SIDE VIEW TRAPEZE HANGER FOR UP TO
453KG [1000 LB.] UNIFORM LOAD
ADJUSTABLE CLEVIS HANGER
TYPE 1 - SEE SPECIFICATIONS
ADJUSTABLE CLEVIS HANGER TYPE
43 - SEE SPECIFICATIONS
MAXIMUM PIPE/TUBING SUPPORT SPACING
NOTE: FOR TRAPEZE HANGER TAKE SPACING OF SMALLEST SIZE ON TRAPEZE.
NOM. SIZE
PIPE
TUBING
PIPE HANGERS
mm
[IN]
mm
[FT]
mm
[FT]
THRU 20
[THRU3
4]
[7]
[5]
[1]
[7]
[6]
[114]
[7]
[7]
[112]
[9]
[8]
[2]
[10]
[8]
[212]
[11]
[9]
[3]
[12]
[10]
[4]
[14]
[12]
[5]
[16]
[13]
[6]
[17]
[14]
[8]
[19]
[16]
[10]
[22]
[12]
[23]
[14]
[25]
[16]
[27]
[18]
[28]
[20]
[30]
[24]
[32]
NTS
SEISMIC BRACING DETAIL
TRANSVERSE
NOTES:
1. MAXIMUM STRUT LENGTH 8"
2. STRUT TO CLIP BOLT DIAMETER 1\2"
3. BY OTHER'S: HILTI'S NUTS, BOLTS, WASHERS.
4. SEISMIC RESTRAINTS SHALL BE PROVIDED PER THE LATEST ADOPTED EDITION OF THE APPLICABLE STATE BUILDING CODE AND THE SMACNA
SEISMIC RESTRAINT MANUAL, GUIDELINES FOR MECHANICAL SYSTEMS. THE CONTRACTOR SHALL SUBMIT SHOP DRAWINGS OF THE PROPOSED
RESTRAINTS, STRUCTURAL ATTACHMENT METHODS AND RESTRAINT LOCATIONS TO THE ARCHITECT FOR REVIEW AND APPROVAL. THE SUBMITTED DOCUMENTS SHALL BE PREPARED AND STAMPED BY A STRUCTURAL ENGINEER LICENSED IN THE PROJECT LOCATION.
CONFIGURATION WORKS
FOR EITHER SIDE
1-5\8" X 1-5\8" X 12 GA
STRUT UNISTRUT P1000
SERIES OR SIMILAR
CONNECTION
TO STRUCTURE
5\8" HILTI KB TZ (4" MIN
EMBEDMENT LENGTH)
A 307 STEEL
BOLT
ANGLE
MIN: 30
MAX: 60
PIPE
U-BOLTS
DECK
LONGITUDINAL
1-5\8" X 1-5\8" X 12 GA
STRUT UNISTRUT P1000
SERIES OR SIMILAR
1-5\8" X 1-5\8" X 12 GA
STRUT UNISTRUT P1000
SERIES OR SIMILAR
1-5\8" X 1-5\8" X 12
GA STRUT
UNISTRUT P1000
SERIES OR SIMILAR
P
D
C
D+[1"]
NTS
D+25mm
PIPE ANCHOR SCHEDULE
D P C N S BOLT PATTERN
STEAM COIL - PIPING CONNECTIONS
NTS4
NTS
SMALL PIPE ANCHOR 38-102mm [11 2"-4"]
INSULATE AS INDICATED FOR ALL
CHILLED WATER. INSULATE PIPE ONLY
FOR STEAM, CONDENSATE
& HEATING WATER.
NOTE:
WHERE USED FOR COPPER TUBE OR PIPE, BRAZE TO FABRICATED
STEEL ANCHOR
D+[21 2"]
D+[43 4"]
D+121mm
D+64mm
D+[11 2"]
D+38mm
D+[33 4"]
D+95mm
8mm
[516"]
ANCHOR BOLTS
N=NUMBER
S=SIZE
DRILL Ø = S+2mm
DRILL Ø = S+[116"]
STL PIPE OR
COPPER TUBE
D=PIPE O.D.
NOTE A
mm in mm in mm in mm in mm in
13 1 2"
102 4
19 3
NOTES:
1. WHEN COIL IS INCLUDED IN CASING MOUNTED ON
VIBRATION ISOLATOR UNITS, THE RUNOUT PIPING FOR
CONNECTIONS TO COIL SHALL BE INSTALLED WITH
SWING JOINTS TO ALLOW FOR THE VIBRATION.
2. PIPING SHALL BE INSTALLED IN SUCH MANNER THAT IT
WILL NOT BLOCK THE SWING OR USE OF ACCESS DOORS
OR PANELS; NEITHER SHALL IT BLOCK THE SERVICING
OF FILTERS, VALVES, OR EQUIPMENT.
3. TRAP EACH COIL SEPARATELY WHEN INSTALLED IN A
BANK OF TWO OR MORE HIGH. ALSO PROVIDE SEPARATE
VACUUM BREAKER FOR EACH COIL.
4. TWO TRAP ASSEMBLIES IN PARALLEL ARE SHOWN. TWO
TRAPS REQUIRED WHEN CONDENSATE LOAD IS 2400
KG/HR [5,000 LBS/HR] OR GREATER.
5. SUPPLY & RETURN PIPES ARE SHOWN FROM SAME END.
REHEAT COIL MAY HAVE SUPPLY & RETURN PIPES FROM
OPPOSITE ENDS.
PIPE HANGER SHALL
SUPPORT PIPING
INDEPENDENT OF
COIL (TYP.)
PITCH COIL DOWN
8mm [1/4"] PER FOOT
TO CONDENSATE
OUTLET
FULL SIZE
TAPPING
PRESSURE
GAGE
SCALE POCKET
SEE NOTE
NO. 4
STEAM CONDENSATE
RETURN
15mm [1 /2"]
CHECK VALVE
VACUUM
BREAKER
INCREASER,
IF REQUIRED
REDUCER,
IF REQUIRED
STEAM SUPPLY
STEAM
CONDENSATE
RETURN
TEMPERATURE
SWITCH
SCALE POCKET
HUMIDIFIER
CONTROL VALVE
TO HUMIDISTAT
MANIFOLD PIPE ADAPTERS
STEAM SUPPLY
ON-OFF CONTROL VALVE DUCT CROSS SECTION
INVERTED
BUCKET
TRAP ASSEMBLY
NOTE:
SEE MANUFACTURER'S PIPING RECOMMENDATIONS FOR
FINAL LAYOUT
STEAM HUMIDIFIER - PIPING CONNECTIONS (MULTIPLE DISPERSION TUBES)
PROVIDE INSULATION SHIELD
& INSERT FOR ALL PIPING
(200mm [8"] MIN.)
BAND
43mm [1-5/8"] 12 GAUGE CHANNEL OR 50x50x6.4mm
[2"X2"X1/4"] ANGLE
15mm [1/2"] DIA.
HANGER RODS WITH
900mm [36"] MAX.
SPACING ON EACH
CHANNEL
WELD
SADDLE
INSULATION SHIELD
AT HANGER
PROVIDE HIGH COMPRESSIVE
STRENGTH INSULATION (9 PSF
MIN. DENSITY) UNDER
INSULATION SHIELD
INSULATION (VAPOR
BARRIER TYPE IS
REQUIRED FOR LOW
TEMPERATURE PIPE)
HANGER ROD
NOTE:
SEE SPECIFER FOR DETAILED HANGER
REQUIREMENTS
m m
[6
M
IN
m m [1
M
IN
D U
C T
H E
IG
H
T
H1 /3
H
/3 H
/3
H
Project NumberProject NumberProject NumberProject Number
Building NumberBuilding NumberBuilding NumberBuilding Number
Drawing NumberDrawing NumberDrawing NumberDrawing Number
Project TitleProject TitleProject TitleProject Title
LocationLocationLocationLocation
Issue DateIssue DateIssue DateIssue Date CheckedCheckedCheckedChecked DrawnDrawnDrawnDrawn
Drawing TitleDrawing TitleDrawing TitleDrawing Title
Approved:Approved:Approved:Approved:
VA FORM 08 - 6231
AAAA
CONSTRUCTION
DOCUMENTS
FULLY
SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
BBBB
CCCC
DDDD
EEEE
PhasePhasePhasePhase
ARCHITECT STAMPSTAMPSTAMPSTAMPCONSULTANTS 523A4-20-205
VAMC WEST ROXBURY
EXPAND EMERGENCY
DEPARTMENT
William Pevear Architects, Inc.
872 Massachusetts Ave. Suite 2-9 Cambridge, MA 02139
T: 617.335.5186
Alares Engineering
248 Copeland Street, 2nd Floor Quincy, MA 02169
T: 617.481.6390
MEP/FP ENGINEER
Drawing ScaleDrawing ScaleDrawing ScaleDrawing Scale
333322221111 4444 5555 6666 7777 8888
AAAA
BBBB
CCCC
DDDD
EEEE
333322221111 4444 5555 6666 7777 8888
1400 VFW PARKWAY, WEST ROXBURY, MA 02132
01/31/2024
CODE CONSULTANT
Hastings Consulting
142 Hanlon Road Holliston, MA 01746
T: 508.397.8417
N
C U se rs
\Q n g u y e n
\D o c u m e n ts
\W R
-E D
M e ch S ta m p e d b g o ld s te in R
C
Y M
.r v t
/2
/2
:3 :1
P
M
NTS
MI-101
HVAC DETAILS
HLHLHLHL PSPSPSPSRevision:Revision:Revision:Revision: Date:Date:Date:Date:
POS # MODULE LENGTH (IN) WEIGHT (LBS)
1 CONTROLS SECTION 27 450.57
2 ACCESS SECTION 10 105.67
3 SUPPLY FAN SECTION 50 1126.25
4 AIR MIXING SECTION 1 36 1
8 438.89
5 AIR MIXING SECTION 2 36 1
8 438.89
6 PRE/ PRIME FILTER SECTION 19 224.47
7 CUSTOM LENGTH SECTION 4 36.77
8 STEAM COIL SECTION 10 291.62
9 ACCESS SECTION 10 135.21
10 CHILLED WATER COIL SECTION 14 532.24
11 ACCESS SECTION 10 135.21
12 HUMIDIFICATION SECTION 14 1
8 406.40
13 ACCESS SECTION 36 1
8 346.37
14 RETURN FAN SECTION 41 1048.79
15 FINAL FILTER SECTION 14 170.33
16 DISCHARGE SECTION 24 1
2 284.65
ROOF CURB 419.87
INSTALLED UNIT WEIGHT 6592.19
37-11/16"
26-1/16"
35"
4-7/16"
3"
30" Sq.
OPENING 25-1/2" Sq.
24 1/2" 14" 41" 36 1/8" 14 1/8" 10" 14" 10" 10" 4' 19" 36 1/8" 50" 10' 27"
319 3/4"
NTS
OUTSIDE AIR INTAKE DETAIL
WIRE MESH SCREEN
AIR FLOW
ROOF
LARGER OPENING TO
PREVENT UNIT FROM
INTAKING SNOW. FACE
VELOCITY MUST BE LESS
THAN 500 FPM.
