This solicitation is for the design and construction of a communications center at Naval Support Activity Souda Bay, Greece. The project involves constructing a three-story concrete facility with exterior concrete walls and shallow foundations to house a communications center, telephone exchange, electronics maintenance shops, and storage. Electrical utilities will include primary and secondary distribution systems, transformers, substation upgrades, telecommunications infrastructure, security systems infrastructure and lighting. The period of performance is approximately 900 days after notice to proceed. The solicitation is for a Design-Bid-Build, Firm Fixed Price contract issued by the Naval Facilities Engineering Command on behalf of the Department of the Navy. Responses are due under solicitation number N62470-21-R-0005.
View the file
Other files
Show all 49
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
DUCTWORK SYMBOLS
ΣΥΜΒΟΛΙΣΜΟΙ ΑΕΡΑΓΩΓΟΥ
(X) (Y)
ER-4
RR-4
(X) (Y)
SR-4
(Y)
RA-4
(Y)
SA-4
BDD
BDD
M
VD
SD
SB
FD
FC
R OR D
600/300
300 ø
600x600
M
VD
SD
SB
FD
FD
FSD
R OR D
300 ø
RECTANGULAR DUCT. FIRST NUMBER
INDICATES SIDE IN VIEW, SECOND
NUMBER INDICATES SIDE IN DEPTH
ΟΘΟΓΩΝΙΚΟΣ ΑΕΡΑΓΩΓΟΣ. Η ΠΡΩΤΗ ΤΙΜΗ
ΥΠΟΔΥΚΝΥΕΙ ΤΗΝ ΔΙΑΣΤΑΣΗ ΤΗΣ ΕΜΦΑΝΟΥΣ
ΠΛΕΥΡΑΣ, Η ΔΕΥΤΕΡΗ ΤΗΝ ΠΛΕΥΡΑ ΣΕ ΒΑΘΟΣ.
ROUND DUCT. NUMBER INDICATES
DUCT DIAMETER
ΚΥΚΛΥΚΟΣ ΑΕΡΑΓΩΓΟΣ. Η ΤΙΜΗ ΥΠΟΔΕΙΚΝΥΕΙ ΤΗΝ
ΔΙΑΜΕΤΡΟ ΤΟΥ ΑΕΡΑΓΩΓΟΥ.
FLAT OVAL DUCT. NUMBER
INDICATED CLEAR INSIDE DIMENSION
ΟΒΑΛ ΑΕΡΑΓΩΓΟΣ. Η ΤΙΜΗ ΥΠΟΔΥΚΝΥΕΙ ΚΑΘΑΡΗ
ΕΣΩΤΕΡΙΚΗ ΔΙΑΣΤΑΣΗ.
INCLINE RISE OR DROP IN
DIRECTION OF AIR FLOW
ΚΛΙΣΗ ΑΝΟΔΙΚΗ Η ΚΑΘΟΔΙΚΗ ΣΤΗΝ ΚΑΤΕΥΘΥΝΣΗ
ΡΟΗΣ ΤΟΥ ΑΕΡΑ.
90° RADIUS ELBOW UP. USE 90°
ELBOW W/ TURNING VANES WHEN
RADIUS DOES NOT FIT
ΚΑΜΠΥΛΗ 90° ΠΡΟΣ ΤΑ ΑΝΩ. ΚΑΝΕΤΕ ΧΡΗΣΗ
ΚΑΜΠΥΛΗΣ 90° ΜΕ ΠΤΕΡΥΓΙΑ ΟΤΑΝ ΑΝΟΙΧΤΗ
ΚΑΜΠΥΛΗ ΔΕΝ ΧΩΡΑΕΙ.
90° RADIUS ELBOW DOWN. USE
90° ELBOW W/ TURNING VANES
WHEN RADIUS DOES NOT FIT
ΚΑΜΠΥΛΗ 90° ΠΡΟΣ ΤΑ ΚΑΤΩ. ΚΑΝΕΤΕ ΧΡΗΣΗ
ΚΑΜΠΥΛΗΣ 90° ΜΕ ΠΤΕΡΥΓΙΑ ΟΤΑΝ ΑΝΟΙΧΤΗ
ΚΑΜΠΥΛΗ ΔΕΝ ΧΩΡΑΕΙ.
DUCT SECTION-SUPPLY AIR/ OSA DUCT
ΤΟΜΗ ΑΕΡΑΓΩΓΟΥ-ΠΡΟΣΑΓΩΓΗΣ ΑΕΡΑ /OSA
DUCT SECTION-RETURN AIR
ΤΟΜΗ ΑΕΡΑΓΩΓΟΥ- ΑΕΡΑΣ ΕΠΙΣΤΡΟΦΗΣ
FLEXIBLE CONNECTOR
ΕΥΚΑΜΠΤΟΣ ΣΥΝΔΕΣΜΟΣ
FLEXIBLE DUCT, SIZED TO MATCH TERMINAL NECK
SIZE
ΕΥΚΑΜΠΤΟΣ ΑΕΡΑΓΩΓΟΣ, ΔΙΑΣΤΑΣΗ ΣΥΜΦΩΝΑ ΜΕ
ΤΗΝ ΔΙΑΣΤΑΣΗ ΛΑΙΜΟΥ ΤΟΥ ΣΤΟΜΙΟΥ.
FIRE DAMPER, HORIZONTAL DUCT
ΔΙΑΦΡΑΓΜΑ ΦΩΤΙΑΣ, ΟΡΙΖΟΝΤΙΟΥ ΑΕΡΑΓΩΓΟΥ
FIRE DAMPER, VERTICAL DUCT
ΔΙΑΦΡΑΓΜΑ ΦΩΤΙΑΣ, ΚΑΘΕΤΟΥ ΑΕΡΑΓΩΓΟΥ
FIRE/SMOKE DAMPER, VERTICAL DUCT
ΔΙΑΦΡΑΓΜΑ ΦΩΤΙΑΣ/ΚΑΠΝΟΥ, ΚΑΘΕΤΟΥ ΑΕΡΑΓΩΓΟΥ
SECURITY BARS
ΜΠΑΡΕΣ ΑΣΦΑΛΕΙΑΣ
SMOKE DAMPER, HORIZONTAL DUCT
ΔΙΑΦΡΑΓΜΑ ΚΑΠΝΟΥ, ΟΡΙΖΟΝΤΙΟΥ ΑΕΡΑΓΩΓΟΥ
VOLUME DAMPER
ΔΙΑΦΡΑΓΜΑ ΠΑΡΟΧΗΣ
MOTORIZED DAMPER
ΜΗΧΑΝΙΚΟ ΔΙΑΦΡΑΓΜΑ
BACKDRAFT DAMPER
ΒΑΡΥΝΤΙΚΟ ΔΙΑΦΡΑΓΜΑ
SUPPLY CEILING DIFFUSER
TYPE 4-AIR QUANTITY (Y) LPS
ΣΤΟΜΙΟ ΠΡΟΣΑΓΩΓΗΣ ΟΡΟΦΗΣ
ΤΥΠΟΣ 4-ΠΑΡΟΧΗ (Υ) LPS
CEILING RETURN AIR
GRILLE, TYPE
4-AIR QUANTITY (Y) LPS
ΣΤΟΜΙΟ ΑΕΡΑ ΕΠΙΣΤΡΟΦΗΣ ΟΡΟΦΗΣ,
ΤΥΠΟΣ 4-ΠΑΡΟΧΗ (Υ) LPS
SUPPLY GRILLE OR REGISTER
(X) NECK SIZE
DUCT-AIR QUANTITY (Y) LPS
ΔΙΑΣΤΑΣΗ ΣΤΟΜΙΟΥ ΠΡΟΣΑΓΩΓΗΣ Η ΕΠΙΣΤΡΟΦΗΣ
ΣΥΜΦΩΝΑ ΜΕ ΤΗΝ ΠΑΡΟΧΗ ΤΟΥ ΑΕΡΑΓΩΓΟΥ (Υ) LPS
RETURN/EXHAUST GRILLE OR REGISTER
SIZE (X) NECK SIZE-AIR QUANTITY
(Y) LPS
ΔΙΑΣΤΑΣΗ ΣΤΟΜΙΟΥ ΕΠΙΣΤΡΟΦΗΣ/ΕΞΑΕΡΙΣΜΟΥ
ΣΥΜΦΩΝΑ ΜΕ ΤΗΝ ΠΑΡΟΧΗ ΤΟΥ ΑΕΡΑΓΩΓΟΥ (Υ) LPS
600x600
600/300
LINEAR SLOT DIFFUSER SIZE TO
MATCH DUCT-AIR QUANTITY (Y) LPS
ΔΙΑΣΤΑΣΗ ΓΡΑΜΜΙΚΟΥ ΣΤΟΜΙΟΥ ΣΥΜΦΩΝΑ ΜΕ ΤΗΝ
ΠΑΡΟΧΗ ΤΟΥ ΑΕΡΑΓΩΓΟΥ (Υ) LPS(Y)
LS
(Y)
EA-4
CEILING EXHAUST AIR GRILLE
TYPE 4-AIR QUANTITY (Y) LPS
ΣΤΟΜΙΟ ΟΡΟΦΗΣ ΕΞΑΕΡΙΣΜΟΥ,
(Χ) ΔΙΑΣΤΑΣΗ ΛΑΙΜΟΥ,
ΤΥΠΟΣ 4-ΠΑΡΟΧΗ (Υ) LPS
(Y)
OA-4
OUTSIDE AIR CEILING DIFFUSER
TYPE 4-AIR QUANTITY (Y) LPS
ΣΤΟΜΙΟ ΠΡΟΣΑΓΩΓΗΣ ΟΡΟΦΗΣ
ΤΥΠΟΣ 4-ΠΑΡΟΧΗ (Υ) LPS
(X) (Y)
OA-4
SUPPLY GRILLE OR REGISTER
(X) NECK SIZE
DUCT-AIR QUANTITY (Y) LPS
ΔΙΑΣΤΑΣΗ ΣΤΟΜΙΟΥ ΠΡΟΣΑΓΩΓΗΣ Η ΕΠΙΣΤΡΟΦΗΣ
ΣΥΜΦΩΝΑ ΜΕ ΤΗΝ ΠΑΡΟΧΗ ΤΟΥ ΑΕΡΑΓΩΓΟΥ (Υ) LPS
STANDARD ROUND BRANCH DUCT (SPIN-IN)
TYΠΙΚΟΣ ΚΛΑΔΟΣ ΚΥΚΛΙΚΟΥ ΑΕΡΑΓΩΓΟΥ (ΜΕ
ΚΟΛΑΡΟ)
STANDARD ROUND BRANCH DUCT (CONICAL)
ΤΥΠΙΚΟΣ ΚΛΑΔΟΣ ΚΥΚΛΙΚΟΥ ΑΕΡΑΓΩΓΟΥ(ΚΩΝΙΚΟΣ)
STANDARD RECTANGULAR BRANCH DUCT
(45° TAKE-OFF)
ΤΥΠΙΚΟΣ ΚΛΑΔΟΣ ΟΡΘΟΓΩΝΙΚΗΣ ΔΙΑΤΟΜΗΣ
(ΜΕ ΓΩΝΙΑ 45°)
STANDARD CONCENTRIC DUCT TRANSITION
ΤΥΠΙΚΗ ΣΥΣΤΟΛΗ ΟΜΟΚΕΝΤΡΩΝ ΑΕΡΑΓΩΓΩΝ
STANDARD ECCENTRIC DUCT TRANSITION
ΤΥΠΙΚΗ ΕΚΚΕΝΤΡΗ ΣΥΣΤΟΛΗ ΑΕΡΑΓΩΓΩΝ
RECTANGULAR-TO-ROUND DUCT TRANSITION
ΣΥΣΤΟΛΗ ΟΡΘΟΓΩΝΙΚΟΥ ΣΕ ΚΥΚΛΙΚΟ ΑΕΡΑΓΩΓΟ
VANED ELBOW (PROVIDE VANES IN ALL SQUARE
OR RECTANGULAR ELBOWS, UNLESS NOTED
OTHERWISE)
ΓΩΝΙΑ ΟΡΘΟΓΩΝΙΚΗΣ ΔΙΑΤΟΜΗΣ (ΠΡΟΜΗΘΕΥΣΤΕ
ΓΩΝΙΕΣ ΜΕ ΠΤΕΡΥΓΙΑ ΣΕ ΟΡΘΟΓΩΝΙΚΕΣ Ή ΤΕΤΡΑΓΩ
ΝΙΚΕΣ ΔΙΑΤΟΜΕΣ, ΕΚΤΟΣ ΚΑΙ ΑΝ ΑΝΑΦΕΡΕΤΑΙ ΑΛΛΙΩΣ)
SUPPLY OR OUTSIDE AIR DUCT DOWN
ΑΕΡΑΓΩΓΟΣ ΠΡΟΣΑΓΩΓΗΣ Ή ΕΞΩΤΕΡΙΚΟΣ
ΠΡΟΣ ΤΑ ΚΑΤΩ.
RETURN AIR DUCT DOWN
ΑΕΡΑΓΩΓΟΣ ΕΠΙΣΤΡΟΦΗΣ ΠΡΟΣ ΤΑ ΚΑΤΩ
RELIEF OR EXHAUST AIR DUCT UP
ΑΕΡΑΓΩΓΟΣ ΕΞΑΕΡΙΣΜΟΥ ΠΡΟΣ ΤΑ ΠΑΝΩ
RELIEF OR EXHAUST AIR DUCT DOWN
ΑΕΡΑΓΩΓΟΣ ΕΞΑΕΡΙΣΜΟΥ ΠΡΟΣ ΤΑ ΚΑΤΩ
PIPING SYMBOLS
ΣΥΜΒΟΛΙΣΜΟΙ ΣΩΛΗΝΩΣΕΩΝ
PRESSURE GAUGE
ΜΕΤΡΗΤΗΣ ΠΙΕΣΗΣ ΜΕ ΒΑΝΑΚΙ
CONNECTION, BOTTOM
ΣΥΝΔΕΣΗ, ΠΥΘΜΕΝΑ
CONNECTION, TOP
ΣΥΝΔΕΣΗ, ΟΡΟΦΗΣ
PIPE TURNING DOWN
ΣΤΡΟΦΗ ΣΩΛΗΝΑΣ ΠΡΟΣ ΤΑ ΚΑΤΩ
PIPE TURNING UP
ΣΤΡΟΦΗ ΣΩΛΗΝΑΣ ΠΡΟΣ ΤΑ ΑΝΩ
TEE, OUTLET UP
ΤΑΥ, ΕΞΟΔΟΣ ΠΡΟΣ ΤΑ ΑΝΩ
TEE, OUTLET DOWN
ΤΑΥ, ΕΞΟΔΟΣ ΠΡΟΣ ΤΑ ΚΑΤΩ
ISOLATION VALVE
(BALL, GATE, OR BUTTERFLY)
ΒΑΝΑ ΑΠΟΜΟΝΩΣΗΣ
(ΣΦΑΙΡΑΣ, ΣΥΡΤΗ, Η ΠΕΤΑΛΟΥΔΑΣ)
CHECK VALVE
ΒΑΛΒΙΔΑ ΑΝΤΕΠΙΣΤΡΟΦΗΣ
STRAINER, W/ BLOWOFF
AND HOSE CONN.
