A4-1f BP1_DWG2026-0430_15_ELECTRICAL_IHS-Whiteriver-Hospital_BID-ADD-B.pdf
PDF 283 KB Posted
- Attached to
- Whiteriver Hospital Construction
- Solicitation number
- 75H70126R00016
About this file
This is an electrical one-line diagram for the IHS Whiteriver Hospital renovation project located at 200 W Hospital Drive, Whiteriver, Arizona 85941. The diagram, designated as drawing E5.5.1, illustrates the electrical service distribution system and is based on the Program of Requirements dated March 26, 2022, with a POR amendment dated February 3, 2025, and schematic drawings approved November 19, 2024. The IHS Project Number is 131445 and the IHS Contract Number is 75H70123R00008, with an award date of February 2, 2024.
The base build scope includes empty conduits for feeders shown on the sheet, while the alternate scope encompasses photovoltaic panels, carports, DC conductors, inverters, AC conductors, AC combiner boxes, and PV distribution boards. Key electrical requirements include voltage drop limitations of 3% for branch circuits and 2% for feeders, coordination of equipment power connections with installers, neutral conductor verification for all equipment, and Type 2 surge protective devices for all life safety and lighting panelboards. The electrical equipment shall be configured with UL891 rear-connected switchboards for service entrance and distribution, and UL1558 switchgear for generator paralleling gear. Notable specifications include a Navopache utility transformer basis of design rated at 2500 KVA with 5% impedance, fire pump controller monitoring by the fire alarm system, arc energy reduction compliance per NEC 240.87, and integration of relay protection elements with multiple generator and PV monitoring control systems. The design firm is SmithGroup, located at 455 North Third Street, Suite 250, Phoenix, Arizona 85004.
View the file
Other files
Show 40 more
Latest 50 of 107 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
LSIG
2500/3
LS
IG
0/
EN
L
EC
LS
IG
0/
EN
L
EA
/3
/3
/3
/3
/3
LS
IG
/3
EN
L
EB
LS
I
0/
EKPH1A
600A
MLO
EKPL1A
400A
MCB/FTL
0/
0/
0/
EAHU-5-6
200A
MLO
EAHU-7-8
200A
MLO
EAHU-9-10
200A
MLO
VFD
/3
LS
IG
/3
EN
L
ED
FP
EKPL1B
225A
MCB
EPW2EHA
400A
MLO
EPW2ELA
400A
MCB
LS
I
0/
LS
I
5/
E N
L
LS
I
0/
VFD
LS
I
0/
LS
I
0/
VFD VFD
LS
I
/3
VFD
LS
I
/3
VFD
LS
I
0/
EP2EHA
250A
MLO
LS
I
0/
EP2ELA
225A
MCB
VFD
0/
LS
I
0/
M
M M M M
M M M M M M M M M M
M M M M M
EKPL1C
125A
MCB
ELSH
200A
MCB
ELSP
50A
MCB
LS
I
0/
M M
SPD
A.
B.
C.
D.
E.
F.
G.
H.
I.
J.
K.
L.
BASE BUILD SCOPE SHALL ONLY INCLUDE EMPTY CONDUITS
OF FEEDERS SHOWN ON THIS SHEET WITH FEEDER TAGS.
ADD ALTERNATE SCOPE SHALL INCLUDE PV PANELS,
CARPORTS, DC CONDUCTORS, INVERTERS, AC CONDUCTORS,
AC COMBINER BOXES, PV DISTRIBUTION BOARDS.
SEE DRAWING E0.1 FOR ABBREVIATIONS, SYMBOLS, GENERAL
NOTES.
THE CONTRACTOR SHALL COORDINATE EXACT LOCATION OF
EQUIPMENT POWER CONNECTIONS WITH EQUIPMENT
INSTALLER PRIOR TO ROUGH-IN.
COORDINATE FINAL LOCATION OF MECHANICAL EQUIPMENT
AND ASSOCIATED DISCONNECT SWITCHES, STARTERS, VFDS,
CONTROL POWER AND OTHER POWER REQUIREMENTS WITH
DIV 23 AND MECHANICAL DRAWINGS.
