ATT H 1615269dwg6of19.pdf

PDF 5 MB Posted

Attached to
P131 Communications Center - Souda Bay
Solicitation number
N62470-21-R-0005
Issued by

About this file

This solicitation is for the design and construction of a communications center at Naval Support Activity Souda Bay in Greece. The project involves constructing a three-story concrete facility with concrete shear walls and shallow foundations to house communications, telephone exchange, electronics maintenance, and storage functions. Exterior facades will be reinforced concrete coated with elastomeric finish. Electrical utilities will include primary and secondary distribution, transformers, telecommunications infrastructure, security systems, and lighting. The performance period is approximately 900 days from notice to proceed. The contract type will be firm fixed price. The Navy's Naval Facilities Engineering Command will award the contract on an unrestricted full and open competitive basis.

View the file

Other files

File Type Posted
N62470-21-R-0005 Amendment 06.pdf PDF
Attachment S - Section 08 60 45.pdf PDF
Attachment T - NAVFAC DWG 14089360 and 14089364.pdf PDF
N62470-21-R-0005 Amendment 05.pdf PDF
Attachment P - Section 07 22 00 ROOF AND DECK INSULATION.pdf PDF
Attachment Q - Section 26 20 00 INTERIOR DISTRIBUTION SYSTEM.pdf PDF
Attachment R - NAVFAC Dwg. Nos. 14089343 and 14089345.pdf PDF
N62470-21-R-0005 Amendment 04.pdf PDF
Attachment E Schedule B Price Proposal Form_revised_Amendment 04.pdf PDF
N62470-21-R-0005 Amendment 03.pdf PDF
Attachment O - Section 13 48 73 SEISMIC CONTROL FOR NON-STRUCTURAL.pdf PDF
Attachment N - Section 01 45 35 SPECIAL INSPECTIONS.pdf PDF
Attachment E Schedule B Price Proposal Form_revised.pdf PDF
Attachment M Pre-Proposal Conference Attendee Log.pdf PDF
Attachment L Pre-Proposal Conference Presentation.pdf PDF
N62470-21-R-0005 Amendment 02.pdf PDF
Attachment K - Pre-Proposal Conference Request Access Form.pdf PDF
N62470-21-R-0005 Amendment 01.pdf PDF
N6247021R0005 Solicitation.pdf PDF
Attachment E Schedule B Price Proposal Form.pdf PDF
ATT H 1615269dwg12of19.pdf PDF
ATT H 1615269dwg9of19.pdf PDF
Attachment C - Construction Experience Project Data Sheet.pdf PDF
ATT H 1615269dwg3of19.pdf PDF
ATT H 1615269dwg15of19.pdf PDF
ATT H 1615269dwg7of19.pdf PDF
ATT H 1615269dwg8of19.pdf PDF
ATT G 1615269spc2of4.pdf PDF
ATT H 1615269dwg4of19.pdf PDF
ATT H 1615269dwg2of19.pdf PDF
Attachment F - LRA Commercial Vehicle Inspection Procedures.pdf PDF
ATT H 1615269dwg13of19.pdf PDF
ATT H 1615269dwg14of19.pdf PDF
ATT H 1615269dwg10of19.pdf PDF
Attachment A - Pre-Proposal Inquiry Form.xls XLS spreadsheet
ATT H 1615269dwg16of19.pdf PDF
ATT H 1615269dwg11of19.pdf PDF
ATT H 1615269dwg18of19.pdf PDF
ATT H 1615269dwg1of19.pdf PDF
Attachment I Geotechnical Report.pdf PDF
ATT H 1615269dwg17of19.pdf PDF
Attachment D - Past Performance Questionnaire.pdf PDF
ATT H 1615269dwg5of19.pdf PDF
ATT G 1615269spc4of4.pdf PDF
Attachment J Hazardous Material Report.pdf PDF
ATT G 1615269spc3of4.pdf PDF
ATT H 1615269dwg19of19.pdf PDF
Attachment B - SEC-NAV_5512_1_11787 Form.pdf PDF
ATT G 1615269spc1of4.pdf PDF
Show all 49

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

D

C

B

1 2 3 4 5

NONE

1615269

DWG

SHEET OF

NAVFAC DRAWING NO.

CONSTR. CONTR. NO.

EPROJECT NO.

SCALE:

N62470-21-C-0005

DESIGN DIRECTOR

BRANCH MANAGER

PM/DM

DES DRW CHK

SATISFACTORY TO DATE

ACTIVITY

FOR COMMANDER NAVFAC

APPROVED

A/E INFO

SEAL

SY

M

DE

SC

RI

PT

IO

N

DA

TE

AP

PR

N

AV

S U

PP

AC

T

SO

U D

A B

AY

N

AV

A L

FA

C

IL

IT

IE

S

EN

G

IN

E

ER

IN

G S

YS

TE

M C

O M

M

AN

D D

E P

AR

TM

E N

T O

F

TH

E N

A

VY

N

AV

AL

F

AC

IL

IT

IE

S E

N G

IN

EE

R

IN

G S

YS

TE

M C

O M

M

AN

D

A

FIRE PROTECTION

N O

R

FO

LK

, V

A A

TL

AN

TI

C

D E

SI

G

N A

N D

C O

N

ST

R U

C

TI

O N

1100 NORTH GLEBE ROAD

SUITE 500

ARLINGTON, VIRGINIA 22201

571.218.1000

FAX: 571.218.1600

D

C

B

A

1 2 3 4 5

RICHARD STEPHENS

TRUEWORTHY,PE / STELMASZEK,RA

PL

O

T

DA

TE

/T

IM

E:

7/

/ 2

3:

:3

PM

C

R ev it_ Lo ca l_

M od el s\

\P

1- D

1-

S_ R

_j oe

.th om as 1.

rv t

14 JUL 2021

RECEIVED BY JACOBIE TISDALE

AND STEVE PARK VIA EMAIL

S-001

LAP JRP GPJ

P

C

O M

M U

N

IC

A

TI

O N

C E

N

TE

RS

O

U D

A B

AY

, G

R

EE

C E

G

EN

ER

A

L

ST

R U

C

TU

R

AL

N O

TE

S

14089102

ΓΕ

Ν

ΙΚ

ΕΣ

ΚΑ

ΤΑ

ΣΚ

ΕΥ

Α

ΣΤ

ΙΚ

ΕΣ

Π

ΑΡ

Α

ΤΗ

Ρ Η

ΣΕ

ΙΣ

JTW

DPS

1.0 DESIGN CRITERIA

1.1 DESIGN CODES AND STANDARDS

ΚΩΔΙΚΕΣ ΣΧΕΔΙΑΣΜΟΥ

EUROCODES:

ΕΥΡΩΚΩΔΙΚΕΣ:

EUROCODE 0 - EN 1990, BASIS OF STRUCTURAL DESIGN

ΒΑΣΕΙΣ ΣΧΕΔΙΑΣΜΟΥ ΔΟΜΗΜΑΤΩΝ

EUROCODE 1 - EN 1991, BASIS OF DESIGN AND ACTIONS ON STRUCTURES

ΔΡΑΣΕΙΣ ΣΕ ΔΟΜΗΜΑΤΑ

EUROCODE 2 - EN 1992, DESIGN OF CONCRETE STRUCTURES

ΣΧΕΔΙΑΣΜΟΣ ΚΑΤΑΣΚΕΥΩΝ ΑΠΟ ΣΚΥΡΟΔΕΜΑ

EUROCODE 3 - EN 1993, DESIGN OF STEEL STRUCTURES

ΣΧΕΔΙΑΣΜΟΣ ΚΑΤΑΣΚΕΥΩΝ ΑΠΟ ΧΑΛΥΒΑ

EUROCODE 4 - EN 1994, DESIGN OF COMPOSITE STEEL AND CONCRETE STRUCTURES

ΣΧΕΔΙΑΣΜΟΣ ΣΥΜΜΙΚΤΩΝ ΚΑΤΑΣΚΕΥΩΝ ΑΠΟ ΧΑΛΥΒΑ ΚΑΙ

ΣΚΥΡΟΔΕΜΑ

EUROCODE 8 - EN 1998, DESIGN OF STRUCTURES FOR EARTHQUAKE

RESISTANCE

ΑΝΤΙΣΕΙΣΜΙΚΟΣ ΣΧΕΔΙΑΣΜΟΣ ΤΩΝ ΚΑΤΑΣΚΕΥΩΝ

GREEK NATIONAL ANNEX FOR EUROCODE

ΕΛΛΗΝΙΚΟ ΠΡΟΣΑΡΤΗΜΑ ΕΥΡΩΚΩΔΙΚΑ

GREEK CODE OF CONCRETE TECHNOLOGY

ΕΛΛΗΝΙΚΟΣ ΚΑΝΟΝΙΣΜΟΣ ΤΕΧΝΟΛΟΓΙΑΣ ΣΚΥΡΟΔΕΜΑΤΟΣ

(GOVERNMENT GAZZETE 1561B/2-6-2016)

(ΦΕΚ/1561/Β/2.6.2016)

US CODES:

ΚΩΔΙΚΕΣ ΗΠΑ:

2018 INTERNATIONAL BUILDING CODE

2018 ΔΙΕΘΝΗΣ ΚΤΙΡΙΑΚΟΣ ΚΑΝΟΝΙΣΜΟΣ

ASCE 7-16, MINIMUM DESIGN LOADS FOR BUILDINGS AND OTHER STUCTURES

ASCE 7-16, ΕΛΑΧΙΣΤΕΣ ΦΟΡΤΙΣΕΙΣ ΓΙΑ ΚΤΙΡΙΑ ΚΑΙ ΕΤΕΡΕΣ ΚΑΤΑΣΚΕΥΕΣ

UFC 1-200-01; GENERAL BUILDING REQUIREMENTS, 08 OCT 2019

ΓΕΝΙΚΕΣ ΚΤΙΡΙΑΚΕΣ ΑΠΑΙΤΗΣΕΙΣ, 08 ΟΚΤΩΒΡΙΟΥ 2019

UFC 3-301-01; STRUCTURAL ENGINEERING, 01 OCT 2019

ΔΟΜΟΣΤΑΤΙΚΗ ΜΗΧΑΝΙΚΗ, 01 ΟΚΤΩΒΡΙΟΥ 2019

UFC 4-010-01; DoD MINIMUM ANTITERRORISM STANDARDS FOR BUILDINGS, CHANGE 1, 19 AUGUST 2020

ΚΑΝΟΝΙΣΜΟΣ ΕΛΑΧΙΣΤΩΝ ΑΠΑΙΤΟΥΜΕΝΩΝ ΑΝΤΙΤΡΟΜΟΚΡΑΤΙΚΩΝ

ΑΠΑΙΤΗΣΕΩΝ ΓΙΑ ΚΤΙΡΙΑ, ΑΛΛΑΓΗ 1, 19 ΑΥΓΟΥΣΤΟΥ 2020.

UFC 4-023-03; DESIGN OF BUILDINGS TO RESIST PROGRESSIVE COLLAPSE,

CHANGE 3, 01 NOVEMBER 2016

ΚΑΝΟΝΙΣΜΟΣ ΓΙΑ ΚΤΙΡΙΑ ΠΡΟΚΕΙΜΕΝΟΥ ΝΑ ΑΝΤΙΣΤΑΘΟΥΝ ΣΤΗΝ ΣΤΑΔΙΑΚΗ

ΚΑΤΑΡΡΕΥΣΗ, ΑΛΛΑΓΗ 3, 01 ΝΟΕΜΒΡΙΟΥ 2016.

1.2. FOR GENERATOR BUILDING DESIGN CRITERIA, SEE S-405

ΓΙΑ ΤΑ ΚΡΙΤΗΡΙΑ ΣΧΕΔΙΑΣΜΟΥ ΤΟΥ ΚΤΙΡΙΟΥ ΓΕΝΝΗΤΡΙΑΣ, ΒΛΕΠΕ ΣΧΕΔΙΟ S-405

FOR SOLAR CARPORT DESIGN CRITERIA, SEE S-408

ΓΙΑ ΤΑ ΚΡΙΤΗΡΙΑ ΣΧΕΔΙΑΣΜΟΥ ΣΤΕΓΑΣΤΡΟΥ ΜΕ ΦΩΤΟΒΟΛΤΑΙΚΑ ΤΟΥ ΧΩΡΟΥ

ΣΤΑΘΜΕΥΣΗΣ ΟΧΗΜΑΤΩΝ, ΒΛΕΠΕ ΣΧΕΔΙΟ S-408

1.3. SUPERIMPOSED DEAD LOADS:

ΕΠΙΠΡΟΣΘΕΤΑ ΜΟΝΙΜΑ (ΝΕΚΡΑ) ΦΟΡΤΙΑ:

STRUCTURE -------------------------------------- USE ACTUAL WEIGHTS

ΚΑΤΑΣΚΕΥΗ -------------------------------------- ΝΑ ΧΡΗΣΙΜΟΠΟΙΗΘΟΥΝ ΤΑ ΠΡΑΓΜΑΤΙΚΑ ΒΑΡΗ RAISED ACCESS FLOORING --------------- 0.6 kPa (APPLIED TO ALL FLOORS) ΥΠΕΡΥΨΩΜΕΝΟ ΔΑΠΕΔΟ ΠΡΟΣΒΑΣΗΣ------0.6KPa (ΕΦΑΡΜΟΖΕΤΑΙ ΣΕ ΟΛΑ ΤΑ ΔΑΠΕΔΑ) 150mm SLAB ON DECK ----------------------- 3.1 kPa (2ND FLOOR ROOMS NOT RECEIVING RAF) 150 mm ΠΛΑΚΑ ΕΞΩΣΤΗ --------- 3.1 KPa (ΤΑ ΔΑΠΕΔΑ ΤΩΝ ΔΩΜΑΤΙΩΝ ΤΟΥ 2ου ΟΡΟΦΟΥ ΔΕΝ

ΠΡΟΣΛΑΜΒΑΝΟΥΝ ΦΟΡΤΙΟ ΥΠΕΡΥΨΩΜΕΝΟΥ ΔΑΠΕΔΟΥ)

ROOFING & INSULATION --------------------- 0.6 kPa ΠΛΑΚΑ ΔΩΜΑΤΟΣ ΚΑΙ ΜΟΝΩΣΕΙΣ --------------------- 0.6ΚPa

ELEVATOR EQUIPMENT ---------------------- SEE S-404

ΕΞΩΠΛΙΣΜΟΣ ΑΝΕΛΚΥΣΤΗΡΑ ---------- ΒΛΕΠΕ S-404

1.4. COLLATERAL LOAD:

ΣΥΜΠΛΗΡΩΜΑΤΙΚΑ ΣΤΑΘΕΡΑ ΦΟΡΤΙΑ

ROOF - (CEILING, MEP, PV PANELS) ---------------------------------------------- 1.7 kPa

ΟΡΟΦΗ (ΕΣΩΤΕΡΙΚΟ ΤΑΒΑΝΙ, ΗΛΕΚΤΡΟΜΗΧΑΝΟΛΟΓΙΚΑ ΚΑΙ

ΥΔΡΑΥΛΙΚΑ, ΦΩΤΟΒΟΛΤΑΪΚΑ ΠΑΝΕΛ)

FLOOR - (FLOORING, CEILING, INSULATION, MEP) ------------------------- 0.7 kPa

ΕΝΔΙΑΜΕΣΟ ΠΑΤΩΜΑ (ΔΑΠΕΔΟ, ΕΣΩΤΕΡΙΚΟ ΤΑΒΑΝΙ, ΜΟΝΩΣΗ,

ΗΛΕΚΤΡΟΜΗΧΑΝΟΛΟΓΙΚΑ ΚΑΙ ΥΔΡΑΥΛΙΚΑ)

1.5. LIVE LOAD:

ΚΙΝΗΤΑ ΦΟΡΤΙΑ

ROOF:

ΣΤΕΓΗ

TYPICAL ROOF: ------------------------------------------------------------------------- 4.8 kPa

ΤΥΠΙΚΗ ΟΡΟΦΗ

PENTHOUSE/DOGHOUSE/CANOPY ROOFS: --------------------------------- 1.0 kPa

ΑΠΟΛΗΞΕΙΣ/ΜΙΚΡΟ ΚΑΤΑΛΥΜΑ/ΕΞΩΤΕΡΙΚΑ ΣΤΕΓΑΣΤΡΑ

FIRST AND SECOND FLOOR: ------------------------------------------------------ 12.0 kPa

ΠΡΩΤΟΣ ΚΑΙ ΔΕΥΤΕΡΟΣ ΟΡΟΦΟΣ

STAIR ---------------------------------------------------------------------------------------- 4.8 kPa

ΚΛΙΜΑΚΟΣΤΑΣΙΟ

PLATFORM: ------------------------------------------------------------------------------- 4.8 kPa

ΕΞΕΔΡΑ

ELEVATOR MACHINE ROOM: ------------------------------------------------------ 6.0 kPa

ΜΗΧΑΝΟΣΤΑΣΙΟ ΑΝΕΛΚΥΣΤΗΡΑ

GROUND FLOOR (SLAB ON GRADE): ------------------------------------------- 12.0 kPa

ΙΣΟΓΕΙΟ (ΠΛΑΚΑ ΕΠΙ ΕΔΑΦΟΥΣ)

1.6. RISK CATEGORY ------------------------------------------------------------------------ IV

ΚΑΤΗΓΟΡΙΑ ΕΠΙΚΙΝΔΥΝΟΤΗΤΑΣ

1.7. SNOW LOAD: (ASCE 7, USING GREEK ANNEX GROUND SNOW LOAD)

ΦΟΡΤΙΟ ΧΙΟΝΙΟΥ: (ASCE 7, ΧΡΗΣΙΜΟΠΟΙΩΝΤΑΣ ΤΟ ΦΟΡΤΙΟ ΠΟΥ ΑΝΑΓΡΑΦΕΤΑΙ ΣΤΟ

ΕΛΛΗΝΙΚΟ ΠΡΟΣΑΡΤΗΜΑ)

GROUND SNOW LOAD, Pg ----------------------------------------------------------- 0.40 kPa

ΦΟΡΤΙΟ ΧΙΟΝΙΟΥ ΕΠΙ ΕΔΑΦΟΥΣ

IMPORTANCE FACTOR, I ------------------------------------------------------------- 1.20

ΣΥΝΤΕΛΕΣΤΗΣ ΣΠΟΥΔΑΙΟΤΗΤΑΣ

EXPOSURE FACTOR, Ce -------------------------------------------------------------- 1.0

ΣΥΝΤΕΛΕΣΤΗΣ ΕΚΘΕΣΗΣ

THERMAL FACTOR, Ct ----------------------------------------------------------------- 1.0

ΣΥΝΤΕΛΕΣΤΗΣ ΘΕΡΜΟΚΡΑΣΙΑΣ

FLAT-ROOF SNOW LOAD, Pf -------------------------------------------------------- 0.46 kPa

ΦΟΡΤΙΟ ΧΙΟΝΙΟΥ ΣΕ ΕΠΙΠΕΔΗ ΣΤΕΓΗ

SNOW DRIFT PER ASCE-7

ΦΟΡΤΙΟ ΧΙΟΝΟΣΤΙΒΑΔΑΣ ΣΥΜΦΩΝΑ ΜΕ ΤΟΝ ASCE-7

ΚΡΙΤΗΡΙΑ ΣΧΕΔΙΑΣΜΟΥ

1.0 DESIGN CRITERIA (CONT)

ΚΡΙΤΗΡΙΑ ΣΧΕΔΙΑΣΜΟΥ (ΣΥΝΕΧΕΙΑ)

1.8. WIND LOAD - ASCE 7:

ΦΟΡΤΙΟ ΑΝΕΜΟΥ- ASCE-7:

BASIC WIND SPEED (3-SECOND GUST) ---------------------------------------- 206 km/hr

ΒΑΣΙΚΗ ΤΑΧΥΤΗΤΑ ΑΝΕΜΟΥ (3- ΔΕΥΤΕΡΟΛΕΠΤΑ ΡΙΠΗ ΑΝΕΜΟΥ)

WIND DIRECTION FACTOR, Kd ----------------------------------------------------- 0.85

ΣΥΝΤΕΛΕΣΤΗΣ ΔΙΕΥΘΥΝΣΗΣ ΑΝΕΜΟΥ

EXPOSURE CATEGORY, C ----------------------------------------------------------- C

ΚΑΤΗΓΟΡΙΑ ΕΚΘΕΣΗΣ

INTERNAL PRESSURE COEFFICIENT, GCpl ----------------------------------- +/- 0.18

ΣΥΝΤΕΛΕΣΤΗΣ ΕΣΩΤΕΡΙΚΗΣ ΠΙΕΣΗΣ

ENCLOSURE CLASSIFICATION ----------------------------------------------------- ENCLOSED

KATHΓΟΡΙΟΠΟΙΗΣΗ ΒΑΣΗ ΑΝΟΙΓΜΑΤΩΝ ΚΤΙΡΙΟΥ

COMPONENTS AND CLADDING WIND PRESSURES:

ΦΟΡΤΙΑ ΑΝΕΜΟΥ ΣΤΗΝ ΕΠΕΝΔΥΣΗ ΚΑΙ ΣΕ ΕΞΑΡΤΗΜΑΤΑ

ROOF AND PARAPET PRESSURES (kPa) BASED ON TRIBUTARY AREA

1.0 m2

ΠΙΕΣΕΙΣ ΟΡΟΦΗΣ ΚΑΙ ΣΤΗΘΑΙΟΥ ΑΝΑΛΟΓΑ ΜΕ ΤΗΝ ΣΥΜΒΑΛΛΟΜΕΝΗ ΠΕΡΙΟΧΗ

ZONE 1

ΖΩΝΗ 1

+0.89 -3.51

ZONE 2 AND 3

ΖΩΝΕΣ 2 ΚΑΙ 3

NOTE: POSITIVE PRESSURES ACT TOWARD THE BUILDING.

