A2-1f BP1_DWG2026-0416_15_ELECTRICAL_IHS-Whiteriver-Hospital_BID-ADD-A.pdf
PDF 8 MB Posted
- Attached to
- Whiteriver Hospital Construction
- Solicitation number
- 75H70126R00016
About this file
This document is a comprehensive electrical design drawing set for the IHS Whiteriver Hospital project located in Whiteriver, Arizona. The project is identified as IHS Project #131445 under IHS Contract #75H70123R00008, with an award date of February 2, 2024. The drawings are based on a Program of Requirements dated March 26, 2022, with amendments dated February 3, 2025, and schematic approvals dated November 19, 2024.
The electrical design encompasses multiple building systems including HVAC mechanical equipment distribution, power distribution across five electrical service areas (labeled A through E), uninterruptible power supply (UPS) configuration, and an alternate scope solar photovoltaic (PV) system with carports. Key electrical infrastructure includes five main switchboards and distribution panels, automatic transfer switches rated at 4-pole with bypass isolation, transformers (primarily 45kVA and 75-112.5kVA units), variable frequency drives (VFDs) for mechanical equipment, and surge protection devices on all life safety and lighting panelboards. The design specifies copper conductors, minimum #10 AWG branch circuit wiring, dedicated neutral conductors, voltage drop limitations of 3% for branch circuits and 2% for feeders, and compliance with UL891 standards for switchboards and UL1558 for generator paralleling gear. Mechanical systems are distributed across five zones with associated boilers (B-1 through B-5), air-cooled chillers (ACCH-1 through ACCH-3), heat pumps, and circulation pumps. The alternate scope solar PV system includes 625 kilowatts of capacity across six carports with multiple 62.5kW inverters, string combiner boxes, and DC/AC conductor routing to integration points within the main electrical distribution system.
View the file
Other files
Show 40 more
Latest 50 of 107 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
M
M
M
M
M
J
M
M
M
M
J
J
J
J
J
J
M
L
M
N
O
P
Q
R
10 11 12 13
14 15 16 17 18
S
MAP-2-02
EWH-9
CP-5
WT-3
AAP-2-03
FCU-2188
CUH-2PCS
CUH-2PCM
CRAC-2153
CRAC-2045
FCU-2046
CUH-2019
CUH-2PCN
CUH-2040
FCU-2034
CRAC-2200
FCU-2029
FSD
FSD
FSD
FSD
E247
APW2LLA- 35
FSD-2-E1
APW2LLA- 37
FSD-2-C1
E247
TYP
E248
BPE2EHA- 17
BPE2EHA- 15
BPE2EHA- 13VAV-2-C1
VAV-2-C2
VAV-2-C3
CORRIDOR
COR-2038
CORRIDOR
COR-2048
WATER TRMT
PUB-2055
STAFF LOCKERS
MSP-2367
STAIR 2
STR-2020
EVS
EVS-2243
SOILED WORKROOM
SUR-2244
ELEVATOR LOBBY
ELV-2033
CORRIDOR
COR-2047
CORRIDOR
COR-2019
SHAFT
SHF-2043
OFFICE, CLINICAL ENGINEERING
CLE-2230
SHOP
CLE-2229
STORAGE, PARTS
CLE-2229C
STORAGE, DIALYSIS
CLE-2227
DIALYSIS WORKROOM
CLE-2226
WORKSTATION, TECH
CLE-2229A
CONFERENCE, SMALL
TCC-2196
QUIET ROOM
EFS-2148
ALCOVE, NOURISHMENT
TCC-2192
STAFF ENTRY VESTIBULE
VST-2039
CONFERENCE, TRAINING
TCC-2193
CONFERENCE, MEDIUM
TCC-2194
ELEVATOR VESTIBULE
ELV-2027
CORRIDOR
COR-2019
WAITING
PFS-2236B
PREP/PACU STAGE 1
SUR-2240
PREP/PACU STAGE 1
SUR-2239
PREP/PACU STAGE 1
SUR-2241
EVS
EVS-2365
SOILED INTAKE
MSP-2366
PREP/PACU STAGE 1
SUR-2242
TOILET, STAFF
OEH-2210A
WAITING
OEH-2210
HUDDLE ROOM
OEH-2214
DRAFTING AREA
OEH-2214A
OFFICE, EH SUPERVISOR
OEH-2219
WORKSTATION, EH OFF
OEH-2220
WORKSTATION, GIS
OEH-2215
OFFICE, ENG SUPERVISOR
OEH-2218
WORKSTATION, ENG
OEH-2216
WORKSTATION, ENG TECH
OEH-2217
ALCOVE, STAFF NOURISHMENT
OEH-2213
WORKSTATION, FLEX
OEH-2211B
RECEPTION
OEH-2212
PLUMBING CHASE
PUB-2235
LACTATION/WELLNESS
EFS-2149
ALCOVE, LOCKERS
ITS-2199A
WORKROOM
ITS-2200
OFFICE, CHIEF INFORMATION OFFICER
ITS-2206
OFFICE, DEPUTY CIO
ITS-2203
OFFICE, INFO SYSTEM SEC
ITS-2205
OFFICE, SHARED, SYSTEMS ADMIN
ITS-2209
OFFICE, SHARED, NETWORK SERV STAFF
ITS-2207
EQUIPMENT STORAGE
ITS-2202
UNIT SUPPLY & FILING
ITS-2208
DECOMMISSION STORAGE
ITS-2204
OFFICE, RMSTP
OEH-2226
STORAGE, RMSTP
OEH-2225
ALCOVE, PLOTTER
OEH-2211A
OFFICE, DIRECTOR
SEC-2143
OFFICE, ASSISTANT DIRECTOR
SEC-2145
WORK AREA
SEC-2147
CONTROL ROOM
SEC-2146
ALCOVE, STAFF NOURISHMENT
SEC-2142A
EQUIPMENT STORAGE
SEC-2147A
LOST & FOUND STORAGE
EFS-2150
WORKSTATIONS
FAC-2160
WORKSTATIONS
FAC-2158
ADMIN SUPPORT
FAC-2157
TOILET/SHOWER, STAFF
CUP-2368A
MAINTENANCE SHOP
FAC-2151
OFFICE, FOREMAN
FAC-2162
OFFICE, GEN ENGINEERING