ΠΛΑΓΙΟ ΦΙΤΡΟ ΣΙΤΑΣ, ΜΕ ΕΚΤΟΝΩΣΗ ΚΑΙ
ΣΥΝΔΕΣΜΟ ΕΥΚΑΜΠΤΟΥ ΣΩΛΗΝΑ
BUTTERFLY VALVE
ΒΑΝΑ ΠΕΤΑΛΟΥΔΑΣ
BALL VALVE
ΣΦΑΙΡΙΚΗ ΒΑΝΑ
FLEXIBLE CONNECTOR
ΕΥΚΑΜΠΤΟΣ ΣΥΝΔΕΣΜΟΣ
FLOW DIRECTION ARROW
ΒΕΛΟΣ ΚΑΤΕΥΘΥΝΣΗΣ ΡΟΗΣ
HOSE END CONNECTION
ΤΕΡΜΑΤΙΚΟΣ ΣΥΝΔΕΣΜΟΣ
ΕΥΚΑΜΠΤΟΥ ΣΩΛΗΝΑ
CAP
ΤΕΡΜΑΤΙΚΟ ΚΑΛΥΜΑ
BLIND FLANGE
ΤΥΦΛΗ ΦΛΑΝΤΖΑ
UNION, FLANGED
ΣΥΝΔΕΣΜΟΣ, ΦΛΑΝΤΖΩΤΟΣ
UNION, SCREWED
ΣΥΝΔΕΣΜΟΣ, ΜΕ ΣΠΕΙΡΩΜΑ
INCREASER, REDUCER
ΔΙΑΣΤΟΛΗ, ΣΥΣΤΟΛΗ
HOT WATER RETURN
ΕΠΙΣΤΡΟΦΗ ΝΕΡΟΥ ΘΕΡΜΑΝΣΗΣ
REFRIGERANT SUCTION /
REFRIGERANT LIQUID
ΑΝΑΡΡΟΦΗΣΗ ΨΥΚΤΙΚΟΥ /
ΨΥΚΤΙΚΟ ΥΓΡΟ
HOT WATER SUPPLY
ΠΡΟΣΑΓΩΓΗ ΝΕΡΟΥ ΘΕΡΜΑΝΣΗΣ
CHILLED WATER RETURN
ΕΠΙΣΤΡΟΦΗ ΝΕΡΟΥ ΨΥΞΗΣ
CHILLED WATER SUPPLY
ΠΡΟΣΑΓΩΓΗ ΝΕΡΟΥ ΨΥΞΗΣ
CHWS
CHWR
HWS
HWR
RS/RL
TWO WAY CONTROL VALVE
ΔΙΟΔΟΣ ΒΑΝΑ ΕΛΕΓΧΟΥ
THREE WAY CONTROL VALVE
ΤΡΙΟΔΟΣ ΒΑΝΑ ΕΛΕΓΧΟΥ
PRESSURE REDUCING VALVE
ΒΑΝΑ ΜΕΙΩΣΗΣ ΠΙΕΣΗΣ
RELIEF VALVE
ΒΑΛΒΙΔΑ ΑΣΦΑΛΕΙΑΣ - ΔΙΑΦΥΓΗΣ
AIR VENT, AUTOMATIC
ΑΥΤΟΜΑΤΟ ΕΞΑΕΡΙΣΤΙΚΟ
AIR VENT, MANUAL
ΧΕΙΡΟΚΙΝΗΤΟ ΕΞΑΕΡΙΣΤΙΚΟ
THERMOMETER
ΘΕΡΜΟΜΕΤΡΟ
FLOW SWITCH
ΔΙΑΚΟΠΤΗΣ ΡΟΗΣ
PRESSURE/TEMPERATURE TAP
ΤΑΠΑ ΓΙΑ ΕΞΟΠΛΙΣΜΟ ΠΙΕΣΗΣ/ΘΕΡΜΟΚΡΑΣΙΑΣ
CONTROL VALVE, BUTTERFLY
ΒΑΝΑ ΕΛΕΓΧΟΥ, ΠΕΤΑΛΟΥΔΑΣ
MANUAL BALANCING VALVE
ΒΑΛΒΙΔΑ ΧΕΙΡΟΚΙΝΗΤΗΣ ΕΞΙΣΟΡΡΟΠΗΣΗΣ
CONDENSATE DRAIN
ΑΠΟΣΤΡΑΓΓΙΣΗ ΣΥΜΠΥΚΝΩΜΑΤΩΝ
CDBALL VALVE
ΣΦΑΙΡΙΚΗ ΒΑΝΑ
WELDED CONNECTION
ΣΥΓΚΟΛΛΗΤΗ ΣΥΝΔΕΣΗ
FLANGED CONNECTION
ΣΥΝΔΕΣΗ ΦΛΑΝΤΖΑΣ
SOLDERED CONNECTION
ΣΥΝΔΕΣΗ ΤΗΞΗΣ
THREADED OR "PRESS"
CONNECTION
ΣΥΝΔΕΣΗ ΣΠΕΙΡΩΜΑΤΟΣ Ή
ΣΥΝΔΕΣΗ ΥΠΟ ΠΙΕΣΗ
BELL & SPIGOT CONNECTION
ΣΥΝΔΕΣΗ ΑΡΣΕΝΙΚΟΥ-ΘΗΛΥΚΟΥ
PIPING LABELS
ΣΥΜΒΟΛΙΣΜΟΙ
ΣΩΛΗΝΩΣΕΩΝ
VENTURI FLOW METER
ΜΕΤΡΗΤΗΣ VENTURI
PITCH DOWN IN DIRECTION OF ARROW
ΚΑΤΕΒΑΣΜΑ ΣΤΗ ΔΙΕΥΘΥΝΣΗ ΤΟΥ ΒΕΛΟΥΣ
MECHANICAL ABBREVIATIONS
ΣΥΝΤΜΗΣΕΙΣ ΜΗΧΑΝΟΛΟΓΙΚΩΝ
A AMPERE
ΑΜΠΕΡ
AFF ABOVE FINISHED FLOOR
ΠΑΝΩ ΑΠΟ ΤΕΛΕΙΩΜΕΝΟ ΔΑΠΕΔΟ
AFS AIR FLOW MEASURING STATION
ΣΤΑΘΜΟΣ ΜΕΤΡΗΣΗΣ ΠΑΡΟΧΗΣ ΑΕΡΑ
AMB AMBIENT
ΠΕΡΙΒΑΛΛΟΝΤΟΣ
AP ACCESS PANEL
ΘΥΡΙΔΑ ΕΠΙΣΚΕΨΗΣ
AVG AVERAGE
ΜΕΣΟΣ ΟΡΟΣ
A/C AIR CHANGE
ΕΝΑΛΛΑΓΕΣ ΑΕΡΑ
ALM ALARM
ΣΥΣΤΗΜΑΤΑ ΣΥΝΑΓΕΡΜΟΥ
BAS BUILDING AUTOMATION SYSTEM
ΣΥΣΤΗΜΑ ΑΥΤΟΜΑΤΙΜΟΥ ΚΤΙΡΙΟΥ
BDD BACK DRAFT DAMPER
ΔΙΑΦΡΑΓΜΑ ΑΝΤΙΡΡΟΗΣ
BOD BOTTOM OF DUCT
ΠΥΘΜΕΝΑΣ ΑΕΡΑΓΩΓΟΥ
BPV BYPASS VALVE
ΒΑΝΑ ΠΑΡΑΚΑΜΨΗΣ
CC COOLING COIL
ΣΤΟΙΧΕΙΟ ΨΥΞΗΣ
CO CLEANOUT
ΣΤΟΜΙΟ ΚΑΘΑΡΙΣΜΟΥ
°C DEGREE CELSIUS
ΒΑΘΜΟΙ ΚΕΛΣΙΟΥ
DB DRY BULB
ΞΗΡΗΣ ΣΦΑΙΡΑΣ(ΒΟΛΒΟΥ)
dB DECIBELS
ΝΤΕΣΙΜΠΕΛ
DDC DIRECT DIGITAL CONTROL
ΑΜΕΣΟΣ ΨΗΦΙΑΚΟΥ ΕΛΕΓΧΟΥ
DEFL DEFLECTION
ΕΚΤΡΟΠΗ
DEG DEGREE
ΒΑΘΜΟΣ
DIA DIAMETER
ΔΙΑΜΕΤΡΟΣ
DIFF DIFFERENCE
ΔΙΑΦΟΡΑ
DL DOOR LOUVER
ΣΤΟΜΙΟ ΘΥΡΑΣ
DN DOWN
ΚΑΤΩ
DSD DUCT SMOKE DETECTOR
ΑΝΙΧΝΕΥΤΗΣ ΚΑΠΝΟΥ ΑΕΡΑΓΩΓΟΥ
DWG DRAWING
ΣΧΕΔΙΟ
DX DIRECT EXPANSION
ΑΠΕΥΘΕΙΑΣ ΕΚΤΟΝΩΣΗΣ
EA EACH
ΚΑΘΕ ΕΝΟΣ
EAT ENTERING AIR TEMPERATURE
ΘΕΡΜΟΚΡΑΣΙΑ ΑΕΡΑ ΕΙΣΟΔΟΥ
EFF EFFICIENCY
ΑΠΟΔΟΣΗ
EL ELEVATION
ΥΨΟΜΕΤΡΟ - ΟΨΗ
ELEC. ELECTRICAL
ΗΛΕΚΤΡΟΛΟΓΙΚΟ
EWT ENTERING WATER TEMPERATURE
ΘΕΡΜΟΚΡΑΣΙΑ ΝΕΡΟΥ ΕΙΣΟΔΟΥ
EA EXHAUST AIR
ΑΕΡΑΣ ΕΞΑΕΡΙΣΜΟΥ
EXT EXTERNAL
ΕΞΩΤΕΡΙΚΟΣ
FA FROM ABOVE
ΑΠΟ ΠΑΝΩ
FB FROM BELOW
ΑΠΟ ΚΑΤΩ
FD FIRE DAMPER
ΔΙΑΦΡΑΓΜΑ ΦΩΤΙΑΣ
FPMM FIN PER MILLIMETER
FIN PER MILLIMETER
FLA FULL LOAD AMP
ΡΕΥΜΑ ΠΛΗΡΟΥΣ ΦΟΡΤΙΟΥ
FLR FLOOR
ΔΑΠΕΔΟ
F O FAIL OPEN
ΑΝΟΙΚΤΟ ΚΑΤΑ ΤΗΝ ΑΣΤΟΧΙΑ
FSD FIRE SMOKE DAMPER
ΔΙΑΦΡΑΓΜΑ ΠΥΡΟΣ ΚΑΠΝΟΥ
HD HEAD ΜΑΝΟΜΕΤΡΙΚΟ
HDPE HIGH DENSITY POLYPROPYLENE
ΠΟΛΥΠΡΟΠΥΛΕΝΙΟ ΥΨΗΛΗΣ
ΠΥΚΝΟΤΗΤΑΣ
HG HOT GAS
ΘΕΡΜΟ ΑΕΡΙΟ
HGR HOT GAS REHEAT
ΑΝΑΘΕΡΜΑΝΣΗ ΘΕΡΜΟΥ ΑΕΡΙΟΥ
HP HORSEPOWER
ΙΠΠΟΔΥΝΑΜΗ
HZ HERTZ ΧΕΡΤΖ
HVAC HEATING VENTILATING
AND AIR CONDITIONING
ΘΕΡΜΑΝΣΗ ΑΕΡΙΣΜΟΣ
ΚΑΙ ΚΛΙΜΑΤΙΣΜΟΣ
ID INSIDE DIAMETER
ΕΣΩΤΕΡΙΚΗ ΔΙΑΜΕΤΡΟΣ
IPLV INTEGRATED PART LOAD VALUE
ΕΝΣΩΜΑΤΩΜΕΝΗ ΤΙΜΗ ΜΕΡΙΚΩΝ
ΦΟΡΤΙΩΝ
KG KILOGRAMS
ΧΙΛΙΟΓΡΑΜΜΑ
KW KILOWATT
ΧΙΛΙΟΒΑΤ
KWH KILOWATT HOUR
ΧΙΛΙΟΒΑΤΩΡΕΣ
LAT LEAVING AIR TEMPERATURE
ΘΕΡΜΟΚΡΑΣΙΑ ΑΕΡΑ ΕΞΟΔΟΥ
LPS LITRES PER SECOND
ΛΙΤΡΑ ΑΝΑ ΔΕΥΤΕΡΟΛΕΠΤΟ
LVG LEAVING
ΑΝΑΧΩΡΗΣΕΩΣ - ΕΞΟΔΟΥ
LWT LEAVING WATER TEMPERATURE
ΘΕΡΜΟΚΡΑΣΙΑ ΝΕΡΟΥ ΕΞΟΔΟΥ
M METER
ΜΕΤΡΟ
MAX MAXIMUM
ΜΕΓΙΣΤΟ
MCA MINIMUM CURRENT AMPERES
ΕΛΑΧΙΣΤΟ ΡΕΥΜΑ ΚΥΚΛΩΜΑΤΟΣ
MIN MINIMUM
ΕΛΑΧΙΣΤΟ
MM MILIMETERS
ΧΙΛΙΟΣΤΟΜΕΤΡΑ
MOP MAXIMUM OVERCURRENT
PROTECTION
ΜΕΓΙΣΤΗ ΠΡΟΣΤΑΣΙΑ ΑΠΟ
ΥΠΕΡΕΝΤΑΣΗ
MPS METERS PER SECOND
ΜΕΤΡΑ ΑΝΑ ΔΕΥΤΕΡΟΛΕΠΤΟ
NC NOISE CRITERIA
ΚΡΙΤΗΡΙΑ ΘΟΡΥΒΟΥ
NC NORMALLY CLOSED
ΚΑΝΟΝΙΚΑ ΚΛΕΙΣΤΟ
NIC NOT IN CONTRACT
ΕΚΤΟΣ ΣΥΜΒΟΛΑΙΟΥ
NO NORMALLY OPEN
ΚΑΝΟΝΙΚΑ ΑΝΟΙΚΤΟ
NTS NOT TO SCALE
ΕΚΤΟΣ ΚΛΙΜΑΚΑΣ
OA OUTSIDE AIR
ΕΞΩΤΕΡΙΚΟΣ ΑΕΡΑΣ
PA PASCAL
PASCAL
PCD PUMPED CONDENSATE DRAIN
ANTΛΟΥΜΕΝΑ ΣΥΜΠΥΚΝΩΜΑΤΑ
ΑΠΟΣΤΡΑΓΓΙΣΗΣ
PD PRESSURE DROP
ΠΤΩΣΗ ΠΙΕΣΗΣ
PH PHASE
ΦΑΣΗ
PRV PRESSURE REDUCING VALVE
ΒΑΛΒΙΔΑ ΜΕΙΩΣΗΣ ΠΙΕΣΗΣ
RA RETURN AIR
ΑΕΡΑΣ ΕΠΙΣΤΡΟΦΗΣ
RAT RETURN AIR TEMPERATURE
ΘΕΡΜΟΚΡΑΣΙΑ ΑΕΡΑ ΕΠΙΣΤΡΟΦΗΣ
RH RELATIVE HUMIDITY
ΣΧΕΤΙΚΗ ΥΓΡΑΣΙΑ
RL REFRIGERANT LIQUID
ΑΝΤΙΨΥΚΤΙΚΟ
RPM REVOLUTIONS PER MINUTE
ΣΤΡΟΦΕΣ ΑΝΑ ΛΕΠΤΟ
RR RETURN AIR REGISTER
ΣΤΟΜΙΟ ΕΠΙΣΤΡΟΦΗΣ ΑΕΡΑ
RS REFRIGERANT SUCTION
ΑΝΑΡΡΟΦΗΣΗ ΑΝΤΙΨΥΚΤΙΚΟΥ
S STEAM
ΑΤΜΟΣ
SA SUPPLY AIR
ΑΕΡΑΣ ΠΡΟΣΑΓΩΓΗΣ
SP STATIC PRESSURE
ΣΤΑΤΙΚΗ ΠΙΕΣΗ
TEMP TEMPERATURE
ΘΕΡΜΟΚΡΑΣΙΑ
TYP TYPICAL
ΤΥΠΙΚΟ
V VOLT
ΒΟΛΤ
VD VOLUME DAMPER
ΔΙΑΦΡΑΓΜΑ ΠΑΡΟΧΗΣ
VAV VARIABLE AIR VOLUME
ΜΕΤΑΒΛΗΤΗ ΠΑΡΟΧΗ ΑΕΡΑ
VFD VARIABLE FREQUENCY DRIVE
ΟΔΗΓΟΣ ΜΕΤΑΒΛΗΤΗΣ ΣΥΧΝΟΤΗΤΑΣ
VSD VARIABLE SPEED DRIVE
ΟΔΗΓΟΣ ΜΕΤΑΒΛΗΤΗΣ ΤΑΧΥΤΗΤΑΣ
W WATT
ΒΑΤ
W/ WITH
ΜΑΖΙ
WB WET BULB
ΥΓΡΗΣ ΣΦΑΙΡΑΣ(ΒΟΛΒΟΥ)
WC WATER COLUMN
ΣΤΗΛΗΣ ΝΕΡΟΥ
WG WATER GAUGE
ΜΑΝΟΜΕΤΡΙΚΟ
WT WEIGHT
ΒΑΡΟΣ
CONTROLS SYMBOLS
ΣΥΜΒΟΛΙΣΜΟΙ ΕΛΕΓΧΟΥ
T
TT
SD
S
SP
E
DDC
CD
UC
DDC CONTROLLER
ΕΛΕΓΚΤΗΣ ΑΠΕΥΘΕΙΑΣ ΨΗΦΙΑΚΟΥ
ΕΛΕΓΧΟΥ
THERMOSTAT OR TEMPERATURE SENSOR
ΘΕΡΜΟΣΤΑΤΗΣ Η ΑΙΣΘΗΤΗΡΙΟ ΘΕΡΜΟΚΡΑΣΙΑΣ
TEMPERATURE TRANSMITTER
ΑΙΣΘΗΤΗΡΙΟ ΜΕΤΑΔΟΣΗΣ ΘΕΡΜΟΚΡΑΣΙΑΣ
DUCT SMOKE DETECTOR
ΑΝΙΧΝΕΥΤΗΣ ΚΑΠΝΟΥ ΑΕΡΑΓΩΓΟΥ
WALL SWITCH
ΕΠΙΤΟΙΧΟΣ ΔΙΑΚΟΠΤΗΣ
DUCT STATIC OR BUILDING
PRESSURE SENSOR
ΑΙΣΘΗΤΗΡΙΟ ΣΤΑΤΙΚΗΣ ΑΕΡΑΓΩΓΟΥ Ή
ΠΙΕΣΗΣ ΚΤΙΡΙΟΥ
BUILDING EMERGENCY
AIR DISTRIBUTION SHUT OFF
ΔΙΑΚΟΠΤΗΣ ΕΚΤΑΚΤΟΥ ΑΝΑΓΚΗΣ
ΔΙΑΚΟΠΗΣ ΔΙΑΝΟΜΗΣ ΑΕΡΑ ΚΤΙΡΙΟΥ
CO2 SENSOR
ΑΙΣΘΗΤΗΡΙΟ ΔΟΞΕΙΔΙΟΥ ΤΟΥ
ΑΝΘΡΑΚΑ
80MM DOOR UNDERCUT
ΚΕΝΟ ΣΤΗΝ ΒΑΣΗ ΤΗΣ ΠΟΡΤΑΣ 80ΜΜ
EXHAUST FAN
ΑΝΕΜΙΣΤΗΡΑΣ ΕΞΑΕΡΙΣΜΟΥ
DPI
DIFFERENTIAL PRESSURE INDICATOR
ΕΝΔΕΙΞΗ ΔΙΑΦΟΡΙΚΗΣ ΠΙΕΣΗΣ
TI TEMPERATURE INDICATOR
ΘΕΡΜΟΜΕΤΡΟ
PI PRESSURE INDICATOR
ΜΑΝΟΜΕΤΡΟ
AFS
VFD
AIRFLOW MEASURING STATION
ΣΤΑΘΜΟΣ ΜΕΤΡΗΣΗΣ ΠΑΡΟΧΗΣ ΑΕΡΑ
VARIABLE FREQUENCY DRIVE
ΟΔΗΓΟΣ ΜΕΤΑΒΛΗΤΗΣ ΣΥΧΝΟΤΗΤΑΣ
FT FLOW TRANSMITTER
ΑΙΣΘΗΤΗΡΙΟ ΜΕΤΑΔΟΣΗΣ ΡΟΗΣ
ZS END SWITCH
ΤΕΡΜΑΤΙΚΟΣ ΔΙΑΚΟΠΤΗΣ
H HUMIDISTAT
ΥΔΡΟΣΤΑΤΗΣ
BACKFLOW PREVENTER
ΕΞΑΡΤΗΜΑ ΑΠΟΤΡΟΠΗΣ ΑΝΤΙΡΡΟΗΣ
BFP
TEMPERATURE GAUGE
ΜΕΤΡΗΤΗΣ ΘΕΡΜΟΚΡΑΣΙΑΣ
TI
FLOW TRANSMITTER
ΜΕΤΑΔΟΤΗΣ ΡΟΗΣFT
FLOW SENSOR
ΑΙΣΘΗΤΗΡΑΣ ΡΟΗΣ
SP
DP
DIFFERENTIAL PRESSURE
SENSOR/TRANSMITTER
ΑΙΣΘΗΤΗΡΑΣ ΔΙΑΦΟΡΙΚΗΣ
ΠΙΕΣΗΣ/ΜΕΤΑΔΟΤΗΣ
DIFFERENTIAL PRESSURE
SENSOR/TRANSMITTER
ΑΙΣΘΗΤΗΡΑΣ ΜΕΤΡΗΣΗΣ
ΔΙΑΦΟΡΙΚΗΣ ΠΙΕΣΗΣ
FLOW SWITCH
ΔΙΑΚΟΠΤΗΣ ΡΟΗΣ
DT
DIFFERENTIAL PRESSURE SWITCH
(DIGITAL)
ΔΙΑΚΟΠΤΗΣ ΔΙΑΦΟΡΙΚΗΣ ΠΙΕΣΗΣ
(ΨΗΦΙΑΚΟΣ)
ELECTRIC DAMPER ACTUATOR
ΗΛΕΚΤΡΙΚΟΣ ΕΠΕΝΕΡΓΗΤΗΣ
ΔΙΑΦΡΑΓΜΑΤΟΣ
DA
F
FS
TEMPERATURE SENSOR
/TRANSMITTER
ΑΙΣΘΗΤΗΡΑΣ
ΘΕΡΜΟΚΡΑΣΙΑΣ/ΜΕΤΑΔΟΤΗΣ
HUMIDITY SENSOR/TRANSMITTER
ΑΙΣΘΗΤΗΡΑΣ ΥΓΡΑΣΙΑΣ/ΜΕΤΑΔΟΤΗΣ
T
H
ELECTRIC ACTUATOR
ΗΛΕΚΤΡΙΚΟΣ ΕΠΕΝΕΡΓΗΤΗΣ
M
NORMAL
OPEN
ΚΑΝΟΝΙΚΑ
ΑΝΟΙΚΤΗ
GLOBE VALVE
ΒΑΛΒΙΔΑ ΕΔΡΑΣ
GATE VALVE
ΒΑΛΒΙΔΑ ΣΥΡΤΗ
3-WAY VALVE
ΤΡΙΟΔΗ ΒΑΝΑ
BUTTERFLY VALVE
ΒΑΛΒΙΔΑ ΠΕΤΑΛΟΥΔΑΣ
ANGLE VALVE
ΓΩΝΙΑΚΗ ΒΑΝΑ
PLUG VALVE
BAΛΒΙΔΑ ΒΥΣΜΑΤΟΣ
BALL VALVE
ΣΦΑΙΡΙΚΗ ΒΑΝΑ
NORMAL
CLOSED
ΚΑΝΟΝΙΚΑ
ΚΛΕΙΣΤΗ
D
C
B
1 2 3 4 5
NONE
1615269
DWG
SHEET OF
NAVFAC DRAWING NO.
CONSTR. CONTR. NO.
EPROJECT NO.