NOTE:
1. REFER TO FP FOR DUCT SIZE.
IN TO AIR HANDLER
NTS
3-EF-50 DETAIL
NTS
3-EF-50 ROOF CURB DETAIL
EXISTING ROOF CURB CUT 25-1/2" Sq. OPENING IN
EXISTING ROOF CURB AND SECURE
NTS
3-AHU-1A DETAIL
1234789 610111213141516
ELEVATION VIEW
TOP VIEW
1234789 610111213141516 5
OUTSIDE AIR INTAKE
DUCTWORK
NTS
AHU ROOF CURB DETAIL
HVAC CURB BY
OTHERS
CONCRETE ROOF SLAB
3-1/2" EMD
2X6 PT SLEEPER W/ 5/8
CONC ANCHORS @ 3' OC
PROVIDE COUNTERSINK
HOLE @3' OC.
NEW RIGID INSULATION &
ROOF MEMBRANE
STAINLESS METAL FLASHING
& NEOPRENE PAD (TYP.)
EXHAUST FAN
NTS
3-EF-50 CONTROLS
1. EXHAUST FAN WILL OPERATE AT
CONSTANT VOLUME OF 3000 CFM (ADJ.).
2. WHEN ROOM TEMPERATURE IS ABOVE 85°F
(ADJ.) THE EXHAUST FAN SHALL BE "ON".
3. WHEN THE ROOM TEMPERATURE IS
BELOW 85°F (ADJ.) THE EXHAUST FAN
SHALL BE "OFF".
LINE VOLTAGE
THERMOSTAT
T
TOP CONNECTION
*REFER TO ARCHITECTURAL FOR MORE DETAILS
FAN TO EXTENSION CURB
CURB OVER OPENING
EXTENSION CURB
Project NumberProject NumberProject NumberProject Number
Building NumberBuilding NumberBuilding NumberBuilding Number
Drawing NumberDrawing NumberDrawing NumberDrawing Number
Project TitleProject TitleProject TitleProject Title
LocationLocationLocationLocation
Issue DateIssue DateIssue DateIssue Date CheckedCheckedCheckedChecked DrawnDrawnDrawnDrawn
Drawing TitleDrawing TitleDrawing TitleDrawing Title
Approved:Approved:Approved:Approved:
VA FORM 08 - 6231
AAAA
CONSTRUCTION
DOCUMENTS
FULLY
SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
BBBB
CCCC
DDDD
EEEE
PhasePhasePhasePhase
ARCHITECT STAMPSTAMPSTAMPSTAMPCONSULTANTS 523A4-20-205
VAMC WEST ROXBURY
EXPAND EMERGENCY
DEPARTMENT
William Pevear Architects, Inc.
872 Massachusetts Ave. Suite 2-9 Cambridge, MA 02139
T: 617.335.5186
Alares Engineering
248 Copeland Street, 2nd Floor Quincy, MA 02169
T: 617.481.6390
MEP/FP ENGINEER
Drawing ScaleDrawing ScaleDrawing ScaleDrawing Scale
333322221111 4444 5555 6666 7777 8888
AAAA
BBBB
CCCC
DDDD
EEEE
333322221111 4444 5555 6666 7777 8888
1400 VFW PARKWAY, WEST ROXBURY, MA 02132
01/31/2024
CODE CONSULTANT
Hastings Consulting
142 Hanlon Road Holliston, MA 01746
T: 508.397.8417
N
C U se rs
\Q n g u y e n
\D o c u m e n ts
\W R
-E D
M e ch S ta m p e d b g o ld s te in R
C
Y M
.r v t
/2
/2
:3 :1
P
M
NTS
MI-102
HVAC DETAILS
AIR DEVICE SCHEDULE (RETURN)
MARK TYPE
AIR FLOW
MAX APD
MOUNTING
PANEL/FRAME SIZE NECK SIZE
NC DAMPER FINISH REMARKSMIN MAX
CFM CFM IN WG IN x IN IN x IN
RG-1 SECURE GRILLE 100 250 0.028 CEILING 14 x14 12 x 12 13 NONE WHITE SEE NOTE 1, 2
NOTE
1. PROVIDE SQUARE TO ROUND ADAPTER.
2. BASIS OF DESIGN: TITUS SG-SD
AIR HANDLING UNIT SCHEDULE
MARK LOCATION
AREA AND/OR BLDG
SERVED
TYPE AIR FLOW
AIR FLOW
SUPPLY FAN MARK
RETURN OR RELIEF FAN
MARK
EXHAUST FAN MARK PREFILTER MARK
PRIMARY FILTER
MARK
FINAL FILTER MARK PREHEAT COIL MARK COOLING COIL MARK REHEAT COIL HUMIDIFIER MARK REMARKSSUPPLY MIN OA RETURN
CFM CFM CFM
3-AHU-1A LOW ROOF 3 ED PRE-ENGINEERED VAV 6200 1700 4500 3-SF-1, 3-SF-2 3-RF-1, 3-RF-2 NA 3-PF-1 3-PRF-1 3-FF-1 3-PHC-1 3-CC-1 AT TU 3-H-1 SEE NOTE 1 AND NOTE 2
NOTES
1. COILS SIZED BASED ON 100% OA EMERGENCY SITUATION
2. BASIS OF DESIGN: TRANE PERFORMANCE CLIMATE CHANGER AIR HANDLER CSAA014
FAN SCHEDULE
MARK LOCATION
AREA AND/OR BLDG
SERVED
SYSTEM AND/OR SERVICE
NEW AIR
FLOW
EXISTING
AIR FLOW
NEW TSP
EXISTING
TSP
FAN MOTOR ELECTRICAL
CONTROL
SEQUENCE
REMARKS
TYPE WHEEL CLASS ARRANGEMENT, ROTATION, AND DISCHARGE
DIAMETER
MIN % EFF DRIVE
NEW FAN
MAX RPM
EXISTING FAN
MAX RPM
NOMINAL POWER
PHASE VOLT RPM SPEED CONTROL
CFM CFM IN IN IN BHP HP
3-EF-50 LOW ROOF 3-GC-100 EMERGENCY GENERATOR ROOM 3000 --- 0.50 --- DOWNBLAST CENTRIFUGAL BIW --- ARR 10, CW ROTATION, DOWNBLAST DISCHARGE 19.5 48% BELT 823 --- 0.56 0.75 1 208 1725 CONSTANT --- SEE NOTE 2 AND NOTE 4
3-SF-1
LOW ROOF 3 ED 3-AHU-1 6200 --- 5.96 --- SINGLE WIDTH SINGLE INLET AIRFOIL --- ARR 4, INLINE, HORIZ. DISCHARGE 15.0 58% DIRECT 3555 --- 5.03 5.0 3 460 1800 VARIABLE INCLUDED SEE NOTE 3
3-SF-2
3-RF-1
LOW ROOF 3 ED 3-AHU-1 6200 --- 2.01 --- SINGLE WIDTH SINGLE INLET AIRFOIL --- ARR 4, INLINE, HORIZ. DISCHARGE 16.5 61% DIRECT 1979 --- 1.60 3.0 3 460 1800 VARIABLE INCLUDED SEE NOTE 3
3-RF-2
NOTE
1. ALL SELECTIONS ARE BASED ON AN ALTITUDE OF 16'.
2. BASIS OF DESIGN: COOK ACE-B 195C6B
3. BASIS OF DESIGN: TRANE PERFORMANCE CLIMATE CHANGER AIR HANDLER CSAA014
4. CONTROLLED WITH LINE VOLTAGE THERMOSTAT. BASIS OF DESIGN: DAYTON 1UHH2
CHILLED WATER COOLING COIL SCHEDULE
MARK LOCATION
AREA
AND/OR
BLDG
SERVED
SYSTEM
AND/OR
SERVICE
AIR FLOW
MAX FACE
VELOCITY
APD
EAT LAT TOTAL
CAPACITY
SENSIBLE
CAPACITY
CHILLED WATER (30% GLYCOL)
REMARKSDb Wb Db Wb FLOW EWT LWT WPD
CFM FPM IN WG °F °F °F °F MBH MBH GPM °F °F FT
3-CC-1 LOW ROOF 3 ED 3-AHU-1 6200 461 0.70 91 73 55.0 54.9 373 247 67.3 44 56 19.6 ---
NOTE
THE COOLING COIL FIN SPACING SHALL NOT EXCEED 132 FINS PER FOOT.
STEAM HEATING COIL SCHEDULE
MARK LOCATION
AREA
AND/OR
BLDG
SERVED
SYSTEM
AND/OR
SERVICE
APPLICATION
AIR FLOW
MAX FACE
VELOCITY
APD
TEMPERATURES TOTAL MIN
CAPACITY
STEAM
REMARKSEAT LAT ENT CONT VALVE ENT COIL FLOW STEAM TRAP
CFM FPM IN WG °F °F MBH PSIG PSIG LBS/HR MARK LBS/HR
3-PHC-1 LOW ROOF 3 ED 3-AHU-1 PREHEAT 6200 496 0.10 5.0 53.5 326 --- 5 339.4 --- --- ---
STEAM HUMIDIFER SCHEDULE
MARK LOCATION
SYSTEM
AND/OR
SEVICE
HUMIDIFIER TYPE
AIR
FLOW # OF
MANIFOLDS
EAT LAT
SOURCE
STEAM
CONTROL
TYPE
TRAP
REMARKSDb DEWPOINT
%RH
DEWPOINT
PRESS ENT
VALVE
PRESS ENT
HEATER
FLOW
MARK
CAPACITY
CFM °F °F °F PSIG PSIG LBS/HR LBS/HR
3-H-1 LOW ROOF 3-AHU-1
UNIT-MOUNTED
DISPERSION TUBE
6200 1 78 39.3 50% 59
BUILDING
STEAM
5.0 --- 148 --- --- --- ---
AIR FILTER SCHEDULE
MARK LOCATION
AREA AND/OR
BLDG SERVED
SYSTEM
AND/OR
SERVICE
MERV RATING
AIR FLOW
APD
HOUSING
TYPE
CARTRIDGES
INITIAL CHANGEOVER
SIZE
ARRANGEMENT REMARKS
CFM IN IN IN
3-PF-1 LOW ROOF 3 ED 3-AHU-1 8 6200 0.631 --- SIDE
4 20 x 16 x 2
3 WIDE BY 2 HIGH ---
2 25 x 16 x 2
3-PRF-1 LOW ROOF 3 ED 3-AHU-1 11 6200 0.622 --- SIDE
4 20 x 16 x 4
3 WIDE BY 2 HIGH ---
2 25 x 16 x 4
3-FF-1 LOW ROOF 3 ED 3-AHU-1 14 6200 0.783 --- SIDE
4 20 x 16 x 4
3 WIDE BY 2 HIGH ---
2 25 x 16 x 4
FAN VFD SCHEDULE
MARK HP V PH INPUT FREQUENCY (HZ) OUTPUT FREQUENCY (HZ) AMPS
MINIMUM POWER
FACTOR
MAX ACCELERATION
TIME (SEC)
MIN ACCELERATION
TIME (SEC)
REMARKS
VFD-3-SF-1A
5 460 3 48-63 97 --- 0.98 1800 1800 SEE NOTE 1
VFD-3-SF-1B
VFD-3-RF-1A
3 460 3 48-63 97 --- 0.98 1800 1800 SEE NOTE 1
VFD-3-RF-1B
NOTE
1. BASIS OF DESIGN: TRANE TR200
AIR DEVICE SCHEDULE (SUPPLY)