SEE MECHANICAL EQUIPMENT SCHEDULE FOR ASSOCIATED
OVERCURRENT DEVICES, DISCONNECT SWITCHES, STARTERS
AND WIRES.
VOLTAGE DROP SHALL BE LIMITED TO LESS THAN 3% FOR ALL
BRANCH CIRCUITS AND 2% FOR ALL FEEDERS.
CONTRACTOR SHALL COORDINATE AND FIELD VERIFY
REQUIREMENT OF NEUTRAL CONDUCTOR FOR ALL EQUIPMENT
AND PROVIDE NEUTRAL CONDUCTOR AS NECESSARY.
ALL LIFE SAFETY AND LIGHTING PANELBOARDS SHALL BE
EQUIPPED WITH TYPE 2 SPD.
ALL AUTOMATIC TRANSFER SWITCHES SHALL BE 4 POLE AND
EQUIPPED WITH BYPASS ISOLATION.
ALL UTILITY TRANSFORMERS DESCRIBED AS NAVOPACHE
TRANSFORMER TO BE COORDINATED WITH UTILITY AND
PROVIDED BY UTILITY. COORDINATE ALL FINAL REQUIREMENTS
AND AVAILABLE FAULT CURRENT CONTRIBUTIONS BASED ON
SUPPLIED EQUIPMENT. BASIS OF DESIGN 2500KVA, AND 5%Z.
ELECTRICAL EQUIPMENT SHALL BE CONFIGURED AS FOLLOWS:
-SERVICE ENTRANCE SECTIONS - UL891 REAR CONNECTED
SWITCHBOARD
-DISTRIBUTION SWITCHBOARDS WITH DRAWOUT CIRCUIT
BREAKERS - UL891 REAR CONNECTED SWITCHBOARD
-GENERATOR PARALLELING GEAR - UL1558 SWITCHGEAR
GENERAL SHEET NOTES
E517
E502
E501 M
LEVEL 1
LEVEL 2
LEVEL 2
LEVEL 3
LEVEL 3
LEVEL 4
LEVEL 1
LEVEL 2
LEVEL 2
LEVEL 3
LEVEL 3
LEVEL 4
LEVEL 4
ROOF
LEVEL 4
ROOF
EQUIPMENT
ATS-EEC
800A
4P
A800
A800
EQUIPMENT
(ELEVATORS)
ATS-EEA
400A
4P
CNTRL
PNL
PUBLIC ELEV 3B
CNTRL
PNL
PUBLIC ELEV 3A
CNTRL
PNL
STAFF ELEV 2
CNTRL
PNL
PUBLIC ELEV 6B
CNTRL
PNL
PUBLIC ELEV 6A
EDE2EH
400A 480-277V
3PH/4W
A400
EQUIPMENT
(KITCHEN & CSPD)
EDM2EHA
1000A
480-277V
3PH/4W
ATS-EEB
1000A
4P
A1000
A1000
TEKPL1A
112.5kVA
T112
MAU-1
EQUIPMENT
EDM2EHB
1200A
480-277V
3PH/4W
ATS-EED
1200A
4P
A1200
A1200
DEDICATED
COMPARTMENT
FOR DIRECT
CONNECTION
OF FIRE PUMP
NEC 695.4(B)(3)(a)
E512
TEPW2ELA
112.5kVA
CSPD PWR CSPD PWR
A400 T112
KITCHEN PWR
EDAHUA
800A
480-277V
3PH/4W
FIRE PUMP
E514
E515
E516
250-3
ASHP-2
250-3 250-3
CHWP-5
50-3
HHWP-5
30-3
EH-5
CUP PWR
TEP2ELA
75kVA
T75
ACCH-4
50-3V2 50-3V2 50-3V2 50-3 50-3
TEKPL1B
75kVA
T75
800-3
NON-COINCIDENT
LOAD
B-5
MAIN
SE1
SE2 SE3 SE4 SE5
DE1 DE2 DE3 DE4 DE5 DE6 DE7 DE8 DE9 DE10
DE11 DE12 DE13 DE14 DE15
A600
300-3
E525E526
250-3
A200 A200 A200V2 60-3 200
A400
A125
(3)
E521
SEL-751
(3)(3)
SES-E
3200A BUS
PER NEC 705.12(B)
480-277V/3PH/4W
NAVOPACHE
TRANSFORMER
TELSP
15kVA
T15
200V1
DE3 DE4
#2
A
E530
A
B
SHEET NUMBER
PROJECT NUMBER
SEALS AND SIGNATURES
ISSUED FOR DATE
Pl ot
Da te:
IHS Whiteriver Hospital 200 W Hospital Drive Whiteriver, Arizona, 85941
IHS Project #: 131445 IHS Contract #: 75H70123R00008 IHS Award Date: 02/02/2024
455 NORTH THIRD STREET
SUITE 250
PHOENIX, AZ 85004
602.265.2200 smithgroup.com
Drawn By: Checked By:
BASED ON PROGRAM OF REQUIREMENTS DATED [ 03/26/22],
POR AMENDMENT DATED [ 02/03/25], AND ON SCHEMATIC
DRAWINGS APPROVED [11/19/24].