NEGATIVE PRESSURES ACT AWAY FROM THE BUILDING

ΠΑΡΑΤΗΡΗΣΗ: ΟΙ ΘΕΤΙΚΕΣ ΠΙΕΣΕΙΣ ΔΡΟΥΝ ΜΕ ΚΑΤΕΥΘΥΝΣΗ

ΠΡΟΣ ΤΟ ΚΤΙΡΙΟ ΕΝΩ ΟΙ ΑΡΝΗΤΙΚΕΣ ΜΕ ΚΑΤΕΥΘΥΝΣΗ

ΑΝΤΙΘΕΤΑ ΑΠΟ ΤΟ ΚΤΙΡΙΟ.

ROOF AND WALL ZONES

ΖΩΝΕΣ ΟΡΟΦΗΣ ΚΑΙ ΤΟΙΧΩΝ

1.0 DESIGN CRITERIA (CONT)

ΚΡΙΤΗΡΙΑ ΣΧΕΔΙΑΣΜΟΥ (ΣΥΝΕΧΕΙΑ)

1.10.SEISMIC LOAD - ASCE 7

ΣΕΙΣΜΙΚΗ ΦΟΡΤΙΣΗ – ASCE 7

0.2 SECOND SPECIAL ACCELERATION, Ss ------- 1.26

ΦΑΣΜΑΤΙΚΗ ΕΠΙΤΑΧΥΝΣΗ ΠΕΡΙΟΔΟΥ 0.2 ΔΕΥΤΕΡΟΛΕΠΤΩΝ, Ss

1 SECOND SPECTRAL ACCELERATION, S1 ------ 0.42

ΦΑΣΜΑΤΙΚΗ ΕΠΙΤΑΧΥΝΣΗ ΠΕΡΙΟΔΟΥ 1 ΔΕΥΤΕΡΟΛΕΠΤΟΥ, S1

IMPORTANCE FACTOR, le -------------------------------- 1.5 ΣΥΝΤΕΛΕΣΤΗΣ ΣΠΟΥΔΑΙΟΤΗΤΑΣ ΧΡΗΣΗΣ, Ιe

LONG-PERIOD TRANSITION PERIOD ---------------- 12

ΠΕΡΙΟΔΟΣ ΕΠΑΝΑΦΟΡΑΣ

SITE CLASS ---------------------------------------------------- C

ΚΛΑΣΗ ΠΕΔΙΟΥ

SITE COEFFICIENT, Fa ------------------------------------ 1.2 ΣΥΝΤΕΛΕΣΤΗΣ ΠΕΔΙΟΥ, Fa SITE COEFFICIENT, Fv ------------------------------------ 1.5 ΣΥΝΤΕΛΕΣΤΗΣ ΠΕΔΙΟΥ, Fv

SDS --------------------------------------------------------------- 1.008

ΠΑΡΑΜΕΤΡΟΣ ΣΧΕΔΙΑΣΜΟΥ ΦΑΣΜΑΤΙΚΗΣ ΑΠΟΚΡΙΣΗΣ ΕΠΙΤΑΧΥΝΣΗΣ ΣΕ

ΜΙΚΡΕΣ ΠΕΡΙΟΔΟΥΣ.

SD1 ---------------------------------------------------------------- 0.42

ΠΑΡΑΜΕΤΡΟΣ ΣΧΕΔΙΑΣΜΟΥ ΦΑΣΜΑΤΙΚΗΣ ΑΠΟΚΡΙΣΗΣ ΕΠΙΤΑΧΥΝΣΗΣ

ΣΕ ΠΕΡΙΟΔΟ 1 ΔΕΥΤΕΡΟΛΕΠΤΟΥ.

RESPONSE MODIFICATION FACTOR, R ------------- 5

ΔΙΟΡΘΩΤΙΚΟΣ ΣΥΝΤΕΛΕΣΤΗΣ ΑΠΟΚΡΙΣΗΣ, R

SEISMIC DESIGN CATEGORY --------------------------- D

ΚΑΤΗΓΟΡΙΑ ΣΕΙΣΜΙΚΟΥ ΣΧΕΔΙΑΣΜΟΥ

LATERAL FORCE RESISTING SYSTEM -------------- BEARING SYSTEM:

SPECIAL REINFORCED

CONCRETE SHEAR WALLS

ΣΥΣΤΗΜΑ ΑΠΟΚΡΙΣΗΣ ΣΕ ΠΛΕΥΡΙΚΑ ΦΟΡΤΙΑ ΦΕΡΩΝ ΟΡΓΑΝΙΣΜΟΣ:

ΕΙΔΙΚΑ ΟΠΛΙΣΜΕΝΑ

ΔΙΑΤΜΗΤΙΚΑ

ΤΟΙΧΕΙΑ ΑΠΟ ΣΚΥΡΟΔΕΜΑ

1.11.SESMIC LOAD - EUROCODE 8 WITH GREEK ANNEX

ΣΕΙΣΜΙΚΗ ΦΟΡΤΙΣΗ – ΕΥΡΩΚΩΔΙΚΑΣ 8 ΜΕ ΕΛΛΗΝΙΚΟ ΠΡΟΣΑΡΤΗΜΑ

SEISMIC RISK ZONE ----------------------------------------------------- II

ΣΕΙΣΜΙΚΗ ΖΩΝΗ ΕΠΙΚΙΝΔΥΝΟΤΗΤΑΣ

SEISMIC GROUND ACCELERATION, agr ------------------------- 0.24

ΣΕΙΣΜΙΚΗ ΕΠΙΤΑΧΥΝΣΗ ΕΔΑΦΟΥΣ

BUILDING IMPORTANCE FACTOR ---------------------------------- 1.4

ΣΥΝΤΕΛΕΣΤΗΣ ΚΑΤΗΓΟΡΙΑΣ ΣΠΟΥΔΑΙΟΤΗΤΑΣ

ELASTIC RESPONSE SPECTRUM ----------------------------------- TYPE I

(MODERATE TO LARGE MAGNITUDE)

ΕΛΑΣΤΙΚΟ ΦΑΣΜΑ ΑΠΟΚΡΙΣΗΣ

(ΜΕΣΑΙΟ ΠΡΟΣ ΜΕΓΑΛΟ ΜΕΓΕΘΟΣ)

GROUND TYPE -------------------------------------------------------------- B

ΤΥΠΟΣ ΕΔΑΦΟΥΣ

SOIL FACTOR, S ------------------------------------------------------------ 1.2

ΣΥΝΤΕΛΕΣΤΗΣ ΕΔΑΦΟΥΣ

SPECTRUM PERIOD, Tb -------------------------------------------------- 0.15 sec ΠΕΡΙΟΔΟΣ ΦΑΣΜΑΤΟΣ Τb SPECTRUM PERIOD, Tc -------------------------------------------------- 0.5 sec ΠΕΡΙΟΔΟΣ ΦΑΣΜΑΤΟΣ Tc SPECTRUM PERIOD, Td -------------------------------------------------- 2.5 sec ΠΕΡΙΟΔΟΣ ΦΑΣΜΑΤΟΣ Td

DUCTILITY CLASS ---------------------------------------------------------- HIGH

ΚΑΤΗΓΟΡΙΑ ΠΛΑΣΤΙΜΟΤΗΤΑΣ ΥΨΗΛΗ

LATERAL FORCE RESISTING SYSTEM --------------------------- REINF CONC

SHEAR WALLS

ΣΥΣΤΗΜΑ ΑΝΤΙΣΤΑΣΗΣ ΣΕ ΠΛΕΥΡΙΚΑ ΦΟΡΤΙΑ -----ΔΙΑΤΜΗΤΙΚΑ ΤΟΙΧΕΙΑ

ΟΠΛΙΣΜΕΝΟΥ ΣΚΥΡΟΔΕΜΑΤΟΣ

BEHAVIOR FACTOR -------------------------------------------------------- 2

ΣΥΝΤΕΛΕΣΤΗΣ ΣΥΜΠΕΡΙΦΟΡΑΣ -------------------------------------- 2

1.12.SOIL DESIGN PARAMETERS:

ΠΑΡΑΜΕΤΡΟΙ ΣΧΕΔΙΑΣΜΟΥ ΕΔΑΦΟΥΣ

ALLOWABLE SOIL BEARING PRESSURE ------------------------------ 200 kPa

ΕΠΙΤΡΕΠΟΜΕΝΗ ΤΑΣΗ ΕΔΑΦΟΥΣ

RETAINING WALLS (STONE BACKFILL):

ΤΟΙΧΕΙΑ ΑΝΤΙΣΤΗΡΙΞΗΣ (ΣΥΜΠΛΗΡΩΣΗ ΜΕ ΛΙΘΟΥΣ)

ACTIVE SOIL PRESSURE (UNRESTRAINED WALLS) --------------- 5.30 kN/m3

ΕΝΕΡΓΗΤΙΚΕΣ ΩΘΗΣΕΙΣ ΓΑΙΩΝ (ΤΟΙΧΕΙΑ ΜΕ

ΕΛΕΥΘΕΡΗ ΜΕΤΑΚΙΝΗΣΗ)

AT-REST SOIL PRESSURE (RESTRAINED WALLS) ----------------- 8.20 kN/m3

ΩΘΗΣΕΙΣ ΓΑΙΩΝ ΣΕ ΗΡΕΜΙΑ (ΤΟΙΧΕΙΑ ΜΕ

ΠΕΡΙΟΡΙΣΜΕΝΗ ΜΕΤΑΚΙΝΗΣΗ)

PASSIVE SOIL PRESSURE -------------------------------------------------- 27.6 kN/m3

ΠΑΘΗΤΙΚΕΣ ΩΘΗΣΕΙΣ ΓΑΙΩΝ

COEFFICIENT OF FRICTION ------------------------------------------------- 0.35

ΣΥΝΤΕΛΕΣΤΗΣ ΤΡΙΒΗΣ

SOIL UNIT WEIGHT ------------------------------------------------------------- 17 kN/m3

ΕΙΔΙΚΟ ΒΑΡΟΣ

FROST DEPTH -------------------------------------------------------------------- 0

ΒΑΘΟΣ ΠΑΓΕΤΟΥ

SOIL SUBGRADE REACTION:

ΜΕΤΡΟ ΑΝΤΙΣΤΑΣΗΣ ΥΠΕΔΑΦΟΥΣ

SLABS ON GRADE ------------------------------------------------------ 13MN/m3

ΠΛΑΚΑ ΕΠΙ ΕΔΑΦΟΥΣ

STRIP FOOTINGS ------------------------------------------------------- 10MN/m3

ΠΕΔΙΛΟΔΟΚΑΡΙΑ

3.1. DESIGN RESPONSIBILITY FOR THE FOLLOWING ENGINEERED

SYSTEMS AND COMPONENTS IS DELEGATED TO A QUALIFIED

SPECIALTY STRUCTURAL ENGINEER RETAINED BY THE CONTRACTOR.

THESE SYSTEMS AND COMPONENTS INCLUDE, BUT ARE NOT LIMITED

TO:

Η ΕΥΘΥΝΗ ΤΟΥ ΣΧΕΔΙΑΣΜΟΥ ΓΙΑ ΤA ΑΚΟΛΟΥΘA ΜΗΧΑΝΙΚA ΣΥΣΤΗΜΑΤΑ ΚΑΙ

ΔΟΜΙΚΑ ΣΤΟΙΧΕΙΑ ΑΝΑΤΙΘΕΤΑΙ ΣΕ ΕΞΕΙΔΙΚΕΥΜΕΝΟ ΔΟΜΟΣΤΑΤΙΚΟ

ΜΗΧΑΝΙΚΟ, ΔΙΟΡΙΣΜΕΝΟ ΑΠΟ ΤΟΝ ΕΡΓΟΛΑΒΟ. ΑΥΤΑ ΤΑ ΣΥΣΤΗΜΑΤΑ ΚΑΙ ΤΑ

ΔΟΜΙΚΑ ΣΤΟΙΧΕΙΑ ΠΕΡΙΛΑΜΒΑΝΟΥΝ, ΑΛΛΑ ΔΕΝ ΠΕΡΙΟΡΙΖΟΝΤΑΙ ΑΠΟ:

A. ATFP BRACING FOR NONSTRUCTURAL COMPONENTS PER

UFC 4-010-01, OR EUROCODE EQUIVALENT.

B. SEISMIC BRACING FOR NON-STRUCTURAL COMPONENTS PER

UFC 3-301-01 AND ASCE 7.

Α. ΣΥΝΔΕΣΕΙΣ ΧΙΑΣΤΙ ΑΝΤΙΑΝΕΜΙΑ ΣΕ ΜΗ ΣΤΑΤΙΚΑ ΔΟΜΙΚΑ ΣΤΟΙΧΕΙΑ ΓΙΑ

ΑΝΤΙΤΡΟΜΟΚΡΑΤΙΚΗ ΠΡΟΣΤΑΣΙΑ, ΣΥΜΦΩΝΑ ΜΕ ΤΟ UFC 4-010-01 'Η

ΑΝΤΙΣΤΟΙΧΕΣ ΠΑΡΑΓΡΑΦΟΙ ΤΟΥ ΕΥΡΩΚΩΔΙΚΑ

Β. ΑΝΤΙΣΕΙΣΜΙΚΕΣ ΣΥΝΔΕΣΕΙΣ ΧΙΑΣΤΙ ΑΝΤΙΑΝΕΜΙΑ ΓΙΑ ΜΗ ΣΤΑΤΙΚΑ

ΔΟΜΙΚΑ ΣΤΟΙΧΕΙΑ ΣΥΜΦΩΝΑ ΜΕ ΤΟ UFC 3-301-01 ΚΑΙ ASCE 7

3.2. DELEGATED ENGINEERED SYSTEMS AND COMPONENTS MUST SATISFY

ASCE 7, OR EUROCODE EQUIVALENT. AND ALL APPLICABLE UFCs, OR

EUROCODE EQUIVALENT. AND MATERIAL SPECIFIC STANDARDS.

ΤΑ ΜΗΧΑΝΙΚΑ ΣΥΣΤΗΜΑΤΑ ΚΑΙ ΔΟΜΙΚΑ ΣΤΟΙΧΕΙΑ ΤΗΣ ΑΝΑΤΕΘΕΙΜΕΝΗΣ

ΜΕΛΕΤΗΣ ΠΡΕΠΕΙ ΝΑ ΕΙΝΑΙ ΣΥΜΦΩΝΑ ΜΕ ΤΟ ASCE 7, Η' ΤΙΣ ΑΝΤΙΣΤΟΙΧΕΣ

ΠΑΡΑΓΡΑΦΟΥΣ ΤΟΥ ΕΥΡΩΚΩΔΙΚΑ. ΚΑΙ ΜΕ ΟΛΑ ΤΑ ΕΦΑΡΜΟΖΟΜΕΝΑ UFC Η'

ΤΙΣ ΑΝΤΙΣΤΟΙΧΕΣ ΠΑΡΑΓΡΑΦΟΥΣ ΤΟΥ ΕΥΡΩΚΩΔΙΚΑ. ΚΑΙ ΜΕ ΤΙΣ ΕΙΔΙΚΕΣ

ΠΡΟΔΙΑΓΡΑΦΕΣ ΤΩΝ ΥΛΙΚΩΝ.

3.0 DELEGATED DESIGN NOTES:

2.0 ANTITERRORISM CRITERIA:

2.1. ANTITERRORISM DESIGN MUST BE IN ACCORDANCE WITH UFC 4-010-01

APPENDIX B AND C USING THE FOLLOWING DESIGN CRITERIA:

Ο ΑΝΤΙΤΡΟΜΟΚΡΑΤΙΚΟΣ ΣΧΕΔΙΑΣΜΟΣ ΠΡΕΠΕΙ ΝΑ ΕΙΝΑΙ ΣΥΜΦΩΝΟΣ ΜΕ ΤΟ

UFC 4-010-01, ΠΑΡΑΡΤΗΜΑ Β ΚΑΙ Γ, ΧΡΗΣΙΜΟΠΟΙΩΝΤΑΣ ΤΑ ΑΚΟΛΟΥΘΑ

ΚΡΙΤΗΡΙΑ ΣΧΕΔΙΑΣΜΟΥ:

LEVEL OF PROTECTION ----------------------------------------- VERY LOW

ΕΠΙΠΕΔΟ ΠΡΟΣΤΑΣΙΑΣ ------------------------------------ ΠΟΛΥ ΧΑΜΗΛΟ

EXPLOSIVE WEIGHT ---------------------------------------------- II

ΒΑΡΟΣ ΕΚΡΗΚΤΙΚΩΝ

MINIMUM STANDOFF PROVIDED ---------------------------- 10m (SEE CIVIL) ΕΛΑΧΙΣΤΗ ΔΙΑΤΙΘΕΜΕΝΗ ΑΠΟΣΤΑΣΗ ΑΣΦΑΛΕΙΑΣ -- 10μ (ΒΛΕΠΕ ΣΧΕΔΙΑ

ΠΟΛΙΤΙΚΟΥ ΜΗΧΑΝΙΚΟΥ)

2.2. FUTURE ALTERATIONS TO THE BUILDING AND/OR SITE MUST NOT

RESULT IN AN INCREASED THREAT OF ATTACK TO ANY PORTION OF

THE FACILITIES UNLESS A NEW BLAST RESISTANCE EVALUATION IS

CONDUCTED.

ΜΕΛΛΟΝΤΙΚΕΣ ΔΙΑΦΟΡΟΠΟΙΗΣΕΙΣ ΣΤΟ ΚΤΙΡΙΟ ΚΑΙ/ Η’ ΣΤΟ ΠΕΔΙΟ, ΔΕΝ

ΠΡΕΠΕΙ ΕΠ’ΟΥΔΕΝΙ ΝΑ ΚΑΤΑΛΗΓΟΥΝ ΣΕ ΕΠΑΥΞΗΜΕΝΗ ΕΚΘΕΣΗ ΣΕ

ΚΙΝΔΥΝΟ ΣΕ ΟΠΟΙΟΔΗΠΟΤΕ ΤΜΗΜΑ ΤΩΝ ΕΚΓΑΤΑΣΤΑΣΕΩΝ ΕΑΝ ΔΕΝ ΕΧΕΙ

ΠΡΟΗΓΟΥΜΕΝΩΣ ΠΡΑΓΜΑΤΟΠΟΙΗΘΕΙ ΜΙΑ ΝΕΑ ΑΞΙΟΛΟΓΗΣΗ ΤΗΣ

ΑΝΤΙΣΤΑΣΗΣ ΣΕ ΕΚΡΗΞΗ.

