELECTRIFIED DOOR HARDWARE (INCLUDING

KEY-CONTROLLED ALARM SHUNT) IN EXISTING BACKBOXES. EXTEND CIRCUITING AS

NECESSARY TO ENSURE CIRCUIT CONTINUITY. ANY DEVICES THAT ARE LOST OR DAMAGED

DURING CONSTRUCTION SHALL BE REPLACED WITH MATCHING AT CONTRACTOR'S EXPENSE.

52 DISCONNECT CONDUIT AND ENSURE ADEQUATE SLACK IN CABLING TO ENSURE FOR

TEMPORARY REMOVAL OF PACS ENCLOSURE. ENSURING TO SUPPORT PACS ENCLOSURE

DURING INSTALLATION OF FIRE TREATED PLYWOOD.

53 INSTALL 4'X8' 3/4" FIRE RATED PLYWOOD BACKBOARD PAINTED WITH TWO COATS OF

HIGH-GLOSS WHITE INTUMESCENT PAINT ON ALL SIDES WITH FIRE STAMP VISIBLE.

54 INSTALL PACS ENCLOSURE TO FIRE TREATED PLYWOOD. EXTEND CIRCUITS AS NECESSARY TO

ENSURE CIRCUIT CONTINUITY AND RECONNECT CONDUIT(S).

55 INSTALL NEW PANIC/DURESS PUSH BUTTON. VERIFY AND MATCH EXISTING CONDITIONS TO

ENSURE INTEGRATION INTO EXISTING SYSTEM.

66 EXISTING 208V THREE PHASE RECEPTACLES TO BE RELOCATED. REMOVE AND PRESERVE FOR

REUSE. REFER TO NEW POWER PLAN FOR MORE INFORMATION.

67 RELOCATE EXISTING 208V THREE PHASE RECEPTACLE AS SHOWN. REFER TO DEMO POWER

PLAN FOR MORE INFORMATION.

72 TR ROOM RECEPTACLES TO BE REFED FROM CRITICAL PANEL D1C-OIT. RELABEL ALL

RECEPTACLES TO CIRCUITS FED FROM IN CRITICAL PANEL D1C-OIT.

73 TR ROOM RECEPTACLES TO BE REFED FROM CRITICAL PANEL B1C1. RELABEL ALL

RECEPTACLES TO CIRCUITS FED FROM IN CRITICAL PANEL B1C1.

74 TR ROOM RECEPTACLES TO BE REFED FROM CRITICAL PANEL F1C-OIT. RELABEL ALL

RECEPTACLES TO CIRCUITS FED FROM IN CRITICAL PANEL F1C-OIT.

86 RENAME EXISTING PANELBOARD TO F1C-OIT.

N

1/4" = 1'-0" REFERENCING DETAIL: 1/ E-101

BLDG 1 - LEVEL 1 - 1B609 - DEMO LTG3

N

1/4" = 1'-0" REFERENCING DETAIL: 1/ E-101

BLDG 1 - LEVEL 1 - 1B609 - NEW LTG4

N

1/4" = 1'-0" REFERENCING DETAIL: 1/ E-101

BLDG 1 - LEVEL 1 - 1A106 - DEMO LTG7

N

1/4" = 1'-0" REFERENCING DETAIL: 1/ E-101

BLDG 1 - LEVEL 1 - 1A106 - NEW LTG8

N

1/4" = 1'-0" REFERENCING DETAIL: 1/ E-101

BLDG 1 - LEVEL 1 - 1B002 - DEMO LTG11N

1/4" = 1'-0" REFERENCING DETAIL: 1/ E-101

BLDG 1 - LEVEL 1 - 1B002 - NEW LTG12

EL

RE

AS

CR

DM

EL

RE

AS

CR

DM

EL

RE

ASCR

DM

EL

RE AS

CR

DM

EL

RE

AS

CR

DM

EL

RE

ASCR

DM

EL

RE

AS

ELEC

2A017

TELECOM

2A018

LCP (ETR)

C2C1 (ETR)

C2E1 (ETR)

C2CA (ETR)

C2NA (ETR)

ETR

ETR

ETR

ETR

ETR

ETR

ETR

ETR

DATA

PANEL

DATA

PANEL

LCP (ETR)

ETR

ETLETL

C2NA (ETR)

C2CA (ETR)

C2C1 (ETR)

C2E1 (ETR)

