Atch 32 - BLDG 115.pdf
PDF 5 MB Posted
- Attached to
- Y1AZ--EHRM Infrastructure Upgrades Construction - St. Cloud Federal contract opportunity
- Solicitation number
- 36C77622B0035
About this file
This federal solicitation requests proposals for infrastructure upgrades at the St. Cloud Veterans Affairs Health Care System facility. Required work includes electrical, telecommunications, data center, HVAC, and hazardous materials abatement services. The contractor must furnish all labor, materials, tools, and equipment to complete upgrades to electrical systems, install a new UPS and building management system interfaces, expand and renovate existing space as needed, upgrade fiber infrastructure between campus buildings, and perform other physical security and network improvements. Proposals are due in response to solicitation number 36C77622B0035 issued by the Department of Veterans Affairs Technology Acquisition Center located in Austin, Texas.
View the file
Other files for this federal contract opportunity
Show all 50
Y1AZ--EHRM Infrastructure Upgrades Construction - St. Cloud has more files on GovTribe.
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
EXISTING FIBER - INSIDE
VFY EXIST
EXISTING FIBER - OUTSIDE
VFY EXIST
FIBER ROUTE - INSIDE
SEE TELECOM
FIBER ROUTE - OUTSIDE
SEE CIVIL
BUILDING OUTLINE
VFY EXIST
CORRIDOR OUTLINE
VFY EXIST
LEGEND
TO 8TH ST WEST ONLYTO 8TH ST EAST & WEST
44TH AVE.
TRAIL 1
TRAIL 2
TRANSFER
SWITCH
CAPACITOR
BANK (3)
SWITCH
(2)
15KV
MAIN
SW
BATT
35 KV
TO
15 KV
TRANSFORMER
35KV
FUSED
SWITCH
METER 35KV
SWITCH
GRAVEL
GRAVEL
GRAVEL
EXISTING
ROAD
CHAIN LINK FENCE
CHAIN LINK FENCE
16' GATE
GRAVEL
ELECTRICAL
SUBSTATION
G E N E R A T O R
FUEL LINES
CONDU ITS TO TU NNEL
M V
D U
C T
B A
N K
1 1 2 W
PHARMACY ADDITION
11 2 E
G E N E R A T O R
B
CORRIDOR LINK
A
C T
TR
A
IL
ER
174 s .f.
256 s .f.
185 s .f.
149 s ..f.
155 s .f.
104 s .f.
70 s. .f .
72 s .f.
110 s .f.
276 s .f.
112 s .f.
99 s .f.
57 s .f.
146 s .f.
434 s .f.
R A
MP
U P
1:
M A X
R A
MP
U P
1:
M A X
RA
M P
UP
1:2 0 M
AX
TRANSFER
SWITCH
CAPACITOR
BANK (3)
SWITCH
(2) 15KV
MAIN
SW
BATT
35 KV
TO
15 KV
TRANSFORMER
35KV
FUSED
SWITCH
METER 35KV
SWITCH
.3
TRANSFORMER
BUILD ING
#91
5,000 GAL.
UNDERGROUND
DIESEL FUEL TANK
EXISTIN G G AS SU P P LY EQ U IP M EN T TO R EM AIN
O P ER ATIO N AL DU R IN G D EM O LITIO N AN D N EW
C O N STR U C TIO N. P R O TEC T EQU IP M EN T AN D
P IP ELIN ES IN AC C O R D AN C E W ITH G AS SU P P LIER 'S
R EC O M M EN D ATIO N S
N EW G AS SU P P LY M AIN
IN TO B U ILD IN G
SP AR E
P H O N E LIN E
EXTEN D S TO
E XISTIN G
P H O N E IN
B O ILER R O O M
P ER P LAN .
SP AR E
P H O N E
LIN E TO
M ETER
TU N N EL
E XTEN D S
A D D ITIO N AL
2'- 0" U N D ER
B U ILD IN G
FUEL LINE
VENT LINE
1,000 GAL.
UNDERGROUND
DIESEL FUEL
TANK
1,000/5,000 GAL.
UNDERGROUND
DIESEL FUEL TANK
1,000 GAL.
UNDERGROUND
DIESEL FUEL TANK
1,000 GAL.
UNDERGROUND
DIESEL FUEL TANK
S 1
LIG H T
N EW G AS SU P P LY
(C O O R D IN ATE W ITH SU P P LIER )
12"D
10"D
"D
TP TP
EXIST. BUILDING
EXIST.
BUS STOP
CC
L O
O P
16"
20"
12"
3"
8"
DN
0.
0’
BIRDCAGE
B
IR
D C
A G
E
NSP ELECTRICAL
FOR HWY DEPT
T101
I.T.
CHILLER
C O
NC
. B
LO
CKS
PAT
I O
C O
NC
. B
LO
CKS
PAT
I O
C O
NC
. B
LO
CKS
PAT
I O
C O
NC
. B
LO
CKS
PAT
I O
C O
NC
. B
LO
CKS
PAT
I O
C O
NC
. B
LO
CKS
PAT
I O
C O
NC
. B
LO
CKS
PAT
I O
C O
NC
. B
LO
CKS
PAT
I O
DN
DN
FD
DN
F B
F
B
F B
F
B
F B
F
B
SOUTH
VESTIBULE
PASS
THROUGH
LINK TO
BUILDI NG 51
6 3. 32 56
1 13 5. 35 78
PARKING
NO
PARKING
93 49
37 6
109 5
1A
S M
O K
E B
L D
G
SMOKE
BLDG
SMOKE
BLDG
S M
O K
E B
L D
G
SMOKE
BLDG
M.H.
STOR.
SMOKE
BLDG
SMOKE
BLDG
SMOKE
BLDG
SMOKE
BLDG
SMOKE
BLDG
STOR.
BIO-
HAZ.
SAUK RIVER
GP
HOLDING POND
I hereby certify that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly Licensed Architect under the laws of the State of
Minnesota.
Name:
Date: License Number: MN# 18157
Typed or Printed Name: Tom Olesak
OWNER AND
CONSULTANTS:
CONTACT:
ADDRESS:
MIKE ENGMARK
ST CLOUD VA MEDICAL CENTER
4801 VETERANS DRIVE
ST. CLOUD, MN 56303
NAME:
ADDRESS:
CONTACT:
ADVANCED STRUCTURAL TECHNOLOGIES
7301 OHMS LANE; SUITE 215
EDINA, MN 55439
ZACHARY CRAIG
PHONE:
NAME:
ADDRESS:
CONTACT:
SPECIALIZED ENGINEERING SOLUTIONS
10360 ELLISON CIRCLE
OMAHA, NE 68134
KRIS BURNHAM
PHONE: 402-991-5520
NAME:
ADDRESS:
CONTACT:
PHONE:
NAME:
ADDRESS:
CONTACT:
PHONE:
NAME:
ADDRESS:
CONTACT:
PHONE:
ANDERSON ENGINEERING OF MN, LLC
13605 1ST AVE NORTH, SUITE 100
PLYMOUTH, MN 55441
IAN WEBER
763-412-4000
ARCHITECT:
ANDERSON ENGINEERING OF MN, LLC
13605 1ST AVE NORTH, SUITE 100
PLYMOUTH, MN 55441
EDWARD MARKFORT
763-412-4000
952-854-9302
SPECIALIZED ENGINEERING SOLUTIONS
10360 ELLISON CIRCLE
OMAHA, NE 68134
KRIS BURNHAM
402-991-5520
No DATEREVISION
DRAWING TITLE
CHECKED BY
ST.CLOUD, MN 56303
VA MEDICAL CENTER
BUILDING No
LOCATION
DRAWING NO.DRAWN
DWG. OF
PROJECT TITLE
PLOT SCALE
PROJECT NO.