2.3. THE CIVIL DRAWINGS INDICATE STAND OFF DISTANCES.

ΤΑ ΣΧΕΔΙΑ ΠΟΛΙΤΙΚΟΥ ΜΗΧΑΝΙΚΟΥ ΥΠΟΔΕΙΚΝΥΟΥΝ ΤΙΣ ΑΠΟΣΤΑΣΕΙΣ

ΑΣΦΑΛΕΙΑΣ

2.4 PROGRESSIVE COLLAPSE CRITERIA

ΚΡΙΤΗΡΙΑ ΣΤΑΔΙΑΚΗΣ ΚΑΤΑΡΡΕΥΣΗΣ

SYSTEM -------------------------------------------------------------- LOAD BEARING WALLS

ΣΥΣΤΗΜΑ ΦΕΡΟΥΣΑ ΤΟΙΧΟΠΟΙΙΑ

RISK CATEGORY ------------------------------------------------- IV

ΚΑΤΗΓΟΡΙΑ ΕΠΙΚΙΝΔΥΝΟΤΗΤΑΣ

DESIGN APPROACH -------------------------------------------- TIE FORCE &

ALTERNATE PATH

ΠΡΟΣΕΓΓΙΣΗ ΣΧΕΔΙΑΣΜΟΥ ---------------------ΜΕΘΟΔΟΣ ΔΥΝΑΜΕΩΝ

ΑΓΚΥΡΩΣΗΣ ΚΑΙ ΕΝΑΛΛΑΚΤΙΚΩΝ ΔΙΑΔΡΟΜΩΝ

DESIGN METHOD ------------------------------------------------ LINEAR STATIC

ΜΕΘΟΔΟΣ ΣΧΕΔΙΑΣΜΟΥ ----------------------- ΓΡΑΜΜΙΚΗ ΣΤΑΤΙΚΗ

DESIGN SOFTWARE -------------------------------------------- ETABS

ΛΟΓΙΣΜΙΚΟ ΣΧΕΔΙΑΣΜΟΥ

ENHANCED LOCAL RESISTANCE -------------------------- FIRST STORY

PERIMETER WALLS

ΕΝΙΣΧΥΣΗ ΑΝΤΙΣΤΑΣΗΣ ΤΟΠΙΚΑ ----------------------- ΠΕΡΙΜΕΤΡΙΚΑ ΤΟΙΧΕΙΑ

ΣΕ ΠΡΩΤΟ ΟΡΟΦΟ

DESIGN OF THE BUILDING IS IN ACCORDANCE WITH UFC 4-023-03,

CHANGE 3, 1 NOVEMBER 2016. FUTURE ADDITIONS TO THIS STRUCTURE

MUST NOT JEOPARDIZE THE REQUIREMENTS FOR PROGRESSIVE

COLLAPSE RESISTANCE.

Ο ΣΧΕΔΙΑΣΜΟΣ ΤΟΥ ΚΤΙΡΙΟΥ ΕΙΝΑΙ ΣΥΜΦΩΝΑ ΜΕ ΤΟ UFC 4-023-03, ΑΛΛΑΓΗ

3, 1 ΝΟΕΜΒΡΙΟΥ 2016. ΜΕΛΛΟΝΤΙΚΕΣ ΠΡΟΣΘΗΚΕΣ ΣΤΗ ΣΥΓΚΕΚΡΙΜΕΝΗ

ΚΑΤΑΣΚΕΥΗ ΔΕΝ ΠΡΕΠΕΙ ΝΑ ΘΕΤΟΥΝ ΣΕ ΚΙΝΔΥΝΟ ΤΙΣ ΠΡΟΔΙΑΓΡΑΦΕΣ ΓΙΑ

ΑΝΤΙΣΤΑΣΗ ΣΕ ΣΤΑΔΙΑΚΗ ΚΑΤΑΡΕΥΣΗ

ΣΗΜΕΙΩΣΕΙΣ ΠΕΡΙ ΑΝΑΤΕΘΕΙΜΕΝΗΣ ΜΕΛΕΤΗΣ

ΚΡΙΤΗΡΙΑ ΣΧΕΤΙΚΑ ΜΕ ΑΝΤΙΤΡΟΜΟΚΡΑΤΙΑ:

1.9. WIND LOAD - EUROCODE 1 WITH GREEK ANNEX.

ΦΟΡΤΙΟ ΑΝΕΜΟΥ – ΕΥΡΩΚΩΔΙΚΑΣ 1 ΜΕ ΕΘΝΙΚΟ ΠΡΟΣΑΡΤΗΜΑ

TERRAIN CATEGORY ------------------------------------------------------------- II

ΚΑΤΗΓΟΡΙΑ ΕΔΑΦΟΥΣ

WIND DIRECTION ------------------------------------------------------------------- 0, 90 DEGREES

ΔΙΕΥΘΥΝΣΗ ΑΝΕΜΟΥ

BASIC WIND VELOCITY ----------------------------------------------------------- Vb = 33 m/s

ΒΑΣΙΚΗ ΤΑΧΥΤΗΤΑ ΑΝΕΜΟΥ

WINDWARD COEFFICIENT ------------------------------------------------------ Cp, wind = 0.8

ΣΥΝΤΕΛΕΣΤΗΣ ΠΡΟΣΗΝΕΜΗΣ ΠΙΕΣΗΣ

LEEWARD COEFFICIENT -------------------------------------------------------- Cp, lee = 0.5

ΣΥΝΤΕΛΕΣΤΗΣ ΥΠΗΝΕΜΗΣ ΠΙΕΣΗΣ

AIR DENSITY -------------------------------------------------------------------------- RHO = 1.25

ΠΥΚΝΟΤΗΤΑ ΑΕΡΑ

STRUCTURAL FACTOR ----------------------------------------------------------- cscd = 1

ΔΟΜΙΚΟΣ ΣΥΝΤΕΛΕΣΤΗΣ

ELEVATION ---------------------------------------------------------------------------- z0 = 0.05

ΥΨΟΜΕΤΡΟ

MINIMUM ELEVATION ------------------------------------------------------------- zmin = 2

ΕΛΑΧΙΣΤΟ ΥΨΟΜΕΤΡΟ

MAXIMUM ELEVATION ------------------------------------------------------------ zmax = 200

ΜΕΓΙΣΤΟ ΥΨΟΜΕΤΡΟ

TURBULENCE FACTOR ----------------------------------------------------------- k1 = 1

ΣΥΝΤΕΛΕΣΤΗΣ ΣΤΡΟΒΙΛΙΣΜΟΥ

OROGRAPHY FACTOR ------------------------------------------------------------ Co = 1

ΣΥΝΤΕΛΕΣΤΗΣ ΟΡΕΟΓΡΑΦΙΑΣ

a = 3100mm

4.6 m2

+0.77 -2.97

18.6 m2

+0.77 -2.51

1.0 m2

+2.01 -4.63

4.6 m2

+1.81 -3.94

18.6 m2

+1.63 -3.34

ROOF

ΟΡΟΦΗ

N/A N/A N/A +6.06 -4.09

+5.14 -3.46

+4.36 -2.91

PARAPET

ΣΤΗΘΑΙΟ

WALL PRESSURES (kPa)

BASED ON TRIBUTARY AREA

1.0 m2

ΠΙΕΣΕΙΣ ΤΟΙΧΩΝ ΑΝΑΛΟΓΑ ΜΕ ΤΗΝ

ΣΥΜΒΑΛΛΟΜΕΝΗ ΠΕΡΙΟΧΗ

ZONE 4

ΖΩΝΗ 4

2.02 -2.18

4.6 m2

1.81 -1.98

18.6 m2

1.63 -1.80

1.0 m2

2.02 -2.69

4.6 m2

1.81 -2.27

18.6 m2

1.63 -1.92

ZONE 5

ΖΩΝΗ 5

B

1 2 3 4 5

NONE

1615269

DWG

SHEET OF

NAVFAC DRAWING NO.

CONSTR. CONTR. NO.

EPROJECT NO.

SCALE:

N62470-21-C-0005

DESIGN DIRECTOR

BRANCH MANAGER

PM/DM

DES DRW CHK

SATISFACTORY TO DATE

ACTIVITY

FOR COMMANDER NAVFAC

APPROVED

A/E INFO

SEAL

SY

M

DE

SC

RI

PT

IO

N

DA

TE

AP

PR

N

AV

S U

PP

AC

T

SO

U D

A B

AY

N

AV

A L

FA

C

IL

IT

IE

S

EN

G

IN

E

ER

IN

G S

YS

TE

M C

O M

M

AN

D D

E P

AR

TM

E N

T O

F

TH

E N

A

VY

N

AV

AL

F

AC

IL

IT

IE

S E

N G

IN

EE

R

IN

G S

YS

TE

M C

O M

M

AN

D

A

FIRE PROTECTION

N O

R

FO

LK

, V

A A

TL

AN

TI

C

D E

SI

G

N A

N D

C O

N

ST

R U

C

TI

O N

1100 NORTH GLEBE ROAD

SUITE 500

ARLINGTON, VIRGINIA 22201

571.218.1000

FAX: 571.218.1600

D

C

B

A

1 2 3 4 5

RICHARD STEPHENS

TRUEWORTHY,PE / STELMASZEK,RA

PL

O

T

DA

TE

/T

IM

E:

7/

/ 2

3:

:3

PM

C

R ev it_ Lo ca l_

M od el s\

\P

1- D

1-

S_ R

_j oe

.th om as 1.

rv t

14 JUL 2021

RECEIVED BY JACOBIE TISDALE

AND STEVE PARK VIA EMAIL

S-002

LAP JT LPF

P

C

O M

M U

N

IC

A

TI

O N

C E

N

TE

RS

O

U D

A B

AY

, G

R

EE

C E

G

EN

ER

A

L

ST

R U

C

TU

R

AL

N O

TE

S

14089103

ΓΕ

Ν

ΙΚ

ΕΣ

ΚΑ

ΤΑ

ΣΚ

ΕΥ

Α

ΣΤ

ΙΚ

ΕΣ

Π

ΑΡ

Α

ΤΗ

Ρ Η

ΣΕ

ΙΣ

JTW

DPS

30.0 CONCRETE:

30.1. CONCRETE WORK MUST CONFORM TO THE FOLLOWING REQUIREMENTS:

EUROCODE 2 - EN 1992/GREEK NATIONAL ANNEX, DESIGN OF CONCRETE STRUCTURES.

GREEK CODE FOR CONCRETE CONSTRUCTION CEMENT (G.G. 69A/28.03.80)

ΟΙ ΕΡΓΑΣΙΕΣ ΜΕ ΣΚΥΡΟΔΕΜΑ ΠΡΕΠΕΙ ΝΑ ΣΥΜΜΟΡΦΩΝΟΝΤΑΙ ΣΤΙΣ ΠΑΡΑΚΑΤΩ ΑΠΑΙΤΗΣΕΙΣ:

ΕΥΡΩΚΩΔΙΚΑΣ 2 - ΕΝ 1992/ ΕΘΝΙΚΟ ΠΡΟΣΑΡΤΗΜΑ, ΣΧΕΔΙΑΣΜΟΣ ΚΑΤΑΣΚΕΥΩΝ ΑΠΟ

ΣΚΥΡΟΔΕΜΑ. ΕΛΛΗΝΙΚΟΣ ΚΑΝΟΝΙΣΜΟΣ ΤΣΙΜΕΝΤΟΥ ΓΙΑ ΕΡΓΑ ΑΠΟ ΣΚΥΡΟΔΕΜΑ (ΦΕΚ

69A/28.03.80)

30.2. CONCRETE PROPERTIES:

ΙΔΙΟΤΗΤΕΣ ΣΚΥΡΟΔΕΜΑΤΟΣ

TYPICAL CONCRETE, UNLESS NOTED OTHERWISE

fck, cube = 45MPa; COMPRESSIVE STRENGTH OF 15cm x 15cm x15cm CUBIC SAMPLE

(EN1992-1-1:2004 PAGE 29 TABLE 3.1)

fck= 35MPa; COMPRESSIVE STRENGTH OF 15cm (dia) x 30cm CYLINDRICAL SAMPLE

(EN1992-1-1:2004 PAGE 29 TABLE 3.1)

ΤΥΠΙΚΟ ΣΚΥΡΟΔΕΜΑ ΕΚΤΟΣ ΚΑΙ ΑΝ ΔΕΙΚΝΥΕΤΑΙ ΔΙΑΦΟΡΕΤΙΚΑ

fck, cube = 45Mpa, ΘΛΙΠΤΙΚΗ ΑΝΤΟΧΗ ΚΥΒΙΚΟΥ ΔΟΚΙΜΙΟΥ 15Χ15Χ15 ΕΚ.

(EN 1992-1-1:2004, ΣΕΛΙΔΑ 29, ΠΙΝΑΚΑΣ 3.1)

fck = 35Mpa, ΘΛΙΠΤΙΚΗ ΑΝΤΟΧΗ ΚΥΛΙΝΔΡΙΚΟΥ ΔΟΚΙΜΙΟΥ 15 ΕΚ. ΔΙΑΜΕΤΡΟΣ Χ 30 ΕΚ.

(EN 1992-1-1:2004, ΣΕΛΙΔΑ 29, ΠΙΝΑΚΑΣ 3.1)

LEAN CONCRETE ON SUBBASE

fck, cube =15MPa; COMPRESSIVE STRENGTH OF 15cm x 15cm x15cm CUBIC SAMPLE

(EN1992-1-1:2004 PAGE 29 TABLE 3.1)

fck= 12MPa; COMPRESSIVE STRENGTH OF 15cm (dia) x 30cm CYLINDRICAL SAMPLE

(EN1992-1-1:2004 PAGE 29 TABLE 3.1)

ΣΚΥΡΟΔΕΜΑ ΕΞΟΜΑΛΥΝΣΗΣ ΒΑΣΗΣ

fck, cube = 15Mpa, ΘΛΙΠΤΙΚΗ ΑΝΤΟΧΗ ΚΥΒΙΚΟΥ ΔΟΚΙΜΙΟΥ 15Χ15Χ15 ΕΚ.

(EN 1992-1-1:2004, ΣΕΛΙΔΑ 29, ΠΙΝΑΚΑΣ 3.1)

fck = 12Mpa, ΘΛΙΠΤΙΚΗ ΑΝΤΟΧΗ ΚΥΛΙΝΔΡΙΚΟΥ ΔΟΚΙΜΙΟΥ 15 ΕΚ. ΔΙΑΜΕΤΡΟΣ Χ 30 ΕΚ.

(EN 1992-1-1:2004, ΣΕΛΙΔΑ 29, ΠΙΝΑΚΑΣ 3.1)

30.3. CONCRETE DENSITY IS NORMAL WEIGHT, 23.5 kN/m3, UNLESS SPECIFICALLY NOTED.

ΕΙΔΙΚΟ ΒΑΡΟΣ ΣΚΥΡΟΔΕΜΑΤΟΣ, 23.5 kN/m3 ΕΚΤΟΣ ΚΑΙ ΥΠΑΡΧΕΙ ΕΙΔΙΚΗ ΑΝΑΦΟΡΑ.

30.4. COORDINATE SIZE AND LOCATION OF EMBEDDED ITEMS, OPENINGS, SLEEVES, INSERTS, DOWELS, DEPRESSIONS, CURBS, PITS, CONDUITS, ETC. WITH MECHANICAL, ELECTRICAL, AND ARCHITECTURAL DRAWINGS, AND EQUIPMENT FURNISHED PRIOR TO PLACEMENT OF

CONCRETE.

ΝΑ ΣΥΝΤΟΝΙΣΤΟΥΝ ΤΟ ΜΕΓΕΘΟΣ ΚΑΙ Η ΘΕΣΗ ΤΩΝ ΕΝΣΩΜΑΤΩΜΕΝΩΝ ΣΤΟ ΣΚΥΡΟΔΕΜΑ

ΑΝΤΙΚΕΙΜΕΝΩΝ, ΑΝΟΙΓΜΑΤΩΝ, ΣΩΛΗΝΩΣΕΩΝ ΑΝΑΜΟΝΗΣ ΑΓΩΓΩΝ , ΡΟΔΕΛΩΝ, ΒΛΗΤΡΩΝ,

ΘΛΙΠΤΗΡΩΝ, ΚΡΑΣΠΕΔΩΝ, ΣΚΑΜΜΑΤΩΝ, ΕΣΟΧΩΝ, ΑΓΩΓΩΝ ΚΤΛ ΜΕ ΤΑ ΜΗΧΑΝΟΛΟΓΙΚΑ,

ΗΛΕΚΤΡΟΛΟΓΙΚΑ ΚΑΙ ΑΡΧΙΤΕΚΤΟΝΙΚΑ ΣΧΕΔΙΑ ΚΑΙ ΜΕ ΤΟΝ ΕΞΟΠΛΙΣΜΟ ΠΟΥ ΘΑ

ΕΓΚΑΤΑΣΤΑΘΕΙ, ΠΡΙΝ ΤΗΝ ΣΚΥΡΟΔΕΤΗΣΗ.

30.5. CONDUITS, PIPES, DUCTS, OR SLEEVES MUST NOT BE EMBEDDED WITHIN SLABS,

WALLS, BEAMS, OR COLUMNS UNLESS SPECIFICALLY INDICATED ON THE DRAWINGS.

EMBEDDED ALUMINUM CONDUITS AND PIPES ARE NOT BE PERMITTED.

ΑΓΩΓΟΙ, ΣΩΛΗΝΕΣ ΚΑΙ ΚΑΛΥΜΜΑΤΑ ΔΕΝ ΠΡΕΠΕΙ ΝΑ ΕΝΣΩΜΑΤΩΝΟΝΤΑΙ ΣΤΙΣ ΠΛΑΚΕΣ,

ΤΟΙΧΕΙΑ, ΔΟΚΑΡΙΑ Η' ΥΠΟΣΤΥΛΩΜΑΤΑ ΕΚΤΟΣ ΚΑΙ ΑΝ ΥΠΑΡΧΕΙ ΕΙΔΙΚΗ ΑΝΑΦΟΡΑ ΣΤΑ

ΣΧΕΔΙΑ. ΕΝΣΩΜΑΤΩΜΕΝΟΙ ΑΓΩΓΟΙ ΚΑΙ ΣΩΛΗΝΕΣ ΑΛΟΥΜΙΝΙΟΥ ΔΕΝ ΕΠΙΤΡΕΠΟΝΤΑΙ.

30.6. EXPOSED EDGES OF CONCRETE (BEAMS, COLUMNS, WALLS, ETC.) MUST BE

CHAMFERED 20mm, UNLESS SPECIFICALLY NOTED OTHERWISE.

ΕΚΤΕΘΕΙΜΕΝΕΣ ΑΚΜΕΣ ΣΚΥΡΟΔΕΜΑΤΟΣ (ΔΟΚΑΡΙΑ, ΥΠΟΣΤΥΛΩΜΑΤΑ, ΤΟΙΧΕΙΑ Κ.Α) ΠΡΕΠΕΙ

ΝΑ ΕΙΝΑΙ ΛΟΞΟΤΟΜΗΜΕΝΕΣ 30MM, ΕΚΤΟΣ ΚΑΙ ΑΝ ΥΠΑΡΧΕΙ ΕΙΔΙΚΗ ΑΝΑΦΟΡΑ.

30.7. ROUGHEN AND CLEAN CONSTRUCTION JOINTS IN WALLS AND SLABS PRIOR TO PLACING

ADJACENT CONCRETE. ROUGHEN TO AN AMPLITUDE OF 5mm.

