A5-1f BP1_DWG2026-0430_11_FIRE-PROTECTION_IHS-Whiteriver-Hospital_BID-ADD-C.pdf
PDF 646 KB Posted
- Attached to
- Whiteriver Hospital Construction
- Solicitation number
- 75H70126R00016
About this file
This is a Fire Suppression Abbreviations and Symbols drawing (Sheet FP0.1) for the IHS Whiteriver Hospital project located at 200 W Hospital Drive, Whiteriver, Arizona 85941. The document is part of the final construction documents issued January 23, 2026, with a bid addendum dated May 14, 2026. The IHS Project Number is 131445 and the IHS Contract Number is 75H70123R00008, with an award date of February 2, 2024.
The scope of work requires a complete hydraulically-calculated automatic sprinkler system throughout the project area, including fire pump, backflow preventer assembly, zone control assemblies, water flow alarm switches, valve supervisory switches, check valves, control valves, piping, hangers, sprinklers, and all associated equipment and appurtenances. All work must conform to applicable building and fire codes and NFPA 13, 14, 20, 22, 70, and 72. The system design specifies a wet pipe sprinkler system in all heated spaces and dry pipe systems with heat trace piping in areas exposed to freezing temperatures. Design criteria vary by occupancy: Light Hazard areas require 0.10 GPM per square foot over 1500 square feet with 100 GPM hose allowance over 30 minutes; Ordinary Hazard areas require 0.15-0.20 GPM per square foot over 1500 square feet with 250 GPM hose allowance over 60 minutes; and Extra Hazard areas require 0.30-0.40 GPM per square foot over 2500 square feet with 500 GPM hose allowance over 90 minutes. The fire pump must deliver 1000 GPM at 115 PSI with 150 horsepower capacity, supported by a jockey pump delivering 10 GPM at 125 PSI. Water supply will be provided by two 325,000-gallon storage tanks providing 650,000 gallons total capacity, with static pressure of 108 PSI and flowing pressure of 86 PSI at 1500 GPM into the fire pump room. The heliport suppression system requires 240.1 GPM at 0.1 GPM per square foot over a 10-minute duration with nozzles sized at K-factor 4.55 and 26.25-foot coverage. All equipment must bear UL listing labels and be installed per manufacturer instructions and applicable codes. Hydrostatic testing must be witnessed by the engineer and authority having jurisdiction before ceiling closeout, with forward flow testing also required. The contractor must obtain fire hydrant flow test data no more than 12 months prior to shop drawing submittal, coordinate all work with other trades, perform all core-drilling with proper verification to prevent structural damage, maintain proper clearances and alignment, provide UL-listed penetration seal assemblies at all wall and floor penetrations, and obtain all required permits and licenses.
View the file
Other files
Show 40 more
Latest 50 of 107 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
FS
TS
ZCA
A
N
A
AP
1. SCOPE OF WORK: PROVIDE A COMPLETE HYDRAULICALLY- CALCULATED AUTOMATIC SPRINKLER SYSTEM THROUGHOUT THE AREA OF WORK, INCLUDING BUT NOT LIMITED TO FIRE PUMP, BACKFLOW PREVENTER ASSEMBLY, ZONE CONTROL ASSEMBLIES, WATER FLOW ALARM SWITCHES, VALVE SUPERVISORY SWITCHES, CHECK VALVES, CONTROL VALVES, PIPING, HANGERS, SPRINKLERS, ALL ASSOCIATED EQUIPMENT, WIRING AND APPURTENANCES, NORMALLY AND CUSTOMARILY REQUIRED, WHETHER INDICATED OR INHERENTLY NECESSARY DUE TO THE NATURE OF THE WORK, FOR A COMPLETE AND
OPERATIONAL SYSTEM.
2. ALL WORK SHALL CONFORM TO THE APPLICABLE PROVISIONS OF THE APPLICABLE BUILDING AND FIRE CODES AND THE REFERENCED EDITIONS OF NFPA 13, 14, 20, 22, 70 AND 72.
3. WHERE ANY CONFLICT AND/OR DISCREPANCY BETWEEN THESE GENERAL NOTES AND ANY OTHER INFORMATION CONTAINED IN THE CONTRACT DOCUMENTS EXISTS, THE MORE STRINGENT REQUIREMENT SHALL PREVAIL AND BE A REQUIREMENT OF THE WORK. THAT NOTWITHSTANDING, ANY SUCH CONFLICT AND/OR DISCREPANCY SHALL PROMPTLY BE BROUGHT TO THE ATTENTION OF THE OWNER, ARCHITECT
AND ENGINEER.
4. A WET PIPE SPRINKLER SYSTEM SHALL BE INSTALLED IN ALL HEATED SPACES. DRY PIPE SYSTEM AND HEAT TRACE PIPING WILL BE INSTALLED IN ALL SPACES REQUIRING A SPRINKLER(S) WHERE EXPOSED TO
FREEZING TEMPERATURES.