LCP (ETR)

2A-DS-018-A

2A-DS-018-B

M,2

M,2

ETR ETR

ETR

ETR

ETRETR

ETR

ETR

TELECOM

2A018

ELEC

2A017

2,4

C2C12,4

C2C1

LCP (ETR)

ETL ETL

ETR

1'-0"

E2E1 (ETR)

E2N1 (ETR)

E2N2 (ETR)

E2N3 (ETR)

E2NA (ETR)

E2CA (ETR)

E2C1 (ETR)

E2C2 (ETR)

LCP (ETR)

T-E2C1 (ETR)

TELECOM

2B003

ELEC

2B004

ETR

ETR

ETR

ETR

ETR

ETRETR

ETR

DATA

PULLBOXES

SECURITY

PANELS

ETR

ETL ETL

E2C2 (ETR)

LCP (ETR)

T-E2C1 (ETR)

E2C1 (ETR)

E2CA (ETR)

E2N3 (ETR)

E2NA (ETR)

E2N2 (ETR)

E2E1 (ETR)

E2N1 (ETR)

M,2

M,2 2B-DS-003-B

2B-DS-003-A

ETR

ETR

ETR

ETR

ETR

ETRETR

ETR

ELEC

2B004

TELECOM

2B003

7,9

E2C-OIT

7,9

E2C-OIT

ETL ETL

ETR

E2C-OIT

(NEW)

F2E2 (ETR)

TELECOM

2B310

ETR

ETR

ETR

ETL

ETL

ETR

F2E2 (ETR)

ETR

ETR

ETR

2B-DS-310-B

2B-DS-310-A

M,2

M,2

ETR

ETR

TELECOM

2B310

19,21

F2E2

19,21

F2E2

ETR

ETL ETL

6767 7575

TELECOM

2A004

A2E1 (ETR)

A2N3 (ETR)

A2C1 (ETR)

J-BOX (ETR)

A2N2 (ETR)

A2N1 (ETR)

GROUND

BAR (ETR)

ELEC

2A005

ETR

ETR

ETR ETR ETR

ETR

ETR

ETL ETL

GROUND

BAR (ETR)

A2N3 (ETR)

A2C1 (ETR)

J-BOX (ETR)

A2N1 (ETR)

A2N2 (ETR)

A2E1 (ETR)

M,2

M,2

2A-DS-004-B

2A-DS-004-A

ETR

ETR

ETR

ETR

ETR

ETR

ETR

ELEC

2A005

TELECOM

2A004

1,3

A2C-OIT

1,3

A2C-OIT

ETL

ETL

NEW

A2C-OIT

(NEW)

TELECOM

2A004

ELEC

2A005

3 3

ETD ETD

ETD

A2E1 (ETR)

A2C1 (ETR)

A2N3 (ETR)

A2N2 (ETR)

A2N1 (ETR)

J-BOX (ETR)

TELECOM

2A004

ELEC

2A005

A2E1 (ETR)

A2C1 (ETR)

A2N3 (ETR)

A2N2 (ETR)

A2N1 (ETR)

J-BOX (ETR)

S1 S1 S1 S1

A2C-OIT

TELECOM

2A018

ETD

ETD

ETD

ELEC

2A017

C2NA (ETR)

LCP (ETR)

C2CA (ETR)

C2C1 (ETR)

C2E1 (ETR)

LCP (ETR)

TELECOM

2A018

ELEC

2A017

S1

S1

S1

S1

C2NA (ETR)

LCP (ETR)

C2CA (ETR)

C2C1 (ETR)

C2E1 (ETR)

LCP (ETR)

C2C1

TELECOM

2B003

ETD

ETD

ELEC

2B004

E2E1 (ETR)E2N1 (ETR)

E2N2 (ETR)

E2N3 (ETR)

E2NA (ETR)

E2CA (ETR)

E2C1 (ETR)

E2C2 (ETR)

LCP (ETR)

TELECOM

2B003 ELEC

2B004

E2E1 (ETR)

E2N1 (ETR)

E2N2 (ETR)

E2N3 (ETR)

E2NA (ETR)

E2CA (ETR)

E2C1 (ETR)

E2C2 (ETR) LCP (ETR)

E2C-OIT

S1

S1

S1

S1

TELECOM

2B310

ETD

ETD

ETD

TELECOM

2B310

S1

S1S1

S1

F2E2th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project NumberCONSULTANTS:

Drawing #

VA Health Care System Approval:

ARCHITECT:

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

ARCH FIRM REG. NO. 20314270 EXP. 06/30/2023

ENGR FIRM REG. NO. 06253 EXP. 06/30/2024

The information on this document is preliminary or incomplete, not for construction, recording purposes, or implementation.