ΝΑ ΤΡΑΧΥΝΘΟΥΝ ΚΑΙ ΝΑ ΚΑΘΑΡΙΣΤΟΥΝ ΟΙ ΚΑΤΑΣΚΕΥΑΣΤΙΚΟΙ ΑΡΜΟΙ ΣΤΟΥΣ ΤΟΙΧΟΥΣ ΚΑΙ

ΤΙΣ ΠΛΑΚΕΣ ΠΡΙΝ ΤΗΝ ΠΑΡΑΚΕΙΜΕΝΗ ΣΚΥΡΟΔΕΤΗΣΗ. ΝΑ ΤΡΑΧΥΝΘΟΥΝ ΣΕ ΕΥΡΟΣ 5mm.

30.8. TO COMPENSATE FOR WET CONCRETE, DEFLECTION OF THE STRUCTURE SLAB

THICKNESSES MUST BE INCREASED AS REQUIRED TO PROVIDE A LEVEL SURFACE WITHIN

TOLERANCE. THE ADDITIONAL CONCRETE MUST BE PROVIDED AT NO ADDITIONAL COST.

ΠΡΟΚΕΙΜΕΝΟΥ ΝΑ ΑΝΤΙΜΕΤΩΠΙΣΤΕΙ ΠΙΘΑΝΗ ΜΗ ΕΠΙΠΕΔΗ ΕΠΙΦΑΝΕΙΑ ΤΟΥ ΣΚΥΡΟΔΕΜΑΤΟΣ

ΕΝΩ ΕΙΝΑΙ ΑΚΟΜΑ ΥΓΡΟ, ΤΟ ΣΤΑΤΙΚΟ ΠΑΧΟΣ ΤΗΣ ΠΛΑΚΑΣ, ΘΑ ΠΡΕΠΕΙ ΝΑ ΑΥΞΗΘΕΙ

ΣΥΜΦΩΝΑ ΜΕ ΤΙΣ ΠΡΟΔΙΑΓΡΑΦΕΣ, ΩΣΤΕ ΝΑ ΠΡΟΚΥΨΕΙ ΕΠΙΠΕΔΗ ΕΠΙΦΑΝΕΙΑ ΕΝΤΟΣ ΑΝΟΧΩΝ.

ΤΟ ΕΠΙΠΛΕΟΝ ΣΚΥΡΟΔΕΜΑ ΘΑ ΠΡΕΠΕΙ ΝΑ ΠΑΡΕΧΕΤΑΙ ΧΩΡΙΣ ΕΠΙΠΛΕΟΝ ΚΟΣΤΟΣ.

30.9. WHERE NOT INDICATED ON DRAWINGS, CONCRETE SLABS ON GROUND MUST BE BOUND

BY CONTRACTION JOINTS WITH AN ENCLOSED AREA NOT EXCEEDING 23 SQUARE METERS

AND A MAXIMUM PANEL LENGTH TO WIDTH RATIO OF 1.5. JOINTS MUST BE LOCATED

ON COLUMN GRID LINES AND AT 4.5 METERS MAXIMUM.

ΟΠΟΥ ΔΕΝ ΔΕΙΚΝΥΕΤΑΙ ΣΤΑ ΣΧΕΔΙΑ, ΟΙ ΠΛΑΚΕΣ ΣΚΥΡΟΔΕΜΑΤΟΣ ΕΠΙ ΕΔΑΦΟΥΣ ΠΡΕΠΕΙ ΝΑ

ΟΡΙΟΘΕΤΟΥΝΤΑΙ ΑΠΟ ΑΡΜΟΥΣ ΣΥΣΤΟΛΗΣ ΣΕ ΕΜΒΑΔΟ ΟΧΙ ΜΕΓΑΛΥΤΕΡΟ ΑΠΟ 23

ΤΕΤΡΑΓΩΝΙΚΑ ΜΕΤΡΑ ΚΑΙ ΣΕ ΜΕΓΙΣΤΗ ΑΝΑΛΟΓΙΑ ΜΗΚΟΥΣ/ΠΛΑΤΟΥΣ 1.5. ΟΙ ΑΡΜΟΙ

ΠΡΕΠΕΙ ΝΑ ΤΟΠΟΘΕΤΟΥΝΤΑΙ ΣΤΟΥΣ ΑΞΟΝΕΣ ΤΟΥ ΚΑΝΑΒΟΥ ΤΩΝ ΥΠΟΣΤΥΛΩΜΑΤΩΝ ΚΑΙ ΣΕ

ΜΕΓΙΣΤΗ ΑΠΟΣΤΑΣΗ 4.5 ΜΕΤΡΑ.

30.10. REINFORCING STEEL MUST BE DETAILED, FABRICATED, AND PLACED IN

ACCORDANCE WITH EUROCODE 2 - EN 1992/GREEK NATIONAL ANNEX, DESIGN OF

CONCRETE STRUCTURES.

ΟΛΟΙ ΟΙ ΧΑΛΥΒΕΣ ΟΠΛΙΣΗΣ ΠΡΕΠΕΙ ΣΧΕΔΙΑΣΤΟΥΝ, ΚΑΤΑΣΚΕΥΑΣΤΟΥΝ ΚΑΙ ΤΟΠΟΘΕΤΗΘΟΥΝ

ΣΥΜΦΩΝΑ ΜΕ ΤΟ ΕΥΡΩΚΩΔΙΚΑ 2 - ΕΝ 1992/ ΕΛΛΗΝΙΚΟ ΕΘΝΙΚΟ ΠΡΟΣΑΡΤΗΜΑ, ΣΧΕΔΙΑΣΜΟΣ

ΚΑΤΑΣΚΕΥΩΝ ΑΠΟ ΣΚΡΟΔΕΜΑ.

30.11. TYPICAL REINFORCING STEEL:

ΤΥΠΙΚΟΣ ΧΑΛΥΒΑΣ ΟΠΛΙΣΗΣ

DEFORMED BARS ------------------------------------------------------------------------B500c; fyk = 500 MPa

ΡΑΒΔΟΙ ΜΕ ΣΠΕΙΡΩΜΑ

30.12. REINFORCEMENT, ANCHORAGE, AND DETAILING NOT CLEARLY SHOWN ON DETAILS

MUST FOLLOW PROVISIONS OF EN 1998.01 AND EN 1992.01.01.

ΟΠΛΙΣΗ, ΑΓΚΥΡΩΣΕΙΣ ΚΑΙ ΛΕΠΤΟΜΕΡΕΙΕΣ ΠΟΥ ΔΕΝ ΦΑΙΝΟΝΤΑΙ ΚΑΘΑΡΑ ΣΤΙΣ

ΛΕΠΤΟΜΕΡΕΙΕΣ ΠΡΕΠΕΙ ΝΑ ΑΚΟΛΟΥΘΟΥΝ ΤΙΣ ΔΙΑΤΑΞΕΙΣ ΤΟΥ ΕN 1998.01 ΚΑΙ EN 1992.01.01

DESCRIPTION COVER

CONCRETE CAST AGAINST AND PERMANENTLY

EXPOSED TO EARTH

ΣΚΥΡΟΔΕΤΗΣΗ ΣΤΟ ΕΔΑΦΟΣ Η΄ ΜΟΝΙΜΑ

ΕΚΤΕΘΕΙΜΕΝΗ ΣΕ ΑΥΤΟ.

75mm

CONCRETE CAST AGAINST FORMS OR LEAN CONCRETE

LAYER AND EXPOSED TO EARTH OR WEATHER

ΣΚΥΡΟΔΕΤΗΣΗ ΣΕ ΚΑΛΟΥΠΙΑ Η' ΕΞΙΣΩΤΙΚΗ ΣΤΡΩΣΗ ΚΑΙ

ΕΚΤΕΘΕΙΜΕΝΗ ΣΤΟ ΕΔΑΦΟΣ Η' ΤΙΣ ΚΑΙΡΙΚΕΣ ΣΥΝΘΗΚΕΣ.

CONCRETE NOT EXPOSED TO

WEATHER OR IN CONTACT

WITH GROUND:

ΣΚΥΡΟΔΕΜΑ ΜΗ ΕΚΤΕΘΕΙΜΕΝΟ

ΣΕ ΚΑΙΡΙΚΕΣ ΣΥΝΘΗΚΕΣ Η΄ ΤΟ

ΕΔΑΦΟΣ.

SLABS ΠΛΑΚΕΣ

WALLS, BEAMS AND COLUMNS (TIES,

STIRRUPS PRIMARY REINFORCMENT,

SPIRALS)

ΤΟΙΧΕΙΑ, ΔΟΚΑΡΙΑ, ΥΠΟΣΤΥΛΩΜΑΤΑ

(ΤΣΕΡΚΙΑ, ΚΛΩΒΟΙ Κ.Α)

50mm

25mm

35mm

30.13. PROVIDE THE MINIMUM CONCRETE COVER INDICATED IN THE FOLLOWING

SCHEDULE, UNLESS NOTED OTHERWISE IN A SPECIFIC SECTION OR DETAIL.

ΝΑ ΠΑΡΕΧΕΤΑΙ ΣΤΟ ΣΚΥΡΟΔΕΜΑ Η ΕΛΑΧΙΣΤΗ ΕΠΙΚΑΛΥΨΗ ΟΠΩΣ ΦΑΙΝΕΤΑΙ ΣΤΟΝ

ΠΑΡΑΚΑΤΩ ΠΙΝΑΚΑ, ΕΚΤΟΣ ΚΑΙ ΑΝ ΔΕΙΚΝΥΕΤΑΙ ΔΙΑΦΟΡΕΤΙΚΑ ΣΕ ΣΥΓΚΕΚΡΙΜΕΝΗ

ΠΑΡΑΓΡΑΦΟ Ή ΛΕΠΤΟΜΕΡΕΙΑ

ΣΚΥΡΟΔΕΜΑ

30.0 CONCRETE: (CONT)

ΣΚΥΡΟΔΕΜΑ (ΣΥΝΕΧΕΙΑ)

30.14. REINFORCING BARS MUST BE COLD BENT. BARS EMBEDDED IN CONCRETE

MUST NOT BE FIELD BENT, EXCEPT WHEN SPECIFICALLY INDICATED ON THE

DRAWINGS.

ΟΙ ΡΑΒΔΟΙ ΟΠΛΙΣΜΟΥ ΠΡΕΠΕΙ ΝΑ ΕΙΝΑΙ ΨΥΧΡΗΣ ΕΛΑΣΗΣ. ΟΙ ΡΑΒΔΟΙ ΠΟΥ

ΕΝΣΩΜΑΤΩΝΟΝΤΑΙ ΣΤΟ ΣΚΥΡΟΔΕΜΑ ΔΕΝ ΠΡΕΠΕΙ ΝΑ ΚΑΜΠΤΟΝΤΑΙ ΣΤΟ ΠΕΔΙΟ,

ΕΚΤΟΣ ΚΑΙ ΑΝ ΥΠΑΡΧΕΙ ΕΙΔΙΚΗ ΑΝΑΦΟΡΑ ΣΤΑ ΣΧΕΔΙΑ.

30.15. DO NOT CUT REINFORCEMENT UNLESS INDICATED BY SECTION

OR DETAIL. AT LOCATIONS OF CONFLICT, SPREAD THE REINFORCEMENT TO

ACCOMMODATE PLACEMENT. PROVIDE ADDITIONAL BARS TO MAINTAIN

SPACING REQUIREMENTS.

ΝΑ ΜΗΝ ΚΟΒΕΤΑΙ Ο ΟΠΛΙΣΜΟΣ ΕΚΤΟΣ ΚΑΙ ΑΝ ΑΝΑΓΡΑΦΕΤΑΙ ΣΕ ΟΡΙΣΜΕΝΗ

ΠΑΡΑΓΡΑΦΟ Ή ΛΕΠΤΟΜΕΡΕΙΑ. ΣΕ ΠΕΡΙΟΧΕΣ ΟΠΟΥ ΥΠΑΡΧΕΙ ΑΝΤΙΠΑΡΑΘΕΣΗ, NA

ΕΠΕΚΤΙΝΕΤΑΙ Ο ΟΠΛΙΣΜΟΣ ΩΣΤΕ ΝΑ ΔΙΕΥΚΟΛΥΝΕΤΑΙ Η ΤΟΠΟΘΕΤΗΣΗ. ΝΑ

ΤΟΠΟΘΕΤΟΥΝΤΑΙ ΕΠΙΠΛΕΟΝ ΟΠΛΙΣΜΟΙ ΩΣΤΕ ΝΑ ΔΙΑΤΗΡΟΥΝΤΑΙ ΟΙ

ΠΡΟΔΙΑΓΡΑΦΕΣ ΤΩΝ ΜΕΤΑΞΥ ΑΠΟΣΤΑΣΕΩΝ

30.16. PROVIDE ISOLATION JOINT WHERE SLABS ON GRADE ABUT WALLS AND

COLUMNS, UNO.

ΝΑ ΔΗΜΙΟΥΡΓΕΙΤΑΙ ΑΡΜΟΣ ΑΠΟΜΟΝΩΣΗΣ ΟΠΟΥ Η ΠΛΑΚΑ ΕΠΙ ΕΔΑΦΟΥΣ

ΣΥΝΑΝΤΑ ΤΟΙΧΕΙΑ ΚΑΙ ΥΠΟΣΤΥΛΩΜΑΤΑ, ΕΚΤΟΣ ΑΝ ΥΠΑΡΧΕΙ ΕΙΔΙΚΗ ΑΝΑΦΟΡΑ.

30.17. WHERE MISCELLANEOUS METALS ARE ATTACHED TO THE UNDERSIDE OF

CONCRETE SLABS OR BEAMS, FASTENER EMBEDMENT MUST NOT EXCEED

25mm, UNLESS SPECIFICALLY NOTED ON A DETAIL.

ΣΕ ΠΕΡIΠΤΩΣΕΙΣ ΟΠΟΥ ΔΙΑΦΟΡΑ ΜΕΤΑΛΛΙΚΑ ΑΝΤΙΚΕΙΜΕΝΑ ΣΥΝΔΕΟΝΤΑΙ ΣΤΗΝ

ΚΑΤΩ ΠΛΕΥΡΑ ΠΛΑΚΩΝ Ή ΔΟΚΑΡΙΩΝ ΣΚΥΡΟΔΕΜΑΤΟΣ, Η ΒΥΘΙΣΗ ΤΟΥ ΔΕΤΗ ΔΕΝ

ΠΡΕΠΕΙ ΝΑ ΞΕΠΕΡΝΑΕΙ ΤΑ 25ΜΜ, ΕΚΤΟΣ ΚΑΙ ΑΝ ΔΕΙΚΝΥΕΤΑΙ ΔΙΑΦΟΡΕΤΙΚΑ ΣΤΗΝ

ΛΕΠΤΟΜΕΡΕΙΑ.

ΠΕΡΙΓΡΑΦΗ

10.0 GENERAL CONSTRUCTION:

10.1. STRUCTURAL DRAWINGS MUST NOT BE SCALED. REFERENCE

SCALES INDICATED ON THE DRAWINGS ARE INTENDED FOR

INFORMATION USE ONLY AND MUST NOT BE USED TO DETERMINE

SPECIFIC DIMENSIONS OR QUANTITY OF MATERIALS.

ΣΤΑ ΣΤΑΤΙΚΑ ΣΧΕΔΙΑ ΟΙ ΚΛΙΜΑΚΕΣ ΔΕΝ ΠΡΕΠΕΙ ΝΑ ΧΡΗΣΙΜΟΠΟΙΟΥΝΤΑΙ

ΓΙΑ ΔΙΑΣΤΑΣΙΟΛΟΓΗΣΗ. ΟΙ ΚΛΙΜΑΚΕΣ ΠΟΥ ΑΝΑΓΡΑΦΟΝΤΑΙ ΣΤΑ ΣΧΕΔΙΑ

ΕΙΝΑΙ ΜΟΝΟ ΓΙΑ ΠΛΗΡΟΦΟΡΗΣΗ ΚΑΙ ΔΕΝ ΠΡΕΠΕΙ ΝΑ ΧΡΗΣΙΜΟΠΟΙΟΥΝΤΑΙ

ΓΙΑ ΝΑ ΚΑΘΟΡΙΣΟΥΝ ΣΥΓΚΕΚΡΙΜΕΝΕΣ ΔΙΑΣΤΑΣΕΙΣ Η' ΓΙΑ ΠΡΟΜΕΤΡΗΣΕΙΣ

ΥΛΙΚΩΝ.

10.2. PRIOR TO FABRICATION AND CONSTRUCTION, THE CONTRACTOR

MUST VERIFY EXISTING ELEVATIONS AND DIMENSIONS ASSOCIATED

WITH THE WORK. OMISSIONS OR CONFLICTS BETWEEN VARIOUS

ELEMENTS OF THE CONTRACT DRAWINGS AND/OR SPECIFICATIONS

MUST BE BROUGHT TO THE IMMEDIATE ATTENTION OF THE C.O. PRIOR

TO PROCEEDING WITH RELATED WORK.

ΠΡΙΝ ΤΗΝ ΠΑΡΑΓΩΓΗ ΚΑΙ ΚΑΤΑΣΚΕΥΗ, Ο ΕΡΓΟΛΑΒΟΣ ΠΡΕΠΕΙ ΝΑ

ΕΠΙΒΕΒΑΙΩΣΕΙ ΥΦΙΣΤΑΜΕΝΑ ΥΨΟΜΕΤΡΑ ΚΑΙ ΔΙΑΣΤΑΣΕΙΣ ΠΟΥ

ΣΧΕΤΙΖΟΝΤΑΙ ΜΕ ΤΙΣ ΕΡΓΑΣΙΕΣ. ΤΥΧΟΝ ΠΑΡΑΛΕΙΨΕΙΣ ΚΑΙ ΑΝΤΙΘΕΣΕΙΣ

ΜΕΤΑΞΥ ΣΤΟΙΧΕΙΩΝ ΤΩΝ ΣΧΕΔΙΩΝ ΚΑΙ/Ή ΤΩΝ ΠΡΟΔΙΑΓΡΑΦΩΝ ΘΑ ΠΡΕΠΕΙ

ΝΑ ΕΠΙΣΗΜΑΝΘΟΥΝ ΣΤΟΝ ΑΞΙΩΜΑΤΙΚΟ ΤΟΥ ΕΡΓΟΥ ΠΡΟΤΟΥ ΞΕΚΙΝΗΣΟΥΝ

ΟΙ ΣΧΕΤΙΚΕΣ ΕΡΓΑΣΙΕΣ.

10.3. COORDINATE WITH THE C.O. TO LOCATE EXISTING UNDERGROUND

UTILITIES AND BURIED ITEMS PRIOR TO CONSTRUCTING FOUNDATIONS.

ΝΑ ΥΠΑΡΞΕΙ ΣΥΝΤΟΝΙΣΜΟΣ ΜΕ ΤΟΝ ΑΞΙΩΜΑΤΙΚΟ ΤΟΥ ΕΡΓΟΥ ΓΙΑ ΝΑ

ΕΝΤΟΠΙΣΤΟΥΝ ΟΛΑ ΤΑ ΥΦΙΣΤΑΜΕΝΑ ΥΠΟΓΕΙΑ ΔΙΚΤΥΑ ΩΦΕΛΕΙΑΣ ΚΑΙ

ΘΑΜΜΕΝΑ ΑΝΤΙΚΕΙΜΕΝΑ ΠΡΙΝ ΤΗΝ ΚΑΤΑΣΚΕΥΗ ΤΗΣ ΘΕΜΕΛΙΩΣΗΣ.

10.4. THE STRUCTURAL DRAWINGS REPRESENT THE FINISHED STRUCTURE

AND DO NOT INDICATE THE METHOD OF CONSTRUCTION.

CONSTRUCTION LOADS MUST NOT EXCEED THE DESIGN LIVE LOADS.

THE CONTRACTOR IS RESPONSIBLE FOR WORK RELATED TO

CONSTRUCTION, ERECTION METHODS, BRACING, SHORING, RIGGING,

GUYS, SCAFFOLDING, FORMWORK, ETC. REQUIRED TO SAFELY

PERFORM THE WORK.