FAC-2161
STORAGE
FAC-2165
CORRIDOR
FAC-2159
CORRIDOR
SEC-2142B
OFFICE, SHARED
ITS-2201
CONFERENCE, SMALL
TCC-2195
CORRIDOR
FAC-2154
UPS
UPS-2029
STORAGE, BEDS
CLE-2232
TOILET, STAFF
FAC-2152A
EVS
EVS-2197
STORAGE, SIM LAB
LAB-2191A
SIM LAB
LAB-2191
SIM LAB MONITORING
LAB-2190
PUBLIC TOILET, FEMALE
PFS-2234
PUBLIC TOILET, MALE
PFS-2233
CSPD WATER
PUB-2056
CORRIDOR
ITS-2199
CORRIDOR
OEH-2211
CONTROL STATION
SUR-2247
ALCOVE, SCALE
SUR-2248
MED PREP
SUR-2238C
PTS
COR-2065A
ANESTHESIA WORK
SUR-2245
STERILE SUPPLY STORAGE
SUR-2281
OR
SUR-2267
ALCOVE, CRASH CART
SUR-2249
SHAFT
SHF-2050
PICKUP/DROP OFF
MSP-2359
OFFICE, SUPERVISOR
MSP-2355
TOILET/SHOWER, STAFF
MSP-2367A
HIGH LEVEL DISINFECTION
MSP-2357
EVS
EVS-2361
SUPPLY BREAKDOWN
MSP-2354
CASE CART STORAGE
MSP-2353C
CASE CART COMPLETION
MSP-2353D
CORRIDOR
COR-2066
OR
SUR-2268
CORRIDOR
COR-2052
ALCOVE, GURNEY
SUR-2266
ALCOVE, PPE
SUR-2246
IDF
IDF-2045
ELECTRICAL
ELC-2046
ELECTRICAL
ELC-2034
CORRIDOR
COR-2049
PUBLIC ELEV 3A
ELV-2023A
ELEVATOR VESTIBULE
ELV-2022
PUBLIC ELEV 4B
ELV-2028B
STAIR 3
STR-2030
VESTIBULE
VST-2040
CORRIDOR
COR-2032
WORKROOM
SEC-2144
OFFICE, SUPERVISOR
FAC-2163
EQUIPMENT STORAGE
CLE-2231
WORKSTATION, TECH
CLE-2229B
CORRIDOR
CLE-2228
WORKSTATION, EH TECH
OEH-2221
WORKSTATIONS
CUP-2369C
CORRIDOR
CUP-2369
STORAGE
FAC-2164
STORAGE
FAC-2166
ALCOVE, STAFF NOURISHMENT
FAC-2155
PUBLIC ELEV 4A
ELV-2028A
PUBLIC ELEV 3B
ELV-2023B
STORAGE
OEH-2224
EVS
EVS-2222
CORRIDOR
COR-2051
DAS
FAC-2153
WORKROOM, DECONTAM
MSP-2364
HIGH LEVEL DISINFECTION
MSP-2358
WAITING
PFS-2236A
EMPLOYEE LOCKER, FEMALE
EFS-2176
STAFF LOUNGE
EFS-2189
LACTATION/WELLNESS
EFS-2168
EXERCISE CENTER
EFS-2188
TOILETS, FEMALE
EFS-2172
CIRCULATION
EFS-2171
SINKS
EFS-2171A
SHW ROOM
EFS-2173 ACC SHW ROOM
EFS-2175
EVS
EVS-2169
SHAFT
SHF-2044
STAFF LOCKERS
FAC-2152
WORKSTATION, TECH
COR-1002B
WORKSTATION, TECH
COR-1002C
DETERGENT/RODI
COR-2085
CART WASH
COR-1002G
STORAGE, FILES
FAC-2156
SECURITY STATION
PFS-2236C
ALCOVE, LOCKERS
OEH-2211C
GURNEY STORAGE
SUR-2268B
ALCOVE, SCRUB
SUR-2267A
CORRIDOR
CLE-2233NOURISHMENT ALCOVE
CLE-2234
CORRIDOR
COR-2064
CIRCULATION
EFS-2170
SHW ROOM
EFS-2174
CIRCULATION
EFS-2177
SINKS
EFS-2191
ALCOVE
EFS-2192
TOILETS, MALE
EFS-2193
SHW ROOM
EFS-2194
SHW ROOM
EFS-2195
ACC SHW ROOM
EFS-2196
EMPLOYEE LOCKER, MALE
EFS-2198
PTS
SCC-4256
FREIGHT ELEV 5
ELV-2035
MV-5
WM-IHW-1
WM-ICW-1
WM-RODI-1
EP2ELA- 33
E280
EP2ELA- 33
A
A.
B.
C.
D.
E.
F.
G.
H.
I.
J.
K.
L.
M.
N.
O.
P.
Q.
R.
S.
T.
SEE DRAWING E0.1 FOR ABBREVIATIONS, SYMBOLS, GENERAL
NOTES AND DEVICE MOUNTING HEIGHT OF WALL MOUNTED
DEVICES, UON.
ALL BRANCH CIRCUIT WIRING SHALL BE A MINIMUM SIZE OF #10
AWG. REFER TO SHEET E0.2 FOR ADDITIONAL SIZING
INFORMATION.
THE CONTRACTOR SHALL COORDINATE EXACT LOCATION OF
EQUIPMENT POWER CONNECTIONS WITH EQUIPMENT
INSTALLER PRIOR TO ROUGH-IN.
SEE MECHANICAL EQUIPMENT SCHEDULE FOR ASSOCIATED
OVERCURRENT DEVICES, DISCONNECT SWITCHES, STARTERS
AND WIRES.
CONTRACTOR SHALL COORDINATE AND FIELD VERIFY
REQUIREMENT OF NEUTRAL CONDUCTOR FOR ALL EQUIPMENT
AND PROVIDE NEUTRAL CONDUCTOR AS NECESSARY.
ALL CIRCUITS SHALL BE EQUIPPED WITH A DEDICATED
NEUTRAL CONDUCTOR, UNLESS NOTED OTHERWISE.
ALL CONDUCTORS SHALL BE COPPER, UNLESS NOTED OR
SCHEDULED OTHERWISE.
TRIPPING OF GFCI RECEPTACLES SHALL NOT AFFECT THE
DOWNSTREAM RECEPTACLES.
NO MORE THAN 3 CIRCUITS MAY SHARE A HOMERUN.
FOR ALL MECHANICAL EQUIPMENT, PROVIDE ADDITIONAL 120V
CONNECTIONS REQUIRED BY MANUFACTURER.
FOR EACH AIR HANDLING UNIT, PROVIDE (1)120V CONNECTION
FOR LIGHTING AND RECEPTACLES. CIRCUIT TO MECHANICAL
PANEL WITHIN THE SPACE.
PROVIDE 120V CIRCUITS FOR CONTROL PANELS AS REQUIRED
BY CONTROL VENDOR. CIRCUIT TO MECHANICAL PANEL WITHIN
THE SPACE.
ALL UNUSED WALL OUTLETS TO BE COVERED WITH BLANK
PLATE. ALL BLANK PLATE COLORS TO MATCH WALL COLOR.
REFER TO 'T' SERIES PLANS FOR LOW VOLTAGE BACK BOX AND
RACEWAY REQUIREMENTS.
ALL CONDUIT ROUTED WITHIN SLAB SHALL COMPLY WITH
GUIDELINES LISTED IN STRUCTURAL DRAWINGS.
COORDINATE FINAL LOCATION OF MECHANICAL AND PLUMBING
EQUIPMENT AND ASSOCIATED DISCONNECT SWITCHES,
STARTERS, VFDS, CONTROL POWER AND OTHER POWER
REQUIREMENTS WITH DIV 22 AND 23.
CONTRACTOR IS RESPONSIBLE FOR ALL WIRING FROM VFDs
AND DISCONNECTS SHOWN IN DRAWINGS TO THE EQUIPMENT
AND IS TO COORDINATE WITH EQUIPMENT MANUFACTURER
AND INSTALLATION INSTRUCTIONS.
