1 J.3b-N254 Structural Calcs-HVAC Anchorage.pdf
PDF 3 MB Posted
- Attached to
- Western Regional Multiple Award Construction Contracts (WRMACC) Federal contract opportunity
- Solicitation number
- 80AFRC25R0001
About this file
This document is a detailed structural calculation report for HVAC support and anchorage at NASA Ames Research Center, prepared by AECOM. The calculation set comprehensively evaluates the structural requirements for installing new HVAC equipment, including two AC units and two exhaust fans, on an existing roof structure. The analysis includes design calculations for wood skid members, equipment and duct support design, anchorage between equipment isolators and sleepers, and an assessment of the existing roof structure's capacity to support the new loads.
The calculations methodically examine multiple aspects of the installation, including dead load and seismic/wind force calculations, design capacity ratios, deflection analysis, and column load evaluations. Key findings indicate that the existing roof beams, columns, and structural elements can adequately support the new HVAC equipment, with the largest design capacity ratio being 0.454 and all existing structural components meeting design requirements. The report uses detailed engineering methodologies, referencing standards like ASCE 7, IEBC, and NDS, and employs computational tools like ETABS for structural modeling and analysis.
View the file
Other files for this federal contract opportunity
Show all 50
Western Regional Multiple Award Construction Contracts (WRMACC) has more files on GovTribe.
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
NASA N254 - HVAC Support
S T R U C T U R A L C A L C U L A T I O NS
Final Submission
July 1, 2024
Prepared by
AECOM
300 Lakeside Dr.
Suite 400 Oakland, CA 94612
AECOM Project No. 60667208
NARC Job No. K21007
Prepared for
NASA Ames Research Center.
Mountain View, CA 94025
© AECOM Restricted Calculation Cover Page Template (Q2[DCS]-351-FM5) Revision 2 December 6, 2021
1/2
DCS
NASA N254 HVAC Support Q2[DCS]-351-FM5
Project Job No.
N254 (K21007) 60667208
Client Department/Discipline
NASA Structural
Software Name
ETABS, TEDDS, Mathcad
Calculation Rev. No. Originator Self Check Reviewer/Checker Independent Peer
Reviewer Approver
0 Stephanie Ruybal Fabiola Macias-Wallis Tom Zimmerman
Add rows as required
Calculation Objective:
Evaluate the existing steel-framed structure for the proposed HVAC system using the existing construction drawings dated 2001 following provisions given by the IEBC. Design the support framing from the equipment base to the existing roof framing.
The proposed HVAC system includes the removal and replacement of existing rooftop HVAC equipment and ductwork. The new HVAC equipment includes 2 AC units, 2 exhaust fans, and ductwork that require the design of equipment support structures that are included in this calculation.
Calculation Methodology:
Evaluate the existing structure for the existing conditions Calculate the equipment reaction forces due to dead load and either wind or seismic loads Design the equipment support members for the equipment reaction forces Calculate the total design capacity ratio and deflection due to both the existing conditions and proposed HVAC equipment
References / Inputs/ Field Data:
References ─ American Institute of Steel Construction (AISC), Seismic Design Manual, 3rd Edition (AISC 341-16) ─ American Institute of Steel Construction (AISC), Steel Construction Manual, 15th Edition ─ American Institute of Steel Construction (AISC), Specification for Structural Steel Buildings (AISC 360-16) ─ American Society of Civil Engineers (ASCE), Minimum Design Load and Associated Criteria for Buildings and
Other Structures (ASCE 7-16) ─ American Society of Civil Engineers (ASCE), Wind Load Design for Petrochemical and Other Industrial
Facilities (ASCE 48303) ─ American Welding Society (AWS) Structural Welding – Steel (AWS D1.1 2015) ─ California Building Code (CBC) 2019 ─ International Code Council (ICC) International Existing Building Code (IEBC 2018)
C-1
© AECOM Restricted Calculation Cover Page Template (Q2[DCS]-351-FM5) Revision 2 December 6, 2021
2/2
─ Original construction drawings 254-9704-G3, 254-9704-S1 thru 254-9704-S11, 254-9704-A1 thru 254-9704- A11
Design Criteria ─ Risk Category IV ─ Seismic Design Category D ─ Floor Live Load = N/A ─ Roof Live Load = N/A ─ Roof Snow Load = 0 psf ─ Basic Design Wind Speed = 102 mph, Exposure C ─ Earthquake Design Data:
▪ Seismic Importance Factor Ie = 1.5
▪ Mapped Spectral Response Acceleration Parameters Ss = 1.5, S1 = 0.6
▪ Site Class D
▪ Design Spectral Response Acceleration Parameters SDS = 1.2, SD1 = 0.68
▪ Horizontal Seismic Design Force FP = 0.311 kip
▪ Response Modification Coefficient R = 2.0
▪ Analysis Procedure Used = Equivalent lateral force procedure
─ Flood Design Data = N/A ─ Special Loads = N/A ─ Roof Rain Load = N/A
See Table of Contents for additional data in the Appendices.
Assumptions: (Include comments on need to revise calculations after more data is collected/confirmed and/or after assumptions have been verified.)
Existing steel beam strength = 36 ksi Existing dead loads = 16 psf (existing condition) that includes the following:
─ Metal deck = 2.7 psf ─ Roofing = 6.3 psf ─ Ceiling = 2.8 psf ─ MEP = 2 psf ─ Insulation = 2.1 psf
AC unit weight = 1800 lb each
Conclusions including confirmations to be obtained:
The existing structure is adequate to support the new HVAC loads.
This calculation is complete and ready for Discipline Review
Stephanie Ruybal 4/25/2024 Originator Name Signature Date
C-2
PROJECT TITLE:
NASA N254
AECOM PROJECT NO.
60667208
SUBJECT/FEATURE:
HVAC SUPPORT
NARC JOB NO.
K21007
Calc By:
S.Ruybal
Date:
4/25/2024
Checked By:
F. Macias-Wallis
Date:
5/1/2024
Table of Contents
Description Page Number
Calculation Cover Page C-1 – C-2
Table of Contents 1
1. Sketches – see project drawings -
2. Design Equipment and Duct Support Members
2.1 Equipment and Duct Support Geometry
2.2 Duct Support Layout
2.3 Duct Support Design
2.4 Calculate AC Equipment Forces
2.5 Design New Wood Skid Members
2.6 Design Anchorage between AC Isolator and Sleeper
2.7 Design Anchorage between Fan and Sleeper
2.8 Design Anchorage between Sleepers and Existing Roof
Beams
2-1 2-3
2-4 – 2-20 2-21 – 2-27 2-28 – 2-40 2-41 – 2-46 2-47 – 2-50 2-51 – 2-60
3. Evaluate Existing Structure
3.1 Construction Document Review
3.2 Proposed HVAC Modifications
3.3 Code Discussion
3.4 Methodology of Evaluating the Existing Structure
3.5 Determine the Design Capacity Ratio (DCR)
3.6 Calculate Deflection
3.7 Evaluate the Existing Columns
3.8 Check that the Existing Structure is Adequate for Lateral
Loads
3-1 3-2 3-2 3-3 3-5 3-6 3-7 3-7
Appendix A – Drawings of Existing Structure
Appendix B – ETABS Model Report of Duct Portal Frames
Appendix C – Equipment Vendor Drawings
Appendix D – ETABS Model Report of Existing Structure
Appendicies are included as a separate document upon request.
AECOM PROJECT NO.
60667208
SUBJECT/FEATURE:
HVAC SUPPORT
NARC JOB NO.
K21007
Calc By:
S.Ruybal
Date:
4/25/2024
Checked By:
F. Macias-Wallis
Date:
5/1/2024
2. Design Equipment and Duct Support Members
The new HVAC system includes 2 identical AC units and 2 identical exhaust fans highlighted in yellow in the following figure
The new ductwork is highlighted in blue in the following figure
─ Bottom of duct elevations are outlined in blue; elevations for the 12” and 14” diameter ducts were measured from drawing 254-2101-M301
Figure 2.1. New HVAC Equipment Layout (see drawing 254-2101-M102)
2.1 Determine Equipment and Duct Support Geometry
Locate the new wood skids under the anchor locations of AC and Exhaust Fan units
The duct supports are designed in this calculation; however, the duct support locations will be by others spaced at 6’-0” max
─ An equipment and duct support layout was completed to determine the geometries and locations using a 3D model as shown in the following screenshot:
2-1
AECOM PROJECT NO.