FIRE PROTECTION ENGR

POOLE FIRE PROTECTION

19910 WEST 161ST ST.

OLATHE, KANSAS 66062

(913) 829-8690

FULLY SPRINKLERED

INDUSTRIAL HYGENIST

RIVERFRONT (RSH)

1139 OLIVE ST, SUITE 300

ST. LOUIS, MO 63101

(713) 864-2900

STRUCT ENGR

STAND (SEI)

8234 ROBINSON ST

OVERLAND PARK, KS 66204

(913) 214-2169

COMMISSIONING

ES2

13401 N SANTE FE AVE

OKLAHOMA CITY, OK

(405) 528-4500

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

STAMP:

Drawing Number

Building Number

TELECOMMUNICATION

ASPEN COMMUNICATIONS

7 KIJI-DAVA CIRCLE, STE A

PRESCOTT, AZ 86301

(928) 774-0992

MECH / ELEC / PLUMB ENGR

SPUR DESIGN

11020 KING STREET, STE 350

OVERLAND PARK, KS 66210

(913) 369-7200

FORCE PROTECT

10901 FRONT BEACH RD, UNIT 1415

PANAMA CITY BEACH, FL 32407

(502) 836-4232

PHYSICAL SECURITY

/3

/2

:2 :2

P

M

ENLARGED PLANS

MIJ 48 OF 78ES

BID DOCUMENTS

EHRM INFRASTRUCTURE

UPGRADES - TIER 2

06/02/2023

757-22-705

CHALMERS P. WYLIE VA

420 NORTH JAMES ROAD

COLUMBUS, OHIO 43219-1834

E-403

BLDG 1, ENERGY BLDG, & ENGR. BLDG

SPUR #: 1791.19

N

1/4" = 1'-0" REFERENCING DETAIL: 2/ E-101

BLDG 1 - LEVEL 2 - 2A018 - DEMO PWR5

N

1/4" = 1'-0" REFERENCING DETAIL: 2/ E-101

BLDG 1 - LEVEL 2 - 2A018 - NEW PWR6

N

1/4" = 1'-0" REFERENCING DETAIL: 2/ E-101

BLDG 1 - LEVEL 2 - 2B003 - DEMO PWR9

N

1/4" = 1'-0" REFERENCING DETAIL: 2/ E-101

BLDG 1 - LEVEL 2 - 2B003 - NEW PWR10

N

1/4" = 1'-0" REFERENCING DETAIL: 2/ E-101

BLDG 1 - LEVEL 2 - 2B310 - DEMO PWR13

N

1/4" = 1'-0" REFERENCING DETAIL: 2/ E-101

BLDG 1 - LEVEL 2 - 2B310 - NEW PWR14

ELECTRICAL KEYNOTES

3 DEMOLISH EXISTING LIGHT FIXTURE AND ASSOCIATED CIRCUIT AND CONTROLS BACK TO THE

NEAREST JUNCTION BOX.

50 REMOVE, RETAIN AND KEEP EXISTING ELECTRIFIED DOOR HARDWARE (INCLUDING

KEY-CONTROLLED ALARM SHUNT) IN GOOD WORKING CONDITION. EXISTING BACKBOXES,

PATHWAYS, AND CABLING TO REMAIN. INSTALL ADDITIONAL DOOR CONTROLLERS AND POWER

SUPLIES AS REQUIRED. COORDINATE SYSTEM INTEGRATION INTO FACILITY SCC.

51 INSTALL PREVIOUSLY REMOVED ELECTRIFIED DOOR HARDWARE (INCLUDING

KEY-CONTROLLED ALARM SHUNT) IN EXISTING BACKBOXES. EXTEND CIRCUITING AS

NECESSARY TO ENSURE CIRCUIT CONTINUITY. ANY DEVICES THAT ARE LOST OR DAMAGED

DURING CONSTRUCTION SHALL BE REPLACED WITH MATCHING AT CONTRACTOR'S EXPENSE.

