A9-1b BP1_DWG2026-0612_15_ELECTRICAL_IHS-Whiteriver-Hospital_BID-ADD-G.pdf

PDF 8 MB Posted

Attached to
Whiteriver Hospital Construction
Solicitation number
75H70126R00016
Issued by

About this file

This document is a comprehensive set of electrical construction drawings and specifications for the IHS Whiteriver Hospital expansion project located in Whiteriver, Arizona. The project is identified as IHS Project #131445 under IHS Contract #75H70123R00008, with an award date of February 2, 2024. The drawings are prepared by SmithGroup and based on a Program of Requirements dated March 26, 2022, with amendments dated February 3, 2025, and schematic drawings approved November 19, 2024.

The electrical design encompasses multiple building systems including power distribution, lighting, receptacles, photovoltaic solar systems, generator backup systems, fire pump connections, UPS systems, and control wiring throughout the multi-level hospital facility. Key electrical infrastructure includes transformers ranging from 45 kVA to 112.5 kVA, automatic transfer switches with 4-pole configurations and bypass isolation, panelboards rated at 225A to 400A with surge protective devices, motor starters with variable frequency drives for HVAC equipment, and lighting control systems with occupancy sensors and dimmers. The photovoltaic system (Additive Option No. 6) specifies parking shade canopy-mounted panels totaling approximately 830 modules distributed across three carports with 62.5 kW inverters connected at 480/277V. The design maintains voltage drop limitations of 2% for feeders and 3% for branch circuits, provides dedicated neutral conductors for each branch circuit, and incorporates ground fault protection in required areas per NEC standards. All work must comply with the National Electrical Code, local building codes, fire codes, and includes comprehensive coordination requirements with mechanical systems, architectural elements, and equipment manufacturers throughout the construction process.

View the file

Other files

File Type Posted
A10-1b 0_SPEC2026-0618_Specifications_IHS-Whiteriver-Hospital_BID-ADD-H.pdf PDF
A10-1f BP1_DWG2026-0618_16_ICT_IHS-Whiteriver-Hospital_BID-ADD-H.pdf PDF
A10-1d BP1_DWG2026-0618_08_ARCHITECTURAL_IHS-Whiteriver-Hospital_BID-ADD-H.pdf PDF
A10-3a Attachment J12a AZ FORM 5000HC_TPT HEALTHCARE EXEMPTION CERTIFICATE.pdf PDF
A10-1c BP1_DWG2026-0618_06_LANDSCAPE_IHS-Whiteriver-Hospital_BID-ADD-H.pdf PDF
A10-1i BP2_DWG2026-0618_08_ARCHITECTURAL_IHS-Whiteriver-WWTP_BID-ADD-H.PDF PDF
A10-1a 0_MEM2026-0618_IHS-Whiteriver-Hospital_BID-Addendum-H.pdf PDF
A10-4 WR Pre-Proposal_RFIs 001 - 163.xlsx XLSX spreadsheet
Amend10 - WR Construction - 24 Jun 2026.pdf PDF
A10-1h BP2_DWG2026-0618_05_CIVIL_IHS-Whiteriver-UC_BID-ADD-H.pdf PDF
A10-1e BP1_DWG2026-0618_15_ELECTRICAL_IHS-Whiteriver-Hospital_BID-H.pdf PDF
A10-5 For RFI 154 - Geotech Reports.pdf PDF
A10-1g BP1_EXH2026-0618_10_MED-EQUIP_IHS-Whiteriver-Hospital_BID-ADD-H.pdf PDF
A10-3 Attachment J12 AZ State Tax Exemption Letter- Phoenix Area IHS.pdf PDF
A10-2 Section B.pdf PDF
A10-1j BP3_DWG2026-0618_05_CIVIL_IHS-Hon-Dah-UC_BID-ADD-H.pdf PDF
A9-1a MEM2026-0612_IHS-Whiteriver-Hospital_BID-Addendum-G.pdf PDF
A9-2 WR Pre-Proposal_RFIs 001 - 163.xlsx XLSX spreadsheet
Amend9 - WR Construction - 17 Jun 2026.pdf PDF
A8-1a 0_MEM2026-0609_IHS-Whiteriver-Hospital_BID-Addendum-F.pdf PDF
A8-1e BP1_DWG2026-0609_16_ICT_IHS-Whiteriver-Hospital_BID-ADD-F.pdf PDF
A8-1b 0_SPEC2026-0609_Specifications_IHS-Whiteriver-Hospital_BID-ADD-F.pdf PDF
A8-2 Section B.pdf PDF
Amend8 - WR Construction - 11 Jun 2026.pdf PDF
A8-1d BP1_DWG2026-0609_08_ARCHITECTURAL_IHS-Whiteriver-Hospital_BID-ADD-F.pdf PDF
A8-3 WR Pre-Proposal_RFIs 001 - 132.xlsx XLSX spreadsheet
A8-1c BP1_DWG2026-0609_06_LANDSCAPE_IHS-Whiteriver-Hospital_BID-ADD-F.pdf PDF
A7-1h BP4_DWG2026-0528_16_ICT_IHS-Whiteriver-Pump-House_BID-ADD-E.pdf PDF
A7-1c BP1_DWG2026-0528_08_ARCHITECTURAL_IHS-Whiteriver-Hospital_BID-ADD-E.pdf PDF
A7-1a 0_MEM2026-0528_IHS-Whiteriver-Hospital_BID-Addendum-E.pdf PDF
A7-2b Contact list Service Unit - RFI 109.xlsx XLSX spreadsheet
A7-1d BP1_DWG2026-0528_15_ELECTRICAL_IHS-Whiteriver-Hospital_BID-ADD-E.pdf PDF
A7-1g BP3_DWG2026-0528_16_ICT_IHS-Hondah-WWTP_BID-ADD-E.pdf PDF
A7-1f BP2_DWG2026-0528_16_ICT_IHS-Whiteriver-WWTP_BID-ADD-E.pdf PDF
A7-1e BP1_DWG2026-0528_16_ICT_IHS-Whiteriver-Hospital_BID-ADD-E.pdf PDF
A7-3 WR Standard Form 1442.pdf PDF
Amend7 - WR Construction - 29 May 2026.pdf PDF
A7-1b 00_SPEC2026-0528_Specifications_IHS-Whiteriver-Hospital_BID-ADD-E.pdf PDF
A7-2a WR Pre-Proposal_RFIs 001 - 121.xlsx XLSX spreadsheet
A6-1c BP1_DWG2026-0520_05_CIVIL_IHS-Whiteriver-ADOT-PLANS_BID-ADD-D.pdf PDF
A6-1a 0_MEM2026-0520_IHS-Whiteriver-Hospital_BID-Addendum-D.pdf PDF
A6-3b Attachment J06b - Highway AZ20260033 rev-0518.pdf PDF
A6-1e BP1_DWG2026-0520_08_ARCHITECTURAL_IHS-Whiteriver-Hospital_BID-ADD-D.pdf PDF
A6-1b SPEC2026-0520_Specifications_IHS-Whiteriver-Hospital_BID-ADD-D.pdf PDF
A6-3c Attachment J06c - Heavy AZ20260054 rev-0518.pdf PDF
A6-2 WR Pre-Proposal_RFIs 001 - 121.xlsx XLSX spreadsheet
A6-1d BP1_DWG2026-0521_06_LANDSCAPE_IHS-Whiteriver-Hospital_BID-ADD-D.pdf PDF
A6-3a Attachment J06a - Building AZ20260027 rev-0518.pdf PDF
A6-1f BP1_DWG2026-0520_16_ICT_IHS-Whiteriver-Hospital_BID-ADD-D.pdf PDF
Amend6 - WR Construction - 22 May 2026.pdf PDF
Show 40 more

Latest 50 of 107 listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

GAP

RP-XXXX SYMBOL INDICATES TO WHICH PANELBOARD INDICATED CIRCUITS IN THE ROOM

ARE TO BE CONNECTED.

GENERATOR ANNUNCIATOR (DERANGEMENT) PANEL

GENERATORG

LCP

RPX

EMU

UPS

PANELBOARD - (FLUSH/SURFACE)

DISTRIBUTION PANELBOARD

LIGHTING CONTROL PANEL, SURFACE MTD. UON.

LOW VOLTAGE LIGHTING RELAY PANEL, SURFACE MTD. UON

(X IS A VARIABLE LETTER BASED ON LEVEL AND AREA)

UNINTERRUPTIBLE POWER SUPPLY

ELECTRONIC METERING UNITM

SPD SURGE PROTECTIVE DEVICE

sEMU ELECTRONIC SUB METERING UNITsM

GROUND

ATS

FUSE

BUS DUCT PLUG-IN UNIT

AUTOMATIC TRANSFER SWITCH

LIGHTNING ARRESTOR

PLUG-IN CIRCUIT BREAKER, IP20 RATED, TOUCH SAFE BARRIER

E

K

T

FUSED SWITCH

DELTA CONNECTION

CPT

ELECTRIC INTERLOCK SYSTEM

CONTROL POWER TRANSFORMER

CURRENT TRANSFORMER

POTENTIAL TRANSFORMER

KEY INTERLOCKING SYSTEM

WYE CONNECTION - SOLID GROUND

SWITCH - SINGLE THROW

DRAWOUT TYPE, CIRCUIT BREAKER

STATIONARY CIRCUIT BREAKER

TRANSFORMER - TYPE AND RATING AS INDICATED

CB

VFD

PC

C CONTACTOR

HAND-OFF-AUTO SELECTOR SWITCH WITH PILOT LIGHT

VARIABLE FREQUENCY DRIVE/VARIABLE FREQUENCY MOTOR CONTROLLER

PACKAGE CONTROL UNIT (PROVIDED BY EQUIPMENT SUPPLIER)

MANUAL MOTOR STARTER WITH PILOT LIGHT AS INDICATED.

PUSHBUTTON STATION

DISCONNECT SWITCH, FUSED.

PROVIDE SWITCH AND FUSE AMPACITY EQUAL TO OR GREATER THAN FEEDER AMPACITY, UON

DISCONNECT SWITCH, NON-FUSED

PROVIDE SWITCH AMPACITY EQUAL TO OR GREATER THAN FEEDER AMPACITY, UON

COMBINATION MOTOR STARTER WITH DISCONNECT SWITCH.

PROVIDE SWITCH AND FUSE AMPACITY EQUAL TO OR GREATER THAN FEEDER AMPACITY, UON

CIRCUIT BREAKER IN NEMA 1 ENCLOSURE (FLUSH/SURFACE)

MOTOR AND CONNECTION

EMERGENCY POWER OFF

M

GROUNDING BUS BAR

DT

D2

PIPI

D2

DT

PH

TS

EM

MED

L

DT

XX LIGHTING FIXTURE TYPE DESIGNATION - "XX" INDICATES SPECIFIC TYPE

REFER TO LIGHT FIXTURE SCHEDULE

EXIT LIGHT - WALL/CEILING MOUNTED - DIRECTIONAL

ARROWS AS INDICATED SHADING INDICATES ILLUMINATED

FACE

LIGHTING TRACK - "X" DENOTES TYPE

LIGHTING FIXTURE - TYPE AS INDICATED

WALL MOUNTED LIGHTING FIXTURE- TYPE AS INDICATED

SITE LIGHTING FIXTURE TYPE AS INDICATED

LIGHTING FIXTURE - TYPE AS INDICATED (SUBSCRIPT INDICATES SWITCH CONTROL)

NICOLAUDIE ARCHITECTURAL STICK-DE3 TOUCH SCREEN CONTROL KEYPAD

FOR USE WITH DMX FIXTURES

SINGLE OR DOUBLE, REMOTE EMERGENCY LIGHTING FIXTURE

DUAL LEVEL SWITCHING. PROVIDE BALLASTS/DRIVERS REQUIRED TO

PROVIDE DUAL LEVEL SWITCHING.