60667208
SUBJECT/FEATURE:
HVAC SUPPORT
NARC JOB NO.
K21007
Calc By:
S.Ruybal
Date:
11/20/2023
Checked By:
F. Macias-Wallis
Date:
11/27/2023
Figure 2. New Wood Skid (green) Layout with New Equipment/Ducts (yellow) and Existing Wood Skids (brown) using Preliminary Duct Support Layout (cyan)
The new wood skids (green) will transfer the equipment and duct loads (yellow) into the existing roof framing members
Equipment support framing will be attached to 8x16 posts
─ The 8x16 posts will be attached (2) shaped blocks to fit the roof deck flutes
─ The shaped blocks will be bolted to the top flange of the existing roof framing members
2-2
AECOM PROJECT NO.
60667208
SUBJECT/FEATURE:
HVAC SUPPORT
NARC JOB NO.
K21007
Calc By:
S.Ruybal
Date:
4/25/2024
Checked By:
F. Macias-Wallis
Date:
5/1/2024
2.2 Duct Support Layout
Figure 3. Duct Support Layout Numbering
2-3
AECOM PROJECT NO.
60667208
SUBJECT/FEATURE:
HVAC SUPPORT
NARC JOB NO.
K21007
Calc By:
S.Ruybal
Date:
4/25/2024
Checked By:
F. Macias-Wallis
Date:
5/1/2024
2.3 Duct Support Design
2-4
CALCULATION SHEET
PROJECT TITLE: __NASA N254______________________________________
SUBJECT/FEATURE: __HVAC Support________________________________
AECOM PROJECT NO. __60667208____________________
NARC JOB NO.:__K21007______________________
CALC. BY:_S. Ruybal_ DATE :__11/14/23_
CHECKED BY:_F. Macias-Wallis_ DATE :_11/23/23_
Duct Support Design Calculate the duct reaction forces due to dead load, wind, & seismic loads and design the duct support frames.
Design Calculations:
A 3D model was created to visualize both the location and the geometry of each duct support Duct supports are located a maximum of 6'-0" spacing The table below summarizes the geometries of the duct supports:
Duct Support Number Height Width Type 1 2'-11" 3'-11" Tall 2 2'-11" 3'-11" Tall 3 7" 2'-7" Short 4 7" 2'-7" Short 5 7" 2'-7" Short 6 7" 1'-8" Short 7 7" 1'-8" Short 8 7" 3'-6" Short 9 1'-2" 3'-8" Tall
10 1'-2" 3'-8" Tall 13 7" 4'-0" Short 14 7" 4'-0" Short 15 7" 1'-8" Short 16 7" 1'-8" Short 17 7" 2'-7" Short 18 7" 2'-7" Short 19 7" 2'-7" Short 20 4'-0" 2'-5" Tall 21 4'-0" 2'-5" Tall 22 4'-7" 2'-1" Tall 23 5'-6" 4'-7" Tall
Not Used Not Used
Duct Supports.xmcd 12/5/2023 9:16 AM
2-5
SUBJECT/FEATURE: __HVAC Support________________________________
Duct Reaction Forces for Governing Tall Support:
Dead Load:
20 ga. duct = 1.5 psf 1" rigid insulation = 1.5 psf Duct sizes (see drawing 254-2101-M102):
Perimeter (in)
20 x 20 80 24 x 18 84 20 x 12 64 18 x 14 64 30 x 18 96
Duct Size (in)
DL 1.5 1.5( )psf 96 in 1.2 28.8 plf Dead load of duct with 20% contingency
2-6
SUBJECT/FEATURE: __HVAC Support________________________________
CALC. BY:_S. Ruybal_ DATE :
CHECKED BY:_F. Macias-Wallis_ DATE :
Seismic Load:
ap 2.5 Component amplification factor; ASCE 7 Table 13.6-1 for ducts
Rp 3 ASCE 7 Table 13.6-1 for ducts
SDS 1.2 Spectral acceleration, see stair tower calculation
Wp DL 6 ft 0.173 kip Duct weight per 6ft spacing
Ip 1.5 Component importance factor h 1.0 Roof height z h 1
Fp.
0.4 ap SDS
Rp Ip
1 2 z h
1.8 Horizontal seismic design force; ASCE 7 Eq. 13.3-1
Fp_min 0.3 SDS Ip 0.54
Fp_max 1.6 SDS Ip 2.88
Fp Fp. Wp 0.311 kip
Duct Supports.xmcd 4/23/2024 2:43 PM
2-7
4/23/24
5/1/24
SUBJECT/FEATURE: __HVAC Support________________________________
Calculate reaction forces due to seismic:
Ev 0.2 SDS Wp 0.041 kip Vertical seismic design force, ASCE 7 Sect 13.3.1.2
DR 0.8 Wp 0.138 kip Reliable dead load to resist seismic
MOT Fp 5.5ft( ) 1.711 kip ft Overturning moment due to seismic (conservatively used max height)
Dead
ASCE 7
2.3.1 Eq.
Vertical Force P
(kip)
Vertical Force P
(kip)
Horizontal Force V
(kip) Moment M
(kip-ft)
0.173 0.041 0.311 1.711
LC1 1.4D 1 0.242 0.000 0.000 0.000
LC2 1.2D+1.0E 6 0.208 0.041 0.311 1.711
LC3 0.9DR+1.0E 7 0.125 0.041 0.311 1.711
SesimicLRFD Load Combinations:
Ev 0.041 kip
Eh Fp 0.311 kip
M MOT 1.711 kip ft
Duct Supports.xmcd 4/23/2024 2:43 PM
2-8
4/23/24
SUBJECT/FEATURE: __HVAC Support________________________________
Summary Table:
Dead
ASCE 7
2.3.1 Eq.
Vertical Force P
(kip)
Vertical Force P
(kip)
Horizontal Force V
(kip) Moment M
(kip-ft)
0.173 0.372 0.471 3.517
LC1 1.4D 1 0.242 0.000 0.000 0.000
LC4 1.2D+1.0W 4 0.208 0.372 0.471 3.517
LC5 0.9DR+1.0W 6 0.125 0.372 0.471 3.517
WindLRFD Load Combinations:
Duct Framing Design:
An ETABS model was created to calculate the forces at the connections and to check the design capacity ratios of the duct portal frame members. Wind was conservatively applied in 3 directions simultaneously in the load combinations.
Check Vertical Framing Members:
Conservatively consider that the total lateral wind force is applied to the top of the vertical framing member and that member is fixed.
P Fh
0.235 kip Horizontal force on each vertical member l 5.5ft Controlling height of vertical member
E 29000ksi Steel modulus of elasticity
I 1.23in4 Moment of inertia for L3x3x1/4
Δ P l3
12 E I
0.158 in Deflection of vertical member l
Δ
417.576 Deflection of vertical member < L/200 OK
Duct Supports.xmcd 4/24/2024 8:35 AM
2-10
4/24/24
Project
NASA N254 HVAC
Job Ref.
Section
TYPE B SUPPORT: WOOD PERPENDICULAR TO ANGLE
Sheet no./rev.
