A7-1d BP1_DWG2026-0528_15_ELECTRICAL_IHS-Whiteriver-Hospital_BID-ADD-E.pdf
PDF 2 MB Posted
- Attached to
- Whiteriver Hospital Construction
- Solicitation number
- 75H70126R00016
About this file
This document is a set of electrical one-line diagrams for the IHS Whiteriver Hospital facility located at 200 W Hospital Drive, Whiteriver, Arizona 85941. The project is identified as IHS Project #131445 under IHS Contract #75H70123R00008, with an award date of February 2, 2024. The drawings were prepared by SmithGroup (455 North Third Street, Suite 250, Phoenix, AZ 85004) based on a Program of Requirements dated March 26, 2022, with a POR Amendment dated February 3, 2025, and schematic drawings approved November 19, 2024.
The electrical system design encompasses five main service configurations (SEE-A through SEE-E) with multiple distribution systems, panelboards, transformers, and associated electrical equipment. The base build scope includes only empty conduits for feeders shown with feeder tags, while the add alternate scope includes PV panels, carports, DC conductors, inverters, AC conductors, AC combiner boxes, and PV distribution boards. Key specifications include: voltage drop limits of less than 3% for branch circuits and 2% for feeders; Type 2 Surge Protective Devices (SPD) on all life safety and lighting panelboards; 4-pole automatic transfer switches with bypass isolation; UL891 switchboards for service entrance and distribution with draw-out molded case circuit breakers; UL1558 switchgear for generator paralleling; utility transformer coordination basis of 2500 kVA at 5% impedance; and coordination requirements with mechanical equipment and equipment installers prior to rough-in. The diagrams include detailed feeder schedules, sheet keynotes, and specifications for multiple transformers rated at 45 kVA to 112.5 kVA, along with solar photovoltaic systems featuring multiple 62.5 kW inverters distributed across carports with varying sub-array module configurations totaling approximately 900-1,050 modules across three carport installations.
View the file
Other files
Show 40 more
Latest 50 of 107 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
LSIG
2500/3
LS
IG
/3
EN
L
AB
LS
IG
0/
EN
L
AA
APW2LHA
225A
MLO
SPD
APW2LLA
150A
MCB
SPD
APW3LHA
80A
MLO
SPD
APW3LLA
60A
MLO
SPD
APW4LHA
80A
MLO
SPD
APW4LLA
60A
MLO
SPD
APW2SHD
225A
FTL
SPD
LS
I
5/
APW2SHE
225A
MLO
SPD
APW2SHA
300A
FTL
APW2SLA
400A
MCB/FTL
LS
I
0/
APW2SLB
400A
MLO
APW2SHB
300A
FTL
APW2SLC
400A
MCB/FTL
LS
I
0/
APW2SLD
400A
MLO
APW2SHC
300A
FTL
APW2SLE
400A
MCB/FTL
LS
I
0/
APW2SLF
400A
MLO
APW1LHA
80A
MLO
SPD
APW1LLA
60A
MLO
SPD
APW1SHD
125A
MLO
SPD
APW1SHE
125A
MLO
SPD
APW1SLA
225A
FTL
APW1SHA
300A
MLO
APW1SLB
225A
MLO
APW1SLC
225A
FTL
APW1SHB
300A
MLO
APW1SLD
225A
MLO
APW1SLE
225A
FTL
APW1SHC
300A
MLO
APW1SLF
225A
MLO
LS
IG
/3
EN
L
AC
APW2CHA
150A
MLO
LS
I
0/
APW1CHA
150A
MLO
LS
I
0/
LS
I
0/
APW1SLH
400A
MCB
APW1SLJ
225A
MLO
5/
M M M M
MM M
M
M
M M60 /3
APA2LHA
100A
MLO
SPD
APA2LLA
60A
MCB
SPD
APA2SHA
200A
MCB
LS
I
0/
M
APA2SLA
150A
MCB/FTL
APA1SLA
150A
MLO
AP2LLA
60A
MCB
SPD
/3
SPD
A.
B.
C.
D.
E.
F.
G.
H.
I.
J.
K.
L.
BASE BUILD SCOPE SHALL ONLY INCLUDE EMPTY CONDUITS
OF FEEDERS SHOWN ON THIS SHEET WITH FEEDER TAGS.
ADD ALTERNATE SCOPE SHALL INCLUDE PV PANELS,
CARPORTS, DC CONDUCTORS, INVERTERS, AC CONDUCTORS,
AC COMBINER BOXES, PV DISTRIBUTION BOARDS.
SEE DRAWING E0.1 FOR ABBREVIATIONS, SYMBOLS, GENERAL
NOTES.
THE CONTRACTOR SHALL COORDINATE EXACT LOCATION OF
EQUIPMENT POWER CONNECTIONS WITH EQUIPMENT
INSTALLER PRIOR TO ROUGH-IN.
COORDINATE FINAL LOCATION OF MECHANICAL EQUIPMENT
AND ASSOCIATED DISCONNECT SWITCHES, STARTERS, VFDS,
CONTROL POWER AND OTHER POWER REQUIREMENTS WITH
DIV 23 AND MECHANICAL DRAWINGS.
SEE MECHANICAL EQUIPMENT SCHEDULE FOR ASSOCIATED
OVERCURRENT DEVICES, DISCONNECT SWITCHES, STARTERS
AND WIRES.
VOLTAGE DROP SHALL BE LIMITED TO LESS THAN 3% FOR ALL
BRANCH CIRCUITS AND 2% FOR ALL FEEDERS.
CONTRACTOR SHALL COORDINATE AND FIELD VERIFY
REQUIREMENT OF NEUTRAL CONDUCTOR FOR ALL EQUIPMENT
AND PROVIDE NEUTRAL CONDUCTOR AS NECESSARY.
ALL LIFE SAFETY AND LIGHTING PANELBOARDS SHALL BE
EQUIPPED WITH TYPE 2 SPD.
ALL AUTOMATIC TRANSFER SWITCHES SHALL BE 4 POLE AND
EQUIPPED WITH BYPASS ISOLATION.
ALL UTILITY TRANSFORMERS DESCRIBED AS NAVOPACHE
TRANSFORMER TO BE COORDINATED WITH UTILITY AND
PROVIDED BY UTILITY. COORDINATE ALL FINAL REQUIREMENTS
AND AVAILABLE FAULT CURRENT CONTRIBUTIONS BASED ON
SUPPLIED EQUIPMENT. BASIS OF DESIGN 2500KVA, AND 5%Z.
ELECTRICAL EQUIPMENT SHALL BE CONFIGURED AS FOLLOWS:
-SERVICE ENTRANCE SECTIONS - UL891 REAR CONNECTED
SWITCHBOARD
-DISTRIBUTION SWITCHBOARDS WITH DRAW-OUT CIRCUIT
BREAKERS - UL891 SWITCHBOARD, DRAW-OUT MOLDED CASE
CIRCUIT BREAKERS
-GENERATOR PARALLELING GEAR - UL1558 SWITCHGEAR
GENERAL SHEET NOTES
OPTIONAL
STANDBYE503
E502
M
NAVOPACHE
TRANSFORMER
ADM2SH
1000A
480-277V
3PH/4W
LIFE
SAFETY
ATS-ALA
250A
4P
LEVEL 1
LEVEL 2
LEVEL 2
LEVEL 3
TAPW2LLA
45kVA
LEVEL 3
LEVEL 4
ATS-ASA
1000A
4P
LTG
TAPW2SLA/B
112.5kVA
PWR
TAPW2SLC/D
112.5kVA
TAPW2SLE/F
112.5kVA
PWR PWR
CRITICAL
ADM2CH
1000A
480-277V
3PH/4W
ATS-ACA
1000A
4P
PWR
PWR
LEVEL 4
ROOF
A1000
A250 A1000
T112T112T112T45
A300
A400
A300 A225
A225
A300
A300 A225
A225
A400
A300
A300 A225
A225
A400
A225
A125 A125
A225
A150
A1000
A1000
A150
E501
TAPW1SLH/J
112.5kVA
A225
LAB PWR
ADM2LH
250A 480-277V
3PH/4W
A225
MAIN
SA1
SA2 SA3 SA4
DA1 DA2 DA3 DA4 DA7
DA5 DA8
A250
TAPA2LLA
15kVA
60V1
T15
EMS PWR
A200V1
EMS BLDG
TAPA2SLA
45kVA
T45
A150
DA6
MATCHLINE
MATCHLINE
TAP2LLA
15kVA T15
T112
SES-A
3200A BUS
PER NEC 705.12(B)
480-277V/3PH/4W (3)
E521
SEL-751
(3)(3)
A
SHEET NUMBER
PROJECT NUMBER
SEALS AND SIGNATURES
ISSUED FOR DATE
Pl ot
Da te:
IHS Whiteriver Hospital 200 W Hospital Drive Whiteriver, Arizona, 85941
IHS Project #: 131445 IHS Contract #: 75H70123R00008 IHS Award Date: 02/02/2024
455 NORTH THIRD STREET
SUITE 250
PHOENIX, AZ 85004
602.265.2200 smithgroup.com
Drawn By: Checked By:
BASED ON PROGRAM OF REQUIREMENTS DATED [ 03/26/22],
POR AMENDMENT DATED [ 02/03/25], AND ON SCHEMATIC
DRAWINGS APPROVED [11/19/24].
5/2 8/2
6 1
2:0 8:4
4 P M
ELECTRICAL ONE LINE
DIAGRAM - SES-A, 1 OF 2
E5.1.1CD
W hit tin gto n
14904.000 Whittington Baca
X FEEDER SCHEDULE
SHEET KEYNOTES
E501 NAVOPACHE UTILITY METER. METER SHALL BE EQUIPPED
WITH CAPABILITY TO INTERFACE WITH BMS. ELECTRICAL
CONTRACTOR SHALL PROVIDE REQUIRED CONDUIT AND
COMMUNICATION WIRING FROM METER TO POINT OF
INTERFACE WITH BMS.
E502 COMPLIANCE WITH "NEC 240.87 ARC ENERGY REDUCTION"
REQUIRED. REDUCTION METHOD SHALL ALLOW FOR
REQUIRED SELECTIVE DEVICE COORDINATION AND ARC
FLASH REQUIREMENTS. REFER TO ELECTRICAL
SPECIFICATIONS FOR ADDITIONAL INFORMATION.
E503 PROVIDE PERMANENT IDENTIFICATION PLAQUE INDICATING
THE FOLLOWING: ELECTRICAL SERVICE #1 OF 5.
GENERATORS LOCATED IN ELECTRICAL EQUIPMENT YARD,
GENERATOR DISCONNECTS LOCATED IN ADJACENT
ELECTRICAL ROOM IN GMDB. PV DISCONNECT LOCATED AT
END OF THIS ELECTRICAL EQUIPMENT LINEUP.
E521 PROVIDE RELAY PROTECTION ELEMENTS REQUIRED BY
UTILITY AND MULTIPLE GENERATOR AND PV MONITORING
AND CONTROL SYSTEM MANUFACTURER. INTEGRATE SEL
RELAY AND PROGRAMMING INTO MULTIPLE GENERATOR
AND PV MONITORING SYSTEM AND CIRCUIT BREAKER.
PROVIDE AND PROGRAM PROTECTION ELEMENT SET POINTS
AND LOGIC WITHIN THE RELAY. REFER TO SEL-751 DETAIL
FOR ADDITIONAL INFORMATION.