PASSIVE INFRARED OCCUPANCY SENSOR (WALL/CEILING)

THREE-WAY SWITCH (S3P-THREE-WAY SWITCH WITH PILOT LIGHT)

SENSORSWITCH NIGHTINGALE 4 BUTTON DIMMER FOR PATIENT ROOMS

REMOTE TEST SWITCH FOR LIGHT FIXTURES EQUIPPED WITH INTEGRAL BATTERIES

FOUR - WAY SWITCH

PASSIVE INFRARED/ULTRASONIC OCCUPANCY SENSOR (WALL/CEILING)

PHOTO CELL

PASSIVE INFRARED/ULTRASONIC OCCUPANCY SENSOR, 2 POLE (WALL/CEILING)

HALF SHADING INDICATES FIXTURE CONNECTED TO CRITICAL BRANCH

SUBSCRIPT EM INDICATES INTEGRAL BATTERY UNIT

SHADING INDICATES FIXTURE CONNECTED TO LIFE SAFETY BRANCH

SUBSCRIPT EM INDICATES INTEGRAL BATTERY UNIT

SUBSCRIPT NL INDICATES FIXTURE TO OPERATE AS UNSWITCHED NIGHT LIGHT

EM

LOW VOLTAGE SWITCH

WALLWASH LIGHT FIXTURE

PASSIVE INFRARED/ULTRASONIC OCCUPANCY SENSOR

ELTD EMERGENCY LIGHTING TRANSFER DEVICE

CS COMBINATION PHOTOCELL/OCCUPANCY SENSOR

L1 SINGLE ZONE LOW VOLTAGE ON/OFF SWITCH

L1D SINGLE ZONE LOW VOLTAGE DIMMER SWITCH

L2 2 ZONE LOW VOLTAGE ON/OFF SWITCH

L2D 2 ZONE LOW VOLTAGE DIMMER SWITCH

L4 4 ZONE LOW VOLTAGE ON/OFF SWITCH

L4D 4 ZONE LOW VOLTAGE DIMMER SWITCH

NL

EM

NL

a

DTD PASSIVE INFRARED/ULTRASONIC OCCUPANCY SENSOR DIMMER

C CRITICAL

E EQUIPMENT

L LIFE SAFETY

S OPTIONAL STANDBY

U UNINTERRUPTIBLE

POWER SUPPLY

DISTRIBUTION BRANCH

D DISTRIBUTION BOARD / PANEL

P BRANCH CIRCUIT PANEL BOARD

KP KITCHEN POWER PANEL BOARD

A AUTOMATIC TRANSFER SWITCH

T TRANSFORMER

B BUSWAY

S SWITCHBOARD

G GENERATOR

EQUIPMENT TYPE

1 FIRST LEVEL

2 SECOND LEVEL

3 THIRD LEVEL

4 FOURTH LEVEL

R ROOF LEVEL

BUILDING LEVEL

X X X X X X X

SES SOURCE

EQUIPMENT TYPE

BUILDING LEVEL

VOLTAGE

A SES-A

B SES-B

C SES-C

D SES-D

E SES-E

SOURCE

C CENTRAL UTILITY PLANT

M MAIN ELECTRICAL ROOM

E SUB ELECTRICAL ROOM, EAST

W SUB ELECTRICAL ROOM, WEST

T COMMUNICATIONS ROOM

X EMS BUILDING

F FACILITIES

Y CENTRAL PLANT YARD

LOCATION

H 480/277V L 208/120V

VOLTAGE

LOCATION

DISTRIBUTION BRANCH

LETTER ID

A-1

TMH

EMH

EHH

FB

UG

GB

G

PB

CT

TELEPHONE MANHOLE

ELECTRIC MANHOLE

GROUND ROD

ELECTRIC HANDHOLE

GROUND BUS

GROUND CABLE, SIZE AS INDICATED

PLUG-IN BUSWAY

FEEDER BUSWAY

UNDERGROUND CONDUIT/DUCTBANK

CABLE TRAY

CONDUIT TURNED DOWN

CONDUIT TURNED UP

CONDUIT CAST IN CONCRETE OR BELOW SLAB

CONDUIT RUN CONCEALED IN FINISHED AREAS, EXPOSED IN UNFINISHED

AREAS OR BELOW ACCESS FLOORS

HOMERUN TO PANEL WITH CIRCUIT NUMBER(S) AS INDICATED

DEMOLITION WORK

J JJ

AFX

FBX

6-30R

ACCESS FLOOR BOX ("X" DENOTES TYPE AS SPECIFIED)

FLOOR BOX ("X" DENOTES TYPE AS SPECIFIED)

JUNCTION BOX (CEILING, FLOOR OR WALL MOUNTED) INDICATED IN POWER, LIGHTING &

FIRE ALARM SYSTEMS PLANS.

DIRECT CONNECTION TO EQUIPMENT

CEILING MOUNTED DUPLEX RECEPTACLE, NEMA 5-20R

("CR" SUBSCRIPT INDICATES CORD REEL)

SPECIAL PURPOSE RECEPTACLE. TYPE AS INDICATED ON DRAWINGS.

COORDINATE RECEPTACLE TYPE WITH ACTUAL EQUIPMENT PRIOR TO INSTALLATION.

HALF SWITCHED DUPLEX RECEPTACLE, NEMA 5-20R

EMERGENCY DUPLEX RECEPTACLE, NEMA 5-20R

(SHADING INDICATING EMERGENCY RECEPTACLE TYPICAL FOR ALL OTHER

RECEPTACLE TYPES)

QUADRUPLEX RECEPTACLE, (2) NEMA 5-20R, FLOOR MTD SERVICE FITTING, FLUSH TYPE UON

("S" DENOTES SURFACE TYPE)

CEILING MOUNTED QUADRUPLEX ISOLATED GROUND RECEPTACLE, (2)NEMA 5-20R,

DUPLEX ISOLATED GROUND RECEPTACLES WITH A COMMON FACEPLATE.

SINGLE RECEPTACLE, NEMA 5-20R, FLOOR MTD SERVICE FITTING, FLUSH TYPE UON

("S" DENOTES SURFACE TYPE)

CEILING MOUNTED DUPLEX ISOLATED GROUND RECEPTACLE, NEMA 5-20R

CEILING MOUNTED SINGLE ISOLATED GROUND RECEPTACLE, NEMA 5-20R

CEILING MOUNTED SINGLE RECEPTACLE, NEMA 5-20R

SINGLE RECEPTACLE, NEMA 5-20R, MOUNTED AT 24" AFF IN CLINICAL AREAS

QUADRUPLEX, (2)NEMA 5-20R, DUPLEX RECEPTACLES WITH A COMMON

FACEPLATE, MOUNTED AT 24" AFF IN CLINICAL AREAS

DUPLEX RECEPTACLE, NEMA 5-20R, MOUNTED AT 24" AFF IN CLINICAL AREAS

DUPLEX RECEPTACLE, NEMA 5-20R (SLASH INDICATES MOUNTING ABOVE FINISH COUNTER)

SINGLE RECEPTACLE, NEMA 5-20R (SLASH INDICATES MOUNTING ABOVE FINISH COUNTER)

RECEPTACLES MOUNTED ABOVE THE CEILING.

QUADRUPLEX RECEPTACLE, (2) NEMA 5-20R, DUPLEX RECEPTACLES WITH A

COMMON FACEPLATE. (SLASH INDICATES MOUNTING ABOVE FINISH COUNTER)

CEILING MOUNTED QUADRUPLEX RECEPTACLE, (2) NEMA 5-20R, DUPLEX RECEPTACLES WITH

A COMMON FACEPLATE.

GFCI, DUPLEX RECEPTACLE, NEMA 5-20R (SLASH INDICATES MOUNTING ABOVE FINISH COUNTER).

THE GFCI MUST BE INSTALLED IN A READILY ACCESSIBLE LOCATION PER NEC 210.8.

SURFACE RACEWAY (FILLED SPACES DENOTE RECEPTACLE LOCATIONS)

HC ADA DOOR ACTUATOR

P P

PD PD

POWER SERVICE FITTING (CEILING, FLOOR OR WALL MOUNTED) FOR CONNECTION TO

FURNITURE SYSTEM AS SPECIFIED.

COMBINATION POWER AND TELECOMMUNICATIONS BOX (CEILING, FLOOR OR WALL MOUNTED)

FOR POWER AND DATA CONNECTION INDICATED IN POWER & SPECIAL SYSTEMS PLANS.

PTX POKE-THROUGH ASSEMBLY ("X" DENOTES TYPE AS SPECIFIED)

SINGLE IG RECEPTACLE, NEMA 5-20R, FLOOR MTD SERVICE FITTING, FLUSH TYPE UON

("S" DENOTES SURFACE TYPE)

WHERE INDICATED IN AN EXISTING FLOOR, PROVIDE CORE DRILL PACKAGE

TO MAINTAIN FIRE RATING OF FLOOR. EXTEND CONDUIT AND WIRING IN

CEILING SPACE OF FLOOR BELOW TO ELECTRICAL CLOSET OR PANELBOARD.

DUPLEX RECEPTACLE, NEMA 5-20R, FLOOR MTD SERVICE FITTING, FLUSH TYPE UON

("S" DENOTES SURFACE TYPE)

DUPLEX IG RECEPTACLE, NEMA 5-20R, FLOOR MTD SERVICE FITTING, FLUSH TYPE UON

("S" DENOTES SURFACE TYPE)

QUADRUPLEX IG RECEPTACLE, (2) NEMA 5-20R, FLOOR MTD SERVICE FITTING, FLUSH TYPE UON

("S" DENOTES SURFACE TYPE)

COMBINATION USB DUPLEX RECEPTACLE, NEMA 5-20R, WITH (2) 5VDC, 2.1A USB CHARGING

PORTS

FULLY CONTROLLED DUPLEX/QUADRUPLEX RECEPTACLE, NEMA 5-20R. PROVIDE

ALL WIRING, EQUIPMENT, POWER PACKS, AND OCCUPANCY SENSOR INTEGRATION

REQUIRED TO TURN OFF RECEPTACLE(S) WHEN SPACE IS UNOCCUPIED.

HALF CONTROLLED DUPLEX/QUADRUPLEX RECEPTACLE, NEMA 5-20R. PROVIDE ALL

WIRING, EQUIPMENT, POWER PACKS, AND OCCUPANCY SENSOR INTEGRATION

REQUIRED TO TURN OFF HALF OF RECEPTACLE(S) WHEN SPACE IS UNOCCUPIED.

P

PD

REFER TO FLOOR BOX / POKE-THROUGH SCHEDULE FOR TYPES.

REFER TO CORRESPONDING ARCHITECTURAL HEADWALL ELEVATION FOR REQUIRED

ELECTRICAL DEVICE PLACEMENT, A8 SERIES PLANS.

BLANK FACE GFCI MODULE WITH VISUAL AND AUDIBLE ALARM, EATON #SGFDA20W, OR EQUIVALENT.

MOUNTED AT 44" AFF. INSTALL IN A READILY ACCESSIBLE LOCATION AND CONNECT TO A RECEPTACLE

REQUIRING GFCI PROTECTION THAT IS NOT IN A READILY ACCESSIBLE LOCATION.

FG

H-##

A B C A B C

A.

B.

C.

D.

E.

F.

G.

H.

I.

J.

K.

L.

M.

N.

O.

P.

Q.

R.

PROVIDE 1#12 + 1#12N + 1#12G FOR 20A BRANCH CIRCUITING,

UON; MAXIMUM OF THREE CIRCUITS PER CONDUIT; MINIMUM

CONDUIT SIZE OF 3/4" C, UON.

PROVIDE A DEDICATED NEUTRAL WIRE FOR EACH BRANCH

CIRCUIT.

COORDINATE DEVICE LOCATIONS AND MOUNTING HEIGHTS

WITH ARCHITECTURAL DRAWINGS PRIOR TO ROUGH-IN.

PROVIDE FIRE STOPPING FOR CONDUITS AND ELECTRICAL

EQUIPMENT FOR FLOOR SLABS, WALLS AND CEILINGS TO

MAINTAIN FIRE RATING.

INSTALL ELECTRICAL WORK IN ACCORDANCE WITH THE

NATIONAL ELECTRICAL CODE AND LOCAL BUILDING AND FIRE

CODES, IN A NEAT AND WORKMANLIKE MANNER.

LIMIT VOLTAGE DROP TO 2% FOR FEEDERS AND 3% FOR

BRANCH CIRCUITS. INCLUDE DERATING FACTOR FOR ROOF-

MOUNTED CONDUITS.

REFER TO ARCH. REFLECTED CEILING PLANS FOR EXACT

LOCATION OF CEILING MOUNTED DEVICES AND LIGHT

FIXTURES, UNLESS OTHERWISE INDICATED.

WHERE MULTIPLE SWITCHES, RECEPTACLES, AND OTHER

OUTLETS (EXCEPT WALL PHONES) ARE INDICATED PROVIDE

MULTI-GANG BACK BOXES WITH GANG BARRIERS AND A

COMMON FACEPLATE.

WHERE DIFFERENT RECESSED ELECTRICAL DEVICES WITH THE

SAME MOUNTING HEIGHTS ARE INDICATED SIDE-BY-SIDE,

MOUNT THE DEVICES SO THAT THERE IS FOUR INCHES

BETWEEN ADJACENT VERTICAL EDGES OF THE FACEPLATES,

UON.

WHERE ELECTRICAL DEVICES WITH DIFFERENT MOUNTING

HEIGHTS ARE LOCATED IN THE SAME AREA ALIGN DEVICES

VERTICALLY THROUGH THEIR CENTERLINES, UON.

WHERE EXIT SIGNS ARE INDICATED ABOVE DOOR MOUNT AS

FOLLOWS, CENTER THE EXIT SIGN BETWEEN TOP OF DOOR

FRAME AND CEILING IF DISTANCE BETWEEN TOP OF DOOR

FRAME AND CEILING IS 24 INCHES OR LESS; OTHERWISE

MOUNT BOTTOM OF EXIT SIGN 6 INCHES FROM TOP OF DOOR

FRAME, MOUNT OTHER WALL MOUNTED EXIT SIGNS IN THE

SAME AREA AT THE SAME HEIGHT. COORDINATE WITH

ARCHITECTURAL DETAILS.

EXIT SIGNS ARE TO BE TYPE "X1", UON.