5. THE TERM “PROVIDE” SHALL MEAN FURNISH, INSTALL AND CONNECT EQUIPMENT/DEVICE FOR A COMPLETE AND OPERATIONAL SYSTEM. THE TERM “REMOVE” SHALL MEAN DISCONNECT AND CLEAR EQUIPMENT/DEVICE FROM SITE, AS WELL AS MAINTAINING UPSTREAM AND DOWNSTREAM EQUIPMENT/DEVICES AS REQUIRED.
6. THE CONTRACT DOCUMENTS ARE DIAGRAMMATIC AND INTENDED TO SHOW DESIGN INTENT ONLY. RUN ALL PIPING STRAIGHT AND TIGHT TO THE FACE OF STRUCTURAL MEMBERS AND WALLS, PARALLEL AND AT
RIGHT ANGLES TO STRUCTURAL STEEL OR CONCRETE ELEMENTS.
7. CONTRACTOR SHALL FIELD VERIFY ALL CONDITIONS AND DIMENSIONS ON DRAWINGS PRIOR TO EXECUTION OF THIS CONTRACT. IT SHALL BE THE RESPONSIBILITY OF CONTRACTOR TO VERIFY JOB CONDITIONS AND COORDINATE ALL SYSTEM COMPONENTS. CONTRACTOR SHALL REPORT ANY DISCREPANCIES WITH THESE DRAWINGS TO THE ENGINEER IMMEDIATELY.
8. COORDINATE ALL WORK AND AVOID ALL CONFLICTS WITH LIGHTING FIXTURES, DIFFUSERS, GRILLS, DUCTS, STRUCTURAL MEMBERS, PIPES AND OTHER OBSTRUCTIONS.
9. NO STRUCTURAL MEMBERS SHALL BE CUT, DRILLED OR BURNED UNLESS PREVIOUSLY APPROVED BY THE STRUCTURAL ENGINEER. FURTHER, ANY APPROVED CUTTING OR PATCHING OF ANY STRUCTURAL WORK SHALL NOT RESULT IN A REDUCTION OF LOAD-CARRYING AND/OR LOAD-DEFLECTION RATIO. PRIOR TO SUCH WORK, OBTAIN APPROVAL FROM THE ENGINEER OF RECORD. INSTALLATION OF PIPING SHALL
FOLLOW REQUIRMENTS OF NFPA 13 18.4.9.
10. ALL WALL AND FLOOR PENETRATIONS SHALL BE CORE-DRILLED. PROVIDE PIPE SLEEVES FOR WALL AND FLOOR PENETRATIONS AS INDICATED IN THE SPECIFICATIONS. ALL PENETRATIONS IN WALLS, CEILINGS AND FLOORS SHALL BE PROVIDED WITH A UL-LISTED PENETRATION SEAL ASSEMBLY, WITH A FIRE RATING EQUIVALENT TO OR GREATER THAN THE FIRE RATING OF THE BARRIER PENETRATED STAIRWAY, SHAFT ENCLOSURES, AND FLOOR SLABS SHALL BE CONSIDERED 2-HOUR FIRE RESISTIVE RATED CONSTRUCTION UNLESS OTHERWISE NOTED.
11. PRIOR TO CORE DRILLING, CONTRACTOR SHALL VERIFY EXISTING CONDITION NOT TO DAMAGE ANY STRUCTURAL ELEMENT, CONDUIT, REBAR, AND ETC. ANY DAMAGE RESULTING FROM THE WORK, WHETHER INTENTIONAL OR NOT, SHALL BE REPAIRED AT NO ADDITIONAL COST TO, AND TO THE SATISFACTION OF THE OWNER.
12. ALL DAMAGE TO WALLS, CEILINGS, FLOORS, AND STRUCTURAL MEMBERS FROM THE WORK SHALL BE PATCHED, REPAIRED AND PAINTED WITH NEW MATERIALS TO MATCH ADJACENT WORK, WHETHER
SPECIFICALLY NOTED OR NOT.
13. WHERE POSSIBLE, SPRINKLERS SHALL BE ALIGNED WITH OTHER SPRINKLERS INSTALLED IN THE SAME ROOM OR AREA.
14. AS A MINIMUM, MAINTAIN 6-FT 8-INCH HEAD ROOM CLEARANCE BETWEEN BOTTOM OF SPRINKLER PIPE AND FINISHED FLOOR, INCLUDING STAIRWELLS.
15. CONTRACTOR SHALL PAY ALL REQUIRED FEES AND OBTAIN ALL NECESSARY PERMITS AND LICENSES FOR INSTALLATION OF THE WORK.
16. COORDINATE AND SEQUENCE THE WORK PRIOR TO FABRICATION AND INSTALLATION OF EQUIPMENT. MAKE NECESSARY ACCOMMODATIONS TO MEET THE INTENT OF THE DRAWINGS AND ENSURE A
COORDINATED INSTALLATION.
