A7-1f BP2_DWG2026-0528_16_ICT_IHS-Whiteriver-WWTP_BID-ADD-E.pdf
PDF 282 KB Posted
- Attached to
- Whiteriver Hospital Construction
- Solicitation number
- 75H70126R00016
About this file
These are technical design and specification documents for Information Communication Technology (ICT) and Security Systems at IHS Whiteriver Hospital in Arizona. The documents establish design intent, installation requirements, and contractor responsibilities for a utility campus construction project (Building Package 2).
The ICT specifications require contractors to install Category 6A telecommunications cabling, conduit infrastructure with pull strings, and various audiovisual and technology devices as detailed in the technology legends. Key infrastructure requirements include routing conduit to nearest accessible ceilings, utilizing J-hooks to cable trays, providing firestopping at fire-rated penetrations, coordinating device locations with architectural elevations, and ensuring 6-inch separation between back-to-back junction boxes with acoustical putty pads for sound transmission prevention. Contractors must coordinate with all building trades to avoid conflicts with mechanical, electrical, plumbing, and structural elements. Installation methods must comply with manufacturer recommendations, local codes, and industry standards. The Security Systems specifications similarly require contractors to mount devices flush to recessed back boxes with concealed conduit, route conduit to nearest accessible ceilings, provide pull strings with sequential footage marking, and comply with bonding and grounding requirements. Flexible conduit is prohibited in both systems. The project is based on a Program of Requirements dated March 26, 2022, amended February 3, 2025, with schematic drawings approved November 19, 2024. The IHS Contract Number is 75H70123R00008 with an award date of February 2, 2024.
View the file
Other files
Show 40 more
Latest 50 of 107 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
A.
B.
C.
D.
E.
F.
G.
H.
THE ICT DRAWINGS ARE A SUBSET OF THE CONSTRUCTION PACKAGE. REFER TO THE COMPLETE DRAWING PACKAGE AND SPECIFICATIONS TO DETERMINE THE COMPLETE PROJECT SCOPE, GENERAL REQUIREMENTS, PRODUCT SPECIFICATIONS, AND
INSTALLATION REQUIREMENTS.
THE DRAWINGS REPRESENT THE ICT DESIGN INTENT AND ARE SCHEMATIC AND DIAGRAMMATICAL. THE SPECIFICATIONS ESTABLISH MINIMUM PERFORMANCE AND PRODUCT INSTALLATION REQUIREMENTS. PROVIDE NECESSARY EQUIPMENT AND ACCESSORIES FOR FULLY FUNCTIONAL SYSTEMS MEETING DESIGN INTENT AND OWNER REQUIREMENTS WHETHER EXPRESSLY SPECIFIED OR NOT. INSTALLATION METHODS MUST BE CONSISTENT WITH THE DESIGN INTENT, MANUFACTURER.
RECOMMENDATIONS, AND ALL LOCAL CODES AND REGULATIONS NECESSARY FOR COMPLETE AND OPERATIONAL ICT SYSTEMS.
THE ARCHITECTURAL DRAWINGS ESTABLISH AND GOVERN THE FINAL FINISHED APPEARANCES AND LOCATION OF THE EXPOSED WORK OF ALL TRADES. REFER TO ARCHITECTURAL DRAWINGS FOR ALL DEVICE MOUNTING REQUIREMENTS AND RULES, UON.
COORDINATE ALL DEVICE LOCATIONS AND MOUNTING HEIGHTS WITH ARCHITECTURAL DRAWINGS PRIOR TO ROUGH-IN.
COORDINATE THE INSTALLATION OF ICT SYSTEMS WITH ALL OTHER TRADES TO AVOID INTERFERENCES WITH PIPING, DUCTWORK, MECHANICAL EQUIPMENT, STRUCTURAL MEMBERS, FURNITURE, AND ALL OTHER GENERAL BUILDING CONSTRUCTION.
REFER TO ELECTRICAL DRAWINGS FOR POWER CIRCUIT REQUIREMENTS SERVING THE ICT SYSTEMS.
PROVIDE FIRESTOPPING AT ALL PENETRATIONS OF FIRE-RATED FLOOR AND WALL ASSEMBLIES, IN ACCORDANCE WITH REQUIREMENTS OF PROJECT FIRESTOPPING SPECIFICATION. ALL BACK BOXES MOUNTED WITHIN FIRE RATED PARTITIONS SHALL
MEET THE FIRE RATING OF THE PARTITION, AS REQUIRED BY CODE.
CONTRACTOR TO FIELD VERIFY ALL UTILITY DATA REQUIREMENTS AND TERMINATION LOCATIONS PER FINAL EQUIPMENT SELECTIONS. SEE PLANS FOR LOCATIONS AND QUANTITIES COORDINATION DURING DESIGN. THIS INCLUDES BUT IS NOT LIMITED TO MECHANICAL, ELECTRICAL, PLUMBING, MEDICAL EQUIPMENT, PNEUMATIC TUBE, FIRE ALARM/FIRE PROTECTION, ETC.