SCALE:
N62470-21-C-0005
DESIGN DIRECTOR
BRANCH MANAGER
PM/DM
DES DRW CHK
SATISFACTORY TO DATE
ACTIVITY
FOR COMMANDER NAVFAC
APPROVED
A/E INFO
SEAL
SY
M
DE
SC
RI
PT
IO
N
DA
TE
AP
PR
N
AV
S U
PP
AC
T
SO
U D
A B
AY
N
AV
A L
FA
C
IL
IT
IE
S
EN
G
IN
E
ER
IN
G S
YS
TE
M C
O M
M
AN
D D
E P
AR
TM
E N
T O
F
TH
E N
A
VY
N
AV
AL
F
AC
IL
IT
IE
S E
N G
IN
EE
R
IN
G S
YS
TE
M C
O M
M
AN
D
A
FIRE PROTECTION
N O
R
FO
LK
, V
A A
TL
AN
TI
C
D E
SI
G
N A
N D
C O
N
ST
R U
C
TI
O N
1100 NORTH GLEBE ROAD
SUITE 500
ARLINGTON, VIRGINIA 22201
571.218.1000
FAX: 571.218.1600
D
C
B
A
1 2 3 4 5
RICHARD STEPHENS
TRUEWORTHY,PE / STELMASZEK,RA
PL
O
T
DA
TE
/T
IM
E:
7/
/ 2
1:
:1
PM
C :\U se rs
\C ha nH \D oc um en ts
\P
1- D
1-
M _R
_h ch an 4Z
9N T.
rv t
14 JUL 2021
RECEIVED BY JACOBIE TISDALE
AND STEVE PARK VIA EMAIL
M-001
GSH HC KG
P
C
O M
M U
N
IC
A
TI
O N
C E
N
TE
RS
O
U D
A B
AY
, G
R
EE
C E
G
EN
ER
A
L N
O
TE
S / A
BB
R
EV
IA
TI
O
N S
14089285
ΓΕ
Ν
ΙΚ
ΕΣ
ΣΗ
Μ Ε
ΙΩ
ΣΕ
ΙΣ
/ Σ
ΥΝ
ΤΜ
Η
ΣΕ
ΙΣ
SCE
DPS
F
A
B
C
D
1 2 3 4 5 6 7 98
UPS
ELEC
MENS
137 DEMARC 1
TR G-1
SIPR CAFE
LOBBY
BUNK
QUARTER DECK
STAIR 1
IT LOGISTICS
122BREAK
123DEMARC 2
STAIR 2
N6 MAINTENANCE
RECEIVING
RECYCLE
FIRE PROT
N6 EQUIPMENT
ROOM
A1 M-302
NIPR CAFE
N6 CONF
N6 ID
N6 ISSM
N6
N6 C3P
ELEV
N6 MAINT
N6 STOR
MOTHERS
JAN
WOMENS
CORRIDOR
UPS
A3 M-302
CRAC-09A
FCU-02
CRAC-03A
FCU-06
A1 M-301
CRAC-09B
CRAC-03B
FPB-06
VAV-06
FPB-05
FPB-04
FPB-02
FPB-01
VAV-04
A4 M-302
610x360 RA
BOD 3556
250x200 EA
SA-01
SA-01
SA-01
SA-01
SA-01
SA-02
SA-01
SA-01
SA-01
SA-02
SA-01
28SA-01
SA-01
SA-10
SA-02
SA-01
0x
SA
360x300 SA
0x
SA
200ø SA
EF-02
UH-4
UH-3
EF-01
0x
O A
150x150 OA
BOD 3465
OA-02
OA-03
OA-02
200ø SA
M D
M D
150x150 EA
150x150 EA
150x150 EA
CRAC-04B
CRAHU-01A CRAHU-01B
RA-02
RA-02
CLOSET
OA LOUVER
760X410
3600 MM AFF
760x410 OA
BOD 3598
16 16
EA LOUVER
635X610
3600 MM AFF
RA-01
RA-04
OA-01
L-8
L-9
L-7 640X610
3250 MM AFF
RA-04
RA-01
OA-01
SA-01
RA-02
M-401 C1
VEST
TYP.3
OA-02
OA-02
BH-01
TYP. 6
TYP. 2
TYP. 2
TYP. 2
OA-03
0ø
S A
TYP. 2
TYP. 2
BH-03
TYP.2
150ø SA
FPB-31
RA-02
460x360 RA
BOD 3556
300x300 RA
BOD 3586
TYP.4
250x150 SA
460/250 SA
BOD 3560
TYP. 2
SA-01
SA-01
TYP. 2
OA-04
0x
R A
460x360 EA
300x200 OA
BOD 3440
SA-09
TYP 12
SA-06
SA-06
250x250 SA
BH-06
VEST
SA-06
TYP.2
250x250 RA
A3 M-301
EA-03
EA-03
EA-03
RA-01
SA-01
RA-09
TYP.3
TYP. 2
FSD-9
CRAC-05A
CRAC-05B
SA-02
CRAC-04A
SA-02
SA-12
SA-13
OA-04
150ø OA
BOD 3119
150ø SA 250ø SA
RA-02
A4 M-301
610x360 RA
BOD 3061
610x360 RA
BOD 3554
RA-04
SA-05
520x320 SA
BOD 2998
810x360 RA
BOD 3554
FPB-03
EA-04
250x200 EA
360x150 SA
SA-06
L-25 410X360
3060 MM AFF
L-20 L-21 460X300
3180 MM AFF 510X360
3150 MM AFF
L-22 460X300
3180 MM AFF
L-23 460X360
3150 MM AFF
L-24 300X300
3100 MM AFF
EA-01
EF-14
EF-13EF-12
EF-11
EF-10
EF-15
360x360 EA
BOD 3098
300x300 EA
BOD 3179
360x360 EA
BOD 3150
300x300 EA
BOD 3179
300x300 EA
BOD 3346
360x360 EA
RA-01
510/250 SA
BOD 3560
430ø SA
560x560 EA 460x300 EA
RA-02
300x300 RA
150ø SA
180ø SA
150ø SA
360x250 RA 360x200 RA
200ø SA
0x
SA
53 53
410x350 RA
360x200 RA
FSD-1
TYP.3
150ø SA
150ø SA
150ø SA
150ø SA
150ø SA
200ø SA
300x300 RA
360x200 RA 360x200 RA
300x300 EA
300x300 EA
RA-01
250ø SA180ø SA
300ø SA 200ø SA
410/200 SARA-02
300x150 RA
TYP. 2
SA-07
TYP. 2
FSD-3
FSD-8
250x250 RA
360x200 RA 320x360 RA
150x150 RA
360x150 SA
FSD-6FSD-5
SA-07
354 FSD-4
SD-1 FSD-7
FSD-10
250x250 RA
EF-04EF-03
L-1 350X300
3150 MM AFF
115 SA-08
FSD-2
SA-05
L-2 350X300
3150 MM AFF
SD-2
SD-4 SD-6
SD
-3
SD
-5
SD-9
SD
-1
SD
-8
SD
-7
SD
-1
FSD-11
SD-19 SD-20
SA-07
EA-07
N6 STOR
N6 C3P
210 210
210 210
DXFCU-02B
DXFCU-02A
DXFCU-01A
DXFCU-01B
EA-07
FSD
FSD
200ø SA
D
C
B
1 2 3 4 5
NONE
1615269
DWG
SHEET OF
NAVFAC DRAWING NO.
CONSTR. CONTR. NO.
EPROJECT NO.
SCALE:
N62470-21-C-0005
DESIGN DIRECTOR
BRANCH MANAGER
PM/DM
DES DRW CHK
SATISFACTORY TO DATE
ACTIVITY
FOR COMMANDER NAVFAC
APPROVED
A/E INFO
SEAL
SY
M
DE
SC
RI
PT
IO
N
DA
TE
AP
PR
N
AV
S U
PP
AC
T
SO
U D
A B
AY
N
AV
A L
FA
C
IL
IT
IE
S
EN
G
IN
E
ER
IN
G S
YS
TE
M C
O M
M
AN
D D
E P
AR
TM
E N
T O
F
TH
E N
A
VY
N
AV
AL
F
AC
IL
IT
IE
S E
N G
IN
EE
R
IN
G S
YS
TE
M C
O M
M
AN
D
A
FIRE PROTECTION
N O
R
FO
LK
, V
A A
TL
AN
TI
C
D E
SI
G
N A
N D
C O
N
ST
R U
C
TI
O N
1100 NORTH GLEBE ROAD
SUITE 500
ARLINGTON, VIRGINIA 22201
571.218.1000
FAX: 571.218.1600
D
C
B
A
1 2 3 4 5
RICHARD STEPHENS
TRUEWORTHY,PE / STELMASZEK,RA
PL
O
T
DA
TE
/T
IM
E:
7/
/ 2
1:
:2
PM
C :\U se rs
\C ha nH \D oc um en ts
\P
1- D
1-
M _R
_h ch an 4Z
9N T.
rv t
14 JUL 2021
RECEIVED BY JACOBIE TISDALE
AND STEVE PARK VIA EMAIL
MH101
GSH HC KG
P
C
O M
M U
N
IC
A
TI
O N
C E
N
TE
RS
O
U D
A B
AY
, G
R
EE
C E
H
VA
C F
LO
O
R P
LA
N
S -G
R O
U N
D F
LO
O
R
14089286
K
AT
O Ψ Ε
ΙΣ
H V
AC
-ΙΣ
Ο
ΓΕ
ΙΟ
SCE
DPS
1 : 100A1 GROUND FLOOR-HVAC IΣΟΓΕΙΟ-HVAC
0 5000 10000
MILLIMETRESSCALE 1:100
30001000
PLAN NORTH
A MAINTAIN MANUFACTURER'S RECOMMENDED CLEARANCES
ON ALL EQUIPMENT.
ΔΙΑΤΗΡΗΣΤΕ ΤΟΝ ΣΥΝΙΣΤΩΜΕΝΟ ΕΛΕΥΘΕΡΟ ΧΩΡΟ ΑΠΟ
ΤΟΝ ΚΑΤΑΣΚΕΥΑΣΤΗ ΓΙΑ ΟΛΟ ΤΟΝ ΕΞΟΠΛΙΣΜΟ
B PROVIDE CLEARANCES FOR ALL ELECTRICAL AND
CONTROL PANELS PER NEC.
ΕΦΟΔΙΑΣΤΕ ΤΟΥΣ ΗΛΕΚΤΡΟΛΟΓΙΚΟΥΣ ΠΙΝΑΚΕΣ ΚΑΙ ΤΟΥΣ
ΠΙΝΑΚΕΣ ΕΛΕΓΧΟΥ ΜΕ ΤΟΝ ΑΠΑΙΤΟΥΜΕΝΟ ΕΛΕΥΘΕΡΟ
ΧΩΡΟ ΣYMΦΩNA ME ΤΟΝ ΕΘΝΙΚΟ ΗΛΕΚΤΡΟΛΟΓΙΚΟ ΚΩΔΙΚΑ.
C PROVIDE REMOTE DAMPER ACTUATORS OR ACCESS PANEL
FOR ALL DAMPERS LOCATED ABOVE HARD CEILINGS.
REFER TO ARCHITECTURE DRAWINGS FOR LOCATIONS
ΕΦΟΔΙΑΣΤΕ ΜΕ ΑΠΟΜΟΜΑΚΡΥΣΜΕΝΟ ΕΝΕΡΓΟΠΟΙΗΤΗ
ΔΙΑΦΡΑΓΜΑΤΟΣ Ή ME ΠΙΝΑΚΑ ΠΡΟΣΒΑΣΗΣ ΓΙΑ ΟΛΑ ΤΑ
ΔΙΑΦΡΑΓΜΑΤΑ ΠΟΥ ΒΡΙΣΚΟΝΤΑΙ ΠΑΝΩ ΑΠΟ ΤΗΝ
ΨΕΥΔΟΟΡΟΦΗ. ΑΝΑΤΡΕΞΤΕ ΣΤΑ ΑΡΧΙΤΕΚΤΟΝΙΚΑ ΣΧΕΔΙΑ ΓΙΑ
ΤΙΣ ΘΕΣΕΙΣ.
D REFER TO PIPING PLAN FOR THERMOSTAT LOCATION.
ΑΝΑΤΡΕΞΤΕ ΣΤΑ ΣΧΕΔΙΑ ΣΩΛΗΝΩΣΕΩΝ ΓΙΑ ΤΗ ΘΕΣΗ ΤΟΥ
ΘΕΡΜΟΣΤΑΤΗ
E PROVIDE BALANCING DAMPER AT EACH TAKEOFF
ΠΡΟΜΗΘΕΥΣΤΕ ΔΙΑΦΡΑΓΜΑΤΑ ΕΞΙΣΟΡΡΟΠΙΣΗΣ ΣΕ ΚΑΘΕ
ΚΛΑΔΟ
F REFER TO SECURITY, FIRE PROTECTION, AND
ARCHITECTURE FOR SECURE WALL RATINGS, FIRE RATED
WALLS AND PENETRATION DETAILS.
ΑΝΑΤΡΕΞΤΕ ΣΤΗΝ ΑΣΦΑΛΕΙΑ, ΣΤΗΝ ΠΥΡΟΠΡΟΣΤΑΣΙΑ ΚΑΙ
ΣΤΑ ΑΡΧΙΤΕΚΤΟΝΙΚΑ ΓΙΑ ΤΟΥΣ ΠΥΡΑΝΤΟΧΟΥΣ ΤΟΙΧΟΥΣ ΚΑΙ
ΤΙΣ ΛΕΠΤΟΜΕΡΕΙΕΣ ΤΩΝ ΔΙΑΤΡΗΣΕΩΝ.
G ALL SUSPENDED EQUIPMENT GREATER THAN 14 KG MUST
BE SUPPORTED WITH BRACING DESIGNED TO SUPPORT A
MINIMUM OF 0.5X THE EQUIPMENT WEIGHT IN THE
HORIZONTAL DIRECTION, AND 1.5X THE EQUIPMENT
WEIGHT IN THE VERTICAL DIRECTION IN ACCORDANCE
WITH UFC 4-010-01.
OΛΟΣ Ο ΑΝΑΡΤΩΜΕΝΟΣ ΕΞΟΠΛΙΣΜΟΣ ΜΕΓΑΛΥΤΕΡΟΣ ΤΩΝ
14KG ΘΑ ΠΡΕΠΕΙ NA ΕΝΙΣΧΥΘΕΙ ME ΣΥΝΔΕΣΜΟΥΣ.
ΣΧΕΔΙΑΣΜΕΝΟΥΣ ΝΑ ΕΝΙΣΧΥΣΟΥΝ ΤΟ ΕΛΑΧΙΣΤΟ 0,5X ΤΟ
ΒΑΡΟΣ ΤΟΥ ΕΞΟΠΛΙΣΜΟΥ ΣΤΗΝ ΟΡΙΖΟΝΤΙΑ ΚΑΤΕΥΘΥΝΣΗ
ΚΑΙ 1,5X ΤΟ ΒΑΡΟΣ ΤΟΥ ΕΞΟΠΛΙΣΜΟΥ ΣΤΗΝ ΚΑΘΕΤΗ
ΚΑΤΕΥΘΥΝΣΗ. ΟΔΗΓΙΑ ΣΥΜΦΩΝΗ ΜΕ ΤΟ UFC 4-010-01.
H FPB AND VAV TERMINAL UNIT DUCT CONNECTIONS TO
MATCH BOX SIZE.
H ΣΥΝΔΕΣΗ ΤΩΝ FPB ΚΑΙ VAV ΤΕΡΜΑΤΙΚΩΝ ΜΟΝΑΔΩΝ
ΑΕΡΑΓΩΓΟΥ ΠΡΕΠΕΙ ΝΑ ΤΑΙΡΙΑΖΕΙ ΜΕ ΤΟ ΜΕΓΕΘΟΣ ΤΩΝ
ΚΟΥΤΙΩΝ.
I DUCT MUST BE MINIMUM OF 26 GAGE. DIFFUSER/GRILLE
CONNECTION TO MATCH THE NECK CONNECTION.
O AEΡΑΓΩΓΟΣ ΠΡΕΠΕΙ ΝΑ ΕΙΝΑΙ ΤΟΥΛΑΧΙΣΤΟΝ 26
GAGE(0,405mm). Η ΣΥΝΔΕΣΗ ΣΤΟΜΙΩΝ/ΓΡΙΛΙΕΣ ΠΡΕΠΕΙ ΝΑ
ΤΑΙΡΙΑΖΕΙ ΜΕ ΤΗΝ ΣΥΝΔΕΣΗ ΤΟΥ ΛΑΙΜΟΥ.
J REFER TO ARCHITECTURE DRAWING FOR DUCT
PENETRATIONS DETAIL.
ΑΝΑΤΡΕΞΕ ΣΤΑ ΑΡΧΙΤΕΚΤΟΝΙΚΑ ΣΧΕΔΙΑ ΓΙΑ ΤΙΣ
ΛΕΠΤΟΜΕΡΕΙΕΣ ΤΩΝ ΔΙΑΤΡΗΣΕΩΝ ΓΙΑ ΤΟΥΣ ΑΕΡΑΓΩΓΟΥΣ
K BRACE EQUIPMENT WEIGHING OVER 14 KG PER DETAIL C4
ON M-505.
ΣΤΗΡΙΓΜΑ ΕΞΟΠΛΙΣΜΟΥ ΠΟΥ ΖΥΓΙΖΕΙ ΠΑΝΩ ΑΠΟ 14KG ΓΙΑ
ΛΕΠΤΟΜΕΡΙΑ C4 ΣΤΟ Μ-505
L VAV PRIMARY AIR DISTRIBUTION DUCT MUST BE ROUND OR
OVAL PREFABRICATED DUCT.
Ο ΠΡΩΤΕΥΩΝ ΑΕΡΑΓΩΓΟΣ ΔΙΑΝΟΜΗΣ ΑΕΡΑ ΤΟΥ VAV ΘΑ
ΠΡΕΠΕΙ ΝΑ ΕΙΝΑΙ ΕΙΤΕ ΣΤΡΟΓΓΥΛΟΣ ΕΙΤΕ
ΠΡΟΚΑΤΑΣΚΕΥΑΣΜΕΝΟΣ ΟΒΑΛ.
SHEET KEYED NOTES:
ΠΑΡΑΤΗΡΗΣΕΙΣ ΣΧΕΔΙΟΥ:
GENERAL NOTES:
ΓΕΝΙΚΕΣ ΠΑΡΑΤΗΡΗΣΕΙΣ:
210 PROVIDE SECURE AREA DUCT PENETRATION. REFER
TO M-515 AND M-514 FOR DETAILS.
ΠΡΟBΛΕΨΤΕ ΔΙΑΤΡΗΣΗ ΑΕΡΑΓΩΓΟΥ ΣΕ ΑΣΦΑΛΗ
ΠΕΡΙΟΧΗ. ΑΝΑΤΡΕΞΕ ΓΙΑ ΛΕΠΤΟΜΕΡΕΙΕΣ ΣΤΟ Μ-515 ΚΑΙ
ΣΤΟ Μ-514
213 PROVIDE ELECTRICAL ENCLOSURE ON THE OPPOSITE
SIDE OF THE VAV BOX.
ΠΡΟΜΗΘΕΥΣΤΕ ΗΛΕΚΤΡΙΚΟ ΠΙΝΑΚΑ ΣΤΗΝ ΑΠΕΝΑΝΤΙ
ΠΛΕΥΡΑ ΑΠΟ ΤΟ ΚΟΥΤΙ VAV.
216 PROVIDE SECURE AREA DUCT PENETRATION. REFER
TO C1/M-504 FOR DETAILS.
ΠΡΟBΛΕΨΤΕ ΔΙΑΤΡΗΣΗ ΑΕΡΑΓΩΓΟΥ ΣΕ ΑΣΦΑΛΗ
ΠΕΡΙΟΧΗ. ΑΝΑΤΡΕΞΕ ΓΙΑ ΛΕΠΤΟΜΕΡΕΙΕΣ ΣΤΟ C1/Μ-504
79 EXHAUST FAN FOR CLEAN AGENT EXHAUST. PROVIDE A
KEY OPERATED MANUAL ACTIVATION SWITCH FOR
EXHAUST FAN AND PERMANENT SIGNAGE TO INDICATE
FIRE SUPPRESSION EXHAUST SYSTEM FOR FIRE
DEPARTMENT USE ONLY. LOCATE CLEAN AGENT
EXHAUST FAN MANUAL SWITCH OUTSIDE THE ROOM IT
SERVES ADJACENT TO THE ENTRY DOOR.