4/3 0/2
6 4
:53 :49
P M
ELECTRICAL ONE LINE
DIAGRAM - SES-E
E5.5.1CD
W hit tin gto n
14904.000 Whittington Baca
X FEEDER SCHEDULE
SHEET KEYNOTES
E501 NAVOPACHE UTILITY METER. METER SHALL BE EQUIPPED
WITH CAPABILITY TO INTERFACE WITH BMS. ELECTRICAL
CONTRACTOR SHALL PROVIDE REQUIRED CONDUIT AND
COMMUNICATION WIRING FROM METER TO POINT OF
INTERFACE WITH BMS.
E502 COMPLIANCE WITH "NEC 240.87 ARC ENERGY REDUCTION"
REQUIRED. REDUCTION METHOD SHALL ALLOW FOR
REQUIRED SELECTIVE DEVICE COORDINATION AND ARC
FLASH REQUIREMENTS. REFER TO ELECTRICAL
SPECIFICATIONS FOR ADDITIONAL INFORMATION.
E512 DIRECT CONNECTION OF FIRE PUMP AS ALLOWED BY NEC
695.3(A)(1) AND IN COMPLIANCE WITH NEC 695.4(A).
E514 FIRE PUMP CONTROLLER SHALL BE MONITORED BY THE FIRE
ALARM SYSTEM. LOSS OF NORMAL POWER SHALL ACTIVATE
SUPERVISORY ALARM AS FACP.
E515 PROVIDE CONTROL WIRING IN COMPLIANCE WITH NEC
695.14. BMS MONITORING SHALL BE PROVIDED.
E516 LISTED SINGLE POINT NORMAL & EMERGENCY CONNECTION
(WITH INTEGRAL AUTOMATIC TRANSFER SWITCH). INTERNAL
WIRING FROM CONTROLLER(S) TO PUMP MOTOR(S) SHALL
BE RUN IN CONDUIT TYPE AS SPECIFIED BY NEC 695.6(D) &
(F). ALL INTERNAL WIRING SHALL BE PROVIDED BY
EQUIPMENT MANUFACTURER. ALL REQUIRED MARKINGS &
APPROPRIATE PLAQUES SHALL BE PROVIDED IN
COMPLIANCE WITH THE NEC.
E517 PROVIDE PERMANENT IDENTIFICATION PLAQUE INDICATING
THE FOLLOWING: ELECTRICAL SERVICE #5 OF 5.
GENERATORS LOCATED IN ELECTRICAL EQUIPMENT YARD,
GENERATOR DISCONNECTS LOCATED IN ADJACENT
ELECTRICAL ROOM IN GMDB. PV DISCONNECT LOCATED AT
END OF THIS ELECTRICAL EQUIPMENT LINEUP.
E521 PROVIDE RELAY PROTECTION ELEMENTS REQUIRED BY
UTILITY AND MULTIPLE GENERATOR AND PV MONITORING
AND CONTROL SYSTEM MANUFACTURER. INTEGRATE SEL
RELAY AND PROGRAMMING INTO MULTIPLE GENERATOR
AND PV MONITORING SYSTEM AND CIRCUIT BREAKER.
PROVIDE AND PROGRAM PROTECTION ELEMENT SET POINTS
AND LOGIC WITHIN THE RELAY. REFER TO SEL-751 DETAIL
FOR ADDITIONAL INFORMATION.