MARK TYPE
AIR FLOW
MAX APD
MOUNTING
PANEL/FRAME SIZE NECK SIZE
NC DAMPER FINISH REMARKSMIN MAX
CFM CFM IN WG IN x IN IN
SD-1 SECURE DIFFUSER 100 250 0.028 CEILING 14 x14 12 x 12 13 NONE WHITE SEE NOTE 2
NOTES
1. PROVIDE SQUARE TO ROUND ADAPTER.
2. BASIS OF DESIGN: TITUS SG-SD
Project NumberProject NumberProject NumberProject Number
Building NumberBuilding NumberBuilding NumberBuilding Number
Drawing NumberDrawing NumberDrawing NumberDrawing Number
Project TitleProject TitleProject TitleProject Title
LocationLocationLocationLocation
Issue DateIssue DateIssue DateIssue Date CheckedCheckedCheckedChecked DrawnDrawnDrawnDrawn
Drawing TitleDrawing TitleDrawing TitleDrawing Title
Approved:Approved:Approved:Approved:
VA FORM 08 - 6231
AAAA
CONSTRUCTION
DOCUMENTS
FULLY
SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
BBBB
CCCC
DDDD
EEEE
PhasePhasePhasePhase
ARCHITECT STAMPSTAMPSTAMPSTAMPCONSULTANTS 523A4-20-205
VAMC WEST ROXBURY
EXPAND EMERGENCY
DEPARTMENT
William Pevear Architects, Inc.
872 Massachusetts Ave. Suite 2-9 Cambridge, MA 02139
T: 617.335.5186
Alares Engineering
248 Copeland Street, 2nd Floor Quincy, MA 02169
T: 617.481.6390
MEP/FP ENGINEER
Drawing ScaleDrawing ScaleDrawing ScaleDrawing Scale
333322221111 4444 5555 6666 7777 8888
AAAA
BBBB
CCCC
DDDD
EEEE
333322221111 4444 5555 6666 7777 8888
1400 VFW PARKWAY, WEST ROXBURY, MA 02132
01/31/2024
CODE CONSULTANT
Hastings Consulting
142 Hanlon Road Holliston, MA 01746
T: 508.397.8417
N
C U se rs
\Q n g u y e n
\D o c u m e n ts
\W R
-E D
M e ch S ta m p e d b g o ld s te in R
C
Y M
.r v t
/2
/2
:3 :1
P
M
NTS
MI-200
HVAC SCHEDULE
1.5"
3" 3"
55% RH
6.1.2. UNOCCUPIED MODE:
HEATING TEMPERATURE SETPOINT: 60°F (ADJ)
COOLING TEMPERATURE SETPOINT: 85°F (ADJ)
ALARM
PROCESSING
D U
T Y
C Y
C
LE
F U
N C
T
IO
N
S C
H E
D U
LE
S
T A
R T /S
T O
P
S T A T U
S
SYSTEM
A
LA
R M
PR
IO
R
IT
Y/
AD
D -A
LT
ER
N
AT
E N
O
E
LE
C T R
IC
D
E V
IC
E
S P
E E
D C
O M
M A
N D
P O
IN
T T
Y P
E
SYSTEM COMPONENT:
RA TEMPERATURE
-- O P
E N
/C
LO
S E
S T A R
T /S
T O
P -- V
A L V
E P
O S
IT
IO
N
D A
M P
E R
P O
S
IT
IO
N
VAV AIR HANDLER
SYSTEM:
LEGEND
POINT
BINARY
T E
M P
E R
A T U
R E T I)
L oc al A la rm
P an el
M as te r A la rm
P an e l
A re a A la rm
P an el
H
IG
H S
T A
T
IC
P R
E S
S U
R E
H
IG
H H
U M
ID
IT
Y
P R
E S
S U
R E
--L O
W T
E M
P E
R A T U
R E
P E
R C
E N
T
P R
E S
S U
R E
P O
S
IT
IO
N
F
LO
W
H
IG
H L
IM
IT
L O
W L
IM
IT
SYSTEM INPUTS
ANA- BINARY ANALOG
S P
A C
E T
E M
P . C
O N
T R
O L
--S T A
T
IC
P R
E S
S U
R E
R E
S E
T
--D E
M A
N D
L
IM
IT
IN
G
T E
M P
E R
A T U
R E R
E S
E T
T E
M P
E R
A T U
R E O
V E
R R
ID
E
E N
T H
A
LP
Y E
C O
N O
M
IZ
E R
T E
M P
E R
A T U
R E E
C O
N O
M
IZ
E R
F A
IL
U
R E
M O
D E
PR
ES
SU
R
E/
VO
LU
M
E C
O N
TR
O
L
REMARKS
F U
LL
C
O M
M U
N
IC
A T
IO
N
SYSTEM SOFTWARE/CONTROL
APPLICATION/FUNCTION
PAGE:
S T A T
IC
P R
E S
S U
R E
C A
R B
O N
M O
N O
X
ID
E
H U
M
ID
IT
Y
V A
C U
U M
AI
T R
E N
D
IN
G
A B
B R
E V
IA
T
IO
N
RAT
OUTPUTS
LOG
RETURN FAN VFD ALARM
SUPPLY FAN VFD ALARM
RETURN FAN STATUS
STATIC PRESSURE HIGH LIMIT
SA FLOW (CFM)
DISCHARGE STATIC PRESSURE
DA TEMPERATURE
MA TEMPREATURE
RA FLOW (CFM)
SUPPLY FAN STATUS
MIXED AIR LOW LIMIT
RETURN AIR DAMPER
RETURN FAN START/STOP
HEATING COIL VALVE
EXHAUST AIR DAMPER
SUPPLY FAN VFD
OUTSIDE AIR DAMPER
RETURN FAN VFD
SUPPLY FAN START/STOP
AI
AI
AI
AI
AI
OA TEMPERATURE AI
BI
BI
BI
BI
BI
BI
AO
AO
AO
AO
AO
AO
BO
BO
FULL COMMUNICATION
FULL COMMUNICATION
RAF
MAT
DAT
DASP
SAF
OAT
RF-STS
SF-STS
TSL-1
SPS-1
SF-ALA
RF-ALA
RF-SPD
SF-SPD
OAD
RAD
EAD
HC-ACV
RF-SST
SF-SST
PRE-FILTER STATUS AI PF-STS
FINAL-FILTER STATUS AI FF-STS
OA FLOW (CFM) AI OAF
COOLING COIL VALVE AO CC-ACV
RA SMOKE DAMPER BI RASD
SA SMOKE DAMPER BI SASD
HUMIDIFIER VALVE AO H-ACV
SPACE HUMIDITY AI RAH
NTS
3-AHU-1A CONTROL DIAGRAM
RETURN
AIR
TT
TT
FT
TT MT
FT
H-1
SD
PSH
ZC
ZC
ZC
FT
PDS PDS
TT
PSL
SASD
SD
RASD
SPSTSL
PDS
HSVFD
IT
SST
ECC
MT
H-2
NTS
PRIME-FILTER STATUS AI PRF-STS
NTS
HSVFD
IT
SST
ECC
HSVFD
IT
SST
ECC
HSVFD
IT
SST
ECC
OUTSIDE AIR HUMIDITY AI OAH
EXHAUST AIR
EAD
RAD
P R
E
F
IL
T E
R
OUTSIDE
AIR
OAD
S
T E
A M
C O
IL
P
R E
H E
A T
C H
W C
O
IL
C O
O L
IN
G
LOCATE SENSOR
OUTSIDE UNDER
SHIELD
CC-ACV
CHWR
CHWS
RETURN FAN
SUPPLY FANS
A F
M D
A F
M D
SUPPLY AIR TO
TERMINAL UNIT
P R
IM
E
F
IL
T
E R
A F
M D
SMOKE
DETECTOR
H-ACV
LPS
F
IN
A L
F
IL
T E
R
LPS
HC-ACV
CURRENT
TRANSMITTER FOR
FAN STATUS, TYP.
VARIABLE FREQUENCY
DRIVE, TYP.
POINTS LIST FOR 3-AHU-1A 3-AHU-1A SEQUENCE OF OPERATION
LOCATE AT 2/3
OF DUCT RUN
RETURN FANS
ZC
ZC
IAD-2
IAD-1 RETURN AIR
FROM BUILDING
RETURN AIR
TO EXISTING AHU-1
ZC
ZC
IAD-4
IAD-3
SUPPLY AIR FROM
EXISTING AHU-1
1. GENERAL
1.1. HVAC WORK SHALL TIE INTO THE EXISTING BUILDING MANAGMENT SYSTEM (TRANE). THE GENERAL CONTRACTOR SHALL BEAR THE COST OF EMPLOYING THE SERVICES OF TRANE (CONTACT MICHAEL SOMMERS, WORK (978) 737-3852 / OFFICE (781) 325-6230, 181 BALLARDVALE STREET, SUITE 201, WILMINGTON, MA, 01887).
1.2. DDC SYSTEM IS PROPRIETARY TRANE TRACER ENSEMBLE.
1.3. PROVIDE OCCUPANCY CONTROLS THROUGH THE TRANE BUILDING AUTOMATION SYSTEM (BAS) FOR NIGHT TIME, WEEKEND AND HOLIDAY TEMPERATURE SET BACK AND FAN SETBACK. INCLUDE REQUIREMENT FOR AHU MIXING BOX TEMP CONTROL TO ENSURE THE MIXING BOX CHAMBER DOES NOT OVER HEAT OR GO INTO FREEZE PROTECTION WHEN THE UNIT IS COMMANDED OFF DURING NIGHT/WEEKEND/HOLIDAY SETBACK.
NORMAL LIGHTS SHALL BE CONTROLLED VIA THE BAS NIGHT/WEEKEND/HOLIDAY SETBACK SCHEDULE.
PROVIDE 20% OPTION FOR PEAK LOAD SHAVING DURING NORMAL BUSINESS HOURS. BAS CONTRACTOR TO PROVIDE INTERFACE TO VA ELECTRICAL SUB-METERING TO INITIATE LOAD REDUCTION AS BUILDING NEARS PEAK ELECTRICAL LOAD. INITIATION OF PEAK SHAVE WILL NOTIFY VA THROUGH EXISTING BAS SYSTEM
INTERFACE.