17. RUN ALL EXPOSED ELEMENTS NEATLY, TIGHT TO THE STRUCTURE (EXCEPT WHERE NOTED), PARALLEL TO WALLS, AND AS INCONSPICUOUSLY AS POSSIBLE.
18. INSTALL ALL CEILING SPRINKLERS IN 2 FT X 2 FT ACOUSTICAL PANEL CEILINGS IN THE CENTER OF THE PANELS; AND IN 2 FT X 4 FT PANELS, INSTALL DEVICE IN THE CENTER OF THE 2 FT X 4 FT OR 2 FT X 2 FT
SQUARE AREAS.
19. PROVIDE SPRINKLER(S) UNDER ALL OBSTRUCTIONS GREATER THAN 48 INCHES IN WIDTH AND AS NEEDED TO PROVIDE PROPER COVERAGE AS REQUIRED BY NFPA 13.
20. PROVIDE LISTED GUARDS FOR SPRINKLER PROTECTION WHEN INSTALLED BELOW 7 FT AFF.
21. CONTRACTOR SHALL PROVIDE AN AUTOMATIC AIR VENTING DEVICE NEAR THE HIGHEST POINT WET PIPE SPRINKLER SYSTEM(S) PER NFPA 13.
22. CONTRACTOR SHALL PROVIDE AUXILIARY LOW POINT DRAINS WHERE REQUIRED PER NFPA 13. WHERE AUXILIARY DRAINS ARE INSTALLED BEHIND HARD CEILINGS, PROVIDE AN ACCESSIBLE PANEL DIRECTLY
BENEATH THE DRAIN.
23. CONTRACTOR SHALL OBTAIN DATA FROM A WATER FLOW TEST CONDUCTED NO MORE THAN 12 MONTHS PRIOR TO SHOP DRAWING PLAN SUBMITTAL TO AUTHORITY HAVING JURISDICTION (AHJ). WATER FLOW
TEST SHALL BE PERFORMED IN ACCORANCE WITH NFPA 291.
24. ALL EQUIPMENT SHALL BEAR UL LISTING LABEL AT MINIMUM, OR IF UL LABEL IS NOT AVAILABLE, THE ITEM SHALL BE TESTED AND LABELED BY A NATIONALLY RECOGNIZED TESTING AGENCY THAT MEETS UL AND AHJ REQUIREMENTS FOR TESTING FACILITIES. ALL EQUIPMENT SHALL BE INSTALLED PER THE LISTING AND MANUFACTURER'S INSTALLATION INSTRUCTIONS.
25. SPRINKLER SYSTEM WATERFLOW AND CONTROL VALVE SUPERVISORY SWITCHES SHALL BE MONITORED BY BUILDING FIRE ALARM SYSTEM. COORDINATE WITH FIRE ALARM CONTRACTOR SO THAT ELECTRICAL
CONNECTION CAN BE MADE BETWEEN THESE DEVICES AND BUILDING FIRE ALARM SYSTEM.
26. CONTRACTOR SHALL TAKE NECESSARY MEASURES TO KEEP THE PREMISES DRY AT ALL TIMES AND PREVENT WATER DAMAGE TO SURFACES. REPAIR WATER DAMAGE RESULTING FROM THE WORK, WHETHER INTENTIONAL OR NOT, AT NO ADDITIONAL COST TO, AND TO THE SATISFACTION OF THE OWNER.
27. CONTRACTOR SHALL COORDINATE WITH OWNER TO AVOID FREEZING CONDITIONS DURING CONSTRUCTION ONCE WATER IS FILLED IN THE SPRINKLER SYSTEM.
28. HYDROSTATIC TESTING OF FIRE SUPPRESSION SYSTEMS SHALL BE WITNESSED BY ENGINEER AND/OR AHJ, BEFORE CEILING CLOSE IN. CONTRACTOR SHALL COORDINATE WITH ENGINEER AND/OR AHJ PRIOR TO
TESTING.
29. CONTRACTOR SHALL CONDUCT FORWARD FLOW TESTING AND THE TESTING SHALL BE WITNESSED BY ENGINEER AND/OR AUTHORITY HAVING JURISDICTION.
30. PROVIDE DRAINS REQUIRED BY APPLICABLE CODES, WHETHER INDICATED IN THESE PLANS OR NOT. DISCHARGE ALL DRAINS TO THE EXTERIOR, UNLESS NOTED OTHERWISE.
A. DISCHARGE DRAINS AT SIX INCHES ABOVE FINISHED GRADE. PROVIDE A CONCRETE SPLASH-BLOCK, WITH MINIMUM DIMENSIONS OF TWO FEET BY TWO FEET, AT EACH DRAIN.