ΑΝΕΜΙΣΤΗΡΑΣ ΕΞΑΕΡΙΣΜΟΥ ΓΙΑ ΕΞΑΕΡΙΣΜΟ
ΠΥΡΟΣΒΕΣΗΣ ΚΑΘΑΡΟΥ ΠΑΡΑΓΟΝΤΑ. ΠΡΟΜΗΘΕΥΣΤΕ
ΔΙΑΚΟΠΤΗ ΧΕΙΡΟΚΙΝΗΤΗΣ ΛΕΙΤΟΥΡΓΙΑΣ ΜΕ ΚΛΕΙΔΙ ΓΙΑ
ΤΟΝ ΕΞΑΕΡΙΣΤΗΡΑ ΚΑΙ ΜΙΑ ΜΟΝΙΜΗ ΕΠΙΓΡΑΦΗ ΝΑ
ΥΠΟΔΕΙΚΝΥΕΙ ΣΥΣΤΗΜΑ ΕΞΑΕΡΙΣΜΟΥ ΚΑΤΑΠΝΙΞΗΣ
ΠΥΡΚΑΓΙΑΣ ΠΥΡΟΣΒΕΣΤΙΚΗ ΜΟΝΟ. Ο ΧΕΙΡΟΚΙΝΗΤΟΣ
ΔΙΑΚΟΠΤΗΣ ΤΟΥ ΕΞΑΕΡΙΣΤΗΡΑ ΠΥΡΟΣΒΕΣΗΣ ΘΑ
ΤΟΠΟΘΕΤΗΘΕΙ ΕΞΩ ΑΠΟ ΤΟ ΔΩΜΑΤΙΟ ΑΚΡΙΒΩΣ ΔΙΠΛΑ
ΣΤΗΝ ΠΟΡΤΑ ΕΙΣΟΔΟΥ.
115 PROVIDE AN INDICATOR LIGHT AT THE UPS DOOR
ENTRY INDICATING GREEN FOR FAN IS RUNNING AND
RED FOR FAN IS NOT RUNNING.
ΠΡΟΜΗΘΕΥΣΤΕ ΦΩΤΕΙΝΗ ΕΝΔΕΙΞΗ ΣΤΗΝ ΠΟΡΤΑ
ΕΙΣΟΔΟΥ ΤΟΥ UPS. ΠΡΑΣΙΝΗ ΕΝΔΕΙΞΗ ΟΤΑΝ Ο
ΑΝΕΜΙΣΤΗΡΑΣ ΛΕΙΤΟΥΓΕΙ ΚΑΙ ΚΟΚΚΙΝΗ ΟΤΑΝ Ο
ΑΝΕΜΙΣΤΗΡΑΣ ΔΕΝ ΛΕΙΤΟΥΡΓΕΙ.
52 MOTORIZED CONTROL DAMPER FOR THE CLEAN AGENT
DISCHARGE. DAMPER TO CLOSE PRIOR TO THE CLEAN
AGENT DISCHARGE. THE DAMPER WILL BE
CONTROLLED BY THE CLEAN AGENT PANEL.
ΗΛΕΚΡΟΚΙΝΗΤΟ ΔΙΑΦΡΑΓΜΑ ΓΙΑ ΚΑΘΑΡΟΥ ΠΑΡΑΓΟΝΤΑ
ΠΥΡΟΣΒΕΣΗ. ΤΟ ΔΙΑΦΡΑΓΜΑ ΚΛΕΙΝΕΙ ΠΡΙΝ ΤΗΝ
ΠΥΡΟΣΒΕΣΗ ΚΑΘΑΡΟΥ ΠΑΡΑΓΟΝΤΑ. ΤΟ ΔΙΑΦΡΑΓΜΑ
ΕΛΕΓΧΕΤΑΙ ΑΠΟ ΤΟΝ ΠΙΝΑΚΑ ΠΥΡΟΣΒΕΣΗΣ ΚΑΘΑΡΟΥ
ΠΑΡΑΓΟΝΤΑ 0
53 INSTALL WIRE MESH INSECT SCREEN.
ΕΓΚΑΤΑΣΤΗΣΤΕ ΠΛΕΓΜΑ ΠΡΟΣΤΑΣΙΑΣ ΑΠΟ ΣΥΡΜΑ, ΓΙΑ
ΤΑ ΕΝΤΟΜΑ.
78 RECEIVING AREA FAN IS A 2-SPEED FAN WITH
THERMOSTAT CONTROL. LOW SPEED PROVIDES CODE
REQUIRED VENTILATION.
ΠΕΡΙΟΧΗ ΛΗΨΗΣ ΑΝΕΜΙΣΤΗΡΑ ΕΙΝΑΙ ΔΥΟ ΤΑΧΥΤΗΤΩΝ
ΑΝΕΜΙΣΤΗΡΑΣ ΜΕ ΕΛΕΓΧΟ ΑΠΟ ΘΕΡΜΟΣΤΑΤΗ. ΣΤΗ
ΧΑΜΗΛΗ ΤΑΧΥΤΗΤΑ ΚΑΛΥΠΤΕΙ ΤΙΣ ΑΠΑΙΤΗΣΕΙΣ ΤΟΥ
ΚΩΔΙΚΑ ΑΕΡΙΣΜΟΥ
16 PROVIDE A FULL SIZE RETURN DUCT CONNECTION TO
ABOVE THE SUSPENDED CEILING.
ΠΡΟΜΗΘΕΥΣΤΕ ΜΕ ΑΕΡΑΓΩΓΟ ΕΠΙΣΤΡΟΦΗΣ ΠΛΗΡΟΥΣ
ΜΕΓΕΘΟΥΣ ΠΑΝΩ ΑΠΟ ΤΗΝ ΨΕΥΔΟΟΡΟΦΗ
27 PROVIDE EMERGENCY AIR DISTRIBUTION SHUT-OFF
SWITCH.
ΠΡΟΜΗΘΕΥΣΤΕ ΔΙΑΚΟΠΤΗ ΕΚΤΑΚΤΟΥ ΑΝΑΓΚΗΣ
ΔΙΑΚΟΠΗΣ ΑΕΡΑ.
32 400X260 RA FROM FIRST LEVEL.
400X260 RA ΑΠΟ ΤΟΝ ΠΡΩΤΟ ΟΡΟΦΟ
51 SEAL UNDERFLOOR WALL PENETRATIONS AND WALL TO
FLOOR SEAMS TO MAINTAIN SUPPLY AIR PLENUM
PRESSURIZATION.
ΜΟΝΩΣΤΕ TIΣ ΔΙΑΤΡΗΣΕΙΣ ΣΤΟΥΣ ΤΟΙΧΟΥΣ ΚΑΤΩ ΑΠΟ
ΤΟ ΠΑΤΩΜΑ ΚΑΙ ΤΙΣ ΡΑΦΕΣ ΜΕΤΑΞΥ ΤΟΙΧΟΥ ΚΑΙ
ΔΑΠΕΔΟΥ ΓΙΑ ΝΑ ΔΙΑΤΗΡΗΘΕΙ Η ΠΙΕΣΗ ΤΟΥ ΑΕΡΑ
ΠΡΟΣΑΓΩΓΗΣ
F
B
C
D
1 2 3 4 5 6 7 98
N9 MAINTENANCE
N9 OPEN OFFICE
STAIR 2
SEC MNGR
NETWORK DIST
AREA
TR 1-1
STAIR 1
A1 M-302
FIN ANLS
SN ENLIST
TECH DIR
N00 COMMAND
ELEC
CORRIDOR
WOMENS
MENS
N9 BCO
ELEV
BREAK
JAN
UNCLASS CONF
A3 M-302
FCU-04
CRAC-06A
A1 M-301
VAV-01
VAV-02
VAV-07
FPB-07 FPB-25 FPB-08
A4 M-302
360x200 EA
SA-01
SA-01
SA-01
SA-01
SA-01
SA-01
SA-01
SA-01
LNSC DIR
LNSC ANALYSIS
230ø SA
280ø SA 360ø SA
0ø
S A
0ø
S A
230ø SA
250ø SA
200x250 SA 230ø SA
280x280 SA
CORRIDOR
OA-02
230ø SA
180ø SA
180ø SA
N3 LNSC
300x150 EA
CRAC-06B
RA-02
330ø SA
RA-02
RA-02
RA-02
RA-01
RA-02
RA-07
RA-02
M-401 C3
TYP. 6
SA-11
TYP. 9
TYP. 4
TYP. 8
TYP. 2
610/410 SA
BOD 3373
SA-10
TYP. 2
OA-02
TYP. 2
TYP. 5
250/200 SA
860x460 RA
BOD 3367
SA-01
TYP. 2
910x460 RA
BOD 3367
SA-01
SA-01
SA-01
230ø SA
360x200 EA
BOD 3072
520x320 SA
0ø
S A
SA-01
A3 M-301
EA-06
EA-06
EA-03
FPB-32
FSD-17
RA-10
TYP. 2
SA-10
200x200 OA
BOD 3252
230ø SA
230ø SA
STORAGE
BD
D
BD
D
OA-01
FSD-16
OA-01
EA-01
L-27
EF-17
300X300
3200 MM AFF
L-26
EF-16
410X360
3350 MM AFF
RA-12
SA-01
150ø SA
710x460 RA 380ø SA
560/410 SA
180ø SA
180ø SA
150ø SA
150ø SA
230ø SA
320x360 RA
320x360 RA
0ø
S A
150ø SA
510/410 SA
RA-01
300x300 EA300x300 EA
MD
300x200 RA
510x300 RA
150ø SA
VAV-08
150ø SA
VAV-03
VAV-10
150ø SA
200ø SA
150ø SA
150ø SA
200ø SA
150ø SA
SA-06
FSD-15
SA-05
320x360 RA
810/360 SA
610x300 SA
360x300 SA
510x300 SA
250x250 RA
RA-10
FPB-11
RA-09
SA-08
SD-13
SD-11
SD-12
SD-14
FSD-12
TYP.2 DXFCU-03A DXFCU-03B
EF-07
410x350 RA
D
C
B
1 2 3 4 5
NONE
1615269
DWG
SHEET OF
NAVFAC DRAWING NO.
CONSTR. CONTR. NO.
EPROJECT NO.
SCALE:
N62470-21-C-0005
DESIGN DIRECTOR
BRANCH MANAGER
PM/DM
DES DRW CHK
SATISFACTORY TO DATE
ACTIVITY
FOR COMMANDER NAVFAC
APPROVED
A/E INFO
SEAL
SY
M
DE
SC
RI
PT
IO
N
DA
TE
AP
PR
N
AV
S U
PP
AC
T
SO
U D
A B
AY
N
AV
A L
FA
C
IL
IT
IE
S
EN
G
IN
E
ER
IN
G S
YS
TE
M C
O M
M
AN
D D
E P
AR
TM
E N
T O
F
TH
E N
A
VY
N
AV
AL
F
AC
IL
IT
IE
S E
N G
IN
EE
R
IN
G S
YS
TE
M C
O M
M
AN
D
A
FIRE PROTECTION
N O
R
FO
LK
, V
A A
TL
AN
TI
C
D E
SI
G
N A
N D
C O
N
ST
R U
C
TI
O N
1100 NORTH GLEBE ROAD
SUITE 500
ARLINGTON, VIRGINIA 22201
571.218.1000
FAX: 571.218.1600
D
C
B
A
1 2 3 4 5
RICHARD STEPHENS
TRUEWORTHY,PE / STELMASZEK,RA
PL
O
T
DA
TE
/T
IM
E:
7/
/ 2
1:
:3
PM
C :\U se rs
\C ha nH \D oc um en ts
\P
1- D
1-
M _R
_h ch an 4Z
9N T.
rv t
14 JUL 2021
RECEIVED BY JACOBIE TISDALE
AND STEVE PARK VIA EMAIL
MH102
GSH HC KG
P
C
O M
M U
N
IC
A
TI
O N
C E
N
TE
RS
O
U D
A B
AY
, G
R
EE
C E
H
VA
C F
LO
O
R P
LA
N
S -F
IR
ST
F
LO
O R
14089287
Κ
ΑΤ
Ο Ψ
ΕΙ
Σ
H
VA
C -Π Ρ Ω
ΤΟ
Σ Ο Ρ Ο Φ Ο Σ
SCE
DPS
1 : 100A1 FIRST FLOOR-HVAC ΠΡΩΤΟΣ ΟΡΟΦΟΣ HVAC
PLAN NORTH
0 5000 10000
MILLIMETRESSCALE 1:100
30001000
53 INSTALL WIRE MESH INSECT SCREEN.
ΕΓΚΑΤΑΣΤΗΣΤΕ ΠΛΕΓΜΑ ΠΡΟΣΤΑΣΙΑΣ ΑΠΟ ΣΥΡΜΑ, ΓΙΑ
ΤΑ ΕΝΤΟΜΑ.
79 EXHAUST FAN FOR CLEAN AGENT EXHAUST. PROVIDE A
KEY OPERATED MANUAL ACTIVATION SWITCH FOR
EXHAUST FAN AND PERMANENT SIGNAGE TO INDICATE
FIRE SUPPRESSION EXHAUST SYSTEM FOR FIRE
DEPARTMENT USE ONLY. LOCATE CLEAN AGENT
EXHAUST FAN MANUAL SWITCH OUTSIDE THE ROOM IT
SERVES ADJACENT TO THE ENTRY DOOR.
ΑΝΕΜΙΣΤΗΡΑΣ ΕΞΑΕΡΙΣΜΟΥ ΓΙΑ ΕΞΑΕΡΙΣΜΟ
ΠΥΡΟΣΒΕΣΗΣ ΚΑΘΑΡΟΥ ΠΑΡΑΓΟΝΤΑ. ΠΡΟΜΗΘΕΥΣΤΕ
ΔΙΑΚΟΠΤΗ ΧΕΙΡΟΚΙΝΗΤΗΣ ΛΕΙΤΟΥΡΓΙΑΣ ΜΕ ΚΛΕΙΔΙ ΓΙΑ
ΤΟΝ ΕΞΑΕΡΙΣΤΗΡΑ ΚΑΙ ΜΙΑ ΜΟΝΙΜΗ ΕΠΙΓΡΑΦΗ ΝΑ
ΥΠΟΔΕΙΚΝΥΕΙ ΣΥΣΤΗΜΑ ΕΞΑΕΡΙΣΜΟΥ ΚΑΤΑΠΝΙΞΗΣ
ΠΥΡΚΑΓΙΑΣ ΠΥΡΟΣΒΕΣΤΙΚΗ ΜΟΝΟ. Ο ΧΕΙΡΟΚΙΝΗΤΟΣ
ΔΙΑΚΟΠΤΗΣ ΤΟΥ ΕΞΑΕΡΙΣΤΗΡΑ ΠΥΡΟΣΒΕΣΗΣ ΘΑ
ΤΟΠΟΘΕΤΗΘΕΙ ΕΞΩ ΑΠΟ ΤΟ ΔΩΜΑΤΙΟ ΑΚΡΙΒΩΣ ΔΙΠΛΑ
ΣΤΗΝ ΠΟΡΤΑ ΕΙΣΟΔΟΥ.
116 LOCATE THE BUILDING DIFFERENTIAL PRESSURE
SENSOR IN THE CORRIDOR.
ΤΟΠΟΘΕΤΗΣΤΕ ΤΟΝ ΑΙΣΘΗΤΗΡΑ ΔΙΑΦΟΡΙΚΗΣ ΠΙΕΣΗΣ
ΤΟΥ ΚΤΙΡΙΟΥ ΣΤΟΝ ΔΙΑΔΡΟΜΟ.
27 PROVIDE EMERGENCY AIR DISTRIBUTION SHUT-OFF
SWITCH.
ΠΡΟΜΗΘΕΥΣΤΕ ΔΙΑΚΟΠΤΗ ΕΚΤΑΚΤΟΥ ΑΝΑΓΚΗΣ
ΔΙΑΚΟΠΗΣ ΑΕΡΑ.
34 360X200 RA FROM SECOND LEVEL.
360X200 RA ΑΠΟ ΤΟΝ ΔΕΥΤΕΡΟ ΟΡΟΦΟ
36 460X200 RA DOWN TO GROUND LEVEL.
460X200 RA ΚΑΤΩ ΠΡΟΣ ΤΟ ΙΣΟΓΕΙΟ
52 MOTORIZED CONTROL DAMPER FOR THE CLEAN AGENT
DISCHARGE. DAMPER TO CLOSE PRIOR TO THE CLEAN
AGENT DISCHARGE. THE DAMPER WILL BE
CONTROLLED BY THE CLEAN AGENT PANEL.
ΗΛΕΚΡΟΚΙΝΗΤΟ ΔΙΑΦΡΑΓΜΑ ΓΙΑ ΚΑΘΑΡΟΥ ΠΑΡΑΓΟΝΤΑ
ΠΥΡΟΣΒΕΣΗ. ΤΟ ΔΙΑΦΡΑΓΜΑ ΚΛΕΙΝΕΙ ΠΡΙΝ ΤΗΝ
ΠΥΡΟΣΒΕΣΗ ΚΑΘΑΡΟΥ ΠΑΡΑΓΟΝΤΑ. ΤΟ ΔΙΑΦΡΑΓΜΑ
ΕΛΕΓΧΕΤΑΙ ΑΠΟ ΤΟΝ ΠΙΝΑΚΑ ΠΥΡΟΣΒΕΣΗΣ ΚΑΘΑΡΟΥ
ΠΑΡΑΓΟΝΤΑ 0
A MAINTAIN MANUFACTURER'S RECOMMENDED CLEARANCES
ON ALL EQUIPMENT.
ΔΙΑΤΗΡΗΣΤΕ ΤΟΝ ΣΥΝΙΣΤΩΜΕΝΟ ΕΛΕΥΘΕΡΟ ΧΩΡΟ ΑΠΟ
ΤΟΝ ΚΑΤΑΣΚΕΥΑΣΤΗ ΓΙΑ ΟΛΟ ΤΟΝ ΕΞΟΠΛΙΣΜΟ
B PROVIDE CLEARANCES FOR ALL ELECTRICAL AND
CONTROL PANELS PER NEC.
ΕΦΟΔΙΑΣΤΕ ΤΟΥΣ ΗΛΕΚΤΡΟΛΟΓΙΚΟΥΣ ΠΙΝΑΚΕΣ ΚΑΙ ΤΟΥΣ
ΠΙΝΑΚΕΣ ΕΛΕΓΧΟΥ ΜΕ ΤΟΝ ΑΠΑΙΤΟΥΜΕΝΟ ΕΛΕΥΘΕΡΟ
ΧΩΡΟ ΣYMΦΩNA ME ΤΟΝ ΕΘΝΙΚΟ ΗΛΕΚΤΡΟΛΟΓΙΚΟ ΚΩΔΙΚΑ.
C PROVIDE REMOTE DAMPER ACTUATORS OR ACCESS PANEL
FOR ALL DAMPERS LOCATED ABOVE HARD CEILINGS.
REFER TO ARCHITECTURE DRAWINGS FOR LOCATIONS
ΕΦΟΔΙΑΣΤΕ ΜΕ ΑΠΟΜΟΜΑΚΡΥΣΜΕΝΟ ΕΝΕΡΓΟΠΟΙΗΤΗ
ΔΙΑΦΡΑΓΜΑΤΟΣ Ή ME ΠΙΝΑΚΑ ΠΡΟΣΒΑΣΗΣ ΓΙΑ ΟΛΑ ΤΑ
ΔΙΑΦΡΑΓΜΑΤΑ ΠΟΥ ΒΡΙΣΚΟΝΤΑΙ ΠΑΝΩ ΑΠΟ ΤΗΝ
ΨΕΥΔΟΟΡΟΦΗ. ΑΝΑΤΡΕΞΤΕ ΣΤΑ ΑΡΧΙΤΕΚΤΟΝΙΚΑ ΣΧΕΔΙΑ ΓΙΑ
ΤΙΣ ΘΕΣΕΙΣ.
D REFER TO PIPING PLAN FOR THERMOSTAT LOCATION.
ΑΝΑΤΡΕΞΤΕ ΣΤΑ ΣΧΕΔΙΑ ΣΩΛΗΝΩΣΕΩΝ ΓΙΑ ΤΗ ΘΕΣΗ ΤΟΥ
ΘΕΡΜΟΣΤΑΤΗ
E PROVIDE BALANCING DAMPER AT EACH TAKEOFF
ΠΡΟΜΗΘΕΥΣΤΕ ΔΙΑΦΡΑΓΜΑΤΑ ΕΞΙΣΟΡΡΟΠΙΣΗΣ ΣΕ ΚΑΘΕ
ΚΛΑΔΟ
F REFER TO SECURITY, FIRE PROTECTION, AND
ARCHITECTURE FOR SECURE WALL RATINGS, FIRE RATED
WALLS AND PENETRATION DETAILS.