SCALE: NOT TO SCALE1 ONE LINE DIAGRAM - SES-A, 1 OF 2
60 4#4 + 1#10 G, 1 1/4" C 60V1 4#1 + 1#6 G, 1 1/2" C 80 4#3 + 1#8 G, 1 1/4" C A125 4#2/0 + 1#6 G, 2" C A150 4#3/0 + 1#4 G, 2" C
A200V1 4#400KCMIL + 1#1 G, 2 1/2" C
A225 4#300KCMIL + 1#2 G, 2 1/2" C
A250 4#350KCMIL + 1#2 G, 2 1/2" C
A300 4#500KCMIL + 1#2 G, 3" C
A400 2 SETS OF 4#250KCMIL + 1#1 G, (2) 2 1/2" C
A1000 3 SETS OF 4#600KCMIL + 1#4/0 G, (3) 3 1/2" C
T15 15KVA TRANSFORMER, 480-208Y/120V, 3PH
PRIMARY FEEDER: 3#10 + 1#10 G, 3/4" C
SECONDARY FEEDER: 4#4 + 1#8 G, 1 1/4" C
BONDING JUMPERS & GROUNDING ELECTRODE
CONDUCTOR: #8
T45 45KVA TRANSFORMER, 480-208Y/120V, 3PH
PRIMARY FEEDER: 3#3 + 1#8 G, 1 1/4" C
SECONDARY FEEDER: 4#1/0 + 1#6 G, 2" C
BONDING JUMPERS & GROUNDING ELECTRODE
CONDUCTOR: #6
T112 112.5KVA TRANSFORMER, 480-208Y/120V, 3PH
PRIMARY FEEDER: 3#3/0 + 1#6 G, 2" C
SECONDARY FEEDER: 2 SETS OF 4#3/0 + 1#2 G, (2)
2" C
BONDING JUMPERS & GROUNDING ELECTRODE
CONDUCTOR: #2
"A" DENOTES ALUMINUM CONDUCTORS, ALL OTHER CONDUCTORS SHALL BE COPPER
FINAL CONSTRUCTION DOCUMENTS 05MAR26
BID ADDENDUM-A 16APR26
BID ADDENDUM-E 28MAY26
AA
B
05-28-26
6-30-28
BE
APW2CHD
225A
MLO/FTL
SPD
LS
I
5/
APW2CHE
225A
MLO
SPD
APW2CLA
125A
MCB
APW2CLB
125A
MCB
APW2CHB
150A
MLO
APW2CLC
125A
MCB
LS
I
0/
APW2CLD
125A
MCB
APW2CHC
150A
MLO
APW2CLE
125A
MCB
LS
I
0/
APW2CLF
125A
MCB
APW1CHD
125A
MLO
SPD
APW1CHE
125A
MLO
SPD
APW1CLA
125A
MCB
APW1CHA
150A
MLO
APW1CLB
125A
MCB
APW1CLD
125A
MCB
APW1CHB
150A
MLO
APW1CLC
125A
MCB
APW1CLF
125A
MCB
APW1CHC
150A
MLO
APW1CLE
125A
MCB
LS
IG
/3
EN
L
AD
LS
I
0/
LS
I
5/
LS
I
5/
LS
I
0/
LS
I
5/
LS
I
5/
LS
I
5/
LS
I
0/
LS
I
5/
LS
I
/3
VFD
LS
I
0/
VFD
LS
I
/3
VFD
LS
I
0/
VFD
LS
IG
0/
PVW
LS
I
0/
LS
IG
0/
EN
L
AE
LS
I
0/
LS
I
0/
APW2EHA
300A
MLO
APW1EHA
150A
MLO
APW2EHB
250A
MLO
APW1EHB
150A
MLO
APW1ELA
150A
MCB
APW1ELB
150A
MCB
LS
I
/3
M M
M M M M M M M M M M M M M M
M M M M M M
M
APA1CLA
60A
MCB
APW2ELA
150A
MCB
APW2ELB
150A
MCB
A.
B.
C.
D.
E.
F.
G.
H.
I.
J.
K.
L.
BASE BUILD SCOPE SHALL ONLY INCLUDE EMPTY CONDUITS
OF FEEDERS SHOWN ON THIS SHEET WITH FEEDER TAGS.
ADD ALTERNATE SCOPE SHALL INCLUDE PV PANELS,
CARPORTS, DC CONDUCTORS, INVERTERS, AC CONDUCTORS,
AC COMBINER BOXES, PV DISTRIBUTION BOARDS.
SEE DRAWING E0.1 FOR ABBREVIATIONS, SYMBOLS, GENERAL
NOTES.
THE CONTRACTOR SHALL COORDINATE EXACT LOCATION OF
EQUIPMENT POWER CONNECTIONS WITH EQUIPMENT
INSTALLER PRIOR TO ROUGH-IN.
COORDINATE FINAL LOCATION OF MECHANICAL EQUIPMENT
AND ASSOCIATED DISCONNECT SWITCHES, STARTERS, VFDS,
CONTROL POWER AND OTHER POWER REQUIREMENTS WITH
DIV 23 AND MECHANICAL DRAWINGS.
SEE MECHANICAL EQUIPMENT SCHEDULE FOR ASSOCIATED
OVERCURRENT DEVICES, DISCONNECT SWITCHES, STARTERS
AND WIRES.
VOLTAGE DROP SHALL BE LIMITED TO LESS THAN 3% FOR ALL
BRANCH CIRCUITS AND 2% FOR ALL FEEDERS.
CONTRACTOR SHALL COORDINATE AND FIELD VERIFY
REQUIREMENT OF NEUTRAL CONDUCTOR FOR ALL EQUIPMENT
AND PROVIDE NEUTRAL CONDUCTOR AS NECESSARY.
ALL LIFE SAFETY AND LIGHTING PANELBOARDS SHALL BE
EQUIPPED WITH TYPE 2 SPD.
ALL AUTOMATIC TRANSFER SWITCHES SHALL BE 4 POLE AND
EQUIPPED WITH BYPASS ISOLATION.
ALL UTILITY TRANSFORMERS DESCRIBED AS NAVOPACHE
TRANSFORMER TO BE COORDINATED WITH UTILITY AND
PROVIDED BY UTILITY. COORDINATE ALL FINAL REQUIREMENTS
AND AVAILABLE FAULT CURRENT CONTRIBUTIONS BASED ON
SUPPLIED EQUIPMENT. BASIS OF DESIGN 2500KVA, AND 5%Z.
ELECTRICAL EQUIPMENT SHALL BE CONFIGURED AS FOLLOWS:
-SERVICE ENTRANCE SECTIONS - UL891 REAR CONNECTED
SWITCHBOARD
-DISTRIBUTION SWITCHBOARDS WITH DRAW-OUT CIRCUIT
BREAKERS - UL891 SWITCHBOARD, DRAW-OUT MOLDED CASE
CIRCUIT BREAKERS
-GENERATOR PARALLELING GEAR - UL1558 SWITCHGEAR
GENERAL SHEET NOTES
LTG
TAPW2CLA/B
75kVA
PWR PWR
EQUIPMENT
ADM2EHA
1600A
480-277V
3PH/4W
ATS-AEA
1600A
4P
LEVEL 1
LEVEL 2
LEVEL 2
LEVEL 3
LEVEL 3
LEVEL 4
PWR PWR
TAPW1CLA/B
75kVA
PWR
PWR
TAPW2CLC/D
75kVA
PWR
PWR
TAPW1CLC/D
75kVA
TAPW2CLE/F
75kVA
PWR
PWR PWR
TAPW1CLE/F
75kVA
LEVEL 4
ROOF
T75D T75D
T75DT75DT75D A150 A150 A225
A225
A150 A150 A150 A125 A125
A1600
A1600
1000-3
ACCH-1
CHWP-1
100-3
HHWP-1
30-3
CBWP-1
100-3
PV A
EH-1
EQUIPMENT
ADM2EHB
600A
480-277V
3PH/4W
ATS-AEB
600A
4P
A600
A600
A250A300
A150 T75D
300-3
TAPW1ELA
45kVA
T45
TAPW1ELB
45kVA
T45
, E O
1000-3
B-1
NON-COINCIDENT
LOAD
SA5 SA6
DA9 DA11 DA13 DA15 DA17 DA19 DA20 DA21 DA22 DA23 DA24 DA25 DA26 DA29
DA8 DA10 DA12 DA14 DA16 DA18
E519
60V1
EMS BLDG
SA7
MATCHLINE
TAPW2ELA
45kVA
T45
TAPW2ELB
45kVA
T45
A150
MATCHLINE
NON-COINCIDENT
LOAD
E530
A
SHEET NUMBER
PROJECT NUMBER
SEALS AND SIGNATURES
ISSUED FOR DATE
Pl ot
Da te:
IHS Whiteriver Hospital 200 W Hospital Drive Whiteriver, Arizona, 85941
IHS Project #: 131445 IHS Contract #: 75H70123R00008 IHS Award Date: 02/02/2024
455 NORTH THIRD STREET
SUITE 250
PHOENIX, AZ 85004
602.265.2200 smithgroup.com
Drawn By: Checked By:
BASED ON PROGRAM OF REQUIREMENTS DATED [ 03/26/22],
POR AMENDMENT DATED [ 02/03/25], AND ON SCHEMATIC
DRAWINGS APPROVED [11/19/24].
5/2 8/2
6 1
2:0 8:4
9 P M
ELECTRICAL ONE LINE
DIAGRAM - SES-A, 2 OF 2
E5.1.2CD
W hit tin gto n
14904.000 Whittington Baca
X FEEDER SCHEDULE
SHEET KEYNOTES
E519 PV CIRCUIT BREAKER SHALL BE LOCATED AT LAST BUSSED
SPACE. PROVIDE PERMANENT IDENTIFICATION PLAQUE
INDICATING THE FOLLOWING: PV POWER SOURCE - DO NOT
RELOCATE THIS CIRCUIT BREAKER
E530 PROVIDE SHUNT TRIP CIRCUIT BREAKER FOR INTERFACE
WITH BOILER EMERGENCY SHUTDOWN EPO SWITCHES.
REFER TO EMP2.2.G FOR ADDITIONAL INFORMATION.
SCALE: NOT TO SCALE1 ONE LINE DIAGRAM - SES-A, 2 OF 2
30-3 3#10 + 1#10 G, 3/4" C 60V1 4#1 + 1#6 G, 1 1/2" C 100-3 3#1 + 1#8 G, 1 1/2" C
300-3 3#350KCMIL + 1#4 G, 3" C
1000-3 3 SETS OF 3#400KCMIL + 1#2/0 G, (3) 3" C
A125 4#2/0 + 1#6 G, 2" C A150 4#3/0 + 1#4 G, 2" C
A225 4#300KCMIL + 1#2 G, 2 1/2" C
A250 4#350KCMIL + 1#2 G, 2 1/2" C
A300 4#500KCMIL + 1#2 G, 3" C
A600 2 SETS OF 4#500KCMIL + 1#2/0 G, (2) 3" C
A1600 5 SETS OF 4#600KCMIL + 1#350KCMIL G, (5) 3 1/2" C
T45 45KVA TRANSFORMER, 480-208Y/120V, 3PH
PRIMARY FEEDER: 3#3 + 1#8 G, 1 1/4" C
SECONDARY FEEDER: 4#1/0 + 1#6 G, 2" C
BONDING JUMPERS & GROUNDING ELECTRODE
CONDUCTOR: #6
T75D 75KVA TRANSFORMER, 480-208Y/120V, 3PH
PRIMARY FEEDER: 3#1/0 + 1#6 G, 1 1/2" C
SECONDARY FEEDERS: 4#1/0 + 1#2 G, 2" C TO EACH PANEL
BONDING JUMPERS & GROUNDING ELECTRODE
CONDUCTOR: #2
"A" DENOTES ALUMINUM CONDUCTORS, ALL OTHER CONDUCTORS SHALL BE COPPER
FINAL CONSTRUCTION DOCUMENTS 05MAR26
BID ADDENDUM-A 16APR26
BID ADDENDUM-E 28MAY26
A
A
B
05-28-26
LS
IG
/3
EN
L
BB
LS
IG
0/
EN
L
BA
BPE2SHD
225A
FTL
SPD
LS
I
5/
BPE2SHE
225A
MLO
SPD
BPE2SHA
300A
FTL
BPE2SLA
400A
MCB/FTL
LS
I
0/
BPE2SLB
400A
MLO
BPE2SHB
300A
FTL
BPE2SLC
225A
MCB/FTL
LS
I
0/
BPE2SLD
225A
MLO
BPE1SHD
125A
MLO
SPD
BPE1SHE
125A
MLO
SPD
BPE1SLA
225A
FTL
BPE1SHA
300A
MLO
BPE1SLB
225A
MLO
BPE1SLC
225A
FTL
BPE1SHB
300A
MLO
BPE1SLD
225A
MLO
/3
/3
/3
/3
/3
LS
IG
/3
LS
I
/3
BPT2SLA
150A
MCB
BPT2SLB
225A
MCB
LS
I
5/
BPT1SLA
80A
MLO
BPT3SLA
80A
MLO
BPT4SLA
80A
MLO
BPT2SLC
225A
MCB
LS
I
5/
BPT1SLB
80A
MLO
BPT3SLB
80A
MLO
BPT4SLB
80A
MLO
BPF2SHA
250A
MLO
BPF2SLA
225A
MCB
LS
I
0/
M
M M
M M M M M M M
SPD
A.
B.
C.
D.
E.
F.
G.
H.
I.
J.
K.
L.
BASE BUILD SCOPE SHALL ONLY INCLUDE EMPTY CONDUITS
OF FEEDERS SHOWN ON THIS SHEET WITH FEEDER TAGS.
ADD ALTERNATE SCOPE SHALL INCLUDE PV PANELS,
CARPORTS, DC CONDUCTORS, INVERTERS, AC CONDUCTORS,
AC COMBINER BOXES, PV DISTRIBUTION BOARDS.
SEE DRAWING E0.1 FOR ABBREVIATIONS, SYMBOLS, GENERAL
NOTES.
THE CONTRACTOR SHALL COORDINATE EXACT LOCATION OF
EQUIPMENT POWER CONNECTIONS WITH EQUIPMENT
INSTALLER PRIOR TO ROUGH-IN.