31. PROVIDE PRINTED METAL OR ENGRAVED PLASTIC NAMEPLATES TO IDENTIFY FUNCTION OF ALL ISOLATION VALVES, DRAIN VALVES, AND OTHER FIRE PROTECTION SYSTEM EQUIPMENT. PERMANENTLY AFFIX TO VALVE BODY OR HANG WITH CHAIN. CONCEALED COMPONENTS SHALL ADDITIONALLY HAVE PRINTED METAL OR ENGRAVED PLASTIC NAMEPLATES IDENTIFYING THE COMPONENT LOCATION AND FUNCTION PERMANENTLY AFFIXED TO ACCESS PANEL DOORS OR THE CEILING GRID WHERE THE COMPONENT IS ACCESSED.
32. REFER TO CIVIL DRAWINGS REGARDING FIRE PROTECTION WATER TANK STORAGE DESIGN. REFER TO CIVIL PLANS FOR WATER TANK, HYDRANT AND WATER MAIN LOCATIONS.
SECTION NUMBER
KEY NOTE
DEMO KEY NOTE
MXXX
DRAWING NUMBER WHERE DRAWN
E0.1
NEW FIRE PROTECTION PIPING
EXISTING FIRE PROTECTION PIPING TO REMAIN
NEW FIRE PROTECTION PIPING - UNDERGROUND
RECESSED PENDENT SPRINKLER
CONCEALED SPRINKLER
PENDENT SPRINKLER
SIDEWALL SPRINKLER
UPRIGHT SPRINKLER
ELBOW
CAP OR PLUG
TEE
TEE DOWN
ELBOW - TURNED DOWN
PIPE CONTINUATION
CONCENTRIC REDUCER
ECCENTRIC REDUCER
OS&Y VALVE
CHECK VALVE
BUTTERFLY VALVE
ALARM CHECK VALVE
DRY PIPE VALVE
PREACTION VALVE
DELUGE VALVE
PRESSURE REDUCING VALVE
PRESSURE RELIEF VALVE
GATE VALVE - NON RISING STEM
WALL MOUNTED POST INDICATOR VALVE
BACKFLOW PREVENTER ASSEMBLY
FIRE PUMP
JOCKEY PUMP
PUMP/BACKFLOW TEST CONNECTION, WALL MOUNTED
PUMP/BACKFLOW TEST CONNECTION, FREESTANDING
FIRE PUMP FLOW METER
ZONE CONTROL ASSEMBLY CONSISTING OF CHECK VALVE, BUTTERFLY VALVE, PRESSURE
GAGE, WATER FLOW SWITCH, VALVE SUPERVISORY SWITCH, PRESSURE RELIEF VALVE, AND
INSPECTORS TEST AND DRAIN.
2.5" FIRE HOSE VALVE CONNECTION
2.5" FIRE HOSE VALVE IN CABINET
HOSE STATION
WATER FLOW SWITCH
VALVE SUPERVISORY SWITCH
AIR PRESSURE SWITCH
INSPECTOR'S TEST CONNECTION
AIR COMPRESSOR
NITROGEN GENERATOR
RISER MOUNTED AIR COMPRESSOR
POINT OF CONNECTION
HYDRAULIC CALCULATION AREA
HYDRAULIC NODE
FDC, WALL MOUNTED
FDC, FREESTANDING
PRESSURE GAUGE
WATER MOTOR GONG
1. FIRE HYDRANT FLOW TEST DATA
a. DATE TEST WAS PERFORMED: APRIL 22, 2024 AT 9:35AM
b. PERFORMED BY: FLOYD VAUGHAN – AZ. FLOW TESTING, LLC
c. PRESSURE HYDRANT:
i. LOCATION: SOUTH-SOUTHEAST CORNER OF PROJECT SITE TO THE NORTH OF APACHE CIRCLE.
ii. OUTLET ELEVATION(FT): 5449
iii. STATIC PRESSURE (PSI): 74
iv. RESIDUAL PRESSURE (PSI): 39
d. FLOW HYDRANT:
i. LOCATION: SOUTHWEST CORNER OF PROJECT SITE TO THE NORTH OF APACHE CIRCLE.
ii. FLOW (GPM): 1407
e. FLOW (GPM) AT 20 PSI: 1778
f. HIGH HGL ELEVATION (FT): 5449 (PRESSURE HYDRANT)
g. LOW HGL ELEVATION (FT): 5447 (FLOW HYDRANT)
2. NEW FIRE WATER STORAGE TANKS ARE BEING ADDED. WATER STORAGE TANK WATER SUPPLY DATA WILL BE USED FOR THE FIRE PROTECTION DESIGN. EXPECTED MEASURMENTS FOR NEW TANKS PROVIDED BY
DIBBLE CORP 2025-08-12:
a. STATIC PRESSURE INTO FIRE PUMP ROOM FROM TANKS (PSI): 108
b. PRESSURE INTO FIRE PUMP ROOM WHILE TANKS ARE FLOWING 1500 GPM (PSI): 86
c. TANK CAPACITY: TWO 325,000 GAL TANKS FOR A TOTAL CAPACITY OF 650,000 GAL.