CONTRACTOR SHALL PROVIDE VFD CABLE FOR LINE AND LOAD
SIDE VFD CONNECTIONS.
CONTRACTOR SHALL PROVIDE RUN PERMISSIVE INTERLOCK
BETWEEN VFD AND LOAD SIDE EQUIPMENT DISCONNECT
SWITCH. DISCONNECT SWITCH SHALL BE EQUIPPED WITH
AUXILIARY CONTACT.
CHILLED BEAM MECHANICAL EQUIPMENT DOES NOT REQUIRE
POWER SOURCE CIRCUITING. SHOWN FOR REFERENCE ONLY.
EXTEND LINE SIDE OF NEAREST 120V GENERAL RECEPTACLE
POWER CIRCUIT TO ELECTRONIC PLUMBING VALVES.
COORDINATE ELECTRONIC PLUMBING VALVE INFRASTRUCTURE
REQUIREMENTS AND LOCATION WITH PLUMBING CONTRACTOR
AND EQUIPMENT MANUFACTURER PRIOR TO COMMENCING
WORK. INSTALL PER EQUIPMENT MANUFACTURERS
SPECIFICATIONS.
GENERAL SHEET NOTES
NORTH
SHEET NUMBER
PROJECT NUMBER
KEYPLAN
SEALS AND SIGNATURES
ISSUED FOR DATE
Pl ot
Da te:
C
IHS Whiteriver Hospital 200 W Hospital Drive Whiteriver, Arizona, 85941
IHS Project #: 131445 IHS Contract #: 75H70123R00008 IHS Award Date: 02/02/2024
455 NORTH THIRD STREET
SUITE 250
PHOENIX, AZ 85004
602.265.2200 smithgroup.com
Drawn By: Checked By:
BASED ON PROGRAM OF REQUIREMENTS DATED [ 03/26/22],
POR AMENDMENT DATED [ 02/03/25], AND ON SCHEMATIC
DRAWINGS APPROVED [11/19/24].
4/1 6/2
6 9
:57 :24
A M
LEVEL 2 (UPPER GROUND)
HVAC PLAN AREA C
EMP2.2.CCD
W hit tin gto n
14904.000 Whittington Baca
SHEET KEYNOTES
GRAPHIC SCALE: 1/8" = 1'-0"
8' 8' 16'0'4'
PROJECT NORTH
E247 CONNECT ALL FIRE SMOKE DAMPERS IN THIS AREA TO
CIRCUIT SHOWN.
E248 CONNECT ALL VAV TRANSFORMERS INSTALLED IN THIS AREA
TO CIRCUITS SHOWN. DEVICE TAGS ARE STRUCTURED
BASED ON LEVEL AND AREA. BMS CONTRACTOR TO PROVIDE
(1) 24V TRANSFORMER TO AN AVERAGE OF (4) VAV'S PER
TRANSFORMER. REFERENCE BMS CONTRACTOR SHOP
DRAWINGS FOR TRANSFORMER LOCATIONS.
E280 PROVIDE WALL MOUNTED EMERGENCY POWER OFF (EPO)
SWITCH ASSEMBLY WITH RED MOMENTARY PUSH BUTTON,
YELLOW BODY, CLEAR FLIP COVER AND CUSTOM LABELING
AS FOLLOWS: "BOILER EMERGENCY SHUTDOWN",
MANUFACTURED BY STI #SS2-2-2-ZA-EN, OR EQUIVALENT.
ACTIVATION OF EPO SHALL SHUNT TRIP ALL CIRCUIT
BREAKERS SERVING BOILERS.
SCALE: 1/8" = 1'-0"1 LEVEL 2 (UPPER GROUND) - HVAC PLAN AREA C
FINAL CONSTRUCTION DOCUMENTS 05MAR26
BID ADDENDUM-A 16APR26
A
04-16-26
6-30-28
J
M
M
M
J
M
J
M
3 54 6 7 8 9 i
K
J
ET-1
BP-1
C H
W P-
C H
W P-
C H
W P-
C H
W P-
C H
W P-
H H
W P-
H H
W P-
H H
W P-
H H
W P-
H H
W P-
B-1 B-2
ACCH-2
ACCH-1
ACCH-3
ASHP-1
ASHP-2
C
BW
P-
C
BW
P-
C
BW
P-
B-4B-3
MAP-2-01
CU-2075A CU-2075B CU-1337 CU-1179
CU-2350
CHWP-1 CHWP-2 CHWP-3 CHWP-4 CHWP-5
VFD- VFD- VFD- VFD- VFD- VFD- VFD- VFD-
CBWP-1 CBWP-2 CBWP-3
VFD-
VFD-
VFD-
VFD-
VFD-
HHWP-1 HHWP-2 HHWP-3 HHWP-4 HHWP-5
EWH-5 EWH-4 EWH-3 EWH-2 EWH-1B-5
FCU-2373
FCU-2370
BCU-2374
BCU-2368
TOILET/SHOWER, STAFF
CUP-2368A
OFFICE, FOREMAN
CUP-2369A
CENTRAL PLANT
CUP-2368
WORKSTATIONS
CUP-2369C
CORRIDOR
CUP-2369
STORAGE, PLANS
CUP-2369B
MAIN ELECTRICAL ROOM
CUP-2371
MAIN NORMAL ELECTRICAL
CUP-2374
CUP ELECTRICAL
CUP-2373
FIRE PUMP
CUP-2370
MEP YARD
CUP-2368B
O2 TANKS YARD
CUP-2368C
WM-HW-1
WM-CW-1
WM-RW-2
WM-CW-4
WM-CW-3
E256
EP2ELA- 29
N
SC
-1 C
P-
C P-
WT-2
WT-1
MV-1
SM
W
P-
VFD-
GF-1
SMWP-1
BCU-2371
E280 TYP
OF 8
EP2ELA- 33
EP2ELA- 33
EP2ELA- 33
EP2ELA- 33
EP2ELA- 33
EP2ELA- 33
EP2ELA- 33 EP2ELA- 33
A
AAA
A
A
A
A.
B.
C.
D.
E.
F.
G.
H.
I.
J.
K.
L.
M.
N.
O.
P.
Q.
R.
S.
T.
SEE DRAWING E0.1 FOR ABBREVIATIONS, SYMBOLS, GENERAL
NOTES AND DEVICE MOUNTING HEIGHT OF WALL MOUNTED
DEVICES, UON.
ALL BRANCH CIRCUIT WIRING SHALL BE A MINIMUM SIZE OF #10
AWG. REFER TO SHEET E0.2 FOR ADDITIONAL SIZING
INFORMATION.
THE CONTRACTOR SHALL COORDINATE EXACT LOCATION OF
EQUIPMENT POWER CONNECTIONS WITH EQUIPMENT
INSTALLER PRIOR TO ROUGH-IN.
SEE MECHANICAL EQUIPMENT SCHEDULE FOR ASSOCIATED
OVERCURRENT DEVICES, DISCONNECT SWITCHES, STARTERS
AND WIRES.