ΤΑ ΣΤΑΤΙΚΑ ΣΧΕΔΙΑ ΕΙΝΑΙ ΑΝΤΙΠΡΟΣΩΠΕΥΤΙΚΑ ΤΗΣ ΟΛΟΚΛΗΡΩΜΕΝΗΣ

ΚΑΤΑΣΚΕΥΗΣ ΚΑΙ ΔΕΝ ΠΡΟΣΔΙΟΡΙΖΟΥΝ ΤΗΝ ΜΕΘΟΔΟ ΑΝΕΓΕΡΣΗΣ. ΤΑ

ΦΟΡΤΙΑ ΚΑΤΑ ΤΗΝ ΔΙΑΡΚΕΙΑ ΤΗΣ ΚΑΤΑΣΚΕΥΗΣ ΔΕ ΠΡΕΠΕΙ ΝΑ ΕΙΝΑΙ

ΜΕΓΑΛΥΤΕΡΑ ΑΠΟ ΤΑ ΚΙΝΗΤΑ ΦΟΡΤΙΑ ΣΧΕΔΙΑΣΜΟΥ. Ο ΕΡΓΟΛΑΒΟΣ ΕΙΝΑΙ

ΥΠΕΥΘΥΝΟΣ ΓΙΑ ΟΛΕΣ ΤΙΣ ΕΡΓΑΣΙΕΣ ΣΧΕΤΙΚΕΣ ΜΕ ΤΗΝ ΚΑΤΑΣΚΕΥΗ, ΓΙΑ

ΤΙΣ ΜΕΘΟΔΟΥΣ ΑΝΕΓΕΡΣΗΣ, ΤΙΣ ΣΥΝΔΕΣΕΙΣ, ΤΙΣ ΥΠΟΣΤΗΡΙΞΕΙΣ, ΤΑ

ΚΑΛΩΔΙΑ ΣΤΗΡΙΞΗΣ, ΤΑ ΙΚΡΙΩΜΑΤΑ, ΤΙΣ ΞΥΛΟΥΡΓΙΚΕΣ ΕΡΓΑΣΙΕΣ ΚΤΛ

ΟΠΟΥ ΧΡΕΙΑΖΟΝΤΑΙ ΓΙΑ ΤΗΝ ΑΣΦΑΛΗ ΕΚΤΕΛΕΣΗ ΤΩΝ ΕΡΓΑΣΙΩΝ.

10.5. STRUCTURAL MEMBERS MUST NOT BE CUT (FOR PIPES, DUCTS, ETC.)

UNLESS SPECIFICALLY DETAILED OR APPROVED IN WRITING BY THE

C.O.

ΔΕΝ ΠΡΕΠΕΙ ΝΑ ΓΙΝΟΝΤΑΙ ΤΟΜΕΣ ΣΤΑ ΣΤΟΙΧΕΙΑ ΤΟΥ ΦΕΡΟΝΤΟΣ

ΟΡΓΑΝΙΣΜΟΥ (ΓΙΑ ΣΩΛΗΝΕΣ, ΑΓΩΓΟΥΣ Κ.Α.) ΕΚΤΟΣ ΚΑΙ ΑΝ ΥΠΑΡΧΕΙ

ΕΙΔΙΚΗ ΑΝΑΦΟΡΑ ΣΤΙΣ ΛΕΠΤΟΜΕΡΕΙΕΣ Η' ΓΡΑΠΤΗ ΕΓΚΡΙΣΗ ΑΠΟ ΤΟΝ

ΑΞΙΩΜΑΤΙΚΟ ΤΟΥ ΕΡΓΟΥ.

10.6. VERIFY SIZE AND LOCATION OF OPENINGS THROUGH FLOORS,

WALLS, SLABS, AND ROOFS WITH MECHANICAL, ELECTRICAL, AND

ARCHITECTURAL DRAWINGS, AND WITH EQUIPMENT FURNISHED

PRIOR TO PROCEEDING WITH RELATED WORK.

ΝΑ ΕΠΑΛΗΘΕΥΤΕΙ ΤΟ ΜΕΓΕΘΟΣ ΚΑΙ Η ΘΕΣΗ ΤΩΝ ΑΝΟΙΓΜΑΤΩΝ ΣΤΑ

ΔΑΠΕΔΑ, ΤΟΙΧΟΥΣ,ΠΛΑΚΕΣ ΚΑΙ ΣΤΕΓΕΣ ΜΕ ΜΗΧΑΝΟΛΟΓΙΚΑ,

ΗΛΕΚΤΡΟΛΟΓΙΚΑ ΚΑΙ ΑΡΧΙΤΕΚΤΟΝΙΚΑ ΣΧΕΔΙΑ, ΚΑΙ ΜΕ ΤΟΝ ΕΞΟΠΛΙΣΜΟ

ΠΟΥ ΘΑ ΕΓΚΑΤΑΣΤΑΘΕΙ ΠΡΙΝ ΓΙΝΕΙ Η ΕΚΑΣΤΟΤΕ ΕΡΓΑΣΙΑ.

10.7. NOTES AND DETAILS ON THE DRAWINGS TAKE PRECEDENCE

OVER GENERAL STRUCTURAL NOTES AND TYPICAL DETAILS.

ΟΙ ΠΑΡΑΤΗΡΗΣΕΙΣ ΚΑΙ ΛΕΠΤΟΜΕΡΕΙΕΣ ΣΤΑ ΣΧΕΔΙΑ ΥΠΕΡΙΣΧΥΟΥΝ ΤΩΝ

ΓΕΝΙΚΩΝ ΣΤΑΤΙΚΩΝ ΠΑΡΑΤΗΡΗΣΕΩΝ ΚΑΙ ΤΩΝ ΤΥΠΙΚΩΝ ΛΕΠΤΟΜΕΡΕΙΩΝ.

10.8. TYPICAL DETAILS AS SHOWN ON THE DRAWINGS APPLY TO SIMILAR

SITUATIONS OCCURRING IN THE PROJECT WHETHER OR NOT THEY

ARE IDENTIFIED IN EACH LOCATION. COORDINATE WITH THE C.O.

FOR INTERPRETATION OF APPLICABILITY OF TYPICAL DETAILS.

ΟΙ ΤΥΠΙΚΕΣ ΛΕΠΤΟΜΕΡΕΙΕΣ ΟΠΩΣ ΕΜΦΑΝΙΖΟΝΤΑΙ ΣΤΑ ΣΧΕΔΙΑ ΕΧΟΥΝ

ΕΦΑΡΜΟΓΗ ΚΑΙ ΣΕ ΠΑΡΑΠΛΗΣΙΕΣ ΠΕΡΙΠΤΩΣΕΙΣ ΤΟΥ ΕΡΓΟΥ

ΑΝΕΞΑΡΤΗΤΑ ΑΠΟ ΤΟ ΑΝ ΠΡΟΣΔΙΟΡΙΖΟΝΤΑΙ ΣΕ ΚΑΘΕ ΘΕΣΗ. ΝΑ

ΥΠΑΡΞΕΙ ΣΥΝΤΟΝΙΣΜΟΣ ΜΕ ΤΟΝ ΑΞΙΩΜΑΤΙΚΟ ΤΟΥ ΕΡΓΟΥ ΓΙΑ

ΔΙΕΥΚΡΙΝΗΣΗ ΤΗΣ ΕΦΑΡΜΟΓΗΣ ΤΗΣ ΤΥΠΙΚΗΣ ΛΕΠΤΟΜΕΡΕΙΑΣ.

10.9. VERIFY DIMENSIONS, ANCHORAGE LAYOUT/DETAILS, AND WEIGHTS OF

ACTUAL PURCHASED OR OWNER FURNISHED EQUIPMENT WITH

STRUCTURAL DETAILS SHOWN ON THE DRAWINGS. NOTIFY THE C.O. OF

DISCREPANCIES PRIOR TO FABRICATION OR INSTALLATION.

WHERE PURCHASED EQUIPMENT IS DIFFERENT THAN THAT USED IN

BASIS OF DESIGN, MODIFY CONCRETE PADS, MATS, FOUNDATIONS AND

STEEL SUPPORT FRAMING AS REQUIRED TO SUPPORT THE ACTUAL

PURCHASED EQUIPMENT AT NO ADDITIONAL COST TO THE

GOVERNMENT. SUBMIT SHOP DRAWINGS FOR MODIFICATIONS TO

THE C.O. FOR APPROVAL PRIOR TO FABRICATION OR ERECTION.

ΝΑ ΕΠΙΒΕΒΑΙΩΘΟΥΝ ΟΙ ΔΙΑΣΤΑΣΕΙΣ, Η ΔΙΑΤΑΞΗ ΚΑΙ ΛΕΠΤΟΜΕΡΕΙΕΣ

ΑΓΚΥΡΩΣΕΩΝ, ΤΟ ΒΑΡΟΣ ΤΟΥ ΥΠΑΡΧΩΝ ΕΞΟΠΛΙΣΜΟΥ ΠΟΥ ΑΓΟΡΑΣΤΗΚΕ

'Η ΕΙΝΑΙ ΙΔΙΟΚΤΗΤΟΣ ΜΕ ΤΑ ΣΧΕΔΙΑ ΣΤΑΤΙΚΩΝ ΛΕΠΤΟΜΕΡΕΙΩΝ. ΝΑ

ΕΝΗΜΕΡΩΘΕΙ Ο ΑΞΙΩΜΑΤΙΚΟΣ ΤΟΥ ΕΡΓΟΥ ΓΙΑ ΤΥΧΟΝ ΔΙΑΦΟΡΟΠΟΙΗΣΕΙΣ

ΠΡΙΝ ΤΗΝ ΣΥΝΑΡΜΟΛΟΓΗΣΗ ΚΑΙ ΤΗΝ ΕΓΚΑΤΑΣΤΑΣΗ. ΣΕ ΠΕΡΙΠΤΩΣΕΙΣ

ΠΟΥ Ο ΕΞΟΠΛΙΣΜΟΣ ΠΟΥ ΑΠΟΚΤΗΘΗΚΕ ΔΙΑΦΕΡΕΙ ΑΠΟ ΑΥΤΟΝ ΠΟΥ

ΑΝΑΓΡΑΦΕΤΑΙ ΣΤΗ ΒΑΣΗ ΣΧΕΔΙΑΣΜΟΥ, Ο ΕΡΓΟΛΑΒΟΣ ΘΑ ΠΡΕΠΕΙ ΝΑ

ΚΑΝΕΙ ΤΙΣ ΑΠΑΡΑΙΤΗΤΕΣ ΤΡΟΠΟΠΟΙΗΣΕΙΣ ΣΤΙΣ ΒΑΣΕΙΣ ΑΠΟ ΣΚΥΡΟΔΕΜΑ,

ΣΤΗ ΘΕΜΕΛΙΩΣΗ ΚΑΙ ΣΤΟ ΜΕΤΑΛΛΙΚΟ ΠΛΑΙΣΙΟ ΣΤΗΡΙΞΗΣ ΟΠΩΣ

ΑΠΑΙΤΕΙΤΑΙ ΩΣΤΕ ΝΑ ΕΠΑΡΚΕΙ ΧΩΡΙΣ ΕΠΙΠΛΕΟΝ ΕΠΙΒΑΡΥΝΣΗ

ΚΟΣΤΟΥΣ ΤΗΣ ΚΥΒΕΡΝΗΣΗΣ. ΝΑ ΚΑΤΑΤΕΘΟΥΝ ΤΑ ΚΑΤΑΣΚΕΥΑΣΤΙΚΑ

ΣΧΕΔΙΑ ΓΙΑ ΜΕΤΑΤΡΟΠΕΣ ΣΤΟΝ ΑΞΙΩΜΑΤΙΚΟ ΤΟΥ ΕΡΓΟΥ ΓΙΑ ΕΓΚΡΙΣΗ

ΠΡΙΝ ΤΗΝ ΣΥΝΑΡΜΟΛΟΓΗΣΗ Η' ΑΝΕΓΕΡΣΗ.

ΓΕΝΙΚΕΣ ΚΑΤΑΣΚΕΥΑΣΤΙΚΕΣ ΟΔΗΓΙΕΣ

20.0 FOUNDATIONS:

20.1. FOUNDATION DESIGN IS BASED ON FINAL GEOTECHNICAL EVALUATION

REPORT TITLED, "ENGINEERING SERVICES IN SUPPORT OF P-131

COMMUNICATION CENTER", DATED 06 AUGUST 2018, PREPARED BY MM

GROUP CONSULTING ENGINEERS, CONTRACT NUMBER:

N33191-17-D-0800 N3319118F4241.

Η ΜΕΛΕΤΗ ΘΕΜΕΛΙΩΣΗΣ ΕΙΝΑΙ ΒΑΣΙΣΜΕΝΗ ΣΕ ΤΕΛΙΚΗ ΓΕΩΤΕΧΝΙΚΗ

ΜΕΛΕΤΗ ΑΞΙΟΛΟΓΗΣΗΣ, ΜΕ ΤΙΤΛΟ «ΥΠΗΡΕΣΙΕΣ ΜΗΧΑΝΙΚΟΥ

ΣΥΝΔΡΑΜΟΝΤΑΣ ΤΟ ΕΡΓΟ P-131 ΚΕΝΤΡΟ ΕΠΙΚΟΙΝΙΩΝΙΩΝ», ΜΕ

ΗΜΕΡΟΜΗΝΙΑ 06 ΑΥΓΟΥΣΤΟΥ 2018, ΠΡΑΓΜΑΤΟΠΟΙΗΜΕΝΗ ΑΠΟ ΤΗΝ

ΕΤΑΙΡΕΙΑ MM GROUP ΣΥΜΒΟΥΛΟΙ ΜΗΧΑΝΙΚΟΙ, ΜΕ ΑΡΙΘΜΟ ΣΥΜΒΟΛΑΙΟΥ:

N33191-17-D-0800 N3319118F4241.

20.2. PRIOR TO FOUNDATION INSTALLATION, A 100mm THICK LAYER OF

LEAN CONCRETE MUST BE INSTALLED.

ΠΡΙΝ ΤΗΝ ΔΗΜΙΟΥΡΓΙΑ ΘΕΜΕΛΙΩΣΗΣ, ΝΑ ΣΧΗΜΑΤΙΣΤΕΙ 100mm

ΕΞΙΣΩΤΙΚΗ ΣΤΡΩΣΗ ΣΚΥΡΟΔΕΜΑΤΟΣ.

20.3. FOUNDATION BEARING SURFACES MUST BE OBSERVED BY A

GEOTECHNICAL ENGINEER, OR DESIGNEE, TO VERIFY

CONFORMANCE WITH THE CONTRACT DOCUMENTS AND

GEOTECHNICAL ENGINEERING REPORT. IN ADDITION, THE

GEOTECHNICAL REPORT RECOMMENDS THAT IF KARSTIC HOLES ARE

DETECTED DURING EXCAVATIONS, THE GEOTECHNICAL ENGINEER

MUST BE NOTIFIED FOR MITIGATION.

Η ΕΠΙΦΑΝΕΙΑ ΕΔΡΑΣΗΣ ΤΗΣ ΘΕΜΕΛΙΩΣΗΣ ΘΑ ΠΡΕΠΕΙ ΝΑ ΕΛΕΧΘΕΙ ΑΠΟ

ΓΕΩΤΕΧΝΙΚΟ ΜΗΧΑΝΙΚΟ ‘Η ΜΕΛΕΤΗΤΗ, ΠΡΟΚΕΙΜΕΝΟΥ ΝΑ ΕΠΙΒΕΒΑΙΩΣΕΙ

ΤΗ ΣΥΜΜΟΡΦΩΣΗ ΜΕ ΤΙΣ ΑΠΑΙΤΗΣΕΙΣ ΜΕ ΤΑ ΕΓΓΡΑΦΑ ΤΟΥ

ΣΥΜΒΟΛΑΙΟΥ, ΚΑΘΩΣ ΚΑΙ ΤΗ ΓΕΩΤΕΧΝΙΚΗ ΜΕΛΕΤΗ. ΕΠΙΠΡΟΣΘΕΤΩΣ, Η

ΓΕΩΤΕΧΝΙΚΗ ΜΕΛΕΤΗ ΣΥΣΤΗΝΕΙ ΟΤΙ ΣΕ ΠΕΡΙΠΤΩΣΗ ΠΟΥ ΕΝΤΟΠΙΣΤΟΥΝ

ΚΑΡΣΤΙΚΕΣ ΟΠΕΣ ΚΑΤΑ ΤΗ ΔΙΑΡΚΕΙΑ ΤΗΣ ΕΚΣΚΑΦΗΣ, Ο ΓΕΩΤΕΧΝΙΚΟΣ

ΜΗΧΑΝΙΚΟΣ ΘΑ ΠΡΕΠΕΙ ΝΑ ΕΝΗΜΕΡΩΘΕΙ ΠΡΟΣ ΑΝΤΙΜΕΤΩΠΙΣΗ ΤΟΥ

ΖΗΤΗΜΑΤΟΣ.

20.4. WALLS SHOWN RESTRAINED AT THE TOP MUST NOT BE BACKFILLED

UNTIL THE STRUCTURE PROVIDING RESTRAINT IS IN PLACE AND HAS

ATTAINED DESIGN STRENGTH. THE CONTRACTOR IS RESPONSIBLE

FOR TEMPORARY WALL BRACING WHEN BACKFILLING OCCURS

PRIOR TO CONSTRUCTION OF THE TOP RESTRAINT. NOTIFY THE C.O.

PRIOR TO PROCEDDING WITH RELATED WORK.

ΤΟΙΧΕΙΑ ΠΟΥ ΣΥΓΚΡΑΤΟΥΝΤΑΙ ΣΤΗΝ ΣΤΕΨΗ ΤΟΥΣ ΔΕ ΠΡΕΠΕΙ ΝΑ

ΕΠΙΧΩΜΑΤΩΝΟΝΤΑΙ ΕΩΣ ΟΤΟΥ Η ΚΑΤΑΣΚΕΥΗ ΠΟΥ ΤΑ ΣΥΓΚΡΑΤΕΙ

ΕΧΕΙ ΤΟΠΟΘΕΤΗΘΕΙ ΚΑΙ ΕΧΕΙ ΑΠΟΚΤΗΣΕΙ ΤΗΝ ΑΝΤΟΧΗ ΤΗΣ

ΣΧΕΔΙΑΣΗΣ.Ο ΕΡΓΟΛΑΒΟΣ ΕΙΝΑΙ ΥΠΕΥΘΥΝΟΣ ΝΑ ΠΑΡΕΧΕΙ ΤΥΧΟΝ

ΠΡΟΣΩΡΙΝΕΣ ΣΤΗΡΙΞΕΙΣ ΚΑΤΑ ΤΗΝ ΔΙΑΡΚΕΙΑ ΤΗΣ ΕΠΙΧΩΜΑΤΩΣΗΣ

ΠΡΙΝ ΤΗΝ ΚΑΤΑΣΚΕΥΗ ΤΟΥ ΣΤΟΙΧΕΙΟΥ ΣΥΓΚΡΑΤΗΣΗΣ ΣΤΗ ΣΤΕΨΗ.

ΝΑ ΕΝΗΜΕΡΩΘΕΙ Ο ΑΞΙΩΜΑΤΙΚΟΣ ΤΟΥ ΕΡΓΟΥ ΠΡΙΝ ΞΕΚΙΝΗΣΟΥΝ

ΣΧΕΤΙΚΕΣ ΕΡΓΑΣΙΕΣ.

20.5. BACKFILL MUST NOT BE PLACED BEHIND CANTILEVERED, FREE TOP

WALLS UNTIL THE CONCRETE HAS ATTAINED DESIGN STRENGTH.