ΑΝΑΤΡΕΞΤΕ ΣΤΗΝ ΑΣΦΑΛΕΙΑ, ΣΤΗΝ ΠΥΡΟΠΡΟΣΤΑΣΙΑ ΚΑΙ
ΣΤΑ ΑΡΧΙΤΕΚΤΟΝΙΚΑ ΓΙΑ ΤΟΥΣ ΠΥΡΑΝΤΟΧΟΥΣ ΤΟΙΧΟΥΣ ΚΑΙ
ΤΙΣ ΛΕΠΤΟΜΕΡΕΙΕΣ ΤΩΝ ΔΙΑΤΡΗΣΕΩΝ.
G ALL SUSPENDED EQUIPMENT GREATER THAN 14 KG MUST
BE SUPPORTED WITH BRACING DESIGNED TO SUPPORT A
MINIMUM OF 0.5X THE EQUIPMENT WEIGHT IN THE
HORIZONTAL DIRECTION, AND 1.5X THE EQUIPMENT
WEIGHT IN THE VERTICAL DIRECTION IN ACCORDANCE
WITH UFC 4-010-01.
OΛΟΣ Ο ΑΝΑΡΤΩΜΕΝΟΣ ΕΞΟΠΛΙΣΜΟΣ ΜΕΓΑΛΥΤΕΡΟΣ ΤΩΝ
14KG ΘΑ ΠΡΕΠΕΙ NA ΕΝΙΣΧΥΘΕΙ ME ΣΥΝΔΕΣΜΟΥΣ.
ΣΧΕΔΙΑΣΜΕΝΟΥΣ ΝΑ ΕΝΙΣΧΥΣΟΥΝ ΤΟ ΕΛΑΧΙΣΤΟ 0,5X ΤΟ
ΒΑΡΟΣ ΤΟΥ ΕΞΟΠΛΙΣΜΟΥ ΣΤΗΝ ΟΡΙΖΟΝΤΙΑ ΚΑΤΕΥΘΥΝΣΗ
ΚΑΙ 1,5X ΤΟ ΒΑΡΟΣ ΤΟΥ ΕΞΟΠΛΙΣΜΟΥ ΣΤΗΝ ΚΑΘΕΤΗ
ΚΑΤΕΥΘΥΝΣΗ. ΟΔΗΓΙΑ ΣΥΜΦΩΝΗ ΜΕ ΤΟ UFC 4-010-01.
H FPB AND VAV TERMINAL UNIT DUCT CONNECTIONS TO
MATCH BOX SIZE.
H ΣΥΝΔΕΣΗ ΤΩΝ FPB ΚΑΙ VAV ΤΕΡΜΑΤΙΚΩΝ ΜΟΝΑΔΩΝ
ΑΕΡΑΓΩΓΟΥ ΠΡΕΠΕΙ ΝΑ ΤΑΙΡΙΑΖΕΙ ΜΕ ΤΟ ΜΕΓΕΘΟΣ ΤΩΝ
ΚΟΥΤΙΩΝ.
I DUCT MUST BE MINIMUM OF 26 GAGE. DIFFUSER/GRILLE
CONNECTION TO MATCH THE NECK CONNECTION.
O AEΡΑΓΩΓΟΣ ΠΡΕΠΕΙ ΝΑ ΕΙΝΑΙ ΤΟΥΛΑΧΙΣΤΟΝ 26
GAGE(0,405mm). Η ΣΥΝΔΕΣΗ ΣΤΟΜΙΩΝ/ΓΡΙΛΙΕΣ ΠΡΕΠΕΙ ΝΑ
ΤΑΙΡΙΑΖΕΙ ΜΕ ΤΗΝ ΣΥΝΔΕΣΗ ΤΟΥ ΛΑΙΜΟΥ.
J REFER TO ARCHITECTURE DRAWING FOR DUCT
PENETRATIONS DETAIL.
ΑΝΑΤΡΕΞΕ ΣΤΑ ΑΡΧΙΤΕΚΤΟΝΙΚΑ ΣΧΕΔΙΑ ΓΙΑ ΤΙΣ
ΛΕΠΤΟΜΕΡΕΙΕΣ ΤΩΝ ΔΙΑΤΡΗΣΕΩΝ ΓΙΑ ΤΟΥΣ ΑΕΡΑΓΩΓΟΥΣ
K BRACE EQUIPMENT WEIGHING OVER 14 KG PER DETAIL C4
ON M-505.
ΣΤΗΡΙΓΜΑ ΕΞΟΠΛΙΣΜΟΥ ΠΟΥ ΖΥΓΙΖΕΙ ΠΑΝΩ ΑΠΟ 14KG ΓΙΑ
ΛΕΠΤΟΜΕΡΙΑ C4 ΣΤΟ Μ-505
L VAV PRIMARY AIR DISTRIBUTION DUCT MUST BE ROUND OR
OVAL PREFABRICATED DUCT.
Ο ΠΡΩΤΕΥΩΝ ΑΕΡΑΓΩΓΟΣ ΔΙΑΝΟΜΗΣ ΑΕΡΑ ΤΟΥ VAV ΘΑ
ΠΡΕΠΕΙ ΝΑ ΕΙΝΑΙ ΕΙΤΕ ΣΤΡΟΓΓΥΛΟΣ ΕΙΤΕ
ΠΡΟΚΑΤΑΣΚΕΥΑΣΜΕΝΟΣ ΟΒΑΛ.
SHEET KEYED NOTES:
ΠΑΡΑΤΗΡΗΣΕΙΣ ΣΧΕΔΙΟΥ:
GENERAL NOTES:
ΓΕΝΙΚΕΣ ΠΑΡΑΤΗΡΗΣΕΙΣ:
B
C
D
1 2 3 4 5 6 7 98
N00 STOR
ELEC
FLEET CYBER -
SECURE
SSO OFFICE
VESTIBULE
TR 2-1
FLEET CYBER -
EQUIP
STAIR 1
N9 EQUIPMENT
ROOM
COMM SECURITY
MATERIAL AREA
STAIR 2
N9 TECH
CONTROL
CORRIDOR
FLEET CYBER -
CONF
CLASSIFIED
CONFERENCE
A1 M-302
N00C KMI
N3 STOR
KMI STOR
WOMENS
MENS
JAN
ELEV
302BREAK
A3 M-302
CRAHU-08A
CRAHU-08B
FCU-05
CRAC-10A
A1 M-301
FPB-27
FPB-14
FPB-16
FPB-29
FPB-28
A4 M-302
CRAC-10BFPB-13
SA-01
SA-01
42 SA-01
SA-01
SA-01
SA-01
SA-01
SA-01
SA-01
SA-01
SA-01
SA-01
SA-01
250x200 SA 460x300 SA
0ø
S A
300ø SA
WATCH CENTER
305 WATCH CMDR
OA-01
150ø OA
OA-03
FPB-30
SA-02
SA-01
CRAHU-08C
CRAHU-08D
0ø
S A
VAV-09
RA-07
RA-04
RA-08
RA-02
0ø
S A
0ø
S A
RA-04
NOO
860/410 SA
860/410 SA
RA-02
M-401 A1
0x
SA
BH-04
TYP. 4
TYP. 6
SA-10
560/360 SA
BOD 4133
760/360 SA
BOD 4133
0x
R A
BO
D
TYP. 2
SA-01
TYP. 5
200x150 SA 300x200 OA
BOD 3920 OA-02
TYP. 3
TYP. 2
0ø
S A
200x150 RA
200ø SA 200ø SA
360x200 EA
BOD 3859
560x250 RA
BOD 4644
200x150 SA
SA-09
TYP 48
TYP. 2
0ø
S A
A3 M-301
EA-03
EA-03
EA-03
RA-05
SA-01
76 SA-01
RA-02
RA-04
560/360 SA
BOD 3657
FSD-20
TYP. 2
TYP. 4
460/300 SA
BOD 3790
460/300 SA
BOD 4145
660x300 SA
660x360 RA
SA-07
EA-04
EA-05
RA-06
RA-02
300x250 SATYP. 3
360x250 RA
BOD 3768
0x
SA
BO
D
250x200 RA
SA-03
708510x510 SA
BDD BDD
STORAGE
OA-05
SA-04
560x250 RA
BOD 3576
250x250 RA
BOD 3843
OA-06
CORRIDOR
ISSM
200ø SA
250x250 RA
360ø SA
320x360 RA
300x300 RA
RA-03
RA-01
TYP. 2
300x300 RA
RA-01
TYP. 2
RA-01
TYP. 2
360x200 RA
250ø SA
150ø SA
200ø SA
200ø SA
200ø SA 300ø SA
150ø SA
300x150 RA
360x200 RA
460x250 RA
150ø SA
250ø SA
470ø SA
360x200 RA
FSD-14
SA-05
FSD-13
SA-05
360x300 SA
FPB-34
320x360 RA
380x380 RA
RA-02
RA-02
RA-02
300x300 RA
SD
-1
SD
-1
SD-15
SD
-1
TYP.2
300x300 EA
FPB-15
150x150 SA
200x200 SA
SA-01
35 320ø SA
VEST
RA-07
RA-04
RA-02
RA-02
A4 M-516
C1 M-516
RA-11
EA-07
910/410 SA
200ø SA
DXFCU-04A
DXFCU-04B
460x300 RA
810x460 RA810x560 RA
D
C
B
1 2 3 4 5
NONE
1615269
DWG
SHEET OF
NAVFAC DRAWING NO.
CONSTR. CONTR. NO.
EPROJECT NO.
SCALE:
N62470-21-C-0005
DESIGN DIRECTOR
BRANCH MANAGER
PM/DM
DES DRW CHK
SATISFACTORY TO DATE
ACTIVITY
FOR COMMANDER NAVFAC
APPROVED
A/E INFO
SEAL
SY
M
DE
SC
RI
PT
IO
N
DA
TE
AP
PR
N
AV
S U
PP
AC
T
SO
U D
A B
AY
N
AV
A L
FA
C
IL
IT
IE
S
EN
G
IN
E
ER
IN
G S
YS
TE
M C
O M
M
AN
D D
E P
AR
TM
E N
T O
F
TH
E N
A
VY
N
AV
AL
F
AC
IL
IT
IE
S E
N G
IN
EE
R
IN
G S
YS
TE
M C
O M
M
AN
D
A
FIRE PROTECTION
N O
R
FO
LK
, V
A A
TL
AN
TI
C
D E
SI
G
N A
N D
C O
N
ST
R U
C
TI
O N
1100 NORTH GLEBE ROAD
SUITE 500
ARLINGTON, VIRGINIA 22201
571.218.1000
FAX: 571.218.1600
D
C
B
A
1 2 3 4 5
RICHARD STEPHENS
TRUEWORTHY,PE / STELMASZEK,RA
PL
O
T
DA
TE
/T
IM
E:
7/
/ 2
1:
:4
PM
C :\U se rs
\C ha nH \D oc um en ts
\P
1- D
1-
M _R
_h ch an 4Z
9N T.
rv t
14 JUL 2021
RECEIVED BY JACOBIE TISDALE
AND STEVE PARK VIA EMAIL
MH103
GSH HC KG
P
C
O M
M U
N
IC
A
TI
O N
C E
N
TE
RS
O
U D
A B
AY
, G
R
EE
C E
H
VA
C F
LO
O
R P
LA
N
S -S
EC
O
N D
F
LO
O R
14089288
Κ
ΑΤ
Ο Ψ Ε
ΙΣ
H V
AC
-Δ Ε
ΥΤ
Ε
ΡΟ
Σ Ο Ρ Ο Φ Ο Σ
SCE
DPS
1 : 100A1 SECOND FLOOR-HVAC ΔΕΥΤΕΡΟΣ ΟΡΟΦΟΣ-HVAC 0 5000 10000
MILLIMETRESSCALE 1:100
30001000
PLAN NORTH
210 PROVIDE SECURE AREA DUCT PENETRATION. REFER
TO M-515 AND M-514 FOR DETAILS.
ΠΡΟBΛΕΨΤΕ ΔΙΑΤΡΗΣΗ ΑΕΡΑΓΩΓΟΥ ΣΕ ΑΣΦΑΛΗ
ΠΕΡΙΟΧΗ. ΑΝΑΤΡΕΞΕ ΓΙΑ ΛΕΠΤΟΜΕΡΕΙΕΣ ΣΤΟ Μ-515 ΚΑΙ
ΣΤΟ Μ-514
215 REFER TO A1/M-515 FOR Z DUCT DETAIL.
ΑΝΑΤΡΕΞΤΕ ΣΤΟ Α1/Μ-515 ΓΙΑ ΛΕΠΤΟΜΕΡΙΑ Ζ
ΑΕΡΑΓΩΓΟΥ
29 250X250 UP TO EF-7 AND EXHAUST FAN FOR CLEAN
AGENT EXHAUST. THE MANUAL ACTIVATION SWITCH
MUST BE LOCATED OUTSIDE OF THE PROTECTED AREA.
PERMANENT SIGNAGE MUST BE PROVIDED INDICATING
"FIRE SUPPRESSION EXHAUST SYSTEM - FIRE
DEPARTMENT USE ONLY".
250X250 ΩΣ ΤΟ EF-7 ΚΑΙ ANEMIΣΤΗΡΑ ΕΞΑΕΡΙΣΜΟΥ ΓΙΑ
ΕΞΑΕΡΙΣΜΟ ΠΥΡΟΣΒΕΣΗΣ ΚΑΘΑΡΟΥ ΠΑΡΑΓΟΝΤΑ.O
XEIΡOKINHTOΣ ΔIAKOΠTHΣ ENEΡΓOΠOIHΣHΣ ΠΡEΠEI NA
TOΠΟΘΕΤΗΘΕΙ EΞΩ AΠO THN ΠΡΟΣTATEYOMENH
ΠEΡIOXH.ΠΡΟΜΗΘΕΥΣΤΕ ΜΟΝΙΜΗ ΠΙΝΑΚΙΔΑ ΝΑ
ΥΠΟΔΕΙΚΝΥΕΙ "ΣΥΣΤΗΜΑ ΕΞΑΕΡΙΣΜΟΥ ΚΑΤΑΠΝΙΞΗΣ
ΠΥΡΚΑΓΙΑΣ-ΠΥΡΟΣΒΕΣΤΙΚΗ ΜΟΝΟ"
37 360X200 RA DOWN TO FIRST LEVEL.
360X200 RA KATΩ ΠΡΟΣ ΤΟΝ ΠΡΩΤΟ ΟΡΟΦΟ
51 SEAL UNDERFLOOR WALL PENETRATIONS AND WALL TO
FLOOR SEAMS TO MAINTAIN SUPPLY AIR PLENUM
PRESSURIZATION.
ΜΟΝΩΣΤΕ TIΣ ΔΙΑΤΡΗΣΕΙΣ ΣΤΟΥΣ ΤΟΙΧΟΥΣ ΚΑΤΩ ΑΠΟ
ΤΟ ΠΑΤΩΜΑ ΚΑΙ ΤΙΣ ΡΑΦΕΣ ΜΕΤΑΞΥ ΤΟΙΧΟΥ ΚΑΙ
ΔΑΠΕΔΟΥ ΓΙΑ ΝΑ ΔΙΑΤΗΡΗΘΕΙ Η ΠΙΕΣΗ ΤΟΥ ΑΕΡΑ
ΠΡΟΣΑΓΩΓΗΣ
117 AHU-1 STATIC PRESSURE SENSOR LOCATION
ΑΗU-1 ΤΟΠΟΘΕΣΙΑ AIΣΘΗΤΗΡΙΟΥ ΠΙΕΣΗΣ
16 PROVIDE A FULL SIZE RETURN DUCT CONNECTION TO
ABOVE THE SUSPENDED CEILING.
ΠΡΟΜΗΘΕΥΣΤΕ ΜΕ ΑΕΡΑΓΩΓΟ ΕΠΙΣΤΡΟΦΗΣ ΠΛΗΡΟΥΣ
ΜΕΓΕΘΟΥΣ ΠΑΝΩ ΑΠΟ ΤΗΝ ΨΕΥΔΟΟΡΟΦΗ
27 PROVIDE EMERGENCY AIR DISTRIBUTION SHUT-OFF
SWITCH.
ΠΡΟΜΗΘΕΥΣΤΕ ΔΙΑΚΟΠΤΗ ΕΚΤΑΚΤΟΥ ΑΝΑΓΚΗΣ
ΔΙΑΚΟΠΗΣ ΑΕΡΑ.
28 460X460 UP TO EF-6 AND EXHAUST FAN FOR CLEAN
AGENT EXHAUST. THE MANUAL ACTIVATION SWITCH
MUST BE LOCATED OUTSIDE OF THE PROTECTED AREA.
PERMANENT SIGNAGE MUST BE PROVIDED INDICATING
"FIRE SUPPRESSION EXHAUST SYSTEM - FIRE
DEPARTMENT USE ONLY".
460X460 ΩΣ ΤΟ EF-6 ΚΑΙ ANEMIΣΤΗΡΑ ΕΞΑΕΡΙΣΜΟΥ ΓΙΑ
ΕΞΑΕΡΙΣΜΟ ΠΥΡΟΣΒΕΣΗΣ ΚΑΘΑΡΟΥ ΠΑΡΑΓΟΝΤΑ.O
XEIΡOKINHTOΣ ΔIAKOΠTHΣ ENEΡΓOΠOIHΣHΣ ΠΡEΠEI NA
TOΠΟΘΕΤΗΘΕΙ EΞΩ AΠO THN ΠΡΟΣTATEYOMENH
ΠEΡIOXH.ΠΡΟΜΗΘΕΥΣΤΕ ΜΟΝΙΜΗ ΠΙΝΑΚΙΔΑ ΝΑ
ΥΠΟΔΕΙΚΝΥΕΙ "ΣΥΣΤΗΜΑ ΕΞΑΕΡΙΣΜΟΥ ΚΑΤΑΠΝΙΞΗΣ
ΠΥΡΚΑΓΙΑΣ-ΠΥΡΟΣΒΕΣΤΙΚΗ ΜΟΝΟ"
A MAINTAIN MANUFACTURER'S RECOMMENDED CLEARANCES
ON ALL EQUIPMENT.
ΔΙΑΤΗΡΗΣΤΕ ΤΟΝ ΣΥΝΙΣΤΩΜΕΝΟ ΕΛΕΥΘΕΡΟ ΧΩΡΟ ΑΠΟ
ΤΟΝ ΚΑΤΑΣΚΕΥΑΣΤΗ ΓΙΑ ΟΛΟ ΤΟΝ ΕΞΟΠΛΙΣΜΟ
B PROVIDE CLEARANCES FOR ALL ELECTRICAL AND
CONTROL PANELS PER NEC.
ΕΦΟΔΙΑΣΤΕ ΤΟΥΣ ΗΛΕΚΤΡΟΛΟΓΙΚΟΥΣ ΠΙΝΑΚΕΣ ΚΑΙ ΤΟΥΣ
ΠΙΝΑΚΕΣ ΕΛΕΓΧΟΥ ΜΕ ΤΟΝ ΑΠΑΙΤΟΥΜΕΝΟ ΕΛΕΥΘΕΡΟ
ΧΩΡΟ ΣYMΦΩNA ME ΤΟΝ ΕΘΝΙΚΟ ΗΛΕΚΤΡΟΛΟΓΙΚΟ ΚΩΔΙΚΑ.
C PROVIDE REMOTE DAMPER ACTUATORS OR ACCESS PANEL
FOR ALL DAMPERS LOCATED ABOVE HARD CEILINGS.
REFER TO ARCHITECTURE DRAWINGS FOR LOCATIONS
ΕΦΟΔΙΑΣΤΕ ΜΕ ΑΠΟΜΟΜΑΚΡΥΣΜΕΝΟ ΕΝΕΡΓΟΠΟΙΗΤΗ
ΔΙΑΦΡΑΓΜΑΤΟΣ Ή ME ΠΙΝΑΚΑ ΠΡΟΣΒΑΣΗΣ ΓΙΑ ΟΛΑ ΤΑ
ΔΙΑΦΡΑΓΜΑΤΑ ΠΟΥ ΒΡΙΣΚΟΝΤΑΙ ΠΑΝΩ ΑΠΟ ΤΗΝ
ΨΕΥΔΟΟΡΟΦΗ. ΑΝΑΤΡΕΞΤΕ ΣΤΑ ΑΡΧΙΤΕΚΤΟΝΙΚΑ ΣΧΕΔΙΑ ΓΙΑ
ΤΙΣ ΘΕΣΕΙΣ.