CONTRACTOR SHALL COORDINATE AND FIELD VERIFY
REQUIREMENT OF NEUTRAL CONDUCTOR FOR ALL EQUIPMENT
AND PROVIDE NEUTRAL CONDUCTOR AS NECESSARY.
ALL CIRCUITS SHALL BE EQUIPPED WITH A DEDICATED
NEUTRAL CONDUCTOR, UNLESS NOTED OTHERWISE.
ALL CONDUCTORS SHALL BE COPPER, UNLESS NOTED OR
SCHEDULED OTHERWISE.
TRIPPING OF GFCI RECEPTACLES SHALL NOT AFFECT THE
DOWNSTREAM RECEPTACLES.
NO MORE THAN 3 CIRCUITS MAY SHARE A HOMERUN.
FOR ALL MECHANICAL EQUIPMENT, PROVIDE ADDITIONAL 120V
CONNECTIONS REQUIRED BY MANUFACTURER.
FOR EACH AIR HANDLING UNIT, PROVIDE (1)120V CONNECTION
FOR LIGHTING AND RECEPTACLES. CIRCUIT TO MECHANICAL
PANEL WITHIN THE SPACE.
PROVIDE 120V CIRCUITS FOR CONTROL PANELS AS REQUIRED
BY CONTROL VENDOR. CIRCUIT TO MECHANICAL PANEL WITHIN
THE SPACE.
ALL UNUSED WALL OUTLETS TO BE COVERED WITH BLANK
PLATE. ALL BLANK PLATE COLORS TO MATCH WALL COLOR.
REFER TO 'T' SERIES PLANS FOR LOW VOLTAGE BACK BOX AND
RACEWAY REQUIREMENTS.
ALL CONDUIT ROUTED WITHIN SLAB SHALL COMPLY WITH
GUIDELINES LISTED IN STRUCTURAL DRAWINGS.
COORDINATE FINAL LOCATION OF MECHANICAL AND PLUMBING
EQUIPMENT AND ASSOCIATED DISCONNECT SWITCHES,
STARTERS, VFDS, CONTROL POWER AND OTHER POWER
REQUIREMENTS WITH DIV 22 AND 23.
CONTRACTOR IS RESPONSIBLE FOR ALL WIRING FROM VFDs
AND DISCONNECTS SHOWN IN DRAWINGS TO THE EQUIPMENT
AND IS TO COORDINATE WITH EQUIPMENT MANUFACTURER
AND INSTALLATION INSTRUCTIONS.
CONTRACTOR SHALL PROVIDE VFD CABLE FOR LINE AND LOAD
SIDE VFD CONNECTIONS.
CONTRACTOR SHALL PROVIDE RUN PERMISSIVE INTERLOCK
BETWEEN VFD AND LOAD SIDE EQUIPMENT DISCONNECT
SWITCH. DISCONNECT SWITCH SHALL BE EQUIPPED WITH
AUXILIARY CONTACT.
CHILLED BEAM MECHANICAL EQUIPMENT DOES NOT REQUIRE
POWER SOURCE CIRCUITING. SHOWN FOR REFERENCE ONLY.
EXTEND LINE SIDE OF NEAREST 120V GENERAL RECEPTACLE
POWER CIRCUIT TO ELECTRONIC PLUMBING VALVES.
COORDINATE ELECTRONIC PLUMBING VALVE INFRASTRUCTURE
REQUIREMENTS AND LOCATION WITH PLUMBING CONTRACTOR
AND EQUIPMENT MANUFACTURER PRIOR TO COMMENCING
WORK. INSTALL PER EQUIPMENT MANUFACTURERS
SPECIFICATIONS.
GENERAL SHEET NOTES
NORTH
SHEET NUMBER
PROJECT NUMBER
KEYPLAN
SEALS AND SIGNATURES
ISSUED FOR DATE
Pl ot
Da te:
G
IHS Whiteriver Hospital 200 W Hospital Drive Whiteriver, Arizona, 85941
IHS Project #: 131445 IHS Contract #: 75H70123R00008 IHS Award Date: 02/02/2024
455 NORTH THIRD STREET
SUITE 250
PHOENIX, AZ 85004
602.265.2200 smithgroup.com
Drawn By: Checked By:
BASED ON PROGRAM OF REQUIREMENTS DATED [ 03/26/22],
POR AMENDMENT DATED [ 02/03/25], AND ON SCHEMATIC
DRAWINGS APPROVED [11/19/24].
4/1 6/2
6 9
:57 :27
A M
LEVEL 2 (UPPER GROUND)
HVAC PLAN AREA G
EMP2.2.GCD
W hit tin gto n
14904.000 Whittington Baca
SHEET KEYNOTES
GRAPHIC SCALE: 1/8" = 1'-0"
8' 8' 16'0'4'
PROJECT NORTH
E256 PROVIDE 120V BRANCH CIRCUIT FOR ENERGY AND WATER
FLOW METER CONNECTIONS IN THIS AREA. COORDINATE
LOCATIONS WITH PLUMBING.
E280 PROVIDE WALL MOUNTED EMERGENCY POWER OFF (EPO)
SWITCH ASSEMBLY WITH RED MOMENTARY PUSH BUTTON,
YELLOW BODY, CLEAR FLIP COVER AND CUSTOM LABELING
AS FOLLOWS: "BOILER EMERGENCY SHUTDOWN",
MANUFACTURED BY STI #SS2-2-2-ZA-EN, OR EQUIVALENT.
ACTIVATION OF EPO SHALL SHUNT TRIP ALL CIRCUIT
BREAKERS SERVING BOILERS.
SCALE: 1/8" = 1'-0"1 LEVEL 2 (UPPER GROUND) - HVAC PLAN AREA G
FINAL CONSTRUCTION DOCUMENTS 23JAN26
BID ADDENDUM-A 16APR26
A
LSIG
2500/3
LS
IG
/3
EN
L
AB
LS
IG
0/
EN
L
AA
APW2LHA
225A
MLO
SPD
APW2LLA
150A
MCB
SPD
APW3LHA
80A
MLO
SPD
APW3LLA
60A
MLO
SPD
APW4LHA
80A
MLO
SPD
APW4LLA
60A
MLO
SPD
APW2SHD
225A
FTL
SPD
LS
I
5/
APW2SHE
225A
MLO
SPD
APW2SHA
300A
FTL
APW2SLA
400A
MCB/FTL
LS
I
0/
APW2SLB
400A
MLO
APW2SHB
300A
FTL
APW2SLC
400A
MCB/FTL
LS
I
0/
APW2SLD
400A
MLO
APW2SHC
300A
FTL
APW2SLE
400A
MCB/FTL
LS
I
0/
APW2SLF
400A
MLO
APW1LHA
80A
MLO
SPD
APW1LLA
60A
MLO
SPD
APW1SHD
125A
MLO
SPD
APW1SHE
125A
MLO
SPD
APW1SLA
225A
FTL
APW1SHA
300A
MLO
APW1SLB
225A
MLO
APW1SLC
225A
FTL
APW1SHB
300A
MLO
APW1SLD
225A
MLO
APW1SLE
225A
FTL
APW1SHC
300A
MLO
APW1SLF
225A
MLO
LS
IG
/3
EN
L
AC
APW2CHA
150A
MLO
LS
I
0/
APW1CHA
150A
MLO
LS
I
0/
LS
I
0/
APW1SLH
400A
MCB
APW1SLJ
225A
MLO
5/
M M M M
MM M
M
M
M M60 /3
APA2LHA
100A
MLO
SPD
APA2LLA
60A
MCB
SPD
APA2SHA
200A
MCB
LS
I
0/
M
APA2SLA
150A
MCB/FTL
APA1SLA
150A
MLO
AP2LLA
60A
MCB
SPD
/3
SPD
A.