PROVIDE SEPARATE NEUTRALS FOR DIMMING CIRCUITS.

PROVIDE FEEDERS AND BRANCH CIRCUITS WHICH HAVE AN

AMPACITY EQUAL TO OR GREATER THAN THE CIRCUIT

OVERCURRENT PROTECTIVE DEVICE RATING, U.O.N.

FURNITURE LAYOUTS ARE FOR REFERENCE ONLY.

COORDINATE THE FINAL LOCATION OF ELECTRICAL DEVICES

AND OUTLETS WITH ARCHITECT, OWNER AND FINAL FURNITURE

PLANS PRIOR TO INSTALLATION.

MOUNT DEVICES FLUSH WITH CONCEALED CONDUIT, EXCEPT

AS NOTED ON THE DRAWINGS AND IN MECHANICAL AND

ELECTRICAL EQUIPMENT ROOMS.

THE DRAWINGS REPRESENT ELECTRICAL DESIGN INTENT. THEY

ARE DIAGRAMMATIC. PROVIDE ALL COMPONENTS NECESSARY

FOR COMPLETE OPERATING ELECTRICAL SYSTEMS.

WHEN MORE THAN ONE 20A., 1P., 120 VOLT CIRCUIT FEEDS A

SURFACE RACEWAY CONNECT RECEPTACLES TO ALTERNATE

CIRCUITS AS FOLLOWS - U.O.N.

SECTION NUMBER

KEY NOTEEXXX

DETAIL NUMBER

DRAWING NUMBER WHERE DRAWN

DRAWING NUMBER WHERE DRAWN

A101

SIM

E0.1

THE FOLLOWING DEVICE TYPES ARE SPECIFIED ON ICT 'T' SERIES PLANS AND ARE ALSO REFLECTED ON 'E' SERIES ELECTRICAL PLANS TO SPECIFY LINE VOLTAGE POWER REQUIREMENTS. REFER TO 'T' SERIES PLANS FOR ELECTRICAL DEVICE REQUIREMENTS.

XX FLOOR MOUNT MULTISERVICE DEVICE

XX WALL MOUNT MULTISERVICE DEVICE

XX CEILING MOUNT MULTISERVICE DEVICE

DB4 DISPLAY BOX WITH TELECOM AND POWER

DB5 DISPLAY BOX WITH TELECOM AND POWER

DP PATIENT ROOM DISPLAY BOX WITH TELECOM AND POWER

FB10 FLOOR BOX WITH AV TELECOM AND POWER

FB34 FLOOR BOX WITH TELECOM AND POWER

PT10 POKE-THRU WITH AV, TELECOM AND POWER

PT11 POLE-THRU WITH TELECOM AND POWER

PT33 FLOOR FURNITURE FEED WITH TELECOM AND POWER

RK1 EQUIPMENT RACK PULL BOX WITH TELECOM AND POWER

RK2 EQUIPMENT RACK PULL BOX WITH TELECOM AND POWER

SYMBOLTAG

THE FOLLOWING SINGLE SERVICE DEVICE TYPES ARE SPECIFIED ON 'E' SERIES PLANS

XX SINGLE SERVICE FLOOR DEVICE

FB1 LEGRAND RFBA 2 GANG, OR EQUIVALENT

(1) 5-20R RECEPTACLE

FB2 LEGRAND RFBA 2 GANG, OR EQUIVALENT

(2) 5-20R RECEPTACLE

FBF LEGRAND RFBA 4 GANG, OR EQUIVALENT

CONFIGURED FOR SYSTEMS FURNITURE FEED

PT1 LEGRAND 6AT, OR EQUIVALENT

(1) 5-20R RECEPTACLE

PT2 LEGRAND 6AT, OR EQUIVALENT

(2) 5-20R RECEPTACLE

PTF LEGRAND 6AT, OR EQUIVALENT

CONFIGURED FOR SYSTEMS FURNITURE FEED

SYMBOLTAG

SHEET NUMBER

PROJECT NUMBER

SEALS AND SIGNATURES

ISSUED FOR DATE

Pl ot

Da te:

IHS Whiteriver Hospital 200 W Hospital Drive Whiteriver, Arizona, 85941

IHS Project #: 131445 IHS Contract #: 75H70123R00008 IHS Award Date: 02/02/2024

455 NORTH THIRD STREET

SUITE 250

PHOENIX, AZ 85004

602.265.2200 smithgroup.com

Drawn By: Checked By:

BASED ON PROGRAM OF REQUIREMENTS DATED [ 03/26/22],

POR AMENDMENT DATED [ 02/03/25], AND ON SCHEMATIC

DRAWINGS APPROVED [11/19/24].

6/1 2/2

6 1

:12 :16

P M

ELECTRICAL

ABBREVIATIONS AND

SYMBOLS

E0.1CD

W hit tin gto n

14904.000 Whittington Baca

ACCESS CONTROL DEVICES 3'-6" AFF

CLOCK OUTLETS 7'-0" AFF

DIMMERS 4'-0" AFF

DISCONNECT SWITCHES 5'-6" AFF

INDIVIDUAL CIRCUIT BREAKERS 5'-6" AFF

INTERCOM 3'-6" AFF

MOTOR STARTERS 5'-6" AFF

PANELBOARDS & CABINETS 6'-0" AFF TO TOP

PUSHBUTTONS 3'-6" AFF

RECEPTACLES 1'-6" AFF

RECEPTACLES ABOVE FINISHED

COUNTER

8" AFC

VANITY LIGHT IN TOILET 6" ABOVE THE MIRROR, UON

VOLUME CONTROLS 3'-6" AFF

WALL SWITCHES 4'-0" AFF

TELECOMMUNICATIONS OUTLETS 1'-6" AFF

TELECOMMUNICATIONS OUTLETS -

WALL PHONE

3'-6" AFF

TV OUTLETS 5'-0" AFF

NURSE CALL DOME LIGHTS 7'-6" AFF

NURSE CALL STATIONS 3'-6" AFF

FIRE ALARM - PULL STATIONS 3'-6" AFF

FIREMAN'S PHONE 3'-6" AFF

FIRE ALARM DEVICES HORN / SPEAKERS

/ STROBES (MOUNTING HEIGHT AT THE

TOP OF THE FIRE ALARM DEVICE OR 6"

BELOW CEILING WHICH IS LOWER)

7'-2" AFF TO TOP

ELECTRICAL ABBREVIATIONS ELECTRICAL LIGHTING SYMBOLS

DISTRIBUTION AND DIAGRAM SYMBOLS

ELECTRICAL WIRING SYMBOLS

ELECTRICAL EQUIPMENT SYMBOLS

ELECTRICAL POWER SYMBOLS GENERAL NOTES

MOUNTING HEIGHTS

REFERENCE SYMBOLS

1.

2.

3.

4.

MOUNTING HEIGHT NOTES:

ALL ELEVATIONS ARE TO CENTER LINE OF DEVICE, UNLESS

OTHERWISE NOTED.

REFER TO EQUIPMENT ELEVATION DRAWINGS FOR

COORDINATION WITH CASEWORK.

MOUNT MANUAL MOTOR STARTER ADJACENT TO OR ON UNIT.

REFER TO ARCHITECTURAL A0 SERIES FOR ADDITIONAL

ELECTRICAL DEVICE MOUNTING HEIGHTS AND DEVICE

ALIGNMENT RULES.

ALL ABBREVIATIONS, SYMBOLS AND LEGENDS SHOWN ON THIS DRAWING ARE NOT NECESSARILY USED.

A A AMPERES

AC ALTERNATING CURRENT

AF AMPERE FRAME (BREAKER RATING)

AFC ABOVE FINISHED COUNTER

AFF ABOVE FINISHED FLOOR

AFG ABOVE FINISHED GRADE

AHU AIR HANDLING UNIT

AIC AMPERE INTERRUPTING CAPACITY

ALT ALTERNATE

ARCH ARCHITECT

AT AMPERES TRIP

ATS AUTOMATIC TRANSFER SWITCH

AUTO AUTOMATIC

AUX AUXILIARY

AWG AMERICAN WIRE GAUGE

B BLDG BUILDING

BRKR, BKR BREAKER

C C CONDUIT

CATV CABLE TELEVISION

CB CIRCUIT BREAKER

CCTV CLOSED CIRCUIT TELEVISION

CE CONTROLLED EMERGENCY

CKT CIRCUIT

CLG CEILING

COM, COMM COMMUNICATIONS

COPY COPIER

CP CONTROL PANEL

CPT CONTROL POWER TRANSFORMER

CT CURRENT TRANSFORMER

CU COPPER

D DC DIRECT CURRENT

DISC DISCONNECT

DIST DISTRIBUTION

DIV DIVISION

DN DOWN

DP DISTRIBUTION PANEL

DPDT DOUBLE POLE DOUBLE THROW

DPST DOUBLE POLE SINGLE THROW

DW DISHWASHER

DWG DRAWING

E E, EX, EXIST EXISTING

EG EQUIPMENT GROUND

ELEC ELECTRIC, ELECTRICAL

ELEV ELEVATOR

EM. EMEG EMERGENCY

EMT ELECTRIC METALLIC CONDUIT

ENCL ENCLOSURE

EO ELECTRICALLY OPERATED

EQ, EQIP EQUIPMENT

EWC ELECTRIC WATER COOLER

EWH ELECTRIC WATER HEATER

F F FUSE

FA FIRE ALARM

FAAP FIRE ALARM ANNUNCIATOR PANEL

FACP FIRE ALARM CONTROL PANEL

FAEP FIRE ALARM EXTENDER PANEL

FC FOOT CANDLE

FDR FEEDER

FESS FLYWHEEL ENERGY STORAGE SYSTEM

FL, FLR FLOOR

FLA FULL LOAD AMPS

FLEX FLEXIBLE

FLUOR FLUORESCENT

FS FLUSH SENSOR

FT FOOT / FEET (')

FTL FEED THROUGH LUGS

G G, GND, GRD GROUND

GEN GENERATOR

GFCI GROUND FAULT CIRCUIT INTERRUPTER

GFI GROUND FAULT INTERRUPTER

H H HORIZONTAL MOUNTING

HH HAND HOLE

HOA HAND-OFF-AUTOMATIC

HP HORSEPOWER

HPS HIGH PRESSURE SODIUM

HR HOUR

HT HEIGHT

HTR HEATER

HVAC HEATING VENTILATION AND AIR

CONDITIONING

HZ HERTZ

I IG ISOLATED GROUND

IN INCH / INCHES (")

INCAND INCANDESCENT

J JB, JBOX JUNCTION BOX

K K KEY INTERLOCK

Kcmil 1000 CIRCULAR mils

KV KILOVOLTS (THOUSAND VOLTS)

KVA KILOVOLTS-AMPERES (THOUSAND

VOLT-AMPS)

kW KILOWATTS (THOUSAND WATTS)

KWH KILOWATT-HOURS

L-G LINE TO GROUND

L-L LINE TO LINE

L-N LINE TO NEUTRAL

L LA LIGHTNING ARRESTOR

LAN LOCAL AREA NETWORK

LC, LCP LIGHTING CONTROL PANEL

LP LIGHTING PANEL

LS LAVATORY SENSOR

LSI LONG-TIME, SHORT-TIME,

INSTANTANEOUS

LSIA LONG-TIME, SHORT-TIME,

INSTANTANEOUS,GROUND-FAULT ALARM

ONLY

LSIG LONG-TIME, SHORT-TIME,

INSTANTANEOUS,GROUND-FAULT

LTG LIGHTING

LV LOW VOLTAGE (BELOW 50 VOLTS)

M MCA MINIMUM CIRCUIT AMPACITY

MCB MAIN CIRCUIT BREAKER

MCC MOTOR CONTROL CENTER

MECH MECHANICAL

MFR MANUFACTURER

MH MANHOLE

MIN MINIMUM

MISC MISCELLANEOUS

MLO MAIN LUGS ONLY

MOCP MAXIMUM OVERCURRENT PROTECTION

MTD MOUNTED

MTG MOUNTING

MTS MANUAL TRANSFER SWITCH

MV MEDIUM VOLTAGE (OVER 600V LESS THAN

35KV)

N N NEUTRAL

NC NORMALLY CLOSED

NEC NATIONAL ELECTRICAL CODE

NEMA NATIONAL ELECTRICAL MANUFACTURERS

ASSOCIATION

NIC NOT IN CONTRACT

NL NIGHTLIGHT

NO NORMALLY OPEN

NO., NUM. # NUMBER

NTS NOT TO SCALE

O OC ON CENTER

OCPD OVERCURRENT PROTECTION DEVICE

OFCI OWNER FURNISHED, CONTRACTOR

INSTALLED

OFOI OWNER FURNISHED, OWNER INSTALLED

OH OVERHEAD

OHD OVERHEAD DOOR

OHE/T OVERHEAD ELECTRIC/TELEPHONE

OPP OPPOSITE

P P POLE

PA PUBLIC ADDRESS

PB PULL BOX

PDP POWER DISTRIBUTION PANEL

PE PHOTO ELECTRIC

PF POWER FACTOR

PH, Ø PHASE

PNL PANEL

PRI PRIMARY

PT POTENTIAL TRANSFORMER

PV PHOTOVOLTAIC

PVC POLYVINYL CHLORIDE

PWR POWER

Q QTY QUANTITY

R R, RE RELOCATE AS SHOWN

RCLP REMOTE CONTROL LIGHTING PANEL

RCPT RECEPTACLE

REF REFRIGERATOR

RF RADIO FREQUENCY

RGB RED, GREEN, BLUE (COLOR CHANGING)