DEVICE ELEVATIONS SHOWN ARE FOR REFERENCE ONLY. CONTRACTOR TO REFER TO ARCHITECTURAL ELEVATIONS A0.3 AND OTHERS AS REQUIRED. CONTRACTOR TO COORDINATE FINAL DEVICE ROUGH-IN WITH ARCHITECTURAL AND OTHER TRADES AS
REQUIRED.
ICT GENERAL NOTES
SECTION NUMBER
KEY NOTETXXX
DETAIL NUMBER
DRAWING NUMBER WHERE DRAWN
DRAWING NUMBER WHERE DRAWN
T0.1
DEMO KEY NOTETDXX
A.
B.
C.
D.
E.
F.
G.
H.
I.
J.
K.
L.
M.
N.
O.
P.
Q.
THE MAKE AND MODEL OF INFRASTRUCTURE DEVICES IN THE TECHNOLOGY LEGENDS HAVE BEEN LISTED TO ESTABLISH THE DESIRED LEVEL OF QUALITY AND PERFORMANCE FOR EACH DEVICE. THE INSTALLING CONTRACTOR MAY PROPOSE SUBSTITUTION OF THESE DEVICES WITH EQUIVALENT PRODUCT BY OTHER MANUFACTURERS PER SPECIFICATIONS, UON.
FURNITURE LAYOUTS ARE FOR REFERENCE ONLY. COORDINATE THE FINAL LOCATION OF DEVICES AND OUTLETS WITH ARCHITECT, OWNER AND FINAL APPROVED FURNITURE PLANS PRIOR TO INSTALLATION. PROVIDE ALL INTERCONNECTING WIRING, FITTINGS, AND HARDWARE REQUIRED FOR A COMPLETE INSTALLATION, EVEN IF NOT EXPLICITLY SHOWN ON PLANS.
TO AVOID SOUND TRANSMISSION THROUGH WALLS, RECESSED JUNCTION BOXES ON OPPOSITE SIDES OF ANY WALL SHALL NOT BE MOUNTED BACK-TO-BACK. PROVIDE A MINIMUM OF 6 INCHES OF SEPARATION BETWEEN BOXES AND PROVIDE ACOUSTICAL PUTTY
PADS AROUND THE BOX.
INFRASTRUCTURE SPECIFIED WITH MOUNTING ELEVATIONS ARE TO CENTERLINE OF BOX, UON. WHERE BOXES WITH DIFFERENT MOUNTING HEIGHTS ARE LOCATED IN THE SAME AREA ALIGN BOXES VERTICALLY AND HORIZONTALLY THROUGH THEIR CENTERLINES, UON. BOXES WHICH ARE NOT ALIGNED PROPERLY SHALL BE RELOCATED AS REQUIRED TO MEET ALIGNMENT REQUIREMENTS AT NO COST TO THE OWNER. THIS INCLUDES DEVICES INSTALLED BY OTHER TRADES.
MOUNT DEVICES FLUSH TO RECESSED BACK BOX WITH CONCEALED CONDUIT, UON ON THE DRAWINGS.
PROVIDE COVERS FOR ALL FLOOR BOXES, JUNCTION BOXES, AND PULL BOXES, AND COORDINATE THE COVER COLOR AND FINISH WITH THE ARCHITECT. INSTALL RAISED COVER WITH DEPTH THAT MATCHES THE WALL THICKNESS.
FURNISH ALL FLOOR BOXES, JUNCTION BOXES, AND PULL BOXES WITH KNOCKOUTS FOR REQUIRED CONDUIT. WHEN MOUNTING JUNCTION BOXES AND PULL BOXES AT OR ABOVE THE FINISHED CEILING LEVEL, ORIENT THE BOXES WITH THEIR OPEN SIDE
FACING DOWNWARD.
THE CONDUIT PATHS SHOWN IN THE DRAWINGS ARE FOR ILLUSTRATIVE PURPOSES ONLY. ACTUAL CONDUIT ROUTES SHOULD ADHERE TO THE SHORTEST FEASIBLE ROUTE WHILE ADHERING TO INDUSTRY STANDARDS AND BEST PRACTICES.
STUB ALL CONDUITS FOR AUDIOVISUAL SYSTEMS TO NEAREST ACCESSIBLE CEILING WITHIN THE SAME ROOM, UON.
ROUTE TO NEAREST TERMINATION LOCATION.
ENSURE THAT ALL CONDUIT INSTALLATIONS INCLUDE A PULL STRING WITH SEQUENTIAL FOOTAGE MARKING.
REAM AND FIT THREADED INSULATION BUSHING ON ALL CONDUIT ENDS.
FLEXIBLE CONDUIT IS NOT ALLOWED, UON.