E525 ELECTRIC FIRE PUMP BY FIRE SUPPRESSION DELEGATED
DESIGN. PROVIDED WITH ATS INTEGRAL TO PUMP
CONTROLLER WITH INTEGRAL DISCONNECT. PROVIDE
CONNECTION AS SHOWN FOR UP TO 150HP 480V/3-PHASE
ELECTRIC PUMP.
E526 ELECTRIC FIRE BOOSTER JOCKEY PUMP BY FIRE
SUPPRESSION DELEGATED DESIGN. PROVIDED WITH PUMP
CONTROLLER WITH INTEGRAL DISCONNECT. PROVIDE
CONNECTION AS SHOWN FOR UP TO 1.5HP 480V/3-PHASE
ELECTRIC PUMP. TAP SHALL ORIGINATE WITHIN FIRE PUMP
ROOM AND BE LESS THAN 10FT CABLE LENGTH TO
CONTROLLER PER TAP RULES.
E530 PROVIDE SHUNT TRIP CIRCUIT BREAKER FOR INTERFACE
WITH BOILER EMERGENCY SHUTDOWN EPO SWITCHES.
REFER TO EMP2.2.G FOR ADDITIONAL INFORMATION.
30-3 3#10 + 1#10 G, 3/4" C 50-3 3#6 + 1#10 G, 3/4" C 50-3V2 3#4 + 1#6 G, 1" C 60-3 3#4 + 1#10 G, 1 1/4" C 200 4#3/0 + 1#6 G, 2" C
200V1 2 SETS OF 4#300KCMIL + 1#1/0 G, (2) 3" C
250 4#250KCMIL + 1#4 G, 3"C
250-3 3#250KCMIL + 1#4 G, 2 1/2" C
300-3 3#350KCMIL + 1#4 G, 3" C
800-3 3 SETS OF 3#300KCMIL + 1#1/0 G, (3) 3" C
A125 4#2/0 + 1#6 G, 2" C
A200 4#250KCMIL + 1#4 G, 2 1/2" C
A200V2 4#300KCMIL + 1#3 G, 2 1/2" C
A400 2 SETS OF 4#250KCMIL + 1#1 G, (2) 2 1/2" C
A600 2 SETS OF 4#500KCMIL + 1#2/0 G, (2) 3" C
A800 3 SETS OF 4#400KCMIL + 1#3/0 G, (3) 3" C
A1000 3 SETS OF 4#600KCMIL + 1#4/0 G, (3) 3 1/2" C
A1200 4 SETS OF 4#500KCMIL + 1#250KCMIL G, (4) 3" C
T15 15KVA TRANSFORMER, 480-208Y/120V, 3PH
PRIMARY FEEDER: 3#10 + 1#10 G, 3/4" C
SECONDARY FEEDER: 4#4 + 1#8 G, 1 1/4" C
BONDING JUMPERS & GROUNDING ELECTRODE
CONDUCTOR: #8
T75 75KVA TRANSFORMER, 480-208Y/120V, 3PH
PRIMARY FEEDER: 3#1/0 + 1#6 G, 1 1/2" C
SECONDARY FEEDER: 4#4/0 + 1#2 G, 2 1/2" C
BONDING JUMPERS & GROUNDING ELECTRODE
CONDUCTOR: #2
T112 112.5KVA TRANSFORMER, 480-208Y/120V, 3PH
PRIMARY FEEDER: 3#3/0 + 1#6 G, 2" C
SECONDARY FEEDER: 2 SETS OF 4#3/0 + 1#2 G, (2)
2" C
BONDING JUMPERS & GROUNDING ELECTRODE
CONDUCTOR: #2
SCALE: NOT TO SCALE1 ONE LINE DIAGRAM - SES-E, 1 OF 2
"A" DENOTES ALUMINUM CONDUCTORS, ALL OTHER CONDUCTORS SHALL BE COPPER
FINAL CONSTRUCTION DOCUMENTS 05MAR26
BID ADDENDUM-A 16APR26
BID ADDENDUM-B 30APR26
A
A
04-30-26
6-30-28
E5.5.1 - ELECTRICAL ONE LINE DIAGRAM - SES-E
File details come from the government source that posted it. Updated .