d. ELEVATIONS:
• HOSPITAL LEVEL 1 FF (FT): 5430.00
• BOTTOM OF TANK (FT): 5650.00
• TANK OUTLET ELEVATION (FT): 5650.66
• TOP OF TANK (FT): 5681.50
*PRESSURE REGULATION FOR BUILDING WATER SUPPLY WILL BE DONE THROUGH A MASTER PRESSURE REDUCING ASSEMBLY LOCATED IN THE FIRE PUMP ROOM.
3. SPRINKLER SYSTEM DESIGN CRITERIA:
a. LIGHT HAZARD OCCUPANCY -
ALL AREAS ARE LIGHT HAZARD UNLESS OTHERWISE NOTED.
b. ORDINARY HAZARD OCCUPANCY -
LOADING DOCK, STORAGE AREAS, MECHANICAL AND ELECTRIC ROOMS AND SIMILAR AREAS WHERE STOCKPILES OF COMBUSTIBLE MATERIALS DO NOT EXCEED 8'-0".
c. EXTRA HAZARD OCCUPANCY -
STORAGE AREAS INCLUDING WHERE DESIGN CRITERIA REQUIRES ENHANCED PROTECTION, AND AREAS STORING PLASTICS EXCEEDING 5FT.
*ALL AREAS SHALL BE CLASSIFIED IN ACCORDANCE WITH NFPA 13.4.3
4. SYSTEM PROTECTION AREA LIMITATIONS:
a. THE MAXIMUM FLOOR AREA ON ANY ONE FLOOR TO BE PROTECTED BY SPRINKLERS SUPPLIED BY ANY ONE SPRINKLER RISER OR COMBINED SYSTEM SHALL BE 52,000 SQ FT FOR LIGHT AND ORDINARY
HAZARD, AND 40,000 SQ FT FOR EXTRA HAZARD.
b. THERE IS NO LIMIT TO THE NUMBER OF FLOORS THAT CAN BE PROTECTED BY A SINGLE RISER, BECAUSE EACH FLOOR IS CONSIDERED A SEPARATE FIRE AREA.
c. SPRINKLER SYSTEM ZONES SHALL ALIGN WITH SMOKE COMPARTMENTS AS REQUIRED BY 2024 NFPA 99 16.9.1.3 AND 2012 NFPA 99 15.8.1.2.
5. SPRINKLER DESIGN DENSITIES/DEMAND CRITERIA/HOSE REQUIRMENTS/SUPPLY DURATION:
a. LIGHT HAZARD - 0.10 GPM PER SQ FT OVER THE HYDRAULICALLY MOST REMOTE 1500 SQ FT. TOTAL COMBINED INSIDE AND OUTSIDE HOSE ALLOWANCE 100 GPM OVER 30 MINUTES.
b. ORDINARY HAZARD 1 - 0.15 GPM PER SQ FT OVER THE HYDRAULICALLY MOST REMOTE 1500 SQ FT. TOTAL COMBINED INSIDE AND OUTSIDE HOSE ALLOWANCE 250 GPM OVER 60 MINUTES.
c. ORDINARY HAZARD 2 - 0.20 GPM PER SQ FT OVER THE HYDRAULICALLY MOST REMOTE 1500 SQ FT. TOTAL COMBINED INSIDE AND OUTSIDE HOSE ALLOWANCE 250 GPM OVER 60 MINUTES.
d. EXTRA HAZARD 1 - 0.30 GPM PER SQ FT OVER THE HYDRAULICALLY MOST REMOTE 2500 SQ FT. TOTAL COMBINED INSIDE AND OUTSIDE HOSE ALLOWANCE 500 GPM OVER 90 MINUTES.
d. EXTRA HAZARD 2 - 0.40 GPM PER SQ FT OVER THE HYDRAULICALLY MOST REMOTE 2500 SQ FT. TOTAL COMBINED INSIDE AND OUTSIDE HOSE ALLOWANCE 500 GPM OVER 90 MINUTES.
*DRY PIPE SYSTEMS AREA OF SPRINKLER OPERATION SHALL BE INCREASED BY 30% AS ALLOWED BY NFPA 13 19.2.3.2.5.