COORDINATE FINAL LOCATION OF MECHANICAL EQUIPMENT
AND ASSOCIATED DISCONNECT SWITCHES, STARTERS, VFDS,
CONTROL POWER AND OTHER POWER REQUIREMENTS WITH
DIV 23 AND MECHANICAL DRAWINGS.
SEE MECHANICAL EQUIPMENT SCHEDULE FOR ASSOCIATED
OVERCURRENT DEVICES, DISCONNECT SWITCHES, STARTERS
AND WIRES.
VOLTAGE DROP SHALL BE LIMITED TO LESS THAN 3% FOR ALL
BRANCH CIRCUITS AND 2% FOR ALL FEEDERS.
CONTRACTOR SHALL COORDINATE AND FIELD VERIFY
REQUIREMENT OF NEUTRAL CONDUCTOR FOR ALL EQUIPMENT
AND PROVIDE NEUTRAL CONDUCTOR AS NECESSARY.
ALL LIFE SAFETY AND LIGHTING PANELBOARDS SHALL BE
EQUIPPED WITH TYPE 2 SPD.
ALL AUTOMATIC TRANSFER SWITCHES SHALL BE 4 POLE AND
EQUIPPED WITH BYPASS ISOLATION.
ALL UTILITY TRANSFORMERS DESCRIBED AS NAVOPACHE
TRANSFORMER TO BE COORDINATED WITH UTILITY AND
PROVIDED BY UTILITY. COORDINATE ALL FINAL REQUIREMENTS
AND AVAILABLE FAULT CURRENT CONTRIBUTIONS BASED ON
SUPPLIED EQUIPMENT. BASIS OF DESIGN 2500KVA, AND 5%Z.
ELECTRICAL EQUIPMENT SHALL BE CONFIGURED AS FOLLOWS:
-SERVICE ENTRANCE SECTIONS - UL891 REAR CONNECTED
SWITCHBOARD
-DISTRIBUTION SWITCHBOARDS WITH DRAW-OUT CIRCUIT
BREAKERS - UL891 SWITCHBOARD, DRAW-OUT MOLDED CASE
CIRCUIT BREAKERS
-GENERATOR PARALLELING GEAR - UL1558 SWITCHGEAR
GENERAL SHEET NOTES
E504
E502
M
NAVOPACHE
TRANSFORMER
LEVEL 1
LEVEL 2
LEVEL 2
LEVEL 3
LEVEL 3
LEVEL 4
LEVEL 4
ROOF
OPTIONAL
STANDBY
BDM2SH
1000A
480-277V
3PH/4W
EQUIPMENT
(ELEVATORS)
ATS-BEA
400A
4P
ATS-BSA
1000A
4P
LTG
TBPE2SLA/B
112.5kVA
TBPE2SLC/D
75kVA
CNTRL
PNL
STAFF/PATIENT
ELEV 1B
CNTRL
PNL
STAFF/PATIENT
ELEV 1A
CNTRL
PNL
FREIGHT ELEV 5
CNTRL
PNL
PUBLIC ELEV 4B
CNTRL
PNL
PUBLIC ELEV 4A
BDW4EH
400A 480-277V
3PH/4W
ATS-BCA
1000A
4P
PWR PWR
A400
A400
A1000
A1000
A300 A300V1 A225
T112 T75
A300 A225
A225
A400
A300
A225
A225
A125 A125
A225V1
TBPT2SLA
45kVA K13
TBPT2SLB
75kVA K13
TBPT2SLC
75kVA K13
T45N T75N T75N
80 80
80 80
80 80
MDF IDF IDF
E501
50-3 50-3 80-3 50-3V1 50-3V1
FAC BLDG
TBPF2SLA
75kVA
MAIN
SB1
SB2 SB3
DB1 DB2 DB3 DB4 DB5 DB6 DB7
MATCHLINE
MATCHLINE
T75
A250
A250
TBPT2SLA
200A/150AF
BPF2SHA
400A/250AF
TBPE1SLC/D
75kVA
T75
TBPT2SLB
400A/225AF
TBPT2SLC
400A/225AF
#2
SES-B
3200A BUS
PER NEC 705.12(B)
480-277V/3PH/4W (3)
E521
SEL-751
(3)(3)
A
SHEET NUMBER
PROJECT NUMBER
SEALS AND SIGNATURES
ISSUED FOR DATE
Pl ot
Da te:
IHS Whiteriver Hospital 200 W Hospital Drive Whiteriver, Arizona, 85941
IHS Project #: 131445 IHS Contract #: 75H70123R00008 IHS Award Date: 02/02/2024
455 NORTH THIRD STREET
SUITE 250
PHOENIX, AZ 85004
602.265.2200 smithgroup.com
Drawn By: Checked By:
BASED ON PROGRAM OF REQUIREMENTS DATED [ 03/26/22],
POR AMENDMENT DATED [ 02/03/25], AND ON SCHEMATIC
DRAWINGS APPROVED [11/19/24].
5/2 8/2
6 1
2:0 8:5
3 P M
ELECTRICAL ONE LINE
DIAGRAM - SES-B, 1 OF 2
E5.2.1CD
W hit tin gto n
14904.000 Whittington Baca
X FEEDER SCHEDULE
SHEET KEYNOTES
E501 NAVOPACHE UTILITY METER. METER SHALL BE EQUIPPED
WITH CAPABILITY TO INTERFACE WITH BMS. ELECTRICAL
CONTRACTOR SHALL PROVIDE REQUIRED CONDUIT AND
COMMUNICATION WIRING FROM METER TO POINT OF
INTERFACE WITH BMS.
E502 COMPLIANCE WITH "NEC 240.87 ARC ENERGY REDUCTION"
REQUIRED. REDUCTION METHOD SHALL ALLOW FOR
REQUIRED SELECTIVE DEVICE COORDINATION AND ARC
FLASH REQUIREMENTS. REFER TO ELECTRICAL
SPECIFICATIONS FOR ADDITIONAL INFORMATION.
E504 PROVIDE PERMANENT IDENTIFICATION PLAQUE INDICATING
THE FOLLOWING: ELECTRICAL SERVICE #2 OF 5.
GENERATORS LOCATED IN ELECTRICAL EQUIPMENT YARD,
GENERATOR DISCONNECTS LOCATED IN ADJACENT
ELECTRICAL ROOM IN GMDB. PV DISCONNECT LOCATED AT
END OF THIS ELECTRICAL EQUIPMENT LINEUP.
E521 PROVIDE RELAY PROTECTION ELEMENTS REQUIRED BY
UTILITY AND MULTIPLE GENERATOR AND PV MONITORING
AND CONTROL SYSTEM MANUFACTURER. INTEGRATE SEL
RELAY AND PROGRAMMING INTO MULTIPLE GENERATOR
AND PV MONITORING SYSTEM AND CIRCUIT BREAKER.
PROVIDE AND PROGRAM PROTECTION ELEMENT SET POINTS
AND LOGIC WITHIN THE RELAY. REFER TO SEL-751 DETAIL
FOR ADDITIONAL INFORMATION.
SCALE: NOT TO SCALE1 ONE LINE DIAGRAM - SES-B, 1 OF 2
50-3 3#6 + 1#10 G, 3/4" C 50-3V1 3#2 + 1#4 G, 1 1/4" C 80 4#3 + 1#8 G, 1 1/4" C 80-3 3#3 + 1#8 G, 1 1/4" C A125 4#2/0 + 1#6 G, 2" C
A225 4#300KCMIL + 1#2 G, 2 1/2" C
A225V1 4#400KCMIL + 1#1/0 G, 2 1/2" C
A250 4#350KCMIL + 1#2 G, 2 1/2" C
A300 4#500KCMIL + 1#2 G, 3" C
A300V1 4#600KCMIL + 1#1 G, 3" C
A400 2 SETS OF 4#250KCMIL + 1#1 G, (2) 2 1/2" C
A1000 3 SETS OF 4#600KCMIL + 1#4/0 G, (3) 3 1/2" C
T45N 45KVA TRANSFORMER, 480-208Y/120V, 3PH
PRIMARY FEEDER: 3#3 + 1#8 G, 1 1/4" C
SECONDARY FEEDER: 3#1/0, 1#4/0 N + 1#6 G, 2" C
BONDING JUMPERS & GROUNDING ELECTRODE
CONDUCTOR: #6
T75 75KVA TRANSFORMER, 480-208Y/120V, 3PH
PRIMARY FEEDER: 3#1/0 + 1#6 G, 1 1/2" C
SECONDARY FEEDER: 4#4/0 + 1#2 G, 2 1/2" C
BONDING JUMPERS & GROUNDING ELECTRODE
CONDUCTOR: #2
T75N 75KVA TRANSFORMER, 480-208Y/120V, 3PH
PRIMARY FEEDER: 3#1/0 + 1#6 G, 1 1/2" C
SECONDARY FEEDER: 3#4/0, 1#500KCMIL N + 1#2
G, 2 1/2" C
BONDING JUMPERS & GROUNDING ELECTRODE
CONDUCTOR: #2
T112 112.5KVA TRANSFORMER, 480-208Y/120V, 3PH
PRIMARY FEEDER: 3#3/0 + 1#6 G, 2" C
SECONDARY FEEDER: 2 SETS OF 4#3/0 + 1#2 G, (2)
2" C
BONDING JUMPERS & GROUNDING ELECTRODE
CONDUCTOR: #2
"A" DENOTES ALUMINUM CONDUCTORS, ALL OTHER CONDUCTORS SHALL BE COPPER
FINAL CONSTRUCTION DOCUMENTS 05MAR26
BID ADDENDUM-A 16APR26
BID ADDENDUM-E 28MAY26
A
B
05-28-26
LS
IG
/3
EN
L
BC
BPE2CHD
225A
FTL
SPD
LS
I
5/
BPE2CHE
225A
MLO
SPD
BPE2CHA
150A
MLO
BPE2CLA
125A
MCB
LS
I
0/
BPE2CLB
125A
MCB
BPE2CHB
150A
MLO
BPE2CLC
125A
MCB
LS
I
0/
BPE2CLD
125A
MCB
BPE1CHD
125A
MLO
SPD
BPE1CHE
125A
MLO
SPD
BPE1CLA
125A
MCB
BPE1CHA
150A
MLO
BPE1CLB
125A
MCB
BPE1CLD
125A
MCB
BPE1CHB
150A
MLO
BPE1CLC
125A
MCB
LS
IG
/3
EN
L
BD
LS
I
0/
LS
I
5/
LS
I
5/
LS
I
0/
LS
I
5/
LS
I
5/
BPE2CLE
125A
MCB
BPE2CLF
125A
MCB
LS
I
5/
LS
I
/3
VFD
LS
I
0/
VFD
LS
I
/3
VFD
LS
I
0/
VFD
LS
I
0/
LS
IG
0/
PVX
LS
IG
0/
EN
L
BE
LS
I
0/
LS
I
0/
BPE2EHA
400A
MLO
BPE1EHA
225A
MLO
BPE2EHB
400A
MLO
BPE1EHB
225A
MLO
BPE1ELA
150A
MCB
BPE1ELB
150A
MCB
LS
I
0/
LS
I
0/
LS
I
0/
UA1 BP1 UB1
LS
I
/3
M M M M
M
M
M M M M M
M M M M M
M M M M M M M M
A.
B.
C.
D.
E.
F.
G.
H.
I.
J.
K.
L.
BASE BUILD SCOPE SHALL ONLY INCLUDE EMPTY CONDUITS
OF FEEDERS SHOWN ON THIS SHEET WITH FEEDER TAGS.
ADD ALTERNATE SCOPE SHALL INCLUDE PV PANELS,
CARPORTS, DC CONDUCTORS, INVERTERS, AC CONDUCTORS,
AC COMBINER BOXES, PV DISTRIBUTION BOARDS.
SEE DRAWING E0.1 FOR ABBREVIATIONS, SYMBOLS, GENERAL
NOTES.
THE CONTRACTOR SHALL COORDINATE EXACT LOCATION OF
EQUIPMENT POWER CONNECTIONS WITH EQUIPMENT
INSTALLER PRIOR TO ROUGH-IN.
COORDINATE FINAL LOCATION OF MECHANICAL EQUIPMENT
AND ASSOCIATED DISCONNECT SWITCHES, STARTERS, VFDS,
CONTROL POWER AND OTHER POWER REQUIREMENTS WITH
DIV 23 AND MECHANICAL DRAWINGS.
SEE MECHANICAL EQUIPMENT SCHEDULE FOR ASSOCIATED
OVERCURRENT DEVICES, DISCONNECT SWITCHES, STARTERS
AND WIRES.
VOLTAGE DROP SHALL BE LIMITED TO LESS THAN 3% FOR ALL
BRANCH CIRCUITS AND 2% FOR ALL FEEDERS.
CONTRACTOR SHALL COORDINATE AND FIELD VERIFY
REQUIREMENT OF NEUTRAL CONDUCTOR FOR ALL EQUIPMENT
AND PROVIDE NEUTRAL CONDUCTOR AS NECESSARY.