WHEN PULLING CABLES INTO CONDUITS AND/OR SLEEVES, FULLY UTILIZE ONE CONDUIT BEFORE MOVING TO THE NEXT TO INCREASE UTILIZATION EFFICIENCY AND FUTURE FLEXIBILITY OF SPARE CONDUITS/SLEEVES. ADHERE TO FILL REQUIREMENTS
PER INSTANCE.
ALL TELECOMMUNICATIONS CABLING SHALL BE CATEGORY 6A AND RATED FOR THE ENVIRONMENT IN WHICH IT IS INSTALLED UON.
SEE DIVISION 27 SPECIFICATIONS FOR ADDITIONAL INFORMATION.
ANY INFRASTRUCTURE BACKBOX OR DEVICE THAT IS LOCATED IN AN OPEN CEILING ENVIRONMENT, CONTRACTOR TO INSTALL CONDUIT AS SPECIFIED FROM THE BACKBOX TO CABLE TRAY OR NEAREST ACCESSIBLE CEILING TO ALLOW CABLING TO BE CONCEALED IN THE CONDUIT IN AN OPEN CEILING ENVIRONMENT AND HOMERUN TO THE SERVING TELECOMMUNICATIONS ROOM.
PROVIDE PASS-THROUGH SLEEVES THROUGH WALLS EXTENDING TO THE DECK WHERE REQUIRED. SLEEVES SHALL BE APPROPRIATELY SIZED TO ACCOMMODATE TELECOM CABLING AS REQUIRED. ENSURE SLEEVES INCLUDE BUSHINGS ON BOTH
ENDS AND COMPLY WITH FIRESTOPPING REQUIREMENTS FOR RATED ASSEMBLIES.
ICT INFRASTRUCTURE NOTES
REFERENCE DESIGN BINDER 4 IHS WHITERIVER TECHNOLOGY SCOPE RESPONSIBILITY
MATRIX.
ICT CONTRACTOR RESPONSIBILITY MATRIX
WALL MOUNT TELECOMMUNICATION OUTLET -
SLASH INDICATES MOUNTING ABOVE FINISH
COUNTER
TELECOM CABLE QTY
WALL MOUNT TELECOMMUNICATION OUTLETXX-#
TYPICAL WALL MOUNT TELECOMMUNICATIONS OUTLET
SPECIAL WALL MOUNT TELECOMMUNICATIONS OUTLET
TELECOM CABLE QTY
SYMBOL TYPE
CEILING MOUNT TELECOMMUNICATIONS OUTLET
A - MOUNT ABOVE FINISHED CEILING
F - MOUNT FLUSH TO FINISHED CEILING
S - MOUNT TO STRUCTURE/DECK
SPECIAL CEILING MOUNT TELECOMMUNICATIONS OUTLET
XX-X-#
TELECOM CABLE QTY
SYMBOL TYPE
CEILING TYPE
ICT SYMBOLS
XX
ICT MULTISERVICE FLOOR MOUNT DEVICE
FLOOR MOUNT MULTISERVICE OUTLET
#TELECOM
CABLE QTY
SYMBOL TYPE
XX
ICT MULTISERVICE WALL MOUNT DEVICE
WALL MOUNT MULTISERVICE OUTLET
#TELECOM
CABLE QTY
SYMBOL TYPE
XX
ICT MULTISERVICE CEILING MOUNT DEVICE
CEILING MOUNT MULTISERVICE OUTLET
#TELECOM
CABLE QTY
SYMBOL TYPE
XX
ICT FLOOR MOUNT DEVICE
FLOOR MOUNT DEVICE
SYMBOL TYPE
XX
ICT WALL MOUNT DEVICE
WALL MOUNT DEVICE
SYMBOL TYPE
XX
ICT CEILING MOUNT DEVICE
SYMBOL TYPE
CEILING MOUNT DEVICE
A - MOUNT ABOVE FINISHED CEILING
F - MOUNT FLUSH TO FINISHED CEILING
S - MOUNT TO STRUCTURE/DECK
CEILING TYPE
X
XX
ICT AV CEILING MOUNT EQUIPMENT
CEILING MOUNT AV EQUIPMENT TO BE PROVIDED AND INSTALLED BY AVC
C - CAMERA
M - MICROPHONE
S - LOUDSPEAKERSYMBOL TYPE
A.
B.
C.
D.
THE PURPOSE OF THIS SHEET IS TO ILLUSTRATE AND DEFINE TYPICAL GRAPHIC SYMBOLS WHICH MAY TYPICALLY OCCUR ON THE ICT
DRAWINGS.
THIS SHEET MAY ILLUSTRATE ABBREVIATIONS, SYMBOLS AND LEGENDS WHICH DO NOT OCCUR AS PART OF THIS PROJECT. REFER TO
THE DRAWINGS TO DETERMINE WHICH ITEMS APPLY TO THE WORK OF THIS PROJECT.
ADDITIONAL SYMBOLS NOT SHOWN OR DEFINED ON THIS SHEET MAY BE USED ON THE ICT DRAWINGS AND ARE TYPICALLY DEFINED ON
OTHER SHEETS.