COVER
DATE:
APPROVED: APPROVED: PROJECTS SECTION MANAGER
APPROVED: OIT MANAGER DATE: APPROVED: ASSISTANT CHIEF ENGINEER DATE:
APPROVED: SAFETY MANAGER
APPROVED: CHIEF OF POLICE
APPROVED: PATIENT SAFETY
DATE:
DATE:
DATE: APPROVED: EMS MANAGER
APPROVED: M/O MANAGER
DATE:
DATE:
DATE:DATE:
APPROVED: MEDICAL CENTER DIRECTOR
APPROVED: PROJECT COR DATE:
APPROVED: INFECTION CONTROL NURSE DATE:
APPROVED: SERVICE LINE DIRECTOR
APPROVED: GEMS COORDINATOR DATE:
DATE:
APPROVED: NURSE EXECUTIVE
APPROVED: CHIEF OF STAFF DATE:
APPROVED: DIRECTOR FMS
APPROVED: ASSOCIATE DIRECTOR
DATE:
DATE:
DATE:
DATE:APPROVED: DATE:
APPROVED: DATE:
APPROVED: DATE:
Main Campus, St. Cloud, Minnesota St. Cloud VA Health Care System
N
CONSULTANT ARCHITECT/ENGINEER OF RECORD STAMP
FULLY
SPRINKLERED
VICINITY MAP:
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PHONE: 320-252-1670
CIVIL ENGINEER:
VA COR:
TELECOMMUNICATIONS ENGINEER:
CONTACT:
ADDRESS:
JONATHAN WEST
ST CLOUD VA MEDICAL CENTER
4801 VETERANS DRIVE
ST. CLOUD, MN 56303
PHONE: 504-250-2699
PROGRAM MANAGER:
EMAIL: Jonathan.West@vciint.com
STRUCTURAL ENGINEER:
MECH/ELEC/PLUMB/FIRE ENGINEER:
C
U s e rs
\P u b li c \D o c u m e n ts \R e v it
P ro je c ts
\1 -1
-R
E
M a rk fo rt
.r v t
/2
/2
:1 :3
P
M
115-GI000
BUILDING 115 COVER SHEET &
SHEET INDEX
EHRM INFRASTRUCTURE
UPGRADES
656‐21‐235
03/30/2022
EM EM
16305
BUILDING 115 - EHRM INFRASTRUCTURE UPGRADES
03/30/2022
0APPROX 150' 300'75'
SHEET INDEX - BUILDING 115
SHEET NO. SHEET TITLE
115-GI000 BUILDING 115 COVER SHEET & SHEET INDEX
115-GI111 FIRST FLOOR - INFECTION CONTROL & PHASING PLAN
115-AS110 FIRST FLOOR PLANS
115-TD110 FIRST FLOOR PLAN - TELECOM - DEMOLITION
115-TN110 FIRST FLOOR PLAN - TELECOMMUNICATIONS
115-TN210 FIRST FLOOR PLAN - TELECOM - CABLE DISTANCE
115-TN400 ENLARGED PLANS - TELECOMMUNICATIONS
115-E201 FIRST FLOOR - ELECTRICAL
115-E300 ELECTRICAL ENLARGED PLANS
115-M101 FIRST FLOOR DEMOLITION - MECHANICAL
115-M201 FIRST FLOOR - MECHANICAL
SEE GENERAL SHEETS FOR ADDITIONAL INFORMATION
ROOM SCHEDULE
NO. NAME C
A
B
LI
N G
P A
T C
H P
A N
E L
F
IB
E R
P O
W E
R
B O
N D
IN
G
U P
S
D E
D
IC
A T
E D
C O
O
LI
N G
T E
M P
E R
A T
U R
E
H U
M
ID
IT
Y
R A
C K
S E
N S
O R
S P
A C
E
AREA
WIDTH
(FT)
LENGTH
(FT)
HT TO
CLG
STRUCT REMARKS
FIRST FLOOR
107 TELECOM ROOM X X X X X 74 SF 8.1 9.0 13.25 UPDATE EXIST IT/DATA ROOM TO EHRM TELECOM ROOM
STANDARDS. SEE TELECOM DRAWINGS
OPENING SCHEDULE
VA Building Number
ASSOCIATED ROOMS OPENING PANEL INFORMATION FRAME INFORMATION
H D
W G
R O
U P
F
IR
E L
A B
E L
(M
IN
G A
S K
E T
E
LE
C T
R
IC
A L
S L
A B
E L
COMMENTSFROM ROOM NAME TO ROOM NAME NUMBER WIDTH HEIGHT
PANEL
TYPE
2ND
PANEL
TYPE
PANEL
GLAZING FRAME TYPE
FRAME
GLAZING
HAZARDOUS MATERIAL SCHEDULE
LEVEL ROOM NO. ROOM NAME
QUESTIONABLE HAZARDOUS
ELEMENT POSSIBLE ABATEMENT ACTION
FIRST FLOOR 107 TELECOM ROOM NONE NONE
HAZARDOUS MATERIALS MAY BE ENCOUNTERED THROUGHOUT THE DISTRIBUTION ROUTING THROUGH CEILING PLENUMS AND UTILITY TUNNELS. INSTALLATION OF DISTRIBUTION SHALL NOT
DISTURB QUESTIONABLE HAZARDOUS MATERIAL.
LEAK PREVENTION / DIVERTER SCHEDULE
LEVEL
ROOM
NO. ROOM NAME OVERHEAD LEAK DIVERTER AND DRAIN PIPING LEAK PREVENTION BARRIER WATERPROOFING
FIRST FLOOR 107 TELECOM ROOM
SEE GENERAL NOTES SHEET FOR DETAIL. MWP = MEMBRANE WATERPROOFING. MASONRY = FLUID-APPLIED WATERPROOFING. INT = INTERIOR. EXT = EXTERIOR
ICRA PHASE CONSTRUCTION ROOM SCHEDULE
LEVEL
ROOM
NO. ROOM NAME
CAI BLDG NAME /
FUNCTION
CONSTRUCTION
PROJECT ACTIVITY
INFECTION CONTROL
RISK GROUP
CONTROL
PROCEDURE CLASS SECTION
CONSTRUCTION ZONE /
OCCUPIED CONSTR
DAY /
NIGHT
FIRST FLOOR 107 TELECOM ROOM MENTAL HEALTH BEDS TYPE C GROUP 2 CLASS III EAST OCCUPIED CONSTRUCTION DAY
SEE GENERAL NOTES SHEET FOR CONSTRUCTION INFECTION CONTROL RISK ASSESSMENT (ICRA) DESCRIPTIONS. TYPE, GROUP AND CLASS SELECTED TO BEST OF DESIGN TEAM'S KNOWLEDGE.
FINAL DETERMINATION BY THE VA WILL BE MADE AT A LATER DATE.
DN
CORRIDOR
PAT TLT
141A
CORRIDOR
CORRIDOR
CORRIDOR
PAT TLT
139A
PAT TLT
140A
PAT RM #1
PAT RM #2
SEMI PRIVATE #1
SEMI PRIVATE #2
OFFICE
WARD CLERK
110PAT TLT
120A
LAUNDRY / TUB
HEAD NURSE
ENVIRON
STORAGE /HSKP
PAT TLT
136A
PAT TLT
132A
CRAWL SPACE
ACCESS
127A
STORAGE
EM EXIT
PAT TLT
129A
PAT TLT
130APAT TLT
131A
SEMI PRIVATE #5
SEMI PRIVATE #6
SEMI PRIVATE #4
SEMI PRIVATE #3
DINING
DAY ROOM
133A
RESTRAINT
ROOM
120C
CORRIDOR
CORRIDOR
CORRIDOR
103-2
RECEIVING
CORRIDOR
RECEPTION
SECURITY DESK
104A
FAMILY WAITING
LOCKERS
104C
CORRIDOR
CORRIDOR
PUBLIC TLT
PUBLIC TLT
SOCIAL WORK
OFFICE (FUTURE
ELEVATOR)
SOCIAL WORK
(FUTURE
ELEVATOR)
EXAM RM
BARIATRIC PAT
RM #6
PAT TLT
121A
OFFICE
PAT RM #8
PAT TLT
124A
PAT TLT
126A
QUIET LOUNGE
PAT TLT
137A
PAT TLT
138A
PAT TLT
123A
ELEC
COPY
SPS
SOILED HOLD
SALLY PORT
SALLY PORT
CLEAN LINEN
INTAKE
ANTE
SECLUSION
120B
MEDS
NURSE WORK
122A
NURSE STATION
VESTIBULE
PAT RM #5
MECHANICAL
STAFF LOUNGE
104D
GROUP
THERAPY
PAT RM #7
STAFF TLT
104B
PAT RM #4
PAT RM #3
TELECOM
ROOM
INFECTION CONTROL RISK ASSESSMENT (ICRA) LEGEND
LIMITS OF CONSTRUCTION
1 HOUR FIRE RATED ICRA / CONSTRUCTION BARRIER
LOCATION, AND DOOR, WHERE SHOWN
TEMPORARY NON-RATED (PLASTIC SHEETING) CONSTRUCTION BARRIER
LOCATION, WHERE APPROVED BY THE VA FOR USE IN RISK TYPE B.
UPGRADE TO 1 HOUR RATED PARTITION WHEN DIRECTED BY THE VA
I hereby certify that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly Licensed Architect under the laws of the State of
Minnesota.
Name:
Date: License Number: MN# 18157
Typed or Printed Name: Tom Olesak
No DATEREVISION
DRAWING TITLE
CHECKED BY
ST.CLOUD, MN 56303
VA MEDICAL CENTER
BUILDING No
LOCATION
DRAWING NO.DRAWN
DWG. OF
PROJECT TITLE
PLOT SCALE
PROJECT NO.