B.
C.
D.
E.
F.
G.
H.
I.
J.
K.
L.
BASE BUILD SCOPE SHALL ONLY INCLUDE EMPTY CONDUITS
OF FEEDERS SHOWN ON THIS SHEET WITH FEEDER TAGS.
ADD ALTERNATE SCOPE SHALL INCLUDE PV PANELS,
CARPORTS, DC CONDUCTORS, INVERTERS, AC CONDUCTORS,
AC COMBINER BOXES, PV DISTRIBUTION BOARDS.
SEE DRAWING E0.1 FOR ABBREVIATIONS, SYMBOLS, GENERAL
NOTES.
THE CONTRACTOR SHALL COORDINATE EXACT LOCATION OF
EQUIPMENT POWER CONNECTIONS WITH EQUIPMENT
INSTALLER PRIOR TO ROUGH-IN.
COORDINATE FINAL LOCATION OF MECHANICAL EQUIPMENT
AND ASSOCIATED DISCONNECT SWITCHES, STARTERS, VFDS,
CONTROL POWER AND OTHER POWER REQUIREMENTS WITH
DIV 23 AND MECHANICAL DRAWINGS.
SEE MECHANICAL EQUIPMENT SCHEDULE FOR ASSOCIATED
OVERCURRENT DEVICES, DISCONNECT SWITCHES, STARTERS
AND WIRES.
VOLTAGE DROP SHALL BE LIMITED TO LESS THAN 3% FOR ALL
BRANCH CIRCUITS AND 2% FOR ALL FEEDERS.
CONTRACTOR SHALL COORDINATE AND FIELD VERIFY
REQUIREMENT OF NEUTRAL CONDUCTOR FOR ALL EQUIPMENT
AND PROVIDE NEUTRAL CONDUCTOR AS NECESSARY.
ALL LIFE SAFETY AND LIGHTING PANELBOARDS SHALL BE
EQUIPPED WITH TYPE 2 SPD.
ALL AUTOMATIC TRANSFER SWITCHES SHALL BE 4 POLE AND
EQUIPPED WITH BYPASS ISOLATION.
ALL UTILITY TRANSFORMERS DESCRIBED AS NAVOPACHE
TRANSFORMER TO BE COORDINATED WITH UTILITY AND
PROVIDED BY UTILITY. COORDINATE ALL FINAL REQUIREMENTS
AND AVAILABLE FAULT CURRENT CONTRIBUTIONS BASED ON
SUPPLIED EQUIPMENT. BASIS OF DESIGN 2500KVA, AND 5%Z.
ELECTRICAL EQUIPMENT SHALL BE CONFIGURED AS FOLLOWS:
-SERVICE ENTRANCE SECTIONS - UL891 REAR CONNECTED
SWITCHBOARD
-DISTRIBUTION SWITCHBOARDS WITH DRAWOUT CIRCUIT
BREAKERS - UL891 REAR CONNECTED SWITCHBOARD
-GENERATOR PARALLELING GEAR - UL1558 SWITCHGEAR
GENERAL SHEET NOTES
OPTIONAL
STANDBYE503
E502
M
NAVOPACHE
TRANSFORMER
ADM2SH
1000A
480-277V
3PH/4W
LIFE
SAFETY
ATS-ALA
250A
4P
LEVEL 1
LEVEL 2
LEVEL 2
LEVEL 3
TAPW2LLA
45kVA
LEVEL 3
LEVEL 4
ATS-ASA
1000A
4P
LTG
TAPW2SLA/B
112.5kVA
PWR
TAPW2SLC/D
112.5kVA
TAPW2SLE/F
112.5kVA
PWR PWR
CRITICAL
ADM2CH
1000A
480-277V
3PH/4W
ATS-ACA
1000A
4P
PWR
PWR
LEVEL 4
ROOF
A1000
A250 A1000
T112T112T112T45
A300
A400
A300 A225
A225
A300
A300 A225
A225
A400
A300
A300 A225
A225
A400
A225
A125 A125
A225
A150
A1000
A1000
A150
E501
TAPW1SLH/J
112.5kVA
A225
LAB PWR
ADM2LH
250A 480-277V
3PH/4W
A225
MAIN
SA1
SA2 SA3 SA4
DA1 DA2 DA3 DA4 DA7
DA5 DA8
A250
TAPA2LLA
15kVA
60V1
T15
EMS PWR
A200V1
EMS BLDG
TAPA2SLA
45kVA
T45
A150
DA6
MATCHLINE
MATCHLINE
TAP2LLA
15kVA T15
T112
SES-A
3200A BUS
PER NEC 705.12(B)
480-277V/3PH/4W (3)
E521
SEL-751
(3)(3)
A
SHEET NUMBER
PROJECT NUMBER
SEALS AND SIGNATURES
ISSUED FOR DATE
Pl ot
Da te:
IHS Whiteriver Hospital 200 W Hospital Drive Whiteriver, Arizona, 85941
IHS Project #: 131445 IHS Contract #: 75H70123R00008 IHS Award Date: 02/02/2024
455 NORTH THIRD STREET
SUITE 250
PHOENIX, AZ 85004
602.265.2200 smithgroup.com
Drawn By: Checked By:
BASED ON PROGRAM OF REQUIREMENTS DATED [ 03/26/22],
POR AMENDMENT DATED [ 02/03/25], AND ON SCHEMATIC
DRAWINGS APPROVED [11/19/24].
4/1 6/2
6 9
:57 :32
A M
ELECTRICAL ONE LINE
DIAGRAM - SES-A, 1 OF 2
E5.1.1CD
W hit tin gto n
14904.000 Whittington Baca
X FEEDER SCHEDULE
SHEET KEYNOTES
E501 NAVOPACHE UTILITY METER. METER SHALL BE EQUIPPED
WITH CAPABILITY TO INTERFACE WITH BMS. ELECTRICAL
CONTRACTOR SHALL PROVIDE REQUIRED CONDUIT AND
COMMUNICATION WIRING FROM METER TO POINT OF
INTERFACE WITH BMS.
E502 COMPLIANCE WITH "NEC 240.87 ARC ENERGY REDUCTION"
REQUIRED. REDUCTION METHOD SHALL ALLOW FOR
REQUIRED SELECTIVE DEVICE COORDINATION AND ARC
FLASH REQUIREMENTS. REFER TO ELECTRICAL
SPECIFICATIONS FOR ADDITIONAL INFORMATION.
E503 PROVIDE PERMANENT IDENTIFICATION PLAQUE INDICATING
THE FOLLOWING: ELECTRICAL SERVICE #1 OF 5.