ALL LIFE SAFETY AND LIGHTING PANELBOARDS SHALL BE
EQUIPPED WITH TYPE 2 SPD.
ALL AUTOMATIC TRANSFER SWITCHES SHALL BE 4 POLE AND
EQUIPPED WITH BYPASS ISOLATION.
ALL UTILITY TRANSFORMERS DESCRIBED AS NAVOPACHE
TRANSFORMER TO BE COORDINATED WITH UTILITY AND
PROVIDED BY UTILITY. COORDINATE ALL FINAL REQUIREMENTS
AND AVAILABLE FAULT CURRENT CONTRIBUTIONS BASED ON
SUPPLIED EQUIPMENT. BASIS OF DESIGN 2500KVA, AND 5%Z.
ELECTRICAL EQUIPMENT SHALL BE CONFIGURED AS FOLLOWS:
-SERVICE ENTRANCE SECTIONS - UL891 REAR CONNECTED
SWITCHBOARD
-DISTRIBUTION SWITCHBOARDS WITH DRAW-OUT CIRCUIT
BREAKERS - UL891 SWITCHBOARD, DRAW-OUT MOLDED CASE
CIRCUIT BREAKERS
-GENERATOR PARALLELING GEAR - UL1558 SWITCHGEAR
GENERAL SHEET NOTES
LEVEL 1
LEVEL 2
LEVEL 2
LEVEL 3
LEVEL 3
LEVEL 4
LEVEL 4
ROOF
CRITICAL
BDM2CH
1000A
480-277V
3PH/4W
ATS-BCA
1000A
4P
LTG
TBPE2CLA/B
75kVA
PWR PWR
EQUIPMENT
BDM2EHA
1600A
480-277V
3PH/4W
ATS-BEB
1600A
4P
PWR PWR
TBPE1CLA/B
75kVA
PWR
PWR
TBPE2CLC/D
75kVA
PWR
PWR
TBPE1CLC/D
75kVA
TBPE2CLE/F
75kVA
PWR
A1000
A1000
A150
T75D
A150V1
T75DV1 T75D
A225
T75D T75DV1
A150 A150V1 A125 A125
A225V1
A1600
A1600
1000-3
ACCH-2
CHWP-2
100-3
HHWP-2
30-3
CBWP-2
100-3
EH-2
PV BEQUIPMENT
BDM2EHB
600A
480-277V
3PH/4W
ATS-BEC
600A
4P
A600
A600
A400V1A400
A225
TBPE1ELA
45kVA
T45
TBPE1ELB
45kVA
T45
, E O
400 400 400
UPS A1
INPUT
UPS B1
INPUT
UPS A1/B1
BYPASS
1000-3
NON-COINCIDENT
LOAD
B-2
E519
SB4 SB5 SB6
DB8
DB9
DB10 DB12 DB14 DB19
DB11 DB13 DB15 DB17 DB18
DB16
DB20 DB21 DB22 DB23 DB24 DB25 DB26 DB27
SB7
MATCHLINE
MATCHLINE
300-3
A225
E530
A
SHEET NUMBER
PROJECT NUMBER
SEALS AND SIGNATURES
ISSUED FOR DATE
Pl ot
Da te:
IHS Whiteriver Hospital 200 W Hospital Drive Whiteriver, Arizona, 85941
IHS Project #: 131445 IHS Contract #: 75H70123R00008 IHS Award Date: 02/02/2024
455 NORTH THIRD STREET
SUITE 250
PHOENIX, AZ 85004
602.265.2200 smithgroup.com
Drawn By: Checked By:
BASED ON PROGRAM OF REQUIREMENTS DATED [ 03/26/22],
POR AMENDMENT DATED [ 02/03/25], AND ON SCHEMATIC
DRAWINGS APPROVED [11/19/24].
5/2 8/2
6 1
2:0 8:5
8 P M
ELECTRICAL ONE LINE
DIAGRAM - SES-B, 2 OF 2
E5.2.2CD
W hit tin gto n
14904.000 Whittington Baca
X FEEDER SCHEDULE
SHEET KEYNOTES
E519 PV CIRCUIT BREAKER SHALL BE LOCATED AT LAST BUSSED
SPACE. PROVIDE PERMANENT IDENTIFICATION PLAQUE
INDICATING THE FOLLOWING: PV POWER SOURCE - DO NOT
RELOCATE THIS CIRCUIT BREAKER
E530 PROVIDE SHUNT TRIP CIRCUIT BREAKER FOR INTERFACE
WITH BOILER EMERGENCY SHUTDOWN EPO SWITCHES.
REFER TO EMP2.2.G FOR ADDITIONAL INFORMATION.
SCALE: NOT TO SCALE1 ONE LINE DIAGRAM - SES-B, 2 OF 2
30-3 3#10 + 1#10 G, 3/4" C 100-3 3#1 + 1#8 G, 1 1/2" C
300-3 3#350KCMIL + 1#4 G, 3" C
400 2 SETS OF 4#3/0 + 1#3 G, (2) 2" C
1000-3 3 SETS OF 3#400KCMIL + 1#2/0 G, (3) 3" C
A125 4#2/0 + 1#6 G, 2" C A150 4#3/0 + 1#4 G, 2" C
A150V1 4#400KCMIL + 1#1/0 G, 2-1/2" C
A225 4#300KCMIL + 1#2 G, 2 1/2" C
A225V1 4#400KCMIL + 1#1/0 G, 2 1/2" C
A400 2 SETS OF 4#250KCMIL + 1#1 G, (2) 2 1/2" C
A400V1 2 SETS OF 4#500KCMIL + 1#2/0 G, (2) 3" C
A600 2 SETS OF 4#500KCMIL + 1#2/0 G, (2) 3" C
A1000 3 SETS OF 4#600KCMIL + 1#4/0 G, (3) 3 1/2" C
A1600 5 SETS OF 4#600KCMIL + 1#350KCMIL G, (5) 3 1/2" C
T45 45KVA TRANSFORMER, 480-208Y/120V, 3PH
PRIMARY FEEDER: 3#3 + 1#8 G, 1 1/4" C
SECONDARY FEEDER: 4#1/0 + 1#6 G, 2" C
BONDING JUMPERS & GROUNDING ELECTRODE
CONDUCTOR: #6
T75D 75KVA TRANSFORMER, 480-208Y/120V, 3PH
PRIMARY FEEDER: 3#1/0 + 1#6 G, 1 1/2" C
SECONDARY FEEDERS: 4#1/0 + 1#2 G, 2" C TO
EACH PANEL
BONDING JUMPERS & GROUNDING ELECTRODE
CONDUCTOR: #2
T75DV1 75KVA TRANSFORMER, 480-208Y/120V, 3PH
PRIMARY FEEDER: 3#3/0 + 1#4 G, 2" C
SECONDARY FEEDERS: 4#1/0 + 1#2 G, 2" C TO
EACH PANEL
BONDING JUMPERS & GROUNDING ELECTRODE
CONDUCTOR: #2
"A" DENOTES ALUMINUM CONDUCTORS, ALL OTHER CONDUCTORS SHALL BE COPPER
FINAL CONSTRUCTION DOCUMENTS 05MAR26
BID ADDENDUM-A 16APR26
BID ADDENDUM-E 28MAY26
A
A
B
05-28-26
LS
IG
/3
EN
L
CA
CPW3SHD
225A
FTL
SPD
LS
I
5/
CPW3SHE
225A
MLO
SPD
CPW3SHA
300A
FTL
CPW3SLA
400A
MCB/FTL
LS
I
0/
CPW3SLB
400A
MLO
CPW3SHB
300A
FTL
CPW3SLC
400A
MCB/FTL
LS
I
0/
CPW3SLD
400A
MLO
CPW3SHC
300A
FTL
CPW3SLE
400A
MCB/FTL
LS
I
0/
CPW3SLF
400A
MLO
CPW4SHD
125A
MLO
SPD
CPW4SHE
125A
MLO
SPD
CPW4SLA
225A
FTL
CPW4SHA
300A
MLO
CPW4SLB
225A
MLO
CPW4SLC
225A
FTL
CPW4SHB
300A
MLO
CPW4SLD
225A
MLO
CPW4SLE
400A
MCB/FTL
CPW4SHC
300A
MLO
CPW4SLF
400A
MLO
LS
IG
/3
CPT1SLA
150A
MCB
LS
I
5/
CPT2SLA
225A
MCB
CPT3SLA
80A
MLO
CPT4SLA
80A
MLO
LS
I
/3
M
M
M
M M M M
M
LS
I
5/
CP2SHA
125A
MLO
M
CP2SLA
150A
MCB
LS
I
5/
CPF2SHA
225A
MLO
M
CPF2SHA
225A
MCB
SPD
A.
B.
C.
D.
E.
F.
G.
H.
I.
J.
K.
L.
BASE BUILD SCOPE SHALL ONLY INCLUDE EMPTY CONDUITS
OF FEEDERS SHOWN ON THIS SHEET WITH FEEDER TAGS.
ADD ALTERNATE SCOPE SHALL INCLUDE PV PANELS,
CARPORTS, DC CONDUCTORS, INVERTERS, AC CONDUCTORS,
AC COMBINER BOXES, PV DISTRIBUTION BOARDS.
SEE DRAWING E0.1 FOR ABBREVIATIONS, SYMBOLS, GENERAL
NOTES.
THE CONTRACTOR SHALL COORDINATE EXACT LOCATION OF
EQUIPMENT POWER CONNECTIONS WITH EQUIPMENT
INSTALLER PRIOR TO ROUGH-IN.
COORDINATE FINAL LOCATION OF MECHANICAL EQUIPMENT
AND ASSOCIATED DISCONNECT SWITCHES, STARTERS, VFDS,
CONTROL POWER AND OTHER POWER REQUIREMENTS WITH
DIV 23 AND MECHANICAL DRAWINGS.
SEE MECHANICAL EQUIPMENT SCHEDULE FOR ASSOCIATED
OVERCURRENT DEVICES, DISCONNECT SWITCHES, STARTERS
AND WIRES.
VOLTAGE DROP SHALL BE LIMITED TO LESS THAN 3% FOR ALL
BRANCH CIRCUITS AND 2% FOR ALL FEEDERS.
CONTRACTOR SHALL COORDINATE AND FIELD VERIFY
REQUIREMENT OF NEUTRAL CONDUCTOR FOR ALL EQUIPMENT
AND PROVIDE NEUTRAL CONDUCTOR AS NECESSARY.
ALL LIFE SAFETY AND LIGHTING PANELBOARDS SHALL BE
EQUIPPED WITH TYPE 2 SPD.
ALL AUTOMATIC TRANSFER SWITCHES SHALL BE 4 POLE AND
EQUIPPED WITH BYPASS ISOLATION.
ALL UTILITY TRANSFORMERS DESCRIBED AS NAVOPACHE
TRANSFORMER TO BE COORDINATED WITH UTILITY AND
PROVIDED BY UTILITY. COORDINATE ALL FINAL REQUIREMENTS
AND AVAILABLE FAULT CURRENT CONTRIBUTIONS BASED ON
SUPPLIED EQUIPMENT. BASIS OF DESIGN 2500KVA, AND 5%Z.
ELECTRICAL EQUIPMENT SHALL BE CONFIGURED AS FOLLOWS:
-SERVICE ENTRANCE SECTIONS - UL891 REAR CONNECTED
SWITCHBOARD
-DISTRIBUTION SWITCHBOARDS WITH DRAW-OUT CIRCUIT
BREAKERS - UL891 SWITCHBOARD, DRAW-OUT MOLDED CASE
CIRCUIT BREAKERS
-GENERATOR PARALLELING GEAR - UL1558 SWITCHGEAR
GENERAL SHEET NOTES
OPTIONAL
STANDBYE505
E502
M
NAVOPACHE
TRANSFORMER
CDM2SH
1000A
480-277V
3PH/4W
LEVEL 1
LEVEL 2
LEVEL 2
LEVEL 3
LEVEL 3
LEVEL 4
SES-C
3200A BUS
PER NEC 705.12(B)
480-277V/3PH/4W
ATS-CSA
1000A
4P
LTG
TCPW3SLA/B
112.5kVA
PWR
TCPW3SLC/D
112.5kVA
TCPW3SLE/F
112.5kVA
PWR PWR
LEVEL 4
ROOF
A300 A225
A225
A400
T112
A300
A300 A225
A225
A400
T112
A300
A300
A400
A400
T112
A300 A225
A225
A125 A125
A1000
A1000
TCPT2SLA
75kVA K13 T75V1
TCPT1SLA
45kVA K13 T45V1
IDF
MDF
E501
MAIN
SC1
DC1
SC2
DC2 DC3 DC4 DC6
DC5
MATCHLINE
MATCHLINE
(3)
E521
TCPW4SLE/F
112.5kVA
T112
DC7
TCP2SLA
45kVA
T45
PWR
A300
TCPT2SLA
400A/225AF
TCPT1SLA
200A/150AF
SEL-751
(3)(3)
DC7
TCPF2SHA
75kVA
T75
MOBILE CLINICS
& EVSE
(FAC BLDG)
A225
A225
CPF2SHA
400A/225AF
#2
A
SHEET NUMBER
PROJECT NUMBER
SEALS AND SIGNATURES
ISSUED FOR DATE
Pl ot
Da te:
IHS Whiteriver Hospital 200 W Hospital Drive Whiteriver, Arizona, 85941
IHS Project #: 131445 IHS Contract #: 75H70123R00008 IHS Award Date: 02/02/2024
455 NORTH THIRD STREET
SUITE 250
PHOENIX, AZ 85004
602.265.2200 smithgroup.com
Drawn By: Checked By:
BASED ON PROGRAM OF REQUIREMENTS DATED [ 03/26/22],
POR AMENDMENT DATED [ 02/03/25], AND ON SCHEMATIC
DRAWINGS APPROVED [11/19/24].