DATE:
CONSULTANT ARCHITECT/ENGINEER OF RECORD STAMP
FULLY
SPRINKLERED
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10 C
U s e rs
\P u b li c \D o c u m e n ts \R e v it
P ro je c ts
\1 -1
-R
E
M a rk fo rt
.r v t
/2
/2
:1 :3
P
M
115-GI111
FIRST FLOOR - INFECTION
CONTROL & PHASING PLAN
EHRM INFRASTRUCTURE
UPGRADES
656‐21‐235
03/30/2022
EM BMW
16305
03/30/2022
1/8" = 1'-0"
FIRST FLOOR - CONST BARRIER PLAN
ROOM ICRA SCHEDULE
LEVEL
ROOM
NO. ROOM NAME CAI BLDG NAME / FUNCTION CONSTRUCTION PROJECT ACTIVITY INFECTION CONTROL RISK GROUP CONTROL PROCEDURE CLASS
FIRST FLOOR 107 TELECOM ROOM MENTAL HEALTH BEDS TYPE C GROUP 2 CLASS III
SEE GENERAL NOTES SHEET FOR CONSTRUCTION INFECTION CONTROL RISK ASSESSMENT (ICRA) DESCRIPTIONS. TYPE, GROUP AND CLASS SELECTED TO BEST OF DESIGN TEAM'S KNOWLEDGE.
FINAL DETERMINATION BY THE VA WILL BE MADE AT A LATER DATE.
N
0 8' 16'4'
PAT TLT
141A
CORRIDOR
CORRIDOR
CORRIDOR
PAT TLT
139A
PAT TLT
140A
PAT RM #1
PAT RM #2
SEMI PRIVATE #1
SEMI PRIVATE #2
OFFICE
WARD CLERK
110PAT TLT
120A
LAUNDRY / TUB
HEAD NURSE
ENVIRON
STORAGE /HSKP
PAT TLT
136A
PAT TLT
132A
CRAWL SPACE
ACCESS
127A
STORAGE
EM EXIT
PAT TLT
129A
PAT TLT
130APAT TLT
131A
SEMI PRIVATE #5
SEMI PRIVATE #6
SEMI PRIVATE #4
SEMI PRIVATE #3
DINING
DAY ROOM
133A
RESTRAINT
ROOM
120C
CORRIDOR
CORRIDOR
CORRIDOR
103-2
RECEIVING
CORRIDOR
RECEPTION
SECURITY DESK
104A
FAMILY WAITING
LOCKERS
104C
CORRIDOR
CORRIDOR
PUBLIC TLT
PUBLIC TLT
SOCIAL WORK
OFFICE (FUTURE
ELEVATOR)
SOCIAL WORK
(FUTURE
ELEVATOR)
EXAM RM
BARIATRIC PAT
RM #6
PAT TLT
121A
OFFICE
PAT RM #8
PAT TLT
124A
PAT TLT
126A
QUIET LOUNGE
PAT TLT
137A
PAT TLT
138A
PAT TLT
123A
ELEC
COPY
SPS
SOILED HOLD
SALLY PORT
SALLY PORT
CLEAN LINEN
INTAKE
ANTE
SECLUSION
120B
MEDS
NURSE WORK
122A
NURSE STATION
VESTIBULE
PAT RM #5
MECHANICAL
STAFF LOUNGE
104D
GROUP
THERAPY
PAT RM #7
STAFF TLT
104B
PAT RM #4
PAT RM #3
TELECOM
ROOM
8' -1
/4
9'-0 1/2"
115-AS110
TELECOM
ROOM
3'-0" 3'-0 3/4"
TELECOM
ROOM
TELECOM
ROOM
I hereby certify that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly Licensed Architect under the laws of the State of
Minnesota.
Name:
Date: License Number: MN# 18157
Typed or Printed Name: Tom Olesak
No DATEREVISION
DRAWING TITLE
CHECKED BY
ST.CLOUD, MN 56303
VA MEDICAL CENTER
BUILDING No
LOCATION
DRAWING NO.DRAWN
DWG. OF
PROJECT TITLE
PLOT SCALE
PROJECT NO.
DATE:
CONSULTANT ARCHITECT/ENGINEER OF RECORD STAMP
FULLY
SPRINKLERED
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10 C
U s e rs
\P u b li c \D o c u m e n ts \R e v it
P ro je c ts
\1 -1
-R
E
M a rk fo rt
.r v t
/2
/2
:1 :4
P
M
115-AS110
FIRST FLOOR PLANS
EHRM INFRASTRUCTURE
UPGRADES
656‐21‐235
03/30/2022
EM EM
16305
03/30/2022
N
0 8' 16'4' 1/8" = 1'-0"
FIRST FLOOR - OVERALL PLAN
1/4" = 1'-0"3
ENLARGED FLOOR PLAN
N
0 4' 8'2'
1/4" = 1'-0"
DEMOLITION PLAN
N
0 8' 16'4'
1/4" = 1'-0"4
REFLECTED CEILING PLAN
N
0 8' 16'4'
DE1
RC1
_DEMOLITION PLAN KEYED NOTES
DE1 PREPARE WALL FOR PLYWOOD BACKBOARD INSTALLATION AND EHRM
REQUIREMENTS, SEE FLOOR PLAN AND TELECOM DRAWINGS
NOTE: NOT ALL KEYED NOTES MAY BE USED ON EACH PLAN
_FLOOR PLAN KEYED NOTES
FL1 ALL FOUR PERIMETER WALL PARTITIONS APPLY 4' BY 8' AC GRADE ¾”
TRADE SIZE FIRE RATED PLYWOOD BACKBOARD FINISHED WITH
HIGH-GLOSS WHITE PAINT OVER TWO COATS OF FIRE RESISTANT PAINT
FOR SERVICE PROVIDER / SECURITY / VIDEO / ET CETERA. DO NOT PAINT
OVER FIRE RATING STAMP.
FL20 TELECOM EQUIPMENT, SEE TELECOM DRAWINGS.
NOTE: NOT ALL KEYED NOTES MAY BE USED ON EACH PLAN
_REFLECTED CEILING PLAN KEYED NOTES
RC1 LED LIGHTING, SEE ELECTRICAL. IN FRONT OF AND BEHIND CABINET
ROWS PROVIDE 500 LUMENS IN HORIZONTAL AND 200 LUMENS IN THE
VERTICAL AT 3 FT AFF. OPERATED BY MOTION SENSOR PER CABINET
ROW OR SECTION.
RC2 OPEN TO STRUCTURAL FLOOR ABOVE
NOTE: NOT ALL KEYED NOTES MAY BE USED ON EACH PLAN
DE1
DE1
FL1 FL20
RC2
_SHEET NOTES
1. SEE GENERAL NOTES AND CAMPUS DRAWINGS FOR GENERAL
INFORMATION, LIFE SAFETY, ICRA, AND PHASING
2. ALL EXISTING CONDITIONS MUST BE FIELD VERIFIED BY THE
CONTRACTOR PRIOR TO DEMOLITION OR CONSTRUCTION. EXISTING
CONDITIONS THAT DIFFER FROM THOSE SHOWN MUST BE BROUGHT TO
THE ATTENTION OF THE C.O.R. TO INFORM THE ARCHITECTS AND
ENGINEERS.
3. THE INFORMATION SHOWN ON THE DRAWINGS IS BASED ON DRAWINGS
AND PHOTOGRAPHS PROVIDED BY THE C.O.R. COMBINED WITH
OBSERVATIONS AND SURVEYED DATA FROM THE ARCHITECTS AND
ENGINEERS.
4. SEE CIVIL, STRUCTURAL, TELECOM, ELECTRICAL, MECHANICAL, AND
PLUMBING DRAWINGS AND SPECIFICATIONS FOR ADDITIONAL
DEMOLITION AND CONSTRUCTION REQUIREMENTS.
5. PORTABLE FIRE EXTINGUISHERS (CO2 OR HALOGENATED TYPE AS
DETERMINED BY THE VA) WITH WALL MOUNT BRACKET AND CODE
REQUIRED SIGNAGE SHALL BE PROVIDED BY THE CONTRACTOR WITHIN
TELECOM ROOMS.
157159
167186
167 60
167 167
60 165
251 64
121 106
112121
88 88
125145
642 607
DESK
30X66
DESK
30X66
LAT. FILE
18X42
B O
O K
S
TABLE
36" DIA.
LAT. FILE
18X42
B O
O K
S
DESK
30X66
B O
O K
S
L A
T . F
IL
E
X
D E
S K
X
LAT. FILE
18X42
BOOKS
TABLE
36" DIA.