GENERATORS LOCATED IN ELECTRICAL EQUIPMENT YARD,
GENERATOR DISCONNECTS LOCATED IN ADJACENT
ELECTRICAL ROOM IN GMDB. PV DISCONNECT LOCATED AT
END OF THIS ELECTRICAL EQUIPMENT LINEUP.
E521 PROVIDE RELAY PROTECTION ELEMENTS REQUIRED BY
UTILITY AND MULTIPLE GENERATOR AND PV MONITORING
AND CONTROL SYSTEM MANUFACTURER. INTEGRATE SEL
RELAY AND PROGRAMMING INTO MULTIPLE GENERATOR
AND PV MONITORING SYSTEM AND CIRCUIT BREAKER.
PROVIDE AND PROGRAM PROTECTION ELEMENT SET POINTS
AND LOGIC WITHIN THE RELAY. REFER TO SEL-751 DETAIL
FOR ADDITIONAL INFORMATION.
SCALE: NOT TO SCALE1 ONE LINE DIAGRAM - SES-A, 1 OF 2
60 4#4 + 1#10 G, 1 1/4" C 60V1 4#1 + 1#6 G, 1 1/2" C 80 4#3 + 1#8 G, 1 1/4" C A125 4#2/0 + 1#6 G, 2" C A150 4#3/0 + 1#4 G, 2" C
A200V1 4#400KCMIL + 1#1 G, 2 1/2" C
A225 4#300KCMIL + 1#2 G, 2 1/2" C
A250 4#350KCMIL + 1#2 G, 2 1/2" C
A300 4#500KCMIL + 1#2 G, 3" C
A400 2 SETS OF 4#250KCMIL + 1#1 G, (2) 2 1/2" C
A1000 3 SETS OF 4#600KCMIL + 1#4/0 G, (3) 3 1/2" C
T15 15KVA TRANSFORMER, 480-208Y/120V, 3PH
PRIMARY FEEDER: 3#10 + 1#10 G, 3/4" C
SECONDARY FEEDER: 4#4 + 1#8 G, 1 1/4" C
BONDING JUMPERS & GROUNDING ELECTRODE
CONDUCTOR: #8
T45 45KVA TRANSFORMER, 480-208Y/120V, 3PH
PRIMARY FEEDER: 3#3 + 1#8 G, 1 1/4" C
SECONDARY FEEDER: 4#1/0 + 1#6 G, 2" C
BONDING JUMPERS & GROUNDING ELECTRODE
CONDUCTOR: #6
T112 112.5KVA TRANSFORMER, 480-208Y/120V, 3PH
PRIMARY FEEDER: 3#3/0 + 1#6 G, 2" C
SECONDARY FEEDER: 2 SETS OF 4#3/0 + 1#2 G, (2)
2" C
BONDING JUMPERS & GROUNDING ELECTRODE
CONDUCTOR: #2
"A" DENOTES ALUMINUM CONDUCTORS, ALL OTHER CONDUCTORS SHALL BE COPPER
FINAL CONSTRUCTION DOCUMENTS 05MAR26
BID ADDENDUM-A 16APR26
AA
APW2CHD
225A
MLO/FTL
SPD
LS
I
5/
APW2CHE
225A
MLO
SPD
APW2CLA
125A
MCB
APW2CLB
125A
MCB
APW2CHB
150A
MLO
APW2CLC
125A
MCB
LS
I
0/
APW2CLD
125A
MCB
APW2CHC
150A
MLO
APW2CLE
125A
MCB
LS
I
0/
APW2CLF
125A
MCB
APW1CHD
125A
MLO
SPD
APW1CHE
125A
MLO
SPD
APW1CLA
125A
MCB
APW1CHA
150A
MLO
APW1CLB
125A
MCB
APW1CLD
125A
MCB
APW1CHB
150A
MLO
APW1CLC
125A
MCB
APW1CLF
125A
MCB
APW1CHC
150A
MLO
APW1CLE
125A
MCB
LS
IG
/3
EN
L
AD
LS
I
0/
LS
I
5/
LS
I
5/
LS
I
0/
LS
I
5/
LS
I
5/
LS
I
5/
LS
I
0/
LS
I
5/
LS
I
/3
VFD
LS
I
0/
VFD
LS
I
/3
VFD
LS
I
0/
VFD
LS
IG
0/
PVW
LS
I
0/
LS
IG
0/
EN
L
AE
LS
I
0/
LS
I
0/
APW2EHA
300A
MLO
APW1EHA
150A
MLO
APW2EHB
250A
MLO
APW1EHB
150A
MLO
APW1ELA
150A
MCB
APW1ELB
150A
MCB
LS
I
/3
M M
M M M M M M M M M M M M M M
M M M M M M
M
APA1CLA
60A
MCB
APW2ELA
150A
MCB
APW2ELB
150A
MCB
A.
B.
C.
D.
E.
F.
G.
H.
I.
J.
K.
L.
BASE BUILD SCOPE SHALL ONLY INCLUDE EMPTY CONDUITS
OF FEEDERS SHOWN ON THIS SHEET WITH FEEDER TAGS.
ADD ALTERNATE SCOPE SHALL INCLUDE PV PANELS,
CARPORTS, DC CONDUCTORS, INVERTERS, AC CONDUCTORS,
AC COMBINER BOXES, PV DISTRIBUTION BOARDS.
SEE DRAWING E0.1 FOR ABBREVIATIONS, SYMBOLS, GENERAL
NOTES.
THE CONTRACTOR SHALL COORDINATE EXACT LOCATION OF
EQUIPMENT POWER CONNECTIONS WITH EQUIPMENT
INSTALLER PRIOR TO ROUGH-IN.
COORDINATE FINAL LOCATION OF MECHANICAL EQUIPMENT
AND ASSOCIATED DISCONNECT SWITCHES, STARTERS, VFDS,
CONTROL POWER AND OTHER POWER REQUIREMENTS WITH
DIV 23 AND MECHANICAL DRAWINGS.
SEE MECHANICAL EQUIPMENT SCHEDULE FOR ASSOCIATED
OVERCURRENT DEVICES, DISCONNECT SWITCHES, STARTERS
AND WIRES.
VOLTAGE DROP SHALL BE LIMITED TO LESS THAN 3% FOR ALL
BRANCH CIRCUITS AND 2% FOR ALL FEEDERS.
CONTRACTOR SHALL COORDINATE AND FIELD VERIFY
REQUIREMENT OF NEUTRAL CONDUCTOR FOR ALL EQUIPMENT
AND PROVIDE NEUTRAL CONDUCTOR AS NECESSARY.
ALL LIFE SAFETY AND LIGHTING PANELBOARDS SHALL BE
EQUIPPED WITH TYPE 2 SPD.
ALL AUTOMATIC TRANSFER SWITCHES SHALL BE 4 POLE AND
EQUIPPED WITH BYPASS ISOLATION.
ALL UTILITY TRANSFORMERS DESCRIBED AS NAVOPACHE
TRANSFORMER TO BE COORDINATED WITH UTILITY AND
PROVIDED BY UTILITY. COORDINATE ALL FINAL REQUIREMENTS
AND AVAILABLE FAULT CURRENT CONTRIBUTIONS BASED ON
SUPPLIED EQUIPMENT. BASIS OF DESIGN 2500KVA, AND 5%Z.