5/2 8/2
6 1
2:0 9:0
2 P M
ELECTRICAL ONE LINE
DIAGRAM - SES-C, 1 OF 2
E5.3.1CD
W hit tin gto n
14904.000 Whittington Baca
X FEEDER SCHEDULE
SHEET KEYNOTES
E501 NAVOPACHE UTILITY METER. METER SHALL BE EQUIPPED
WITH CAPABILITY TO INTERFACE WITH BMS. ELECTRICAL
CONTRACTOR SHALL PROVIDE REQUIRED CONDUIT AND
COMMUNICATION WIRING FROM METER TO POINT OF
INTERFACE WITH BMS.
E502 COMPLIANCE WITH "NEC 240.87 ARC ENERGY REDUCTION"
REQUIRED. REDUCTION METHOD SHALL ALLOW FOR
REQUIRED SELECTIVE DEVICE COORDINATION AND ARC
FLASH REQUIREMENTS. REFER TO ELECTRICAL
SPECIFICATIONS FOR ADDITIONAL INFORMATION.
E505 PROVIDE PERMANENT IDENTIFICATION PLAQUE INDICATING
THE FOLLOWING: ELECTRICAL SERVICE #3 OF 5.
GENERATORS LOCATED IN ELECTRICAL EQUIPMENT YARD,
GENERATOR DISCONNECTS LOCATED IN ADJACENT
ELECTRICAL ROOM IN GMDB. PV DISCONNECT LOCATED AT
END OF THIS ELECTRICAL EQUIPMENT LINEUP.
E521 PROVIDE RELAY PROTECTION ELEMENTS REQUIRED BY
UTILITY AND MULTIPLE GENERATOR AND PV MONITORING
AND CONTROL SYSTEM MANUFACTURER. INTEGRATE SEL
RELAY AND PROGRAMMING INTO MULTIPLE GENERATOR
AND PV MONITORING SYSTEM AND CIRCUIT BREAKER.
PROVIDE AND PROGRAM PROTECTION ELEMENT SET POINTS
AND LOGIC WITHIN THE RELAY. REFER TO SEL-751 DETAIL
FOR ADDITIONAL INFORMATION.
SCALE: NOT TO SCALE1 ONE LINE DIAGRAM - SES-C, 1 OF 2
80 4#3 + 1#8 G, 1 1/4" C A125 4#2/0 + 1#6 G, 2" C
A225 4#300KCMIL + 1#2 G, 2 1/2" C
A300 4#500KCMIL + 1#2 G, 3" C
A400 2 SETS OF 4#250KCMIL + 1#1 G, (2) 2 1/2" C
A1000 3 SETS OF 4#600KCMIL + 1#4/0 G, (3) 3 1/2" C
T45 45KVA TRANSFORMER, 480-208Y/120V, 3PH
PRIMARY FEEDER: 3#3 + 1#8 G, 1 1/4" C
SECONDARY FEEDER: 4#1/0 + 1#6 G, 2" C
BONDING JUMPERS & GROUNDING ELECTRODE
CONDUCTOR: #6
T45V1 45KVA TRANSFORMER, 480-208Y/120V, 3PH
PRIMARY FEEDER: 3#1 + 1#4 G, 1 1/2" C
SECONDARY FEEDER: 4#1/0 + 1#6 G, 2" C
BONDING JUMPERS & GROUNDING ELECTRODE
CONDUCTOR: #6
T75 75KVA TRANSFORMER, 480-208Y/120V, 3PH
PRIMARY FEEDER: 3#1/0 + 1#6 G, 1 1/2" C
SECONDARY FEEDER: 4#4/0 + 1#2 G, 2 1/2" C
BONDING JUMPERS & GROUNDING ELECTRODE
CONDUCTOR: #2
T75V1 75KVA TRANSFORMER, 480-208Y/120V, 3PH
PRIMARY FEEDER: 3#3/0 + 1#4 G, 2" C
SECONDARY FEEDER: 4#4/0 + 1#2 G, 2 1/2" C
BONDING JUMPERS & GROUNDING ELECTRODE
CONDUCTOR: #2
T112 112.5KVA TRANSFORMER, 480-208Y/120V, 3PH
PRIMARY FEEDER: 3#3/0 + 1#6 G, 2" C
SECONDARY FEEDER: 2 SETS OF 4#3/0 + 1#2 G, (2)
2" C
BONDING JUMPERS & GROUNDING ELECTRODE
CONDUCTOR: #2
"A" DENOTES ALUMINUM CONDUCTORS, ALL OTHER CONDUCTORS SHALL BE COPPER
FINAL CONSTRUCTION DOCUMENTS 05MAR26
BID ADDENDUM-A 16APR26
BID ADDENDUM-E 28MAY26
A
B
05-28-26
/3
EN
L
CB
CPW3CHD
225A
MLO/FTL
SPD
LS
I
5/
CPW3CHE
225A
MLO
SPD
CPW3CHA
150A
MLO
CPW3CLA
125A
MCB
LS
I
0/
CPW3CLB
125A
MCB
CPW3CHB
150A
MLO
CPW3CLC
125A
MCB
LS
I
0/
CPW3CLD
125A
MCB
CPW3CHC
150A
MLO
CPW3CLE
125A
MCB
LS
I
0/
CPW3CLF
125A
MCB
CPW4CHD
125A
MLO
SPD
CPW4CHE
125A
MLO
SPD
CPW4CLA
125A
MCB
CPW4CHA
150A
MLO
CPW4CLB
125A
MCB
CPW4CLD
125A
MCB
CPW4CHB
150A
MLO
CPW4CLC
125A
MCB
CPW4CLF
125A
MCB
CPW4CHC
150A
MLO
CPW4CLE
125A
MCB
LS
IG
/3
EN
L
CC
LS
I
5/
LS
I
5/
LS
I
5/
LS
I
0/
LS
I
5/
LS
I
0/
LS
I
0/
LS
I
5/
LS
I
5/
LS
I
/3
VFD
LS
I
0/
VFD
LS
I
/3
VFD
LS
I
0/
VFD
LS
I
0/
LS
I
5/
/1
IPP2A
10kVA 125A
MCB
IPP2B
10kVA 125A
MCB
P1
IPP2C
10kVA 125A
MCB
/1
/1
P2
/1
P3
/2
IPPLE
25kVA 150A
MCB
LS
IG
0/
EN
L
CD
LS
I
0/
LS
I
0/
CPW3EHA
400A
MLO
CPW4EHA
225A
MLO
CPW3EHB
250A
MLO
CPW4EHB
150A
MLO
LS
I
5/
LS
I
5/
LS
I
5/
BP2 UA2 UB2
LS
I
/3
M
M M M
M M
M M M M M M M M M M M M M
M M M M M
M M M M M M M M
SPD
CPW4ELB
150A
MCB
CPW4ELA
150A
MCB
CPW3ELA
150A
MCB
CPW3ELB
150A
MCB
CPW1EHD
500A
MCB
CPW1EHC
500A
MCB
LS
I
0/
LS
I
0/
M M
LS
I
LS
IG
0/
PVY
M
A.
B.
C.
D.
E.
F.
G.
H.
I.
J.
K.
L.
BASE BUILD SCOPE SHALL ONLY INCLUDE EMPTY CONDUITS
OF FEEDERS SHOWN ON THIS SHEET WITH FEEDER TAGS.
ADD ALTERNATE SCOPE SHALL INCLUDE PV PANELS,
CARPORTS, DC CONDUCTORS, INVERTERS, AC CONDUCTORS,
AC COMBINER BOXES, PV DISTRIBUTION BOARDS.
SEE DRAWING E0.1 FOR ABBREVIATIONS, SYMBOLS, GENERAL
NOTES.
THE CONTRACTOR SHALL COORDINATE EXACT LOCATION OF
EQUIPMENT POWER CONNECTIONS WITH EQUIPMENT
INSTALLER PRIOR TO ROUGH-IN.
COORDINATE FINAL LOCATION OF MECHANICAL EQUIPMENT
AND ASSOCIATED DISCONNECT SWITCHES, STARTERS, VFDS,
CONTROL POWER AND OTHER POWER REQUIREMENTS WITH
DIV 23 AND MECHANICAL DRAWINGS.
SEE MECHANICAL EQUIPMENT SCHEDULE FOR ASSOCIATED
OVERCURRENT DEVICES, DISCONNECT SWITCHES, STARTERS
AND WIRES.
VOLTAGE DROP SHALL BE LIMITED TO LESS THAN 3% FOR ALL
BRANCH CIRCUITS AND 2% FOR ALL FEEDERS.
CONTRACTOR SHALL COORDINATE AND FIELD VERIFY
REQUIREMENT OF NEUTRAL CONDUCTOR FOR ALL EQUIPMENT
AND PROVIDE NEUTRAL CONDUCTOR AS NECESSARY.
ALL LIFE SAFETY AND LIGHTING PANELBOARDS SHALL BE
EQUIPPED WITH TYPE 2 SPD.
ALL AUTOMATIC TRANSFER SWITCHES SHALL BE 4 POLE AND
EQUIPPED WITH BYPASS ISOLATION.
ALL UTILITY TRANSFORMERS DESCRIBED AS NAVOPACHE
TRANSFORMER TO BE COORDINATED WITH UTILITY AND
PROVIDED BY UTILITY. COORDINATE ALL FINAL REQUIREMENTS
AND AVAILABLE FAULT CURRENT CONTRIBUTIONS BASED ON
SUPPLIED EQUIPMENT. BASIS OF DESIGN 2500KVA, AND 5%Z.
ELECTRICAL EQUIPMENT SHALL BE CONFIGURED AS FOLLOWS:
-SERVICE ENTRANCE SECTIONS - UL891 REAR CONNECTED
SWITCHBOARD
-DISTRIBUTION SWITCHBOARDS WITH DRAW-OUT CIRCUIT
BREAKERS - UL891 SWITCHBOARD, DRAW-OUT MOLDED CASE
CIRCUIT BREAKERS
-GENERATOR PARALLELING GEAR - UL1558 SWITCHGEAR
GENERAL SHEET NOTES
CRITICAL
CDM2CH
1000A
480-277V
3PH/4W
ATS-CCA
1000A
4P
LTG
TCPW3CLA/B
75kVA
PWR PWR PWR
EQUIPMENT
CDM2EHA
1600A
480-277V
3PH/4W
ATS-CEA
1600A
4P
PWR
TCPW3CLC/D
75kVA
PWR
TCPW3CLE/F
75kVA
PWR
TCPW4CLA/B
75kVA
TCPW4CLC/D
75kVA
TCPW4CLE/F
75kVA
PWR PWR PWR PWRPWR PWR
A1000
A1000
A1600
A1600
A150 T75D
T75D
A150 A150 T75D
T75D
A150 A150 T75D
T75D
A150 A225
A225
A125 A125
1000-3
ACCH-3
CHWP-3
100-3
HHWP-3
30-3
CBWP-3
100-3
EWH-3
OR PWR
FESS-1
80kVA
INPUT
OUTPUT
CDSUR1
400A 480V
3PH/4W
50-2
SUR-2268
50-2 50-2 50-2 80-2
OR LASER
EQUIPMENT
IPP3B
SUR-2267
225-3
EQUIPMENT
CDM2EHB
600A
480-277V
3PH/4W
ATS-CEB
600A
4P
A600
A600
A250A300
A225 A150
IPP1B
SUR-2272
225V1 225V1 225V1
UPS B2
INPUT
UPS A2/B2
BYPASS
UPS A2
INPUT
1000-3
NON-COINCIDENT
LOAD
B-3
SC3
DC22 DC18 DC19
SC4 SC5
DC7 DC8 DC9 DC10 DC11 DC12 DC13 DC14 DC15 DC20 DC21
DC16 DC17
DC23 DC24 DC25 DC26 DC27
DC28 DC29 DC30 DC31 DC32 DC33 DC34 DC35
MATCHLINE
MATCHLINE
TCPW4ELB
45kVA
T45
TCPW4ELA
45kVA
T45
TCPW4ELA
45kVA
T45
TCPW3ELB
45kVA
T45
300-3
TCPW1EHD
150kVA K-13
ISO XFMR
TCPW1EHC
150kVA K-13
ISO XFMR
IMAGING IMAGING
T150NT150N
DC36 DC37
PV C
, E O
E519
SC6
LEVEL 1
LEVEL 2
LEVEL 2
LEVEL 3
LEVEL 3
LEVEL 4
LEVEL 4
ROOF
E530
A
SHEET NUMBER
PROJECT NUMBER
SEALS AND SIGNATURES
ISSUED FOR DATE
Pl ot
Da te:
IHS Whiteriver Hospital 200 W Hospital Drive Whiteriver, Arizona, 85941
IHS Project #: 131445 IHS Contract #: 75H70123R00008 IHS Award Date: 02/02/2024
455 NORTH THIRD STREET
SUITE 250
PHOENIX, AZ 85004
602.265.2200 smithgroup.com
Drawn By: Checked By:
BASED ON PROGRAM OF REQUIREMENTS DATED [ 03/26/22],
POR AMENDMENT DATED [ 02/03/25], AND ON SCHEMATIC
DRAWINGS APPROVED [11/19/24].