DESK
30X66
L A
T . F
IL
E
X
B O
O K
S
D E
S K
X
LAT. FILE
18X42
B O
O K
S
DN
CORRIDOR
PAT TLT
141A
LINK
CONCOURSE
CORRIDOR
CORRIDOR
CORRIDOR
PAT TLT
139A
PAT TLT
140A
PAT RM #1
PAT RM #2
SEMI PRIVATE #1
OFFICE
WARD CLERK
110PAT TLT
120A
LAUNDRY / TUB
HEAD NURSE
ENVIRON
STORAGE /HSKP
PAT TLT
136A
PAT TLT
132A
CRAWL SPACE
ACCESS
127A
STORAGE
EM EXIT
PAT TLT
129A
PAT TLT
130APAT TLT
131A
SEMI PRIVATE #5
SEMI PRIVATE #6
SEMI PRIVATE #4
SEMI PRIVATE #3
DINING
DAY ROOM
133A
RESTRAINT
ROOM
120C
CORRIDOR
CORRIDOR
CORRIDOR
103-2
RECEIVING
CORRIDOR
RECEPTION
SECURITY DESK
104A
FAMILY WAITING
LOCKERS
104C
CORRIDOR
CORRIDOR
PUBLIC TLT
PUBLIC TLT
SOCIAL WORK
OFFICE (FUTURE
ELEVATOR)
SOCIAL WORK
(FUTURE
ELEVATOR)
EXAM RM
BARIATRIC PAT
RM #6
PAT TLT
121A
OFFICE
PAT RM #8
PAT TLT
124A
PAT TLT
126A
QUIET LOUNGE
PAT TLT
137A
PAT TLT
138A
PAT TLT
123A
ELEC
COPY
SPS
SOILED HOLD
SALLY PORT
SALLY PORT
CLEAN LINEN
INTAKE
ANTE
SECLUSION
120B
MEDS
NURSE WORK
122A
NURSE STATION
VESTIBULE
PAT RM #5
MECHANICAL
STAFF LOUNGE
104D
GROUP
THERAPY
PAT RM #7
STAFF TLT
104B
PAT RM #4
PAT RM #3
TEL / DATA
157159
167186
167 60
167 167
60 165
251 64
121 106
112121
88 88
125145
642 607
DESK
30X66
DESK
30X66
LAT. FILE
18X42
B O
O K
S
TABLE
36" DIA.
LAT. FILE
18X42
B O
O K
S
DESK
30X66
B O
O K
S
L A
T . F
IL
E
X
D E
S K
X
LAT. FILE
18X42
BOOKS
TABLE
36" DIA.
DESK
30X66
L A
T . F
IL
E
X
B O
O K
S
D E
S K
X
LAT. FILE
18X42
B O
O K
S
DN
CORRIDOR
PAT TLT
141A
LINK
CONCOURSE
CORRIDOR
CORRIDOR
CORRIDOR
PAT TLT
139A
PAT TLT
140A
PAT RM #1
PAT RM #2
SEMI PRIVATE #1
OFFICE
WARD CLERK
110PAT TLT
120A
LAUNDRY / TUB
HEAD NURSE
ENVIRON
STORAGE /HSKP
PAT TLT
136A
PAT TLT
132A
CRAWL SPACE
ACCESS
127A
STORAGE
EM EXIT
PAT TLT
129A
PAT TLT
130APAT TLT
131A
SEMI PRIVATE #5
SEMI PRIVATE #6
SEMI PRIVATE #4
SEMI PRIVATE #3
DINING
DAY ROOM
133A
RESTRAINT
ROOM
120C
CORRIDOR
CORRIDOR
CORRIDOR
103-2
RECEIVING
CORRIDOR
RECEPTION
SECURITY DESK
104A
FAMILY WAITING
LOCKERS
104C
CORRIDOR
CORRIDOR
PUBLIC TLT
PUBLIC TLT
SOCIAL WORK
OFFICE (FUTURE
ELEVATOR)
SOCIAL WORK
(FUTURE
ELEVATOR)
EXAM RM
BARIATRIC PAT
RM #6
PAT TLT
121A
OFFICE
PAT RM #8
PAT TLT
124A
PAT TLT
126A
QUIET LOUNGE
PAT TLT
137A
PAT TLT
138A
PAT TLT
123A
ELEC
COPY
SPS
SOILED HOLD
SALLY PORT
SALLY PORT
CLEAN LINEN
INTAKE
ANTE
SECLUSION
120B
MEDS
NURSE WORK
122A
NURSE STATION
VESTIBULE
PAT RM #5
MECHANICAL
STAFF LOUNGE
104D
GROUP
THERAPY
PAT RM #7
STAFF TLT
104B
PAT RM #4
PAT RM #3
TEL / DATA
LAT. FILE
18X42
CORRIDOR
CORRIDOR
TEL / DATA
LAT. FILE
18X42
CORRIDOR
CORRIDOR
TEL / DATA
C
115-TD110
LIMITS OF DATA CABLING DEMOLITION
E
E
E
EE
E
12"x2"
12"x2"
"x
2"
12"x2"
12"x2"
"x
2"
"x 2"
E E
E
12"x2"
"x
2"
3" 3"
D
D
DATA RACKS
E
R
Nathan M. TimmNo DATEREVISION
DRAWING TITLE
CHECKED BY
ST.CLOUD, MN 56303
VA MEDICAL CENTER
BUILDING No
LOCATION
DRAWING NO.DRAWN
DWG. OF
PROJECT TITLE
PLOT SCALE
PROJECT NO.
DATE:
CONSULTANT ARCHITECT/ENGINEER OF RECORD STAMP
FULLY
SPRINKLERED
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
B
IM
/2
.0
V A
S t C lo u d E
H R
M I n fr a s tr u c tu re U p g ra d e s /6
-2
.B
.T
R
.r v t
/1
/2
:0
:1
P
M
115-TD110
FIRST FLOOR PLAN -
TELECOM - DEMOLITION
EHRM INFRASTRUCTURE
UPGRADES
656‐21‐235
03/30/2022
KSB SSK
16305
N
0 8' 16'4' 1/8" = 1'-0"
FIRST FLOOR PLAN - TELECOM - DEMOLITION
1/4" = 1'-0"
ENLARGED PLAN -EXIST RM 107 - TELECOM - DEMO
N
0 4' 8'2'
SHEET NOTES:
1. EXISTING TELECOMMUNICATIONS CAGE AND RACK SHALL BE INCLUDED WITHIN THE SCOPE OF DEMOLITION.
EXISTING CABLING AND ASSOCIATED OUTLETS SHALL BE REMOVED AND REPLACED 1 FOR 1 AND REFED FROM DISTRIBUTION EQUIPMENT LOCATED WITHIN THE NEW TELECOMMUNICATIONS ROOM. REFER TO GENERAL CABLING NOTES FOR APPROXIMATE QUANTITIES. REFER TO NEW WORK PLANS FOR SERVING
COMMUNICATIONS ROOM LOCATION AND NEW CABLING ROUTES.
GENERAL NOTES:
A. REFER TO GENERAL DEMOLITION NOTES ON SHEET T000 FOR ADDITIONAL DEMOLITION SCOPE.
CABLING NOTE:
CABLING NOTES:
A. THE EXISTING CABLE COUNT ARE THE CABLES CURRENTLY PRESENT IN THE SPACE. THE CABLE
RELOCATION COUNT ARE THE NEW OR RELOCATED CABLES TO BE FED FROM THE SPACE. THE FINAL CABLE COUNT ARE THE CABLES THAT WILL BE PRESENT IN THE SPACE AT THE COMPLETION OF THE
PROJECT.