ELECTRICAL EQUIPMENT SHALL BE CONFIGURED AS FOLLOWS:
-SERVICE ENTRANCE SECTIONS - UL891 REAR CONNECTED
SWITCHBOARD
-DISTRIBUTION SWITCHBOARDS WITH DRAWOUT CIRCUIT
BREAKERS - UL891 REAR CONNECTED SWITCHBOARD
-GENERATOR PARALLELING GEAR - UL1558 SWITCHGEAR
GENERAL SHEET NOTES
LTG
TAPW2CLA/B
75kVA
PWR PWR
EQUIPMENT
ADM2EHA
1600A
480-277V
3PH/4W
ATS-AEA
1600A
4P
LEVEL 1
LEVEL 2
LEVEL 2
LEVEL 3
LEVEL 3
LEVEL 4
PWR PWR
TAPW1CLA/B
75kVA
PWR
PWR
TAPW2CLC/D
75kVA
PWR
PWR
TAPW1CLC/D
75kVA
TAPW2CLE/F
75kVA
PWR
PWR PWR
TAPW1CLE/F
75kVA
LEVEL 4
ROOF
T75D T75D
T75DT75DT75D A150 A150 A225
A225
A150 A150 A150 A125 A125
A1600
A1600
1000-3
ACCH-1
CHWP-1
100-3
HHWP-1
30-3
CBWP-1
100-3
PV A
EH-1
EQUIPMENT
ADM2EHB
600A
480-277V
3PH/4W
ATS-AEB
600A
4P
A600
A600
A250A300
A150 T75D
300-3
TAPW1ELA
45kVA
T45
TAPW1ELB
45kVA
T45
, E O
1000-3
B-1
NON-COINCIDENT
LOAD
SA5 SA6
DA9 DA11 DA13 DA15 DA17 DA19 DA20 DA21 DA22 DA23 DA24 DA25 DA26 DA29
DA8 DA10 DA12 DA14 DA16 DA18
E519
60V1
EMS BLDG
SA7
MATCHLINE
TAPW2ELA
45kVA
T45
TAPW2ELB
45kVA
T45
A150
MATCHLINE
NON-COINCIDENT
LOAD
E530
A
SHEET NUMBER
PROJECT NUMBER
SEALS AND SIGNATURES
ISSUED FOR DATE
Pl ot
Da te:
IHS Whiteriver Hospital 200 W Hospital Drive Whiteriver, Arizona, 85941
IHS Project #: 131445 IHS Contract #: 75H70123R00008 IHS Award Date: 02/02/2024
455 NORTH THIRD STREET
SUITE 250
PHOENIX, AZ 85004
602.265.2200 smithgroup.com
Drawn By: Checked By:
BASED ON PROGRAM OF REQUIREMENTS DATED [ 03/26/22],
POR AMENDMENT DATED [ 02/03/25], AND ON SCHEMATIC
DRAWINGS APPROVED [11/19/24].
4/1 6/2
6 9
:57 :37
A M
ELECTRICAL ONE LINE
DIAGRAM - SES-A, 2 OF 2
E5.1.2CD
W hit tin gto n
14904.000 Whittington Baca
X FEEDER SCHEDULE
SHEET KEYNOTES
E519 PV CIRCUIT BREAKER SHALL BE LOCATED AT LAST BUSSED
SPACE. PROVIDE PERMANENT IDENTIFICATION PLAQUE
INDICATING THE FOLLOWING: PV POWER SOURCE - DO NOT
RELOCATE THIS CIRCUIT BREAKER
E530 PROVIDE SHUNT TRIP CIRCUIT BREAKER FOR INTERFACE
WITH BOILER EMERGENCY SHUTDOWN EPO SWITCHES.
REFER TO EMP2.2.G FOR ADDITIONAL INFORMATION.
SCALE: NOT TO SCALE1 ONE LINE DIAGRAM - SES-A, 2 OF 2
30-3 3#10 + 1#10 G, 3/4" C 60V1 4#1 + 1#6 G, 1 1/2" C 100-3 3#1 + 1#8 G, 1 1/2" C
300-3 3#350KCMIL + 1#4 G, 3" C
1000-3 3 SETS OF 3#400KCMIL + 1#2/0 G, (3) 3" C
A125 4#2/0 + 1#6 G, 2" C A150 4#3/0 + 1#4 G, 2" C
A225 4#300KCMIL + 1#2 G, 2 1/2" C
A250 4#350KCMIL + 1#2 G, 2 1/2" C
A300 4#500KCMIL + 1#2 G, 3" C
A600 2 SETS OF 4#500KCMIL + 1#2/0 G, (2) 3" C
A1600 5 SETS OF 4#600KCMIL + 1#350KCMIL G, (5) 3 1/2" C
T45 45KVA TRANSFORMER, 480-208Y/120V, 3PH
PRIMARY FEEDER: 3#3 + 1#8 G, 1 1/4" C
SECONDARY FEEDER: 4#1/0 + 1#6 G, 2" C
BONDING JUMPERS & GROUNDING ELECTRODE
CONDUCTOR: #6
T75D 75KVA TRANSFORMER, 480-208Y/120V, 3PH
PRIMARY FEEDER: 3#1/0 + 1#6 G, 1 1/2" C
SECONDARY FEEDERS: 4#1/0 + 1#2 G, 2" C TO EACH PANEL
BONDING JUMPERS & GROUNDING ELECTRODE
CONDUCTOR: #2
"A" DENOTES ALUMINUM CONDUCTORS, ALL OTHER CONDUCTORS SHALL BE COPPER
FINAL CONSTRUCTION DOCUMENTS 05MAR26
BID ADDENDUM-A 16APR26
A
A
LS
IG
/3
EN
L
BB
LS
IG
0/
EN
L
BA
BPE2SHD
225A
FTL
SPD
LS
I
5/
BPE2SHE
225A
MLO
SPD
BPE2SHA
300A
FTL
BPE2SLA
400A
MCB/FTL
LS
I
0/
BPE2SLB
400A
MLO
BPE2SHB
300A
FTL
BPE2SLC
225A
MCB/FTL
LS
I
0/
BPE2SLD
225A
MLO
BPE1SHD
125A
MLO
SPD
BPE1SHE
125A
MLO
SPD
BPE1SLA
225A
FTL
BPE1SHA
300A
MLO
BPE1SLB
225A
MLO
BPE1SLC
225A
FTL
BPE1SHB
300A
MLO
BPE1SLD
225A
MLO
/3
/3
/3
/3
/3
LS
IG
/3
LS
I
/3
BPT2SLA
150A
MCB
BPT2SLB
225A
MCB
LS
I
5/
BPT1SLA
80A
MLO
BPT3SLA
80A
MLO
BPT4SLA
80A
MLO
BPT2SLC
225A
MCB
LS
I
5/
BPT1SLB
80A
MLO
BPT3SLB
80A
MLO
BPT4SLB
80A
MLO
BPF2SHA
250A
MLO
BPF2SLA
225A
MCB
LS
I
0/
M
M M
M M M M M M M
SPD
A.