Calc. by
S. Ruybal Date
11/21/2023 Chk'd by Date App'd by Date
Total number of lag screw Ntotal = R C = 2
Applied load Applied load to the connection P = 627 lb
Dowel bearing length (main) (12.3.5) Size of tapered tip E = 0.406 in Actual penetration in main member Pact = L - W - ts = 4.625 in Dowel bearing length in main member lm = 3.500 in
Dowel bearing length (connected) (12.3.5) Dowel bearing length in connected member ls = ts = 0.250 in
Bending yield strength (lag screw) (Table 12J to 12K footnote no. 2) Bending yield strength of lag screw Fyb = 45000 psi
Dowel bearing strength (main member) (Table 12.3.3 footnote no. 2) Dowel bearing strength parallel to grain Fe_par = 11200 Gm 1 psi = 5152 psi
Dowel bearing strength perpendicular to grain Fe_perp = 6100 Gm1.45 1 psi / (D / 1 in) = 2503 psi
Dowel bearing strength for small dia. fasteners Fe = 16600 Gm1.84 1 psi = 3977 psi
Dowel bearing strength at an angle of load to grain Fem = (Fe_par Fe_perp) / ((Fe_par (sin(m))2) + (Fe_perp (cos(m))2)) Fem = 2503 psi Dowel bearing strength of main member Fem = 2503 psi
Dowel bearing strength (connected steel member) (Table 12K footnote no. 2) Dowel bearing strength of connected member Fes = 87000 psi
Preliminary yield limit equation coefficients (Table 12.3.1A notes) Dowel bearing strength ratio Re = Fem / Fes = 0.029 Dowel bearing length ratio Rt = lm / ls = 14.000 Preliminary yield limit equation coefficient k1 k1 = (((Re+(2Re2(1+Rt+Rt2))+(Rt2Re3)))-(Re(1+Rt)))/(1+Re) k1 = 0.182 Preliminary yield limit equation coefficient k2 k2 = -1+((2(1+Re))+((2Fyb(1+(2Re))Dr2))/(3Femlm2)) k2 = 0.512 Preliminary yield limit equation coefficient k3 k3 = -1+(((2(1+Re))/Re)+((2Fyb(2+Re)Dr2))/(3Femls2)) k3= 11.564 Angle of load to grain coefficient k k = 1 + (0.25 max (m, s) / 90) = 1.250 Reduction term (Table 12.3.1B) KD = 3.00
Yield limit equations (single shear) Mode Im (eq. 12.3-1) ZIm = (Dr lm Fem) / (4 k) = 825 lb
Mode Is (eq. 12.3-2) ZIs = (Dr ls Fes) / (4 k) = 2049 lb
Mode II (eq. 12.3-3) ZII = (k1 Dr ls Fes) / (3.6 k) = 414 lb
Mode IIIm (eq. 12.3-4) ZIIIm = (k2 Dr lm Fem) / ((1 + (2 Re)) 3.2 k) = 500 lb
Mode IIIs (eq. 12.3-5) ZIIIs = (k3 Dr ls Fem) / ((2 + Re) 3.2 k) = 420 lb
Mode IV (eq. 12.3-6) ZIV = (Dr 2 (((2 Fem Fyb) / (3 (1 + Re))))) / (3.2 k) = 474 lb Z = min (ZIm, ZIs,ZII, ZIIIm, ZIIIs, ZIV) = 414 lb Nominal capacity of single fastener Z = 414 lb
Actual load applied to the connection = 314 lb;
conservatively left load applied to the connection as 627 lb
2-14
Job Ref.
Section
TYPE B SUPPORT: WOOD PERPENDICULAR TO ANGLE
Sheet no./rev.
Calc. by
S. Ruybal Date
11/21/2023 Chk'd by Date App'd by Date
Slenderness (Table 12.5.1C footnote no.1) Slenderness l / D = 5.600
Spacing requirements (perpendicular to grain loading)
End distance (Table 12.5.1A) End distance (full stregnth) aq_full = 4 D = 2.500 in End distance (minimum) aq_min = 2 D = 1.250 in End distance (actual) aq = 2.500 in
Edge distance (Table 12.5.1C) Loaded edge eq = 4 D = 2.500 in Unloaded edge ep = 1.5 D = 0.938 in
Center to center spacing (Table 12.5.1B) Center to center spacing (full strength) s_full = 4 D = 2.500 in Center to center spacing (minimum) s_min = 3 D = 1.875 in Center to center spacing (actual) s = 3.500 in
Row spacing (Table 12.5.1D) Row spacing srow = ((5 l) + (10 D)) / 8 = 2.969 in
Geometry factor C (12.5.1) End distance (actual) aq = 2.500 in End distance (full strength) aq_full = 2.500 in Geometry factor for end distance C = aq / aq_full = 1.00 Center to center spacing (actual) s = 3.500 in Center to center spacing (full strength) s_full = 2.500 in Geometry factor for spacing C = s / s_full = 1.40 Geometry factor C = min(1,C C) = 1.00
Adjustment factor Load duration factor (Table 2.3.2) CD = 1.00 Wet service factor (Table 11.3.3) CM = 1.0 Temperature factor (Table 11.3.4) Ct = 1.0 Group action factor (eq. 11.3-1) Cg = 1.0 Geometry factor (12.5.1) C = 1.00 End grain factor (12.5.2) Ceg = 1.0 Diaphragm factor (12.5.3) Cdi = 1.0 Toe nail factor (12.5.4) Ctn = 1.0
Total capacity of connection Capacity of connection Z’ = Z Ntotal Nint CD CM C= 828 lb P / Z' = 0.757
Design result PASS - Connection capacity exceeds applied load
2-15
SUBJECT/FEATURE: __HVAC Support________________________________
Design Duct Support 23/24:
This duct support is unique because it is not supported by an existing or new skid This support will be constructed on Durabloks that are set on an architectural pad The same frame design as the tall duct support designed in this calculation can be used This portion of the calculation will check the existing deck point loads, designing a brace to transfer lateral and any vertical forces, and design the connection to the Durablock
Check existing deck point load:
Rv 0.2076kip
0.342kip
2.898kip ft 4.583ft
0.907 kip Vertical reaction of 1 leg of support 23 due to wind
Apad 3.25ft 3.25 ft 10.563 ft2 Area of architectural support pad
Rv_area Rv
Apad
85.883 psf Vertical load spread over architectural support pad
Rv_all 92psf Allowable LRFD load of 22 gage roof deck with 8'-0" span
Rv_area Rv_all
0.934 CheckRv "OK"
Rv_area Rv_all
1.0if
"Decking NG" otherwise
"OK"
2-16
SUBJECT/FEATURE: __HVAC Support________________________________
Brace Design:
Fh 0.471 kip Horizontal design force
Rv 0.907 kip Vertical design force
By inspection, an L3x3x1/4" angle is adequate as a brace member and (2) 1/2" dia. bolts are adequate as calculated above. By inspection, a 3/8" thick gusset plate with 3/16" fillet weld is adequate.
Check withdrawal using same values as above except for design load and withdrawal angle Conservatively design top lag screws for entire design load Tedds is used to check the top screws for lateral forces and to calculate Z` for this connection Calculate the actual vertical design force accounting for structure dead load
Rv_24 Rv Wp 175lbf
0.733 kip Vertical reaction from wind counteracted by DL of duct and steel (considered to weigh 175 lbf) p24 4.625in Fastener penetration, 5" length
Z'24 1254lb Adjusted lateral design value per connection; see Tedds output next sheets
W' 1446.939 lb in
Adjusted withdrawal design value per connection; NDS αmin 22.5deg Minimum withdrawal angle
Z'α24 W' p24 Z'24
W' p24 cos αmin 2 Z'24 sin αmin 2
1423.39 lb NDS Eq 12.4-1
Zα24 Fh 2 Rv_24
871.287 lbf
871.287 1423.39
0.612 OK
2-17
Job Ref.
Section
Brace Support Sheet no./rev.
Calc. by
S. Ruybal Date
11/21/2023 Chk'd by Date App'd by Date
LAG SCREW TIMBER TO STEEL CONNECTION DESIGN
In accordance with NDS 2018 Tedds calculation version 1.2.04
Design results summary Unit Required Provided Utilization Result
Connection capacity lbs 871 1254 0.695 PASS
P Main member
Connected member tm ts m
Main timber member details Species of main member Douglas Fir-South Size of main member (Table 1B) 6 x 8 Number of main member Nm = 1 Thickness of main member tm = 5.500 in Angle of load to grain of main member m = 25
Connected steel member details Number of connected steel member Ns = 1 Connected steel member thickness ts = 0.250 in Number of interfaces Nint = (Nm + Ns) – 1 = 1
Lag screw details Lag screw diameter (Table L2) 5/8'' Lag screw root diameter of threaded portion Dr = 0.471 in Length of lag screw L = 5.000 in Washer thickness W = 0.125 in Number of rows of lag screw R = 1 Number of columns of lag screw C = 2 Total number of lag screw Ntotal = R C = 2
2-18
Job Ref.
Section
Brace Support Sheet no./rev.