RLA RATED (RUNNING) LOAD AMPS

RM ROOM

RP RECEPTACLE PANELBOARD

RSC RIGID STEEL CONDUIT

S SCH, SCHED SCHEDULE

SEC SECONDARY

SES SERVICE ENTRANCE SECTION

SF SQUARE FOOT

SPD SURGE PROTECTIVE DEVICE

SPDT SINGLE POLE DOUBLE THROW

SPEC(S) SPECIFICATION(S)

SPKR SPEAKER

SPST SINGLE POLE SINGLE THROW

STD STANDARD

SW SWITCH

SWBD SWITCHBOARD

SWGR SWITCHGEAR

SYM SYMMETRICAL

T T TAMPER RESISTANT

TB TERMINAL BLOCK

TBB TELEPHONE BACKBOARD

TC TIME CLOCK

TEL, TELE TELEPHONE

TELECOM TELECOMMUNICATIONS

TP TAMPERPROOF

TV TELEVISION

TYP TYPICAL

U UG UNDERGROUND

UGP UNDERGROUND PRIMARY

UGS UNDERGROUND SECONDARY

UGT UNDERGROUND TELEPHONE

UL UNDERWRITER'S LABORATORY

UON UNLESS OTHERWISE NOTED

UPS UNINTERRUPTIBLE POWER SUPPLY

V V VOLTS

VA VOLT-AMPERES

VFD VARIABLE FREQUENCY DRIVE/ VARIABLE

FREQUENCY MOTOR CONTROLLER

W W WIRE

W/ WITH

W/O WITHOUT

WHM WATT HOUR METER

WP WEATHERPROOF

WR WEATHER RESISTANT RATED

RECEPTACLE & WEATHER PROOF METAL

IN-USE COVER

X X REMOVE DEVICE

XFMR TRANSFORMER

Z %Z PERCENT IMPEDANCE

ELECTRICAL EQUIPMENT NAMING CONVENTION KEY

ALL ABBREVIATIONS, SYMBOLS AND LEGENDS SHOWN ON THIS DRAWING ARE NOT NECESSARILY USED.

ICT MULTISERVICE DEVICE SYMBOLSSINGLE SERVICE FLOOR DEVICE SYMBOLS

FINAL CONSTRUCTION DOCUMENTS 05MAR26

BID ADDENDUM-G 12JUN26

G

06-12-26

6-30-28

DN

DN

T TT T T

A,1 N 1049396.97E 762103.57

A,5N 1049607.57E 762146.84

C,5N 1049594.09E 762212.47

O

HE

O

HE

O

HE

G

G

G

G

G

G

G

G

G

G

G

G

G

G

G

G

G

G

G

G

G

G

G

G G

G

G

G

G

6"W (A

C)

4"W

(PVC)

2"W (P

VC)

4"W

(PVC

6"W (A

C)

4" W

(P

VC

8"W (P

VC)

8" W

(P

VC

6"

W (A

C)

3"W (PVC)

3"W (PVC)

36"SD

"X30

"SD

12"SD

"S

D

36"SD

24"SD

42"SD

42"SD

TS

TS

E

SS

S

S

S

SS

SD SD

SD

S

S

S

S

S

SD

S S

S

S

SD

SD

SD

SD

SD

SD

SD

S

S

S

S

ARV

ARV

ARV

ARV

ARV

SD

SD

SD

SD

SD

S

S

S S

S

S

CLEAR ZONE

360'

Thru Lane Begins

10.0000

20.0000

88.0000

10.0000

20.0000

88.0000

20.0000

88.0000

7' x1

5' x8

0C F

6"S(FM)

6"S(FM)

12"W

"W

6"

8" W

"W

8" W

"W

8" W

12"W

"W

"W

"W

"W

"W

"W

8" W

"W

"W

8" W

"W

"W

8" W

8"F

1.5"W

8"W

8"W

6"

24"SD

24"SD

72"SD

"S

D

12"SD

12"SD

"S

D

"S

D

"S

D

"S

D

6"S(FM)

6"S(FM

6"S(FM)

6" S(

FM

6" S(

FM

6" S(

FM

6" S(

FM

6"S(FM)

6"S(FM)

6" S(

FM

6" S(

FM

6" S(

FM

6" S(

FM

6" S(

FM

6" S(

FM

S S

S

S

S

S

S

S

S

S

S

S

S

S

S

S

SD

536870914 5610.87

BASE SET-AT

MISC

MISC

5407.19

SET-AT

5397.92

SET-AT

5371.38

SET-AT

5393.98

SET-AT

5532.80

SET-AT

5407.15

SET-AT

5400.37

SET-AT

5604.95

SET-AT

536870913 5398.06

BASE

WATER

T

T

CARPORT#2

EXISTING BUILDING

TO REMAIN

EXISTING BUILDING

TO REMAIN

EXISTING BUILDING

TO REMAIN

TYP

E103

E118

E119

ACC-2 A.

B.

C.

D.

ADDITIVE OPTION NO. 6, BASE BID PROVIDE ALL

UNDERGROUND CONDUITS ASSOCIATED WITH PHOTOVOLTAIC

SYSTEM INCLUDING BUT NOT LIMITED TO, HANDHOLES,

CONDUIT STUB-UPS BETWEEN MAIN ELECTRICAL ROOM,

PHOTOVOLTAIC DISTRIBUTION PANEL AND AC COMBINER

BOXES. CAP, PROTECT AND MARK CONDUIT LOCATIONS WITH

DETECTABLE UNDERGROUND TAPE FOR IMPLEMENTATION OF

FULLY FUNCTIONING PHOTOVOLTAIC SYSTEM IN THE FUTURE.

A PLAN INDICATING UNDERGROUND CONDUIT

SIZE/QUANTITY/ROUTING FOR FUTURE PHOTOVOLTAIC WILL BE

REQUIRED FOR REVIEW PRIOR TO BACKFILL. ALL

UNDERGROUND CONDUITS WILL BE REQUIRED TO BE SHOWN

IN AS-BUILT DOCUMENTATION.

ADDITIVE OPTION NO. 6, OPTION PROVIDE PARKING SHADE

CANOPY MOUNTED PHOTOVOLTAIC PANELS, DC CONDUCTORS,

INVERTERS, AC COMBINER BOXES, PHOTOVOLTAIC

DISTRIBUTION PANELBOARDS, AND ALL OTHER REQUIRED

PHOTOVOLTAIC HARDWARE AND ACCESSORIES FOR THE

CONSTRUCTION OF A COMPLETE AND FUNCTIONING

PHOTOVOLTAIC SYSTEM AS NOTED IN CONSTRUCTION

DRAWINGS AND SPECIFICATIONS. NOTE, PARKING SHADE

CANOPIES ARE NOT PART OF PHOTOVOLTAIC SYSTEM OPTION

AND ARE PROVIDED BY OTHERS.

COORDINATE WITH LOCAL UTILITY FOR ALL SITE SERVICE

REQUIREMENTS.

CONTACT LOCAL UTILITY TO IDENTIFY ALL EXISTING

UNDERGROUND UTILITIES.

GENERAL SHEET NOTES

SHEET NUMBER

PROJECT NUMBER

SEALS AND SIGNATURES

ISSUED FOR DATE

Pl ot

Da te:

IHS Whiteriver Hospital 200 W Hospital Drive Whiteriver, Arizona, 85941

IHS Project #: 131445 IHS Contract #: 75H70123R00008 IHS Award Date: 02/02/2024

455 NORTH THIRD STREET

SUITE 250

PHOENIX, AZ 85004

602.265.2200 smithgroup.com

Drawn By: Checked By:

BASED ON PROGRAM OF REQUIREMENTS DATED [ 03/26/22],

POR AMENDMENT DATED [ 02/03/25], AND ON SCHEMATIC

DRAWINGS APPROVED [11/19/24].

6/1 2/2

6 1

:12 :23

P M

ELECTRICAL SITE

PHOTOVOLTAIC SYSTEM

PLAN PHASE 1

E1.2.P1CD

W hit tin gto n

14904.000 Whittington Baca

E103 590W Q CELL PANELS OR APPROVED SIMILAR ARE THE

BASIS OF DESIGN FOR THE SOLAR ARRAY. ANY PROPOSED

DEVIATION FROM THIS SPECIFICATION MUST BE

COORDINATED WITH THE ENGINEER BEFORE

IMPLEMENTATION.

E118 PROVIDE (4) 3" CONDUITS FROM ACC-2, ROUTED

UNDERGROUND AND STUBBED UP INTO ELECTRICAL

ELC-2056. CONDUITS SHALL THEN BE ROUTED VERTICALLY

TO 2ND LEVEL CEILING SPACE AND EXTENDED OVERHEAD

TO PV-DPB LOCATED IN MAIN NORMAL ELECTRICAL

CUP-2374. PROVIDE PULL BOX(ES) AS REQUIRED.

UNDERGROUND ELBOWS SHALL BE PVC COATED GRMC.

EXPOSED EXTERIOR CONDUIT SHALL BE GRMC. PULL BOX

LOCATIONS SHALL BE COORDINATED WITH EOR PRIOR TO

COMMENCING WORK. REFER TO PV DIAGRAMS FOR

ADDITIONAL INFORMATION.

E119 PROVIDE (2) 3" CONDUITS FROM PV-DPA, (4) 3" CONDUITS

FROM PV-DPC, AND (4) 3" CONDUITS FROM PV-DPD, ROUTED

UNDERGROUND AND STUBBED TO AREA SHOWN. PV

DISTRIBUTION PANELS LOCATED IN MAIN NORMAL

ELECTRICAL ROOM CUP-2374. REFER TO SHEET E6.2.1 FOR

ADDITIONAL INFORMATION.

0 60' 120' 180'

GRAPHIC SCALE: 1" = 60' - 0"

PROJECT NORTH

SHEET KEYNOTES

SCALE: 1" = 80'-0"1 ELECTRICAL SITE PHOTOVOLTAIC SYSTEM PLAN PHASE 1

FINAL CONSTRUCTION DOCUMENTS 23JAN26

BID ADDENDUM-G 12JUN26

G

5407.15

SET-AT

5407.19

SET-AT

5397.92

SET-AT

5371.38

SET-AT

5393.98

SET-AT

5400.37

SET-AT

5532.80

SET-AT

5604.95

SET-AT

MISC

MISC

536870913 5398.06

BASE

WATER

536870914 5610.87

BASE SET-AT

O

HE

O

HE

O

HE

S

6" S(

VC

P)

6"S(VCP)6"S(VCP)

8"S

8"S

8"S

8" S

8"S

8" S

8"S 8"S

S 8"S(VCP)

8"S(VCP)

8" S

8" S

8" S

CLEAR ZONE

CLEAR ZONE

CLEAR ZONE

360'

Thru Lane Begins

10.0000

20.0000

88.0000

10.0000

20.0000

88.0000

20.0000

88.0000

SU

RG

ER

Y

VIS

ITO

R

SU

RG

ER

Y

VIS

ITO

R

SU

RG

ER

Y

VIS

ITO

R

A,1 N 1049396.97E 762103.57

A,5N 1049607.57E 762146.84

C,5N 1049594.09E 762212.47

DN

DN

T TT T T

T

J

J

J

J J J

J J J

A.

B.

C.

D.

ADDITIVE OPTION NO. 6, BASE BID PROVIDE ALL

UNDERGROUND CONDUITS ASSOCIATED WITH PHOTOVOLTAIC

SYSTEM INCLUDING BUT NOT LIMITED TO, HANDHOLES,

CONDUIT STUB-UPS BETWEEN MAIN ELECTRICAL ROOM,

PHOTOVOLTAIC DISTRIBUTION PANEL AND AC COMBINER

BOXES. CAP, PROTECT AND MARK CONDUIT LOCATIONS WITH

DETECTABLE UNDERGROUND TAPE FOR IMPLEMENTATION OF

FULLY FUNCTIONING PHOTOVOLTAIC SYSTEM IN THE FUTURE.

A PLAN INDICATING UNDERGROUND CONDUIT

SIZE/QUANTITY/ROUTING FOR FUTURE PHOTOVOLTAIC WILL BE

REQUIRED FOR REVIEW PRIOR TO BACKFILL. ALL

UNDERGROUND CONDUITS WILL BE REQUIRED TO BE SHOWN

IN AS-BUILT DOCUMENTATION.