D REFER TO PIPING PLAN FOR THERMOSTAT LOCATION.
ΑΝΑΤΡΕΞΤΕ ΣΤΑ ΣΧΕΔΙΑ ΣΩΛΗΝΩΣΕΩΝ ΓΙΑ ΤΗ ΘΕΣΗ ΤΟΥ
ΘΕΡΜΟΣΤΑΤΗ
E PROVIDE BALANCING DAMPER AT EACH TAKEOFF
ΠΡΟΜΗΘΕΥΣΤΕ ΔΙΑΦΡΑΓΜΑΤΑ ΕΞΙΣΟΡΡΟΠΙΣΗΣ ΣΕ ΚΑΘΕ
ΚΛΑΔΟ
F REFER TO SECURITY, FIRE PROTECTION, AND
ARCHITECTURE FOR SECURE WALL RATINGS, FIRE RATED
WALLS AND PENETRATION DETAILS.
ΑΝΑΤΡΕΞΤΕ ΣΤΗΝ ΑΣΦΑΛΕΙΑ, ΣΤΗΝ ΠΥΡΟΠΡΟΣΤΑΣΙΑ ΚΑΙ
ΣΤΑ ΑΡΧΙΤΕΚΤΟΝΙΚΑ ΓΙΑ ΤΟΥΣ ΠΥΡΑΝΤΟΧΟΥΣ ΤΟΙΧΟΥΣ ΚΑΙ
ΤΙΣ ΛΕΠΤΟΜΕΡΕΙΕΣ ΤΩΝ ΔΙΑΤΡΗΣΕΩΝ.
G ALL SUSPENDED EQUIPMENT GREATER THAN 14 KG MUST
BE SUPPORTED WITH BRACING DESIGNED TO SUPPORT A
MINIMUM OF 0.5X THE EQUIPMENT WEIGHT IN THE
HORIZONTAL DIRECTION, AND 1.5X THE EQUIPMENT
WEIGHT IN THE VERTICAL DIRECTION IN ACCORDANCE
WITH UFC 4-010-01.
OΛΟΣ Ο ΑΝΑΡΤΩΜΕΝΟΣ ΕΞΟΠΛΙΣΜΟΣ ΜΕΓΑΛΥΤΕΡΟΣ ΤΩΝ
14KG ΘΑ ΠΡΕΠΕΙ NA ΕΝΙΣΧΥΘΕΙ ME ΣΥΝΔΕΣΜΟΥΣ.
ΣΧΕΔΙΑΣΜΕΝΟΥΣ ΝΑ ΕΝΙΣΧΥΣΟΥΝ ΤΟ ΕΛΑΧΙΣΤΟ 0,5X ΤΟ
ΒΑΡΟΣ ΤΟΥ ΕΞΟΠΛΙΣΜΟΥ ΣΤΗΝ ΟΡΙΖΟΝΤΙΑ ΚΑΤΕΥΘΥΝΣΗ
ΚΑΙ 1,5X ΤΟ ΒΑΡΟΣ ΤΟΥ ΕΞΟΠΛΙΣΜΟΥ ΣΤΗΝ ΚΑΘΕΤΗ
ΚΑΤΕΥΘΥΝΣΗ. ΟΔΗΓΙΑ ΣΥΜΦΩΝΗ ΜΕ ΤΟ UFC 4-010-01.
H FPB AND VAV TERMINAL UNIT DUCT CONNECTIONS TO
MATCH BOX SIZE.
H ΣΥΝΔΕΣΗ ΤΩΝ FPB ΚΑΙ VAV ΤΕΡΜΑΤΙΚΩΝ ΜΟΝΑΔΩΝ
ΑΕΡΑΓΩΓΟΥ ΠΡΕΠΕΙ ΝΑ ΤΑΙΡΙΑΖΕΙ ΜΕ ΤΟ ΜΕΓΕΘΟΣ ΤΩΝ
ΚΟΥΤΙΩΝ.
I DUCT MUST BE MINIMUM OF 26 GAGE. DIFFUSER/GRILLE
CONNECTION TO MATCH THE NECK CONNECTION.
O AEΡΑΓΩΓΟΣ ΠΡΕΠΕΙ ΝΑ ΕΙΝΑΙ ΤΟΥΛΑΧΙΣΤΟΝ 26
GAGE(0,405mm). Η ΣΥΝΔΕΣΗ ΣΤΟΜΙΩΝ/ΓΡΙΛΙΕΣ ΠΡΕΠΕΙ ΝΑ
ΤΑΙΡΙΑΖΕΙ ΜΕ ΤΗΝ ΣΥΝΔΕΣΗ ΤΟΥ ΛΑΙΜΟΥ.
J REFER TO ARCHITECTURE DRAWING FOR DUCT
PENETRATIONS DETAIL.
ΑΝΑΤΡΕΞΕ ΣΤΑ ΑΡΧΙΤΕΚΤΟΝΙΚΑ ΣΧΕΔΙΑ ΓΙΑ ΤΙΣ
ΛΕΠΤΟΜΕΡΕΙΕΣ ΤΩΝ ΔΙΑΤΡΗΣΕΩΝ ΓΙΑ ΤΟΥΣ ΑΕΡΑΓΩΓΟΥΣ
K BRACE EQUIPMENT WEIGHING OVER 14 KG PER DETAIL C4
ON M-505.
ΣΤΗΡΙΓΜΑ ΕΞΟΠΛΙΣΜΟΥ ΠΟΥ ΖΥΓΙΖΕΙ ΠΑΝΩ ΑΠΟ 14KG ΓΙΑ
ΛΕΠΤΟΜΕΡΙΑ C4 ΣΤΟ Μ-505
L VAV PRIMARY AIR DISTRIBUTION DUCT MUST BE ROUND OR
OVAL PREFABRICATED DUCT.
Ο ΠΡΩΤΕΥΩΝ ΑΕΡΑΓΩΓΟΣ ΔΙΑΝΟΜΗΣ ΑΕΡΑ ΤΟΥ VAV ΘΑ
ΠΡΕΠΕΙ ΝΑ ΕΙΝΑΙ ΕΙΤΕ ΣΤΡΟΓΓΥΛΟΣ ΕΙΤΕ
ΠΡΟΚΑΤΑΣΚΕΥΑΣΜΕΝΟΣ ΟΒΑΛ.
SHEET KEYED NOTES:
ΠΑΡΑΤΗΡΗΣΕΙΣ ΣΧΕΔΙΟΥ:
C
D
1 2 3 4 5 6 7 98
CH-01CH-02
HPCH-01
STAIR 2
EF-06
FCU-03
ELEVATOR
MACHINE ROOM
110C1
MP104
CU-06B CU-06A CU-10A CU-10B
CU-09A
CU-04B CU-04ACU-05A CU-05B
CU-01A
CU-01BCU-03B
CU-03A
CU-07A
CU-07B
CU-02B
CU-02A
TYP
A4 M-516
C1 M-516
EF-07
D
C
B
1 2 3 4 5
1615269
DWG
SHEET OF
NAVFAC DRAWING NO.
CONSTR. CONTR. NO.
EPROJECT NO.
SCALE:
N62470-21-C-0005
DESIGN DIRECTOR
BRANCH MANAGER
PM/DM
DES DRW CHK
SATISFACTORY TO DATE
ACTIVITY
FOR COMMANDER NAVFAC
APPROVED
A/E INFO
SEAL
SY
M
DE
SC
RI
PT
IO
N
DA
TE
AP
PR
AS NOTED
N
AV
S U
PP
AC
T
SO
U D
A B
AY
N
AV
A L
FA
C
IL
IT
IE
S
EN
G
IN
E
ER
IN
G S
YS
TE
M C
O M
M
AN
D D
E P
AR
TM
E N
T O
F
TH
E N
A
VY
N
AV
AL
F
AC
IL
IT
IE
S E
N G
IN
EE
R
IN
G S
YS
TE
M C
O M
M
AN
D
A
FIRE PROTECTION
N O
R
FO
LK
, V
A A
TL
AN
TI
C
D E
SI
G
N A
N D
C O
N
ST
R U
C
TI
O N
1100 NORTH GLEBE ROAD
SUITE 500
ARLINGTON, VIRGINIA 22201
571.218.1000
FAX: 571.218.1600
D
C
B
A
1 2 3 4 5
RICHARD STEPHENS
TRUEWORTHY,PE / STELMASZEK,RA
PL
O
T
DA
TE
/T
IM
E:
7/
/ 2
1:
:5
PM
C :\U se rs
\C ha nH \D oc um en ts
\P
1- D
1-
M _R
_h ch an 4Z
9N T.
rv t
14 JUL 2021
RECEIVED BY JACOBIE TISDALE
AND STEVE PARK VIA EMAIL
MH104
GSH HC KG
P
C
O M
M U
N
IC
A
TI
O N
C E
N
TE
RS
O
U D
A B
AY
, G
R
EE
C E
H
VA
C R
O O
F
PL
AN
14089289
H
VA
C Σ Χ
ΕΔ
ΙΟ
Δ Ω Μ
ΑΤ
Ο Σ
SCE
DPS
1 : 100A1
ROOF-HVAC
ΔΩΜΑ-HVAC
PLAN NORTH
0 5000 10000
MILLIMETRESSCALE 1:100
30001000
109 LOCATE THE WEATHER STATION AT THE ROOF OF THE
ELEVATOR MACHINE ROOM. PROVIDE TWO WEATHER
STATIONS.
ΤΟΠΟΘΕΤΗΣΤΕ ΤΟΝ ΜΕΤΕΩΡΟΛΟΓΙΚΟ ΣΤΑΘΜΟ ΣΤΗΝ
ΟΡΟΦΗ ΤΟΥ ΜΗΧΑΝΟΣΤΑΣΙΟΥ ΤΟΥ
ΑΝΕΛΚΥΣΤΗΡΑ.ΠΡΟΜΗΘΕΥΣΤΕ ΔΥΟ ΜΕΤΕΩΡΟΛΟΓΙΚΟΥΣ
ΣΤΑΘΜΟΥΣ
110 PROVIDE A ROOFTOP WALKWAY TO ACCESS THE
CHILLER AND HEAT PUMP CONTROL PANELS. REFER TO
SPECIFICATION SECTION 23 05 15 COMMON PIPING FOR
HVAC FOR ROOF WALKWAY SPECIFICATIONS.
ΠΡΟΝΟΗΣΤΕ ΓΙΑ ΜΙΑ ΔΙΑΔΡΟΜΗ ΠΡΟΣΒΑΣΗΣ ΣΤΗΝ
ΟΡΟΦΗ ΓΙΑ ΤΟΥΣ ΠΙΝΑΚΕΣ ΕΛΕΓΧΟΥ ΤΟΥ ΨΥΚΤΗ ΚΑΙ
ΤΗΣ ΑΝΤΛΙΑΣ ΘΕΡΜΟΤΗΤΑΣ. ΑΝΑΤΡΕΞΤΕ ΣΤΙΣ
ΠΡΟΔΙΑΓΡΑΦΕΣ ΣΤΟ ΤΜΗΜΑ 23 05 15 ΓΙΑ ΣΥΝΗΘΕΙΣ
ΣΩΛΗΝΩΣΕΙΣ HVAC ΓΙΑ ΔΙΑΔΡΟΜΟΥΣ ΠΡΟΣΒΑΣΗΣ ΣΤΗΝ
ΟΡΟΦΗ.
211 REFER TO B1/A-531 FOR CONDENSER EQUIPMENT
SUPPORTS.
ΑΝΑΤΡΕΞΤΕ ΣΤΗΝ B1/A-531 ΓΙΑ ΤΗΝ ΣΤΗΡΙΞΗ ΤΟΥ
ΕΞΟΠΛΙΣΜΟΥ ΣΥΜΠΥΚΝΩΜΑΤΩΝ
A MAINTAIN MANUFACTURER'S RECOMMENDED CLEARANCES
ON ALL EQUIPMENT.
ΔΙΑΤΗΡΗΣΤΕ ΤΟΝ ΣΥΝΙΣΤΩΜΕΝΟ ΕΛΕΥΘΕΡΟ ΧΩΡΟ ΑΠΟ
ΤΟΝ ΚΑΤΑΣΚΕΥΑΣΤΗ ΓΙΑ ΟΛΟ ΤΟΝ ΕΞΟΠΛΙΣΜΟ
B PROVIDE CLEARANCES FOR ALL ELECTRICAL AND
CONTROL PANELS PER NEC.
ΕΦΟΔΙΑΣΤΕ ΤΟΥΣ ΗΛΕΚΤΡΟΛΟΓΙΚΟΥΣ ΠΙΝΑΚΕΣ ΚΑΙ ΤΟΥΣ
ΠΙΝΑΚΕΣ ΕΛΕΓΧΟΥ ΜΕ ΤΟΝ ΑΠΑΙΤΟΥΜΕΝΟ ΕΛΕΥΘΕΡΟ
ΧΩΡΟ ΣYMΦΩNA ME ΤΟΝ ΕΘΝΙΚΟ ΗΛΕΚΤΡΟΛΟΓΙΚΟ ΚΩΔΙΚΑ.
C PROVIDE REMOTE DAMPER ACTUATORS OR ACCESS PANEL
FOR ALL DAMPERS LOCATED ABOVE HARD CEILINGS.
REFER TO ARCHITECTURE DRAWINGS FOR LOCATIONS
ΕΦΟΔΙΑΣΤΕ ΜΕ ΑΠΟΜΟΜΑΚΡΥΣΜΕΝΟ ΕΝΕΡΓΟΠΟΙΗΤΗ
ΔΙΑΦΡΑΓΜΑΤΟΣ Ή ME ΠΙΝΑΚΑ ΠΡΟΣΒΑΣΗΣ ΓΙΑ ΟΛΑ ΤΑ
ΔΙΑΦΡΑΓΜΑΤΑ ΠΟΥ ΒΡΙΣΚΟΝΤΑΙ ΠΑΝΩ ΑΠΟ ΤΗΝ
ΨΕΥΔΟΟΡΟΦΗ. ΑΝΑΤΡΕΞΤΕ ΣΤΑ ΑΡΧΙΤΕΚΤΟΝΙΚΑ ΣΧΕΔΙΑ ΓΙΑ
ΤΙΣ ΘΕΣΕΙΣ.
D REFER TO PIPING PLAN FOR THERMOSTAT LOCATION.
ΑΝΑΤΡΕΞΤΕ ΣΤΑ ΣΧΕΔΙΑ ΣΩΛΗΝΩΣΕΩΝ ΓΙΑ ΤΗ ΘΕΣΗ ΤΟΥ
ΘΕΡΜΟΣΤΑΤΗ
E PROVIDE BALANCING DAMPER AT EACH TAKEOFF
ΠΡΟΜΗΘΕΥΣΤΕ ΔΙΑΦΡΑΓΜΑΤΑ ΕΞΙΣΟΡΡΟΠΙΣΗΣ ΣΕ ΚΑΘΕ
ΚΛΑΔΟ
F REFER TO SECURITY, FIRE PROTECTION, AND
ARCHITECTURE FOR SECURE WALL RATINGS, FIRE RATED
WALLS AND PENETRATION DETAILS.
ΑΝΑΤΡΕΞΤΕ ΣΤΗΝ ΑΣΦΑΛΕΙΑ, ΣΤΗΝ ΠΥΡΟΠΡΟΣΤΑΣΙΑ ΚΑΙ
ΣΤΑ ΑΡΧΙΤΕΚΤΟΝΙΚΑ ΓΙΑ ΤΟΥΣ ΠΥΡΑΝΤΟΧΟΥΣ ΤΟΙΧΟΥΣ ΚΑΙ
ΤΙΣ ΛΕΠΤΟΜΕΡΕΙΕΣ ΤΩΝ ΔΙΑΤΡΗΣΕΩΝ.
G ALL SUSPENDED EQUIPMENT GREATER THAN 14 KG MUST
BE SUPPORTED WITH BRACING DESIGNED TO SUPPORT A
MINIMUM OF 0.5X THE EQUIPMENT WEIGHT IN THE
HORIZONTAL DIRECTION, AND 1.5X THE EQUIPMENT
WEIGHT IN THE VERTICAL DIRECTION IN ACCORDANCE
WITH UFC 4-010-01.
OΛΟΣ Ο ΑΝΑΡΤΩΜΕΝΟΣ ΕΞΟΠΛΙΣΜΟΣ ΜΕΓΑΛΥΤΕΡΟΣ ΤΩΝ
14KG ΘΑ ΠΡΕΠΕΙ NA ΕΝΙΣΧΥΘΕΙ ME ΣΥΝΔΕΣΜΟΥΣ.
ΣΧΕΔΙΑΣΜΕΝΟΥΣ ΝΑ ΕΝΙΣΧΥΣΟΥΝ ΤΟ ΕΛΑΧΙΣΤΟ 0,5X ΤΟ
ΒΑΡΟΣ ΤΟΥ ΕΞΟΠΛΙΣΜΟΥ ΣΤΗΝ ΟΡΙΖΟΝΤΙΑ ΚΑΤΕΥΘΥΝΣΗ
ΚΑΙ 1,5X ΤΟ ΒΑΡΟΣ ΤΟΥ ΕΞΟΠΛΙΣΜΟΥ ΣΤΗΝ ΚΑΘΕΤΗ
ΚΑΤΕΥΘΥΝΣΗ. ΟΔΗΓΙΑ ΣΥΜΦΩΝΗ ΜΕ ΤΟ UFC 4-010-01.
H FPB AND VAV TERMINAL UNIT DUCT CONNECTIONS TO
MATCH BOX SIZE.
H ΣΥΝΔΕΣΗ ΤΩΝ FPB ΚΑΙ VAV ΤΕΡΜΑΤΙΚΩΝ ΜΟΝΑΔΩΝ
ΑΕΡΑΓΩΓΟΥ ΠΡΕΠΕΙ ΝΑ ΤΑΙΡΙΑΖΕΙ ΜΕ ΤΟ ΜΕΓΕΘΟΣ ΤΩΝ
ΚΟΥΤΙΩΝ.
I DUCT MUST BE MINIMUM OF 26 GAGE. DIFFUSER/GRILLE
CONNECTION TO MATCH THE NECK CONNECTION.
O AEΡΑΓΩΓΟΣ ΠΡΕΠΕΙ ΝΑ ΕΙΝΑΙ ΤΟΥΛΑΧΙΣΤΟΝ 26
GAGE(0,405mm). Η ΣΥΝΔΕΣΗ ΣΤΟΜΙΩΝ/ΓΡΙΛΙΕΣ ΠΡΕΠΕΙ ΝΑ
ΤΑΙΡΙΑΖΕΙ ΜΕ ΤΗΝ ΣΥΝΔΕΣΗ ΤΟΥ ΛΑΙΜΟΥ.
J REFER TO ARCHITECTURE DRAWING FOR DUCT
PENETRATIONS DETAIL.
ΑΝΑΤΡΕΞΕ ΣΤΑ ΑΡΧΙΤΕΚΤΟΝΙΚΑ ΣΧΕΔΙΑ ΓΙΑ ΤΙΣ
ΛΕΠΤΟΜΕΡΕΙΕΣ ΤΩΝ ΔΙΑΤΡΗΣΕΩΝ ΓΙΑ ΤΟΥΣ ΑΕΡΑΓΩΓΟΥΣ
K BRACE EQUIPMENT WEIGHING OVER 14 KG PER DETAIL C4
ON M-505.
ΣΤΗΡΙΓΜΑ ΕΞΟΠΛΙΣΜΟΥ ΠΟΥ ΖΥΓΙΖΕΙ ΠΑΝΩ ΑΠΟ 14KG ΓΙΑ
ΛΕΠΤΟΜΕΡΙΑ C4 ΣΤΟ Μ-505
L VAV PRIMARY AIR DISTRIBUTION DUCT MUST BE ROUND OR
OVAL PREFABRICATED DUCT.
