271313 Communications Copper Backbone Cabling.pdf

PDF 29 KB Posted

Attached to
EHRM Infrastructure Upgrades Construction Sioux Falls VAMC Federal contract opportunity
Solicitation number
36C77622R0049
Issued by
Department of Veterans Affairs Technology Acquisition Center Austin

About this file

This document includes specifications for communications copper backbone cabling and a related federal contract opportunity for EHRM infrastructure upgrades at the Sioux Falls VA Medical Center. The specifications call for Category 6A copper backbone and horizontal cabling to connect main distribution areas, horizontal distribution areas, and server cabinets. Cables must meet TIA-EIA-568-C.2-10 standards, be UL listed, and factory tested and certified. Plenum and riser jackets are specified depending on routing. The federal contract opportunity is a service-disabled veteran-owned small business set-aside solicited as a request for proposal to be awarded based on the procedures in the solicitation. The work includes construction and commissioning of infrastructure for a nationwide electronic health records modernization project at the medical center, touching several departments. A new server room is to be built, and material storage must be planned off-site due to limited on-site capacity. The period of performance is approximately 450 calendar days and the magnitude of construction is estimated between $20-50 million.

View the file

Other files for this federal contract opportunity

Other files attached to EHRM Infrastructure Upgrades Construction Sioux Falls VAMC, newest first.
File Type Posted
36C77622R0049 0006.pdf PDF
Technical Question Tracking Sheet Infra Upgrades Final.pdf PDF
36C77622R0049 0005.pdf PDF
271116 Communications Cabinets Racks Frames and Enclosures.pdf PDF
36C77622R0049 0004.pdf PDF
271619 Communications Patch Cords Station Cords and Cross Connect Wire.pdf PDF
2020 Elec Combined One Lines.pdf PDF
270536 Cable Trays for Communications Systems.pdf PDF
271119 Communications Termination Blocks and Patch Panels.pdf PDF
271313.13 Communications Copper Cable Splicing and Terminations.pdf PDF
270526 Grounding and Bonding for Communications Systems.pdf PDF
271513.13 Communications Optical Fiber Cable Splicing and Terminations.pdf PDF
271000 Structured Cabling.pdf PDF
271323 Communications Optical Fiber Backbone Cabling.pdf PDF
270533 Conduits and Backboxes for Communications Systems.pdf PDF
271126 Communications Rack Mounted Power Protection and Power Strips.pdf PDF
36C77622R0049 0003.pdf PDF
OIT InfrastrucStdTelecomSpaces 3.1.pdf PDF
SF Site Utility Dwg.pdf PDF
270553 Identification for Communications Systems.pdf PDF
271513 Communications Copper Horizontal Cabling.pdf PDF
Technical Question Tracking Sheet - Infra Upgrades - Final.pdf PDF
EHRM Site Visit Attendance Sheet.pdf PDF
36C77622R0049 0002.pdf PDF
Technical Question Tracking Sheet - Infra Upgrades.pdf PDF
Building 1C Sheet 6 - Pipe Tunnel.pdf PDF
Specification - Vol 2 Revision 2.pdf PDF
36C77622R0049 0001.pdf PDF
Dwgs Bid Documents-part 7-1 REV.pdf PDF
VHA Suppl. Contract Rqmnts for Combatting COVID-19 Updated 12-14-2021.pdf PDF
Supplement to General Requirements Spec 01 00 00.pdf PDF
36C77622R0049.pdf PDF
Dwgs Bid Documents-part 6-1 REV.pdf PDF
Dwgs Bid Documents-part 3-1 REV.pdf PDF
Asbestos - Appendix-A part 1.pdf PDF
Specifications Revision 2.pdf PDF
Dwgs Bid Documents-part 1-1 REV.pdf PDF
Asbestos - Appendix-A part 3.pdf PDF
Dwgs Bid Documents-part 4-1 REV.pdf PDF
Dwgs Bid Documents-part 5-1 REV.pdf PDF
Dwgs Bid Documents-part 2-1 REV.pdf PDF
Asbestos - Appendix-A part 4.pdf PDF
Asbestos - Appendix-A part 2.pdf PDF
Construction Wage Rates - Minnehaha - 2-25-22.pdf PDF
Show all 44

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Sioux Falls VAHCS, Sioux Falls, SD VA Project 438-20-910

EHRM Infrastructure Upgrades 04-04-2022

2501 West 22nd St. Bid Documents

Sioux Falls, SD 57105

27 13 13 - 1

SECTION 27 13 13

COMMUNICATIONS COPPER BACKBONE CABLING

PART 1 - GENERAL

1.1 DESCRIPTION:

A. This section specifies requirements for telecommunications copper (UTP) backbone and horizontal cabling in structured cabling systems in computer rooms.

1.2 SUMMARY

A. Section Includes:

1. Copper (UTP) Backbone Cables.

1.3 REFERENCES

A. VA Infrastructure Standard for Telecommunications Spaces.

1.4 RELATED WORK:

A. Computer room structured cabling: Section 27 10 00, STRUCTURED CABLING.

B. Termination equipment: Section 27 11 19, COMMUNICATIONS TERMINATION

BLOCKS AND PATCH PANELS.

C. Cable labeling requirements: Section 27 05 53, IDENTIFICATION FOR

COMMUNICATIONS SYSTEMS.

1.5 SUBMITTALS:

A. Submit in accordance with Section 27 05 00, COMMON WORK RESULTS FOR

COMMUNICATIONS SYSTEMS.

PART 2 - PRODUCTS

2.1 COPPER (UTP) BACKBONE CABLES.

A. Copper (UTP) backbone and horizontal cables are used in computer room structured cabling to connect Main Distribution Areas (MDAs), Horizontal Distribution Areas (HDAs), and server cabinet Equipment

Distributors (EDs).

1. Performance Category. Copper (UTP) backbone cables shall meet the

Category 6A performance requirements. Category 6A connectors are required.

2. Performance Specifications. Meets or exceeds TIA-EIA-568-C.2-10 and

TSB-155.

3. Limited Power (LP) Certification. UL Listed as x-LP (0.5A).

4. Termination. Factory pre-terminated TIA 568B.

Sioux Falls VAHCS, Sioux Falls, SD VA Project 438-20-910

EHRM Infrastructure Upgrades 04-04-2022

2501 West 22nd St. Bid Documents

Sioux Falls, SD 57105

27 13 13 - 2

5. Testing. Factory certified to meet performance category requirements per TIA 568-C.2.

6. Conductor Size. 22-24AWG.

7. Jacket Rating. Communications Multipurpose Cable, Plenum (CMP) shall be specified if any portion of the cable passes through an NEC-defined plenum. Communications Multipurpose Cable, Riser (CMR) shall be specified for all other applications. CMP may be used as a substitute for CMR.

8. Bundling and Construction. Copper (UTP) backbone cables shall be provided in 6-cable bundles with individual 8P8C media interface connectors (RJ-45 ‘jacks’) or 6-jack cassettes designed to fit in copper (UTP) patch panels.

9. Color. A-side 8P8C media interface connectors (RJ-45) shall be blue.

B-side 8P8C connectors shall be yellow.

10. Length. Backbone cabling used shall be procured to the specific length required by the design (horizontal and vertical paths) with no more than 2 feet of excess length.

PART 3 - EXECUTION

3.1 IMPLEMENTATION.

A. All cabling and equipment shall be labeled per the requirements of the

VA Infrastructure Standard for Telecommunications Spaces.

B. Install first level backbone and horizontal structured cabling in the computer room in cable tray and fiber raceway systems following diverse path routing.

- - - E N D - - -