Calc. by
S. Ruybal Date
11/21/2023 Chk'd by Date App'd by Date
Applied load Applied load to the connection P = 871 lb
Dowel bearing length (main) (12.3.5) Size of tapered tip E = 0.406 in Actual penetration in main member Pact = L - W - ts = 4.625 in Dowel bearing length in main member lm = 4.422 in
Dowel bearing length (connected) (12.3.5) Dowel bearing length in connected member ls = ts = 0.250 in
Bending yield strength (lag screw) (Table 12J to 12K footnote no. 2) Bending yield strength of lag screw Fyb = 45000 psi
Dowel bearing strength (main member) (Table 12.3.3 footnote no. 2) Dowel bearing strength parallel to grain Fe_par = 11200 Gm 1 psi = 5152 psi
Dowel bearing strength perpendicular to grain Fe_perp = 6100 Gm1.45 1 psi / (D / 1 in) = 2503 psi
Dowel bearing strength for small dia. fasteners Fe = 16600 Gm1.84 1 psi = 3977 psi
Dowel bearing strength at an angle of load to grain Fem = (Fe_par Fe_perp) / ((Fe_par (sin(m))2) + (Fe_perp (cos(m))2)) Fem = 4333 psi Dowel bearing strength of main member Fem = 4333 psi
Dowel bearing strength (connected steel member) (Table 12K footnote no. 2) Dowel bearing strength of connected member Fes = 87000 psi
Preliminary yield limit equation coefficients (Table 12.3.1A notes) Dowel bearing strength ratio Re = Fem / Fes = 0.050 Dowel bearing length ratio Rt = lm / ls = 17.688 Preliminary yield limit equation coefficient k1 k1 = (((Re+(2Re2(1+Rt+Rt2))+(Rt2Re3)))-(Re(1+Rt)))/(1+Re) k1 = 0.367 Preliminary yield limit equation coefficient k2 k2 = -1+((2(1+Re))+((2Fyb(1+(2Re))Dr2))/(3Femlm2)) k2 = 0.479 Preliminary yield limit equation coefficient k3 k3 = -1+(((2(1+Re))/Re)+((2Fyb(2+Re)Dr2))/(3Femls2)) k3= 8.620 Angle of load to grain coefficient k k = 1 + (0.25 max (m, s) / 90) = 1.069 Reduction term (Table 12.3.1B) KD = 3.00
Yield limit equations (single shear) Mode Im (eq. 12.3-1) ZIm = (Dr lm Fem) / (4 k) = 2109 lb
Mode Is (eq. 12.3-2) ZIs = (Dr ls Fes) / (4 k) = 2395 lb
Mode II (eq. 12.3-3) ZII = (k1 Dr ls Fes) / (3.6 k) = 978 lb
Mode IIIm (eq. 12.3-4) ZIIIm = (k2 Dr lm Fem) / ((1 + (2 Re)) 3.2 k) = 1147 lb
Mode IIIs (eq. 12.3-5) ZIIIs = (k3 Dr ls Fem) / ((2 + Re) 3.2 k) = 627 lb
Mode IV (eq. 12.3-6) ZIV = (Dr 2 (((2 Fem Fyb) / (3 (1 + Re))))) / (3.2 k) = 721 lb Z = min (ZIm, ZIs,ZII, ZIIIm, ZIIIs, ZIV) = 627 lb Nominal capacity of single fastener Z = 627 lb
2-19
Job Ref.
Section
Brace Support Sheet no./rev.
Calc. by
S. Ruybal Date
11/21/2023 Chk'd by Date App'd by Date
Slenderness (Table 12.5.1C footnote no.1) Slenderness l / D = 7.075
Spacing requirements (perpendicular to grain loading)
End distance (Table 12.5.1A) End distance (full stregnth) aq_full = 4 D = 2.500 in End distance (minimum) aq_min = 2 D = 1.250 in End distance (actual) aq = 2.500 in
Edge distance (Table 12.5.1C) Loaded edge eq = 4 D = 2.500 in Unloaded edge ep = 1.5 D = 0.938 in
Center to center spacing (Table 12.5.1B) Center to center spacing (full strength) s_full = 4 D = 2.500 in Center to center spacing (minimum) s_min = 3 D = 1.875 in Center to center spacing (actual) s = 3.500 in
Row spacing (Table 12.5.1D) Row spacing srow = (5 D) = 3.125 in
Geometry factor C (12.5.1) End distance (actual) aq = 2.500 in End distance (full strength) aq_full = 2.500 in Geometry factor for end distance C = aq / aq_full = 1.00 Center to center spacing (actual) s = 3.500 in Center to center spacing (full strength) s_full = 2.500 in Geometry factor for spacing C = s / s_full = 1.40 Geometry factor C = min(1,C C) = 1.00
Adjustment factor Load duration factor (Table 2.3.2) CD = 1.00 Wet service factor (Table 11.3.3) CM = 1.0 Temperature factor (Table 11.3.4) Ct = 1.0 Group action factor (eq. 11.3-1) Cg = 1.0 Geometry factor (12.5.1) C = 1.00 End grain factor (12.5.2) Ceg = 1.0 Diaphragm factor (12.5.3) Cdi = 1.0 Toe nail factor (12.5.4) Ctn = 1.0
Total capacity of connection Capacity of connection Z’ = Z Ntotal Nint CD CM C= 1254 lb P / Z' = 0.695
Design result
2-20
AECOM PROJECT NO.
60667208
SUBJECT/FEATURE:
HVAC SUPPORT
NARC JOB NO.
K21007
Calc By:
S.Ruybal
Date:
4/25/2024
Checked By:
F. Macias-Wallis
Date:
5/1/2024
2.4 Calculate AC Equipment Forces
2-21
SUBJECT/FEATURE: __HVAC Support________________________________
Calculate AC Equipment Forces
Equipment Dimensions:
Air Conditioner:
LAC 82.25in Length of AC
BAC 79in Width of AC hAC 44in Height of AC
Reference: RN Series A- Cabinet Standard ~ 6-10 Ton
Dead Loads:
DLAC 1500lbf Weight of AC unit, drawing 254-2101-M601 for AC-1A & AC-1B
DLACcurb 300lbf Weight of AC roof curb, drawing 254-2101-M601 for AC-1A & AC-1B
The dead load shown on drawing 254-2101-M601 for AC-1A & AC-1B is more than that on vendor documents showing equipment corner loads, RN-008-3-0-KB09-000:0000-00A-DCE-AGC-OOFAOOD-00-0000000VB. This may be because the weight estimate on the vendor document states that it does not account for an SPAs.
Calculate the corner loads of the equipment based on 1500 lbs instead of 1149 lbs by scaling the loads
Add roof curb as a point load to each corner
SF
1500lbf 1149lbf
1.305 Scale factor
Load Development.xmct 5/8/2024 3:41 PM
2-22
SUBJECT/FEATURE: __HVAC Support________________________________
Calculate Wind Forces on Equipment:
qh 16.514psf Velocity pressure: Velocity pressure calculated for duct supports
G 0.85 Gust effect factor: Gust effect factor from Section 26.11 of ASCE 7
B 6 4210 mm( ) 2 305 mm( ) 84.875 ft Width of building, see drawing 254-9704-S1 in Appendix A
L 2 7400 mm 48.556 ft Length of building, see drawing 254-9704-S1 in Appendix A h 4128 76( )mm 13.294 ft Height of building, see drawing 254-9704-S4 in Appendix A
Lateral Wind Force:
B h 1128.329 ft2 Vertical projected area of building
Af hAC max BAC LAC 25.132 ft2 Vertical projected area of equipment
GCr_1 1.9 Af 0.1B hif
"Interpolate per ASCE" otherwise
1.9 See ASCE 7 section 29.4.1
Fh qh GCr_1 Af 0.789 kip Lateral wind force, ASCE 7 equation 29.4-2
Vertical (uplift) Wind Force:
B L 4121.243 ft2 Horizontal projected area of building
Ar BAC LAC 45.123 ft2 Horizontal projected area of equipment
GCr_v 1.5 Ar 0.1B Lif
"Interpolate per ASCE" otherwise
1.5 See ASCE 7 section 29.4.1
Fv qh GCr_v Ar 1.118 kip Vertical upl ift force; ASCE 7 equation 29.4-3
Uplift DLAC DLACcurb Fv 0.682 kip No uplift exists
Load Development.xmct 12/5/2023 9:48 AM
2-24
SUBJECT/FEATURE: __HVAC Support________________________________
Calculate Seismic Forces on Equipment:
ap 2.5 Component amplification factor; ASCE 7 Table 13.6-1 for vibration-isolated components
SDS 1.2 Spectral acceleration
Ip 1.5 Component importance factor, ASCE 7 Section 13.1.3 for Risk Category IV
Wp DLAC DLACcurb 1.8 kip Component operating weight
Rp 2 ASCE 7 Table 13.6-1 z 1 Height of structure of point of attachment for roof-mount h 1 Average roof height of structure
Fp_1
0.4 ap SDS
2.7 Seismic design force, equation 13.3-1 ASCE 7
Fp_max 1.6 SDS Ip 2.88 Max seismic design force, equation 13.3-2 ASCE 7
Fp_min 0.3 SDS Ip 0.54 Min seismic design force, equation 13.3-2 ASCE 7
Fp Fp_1 Wp 4.86 kip Seismic horizontal design force
Ev 0.2 SDS Wp 0.432 kip Vertical seismic force, section 13.3.1.2 of ASCE 7
Load Development.xmct 4/24/2024 4:04 PM
2-25
SUBJECT/FEATURE: __HVAC Support________________________________
LAC (ft) = 6.85 DL Equipment Vertical Seismic
Ev Horizontal Seismic Fp
0.629 0.159 1.793
0.184 0.046 0.523
Point Load from Isolator (kip) Uniform Load (klf)
Calculate moment from AC:
d1 6 4 4.5( )in 14.5 in Distance from AC unit to curb support d2 16 8( )in 24 in Distance from curb to sleeper
Meq hAC d1 d2
Fp 27.472 kip ft Moment about horizontal axis due to seismic, assumes vertical center of gravity of AC unit is 2/3 the height of the unit
LRFD Load Combinations for controlling support (front left corner):
Dead Vertical Force P
(klf) Vertical Force Ev
(klf) Horizontal Force
V (klf) Moment M (kip-ft)
0.184 0.046 0.523 27.472
LC 1 1.4D 0.258 0.000 0.000 1.000
LC 2 1.2D+E 0.221 0.046 0.523 27.472
LC 3 0.9DR+E 0.132 0.046 0.523 27.472
Seismic
DR 0.8( ) 0.184 klf 0.147 klf Reliable dead load to resist seismic; reduction of dead load that resists seismic that is equal to 80% of the total dead load
Load Development.xmct 5/8/2024 3:41 PM
2-27
AECOM PROJECT NO.