52 DISCONNECT CONDUIT AND ENSURE ADEQUATE SLACK IN CABLING TO ENSURE FOR

TEMPORARY REMOVAL OF PACS ENCLOSURE. ENSURING TO SUPPORT PACS ENCLOSURE

DURING INSTALLATION OF FIRE TREATED PLYWOOD.

53 INSTALL 4'X8' 3/4" FIRE RATED PLYWOOD BACKBOARD PAINTED WITH TWO COATS OF

HIGH-GLOSS WHITE INTUMESCENT PAINT ON ALL SIDES WITH FIRE STAMP VISIBLE.

54 INSTALL PACS ENCLOSURE TO FIRE TREATED PLYWOOD. EXTEND CIRCUITS AS NECESSARY TO

ENSURE CIRCUIT CONTINUITY AND RECONNECT CONDUIT(S).

55 INSTALL NEW PANIC/DURESS PUSH BUTTON. VERIFY AND MATCH EXISTING CONDITIONS TO

ENSURE INTEGRATION INTO EXISTING SYSTEM.

56 INSTALL NEW ELECTRIFIED DOOR HARDWARE (INCLUDING KEY-CONTROLLED ALARM SHUNT).

CONNECT TO EXISTING PACS ENCLOSURE. FIELD VERIFY EXISTING SPARE CAPACITY AND

EXPAND AS NECESSARY TO ENSURE FULLY FUNCTIONAL SYSTEM. INSTALL ADDITIONAL DOOR

CONTROLLERS AND POWER SUPLIES AS REQUIRED. COORDINATE SYSTEM INTEGRATION INTO

FACILITY SCC.

66 EXISTING 208V THREE PHASE RECEPTACLES TO BE RELOCATED. REMOVE AND PRESERVE FOR

REUSE. REFER TO NEW POWER PLAN FOR MORE INFORMATION.

67 RELOCATE EXISTING 208V THREE PHASE RECEPTACLE AS SHOWN. REFER TO DEMO POWER

PLAN FOR MORE INFORMATION.

75 TR ROOM RECEPTACLES TO BE REFED FROM CRITICAL PANEL F2C-OIT. RELABEL ALL

RECEPTACLES TO CIRCUITS FED FROM IN CRITICAL PANEL F2C-OIT.

76 TR ROOM RECEPTACLES TO BE REFED FROM CRITICAL PANEL E2C-OIT. RELABEL ALL

RECEPTACLES TO CIRCUITS FED FROM IN CRITICAL PANEL E2C-OIT.

77 TR ROOM RECEPTACLES TO BE REFED FROM CRITICAL PANEL C2C1. RELABEL ALL

RECEPTACLES TO CIRCUITS FED FROM IN CRITICAL PANEL C2C1.

78 TR ROOM RECEPTACLES TO BE REFED FROM CRITICAL PANEL A2-OIT. RELABEL ALL

RECEPTACLES TO CIRCUITS FED FROM IN CRITICAL PANEL A2C-OIT.

87 RENAME EXISTING PANELBOARD TO F2C-OIT.

N

1/4" = 1'-0" REFERENCING DETAIL: 2/ E-101

BLDG 1 - LEVEL 2 - 2A004 - DEMO PWR1

N

1/4" = 1'-0" REFERENCING DETAIL: 2/ E-101

BLDG 1 - LEVEL 2 - 2A004 - NEW PWR2

N

1/4" = 1'-0" REFERENCING DETAIL: 2/ E-101

BLDG 1 - LEVEL 2 - 2A004 - DEMO LTG3

N

1/4" = 1'-0" REFERENCING DETAIL: 2/ E-101

BLDG 1 - LEVEL 2 - 2A004 - NEW LTG4

N

1/4" = 1'-0" REFERENCING DETAIL: 2/ E-101

BLDG 1 - LEVEL 2 - 2A018 - DEMO LTG7

N

1/4" = 1'-0" REFERENCING DETAIL: 2/ E-101

BLDG 1 - LEVEL 2 - 2A018 - NEW LTG8

N

1/4" = 1'-0" REFERENCING DETAIL: 2/ E-101

BLDG 1 - LEVEL 2 - 2B003 - DEMO LTG11

N

1/4" = 1'-0" REFERENCING DETAIL: 2/ E-101

BLDG 1 - LEVEL 2 - 2B003 - NEW LTG12

N

1/4" = 1'-0" REFERENCING DETAIL: 2/ E-101

BLDG 1 - LEVEL 2 - 2B310 - DEMO LTG15

N

1/4" = 1'-0" REFERENCING DETAIL: 2/ E-101

BLDG 1 - LEVEL 2 - 2B310 - NEW LTG16

EL

RE

ASCR

DM

EL

REAS

CRDM

EL

RE

ASCR

DM

EL

RE AS

CR

DM

EL

RE

ASCR

DM

EL

RE

AS

TELECOM

2A143

B2NA (ETR)