6. STANDPIPE DESIGN CRITERIA:
a. DESIGN IN ACCORDANCE WITH NFPA 14 FOR CLASS I SYSTEMS, THE MINIMUM FLOW RATE FOR HYDRAULICALLY MOST REMOTE STANDPIPE SHALL BE 500 GPM. THE MINIMUM FLOW RATE FOR ADDITIONAL
STANDPIPES SHALL BE 500 GPM PER STANDPIPE, WITH THE TOTAL NOT TO EXCEED 1000 GPM.
b. FOR COMBINED SYSTEMS WITH AN APPROVED AUTOMATIC SPRINKLER SYSTEM, A SEPARATE SPRINKLER DEMAND IS NOT REQUIRED, AND THE SYSTEM SHALL NOT BE REQUIRED TO EXCEED 1000 GPM.
7. FIRE PUMP DESIGN CRITERIA:
a. DESIGN IN ACCORDANCE WITH NFPA 20
b. THE FIRE PUMP MUST MEET THE FOLLOWING REQUIREMENTS:
i. EACH PUMP MUST BE CAPABLE OF WITHSTANDING A HYDROSTATIC PRESSURE OF TWICE THE MAXIMUM PRESSURE.
ii. PUMPS MUST FURNISH NOT LESS THEN 150% OF THE RATED HEAD AT 65% OF THE RATED PRESSURE (SHUT-OFF NOT TO EXCEED 120% OF THE RATED PRESSURE)
iii. THE MAXIMUM PUMP BRAKE HORSEPOWER MUST NOT EXCEED THE RATING OF THE PARTICULAR DRIVER.
iv. POWER MUST BE UNINTERRUPTIBLE WITH THE PROPER PROTECTION CABLING AND EMERGENCY POWER. ALARMS SHOULD SOUND IF NORMAL IS INTERRUPTED.
v. A JOCKEY PUMP WITH IT'S OWN CONTROL PANEL IS REQUIRED.
c. FIRE PUMP PERFORMANCE REQUIRMENTS:
i. PRESSURE: 115 PSI
ii. FLOW: 1000 GPM
iii. HORSEPOWER: 150 HP
d. JOCKEY PUMP PERFORMANCE REQUIRMENTS:
i. PRESSURE: 125 PSI
ii. FLOW: 10 GPM
iii. HORSEPOWER: 1.5
8. HELIPORT SUPPRESSION (NFPA 418, CAP 1264)
a. HELIDECK DIAMETER: 49 FT
b. TOTAL PROTECTED AREA: 2401 FT
c. APPLICATION RATE: 0.1 GPM/FT2
d. MINIMUM APPLICATION RATE ON HELIDECK: 0.1*2401 = 240.1 GPM
e. DURATION OF PROTECTION: 10 MIN
f. NOZZLE COVERAGE: 26.25 FT
g. NOZZLE "K" FACTOR: 4.55
h. HOSE REEL FLOW RATE: 100 GPM
i. HOSE REEL PRESSURE: 100 PSI
OCCUPANCY CLASSIFICATION...............................LIGHT HAZARD
DESIGN DENSITY.......................................................0.10 GPM/SF
REMOTE HYDRAULIC AREA ....................................1500SF
OCCUPANCY CLASSIFICATION...............................ORDINARY HAZARD 1
DESIGN DENSITY......................................................0.15GPM/SF
REMOTE HYDRAULIC AREA ....................................1500SF
OCCUPANCY CLASSIFICATION...............................ORDINARY HAZARD 2
DESIGN DENSITY.......................................................0.20 GPM/SF
REMOTE HYDRAULIC AREA ....................................1500SF
OCCUPANCY CLASSIFICATION...............................EXTRA HAZARD 1
DESIGN DENSITY......................................................0.3GPM/SF
REMOTE HYDRAULIC AREA ....................................2500SF
OCCUPANCY CLASSIFICATION...............................EXTRA HAZARD 2
DESIGN DENSITY.......................................................0.40 GPM/SF
REMOTE HYDRAULIC AREA ....................................2500SF
NFPA 13 HAZARD CLASSIFICATION
SHEET NUMBER
PROJECT NUMBER
SEALS AND SIGNATURES
ISSUED FOR DATE
NOT FOR
CONSTRUCTION
P lo t D at e:
IHS Whiteriver Hospital
200 W Hospital Drive Whiteriver, Arizona, 85941
IHS Project #: 131445 IHS Contract #: 75H70123R00008 IHS Award Date: 02/02/2024
455 NORTH THIRD STREET
SUITE 250
PHOENIX, AZ 85004
602.265.2200 smithgroup.com
Drawn By: Checked By:
BASED ON PROGRAM OF REQUIREMENTS DATED [03/26/22],
POR AMENDMENT DATED [02/03/25], AND ON SCHEMATIC
DRAWINGS APPROVED [11/19/24].