1. ROOM 107
EXISTING CABLE COUNT
DATA (CAT6): 0
DATA (CAT5e): 94
DATA (CAT5): 0
DATA (CAT3): 0
CABLE RELOCATION COUNT
DATA (CAT6): 0
DATA (CAT5e): 0
DATA (CAT5): 0
DATA (CAT3): 0
EXISTING CABLE TO REMAIN
DATA (CAT6): 0
DATA (CAT5e): 0
DATA (CAT5): 0
DATA (CAT3): 0
FINAL CABLE COUNT
DATA (CAT6): 0
DATA (CAT5e): 0
DATA (CAT5): 0
DATA (CAT3): 0
PAT TLT
141A
LINK
CONCOURSE
CORRIDOR
CORRIDOR
CORRIDOR
PAT TLT
139A
PAT TLT
140A
PAT RM #1
PAT RM #2
SEMI PRIVATE #1
OFFICE
WARD CLERK
110PAT TLT
120A
LAUNDRY / TUB
HEAD NURSE
ENVIRON
STORAGE /HSKP
PAT TLT
136A
PAT TLT
132A
CRAWL SPACE
ACCESS
127A
STORAGE
EM EXIT
PAT TLT
129A
PAT TLT
130APAT TLT
131A
SEMI PRIVATE #5
SEMI PRIVATE #6
SEMI PRIVATE #4
SEMI PRIVATE #3
DINING
DAY ROOM
133A
RESTRAINT
ROOM
120C
CORRIDOR
CORRIDOR
CORRIDOR
103-2
RECEIVING
CORRIDOR
RECEPTION
SECURITY DESK
104A
FAMILY WAITING
LOCKERS
104C
CORRIDOR
CORRIDOR
PUBLIC TLT
PUBLIC TLT
SOCIAL WORK
OFFICE (FUTURE
ELEVATOR)
SOCIAL WORK
(FUTURE
ELEVATOR)
EXAM RM
BARIATRIC PAT
RM #6
PAT TLT
121A
OFFICE
PAT RM #8
PAT TLT
124A
PAT TLT
126A
QUIET LOUNGE
PAT TLT
137A
PAT TLT
138A
PAT TLT
123A
ELEC
COPY
SPS
SOILED HOLD
SALLY PORT
SALLY PORT
CLEAN LINEN
INTAKE
ANTE
SECLUSION
120B
MEDS
NURSE WORK
122A
NURSE STATION
VESTIBULE
PAT RM #5
MECHANICAL
STAFF LOUNGE
104D
GROUP
THERAPY
PAT RM #7
STAFF TLT
104B
PAT RM #4
PAT RM #3
DN
CORRIDOR
PAT TLT
141A
LINK
CONCOURSE
CORRIDOR
CORRIDOR
CORRIDOR
PAT TLT
139A
PAT TLT
140A
PAT RM #1
PAT RM #2
SEMI PRIVATE #1
OFFICE
WARD CLERK
110PAT TLT
120A
LAUNDRY / TUB
HEAD NURSE
ENVIRON
STORAGE /HSKP
PAT TLT
136A
PAT TLT
132A
CRAWL SPACE
ACCESS
127A
STORAGE
EM EXIT
PAT TLT
129A
PAT TLT
130APAT TLT
131A
SEMI PRIVATE #5
SEMI PRIVATE #6
SEMI PRIVATE #4
SEMI PRIVATE #3
DINING
DAY ROOM
133A
RESTRAINT
ROOM
120C
CORRIDOR
CORRIDOR
CORRIDOR
103-2
RECEIVING
CORRIDOR
RECEPTION
SECURITY DESK
104A
FAMILY WAITING
LOCKERS
104C
CORRIDOR
CORRIDOR
PUBLIC TLT
PUBLIC TLT
SOCIAL WORK
OFFICE (FUTURE
ELEVATOR)
SOCIAL WORK
(FUTURE
ELEVATOR)
EXAM RM
BARIATRIC PAT
RM #6
PAT TLT
121A
OFFICE
PAT RM #8
PAT TLT
124A
PAT TLT
126A
QUIET LOUNGE
PAT TLT
137A
PAT TLT
138A
PAT TLT
123A
ELEC
COPY
SPS
SOILED HOLD
SALLY PORT
SALLY PORT
CLEAN LINEN
INTAKE
ANTE
SECLUSION
120B
MEDS
NURSE WORK
122A
NURSE STATION
VESTIBULE
PAT RM #5
MECHANICAL
STAFF LOUNGE
104D
GROUP
THERAPY
PAT RM #7
STAFF TLT
104B
PAT RM #4
PAT RM #3
TELECOM ROOM
115-TN400
LIMITS OF DATA CABLING REPLACEMENT
FROM ROOM 107
C2 126"
3"3"
4"
4"
12"x2"
12"x2"
"x
2"
"x
2"
12"x2"
12"x2"
"x
2"
E
E
E
EE
E
4"
12"x2" E E
E
"x
2"
Nathan M. TimmNo DATEREVISION
DRAWING TITLE
CHECKED BY
ST.CLOUD, MN 56303
VA MEDICAL CENTER
BUILDING No
LOCATION
DRAWING NO.DRAWN
DWG. OF
PROJECT TITLE
PLOT SCALE
PROJECT NO.
DATE:
CONSULTANT ARCHITECT/ENGINEER OF RECORD STAMP
FULLY
SPRINKLERED
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
B
IM
/2
.0
V A
S t C lo u d E
H R
M I n fr a s tr u c tu re U p g ra d e s /6
-2
.B
.T
R
.r v t
/1
/2
:0
:1
P
M
115-TN110
FIRST FLOOR PLAN -
TELECOMMUNICATIONS
EHRM INFRASTRUCTURE
UPGRADES
656‐21‐235
03/30/2022
KSB SSK
16305
SHEET NOTES:
1. PROVIDE JUNCTION BOX TO CONNECT EXISTING FIBER CONDUIT ENTRY TO EXTEND CONDUIT
PATHWAY TO THE NEW TELECOM ROOM.
N
0 8' 16'4' 1/8" = 1'-0"
FIRST FLOOR PLAN - TELECOMMUNICATIONS
GENERAL NOTES:
A. REFER TO GENERAL NOTES ON SHEET T000 FOR ADDITIONAL SCOPE.
PAT TLT
141A
LINK
CONCOURSE
CORRIDOR
CORRIDOR
CORRIDOR
PAT TLT
139A
PAT TLT
140A
PAT RM #1
PAT RM #2
SEMI PRIVATE #1
OFFICE
WARD CLERK
110PAT TLT
120A
LAUNDRY / TUB
HEAD NURSE
ENVIRON
STORAGE /HSKP
PAT TLT
136A
PAT TLT
132A
CRAWL SPACE
ACCESS
127A
STORAGE
EM EXIT
PAT TLT
129A
PAT TLT
130APAT TLT
131A
SEMI PRIVATE #5
SEMI PRIVATE #6
SEMI PRIVATE #4
SEMI PRIVATE #3
DINING
DAY ROOM
133A
RESTRAINT
ROOM
120C
CORRIDOR
CORRIDOR
CORRIDOR
103-2
RECEIVING
CORRIDOR
RECEPTION
SECURITY DESK
104A
FAMILY WAITING
LOCKERS
104C
CORRIDOR
CORRIDOR
PUBLIC TLT
PUBLIC TLT
SOCIAL WORK
OFFICE (FUTURE
ELEVATOR)
SOCIAL WORK
(FUTURE
ELEVATOR)
EXAM RM
BARIATRIC PAT
RM #6
PAT TLT
121A
OFFICE
PAT RM #8
PAT TLT
124A
PAT TLT
126A
QUIET LOUNGE
PAT TLT
137A
PAT TLT
138A
PAT TLT
123A
ELEC
COPY
SPS
SOILED HOLD
SALLY PORT
SALLY PORT
CLEAN LINEN
INTAKE
ANTE
SECLUSION
120B
MEDS
NURSE WORK
122A
NURSE STATION
VESTIBULE
PAT RM #5
MECHANICAL
STAFF LOUNGE
104D
GROUP
THERAPY
PAT RM #7
STAFF TLT
104B
PAT RM #4
PAT RM #3
DN
CORRIDOR
PAT TLT
141A
LINK
CONCOURSE
CORRIDOR
CORRIDOR
CORRIDOR
PAT TLT
139A
PAT TLT
140A
PAT RM #1
PAT RM #2
SEMI PRIVATE #1
OFFICE
WARD CLERK
110PAT TLT
120A
LAUNDRY / TUB
HEAD NURSE
ENVIRON
STORAGE /HSKP
PAT TLT
136A
PAT TLT
132A
CRAWL SPACE
ACCESS
127A
STORAGE
EM EXIT
PAT TLT
129A
PAT TLT
130APAT TLT
131A
SEMI PRIVATE #5
SEMI PRIVATE #6
SEMI PRIVATE #4
SEMI PRIVATE #3
DINING
DAY ROOM
133A
RESTRAINT
ROOM
120C
CORRIDOR
CORRIDOR
CORRIDOR
103-2
RECEIVING
CORRIDOR
RECEPTION
SECURITY DESK
104A
FAMILY WAITING
LOCKERS
104C
CORRIDOR
CORRIDOR
PUBLIC TLT
PUBLIC TLT
SOCIAL WORK
OFFICE (FUTURE
ELEVATOR)
SOCIAL WORK
(FUTURE
ELEVATOR)
EXAM RM
BARIATRIC PAT
RM #6
PAT TLT
121A
OFFICE
PAT RM #8
PAT TLT
124A
PAT TLT
126A
QUIET LOUNGE
PAT TLT
137A
PAT TLT
138A
PAT TLT
123A
ELEC
COPY
SPS
SOILED HOLD
SALLY PORT
SALLY PORT
CLEAN LINEN
INTAKE
ANTE
SECLUSION
120B
MEDS
NURSE WORK
122A
NURSE STATION
VESTIBULE
PAT RM #5
MECHANICAL
STAFF LOUNGE
104D
GROUP
THERAPY
PAT RM #7
STAFF TLT
104B
PAT RM #4
PAT RM #3
Nathan M. TimmNo DATEREVISION
DRAWING TITLE
CHECKED BY
ST.CLOUD, MN 56303
VA MEDICAL CENTER
BUILDING No
LOCATION
DRAWING NO.DRAWN
DWG. OF
PROJECT TITLE
PLOT SCALE
PROJECT NO.
