Asbestos - Appendix-A part 2.pdf

PDF 6 MB Posted

Attached to
EHRM Infrastructure Upgrades Construction Sioux Falls VAMC Federal contract opportunity
Solicitation number
36C77622R0049
Issued by
Department of Veterans Affairs Technology Acquisition Center Austin

About this file

This solicitation is for construction and commissioning services related to infrastructure upgrades needed for an Electronic Health Record Modernization project at the Sioux Falls VAMC. Key details include that the project will touch several departments and service areas, with work required on multiple phases including structural and civil work. A new server room will be built on the roof between two buildings. The estimated construction value is between $20-50 million. The period of performance is approximately 450 calendar days from notice to proceed. The solicitation is advertised as a total SDVOSB set-aside. Questions must be submitted in writing by a specified date.

View the file

Other files for this federal contract opportunity

Other files attached to EHRM Infrastructure Upgrades Construction Sioux Falls VAMC, newest first.
File Type Posted
36C77622R0049 0006.pdf PDF
Technical Question Tracking Sheet Infra Upgrades Final.pdf PDF
36C77622R0049 0005.pdf PDF
271619 Communications Patch Cords Station Cords and Cross Connect Wire.pdf PDF
271116 Communications Cabinets Racks Frames and Enclosures.pdf PDF
36C77622R0049 0004.pdf PDF
2020 Elec Combined One Lines.pdf PDF
270536 Cable Trays for Communications Systems.pdf PDF
271119 Communications Termination Blocks and Patch Panels.pdf PDF
270533 Conduits and Backboxes for Communications Systems.pdf PDF
271126 Communications Rack Mounted Power Protection and Power Strips.pdf PDF
271313 Communications Copper Backbone Cabling.pdf PDF
36C77622R0049 0003.pdf PDF
271313.13 Communications Copper Cable Splicing and Terminations.pdf PDF
270526 Grounding and Bonding for Communications Systems.pdf PDF
271513.13 Communications Optical Fiber Cable Splicing and Terminations.pdf PDF
271000 Structured Cabling.pdf PDF
271323 Communications Optical Fiber Backbone Cabling.pdf PDF
OIT InfrastrucStdTelecomSpaces 3.1.pdf PDF
SF Site Utility Dwg.pdf PDF
270553 Identification for Communications Systems.pdf PDF
271513 Communications Copper Horizontal Cabling.pdf PDF
Technical Question Tracking Sheet - Infra Upgrades - Final.pdf PDF
EHRM Site Visit Attendance Sheet.pdf PDF
36C77622R0049 0002.pdf PDF
Technical Question Tracking Sheet - Infra Upgrades.pdf PDF
Building 1C Sheet 6 - Pipe Tunnel.pdf PDF
36C77622R0049 0001.pdf PDF
Specification - Vol 2 Revision 2.pdf PDF
Dwgs Bid Documents-part 7-1 REV.pdf PDF
VHA Suppl. Contract Rqmnts for Combatting COVID-19 Updated 12-14-2021.pdf PDF
Supplement to General Requirements Spec 01 00 00.pdf PDF
36C77622R0049.pdf PDF
Specifications Revision 2.pdf PDF
Dwgs Bid Documents-part 1-1 REV.pdf PDF
Asbestos - Appendix-A part 3.pdf PDF
Dwgs Bid Documents-part 6-1 REV.pdf PDF
Dwgs Bid Documents-part 3-1 REV.pdf PDF
Asbestos - Appendix-A part 1.pdf PDF
Dwgs Bid Documents-part 4-1 REV.pdf PDF
Dwgs Bid Documents-part 5-1 REV.pdf PDF
Dwgs Bid Documents-part 2-1 REV.pdf PDF
Asbestos - Appendix-A part 4.pdf PDF
Construction Wage Rates - Minnehaha - 2-25-22.pdf PDF
Show all 44

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

442A

TOILET

STAIR 3

TOILET

A

ELEVATOR

B

ELEVATOR

C

ELEVATOR

D

ELEVATOR

STAIR 4

Room

TELECOM 434

ROOM

Room

Room

AUDIOLOGY

RECEPTION

Room

Room

Room

Room406

Room

Room

Room

404A Room

Room

Room

Room 439

Room

Room

440A Room

CORRIDOR

432A Room

BREAK

Room

ELEVATOR

LOBBY

READY

ROOM

READY

ROOM

READY

ROOM

READY

ROOM

NURSE

PROCESSING

PROCEDURE

PROCEDURE

PROCEDURE

READY

ROOM

READY

ROOM

READY

ROOM

Room

Room

Room

426A

TOILET

415A

TOILET

417A

TOILET

454A

TOILET

427A Room

414A

STAIR 10

421A

STAIR 5

CORRIDOR

414B Room

ELEVATOR

LOBBY

LOBBY

443A

CORRIDOR

443B

RECEPTION

443D

TOILET

443E

EXAM

443F

EXAM

443G

PROSTHETISIT

443I

LAB

443H

CORRIDOR

443J

O&P

SUPPLY

443C

SOILED

BU

IL

DI

NG

AR

EA

A

BU

IL

DI

NG

AR

EA

C

BU

IL

DI

NG

AR

EA

A

BU

IL

DI

NG

AR

EA

C

BUILDING 5 - AREA A

BUILDING 5 - AREA C

BUILDING 5 - AREA A

BUILDING 5 - AREA B

LIMITS OF CONSTRUCTION

ROOF BELOW

CR

AE414

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

35% CONSTRUCTION

DOCUMENT REVIEW

FULLY

SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

NOT FOR CONSTRUCTION

C U s e rs

\P u b lic \D o c u m e n ts \R e v it P ro je c ts

\1

-R g b a rb a ri a e -m n .c o m

.r v t

/2

/2

:1

:0

P

M

AE141-05-C

FOURH LEVEL FLOOR PLAN -

BUILDING 5 - AREA C

VAMC SIOUX FALLS EHRM

INFRASTRUCTURE UPGRADES

Sioux Falls, SD

438-20-910

03/26/2021 Checker Author16090

1/8" = 1'-0"1 FOURTH LEVEL FLOOR PLAN - BUILDING 5 - AREA C

Revisions: Date:

5-433-1

5-451-2

5-451-3

5-451-4

5-451-5 5-451-6

- Negative Asbestos Bulk Sample LocationX-XX-X

- Positive Asbestos Bulk Sample LocationX-XX-X

LEGEND

CORRIDOR

510B

WOMENS

TOILET

510C

MENS

LOCKER

510D

MENS

TOILET

510A

WOMENS

LOCKER

TELECOMM

TOILET

TOILET

EQUIPMENT

STORAGE

OFFICE

OFFICE

MECH/ELEC

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE536

COMPUTER

OFFICE

OFFICE539

OFFICE

OFFICE

OFFICE542

OFFICE

HAC

STERILE

STORAGE 517

CLEAN

EXAM

EXAM

DATA

ELECTRICAL

Room

MEDICATION 513

SOILED

MINOR

PROCEDURE

MINOR

PROCDURE

502A

WORK

ROOM

TOILET

CONFRENCE

OFFICE

OFFICE

OFFICE

BREAK

PATIENT

INTAKE

LINEN

ALCOVE

ELEVATOR

LOBBY500A

STAIR

Room

534B

STAIR

STORAGE

MECHANICAL

RECEPTION

WAITING

501A

CORRIDOR

500E

LINEN

500D

CRASH

CART

ALCOVE

STAIR 6

MECHANICAL

PROVIDE:

- STATIC DISSIPATIVE FLOORING

-4' x8' PLYWOOD ALL WALLS WITH FIREPROOF PAINT AND GLOSS WHITE TOP COAT

AE414

GENERAL NOTES

1. THE ARCHITECTURAL DRAWINGS SHOW PRINCIPAL AREAS AND LIMITS OF CONSTRUCTION

WHERE WORK MUST BE ACCOMPLISHED UNDER THIS CONTRACT. INCIDENTAL WORK MAY BE

NECESSARY IN AREAS NOT SHOWN ON ARCHITECTURAL DRAWINGS DUE TO CHANGES

AFFECTING ELECTRICAL, MECHANICAL AND PLUMBING ALONG WITH OTHER SYSTEMS. THIS

INCIDENTAL WORK SHALL BE PART OF THIS CONTRACT, AND ALL TRADES SHALL INSPECT THESE

AREAS, ASCERTAIN WORK REQUIRED AND DO THE WORK IN ACCORDANCE OF CONTRACT

REQUIREMENTS AT NO ADDITIONAL COST.

2. CONTRACTORS SHALL VISIT THE SITE DURING BIDDING TO BECOME FAMILIAR WITH THE

EXISTING CONDITIONS. THE GENERAL CONTRACTOR SHALL LOCATE, INSPECT AND FIELD VERIFY

ALL EXISTING CONDITIONS, DIMENSIONS AND ELEVATIONS PRIOR TO DEMOLITION AND

CONSTRUCTION. NOTIFY ARCHITECT IMMEDIATELY OF ANY DISCREPANCIES.

3. DO NOT SCALE DRAWINGS. NOTIFY ARCHITECT IMMEDIATELY OF ANY DISCREPANCIES.

4. WHEREVER OPENINGS ARE CUT THROUGH FIRE RATED PARTITIONS, IT SHALL BE THE

RESPONSIBILITY OF THE CONTRACTOR FOR WHOM THE HOLE IS CUT TO PATCH AND REPAIR ANY

OPENING TO MAINTAIN THE INTEGRITY OF THE FIRE RATING.

5. GENERAL CONTRACTOR TO CHECK MECHANICAL DRAWINGS FOR EXISTING PIPES AND DUCTS

FURRED IN WALLS. VERIFY SIZE AND LOCATION WITH MECHANICAL CONTRACTOR PRIOR TO

PROCEEDING WITH REMODELING.

6. FIREPROOFING SHALL BE UNPIERCED. ANY SUBCONTRACTOR PENETRATING THE FIREPROOFING

SHALL BE REQUIRED TO REPLACE FIREPROOFING TO THE ORIGINAL CONDITION AND FIRE

RATING, AT THE SUBCONTRACTORS EXPENSE.

7. EQUIPMENT UNIT DIMENSIONS ARE FOR PRODUCT DESCRIPTION ONLY, VERIFY SIZE WITH

MANUFACTURER.