5/2 8/2
6 1
2:0 9:0
7 P M
ELECTRICAL ONE LINE
DIAGRAM - SES-C, 2 OF 2
E5.3.2CD
W hit tin gto n
14904.000 Whittington Baca
X FEEDER SCHEDULE
SHEET KEYNOTES
E519 PV CIRCUIT BREAKER SHALL BE LOCATED AT LAST BUSSED
SPACE. PROVIDE PERMANENT IDENTIFICATION PLAQUE
INDICATING THE FOLLOWING: PV POWER SOURCE - DO NOT
RELOCATE THIS CIRCUIT BREAKER
E530 PROVIDE SHUNT TRIP CIRCUIT BREAKER FOR INTERFACE
WITH BOILER EMERGENCY SHUTDOWN EPO SWITCHES.
REFER TO EMP2.2.G FOR ADDITIONAL INFORMATION.
30-3 3#10 + 1#10 G, 3/4" C 50-2 2#6 + 1#10 G, 3/4" C 80-2 2#3 + 1#8 G, 1 1/4" C 100-3 3#1 + 1#8 G, 1 1/2" C 225-3 3#4/0 + 1#4 G, 2" C
225V1 4#250KCMIL + 1#3 G, 2 1/2" C
300-3 3#350KCMIL + 1#4 G, 3" C
400 2 SETS OF 4#3/0 + 1#3 G, (2) 2" C
1000-3 3 SETS OF 3#400KCMIL + 1#2/0 G, (3) 3" C
A125 4#2/0 + 1#6 G, 2" C A150 4#3/0 + 1#4 G, 2" C
A225 4#300KCMIL + 1#2 G, 2 1/2" C
A250 4#350KCMIL + 1#2 G, 2 1/2" C
A300 4#500KCMIL + 1#2 G, 3" C
A600 2 SETS OF 4#500KCMIL + 1#2/0 G, (2) 3" C
A1000 3 SETS OF 4#600KCMIL + 1#4/0 G, (3) 3 1/2" C
A1600 5 SETS OF 4#600KCMIL + 1#350KCMIL G, (5) 3 1/2" C
T45 45KVA TRANSFORMER, 480-208Y/120V, 3PH
PRIMARY FEEDER: 3#3 + 1#8 G, 1 1/4" C
SECONDARY FEEDER: 4#1/0 + 1#6 G, 2" C
BONDING JUMPERS & GROUNDING ELECTRODE
CONDUCTOR: #6
T75D 75KVA TRANSFORMER, 480-208Y/120V, 3PH
PRIMARY FEEDER: 3#1/0 + 1#6 G, 1 1/2" C
SECONDARY FEEDERS: 4#1/0 + 1#2 G, 2" C TO
EACH PANEL
BONDING JUMPERS & GROUNDING ELECTRODE
CONDUCTOR: #2
T150N 150KVA TRANSFORMER, 480-208Y/120V, 3PH
PRIMARY FEEDER: 3#250KCMIL + 1#4 G, 2 1/2" C
SECONDARY FEEDER: 2 SETS OF 3#250KCMIL,
1#500KCMIL N + 1/0 G, (2) 3" C
BONDING JUMPERS & GROUNDING ELECTRODE
CONDUCTOR: #1/0
SCALE: NOT TO SCALE1 ONE LINE DIAGRAM - SES-C, 2 OF 2
"A" DENOTES ALUMINUM CONDUCTORS, ALL OTHER CONDUCTORS SHALL BE COPPER
FINAL CONSTRUCTION DOCUMENTS 05MAR26
BID ADDENDUM-A 16APR26
BID ADDENDUM-E 28MAY26
A
A
B
05-28-26
0/
EN
L
DA
DPE1LHA
60A
MLO
SPD
DPE1LLA
60A
MLO
SPD
DPE2LHA
80A
MLO
SPD
DPE2LLA
60A
MCB
SPD
DPE3LHA
225A
MLO
SPD
DPE3LLA
60A
MCB
SPD
DPE4LHA
60A
MLO
SPD
DPE4LLA
60A
MLO
SPD
LSIG
2500/3
LS
IG
/3
EN
L
DB
DPE3SHC
225A
FTL
SPD
LS
I
5/
DPE3SHD
225A
MLO
SPD
DPE3SHA
300A
FTL
DPE3SLA
400A
MCB/FTL
LS
I
0/
DPE3SLB
400A
MLO
DPE3SHB
300A
FTL
DPE3SLC
400A
MCB/FTL
LS
I
0/
DPE3SLD
400A
MLO
DPE4SHC
125A
MLO
SPD
DPE4SHD
125A
MLO
SPD
DPE4SLA
400A
MCB/FTL
DPE4SHA
300A
MLO
DPE4SLB
400A
MLO
DPE4SLC
400A
MCB/FTL
DPE4SHB
300A
MLO
DPE4SLD
400A
MLO
LS
IG
/3
M
M M
M M M
DPF2LHA
200A
MLO
SPD
0/
DPF2LLA
100A
MCB
SPD
5/
SPD
A.
B.
C.
D.
E.
F.
G.
H.
I.
J.
K.
L.
BASE BUILD SCOPE SHALL ONLY INCLUDE EMPTY CONDUITS
OF FEEDERS SHOWN ON THIS SHEET WITH FEEDER TAGS.
ADD ALTERNATE SCOPE SHALL INCLUDE PV PANELS,
CARPORTS, DC CONDUCTORS, INVERTERS, AC CONDUCTORS,
AC COMBINER BOXES, PV DISTRIBUTION BOARDS.
SEE DRAWING E0.1 FOR ABBREVIATIONS, SYMBOLS, GENERAL
NOTES.
THE CONTRACTOR SHALL COORDINATE EXACT LOCATION OF
EQUIPMENT POWER CONNECTIONS WITH EQUIPMENT
INSTALLER PRIOR TO ROUGH-IN.
COORDINATE FINAL LOCATION OF MECHANICAL EQUIPMENT
AND ASSOCIATED DISCONNECT SWITCHES, STARTERS, VFDS,
CONTROL POWER AND OTHER POWER REQUIREMENTS WITH
DIV 23 AND MECHANICAL DRAWINGS.
SEE MECHANICAL EQUIPMENT SCHEDULE FOR ASSOCIATED
OVERCURRENT DEVICES, DISCONNECT SWITCHES, STARTERS
AND WIRES.
VOLTAGE DROP SHALL BE LIMITED TO LESS THAN 3% FOR ALL
BRANCH CIRCUITS AND 2% FOR ALL FEEDERS.
CONTRACTOR SHALL COORDINATE AND FIELD VERIFY
REQUIREMENT OF NEUTRAL CONDUCTOR FOR ALL EQUIPMENT
AND PROVIDE NEUTRAL CONDUCTOR AS NECESSARY.
ALL LIFE SAFETY AND LIGHTING PANELBOARDS SHALL BE
EQUIPPED WITH TYPE 2 SPD.
ALL AUTOMATIC TRANSFER SWITCHES SHALL BE 4 POLE AND
EQUIPPED WITH BYPASS ISOLATION.
ALL UTILITY TRANSFORMERS DESCRIBED AS NAVOPACHE
TRANSFORMER TO BE COORDINATED WITH UTILITY AND
PROVIDED BY UTILITY. COORDINATE ALL FINAL REQUIREMENTS
AND AVAILABLE FAULT CURRENT CONTRIBUTIONS BASED ON
SUPPLIED EQUIPMENT. BASIS OF DESIGN 2500KVA, AND 5%Z.
ELECTRICAL EQUIPMENT SHALL BE CONFIGURED AS FOLLOWS:
-SERVICE ENTRANCE SECTIONS - UL891 REAR CONNECTED
SWITCHBOARD
-DISTRIBUTION SWITCHBOARDS WITH DRAW-OUT CIRCUIT
BREAKERS - UL891 SWITCHBOARD, DRAW-OUT MOLDED CASE
CIRCUIT BREAKERS
-GENERATOR PARALLELING GEAR - UL1558 SWITCHGEAR
GENERAL SHEET NOTES
LIFE
SAFETY
ATS-DLA
400A
4P
TDPE2LLA
15kVA
OPTIONAL
STANDBYE506
E502
M
NAVOPACHE
TRANSFORMER
DDM2SH
1000A
480-277V
3PH/4W
LEVEL 1
LEVEL 2
LEVEL 2
LEVEL 3
LEVEL 3
LEVEL 4
ATS-DSA
1000A
4P
LTG
TDPE3SLA/B
112.5kVA
PWR
TDPE3SLC/D
112.5kVA
PWR
ATS-DCA
1000A
4P
LEVEL 4
ROOF
A400
T15
A225V2
A1000
A1000 A1000
A400
A400
T112
A300V1
A300
A400
A400
T112
A300V2 A225V1
A225
A125 A1256060
E501
MAIN
SD1
SD2 SD3
DD1 DD2 DD3
MATCHLINE
MATCHLINE
TDPF2LLA
30kVA
T30
FAC BLDG
A200
A200
DDM2LH
400A 480-277V
3PH/4W
A400
A300
TDPE4SLA/B
112.5kVA
T112
#2
DPF2LHA
200A/200AF
TDPE3LLA
15kVA
T15
TDPE4SLC/D
112.5kVA
T112
SES-D
3200A BUS
PER NEC 705.12(B)
480-277V/3PH/4W (3)
E521
SEL-751
(3)(3)
A
SHEET NUMBER
PROJECT NUMBER
SEALS AND SIGNATURES
ISSUED FOR DATE
Pl ot
Da te:
IHS Whiteriver Hospital 200 W Hospital Drive Whiteriver, Arizona, 85941
IHS Project #: 131445 IHS Contract #: 75H70123R00008 IHS Award Date: 02/02/2024
455 NORTH THIRD STREET
SUITE 250
PHOENIX, AZ 85004
602.265.2200 smithgroup.com
Drawn By: Checked By:
BASED ON PROGRAM OF REQUIREMENTS DATED [ 03/26/22],
POR AMENDMENT DATED [ 02/03/25], AND ON SCHEMATIC
DRAWINGS APPROVED [11/19/24].
5/2 8/2
6 1
2:0 9:1
1 P M
ELECTRICAL ONE LINE
DIAGRAM - SES-D, 1 OF 2
E5.4.1CD
W hit tin gto n
14904.000 Whittington Baca
X FEEDER SCHEDULE
SHEET KEYNOTES
E501 NAVOPACHE UTILITY METER. METER SHALL BE EQUIPPED
WITH CAPABILITY TO INTERFACE WITH BMS. ELECTRICAL
CONTRACTOR SHALL PROVIDE REQUIRED CONDUIT AND
COMMUNICATION WIRING FROM METER TO POINT OF
INTERFACE WITH BMS.
E502 COMPLIANCE WITH "NEC 240.87 ARC ENERGY REDUCTION"
REQUIRED. REDUCTION METHOD SHALL ALLOW FOR
REQUIRED SELECTIVE DEVICE COORDINATION AND ARC
FLASH REQUIREMENTS. REFER TO ELECTRICAL
SPECIFICATIONS FOR ADDITIONAL INFORMATION.
E506 PROVIDE PERMANENT IDENTIFICATION PLAQUE INDICATING
THE FOLLOWING: ELECTRICAL SERVICE #4 OF 5.
GENERATORS LOCATED IN ELECTRICAL EQUIPMENT YARD,
GENERATOR DISCONNECTS LOCATED IN ADJACENT
ELECTRICAL ROOM IN GMDB. PV DISCONNECT LOCATED AT
END OF THIS ELECTRICAL EQUIPMENT LINEUP.