ΣΤΟΥΣ ΤΟΙΧΟΥΣ ΑΝΤΙΣΤΗΡΙΞΗΣ Η ΕΠΙΧΩΜΑΤΩΣΗ ΝΑ ΜΗΝ ΓΙΝΕΤΑΙ ΕΩΣ

ΟΤΟΥ ΤΟ ΣΚΥΡΟΔΕΜΑ ΑΠΟΚΤΗΣΕΙ ΤΙΣ ΑΝΤΟΧΕΣ ΠΟΥ ΠΡΟΒΛΕΠΟΝΤΑΙ

ΣΤΗ ΜΕΛΕΤΗ.

20.6 ALL BUILDING FOUNDATIONS MUST BEAR ON NATIVE SOIL OR

ENGINEERED FILL. WHERE ROCK IS ENCOUNTERED OR VERIFIED BY

HAND PROBING WITHIN THE LIMITS OF THE FOUNDATIONS, THE ROCK

MUST BE OVER-EXCAVATED A MINIMUM OF 500mm BELOW THE

FOUNDATION BEARING ELEVATION AND BACKFILLED WITH

ENGINEERED FILL.

ΟΛΕΣ ΟΙ ΘΕΜΕΛΙΩΣΕΙΣ ΤΟΥ ΚΤΙΡΙΟΥ ΘΑ ΠΡΕΠΕΙ ΝΑ ΕΔΡΑΖΟΝΤΑΙ ΣΕ

ΕΓΓΕΝΕΣ ΕΔΑΦΟΣ ‘Η ΜΗΧΑΝΙΚΑ ΕΠΕΞΕΡΓΑΣΜΕΝΟ ΕΠΙΧΩΜΑ. ΟΠΟΥ

ΣΥΝΑΝΤΗΘΕΙ ΒΡΑΧΟΣ Ή ΔΙΑΠΙΣΤΩΘΕΙ Η ΥΠΑΡΞΗ ΤΟΥ ΑΠΟ

ΧΕΙΡΟΝΑΚΤΙΚΕΣ ΕΡΓΑΣΙΕΣ, ΘΑ ΠΡΕΠΕΙ ΝΑ ΕΚΣΚΑΦΕΙ ΤΟΥΛΑΧΙΣΤΟΝ ΓΙΑ

500ΜΜ ΚΑΤΩ ΑΠΟ ΤΟ ΕΠΙΠΕΔΟ ΕΠΑΦΗΣ ΜΕ ΤΟ ΕΔΑΦΟΣ ΤΗΣ

ΘΕΜΕΛΙΩΣΗΣ ΚΑΙ ΝΑ ΓΙΝΕΙ ΓΕΜΙΣΜΑ ΜΕ ΕΠΕΞΕΡΓΑΣΜΕΝΟ ΕΠΙΧΩΜΑ.

ΘΕΜΕΛΙΩΣΕΙΣ:

11.0 DIMENSIONS AND DATUM:

11.1. UNLESS NOTED OTHERWISE, BEAMS ARE EQUALLY SPACED BETWEEN

DIMENSIONS SHOWN.

ΕΚΤΟΣ ΚΑΙ ΑΝ ΥΠΑΡΧΕΙ ΕΙΔΙΚΗ ΑΝΑΦΟΡΑ, ΤΑ ΔΟΚΑΡΙΑ ΕΙΝΑΙ

ΙΣΟΚΑΤΑΝΕΜΗΜΕΝΑ ΜΕΤΑΞΥ ΤΩΝ ΑΝΑΓΡΑΦΟΜΕΝΩΝ ΔΙΑΣΤΑΣΕΩΝ.

11.2. COLUMNS, FOOTINGS, OR OTHER FOUNDATION ELEMENTS ARE

CENTERED ON GRID LINES, UNLESS NOTED OTHERWISE.

ΥΠΟΣΤΥΛΩΜΑΤΑ, ΠΕΔΙΛΑ Ή ΑΛΛΑ ΣΤΟΙΧΕΙΑ ΘΕΜΕΛΙΩΣΗΣ ΕΙΝΑΙ

ΚΕΝΤΡΑΡΙΣΜΕΝΑ ΣΤΙΣ ΓΡΑΜΜΕΣ ΤΟΥ ΚΑΝΝΑΒΟΥ, ΕΚΤΟΣ ΚΑΙ ΑΝ

ΥΠΑΡΧΕΙ ΕΙΔΙΚΗ ΑΝΑΦΟΡΑ.

11.3. DIMENSIONS SHOWN ARE TO THE CENTERLINE OF MEMBERS OR

FACE OF WALLS, UNLESS NOTED OTHERWISE

ΟΙ ΔΙΑΣΤΑΣΕΙΣ ΠΟΥ ΔΕΙΚΝΥΟΝΤΑΙ ΕΙΝΑΙ ΕΙΤΕ ΑΠΟ ΤΟΝ ΑΞΟΝΑ ΤΟΥ

ΣΤΟΙΧΕΙΟΥ ΕΙΤΕ ΑΠΟ ΤΗΝ ΠΑΡΕΙΑ ΤΟΥ ΤΟΙΧΟΥ, ΕΚΤΟΣ ΚΑΙ ΑΝ

ΥΠΑΡΧΕΙ ΕΙΔΙΚΗ ΑΝΑΦΟΡΑ.

11.4. ELEVATIONS ARE REFERENCED TO RELATIVE FINISH FLOOR

DATUM ELEVATION OF 10000mm. REFER TO THE CIVIL SITE PLAN

FOR ACTUAL FINISH FLOOR DATUM ELEVATION AND BUILDING

COORDINATE LOCATIONS.

ΟΛΑ ΤΑ ΥΨΟΜΕΤΡΑ ΑΝΑΦΕΡΟΝΤΑΙ ΣΤΟ ΕΠΙΠΕΔΟ ΑΝΑΦΟΡΑΣ

ΣΧΕΤΙΚΟΥ ΥΨΟΜΕΤΡΟΥ ΤΕΛΙΚΗΣ ΣΤΑΘΜΗΣ ΔΑΠΕΔΟΥ 10000mm.

ΒΛΕΠΕ ΣΧΕΔΙΑ ΟΡΙΖΟΝΤΙΟΓΡΑΦΙΑΣ ΠΟΛΙΤΙΚΟΥ ΜΗΧΑΝΙΚΟΥ ΓΙΑ

ΕΠΙΠΕΔΑ ΑΝΑΦΟΡΑΣ ΠΡΑΓΜΑΤΙΚΟΥ ΥΨΟΜΕΤΡΟΥ ΤΕΛΙΚΗΣ ΣΤΑΘΜΗΣ

ΔΑΠΕΔΟΥ ΚΑΙ ΘΕΣΕΙΣ ΣΥΝΤΕΤΑΓΜΕΝΩΝ ΚΤΙΡΙΟΥ.

ΔΙΑΣΤΑΣΕΙΣ ΚΑΙ ΔΕΔΟΜΕΝΑ

B

1 2 3 4 5

NONE

1615269

DWG

SHEET OF

NAVFAC DRAWING NO.

CONSTR. CONTR. NO.

EPROJECT NO.

SCALE:

N62470-21-C-0005

DESIGN DIRECTOR

BRANCH MANAGER

PM/DM

DES DRW CHK

SATISFACTORY TO DATE

ACTIVITY

FOR COMMANDER NAVFAC

APPROVED

A/E INFO

SEAL

SY

M

DE

SC

RI

PT

IO

N

DA

TE

AP

PR

N

AV

S U

PP

AC

T

SO

U D

A B

AY

N

AV

A L

FA

C

IL

IT

IE

S

EN

G

IN

E

ER

IN

G S

YS

TE

M C

O M

M

AN

D D

E P

AR

TM

E N

T O

F

TH

E N

A

VY

N

AV

AL

F

AC

IL

IT

IE

S E

N G

IN

EE

R

IN

G S

YS

TE

M C

O M

M

AN

D

A

FIRE PROTECTION

N O

R

FO

LK

, V

A A

TL

AN

TI

C

D E

SI

G

N A

N D

C O

N

ST

R U

C

TI

O N

1100 NORTH GLEBE ROAD

SUITE 500

ARLINGTON, VIRGINIA 22201

571.218.1000

FAX: 571.218.1600

D

C

B

A

1 2 3 4 5

RICHARD STEPHENS

TRUEWORTHY,PE / STELMASZEK,RA

PL

O

T

DA

TE

/T

IM

E:

7/

/ 2

3:

:3

PM

C

R ev it_ Lo ca l_

M od el s\

\P

1- D

1-

S_ R

_j oe

.th om as 1.

rv t

14 JUL 2021

RECEIVED BY JACOBIE TISDALE

AND STEVE PARK VIA EMAIL

S-003

LAP JT LPF

P

C

O M

M U

N

IC

A

TI

O N

C E

N

TE

RS

O

U D

A B

AY

, G

R

EE

C E

G

EN

ER

A

L

ST

R U

C

TU

R

AL

N O

TE

S

14089104

ΓΕ

Ν

ΙΚ

ΕΣ

ΚΑ

ΤΑ

ΣΚ

ΕΥ

Α

ΣΤ

ΙΚ

ΕΣ

Π

ΑΡ

Α

ΤΗ

Ρ Η

ΣΕ

ΙΣ

JTW

DPS

31.0 POST-INSTALLED ANCHORS:

31.1. INSTALLATION AND INSPECTION OF POST-INSTALLED ANCHORS MUST

CONFORM TO THE MANUFACTURER'S PUBLISHED INSTALLATION

INSTRUCTIONS, THE EQUIPMENT MANUFACTURER'S REQUIREMENTS, THE

REQUIREMENTS OF THE RESPECTIVE ICC-ES REPORT, AND THE APPLICABLE

BUILDING CODE OR EQUIVALENT EUROPEAN CERTIFICATION.

Η ΕΦΑΡΜΟΓΗ ΚΑΙ ΕΠΙΒΛΕΨΗ ΟΛΩΝ ΤΩΝ ΑΓΚΥΡΙΩΝ ΜΕΤΑ ΤΗΝ ΣΚΥΡΟΔΕΤΗΣΗ

ΠΡΕΠΕΙ ΝΑ ΓΙΝΕΤΑΙ ΣΥΜΦΩΝΑ ΜΕ ΤΙΣ ΟΔΗΓΙΕΣ ΠΟΥ ΕΧΕΙ ΔΗΜΟΣΙΕΥΣΕΙ Ο

ΚΑΤΑΣΚΕΥΑΣΤΗΣ, ΤΙΣ ΑΠΑΙΤΗΣΕΙΣ ΤΟΥ ΚΑΤΑΣΚΕΥΑΣΤΗ, ΤΙΣ ΑΠΑΙΤΗΣΕΙΣ ΤΗΣ

ΕΚΘΕΣΗ ICC-ES ΚΑΙ ΤΟΥ ΑΝΤΙΣΤΟΙΧΟΥ ΟΙΚΟΔΟΜΙΚΟΥ ΚΑΝΟΝΙΣΜΟΥ Η' ΤΗΣ

ΑΝΤΙΣΤΟΙΧΗ ΕΥΡΩΠΑΙΚΗΣ ΠΙΣΤΟΠΟΙΗΣΗΣ.

31.2. A MANUFACTURER'S TECHNICAL REPRESENTATIVE (NOT A DISTRIBUTOR OR

AGENT) MUST TRAIN INSTALLERS ON THE INSTALLATION

PROCEDURES AND MUST OBSERVE INITIAL INSTALLATION OF THE ANCHORS.

ΕΝΑΣ ΤΕΧΝΙΚΟΣ ΑΝΤΙΠΡΟΣΩΠΟΣ ΤΟΥ ΚΑΤΑΣΚΕΥΑΣΤΗ (ΟΧΙ ΑΠΛΑ ΕΜΠΟΡΙΚΟΣ

ΑΝΤΙΠΡΟΣΩΠΟΣ Η' ΣΤΕΛΕΧΟΣ) ΠΡΕΠΕΙ ΝΑ ΕΚΠΑΙΔΕΥΣΕΙ ΤΑ ΑΤΟΜΑ ΠΟΥ ΘΑ

ΚΑΝΟΥΝ ΤΗΝ ΕΓΚΑΤΑΣΤΑΣΗ ΣΤΙΣ ΟΡΘΕΣ ΜΕΘΟΔΟΛΟΓΙΕΣ ΕΦΑΡΜΟΓΗΣ ΚΑΙ ΝΑ

ΕΠΙΒΛΕΨΕΙ ΤΙΣ ΑΡΧΙΚΕΣ ΕΦΑΡΜΟΓΕΣ ΑΓΚΥΡΙΩΝ.

31.3. ADHESIVE ANCHORING SYSTEMS IN CONCRETE MUST CONFORM TO AN

APPLICABLE ICC-ES REPORT OR EQUIVALENT EUROPEAN CERTIFICATION AND

REQUIRE CONTINUOUS INSPECTION DURING INSTALLATION.

ΤΑ ΧΗΜΙΚΑ ΣΥΣΤΗΜΑΤΑ ΑΓΚΥΡΩΣΗΣ ΣΕ ΣΚΥΡΟΔΕΜΑ ΠΡΕΠΕΙ ΝΑ

ΣΥΜΜΟΡΦΩΝΟΝΤΑΙ ΜΕ ΤΗΝ ΕΚΘΕΣΗ ICC-ES Η' ΑΝΤΙΣΤΟΙΧΗ ΕΥΡΩΠΑΙΚΗ

ΠΙΣΤΟΠΟΙΗΣΗ ΚΑΙ ΑΠΑΙΤΕΙΤΑΙ Η ΣΥΝΕΧΗΣ ΕΠΙΒΛΕΨΗ ΚΑΤΑ ΤΗΝ ΔΙΑΡΚΕΙΑ ΤΗΣ

ΕΦΑΡΜΟΓΗΣ ΤΟΥΣ.

31.4. MECHANICAL ANCHORING SYSTEMS IN CONCRETE MUST CONFORM TO AN

APPLICABLE ICC-ES REPORT OR EQUIVALENT EUROPEAN CERTIFICATION.

ΤΑ ΜΗΧΑΝΙΚΑ ΣΥΣΤΗΜΑΤΑ ΑΓΚΥΡΩΣΗΣ ΣΕ ΣΚΥΡΟΔΕΜΑ ΠΡΕΠΕΙ ΝΑ

ΣΥΜΜΟΡΦΩΝΟΝΤΑΙ ΜΕ ΤΗΝ ΕΚΘΕΣΗ ICC-ES Η' ΑΝΤΙΣΤΟΙΧΗ ΕΥΡΩΠΑΙΚΗ

ΠΙΣΤΟΠΟΙΗΣΗ.

31.5. ANCHOR RODS USED IN ADHESIVE ANCHORING SYSTEMS MUST CONFORM WITH

EUROCODE 3 - EN 1993; DESIGN OF STEEL STRUCTURES. MECHANICAL

ANCHORING SYSTEMS MUST BE ZINC PLATED CARBON STEEL, UNLESS NOTED

OTHERWISE.

OI ΡΑΒΔΟΙ ΑΓΚΥΡΩΣΗΣ ΠΟΥ ΧΡΗΣΙΜΟΠΟΙΟΥΝΤΑΙ ΣΤΟ ΧΗΜΙΚΟ ΣΥΣΤΗΜΑ

ΑΓΚΥΡΩΣΗΣ ΠΡΕΠΕΙ ΝΑ ΣΥΜΜΟΡΦΩΝΟΝΤΑΙ ΜΕ ΤΟΝ ΕΥΡΟΚΩΔΙΚΑ 3 - ΕΝ 1993:

ΣΧΕΔΙΑΣΜΟΣ ΚΑΤΑΣΚΕΥΩΝ ΑΠΟ ΧΑΛΥΒΑ. ΤΑ ΜΗΧΑΝΙΚΑ ΑΓΚΥΡΙΑ ΠΡΕΠΕΙ ΝΑ

ΕΧΟΥΝ ΠΡΟΣΤΑΤΕΥΡΙΚΗ ΣΤΡΩΣΗ ΨΕΥΔΑΡΓΥΡΟΥ ΕΚΤΟΣ ΚΑΙ ΑΝ ΥΠΑΡΧΕΙ ΕΙΔΙΚΗ

ΑΝΑΦΟΡΑ.

31.6. MINIMUM EMBEDMENT DEPTHS AND ULTIMATE DESIGN VALUES ARE INDICATED

IN THE FOLLOWING SCHEDULES, UNLESS NOTED OTHERWISE IN A SPECIFIC

SECTION OR DETAIL.

ΤΟ ΕΛΑΧΙΣΤΟ ΒΑΘΟΣ ΕΝΣΩΜΑΤΩΣΗΣ ΚΑΙ ΟΡΙΑΚΕΣ ΤΑΣΕΙΣ ΣΧΕΔΙΑΣΜΟΥ

ΔΕΙΚΝΥΟΝΤΑΙ ΣΤΟΥΣ ΠΑΡΑΚΑΤΩ ΠΙΝΑΚΕΣ ΕΚΤΟΣ ΚΑΙ ΑΝ ΥΠΑΡΧΕΙ ΕΙΔΙΚΗ

ΑΝΑΦΟΡΑ.

ADHESIVE ANCHORS

THREADED ANCHOR

DIAMETER

12mm

EMBEDMENT

16mm

20mm

22mm

25mm

115mm

145mm

175mm

200mm

230mm

MECHANICAL ANCHORS

ANCHOR DIAMETER

12mm

EMBEDMENT

16mm

20mm

90mm

115mm

145mm

ULTIMATE DESIGN

SHEAR CAPACITY *

ULTIMATE DESIGN

TENSION CAPACITY *

ULTIMATE DESIGN

SHEAR CAPACITY *

ULTIMATE DESIGN

TENSION CAPACITY *

* THE VALUES LISTED ARE THE MINIMUM CAPACITIES FOR A SINGLE ANCHOR

WITHOUT REDUCTIONS TAKEN FOR EDGE DISTANCE AND ANCHOR SPACING.

DETAILS INDICATE CRITICAL DIMENSIONS WHICH MUST COMPLY WITH ANCHOR

SYSTEM ICC-ES REPORT, OR EQUIVALENT EUROPEAN CERTIFICATION.

*ΟΙ ΑΝΑΓΡΑΦΟΜΕΝΕΣ ΤΙΜΕΣ ΠΕΡΙΓΡΑΦΟΥΝ ΤΗΝ ΕΛΑΧΙΣΤΗ ΙΚΑΝΟΤΗΤΑ ΜΙΑΣ ΑΓΚΥΡΩΣΗΣ

ΧΩΡΙΣ ΤΗΝ ΑΠΟΜΕΙΩΣΗ ΛΟΓΟ ΑΠΟΣΤΑΣΗΣ ΑΠΟ ΤΟ ΑΚΡΟ Η' ΛΟΓΟ ΔΙΑΤΑΞΗΣ ΑΓΚΥΡΙΩΝ.

ΟΙ ΛΕΠΤΟΜΕΡΕΙΕΣ ΔΕΙΚΝΥΟΥΝ ΚΡΙΣΙΜΕΣ ΔΙΑΣΤΑΣΕΙΣ ΟΙ ΟΠΟΙΕΣ ΠΡΕΠΕΙ ΝΑ

ΣΥΜΜΟΡΦΩΝΟΝΤΑΙ ΜΕ ΤΗΝ ΕΚΘΕΣΗ ICC-ES, Η' ΑΝΤΙΣΤΟΙΧΗ ΕΥΡΩΠΑΙΚΗ ΠΙΣΤΟΠΟΙΗΣΗ.