Ο ΠΡΩΤΕΥΩΝ ΑΕΡΑΓΩΓΟΣ ΔΙΑΝΟΜΗΣ ΑΕΡΑ ΤΟΥ VAV ΘΑ
ΠΡΕΠΕΙ ΝΑ ΕΙΝΑΙ ΕΙΤΕ ΣΤΡΟΓΓΥΛΟΣ ΕΙΤΕ
ΠΡΟΚΑΤΑΣΚΕΥΑΣΜΕΝΟΣ ΟΒΑΛ.
SHEET KEYED NOTES:
ΠΑΡΑΤΗΡΗΣΕΙΣ ΣΧΕΔΙΟΥ:
C
D
1 2 3 4 5 6 7 98
A4 M-301
UPS
ELEC
MENS
STAIR 1
LOBBY
QUARTER DECK
BUNK
IT LOGISTICS
RECYCLE
BREAK
RECEIVING
STAIR 2
DEMARC 2
FIRE PROT
N6 EQUIPMENT
ROOM
N6 MAINTENANCE
NIPR CAFE
N6 CONF
N6 ID
N6 ISSM
N6 C3P
N6
CORRIDOR
VEST
VEST
N6 MAINT
N6 STOR
MOTHERS
ELEV
WOMENS
JAN
UPS
CRAHU-01A CRAHU-01B
DEMARC 1
141 SIPR CAFE
TR G-1
CORRIDOR
40 - CHWS
40 - CHWS
40 - CHWR
40 - CHWR
20 - PCD
20 - PCD
D
C
B
1 2 3 4 5
1615269
DWG
SHEET OF
NAVFAC DRAWING NO.
CONSTR. CONTR. NO.
EPROJECT NO.
SCALE:
N62470-21-C-0005
DESIGN DIRECTOR
BRANCH MANAGER
PM/DM
DES DRW CHK
SATISFACTORY TO DATE
ACTIVITY
FOR COMMANDER NAVFAC
APPROVED
A/E INFO
SEAL
SY
M
DE
SC
RI
PT
IO
N
DA
TE
AP
PR
AS NOTED
N
AV
S U
PP
AC
T
SO
U D
A B
AY
N
AV
A L
FA
C
IL
IT
IE
S
EN
G
IN
E
ER
IN
G S
YS
TE
M C
O M
M
AN
D D
E P
AR
TM
E N
T O
F
TH
E N
A
VY
N
AV
AL
F
AC
IL
IT
IE
S E
N G
IN
EE
R
IN
G S
YS
TE
M C
O M
M
AN
D
A
FIRE PROTECTION
N O
R
FO
LK
, V
A A
TL
AN
TI
C
D E
SI
G
N A
N D
C O
N
ST
R U
C
TI
O N
1100 NORTH GLEBE ROAD
SUITE 500
ARLINGTON, VIRGINIA 22201
571.218.1000
FAX: 571.218.1600
D
C
B
A
1 2 3 4 5
RICHARD STEPHENS
TRUEWORTHY,PE / STELMASZEK,RA
PL
O
T
DA
TE
/T
IM
E:
7/
/ 2
1:
:1
PM
C :\U se rs
\C ha nH \D oc um en ts
\P
1- D
1-
M _R
_h ch an 4Z
9N T.
rv t
14 JUL 2021
RECEIVED BY JACOBIE TISDALE
AND STEVE PARK VIA EMAIL
MP101U
GSH HC KG
P
C
O M
M U
N
IC
A
TI
O N
C E
N
TE
RS
O
U D
A B
AY
, G
R
EE
C E
M
EC
H P
IP
IN
G P
LA
N
G
R O
U N
D L
EV
EL
R
AI
SE
D
F
LR
14089290
Μ Η
ΧΑ
Ν Ο
ΛΟ
ΓΙ
Κ Ο
ΣΧ
Ε
ΔΙ
Ο
ΣΩ
ΛΗ
Ν Ω
ΣΕ
Ω Ν
-ΙΣ
Ο
ΓΕ
ΙΟ
ΥΠ
Ε
ΡΥ
Ψ Ω Μ
ΕΝ
Ο
ΔΑ
Π Ε
ΔΟ
SCE
DPS
1 : 100A1
MECHANICAL PIPING PLAN - GROUND FLOOR RAISED FLOOR
ΜΗΧΑΝΟΛΟΓΙΚΟ ΣΧΕΔΙΟ ΣΩΛΗΝΩΣΕΩΝ -ΥΠΕΡΥΨΩΜΕΝΟ
ΔΑΠΕΔΟ ΙΣΟΓΕΙΟΥ
17 WATER DETECTION TAPE. CONNECT TAPE TO CRAHU
UNIT FOR MONITORING AND ALARM. PROVIDE A
GENERAL ALARM TO THE BUILDING AUTOMATION
SYSTEM UPON DETECTION OF WATER.
ΤΑΙΝΙΑ ΑΝΙΧΝΕΥΣΗΣ ΔΙΑΡΡΟΗΣ ΝΕΡΟΥ. ΣΥΝΔΕΣΗ ΤΗΣ
ΤΑΙΝΙΑΣ ΜΕ ΤΗΝ ΜΟΝΑΔΑ CRAHU ΓΙΑ ΕΛΕΓΧΟ ΚΑΙ
ΣΥΝΑΓΕΡΜΟ. ΠΡΟΜΗΘΕΥΣΤΕ ΕΝΑ ΓΕΝΙΚΟ ΣΥΝΑΓΕΡΜΟ
ΣΤΟΝ ΠΙΝΑΚΑ ΕΛΕΓΧΟΥ ΑΥΤΟΜΑΤΙΣΜΟΥ ΤΟΥ ΚΤΗΡΙΟΥ
ΚΑΤΑ ΤΗΝ ΑΝΙΧΝΕΥΣΗ ΔΙΑΡΡΟΗΣ ΝΕΡΟΥ.
56 40 CHWS FROM GROUND LEVEL.
40 CHWS ΑΠΟ ΤΟ ΙΣΟΓΕΙΟ
58 INCLUDE BYPASS LINE WITH BALANCING VALVE. SEE
A2/M-505.
ΠΕΡΙΛΑΜΒΑΝΕΙ ΓΡΑΜΜΗ ΠΑΡΑΚΑΜΨΗΣ BYPASS ΜΕ
ΑΥΤΟΜΑΤΗ ΒΑΛΒΙΔΑ ΕΞΙΣΟΡΡΟΠΗΣΗΣ. ΑΝΑΤΡΕΞΤΕ ΣΤΟ
Α2/Μ-505
A MAINTAIN MANUFACTURER'S RECOMMENDED
CLEARANCES ON ALL EQUIPMENT.
ΔΙΑΤΗΡΗΣΤΕ ΤΟΝ ΣΥΝΙΣΤΩΜΕΝΟ ΕΛΕΥΘΕΡΟ ΧΩΡΟ ΑΠΟ
ΤΟΝ ΚΑΤΑΣΚΕΥΑΣΤΗ ΓΙΑ ΟΛΟ ΤΟΝ ΕΞΟΠΛΙΣΜΟ
B PROVIDE CLEARANCE FOR ALL ELECTRICAL AND CONTROL
PANELS PER CODE REQUIREMENT.
ΕΦΟΔΙΑΣΤΕ ΤΟΥΣ ΗΛΕΚΤΡΟΛΟΓΙΚΟΥΣ ΠΙΝΑΚΕΣ ΚΑΙ ΤΟΥΣ
ΠΙΝΑΚΕΣ ΕΛΕΓΧΟΥ ΜΕ ΤΟΝ ΑΠΑΙΤΟΥΜΕΝΟ ΕΛΕΥΘΕΡΟ
ΧΩΡΟ ΣΥΜΦΩΝΑ ΜΕ ΤΟΥΣ ΚΑΝΟΝΙΣΜΟΥΣ
C FOR PIPING NOT BURIED, ROUTE PIPING TIGHT TO
OVERHEAD STRUCTURE. DO NOT ROUTE PIPING ABOVE
ELECTRICAL EQUIPMENT.
ΓΙΑ ΣΩΛΗΝΩΣΕΙΣ ΠΟΥ ΔΕΝ ΕΙΝΑΙ ΘΑΜΜΕΝΕΣ, ΓΙΑ ΔΙΑΔΡΟΜΗ
ΣΩΛΗΝΩΝ ΠΟΥ ΕΙΝΑΙ ΔΕΜΕΝΕΣ ΠΑΝΩ ΣΤΗΝ ΚΑΤΑΣΚΕΥΗ, Η
ΔΙΑΔΡΟΜΗ ΤΩΝ ΣΩΛΗΝΩΝ ΝΑ ΜΗΝ ΕΙΝΑΙ ΠΑΝΩ ΑΠΟ
ΗΛΕΚΤΡΟΛΟΓΙΚΟ ΕΞΟΠΛΙΣΜΟ
D COORDINATE WORK WITH ALL OTHER TRADES.
ΣΥΝΤΟΝΙΣΤΕ ΤΗΝ ΕΡΓΑΣΙΑ ΜΕ ΟΛΑ ΤΑ ΑΛΛΑ ΤΜΗΜΑΤΑ
E CONTRACTOR TO VERIFY EXACT LOCATIONS, SIZES,
PIPING MTERIAL OF EXISTING UTILITIES AT JOB SITE
BEFORE COMMENCEMENT OF ANY WORKS. CONTRACTOR
WILL NOTIFY OWNER AND ARCHITECT/ENGINEER OF ANY
DISCREPENCIES FOUND ON SITE BETWEEN
CONSTRUCTION DOCUMENTS AND ACTUAL CONDITIONS.
Ο ΕΡΓΟΛΑΒΟΣ ΘΑ ΠΡΕΠΕΙ ΝΑ ΕΠΑΛΗΘΕΥΣΕΙ ΤΗΝ ΑΚΡΙΒΗ
ΘΕΣΗ,ΜΕΓΕΘΟΣ, ΤΟ ΥΛΙΚΟ ΤΩΝ ΣΩΛΗΝΩΣΕΩΝ ΤΩΝ
ΥΠΑΡΧΟΝΤΩΝ ΣΤΟΙΧΕΙΩΝ ΠΡΙΝ ΞΕΚΙΝΗΣΕΙ ΟΠΟΙΑΔΗΠΟΤΕ
ΕΡΓΑΣΙΑ. Ο ΕΡΓΟΛΑΒΟΣ ΘΑ ΠΡΕΠΕΙ ΝΑ ΕΝΗΜΕΡΩΣΕΙ ΤΟΝ
ΙΔΙΟΚΤΗΤΗ ΚΑΙ ΤΟΝ ΑΡΧΙΤΕΚΤΟΝΑ/ΜΗΧΑΝΙΚΟ ΓΙΑ
ΟΠΟΙΑΔΗΠΟΤΕ ΔΙΑΦΟΡΑ ΒΡΗΚΕ ΣΤΑ ΚΑΤΑΣΚΕΥΑΣΤΙΚΑ
ΣΧΕΔΙΑ ΚΑΙ ΣΤΙΣ ΠΡΑΓΜΑΤΙΚΕΣ ΣΥΝΘΗΚΕΣ.
F COORDINATE WORK WITH ARCHITECTUAL FEATURES SO
THAT INTERFERENCE BETWEEN PIPING, EQUIPMENT,
MECHANICAL WORK, ELECTRICAL WORK, AND BUILDING
STRUCTURE WILL BE AVOIDED.
ΣΥΝΤΟΝΙΣΤΕ ΤΙΣ ΕΡΓΑΣΙΕΣ ΜΕ ΤΑ ΑΡΧΙΤΕΚΤΟΝΙΚΑ ΣΧΕΔΙΑ
ΕΤΣΙ ΩΣΤΕ ΟΠΟΙΑΔΗΠΟΤΕ ΕΜΠΛΟΚΗ ΜΕΤΑΞΥ
ΣΩΛΗΝΩΣΕΩΝ, ΕΞΟΠΛΙΣΜΟΥ, ΜΗΧΑΝΟΛΟΓΙΚΩΝ ΕΡΓΑΣΙΩΝ,
ΗΛΕΚΤΡΟΛΟΓΙΚΩΝ ΕΡΓΑΣΙΩΝ ΚΑΙ ΣΤΑΤΙΚΩΝ ΚΤΙΡΙΟΥ ΝΑ
ΑΠΟΦΕΥΓΘΟΥΝ
G PROVIDE ISOLATION VALVES FOR EACH BRANCH RUN OF
HYDRONIC PIPING.
ΠΡΟΜΗΘΕΥΣΤΕ ΒΑΝΕΣ ΑΠΟΜΟΝΩΣΗΣ ΓΙΑ ΚΑΘΕ ΚΛΑΔΟ
ΤΩΝ ΥΔΡΑΥΛΙΚΩΝ ΣΩΛΗΝΩΣΕΩΝ
H REFER TO M-001 FOR LEGEND AND GENERAL NOTES.
ΑΝΑΤΡΕΞΤΕ ΣΤΟ ΣΧΕΔΙΟ Μ-001 ΓΙΑ ΥΠΟΜΝΗΜΑΤΑ ΚΑΙ
ΓΕΝΙΚΕΣ ΣΗΜΕΙΩΣΕΙΣ
I SEE PLUMBING PLANS FOR LOCATIONS OF FLOOR
SINKS/DRAINS AND SUMP PUMPS FOR MECHANICAL
EQUIPMENT CONDENSATE PIPE.
ΑΝΕΤΡΕΞΕ ΣΤΑ ΥΔΡΑΥΛΙΚΑ ΣΧΕΔΙΑ ΓΙΑ ΤΗΝ ΘΕΣΗ ΤΩΝ
ΣΙΦΩΝΙΩΝ/ΝIΠΤHΡΑ ΣΦΟΥΓΓΑΡΙΣΜΑΤΟΣ ΚΑΙ ΤΩΝ ΑΝΤΛΙΩΝ
ΛΥΜΑΤΩΝ
J REFER TO MANUFACTURER'S INSTALLATION GUIDE FOR
REFRIGERANT PIPE SIZE REQUIREMENT.
AΝΑΤΡΕΞΤΕ ΣΤΟ ΕΓΧΕΙΡΙΔΙΟ ΕΓΚΑΤΑΣΤΑΣΗΣ ΤΟΥ
ΚΑΤΑΣΚΕΥΑΣΤΗ ΓΙΑ ΤΟ ΜΕΓΕΘΟΣ ΤΩΝ ΣΩΛΗΝΩΣΕΩΝ
ΨΥΚΤΙΚΟΥ ΠΟΥ ΑΠΑΙΤΕΙΤΑΙ
K CONTRACTOR MUST COORDINATE EQUIPMENT LOCATION
WITH OTHER TRADES.
O EΡΓΟΛΑΒΟΣ ΘΑ ΠΡΕΠΕΙ ΝΑ ΣΥΝΤΟΝΙΣΕΙ ΤΗΝ
ΧΩΡΟΘΕΤΗΣΗ ΤΟΥ ΕΞΟΠΛΙΣΜΟΥ ΜΕ ΤΑ ΑΛΛΑ ΤΜΗΜΑΤΑ
L ALL EQUIPMENT, DUCTWORK AND PIPING SUPPORTS MUST
BE SEISMIC RATED.
ΟΛΟΣ Ο ΕΞΟΠΛΙΣΜΟΣ, ΑΕΡΑΓΩΓΩΝ ΚΑΙ ΣΤΗΡΙΓΜΑΤΑ
ΣΩΛΗΝΩΣΕΩΝ ΠΡΕΠΕΙ ΝΑ ΝΑΙ ΣΕΙΣΜΙΚΑ
ΒΑΘΜΟΝΟΜΗΜΕΝΟΙ
M REFER TO A3/M-507 FOR TYPICAL CHILLED WATER COIL
CONNECTION DETAILS, A1/M-504 FOR TYPICAL HEATING
WATER COIL CONNECTION, A1/M-507 FOR TYPICAL
CONNECTIONS TO FLOOR MOUNTED CRAHUS, AND C4 &
A4/M-511 FOR ROOFTOP MECHANICAL EQUIPMENT
CONNECTION DETAILS.
ΑΝΑΤΡΕΞΤΕ ΣΤΗΝ ΛΕΠΤΟΜΕΡΕΙΑ A3/M-507 ΓΙΑ ΤΗΝ ΤΥΠΙΚΗ
ΣΥΝΔΕΣΗ TOY ΣΤΟΙΧΕΙΟΥ ΨΥΞΗΣ ΝΕΡΟΥ ,ΣΤΗΝ Α1/Μ-504
ΓΙΑ ΤΗΝ ΤΥΠΙΚΗ ΣΥΝΔΕΣΗ TOY ΣΤΟΙΧΕΙΟΥ ΘΕΡΜΑΝΣΗΣ
ΝΕΡΟΥ, ΣΤΗΝ Α1/Μ-507 ΓΙΑ ΤΗΝ ΤΥΠΙΚΗ ΣΥΝΔΕΣΗ ΓΙΑ
ΕΔΡΑΖΟΜΕΝΑ ΣΤΟ ΕΔΑΦΟΣ CRAHUS, ΚΑΙ ΣΤΙΣ
ΛΕΠΤΟΜΕΡΕΙΕΣ C4 & Α4/Μ-511 ΤΗΝ ΣΥΝΔΕΣΗ ΓΙΑ ΤΟΝ
ΜΗΧΑΝΟΛΟΓΙΚΟ ΕΞΟΠΛΙΣΜΟΥ ΣΤΟ ΔΩΜΑ
N PROVIDE DRIP PAN UNDER ANY PIPING THAT IS ABOVE
ELECTRICAL EQUIPMENT.
ΠΡΟΜΗΘΕΥΣΤΕ ΛΕΚΑΝΗ ΑΠΟΣΤΡΑΓΓΙΣΗΣ ΚΑΤΩ ΑΠΟ
ΣΩΛΗΝΩΣΕΙΣ ΠΟΥ ΕΙΝΑΙ ΠΑΝΩ ΑΠΟ ΗΛΕΚΤΡΙΚΟ ΕΞΟΠΛΙΣΜΟ
O REFER TO A1/M-502 FOR CONDENSATE DRAIN DETAILS.
ΑΝΑΤΡΕΞΤΕ ΣΤΗ ΛΕΠΤΟΜΕΡΕΙΑ Α1/Μ502 ΓΙΑ ΤHN
AΠΟΣΤΡΑΓΓΙΣΗ ΣΥΜΠΥΚΝΩΜΑΤΩΝ
P ΟΛΕΣ ΟΙ ΣΩΛΗΝΩΣΕΙΣ ΑΠΟΣΤΡΑΓΓΙΣΗΣ ΣΥΜΠΥΚΝΩΜΑΤΩΝ
ΝΑ ΕΧΟΥΝ ΚΛΙΣΗ 1% ΕΚΤΟΣ ΑΝ ANAΦEΡETAI ΔΙΑΦΟΡΕΤΙΚΑ
SHEET KEYED NOTES:
ΠΑΡΑΤΗΡΗΣΕΙΣ ΣΧΕΔΙΟΥ:
GENERAL NOTES:
ΓΕΝΙΚΕΣ ΠΑΡΑΤΗΡΗΣΕΙΣ:
PLAN NORTH
0 5000 10000
MILLIMETRESSCALE 1:100
30001000
T T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
CD
T
T T
T
T
T
T
T
T
T
H
H
A
B
C
D
1 2 3 4 5 6 7 98
UPS
ELEC
MENS
STAIR 1
LOBBY
QUARTER DECK
BUNK
IT LOGISTICS
RECYCLE
BREAK
RECEIVING
STAIR 2
DEMARC 2
FIRE PROT
127 N6 EQUIPMENT
ROOM
N6 MAINTENANCE
NIPR CAFE
N6 CONF
N6 ID
N6 ISSM
N6 C3P
N6
CORRIDOR
VEST
VEST
N6 MAINT
N6 STOR
MOTHERS
ELEV
WOMENS
JAN
UPS
A1 M-301
50 - CHWR
FPB-02
VAV-04
CRAHU-01A CRAHU-01B
FPB-01
FPB-04
FCU-06
FPB-06
VAV-06
CRAC-03A
CRAC-03B
FPB-03
CRAC-09A
CRAC-09B
40 - HWR
25 - CHWS
25 - CHWS
40 - HWS
25 - CHWR
25 - CHWR
5 4
CRAC-04B
FPB-05
FCU-02
CRAC-05B
CRAC-05A
UH-4
DEMARC 1
SIPR CAFE
TR G-1
CORRIDOR
UH-3
M-401 C1
EF-02
A3 M-301
40 - HWR
40 - HWS
20 - HWR
20 - HWS
20 - HWR
20 - HWS
20 - HWR
20 - HWS
20 - HWS
20 - HWR
20 - HWR
20 - HWS
20 - HWR
20 - HWS
20 - HWS
20 - HWR
50 - CHWS
50 - CHWS
50 - HWR
40 - HWS
25 - HWR
20 - HWR
20 - HWS
15 - HWS
15 - HWR
20 - CHWR
20 - CHWS
20 - HWS
15 - HWR
50 - HWR
20 - CHWS
20 - CHWR
50 - CHWR
25 - HWR
20 - CHWS
20 - CHWS
20 - CHWR
20 - CHWR
20 - HWR
20 - HWS
25 - HWS
40 - CHWR
40 - CHWR
FPB-31
CRAC-04A
BH-01
BH-03
A4
M-301
595959
CO
CO
CO
40 - PCD
40 - CD
DP-04
DP-03
DP-02
40 - HWS
40 - HWR
40 - CD
CO
20 - CD
20 - CD
CO
20 - PCD
40 - CD
CO
20 - PCD
20 - PCD
20 - PCD
20 - PCD
20 - PCD
20 - PCD
80 - CHWR
80 - CHWR
BH-06
UPS
DXFCU-01A
DXFCU-02A DXFCU-02B
DXFCU-01B
50 - CHWR
50 - CHWR
80 - CHWR
80 - CHWR
20 - HWS
50 - HWS
80 - CHWS
124124 123
20 - PCD
25 - HWS
20 - RS
15 - RL
16 - RS
10 - RL
D
C
B
1 2 3 4 5
1615269
DWG
SHEET OF
NAVFAC DRAWING NO.