SYMBOLS ARE NOT DRAWN TO SCALE. TO DETERMINE THE ACTUAL SIZES OF ELEMENTS REPRESENTED BY SYMBOLS, REFER TO THE
SPECIFICATIONS AND OTHER SHEETS, AS MAY APPLY.
SHEET NUMBER
PROJECT NUMBER
SEALS AND SIGNATURES
ISSUED FOR DATE
Pl ot
Da te:
IHS Whiteriver Hospital 200 W Hospital Drive Whiteriver, Arizona, 85941
IHS Project #: 131445 IHS Contract #: 75H70123R00008 IHS Award Date: 02/02/2024
455 NORTH THIRD STREET
SUITE 250
PHOENIX, AZ 85004
602.265.2200 smithgroup.com
Drawn By: Checked By:
BASED ON PROGRAM OF REQUIREMENTS DATED [ 03/26/22],
POR AMENDMENT DATED [ 02/03/25], AND ON SCHEMATIC
DRAWINGS APPROVED [11/19/24].
BUILDING PACKAGE 2 (BP2)
UTILITY CAMPUS -
WHITERIVER FACILITY
5/2 8/2
6 2
:24 :22
P M
ICT ABBREVIATIONS AND
SYMBOLS
T0.1BP2
Vo llm er
14904 Vollmer Foster
ICT ABBREVIATIONS ICT DEVICE SCHEDULES
REFERENCE SYMBOLS
ALL ABBREVIATIONS, SYMBOLS AND LEGENDS SHOWN ON THIS DRAWING ARE NOT NECESSARILY USED.
# NUMBER
+ #" MOUNTING HEIGHTS ARE TO CENTERLINE
OF DEVICE ABOVE FINISHED FLOOR OR
FINISHED GRADE
(A)
AC ALTERNATING CURRENT
ADA AMERICAN WITH DISABILITIES ACT
ADJ ADJACENT
AFC ABOVE FINISHED CEILING
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
AFS ABOVE FINISHED SLAB
AHJ AUTHORITY HAVING JURISDICTION
ALT ALTERNATE
ARCH ARCHITECT
AUX AUXILIARY
AV AUDIOVISUAL
AVC AUDIOVISUAL CONTRACTOR
AWG AMERICAN WIRE GAUGE
A AMPERES
(B)
BLDG BUILDING
B BURIED
BET BUILDING ENTRANCE TERMINAL
BD BLACK DROP
(C)
CA CABLE
CAB CABINET
CH CASE HEIGHT
CW CASE WIDTH
CD CASE DEPTH
CAT CATALOG
CATV CABLE TELEVISION
CCTV CLOSED CIRCUIT TELEVISION
CL CENTERLINE
CLG CEILING
COAX COAXIAL CABLING
COMM COMMUNICATIONS
C CONDUIT
(D)
D DEPTH
DC DIRECT CURRENT
DIST DISTRIBUTION
DIV DIVISION
DN DOWN
DWG(S) DRAWING(S)
DWGS DRAWINGS
(E)
EMT ELECTRICAL METALLIC TUBING
ENCL ENCLOSURE
EC ELECTRICAL CONTRACTOR
EF ENTRANCE FACILITY
EST ESTIMATE
EQ EQUIPMENT
(E), E, EX, EXIST EXISTING
ESS ELECTRONIC SECURITY SYSTEMS
(F)
FACP FIRE ALARM CONTROL PANEL
FC FOOT CANDLE
FLR FLOOR
FPD FLAT PANEL DISPLAY
FT FOOT/FEET (')
FURN FURNITURE
(G)
GC GENERAL CONTRACTOR
GND GROUND
GRC GALVANIZED RIGID CONDUIT
(H)
HH HANDHOLE
HT HEIGHT
(I)
ICT INFORMATION AND COMMUNICATIONS
TECHNOLOGY
IN INCH/INCHES (")
IW IMAGE WIDTH
IH IMAGE HEIGHT
IHAF IMAGE HEIGHT ABOVE FINISHED FLOOR
(J)
JB JUNCTION BOX
(K)
KO KNOCK OUT
(L)
L LENGTH, LONG
LAN LOCAL AREA NETWORK
LV LOW VOLTAGE (BELOW 50 VOLTS)
(M)
MH MANHOLE
MIC MICROPHONE
MTR MOTOR
MAX MAXIMUM
MFR MANUFACTURER
MIN MINIMUM
MISC MISCELLANEOUS
MTD MOUNTED
MTG MOUNTING
MTR MAIN TELECOMMUNICATIONS ROOM
(N)
NA NOT APPLICABLE
NEC NATIONAL ELECTRICAL CODE
NEMA NATIONAL ELECTRICAL MANUFACTURERS
ASSOCIATION
NIC NOT IN CONTRACT
NO., NUM. # NUMBER
NTS NOT TO SCALE
NC NURSE CALL
(O)
OC ON CENTER
OFCI OWNER FURNISHED, CONTRACTOR