ΕΦΑΡΜΟΓΗ ΑΓΚΥΡΙΩΝ ΜΕΤΑ ΤΗΝ ΣΚΥΡΟΔΕΤΗΣΗ

ΧΗΜΙΚΑ ΑΓΚΥΡΙΑ

ΔΙΑΜΕΤΡΟΣ ΚΟΧΛΙΑ

ΑΓΚΥΡΩΣΗΣ

ΟΡΙΑΚΗ ΤΑΣΗ

ΔΙΑΤΜΗΣΗΣ

ΟΡΙΑΚΗ ΤΑΣΗ

ΕΦΕΛΚΥΣΜΟΥ

ΒΑΘΟΣ

ΕΝΣΩΜΑΤΩΣΗΣ

ΔΙΑΜΕΤΡΟΣ

ΑΓΚΥΡΙΟΥ

ΟΡΙΑΚΗ ΤΑΣΗ

ΔΙΑΤΜΗΣΗΣ

ΟΡΙΑΚΗ ΤΑΣΗ

ΕΦΕΛΚΥΣΜΟΥ

ΒΑΘΟΣ

ΕΝΣΩΜΑΤΩΣΗΣ

ΜΗΧΑΝΙΚΑ ΑΓΚΥΡΙΑ

14kN

22kN

32kN

54kN

58kN

20kN

32kN

46kN

53kN

69kN

16kN

22kN

34kN

18kN

25kN

32kN

52.0 COMPOSITE STEEL DECK:

52.1. COMPOSITE STEEL DECK MUST BE DETAILED, FABRICATED, AND

ERECTED IN ACCORDANCE WITH THE FOLLOWING, UNLESS OTHERWISE

SPECIFIED:

ΟΛΑ ΤΑ ΣΥΜΜΕΙΚΤΑ ΔΑΠΕΔΑ ΠΡΕΠΕΙ ΝΑ ΣΧΕΔΙΑΣΤΟΥΝ, ΚΑΤΑΣΚΕΥΑΣΤΟΥΝ ΚΑΙ ΝΑ

ΑΝΕΓΕΡΘΟΥΝ ΣΥΜΦΩΝΑ ΜΕ ΤΑ ΠΑΡΑΚΑΤΩ, ΕΚΤΟΣ ΚΑΙ ΑΝ ΥΠΑΡΧΕΙ ΕΙΔΙΚΗ

ΑΝΑΦΟΡΑ

EUROCODE 3 -EN 1993; DESIGN OF STEEL STRUCTURES

ΕΥΡΩΚΩΔΙΚΑΣ 3 - ΕΝ 1993; ΣΧΕΔΙΑΣΜΟΣ ΚΑΤΑΣΚΕΥΩΝ ΑΠΟ ΧΑΛΥΒΑ

52.2. MINIMUM COMPOSITE STEEL DECK PROPERTIES:

ΕΛΑΧΙΣΤΕΣ ΤΙΜΕΣ ΣΤΗΣ ΙΔΙΟΤΗΤΕΣ ΤΩΝ ΣΥΜΜΕΙΚΤΩΝ ΔΑΠΕΔΩΝ.

DEPTH ---------------------------------------------------------------------------- 73 mm

ΥΨΟΣ

THICKNESS --------------------------------------------------------------------- 0.8 mm

ΠΑΧΟΣ

MINIMUM YIELD STRENGTH ---------------------------------------------- S275

ΕΛΑΧΙΣΤΟ ΟΡΙΟ ΕΛΑΣΤΙΚΟΤΗΤΑΣ

SECOND MOMENT OF INTERIA ----------------------------------------- 117.33 cm4/m

ΡΟΠΗ ΑΔΡΑΝΕΙΑΣ ΕΠΙΦΑΝΕΙΑΣ

SECTION MODULUS ---------------------------------------------------------- 29.48 cm3/m

ΡΟΠΗ ΑΝΤΙΣΤΑΣΗΣ

CROSS SECTION AREA ----------------------------------------------------- 13.533 cm2/m

ΕΠΙΦΑΝΕΙΑ ΔΙΑΤΟΜΗΣ

FINISH ----------------------------------------------------------------------------- HOT DIP ZINC COATED

ΤΕΛΕΙΩΜΑ STEEL TO BS EN 10346

S280GD+Z275

ΧΑΛΥΒΑΣ ΜΕ ΕΠΙΣΤΡΩΣΗ

ΨΕΥΔΑΡΓΥΡΟΥ ΕΝ ΘΕΡΜΩ

ΣΥΜΦΩΝΑ ΜΕ BS ΕΝ10346

S280GD+Z275

52.3. COMPOSITE STEEL DECK ATTACHMENT:

ΣΥΝΔΕΣΗ ΣΥΜΜΕΙΚΤΟΥ ΜΕΤΑΛΛΙΚΟΥ ΔΑΠΕΔΟΥ

ALLOWABLE SUPPORT FASTENERS INCLUDE:

ΣΤΑ ΕΠΙΤΡΕΠΟΜΕΝΑ ΣΤΟΙΧΕΙΑ ΣΤΗΡΙΞΗΣ ΠΕΡΙΕΧΟΝΤΑΙ:

a) MINIMUM VISIBLE 16mm DIAMETER ARC PUDDLE WELDS ΣΥΓΚΟΛΛΗΣΗ ΜΕ ΑΝΑΔΕΥΣΗ ΕΛΑΧΙΣΤΗΣ ΕΜΦΑΝΗΣ ΔΙΑΜΕΤΡΟΥ 16mm

b) SHEAR STUD CONNECTORS WELDED THROUGH THE COMPOSITE STEEL DECK WITH A MINIMUM CLEARANCE OF 25mm FROM EDGE OF DECK TO

STUD CENTERLINE

ΟΙ ΣΥΝΔΕΣΜΟΙ ΔΙΑΤΜΗΣΗΣ ΝΑ ΕΙΝΑΙ ΗΛΕΚΤΡΟΣΥΓΚΟΛΛΗΜΕΝΟΙ ΣΤΟ

ΣΥΜΜΕΙΚΤΟ ΔΑΠΕΔΟ ΜΕ ΕΛΑΧΙΣΤΗ ΑΠΟΣΤΑΣΗ 25mm ΑΠΟ ΤΟ ΑΚΡΟ ΤΟΥ

ΔΑΠΕΔΟΥ ΣΤΟΝ ΑΞΟΝΑ ΤΟΥ ΣΥΝΔΕΣΜΟΥ.

SUPPORTS -------------------------------------------------------------------- 4 PER 900mm

ΣΤΗΡΙΞΕΙΣ

SUPPORTS PARALLEL TO DECK ------------------------------------- 300mm MAXIMUM

ΣΤΗΡΙΞΕΙΣ ΠΑΡΑΛΛΗΛΕΣ ΣΤΟ ΔΑΠΕΔΟ

SIDELAPS ---------------------------------------------------------------------- 5mm SCREWS OR

ΠΛΕΥΡΙΚΗ ΑΛΛΗΛΟΚΑΛΥΨΗ CRIMP/BUTTON PUNCHES

@ 900mm MAXIMUM 5mm ΒΙΔΕΣ Η'

ΦΛΑΝΤΖΑ ΣΥΝΔΕΣΗΣ

ΑΝΑ 900mm ΜΕΓΙΣΤΟ

52.4. DECK MUST BE CONTINUOUS OVER TWO OR MORE SPANS. FOR CONDITIONS

WITH LESS THAN TWO SPANS, SHORE THE DECK IN ACCORDANCE WITH THE

MANUFACTURER'S SPAN REQUIREMENTS.

ΤΟ ΔΑΠΕΔΟ ΠΡΕΠΕΙ ΝΑ ΕΙΝΑΙ ΣΥΝΕΧΕΣ ΓΙΑ ΤΟΥΛΑΧΙΣΤΩΝ ΔΥΟ ΣΤΗΡΙΞΕΙΣ . ΣΕ

ΠΕΡΙΠΤΩΣΗ ΠΟΥ ΔΕ ΜΠΟΡΕΙ ΝΑ ΕΠΙΤΕΥΧΘΕΙ, ΝΑ ΓΙΝΟΥΝ ΟΙ ΑΠΑΡΑΙΤΗΤΕΣ

ΣΥΝΔΕΣΕΙΣ ΣΥΜΦΩΝΑ ΜΕ ΤΙΣ ΑΠΑΙΤΗΣΕΙΣ ΤΟΥ ΚΑΤΑΣΚΕΥΑΣΤΗ.

52.5. SHEETS MUST HAVE LAPPED ENDS. MINIMUM LAP IS 50mm.

ΤΑ ΦΥΛΛΑ ΠΡΕΠΕΙ ΝΑ ΕΧΟΥΝ ΑΛΛΗΛΟΚΑΛΥΨΗ ΣΤΑ ΑΚΡΑ ΤΟΥΣ. Η ΕΛΑΧΙΣΤΗ

ΑΛΛΗΛΟΚΑΛΥΨΗ ΕΙΝΑΙ 50mm.

52.6. MINIMUM DECK BEARING IS 50mm ON SUPPORTS.

ΕΛΑΧΙΣΤΟ ΠΑΤΗΜΑ ΔΑΠΕΔΟΥ 50mm ΣΤΙΣ ΣΤΗΡΙΞΕΙΣ.

52.7. CONCRETE WITH CALCIUM CHLORIDE OR ANY ADMIXTURE CONTAINING

CHLORIDES MUST NOT BE USED WITH COMPOSITE STEEL DECK.

ΣΚΥΡΟΔΕΜΑ ΜΕ ΧΛΩΡΙΟΥΧΟ ΑΣΒΕΣΤΙΟ Η' ΆΛΛΟ ΠΡΟΣΘΕΤΟ ΠΟΥ ΠΕΡΙΕΧΕΙ

ΧΛΩΡΙΟΝΤΑ ΔΕ ΠΡΕΠΕΙ ΝΑ ΧΡΗΣΙΜΟΠΟΙΕΙΤΕ ΣΤΑ ΣΥΜΜΕΙΚΤΑ ΔΑΠΕΔΑ.

52.8. THE FIRST SHEET OF STEEL DECK ADJACENT AND PARALLEL TO WALLS,

PERIMETER MEMBERS OR MEMBERS IDENTIFIED AS CHORD, COLLECTOR OR

DRAG MEMBERS (ON ONE OR BOTH SIDES AS APPLICABLE) MUST BE FULL PANEL

WIDTH SHEETS.

ΤΟ ΠΡΩΤΟ ΦΥΛΛΟ ΤΟΥ ΣΥΜΜΕΙΚΤΟΥ ΔΑΠΕΔΟΥ ΠΑΡΑΚΕΙΜΕΝΟ ΚΑΙ ΠΑΡΑΛΛΗΛΟ ΣΕ

ΤΟΙΧΟ, ΣΤΟΙΧΕΙΑ ΤΗΣ ΠΕΡΙΜΕΤΡΟΥ Ή ΣΤΟΙΧΕΙΑ ΠΟΥ ΟΡΙΖΟΝΤΑΙ ΩΣ ΧΟΡΔΕΣ, ΜΕΛΗ

ΣΤΗΡΙΞΗΣ Ή ΑΝΤΙΡΙΔΕΣ (ΣΤΗ ΜΙΑ 'Η ΚΑΙ ΣΤΙΣ ΔΥΟ ΠΛΕΥΡΕΣ ΑΝΑΛΟΓΩΣ) ΟΦΕΙΛΟΥΝ

ΝΑ ΕΙΝΑΙ ΑΚΕΡΑΙΑ ΤΕΜΑΧΙΑ ΦΥΛΛΟΥ.

52.9. WELDING MUST BE PERFORMED BY WELDERS EXPERIENCED IN COLD-FORMED

STEEL DECK WORK. WELDING MUST CONFORM TO ELOT EN 287-1.

ΟΛΕΣ ΟΙ ΣΥΓΚΟΛΛΗΣΕΙΣ ΠΡΕΠΕΙ ΝΑ ΠΡΑΓΜΑΤΟΠΟΙΟΥΝΤΑΙ ΑΠΟ ΤΕΧΝΙΤΕΣ ΜΕ

ΕΜΠΕΙΡΙΑ ΣΕ ΕΡΓΑΣΙΕΣ ΣΕ ΔΑΠΕΔΑ ΨΥΧΡΗΣ ΕΛΑΣΗΣ. ΟΛΕΣ ΟΙ ΣΥΓΚΟΛΛΗΣΕΙΣ

ΠΡΕΠΕΙ ΝΑ ΓΙΝΟΝΤΑΙ ΣΥΜΦΩΝΑ ΜΕ ΕΛΟΤ ΕΝ 287-1.

ΣΥΜΜΕΙΚΤΟ ΔΑΠΕΔΟ ΧΑΛΥΒΑ

50.0 STRUCTURAL STEEL:

50.1. STRUCTURAL STEEL MUST BE DETAILED, FABRICATED, AND

ERECTED IN ACCORDANCE WITH:

EUROCODE 3 - EN 1993/GREEK NATIONAL ANNEX, DESIGN OF STEEL

STRUCTURES.

GREEK CODE FOR STEEL TECHNOLOY (G.G. 1416B/17.07.08 AND G.G.

2113B/13.10.08)

Ο ΚΑΤΑΣΚΕΥΑΣΤΙΚΟΣ ΧΑΛΥΒΑΣ ΠΡΕΠΕΙ ΝΑ ΕΧΕΙ ΣΧΕΔΙΑΣΤΕΙ,

ΚΑΤΑΣΚΕΥΑΣΤΕΙ ΚΑΙ ΑΝΕΓΕΡΘΕΙ ΣΥΜΦΩΝΑ ΜΕ:

ΕΥΡΩΚΩΔΙΚΑ 3 - ΕΝ 1993/ ΕΛΛΗΝΙΚΟ ΕΘΝΙΚΟ ΠΡΟΣΑΡΤΗΜΑ,

ΣΧΕΔΙΑΣΜΟΣ ΚΑΤΑΣΚΕΥΩΝ ΑΠΟ ΧΑΛΥΒΑ.

ΕΛΛΗΝΙΚΟ ΚΑΝΟΝΙΣΜΟ ΤΕΧΝΟΛΟΓΙΑΣ ΧΑΛΥΒΩΝ (ΦΕΚ 1416B/17.07.08

ΚΑΙ ΦΕΚ 2113B/13.10.08)

50.2. STRUCTURAL SHAPES AND PLATES:

ΔΟΜΙΚΟΣ ΜΟΡΦΟΣΙΔΗΡΟΣ ΚΑΙ ΕΛΑΣΜΑΤΑ

CLASS Fe430 (S275) Fy = 27.5 kN/cm2; Fu = 43 kN/cm2

ΚΑΤΗΓΟΡΙΑ ΧΑΛΥΒΑ S275 Fy = 27.5 kN/cm2; Fu = 43 kN/cm2

50.3. TIGHTEN BOLTS TO THE SNUG-TIGHT OR PRE-TENSIONED

CONDITION, EXCEPT WHERE INDICATED AS SLIP CRITICAL (SC).

SLIP-CRITICAL CONNECTIONS MUST BE FULLY PRE-TENSIONED AND

INSPECTED USING TENSION-CONTROL BOLT ASSEMBLIES, DIRECT-

TENSION INDICATORS, OR BY THE TURN-OF-THE-NUT METHOD

CONFORMING TO RCSC. SLIP-CRITICAL CONNECTIONS MUST

HAVE FAYING SURFACES PREPARED FOR SLIP-CRITICAL CLASS A.

ΝΑ ΣΦΙΞΟΥΝ ΟΙ ΒΙΔΕΣ ΣΕ ΚΑΤΑΣΤΑΣΗ ΠΡΟΕΝΤΑΣΗΣ, ΕΚΤΟΣ ΚΑΙ ΑΝ

ΑΝΑΦΕΡΕΤΑΙ ΩΣ ΚΡΙΣΙΜΗ Η ΟΛΙΣΘΗΣΗ (SC). ΟΛΕΣ ΟΙ ΣΥΝΔΕΣΕΙΣ ΜΕ

ΚΡΙΣΙΜΗ ΤΗΝ ΟΛΙΣΘΗΣΗ ΠΡΕΠΕΙ ΝΑ ΕΙΝΑΙ ΠΛΗΡΩΣ ΠΡΟΕΝΤΕΤΑΜΕΝΕΣ

ΚΑΙ ΝΑ ΕΠΙΘΕΩΡΟΥΝΤΑΙ ΧΡΗΣΙΜΟΠΟΙΩΝΤΑΣ ΣΥΣΤΗΜΑΤΑ

ΜΠΟΥΛΟΝΙΩΝ ΕΛΕΓΧΟΥ ΕΝΤΑΣΗΣ, ΔΕΙΚΤΕΣ ΑΜΕΣΗΣ ΤΑΣΗΣ, Ή ΤΗ

ΜΕΘΟΔΟ ΠΕΡΙΣΤΡΟΦΗΣ ΠΕΡΙΚΟΧΛΙΟΥ ΣΥΜΦΩΝΑ ΜΕ ΤΟ RCSC. ΟΛΕΣ

ΟΙ ΣΥΝΔΕΣΕΙΣ ΜΕ ΚΡΙΣΙΜΗ ΤΗΝ ΟΛΙΣΘΗΣΗ ΠΡΕΠΕΙ ΝΑ ΕΧΟΥΝ

ΚΑΤΑΛΛΗΛΕΣ ΕΠΙΦΑΝΕΙΣ ΠΡΟΕΤΟΙΜΑΣΜΕΝΕΣ ΓΙΑ ΚΡΙΣΙΜΗ ΟΛΙΣΘΗΣΗ

ΚΛΑΣΗΣ Α.

50.4. WELDING OF STRUCTURAL STEEL MUST CONFORM TO ELOT

EN 287-1 AND PERFORMED BY QUALIFIED WELDERS IN

FABRICATION FACILITIES.

ΟΛΕΣ ΟΙ ΣΥΓΚΟΛΛΗΣΕΙΣ ΔΟΜΙΚΟΥ ΧΑΛΥΒΑ ΠΡΕΠΕΙ ΝΑ

ΣΥΜΜΟΡΦΏΝΟΝΤΑΙ ΜΕ ΤΟΝ ΕΛΟΤ EN 287-1 ΚΑΙ ΝΑ ΥΛΟΠΟΙΟΥΝΤΑΙ

ΑΠΟ ΠΙΣΤΟΠΟΙΗΜΕΝΟΥΣ ΗΛΕΚΤΡΟΣΥΓΚΟΛΛΗΤΕΣ ΣΕ ΕΓΚΑΤΑΣΤΑΣΕΙΣ

ΠΑΡΑΓΩΓΗΣ

50.5. UNLESS NOTED OTHERWISE, FILLET WELD SIZES MUST BE 5mm

MINIMUM THICKNESS.

ΕΚΤΟΣ ΑΝ ΑΝΑΦΕΡΕΤΑΙ ΔΙΑΦΟΡΕΤΙΚΑ, ΟΙ ΡΑΦΗ

ΗΛΕΚΤΡΟΣΥΓΚΟΛΛΗΣΗΣ ΠΡΕΠΕΙ ΝΑ ΕΧΕΙ ΚΑΤ΄ ΕΛΑΧΙΣΤΟΝ 5mm

ΠΑΧΟΣ.

50.6. BEAMS MUST BE ERECTED WITH THE NATURAL CAMBER

UPWARDS.

ΟΛΑ ΤΑ ΔΟΚΑΡΙΑ ΠΡΕΠΕΙ ΝΑ ΤΟΠΟΘΕΤΗΘΟΥΝ ΜΕ ΤΟ ΦΥΣΙΚΟ ΒΕΛΟΣ

ΠΡΟΣ ΤΑ ΠΑΝΩ.

50.7. OPEN ENDS OF TUBE OR PIPE MEMBERS MUST HAVE 6mm

CLOSURE PLATES, SEAL WELDED ALL AROUND.

ΣΤΑ ΑΝΟΙΧΤΑ ΑΚΡΑ ΣΩΛΗΝΩΝ Ή ΑΓΩΓΩΝ ΠΡΕΠΕΙ ΝΑ ΤΟΠΟΘΕΤΕΙΤΑΙ

ΕΛΑΣΜΑ 6mm ΚΑΙ ΝΑ ΣΤΕΓΑΝΟΠΟΙOYNΤΑΙ ΜΕ ΗΛΕΚΤΡΟΣΥΓΚΟΛΗΣΗ

ΠΕΡΙΜΕΤΡΙΚΑ.

50.8. HOLES OR OPENINGS MUST NOT BE CUT IN STRUCTURAL

MEMBERS UNLESS SPECIFICALLY DETAILED OR APPROVED IN

WRITING BY THE C.O.