CONSTR. CONTR. NO.
EPROJECT NO.
SCALE:
N62470-21-C-0005
DESIGN DIRECTOR
BRANCH MANAGER
PM/DM
DES DRW CHK
SATISFACTORY TO DATE
ACTIVITY
FOR COMMANDER NAVFAC
APPROVED
A/E INFO
SEAL
SY
M
DE
SC
RI
PT
IO
N
DA
TE
AP
PR
AS NOTED
N
AV
S U
PP
AC
T
SO
U D
A B
AY
N
AV
A L
FA
C
IL
IT
IE
S
EN
G
IN
E
ER
IN
G S
YS
TE
M C
O M
M
AN
D D
E P
AR
TM
E N
T O
F
TH
E N
A
VY
N
AV
AL
F
AC
IL
IT
IE
S E
N G
IN
EE
R
IN
G S
YS
TE
M C
O M
M
AN
D
A
FIRE PROTECTION
N O
R
FO
LK
, V
A A
TL
AN
TI
C
D E
SI
G
N A
N D
C O
N
ST
R U
C
TI
O N
1100 NORTH GLEBE ROAD
SUITE 500
ARLINGTON, VIRGINIA 22201
571.218.1000
FAX: 571.218.1600
D
C
B
A
1 2 3 4 5
RICHARD STEPHENS
TRUEWORTHY,PE / STELMASZEK,RA
PL
O
T
DA
TE
/T
IM
E:
7/
/ 2
1:
:0
PM
C :\U se rs
\C ha nH \D oc um en ts
\P
1- D
1-
M _R
_h ch an 4Z
9N T.
rv t
14 JUL 2021
RECEIVED BY JACOBIE TISDALE
AND STEVE PARK VIA EMAIL
MP101
GSH HC KG
P
C
O M
M U
N
IC
A
TI
O N
C E
N
TE
RS
O
U D
A B
AY
, G
R
EE
C E
M
EC
H P
IP
IN
G F
LO
O
R P
LA
N
G
R O
U N
D F
LO
O
R
14089291
M H
XA
N
O
ΛΟ
ΓΙ
ΚΑ
ΣΧ
ΕΔ
ΙΑ
ΣΩ
Λ Η Ν Ω
ΣΕ
Ω Ν
-ΙΣ
Ο
ΓΕ
ΙΟ
SCE
DPS
1 : 100A1
MECHANICAL PIPING PLAN - GROUND FLOOR
ΜΗΧΑΝΟΛΟΓΙΚΑ ΣΧΕΔΙΑ ΣΩΛΗΝΩΣΕΩΝ-ΙΣΟΓΕΙΟ
124 ROUTE REFRIGERANT PIPING UP TO FIRST LEVEL
INSIDE THE STUD WALL. COORDINATE WITH
STRUCTURAL DRAWINGS FOR CORE DRILLING
REQUIREMENT. ΔΙΑΔΡΟΜΗ ΨΥΚΤΙΚΩΝ ΣΩΛΗΝΩΝ ΜΕΧΡΙ
ΚΑΙ ΤΟΝ ΠΡΩΤΟ ΟΡΟΦΟ ΜΕΣΑ ΣΤΟΝ ΤΟΙΧΟ
ΓΥΨΟΣΑΝΙΔΑΣ. ΣΥΝΤΟΝΙΣΜΟΣ ΜΕ ΤΑ ΣΤΑΤΙΚΑ ΣΧΕΔΙΑ
ΓΙΑ ΤΟ ΚΕΝΤΡΟ ΤΩΝ ΟΠΩΝ ΠΟΥ ΑΠΑΙΤΕΙΤΑΙ.
65 PROVIDE DIELECTRIC UNION ON THE SECURE SIDE OF
CROSSING. SEAL PENETRATION AROUND PIPE WITH
ACCOUSTIC SEALEANT. REFER TO M-512 FOR DETAILS.
ΠΡΟΜΗΘΕΥΣΤΕ ΔΙΗΛΕΚΤΙΚΗ ΕΝΩΣΗ ΣΤΗΝ ΑΣΦΑΛΗ
ΠΛΕΥΡΑ ΤΟΥ ΔΙΑΚΟΠΤΗ.ΣΦΡΑΓΙΣΤΕ ΤΗΝ ΟΠΗ ΕΙΣΟΔΟΥ
ΤΟΥ ΣΩΛΗΝΑ ΜΕ HXOMΟΝΩΤΙΚΟ ΥΛΙΚΟ. ΑΝΑΤΡΕΞΤΕ
ΣΤΟ Μ-512 ΓΙΑ ΛΕΠΤΟΜΕΡΕΙΕΣ.
87 20 CHWS/R UP TO FIRST LEVEL.
20 CHWS/R ΠΑΝΩ ΠΡΟΣ ΤΟΝ ΠΡΩΤΟ ΟΡΟΦΟ
105 40 CHWS DOWN TO RAISED FLOOR.
40 CHWS ΚΑΤΩ ΠΡΟΣ ΤΟ ΥΠΕΡΥΨΩΜΕΝΟ ΔΑΠΕΔΟ 0
114 PROVIDE THERMOSTAT FOR SPACE TEMPERATURE
MONITORING AT THE BAS.
ΠΡΟΜΗΘΕΥΣΤΕ ΘΕΡΜΟΣΤΑΤΗ ΓΙΑ ΤΗΝ
ΠΑΡΑΚΟΛΟΥΘΗΣΗ ΘΕΡΜΟΚΡΑΣΙΑΣ ΤΟΥ ΧΩΡΟΥ ΣΤΟ
ΣΥΣΤΗΜΑ AYTOMATIΣMOY KTHΡIOY
119 HUMIDITY SENSOR FOR AHU-1 HUMIDIFIER CONTROL
ΑΙΣΘΗΤΗΡΙΟ ΥΓΡΑΣΙΑΣ ΓΙΑ ΤΟΝ ΕΛΕΚΤΗ ΤΟΥ
ΥΓΡΑΝΤΗΡΑ ΤΗΣ AHU-1
123 REFRIGERANT PIPING UP TO FIRST LEVEL.
ΨΥΚΤΙΚΕΣ ΣΩΛΗΝΩΣΕΙΣ ΠΑΝΩ ΜΕΧΡΙ ΤΟΝ ΠΡΩΤΟ
ΟΡΟΦΟ.
4 80 CHWS FA.
80 ΠΡΟΣΑΓΩΓΗ ΝΕΡΟΥ ΨΥΞΗΣ ΑΠΟ ΠΑΝΩ
5 50 HWR UP.
50 ΕΠΙΣΤΡΟΦΗ ΝΕΡΟΥ ΘΕΡΜΑΝΣΗΣ ΠΑΝΩ
58 INCLUDE BYPASS LINE WITH BALANCING VALVE. SEE
A2/M-505.
ΠΕΡΙΛΑΜΒΑΝΕΙ ΓΡΑΜΜΗ ΠΑΡΑΚΑΜΨΗΣ BYPASS ΜΕ
ΑΥΤΟΜΑΤΗ ΒΑΛΒΙΔΑ ΕΞΙΣΟΡΡΟΠΗΣΗΣ. ΑΝΑΤΡΕΞΤΕ ΣΤΟ
Α2/Μ-505
59 PROVIDE 20 DRAIN PIPE WITH ISOLATION VALVE TO
DRAIN DOWN HEADER DURING MAINTENANCE.
ΠΡΟΜΗΘΕΥΣΤΕ 20 ΣΩΛΗΝΑ ΑΠΟΣΤΡΑΓΓΙΣΗΣ ΜΕ ΒΑΝΑ
ΑΠΟΜΟΝΩΣΗΣ ΓΙΑ ΑΔΕΙΑΣΜΑ ΚΑΤΑ ΤΗΝ ΔΙΑΡΚΕΙΑ ΤΩΝ
ΕΡΓΑΣΙΩΝ ΣΥΝΤΗΡΗΣΗΣ
A MAINTAIN MANUFACTURER'S RECOMMENDED
CLEARANCES ON ALL EQUIPMENT.
ΔΙΑΤΗΡΗΣΤΕ ΤΟΝ ΣΥΝΙΣΤΩΜΕΝΟ ΕΛΕΥΘΕΡΟ ΧΩΡΟ ΑΠΟ
ΤΟΝ ΚΑΤΑΣΚΕΥΑΣΤΗ ΓΙΑ ΟΛΟ ΤΟΝ ΕΞΟΠΛΙΣΜΟ
B PROVIDE CLEARANCE FOR ALL ELECTRICAL AND CONTROL
PANELS PER CODE REQUIREMENT.
ΕΦΟΔΙΑΣΤΕ ΤΟΥΣ ΗΛΕΚΤΡΟΛΟΓΙΚΟΥΣ ΠΙΝΑΚΕΣ ΚΑΙ ΤΟΥΣ
ΠΙΝΑΚΕΣ ΕΛΕΓΧΟΥ ΜΕ ΤΟΝ ΑΠΑΙΤΟΥΜΕΝΟ ΕΛΕΥΘΕΡΟ
ΧΩΡΟ ΣΥΜΦΩΝΑ ΜΕ ΤΟΥΣ ΚΑΝΟΝΙΣΜΟΥΣ
C FOR PIPING NOT BURIED, ROUTE PIPING TIGHT TO
OVERHEAD STRUCTURE. DO NOT ROUTE PIPING ABOVE
ELECTRICAL EQUIPMENT.
ΓΙΑ ΣΩΛΗΝΩΣΕΙΣ ΠΟΥ ΔΕΝ ΕΙΝΑΙ ΘΑΜΜΕΝΕΣ, ΓΙΑ ΔΙΑΔΡΟΜΗ
ΣΩΛΗΝΩΝ ΠΟΥ ΕΙΝΑΙ ΔΕΜΕΝΕΣ ΠΑΝΩ ΣΤΗΝ ΚΑΤΑΣΚΕΥΗ, Η
ΔΙΑΔΡΟΜΗ ΤΩΝ ΣΩΛΗΝΩΝ ΝΑ ΜΗΝ ΕΙΝΑΙ ΠΑΝΩ ΑΠΟ
ΗΛΕΚΤΡΟΛΟΓΙΚΟ ΕΞΟΠΛΙΣΜΟ
D COORDINATE WORK WITH ALL OTHER TRADES.
ΣΥΝΤΟΝΙΣΤΕ ΤΗΝ ΕΡΓΑΣΙΑ ΜΕ ΟΛΑ ΤΑ ΑΛΛΑ ΤΜΗΜΑΤΑ
E CONTRACTOR TO VERIFY EXACT LOCATIONS, SIZES,
PIPING MTERIAL OF EXISTING UTILITIES AT JOB SITE
BEFORE COMMENCEMENT OF ANY WORKS. CONTRACTOR
WILL NOTIFY OWNER AND ARCHITECT/ENGINEER OF ANY
DISCREPENCIES FOUND ON SITE BETWEEN
CONSTRUCTION DOCUMENTS AND ACTUAL CONDITIONS.
Ο ΕΡΓΟΛΑΒΟΣ ΘΑ ΠΡΕΠΕΙ ΝΑ ΕΠΑΛΗΘΕΥΣΕΙ ΤΗΝ ΑΚΡΙΒΗ
ΘΕΣΗ,ΜΕΓΕΘΟΣ, ΤΟ ΥΛΙΚΟ ΤΩΝ ΣΩΛΗΝΩΣΕΩΝ ΤΩΝ
ΥΠΑΡΧΟΝΤΩΝ ΣΤΟΙΧΕΙΩΝ ΠΡΙΝ ΞΕΚΙΝΗΣΕΙ ΟΠΟΙΑΔΗΠΟΤΕ
ΕΡΓΑΣΙΑ. Ο ΕΡΓΟΛΑΒΟΣ ΘΑ ΠΡΕΠΕΙ ΝΑ ΕΝΗΜΕΡΩΣΕΙ ΤΟΝ
ΙΔΙΟΚΤΗΤΗ ΚΑΙ ΤΟΝ ΑΡΧΙΤΕΚΤΟΝΑ/ΜΗΧΑΝΙΚΟ ΓΙΑ
ΟΠΟΙΑΔΗΠΟΤΕ ΔΙΑΦΟΡΑ ΒΡΗΚΕ ΣΤΑ ΚΑΤΑΣΚΕΥΑΣΤΙΚΑ
ΣΧΕΔΙΑ ΚΑΙ ΣΤΙΣ ΠΡΑΓΜΑΤΙΚΕΣ ΣΥΝΘΗΚΕΣ.
F COORDINATE WORK WITH ARCHITECTUAL FEATURES SO
THAT INTERFERENCE BETWEEN PIPING, EQUIPMENT,
MECHANICAL WORK, ELECTRICAL WORK, AND BUILDING
STRUCTURE WILL BE AVOIDED.
ΣΥΝΤΟΝΙΣΤΕ ΤΙΣ ΕΡΓΑΣΙΕΣ ΜΕ ΤΑ ΑΡΧΙΤΕΚΤΟΝΙΚΑ ΣΧΕΔΙΑ
ΕΤΣΙ ΩΣΤΕ ΟΠΟΙΑΔΗΠΟΤΕ ΕΜΠΛΟΚΗ ΜΕΤΑΞΥ
ΣΩΛΗΝΩΣΕΩΝ, ΕΞΟΠΛΙΣΜΟΥ, ΜΗΧΑΝΟΛΟΓΙΚΩΝ ΕΡΓΑΣΙΩΝ,
ΗΛΕΚΤΡΟΛΟΓΙΚΩΝ ΕΡΓΑΣΙΩΝ ΚΑΙ ΣΤΑΤΙΚΩΝ ΚΤΙΡΙΟΥ ΝΑ
ΑΠΟΦΕΥΓΘΟΥΝ
G PROVIDE ISOLATION VALVES FOR EACH BRANCH RUN OF
HYDRONIC PIPING.
ΠΡΟΜΗΘΕΥΣΤΕ ΒΑΝΕΣ ΑΠΟΜΟΝΩΣΗΣ ΓΙΑ ΚΑΘΕ ΚΛΑΔΟ
ΤΩΝ ΥΔΡΑΥΛΙΚΩΝ ΣΩΛΗΝΩΣΕΩΝ
H REFER TO M-001 FOR LEGEND AND GENERAL NOTES.
ΑΝΑΤΡΕΞΤΕ ΣΤΟ ΣΧΕΔΙΟ Μ-001 ΓΙΑ ΥΠΟΜΝΗΜΑΤΑ ΚΑΙ
ΓΕΝΙΚΕΣ ΣΗΜΕΙΩΣΕΙΣ
I SEE PLUMBING PLANS FOR LOCATIONS OF FLOOR
SINKS/DRAINS AND SUMP PUMPS FOR MECHANICAL
EQUIPMENT CONDENSATE PIPE.
ΑΝΕΤΡΕΞΕ ΣΤΑ ΥΔΡΑΥΛΙΚΑ ΣΧΕΔΙΑ ΓΙΑ ΤΗΝ ΘΕΣΗ ΤΩΝ
ΣΙΦΩΝΙΩΝ/ΝIΠΤHΡΑ ΣΦΟΥΓΓΑΡΙΣΜΑΤΟΣ ΚΑΙ ΤΩΝ ΑΝΤΛΙΩΝ
ΛΥΜΑΤΩΝ
J REFER TO MANUFACTURER'S INSTALLATION GUIDE FOR
REFRIGERANT PIPE SIZE REQUIREMENT.
AΝΑΤΡΕΞΤΕ ΣΤΟ ΕΓΧΕΙΡΙΔΙΟ ΕΓΚΑΤΑΣΤΑΣΗΣ ΤΟΥ
ΚΑΤΑΣΚΕΥΑΣΤΗ ΓΙΑ ΤΟ ΜΕΓΕΘΟΣ ΤΩΝ ΣΩΛΗΝΩΣΕΩΝ
ΨΥΚΤΙΚΟΥ ΠΟΥ ΑΠΑΙΤΕΙΤΑΙ
K CONTRACTOR MUST COORDINATE EQUIPMENT LOCATION
WITH OTHER TRADES.
O EΡΓΟΛΑΒΟΣ ΘΑ ΠΡΕΠΕΙ ΝΑ ΣΥΝΤΟΝΙΣΕΙ ΤΗΝ
ΧΩΡΟΘΕΤΗΣΗ ΤΟΥ ΕΞΟΠΛΙΣΜΟΥ ΜΕ ΤΑ ΑΛΛΑ ΤΜΗΜΑΤΑ
L ALL EQUIPMENT, DUCTWORK AND PIPING SUPPORTS MUST
BE SEISMIC RATED.
ΟΛΟΣ Ο ΕΞΟΠΛΙΣΜΟΣ, ΑΕΡΑΓΩΓΩΝ ΚΑΙ ΣΤΗΡΙΓΜΑΤΑ
ΣΩΛΗΝΩΣΕΩΝ ΠΡΕΠΕΙ ΝΑ ΝΑΙ ΣΕΙΣΜΙΚΑ
ΒΑΘΜΟΝΟΜΗΜΕΝΟΙ
M REFER TO A3/M-507 FOR TYPICAL CHILLED WATER COIL
CONNECTION DETAILS, A1/M-504 FOR TYPICAL HEATING
WATER COIL CONNECTION, A1/M-507 FOR TYPICAL
CONNECTIONS TO FLOOR MOUNTED CRAHUS, AND C4 &
A4/M-511 FOR ROOFTOP MECHANICAL EQUIPMENT
CONNECTION DETAILS.
ΑΝΑΤΡΕΞΤΕ ΣΤΗΝ ΛΕΠΤΟΜΕΡΕΙΑ A3/M-507 ΓΙΑ ΤΗΝ ΤΥΠΙΚΗ
ΣΥΝΔΕΣΗ TOY ΣΤΟΙΧΕΙΟΥ ΨΥΞΗΣ ΝΕΡΟΥ ,ΣΤΗΝ Α1/Μ-504
ΓΙΑ ΤΗΝ ΤΥΠΙΚΗ ΣΥΝΔΕΣΗ TOY ΣΤΟΙΧΕΙΟΥ ΘΕΡΜΑΝΣΗΣ
ΝΕΡΟΥ, ΣΤΗΝ Α1/Μ-507 ΓΙΑ ΤΗΝ ΤΥΠΙΚΗ ΣΥΝΔΕΣΗ ΓΙΑ
ΕΔΡΑΖΟΜΕΝΑ ΣΤΟ…