This document contains specifications for a federal construction solicitation and the related opportunity notice. The solicitation is for the construction and commissioning of infrastructure upgrades needed for an Electronic Health Record Modernization project at the Sioux Falls VA Medical Center. Key requirements include building a new server room, structural and civil work, and coordination across hospital departments and areas. The solicitation will be issued as a Request for Proposal conducted according to FAR Parts 15, 19, and 36. The opportunity is set aside solely for Service-Disabled Veteran-Owned Small Businesses. The period of performance is approximately 450 calendar days from notice to proceed. The estimated value is between $20-50 million. Questions must be submitted in writing by the specified deadline to the issuing office.
View the file
Other files for this federal contract opportunity
Show all 44
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Sioux Falls VAHCS, Sioux Falls, SD VA Project 438-20-910
EHRM Infrastructure Upgrades 04-04-2022
2501 West 22nd St. Bid Documents
Sioux Falls, SD 57105
27 15 13 - 1
SECTION 27 15 13
COMMUNICATIONS COPPER HORIZONTAL CABLING
PART 1 - GENERAL
1.1 DESCRIPTION:
A. This section specifies requirements for telecommunications copper (UTP) horizontal distribution cabling outside of the computer room. For copper (UTP) horizontal cabling in structured cabling systems in the computer room, see Section 27 13 13 Communications Copper Backbone
Cabling.
1.2 SUMMARY
A. Section Includes:
1. Copper (UTP) Horizontal Cables.
1.3 REFERENCES
A. VA Infrastructure Standard for Telecommunications Spaces.
1.4 RELATED WORK:
A. Computer room structured cabling: Section 27 10 00, STRUCTURED CABLING.
B. Termination equipment: Section 27 11 19, COMMUNICATIONS TERMINATION
BLOCKS AND PATCH PANELS.
C. Cable labeling requirements: Section 27 05 53, IDENTIFICATION FOR
COMMUNICATIONS SYSTEMS.
1.5 SUBMITTALS:
A. Submit in accordance with Section 27 05 00, COMMON WORK RESULTS FOR
COMMUNICATIONS SYSTEMS.
PART 2 - PRODUCTS
2.1 COPPER (UTP) HORIZONTAL CABLES.
A. Copper (UTP) horizontal cables connect the Telecommunications Room (TR) to each end-user Work Area Outlet (WAO) (horizontal distribution).
1. Performance Category. Copper (UTP) horizontal cables shall meet the
Category 6A performance requirements. Category 6A connectors are required.
2. Performance Specifications. Meets or exceeds TIA-EIA-568-C.2-10 and
TSB-155.
3. Limited Power (LP) Certification. UL Listed as x-LP (0.5A).
4. Termination. Field terminated TIA 568B.
5. Testing. Following installation, each cable shall be field certified to meet performance category requirements per TIA 568-C.2.
Sioux Falls VAHCS, Sioux Falls, SD VA Project 438-20-910
EHRM Infrastructure Upgrades 04-04-2022
2501 West 22nd St. Bid Documents
Sioux Falls, SD 57105
27 15 13 - 2
6. Conductor Size. 22-24AWG.
7. Jacket Rating. Communications Multipurpose Cable, Plenum (CMP) shall be specified if any portion of the cable passes through an NEC-defined plenum. Communications Multipurpose Cable, Riser (CMR) shall be specified for all other applications. CMP may be used as a substitute for CMR.
8. Construction. Copper Clad Aluminum (CCA) cable is not permitted.
9. Length. The maximum distance for UTP horizontal cables is limited to
295 feet.
PART 3 - EXECUTION
3.1 IMPLEMENTATION
A. All cabling and equipment shall be labeled per the requirements of the
VA Infrastructure Standard for Telecommunications Spaces.
B. Interior to the TR, install horizontal copper (UTP) structured cabling in overhead cable tray.