1.4. AT COMPLETION OF PHASED WORK, OR COMPLETION OF PROJECT, TRANE SHALL HAVE ACCOUNT EXECUTIVE, TECHNICAL REPRESENTATIVE & SERVICE REPRESENTATIVE PERFORM A WALKTHROUGH WITH VA PROJECT ENGINEER, HVAC SHOP, M&O MAINTENANCE BOILER PLANT OPERATORS, ETC. TO REVIEW ALL SYSTEMS, COMPONENTS, DEVICES, CONTROLS, PANELS, ETC. INSTALLED & INSTRUCT & DISPLAY ALL WORKING SET POINTS. THIS SHALL BE IN ADDITION TO TRAINING & INSTRUCTIONS ALREADY DESCRIBED IN SPECIFICATIONS.
THIS SHALL BE COORDINATED & SCHEDULED TO OCCUR PRIOR TO TURNING OVER THE SPACE TO THE VA.
1.5. THE TRANE CONTRACTOR SHALL PROVIDE TO THE VA A DUCTWORK MAP TO INDICATE THE AREA THAT 3-AHU-1
SERVES.
1.6. UNIT IS NORMALLY STARTED AND STOPPED REMOTELY AT THE BAS. H-O-A SWITCH SHALL BE KEPT IN THE
"AUTO" POSITION. "HAND" AND "OFF" POSITIONS SHALL BE USED ONLY FOR MAINTENANCE.
1.6.1. WHEN THE UNIT IS "OFF", ALL DAMPERS SHALL BE FULLY CLOSED.
1.6.2. WHEN THE UNIT IS "ON", SDs SHALL BE FULLY OPEN. OAD, EAD, AND RAD SHALL MODULATE IN
ACCORDANCE WITH THE FOLLOWING SEQUENCE:
1.7. SUPPLY OR RETURN SMOKE DETECTORS SHALL BE FURNISHED AND WIRED TO THE FIRE ALARM SYSTEM BY
DIVISION 26. CONTROL CONTRACTOR SHALL MOUNT DETECTORS AND WIRE TO CONTROL SYSTEM.
2. ALARM:
2.1. ALARM SHALL INDICATE AT THE BAS WHEN THE FOLLOWING HAPPEN:
2.1.1. H-O-A SWITCH IS ON "HAND" POSITION.
2.1.2. AHU IS COMMANDED TO RUN, BUT SUPPLY/RETURN FAN OPERATION IS NOT DETECTED BY IT.
2.1.3. SUPPLY AND RETURN FAN VFD FAILURE
2.1.4. OAD, EAD AND RAD POSITIONS ARE NOT VERIFIED BY ZC.
2.1.5. FREEZESTAT TRIPS.
2.1.6. SMOKE IS DETECTED.
2.1.7. THE SUPPLY AIR TEMPERATURE IS 5° F(ADJ.) GREATER THAN THE SUPPLY AIR TEMPERATURE SETPOINT
FOR 20 CONSECUTIVE MIN (ADJ.) IN COOLING MODE.
2.1.8. THE SUPPLY AIR TEMPERATURE IS 5° F(ADJ.) LESS THAN THE SUPPLY AIR TEMPERATURE SETPOINT FOR 20
CONSECUTIVE MIN (ADJ.) IN HEATING MODE.
2.1.9. SUPPLY FAN TRIPS ON HIGH STATIC PRESSURE.
2.1.10. RETURN FAN TRIPS ON LOW STATIC PRESSURE.
3. TEMPERATURE CONTROL
3.1. SUPPLY AIR TEMPERATURE, SENSED BY TT-1, SHALL BE MAINTAINED AT SETPOINT OF 55°F (ADJ.).
3.2. WHEN THE TEMPERATURE OF THE OUTSIDE AIR, SENSED BY TT-2, IS ABOVE 70°F (ADJ.), THE AHU SHALL OPERATE AT MINIMUM OUTSIDE AIR POSITION. RAD SHALL FULLY OPEN, OAD AND EAD SHALL MODULATE IN UNISON TO MAINTAIN MINIMUM OA AIRFLOW RATE, SENSED BY FT-1. THE CONTROLLER SHALL MODULATE CHW COOLING COIL CC-ACV TO MAINTAIN THE SUPPLY AIR TEMPERATURE SET POINT SENSED BY TT-1.
3.3. WHEN THE TEMPERATURE OF THE OUTSIDE AIR SENSED BY TT-2 IS BELOW 70°F AND THE ENTHALPY, SENSED BY MT-H-2 IS LESS THAN RETURN AIR ENTHALPY SENSED BY MT-H-1, THE AHU SHALL OPERATE IN ECONOMIZER MODE. DAMPER RAD SHALL FULLY CLOSE AND OAD AND EAD SHALL BE FULLY OPEN (MAXIMUM OUTSIDE AIR POSITION). THE CONTROLLER SHALL MODULATE CHW COOLING COIL CC-ACV AS NEEDED TO MAINTAIN THE
SUPPLY AIR TEMPERATURE SET POINT SENSED BY TT-1.
3.4. WHEN THE TEMPERATURE OF THE OUTSIDE AIR SENSED BY TT-2 IS BELOW 50°F (ADJ.), THE AHU SHALL OPERATE AT MINIMUM OUTSIDE AIR POSITION. RAD SHALL FULLY OPEN, OAD AND EAD SHALL MODULATE IN UNISON TO MAINTAIN MINIMUM OA AIRFLOW RATE SENSED BY FT-1. THE CONTROLLER SHALL MODULATE LPS PREHEAT COIL HC-ACV TO MAINTAIN THE SUPPLY AIR TEMPERATURE SET POINT SENSED BY TT-1.
4. AIR FLOW CONTROL
4.1. THE CONTROL SYSTEM SHALL MONITOR AND DISPLAY SUPPLY AIR FLOW, RETURN AIR FLOW, AND OUTSIDE AIR FLOW IN CFM ON THE BAS. IT WILL CALCULATE, AND DISPLAY OUTDOOR AIR PERCENTAGE FROM THE
MEASURED VALUES BASED ON THE FOLLOWING FORMULA:
RETURN AIR TEMP - MIXED AIR TEMP
%OA = ----------------------------------------------------------- X 100
RETURN AIR TEMP - OUTSIDE AIR TEMP
4.2. THE SUPPLY AIR FLOW: THE CONTROLLER SHALL MODULATING BOTH SUPPLY FAN VFDs IN UNISON TO MAINTAIN OF DUCT STATIC PRESSURE (TO BE SET BY THE TEST AND BALANCING CONTRACTOR), SENSED BY SPS-1.
THE SUPPLY FAN VFD SPEEDS SHALL NOT DROP BELOW 30% (ADJ.).
4.3. THE RETURN AIR FLOW: THE CONTROLLER SHALL USE TOTAL SUPPLY AIR AND RETURN AIR FLOW SIGNALS AND MODULATE BOTH RETURN FAN VFDs IN UNISON TO MAINTAIN RETURN AIRFLOW SETPOINT. RETURN AIR FLOW RATE SHALL BE EQUAL TO SUPPLY AIR FLOW MINUS 10% (ADJ.) AND MINUS EXHAUST AIR FLOW. THE RETURN
FAN VFD SPEEDS SHALL NOT DROP BELOW 30%(ADJ.).
4.4. PRESSURE SWITCH HIGH (PSH) AT THE SUPPLY FAN DISCHARGE SHALL PREVENT THE SUPPLY FANS FROM DEVELOPING OVER OF STATIC PRESSURE (FIELD ADJUSTABLE). IF STATIC PRESSURE DOES EXCEED THE
SUPPLY AIR FANS SHALL STOP.
4.5. PRESSURE SWITCH LOW (PSL) AT THE RETURN FAN INLET SHALL PREVENT THE RETURN FANS FROM DEVELOPING OVER -3" OF NEGATIVE STATIC PRESSURE (FIELD ADJUSTABLE). IF STATIC PRESSURE DOES GET
BELOW -3" THE RETURN AIR FANS SHALL STOP.
4.6. THE SUPPLY FANS SHALL RUN ANYTIME THE UNIT IS COMMANDED TO RUN UNLESS SHUTDOWN ON SAFETIES.
TO PREVENT SHORT CYCLING, THE SUPPLY FANS SHALL HAVE A USER DEFINABLE (ADJ.) MINIMUM RUNTIME.
5. HUMIDITY CONTROL
5.1. SPACE HUMIDITY, SENSED BY MT-H-1, SHALL BE MAINTAINED AT SETPOINT (ADJ.).
5.2. THE CONTROLLER SHALL MODULATE HUMIDIFIER VALVE TO MAINTAIN THE SPACE HUMIDITY SET POINT.
6. TEMPERATURE AND STATIC PRESSURE RESET
6.1. TRANE CONTRACTOR SHALL ESTABLISH AN OCCUPANCY AND TEMPERATURE SCHEDULE WITH THE VA
INCLUDING WEEKDAY, WEEKEND, AND HOLIDAYS.
6.1.1. OCCUPIED MODE:
HEATING TEMPERATURE SETPOINT: 70°F (ADJ)
COOLING TEMPERATURE SETPOINT: 75°F (ADJ)
6.2. SUPPLY TEMPERATURE RESET:
6.2.1. THE INITIAL SETPOINT IS 55°F (ADJ.)
6.2.2. THE SUPPLY TEMPERATURE SETPOINT SHALL BE RESET USING THE COOLING DEMAND COMMANDS AT
TERMINAL UNITS. THE SUPPLY AIR SHALL RANGE BETWEEN 65 AND 55 (ADJ.) DEGREES.
6.2.3. COOLING DEMAND CAN BE USED TO PROVIDE DAT SETPOINT RESET. IF THERE IS NO COOLING REQUEST
FROM ALL VAVS, THEN AT TWENTY-MINUTE INTERVALS, THE DAT SETPOINT SHALL INCREMENT UP BY 0.5°F (ADJ.) UNITL IT REACHES ITS MAXIMUM ALLOWABLE RESET VALUE OF 58°F (ADJ.) OR ONE VAV REACHES 90% OPEN. THE DAT SETPOINT IS HELD FOR 20 MINUTES (ADJ.) AND THEN START DECREMENT BY 0.5°F (ADJ) UNTIL IT REACHES ITS MINIMUM ALLOWABLE RESET VALUE OF 53°F (ADJ.) OR ALL VAV BOXES ARE 85%
OPEN OR LESS.
6.3. SUPPLY AIR STATIC PRESSURE RESET:
6.3.1. WHEN TWO (ADJ.) OR MORE VAV DAMPERS ARE MORE THAN 90% (ADJ.) OPEN, THE SUPPLY FAN STATIC
PRESSURE SETPOINT SHALL BE RESET UPWARD. THIS WILL CONTINUE UNTIL NO MORE VAV DAMPERS ARE 90% (ADJ.). THE STATIC PRESSURE MAXIMUM SETPOINT TO BE DETERMINED DOCUMENTED BY TEST AND
BALANCE CONTRACTOR).
6.3.2. WHEN ALL BUT ONE (ADJ.) VAV DAMPERS ARE LESS THAN 80% (ADJ.) OPEN, THE SUPPLY FAN STATIC PRESSURE SETPOINT SHALL BE RESET DOWNWARD, UNTIL AT LEAST TWO (ADJ.) DAMPERS ARE MORE THAN 80% OPEN OR THE STATIC PRESSURE SETPOINT HAS RESET TO THE SYSTEM MINIMUM STATIC PRESSURE SETPOINT TO BE DETERMINED AND DOCUMENTED BY TEST AND BALANCE CONTRACTOR).