60667208
SUBJECT/FEATURE:
HVAC SUPPORT
NARC JOB NO.
K21007
Calc By:
S.Ruybal
Date:
4/25/2024
Checked By:
F. Macias-Wallis
Date:
5/1/2024
2.5 Design New Wood Skid Members
2-28
Job Ref.
Section
Wood Beam A - Vertical & Axial Sheet no./rev.
Calc. by
SSR
Date
11/22/2023 Chk'd by Date App'd by Date
Node Force Moment Fx Fz My
(kips) (kips) (kip_ft) 2 0 0.095 0 3 0 0.029 0
Load case: Dead Node Force Moment
Fx Fz My (kips) (kips) (kip_ft)
1 0 0.004 0 2 0 1.236 0 3 0 0.236 0
Load case: Seismic Node Force Moment
Fx Fz My (kips) (kips) (kip_ft)
1 -0.245 0.323 0 2 -2.895 2.992 0 3 -0.883 0.932 0
Load combination: 1.0D (Strength) Node Force Moment
Fx Fz My (kips) (kips) (kip_ft)
1 0 0.033 0 2 0 1.33 0 3 0 0.265 0
Load combination: 1.0D + 0.7E (Strength) Node Force Moment
Fx Fz My (kips) (kips) (kip_ft)
1 -0.172 0.259 0 2 -2.026 3.425 0 3 -0.618 0.917 0
Load combination: 0.6D + 0.7E (Strength) Node Force Moment
Fx Fz My (kips) (kips) (kip_ft)
1 -0.172 0.246 0 2 -2.026 2.892 0 3 -0.618 0.811 0
2-31
Job Ref.
Section
Wood Beam A - Vertical & Axial Sheet no./rev.
Calc. by
SSR
Date
11/22/2023 Chk'd by Date App'd by Date
Load combination: 1.4D (Strength) Node Force Moment
Fx Fz My (kips) (kips) (kip_ft)
1 0 0.046 0 2 0 1.862 0 3 0 0.371 0
Load combination: 1.2D + 1.0E (Strength) Node Force Moment
Fx Fz My (kips) (kips) (kip_ft)
1 -0.245 0.362 0 2 -2.895 4.588 0 3 -0.883 1.25 0
Load combination: 0.9D + 1.0E (Strength) Node Force Moment
Fx Fz My (kips) (kips) (kip_ft)
1 -0.245 0.352 0 2 -2.895 4.189 0 3 -0.883 1.17 0
Load combination: 1.0D - 0.7E (Strength) Node Force Moment
Fx Fz My (kips) (kips) (kip_ft)
1 0.172 -0.193 0 2 2.026 -0.764 0 3 0.618 -0.388 0
Load combination: 0.6D - 0.7E (Strength) Node Force Moment
Fx Fz My (kips) (kips) (kip_ft)
1 0.172 -0.206 0 2 2.026 -1.296 0 3 0.618 -0.493 0
Load combination: 1.2D -1.0E (Strength) Node Force Moment
Fx Fz My (kips) (kips) (kip_ft)
1 0.245 -0.283 0 2 2.895 -1.396 0 3 0.883 -0.614 0
2-32
Job Ref.
Section
Wood Beam A - Vertical & Axial Sheet no./rev.
Calc. by
SSR
Date
11/22/2023 Chk'd by Date App'd by Date
Load combination: 0.9D - 1.0E (Strength) Node Force Moment
Fx Fz My (kips) (kips) (kip_ft)
1 0.245 -0.293 0 2 2.895 -1.795 0 3 0.883 -0.694 0
Beam - Span 1
Member details Service condition Wet Elevated temperature 100 degF to 125 degF
Sawn lumber section details Number of sections in member N = 1 Nominal breadth of sections bnom = 6 in Breadth of sections b = 5.5 in Nominal depth of sections dnom = 8 in Depth of sections d = 7.5 in Material Douglas Fir-South, Posts and timbers, No.1 grade
7.
5"
5.5"
6''x8'' sawn lumber section Cross-sectional area, A, 41.25 in 2
Section modulus, S x, 51.6 in3
Section modulus, S y, 37.8 in3
Second moment of area, I x, 193.4 in4
Second moment of area, I y, 104 in4
Radius of gyration, r x, 2.165 in Radius of gyration, r y, 1.588 in Douglas Fir-South, Posts and timbers, No.1 grade Bending, Fb, 1150 psi Shear parallel to grain, F v, 165 psi Compression parallel to grain, F c, 925 psi Compression perpendicular to grain, F c_perp, 520 psi Tension parallel to grain, F t, 775 psi Modulus of elasticity, E, 1200000 psi Minimum modulus of elasticity, Emin, 440000 psi Density, , 33.193 lbm/ft 3
Specific gravity, G, 0.46
Span details Bearing length Lb = 7.5 in
Consider Combination 5 - 1.2D + 1.0E (Strength)
Adjustment factors - Table 4.3.1 Wet service factor for bending - Table 4D CMb = 1 Wet service factor for shear - Table 4D CMv = 1 Wet service factor for tension - Table 4D CMt = 1 Wet service factor for perp.comp. - Table 4D CMc_perp = 0.67 Wet service factor for mod.of elasticity - Table 4D CME = 1
2-33
Job Ref.
Section
Wood Beam A - Vertical & Axial Sheet no./rev.
