This solicitation package describes a construction project and opportunity. The Sioux Falls VA Medical Center is upgrading its infrastructure for an Electronic Health Record Modernization project. Construction and commissioning will be in accordance with final drawings and specifications to build a new server room and make other upgrades throughout hospital departments and service areas. The majority of work will likely need to be done on off hours and weekends due to limited onsite storage. The solicitation will be issued as a Request for Proposal conducted according to FAR Parts 15, 19, and 36 and evaluated per the procedures in the solicitation. This is advertised as a total Service-Disabled Veteran-Owned Small Business set-aside opportunity. The NAICS code is 236220 with a size standard of $39.5 million. The period of performance is approximately 450 calendar days from notice to proceed. The magnitude of construction is estimated between $20-50 million. All questions must be submitted in writing by the stated deadline.
View the file
Other files for this federal contract opportunity
Show all 44
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Sioux Falls VAHCS, Sioux Falls, SD VA Project 438-20-910
EHRM Infrastructure Upgrades 04-04-2022
2501 West 22nd St. Bid Documents
Sioux Falls, SD 57105
27 13 13.13 - 1
SECTION 27 13 13.13
COMMUNICATIONS COPPER CABLE SPLICING AND TERMINATIONS
PART 1 - GENERAL
1.1 DESCRIPTION:
A. This section specifies requirements for terminations of copper (UTP) cabling.
1.2 SUMMARY
A. Section Includes:
1. Termination Requirements.
2. Splicing.
1.3 REFERENCES
A. VA Infrastructure Standard for Telecommunications Spaces.
1.4 RELATED WORK:
A. Termination equipment: Section 27 11 19, COMMUNICATIONS TERMINATION
BLOCKS AND PATCH PANELS.
B. Copper (UTP) cabling requirements: Section 27 13 13, COMMUNICATIONS
COPPER BACKBONE CABLING.
C. Copper (UTP) cabling requirements: Section 27 15 13, COMMUNICATIONS
COPPER HORIZONTAL CABLING.
1.5 SUBMITTALS:
A. Submit in accordance with Section 27 05 00, COMMON WORK RESULTS FOR
COMMUNICATIONS SYSTEMS.
PART 2 - PRODUCTS (NOT USED)
PART 3 - EXECUTION
3.1 TERMINATION REQUIREMENTS.
A. Terminate copper (UTP) cabling used for data communications per TIA
568B.
B. Connections shall be made to equipment certified to performance category 6a.
C. Pre-terminated connections are required for computer room structured cabling applications. Field termination for non-computer room applications is acceptable.
3.2 SPLICING.
A. Splicing of copper (UTP) cabling is prohibited.
- - - E N D - - -