5/
/2
2:
:1
P
M
FIRE SUPPRESSION
ABBREVIATIONS AND
SYMBOLS
FP0.1CD
M U
R R
A Y
14094
MURRAY OCHSANKEHL
FIRE SUPPRESSION ABBREVIATIONS
REFRENCE SYMBOLS
FIRE SUPPRESSION LEGENDS AND SYMBOLS FIRE SUPPRESSION GENERAL NOTES
FIRE SUPPRESSION DESIGN PARAMETERS
SPRINKLER HAZARD CLASSIFICATION CRITERIA
(A)
A AMPERES
AC ALTERNATING CURRENT
AF AMPERE FRAME (BREAKER RATING)
AFC ABOVE FINISHED COUNTER
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
AHU AIR HANDLING UNIT
AIC AMPERE INTERRUPTING CAPACITY
ALT ALTERNATE
ARCH ARCHITECT
AT AMPERES TRIP
ATS AUTOMATIC TRANSFER SWITCH
AUTO AUTOMATIC
AUX AUXILIARY
AWG AMERICAN WIRE GAUGE
(B)
BLDG BUILDING
BRKR, BKR BREAKER
(C)
C CONDUIT
CATV CABLE TELEVISION
CB CIRCUIT BREAKER
CCTV CLOSED CIRCUIT TELEVISION
CKT CIRCUIT
CLG CEILING
COM, COMM COMMUNICATIONS
COTR CONTRACTING OFFICER'S TECHNICAL REPRESENTATITIVE
CP CONTROL PANEL
CPT CONTROL POWER TRANSFORMER
CT CURRENT TRANSFORMER
CU COPPER
(D)
DC DIRECT CURRENT
DISC DISCONNECT
DIST DISTRIBUTION
DIV DIVISION
DN DOWN
DP DISTRIBUTION PANEL
DPDT DOUBLE POLE DOUBLE THROW
DPST DOUBLE POLE SINGLE THROW
DWG DRAWING
(E)
E, EX, EXIST EXISTING
EG EQUIPMENT GROUND
ELEC ELECTRIC, ELECTRICAL
ELEV ELEVATOR
EM, EMERG EMERGENCY
EMT ELECTRIC METALLIC CONDUIT
ENCL ENCLOSURE
EQ, EQUIP EQUIPMENT
EWC ELECTRIC WATER COOLER
EWH ELECTRIC WATER HEATER
(F)
F FUSE
FA FIRE ALARM
FAAP FIRE ALARM ANNUNCIATOR PANEL
FACP FIRE ALARM CONTROL PANEL
FC FOOT CANDLE
FDR FEEDER
FL, FLR FLOOR
FLA FULL LOAD AMPS
FLEX FLEXIBLE
FLUOR FLUORESCENT
FT FOOT/FEET (')
NAC FIRE ALARM EXTENDER PANEL
(G)
G, GND, GRD GROUND
GEN GENERATOR
GFI GROUND FAULT INTERRUPTER
(H)
H HORIZONTAL MOUNTING
HH HAND HOLE
HOA HAND-OFF-AUTOMATIC
HP HORSEPOWER
HPS HIGH PRESSURE SODIUM
HR HOUR
HT HEIGHT
HTR HEATER
HVAC HEATING VENTILATION AND AIR CONDITIONING
HZ HERTZ
(I)
IG ISOLATED GROUND
IN INCH/INCHES (")
INCAND INCANDESCENT
(J)
JB, JBOX JUNCTION BOX
(K)
K KEY INTERLOCK
Kcmil 1000 CIRCULAR mils
KV KILOVOLTS (THOUSAND VOLTS)
KVA KILOVOLTS-AMPERES (THOUSAND VOLT-AMPS)
kW KILOWATTS (THOUSAND WATTS)
KWH KILOWATT-HOURS
(L)
L-G LINE TO GROUND
L-L LINE TO LINE
L-N LINE TO NEUTRAL
LA LIGHTNING ARRESTOR
LAN LOCAL AREA NETWORK
LC, LCP LIGHTING CONTROL PANEL
LP LIGHTING PANEL
LSI LONG-TIME, SHORT-TIME, INSTANTANEOUS
LSIA LONG-TIME, SHORT-TIME, INSTANTANEOUS,
GROUND-FAULT ALARM ONLY
LSIG LONG-TIME, SHORT-TIME, INSTANTANEOUS,
GROUND-FAULT
LTG LIGHTING
LV LOW VOLTAGE (BELOW 50 VOLTS)
(M)
MCA MINIMUM CIRCUIT AMPACITY
MCB MAIN CIRCUIT BREAKER
MCC MOTOR CONTROL CENTER
MECH MECHANICAL
MFR MANUFACTURER
MH MANHOLE
MIN MINIMUM
MISC MISCELLANEOUS
MLO MAIN LUGS ONLY
MOCP MAXIMUM OVERCURRENT PROTECTION
MTD MOUNTED
MTG MOUNTING
MTS MANUAL TRANSFER SWITCH
MV MEDIUM VOLTAGE (OVER 600V LESS THAN 35KV)