ADDITIVE OPTION NO. 6, OPTION PROVIDE PARKING SHADE

CANOPY MOUNTED PHOTOVOLTAIC PANELS, DC CONDUCTORS,

INVERTERS, AC COMBINER BOXES, PHOTOVOLTAIC

DISTRIBUTION PANELBOARDS, AND ALL OTHER REQUIRED

PHOTOVOLTAIC HARDWARE AND ACCESSORIES FOR THE

CONSTRUCTION OF A COMPLETE AND FUNCTIONING

PHOTOVOLTAIC SYSTEM AS NOTED IN CONSTRUCTION

DRAWINGS AND SPECIFICATIONS. NOTE, PARKING SHADE

CANOPIES ARE NOT PART OF PHOTOVOLTAIC SYSTEM OPTION

AND ARE PROVIDED BY OTHERS.

COORDINATE WITH LOCAL UTILITY FOR ALL SITE SERVICE

REQUIREMENTS.

CONTACT LOCAL UTILITY TO IDENTIFY ALL EXISTING

UNDERGROUND UTILITIES.

GENERAL SHEET NOTES

CARPORT#1

CARPORT#4

EXISTING BUILDING

TO REMAIN

EXISTING BUILDING

TO REMAIN

EXISTING BUILDING

TO REMAIN

ACC-2

ACC-6

ACC-4

ACC-1

CARPORT#3

CARPORT#2

E120

TYP

E121

E122

CARPORT#5

CARPORT#6

ACC-3

ACC-4

SHEET NUMBER

PROJECT NUMBER

SEALS AND SIGNATURES

ISSUED FOR DATE

Pl ot

Da te:

IHS Whiteriver Hospital 200 W Hospital Drive Whiteriver, Arizona, 85941

IHS Project #: 131445 IHS Contract #: 75H70123R00008 IHS Award Date: 02/02/2024

455 NORTH THIRD STREET

SUITE 250

PHOENIX, AZ 85004

602.265.2200 smithgroup.com

Drawn By: Checked By:

BASED ON PROGRAM OF REQUIREMENTS DATED [ 03/26/22],

POR AMENDMENT DATED [ 02/03/25], AND ON SCHEMATIC

DRAWINGS APPROVED [11/19/24].

6/1 2/2

6 1

:12 :35

P M

ELECTRICAL SITE

PHOTOVOLTAIC SYSTEM

PLAN PHASE 2

E1.2.P2CD

W hit tin gto n

14904.000 Whittington Baca

E120 EXTEND FROM STUBBED LOCATION, UNDERGROUND

CONDUITS ORIGINATING FROM PV-DBD TO ACC. PROVIDE

PULL BOX(ES) AS REQUIRED. UNDERGROUND ELBOWS

SHALL BE PVC COATED GRMC. EXPOSED EXTERIOR

CONDUIT SHALL BE GRMC. PULL BOX LOCATIONS SHALL BE

COORDINATED WITH EOR PRIOR TO COMMENCING WORK.

REFER TO PV DIAGRAMS FOR ADDITIONAL INFORMATION

INCLUDING CONDUIT SIZES.

E121 EXTEND FROM STUBBED LOCATION, UNDERGROUND

CONDUITS ORIGINATING FROM PV-DBC TO ACC. PROVIDE

PULL BOX(ES) AS REQUIRED. UNDERGROUND ELBOWS

SHALL BE PVC COATED GRMC. EXPOSED EXTERIOR

CONDUIT SHALL BE GRMC. PULL BOX LOCATIONS SHALL BE

COORDINATED WITH EOR PRIOR TO COMMENCING WORK.

REFER TO PV DIAGRAMS FOR ADDITIONAL INFORMATION

INCLUDING CONDUIT SIZES.

E122 EXTEND FROM STUBBED LOCATION, UNDERGROUND

CONDUITS ORIGINATING FROM PV-DBA TO ACC. PROVIDE

PULL BOX(ES) AS REQUIRED. UNDERGROUND ELBOWS

SHALL BE PVC COATED GRMC. EXPOSED EXTERIOR

CONDUIT SHALL BE GRMC. PULL BOX LOCATIONS SHALL BE

COORDINATED WITH EOR PRIOR TO COMMENCING WORK.

REFER TO PV DIAGRAMS FOR ADDITIONAL INFORMATION

INCLUDING CONDUIT SIZES.

0 60' 120' 180'

GRAPHIC SCALE: 1" = 60' - 0"

PROJECT NORTH

SHEET KEYNOTES

SCALE: 1" = 80'-0"1 ELECTRICAL SITE PHOTOVOLTAIC SYSTEM PLAN PHASE 2

FINAL CONSTRUCTION DOCUMENTS 23JAN26

BID ADDENDUM-G 12JUN26

G

LSIG

2500/3

LS

IG

/3

EN

L

AB

LS

IG

0/

EN

L

AA

APW2LHA

225A

MLO

SPD

APW2LLA

150A

MCB

SPD

APW3LHA

80A

MLO

SPD

APW3LLA

60A

MLO

SPD

APW4LHA

80A

MLO

SPD

APW4LLA

60A

MLO

SPD

APW2SHD

225A

FTL

SPD

LS

I

5/

APW2SHE

225A

MLO

SPD

APW2SHA

300A

FTL

APW2SLA

400A

MCB/FTL

LS

I

0/

APW2SLB

400A

MLO

APW2SHB

300A

FTL

APW2SLC

400A

MCB/FTL

LS

I

0/

APW2SLD

400A

MLO

APW2SHC

300A

FTL

APW2SLE

400A

MCB/FTL

LS

I

0/

APW2SLF

400A

MLO

APW1LHA

80A

MLO

SPD

APW1LLA

60A

MLO

SPD

APW1SHD

125A

MLO

SPD

APW1SHE

125A

MLO

SPD

APW1SLA

225A

FTL

APW1SHA

300A

MLO

APW1SLB

225A

MLO

APW1SLC

225A

FTL

APW1SHB

300A

MLO

APW1SLD

225A

MLO

APW1SLE

225A

FTL

APW1SHC

300A

MLO

APW1SLF

225A

MLO

LS

IG

/3

EN

L

AC

APW2CHA

150A

MLO

LS

I

0/

APW1CHA

150A

MLO

LS

I

0/

LS

I

0/

APW1SLH

400A

MCB

APW1SLJ

225A

MLO

5/

M M M M

MM M

M

M

M M60 /3

APA2LHA

100A

MLO

SPD

APA2LLA

60A

MCB

SPD

APA2SHA

200A

MCB

LS

I

0/

M

APA2SLA

150A

MCB/FTL

APA1SLA

150A

MLO

AP2LLA

60A

MCB

SPD

/3

SPD

A.

B.

C.

D.

E.

F.

G.

H.

I.

J.

K.

L.

ADDITIVE OPTION NO. 6, BASE BID PROVIDE ALL

UNDERGROUND CONDUITS ASSOCIATED WITH PHOTOVOLTAIC

SYSTEM INCLUDING BUT NOT LIMITED TO, HANDHOLES,

CONDUIT STUB-UPS BETWEEN MAIN ELECTRICAL ROOM,

PHOTOVOLTAIC DISTRIBUTION PANEL AND AC COMBINER

BOXES. CAP, PROTECT AND MARK CONDUIT LOCATIONS WITH

DETECTABLE UNDERGROUND TAPE FOR IMPLEMENTATION OF

FULLY FUNCTIONING PHOTOVOLTAIC SYSTEM IN THE FUTURE.

A PLAN INDICATING UNDERGROUND CONDUIT

SIZE/QUANTITY/ROUTING FOR FUTURE PHOTOVOLTAIC WILL BE

REQUIRED FOR REVIEW PRIOR TO BACKFILL. ALL

UNDERGROUND CONDUITS WILL BE REQUIRED TO BE SHOWN

IN AS-BUILT DOCUMENTATION.

ADDITIVE OPTION NO. 6, OPTION PROVIDE PARKING SHADE

CANOPY MOUNTED PHOTOVOLTAIC PANELS, DC CONDUCTORS,

INVERTERS, AC COMBINER BOXES, PHOTOVOLTAIC

DISTRIBUTION PANELBOARDS, AND ALL OTHER REQUIRED

PHOTOVOLTAIC HARDWARE AND ACCESSORIES FOR THE

CONSTRUCTION OF A COMPLETE AND FUNCTIONING

PHOTOVOLTAIC SYSTEM AS NOTED IN CONSTRUCTION

DRAWINGS AND SPECIFICATIONS. NOTE, PARKING SHADE

CANOPIES ARE NOT PART OF PHOTOVOLTAIC SYSTEM OPTION

AND ARE PROVIDED BY OTHERS.

SEE DRAWING E0.1 FOR ABBREVIATIONS, SYMBOLS, GENERAL

NOTES.

THE CONTRACTOR SHALL COORDINATE EXACT LOCATION OF

EQUIPMENT POWER CONNECTIONS WITH EQUIPMENT

INSTALLER PRIOR TO ROUGH-IN.

COORDINATE FINAL LOCATION OF MECHANICAL EQUIPMENT

AND ASSOCIATED DISCONNECT SWITCHES, STARTERS, VFDS,

CONTROL POWER AND OTHER POWER REQUIREMENTS WITH

DIV 23 AND MECHANICAL DRAWINGS.

SEE MECHANICAL EQUIPMENT SCHEDULE FOR ASSOCIATED

OVERCURRENT DEVICES, DISCONNECT SWITCHES, STARTERS

AND WIRES.

VOLTAGE DROP SHALL BE LIMITED TO LESS THAN 3% FOR ALL

BRANCH CIRCUITS AND 2% FOR ALL FEEDERS.

CONTRACTOR SHALL COORDINATE AND FIELD VERIFY

REQUIREMENT OF NEUTRAL CONDUCTOR FOR ALL EQUIPMENT

AND PROVIDE NEUTRAL CONDUCTOR AS NECESSARY.

ALL LIFE SAFETY AND LIGHTING PANELBOARDS SHALL BE

EQUIPPED WITH TYPE 2 SPD.

ALL AUTOMATIC TRANSFER SWITCHES SHALL BE 4 POLE AND

EQUIPPED WITH BYPASS ISOLATION.

ALL UTILITY TRANSFORMERS DESCRIBED AS NAVOPACHE

TRANSFORMER TO BE COORDINATED WITH UTILITY AND

PROVIDED BY UTILITY. COORDINATE ALL FINAL REQUIREMENTS

AND AVAILABLE FAULT CURRENT CONTRIBUTIONS BASED ON

SUPPLIED EQUIPMENT. BASIS OF DESIGN 2500KVA, AND 5%Z.

BASIS OF DESIGN ELECTRICAL EQUIPMENT MANUFACTURERS

ARE SIEMENS, ASCO, AND CATERPILLAR. EQUIVALENT

EQUIPMENT FROM APPROVED MANUFACTURERS IS

ACCEPTABLE, PER DIV 26 SPECIFICATIONS.

GENERAL SHEET NOTES

OPTIONAL

STANDBYE503

E502

M

NAVOPACHE

TRANSFORMER

ADM2SH

1000A

480-277V

3PH/4W

LIFE

SAFETY

ATS-ALA

400A

4P

LEVEL 1

LEVEL 2

LEVEL 2

LEVEL 3

TAPW2LLA

45kVA

LEVEL 3

LEVEL 4

ATS-ASA

1000A

4P

LTG

TAPW2SLA/B

112.5kVA

PWR

TAPW2SLC/D

112.5kVA

TAPW2SLE/F

112.5kVA

PWR PWR

CRITICAL

ADM2CH

1000A

480-277V

3PH/4W

ATS-ACA

1000A

4P

PWR

PWR

LEVEL 4

ROOF

A1000

A400 A1000

T112T112T112T45

A300

A400

A300 A225

A225

A300

A300 A225

A225

A400

A300

A300 A225

A225

A400

A225

A125 A125

A225

A150

A1000

A1000

A150

E501

TAPW1SLH/J

112.5kVA

A225

LAB PWR

ADM2LH

400A 480-277V

3PH/4W

A225

MAIN

SA1

SA2 SA3 SA4

DA1 DA2 DA3 DA4 DA7

DA5 DA8

A400

TAPA2LLA

15kVA

60V1

T15

EMS PWR

A200V1

EMS BLDG

TAPA2SLA

45kVA

T45

A150

DA6

MATCHLINE

MATCHLINE

TAP2LLA

15kVA T15

T112

SES-A

3200A BUS

PER NEC 705.12(B)

480-277V/3PH/4W (3)

E521

SEL-751

(3)(3)

G

G G

G

G G G

G

G

G

G

E531

G

E532 E532

G

E532

G

G

G

SHEET NUMBER

PROJECT NUMBER

SEALS AND SIGNATURES

ISSUED FOR DATE

Pl ot

Da te:

IHS Whiteriver Hospital 200 W Hospital Drive Whiteriver, Arizona, 85941

IHS Project #: 131445 IHS Contract #: 75H70123R00008 IHS Award Date: 02/02/2024

455 NORTH THIRD STREET

SUITE 250

PHOENIX, AZ 85004

602.265.2200 smithgroup.com

Drawn By: Checked By:

BASED ON PROGRAM OF REQUIREMENTS DATED [ 03/26/22],

POR AMENDMENT DATED [ 02/03/25], AND ON SCHEMATIC

DRAWINGS APPROVED [11/19/24].