INSTALLED
OFOI OWNER FURNISHED, OWNER INSTALLED
OPS OUTSIDE PLANT
(P)
PA PUBLIC ADDRESS
PB PULL BOX
PS POWER SUPPLY
PRJ PROJECTOR
PRS PROJECTION SCREEN
PWR POWER
(Q)
QTY QUANTITY
(R)
REQ'D REQUIRED
RF RADIO FREQUENCY
RFID RADIO FREQUENCY IDENTIFICATION
RSC RIGID STEEL CONDUIT
RE, (R) RELOCATE AS SHOWN
(S)
SC SECURITY CONTRACTOR
SCH, SCHED SCHEDULE
SF SQUARE FOOT
STP SHIELDED TWISTED PAIR
SPEC(S) SPECIFICATION(S)
STD STANDARD
(T)
TCC TELECOMMUNICATIONS CABLE
CONTRACTOR
TBD TO BE DETERMINED
TELECOM TELECOMMUNICATIONS
TYP TYPICAL
TR TELECOMMUNICATIONS ROOM
(U)
UG UNDERGROUND
UON UNLESS OTHERWISE NOTED
UPS UNINTERRUPTIBLE POWER SUPPLY
UTP UNSHIELDED TWISTED PAIR
(V)
V VOLTS
(W)
W/ WITH
W/O WITHOUT
WP WEATHERPROOF
WT WEIGHT
ICT TELECOM DEVICE SCHEDULE
SYMBOL TYPE DESCRIPTION BACKBOX MOUNTING
TELECOM
CONDUIT TELECOM CONDUIT NOTES
# (DATA) DATA OUTLET(S) DOUBLE-GANG 4-11/16" SQUARE BOX, RAISED ONE-DEVICE COVER PROJECT STANDARD OUTLET HEIGHT, REFER TO ARCH. DRAWINGS
(UON)
(1) 1 1/4" STUB TO NEAREST ACCESSIBLE CEILING, J-HOOK TO CABLE TRAY
AP-S-# CEILING ACCESS POINT DATA
OUTLET(S)
DOUBLE-GANG 4-11/16" SQUARE BOX, RAISED ONE-DEVICE COVER SURFACE MOUNT TO DECK (1) 1" STUB TO NEAREST ACCESSIBLE CEILING, J-HOOK TO CABLE TRAY
FO-# IN-FURNITURE DATA
OUTLET(S)
COORDINATE WITH FURNITURE IN FURNITURE PATHWAY
PROVIDED WITHIN
FURNITURE
STUB TO NEAREST ACCESSIBLE CEILING, J-HOOK TO CABLE TRAY
SC-# SECURITY CAMERA DATA
OUTLET(S)
DOUBLE-GANG 4-11/16" SQUARE BOX, RAISED ONE-DEVICE COVER
(UON)
WALL / 120" AFF (UON) (1) 1" STUB TO NEAREST ACCESSIBLE CEILING, J-HOOK TO CABLE TRAY
SC-S-# CEILING SECURITY CAMERA
DATA OUTLET(S)
DOUBLE-GANG 4-11/16" SQUARE BOX, RAISED ONE-DEVICE COVER SURFACE MOUNT TO DECK (1) 1" STUB TO NEAREST ACCESSIBLE CEILING, J-HOOK TO CABLE TRAY
SCP-# SECURITY DEVICE POLE
MOUNTED DATA OUTLET(S)
DOUBLE-GANG 4-11/16" SQUARE BOX, RAISED ONE-DEVICE COVER,
COORDINATE WITH POLE INSTALLATION REQUIREMENTS
COORDINATE WITH POLE MOUNTED SECURITY SYSTEM DEVICE
INSTALLATION REQUIREMENTS
(1) 2" CONDUIT TO ENTER BUILDING, STUB TO NEAREST ACCESSIBLE
CEILING, J-HOOK TO CABLE TRAY
ICT MULTISERVICE DEVICE SCHEDULE
SYMBOL TYPE DESCRIPTION BACKBOX MOUNTING AV CONDUIT AV CONDUIT NOTES
TELECOM
CONDUIT TELECOM CONDUIT NOTES
ELECTRICAL
POWER NOTES
FB30 FLOOR BOX W/ TELECOM
AND POWER
WIREMOLD EFBFF FLUSH WITH FINISHED FLOOR N/A N/A (1) 1 1/4" STUB TO NEAREST ACCESSIBLE CEILING (UON) DUPLEX - 20A/120V
SYMBOL SHEET NOTES
FINAL CONSTRUCTION DOCUMENTS 23JAN26
BID ADDENDUM-E 28MAY26
E
A.
B.
C.
D.
E.
F.
THE SECURITY DRAWINGS ARE A SUBSET OF THE
CONSTRUCTION PACKAGE. REFER TO THE COMPLETE
DRAWING PACKAGE AND SPECIFICATIONS TO DETERMINE THE
COMPLETE PROJECT SCOPE, GENERAL REQUIREMENTS,
PRODUCT SPECIFICATIONS, AND INSTALLATION
REQUIREMENTS.