E521 PROVIDE RELAY PROTECTION ELEMENTS REQUIRED BY
UTILITY AND MULTIPLE GENERATOR AND PV MONITORING
AND CONTROL SYSTEM MANUFACTURER. INTEGRATE SEL
RELAY AND PROGRAMMING INTO MULTIPLE GENERATOR
AND PV MONITORING SYSTEM AND CIRCUIT BREAKER.
PROVIDE AND PROGRAM PROTECTION ELEMENT SET POINTS
AND LOGIC WITHIN THE RELAY. REFER TO SEL-751 DETAIL
FOR ADDITIONAL INFORMATION.
SCALE: NOT TO SCALE1 ONE LINE DIAGRAM - SES-D, 1 OF 2
60 4#4 + 1#10 G, 1 1/4" C 80 4#3 + 1#8 G, 1 1/4" C A125 4#2/0 + 1#6 G, 2" C
A200 4#250KCMIL + 1#4 G, 2 1/2" C
A225 4#300KCMIL + 1#2 G, 2 1/2" C
A225V1 4#400KCMIL + 1#1/0 G, 2 1/2" C
A225V2 4#350KCMIL + 1#1/0 G, 2 1/2" C
A300 4#500KCMIL + 1#2 G, 3" C
A300V1 4#600KCMIL + 1#1 G, 3" C
A300V2 2 SETS OF 4#400KCMIL + 1#2/0 G, (2) 2 1/2" C
A400 2 SETS OF 4#250KCMIL + 1#1 G, (2) 2 1/2" C
A1000 3 SETS OF 4#600KCMIL + 1#4/0 G, (3) 3 1/2" C
T15 15KVA TRANSFORMER, 480-208Y/120V, 3PH
PRIMARY FEEDER: 3#10 + 1#10 G, 3/4" C
SECONDARY FEEDER: 4#4 + 1#8 G, 1 1/4" C
BONDING JUMPERS & GROUNDING ELECTRODE
CONDUCTOR: #8
T30 30KVA TRANSFORMER, 480-208Y/120V, 3PH
PRIMARY FEEDER: 3#6 + 1#10 G, 3/4" C
SECONDARY FEEDER: 4#1 + 1#6 G, 1 1/2" C
BONDING JUMPERS & GROUNDING ELECTRODE
CONDUCTOR: #6
T112 112.5KVA TRANSFORMER, 480-208Y/120V, 3PH
PRIMARY FEEDER: 3#3/0 + 1#6 G, 2" C
SECONDARY FEEDER: 2 SETS OF 4#3/0 + 1#2 G, (2)
2" C
BONDING JUMPERS & GROUNDING ELECTRODE
CONDUCTOR: #2
"A" DENOTES ALUMINUM CONDUCTORS, ALL OTHER CONDUCTORS SHALL BE COPPER
FINAL CONSTRUCTION DOCUMENTS 05MAR26
BID ADDENDUM-A 16APR26
BID ADDENDUM-E 28MAY26
A
B
05-28-26
DPE3SHD
225A
MLO
SPD
DPE4SHD
125A
MLO
SPD
LS
IG
/3
EN
L
DC
DPE3CHC
225A
MLO/FTL
SPD
LS
I
5/
DPE3CHD
225A
MLO
SPD
DPE3CHA
150A
MLO
DPE3CLA
125A
MCB
LS
I
0/
DPE3CLB
125A
MCB
DPE3CHB
150A
MLO
DPE3CLC
125A
MCB
LS
I
0/
DPE3CLD
125A
MCB
DPE4CHC
125A
MLO
SPD
DPE4CHD
125A
MLO
SPD
DPE4CLA
125A
MCB
DPE4CHA
150A
MLO
DPE4CLB
125A
MCB
DPE4CLD
125A
MCB
DPE4CHB
150A
MLO
DPE4CLC
125A
MCB
LS
IG
/3
EN
L
DD
LS
I
5/
LS
I
5/
LS
I
0/
LS
I
5/
LS
I
0/
LS
I
5/
LS
I
0/
VFD
LS
IG
0/
PVZ
LS
I
5/
/1
IPP1A
125A
MCB
IPP1B
125A
MCB
P2
IPP1C
125A
MCB
/1
/1
P1
/1
IPP3A
125A
MCB
IPP3B
125A
MCB
P3
IPP3C
125A
MCB
/1
LS
IG
0/
EN
L
DE
0/
5/
DAHU-3-4
225A
MLO
DAHU-1-2
400A
MLO
LS
I
0/
LS
I
0/
VFD VFD
LS
I
/3
VFD
LS
I
/3
VFD
LS
I
0/
LS
IG
0/
EN
L
DF
LS
I
0/
LS
I
0/
DPE3EHA
250A
MLO
DPE4EHA
150A
MLO
DPE3EHB
250A
MLO
DPE4EHB
150A
MLO
LS
I
0/
M M M M M
M M M M M M M M M
M
M M M M M
M M M M M M M M M
M M
SPD
DPE3ELA
150A
MCB
DPE3ELB
150A
MCB
DPE4ELA
150A
MCB
DPE4ELB
225A
MCB
DPA1ELA
100A
MCB
DPA2EHA
225A
MCB
LS
I
5/
M
A.
B.
C.
D.
E.
F.
G.
H.
I.
J.
K.
L.
BASE BUILD SCOPE SHALL ONLY INCLUDE EMPTY CONDUITS
OF FEEDERS SHOWN ON THIS SHEET WITH FEEDER TAGS.
ADD ALTERNATE SCOPE SHALL INCLUDE PV PANELS,
CARPORTS, DC CONDUCTORS, INVERTERS, AC CONDUCTORS,
AC COMBINER BOXES, PV DISTRIBUTION BOARDS.
SEE DRAWING E0.1 FOR ABBREVIATIONS, SYMBOLS, GENERAL
NOTES.
THE CONTRACTOR SHALL COORDINATE EXACT LOCATION OF
EQUIPMENT POWER CONNECTIONS WITH EQUIPMENT
INSTALLER PRIOR TO ROUGH-IN.
COORDINATE FINAL LOCATION OF MECHANICAL EQUIPMENT
AND ASSOCIATED DISCONNECT SWITCHES, STARTERS, VFDS,
CONTROL POWER AND OTHER POWER REQUIREMENTS WITH
DIV 23 AND MECHANICAL DRAWINGS.
SEE MECHANICAL EQUIPMENT SCHEDULE FOR ASSOCIATED
OVERCURRENT DEVICES, DISCONNECT SWITCHES, STARTERS
AND WIRES.
VOLTAGE DROP SHALL BE LIMITED TO LESS THAN 3% FOR ALL
BRANCH CIRCUITS AND 2% FOR ALL FEEDERS.
CONTRACTOR SHALL COORDINATE AND FIELD VERIFY
REQUIREMENT OF NEUTRAL CONDUCTOR FOR ALL EQUIPMENT
AND PROVIDE NEUTRAL CONDUCTOR AS NECESSARY.
ALL LIFE SAFETY AND LIGHTING PANELBOARDS SHALL BE
EQUIPPED WITH TYPE 2 SPD.
ALL AUTOMATIC TRANSFER SWITCHES SHALL BE 4 POLE AND
EQUIPPED WITH BYPASS ISOLATION.
ALL UTILITY TRANSFORMERS DESCRIBED AS NAVOPACHE
TRANSFORMER TO BE COORDINATED WITH UTILITY AND
PROVIDED BY UTILITY. COORDINATE ALL FINAL REQUIREMENTS
AND AVAILABLE FAULT CURRENT CONTRIBUTIONS BASED ON
SUPPLIED EQUIPMENT. BASIS OF DESIGN 2500KVA, AND 5%Z.
ELECTRICAL EQUIPMENT SHALL BE CONFIGURED AS FOLLOWS:
-SERVICE ENTRANCE SECTIONS - UL891 REAR CONNECTED
SWITCHBOARD
-DISTRIBUTION SWITCHBOARDS WITH DRAW-OUT CIRCUIT
BREAKERS - UL891 SWITCHBOARD, DRAW-OUT MOLDED CASE
CIRCUIT BREAKERS
-GENERATOR PARALLELING GEAR - UL1558 SWITCHGEAR
GENERAL SHEET NOTES
CRITICAL
DDM2CH
1000A
480-277V
3PH/4W
ATS-DCA
1000A
4P
LTG
TDPE3CLA/B
75kVA
PWR PWR
EQUIPMENT
DDM2EHA
1200A
480-277V
3PH/4W
ATS-DEA
1200A
4P
LEVEL 1
LEVEL 2
LEVEL 2
LEVEL 3
LEVEL 3
LEVEL 4
PWR
TDPE3CLC/D
75kVA
PWR
LEVEL 4
ROOF
TDPE4CLA/B
75kVA
TDPE4CLC/D
75kVA
PWR PWR PWR PWR
A1000
A1000
A1200
A1200
A150V2 T75DV2
T75DV2
A150V3 A150V1 T75DV3
T75DV3
A150V1 A225V1
A225
A125 A125
250-3
ASHP-1
PV D
OR PWR
FESS-2
80kVA
INPUT
OUTPUT
DDSUR2
400A 480V
3PH/3W
50-2
SUR-2272
50-2 50-2 50-2
SUR-2267
50-2
IPP2B
SUR-2268
225-3
EQUIPMENT
ATS-DEB
600A
4P
A600
A600
DDAHUA
600A
480-277V
3PH/4W
250-3 250-3
CHWP-4
50-3
HHWP-4
30-3
EH-4
EQUIPMENT
DDM2EHB
600A
480-277V
3PH/4W
ATS-DEC
600A
4P
A600
A600
A250V2A250V1
A150 A150
, E O
800-3
NON-COINCIDENT
LOAD
B-4
E519
SD4 SD5 SD6 SD7
DD4 DD5 DD6 DD7 DD8 DD9 DD10 DD11 DD12
DD13
DD14 DD15 DD16 DD17 DD18
DD19 DD20 DD21 DD22 DD23 DD24 DD25 DD26 DD27
DD28 DD29
SD8
MATCHLINE
MATCHLINE
TDPE3ELA
45kVA
T45
TDPE3ELB
45kVA
T45
TDPE4ELA
45kVA
T45
TDPE4ELB
75kVA
T75
EMS BLDG
300-3
DD30
A225V3
T30TDPA1ELA
30kVA
400 225
E530
A
SHEET NUMBER
PROJECT NUMBER
SEALS AND SIGNATURES
ISSUED FOR DATE
Pl ot
Da te:
IHS Whiteriver Hospital 200 W Hospital Drive Whiteriver, Arizona, 85941
IHS Project #: 131445 IHS Contract #: 75H70123R00008 IHS Award Date: 02/02/2024
455 NORTH THIRD STREET
SUITE 250
PHOENIX, AZ 85004
602.265.2200 smithgroup.com
Drawn By: Checked By:
BASED ON PROGRAM OF REQUIREMENTS DATED [ 03/26/22],
POR AMENDMENT DATED [ 02/03/25], AND ON SCHEMATIC
DRAWINGS APPROVED [11/19/24].
5/2 8/2
6 1
2:0 9:1
6 P M
ELECTRICAL ONE LINE
DIAGRAM - SES-D, 2 OF 2
E5.4.2CD
W hit tin gto n
14904.000 Whittington Baca
X FEEDER SCHEDULE
SHEET KEYNOTES
E519 PV CIRCUIT BREAKER SHALL BE LOCATED AT LAST BUSSED
SPACE. PROVIDE PERMANENT IDENTIFICATION PLAQUE
INDICATING THE FOLLOWING: PV POWER SOURCE - DO NOT
RELOCATE THIS CIRCUIT BREAKER
E530 PROVIDE SHUNT TRIP CIRCUIT BREAKER FOR INTERFACE
WITH BOILER EMERGENCY SHUTDOWN EPO SWITCHES.
REFER TO EMP2.2.G FOR ADDITIONAL INFORMATION.