6/1 2/2

6 1

:12 :40

P M

ELECTRICAL ONE LINE

DIAGRAM - SES-A, 1 OF 2

E5.1.1CD

W hit tin gto n

14904.000 Whittington Baca

X FEEDER SCHEDULE

SHEET KEYNOTES

E501 NAVOPACHE UTILITY METER. METER SHALL BE EQUIPPED

WITH CAPABILITY TO INTERFACE WITH BMS. ELECTRICAL

CONTRACTOR SHALL PROVIDE REQUIRED CONDUIT AND

COMMUNICATION WIRING FROM METER TO POINT OF

INTERFACE WITH BMS.

E502 COMPLIANCE WITH "NEC 240.87 ARC ENERGY REDUCTION"

REQUIRED. REDUCTION METHOD SHALL ALLOW FOR

REQUIRED SELECTIVE DEVICE COORDINATION AND ARC

FLASH REQUIREMENTS. REFER TO ELECTRICAL

SPECIFICATIONS FOR ADDITIONAL INFORMATION.

E503 PROVIDE PERMANENT IDENTIFICATION PLAQUE INDICATING

THE FOLLOWING: ELECTRICAL SERVICE #1 OF 5.

GENERATORS LOCATED IN ELECTRICAL EQUIPMENT YARD,

GENERATOR DISCONNECTS LOCATED IN ADJACENT

ELECTRICAL ROOM IN GMDB. PV DISCONNECT LOCATED AT

END OF THIS ELECTRICAL EQUIPMENT LINEUP.

E521 PROVIDE RELAY PROTECTION ELEMENTS REQUIRED BY

UTILITY AND MULTIPLE GENERATOR AND PV MONITORING

AND CONTROL SYSTEM MANUFACTURER. INTEGRATE SEL

RELAY AND PROGRAMMING INTO MULTIPLE GENERATOR

AND PV MONITORING SYSTEM AND CIRCUIT BREAKER.

PROVIDE AND PROGRAM PROTECTION ELEMENT SET POINTS

AND LOGIC WITHIN THE RELAY. REFER TO SEL-751 DETAIL

FOR ADDITIONAL INFORMATION.

E531 ELECTRICAL EQUIPMENT CONSTRUCTION =

UL891 REAR CONNECTED SWITCHBOARD

DRAW-OUT LOW VOLTAGE POWER CIRCUIT BREAKERS

E532 ELECTRICAL EQUIPMENT CONSTRUCTION =

UL67 PANELBOARD

IP20, TOUCH-SAFE, PLUG-IN MOLDED CASE CIRCUIT

BREAKERS, ELECTRONIC TRIP UNIT

SCALE: NOT TO SCALE1 ONE LINE DIAGRAM - SES-A, 1 OF 2

60 4#4 + 1#10 G, 1 1/4" C 60V1 4#1 + 1#6 G, 1 1/2" C 80 4#3 + 1#8 G, 1 1/4" C A125 4#2/0 + 1#6 G, 2" C A150 4#3/0 + 1#4 G, 2" C

A200V1 4#400KCMIL + 1#1 G, 2 1/2" C

A225 4#300KCMIL + 1#2 G, 2 1/2" C

A300 4#500KCMIL + 1#2 G, 3" C

A400 2 SETS OF 4#250KCMIL + 1#1 G, (2) 2 1/2" C

A1000 3 SETS OF 4#600KCMIL + 1#4/0 G, (3) 3 1/2" C

T15 15KVA TRANSFORMER, 480-208Y/120V, 3PH

PRIMARY FEEDER: 3#10 + 1#10 G, 3/4" C

SECONDARY FEEDER: 4#4 + 1#8 G, 1 1/4" C

BONDING JUMPERS & GROUNDING ELECTRODE

CONDUCTOR: #8

T45 45KVA TRANSFORMER, 480-208Y/120V, 3PH

PRIMARY FEEDER: 3#3 + 1#8 G, 1 1/4" C

SECONDARY FEEDER: 4#1/0 + 1#6 G, 2" C

BONDING JUMPERS & GROUNDING ELECTRODE

CONDUCTOR: #6

T112 112.5KVA TRANSFORMER, 480-208Y/120V, 3PH

PRIMARY FEEDER: 3#3/0 + 1#6 G, 2" C

SECONDARY FEEDER: 2 SETS OF 4#3/0 + 1#2 G, (2)

2" C

BONDING JUMPERS & GROUNDING ELECTRODE

CONDUCTOR: #2

"A" DENOTES ALUMINUM CONDUCTORS, ALL OTHER CONDUCTORS SHALL BE COPPER

FINAL CONSTRUCTION DOCUMENTS 05MAR26

BID ADDENDUM-A 16APR26

BID ADDENDUM-E 28MAY26

BID ADDENDUM-G 12JUN26

G

G

G

APW2CHD

225A

MLO/FTL

SPD

LS

I

5/

APW2CHE

225A

MLO

SPD

APW2CLA

125A

MCB

APW2CLB

125A

MCB

APW2CHB

150A

MLO

APW2CLC

125A

MCB

LS

I

0/

APW2CLD

125A

MCB

APW2CHC

150A

MLO

APW2CLE

125A

MCB

LS

I

0/

APW2CLF

125A

MCB

APW1CHD

125A

MLO

SPD

APW1CHE

125A

MLO

SPD

APW1CLA

125A

MCB

APW1CHA

150A

MLO

APW1CLB

125A

MCB

APW1CLD

125A

MCB

APW1CHB

150A

MLO

APW1CLC

125A

MCB

APW1CLF

125A

MCB

APW1CHC

150A

MLO

APW1CLE

125A

MCB

LS

IG

/3

EN

L

AD

LS

I

0/

LS

I

5/

LS

I

5/

LS

I

0/

LS

I

5/

LS

I

5/

LS

I

5/

LS

I

0/

LS

I

5/

LS

I

/3

VFD

LS

I

0/

VFD

LS

I

/3

VFD

LS

I

0/

VFD

LS

IG

0/

PVW

LS

I

0/

LS

IG

0/

EN

L

AE

0/

0/

APW2EHA

300A

MLO

APW1EHA

150A

MLO

APW2EHB

250A

MLO

APW1EHB

150A

MLO

APW1ELA

150A

MCB

APW1ELB

150A

MCB

LS

I

/3

M M

M M M M M M M M M M M M M M

M M M M M M

M

APA1CLA

60A

MCB

APW2ELA

150A

MCB

APW2ELB

150A

MCB

A.

B.

C.

D.

E.

F.

G.

H.

I.

J.

K.

L.

ADDITIVE OPTION NO. 6, BASE BID PROVIDE ALL

UNDERGROUND CONDUITS ASSOCIATED WITH PHOTOVOLTAIC

SYSTEM INCLUDING BUT NOT LIMITED TO, HANDHOLES,

CONDUIT STUB-UPS BETWEEN MAIN ELECTRICAL ROOM,

PHOTOVOLTAIC DISTRIBUTION PANEL AND AC COMBINER

BOXES. CAP, PROTECT AND MARK CONDUIT LOCATIONS WITH

DETECTABLE UNDERGROUND TAPE FOR IMPLEMENTATION OF

FULLY FUNCTIONING PHOTOVOLTAIC SYSTEM IN THE FUTURE.

A PLAN INDICATING UNDERGROUND CONDUIT

SIZE/QUANTITY/ROUTING FOR FUTURE PHOTOVOLTAIC WILL BE

REQUIRED FOR REVIEW PRIOR TO BACKFILL. ALL

UNDERGROUND CONDUITS WILL BE REQUIRED TO BE SHOWN

IN AS-BUILT DOCUMENTATION.

ADDITIVE OPTION NO. 6, OPTION PROVIDE PARKING SHADE

CANOPY MOUNTED PHOTOVOLTAIC PANELS, DC CONDUCTORS,

INVERTERS, AC COMBINER BOXES, PHOTOVOLTAIC

DISTRIBUTION PANELBOARDS, AND ALL OTHER REQUIRED

PHOTOVOLTAIC HARDWARE AND ACCESSORIES FOR THE

CONSTRUCTION OF A COMPLETE AND FUNCTIONING

PHOTOVOLTAIC SYSTEM AS NOTED IN CONSTRUCTION

DRAWINGS AND SPECIFICATIONS. NOTE, PARKING SHADE

CANOPIES ARE NOT PART OF PHOTOVOLTAIC SYSTEM OPTION

AND ARE PROVIDED BY OTHERS.

SEE DRAWING E0.1 FOR ABBREVIATIONS, SYMBOLS, GENERAL

NOTES.

THE CONTRACTOR SHALL COORDINATE EXACT LOCATION OF

EQUIPMENT POWER CONNECTIONS WITH EQUIPMENT

INSTALLER PRIOR TO ROUGH-IN.

COORDINATE FINAL LOCATION OF MECHANICAL EQUIPMENT

AND ASSOCIATED DISCONNECT SWITCHES, STARTERS, VFDS,

CONTROL POWER AND OTHER POWER REQUIREMENTS WITH

DIV 23 AND MECHANICAL DRAWINGS.

SEE MECHANICAL EQUIPMENT SCHEDULE FOR ASSOCIATED

OVERCURRENT DEVICES, DISCONNECT SWITCHES, STARTERS

AND WIRES.

VOLTAGE DROP SHALL BE LIMITED TO LESS THAN 3% FOR ALL

BRANCH CIRCUITS AND 2% FOR ALL FEEDERS.

CONTRACTOR SHALL COORDINATE AND FIELD VERIFY

REQUIREMENT OF NEUTRAL CONDUCTOR FOR ALL EQUIPMENT

AND PROVIDE NEUTRAL CONDUCTOR AS NECESSARY.

ALL LIFE SAFETY AND LIGHTING PANELBOARDS SHALL BE

EQUIPPED WITH TYPE 2 SPD.

ALL AUTOMATIC TRANSFER SWITCHES SHALL BE 4 POLE AND

EQUIPPED WITH BYPASS ISOLATION.

ALL UTILITY TRANSFORMERS DESCRIBED AS NAVOPACHE

TRANSFORMER TO BE COORDINATED WITH UTILITY AND

PROVIDED BY UTILITY. COORDINATE ALL FINAL REQUIREMENTS

AND AVAILABLE FAULT CURRENT CONTRIBUTIONS BASED ON

SUPPLIED EQUIPMENT. BASIS OF DESIGN 2500KVA, AND 5%Z.

BASIS OF DESIGN ELECTRICAL EQUIPMENT MANUFACTURERS

ARE SIEMENS, ASCO, AND CATERPILLAR. EQUIVALENT

EQUIPMENT FROM APPROVED MANUFACTURERS IS

ACCEPTABLE, PER DIV 26 SPECIFICATIONS.

GENERAL SHEET NOTES

LTG

TAPW2CLA/B

75kVA

PWR PWR

EQUIPMENT

ADM2EHA

1600A

480-277V

3PH/4W

ATS-AEA

1600A

4P

LEVEL 1

LEVEL 2

LEVEL 2

LEVEL 3

LEVEL 3

LEVEL 4

PWR PWR

TAPW1CLA/B

75kVA

PWR

PWR

TAPW2CLC/D

75kVA

PWR

PWR

TAPW1CLC/D

75kVA

TAPW2CLE/F

75kVA

PWR

PWR PWR

TAPW1CLE/F

75kVA

LEVEL 4

ROOF

T75D T75D

T75DT75DT75D A150 A150 A225

A225

A150 A150 A150 A125 A125

A1600

A1600

1000-3

ACCH-1

CHWP-1

100-3

HHWP-1

30-3

CBWP-1

100-3

PV A

EH-1

EQUIPMENT

ADM2EHB

600A

480-277V

3PH/4W

ATS-AEB

600A

4P

A600

A600

A250A300

A150 T75D

300-3

TAPW1ELA

45kVA

T45

TAPW1ELB

45kVA

T45

, E O

1000-3

B-1

NON-COINCIDENT

LOAD

SA5 SA6

DA9 DA11 DA13 DA15 DA17 DA19 DA20 DA21 DA22 DA23 DA24 DA25 DA26 DA29

DA8 DA10 DA12 DA14 DA16 DA18

E519

60V1

EMS BLDG

SA7

MATCHLINE

TAPW2ELA

45kVA

T45

TAPW2ELB

45kVA

T45

A150

MATCHLINE

NON-COINCIDENT

LOAD

E530 G

G

G

G

G

G

G

G

G

G

G

G

G G G G G

G

G

E533 E532

SHEET NUMBER

PROJECT NUMBER

SEALS AND SIGNATURES

ISSUED FOR DATE

Pl ot

Da te:

IHS Whiteriver Hospital 200 W Hospital Drive Whiteriver, Arizona, 85941

IHS Project #: 131445 IHS Contract #: 75H70123R00008 IHS Award Date: 02/02/2024

455 NORTH THIRD STREET

SUITE 250

PHOENIX, AZ 85004

602.265.2200 smithgroup.com

Drawn By: Checked By:

BASED ON PROGRAM OF REQUIREMENTS DATED [ 03/26/22],

POR AMENDMENT DATED [ 02/03/25], AND ON SCHEMATIC

DRAWINGS APPROVED [11/19/24].