ΟΠΕΣ ΚΑΙ ΑΝΟΙΓΜΑΤΑ ΔΕΝ ΠΡΕΠΕΙ ΝΑ ΔΗΜΙΟΥΡΓΟΥΝΤΑΙ ΣΕ ΔΟΜΙΚΑ

ΣΤΟΙΧΕΙΑ ΕΚΤΟΣ ΚΑΙ ΑΝ ΠΡΟΒΛΕΠΕΤΑΙ ΑΠΟ ΤΑ ΣΧΕΔΙΑ

ΛΕΠΤΟΜΕΡΕΙΩΝ Η' ΔΟΘΕΙ ΕΓΚΡΙΣΗ ΓΡΑΠΤΩΣ ΑΠΟ ΤΟΝ ΑΞΙΩΜΑΤΙΚΟ

ΤΟΥ ΕΡΓΟΥ.

50.9. PROVIDE TEMPORARY GUYING AND BRACING NECESSARY TO

ERECT, STABILIZE, AND MAINTAIN STEEL MEMBERS IN ALIGNMENT

UNTIL DECK, PERMANENT BRACING, FLOOR SLABS,

CONNECTIONS, ETC. ARE IN PLACE. COLUMN ANCHOR BOLTS ARE

NOT DESIGNED TO PROVIDE TEMPORARY STABILITY FOR COLUMNS

DURING STEEL ERECTION. PLACE NON-SHRINK GROUT BELOW

COLUMN BASE PLATES BEFORE POURING CONCRETE ON DECKS OR

APPLYING LOAD TO THE STRUCTURE.

ΝΑ ΤΟΠΟΘΕΤΗΘΟΥΝ ΤΑ ΑΠΑΡΑΙΤΗΤΑ ΠΡΟΣΩΡΙΝΑ ΣΤΗΡΙΓΜΑΤΑ ΚΑΙ

ΣΥΝΔΕΣΕΙΣ ΓΙΑ ΤΗΝ ΑΝΕΓΕΡΣΗ, ΣΤΑΘΕΡΟΠΟΙΗΣΗ ΚΑΙ ΟΡΘΗ

ΕΥΘΥΓΡΑΜΜΙΣΗ ΤΗΣ ΜΕΤΑΛΛΙΚΗΣ ΚΑΤΑΣΚΕΥΗΣ ΕΩΣ ΤΗΝ

ΟΛΟΚΛΗΡΩΣΗ ΤΩΝ ΔΑΠΕΔΩΝ, ΤΩΝ ΜΟΝΙΜΩΝ ΣΤΗΡΙΞΕΩΝ, ΤΩΝ

ΠΛΑΚΩΝ, ΤΩΝ ΣΥΝΔΕΣΕΩΝ ΚΤΛ. ΤΑ ΑΓΚΥΡΙΑ ΤΩΝ ΥΠΟΣΤΥΛΩΜΑΤΩΝ

ΔΕΝ ΕΙΝΑΙ ΣΧΕΔΙΑΣΜΕΝΑ ΩΣΤΕ NA ΠΑΡΕΧΟΥΝ ΠΡΟΣΩΡΙΝΗ

ΣΤΑΘΕΡΟΤΗΤΑ ΤΩΝ ΥΠΟΣΤΥΛΩΜΑΤΩΝ ΚΑΤΑ ΤΗΝ ΔΙΑΡΚΕΙΑ ΤΗΝ

ΑΝΕΓΕΡΣΗΣ ΤΗΣ ΜΕΤΑΛΛΙΚΗΣ ΚΑΤΑΣΚΕΥΗΣ. ΝΑ ΤΟΠΟΘΕΤΗΘΕΙ ΜΗ

ΣΥΡΡΙΚΝΟΥΜΕΝΟ ΕΝΕΜΑ ΚΑΤΩ ΑΠΟ ΤΑ ΥΠΟΣΤΥΛΩΜΑΤΑ ΤΩΝ ΠΛΑΚΩΝ

ΕΔΡΑΣΗΣ ΠΡΙΝ ΤΗΝ ΣΚΥΡΟΔΕΤΗΣΗ ΤΩΝ ΔΑΠΕΔΩΝ 'Η ΤΗΣ ΦΟΡΤΙΣΗΣ

ΤΗΣ ΚΑΤΑΣΚΕΥΗΣ.

ΚΑΤΑΣΚΕΥΑΣΤΙΚΟΣ ΧΑΛΥΒΑΣ

53.0 MISCELLANEOUS METALS:

52.1. STEEL GRATING MUST BE STANDARD WELDED TYPE, FABRICATED WITH 5mm THICK BEARING BARS SPACED AT 30mm ON CENTER, DEPTH AS INDICATED ON THE DRAWINGS. PROVIDE CROSS BARS AT 100mm ON CENTER. ATTACH PANELS

TO SUPPORTING MEMBERS WITH MANUFACTURER'S STANDARD GALVANIZED

HOLDDOWN CLIPS WITH A MINIMUM OF 4 FASTENERS PER PANEL. BAND EDGES

OF GRATING. GRATING SURFACES MUST BE SERRATED WITH HOT DIPPED

GALVANIZED FINISH.

ΟΙ ΣΧΑΡΕΣ ΑΠΟ ΧΑΛΥΒΑ ΠΡΕΠΕΙ ΝΑ ΕΙΝΑΙ ΤΥΠΙΚΗΣ ΣΥΓΚΟΛΛΗΣΗΣ,

ΚΑΤΑΣΚΕΥΑΣΜΕΝΕΣ ΜΕ ΧΑΜΗΛΗΣ ΦΕΡΟΥΣΑΣ ΙΚΑΝΟΤΗΤΑΣ ΡΑΒΔΟΥΣ ΑΝΑ 30ΜΜ

ΚΕΝΤΡΙΚΑ, ΒΑΘΟΣ ΟΠΩΣ ΑΝΑΓΡΑΦΕΤΑΙ ΣΤΑ ΣΧΕΔΙΑ. ΝΑ ΤΟΠΟΘΕΤΟΥΝΤΑΙ

ΣΤΑΥΡΟΕΙΔΕΙΣ ΡΑΒΔΟΙ ΑΝΑ 100ΜΜ ΚΕΝΤΡΙΚΑ. ΝΑ ΓΙΝΕΤΑΙ ΣΥΝΔΕΣΗ ΤΩΝ ΠΑΝΕΛ ΜΕ

ΤΑ ΜΕΛΗ ΣΤΗΡΙΞΗΣ ΜΕ ΤΥΠΙΚΟΥΣ ΓΑΛΒΑΝΙΖΕ ΣΥΝΔΕΤΗΡΕΣ ΣΥΓΚΡΑΤΗΣΗΣ ΤΟΥ

ΚΑΤΑΣΚΕΥΑΣΤΗ, ΜΕ ΤΟΥΛΑΧΙΣΤΟΝ 4 ΔΕΤΕΣ ΑΝΑ ΠΑΝΕΛ. ΝΑ ΔΕΝΟΝΤΑΙ ΟΙ ΑΚΡΕΣ

ΤΩΝ ΕΣΧΑΡΩΝ. ΟΙ ΕΠΙΦΑΝΕΙΕΣ ΤΩΝ ΕΣΧΑΡΩΝ ΠΡΕΠΕΙ ΝΑ ΕΙΝΑΙ ΟΔΟΝΤΩΤΕΣ ΜΕ ΕΝ

ΘΕΡΜΩ ΦΙΝΙΡΙΣΜΑ ΓΑΛΒΑΝΙΣΜΕΝΟ.

ΔΙΑΦΟΡΑ ΜΕΤΑΛΛΑ:

B

1 2 3 4 5

NONE

1615269

DWG

SHEET OF

NAVFAC DRAWING NO.

CONSTR. CONTR. NO.

EPROJECT NO.

SCALE:

N62470-21-C-0005

DESIGN DIRECTOR

BRANCH MANAGER

PM/DM

DES DRW CHK

SATISFACTORY TO DATE

ACTIVITY

FOR COMMANDER NAVFAC

APPROVED

A/E INFO

SEAL

SY

M

DE

SC

RI

PT

IO

N

DA

TE

AP

PR

N

AV

S U

PP

AC

T

SO

U D

A B

AY

N

AV

A L

FA

C

IL

IT

IE

S

EN

G

IN

E

ER

IN

G S

YS

TE

M C

O M

M

AN

D D

E P

AR

TM

E N

T O

F

TH

E N

A

VY

N

AV

AL

F

AC

IL

IT

IE

S E

N G

IN

EE

R

IN

G S

YS

TE

M C

O M

M

AN

D

A

FIRE PROTECTION

N O

R

FO

LK

, V

A A

TL

AN

TI

C

D E

SI

G

N A

N D

C O

N

ST

R U

C

TI

O N

1100 NORTH GLEBE ROAD

SUITE 500

ARLINGTON, VIRGINIA 22201

571.218.1000

FAX: 571.218.1600

D

C

B

A

1 2 3 4 5

RICHARD STEPHENS

TRUEWORTHY,PE / STELMASZEK,RA

PL

O

T

DA

TE

/T

IM

E:

7/

/ 2

3:

:3

PM

C

R ev it_ Lo ca l_

M od el s\

\P

1- D

1-

S_ R

_j oe

.th om as 1.

rv t

14 JUL 2021

RECEIVED BY JACOBIE TISDALE

AND STEVE PARK VIA EMAIL

S-004

LAP JT LPF

P

C

O M

M U

N

IC

A

TI

O N

C E

N

TE

RS

O

U D

A B

AY

, G

R

EE

C E

G

EN

ER

A

L

ST

R U

C

TU

R

AL

N O

TE

S

14089105

ΓΕ

Ν

ΙΚ

ΕΣ

ΚΑ

ΤΑ

ΣΚ

ΕΥ

Α

ΣΤ

ΙΚ

ΕΣ

Π

ΑΡ

Α

ΤΗ

Ρ Η

ΣΕ

ΙΣ

JTW

DPS

STRUCTURAL ABBREVIATIONS:

AB

ADDL

ALT

ALUM

APPD

APPROX

ARCH

BF

BLDG

BM

B.O.

BOF

BOS

BOSD

BOT

B/

BP

BRCG

BRDG

BRG

CG

CIP

CJ

CJP

CL

CLG

CLR

C.O.

COL

CONC

CONN

CONST

CONT

CTR

D

DIA

DIAG

DIM

DL

DN

DWG

DWL

AT

ΣΤΑ

GREATER THAN

ΜΕΓΑΛΥΤΕΡΟ ΑΠΟ

LESS THAN

ΜΙΚΡΟΤΕΡΟ ΑΠΟ

EQUALS

ΙΣΟΥΤΑΙ

PLUS OR MINUS

ΣΥΝ Η' ΠΛΗΝ

DIAMETER

ΔΙΑΜΕΤΡΟΣ

ANCHOR BOLT

ΒΙΔΑ ΑΓΚΥΡΩΣΗΣ

ADDITIONAL

ΕΠΙΠΛΕΟΝ

ALTERNATE

ΕΝΑΛΛΑΚΤΙΚΟ

ALUMINUM

ΑΛΟΥΜΙΝΙΟ

APPROVED

ΕΓΚΕΚΡΙΜΕΝΟ

APPROXIMATE

ΚΑΤΑ ΠΡΟΣΕΓΓΙΣΗ

ARCHITECTURAL

ΑΡΧΙΤΕΚΤΟΝΙΚΟ

BOTTOM FACE

ΚΑΤΩ ΟΨΗ

BUILDING

ΚΤΙΡΙΟ

BEAM

ΔΟΚΑΡΙ

BOTTOM OF

ΚΑΤΩ ΣΤΑΘΜΗ ΤΟΥ

BOTTOM OF FOOTING

ΚΑΤΩ ΠΑΡΕΙΑ ΠΕΔΙΛΟΥ

BOTTOM OF STEEL

ΚΑΤΩ ΠΑΡΕΙΑ ΧΑΛΥΒΑ

BOTTOM OF STEEL DECK

ΚΑΤΩ ΣΤΑΘΜΗ

ΜΕΤΑΛΛΙΚΟΥ ΔΑΠΕΔΟΥ

BOTTOM

ΠΥΘΜΕΝΑΣ

BOTTOM OF

ΚΑΤΩ ΠΑΡΕΙΑ ΤΟΥ

BASE PLATE

ΠΛΑΚΑ ΕΔΡΑΣΗΣ

BRACING

ΣΥΝΔΕΣΜΟΣ ΣΤΗΡΙΞΗΣ

BRIDGING

ΓΕΦΥΡΩΣΗ

BEARING

ΥΠΟΣΤΗΡΙΓΜΑ

CENTER OF GRAVITY

ΚΕΝΤΡΟ ΒΑΡΟΥΣ

CAST-IN-PLACE

ΕΠΙΤΟΠΙΑ (ΣΚΥΡΟΔΕΤΗΣΗ)

CONTROL /

CONTRACTION JOINT

ΑΡΜΟΣ ΣΥΣΤΟΛΗΣ

COMPLETE JOINT

PENETRATION

ΕΣΩΡΑΦΗ ΠΛΗΡΟΥΣ

ΔΙΕΙΣΔΥΣΗΣ

CENTER LINE

ΚΕΝΤΡΙΚΟΣ ΑΞΟΝΑΣ

CEILING

ΨΕΥΔΟΡΟΦΗ

CLEAR

ΚΑΘΑΡΟΤΗΤΑ

CONTRACTING OFFICER

ΑΞΙΩΜΑΤΙΚΟΣ ΕΡΓΟΥ

COLUMN

ΥΠΟΣΤΥΛΩΜΑ

CONCRETE

ΣΚΥΡΟΔΕΜΑ

CONNECTION

ΣΥΝΔΕΣΗ

CONSTRUCTION

ΚΑΤΑΣΚΕΥΗ

CONTINUOUS

ΣΥΝΕΧΕΣ

CENTER

ΚΕΝΤΡΟ

DEPTH

ΒΑΘΟΣ

DIAMETER

ΔΙΑΜΕΤΡΟΣ

DIAGONAL

ΔΙΑΓΩΝΙΟ

DIMENSION

ΔΙΑΣΤΑΣΗ

DEAD LOAD

ΜΟΝΙΜΑ ΦΟΡΤΙΑ

DOWN

ΚΑΤΩ

DRAWING

ΣΧΕΔΙΟ

DOWEL

ΑΝΑΜΟΝΗ/ΑΓΚΥΡΙΟ

I.D

I.F.

INFO

INT

JST

JT

kg km kPa

L

Ld

Ls

LL

LLH

LLV

LONG

LP

INSIDE DIAMETER

ΕΣΩΤΕΡΙΚΗ ΔΙΑΜΕΤΡΟΣ

INSIDE FACE

ΕΣΩΤΕΡΙΚΗ ΠΛΕΥΡΑ

INFORMATION

ΠΛΗΡΟΦΟΡΙΑ

INTERIOR

ΕΣΩΤΕΡΙΚΟ

JOIST

ΔΙΚΤΥΩΜΑ

JOINT

ΑΡΜΟΣ

KILOGRAMS

ΧΙΛΙΟΓΡΑΜΜΑ

KILOMETER(S)

ΧΙΛΙΟΜΕΤΡΑ

KILOPASCALS

ΚΙΛΟΠΑΣΚΑΛ

LENGTH

ΜΗΚΟΣ

DEVELOPMENT LEGNTH

ΜΗΚΟΣ ΑΓΚΥΡΩΣΗΣ

LAP SPLICE LENGTH

ΜΗΚΟΣ ΥΠΕΡΚΑΛΥΨΗΣ

LIVE LOAD

ΚΙΝΗΤΑ ΦΟΡΤΙΑ

LONG LEG HORIZONTAL

ΜΕΓ.ΔΙΑΣΤΑΣΗ ΟΡΙΖ/ΝΤΙΑ

LONG LEG VERTICAL

ΜΕΓ.ΔΙΑΣΤΑΣΗ ΚΑΤΑΚ/ΦΑ

LONGITUDINAL

ΚΑΤΑ ΜΗΚΟΣ

LOW POINT

ΧΑΜΗΛΟ ΣΗΜΕΙΟ

PJF

PL

PROJ

QTY

R

RAD

RAF

RC

RD

RECT

REF

REINF

REQD

SCHED

SDL

SECT

SHT

SIM

SOG

SPA

SPEC

SQ

STD

STGR

STIF

STIR

STL

STRUCT

SYM

PREMOLDED JOINT FILLER

ΠΡΟΚΑΤΑΣΚΕΥΑΣΜΕΝΟΣ

ΑΡΜΟΣ ΠΛΗΡΩΣΗΣ

PLATE

ΕΛΑΣΜΑ-ΠΛΑΚΑ

PROJECTION

ΠΡΟΒΟΛΗ

QUANTITY

ΠΟΣΟΤΗΤΑ

RISER

ΥΨΟΣ ΣΚΑΛΟΠΑΤΙΟΥ

RADIUS

ΑΚΤΙΝΑ

RAISED ACCESS FLOOR

ΥΠΕΡΥΨΩΜΕΝΟ ΔΑΠΕΔΟ ΜΕ ΠΡΟΣΒΑΣΗ

REINFORCED CONCRETE

ΟΠΛΙΣΜΕΝΟ ΣΚΥΡΟΔΕΜΑ

ROOF DRAIN

ΑΠΟΣΤΡΑΓΓΙΣΗ ΟΡΟΦΗΣ

RECTANGULAR

ΟΡΘΟΓΩΝΙΚΟ

REFER TO

ΒΛΕΠΕ

REINFORCEMENT

ΟΠΛΙΣΜΟΣ

REQUIRED

ΑΠΑΙΤΕΙΤΑΙ

SCHEDULE

ΠΙΝΑΚΑΣ/ΠΡΟΓΡΑΜΜΑ

SUPERIMPOSED DEAD LOAD

ΕΠΙΠΛΕΟΝ ΜΟΝΙΜΟ ΦΟΡΤΙΟ

SECTION

ΤΟΜΗ

SHEET

ΣΧΕΔΙΟ/ΦΥΛΛΟ

SIMILAR

ΠΑΡΟΜΟΙΟ

SLAB ON GRADE

ΠΛΑΚΑ ΕΠΙ ΕΔΑΦΟΥΣ

SPACING

ΔΙΑΤΑΞΗ ΣΤΟ ΧΩΡΟ

SPECIFICATION

ΠΡΟΔΙΑΓΡΑΦΗ

SQUARE

ΤΕΤΡΑΓΩΝΟ

STANDARD

ΠΡΟΤΥΠΟ

STRINGER

ΟΡΘΟΣΤΑΤΗΣ

STIFFENER

ΕΛΑΣΜΑ ΕΝΙΣΧΥΣΗΣ

STIRRUP

ΤΣΕΡΚΙ

STEEL

ΧΑΛΥΒΑΣ

STRUCTURAL

ΔΟΜΟΣΤΑΤΙΚΑ

SYMETRICAL

ΣΥΜΜΕΤΡΙΚΑ

ΣΥΝΤΟΜΟΓΡΑΦΙΕΣ ΣΤΑΤΙΚΩΝ ΣΧΕΔΙΩΝ

EA

EF

EJ

EL

ELEC

EMBED

EOS

EQ

EQUIP

EW

EXIST

EXT

FD

FDN

FFE

FG

FL

FLG

FS

FTG

GA

GALV

GB

GR

GRTG

HAS

HORIZ

HP

HR

HT

EACH

ΚΑΘΕ

EACH FACE

ΚΑΘΕ ΟΨΗ/ΠΑΡΕΙΑ

EXPANSION JOINT

ΑΡΜΟΣ ΔΙΑΣΤΟΛΗΣ

ELEVATION

ΥΨΟΜΕΤΡΟ

ELECTRICAL

ΗΛΕΚΤΡΟΛΟΓΙΚΑ

EMBEDMENT

ΕΝΣΩΜΑΤΩΣΗ

EDGE OF SLAB

ΠΑΡΕΙΑ ΠΛΑΚΑΣ

EQUAL

ΙΣΟΣ

EQUIPMENT

ΕΞΟΠΛΙΣΜΟΣ

EACH…

This is the start of the file's text. The full file is on GovTribe.