B2CA

B2N1 (ETR)

B2N2 (ETR)

B2N3 (ETR)

B2C2 (ETR)

B2C1 (ETR)

ELEC

2A145

ETR

ETR

ETR

ETR ETR ETR

ETR

ETR

ETR

ETR

ETR

ETR

ETLETL

B2NA (ETR)

B2CA

B2N1 (ETR)

B2N2 (ETR)

B2N3 (ETR)

B2C2 (ETR)

B2C1 (ETR)

2A-DS-143-A

2A-DS-143-B

M,2

M,2

ETR

ETR

ETR

ETR ETR

ETR

ETR

ETR

ETRTELECOM

2A143

ELEC

2A145

ETL

ETL

ETR

B2C-OIT

(NEW)

12,14

B2C-OIT

12,14

B2C-OIT

A3C1

A3E1 (ETR)

A3N1 (ETR)

A3N2 (ETR)

TELECOM

3A004

ELEC

3A005

ETR

ETR

ETR

ETR

ETR

ETR

DATA

PANEL

DATA

PANEL

FIRE

ALARM

PANELS

(ETR)

DATA

PANEL

ETR

ETLETLA3C1 (ETR)

A3E1 (ETR)

A3N1 (ETR)

A3N2 (ETR)

3A-DS-004-B

3A-DS-004-A

M,7

M,2

ETR

ETR

ETR

ETR

ETR

TELECOM

3A004

ELEC

3A005

1,3

A3C1

1,3

A3C1

ETL

ETL

ETR

ETR

TELECOM

2B102

ETR

ETR

ETR

ETRETRETR

ETR

ETR

ETR

DATA BOX NURSE CALL DATA PANEL

DATA PANEL

FIRE

ALARM

PANELS

DATA

PANEL

D2N3 (ETR) D2CA (ETR)

D2N1 (ETR)

D2C1 (ETR)

D2E1 (ETR)

J-BOX (ETR)

D2DNA (ETR)

D2NA (ETR)

LCP (ETR)D2NB (ETR)

D2N1 (ETR)

D2N2 (ETR)

ELEC

2B103

ETL ETL

2B-DS-102-A

2B-DS-102-B

M,2

M,2

D2N3 (ETR)

D2N2 (ETR)

D2N1 (ETR)

LCP (ETR)D2NB (ETR)

D2NA (ETR)

D2DNA (ETR)

D2N1 (ETR)

D2CA (ETR)

D2C1 (ETR)

D2E1 (ETR)

J-BOX (ETR)

ETR

ETR

ETR

ETR

ETRETR

ETR

ETR

ETR

ELEC

2B103

TELECOM

2B102

2,4

D2C-OIT

2,4

D2C-OIT

ETL ETL

NEW

D2C-OIT

TELECOM

2A143

ELEC

2A145

ETDETD3 3

ETD

TELECOM

2A143

ELEC

2A145

S2S2 S2 S2

B2C-OIT

D2C1 (ETR)

D2N1 (ETR)

D2E1 (ETR)

J-BOX (ETR)

D2DNA (ETR)

D2NA (ETR)

D2NB (ETR)

D2N1 (ETR)

D2N2 (ETR)

D2N3 (ETR) D2CA (ETR)

LCP (ETR)

TELECOM

2B102

ETD

ETD 3

ETD

ELEC

2B103

D2C1

D2N1

D2E1

J-BOX

D2DNA (ETR)

D2NA

D2NB

D2N1

D2N2

D2N3 D2CA

LCP

TELECOM

2B102

ELEC

2B103

S1

S1

S1

S1

D2C-OIT

D2C-OIT

(NEW)

A3C1

A3E1 (ETR)

A3N1 (ETR)

A3N2 (ETR)

TELECOM

3A004

ELEC

3A005

ETD

ETD 3

ETD

A3C1

A3E1 (ETR)

A3N1 (ETR)

A3N2 (ETR)

TELECOM

3A004ELEC

3A005 S1 S1S1S1

A3C1 th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project NumberCONSULTANTS:

Drawing #

VA Health Care System Approval:

ARCHITECT:

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

ARCH FIRM REG. NO. 20314270 EXP. 06/30/2023

ENGR FIRM REG. NO. 06253 EXP. 06/30/2024

The information on this document is preliminary or incomplete, not for construction, recording purposes, or implementation.

