271126 Communications Rack Mounted Power Protection and Power Strips.pdf
PDF 48 KB Posted
- Attached to
- EHRM Infrastructure Upgrades Construction Sioux Falls VAMC Federal contract opportunity
- Solicitation number
- 36C77622R0049
About this file
This document includes specifications for communications rack mounted power protection and power strips required for an Electronic Health Record Modernization infrastructure upgrade project at the Sioux Falls VA Medical Center. Key requirements include a 5kW three-phase 208V rack-mounted uninterruptible power supply with L21-20 connections and a 10-minute battery capacity. Also required are metered and monitored three-phase 208V vertical rack power distribution units with IEC60320 outlets and a 5.7kW power capacity. Specifications cover enclosure types, mounting, metering, monitoring and installation details.
The related federal contract opportunity is a Request for Proposal to provide construction and commissioning services for the infrastructure upgrade project. The project scope includes building a new server room and upgrades throughout the hospital. The solicitation is set aside for Service-Disabled Veteran-Owned Small Businesses. The period of performance is approximately 450 calendar days and the magnitude of construction is estimated between $20-50 million. The issuing office is the VA Technology Acquisition Center Austin and all questions must be submitted in writing by the specified date.
View the file
Other files for this federal contract opportunity
Show all 44
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Sioux Falls VAHCS, Sioux Falls, SD VA Project 438-20-910
EHRM Infrastructure Upgrades 04-04-2022
2501 West 22nd St. Bid Documents
Sioux Falls, SD 57105
26 33 53 - 1
SECTION 27 11 26
COMMUNICATIONS RACK MOUNTED POWER PROTECTION AND POWER STRIPS
PART 1 - GENERAL
1.1 DESCRIPTION
A. This section specifies power distribution equipment and interconnections supporting equipment deployed in telecommunications spaces (entrance rooms, computer rooms, and telecommunications rooms).
1.2 SUMMARY
A. Section Includes:
2. Rack-Mounted Uninterruptible Power Supply (UPS) Units.
3. Rack Power Distribution Units (rPDUs).
1.3 REFERENCES
A. VA Infrastructure Standard for Telecommunications Spaces.
1.4 RELATED WORK
A. General electrical requirements that are common to more than one section in Division 27: Section 27 05 11, REQUIREMENTS FOR
COMMUNICATIONS INSTALLATIONS.
B. IT equipment enclosures: Section 27 11 16, COMMUNICATIONS
CABINETS, RACKS, FRAMES, AND ENCLOSURES
1.5 SUBMITTALS
A. Submit in accordance with Section 27 05 00, COMMON WORK RESULTS
FOR COMMUNICATIONS SYSTEMS.
B. For each type of product:
1. Include construction details, material descriptions, dimensions of individual components and profiles, and finishes for rack-mounted power protection and power strips.
2. Include rated capacities, operating characteristics, electrical characteristics, and furnished specialties and accessories.
PART 2 - PRODUCTS
2.2 RACK-MOUNTED UNINTERRUPTIBLE POWER SUPPLY (UPS) UNITS
A. Provide components from a single manufacturer.
B. Description: 5kW three-phase 208V 20A rack-mounted UPS with L21-
20 input and output connections.
C. Input Connection: Single input NEMA L21-20P plug (twistlock
26 33 53 - 2 three-phase five wire L+L+L+N+G). Power cord minimum 3’ (1m) length.(twistlock three-phase five wire L+L+L+N+G). Power cord
10’ (3m) length. (twistlock three-phase five wire L+L+L+N+G).
Power cord 10’ (3m) length. (twistlock three-phase five wire
L+L+L+N+G). Power cord 10’ (3m) length. (twistlock three-phase five wire L+L+L+N+G). Power cord 10’ (3m) length (twistlock three-phase five wire L+L+L+N+G). Power cord 10’ (3m) length.
D. Output Connection: Single output NEMA L21-20R receptacle.
E. Power Capacity: 5kW
F. Enclosure: Fully self-contained.
G. Mounting: 19” rack mount.
H. Battery Capacity: Ten minutes at 70% load (3.5kW).
I. Cooling: Fan-cooled, front air entry, rear exhaust.
2.3 RACK POWER DISTRIBUTION UNITS (RACK PDUS)
A. Provide components from a single manufacturer.
B. Description: Metered/monitored three-phase 208V 20A vertical
Rack Power Distribution Unit (Rack PDU), 5.7kW, with IEC60320 outlets.
C. Input Connection: Single input NEMA L21-20P plug (twistlock three-phase five wire L+L+L+N+G). Power cord 10’ (3m) length.
D. Output Connections.
1. For Computer Room applications: Minimum 30 each C13 and 6 each C19. Outlets grouped in phase-grouping banks (A-B, B-C, C-A) or alternating to assist with phase balancing. Outlets labelled with associated phase-grouping bank.
2. For Telecommunications Room (TR) and entrance room applications: Minimum 30 each C13, 6 each C19, 2 each L5-20.
Outlets grouped in phase-grouping banks (A-B, B-C, C-A) or alternating to assist with phase balancing. Outlets labelled with associated phase-grouping bank.
E. Power Capacity: 5.7kW rated.
F. Enclosure: Fully self-contained.
G. Mounting: Toolless mounting, orientation vertical at rear of enclosure, taking up zero RU spaces. Up to two Rack PDUs must be able to be installed on each side for High Density (10kW) enclosures.
26 33 53 - 3
H. Mounting Hardware: As required to connect to the specific enclosure make/model.
I. Number of RPDUs: 2 for Standard Density (up to 5kW) enclosures, 4 for High Density (10kW) enclosures.
J. Metering: Local display provides input line currents (Amperage).
Additional metering items (voltage, power, energy, power factor) across the unit or at individual outlets, is acceptable.
K. Monitoring: RJ45 Ethernet port allows connection to an external monitoring system. Supports SNMP v3 with SSL Encryption.
PART 3 - EXECUTION
3.1 INSTALLATION
A. DEFINITION: Sides (left/right) of the enclosure are as when viewed from the rear (hot aisle) of the enclosure for the purposes of this section.
B. Rack-Mounted UPS Units.
1. Install rack-mounted UPS units only in enclosures that require them. Rack-mounted UPS units shall not be installed downstream of another UPS system (cascaded).
2. Where non-redundant UPS power is required to support the enclosure, install the rack-mounted UPS unit in the A side power distribution.
3. Install rack-mounted UPS units beginning in RU position 1, at the bottom of the 19” rack, with the exhaust ports facing the rear of the enclosure. No other equipment should be installed below the rack-mounted UPS units.
4. Connect the rack-mounted UPS unit power cord to the appropriate (A side) power receptacle on the upstream Zone
PDU.
C. Rack PDUs.
1. Install Rack PDUs in matched A/B pairs only.
2. Install A side Rack PDUs on the left side of the enclosure and
B side Rack PDUs on the right side of the enclosure, interior to the rear enclosure door.
3. Connect the Rack PDU power cord to the upstream rack-mounted
UPS unit (where present) or the appropriate power receptacle on the upstream Zone PDU.
26 33 53 - 4
- - - E N D - - -