THE DRAWINGS REPRESENT THE SECURITY DESIGN INTENT
AND ARE SCHEMATIC AND DIAGRAMMATICAL. THE
SPECIFICATIONS ESTABLISH MINIMUM PERFORMANCE AND
PRODUCT INSTALLATION REQUIREMENTS. PROVIDE
NECESSARY EQUIPMENT AND ACCESSORIES FOR FULLY
FUNCTIONAL SYSTEMS MEETING DESIGN INTENT AND OWNER
REQUIREMENTS WHETHER EXPRESSLY SPECIFIED OR NOT.
INSTALLATION METHODS MUST BE CONSISTENT WITH THE
DESIGN INTENT, MANUFACTURER RECOMMENDATIONS, AND
ALL LOCAL CODES AND REGULATIONS NECESSARY FOR
COMPLETE AND OPERATIONAL SECURITY SYSTEMS.
THE ARCHITECTURAL DRAWINGS ESTABLISH AND GOVERN THE
FINAL FINISHED APPEARANCES AND LOCATION OF THE
EXPOSED WORK OF ALL TRADES. REFER TO ARCHITECTURAL
DRAWINGS FOR ALL DEVICE MOUNTING REQUIREMENTS AND
RULES, UON. COORDINATE ALL DEVICE LOCATIONS AND
MOUNTING HEIGHTS WITH ARCHITECTURAL DRAWINGS PRIOR
TO ROUGH-IN.
COORDINATE THE INSTALLATION OF SECURITY SYSTEMS WITH
ALL OTHER TRADES TO AVOID INTERFERENCES WITH PIPING,
DUCTWORK, MECHANICAL EQUIPMENT, STRUCTURAL
MEMBERS, FURNITURE, AND ALL OTHER GENERAL BUILDING
CONSTRUCTION.
REFER TO ELECTRICAL DRAWINGS FOR POWER CIRCUIT
REQUIREMENTS SERVING THE SECURITY SYSTEMS.
PROVIDE FIRESTOPPING AT ALL PENETRATIONS OF FIRE-RATED
FLOOR AND WALL ASSEMBLIES, IN ACCORDANCE WITH
REQUIREMENTS OF PROJECT FIRESTOPPING SPECIFICATION.
ALL BACK BOXES MOUNTED WITHIN FIRE RATED PARTITIONS
SHALL MEET THE FIRE RATING OF THE PARTITION, AS
REQUIRED BY CODE.
SECURITY GENERAL NOTES
A.
B.
C.
D.
E.
F.
G.
H.
I.
MOUNT SECURITY DEVICES FLUSH TO RECESSED BACK BOX WITH
CONCEALED CONDUIT, UON ON THE DRAWINGS.
CONDUIT PATHS INDICATED ON DRAWINGS ARE DIAGRAMMATICAL
ONLY. CONDUIT ROUTES SHALL FOLLOW THE SHORTEST PATH
POSSIBLE WHILE COMPLYING WITH INDUSTRY STANDARDS AND
BEST PRACTICES.
ROUTE ALL SECURITY DEVICE CONDUITS TO THE NEAREST
ACCESSIBLE CEILING TO FACILITATE ROUTING TO TERMINATION
LOCATION.
ALL CONDUIT RUNS SHALL BE PROVIDED WITH A PULL STRING
WITH SEQUENTIAL FOOTAGE MARKING.
REAM AND FIT THREADED INSULATION BUSHING ON ALL CONDUIT
ENDS.
BOND TO GROUND ONE OR BOTH ENDS OF ALL CONDUITS IN
ACCORDANCE WITH NATIONAL AND LOCAL REGULATIONS.
FLEXIBLE CONDUIT IS NOT ALLOWED, UON.
REFER TO SECURITY DETAILS SHEETS FOR DOOR AND DEVICE
ROUGH-IN REQUIREMENTS.
CONFIRM AND COORDINATE SECURITY ACCESS CONTROL DOOR
CONDUIT ROUGH-IN REQUIREMENTS WITH DIV-08 DOOR
HARDWARE SPECIFICATION.
INFRASTRUCTURE NOTES
SECTION NUMBER
KEY NOTETYXX
DETAIL NUMBER
DRAWING NUMBER WHERE DRAWN
DRAWING NUMBER WHERE DRAWN
TY0.1
DEMO KEY NOTETDYX
SECURITY CONTRACTOR RESPONSIBILITY MATRIX
REFERENCE DESIGN BINDER 4 IHS WHITERIVER TECHNOLOGY SCOPE RESPONSIBILITY
MATRIX.