Calc. by
SSR
Date
11/22/2023 Chk'd by Date App'd by Date
Temperature factor - Table 2.3.3 Ct = 0.7 Temp.factor for modulus of elasticity - Table 2.3.3 CtE = 0.9 Depth-to-breadth ratio dnom / bnom = 1.33 Slenderness ratio - eq.3.3-5 RB = (Le,y d / b2) = 5.140 Reference bending design value Fb = Fb Ct KFb b = 1390 lb/in2
Adjusted modulus of elasticity Emin' = Emin CtE KFE s = 592416 lb/in2
Critical buckling design value - cl.3.3.3.8 FbE = 1.2 Emin' / RB2 = 26908 lb/in2
Beam stability factor - eq.3.3-6 CL = [1 + (FbE / Fb)] / 1.9 - [([1 + (FbE / Fb)] / 1.9)2 - (FbE / Fb) / 0.95] = 0.997
Time dependent deformation factor - cl.3.5.2 Kcr = 2 Format conversion factor for bending - Table 2.3.5 KFb = 2.54 Format conversion factor for shear - Table 2.3.5 KFv = 2.88 Format conversion factor for tension - Table 2.3.5 KFt = 2.7 Format conv.factor for perp.comp. - Table 2.3.5 KFc_perp = 1.67 Form.conv.factor for mod.of elasticity - Table 2.3.5 KFE = 1.76 Resistance factor for bending - Table 2.3.6 b = 0.85 Resistance factor for shear - Table 2.3.6 v = 0.75 Resistance factor for compression - Table 2.3.6 c = 0.9 Resistance factor for tension - Table 2.3.6 t = 0.8 Resistance factor for mod.of elasticity - Table 2.3.6 s = 0.85 Time effect factor - Table N.3 = 0.8
Check design at end of span
Compression members - General - cl.3.6 Design axial compression force P = 1091 lb Design compression parallel to grain - Table 4.3.1 Fc' = Fc CMc Ct CP KFc c = 835 lb/in2
Actual compression parallel to grain fc = P / (b d) = 26 lb/in2 fc / Fc' = 0.032 PASS - Design compression stress exceeds actual compression stress
Bending members - Flexure - cl.3.3 Design bending moment Mx = 3376 lb_ft Design bending stress - Table 4.3.1 Fb,x' = Fb Ct CL KFb b = 1387 lb/in2
Actual bending stress - eq.3.3-2 fb,x = Mx / Sx = 786 lb/in2 fb,x / Fb,x' = 0.567 PASS - Design bending stress exceeds actual bending stress
Bending members - Shear - cl.3.4 Design shear force Vx = 2058 lb Design shear stress - Table 4.3.1 Fv,x' = Fv Ct KFv v = 200 lb/in2
Actual shear stress - eq.3.4-2 fv,x = 3 Vx / (2 b d) = 75 lb/in2 fv,x / Fv,x' = 0.375 PASS - Design shear stress exceeds actual shear stress
Design for bearing - cl.3.10 Design perpendicular compression Rx = 4588 lb
2-34
Job Ref.
Section
Wood Beam A - Vertical & Axial Sheet no./rev.
Calc. by
SSR
Date
11/22/2023 Chk'd by Date App'd by Date
Design bearing stress - Table 4.3.1 Fc_perp,x' = Fc_perp CMc_perp Ct KFc_perp c = 367 lb/in2
Actual bearing stress fc_perp,x = Rx / (b Lb) = 111 lb/in2 fc_perp,x / Fc_perp,x' = 0.303 PASS - Design bearing stress exceeds actual bearing stress perpendicular to grain
Combined bending and axial loading - cl.3.9 Critical buckling design value in x-axis FcE1 = 0.822 Emin' / (Lb,x / d)2 = 2972 lb/in2
Critical buckling design value in y-axis FcE2 = 0.822 Emin' / (Lb,y / b)2 = 1598 lb/in2
Bending and compression check - eqs.3.9-3 and 3.9-4 max((fc / Fc')2 + fb,x / (Fb,x' (1 - (fc / FcE1))), (fc / FcE2)) = 0.573 < 1.0
PASS - Combined bending and compressive stresses are within permissible limits
Consider Combination 6 - 0.9D + 1.0E (Strength)
Check design 3ft 9.601in along span
Bending members - Deflection - cl.3.5 Instantaneous deflection x' = x / CtE = 0.052 in Final deflection x,Final = Kcr x' = 0.104 in Allowable deflection x,Allowable = Lm1_s1 / 250 = 0.384 in x,Final / x,Allowable = 0.27
PASS - Allowable deflection exceeds final deflection
Beam - Span 2
Member details Service condition Wet Elevated temperature 100 degF to 125 degF
Sawn lumber section details Number of sections in member N = 1 Nominal breadth of sections bnom = 6 in Breadth of sections b = 5.5 in Nominal depth of sections dnom = 8 in Depth of sections d = 7.5 in Material Douglas Fir-South, Posts and timbers, No.1 grade
2-35
Job Ref.
Section
Wood Beam A - Vertical & Axial Sheet no./rev.
Calc. by
SSR
Date
11/22/2023 Chk'd by Date App'd by Date
7.
5"
5.5"
6''x8'' sawn lumber section Cross-sectional area, A, 41.25 in 2
Section modulus, S x, 51.6 in3
Section modulus, S y, 37.8 in3
Second moment of area, I x, 193.4 in4
Second moment of area, I y, 104 in4
Radius of gyration, r x, 2.165 in Radius of gyration, r y, 1.588 in Douglas Fir-South, Posts and timbers, No.1 grade Bending, Fb, 1150 psi Shear parallel to grain, F v, 165 psi Compression parallel to grain, F c, 925 psi Compression perpendicular to grain, F c_perp, 520 psi Tension parallel to grain, F t, 775 psi Modulus of elasticity, E, 1200000 psi Minimum modulus of elasticity, Emin, 440000 psi Density, , 33.193 lbm/ft 3
Specific gravity, G, 0.46
Span details Bearing length Lb = 7.5 in
Consider Combination 6 - 0.9D + 1.0E (Strength)
Adjustment factors - Table 4.3.1 Wet service factor for bending - Table 4D CMb = 1 Wet service factor for shear - Table 4D CMv = 1 Wet service factor for tension - Table 4D CMt = 1 Wet service factor for perp.comp. - Table 4D CMc_perp = 0.67 Wet service factor for mod.of elasticity - Table 4D CME = 1 Temperature factor - Table 2.3.3 Ct = 0.7 Temp.factor for modulus of elasticity - Table 2.3.3 CtE = 0.9 Depth-to-breadth ratio dnom / bnom = 1.33 Slenderness ratio - eq.3.3-5 RB = (Le,y d / b2) = 5.140 Reference bending design value Fb = Fb Ct KFb b = 1738 lb/in2
Adjusted modulus of elasticity Emin' = Emin CtE KFE s = 592416 lb/in2
Critical buckling design value - cl.3.3.3.8 FbE = 1.2 Emin' / RB2 = 26908 lb/in2
Beam stability factor - eq.3.3-6 CL = [1 + (FbE / Fb)] / 1.9 - [([1 + (FbE / Fb)] / 1.9)2 - (FbE / Fb) / 0.95] = 0.997
Time dependent deformation factor - cl.3.5.2 Kcr = 2 Format conversion factor for bending - Table 2.3.5 KFb = 2.54 Format conversion factor for shear - Table 2.3.5 KFv = 2.88 Format conversion factor for tension - Table 2.3.5 KFt = 2.7 Format conv.factor for perp.comp. - Table 2.3.5 KFc_perp = 1.67 Form.conv.factor for mod.of elasticity - Table 2.3.5 KFE = 1.76 Resistance factor for bending - Table 2.3.6 b = 0.85 Resistance factor for shear - Table 2.3.6 v = 0.75 Resistance factor for compression - Table 2.3.6 c = 0.9 Resistance factor for tension - Table 2.3.6 t = 0.8
2-36
Job Ref.
Section
Wood Beam A - Vertical & Axial Sheet no./rev.
Calc. by
SSR
Date
11/22/2023 Chk'd by Date App'd by Date
Resistance factor for mod.of elasticity - Table 2.3.6 s = 0.85 Time effect factor - Table N.3 = 1
Check design 4ft 9.331in along span
Compression members - General - cl.3.6 Design axial compression force P = 695 lb Design compression parallel to grain - Table 4.3.1 Fc' = Fc CMc Ct CP KFc c = 972 lb/in2
Actual compression parallel to grain fc = P / (b d) = 17 lb/in2 fc / Fc' = 0.017 PASS - Design compression stress exceeds actual compression stress
Bending members - Flexure - cl.3.3 Design bending moment Mx = 2359 lb_ft Design bending stress - Table 4.3.1 Fb,x' = Fb Ct CL KFb b = 1732 lb/in2
Actual bending stress - eq.3.3-2 fb,x = Mx / Sx = 549 lb/in2 fb,x / Fb,x' = 0.317 PASS - Design bending stress exceeds actual bending stress
Combined bending and axial loading - cl.3.9 Critical buckling design value in x-axis FcE1 = 0.822 Emin' / (Lb,x / d)2 = 2972 lb/in2
Critical buckling design value in y-axis FcE2 = 0.822 Emin' / (Lb,y / b)2 = 1598 lb/in2
Bending and compression check - eqs.3.9-3 and 3.9-4 max((fc / Fc')2 + fb,x / (Fb,x' (1 - (fc / FcE1))), (fc / FcE2)) = 0.319 < 1.0
PASS - Combined bending and compressive stresses are within permissible limits
Check design 4ft 4.876in along span
Bending members - Deflection - cl.3.5 Instantaneous deflection x' = x / CtE = 0.128 in Final deflection x,Final = Kcr x' = 0.255 in Allowable deflection x,Allowable = Lm1_s2 / 250 = 0.384 in x,Final / x,Allowable = 0.664
PASS - Allowable deflection exceeds final deflection
2-37
Job Ref.