7. FREEZE PROTECTION
7.1. IF THE AIR TEMPERATURE AS SENSED BY TT-3 FALLS BELOW 45°F, AN ALARM SIGNAL SHALL INDICATE AT THE
BAS.
7.2. IF THIS TEMPERATURE FALLS BELOW 38°F (ADJ.) AS SENSED BY TSL-1, THE FOLLOWING SEQUENCE SHALL
OCCUR:
7.2.1. SUPPLY AND RETURN FANS SHALL SHUT DOWN AND A CRITICAL ALARM SHALL INDICATE AT THE BAS.
7.2.2. DAMPERS OAD AMD EAD SHALL CLOSE.
7.2.3. LPS PREHEAT COIL HC-ACV SHALL OPEN TO 100% (ADJ)
7.3. TSL WILL REQUIRE MANUAL RESET AT THE DEVICE.
8. AUTOMATIC SHUTDOWN/RESTART
8.1. WHEN SMOKE IS DETECTED BY DUCT SMOKE DETECTOR, SD, THE SUPPLY AND RETURN FANS SHALL SHUT "OFF" UNDER ANY OPERATION MODE AND AN ALARM SIGNAL SHALL BE TRANSMITTED TO THE FIRE ALARM
SYSTEM. ALL SMOKE DAMPERS IN THE SUPPLY AND RETURN DUCTS SHALL CLOSE.
8.2. PRESSURE SWITCH HIGH AND LOW SHALL ALSO SHUT "OFF" THE FANS WHEN THE DAMPERS ARE CLOSED.
8.3. ANY EXHAUST FANS SERVING AREA OF THE SUPPLY FAN SHALL CONTINUE TO RUN.
8.4. SUPPLY AND RETURN FANS SHALL RESTART AND SMOKE DAMPERS SHALL OPEN WHEN FIRE ALARM CIRCUIT IS
RESET.
9. FILTERS ALARMS
9.1. PRE-FILTER DIRTY: DIFFERENTIAL PRESSURE IS 1" (ADJ.) GREATER THAN CLEAN FILTER
9.2. PRIME-FILTER DIRTY: DIFFERENTIAL PRESSURE IS 1" (ADJ.) GREATER THAN CLEAN FILTER
9.3. FINAL FILTER DIRTY: DIFFERENTIAL PRESSURE IS 1" (ADJ.) GREATER THAN CLEAN FILTER
10. EMERGENCY CONSTANT SPEED OPERATION
10.1. UPON FAILURE OF A VFD, BOTH SUPPLY AND BOTH RETURN FANS SHALL BE STARTED/STOPPED MANUALLY AT THE DIGITAL CONTROL PANEL OR THE BAS THROUGH THE BY-PASS STARTER. FANS SHALL THEN BE OPERATED
AT CONSTANT SPEED.
11. REDUNDANCY CONTROL
11.1. UPON FAILURE OF ONE OF THE SUPPLY OR RETURN FANS, THE REMAINING SUPPLY OR RETURN FAN SHALL
RAMP UP TO MAINTAIN 1.5" OF DUCT STATIC PRESSURE, SENSED BY SPS-1.
12. EMERGENCY 100% OA OPPERATION
12.1. UNIT SHALL BE CAPABLE OF OPERATING IN 100% OUTDOOR AIR MODE DURING A MEDICAL EMERGENCY CREATED BY A PANDEMIC OF CONTAGIOUS DISEASES. THE 100% OUTDOOR AIR MODE SHALL BE ACTIVATED
MANUALLY THROUGH THE BAS.
12.2. WHEN IN EMERGENCY 100% OUTDOOR AIR MODE DAMPER RAD SHALL FULLY CLOSE AND OAD AND EAD SHALL
BE FULLY OPEN (MAXIMUM OUTSIDE AIR POSITION).
12.3. PREHEAT COIL HC-ACV AND/OR COOLING COIL CC-ACV SHALL MODULATE AS NEEDED TO MAINTAIN THE SUPPLY
AIR TEMPERATURE SET POINT SENSED BY TT-1.
13. COLD START SEQUENCE
13.1. WHENEVER UNIT IS STARTED AND OUTDOOR AIR TEMPERATURE IS BELOW 30° F INITIATE THE FOLLOWING
SEQUENCE.
13.1.1. DAMPERS OAD AND EAD SHALL BE CLOSED.
13.1.2. DAMPER RAD SHALL BE 100% OPEN (ECONOMIZER DISABLED).
13.1.3. COMMAND OPEN LPS PREHEAT COIL HC-ACV.
13.1.4. HC-ACV SHALL MODULATE TO MAINTAIN 80 DEGREE SUPPLY AIR TEMPERATURE.
13.1.5. SMOKE DAMPER SHALL BE OPEN.
13.1.6. COMMAND ON SUPPLY AND RETURN (DRIVE) AND ALLOW TO RAMP UP NORMALLY.
13.1.7. SET MIXED AIR SETPOINT TO 70° F ONCE SUPPLY/RETURN FAN ON STATUS HAS BEEN PROVEN.
13.1.8. FIVE MINUTES AFTER SUPPLY/RETURN FAN-ON STATUS HAS BEEN PROVEN, DAMPER OAD SHALL DELIVER
5% OF CFM, RAD AND EAD DAMPERS SHOULD OPEN/CLOSE SIMULTANEOUSLY WITH DAMPER OAD. (OA=5%
RA= 95% EX=5%).
13.1.9. FIVE MINUTES AFTER DAMPER OAD STARTED DELIVERING 5%, RELEASE OAD, RAD, EAD AIR DAMPERS TO
CONTROL TO MEET MINIMUM OA AIR FLOW SETPOINT.
13.1.10. LOWER MIXED SET POINT TO 60 DEGREES FOR 10 MINUTES.
13.1.11. RELEASE MIXED AIR SET POINT BACK TO ORIGINAL SETTING
14. AHU SWITCH-OVER SEQUENCE
14.1. WHEN 3-AHU-1A STATUS IS "ON" AND AHU-1 STATUS IS "OFF":
14.1.1. IAD-2 AND IAD-4 SHALL BE OPEN.
14.1.2. IAD-1 AND IAD-3 SHALL BE CLOSED.
14.2. WHEN 3-AHU-1A STATUS IS "OFF" AND AHU-1 STATUS IS "ON":
14.2.1. IAD-2 AND IAD-4 SHALL BE CLOSED.
14.2.2. IAD-2 AND IAD-4 SHALL BE OPEN.
PRESSURE SWITCH LOW
TO DISABLE RETURN FAN WHEN SMOKE
DAMPER IN RETURN DUCT CLOSES
PRESSURE SWITCH HIGH
TO DISABLE FAN WHEN
HIGH PRESSURE LIMIT
SETPOINT IS REACHED
Project NumberProject NumberProject NumberProject Number
Building NumberBuilding NumberBuilding NumberBuilding Number
Drawing NumberDrawing NumberDrawing NumberDrawing Number
Project TitleProject TitleProject TitleProject Title
LocationLocationLocationLocation
Issue DateIssue DateIssue DateIssue Date CheckedCheckedCheckedChecked DrawnDrawnDrawnDrawn
Drawing TitleDrawing TitleDrawing TitleDrawing Title
Approved:Approved:Approved:Approved:
VA FORM 08 - 6231
AAAA
CONSTRUCTION
DOCUMENTS
FULLY
SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
BBBB
CCCC
DDDD
EEEE
PhasePhasePhasePhase
ARCHITECT STAMPSTAMPSTAMPSTAMPCONSULTANTS 523A4-20-205
VAMC WEST ROXBURY
EXPAND EMERGENCY
DEPARTMENT
William Pevear Architects, Inc.
872 Massachusetts Ave. Suite 2-9 Cambridge, MA 02139
T: 617.335.5186
Alares Engineering
248 Copeland Street, 2nd Floor Quincy, MA 02169
T: 617.481.6390
MEP/FP ENGINEER
Drawing ScaleDrawing ScaleDrawing ScaleDrawing Scale
333322221111 4444 5555 6666 7777 8888
AAAA
BBBB
CCCC
DDDD
EEEE
333322221111 4444 5555 6666 7777 8888
1400 VFW PARKWAY, WEST ROXBURY, MA 02132
01/31/2024
CODE CONSULTANT
Hastings Consulting
142 Hanlon Road Holliston, MA 01746
T: 508.397.8417
N
C U se rs
\Q n g u y e n
\D o c u m e n ts
\W R
-E D
M e ch S ta m p e d b g o ld s te in R
C
Y M
.r v t
/2
/2
:3 :1
P
M
NTS
MI-300
HVAC CONTROLS
POWER
208/120V BRANCH CIRCUIT PANELBOARD
480/277V BRANCH CIRCUIT PANELBOARD
TRANSFORMER
MOTOR CONNECTION. NUMBER INDICATES HORSEPOWER
UNFUSED DISCONNECT SWITCH. SIZE AS NOTED
FUSED DISCONNECT SWITCH, SIZE AS NOTED
COMBINATION DISCONNECT SWITCH AND MAGNETIC MOTOR CONTROLLER,
SIZE AS NOTED
FLUSH WALL JUNCTION BOX OR JUNCTION BOX
ABOVE CEILING
DEMOLITION
RECEPTACLE
EXISTING
NEW WORK
GENERAL
UNDERGROUND
SINGLE-POLE SWITCH
GFCI RECEPTACLE
L1-XX
CIRCUIT
DESIGNATION
LIGHTING
2'x4' LIGHTING FIXTURE. SHADING INDICATES FIXTURE TO BE ON
EMERGENCY OR NIGHT LIGHT CIRCUITING.
SPECIAL SYSTEMS
ANTI LIGATURE RECEPTACLE
CONTROL WIRING
NO ELECTRICAL WORK IN AREA
DEMOLITION NOTES
WEATHERPROOF WHILE IN USE GFCI RECEPTACLE
RECEPTACLE. SHADING INDICATES RECEPTACLE IS
MOUTED AT 42" A.F.F.
EXISTING TO REMAIN
TAMPER PROOF RECEPTACLE
CEILING MOUNTED RECEPTACLE
S
T
J
A
TP
WP
GFCI
M
TELECOMMUNICATION CONNECTION
N P
SINGLE PATIENT STATION (ENHANCED) WITH PILLOW
SPEAKER, CODE AND STAFF ASSIST TOUCH POINTS.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
CONSTRUCTION
DOCUMENTS
FULLY
SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
PhaseARCHITECT STAMPCONSULTANTS
Revision: Date:
523A4-20-205
VAMC WEST ROXBURY
EXPAND EMERGENCY
DEPARTMENT
William Pevear Architects, Inc.