XX
WALL OR POLE MOUNTED CAMERA
CEILING MOUNT CAMERA
SECURITY DEVICE TYPE
WALL MOUNT DEVICE
CEILING MOUNT DEVICE
###-C# CAMERA ID #
###-# DEVICE ID #
BR BIOMETRIC READER
CR CARD READER
CRI CARD READER INTEGRATED LOCKSET
CRK CARD READER WITH KEYPAD
DC MONITORED DOOR CONTACT
EL ELECTRIFIED LOCK CONTROL
FCR FUTURE CARD READER, ROUGH-IN ONLY
IL INTERLOCKED DOORS
VTR VEHICLE TAG READER LONG RANGE
SECURITY SYMBOL KEY
SECURITY CAMERAS
SECURITY DOOR DEVICES
SECURITY DEVICES
SECURITY SYSTEM SYMBOLS
FIX IP CAMERA FIXED FOV
180 IP CAMERA 180° FOV
270 IP CAMERA 270° FOV
360 IP CAMERA 360° FOV
DUAL IP CAMERA DUAL FOV 180°
DUAL IP CAMERA DUAL FOV 90°
LPR IP CAMERA LICENSE PLATE RECOGNITION
PTZ IP CAMERA PAN-TILT-ZOOM
FIX
DUAL
DUAL
LPR
PTZ
LA LOCAL ALARM SOUNDER
KP ARMING KEYPAD
ACP ACCESS CONTROL PANEL
BP BADGE PRINTER
IDP INTRUSION DETECTION PANEL
NVR NETWORK VIDEO RECORDER
SMS SECURITY MANAGEMENT SYSTEM SERVER
UPS UNINTERRUPTIBLE POWER SUPPLY
VIM VIDEO INTERCOM MASTER STATION
ICM INTERCOM MASTER STATION
CS EMERGENCY CALL STATION - WALL MOUNT
CST EMERGENCY CALL STATION - TOWER STANCHION
GB GLASS BREAK DETECTOR -
CEILING MOUNT
MD MOTION DETECTOR - CEILING MOUNT
PB PANIC BUTTON
IC INTERCOM STATION
GB GLASS BREAK DETECTOR - WALL MOUNT
LD LOCKDOWN BUTTON
LD LOCKDOWN BUTTON - WALL MOUNT
MD MOTION DETECTOR - WALL MOUNT
PB PANIC BUTTON - WALL MOUNT
VI VIDEO INTERCOM STATION
VK VISITOR MANAGEMENT KIOSK
WS SECURITY WORKSTATION
SECURITY POWER SUPPLY
RB DOOR RELEASE BUTTON
PS
DB DURESS BUTTON
DB DURESS BUTTON - WALL MOUNT
A.
B.
C.
D.
THE PURPOSE OF THIS SHEET IS TO ILLUSTRATE AND DEFINE
TYPICAL GRAPHIC SYMBOLS WHICH MAY TYPICALLY OCCUR ON
THE ICT DRAWINGS.
THIS SHEET MAY ILLUSTRATE ABBREVIATIONS, SYMBOLS AND
LEGENDS WHICH DO NOT OCCUR AS PART OF THIS PROJECT.
REFER TO THE DRAWINGS TO DETERMINE WHICH ITEMS APPLY
TO THE WORK OF THIS PROJECT.
ADDITIONAL SYMBOLS NOT SHOWN OR DEFINED ON THIS
SHEET MAY BE USED ON THE ICT DRAWINGS AND ARE
TYPICALLY DEFINED ON OTHER SHEETS.
SYMBOLS ARE NOT DRAWN TO SCALE. TO DETERMINE THE
ACTUAL SIZES OF ELEMENTS REPRESENTED BY SYMBOLS,
REFER TO THE SPECIFICATIONS AND OTHER SHEETS, AS MAY
APPLY. SHEET NUMBER
PROJECT NUMBER
SEALS AND SIGNATURES
ISSUED FOR DATE
Pl ot
Da te:
IHS Whiteriver Hospital 200 W Hospital Drive Whiteriver, Arizona, 85941
IHS Project #: 131445 IHS Contract #: 75H70123R00008 IHS Award Date: 02/02/2024
455 NORTH THIRD STREET
SUITE 250
PHOENIX, AZ 85004
602.265.2200 smithgroup.com
Drawn By: Checked By:
BASED ON PROGRAM OF REQUIREMENTS DATED [ 03/26/22],
POR AMENDMENT DATED [ 02/03/25], AND ON SCHEMATIC
DRAWINGS APPROVED [11/19/24].
BUILDING PACKAGE 2 (BP2)
UTILITY CAMPUS -
WHITERIVER FACILITY
5/2 8/2
6 2
:28 :41
P M
SECURITY
ABBREVIATIONS AND
SYMBOLS
TY0.1BP2
Vo llm er
14904 Vollmer Foster
SECURITY SYSTEMS ABBREVIATIONS
REFERENCE SYMBOLS
ALL ABBREVIATIONS, SYMBOLS AND LEGENDS SHOWN ON THIS DRAWING ARE NOT NECESSARILY USED.