8. ALL DIMENSIONS PERTAINING TO MECHANICAL OR ELECTRICAL SERVICES OR EQUIPMENT SHALL

BE VERIFIED WITH THE RESPECTIVE TRADE.

9. ALL CONTRACTORS THAT PENETRATE AND/OR DISTURB ANY AREAS AT EXISTING CONDITIONS

SHALL PATCH AREA TO MATCH EXISTING ADJACENT AREA OR SURFACE AND PREPARE FOR

SCHEDULED FINISH APPLICATION. COORDINATE WORK WITH GENERAL CONTRACTOR PRIOR TO

PROCEEDING.

10. VERIFY HEIGHTS AND LOCATIONS OF ACCESS PANELS (AP) AND COORDINATE TYPES WITH

TRADES WHICH REQUIRE THEM.

11. PROVIDE LINTELS AND FRAMING FOR GRILLES, LOUVERS, AND ROOF VENTS AS REQUIRED BY

MECHANICAL CONTRACTOR, VERIFY SIZE AND LOCATION.

12. STRUCTURAL, MECHANICAL, AND ELECTRICAL ABBREVIATIONS AND SYMBOLS MAY DIFFER FROM

ARCHITECTURAL. SEE RESPECTIVE SECTIONS AND/OR DRAWINGS FOR DEFINITIONS.

13. AT MECHANICAL AND ELECTRICAL EQUIPMENT ROOMS, PROVIDE 3/4" FRT PLYWOOD BACKING

BEHIND ALL SURFACE MOUNTED FIXTURES AND EQUIPMENT, UNLESS NOTED OTHERWISE.

14. CONTRACTOR SHALL EVALUATE INTEGRITY OF ALL PARTITIONS INDICATED BY SYMBOLS ON THE

LIFE SAFETY PLAN(S) WITHIN THE PROJECT SCOPE AND UPGRADE AS REQUIRED. ALL FIRE

RESISTIVE RATED WALLS SHALL BE CONSTRUCTED OF MATERIALS / ASSEMBLIES MEETING THE

RATING INDICATED, TERMINATE AT THE DECK ABOVE WITH A TESTED HEAD OF WALL ASSEMBLY AND ALL PENETRATIONS SHALL BE SEALED WITH A TESTED ASSEMBLY. ALL SMOKE PARTITIONS

SHALL BE CONSTRUCTED OF MATERIALS THAT RESIST THE PASSAGE OF SMOKE, TERMINATE AT

THE DECK ABOVE WITH A JOINT SEALED WITH FIRE CAULK AND ALL PENETRATIONS SHALL BE

SEALED WITH FIRE CAULK.

FLOOR PLAN SYMBOLS

EXISTING WALL TO

REMAIN

WALL

EXISTING DOOR AND

FRAME TO REMAIN

DOOR

INTERIOR BORROWED

LIGHT

101B

101A

8'-0" DIMENSION LINE,

NOMINAL

8'-0" EXTENDED

DIMENSION LINE,

NOMINAL

AE2111A

INTERIOR ELEVATION

INDICATOR TAG2B

AE2O1

EXTERIOR ELEVATION

INDICATOR TAG

1A

203 EQUIPMENT TAG

100 FLOOR SPOT

ELEVATIONWALL TAG

OFFICE

ROOM NAME AND

NUMBER AE501

1A

DETAIL REFERENCE

TAG

AE2O1

EXTERIOR SECTION

REFERENCE TAG

1A

AE2O1

INTERIOR SECTION

REFERENCE TAG

1A

KEY NOTE

A

GRIDLINE

REVISION TAG

PR01

REVISION CLOUD

NOTE: NOT ALL SYMBOLS MAY BE USED ON EACH PLAN

FP10

B3

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

35% CONSTRUCTION

DOCUMENT REVIEW

FULLY

SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

NOT FOR CONSTRUCTION

C U s e rs

\P u b lic \D o c u m e n ts \R e v it P ro je c ts

\1

-R g b a rb a ri a e -m n .c o m

.r v t

/2

/2

:1

:1

P

M

AE151-05

FIFTH LEVEL OVERALL FLOOR

PLAN - BUILDING 5

VAMC SIOUX FALLS EHRM

INFRASTRUCTURE UPGRADES

Sioux Falls, SD

438-20-910

03/26/2021 Checker GJB16090

1/8" = 1'-0"1 FIFTH LEVEL FLOOR PLAN - BUILDING 5

Revisions: Date:

5-510A-1

5-510A-2

5-510A-3

5-510A-4 5-510A-5

5-546-1

5-546-2 5-546-3

5-546-4

- Negative Asbestos Bulk Sample LocationX-XX-X

CARPENTER

SHOP

PAINT SHOP

BREAK

ROOM

TOILET

PAINT

BOOTH

TELECOM

PLUMBING

SHOP

LABORERS

SHOP

GARDEN

TOOLS

VESTIBULE

PROVIDE:

- STATIC DISSIPATIVE FLOORING

-4' x8' PLYWOOD ALL WALLS WITH

FIREPROOF PAINT AND GLOSS WHITE

TOP COAT

LIMITS OF CONSTRUCTION

LIMITS OF CONSTRUCTION

AE111-07

GENERAL NOTES

1. THE ARCHITECTURAL DRAWINGS SHOW PRINCIPAL AREAS AND LIMITS OF CONSTRUCTION

WHERE WORK MUST BE ACCOMPLISHED UNDER THIS CONTRACT. INCIDENTAL WORK MAY BE

NECESSARY IN AREAS NOT SHOWN ON ARCHITECTURAL DRAWINGS DUE TO CHANGES

AFFECTING ELECTRICAL, MECHANICAL AND PLUMBING ALONG WITH OTHER SYSTEMS. THIS

INCIDENTAL WORK SHALL BE PART OF THIS CONTRACT, AND ALL TRADES SHALL INSPECT THESE

AREAS, ASCERTAIN WORK REQUIRED AND DO THE WORK IN ACCORDANCE OF CONTRACT

REQUIREMENTS AT NO ADDITIONAL COST.

2. CONTRACTORS SHALL VISIT THE SITE DURING BIDDING TO BECOME FAMILIAR WITH THE

EXISTING CONDITIONS. THE GENERAL CONTRACTOR SHALL LOCATE, INSPECT AND FIELD VERIFY

ALL EXISTING CONDITIONS, DIMENSIONS AND ELEVATIONS PRIOR TO DEMOLITION AND

CONSTRUCTION. NOTIFY ARCHITECT IMMEDIATELY OF ANY DISCREPANCIES.

3. DO NOT SCALE DRAWINGS. NOTIFY ARCHITECT IMMEDIATELY OF ANY DISCREPANCIES.

4. WHEREVER OPENINGS ARE CUT THROUGH FIRE RATED PARTITIONS, IT SHALL BE THE

RESPONSIBILITY OF THE CONTRACTOR FOR WHOM THE HOLE IS CUT TO PATCH AND REPAIR ANY

OPENING TO MAINTAIN THE INTEGRITY OF THE FIRE RATING.

5. GENERAL CONTRACTOR TO CHECK MECHANICAL DRAWINGS FOR EXISTING PIPES AND DUCTS

FURRED IN WALLS. VERIFY SIZE AND LOCATION WITH MECHANICAL CONTRACTOR PRIOR TO

PROCEEDING WITH REMODELING.

6. FIREPROOFING SHALL BE UNPIERCED. ANY SUBCONTRACTOR PENETRATING THE FIREPROOFING

SHALL BE REQUIRED TO REPLACE FIREPROOFING TO THE ORIGINAL CONDITION AND FIRE

RATING, AT THE SUBCONTRACTORS EXPENSE.

7. EQUIPMENT UNIT DIMENSIONS ARE FOR PRODUCT DESCRIPTION ONLY, VERIFY SIZE WITH

MANUFACTURER.

8. ALL DIMENSIONS PERTAINING TO MECHANICAL OR ELECTRICAL SERVICES OR EQUIPMENT SHALL

BE VERIFIED WITH THE RESPECTIVE TRADE.

9. ALL CONTRACTORS THAT PENETRATE AND/OR DISTURB ANY AREAS AT EXISTING CONDITIONS

SHALL PATCH AREA TO MATCH EXISTING ADJACENT AREA OR SURFACE AND PREPARE FOR

SCHEDULED FINISH APPLICATION. COORDINATE WORK WITH GENERAL CONTRACTOR PRIOR TO

PROCEEDING.

10. VERIFY HEIGHTS AND LOCATIONS OF ACCESS PANELS (AP) AND COORDINATE TYPES WITH

TRADES WHICH REQUIRE THEM.

11. PROVIDE LINTELS AND FRAMING FOR GRILLES, LOUVERS, AND ROOF VENTS AS REQUIRED BY

MECHANICAL CONTRACTOR, VERIFY SIZE AND LOCATION.

12. STRUCTURAL, MECHANICAL, AND ELECTRICAL ABBREVIATIONS AND SYMBOLS MAY DIFFER FROM

ARCHITECTURAL. SEE RESPECTIVE SECTIONS AND/OR DRAWINGS FOR DEFINITIONS.

13. AT MECHANICAL AND ELECTRICAL EQUIPMENT ROOMS, PROVIDE 3/4" FRT PLYWOOD BACKING

BEHIND ALL SURFACE MOUNTED FIXTURES AND EQUIPMENT, UNLESS NOTED OTHERWISE.

14. CONTRACTOR SHALL EVALUATE INTEGRITY OF ALL PARTITIONS INDICATED BY SYMBOLS ON THE

LIFE SAFETY PLAN(S) WITHIN THE PROJECT SCOPE AND UPGRADE AS REQUIRED. ALL FIRE

RESISTIVE RATED WALLS SHALL BE CONSTRUCTED OF MATERIALS / ASSEMBLIES MEETING THE

RATING INDICATED, TERMINATE AT THE DECK ABOVE WITH A TESTED HEAD OF WALL ASSEMBLY AND ALL PENETRATIONS SHALL BE SEALED WITH A TESTED ASSEMBLY. ALL SMOKE PARTITIONS

SHALL BE CONSTRUCTED OF MATERIALS THAT RESIST THE PASSAGE OF SMOKE, TERMINATE AT

THE DECK ABOVE WITH A JOINT SEALED WITH FIRE CAULK AND ALL PENETRATIONS SHALL BE

SEALED WITH FIRE CAULK.