872 Massachusetts Ave. Suite 2-9 Cambridge, MA 02139
T: 617.335.5186
Alares Engineering
248 Copeland Street, 2nd Floor Quincy, MA 02169
T: 617.481.6390
MEP/FP ENGINEER
Drawing Scale
321 4 5 6 7 8
A
B
C
D
E
321 4 5 6 7 8
255 SPRING ST, WEST ROXBURY, MA 02132
1/31/2024
CODE CONSULTANT
Hastings Consulting
142 Hanlon Road Holliston, MA 01746
T: 508.397.8417
E-001DLE VAC
ELECTRICAL SYMBOLS &
NOTES
360° SECURITY CAMERAC1
CARD READER
AI PHONE
CR
AI
1. REMOVE ALL OBSOLETE ELECTRICAL EQUIPMENT, FIXTURES, CONDUIT, WIRING, CONTROLS, HANGERS, PADS, AND SUPPORTS UNLESS OTHERWISE INDICATED TO REMAIN. DISCONNECT CIRCUIT AND WIRING FROM EQUIPMENT WHICH IS TO BE REMOVED BY OTHERS. WIRING MADE OBSOLETE BY THE NEW CONSTRUCTION SHALL BE REMOVED.
CONDUIT MADE OBSOLETE BY THE NEW CONSTRUCTION SHALL BE REMOVED OR SECURELY SEALED AND CAPPED ABOVE CEILINGS, BELOW FLOORS, GRADE OR IN WALLS SO THAT IT IS COMPLETELY CONCEALED AT THE COMPLETION OF THE PROJECT. PIPING AND WIRING REMOVED FROM THE EXISTING ELECTRICAL SYSTEMS SHALL NOT BE USED IN
THE INSTALLATION OF THE NEW SYSTEMS.
2. DEMOLITION INCLUDES, BUT IS NOT LIMITED TO, REMOVAL AND LEGAL DISPOSAL OF EQUIPMENT AND SYSTEMS MADE OBSOLETE AND/OR REPLACED BY NEW WORK. DEMOLITION INCLUDES RELOCATION OR REINSTALLATION, DISCONNECTIONS AND RECONNECTIONS OF SERVICES, SUPPORTS, AND SUBSEQUENT FINAL SUPPORTS, TEMPORARY CAPPING, AND REROUTING OF TEMPORARY SERVICES TO PERMIT NEW OR RENOVATION WORK TO PROCEED.
3. THE DEMOLITION WORK INDICATED ON THE DRAWING IS INTENDED TO ASSIST THE CONTRACTOR AND GIVE GENERAL INFORMATION. NOT ALL DEMOLITION OR TEMPORARY CONNECTIONS ARE SHOWN. PRIOR TO SUBMITTING BID, THE CONTRACTOR SHALL VISIT THE PROJECT SITE AND REVIEW ORIGINAL DRAWINGS IF AVAILABLE. CONTRACTOR IS RESPONSIBLE TO DETERMINE THE FULL EXTENT OF DEMOLITION, AND INCLUDE ALL REQUIRED DEMOLITION WORK IN HIS BID, WHETHER OR NOT SPECIFICALLY SHOWN ON DRAWINGS. NO ADDITIONAL COST WILL BE GRANTED FOR DEMOLITION. LEGALLY DISPOSE OF ALL ITEMS AND MATERIALS, EXCEPT ANY ITEMS SPECIFICALLY DESIGNATED BY THE OWNER TO BE SALVAGED. REMOVE AND REPLACE THE DESIGNATED SALVAGED EQUIPMENT AND STORE IN A
LOCATION DIRECTED BY THE OWNER AT NO ADDITIONAL EXPENSE.
4. REFER TO GENERAL CONSTRUCTION TRADE DEMOLITION DRAWINGS AS WELL AS THE MECHANICAL, PLUMBING & FIRE PROTECTION DRAWINGS FOR DEVICES AND EQUIPMENT THAT HAVE TO BE REMOVED DUE TO THE NEW CONSTRUCTION AND RENOVATIONS AND EXTENT OF AREA TO BE DEMOLISHED. DISCONNECT POWER AND CONTROLS SERVING SUCH DEVICES AND EQUIPMENT WHETHER OR NOT SPECIFICALLY SHOWN ON ELECTRICAL DRAWINGS TO
FACILITATE DEMOLITION AND NEW CONSTRUCTION.
5. ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR CUTTING AND PATCHING CONCRETE FLOOR IN AREAS WHERE NEW FINISH FLOOR IS PROVIDED BY THE GENERAL CONTRACT. IN AREAS WHERE THE FINISH FLOOR IS TO REMAIN, THE ELECTRICAL CONTRACTOR SHALL CUT AND PATCH THE EXISTING CONCRETE FLOOR AND PROVIDE A NEW FINISH FLOOR TO MATCH EXISTING. ELECTRICAL CONTRACTOR SHALL REMOVE/REPLACE EXISTING CEILING TILES AND GRID AS REQUIRED TO ACCOMPLISH INDICATED ELECTRICAL WORK, UNLESS SPECIFICALLY INDICATED OTHERWISE. REFER
TO THE ARCHITECTURAL DRAWINGS FOR FINISH TREATMENT OF SPACES.
6. EXISTING CONDUIT AND WIRING THRU THE ROOF THAT ARE NO LONGER NEEDED SHALL BE REMOVED IN THEIR ENTIRETY UNLESS NOTED OTHERWISE. PATCH RESULTING OPENINGS IN THE DECK AND PROVIDE NEW INSULATION AND ROOFING. THE ELECTRICAL CONTRACTOR SHALL RETAIN THE SERVICES OF A QUALIFIED ROOFING CONTRACTOR IN ACCORDANCE WITH THE ROOF MANUFACTURER'S REQUIREMENTS TO MAINTAIN ORIGINAL WARRANTY. REMOVE ALL
OBSOLETE CONDUIT AND WIRING IN CEILING SPACE.
7. MAINTAIN CONTINUITY OF EXISTING CIRCUITS FOR EQUIPMENT AND DEVICES TO REMAIN. IF A DEVICE OR EQUIPMENT IS REMOVED AND IS PART OF AN EXISTING CIRCUIT TO REMAIN, THE CIRCUIT SHALL BE MODIFIED TO SUSTAIN
OPERATION OF EXISTING DEVICES SOURCE BY ORIGINAL CIRCUIT.
8. CONTRACTOR SHALL ENSURE ALL INSTALLATIONS WITHIN MENTAL HEALTH SPACES MEET THE REQUIREMENTS OF THE
NEW YORK STATE MENTAL HEALTH GUIDELINES, NED, AND VA DESIGN MANUALS.
9. CONTRACTOR SHALL VERIFY ALL BRANCH CIRCUITS ASSOCIATED WITH THIS WORK PRIOR TO DEMOLITION.
WALL PACK LIGHTING FIXTURE. SHADING INDICATES FIXTURE TO BE ON
EMERGENCY OR NIGHT LIGHT CIRCUITING. SLASH INDICATES FIXTURE IS
RECESSED.
SINGLE-POLE DIMMABLE SWITCHSD
P ANIT-LIGATURE SECURITY/DURESS-ALARM BUTTON WALL
MOUNTED 40" (1000 MM) UNLESS OTHERWISE NOTED.A
C CENTRAK REAL TIME LOCATION SYSTEM DATA RECORDER
N E
EMERGENCY NURSE CALL - MOUNTED 40" AFF FOR
SHOWER INSTALLATIONS MOUNT WITHIN 18" OF
SHOWER HEAD AND OR 72" AFF.
TASK LIGHT FIXTURE
EGISTERE
ROF
o. PE045114
FL. FLOOR
FLA FULL LOAD AMPERES
FLUOR. FLUORESCENT
GA. GAGE/GAUGE
GALV. GALVANIZED
G.C. GENERAL CONTRACTOR
GEN. GENERATOR
GEC GROUNDING ELECTRODE CONDUCTOR
GND. GROUND
G.F.A. GROUND FAULT INTERRUPTER
G.R.S.C. GALVANIZED RIGID STEEL CONDUIT
HH HANDHOLE
HT. HEIGHT
H.I.D. HIGH INTENSITY DISCHARGE
HORIZ. HORIZONTAL
H.O.A. HAND OFF AUTO
HP. HORSEPOWER
H.P.S. HIGH PRESSURE SODIUM
HVAC HEATING, VENTILATING, AIR CONDITIONING
HZ. HERTZ
INC. INCANDESCENT
IMC INTERMEDIATE CONDUIT
ISOL. ISOLATED
INSUL. INSULATION/INSULATED
J JUNCTION BOX
KA KILOAMPERE
KAIC THOUSAND AMPERE INTERRUPTING CAPACITY
KCMIL THOUSAND CIRCULAR MILS
KHZ KILOHERTZ
KW KILOWATT
KWH KILOWATT HOUR
KVA KILOVOLT-AMPERE(S)
KVAR KILOVAR
KV KILOVOLT(S)
LA LIGHTNING ARRESTOR
LAN LOCAL AREA NETWORK
LG. LENGTH
LF LINEAR FEET
LT LIGHT
LTG LIGHTING
L/R LOCAL/REMOTE
LRA LOCKED ROTOR AMPERES
L/LG LONG
LT LONG TIME
MAX. MAXIMUM
MB MAIN BREAKER
MCC MOTOR CONTROL CENTER
MCCB MOLDED CASE CIRCUIT BREAKER
M.C. MECHANICAL CONTRACTOR
M/C MULTI-CONDUCTOR
MD MAIN DISCONNECT
MDP MAIN DISTRIBUTION PANEL
MANUF. MANUFACTURER
MECH. MECHANICAL
MF MAINTENANCE FACTOR
MFR MALFUNCTION RELAY
MFR-F MALFUNCTION RELAY FEEDER PROTECTION
MFR-S MALFUNCTION RELAY SOURCE WAY PROTECTION
MFR-T MALFUNCTION RELAY TIE PROTECTION
MG MOTOR GENERATOR
MH MANHOLE
MIN. MINIMUM
M.L.O. MAIN LUGS ONLY
MS MODE SWITCH(MANUAL/AUTO)
MSB MAIN SWITCHBOARD
MTD. MOUNTED
MTS MANUAL TRANSFER SWITCH
MV MEDIUM VOLTAGE
MVA MEGAVOLT-AMPERES
N. NEUTRAL
NA NOT APPLICABLE
NC NORMAL CLOSED
N.E.C. NATIONAL ELECTRICAL CODE
NEMA NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION
NIC NOT IN CONTRACT
NO NORMALLY OPEN
NTS NOT TO SCALE
NO./# NUMBER
OC,O/C ON CENTER
P POLE
PP PART PLAN
PADMT/PM PADMOUNT
PJB PEDESTAL JUNCTION BOX
ɸ,PH PHASE
P.V.C. POLYVINYLCHLORIDE
PB PULL BOX
PNL/PNLBD PANELBOARD
POFB PULL OUT FUSE BLOCK
PROT PROTECTION
P.C. PLUMBING CONTRACTOR