6/1 2/2

6 1

:12 :45

P M

ELECTRICAL ONE LINE

DIAGRAM - SES-A, 2 OF 2

E5.1.2CD

W hit tin gto n

14904.000 Whittington Baca

X FEEDER SCHEDULE

SHEET KEYNOTES

E519 PV CIRCUIT BREAKER SHALL BE LOCATED AT LAST BUSSED

SPACE. PROVIDE PERMANENT IDENTIFICATION PLAQUE

INDICATING THE FOLLOWING: PV POWER SOURCE - DO NOT

RELOCATE THIS CIRCUIT BREAKER

E530 PROVIDE SHUNT TRIP CIRCUIT BREAKER FOR INTERFACE

WITH BOILER EMERGENCY SHUTDOWN EPO SWITCHES.

REFER TO EMP2.2.G FOR ADDITIONAL INFORMATION.

E532 ELECTRICAL EQUIPMENT CONSTRUCTION =

UL67 PANELBOARD

IP20, TOUCH-SAFE, PLUG-IN MOLDED CASE CIRCUIT

BREAKERS, ELECTRONIC TRIP UNIT

E533 ELECTRICAL EQUIPMENT CONSTRUCTION =

UL891 SWITCHBOARD

</= 600A IP20, TOUCH-SAFE, PLUG-IN MOLDED CASE CIRCUIT

BREAKERS, ELECTRONIC TRIP UNIT

> 600A FIXED MOUNT MOLDED CASE CIRCUIT BREAKERS,

ELECTRONIC TRIP UNIT

SCALE: NOT TO SCALE1 ONE LINE DIAGRAM - SES-A, 2 OF 2

30-3 3#10 + 1#10 G, 3/4" C 60V1 4#1 + 1#6 G, 1 1/2" C 100-3 3#1 + 1#8 G, 1 1/2" C

300-3 3#350KCMIL + 1#4 G, 3" C

1000-3 3 SETS OF 3#400KCMIL + 1#2/0 G, (3) 3" C

A125 4#2/0 + 1#6 G, 2" C A150 4#3/0 + 1#4 G, 2" C

A225 4#300KCMIL + 1#2 G, 2 1/2" C

A250 4#350KCMIL + 1#2 G, 2 1/2" C

A300 4#500KCMIL + 1#2 G, 3" C

A600 2 SETS OF 4#500KCMIL + 1#2/0 G, (2) 3" C

A1600 5 SETS OF 4#600KCMIL + 1#350KCMIL G, (5) 3 1/2" C

T45 45KVA TRANSFORMER, 480-208Y/120V, 3PH

PRIMARY FEEDER: 3#3 + 1#8 G, 1 1/4" C

SECONDARY FEEDER: 4#1/0 + 1#6 G, 2" C

BONDING JUMPERS & GROUNDING ELECTRODE

CONDUCTOR: #6

T75D 75KVA TRANSFORMER, 480-208Y/120V, 3PH

PRIMARY FEEDER: 3#1/0 + 1#6 G, 1 1/2" C

SECONDARY FEEDERS: 4#1/0 + 1#2 G, 2" C TO EACH PANEL

BONDING JUMPERS & GROUNDING ELECTRODE

CONDUCTOR: #2

"A" DENOTES ALUMINUM CONDUCTORS, ALL OTHER CONDUCTORS SHALL BE COPPER

FINAL CONSTRUCTION DOCUMENTS 05MAR26

BID ADDENDUM-A 16APR26

BID ADDENDUM-E 28MAY26

BID ADDENDUM-G 12JUN26

G

G

G

LS

IG

/3

EN

L

BB

LS

IG

0/

EN

L

BA

BPE2SHD

225A

FTL

SPD

LS

I

5/

BPE2SHE

225A

MLO

SPD

BPE2SHA

300A

FTL

BPE2SLA

400A

MCB/FTL

LS

I

0/

BPE2SLB

400A

MLO

BPE2SHB

300A

FTL

BPE2SLC

225A

MCB/FTL

LS

I

0/

BPE2SLD

225A

MLO

BPE1SHD

125A

MLO

SPD

BPE1SHE

125A

MLO

SPD

BPE1SLA

225A

FTL

BPE1SHA

300A

MLO

BPE1SLB

225A

MLO

BPE1SLC

225A

FTL

BPE1SHB

300A

MLO

BPE1SLD

225A

MLO

/3

/3

/3

/3

/3

LS

IG

/3

LS

I

/3

BPT2SLA

150A

MCB

BPT2SLB

225A

MCB

LS

I

5/

BPT1SLA

80A

MLO

BPT3SLA

80A

MLO

BPT4SLA

80A

MLO

BPT2SLC

225A

MCB

LS

I

5/

BPT1SLB

80A

MLO

BPT3SLB

80A

MLO

BPT4SLB

80A

MLO

BPF2SHA

250A

MLO

BPF2SLA

225A

MCB

LS

I

0/

M

M M

M M M M M M M

SPD

A.

B.

C.

D.

E.

F.

G.

H.

I.

J.

K.

L.

ADDITIVE OPTION NO. 6, BASE BID PROVIDE ALL

UNDERGROUND CONDUITS ASSOCIATED WITH PHOTOVOLTAIC

SYSTEM INCLUDING BUT NOT LIMITED TO, HANDHOLES,

CONDUIT STUB-UPS BETWEEN MAIN ELECTRICAL ROOM,

PHOTOVOLTAIC DISTRIBUTION PANEL AND AC COMBINER

BOXES. CAP, PROTECT AND MARK CONDUIT LOCATIONS WITH

DETECTABLE UNDERGROUND TAPE FOR IMPLEMENTATION OF

FULLY FUNCTIONING PHOTOVOLTAIC SYSTEM IN THE FUTURE.

A PLAN INDICATING UNDERGROUND CONDUIT

SIZE/QUANTITY/ROUTING FOR FUTURE PHOTOVOLTAIC WILL BE

REQUIRED FOR REVIEW PRIOR TO BACKFILL. ALL

UNDERGROUND CONDUITS WILL BE REQUIRED TO BE SHOWN

IN AS-BUILT DOCUMENTATION.

ADDITIVE OPTION NO. 6, OPTION PROVIDE PARKING SHADE

CANOPY MOUNTED PHOTOVOLTAIC PANELS, DC CONDUCTORS,

INVERTERS, AC COMBINER BOXES, PHOTOVOLTAIC

DISTRIBUTION PANELBOARDS, AND ALL OTHER REQUIRED

PHOTOVOLTAIC HARDWARE AND ACCESSORIES FOR THE

CONSTRUCTION OF A COMPLETE AND FUNCTIONING

PHOTOVOLTAIC SYSTEM AS NOTED IN CONSTRUCTION

DRAWINGS AND SPECIFICATIONS. NOTE, PARKING SHADE

CANOPIES ARE NOT PART OF PHOTOVOLTAIC SYSTEM OPTION

AND ARE PROVIDED BY OTHERS.

SEE DRAWING E0.1 FOR ABBREVIATIONS, SYMBOLS, GENERAL

NOTES.

THE CONTRACTOR SHALL COORDINATE EXACT LOCATION OF

EQUIPMENT POWER CONNECTIONS WITH EQUIPMENT

INSTALLER PRIOR TO ROUGH-IN.

COORDINATE FINAL LOCATION OF MECHANICAL EQUIPMENT

AND ASSOCIATED DISCONNECT SWITCHES, STARTERS, VFDS,

CONTROL POWER AND OTHER POWER REQUIREMENTS WITH

DIV 23 AND MECHANICAL DRAWINGS.

SEE MECHANICAL EQUIPMENT SCHEDULE FOR ASSOCIATED

OVERCURRENT DEVICES, DISCONNECT SWITCHES, STARTERS

AND WIRES.

VOLTAGE DROP SHALL BE LIMITED TO LESS THAN 3% FOR ALL

BRANCH CIRCUITS AND 2% FOR ALL FEEDERS.

CONTRACTOR SHALL COORDINATE AND FIELD VERIFY

REQUIREMENT OF NEUTRAL CONDUCTOR FOR ALL EQUIPMENT

AND PROVIDE NEUTRAL CONDUCTOR AS NECESSARY.

ALL LIFE SAFETY AND LIGHTING PANELBOARDS SHALL BE

EQUIPPED WITH TYPE 2 SPD.

ALL AUTOMATIC TRANSFER SWITCHES SHALL BE 4 POLE AND

EQUIPPED WITH BYPASS ISOLATION.

ALL UTILITY TRANSFORMERS DESCRIBED AS NAVOPACHE

TRANSFORMER TO BE COORDINATED WITH UTILITY AND

PROVIDED BY UTILITY. COORDINATE ALL FINAL REQUIREMENTS

AND AVAILABLE FAULT CURRENT CONTRIBUTIONS BASED ON

SUPPLIED EQUIPMENT. BASIS OF DESIGN 2500KVA, AND 5%Z.

BASIS OF DESIGN ELECTRICAL EQUIPMENT MANUFACTURERS

ARE SIEMENS, ASCO, AND CATERPILLAR. EQUIVALENT

EQUIPMENT FROM APPROVED MANUFACTURERS IS

ACCEPTABLE, PER DIV 26 SPECIFICATIONS.

GENERAL SHEET NOTES

E504

E502

M

NAVOPACHE

TRANSFORMER

LEVEL 1

LEVEL 2

LEVEL 2

LEVEL 3

LEVEL 3

LEVEL 4

LEVEL 4

ROOF

OPTIONAL

STANDBY

BDM2SH

1000A

480-277V

3PH/4W

EQUIPMENT

(ELEVATORS)

ATS-BEA

400A

4P

ATS-BSA

1000A

4P

LTG

TBPE2SLA/B

112.5kVA

TBPE2SLC/D

75kVA

CNTRL

PNL

STAFF/PATIENT

ELEV 1B

CNTRL

PNL

STAFF/PATIENT

ELEV 1A

CNTRL

PNL

FREIGHT ELEV 5

CNTRL

PNL

PUBLIC ELEV 4B

CNTRL

PNL

PUBLIC ELEV 4A

BDW4EH

400A 480-277V

3PH/4W

ATS-BCA

1000A

4P

PWR PWR

A400

A400

A1000

A1000

A300 A300V1 A225

T112 T75

A300 A225

A225

A400

A300

A225

A225

A125 A125

A225V1

TBPT2SLA

45kVA K13

TBPT2SLB

75kVA K13

TBPT2SLC

75kVA K13

T45N T75N T75N

80 80

80 80

80 80

MDF IDF IDF

E501

50-3 50-3 80-3 50-3V1 50-3V1

FAC BLDG

TBPF2SLA

75kVA

MAIN

SB1

SB2 SB3

DB1 DB2 DB3 DB4 DB5 DB6 DB7

MATCHLINE

MATCHLINE

T75

A250

A250

TBPT2SLA

200A/150AF

BPF2SHA

400A/250AF

TBPE1SLC/D

75kVA

T75

TBPT2SLB

400A/225AF

TBPT2SLC

400A/225AF

#2

SES-B

3200A BUS

PER NEC 705.12(B)

480-277V/3PH/4W (3)

E521

SEL-751

(3)(3)

G G G G G

GGGGGG

G

E531

G

E532

E532

G

E532

SHEET NUMBER

PROJECT NUMBER

SEALS AND SIGNATURES

ISSUED FOR DATE

Pl ot

Da te:

IHS Whiteriver Hospital 200 W Hospital Drive Whiteriver, Arizona, 85941

IHS Project #: 131445 IHS Contract #: 75H70123R00008 IHS Award Date: 02/02/2024

455 NORTH THIRD STREET

SUITE 250

PHOENIX, AZ 85004

602.265.2200 smithgroup.com

Drawn By: Checked By:

BASED ON PROGRAM OF REQUIREMENTS DATED [ 03/26/22],

POR AMENDMENT DATED [ 02/03/25], AND ON SCHEMATIC

DRAWINGS APPROVED [11/19/24].

6/1 2/2

6 1

:12 :49

P M

ELECTRICAL ONE LINE

DIAGRAM - SES-B, 1 OF 2

E5.2.1CD

W hit tin gto n

14904.000 Whittington Baca

X FEEDER SCHEDULE

SHEET KEYNOTES

E501 NAVOPACHE UTILITY METER. METER SHALL BE EQUIPPED

WITH CAPABILITY TO INTERFACE WITH BMS. ELECTRICAL

CONTRACTOR SHALL PROVIDE REQUIRED CONDUIT AND

COMMUNICATION WIRING FROM METER TO POINT OF

INTERFACE WITH BMS.

E502 COMPLIANCE WITH "NEC 240.87 ARC ENERGY REDUCTION"

REQUIRED. REDUCTION METHOD SHALL ALLOW FOR

REQUIRED SELECTIVE DEVICE COORDINATION AND ARC

FLASH REQUIREMENTS. REFER TO ELECTRICAL

SPECIFICATIONS FOR ADDITIONAL INFORMATION.

E504 PROVIDE PERMANENT IDENTIFICATION PLAQUE INDICATING

THE FOLLOWING: ELECTRICAL SERVICE #2 OF 5.