Section
Wood Beam A - Vertical & Axial Sheet no./rev.
Calc. by
SSR
Date
11/21/2023 Chk'd by Date App'd by Date
WOOD BEAM A - LATERAL MOMENT CALCULATION
In accordance with the ANSI/AF&PA NDS 2018 using the LRFD method Tedds calculation version 2.2.20
ANALYSIS
Tedds calculation version 1.0.37
Results
Forces
Strength combinations - Moment envelope (kip_ft)
0.1
-1.1
0.9
-1.1
Strength combinations - Shear envelope (kips)
-0.7
-0.3
Member results
Envelope - Strength combinations Member Position Shear force Moment
(ft) (kips) (kip_ft) Beam 8 1.026 (max abs) -0.718 0 -1.096 (min)
11.95 0 0.928 (max) 0
2-38
SUBJECT/FEATURE: __HVAC Support________________________________
CHECKED BY:_F. Macias-Wallis_ DATE :_11/27/23_
Design Wood Beam Members for Combined Bending and Axial Loads Purpose:
Apply the NDS combined bending and axial compression equation 3.9-3 to design the wood beam Only Beam A will be designed since it experiences the largest loads from the equipment
Results from Tedds:
fb1 786psi Actual bending stress, see Tedds output fc 44ps Actual compression parallel to grain, see Tedds output
Sy 37.8in3 Section modulus, see Tedds output
FbE 26908ps Critical buckling design value, see Tedds output
FcE2 1598psi Critical buckling design value, see Tedds output
My 1.096kip ft Design bending moment, see Tedds output (note that Tedds was used only to calculate the moment due to the seismic lateral loads)
Design Calculations:
Minor Axis Bending Capacity:
λ 1 Time effect factor for 1.4D=0.6, can be increased to 1.0 for other load combinations; NDS Table N3 ϕb 0.85 Resistance factor, NDS Table N2
KF_Fb 2.16 ϕb
2.541 Format conversion factor, NDS Table N1
Fb 1000psi Bending; NDS Supplement Table 4A for Douglas Fir-Larch No. 1
CF_Fc 1.05 Size factor for compression; NDS Supplement Cf Table
CM_Fb 0.85 Fb CF_Fc 1150psiif
1.0 otherwise
0.85 Wet Service Factor, NDS Supplement Wet Service Factor
Ct 0.7 Temperature factor, NDS 2.3.3
Wood Beam Interaction 11/22/2023 8:41 AM
2-39
SUBJECT/FEATURE: __HVAC Support________________________________
CHECKED BY:_F. Macias-Wallis_ DATE :_11/27/23_
CF_Fb 1.3 Size factor for bending; NDS Supplement Cf Table
Ci 1.0 Insising factor
Cr 1.0 Repetitive member factor; NDS Supplemental Repetitive Member Factor
Cfu 1.05 Flat Use Design Factor, NDS Supplement
F'b2 λ KF_Fb ϕb Fb CM_Fb Ct CF_Fb Ci Cr Cfu 1754.298 psi fb2 My Sy
0.348 ksi
Combined Interaction Equation:
Axial Capacity Term:
fc F'c
2 fb1
F'b1 1
FcE1
= 0.601 See Tedds output
Minor Axis Bending Term:
fb2
F'b2 1
FcE2 fb1 FbE
0.204
Combined Interaction Equation:
0.601 fb2
F'b2 1
FcE2 fb1 FbE
0.805 NDS Equation 3.9-3
A single 6x8 No. 1 Douglas Fir (south) is acceptable for the design forces for all wood skid beams.
Wood Beam Interaction 11/22/2023 8:41 AM
2-40
AECOM PROJECT NO.
60667208
SUBJECT/FEATURE:
HVAC SUPPORT
NARC JOB NO.
K21007
Calc By:
S.Ruybal
Date:
4/25/2024
Checked By:
F. Macias-Wallis
Date:
5/1/2024
2.6 Design Anchorage between AC Isolator and Sleeper
2-41
SUBJECT/FEATURE: __HVAC Support________________________________
AC Curb to 6x8 Anchorage Design Caluclate the size and minimum number of anchors between the AC equipment curb and the new wood 6x8 skid members.
Design Parameters:
AC Curb Reactions:
The factored max shear = 0.523 klf; factored max tension = 0.046 klf + moment calculated previously that is spread along a 6.85ft curb
Vu 0.523klf Design shear per foot of curb
Tu 0.046klf( ) 6.85ft( )[ ] 27.472kip ft
79in
4.488 kip Design tension along 1 new wood skid member
Design Calculations:
Use Tedds to check lateral forces on wood and bolts per foot of curb, see next sheets Check combined lateral and withdrawal n 2 Number of lag screws per foot of curb nmin ceil n ft
6.85 ft
14 Minimum number of lag screws per wood skid member
Vu_s Vu 6.85 ft nmin
0.256 kip Design shear per bolt
Tu_s Tu nmin
0.321 kip Design tension per bolt
Curb to 6x8.xmcd 4/24/2024 4:42 PM
2-42
4/24/24
Job Ref.
60667208 Section
AC Curb to 6x8
Calc. by
S. Ruybal Date
11/21/2023 Chk'd by
F. Macias- Date
11/27/2023
LAG SCREW TIMBER TO STEEL CONNECTION DESIGN
In accordance with NDS 2018 Tedds calculation version 1.2.04
Design results summary Unit Required Provided Utilization Result
Connection capacity lbs 341 420 0.812 PASS
P
Main member
Connected member tm ts
Main timber member details Species of main member Douglas Fir-South Size of main member (Table 1B) 6 x 8 Number of main member Nm = 1 Thickness of main member tm = 5.500 in Angle of load to grain of main member m = 90
Connected steel member details Number of connected steel member Ns = 1 Connected steel member thickness ts = 0.250 in Number of interfaces Nint = (Nm + Ns) – 1 = 1
Lag screw details Lag screw diameter (Table L2) 5/8'' Lag screw root diameter of threaded portion Dr = 0.471 in Length of lag screw L = 5.000 in Washer thickness W = 0.125 in Number of rows of lag screw R = 1 Number of columns of lag screw C = 1
2-43
Job Ref.
60667208 Section
AC Curb to 6x8
Calc. by
S. Ruybal Date
11/21/2023 Chk'd by
F. Macias- Date
11/27/2023
Total number of lag screw Ntotal = R C = 1
Applied load Applied load to the connection P = 341 lb
Dowel bearing length (main) (12.3.5) Size of tapered tip E = 0.406 in Actual penetration in main member Pact = L - W - ts = 4.625 in Dowel bearing length in main member lm = 4.422 in
Dowel bearing length (connected) (12.3.5) Dowel bearing length in connected member ls = ts = 0.250 in
Bending yield strength (lag screw) (Table 12J to 12K footnote no. 2) Bending yield strength of lag screw Fyb = 45000 psi
Dowel bearing strength (main member) (Table 12.3.3 footnote no. 2) Dowel bearing strength parallel to grain Fe_par = 11200 Gm 1 psi = 5152 psi
Dowel bearing strength perpendicular to grain Fe_perp = 6100 Gm1.45 1 psi / (D / 1 in) = 2503 psi
Dowel bearing strength for small dia. fasteners Fe = 16600 Gm1.84 1 psi = 3977 psi
Dowel bearing strength at an angle of load to grain Fem = (Fe_par Fe_perp) / ((Fe_par (sin(m))2) + (Fe_perp (cos(m))2)) Fem = 2503 psi Dowel bearing strength of main member Fem = 2503 psi
Dowel bearing strength (connected steel member) (Table 12K footnote no. 2) Dowel bearing strength of connected member Fes = 87000 psi
Preliminary yield limit equation coefficients (Table 12.3.1A notes) Dowel bearing strength ratio Re = Fem / Fes = 0.029 Dowel bearing length ratio Rt = lm / ls = 17.688 Preliminary yield limit equation coefficient k1 k1 = (((Re+(2Re2(1+Rt+Rt2))+(Rt2Re3)))-(Re(1+Rt)))/(1+Re) k1 = 0.221 Preliminary yield limit equation coefficient k2 k2 = -1+((2(1+Re))+((2Fyb(1+(2Re))Dr2))/(3Femlm2)) k2 = 0.484 Preliminary yield limit equation coefficient k3 k3 = -1+(((2(1+Re))/Re)+((2Fyb(2+Re)Dr2))/(3Femls2)) k3= 11.564 Angle of load to grain coefficient k k = 1 + (0.25 max (m, s) / 90) = 1.250 Reduction term (Table 12.3.1B) KD = 3.00
Yield limit equations (single shear) Mode Im (eq. 12.3-1) ZIm = (Dr lm Fem) / (4 k) = 1042 lb
Mode Is (eq. 12.3-2) ZIs = (Dr ls Fes) / (4 k) = 2049 lb
Mode II (eq. 12.3-3) ZII = (k1 Dr ls Fes) / (3.6 k) = 503 lb
Mode IIIm (eq. 12.3-4) ZIIIm = (k2 Dr lm Fem) / ((1 + (2 Re)) 3.2 k) = 596 lb
Mode IIIs (eq. 12.3-5) ZIIIs = (k3 Dr ls Fem) / ((2 + Re) 3.2 k) = 420 lb
Mode IV (eq. 12.3-6) ZIV = (Dr 2 (((2 Fem Fyb) / (3 (1 + Re))))) / (3.2 k) = 474 lb Z = min (ZIm, ZIs,ZII, ZIIIm, ZIIIs, ZIV) = 420 lb Nominal capacity of single fastener Z = 420 lb
2-44
Job Ref.