PNL. PRIMARY
PSI POUNDS PER SQUARE INCH
PU PICKUP
PV PHOTOVOLTAIC
PVC POLYVINYL CHLORIDE
R. RADIUS
RF RADIO FREQUENCY
REBAR. REINFORCING BAR
RECEPT. RECEPTACLE
REQ'D REQUIRED
REV. REVISE/REVISION
REC. RECESSED
R..SW. REMOTE CONTROL SWITCH
RGS/RCS RIGID GALVANIZED STEEL CONDUIT
RM ROOM
RMS ROOT MEAN SQUARE
RTU REMOTE TERMINAL UNIT OR ROOF TOP
UNIT
SCHED SCHEDULE
SECT. SECTION
SEC. SECONDARY
SERV. SERVICE
1/C SINGLE CONDUCTOR
SK. SKETCH
SP SPARE
SPECS. SPECIFICATIONS
SQ. SQUARE
S.F. SQUARE FEET
STA. STATION
SW. SWITCH
S.S. STAINLESS STEEL
SW'BD SWITCHBOARD
SWGR SWITCHGEAR
SYM. SYMMETRICAL
SUSP. SUSPENDED
SEP. SEPARATE
SHT. SHEET
SIG. SIGNAL
SN SOLID NEUTRAL
ST SHORT TIME
SURF. SURFACE
SYM SYMMETRICAL
SYS SYSTEM
TBD TO BE DETERMINED
THRU THROUGH
TEL. TELEPHONE
TEMP TEMPORARY
TRANSF./XFMR TRANSFORMER
TYP. TYPICAL
UG UNDERGROUND
U.O.C./UON UNLESS OTHERWISE NOTED
U.R.C. UNDER RAISED FLOOR
UNK UNKNOWN
VS. VERSUS
VERT. VERTICAL
VD VOLTAGE DROP
V. VOLTAGE/VOLTS
VAC VOLTS ALTERNATING CURRENT
VDC VOLTS DIRECT CURRENT
VT VOLTAGE TRANSFORMER
VI VACUUM INTERRUPTER
W WIRE
WP WEATHERPROOF
WD. WIDE
W/ WITH
W/O WITHOUT
W/I WROUGHT IRON
XFMR TRANSFORMER
Y WYE
1/C ONE
CONDUCTOR
AMP./A. AMPERE
AC. ALTERNATING CURRENT
A/C. AIR CONDITION
AF AMP FRAME
A.F.F. ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
A.I.C. AMPERES INTERRUPTING CAPACITY
AL ALUMINUM
ARCH. ARCHITECTURAL
ART ARTICLE
A.R.F. ABOVE RAISED FLOOR
ASY. ASYMMETRICAL
AT AMP TRIP
A.T.C. AUTOMATIC TEMPERATURE CONTROL
ATS AUTOMATIC TRANSFER SWITCH
AUX. AUXILIARY
AWG AMERICAN WIRE GAUGE
BCSD BARE COPPER SOFT DRAWN
B.F.S. BELOW FINISHED CEILING
BIL BASIC INSULATION LEVEL
BLDG. BUILDING
BKR. BREAKER
BSMT. BASEMENT
.C. CENTIGRADE DEGREES
CLG. CEILING
CLR CLEAR
CKT. CIRCUIT
CB CIRCUIT BREAKER
CW CLOCKWISE
COL. COLUMN
CONC. CONCRETE
CCTV CLOSED CIRCUIT TELEVISION
C. CONDUIT
CONDR. CONDUCTOR
CU.FT. CUBIC FEET
CONTR. CONTRACTOR
CU. COPPER
COMM COMMUNICATION
CONST. CONSTRUCTION
COAX. COAXIAL
COORD. COORDINATE
CONFIG CONFIGURATION
CONN CONNECTION, OR CONNECTED, AS APPLICABLE
CONT. CONTINUATION
COR CONTACTING OFFICERS REPRESENTATIVE
CMU CONCRETE MASONRY UNIT
CPT CONTROL POWER TRANSFORMER
C.T. CURRENT TRANSFORMER
CWP CHILLED WATER PIPING
DB DUCT BANK
DC DIRECT CURRENT
DCCB DIRECT CURRENT CIRCUIT BREAKER
DEMO DEMOLITION
DIA DIAMETER
DIM DIMENSION
DISC. DISCONNECT SWITCH
DIV. DIVISION
DN. DOWN
EA. EACH
E.F. EXHAUST FAN
EGC EQUIPMENT GROUNDING CONDUCTOR
ELEC. CL. ELECTRICAL CLOSET
ELEC. ELECTRICAL
E.C. ELECTRICAL CONTRACTOR
ELEV/EL. ELEVATION/ELEVATOR
E.M.A./EMT ELECTRICAL METALLIC TUBING
EMH EXISTING MANHOLE
EST ESTIMATED
ETR EXISTING TO REMAIN
EQ. EQUAL
EQUIP. EQUIPMENT
EV EXPLODED VIEW
E.W. EACH WAY
EXIST EXISTING
EXT. EXTERNAL/EXTERIOR
F.A. FIRE ALARM
FACP FIRE ALARM CONTROL PANEL
.F. FAHRENHEIT DEGREES
FC FOOTCANDLE
FDR FEEDER
FT. FEET
F.E. FIRE EXTINGUISHER
FDN. FOUNDATION
F.O. FIBER OPTIC
FIN. FINISH/FINISHED
FIXT. FIXTURE
FLEX. FLEXIBLE
NOTE: NOT ALL ABBREVIATIONS ARE USED.
E-002
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
CONSTRUCTION
DOCUMENTS
FULLY
SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
PhaseARCHITECT STAMPCONSULTANTS
Revision: Date:
523A4-20-205
VAMC WEST ROXBURY
EXPAND EMERGENCY
DEPARTMENT
William Pevear Architects, Inc.
872 Massachusetts Ave. Suite 2-9 Cambridge, MA 02139
T: 617.335.5186
Alares Engineering
248 Copeland Street, 2nd Floor Quincy, MA 02169
T: 617.481.6390
MEP/FP ENGINEER
Drawing Scale
321 4 5 6 7 8
A
B
C
D
E
321 4 5 6 7 8
255 SPRING ST, WEST ROXBURY, MA 02132
1/31/2024
CODE CONSULTANT
Hastings Consulting
142 Hanlon Road Holliston, MA 01746
T: 508.397.8417
DLE VAC
ELECTRICAL
ABBREVIATIONS
EGISTERE
N E
P A
C
TELE-
PHONE
CLOSET
ELECTRICAL
CLOSET
EXAM 17
GA-146
EXAM 11
GA-187
MH EXAM 8
GA-180
MH FLEX
EXAM 9
GA-181
MH FLEX
EXAM 10
GA-182
EXAM 16
GA-147
EXAM 15
GA-145
PANEL HDPGA 480/277V (ETR) - NORMAL
PANEL HLPGA 480/277V (ETR) - NORMAL
PANEL LPPGA 208/120V (ETR) - NORMAL
PANEL LPPGA1 208/120V (ETR) - NORMAL
PANEL LCGA 208/120V (ETR) - EMERGENCY
PANEL LEGA 208/120V (ETR) - EMERGENCY
PANEL HEGA 480/277V (ETR) - EMERGENCY
PANEL HLSGA 480/277V (ETR) - EMERGENCY
KEYED PANELBOARD NOTES
1.
2.
3.
FOR ALL DEMOLITION HATCHED ROOMS, REMOVE EXISTING PANELBOARDS,
RECEPTACLES, EQUIPMENT POWER SUPPLIES, ASSOCIATED CONDUIT,
JUNCTION BOXES, AND CONDUCTORS TO SOURCE PANEL.
FOR ALL DEMOLITION HATCHED ROOMS AND ASSOCIATED MECHANICAL
EQUIPMENT BEING DEMOLISHED (SEE MECHANICAL PLANS) REMOVE
ASSOCIATED DISCONNECTS, ELECTRICAL POWER, DATA CONNECTIONS,
ASSOCIATED CONDUIT JUNCTION BOXES, AND CONDUCTORS TO SOURCE
PANEL.
FOR ALL DEMOLITION HATCHED ROOMS, REMOVE EXISTING DATA PORT
CONNECTIONS, NURSE CALL, SECURITY, ALARM SYSTEMS, AND ASSOCIATED
CONDUIT, JUNCTION BOXES, AND CONDUCTORS BACK TO SOURCE OR ORIGIN.
GENERAL DEMOLITION NOTES
ED-100
DEMOLITION ELECTRICAL PLAN
1/8"=1'-0"
BUILDING 3 EXISTING CONDITIONS/
N
PROJECT
NORTH
4. FOR ALL REAL TIME LOCATION SYSTEM (RLTS) CENTRAK UNITS, REMOVE UNIT
AND PROTECT FOR REINSTALLATION. PROVIDE THE SERVICES OF
MANUFACTURER, CENTRAK INC., TO SUPERVISE REMOVAL AND
REINSTALLATION.
DLE VAC
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
CONSTRUCTION
DOCUMENTS
FULLY
SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
PhaseARCHITECT STAMPCONSULTANTS
Revision: Date:
523A4-20-205
VAMC WEST ROXBURY
EXPAND EMERGENCY
DEPARTMENT
William Pevear Architects, Inc.
872 Massachusetts Ave. Suite 2-9 Cambridge, MA 02139
T: 617.335.5186
Alares Engineering
248 Copeland Street, 2nd Floor Quincy, MA 02169
T: 617.481.6390
MEP/FP ENGINEER
Drawing Scale
321 4 5 6 7 8
A
B
C
D
E
321 4 5 6 7 8
255 SPRING ST, WEST ROXBURY, MA 02132
1/31/2024
CODE CONSULTANT
Hastings Consulting
142 Hanlon Road Holliston, MA 01746
T: 508.397.8417
BUILDING 3 EXISTING
CONDITIONS/ DEMOLITION
ELECTRICAL PLANEGISTERE
PANEL HDPGA 480/277V (ETR) - NORMAL
PANEL HLPGA 480/277V (ETR) - NORMAL
PANEL LPPGA 208/120V (ETR) - NORMAL
PANEL LPPGA1 208/120V (ETR) - NORMAL
PANEL LCGA 208/120V (ETR) - EMERGENCY
PANEL LEGA 208/120V (ETR) - EMERGENCY
PANEL HEGA 480/277V (ETR) - EMERGENCY
PANEL HLSGA 480/277V (ETR) - EMERGENCY
KEYED PANELBOARD NOTES
PANEL LCGA-1 208/120V - EMERGENCY9
GA-180
TELE-
PHONE
CLOSET
ELECTRICAL
CLOSET
EXAM 17
GA-146
EXAM 11
GA-187
EXAM 12
GA-186
EXAM 13
GA-184
EXAM 6
GA-178
EXAM 7
GA-179
MH FLEX
EXAM 9
GA-181
MH FLEX
EXAM 10
GA-182
EXAM 16
GA-147
EXAM 15
GA-145
MH EXAM 8
GA-180
ED-101
1. FOR ALL DEMOLITION HATCHED ROOMS, REMOVE EXISTING LIGHT FIXTURES,
SWITCHES, ASSOCIATED CONDUIT, JUNCTION BOXES, AND CONDUCTORS TO
SOURCE PANEL.