FLOOR PLAN SYMBOLS

EXISTING WALL TO

REMAIN

WALL

EXISTING DOOR AND

FRAME TO REMAIN

DOOR

INTERIOR BORROWED

LIGHT

101B

101A

8'-0" DIMENSION LINE,

NOMINAL

8'-0" EXTENDED

DIMENSION LINE,

NOMINAL

AE2111A

INTERIOR ELEVATION

INDICATOR TAG2B

AE2O1

EXTERIOR ELEVATION

INDICATOR TAG

1A

203 EQUIPMENT TAG

100 FLOOR SPOT

ELEVATIONWALL TAG

OFFICE

ROOM NAME AND

NUMBER AE501

1A

DETAIL REFERENCE

TAG

AE2O1

EXTERIOR SECTION

REFERENCE TAG

1A

AE2O1

INTERIOR SECTION

REFERENCE TAG

1A

KEY NOTE

A

GRIDLINE

REVISION TAG

PR01

REVISION CLOUD

NOTE: NOT ALL SYMBOLS MAY BE USED ON EACH PLAN

FP10

B3

TELECOM

PAINT SHOP

TOILET

PLUMBING

SHOP

PLUMBING

SHOP

VESTIBULE

CARD READER

B3

PLYWOOD 3 SIDES OF ROOM. SEE TYPICAL

ELEVATIONS SHEET AE211

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

35% CONSTRUCTION

DOCUMENT REVIEW

FULLY

SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

NOT FOR CONSTRUCTION

C U s e rs

\P u b lic \D o c u m e n ts \R e v it P ro je c ts

\1

-R g b a rb a ri a e -m n .c o m

.r v t

/2

/2

:1

:3

P

M

AE111-07

FIRST LEVEL FLOOR PLAN -

BUILDING 7

VAMC SIOUX FALLS EHRM

INFRASTRUCTURE UPGRADES

Sioux Falls, SD

438-20-910

03/26/2021 Checker Author16090

1/4" = 1'-0"1 FIRST LEVEL FLOOR PLAN - BUILDING 7

1:48

4' 6'

1/2" = 1'-0"2 ENLARGED PLAN - TELECOM 1151 - BUILDING 7

Revisions: Date:

7-107-1A 7-107-1B 7-107-1C

7-107-2 7-107-3 7-107-4

7-107-5 7-107-6 7-107-7

- Negative Asbestos Bulk Sample LocationX-XX-X

STORAGE

STORAGE

TELECOM

ELEC 002A

IT

STORAGE

STORAGE

MECH

LIMITS OF CONSTRUCION

CR

AE111-16

GENERAL NOTES

1. THE ARCHITECTURAL DRAWINGS SHOW PRINCIPAL AREAS AND LIMITS OF CONSTRUCTION

WHERE WORK MUST BE ACCOMPLISHED UNDER THIS CONTRACT. INCIDENTAL WORK MAY BE

NECESSARY IN AREAS NOT SHOWN ON ARCHITECTURAL DRAWINGS DUE TO CHANGES

AFFECTING ELECTRICAL, MECHANICAL AND PLUMBING ALONG WITH OTHER SYSTEMS. THIS

INCIDENTAL WORK SHALL BE PART OF THIS CONTRACT, AND ALL TRADES SHALL INSPECT THESE

AREAS, ASCERTAIN WORK REQUIRED AND DO THE WORK IN ACCORDANCE OF CONTRACT

REQUIREMENTS AT NO ADDITIONAL COST.

2. CONTRACTORS SHALL VISIT THE SITE DURING BIDDING TO BECOME FAMILIAR WITH THE

EXISTING CONDITIONS. THE GENERAL CONTRACTOR SHALL LOCATE, INSPECT AND FIELD VERIFY

ALL EXISTING CONDITIONS, DIMENSIONS AND ELEVATIONS PRIOR TO DEMOLITION AND

CONSTRUCTION. NOTIFY ARCHITECT IMMEDIATELY OF ANY DISCREPANCIES.

3. DO NOT SCALE DRAWINGS. NOTIFY ARCHITECT IMMEDIATELY OF ANY DISCREPANCIES.

4. WHEREVER OPENINGS ARE CUT THROUGH FIRE RATED PARTITIONS, IT SHALL BE THE

RESPONSIBILITY OF THE CONTRACTOR FOR WHOM THE HOLE IS CUT TO PATCH AND REPAIR ANY

OPENING TO MAINTAIN THE INTEGRITY OF THE FIRE RATING.

5. GENERAL CONTRACTOR TO CHECK MECHANICAL DRAWINGS FOR EXISTING PIPES AND DUCTS

FURRED IN WALLS. VERIFY SIZE AND LOCATION WITH MECHANICAL CONTRACTOR PRIOR TO

PROCEEDING WITH REMODELING.

6. FIREPROOFING SHALL BE UNPIERCED. ANY SUBCONTRACTOR PENETRATING THE FIREPROOFING

SHALL BE REQUIRED TO REPLACE FIREPROOFING TO THE ORIGINAL CONDITION AND FIRE

RATING, AT THE SUBCONTRACTORS EXPENSE.

7. EQUIPMENT UNIT DIMENSIONS ARE FOR PRODUCT DESCRIPTION ONLY, VERIFY SIZE WITH

MANUFACTURER.

8. ALL DIMENSIONS PERTAINING TO MECHANICAL OR ELECTRICAL SERVICES OR EQUIPMENT SHALL

BE VERIFIED WITH THE RESPECTIVE TRADE.

9. ALL CONTRACTORS THAT PENETRATE AND/OR DISTURB ANY AREAS AT EXISTING CONDITIONS

SHALL PATCH AREA TO MATCH EXISTING ADJACENT AREA OR SURFACE AND PREPARE FOR

SCHEDULED FINISH APPLICATION. COORDINATE WORK WITH GENERAL CONTRACTOR PRIOR TO

PROCEEDING.

10. VERIFY HEIGHTS AND LOCATIONS OF ACCESS PANELS (AP) AND COORDINATE TYPES WITH

TRADES WHICH REQUIRE THEM.

11. PROVIDE LINTELS AND FRAMING FOR GRILLES, LOUVERS, AND ROOF VENTS AS REQUIRED BY

MECHANICAL CONTRACTOR, VERIFY SIZE AND LOCATION.

12. STRUCTURAL, MECHANICAL, AND ELECTRICAL ABBREVIATIONS AND SYMBOLS MAY DIFFER FROM

ARCHITECTURAL. SEE RESPECTIVE SECTIONS AND/OR DRAWINGS FOR DEFINITIONS.

13. AT MECHANICAL AND ELECTRICAL EQUIPMENT ROOMS, PROVIDE 3/4" FRT PLYWOOD BACKING

BEHIND ALL SURFACE MOUNTED FIXTURES AND EQUIPMENT, UNLESS NOTED OTHERWISE.

14. CONTRACTOR SHALL EVALUATE INTEGRITY OF ALL PARTITIONS INDICATED BY SYMBOLS ON THE

LIFE SAFETY PLAN(S) WITHIN THE PROJECT SCOPE AND UPGRADE AS REQUIRED. ALL FIRE

RESISTIVE RATED WALLS SHALL BE CONSTRUCTED OF MATERIALS / ASSEMBLIES MEETING THE

RATING INDICATED, TERMINATE AT THE DECK ABOVE WITH A TESTED HEAD OF WALL ASSEMBLY AND ALL PENETRATIONS SHALL BE SEALED WITH A TESTED ASSEMBLY. ALL SMOKE PARTITIONS

SHALL BE CONSTRUCTED OF MATERIALS THAT RESIST THE PASSAGE OF SMOKE, TERMINATE AT

THE DECK ABOVE WITH A JOINT SEALED WITH FIRE CAULK AND ALL PENETRATIONS SHALL BE

SEALED WITH FIRE CAULK.

FLOOR PLAN SYMBOLS

EXISTING WALL TO

REMAIN

WALL

EXISTING DOOR AND

FRAME TO REMAIN

DOOR

INTERIOR BORROWED

LIGHT

101B

101A

8'-0" DIMENSION LINE,

NOMINAL

8'-0" EXTENDED

DIMENSION LINE,

NOMINAL

AE2111A

INTERIOR ELEVATION

INDICATOR TAG2B

AE2O1

EXTERIOR ELEVATION

INDICATOR TAG

1A

203 EQUIPMENT TAG

100 FLOOR SPOT

ELEVATIONWALL TAG

OFFICE

ROOM NAME AND

NUMBER AE501

1A

DETAIL REFERENCE

TAG

AE2O1

EXTERIOR SECTION

REFERENCE TAG

1A

AE2O1

INTERIOR SECTION

REFERENCE TAG

1A

KEY NOTE

A

GRIDLINE

REVISION TAG

PR01

REVISION CLOUD

NOTE: NOT ALL SYMBOLS MAY BE USED ON EACH PLAN

FP10

B3

TELECOM

STORAGE

STORAGE

ELEC

CARD READER

PROVIDE:

- STATIC DISSIPATIVE FLOORING

-PLYWOOD 3 SIDES OF ROOM. SEE TYPICAL ELEVATIONS SHEET AE211

PROVIDE OPAQUE WINDOW FILM

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

35% CONSTRUCTION

DOCUMENT REVIEW

FULLY

SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

NOT FOR CONSTRUCTION

C U s e rs

\P u b lic \D o c u m e n ts \R e v it P ro je c ts

\1

-R g b a rb a ri a e -m n .c o m

.r v t

/2

/2

:1

:4

P

M

AE111-16

LOWER LEVEL FLOOR PLAN -

BUILDING 16

VAMC SIOUX FALLS EHRM

INFRASTRUCTURE UPGRADES

Sioux Falls, SD

438-20-910

03/26/2021 Checker Author16090

1/4" = 1'-0"1 LOWER LEVEL FLOOR PLAN - BUILDING 16

1/2" = 1'-0"2 ENLARGED PLAN - TELECOM 1032 - BUILDING 16

Revisions: Date:

16-IT-1A

16-IT-1B

16-IT-1C

16-IT-2

- Negative Asbestos Bulk Sample LocationX-XX-X

VESTIBULE

OFFICE

SECRATARY

OFFICE

LAB 1

LAB 2

LAB 3

105A

STORAGE

CORRIDOR

TOILET

HAC

Room

GENERAL

STERILE

MECH /

ELEC

VESTIBULE

MECH

RAT

HOLDING

TELECOM

ENTRY

MECH

LAB 6

RABBIT

HOLDING

LAB 5

LAB 4

VIROLOGY

COMMON

SERVICE

COMMON

SERVICE

C02

CORRIDOR C01

CORRIDOR

ELEC

AE111-28

GENERAL NOTES

1. THE ARCHITECTURAL DRAWINGS SHOW PRINCIPAL AREAS AND LIMITS OF CONSTRUCTION

WHERE WORK MUST BE ACCOMPLISHED UNDER THIS CONTRACT. INCIDENTAL WORK MAY BE

NECESSARY IN AREAS NOT SHOWN ON ARCHITECTURAL DRAWINGS DUE TO CHANGES

AFFECTING ELECTRICAL, MECHANICAL AND PLUMBING ALONG WITH OTHER SYSTEMS. THIS

INCIDENTAL WORK SHALL BE PART OF THIS CONTRACT, AND ALL TRADES SHALL INSPECT THESE

AREAS, ASCERTAIN WORK REQUIRED AND DO THE WORK IN ACCORDANCE OF CONTRACT

REQUIREMENTS AT NO ADDITIONAL COST.

