This document outlines a solicitation for infrastructure upgrades at the Sioux Falls VA Medical Center. The project involves construction and commissioning work to support the nationally mandated Electronic Health Record Modernization initiative. Key aspects include building a new server room on the hospital roof between existing structures, upgrading infrastructure throughout multiple departments in a phased approach, and coordinating structural/civil work at the beginning of the project. The solicitation will be issued as a Request for Proposal to SDVOSB concerns only, with an estimated value between $20-50 million under NAICS code 236220. The performance period is approximately 450 calendar days from notice to proceed. Questions must be submitted in writing by a specified deadline.
View the file
Other files for this federal contract opportunity
Show all 44
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Sioux Falls VAHCS, Sioux Falls, SD VA Project 438-20-910
EHRM Infrastructure Upgrades 04-04-2022
2501 West 22nd St. Bid Documents
Sioux Falls, SD 57105
27 11 19 - 1
SECTION 27 11 19
COMMUNICATIONS TERMINATION BLOCKS AND PATCH PANELS
PART 1 - GENERAL
1.1 DESCRIPTION:
A. This section specifies cable termination and management equipment to be mounted in information technology (IT) equipment cabinets and racks.
1.2 SUMMARY
A. Section Includes:
1. Copper UTP Patch Panels.
2. Fiber Optic Distribution Cabinets.
3. Fiber Optic Distribution Cassettes.
4. Fiber Optic Splice Cassettes.
5. Horizontal Cable Managers.
6. Blanking Panels.
1.3 REFERENCES
A. VA Infrastructure Standard for Telecommunications Spaces.
1.4 RELATED WORK:
A. Server cabinets and network racks: Section 27 11 16, COMMUNICATIONS
CABINETS, RACKS, FRAMES, AND ENCLOSURES.
B. Cable management equipment: Section 27 11 23, COMMUNICATIONS CABLE
MANAGEMENT AND LADDER RACK.
C. Labeling and identification requirements: Section 27 05 53, IDENTIFICATION FOR COMMUNICATIONS SYSTEMS.
D. Copper UTP cabling: Section 27 13 13, COMMUNICATIONS COPPER BACKBONE
CABLING.
E. Copper UTP cabling termination: Section 27 13 13.13, COMMUNICATIONS
COPPER CABLE SPLICING AND TERMINATIONS.
F. Fiber optic cabling: Section 27 13 23, COMMUNICATIONS OPTICAL FIBER
BACKBONE CABLING.
G. Fiber optic cabling termination: Section 27 13 23.13, COMMUNICATIONS
OPTICAL FIBER SPLICING AND TERMINATIONS.
1.5 SUBMITTALS:
A. Submit in accordance with Section 27 05 00, COMMON WORK RESULTS FOR
COMMUNICATIONS SYSTEMS.
27 11 19 - 2
PART 2 - PRODUCTS
2.1 COPPER (UTP) PATCH PANELS.
A. Form Factor. 1U, 19” rack-mountable. Default form factor for patch panels shall be angled to extend not less than 4” (104mm) forward from the mounting rail.
B. Capacity. 48 copper 8P8C ports in groupings of 6.
C. Interface. Copper (UTP) patch panels shall accept pre-terminated single
8P8C keystone jacks and 6-jack cassettes.
D. Accessories. Provide each patch panel installation with the following accessories.
1. Angled panel cover. Specify angled panel covers at the top and bottom of each stack of angled patch panels. Covers shall mount to the same RU rail positions as the top and bottom patch panels.
2. Rear cable manager tray. Specify one rear cable manager tray per patch panel. Trays shall mount to the same RU rail positions as the patch panel.
2.2 FIBER OPTIC DISTRIBUTION CABINETS.
A. Form Factor. 1U, 19” rack-mountable, angled to extend not less than 4”
(104mm) forward from the mounting rail.
B. Capacity. 144 fibers in a variety of distribution and/or splice cassettes.
C. Door. Cabinets shall be supplied with a locking front cover.
D. Accessories. Provide each distribution cabinet with the following accessories.
1. Rear cable manager. Specify one rear cable manager with fiber storage rings per distribution cabinet. Trays shall mount to the same RU rail positions as the distribution cabinet.
2. 0RU patch cord managers. Specify one pair of patch cord managers per distribution cabinet. Managers shall mount to the same RU rail positions as the distribution cabinet and rear cable manager.
2.3 FIBER OPTIC DISTRIBUTION CASSETTES.
A. Fiber optic distribution cassettes are used in structured cabling in the computer room to connect Main Distribution Areas (MDAs), Horizontal
Distribution Areas (HDAs), and Equipment Distributors (EDs) where pre-terminated cable is used.
27 11 19 - 3
1. Form Factor. Designed to install in rack-mounted fiber optic distribution cabinet.
2. Connections. The rear connection shall accept 12-strand multi-fiber push-on (MPO) connectors or 24-strand multi-fiber push-on (MPO) connectors. Adapters on the front of the cassette shall accept 6 or
12 duplex Lucent connector (LC) fiber pairs.
3. Polarity. Provide type universal polarity cassettes.
2.4 FIBER OPTIC SPLICE CASSETTES.
A. Fiber optic splice cassettes are used in backbone structured cabling connecting the Entrance Rooms to the Main Distribution Areas (MDAs) in the computer room, and the MDAs to Telecommunications Rooms (TRs) where field-terminated (fusion spliced) cable is used.
1. Form Factor. Designed to install in rack-mounted fiber optic distribution cabinet.
2. Connections. Adapters on the front of the cassette shall accept 6 or
12 duplex Lucent connector (LC) fiber pairs.
3. Design. Splice cassette modules shall be self-contained to integrate fiber adapter bulkhead and splice holders. No additional splice trays shall be necessary. Each module shall provide 24 fiber splice connections.
4. Fiber Type. Provide multimode OM4 and single-mode OS1 and OS2 splice cassettes as required by the quantity of each type of fiber installed.
2.5 HORIZONTAL CABLE MANAGERS.
A. Form Factor. 1U or 2U per rack/cabinet elevations, 19” rack-mountable.
B. Door. Horizontal cable managers shall have a double-hinged front cover to protect installed cables.
2.6 BLANKING PANELS.
A. Form Factor. 1U, 2U,or 3U per rack/cabinet elevations, 19” rack-mountable, angled to extend 4” (104mm) forward from the mounting rail.
B. Quantity. Provide blanking panels to fill 75% of all RUs in all server cabinets and network cabinets.
PART 3 - EXECUTION (NOT USED)
- - - E N D - - -