SCALE: NOT TO SCALE1 ONE LINE DIAGRAM - SES-D, 2 OF 2
30-3 3#10 + 1#10 G, 3/4" C 50-2 2#6 + 1#10 G, 3/4" C 50-3 3#6 + 1#10 G, 3/4" C 225 4#4/0 + 1#4 G, 2 1/2" C 225-3 3#4/0 + 1#4 G, 2" C
250-3 3#250KCMIL + 1#4 G, 2 1/2" C
300-3 3#350KCMIL + 1#4 G, 3" C
400 2 SETS OF 4#3/0 + 1#3 G, (2) 2" C
800-3 3 SETS OF 3#300KCMIL + 1#1/0 G, (3) 3" C
A125 4#2/0 + 1#6 G, 2" C A150 4#3/0 + 1#4 G, 2" C
A150V1 4#400KCMIL + 1#1/0 G, 2-1/2" C
A150V2 4#250KCMIL + 1#2 G, 2-1/2" C
A150V3 4#300KCMIL + 1#1 G, 2-1/2" C
A225 4#300KCMIL + 1#2 G, 2 1/2" C
A225V1 4#400KCMIL + 1#1/0 G, 2 1/2" C
A225V3 4#500KCMIL + 1#2/0 G, 3" C
A250V1 4#400KCMIL + 1#1 G, 2 1/2" C
A250V2 4#600KCMIL + 1#2/0 G, 3" C
A600 2 SETS OF 4#500KCMIL + 1#2/0 G, (2) 3" C
A1000 3 SETS OF 4#600KCMIL + 1#4/0 G, (3) 3 1/2" C
A1200 4 SETS OF 4#500KCMIL + 1#250KCMIL G, (4) 3" C
T30 30KVA TRANSFORMER, 480-208Y/120V, 3PH
PRIMARY FEEDER: 3#6 + 1#10 G, 3/4" C
SECONDARY FEEDER: 4#1 + 1#6 G, 1 1/2" C
BONDING JUMPERS & GROUNDING ELECTRODE
CONDUCTOR: #6
T45 45KVA TRANSFORMER, 480-208Y/120V, 3PH
PRIMARY FEEDER: 3#3 + 1#8 G, 1 1/4" C
SECONDARY FEEDER: 4#1/0 + 1#6 G, 2" C
BONDING JUMPERS & GROUNDING ELECTRODE
CONDUCTOR: #6
T75 75KVA TRANSFORMER, 480-208Y/120V, 3PH
PRIMARY FEEDER: 3#1/0 + 1#6 G, 1 1/2" C
SECONDARY FEEDER: 4#4/0 + 1#2 G, 2 1/2" C
BONDING JUMPERS & GROUNDING ELECTRODE
CONDUCTOR: #2
T75DV2 75KVA TRANSFORMER, 480-208Y/120V, 3PH
PRIMARY FEEDER: 3#2/0 + 1#4 G, 1 1/2" C
SECONDARY FEEDERS: 4#1/0 + 1#2 G, 2" C TO
EACH PANEL
BONDING JUMPERS & GROUNDING ELECTRODE
CONDUCTOR: #2
T75DV3 75KVA TRANSFORMER, 480-208Y/120V, 3PH
PRIMARY FEEDER: 3#4/0 + 1#3 G, 2" C
SECONDARY FEEDERS: 4#1/0 + 1#2 G, 2" C TO
EACH PANEL
BONDING JUMPERS & GROUNDING ELECTRODE
CONDUCTOR: #2
"A" DENOTES ALUMINUM CONDUCTORS, ALL OTHER CONDUCTORS SHALL BE COPPER
FINAL CONSTRUCTION DOCUMENTS 05MAR26
BID ADDENDUM-A 16APR26
BID ADDENDUM-E 28MAY26
A
A
B
05-28-26
LS
IG
0/
EN
L
EC
LS
IG
0/
EN
L
EA
/3
/3
/3
/3
/3
LS
IG
/3
EN
L
EB
LS
I
0/
EKPH1A
600A
MLO
EKPL1A
400A
MCB/FTL
0/
0/
0/
EAHU-5-6
200A
MLO
EAHU-7-8
200A
MLO
EAHU-9-10
200A
MLO
VFD
/3
LS
IG
/3
EN
L
ED
FP
EKPL1B
225A
MCB
EPW2EHA
400A
MLO
EPW2ELA
400A
MCB
LS
I
0/
LS
I
5/
E N
L
LS
I
0/
VFD
LS
I
0/
LS
I
0/
VFD VFD
LS
I
/3
VFD
LS
I
/3
VFD
LS
I
0/
EP2EHA
250A
MLO
LS
I
0/
EP2ELA
225A
MCB
VFD
0/
LS
I
0/
M
M M M M
M M M M M M M M M M
M M M M M
EKPL1C
125A
MCB
ELSH
200A
MCB
ELSP
50A
MCB
LS
I
0/
M M
SPD
A.
B.
C.
D.
E.
F.
G.
H.
I.
J.
K.
L.
BASE BUILD SCOPE SHALL ONLY INCLUDE EMPTY CONDUITS
OF FEEDERS SHOWN ON THIS SHEET WITH FEEDER TAGS.
ADD ALTERNATE SCOPE SHALL INCLUDE PV PANELS,
CARPORTS, DC CONDUCTORS, INVERTERS, AC CONDUCTORS,
AC COMBINER BOXES, PV DISTRIBUTION BOARDS.
SEE DRAWING E0.1 FOR ABBREVIATIONS, SYMBOLS, GENERAL
NOTES.
THE CONTRACTOR SHALL COORDINATE EXACT LOCATION OF
EQUIPMENT POWER CONNECTIONS WITH EQUIPMENT
INSTALLER PRIOR TO ROUGH-IN.
COORDINATE FINAL LOCATION OF MECHANICAL EQUIPMENT
AND ASSOCIATED DISCONNECT SWITCHES, STARTERS, VFDS,
CONTROL POWER AND OTHER POWER REQUIREMENTS WITH
DIV 23 AND MECHANICAL DRAWINGS.
SEE MECHANICAL EQUIPMENT SCHEDULE FOR ASSOCIATED
OVERCURRENT DEVICES, DISCONNECT SWITCHES, STARTERS
AND WIRES.
VOLTAGE DROP SHALL BE LIMITED TO LESS THAN 3% FOR ALL
BRANCH CIRCUITS AND 2% FOR ALL FEEDERS.
CONTRACTOR SHALL COORDINATE AND FIELD VERIFY
REQUIREMENT OF NEUTRAL CONDUCTOR FOR ALL EQUIPMENT
AND PROVIDE NEUTRAL CONDUCTOR AS NECESSARY.
ALL LIFE SAFETY AND LIGHTING PANELBOARDS SHALL BE
EQUIPPED WITH TYPE 2 SPD.
ALL AUTOMATIC TRANSFER SWITCHES SHALL BE 4 POLE AND
EQUIPPED WITH BYPASS ISOLATION.
ALL UTILITY TRANSFORMERS DESCRIBED AS NAVOPACHE
TRANSFORMER TO BE COORDINATED WITH UTILITY AND
PROVIDED BY UTILITY. COORDINATE ALL FINAL REQUIREMENTS
AND AVAILABLE FAULT CURRENT CONTRIBUTIONS BASED ON
SUPPLIED EQUIPMENT. BASIS OF DESIGN 2500KVA, AND 5%Z.
ELECTRICAL EQUIPMENT SHALL BE CONFIGURED AS FOLLOWS:
-SERVICE ENTRANCE SECTIONS - UL891 REAR CONNECTED
SWITCHBOARD
-DISTRIBUTION SWITCHBOARDS WITH DRAW-OUT CIRCUIT
BREAKERS - UL891 SWITCHBOARD, DRAW-OUT MOLDED CASE
CIRCUIT BREAKERS
-GENERATOR PARALLELING GEAR - UL1558 SWITCHGEAR
GENERAL SHEET NOTES
E517
E502
E501 M
LEVEL 1
LEVEL 2
LEVEL 2
LEVEL 3
LEVEL 3
LEVEL 4
LEVEL 1
LEVEL 2
LEVEL 2
LEVEL 3
LEVEL 3
LEVEL 4
LEVEL 4
ROOF
LEVEL 4
ROOF
EQUIPMENT
ATS-EEC
800A
4P
A800
A800
EQUIPMENT
(ELEVATORS)
ATS-EEA
400A
4P
CNTRL
PNL
PUBLIC ELEV 3B
CNTRL
PNL
PUBLIC ELEV 3A
CNTRL
PNL
STAFF ELEV 2
CNTRL
PNL
PUBLIC ELEV 6B
CNTRL
PNL
PUBLIC ELEV 6A
EDE2EH
400A 480-277V
3PH/4W
A400
EQUIPMENT
(KITCHEN & CSPD)
EDM2EHA
1000A
480-277V
3PH/4W
ATS-EEB
1000A
4P
A1000
A1000
TEKPL1A
112.5kVA
T112
MAU-1
EQUIPMENT
EDM2EHB
1200A
480-277V
3PH/4W
ATS-EED
1200A
4P
A1200
A1200
DEDICATED
COMPARTMENT
FOR DIRECT
CONNECTION
OF FIRE PUMP
NEC 695.4(B)(3)(a)
E512
TEPW2ELA
112.5kVA
CSPD PWR CSPD PWR
A400 T112
KITCHEN PWR
EDAHUA
800A
480-277V
3PH/4W
FIRE PUMP
E514
E515
E516
250-3
ASHP-2
250-3 250-3
CHWP-5
50-3
HHWP-5
30-3
EH-5
CUP PWR
TEP2ELA
75kVA
T75
ACCH-4
50-3V2 50-3V2 50-3V2 50-3 50-3
TEKPL1B
75kVA
T75
800-3
NON-COINCIDENT
LOAD
B-5
MAIN
SE1
SE2 SE3 SE4 SE5
DE1 DE2 DE3 DE4 DE5 DE6 DE7 DE8 DE9 DE10
DE11 DE12 DE13 DE14 DE15
A600
300-3
E525E526
250-3
A200 A200 A200V2 60-3 200
A400
A125
(3)
E521
SEL-751
(3)(3)
SES-E
3200A BUS
PER NEC 705.12(B)
480-277V/3PH/4W
NAVOPACHE
TRANSFORMER
TELSP
15kVA
T15
200V1
DE3 DE4
#2
A
E530
A
B
SHEET NUMBER
PROJECT NUMBER
SEALS AND SIGNATURES
ISSUED FOR DATE
Pl ot
Da te:
IHS Whiteriver Hospital 200 W Hospital Drive Whiteriver, Arizona, 85941
IHS Project #: 131445 IHS Contract #: 75H70123R00008 IHS Award Date: 02/02/2024
455 NORTH THIRD STREET
SUITE 250
PHOENIX, AZ 85004
602.265.2200 smithgroup.com
Drawn By: Checked By:
BASED ON PROGRAM OF REQUIREMENTS DATED [ 03/26/22],
POR AMENDMENT DATED [ 02/03/25], AND ON SCHEMATIC
DRAWINGS APPROVED [11/19/24].
5/2 8/2
6 1
2:0 9:1
7 P M
ELECTRICAL ONE LINE
DIAGRAM - SES-E
E5.5.1CD
W hit tin gto n
14904.000 Whittington Baca
X FEEDER SCHEDULE
SHEET KEYNOTES
E501 NAVOPACHE UTILITY METER. METER SHALL BE EQUIPPED
WITH CAPABILITY TO INTERFACE WITH BMS. ELECTRICAL
CONTRACTOR SHALL PROVIDE REQUIRED CONDUIT AND
COMMUNICATION WIRING FROM METER TO POINT OF
INTERFACE WITH BMS.
E502 COMPLIANCE WITH "NEC 240.87 ARC ENERGY REDUCTION"
REQUIRED. REDUCTION METHOD SHALL ALLOW FOR
REQUIRED SELECTIVE DEVICE COORDINATION AND ARC
FLASH REQUIREMENTS. REFER TO ELECTRICAL
SPECIFICATIONS FOR ADDITIONAL INFORMATION.
E512 DIRECT CONNECTION OF FIRE PUMP AS ALLOWED BY NEC
695.3(A)(1) AND IN COMPLIANCE WITH NEC 695.4(A).
E514 FIRE PUMP CONTROLLER SHALL BE MONITORED BY THE FIRE
ALARM SYSTEM. LOSS OF NORMAL POWER SHALL ACTIVATE
SUPERVISORY ALARM AS FACP.
E515 PROVIDE CONTROL WIRING IN COMPLIANCE WITH NEC
695.14. BMS MONITORING SHALL BE PROVIDED.
E516 LISTED SINGLE POINT NORMAL & EMERGENCY CONNECTION
(WITH INTEGRAL AUTOMATIC TRANSFER SWITCH). INTERNAL
WIRING FROM CONTROLLER(S) TO PUMP MOTOR(S) SHALL
BE RUN IN CONDUIT TYPE AS SPECIFIED BY NEC 695.6(D) &
(F). ALL INTERNAL WIRING SHALL BE PROVIDED BY
EQUIPMENT MANUFACTURER. ALL REQUIRED MARKINGS &
APPROPRIATE PLAQUES SHALL BE PROVIDED IN
COMPLIANCE WITH THE NEC.
E517 PROVIDE PERMANENT IDENTIFICATION PLAQUE INDICATING
THE FOLLOWING: ELECTRICAL SERVICE #5 OF 5.
GENERATORS LOCATED IN ELECTRICAL EQUIPMENT YARD,
GENERATOR DISCONNECTS LOCATED IN ADJACENT
ELECTRICAL ROOM IN GMDB. PV DISCONNECT LOCATED AT
END OF THIS ELECTRICAL EQUIPMENT LINEUP.
E521 PROVIDE RELAY PROTECTION ELEMENTS REQUIRED BY
UTILITY AND MULTIPLE GENERATOR AND PV MONITORING
AND CONTROL…