# NUMBER
+ #" MOUNTING HEIGHTS ARE TO CENTERLINE
OF DEVICE ABOVE FINISHED FLOOR OR
FINISHED GRADE
(A)
A AMPERES
AC ALTERNATING CURRENT
ADA AMERICAN WITH DISABILITIES ACT
ADJ ADJACENT
AFC ABOVE FINISHED CEILING
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
AFS ABOVE FINISHED SLAB
AHJ AUTHORITY HAVING JURISDICTION
ALT ALTERNATE
ARCH ARCHITECT
AUX AUXILIARY
AV AUDIOVISUAL
AVC AUDIOVISUAL CONTRACTOR
AWG AMERICAN WIRE GAUGE
(B)
B BURIED
BLDG BUILDING
BET BUILDING ENTRANCE TERMINAL
BD BLACK DROP
(C)
C CONDUIT
CA CABLE
CAB CABINET
CH CASE HEIGHT
CW CASE WIDTH
CD CASE DEPTH
CAT CATALOG
CATV CABLE TELEVISION
CCTV CLOSED CIRCUIT TELEVISION
CL CENTERLINE
CLG CEILING
COAX COAXIAL CABLING
COMM COMMUNICATIONS
(D)
D DEPTH
DC DIRECT CURRENT
DIST DISTRIBUTION
DIV DIVISION
DN DOWN
DWG(S) DRAWING(S)
DWGS DRAWINGS
(E)
EMT ELECTRICAL METALLIC TUBING
ENCL ENCLOSURE
EC ELECTRICAL CONTRACTOR
EF ENTRANCE FACILITY
EST ESTIMATE
EQ EQUIPMENT
(E), E, EX, EXIST EXISTING
ESS ELECTRONIC SECURITY SYSTEMS
(F)
FACP FIRE ALARM CONTROL PANEL
FC FOOT CANDLE
FLR FLOOR
FPD FLAT PANEL DISPLAY
FT FOOT/FEET (')
FURN FURNITURE
(G)
GC GENERAL CONTRACTOR
GND GROUND
GRC GALVANIZED RIGID CONDUIT
(H)
HH HANDHOLE
HT HEIGHT
(I)
ICT INFORMATION AND COMMUNICATIONS
TECHNOLOGY
IN INCH/INCHES (")
IW IMAGE WIDTH
IH IMAGE HEIGHT
IHAF IMAGE HEIGHT ABOVE FINISHED FLOOR
(J)
JB JUNCTION BOX
(K)
KO KNOCK OUT
(L)
L LENGTH, LONG
LAN LOCAL AREA NETWORK
LV LOW VOLTAGE (BELOW 50 VOLTS)
(M)
MH MANHOLE
MIC MICROPHONE
MTR MOTOR
MAX MAXIMUM
MFR MANUFACTURER
MIN MINIMUM
MISC MISCELLANEOUS
MTD MOUNTED
MTG MOUNTING
MTR MAIN TELECOMMUNICATIONS ROOM
(N)
NA NOT APPLICABLE
NEC NATIONAL ELECTRICAL CODE
NEMA NATIONAL ELECTRICAL MANUFACTURERS
ASSOCIATION
NIC NOT IN CONTRACT
NO., NUM. # NUMBER
NTS NOT TO SCALE
(O)
OC ON CENTER
OFCI OWNER FURNISHED, CONTRACTOR
INSTALLED
OFOI OWNER FURNISHED, OWNER INSTALLED
OPS OUTSIDE PLANT
(P)
PA PUBLIC ADDRESS
PB PULL BOX
PS POWER SUPPLY
PRJ PROJECTOR
PRS PROJECTION SCREEN
PWR POWER
(Q)
QTY QUANTITY
(R)
REQ'D REQUIRED
RF RADIO FREQUENCY
RFID RADIO FREQUENCY IDENTIFICATION
RSC RIGID STEEL CONDUIT
RE, (R) RELOCATE AS SHOWN
(S)
SC SECURITY CONTRACTOR
SCH, SCHED SCHEDULE
SF SQUARE FOOT
STP SHIELDED TWISTED PAIR
SPEC(S) SPECIFICATION(S)
STD STANDARD
(T)
TCC TELECOMMUNICATIONS CABLE
CONTRACTOR
TBD TO BE DETERMINED
TELECOM TELECOMMUNICATIONS
TYP TYPICAL
TR TELECOMMUNICATIONS ROOM
(U)
UG UNDERGROUND
UON UNLESS OTHERWISE NOTED
UPS UNINTERRUPTIBLE POWER SUPPLY
UTP UNSHIELDED TWISTED PAIR
(V)
V VOLTS
(W)
W/ WITH
W/O WITHOUT
WP WEATHERPROOF
WT WEIGHT
SYMBOL SHEET NOTES
FINAL CONSTRUCTION DOCUMENTS 23JAN26
BID ADDENDUM-E 28MAY26
E
| T0.1 - ICT ABBREVIATIONS AND SYMBOLS |
| TY0.1 - SECURITY ABBREVIATIONS AND SYMBOLS |