GENERATORS LOCATED IN ELECTRICAL EQUIPMENT YARD,

GENERATOR DISCONNECTS LOCATED IN ADJACENT

ELECTRICAL ROOM IN GMDB. PV DISCONNECT LOCATED AT

END OF THIS ELECTRICAL EQUIPMENT LINEUP.

E521 PROVIDE RELAY PROTECTION ELEMENTS REQUIRED BY

UTILITY AND MULTIPLE GENERATOR AND PV MONITORING

AND CONTROL SYSTEM MANUFACTURER. INTEGRATE SEL

RELAY AND PROGRAMMING INTO MULTIPLE GENERATOR

AND PV MONITORING SYSTEM AND CIRCUIT BREAKER.

PROVIDE AND PROGRAM PROTECTION ELEMENT SET POINTS

AND LOGIC WITHIN THE RELAY. REFER TO SEL-751 DETAIL

FOR ADDITIONAL INFORMATION.

E531 ELECTRICAL EQUIPMENT CONSTRUCTION =

UL891 REAR CONNECTED SWITCHBOARD

DRAW-OUT LOW VOLTAGE POWER CIRCUIT BREAKERS

E532 ELECTRICAL EQUIPMENT CONSTRUCTION =

UL67 PANELBOARD

IP20, TOUCH-SAFE, PLUG-IN MOLDED CASE CIRCUIT

BREAKERS, ELECTRONIC TRIP UNIT

SCALE: NOT TO SCALE1 ONE LINE DIAGRAM - SES-B, 1 OF 2

50-3 3#6 + 1#10 G, 3/4" C 50-3V1 3#2 + 1#4 G, 1 1/4" C 80 4#3 + 1#8 G, 1 1/4" C 80-3 3#3 + 1#8 G, 1 1/4" C A125 4#2/0 + 1#6 G, 2" C

A225 4#300KCMIL + 1#2 G, 2 1/2" C

A225V1 4#400KCMIL + 1#1/0 G, 2 1/2" C

A250 4#350KCMIL + 1#2 G, 2 1/2" C

A300 4#500KCMIL + 1#2 G, 3" C

A300V1 4#600KCMIL + 1#1 G, 3" C

A400 2 SETS OF 4#250KCMIL + 1#1 G, (2) 2 1/2" C

A1000 3 SETS OF 4#600KCMIL + 1#4/0 G, (3) 3 1/2" C

T45N 45KVA TRANSFORMER, 480-208Y/120V, 3PH

PRIMARY FEEDER: 3#3 + 1#8 G, 1 1/4" C

SECONDARY FEEDER: 3#1/0, 1#4/0 N + 1#6 G, 2" C

BONDING JUMPERS & GROUNDING ELECTRODE

CONDUCTOR: #6

T75 75KVA TRANSFORMER, 480-208Y/120V, 3PH

PRIMARY FEEDER: 3#1/0 + 1#6 G, 1 1/2" C

SECONDARY FEEDER: 4#4/0 + 1#2 G, 2 1/2" C

BONDING JUMPERS & GROUNDING ELECTRODE

CONDUCTOR: #2

T75N 75KVA TRANSFORMER, 480-208Y/120V, 3PH

PRIMARY FEEDER: 3#1/0 + 1#6 G, 1 1/2" C

SECONDARY FEEDER: 3#4/0, 1#500KCMIL N + 1#2

G, 2 1/2" C

BONDING JUMPERS & GROUNDING ELECTRODE

CONDUCTOR: #2

T112 112.5KVA TRANSFORMER, 480-208Y/120V, 3PH

PRIMARY FEEDER: 3#3/0 + 1#6 G, 2" C

SECONDARY FEEDER: 2 SETS OF 4#3/0 + 1#2 G, (2)

2" C

BONDING JUMPERS & GROUNDING ELECTRODE

CONDUCTOR: #2

"A" DENOTES ALUMINUM CONDUCTORS, ALL OTHER CONDUCTORS SHALL BE COPPER

FINAL CONSTRUCTION DOCUMENTS 05MAR26

BID ADDENDUM-A 16APR26

BID ADDENDUM-E 28MAY26

BID ADDENDUM-G 12JUN26

G

G

G

LS

IG

/3

EN

L

BC

BPE2CHD

225A

FTL

SPD

LS

I

5/

BPE2CHE

225A

MLO

SPD

BPE2CHA

150A

MLO

BPE2CLA

125A

MCB

LS

I

0/

BPE2CLB

125A

MCB

BPE2CHB

150A

MLO

BPE2CLC

125A

MCB

LS

I

0/

BPE2CLD

125A

MCB

BPE1CHD

125A

MLO

SPD

BPE1CHE

125A

MLO

SPD

BPE1CLA

125A

MCB

BPE1CHA

150A

MLO

BPE1CLB

125A

MCB

BPE1CLD

125A

MCB

BPE1CHB

150A

MLO

BPE1CLC

125A

MCB

LS

IG

/3

EN

L

BD

LS

I

0/

LS

I

5/

LS

I

5/

LS

I

0/

LS

I

5/

LS

I

5/

BPE2CLE

125A

MCB

BPE2CLF

125A

MCB

LS

I

5/

LS

I

/3

VFD

LS

I

0/

VFD

LS

I

/3

VFD

LS

I

0/

VFD

LS

I

0/

LS

IG

0/

PVX

LS

IG

0/

EN

L

BE

LS

I

0/

LS

I

0/

BPE2EHA

400A

MLO

BPE1EHA

225A

MLO

BPE2EHB

400A

MLO

BPE1EHB

225A

MLO

BPE1ELA

150A

MCB

BPE1ELB

150A

MCB

LS

I

0/

LS

I

0/

LS

I

0/

UA1 BP1 UB1

LS

I

/3

M M M M

M

M

M M M M M

M M M M M

M M M M M M M M

A.

B.

C.

D.

E.

F.

G.

H.

I.

J.

K.

L.

ADDITIVE OPTION NO. 6, BASE BID PROVIDE ALL

UNDERGROUND CONDUITS ASSOCIATED WITH PHOTOVOLTAIC

SYSTEM INCLUDING BUT NOT LIMITED TO, HANDHOLES,

CONDUIT STUB-UPS BETWEEN MAIN ELECTRICAL ROOM,

PHOTOVOLTAIC DISTRIBUTION PANEL AND AC COMBINER

BOXES. CAP, PROTECT AND MARK CONDUIT LOCATIONS WITH

DETECTABLE UNDERGROUND TAPE FOR IMPLEMENTATION OF

FULLY FUNCTIONING PHOTOVOLTAIC SYSTEM IN THE FUTURE.

A PLAN INDICATING UNDERGROUND CONDUIT

SIZE/QUANTITY/ROUTING FOR FUTURE PHOTOVOLTAIC WILL BE

REQUIRED FOR REVIEW PRIOR TO BACKFILL. ALL

UNDERGROUND CONDUITS WILL BE REQUIRED TO BE SHOWN

IN AS-BUILT DOCUMENTATION.

ADDITIVE OPTION NO. 6, OPTION PROVIDE PARKING SHADE

CANOPY MOUNTED PHOTOVOLTAIC PANELS, DC CONDUCTORS,

INVERTERS, AC COMBINER BOXES, PHOTOVOLTAIC

DISTRIBUTION PANELBOARDS, AND ALL OTHER REQUIRED

PHOTOVOLTAIC HARDWARE AND ACCESSORIES FOR THE

CONSTRUCTION OF A COMPLETE AND FUNCTIONING

PHOTOVOLTAIC SYSTEM AS NOTED IN CONSTRUCTION

DRAWINGS AND SPECIFICATIONS. NOTE, PARKING SHADE

CANOPIES ARE NOT PART OF PHOTOVOLTAIC SYSTEM OPTION

AND ARE PROVIDED BY OTHERS.

SEE DRAWING E0.1 FOR ABBREVIATIONS, SYMBOLS, GENERAL

NOTES.

THE CONTRACTOR SHALL COORDINATE EXACT LOCATION OF

EQUIPMENT POWER CONNECTIONS WITH EQUIPMENT

INSTALLER PRIOR TO ROUGH-IN.

COORDINATE FINAL LOCATION OF MECHANICAL EQUIPMENT

AND ASSOCIATED DISCONNECT SWITCHES, STARTERS, VFDS,

CONTROL POWER AND OTHER POWER REQUIREMENTS WITH

DIV 23 AND MECHANICAL DRAWINGS.

SEE MECHANICAL EQUIPMENT SCHEDULE FOR ASSOCIATED

OVERCURRENT DEVICES, DISCONNECT SWITCHES, STARTERS

AND WIRES.

VOLTAGE DROP SHALL BE LIMITED TO LESS THAN 3% FOR ALL

BRANCH CIRCUITS AND 2% FOR ALL FEEDERS.

CONTRACTOR SHALL COORDINATE AND FIELD VERIFY

REQUIREMENT OF NEUTRAL CONDUCTOR FOR ALL EQUIPMENT

AND PROVIDE NEUTRAL CONDUCTOR AS NECESSARY.

ALL LIFE SAFETY AND LIGHTING PANELBOARDS SHALL BE

EQUIPPED WITH TYPE 2 SPD.

ALL AUTOMATIC TRANSFER SWITCHES SHALL BE 4 POLE AND

EQUIPPED WITH BYPASS ISOLATION.

ALL UTILITY TRANSFORMERS DESCRIBED AS NAVOPACHE

TRANSFORMER TO BE COORDINATED WITH UTILITY AND

PROVIDED BY UTILITY. COORDINATE ALL FINAL REQUIREMENTS

AND AVAILABLE FAULT CURRENT CONTRIBUTIONS BASED ON

SUPPLIED EQUIPMENT. BASIS OF DESIGN 2500KVA, AND 5%Z.

BASIS OF DESIGN ELECTRICAL EQUIPMENT MANUFACTURERS

ARE SIEMENS, ASCO, AND CATERPILLAR. EQUIVALENT

EQUIPMENT FROM APPROVED MANUFACTURERS IS

ACCEPTABLE, PER DIV 26 SPECIFICATIONS.

GENERAL SHEET NOTES

LEVEL 1

LEVEL 2

LEVEL 2

LEVEL 3

LEVEL 3

LEVEL 4

LEVEL 4

ROOF

CRITICAL

BDM2CH

1000A

480-277V

3PH/4W

ATS-BCA

1000A

4P

LTG

TBPE2CLA/B

75kVA

PWR PWR

EQUIPMENT

BDM2EHA

1600A

480-277V

3PH/4W

ATS-BEB

1600A

4P

PWR PWR

TBPE1CLA/B

75kVA

PWR

PWR

TBPE2CLC/D

75kVA

PWR

PWR

TBPE1CLC/D

75kVA

TBPE2CLE/F

75kVA

PWR

A1000

A1000

A150

T75D

A150V1

T75DV1 T75D

A225

T75D T75DV1

A150 A150V1 A125 A125

A225V1

A1600

A1600

1000-3

ACCH-2

CHWP-2

100-3

HHWP-2

30-3

CBWP-2

100-3

EH-2

PV BEQUIPMENT

BDM2EHB

600A

480-277V

3PH/4W

ATS-BEC

600A

4P

A600

A600

A400V1A400

A225

TBPE1ELA

45kVA

T45

TBPE1ELB

45kVA

T45

, E O

400 400 400

UPS A1

INPUT

UPS B1

INPUT

UPS A1/B1

BYPASS

1000-3

NON-COINCIDENT

LOAD

B-2

E519

SB4 SB5 SB6

DB8

DB9

DB10 DB12 DB14 DB19

DB11 DB13 DB15 DB17 DB18

DB16

DB20 DB21 DB22 DB23 DB24 DB25 DB26 DB27

SB7

MATCHLINE

MATCHLINE

300-3

A225

E530

G

G G G G G

GGGGG

G

G G G G G

G

G

E532 E532E533

SHEET NUMBER

PROJECT NUMBER

SEALS AND SIGNATURES

ISSUED FOR DATE

Pl ot

Da te:

IHS Whiteriver Hospital 200 W Hospital Drive Whiteriver, Arizona, 85941

IHS Project #: 131445 IHS Contract #: 75H70123R00008 IHS Award Date: 02/02/2024

455 NORTH THIRD STREET

SUITE 250

PHOENIX, AZ 85004

602.265.2200 smithgroup.com

Drawn By: Checked By:

BASED ON PROGRAM OF REQUIREMENTS DATED [ 03/26/22],

POR AMENDMENT DATED [ 02/03/25], AND ON SCHEMATIC

DRAWINGS APPROVED [11/19/24].

6/1 2/2

6 1

:12 :54

P M

ELECTRICAL ONE LINE

DIAGRAM - SES-B, 2 OF 2

E5.2.2CD

W hit tin gto n

14904.000 Whittington Baca

X FEEDER SCHEDULE

SHEET KEYNOTES

E519 PV CIRCUIT BREAKER SHALL BE LOCATED AT LAST BUSSED

SPACE. PROVIDE PERMANENT IDENTIFICATION PLAQUE

INDICATING THE…