60667208 Section
AC Curb to 6x8
Calc. by
S. Ruybal Date
11/21/2023 Chk'd by
F. Macias- Date
11/27/2023
Slenderness (Table 12.5.1C footnote no.1) Slenderness l / D = 7.075
Spacing requirements (perpendicular to grain loading)
End distance (Table 12.5.1A) End distance (full stregnth) aq_full = 4 D = 2.500 in End distance (minimum) aq_min = 2 D = 1.250 in End distance (actual) aq = 3.500 in
Edge distance (Table 12.5.1C) Loaded edge eq = 4 D = 2.500 in Unloaded edge ep = 1.5 D = 0.938 in
Geometry factor C (12.5.1) End distance (actual) aq = 3.500 in End distance (full strength) aq_full = 2.500 in Geometry factor for end distance C = min(1,aq / aq_full) = 1.00
Adjustment factor Load duration factor (Table 2.3.2) CD = 1.00 Wet service factor (Table 11.3.3) CM = 1.0 Temperature factor (Table 11.3.4) Ct = 1.0 Group action factor (eq. 11.3-1) Cg = 1.0 Geometry factor (12.5.1) C = 1.00 End grain factor (12.5.2) Ceg = 1.0 Diaphragm factor (12.5.3) Cdi = 1.0 Toe nail factor (12.5.4) Ctn = 1.0
Total capacity of connection Capacity of connection Z’ = Z Ntotal Nint CD CM C= 420 lb P / Z' = 0.812
Design result
2-45
AECOM PROJECT NO.
60667208
SUBJECT/FEATURE:
HVAC SUPPORT
NARC JOB NO.
K21007
Calc By:
S.Ruybal
Date:
4/25/2024
Checked By:
F. Macias-Wallis
Date:
5/1/2024
2.7 Design Anchorage between Fan and Sleeper
2-47
SUBJECT/FEATURE: __HVAC Support________________________________
CALC. BY:_S. Ruybal_ DATE :__4/24/24
CHECKED BY:_F. Macias-Wallis_ DATE :_5/1/24 _
Exhaust Fan Anchorage Equipment Dimensions:
LEF 35.5625in Length of Exhaust Fan
BEF 22.3125in Width of Exhaust Fan hEF 30.5in Height of Exhaust Fan
Reference: Flat Blade Centrifugal Blower Clockwise Top Horizontal Arrangement 10, Class I page 1 of 8
Dead Loads:
wtEF 250lbf Weight of each exhaust fan unit, drawing 254-2101-M601
DLEF
wtEF
0.063 kip DL on each corner of each exhaust fan
Calculate Wind Forces on Equipment:
qz 15.3psf Velocity pressure: Velocity pressure calculated for stair tower design
G 0.85 Gust effect factor: Gust effect factor from Section 26.11 of ASCE 7
Cf_AC_check hEF min LEF BEF 1.367
Cf 1.0 Force Coefficient, ASCE 7 Figure 29.4-1
Af hEF max LEF BEF 7.532 ft2
Fw qz G Cf Af 0.098 kip Design wind force, Equation 29.4-1 ASCE 7
WindEF Fw
0.024 kip Design wind force at each corner of each equipment
Exhaust Fan Loads.xmcd 4/24/2024 5:02 PM
2-48
SUBJECT/FEATURE: __HVAC Support________________________________
Calculate Seismic Forces on Equipment:
ap 2.5 Component amplification factor; ASCE 7 Table 13.6-1 for air conditioning units
SDS 1.0 Spectral acceleration, ATC Hazards for Seismic in Appendix of stair tower calculation
Ip 1.0 Component importance factor, ASCE 7 Section 13.1.3
Wp wtEF 0.25 kip Component operating weight
Rp 6 ASCE 7 Table 13.6-1 for air conditioning units z 1 Height of structure of point of attachment for roof-mount h 1 Average roof height of structure
Fp_1
0.4 ap SDS
0.5 Seismic design force, equation 13.3-1 ASCE 7
Fp_max 1.6 SDS Ip 1.6 Max seismic design force, equation 13.3-2 ASCE 7
Fp_min 0.3 SDS Ip 0.3 Min seismic design force, equation 13.3-2 ASCE 7
Fp Fp_1 Wp 0.125 kip Seismic horizontal design force
Fp_EF Fp
0.031 kip Seismic horizontal design force at each corner of each exhaust fan
Meq hEF Fp 0.212 kip ft Moment about horizontal axis due to seismic, assumes vertical center of gravity of equipment is 2/3 the height of the unit
Feq Meq min LEF BEF
0.114 kip Vertical force due to seismic moment
Exhaust Fan Loads.xmcd 4/24/2024 5:02 PM
2-49
SUBJECT/FEATURE: __HVAC Support________________________________
Feq_EF Feq
0.028 kip Vertical force due to seismic moment at each corner of each exhaust fan
Ev 0.2 SDS Wp 0.05 kip Vertical seismic force, section 13.3.1.2 of ASCE 7
Ev_EF Ev
0.013 kip Vertical seismic force at each corner of each exhaust fan
Load Summary:
DL Equipment (kip)
Vertical Seismic Ev (kip)
Horizontal Seismic Fp (kip)
Vertical Seismic Feq (kip)
Each Corner of Exhaust Fan 0.063 0.013 0.031 0.028
Design Anchorage to 6x8
Vu Fp_EF 0.031 kip Design shear per bolt
Tu Feq_EF Ev_EF 0.041 kip Design tension per bolt
Because the design shear and tension values are << than those of the AC bolt design shear and tension, by inspection, (1) 1/2" dia x 5" long lag screw is OK at each corner
Exhaust Fan Loads.xmcd 4/24/2024 5:07 PM
2-50
AECOM PROJECT NO.
60667208
SUBJECT/FEATURE:
HVAC SUPPORT
NARC JOB NO.
K21007
Calc By:
S.Ruybal
Date:
4/25/2024
Checked By:
F. Macias-Wallis
Date:
5/1/2024
2.8 Design Anchorage between Sleepers and Existing Roof Beams
2-51
Job Ref.
60667208 Section
Sleeper to 8x16 Anchorage
Calc. by
S. Ruybal Date
4/24/2024 Chk'd by
F. Macias- Date
5/1/2024
LAG SCREW TIMBER TO STEEL CONNECTION DESIGN
In accordance with NDS 2018 Tedds calculation version 1.2.04
Design results summary Unit Required Provided Utilization Result
Connection capacity lbs 3000 3413 0.879 PASS
P Main member
Connected member tm ts m
Main timber member details Species of main member Douglas Fir-South Size of main member (Table 1B) 8 x 16 Number of main member Nm = 1 Thickness of main member tm = 7.500 in Angle of load to grain of main member m = 45
Connected steel member details Number of connected steel member Ns = 2…