2. CONTRACTORS SHALL VISIT THE SITE DURING BIDDING TO BECOME FAMILIAR WITH THE

EXISTING CONDITIONS. THE GENERAL CONTRACTOR SHALL LOCATE, INSPECT AND FIELD VERIFY

ALL EXISTING CONDITIONS, DIMENSIONS AND ELEVATIONS PRIOR TO DEMOLITION AND

CONSTRUCTION. NOTIFY ARCHITECT IMMEDIATELY OF ANY DISCREPANCIES.

3. DO NOT SCALE DRAWINGS. NOTIFY ARCHITECT IMMEDIATELY OF ANY DISCREPANCIES.

4. WHEREVER OPENINGS ARE CUT THROUGH FIRE RATED PARTITIONS, IT SHALL BE THE

RESPONSIBILITY OF THE CONTRACTOR FOR WHOM THE HOLE IS CUT TO PATCH AND REPAIR ANY

OPENING TO MAINTAIN THE INTEGRITY OF THE FIRE RATING.

5. GENERAL CONTRACTOR TO CHECK MECHANICAL DRAWINGS FOR EXISTING PIPES AND DUCTS

FURRED IN WALLS. VERIFY SIZE AND LOCATION WITH MECHANICAL CONTRACTOR PRIOR TO

PROCEEDING WITH REMODELING.

6. FIREPROOFING SHALL BE UNPIERCED. ANY SUBCONTRACTOR PENETRATING THE FIREPROOFING

SHALL BE REQUIRED TO REPLACE FIREPROOFING TO THE ORIGINAL CONDITION AND FIRE

RATING, AT THE SUBCONTRACTORS EXPENSE.

7. EQUIPMENT UNIT DIMENSIONS ARE FOR PRODUCT DESCRIPTION ONLY, VERIFY SIZE WITH

MANUFACTURER.

8. ALL DIMENSIONS PERTAINING TO MECHANICAL OR ELECTRICAL SERVICES OR EQUIPMENT SHALL

BE VERIFIED WITH THE RESPECTIVE TRADE.

9. ALL CONTRACTORS THAT PENETRATE AND/OR DISTURB ANY AREAS AT EXISTING CONDITIONS

SHALL PATCH AREA TO MATCH EXISTING ADJACENT AREA OR SURFACE AND PREPARE FOR

SCHEDULED FINISH APPLICATION. COORDINATE WORK WITH GENERAL CONTRACTOR PRIOR TO

PROCEEDING.

10. VERIFY HEIGHTS AND LOCATIONS OF ACCESS PANELS (AP) AND COORDINATE TYPES WITH

TRADES WHICH REQUIRE THEM.

11. PROVIDE LINTELS AND FRAMING FOR GRILLES, LOUVERS, AND ROOF VENTS AS REQUIRED BY

MECHANICAL CONTRACTOR, VERIFY SIZE AND LOCATION.

12. STRUCTURAL, MECHANICAL, AND ELECTRICAL ABBREVIATIONS AND SYMBOLS MAY DIFFER FROM

ARCHITECTURAL. SEE RESPECTIVE SECTIONS AND/OR DRAWINGS FOR DEFINITIONS.

13. AT MECHANICAL AND ELECTRICAL EQUIPMENT ROOMS, PROVIDE 3/4" FRT PLYWOOD BACKING

BEHIND ALL SURFACE MOUNTED FIXTURES AND EQUIPMENT, UNLESS NOTED OTHERWISE.

14. CONTRACTOR SHALL EVALUATE INTEGRITY OF ALL PARTITIONS INDICATED BY SYMBOLS ON THE

LIFE SAFETY PLAN(S) WITHIN THE PROJECT SCOPE AND UPGRADE AS REQUIRED. ALL FIRE

RESISTIVE RATED WALLS SHALL BE CONSTRUCTED OF MATERIALS / ASSEMBLIES MEETING THE

RATING INDICATED, TERMINATE AT THE DECK ABOVE WITH A TESTED HEAD OF WALL ASSEMBLY AND ALL PENETRATIONS SHALL BE SEALED WITH A TESTED ASSEMBLY. ALL SMOKE PARTITIONS

SHALL BE CONSTRUCTED OF MATERIALS THAT RESIST THE PASSAGE OF SMOKE, TERMINATE AT

THE DECK ABOVE WITH A JOINT SEALED WITH FIRE CAULK AND ALL PENETRATIONS SHALL BE

SEALED WITH FIRE CAULK.

FLOOR PLAN SYMBOLS

EXISTING WALL TO

REMAIN

WALL

EXISTING DOOR AND

FRAME TO REMAIN

DOOR

INTERIOR BORROWED

LIGHT

101B

101A

8'-0" DIMENSION LINE,

NOMINAL

8'-0" EXTENDED

DIMENSION LINE,

NOMINAL

AE2111A

INTERIOR ELEVATION

INDICATOR TAG2B

AE2O1

EXTERIOR ELEVATION

INDICATOR TAG

1A

203 EQUIPMENT TAG

100 FLOOR SPOT

ELEVATIONWALL TAG

OFFICE

ROOM NAME AND

NUMBER AE501

1A

DETAIL REFERENCE

TAG

AE2O1

EXTERIOR SECTION

REFERENCE TAG

1A

AE2O1

INTERIOR SECTION

REFERENCE TAG

1A

KEY NOTE

A

GRIDLINE

REVISION TAG

PR01

REVISION CLOUD

NOTE: NOT ALL SYMBOLS MAY BE USED ON EACH PLAN

FP10

B3

TELECOM

RAT

HOLDING

MECH

ENTRY

CARD READER

PROVIDE:

- STATIC DISSIPATIVE FLOORING

-PLYWOOD 3 SIDES OF ROOM. SEE

TYPICAL ELEVATIONS SHEET AE211

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

35% CONSTRUCTION

DOCUMENT REVIEW

FULLY

SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

NOT FOR CONSTRUCTION

C U s e rs

\P u b lic \D o c u m e n ts \R e v it P ro je c ts

\1

-R g b a rb a ri a e -m n .c o m

.r v t

/2

/2

:1

:4

P

M

AE111-28

FIRST LEVEL FLOOR PLAN -

BUILDING 28

VAMC SIOUX FALLS EHRM

INFRASTRUCTURE UPGRADES

Sioux Falls, SD

438-20-910

03/26/2021 Checker Author16090

1/8" = 1'-0"1 FIRST LEVEL FLOOR PLAN - BUILDING 28

1/2" = 1'-0"2 ENLARGED PLAN - TELECOM 1081 - BUILDING 28

Revisions: Date:

28-123-1A28-123-1B

28-123-1C

28-123-2 28-123-3

28-123-4

28-123-5

- Negative Asbestos Bulk Sample LocationX-XX-X

D.A.V.

P.V.A.

OPEN

OFFICE

OFFICE

CLASROOM

108A

WORK

ROOM

105A

HEARING

ROOM

OFFICE

C01A

VESTIBULE

105B

WAITING

WOMENS

TOILET

HAC

13A

OFFICE 138B

Room

STROAGE

OFFICE

OFFICE 129

TELECOM

OFFICE

MENS

TOILET

TELEPHONE

ELECTRICAL

VENDING

Room

Room

Room136

Room

VESTIBULE

RECEIVING

OPEN AREA

OPEN

OFFICE

MECHANICAL 116

ELECTRICAL

ACCOUNTING

OFFICE

FISCAL

SERVICE

PUBLICATIONS

117A

OFFICE

OPEN

OFFICE

DSS

FEE BASIS

OFFICE

BUDGET

ANALYST

110C

OFFICE

RECEPTION109

WAITING

109A

OFFICE 109B

OFFICE 109C

JOB LAB 110A

OFFICE

110B

OFFICE

145A

WORK

ATTORNEY

DIST

COUNSEL

OPEN

OFFICE

LIBRBARY /

CONFRENCE

OPEN

OFFICE

TOILET

C02

LOBBY

C04

CORRDOR

C06

CORRIDOR

C08

CORRIDOR

C11

CORRIDOR

RECEPTION

C10

CORRIDOR

C05

CORRIDOR

C03

CORRIDOR

131A

STORAGE

TOILET

C01

ENTRANCE

C01B

EXIT 105

EMS

108B

OFFICE

108C

OFFICE

AE111-38

LI

M

IT

S

OF

C

ON

ST

RU

CT

IO

N

GENERAL NOTES

1. THE ARCHITECTURAL DRAWINGS SHOW PRINCIPAL AREAS AND LIMITS OF CONSTRUCTION

WHERE WORK MUST BE ACCOMPLISHED UNDER THIS CONTRACT. INCIDENTAL WORK MAY BE

NECESSARY IN AREAS NOT SHOWN ON ARCHITECTURAL DRAWINGS DUE TO CHANGES

AFFECTING ELECTRICAL, MECHANICAL AND PLUMBING ALONG WITH OTHER SYSTEMS. THIS

INCIDENTAL WORK SHALL BE PART OF THIS CONTRACT, AND ALL TRADES SHALL INSPECT THESE

AREAS, ASCERTAIN WORK REQUIRED AND DO THE WORK IN ACCORDANCE OF CONTRACT

REQUIREMENTS AT NO ADDITIONAL COST.