DATE:
CONSULTANT ARCHITECT/ENGINEER OF RECORD STAMP
FULLY
SPRINKLERED
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
B
IM
/2
.0
V A
S t C lo u d E
H R
M I n fr a s tr u c tu re U p g ra d e s /6
-2
.B
.T
R
.r v t
/1
/2
:0
:1
P
M
115-TN210
FIRST FLOOR PLAN -
TELECOM - CABLE DISTANCE
EHRM INFRASTRUCTURE
UPGRADES
656‐21‐235
03/30/2022
KSB SSK
16305
N
0 30' 60'15' 1" = 30'-0"
FIRST FLOOR PLAN - TELECOM - CABLE DISTANCE
CORRIDOR
CORRIDOR
A C
C R
C
E
12"x2"
12"x2"
12"x2" 12"x2"
12"x2"
CABLE TRAY
115-TN400
1 - a b
1 - c d
C2 126"
KEYPAD
W
DATA
RACK
4"
3"
E 12"x2"
E
AC
R
NOTES:
1. REFER TO NEW WORK PLAN FOR RACK LOCATIONS.
2. COORDINATE EXACT RACK COUNT AND LOCATION WITH OWNER PRIOR TO PERMANENT INSTALLATION.
3. SEE PROJECT SPECIFICATIONS FOR ADDITIONAL RACK COMPONENTS.
4. RACK ELEVATION SHOWS A FULLY CONFIGURED SAMPLE RACK. CONTRACTOR TO PROVIDE REQUIRED EQUIPMENT TO
SUPPORT THE FINAL DATA COUNT FROM THE ENLARGED NEW SHEET. (NOT TO EXCEED 288 PORTS PER RACK).
5. COORDINATE FINAL RACK COMPONENT LAYOUT WITH OWNER'S IS/IT REPRESENTATIVE.
6. CONTRACTOR IS RESPONSIBLE FOR FINAL CABLE COUNT, QUANTITY OF PATCH PANELS, SWITCHES, FIBER
ENCLOSURES, BLANKING PANELS, CABLE MANAGEMENT, AND MOUNTING HARDWARE NOT MARKED AS “OIT PROVIDED”.
7. PUNCHDOWN COPPER BACKBONES ON RACK MOUNT PATCH PANELS. TERMINATE ONE (1) PAIR PER PATCH PANEL PORT.
VERTICAL CABLE
MANAGEMENT (TYP)
RACK 1
1U 144 STRAND OM4 AND OS2 DISTRIBUTION PANEL
1U BONDING BUS BAR (BACK) 1U BLANKING PANEL (FRONT)
1U 48 PORT CAT5E BACKBONE PATCH PANEL
1U CABLE MANAGEMENT
1U CABLE MANAGEMENT
1U 48 PORT CAT6A ANGLED DATA PATCH PANEL
6U 5KW RACK MOUNT UPS
6U SPACE FOR FUTURE USE. PROVIDE BLANK
PANELS FOR UNUSED SPACES.
V E
R T
IC
A
L R
A C
K P
D U
V E
R T
IC
A
L R
A C
K P
D U
NEMA L21-20R (TYP)
CHANNEL RACK (TYP)
D
PROVIDE DATA CABLE TO RACK
MOUNTED UPS FOR CONNECTION
TO MONITORING SYSTEM
RACK 1
1U 48 PORT CAT6A ANGLED DATA PATCH PANEL
1U 48 PORT CAT6A ANGLED DATA PATCH PANEL
1U 48 PORT CAT6A ANGLED DATA PATCH PANEL
1U 48 PORT CAT6A ANGLED DATA PATCH PANEL
1U 48 PORT CAT6A ANGLED DATA PATCH PANEL
1U CABLE MANAGEMENT
VA OIT PROVIDED 1U 48 PORT SWITCH
2U CABLE MANAGEMENT
VA OIT PROVIDED 1U 48 PORT SWITCH
VA OIT PROVIDED 1U 48 PORT SWITCH
2U CABLE MANAGEMENT
1U CABLE MANAGEMENT
VA OIT PROVIDED 1U 48 PORT SWITCH
2U CABLE MANAGEMENT
VA OIT PROVIDED 1U 48 PORT SWITCH
2U CABLE MANAGEMENT
2U CABLE MANAGEMENT
VA OIT PROVIDED 1U 48 PORT SWITCH
SPACE FOR FUTURE HORIZONTAL CABLE
DISTRIBUTION. PROVIDE BLANKING PANELS FOR
UNUSED SPACES.
Nathan M. TimmNo DATEREVISION
DRAWING TITLE
CHECKED BY
ST.CLOUD, MN 56303
VA MEDICAL CENTER
BUILDING No
LOCATION
DRAWING NO.DRAWN
DWG. OF
PROJECT TITLE
PLOT SCALE
PROJECT NO.
DATE:
CONSULTANT ARCHITECT/ENGINEER OF RECORD STAMP
FULLY
SPRINKLERED
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
B
IM
/2
.0
V A
S t C lo u d E
H R
M I n fr a s tr u c tu re U p g ra d e s /6
-2
.B
.T
R
.r v t
/1
/2
:0
:2
P
M
115-TN400
ENLARGED PLANS -
TELECOMMUNICATIONS
EHRM INFRASTRUCTURE
UPGRADES
656‐21‐235
03/30/2022
KSB SSK
16305
N
0 2' 4'1'
0 4' 8'2' 0 4' 8'2' 0 4' 8'2' 0 4' 8'2'
GENERAL NOTES:
A. REFER TO GENERAL NOTES ON SHEET T000 FOR ADDITIONAL SCOPE.
CABLING NOTE:
CABLING NOTES:
A. THE EXISTING CABLE COUNT ARE THE CABLES CURRENTLY PRESENT IN THE SPACE.
THE CABLE RELOCATION COUNT ARE THE NEW OR RELOCATED CABLES TO BE FED
FROM THE SPACE. THE FINAL CABLE COUNT ARE THE CABLES THAT WILL BE
PRESENT IN THE SPACE AT THE COMPLETION OF THE PROJECT.
1. ROOM 107
EXISTING CABLE COUNT
DATA (CAT6): 0
DATA (CAT5e): 94
DATA (CAT5): 0
DATA (CAT3): 0
CABLE RELOCATION COUNT
DATA (CAT6): 0
DATA (CAT5e): 0
DATA (CAT5): 0
DATA (CAT3): 0
EXISTING CABLE TO REMAIN
DATA (CAT6): 0
DATA (CAT5e): 0
DATA (CAT5): 0
DATA (CAT3): 0
FINAL CABLE COUNT
DATA (CAT6A): 94
DATA (CAT6): 0
1/2" = 1'-0"
ENLARGED PLAN - TR 107 - TELECOM - CABLE TRAY AND DATA
1/4" = 1'-0"
1 - a
1/4" = 1'-0"
1 - b
1/4" = 1'-0"
1 - c
1/4" = 1'-0"
1 - d
NOT TO SCALE
COMMUNICATIONS - TYPICAL ONE RACK ELEVATION WITH RACK MOUNT UPS - TR 107
SHEET NOTES:
1. IF NO ACCESS CONTROL PANEL IS PRESENT IN THE TR, PROVIDE A NEW ACCESS CONTROL PANEL TO BE INSTALLED IN THE TELECOM ROOM. THE CARD READER AND KEYPAD FOR THIS ROOM TO BE WIRED TO THE NEW ACCESS CONTROL PANEL. EXISTING CARD READERS AND KEYPADS WILL BE MOVED TO
THE NEW CONTROL PANEL UNDER A DIFFERENT PROJECT.
E
CORRIDOR
PAT TLT
141A
LINK
CONCOURSE
CORRIDOR
CORRIDOR
CORRIDOR
PAT TLT
139A
PAT TLT
140A
PAT RM #1
PAT RM #2
SEMI PRIVATE #1
SEMI PRIVATE #2
OFFICE
WARD CLERK
110PAT TLT
120A
LAUNDRY / TUB
HEAD NURSE
ENVIRON
STORAGE /HSKP
PAT TLT
136A
PAT TLT
132A
CRAWL SPACE
ACCESS
127A
STORAGE
EM EXIT
PAT TLT
129A
PAT TLT
130APAT TLT
131A
SEMI PRIVATE #5
SEMI PRIVATE #6
SEMI PRIVATE #4
SEMI PRIVATE #3
DINING
DAY ROOM
133A
RESTRAINT
ROOM
120C
CORRIDOR
CORRIDOR
CORRIDOR
103-2
RECEIVING
CORRIDOR
RECEPTION
SECURITY DESK
104A
FAMILY WAITING
LOCKERS
104C
CORRIDOR
CORRIDOR
PUBLIC TLT
PUBLIC TLT
SOCIAL WORK
OFFICE (FUTURE
ELEVATOR)
SOCIAL WORK
(FUTURE
ELEVATOR)
EXAM RM
BARIATRIC PAT
RM #6
PAT TLT
121A
OFFICE
PAT RM #8
PAT TLT
124A
PAT TLT
126A
QUIET LOUNGE
PAT TLT
137A
PAT TLT
138A
PAT TLT
123A
ELEC
COPY
SPS
SOILED HOLD
SALLY PORT
SALLY PORT
CLEAN LINEN
INTAKE
ANTE
SECLUSION
120B
MEDS
NURSE WORK
122A
NURSE STATION
VESTIBULE
PAT RM #5
MECHANICAL
STAFF LOUNGE
104D
GROUP
THERAPY
PAT RM #7
STAFF TLT
104B
PAT RM #4
PAT RM #3
TELECOM
ROOM
115-E300
CU-115-1
115-L1-3-42
WP
115-EC1-1-40,42
No DATEREVISION
DRAWING TITLE
CHECKED BY
ST.CLOUD, MN 56303
VA MEDICAL CENTER
BUILDING No
LOCATION
DRAWING NO.DRAWN
DWG. OF
PROJECT TITLE
PLOT SCALE
PROJECT NO.