(N)
N NEUTRAL
NC NORMALLY CLOSED
NEC NATIONAL ELECTRICAL CODE
NEMA NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION
NIC NOT IN CONTRACT
NO NORMALLY OPEN
NO., NUM, # NUMBER
NTS NOT TO SCALE
(O)
OC ON CENTER
OCPD OVERCURRENT PROTECTION DEVICE
OFCI OWNER FURNISHED, CONTRACTOR INSTALLED
OFOI OWNER FURNISHED, OWNER INSTALLED
OH OVERHEAD
OHE/T OVERHEAD ELECTRIC/TELEPHONE
OPP OPPOSITE
(P)
P POLE
PA PUBLIC ADDRESS
PB PULL BOX
PDP POWER DISTRIBUTION PANEL
PE PHOTO ELECTRIC
PF POWER FACTOR
PH, Ø PHASE
PNL PANEL
PRI PRIMARY
PT POTENTIAL TRANSFORMER
PVC POLYVINYL CHLORIDE
PWR POWER
(Q)
QTY QUANTITY
(R)
R, RE RELOCATE AS SHOWN
RCLP REMOTE CONTROL LIGHTING PANEL
RCPT RECEPTACLE
REF REFRIGERATOR
RF RADIO FREQUENCY
RLA RATED (RUNNING) LOAD AMPS
RM ROOM
RP RECEPTACLE PANELBOARD
RSC RIGID STEEL CONDUIT
(S)
SCH, SCHED SCHEDULE
SEC SECONDARY
SF SQUARE FOOT
SPD SURGE PROTECTIVE DEVICE
SPDT SINGLE POLE DOUBLE THROW
SPEC(S) SPECIFICATION(S)
SPKR SPEAKER
SPST SINGLE POLE SINGLE THROW
STD STANDARD
SW SWITCH
SWBD SWITCHBOARD
SWGR SWITCHGEAR
SYM SYMMETRICAL
(T)
TB TERMINAL BLOCK
TBB TELEPHONE BACKBOARD
TC TIME CLOCK
TEL, TELE TELEPHONE
TELECOM TELECOMMUNICATIONS
TP TAMPERPROOF
TV TELEVISION
TYP TYPICAL
(U)
UG UNDERGROUND
UGP UNDERGROUND PRIMARY
UGS UNDERGROUND SECONDARY
UGT UNDERGROUND TELEPHONE
UL UNDERWRITER'S LABORATORY
UON UNLESS OTHERWISE NOTED
UPS UNINTERRUPTIBLE POWER SUPPLY
(V)
V VOLTS
VA VOLT-AMPERES
VFD VARIABLE FREQUENCY DRIVE/
VARIABLE FREQUENCY MOTOR
CONTROLLER
(W)
W WIRE
W/ WITH
W/O WITHOUT
WHM WATT HOUR METER
WP, W.P. WEATHERPROOF
(X)
X REMOVE DEVICE
XFMR TRANSFORMER
(Z)
% Z PERCENT IMPEDANCE
FIRE FLOW CALCULATIONS
FIRE FLOW DEMAND:
THE CONSTRUCTION TYPE OF THE BUILDING PER NFPA 220 IS TYPE II (222); THEREFORE, THE FIRE FLOW CALCULATION AREA SHALL BE THE TOTAL AREA OF THE THREE LARGEST SUCCESSIVE FLOORS. A 75% REDUCTION IN FIRE FLOW IS PERMITTED PER NFPA 1 18.4.4.3.2 SINCE THE BUILDING IS PROTECTED THROUGHOUT BY AN APPROVED AUTOMATIC SPRINKLER SYSTEM.
AREA OF THREE LARGEST LEVELS INCLUDING BUILDING OVERHANGS: 346,375 SF
LEVEL 1: 111,173 SF
LEVEL 2: 143,935 SF
LEVEL 3: 91,267 SF
MINIMUM FIRE FLOW RATE AND DURATION PER NFPA 1 TABLE 18.4.4.2.1: 6000 GPM FOR 4 HOURS MINIMUM FIRE FLOW RATE AND DURATION UTILIZING THE 75% REDUCTION: 1500 GPM FOR 2 HOURS
FIRE HYDRANT REQUIRMENTS (NFPA 1 18.5):
MINIMUM NUMBER OF HYDRANTS PER NFPA 1 TABLE 18.5.4.3: 1 HYDRANT
NUMBER OF HYDRANTS PROVIDED FOR THE SITE: 9 HYDRANTS
MAXIMUM DISTANCE BETWEEN FIRE HYDRANTS: 500 FT
MAXIMUM DISTANCE FROM CLOSEST POINT ON THE BUILDING: 400 FT
C
FINAL CONSTRUCTION DOCUMENTS 23JAN26
BID ADDENDUM-C 14MAY26
May 14, 2026 lnigam Rectangle lnigam Image lnigam Text Box May 14, 2026
FP0.1 - FIRE SUPPRESSION ABBREVIATIONS AND SYMBOLS