2. CONTRACTORS SHALL VISIT THE SITE DURING BIDDING TO BECOME FAMILIAR WITH THE

EXISTING CONDITIONS. THE GENERAL CONTRACTOR SHALL LOCATE, INSPECT AND FIELD VERIFY

ALL EXISTING CONDITIONS, DIMENSIONS AND ELEVATIONS PRIOR TO DEMOLITION AND

CONSTRUCTION. NOTIFY ARCHITECT IMMEDIATELY OF ANY DISCREPANCIES.

3. DO NOT SCALE DRAWINGS. NOTIFY ARCHITECT IMMEDIATELY OF ANY DISCREPANCIES.

4. WHEREVER OPENINGS ARE CUT THROUGH FIRE RATED PARTITIONS, IT SHALL BE THE

RESPONSIBILITY OF THE CONTRACTOR FOR WHOM THE HOLE IS CUT TO PATCH AND REPAIR ANY

OPENING TO MAINTAIN THE INTEGRITY OF THE FIRE RATING.

5. GENERAL CONTRACTOR TO CHECK MECHANICAL DRAWINGS FOR EXISTING PIPES AND DUCTS

FURRED IN WALLS. VERIFY SIZE AND LOCATION WITH MECHANICAL CONTRACTOR PRIOR TO

PROCEEDING WITH REMODELING.

6. FIREPROOFING SHALL BE UNPIERCED. ANY SUBCONTRACTOR PENETRATING THE FIREPROOFING

SHALL BE REQUIRED TO REPLACE FIREPROOFING TO THE ORIGINAL CONDITION AND FIRE

RATING, AT THE SUBCONTRACTORS EXPENSE.

7. EQUIPMENT UNIT DIMENSIONS ARE FOR PRODUCT DESCRIPTION ONLY, VERIFY SIZE WITH

MANUFACTURER.

8. ALL DIMENSIONS PERTAINING TO MECHANICAL OR ELECTRICAL SERVICES OR EQUIPMENT SHALL

BE VERIFIED WITH THE RESPECTIVE TRADE.

9. ALL CONTRACTORS THAT PENETRATE AND/OR DISTURB ANY AREAS AT EXISTING CONDITIONS

SHALL PATCH AREA TO MATCH EXISTING ADJACENT AREA OR SURFACE AND PREPARE FOR

SCHEDULED FINISH APPLICATION. COORDINATE WORK WITH GENERAL CONTRACTOR PRIOR TO

PROCEEDING.

10. VERIFY HEIGHTS AND LOCATIONS OF ACCESS PANELS (AP) AND COORDINATE TYPES WITH

TRADES WHICH REQUIRE THEM.

11. PROVIDE LINTELS AND FRAMING FOR GRILLES, LOUVERS, AND ROOF VENTS AS REQUIRED BY

MECHANICAL CONTRACTOR, VERIFY SIZE AND LOCATION.

12. STRUCTURAL, MECHANICAL, AND ELECTRICAL ABBREVIATIONS AND SYMBOLS MAY DIFFER FROM

ARCHITECTURAL. SEE RESPECTIVE SECTIONS AND/OR DRAWINGS FOR DEFINITIONS.

13. AT MECHANICAL AND ELECTRICAL EQUIPMENT ROOMS, PROVIDE 3/4" FRT PLYWOOD BACKING

BEHIND ALL SURFACE MOUNTED FIXTURES AND EQUIPMENT, UNLESS NOTED OTHERWISE.

14. CONTRACTOR SHALL EVALUATE INTEGRITY OF ALL PARTITIONS INDICATED BY SYMBOLS ON THE

LIFE SAFETY PLAN(S) WITHIN THE PROJECT SCOPE AND UPGRADE AS REQUIRED. ALL FIRE

RESISTIVE RATED WALLS SHALL BE CONSTRUCTED OF MATERIALS / ASSEMBLIES MEETING THE

RATING INDICATED, TERMINATE AT THE DECK ABOVE WITH A TESTED HEAD OF WALL ASSEMBLY AND ALL PENETRATIONS SHALL BE SEALED WITH A TESTED ASSEMBLY. ALL SMOKE PARTITIONS

SHALL BE CONSTRUCTED OF MATERIALS THAT RESIST THE PASSAGE OF SMOKE, TERMINATE AT

THE DECK ABOVE WITH A JOINT SEALED WITH FIRE CAULK AND ALL PENETRATIONS SHALL BE

SEALED WITH FIRE CAULK.

FLOOR PLAN SYMBOLS

EXISTING WALL TO

REMAIN

WALL

EXISTING DOOR AND

FRAME TO REMAIN

DOOR

INTERIOR BORROWED

LIGHT

101B

101A

8'-0" DIMENSION LINE,

NOMINAL

8'-0" EXTENDED

DIMENSION LINE,

NOMINAL

AE2111A

INTERIOR ELEVATION

INDICATOR TAG2B

AE2O1

EXTERIOR ELEVATION

INDICATOR TAG

1A

203 EQUIPMENT TAG

100 FLOOR SPOT

ELEVATIONWALL TAG

OFFICE

ROOM NAME AND

NUMBER AE501

1A

DETAIL REFERENCE

TAG

AE2O1

EXTERIOR SECTION

REFERENCE TAG

1A

AE2O1

INTERIOR SECTION

REFERENCE TAG

1A

KEY NOTE

A

GRIDLINE

REVISION TAG

PR01

REVISION CLOUD

NOTE: NOT ALL SYMBOLS MAY BE USED ON EACH PLAN

FP10

B3

TELECOM

OFFICE

C06

CORRIDOR

131A

STORAGE

OPEN

OFFICE

TOILET

MENS

TOILET

PROVIDE:

- STATIC DISSIPATIVE FLOORING

-PLYWOOD 3 SIDES OF ROOM. SEE TYPICAL ELEVATIONS SHEET AE211

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

35% CONSTRUCTION

DOCUMENT REVIEW

FULLY

SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

NOT FOR CONSTRUCTION

C U s e rs

\P u b lic \D o c u m e n ts \R e v it P ro je c ts

\1

-R g b a rb a ri a e -m n .c o m

.r v t

/2

/2

:1

:5

P

M

AE111-38

FIRST LEVEL FLOOR PLAN -

BUILDING 38

VAMC SIOUX FALLS EHRM

INFRASTRUCTURE UPGRADES

Sioux Falls, SD

438-20-910

03/26/2021 Checker Author16090

1/8" = 1'-0"1 FIRST LEVEL FLOOR PLAN

1/2" = 1'-0"2 ENLARGEDPLAN - COMPUTER ROOM 129- BUILDING 38

Revisions: Date:

38-129-1A

38-129-1B38-129-1C 38-129-7 38-129-8

38-129-2 38-129-3

38-129-9

38-129-6

38-129-4 38-129-5

- Negative Asbestos Bulk Sample LocationX-XX-X

Room

Room

142A Room

142B Room

142D Room

142C Room

Room

144A Room

Room

143A Room

143B Room

191B Room

191A Room

Room

198A Room

Room

230R Room

230S Room

230T Room

STAIR 6

194A Room

Room

CORRIDOR

191C Room

191E Room

191D Room

Room

193A

MECHANICAL

193C Room

195A Room

196B

WOMENS

TOILET

196A

MENS

TOILET

Room

193B

CLOSET

OFFICE

180A

OFFICE

139B

DOCK

188A

IT

Room

Room

Room

Room

Room

Room

Room

Room

STAIR 1

CORRIDOR

BU

IL

DI

NG

AR

EA

A

BU

IL

DI

NG

AR

EA

C

BUILDING 5 - AREA A

BUILDING 5 - AREA B

GROUP

107A

CLOSET

STORAGE

OFFICE

OFFICE

101A

CORRIDOR

TELECOM

OFFICE108

EXAM

EXAM

EXAM

BREAK

ROOM

STORAGE

HAC

STAF

TOILET

WOMENS

TOILET

MENS

TOILET

MECH

CORRIDOR

RECEP /

WAITING

LIMITS OF CONSTRUCTION

PROVIDE:

- STATIC DISSIPATIVE FLOORING

-4' x8' PLYWOOD ALL WALLS WITH FIREPROOF PAINT AND GLOSS WHITE TOP COAT

180B

OFFICE

180C

OFFICE

180D

OFFICE

180E

OFFICE

Room

195B

TELE

E125 Room

E124 Room

E123

INTERSTITIAL

189A

STAIR 7

CR

AE413

BUILDING 52

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

35% CONSTRUCTION

DOCUMENT REVIEW

FULLY

SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

NOT FOR CONSTRUCTION

C U s e rs

\P u b lic \D o c u m e n ts \R e v it P ro je c ts

\1

-R g b a rb a ri a e -m n .c o m

.r v t

/2

/2

:1

:2

P

M

AE111-05-A

FIRST LEVEL FLOOR PLAN -

BUILDING 5 & 52 - AREA A

VAMC SIOUX FALLS EHRM

INFRASTRUCTURE UPGRADES

Sioux Falls, SD

438-20-910

03/26/2021 Checker Author16090

1/8" = 1'-0"1 FIRST LEVEL FLOOR PLAN- BUILDING 5 - AREA A

Revisions: Date:

52-106-3 52-106-4

52-106-1 52-106-2

52-106-5A, 5B, 5C

52-106-6

- Negative Asbestos Bulk Sample LocationX-XX-X

SanAir ID#: 21024221

Project #: 19149.02

Project Name: EHRM Update

Report Date: 5/24/2021

Analysis Report prepared for Landmark Environmental

Dear Mark Meier, We at SanAir would like to thank you for the work you recently submitted. The 181 sample(s) were received on Tuesday, May 18, 2021 via FedEx. The final report(s) is enclosed for the following sample(s): 5-1002-1, 5-1002-2A, 5 -1002-3, 5-1002-4, 5-1002-5, 5-1114-1, 5-1114-2A, 5-1114-3, 5-1114-4, 5-111-1, 5-111-2, 5-111-3, 5-268-1, 5-268-2, 5-268-3, 5-268-4, 5-268-5, 5-268-6, 5-268-7, 5-268-8, 5-270-5-1, 5-270-5-2, 5-270-5-3, 5-226C-1, 5-226C-2, 5- 226C-3, 5-226C-4, 5-226C-5, 5-296C-1A, 5-296C-1B, 5-296C-1C, 5-296C-2, 5-296C-3, 5-296-1, 5-296-2A, 5-296- 2B, 5-296-2C, 5-296-3, 5-296-4, 5-296-5, 5-296-6, 5-296-7, 5-296-8, 5-A27-1, 5-A27-2, 5-A27-3, 5-A27-4, 5-A27-5, 5- B23-1, 5-B23-2, 5-B23-3, 5-B23-4, 5-B23-5, 5-E05-1, 5-E05-2, 5-E150A-1, 5-E150A-2, 5-E150A-3, 5-330C-1, 5- 330C-2, 5-330C-3, 5-330C-4A, 5-330C-4B, 5-330C-4C, 5-546-1, 5-546-2, 5-546-3, 5-546-4, 1-314-1, 1-314-2, 1-314- 3, 1-314-4, 1-314-5, 1-314-6, 1-314-7, 5-Nurse-1, 5-Nurse-2, 5-Nurse-4, 5-B66A-1, 5-B66A-2, 5-B66A-3, 1-02-1, 1-02 -2, 1-02-3, 1-02-4, 1-02-5, 1-02-6, 1-02-7, 1-037-1, 1-037-2, 1-037-3, 5-149-1, 5-149-2, 5-149-3, 5-149-4, 5-149-5, 5- 149-6, 5-149-7, 5-178-1, 5-178-2, 5-178-3, 5-178-4, 5-178-5, 5-178-6, 5-178-7, 5-178-8, 5-178-9, 5-178-10, 5-178-11, 5-178-12, 5-178-13, 5-178-14, 5-175-1, 5-175-2, 5-175-3, 5-175-4, 5-175-5, 5-201-1A, 5-201-1B, 5-201-1C, 5-433-1, 5-433-2, 5-433-3, 5-433-4, 5-433-5, 5-433-6, 5-451-1, 5-451-2, 5-451-3, 5-451-4, 5-451-5, 5-451-6, 5-451-7, 5-451-8, 5-510A-1, 5-510A-2, 5-510A-3, 5-510A-4, 5-510A-5, 52-106-1, 52-106-2, 52-106-3, 52-106-4, 52-106-5A, 52-106-5B, 52-106-5C, 52-106-6, 7-107-1A, 7-107-1B, 7-107-1C, 7-107-2, 7-107-3, 7-107-4, 7-107-5, 7-107-6, 7-107-7, 16- IT-1A, 16-IT-1B, 16-IT-1C, 16-IT-2, 28-123-1A, 28-123-1B, 28-123-1C, 28-123-2, 28-123-3, 28-123-4, 28-123-5, 38- 129-1A, 38-129-1B, 38-129-1C, 38-129-2, 38-129-3, 38-129-4, 38-129-5, 38-129-6, 38-129-7, 38-129-8, 38-129-9, 5- 1002-2B, 5-1114-2B, 1-037-1B.

These results only pertain to this job and should not be used in the interpretation of any other job. This report is only complete in its entirety. Refer to the listing below of the pages included in a complete final report.

Sincerely, Sandra Sobrino Asbestos & Materials Laboratory Manager SanAir Technologies Laboratory

Final Report Includes:

- Cover Letter

- Analysis Pages

- Disclaimers and Additional Information

Sample conditions:

- 181 samples in Good condition.

1551 Oakbridge Dr. Suite B, Powhatan, VA 23139 | 804.897.1177 | Fax: 804.897.0070 | www.SanAir.com | IAQ@SanAir.com

19149.02Project Number:

P.O. Number:

Project Name: EHRM Update

5/13/2021Collected Date:

5/18/2021 10:05:00 AMReceived Date:

5/24/2021 9:58:38 AM

21024221 SanAir ID Number

FINAL REPORT

Landmark EnvironmentalName:

Address: 2042 West 98th Street

Bloomington, MN 55431

952-666-2422Phone:

Analyst: Vaughan, Nathaniel | Childress, Susan

Asbestos Bulk PLM EPA 600/R-93/116 Stereoscopic Components

SanAir ID / Description Appearance % Fibrous % Non-fibrous Asbestos Fibers

5-1002-1 / 21024221-001 SR & JC, Sheetrock

White Non-Fibrous

Heterogeneous

5% Cellulose 95% Other None Detected

5-1002-1 / 21024221-001 SR & JC, Joint Compound

White Non-Fibrous

Heterogeneous

100% Other None Detected

5-1002-2A / 21024221-002 Fireproofing

White Fibrous

Heterogeneous

65% Cellulose 35% Other None Detected

5-1002-3 / 21024221-003 F.S. Putty

Red Non-Fibrous

Heterogeneous

100% Other None Detected

5-1002-4 / 21024221-004 Old Roof Epoxy Like

Off-White Non-Fibrous

Heterogeneous

100% Other None Detected

5-1002-5 / 21024221-005 Remnant Roofing Felt

Black Fibrous

Heterogeneous

65% Cellulose 35% Other None Detected

5-1114-1 / 21024221-006 SR & JC, Sheetrock

White Non-Fibrous

Heterogeneous

5% Cellulose 95% Other None Detected

5-1114-1 / 21024221-006 SR & JC, Joint Compound

White Non-Fibrous

Heterogeneous

100% Other None Detected

5-1114-2A / 21024221-007 Fireproofing

White Fibrous

Heterogeneous

5% Cellulose 55% Glass

40% Other None Detected

5-1114-3 / 21024221-008 Baseboard

Brown Non-Fibrous

Heterogeneous

100% Other None Detected

Analyst:

Analysis Date: 5/22/2021 Date: 5/24/2021

Approved Signatory:

19149.02Project Number:

P.O. Number:

Project Name: EHRM Update

5/13/2021Collected Date:

5/18/2021 10:05:00 AMReceived Date:

5/24/2021 9:58:38 AM

21024221 SanAir ID Number

FINAL REPORT

Landmark EnvironmentalName:

Address: 2042 West 98th Street

Bloomington, MN 55431

Stereoscopic Components

SanAir ID / Description Appearance % Fibrous % Non-fibrous Asbestos Fibers

5-1114-4 / 21024221-009 BB Adhesive

Yellow Non-Fibrous

Heterogeneous

100% Other None Detected

5-111-1 / 21024221-010 Floor Level/Carpet Adh.

Yellow Non-Fibrous

Heterogeneous

100% Other None Detected

5-111-2 / 21024221-011 2x2 CT W/ FDH

White Fibrous

Heterogeneous

65% Cellulose 20% Glass

12% Min. Wool

3% Other None Detected

5-111-3 / 21024221-012 Plaster, Plaster

Brown Non-Fibrous

Heterogeneous

100% Other None Detected

5-111-3 / 21024221-012 Plaster, Skim Coat

White Non-Fibrous

Heterogeneous

100% Other None Detected

5-268-1 / 21024221-013 2x2 CT W/ FDH

White Fibrous

Heterogeneous

65% Cellulose 20% Glass

12% Min. Wool

3% Other None Detected

5-268-2 / 21024221-014 Floor Sheet, Floor Sheet

Brown Non-Fibrous

Heterogeneous

100% Other None Detected

5-268-2 / 21024221-014 Floor Sheet, Mastic

Yellow Non-Fibrous

Heterogeneous

100% Other None Detected

5-268-3 / 21024221-015 Baseboard

Brown Non-Fibrous

Heterogeneous

100% Other None Detected

5-268-4 / 21024221-016 BB Adh

Yellow Non-Fibrous

Heterogeneous

100% Other None Detected

Analyst:

Analysis Date: 5/22/2021 Date: 5/24/2021

Approved Signatory:

1551 Oakbridge Dr. Suite B, Powhatan, VA 23139 | 804.897.1177 | Fax: 804.897.0070 | www.SanAir.com | IAQ@SanAir.com

19149.02Project Number:

P.O. Number:

Project Name: EHRM Update

5/13/2021Collected Date:

5/18/2021 10:05:00 AMReceived Date:

5/24/2021 9:58:38 AM

21024221 SanAir ID Number

FINAL REPORT

Landmark EnvironmentalName:

Address: 2042 West 98th Street

Bloomington, MN 55431

Stereoscopic Components

SanAir ID / Description Appearance % Fibrous % Non-fibrous Asbestos Fibers

5-268-5 / 21024221-017 SR & JC, Sheetrock

White Non-Fibrous

Heterogeneous

5% Cellulose 95% Other None Detected

5-268-5 / 21024221-017 SR & JC, Joint Compound

White Non-Fibrous

Heterogeneous

100% Other None Detected

5-268-6 / 21024221-018 4" Ceramic Wall Tile

White Non-Fibrous

Heterogeneous

100% Other None Detected

5-268-7 / 21024221-019 4" Ceramic Mortar/Adh.

Yellow Non-Fibrous

Heterogeneous

100% Other None Detected

5-268-8 / 21024221-020 4" Ceramic Grout

White Non-Fibrous

Heterogeneous

100% Other None Detected

5-270-5-1 / 21024221-021 Floor Sheet

Brown Non-Fibrous

Heterogeneous

100% Other None Detected

5-270-5-2 / 21024221-022 FS Putty

Red Non-Fibrous

Heterogeneous

100% Other None Detected

5-270-5-3 / 21024221-023 Plaster, Plaster

Brown Non-Fibrous

Heterogeneous

100% Other None Detected

5-270-5-3 / 21024221-023 Plaster, Skim Coat

White Non-Fibrous

Heterogeneous

100% Other None Detected

5-226C-1 / 21024221-024 Fireproofing

Gray Fibrous

Heterogeneous

8% Cellulose 55% Glass

37% Other None Detected

Analyst:

Analysis Date: 5/22/2021 Date: 5/24/2021

Approved Signatory:

1551 Oakbridge Dr. Suite B, Powhatan, VA 23139 | 804.897.1177 | Fax: 804.897.0070 | www.SanAir.com | IAQ@SanAir.com

19149.02Project Number:

P.O. Number:

Project Name: EHRM Update

5/13/2021Collected Date:

5/18/2021 10:05:00 AMReceived Date:

5/24/2021 9:58:38 AM

21024221 SanAir ID Number

FINAL REPORT

Landmark EnvironmentalName:

Address: 2042 West 98th Street

Bloomington, MN 55431

Stereoscopic Components

SanAir ID / Description Appearance % Fibrous % Non-fibrous Asbestos Fibers

5-226C-2 / 21024221-025

BB

Brown Non-Fibrous

Heterogeneous

100% Other None Detected

5-226C-3 / 21024221-026 BB Adh

Yellow Non-Fibrous

Heterogeneous

100% Other None Detected

5-226C-4 / 21024221-027 Firestop Putty

Brown Non-Fibrous

Heterogeneous

100% Other None Detected

5-226C-5 / 21024221-028 Firestop Putty

Red Non-Fibrous

Heterogeneous

100% Other None Detected

5-296C-1A / 21024221-029 Plaster

White Non-Fibrous

Heterogeneous

100% Other None Detected

5-296C-1B / 21024221-030 Plaster, Plaster

Brown Non-Fibrous

Heterogeneous

100% Other None Detected

5-296C-1B / 21024221-030 Plaster, Skim Coat

White Non-Fibrous

Heterogeneous

100% Other None Detected

5-296C-1C / 21024221-031 Plaster

White Non-Fibrous

Heterogeneous

100% Other None Detected

5-296C-2 / 21024221-032 Firestop Putty

Brown Non-Fibrous

Heterogeneous

100% Other None Detected

5-296C-3 / 21024221-033 Tar Wall Panel Adh

Yellow Non-Fibrous

Heterogeneous

100% Other None Detected

Analyst:

Analysis Date: 5/22/2021 Date: 5/24/2021

Approved Signatory:

1551 Oakbridge Dr. Suite B, Powhatan, VA 23139 | 804.897.1177 | Fax: 804.897.0070 | www.SanAir.com | IAQ@SanAir.com

19149.02Project Number:

P.O. Number:

Project Name: EHRM Update

5/13/2021Collected Date:

5/18/2021 10:05:00 AMReceived Date:

5/24/2021 9:58:38 AM

21024221 SanAir ID Number

FINAL REPORT

Landmark EnvironmentalName:

Address: 2042 West 98th Street

Bloomington, MN 55431

Stereoscopic Components

SanAir ID / Description Appearance % Fibrous % Non-fibrous Asbestos Fibers

5-296-1 / 21024221-034 SR & JC, Sheetrock

White Non-Fibrous

Heterogeneous

8% Cellulose 92% Other None Detected

5-296-1 / 21024221-034 SR & JC, Joint Compound

Beige Non-Fibrous

Heterogeneous

98% Other 2% Chrysotile

5-296-2A / 21024221-035 Wall Texture

White Non-Fibrous

Heterogeneous

100% Other < 1% Chrysotile

5-296-2B / 21024221-036 Wall Texture

White Non-Fibrous

Heterogeneous

100% Other < 1% Chrysotile

5-296-2C / 21024221-037 Wall Texture

White Non-Fibrous

Heterogeneous

100% Other < 1% Chrysotile

5-296-3 / 21024221-038 Tall BB

Gray Non-Fibrous

Heterogeneous

100% Other None Detected

5-296-4 / 21024221-039 BB Adh

Yellow Non-Fibrous

Heterogeneous

100% Other None Detected

5-296-5 / 21024221-040 2x4 CT

White Fibrous

Heterogeneous

65% Cellulose 20% Glass

12% Min. Wool

3% Other None Detected

5-296-6 / 21024221-041 2x4 CT W/ FDH

White Fibrous

Heterogeneous

65% Cellulose 20% Glass

12% Min. Wool

3% Other None Detected

5-296-7 / 21024221-042 12x12 FT

Gray Non-Fibrous

Heterogeneous

100% Other None Detected

Analyst:

Analysis Date: 5/22/2021 Date: 5/24/2021

Approved Signatory:

1551 Oakbridge Dr. Suite B, Powhatan, VA 23139 | 804.897.1177 | Fax: 804.897.0070 | www.SanAir.com | IAQ@SanAir.com

19149.02Project Number:

P.O. Number:

Project Name: EHRM Update

5/13/2021Collected Date:

5/18/2021 10:05:00 AMReceived Date:

5/24/2021 9:58:38 AM

21024221 SanAir ID Number

FINAL REPORT

Landmark EnvironmentalName:

Address: 2042 West 98th Street

Bloomington, MN 55431

Stereoscopic Components

SanAir ID / Description Appearance % Fibrous % Non-fibrous Asbestos Fibers

5-296-8 / 21024221-043 FT Mastic

Yellow Non-Fibrous

Heterogeneous

100% Other None Detected

5-A27-1 / 21024221-044 2x2 Reveal/ D & H

White Fibrous

Heterogeneous

65% Cellulose 20% Glass

12% Min. Wool

3% Other None Detected

5-A27-2 / 21024221-045 Flooring

Gray Non-Fibrous

Heterogeneous

100% Other None Detected

5-A27-3 / 21024221-046 Baseboard

Tan Non-Fibrous

Heterogeneous

100% Other None Detected

5-A27-4 / 21024221-047 BB Adhesive

Yellow Non-Fibrous

Heterogeneous

100% Other None Detected

5-A27-5 / 21024221-048 Sheetrock & Joint Compound, Sheetrock

White Non-Fibrous

Heterogeneous

8% Cellulose 92% Other None Detected

5-A27-5 / 21024221-048 Sheetrock & Joint Compound, Joint Compound

White Non-Fibrous

Homogeneous

100% Other None Detected

5-B23-1 / 21024221-049 Wood Floor Sheet

Brown Non-Fibrous

Heterogeneous

100% Other None Detected

5-B23-2 / 21024221-050

BB

Gray Non-Fibrous

Heterogeneous

100% Other None Detected

5-B23-3 / 21024221-051 BB Adh

Yellow Non-Fibrous

Heterogeneous

100% Other None Detected

Analyst:

Analysis Date: 5/22/2021 Date: 5/24/2021

Approved Signatory:

1551 Oakbridge Dr. Suite B, Powhatan, VA 23139 | 804.897.1177 | Fax: 804.897.0070 | www.SanAir.com | IAQ@SanAir.com

19149.02Project Number:

P.O. Number:

Project Name: EHRM Update

5/13/2021Collected Date:

5/18/2021 10:05:00 AMReceived Date:

5/24/2021 9:58:38 AM

21024221 SanAir ID Number

FINAL REPORT

Landmark EnvironmentalName:

Address: 2042 West 98th Street

Bloomington, MN 55431

Stereoscopic Components

SanAir ID / Description Appearance % Fibrous % Non-fibrous Asbestos Fibers

5-B23-4 / 21024221-052 SR & JC, Sheetrock

White Non-Fibrous

Heterogeneous

8% Cellulose 92% Other None Detected

5-B23-4 / 21024221-052 SR & JC, Joint Compound

Beige Non-Fibrous

Heterogeneous

98% Other 2% Chrysotile

5-B23-5 / 21024221-053 ST Putty

Red Non-Fibrous

Heterogeneous

100% Other None Detected

5-E05-1 / 21024221-054 Sheetrock & Joint Compound, Sheetrock

White Non-Fibrous

Heterogeneous

8% Cellulose 92% Other None Detected

5-E05-1 / 21024221-054 Sheetrock & Joint Compound, Joint Compound

Beige Non-Fibrous

Heterogeneous

98% Other 2% Chrysotile

5-E05-2 / 21024221-055 2x2 CT

White Fibrous

Heterogeneous

65% Cellulose 20% Glass

12% Min. Wool

3% Other None Detected

5-E150A-1 / 21024221-056 Fire Stop Putty

Red Non-Fibrous

Heterogeneous

100% Other None Detected

5-E150A-2 / 21024221-057 Fire Stop Putty

Orange Non-Fibrous

Heterogeneous

100% Other None Detected

5-E150A-3 / 21024221-058 Fire Stop Putty

White Non-Fibrous

Heterogeneous

100% Other None Detected

5-330C-1 / 21024221-059 SR & JC, Sheetrock

White Non-Fibrous

Heterogeneous

8% Cellulose 92% Other None Detected

Analyst:

Analysis Date: 5/22/2021 Date: 5/24/2021

Approved Signatory:

1551 Oakbridge Dr. Suite B, Powhatan, VA 23139 | 804.897.1177 | Fax: 804.897.0070 | www.SanAir.com | IAQ@SanAir.com

19149.02Project Number:

P.O. Number:

Project Name: EHRM Update

5/13/2021Collected Date:

5/18/2021 10:05:00 AMReceived Date:

5/24/2021 9:58:38 AM

21024221 SanAir ID Number

FINAL REPORT

Landmark EnvironmentalName:

Address: 2042 West 98th Street

Bloomington, MN 55431

Stereoscopic Components

SanAir ID / Description Appearance % Fibrous % Non-fibrous Asbestos Fibers

5-330C-1 / 21024221-059 SR & JC, Joint Compound

Beige Non-Fibrous

Heterogeneous

98% Other 2% Chrysotile

5-330C-2 / 21024221-060 Baseboard

Brown Non-Fibrous

Heterogeneous

100% Other None Detected

5-330C-3 / 21024221-061 BB Adh

Yellow Non-Fibrous

Heterogeneous

100% Other None Detected

5-330C-4A / 21024221-062 Fireproofing

Gray Fibrous

Homogeneous

8% Cellulose 55% Glass

37% Other None Detected

5-330C-4B / 21024221-063 Fireproofing

Gray Fibrous

Homogeneous

8% Cellulose 55% Glass

37% Other None Detected

5-330C-4C / 21024221-064 Fireproofing

Gray Fibrous

Homogeneous

8% Cellulose 55% Glass

37% Other None Detected

5-546-1 / 21024221-065 Floor Sheet

Tan Non-Fibrous

Heterogeneous

100% Other None Detected

5-546-2 / 21024221-066

BB

Gray Non-Fibrous

Heterogeneous

100% Other None Detected

5-546-3 / 21024221-067 BB Adh

Yellow Non-Fibrous

Heterogeneous

100% Other None Detected

5-546-4 / 21024221-068 SR & JC, Sheetrock

White Non-Fibrous

Heterogeneous

8% Cellulose 92% Other None Detected

Analyst:

Analysis Date: 5/22/2021 Date: 5/24/2021

Approved Signatory:

1551 Oakbridge Dr. Suite B, Powhatan, VA 23139 | 804.897.1177 | Fax: 804.897.0070 | www.SanAir.com | IAQ@SanAir.com

19149.02Project Number:

P.O. Number:

Project Name: EHRM Update

5/13/2021Collected Date:

5/18/2021 10:05:00 AMReceived Date:

5/24/2021 9:58:38 AM

21024221 SanAir ID Number

FINAL REPORT

Landmark EnvironmentalName:

Address: 2042 West 98th Street

Bloomington, MN 55431

Stereoscopic Components

SanAir ID / Description Appearance % Fibrous % Non-fibrous Asbestos Fibers

5-546-4 / 21024221-068 SR & JC, Joint Compound

Beige Non-Fibrous

Heterogeneous

98% Other 2% Chrysotile

1-314-1 / 21024221-069 Plaster

Brown Non-Fibrous

Heterogeneous

100% Other None Detected

1-314-2 / 21024221-070 Baseboard Adh

Brown Non-Fibrous

Heterogeneous

100% Other None Detected

1-314-3 / 21024221-071 Baseboard Adh

Tan Non-Fibrous

Heterogeneous

100% Other None Detected

1-314-4 / 21024221-072 Sheetrock & Joint Compound, Sheetrock

White Non-Fibrous

Heterogeneous

8% Cellulose 92% Other None Detected

1-314-4 / 21024221-072 Sheetrock & Joint Compound, Joint Compound

Beige Non-Fibrous

Heterogeneous

98% Other 2% Chrysotile

1-314-5 / 21024221-073 Wood Grain Floor Sheet

Brown Non-Fibrous

Heterogeneous

100% Other None Detected

1-314-6 / 21024221-074 Firestop Putty

Red Non-Fibrous

Heterogeneous

100% Other None Detected

1-314-7 / 21024221-075 2x4 W/ Holes

White Fibrous

Heterogeneous

65% Cellulose 25% Glass

5% Min. Wool

5% Other None Detected

5-Nurse-1 / 21024221-076 Duct Sealant

Gray Non-Fibrous

Heterogeneous

100% Other None Detected

Analyst:

Analysis Date: 5/22/2021 Date: 5/24/2021

Approved Signatory:

1551 Oakbridge Dr. Suite B, Powhatan, VA 23139 | 804.897.1177 | Fax: 804.897.0070 | www.SanAir.com | IAQ@SanAir.com

19149.02Project Number:

P.O. Number:

Project Name: EHRM Update

5/13/2021Collected Date:

5/18/2021 10:05:00 AMReceived Date:

5/24/2021 9:58:38 AM

21024221 SanAir ID Number

FINAL REPORT

Landmark EnvironmentalName:

Address: 2042 West 98th Street

Bloomington, MN 55431

Stereoscopic Components

SanAir ID / Description Appearance % Fibrous % Non-fibrous Asbestos Fibers

5-Nurse-2 / 21024221-077 2x2 CT W/ F&H

White Fibrous

Heterogeneous

65% Cellulose 25% Glass

5% Min. Wool

5% Other None Detected

5-Nurse-4 / 21024221-078 Floor Sheeting

Tan Non-Fibrous

Heterogeneous

100% Other None Detected

5-B66A-1 / 21024221-079 Firestop Putty

Gray Non-Fibrous

Heterogeneous

100% Other None Detected

5-B66A-2 / 21024221-080 Wall Adh

Tan Non-Fibrous

Heterogeneous

100% Other None Detected

5-B66A-3 / 21024221-081 Wind Caulk

Gray Non-Fibrous

Heterogeneous

100% Other None Detected

1-02-1 / 21024221-082 12x12 FT

Tan Non-Fibrous

Heterogeneous

100% Other None Detected

1-02-2 / 21024221-083 FT Mastic

Yellow Non-Fibrous

Heterogeneous

100% Other None Detected

1-02-3 / 21024221-084 Sheetrock & Joint Compound, Sheetrock

White Non-Fibrous

Heterogeneous

8% Cellulose 92% Other None Detected

1-02-3 / 21024221-084 Sheetrock & Joint Compound, Joint Compound

Beige Non-Fibrous

Heterogeneous

98% Other 2% Chrysotile

1-02-4 / 21024221-085 2x2 CT W/ Holes

White Fibrous

Heterogeneous

65% Cellulose 20% Glass

10% Min. Wool

5% Other None Detected

Analyst:

Analysis Date: 5/22/2021 Date: 5/24/2021

Approved Signatory:

1551 Oakbridge Dr. Suite B, Powhatan, VA 23139 | 804.897.1177 | Fax: 804.897.0070 | www.SanAir.com | IAQ@SanAir.com

19149.02Project Number:

P.O. Number:

Project Name: EHRM Update

5/13/2021Collected Date:

5/18/2021 10:05:00 AMReceived Date:

5/24/2021 9:58:38 AM

21024221 SanAir ID Number

FINAL REPORT

Landmark EnvironmentalName:

Address: 2042 West 98th Street

Bloomington, MN 55431

Stereoscopic Components

SanAir ID / Description Appearance % Fibrous % Non-fibrous Asbestos Fibers

1-02-5 / 21024221-086 Baseboard

Gray Non-Fibrous

Heterogeneous

100% Other None Detected

1-02-6 / 21024221-087 BB Adh

Yellow Non-Fibrous

Heterogeneous

100% Other None Detected

1-02-7 / 21024221-088 Firestop Putty

Red Non-Fibrous

Heterogeneous

100% Other None Detected

1-037-1 / 21024221-089 Plaster

Brown Non-Fibrous

Heterogeneous

100% Other None Detected

1-037-2 / 21024221-090 F.S. Putty

Brown Non-Fibrous

Heterogeneous

100% Other None Detected

1-037-3 / 21024221-091 F.S. Putty

Red Non-Fibrous

Heterogeneous

100% Other None Detected

5-149-1 / 21024221-092 Tall Baseboard

Brown Non-Fibrous

Heterogeneous

100% Other None Detected

5-149-2 / 21024221-093 BB Adh

Yellow Non-Fibrous

Heterogeneous

100% Other None Detected

5-149-3 / 21024221-094 Plaster

White Non-Fibrous

Heterogeneous

100% Other None Detected

5-149-4 / 21024221-095 Sheetrock & Joint Comp, Sheetrock

White Non-Fibrous

Heterogeneous

8% Cellulose 92% Other None Detected

Analyst:

Analysis Date: 5/22/2021 Date: 5/24/2021

Approved Signatory:

1551 Oakbridge Dr. Suite B, Powhatan, VA 23139 | 804.897.1177 | Fax: 804.897.0070 | www.SanAir.com | IAQ@SanAir.com

19149.02Project Number:

P.O. Number:

Project Name: EHRM Update

5/13/2021Collected Date:

5/18/2021 10:05:00 AMReceived Date:

5/24/2021 9:58:38 AM

21024221 SanAir ID Number

FINAL REPORT

Landmark EnvironmentalName:

Address: 2042 West 98th Street

Bloomington, MN 55431

Stereoscopic Components

SanAir ID / Description Appearance % Fibrous % Non-fibrous Asbestos Fibers

5-149-4 / 21024221-095 Sheetrock & Joint Comp, Joint Compound

Beige Non-Fibrous

Heterogeneous

98% Other 2% Chrysotile

5-149-5 / 21024221-096 2x2 CT W/ F&H

White Fibrous

Heterogeneous

65% Cellulose 20% Glass

12% Min. Wool

3% Other None Detected

5-149-6 / 21024221-097 Floor Tile Under Carpet

Gray Fibrous

Heterogeneous

97% Other 3% Chrysotile

5-149-7 / 21024221-098 FT Mastic

Black Non-Fibrous

Heterogeneous

96% Other 4% Chrysotile

5-178-1 / 21024221-099 SR & JC, Sheetrock

White Non-Fibrous

Heterogeneous

8% Cellulose 92% Other None Detected

5-178-1 / 21024221-099 SR & JC, Joint Compound

Beige Non-Fibrous

Heterogeneous

98% Other 2% Chrysotile

5-178-2 / 21024221-100 Plaster, Plaster

Brown Non-Fibrous

Heterogeneous

100% Other None Detected

5-178-2 / 21024221-100 Plaster, Skim Coat

White Non-Fibrous

Heterogeneous

100% Other None Detected

5-178-3 / 21024221-101 2x4 CT W/ FDH

White Fibrous

Heterogeneous

65% Cellulose 20% Glass

10% Min. Wool

5% Other None Detected

5-178-4 / 21024221-102 Baseboard

Black Non-Fibrous

Heterogeneous

100% Other None Detected

Analyst:

Analysis Date: 5/22/2021 Date: 5/24/2021

Approved Signatory:

1551 Oakbridge Dr. Suite B, Powhatan, VA 23139 | 804.897.1177 | Fax: 804.897.0070 | www.SanAir.com | IAQ@SanAir.com

19149.02Project Number:

P.O. Number:

Project Name: EHRM Update

5/13/2021Collected Date:

5/18/2021 10:05:00 AMReceived Date:

5/24/2021 9:58:38 AM

21024221 SanAir ID Number

FINAL REPORT

Landmark EnvironmentalName:

Address: 2042 West 98th Street

Bloomington, MN 55431

Stereoscopic Components

SanAir ID / Description Appearance % Fibrous % Non-fibrous Asbestos Fibers

5-178-5 / 21024221-103 BB Adhesive

Yellow Non-Fibrous

Heterogeneous

100% Other None Detected

5-178-6 / 21024221-104 12x12 FT

Gray Non-Fibrous

Heterogeneous

97% Other 3% Chrysotile

5-178-7 / 21024221-105 FT Mastic

Black Non-Fibrous

Heterogeneous

96% Other 4% Chrysotile

5-178-8 / 21024221-106 Pedestal Adhesive

Black Non-Fibrous

Heterogeneous

100% Other None Detected

5-178-9 / 21024221-107 Pedestal Adhesive

Tan Non-Fibrous

Heterogeneous

100% Other None Detected

5-178-10 / 21024221-108 12x12 FT

Brown Non-Fibrous

Heterogeneous

100% Other None Detected

5-178-11 / 21024221-109 FT Mastic

Black Non-Fibrous

Heterogeneous

97% Other 3% Chrysotile

5-178-12 / 21024221-110 Bottom Layer FT

Beige Non-Fibrous

Heterogeneous

97% Other 3% Chrysotile

5-178-13 / 21024221-111 FT Mastic

Black Non-Fibrous

Heterogeneous

97% Other 3% Chrysotile

5-178-14 / 21024221-112 Tar On Ext. Wall

Black Non-Fibrous

Heterogeneous

100% Other None Detected

Analyst:

Analysis Date: 5/22/2021 Date: 5/24/2021

Approved Signatory:

1551 Oakbridge Dr. Suite B, Powhatan, VA 23139 | 804.897.1177 | Fax: 804.897.0070 | www.SanAir.com |…