DATE:
CONSULTANT ARCHITECT/ENGINEER OF RECORD STAMP
FULLY
SPRINKLERED
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
I hereby certify that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly Licensed Engineer under the laws of the State of Minnesota.
Name:
Date: 03/30/2022
License Number: MN#
03/30/2022
B
IM
/2
.0
V A
S t C lo u d
E H
R M
I n fr a s tr u c tu re U p g ra d e s /6
-2
.B
.E
R
.r v t
/6
/2
:1
:2
P
M
115-E201
FIRST FLOOR - ELECTRICAL
EHRM INFRASTRUCTURE
UPGRADES
656-21-235
TBD GJL
16305
KEYNOTES:
1. PROVIDE ELECTRICAL CONNECTION TO
CONDENSING UNIT, AS REQUIRED.
COORDINATE FINAL LOCATION AND
CONNECTION REQUIREMENTS WITH
MECHANICAL.
1/8" = 1'-0"
FIRST FLOOR - ELECTRICAL
0 8' 16'4'
N
100% CD 03/30
STAMP
I hereby certify that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly Licensed Engineer under the laws of the State of Minnesota.
Name:
Date: 03/30/2022
License Number: MN# hereby certify that this plan, specification or port was prepared by me or under my direc upervision and that I am a duly Licensed ngineer under the laws of the State of Minn ame:
ate: 03/30/2022 cense Number: MN# 05-06-2022
E
GB
CORRIDOR
CORRIDOR
103-2 ELEC
STAFF LOUNGE
104D
TELECOM
ROOM
115-EQ1-1 115-EQ1-2 115-EQ1-3 115-EC1-1 115-L1-3
115-L1-1
115-MSB-1
TF-115-EMC1-1TF-115-EQ1-1
TF-115-L1-1TF-115-L1-2115-ES1-ATS1
115-EC1-ATS1
115-EQ1-ATS1
FAP
AC-115-1
115-L1-3-37,39,41
115-EC1-1-37,39,41
2 3
No DATEREVISION
DRAWING TITLE
CHECKED BY
ST.CLOUD, MN 56303
VA MEDICAL CENTER
BUILDING No
LOCATION
DRAWING NO.DRAWN
DWG. OF
PROJECT TITLE
PLOT SCALE
PROJECT NO.
DATE:
CONSULTANT ARCHITECT/ENGINEER OF RECORD STAMP
FULLY
SPRINKLERED
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
I hereby certify that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly Licensed Engineer under the laws of the State of Minnesota.
Name:
Date: 03/30/2022
License Number: MN#
03/30/2022
B
IM
/2
.0
V A
S t C lo u d
E H
R M
I n fr a s tr u c tu re U p g ra d e s /6
-2
.B
.E
R
.r v t
/6
/2
:1
:2
P
M
115-E300
ELECTRICAL ENLARGED
PLANS
EHRM INFRASTRUCTURE
UPGRADES
656-21-235
TBD GJL
16305
1/4" = 1'-0"
FIRST FLOOR ENLARGED - ELEC 107 & 160 - ELECTRICAL
N
0 4' 8'2'
CIRCUIT KEY NOTES:
*TOTAL DEMAND CALCS SUBTRACT ANY REDUNDANT LOAD AND THE SMALLER OF ANY NONCOINCIDENT HVAC LOADS. THIS CALC IS DONE AT EACH PANEL.
TOTAL ESTIMATED DEMAND AMPS: 13.9 A
TOTAL CONNECTED AMPS: 13.88 A
TOTAL ESTIMATED DEMAND LOAD: 5 kVA
TOTAL CONNECTED LOAD: 5.00 kVA
Power 5 kVA 100.00% 5 kVA
LOAD CLASSIFICATION CONNECTED LOAD DEMAND FACTOR ESTIMATED DEMAND
TOTALS*
LOAD SUMMARY
Total Amps: 13.89 13.89 13.89
Total Load: 1.67 kVA 1.67 kVA 1.67 kVA
-- 41 -- -- -- -- -- -- 1.67 0 -- -- -- -- -- -- 42 --
-- 39 -- -- -- -- -- -- 1.67 0 2 20 A CU-115-1 40
37 L21-20R 20 A 3 1.67 38
35 36
33 34
31 32
29 30
27 28
25 26
23 24
21 22
19 20
17 18
15 16
13 14
11 12
9 10
7 8
5 6
3 4
1 2
K E Y
CKT
NO. LOAD DESCRIPTION
OCPD
AMPS P
WIRE
SIZE
H N G
A B C
WIRE
SIZE
G N H
OCPD
P AMPS LOAD DESCRIPTION
CKT
NO.
K E Y
NOTES:
ISC UNKNOWN 0.00 kA
SCCR: 65 kA
LOCATION: WIRE: 4
FED FROM: 0 A/0P @ GROUND BUS PHASE: 3
ENCLOSURE: NEMA PB 1 SOLID NEUTRAL VOLTS: 120/208 Wye
MOUNTING: SURFACE MAIN: 100 A MCB
EXISTING PANEL 115-EC1-1
CIRCUIT KEY NOTES:
*TOTAL DEMAND CALCS SUBTRACT ANY REDUNDANT LOAD AND THE SMALLER OF ANY NONCOINCIDENT HVAC LOADS. THIS CALC IS DONE AT EACH PANEL.
TOTAL ESTIMATED DEMAND AMPS: 14.4 A
TOTAL CONNECTED AMPS: 14.38 A
TOTAL ESTIMATED DEMAND LOAD: 5.18 kVA
Receptacles 0.18 kVA 100.00% 0.18 kVA TOTAL CONNECTED LOAD: 5.18 kVA
Power 5 kVA 100.00% 5 kVA
LOAD CLASSIFICATION CONNECTED LOAD DEMAND FACTOR ESTIMATED DEMAND
TOTALS*
LOAD SUMMARY
Total Amps: 13.89 13.89 15.39
Total Load: 1.67 kVA 1.67 kVA 1.85 kVA
-- 41 -- -- -- -- -- -- 1.67 0.18 1 20 A GFI RECEPTACLE 42
-- 39 -- -- -- -- -- -- 1.67 40
37 L21-20R 20 A 3 1.67 38
35 36
33 34
31 32
29 30
27 28
25 26
23 24
21 22
19 20
17 18
15 16
13 14
11 12
9 10
7 8
5 6
3 4
1 2
K E Y
CKT
NO. LOAD DESCRIPTION
OCPD
AMPS P
WIRE
SIZE
H N G
A B C
WIRE
SIZE
G N H
OCPD
P AMPS LOAD DESCRIPTION
CKT
NO.
K E Y
NOTES:
ISC UNKNOWN 0.00 kA
SCCR: 65 kA
LOCATION: WIRE: 4
FED FROM: 0 A/0P @ GROUND BUS PHASE: 3
ENCLOSURE: NEMA PB 1 SOLID NEUTRAL VOLTS: 120/208 Wye
MOUNTING: SURFACE MAIN: 100 A MCB
EXISTING PANEL 115-L1-3
KEYNOTES:
1. COORDINATE FINAL LOCATION OF
RECEPTACLE L21-20R WITH TELECOM
CONTRACTOR. PROVIDE 3/4"C-4#12, 1#12 GND
TO PANEL FOR EACH RECEPTACLE.
2. PROVIDE EATON BLADEUPS, 5KW, 120/208V, 3-
PHASE,4-WIRE RACK MOUNTED UPS FOR EACH
RACK TOWER.
3. PROVIDE APC#AP8861 RPDU RACK PDU 2G
WITH L21-20P CORD. (120/208V, 3-PHASE, 20A,
ZERO U, 5.7 KW, 208V, (36) C13 (6) C19 (2) 5-20R
OUTLETS. PROVIDE TWO PER RACK, MOUNTED
PER MANUFACTURER'S REQUIREMENTS.
4. INDOOR UNIT TO BE POWERED BY OUTDOOR
UNIT. COORDINATE EXACT LOCATION WITH
M.C.
5. VERIFY EXACT BREAKER LOACTION WITH
SPACE IN PANEL.
100% CD 03/30
TF-115-EMC1-1
TF-115-L1-2
STAMP
I hereby certify that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly Licensed Engineer under the laws of the State of Minnesota.
Name:
Date: 03/30/2022
License Number: MN# hereby certify that this plan, specification or port was prepared by me or under my direc upervision and that I am a duly Licensed ngineer under the laws of the State of Minn ame:
ate: 03/30/2022 cense Number: MN# 05-06-2022
T
DESK
30X66
LAT. FILE
18X42
B O
O K
S
EXISTING RACK
TEL / DATA
CORRIDOR
CORRIDOR
103-2
HEAD NURSE
No DATEREVISION
DRAWING TITLE
CHECKED BY
ST.CLOUD, MN 56303
VA MEDICAL CENTER
BUILDING No
LOCATION
DRAWING NO.DRAWN
DWG. OF
PROJECT TITLE
PLOT SCALE
PROJECT NO.