GENERAL DEMOLITION NOTE
ELECTRICAL REFLECTED CEILING PLAN
1/8"=1'-0"
BUILDING 3 EXISTING CONDITIONS/DEMOLITION
N
PROJECT
NORTH
BUILDING 3 EXISTING CONDITIONS/
DEMOLITION ELECTRICAL
REFLECTED CEILING PLAN
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
CONSTRUCTION
DOCUMENTS
FULLY
SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
PhaseARCHITECT STAMPCONSULTANTS
Revision: Date:
523A4-20-205
VAMC WEST ROXBURY
EXPAND EMERGENCY
DEPARTMENT
William Pevear Architects, Inc.
872 Massachusetts Ave. Suite 2-9 Cambridge, MA 02139
T: 617.335.5186
Alares Engineering
248 Copeland Street, 2nd Floor Quincy, MA 02169
T: 617.481.6390
MEP/FP ENGINEER
Drawing Scale
321 4 5 6 7 8
A
B
C
D
E
321 4 5 6 7 8
255 SPRING ST, WEST ROXBURY, MA 02132
1/31/2024
CODE CONSULTANT
Hastings Consulting
142 Hanlon Road Holliston, MA 01746
T: 508.397.8417
DLE VAC
EGISTERE
ROF
o. PE045114
AutoCAD SHX Text
HLSGA-XX
AutoCAD SHX Text
HLSGA-XX
11 17 18 19 2016
3-AHU-1
RTU-1
1 EXISTING AHU TO REMAIN.
2 REMOVE ALL EXISTING WIRING FROM THE EXISTING ROOF TOP UNIT RTU-1 (TO
BE DEMOLISHED) TO THE ASSOCIATED DISCONNECT. SEE MECHANICAL PLANS
FOR REMOVAL OF RTU. REMOVE ASSOCIATED RTU DISCONNECT, REMOVE ALL
ASSOCIATED CONDUIT JUNCTION BOXES, AND CONDUCTORS TO SOURCE
PANEL.
DEMOLITION KEYED NOTES
ED-102
BUILDING 3 ROOF EXISTING
CONDITIONS/DEMOLITION
ELECTRICAL PLAN
CONDITIONS/DEMOLITION ELECTRICAL PLAN
1/8"=1'-0"
BUILDING 3 ROOF EXISTING
N
PROJECT
NORTH
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
CONSTRUCTION
DOCUMENTS
FULLY
SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
PhaseARCHITECT STAMPCONSULTANTS
Revision: Date:
523A4-20-205
VAMC WEST ROXBURY
EXPAND EMERGENCY
DEPARTMENT
William Pevear Architects, Inc.
872 Massachusetts Ave. Suite 2-9 Cambridge, MA 02139
T: 617.335.5186
Alares Engineering
248 Copeland Street, 2nd Floor Quincy, MA 02169
T: 617.481.6390
MEP/FP ENGINEER
Drawing Scale
321 4 5 6 7 8
A
B
C
D
E
321 4 5 6 7 8
255 SPRING ST, WEST ROXBURY, MA 02132
1/31/2024
CODE CONSULTANT
Hastings Consulting
142 Hanlon Road Holliston, MA 01746
T: 508.397.8417
1. SOURCE PANELBOARD AND ASSOCIATED CIRCUIT SHALL BE VERIFIED BY THE
CONTRACTOR PRIOR TO THE START OF ANY DEMOLITION WORK. THE
CONTRACTOR SHALL BE RESPONSIBLE TO ENSURE THAT NO SYSTEMS THAT
ARE EXISTING TO REMAIN ARE COMPROMISED DURING DEMOLITION. ALL
EXISTING BRANCH CIRCUITING SHALL REMAIN UNLESS OTHERWISE NOTED.
GENERAL NOTE
EGISTERE
ROF
o. PE045114
HEDGC-12
ELECTRICAL
CLOSET
EXAM 17
GA-146
EXAM 11
GA-187
EXAM 12
GA-186
EXAM 13
GA-184
EXAM 6
GA-178
EXAM 7
GA-179
MH EXAM 8
GA-180
MH FLEX
EXAM 9
GA-181
MH FLEX
EXAM 10
GA-182
EXAM 16
GA-147
EXAM 15
GA-145
ALL INSTALLATIONS WITHIN ROOM SHALL BE ANTI LIGATURE
EQUIPMENT.CONTRACTOR SHALL PROVIDE SHOP DRAWINGS
OF ALL EQUIPMENT.
KEYED NOTES
2 REPLACE CARD READER FOR ASSOCIATED DOOR. VERIFY
CARD READER TYPE WITH VA. EXISTING ELECTRICAL TO BE
REUSED. CARD READER ACTIVATION TO BE TIED INTO DOOR
OPERATOR.
PANEL HDPGA 480/277V (ETR) - NORMAL
PANEL HLPGA 480/277V (ETR) - NORMAL
PANEL LPPGA 208/120V (ETR) - NORMAL
PANEL LPPGA1 208/120V (ETR) - NORMAL
PANEL LCGA 208/120V (ETR) - EMERGENCY
PANEL LEGA 208/120V (ETR) - EMERGENCY
PANEL HEGA 480/277V (ETR) - EMERGENCY
PANEL HLSGA 480/277V (ETR) - EMERGENCY
KEYED PANELBOARD NOTES
PANEL LCGA-1 208/120V - EMERGENCY9
E-100
1. ALL DEVICES INSTALLED WITHIN MENTAL HEALTH ROOMS
SHALL BE NEW YORK STATE OFFICE OF MENTAL HEALTH
GUIDELINE APPROVED ANTI-LIGATURE DEVICES AND MEET
ASSOCIATED INSTALLATION REQUIREMENTS.
2. FOR NEWLY INSTALLED RECEPTACLE CIRCUITS: PROVIDE 20A
SINGLE POLE CIRCUIT BREAKER. (2)#12 CONDUCTORS, (1)#12
GROUND, IN 3/4" CONDUIT TO ASSOCIATED PANELBOARD.
3. MENTAL HEALTH ROOMS RECEPTACLES SHALL BE TAMPER
RESISTANT RECEPTACLES WITH DUAL PROTECTION (ARC
FAULT AND GROUND FAULT INTERRUPTION). COVER PLATES
SHALL BE BEVELED, METAL-EDGED AND SHALL HAVE TAMPER
PROOF SCREWS.
4. FOR ALL DEVICES INSTALLED WITHIN METAL HEALTH SPACES
PROVIDE DUAL PROTECTION CIRCUIT BREAKERS WHEN IT IS
NOT FEASIBLE TO PROVIDE DUAL PROTECTION AT THE
RECEPTACLE LOCATION.
GENERAL NOTES
NEW WORK ELECTRICAL PLAN
1/8"=1'-0"
BUILDING 3 GROUND FLOOR
N
PROJECT
NORTH
BUILDING 3 GROUND FLOOR
NEW WORK ELECTRICAL PLAN
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
CONSTRUCTION
DOCUMENTS
FULLY
SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
PhaseARCHITECT STAMPCONSULTANTS
Revision: Date:
523A4-20-205
VAMC WEST ROXBURY
EXPAND EMERGENCY
DEPARTMENT
William Pevear Architects, Inc.
872 Massachusetts Ave. Suite 2-9 Cambridge, MA 02139
T: 617.335.5186
Alares Engineering
248 Copeland Street, 2nd Floor Quincy, MA 02169
T: 617.481.6390
MEP/FP ENGINEER
Drawing Scale
321 4 5 6 7 8
A
B
C
D
E
321 4 5 6 7 8
255 SPRING ST, WEST ROXBURY, MA 02132
1/31/2024
CODE CONSULTANT
Hastings Consulting
142 Hanlon Road Holliston, MA 01746
T: 508.397.8417
EGISTERE
ROF
o. PE045114
AutoCAD SHX Text A
AutoCAD SHX Text A
AutoCAD SHX Text S
AutoCAD SHX Text A
AutoCAD SHX Text
LPPGA-#
AutoCAD SHX Text
LCGA1-24
AutoCAD SHX Text A
AutoCAD SHX Text A
AutoCAD SHX Text
LCGA1-22
AutoCAD SHX Text S
S
MECHANICAL
ROOM
GC-104
EMERGENCY
GENERATOR
ROOM
GC-100
PANEL HEDGC 480/277V (ETR)
PROVIDE 225A 480/227V PANELBOARD
"HEDEQ" (SEE PARTIAL ONE-LINE
DIAGRAM)
3 ATS #4 (ETR)
KEYED ELECTRICAL NOTES
(4) #4/0 AWG (1)
#4 AWG GND
2 1/2"
CONDUIT
BLDG 3
RM GC-100
HEDGC
EMERGENCY
480/277V
600A MCB
CONTINUES
TO
ATS #4
250AF/
225AT
(EXISTING
SPARE)
MCB
600A
BLDG 3
RM GC-100
HEDEQ
EMERGENCY
480/277V
225A MCB
AHU-1A
20A
MCB
225A
AHU-1A
SUPPLY FAN
AHU-1A
20A
AHU-1A
EXHAUST FAN
M M
30AF/
20AT
30AF/
15AT
(4) #10 AWG
(1) #10 AWG GND
1" C.
(4) #10 AWG
(1) #10 AWG GND
1" C.
AS INDICATED
E-101
ELECTRICAL NEW WORK PLAN
1/8"=1'-0"
BUILDING 3 ROOMS GC-100 & GC-104
PARTIAL NEW WORK ONE-LINE DIAGRAM
N.T.S.2
BLDG 3 ONE-LINE DIAGRAM
& ROOM GC-100 ELECTRICAL
NEW WORK PLAN
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
CONSTRUCTION
DOCUMENTS
FULLY
SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
PhaseARCHITECT STAMPCONSULTANTS
Revision: Date:
523A4-20-205
VAMC WEST ROXBURY
EXPAND EMERGENCY
DEPARTMENT
William Pevear Architects, Inc.
872 Massachusetts Ave. Suite 2-9 Cambridge, MA 02139
T: 617.335.5186
Alares Engineering
248 Copeland Street, 2nd Floor Quincy, MA 02169
T: 617.481.6390
MEP/FP ENGINEER
Drawing Scale
321 4 5 6 7 8
A
B
C
D
E
321 4 5 6 7 8
255 SPRING ST, WEST ROXBURY, MA 02132
1/31/2024
CODE CONSULTANT
Hastings Consulting
142 Hanlon Road Holliston, MA 01746
T: 508.397.8417
1. ALL DEVICES INSTALLED WITHIN MENTAL HEALTH ROOMS
SHALL BE NEW YORK STATE OFFICE OF MENTAL HEALTH
GUIDELINE APPROVED ANTI-LIGATURE DEVICES.
FOR NEWLY INSTALLED RECEPTACLE CIRCUITS: PROVIDE 20A
SINGLE POLE CIRCUIT BREAKER. (2)#12 CONDUCTORS, (1)#12
GROUND, IN 3/4" CONDUIT TO ASSOCIATED PANELBOARD.
GENERAL NOTES