FIRE PROTECTION ENGR

POOLE FIRE PROTECTION

19910 WEST 161ST ST.

OLATHE, KANSAS 66062

(913) 829-8690

FULLY SPRINKLERED

INDUSTRIAL HYGENIST

RIVERFRONT (RSH)

1139 OLIVE ST, SUITE 300

ST. LOUIS, MO 63101

(713) 864-2900

STRUCT ENGR

STAND (SEI)

8234 ROBINSON ST

OVERLAND PARK, KS 66204

(913) 214-2169

COMMISSIONING

ES2

13401 N SANTE FE AVE

OKLAHOMA CITY, OK

(405) 528-4500

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

STAMP:

Drawing Number

Building Number

TELECOMMUNICATION

ASPEN COMMUNICATIONS

7 KIJI-DAVA CIRCLE, STE A

PRESCOTT, AZ 86301

(928) 774-0992

MECH / ELEC / PLUMB ENGR

SPUR DESIGN

11020 KING STREET, STE 350

OVERLAND PARK, KS 66210

(913) 369-7200

FORCE PROTECT

10901 FRONT BEACH RD, UNIT 1415

PANAMA CITY BEACH, FL 32407

(502) 836-4232

PHYSICAL SECURITY

/3

/2

:2 :2

P

M

ENLARGED PLANS

MIJ 49 OF 78ES

BID DOCUMENTS

EHRM INFRASTRUCTURE

UPGRADES - TIER 2

06/02/2023

757-22-705

CHALMERS P. WYLIE VA

420 NORTH JAMES ROAD

COLUMBUS, OHIO 43219-1834

E-404

BLDG 1, ENERGY BLDG, & ENGR. BLDG

SPUR #: 1791.19

N

1/4" = 1'-0" REFERENCING DETAIL: 2/ E-101

BLDG 1 - LEVEL 2 - 2A143 - DEMO PWR5

N

1/4" = 1'-0" REFERENCING DETAIL: 2/ E-101

BLDG 1 - LEVEL 2 - 2A143 - NEW PWR6

N

1/4" = 1'-0" REFERENCING DETAIL: 1/ E-102

BLDG 1 - LEVEL 3 - 3A004 - DEMO PWR9

N

1/4" = 1'-0" REFERENCING DETAIL: 1/ E-102

BLDG 1 - LEVEL 3 - 3A004 - NEW PWR10

ELECTRICAL KEYNOTES

3 DEMOLISH EXISTING LIGHT FIXTURE AND ASSOCIATED CIRCUIT AND CONTROLS BACK TO THE

NEAREST JUNCTION BOX.

50 REMOVE, RETAIN AND KEEP EXISTING ELECTRIFIED DOOR HARDWARE (INCLUDING

KEY-CONTROLLED ALARM SHUNT) IN GOOD WORKING CONDITION. EXISTING BACKBOXES,

PATHWAYS, AND CABLING TO REMAIN. INSTALL ADDITIONAL DOOR CONTROLLERS AND POWER

SUPLIES AS REQUIRED. COORDINATE SYSTEM INTEGRATION INTO FACILITY SCC.

51 INSTALL PREVIOUSLY REMOVED ELECTRIFIED DOOR HARDWARE (INCLUDING

KEY-CONTROLLED ALARM SHUNT) IN EXISTING BACKBOXES. EXTEND CIRCUITING AS

NECESSARY TO ENSURE CIRCUIT CONTINUITY. ANY DEVICES THAT ARE LOST OR DAMAGED

DURING CONSTRUCTION SHALL BE REPLACED WITH MATCHING AT CONTRACTOR'S EXPENSE.

52 DISCONNECT CONDUIT AND ENSURE ADEQUATE SLACK IN CABLING TO ENSURE FOR

TEMPORARY REMOVAL OF PACS ENCLOSURE. ENSURING TO SUPPORT PACS ENCLOSURE

DURING…

This is the start of the file's text. The full file is on GovTribe.