DATE:
CONSULTANT ARCHITECT/ENGINEER OF RECORD STAMP
FULLY
SPRINKLERED
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
I hereby certify that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly Licensed Engineer under the laws of the State of Minnesota.
Name:
Date: 03/30/2022
License Number: MN#
03/30/2022
B
IM
/2
.0
V A
S t C lo u d
E H
R M
I n fr a s tr u c tu re U p g ra d e s /6
-2
.B
.M
R
.r v t
/1
/2
:3
:3
P
M
115-M101
FIRST FLOOR DEMOLITION -
MECHANICAL
EHRM INFRASTRUCTURE
UPGRADES
656-21-235
RDL DJC
16305
KEYNOTES 1/115-M101:
1. REMOVE AND DISPOSE OF EXISTING DRIP PANNED 3"
HYDRONIC HEATING PIPE AS SHOWN. PREPARE FOR
RECONNECTION.
2. REMOVE AND DISPOSE OF EXISTING SUPPLY AIR DIFFUSER.
CAP DUCT.
3. REMOVE AND DISPOSE OF EXISTING RETURN AIR GRILLE.
CAP DUCT.
4. REMOVE AND DISPOSE OF EXISTING THERMOSTAT AND
ASSOCIATED WIRING.
5. REMOVE AND DISPOSE OF 3/4" DRAIN TO FLOOR.
1/2" = 1'-0"
FIRST FLOOR DEMOLITION - MECHANICAL - EXIST 107
FIELD VERIFICATION NOTES
1. THE HVAC CONTRACTOR SHOULD VISIT THE SITE PRIOR TO BID TO FIELD VERIFY ALL EXISTING CONDITIONS WHICH MAY AFFECT
THEIR BID. THE FOLLOWING ITEMS SHALL BE VERIFIED:
A. EXACT PLACEMENT, SIZE, CAPACITY, MANUFACTURER AND AND CONDITION OF ALL EXISTING HVAC EQUIPMENT WITHIN
SCOPE OF WORK, WHETHER EXPLICITLY SHOWN OR NOT.
B. SIZE AND LOCATION OF ALL EXISTING DUCTWORK.
C. SIZE AND LOCATION OF ALL EXISTING GRILLES, REGISTERS AND DIFFUSERS.
D. SIZE AND LOCATION OF EXISTING THERMOSTATIC CONTROL DEVICES
E. SIZE AND LOCATION OF EXISTING PLUMBING AND HYDRONIC PIPING.
2. ALL REFERENCES ON THESE DRAWINGS TO EXISTING EQUIPMENT, DUCTWORK, DIFFUSERS, THERMOSTATS, AND PIPING ARE FOR REFERENCE ONLY. IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO VERIFY ALL THESE ITEMS PRIOR TO THEIR BID AND INCLUDE
IN THEIR BID ANY AND ALL AMOUNTS REQUIRED TO ACCOMMODATE EXISTING CONDITIONS.
3. ANY DISCREPANCIES WHICH MAY AFFECT CONTRACTORS BID SHALL BE BROUGHT TO THE ATTENTION OF THE ENGINEER AND
ARCHITECT FOR DIRECTION
0 2' 4'1'
N
100% CD 03/30
T
DESK
30X66
LAT. FILE
18X42
B O
O K
S
EXISTING RACK
PROVIDED BY
OTHERS
CP-115-1
DRIP PAN CONDENSATE
PIPING IN ROOM
TEL / DATA
CORRIDOR
CORRIDOR
103-2
HEAD NURSE
AC-115-1
CU-115-1
ELEC
STAFF LOUNGE
104D
LOCKERS
104C
SUC
LIQ
No DATEREVISION
DRAWING TITLE
CHECKED BY
ST.CLOUD, MN 56303
VA MEDICAL CENTER
BUILDING No
LOCATION
DRAWING NO.DRAWN
DWG. OF
PROJECT TITLE
PLOT SCALE
PROJECT NO.
DATE:
CONSULTANT ARCHITECT/ENGINEER OF RECORD STAMP
FULLY
SPRINKLERED
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
I hereby certify that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly Licensed Engineer under the laws of the State of Minnesota.
Name:
Date: 03/30/2022
License Number: MN#
03/30/2022
B
IM
/2
.0
V A
S t C lo u d
E H
R M
I n fr a s tr u c tu re U p g ra d e s /6
-2
.B
.M
R
.r v t
/1
/2
:3
:4
P
M
115-M201
FIRST FLOOR - MECHANICAL
EHRM INFRASTRUCTURE
UPGRADES
656-21-235
RDL DJC
16305
KEYNOTES, 1/115-M201:
1. REROUTE AND RECONNECT EXISTING 3" HYDRONIC HEATING PIPE - FIELD
VERIFY EXACT REQUIREMENTS.
2. PROVIDE NEW SPLIT SYSTEM AC UNIT.
3. ROUTE REFRIGERANT PIPING TO NEW AIR-COOLED CONDENSING UNIT
LOCATED AT EAST EXTERIOR OF BUILDING. SEE 2/115-M201.
4. ROUTE 1" PUMPED CONDENSATE PIPING TO FLOOR DRAIN IN MECHANICAL
ROOM 159, APPROXIMATELY 30 FT NORTH. FIELD COORDINATE FINAL ROUTING.
5. PROVIDE NEW THERMOSTAT.
6. PROVIDE NEW FIRE-SPRINKLER HEAD AND BRANCH PIPE. CONNECT TO
SPRINKLER MAIN IN CORRIDOR. FIELD VERIFY REQUIREMENTS.
1/2" = 1'-0"
FIRST FLOOR - MECHANICAL
FIELD VERIFICATION NOTES
1. THE HVAC CONTRACTOR SHOULD VISIT THE SITE PRIOR TO BID TO FIELD VERIFY ALL EXISTING CONDITIONS WHICH MAY AFFECT T
HEIR BID. THE FOLLOWING ITEMS SHALL BE VERIFIED:
A. EXACT PLACEMENT, SIZE, CAPACITY, MANUFACTURER AND AND CONDITION OF ALL EXISTING HVAC EQUIPMENT WITHIN
SCOPE OF WORK, WHETHER EXPLICITLY SHOWN OR NOT.
B. SIZE AND LOCATION OF ALL EXISTING DUCTWORK.
C. SIZE AND LOCATION OF ALL EXISTING GRILLES, REGISTERS AND DIFFUSERS.
D. SIZE AND LOCATION OF EXISTING THERMOSTATIC CONTROL DEVICES
E. SIZE AND LOCATION OF EXISTING PLUMBING AND HYDRONIC PIPING.
2. ALL REFERENCES ON THESE DRAWINGS TO EXISTING EQUIPMENT, DUCTWORK, DIFFUSERS, THERMOSTATS, AND PIPING ARE FOR REFERENCE ONLY. IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO VERIFY ALL THESE ITEMS PRIOR TO THEIR BID AND INCLUDE
IN THEIR BID ANY AND ALL AMOUNTS REQUIRED TO ACCOMMODATE EXISTING CONDITIONS.
3. ANY DISCREPANCIES WHICH MAY AFFECT CONTRACTORS BID SHALL BE BROUGHT TO THE ATTENTION OF THE ENGINEER AND
ARCHITECT FOR DIRECTION
1/2" = 1'-0"
FIRST FLOOR - MECHANICAL - CONDENSING UNIT
KEYNOTES, 2/115-M201:
1. ROUTE REFRIGERANT PIPING FROM AIR COOLED CONDENSING UNIT TO RM
108AC UNIT. FIELD COORDINATE EXACT ROUTING REQUIREMENTS.
2. PROVIDE NEW CONDENSING UNIT ON GRADE. PROVIDE CONCRETE PAD. REFER
TO REFRIGERANT PIPING DETAIL 1/0-GM400 AND PAD MOUNTING DETAIL
3/0-GM400.
N N
0 2' 4'1'0 2' 4'1'
100% CD 03/30
| 115-GI000 - BUILDING 115 COVER SHEET & SHEET INDEX |
| 115-GI111 - FIRST FLOOR - INFECTION CONTROL & PHASING PLAN |
| 115-AS110 - FIRST FLOOR PLANS |
| 115-TD110 - FIRST FLOOR PLAN - TELECOM - DEMOLITION |
| 115-TN110 - FIRST FLOOR PLAN - TELECOMMUNICATIONS |
| 115-TN210 - FIRST FLOOR PLAN - TELECOM - CABLE DISTANCE |
| 115-TN400 - ENLARGED PLANS - TELECOMMUNICATIONS |
| 115-E201 - FIRST FLOOR - ELECTRICAL |
| 115-E300 - ELECTRICAL ENLARGED PLANS |
| 115-M101 - FIRST FLOOR DEMOLITION - MECHANICAL |
| 115-M201 - FIRST FLOOR - MECHANICAL |
File details come from the government source that posted it. Updated .