B.
C.
D.
E.
F.
G.
H.
I.
J.
K.
L.
BASE BUILD SCOPE SHALL ONLY INCLUDE EMPTY CONDUITS
OF FEEDERS SHOWN ON THIS SHEET WITH FEEDER TAGS.
ADD ALTERNATE SCOPE SHALL INCLUDE PV PANELS,
CARPORTS, DC CONDUCTORS, INVERTERS, AC CONDUCTORS,
AC COMBINER BOXES, PV DISTRIBUTION BOARDS.
SEE DRAWING E0.1 FOR ABBREVIATIONS, SYMBOLS, GENERAL
NOTES.
THE CONTRACTOR SHALL COORDINATE EXACT LOCATION OF
EQUIPMENT POWER CONNECTIONS WITH EQUIPMENT
INSTALLER PRIOR TO ROUGH-IN.
COORDINATE FINAL LOCATION OF MECHANICAL EQUIPMENT
AND ASSOCIATED DISCONNECT SWITCHES, STARTERS, VFDS,
CONTROL POWER AND OTHER POWER REQUIREMENTS WITH
DIV 23 AND MECHANICAL DRAWINGS.
SEE MECHANICAL EQUIPMENT SCHEDULE FOR ASSOCIATED
OVERCURRENT DEVICES, DISCONNECT SWITCHES, STARTERS
AND WIRES.
VOLTAGE DROP SHALL BE LIMITED TO LESS THAN 3% FOR ALL
BRANCH CIRCUITS AND 2% FOR ALL FEEDERS.
CONTRACTOR SHALL COORDINATE AND FIELD VERIFY
REQUIREMENT OF NEUTRAL CONDUCTOR FOR ALL EQUIPMENT
AND PROVIDE NEUTRAL CONDUCTOR AS NECESSARY.
ALL LIFE SAFETY AND LIGHTING PANELBOARDS SHALL BE
EQUIPPED WITH TYPE 2 SPD.
ALL AUTOMATIC TRANSFER SWITCHES SHALL BE 4 POLE AND
EQUIPPED WITH BYPASS ISOLATION.
ALL UTILITY TRANSFORMERS DESCRIBED AS NAVOPACHE
TRANSFORMER TO BE COORDINATED WITH UTILITY AND
PROVIDED BY UTILITY. COORDINATE ALL FINAL REQUIREMENTS
AND AVAILABLE FAULT CURRENT CONTRIBUTIONS BASED ON
SUPPLIED EQUIPMENT. BASIS OF DESIGN 2500KVA, AND 5%Z.
ELECTRICAL EQUIPMENT SHALL BE CONFIGURED AS FOLLOWS:
-SERVICE ENTRANCE SECTIONS - UL891 REAR CONNECTED
SWITCHBOARD
-DISTRIBUTION SWITCHBOARDS WITH DRAWOUT CIRCUIT
BREAKERS - UL891 REAR CONNECTED SWITCHBOARD
-GENERATOR PARALLELING GEAR - UL1558 SWITCHGEAR
GENERAL SHEET NOTES
E504
E502
M
NAVOPACHE
TRANSFORMER
LEVEL 1
LEVEL 2
LEVEL 2
LEVEL 3
LEVEL 3
LEVEL 4
LEVEL 4
ROOF
OPTIONAL
STANDBY
BDM2SH
1000A
480-277V
3PH/4W
EQUIPMENT
(ELEVATORS)
ATS-BEA
400A
4P
ATS-BSA
1000A
4P
LTG
TBPE2SLA/B
112.5kVA
TBPE2SLC/D
75kVA
CNTRL
PNL
STAFF/PATIENT
ELEV 1B
CNTRL
PNL
STAFF/PATIENT
ELEV 1A
CNTRL
PNL
FREIGHT ELEV 5
CNTRL
PNL
PUBLIC ELEV 4B
CNTRL
PNL
PUBLIC ELEV 4A
BDW4EH
400A 480-277V
3PH/4W
ATS-BCA
1000A
4P
PWR PWR
A400
A400
A1000
A1000
A300 A300V1 A225
T112 T75
A300 A225
A225
A400
A300
A225
A225
A125 A125
A225V1
TBPT2SLA
45kVA K13
TBPT2SLB
75kVA K13
TBPT2SLC
75kVA K13
T45N T75N T75N
80 80
80 80
80 80
MDF IDF IDF
E501
50-3 50-3 80-3 50-3V1 50-3V1
FAC BLDG
TBPF2SLA
75kVA
MAIN
SB1
SB2 SB3
DB1 DB2 DB3 DB4 DB5 DB6 DB7
MATCHLINE
MATCHLINE
T75
A250
A250
TBPT2SLA
200A/150AF
BPF2SHA
400A/250AF
TBPE1SLC/D
75kVA
T75
TBPT2SLB
400A/225AF
TBPT2SLC
400A/225AF
#2
SES-B
3200A BUS
PER NEC 705.12(B)
480-277V/3PH/4W (3)
E521
SEL-751
(3)(3)
A
SHEET NUMBER
PROJECT NUMBER
SEALS AND SIGNATURES
ISSUED FOR DATE
Pl ot
Da te:
IHS Whiteriver Hospital 200 W Hospital Drive Whiteriver, Arizona, 85941
IHS Project #: 131445 IHS Contract #: 75H70123R00008 IHS Award Date: 02/02/2024
455 NORTH THIRD STREET
SUITE 250
PHOENIX, AZ 85004
602.265.2200 smithgroup.com
Drawn By: Checked By:
BASED ON PROGRAM OF REQUIREMENTS DATED [ 03/26/22],
POR AMENDMENT DATED [ 02/03/25], AND ON SCHEMATIC
DRAWINGS APPROVED [11/19/24].
4/1 6/2
6 9
:57 :43
A M
ELECTRICAL ONE LINE
DIAGRAM - SES-B, 1 OF 2
E5.2.1CD
W hit tin gto n
14904.000 Whittington Baca
X FEEDER SCHEDULE
SHEET KEYNOTES
E501 NAVOPACHE UTILITY METER. METER SHALL BE EQUIPPED
WITH CAPABILITY TO INTERFACE WITH BMS. ELECTRICAL
CONTRACTOR SHALL PROVIDE REQUIRED CONDUIT AND
COMMUNICATION WIRING FROM METER TO POINT OF
INTERFACE WITH BMS.
E502 COMPLIANCE WITH "NEC 240.87 ARC ENERGY REDUCTION"
REQUIRED. REDUCTION METHOD SHALL ALLOW FOR
REQUIRED SELECTIVE DEVICE COORDINATION AND ARC
FLASH REQUIREMENTS. REFER TO ELECTRICAL
SPECIFICATIONS FOR ADDITIONAL INFORMATION.
E504 PROVIDE PERMANENT IDENTIFICATION PLAQUE INDICATING
THE FOLLOWING: ELECTRICAL SERVICE #2 OF 5.
GENERATORS LOCATED IN ELECTRICAL EQUIPMENT YARD,
GENERATOR DISCONNECTS LOCATED IN ADJACENT
ELECTRICAL ROOM IN GMDB. PV DISCONNECT LOCATED AT
END OF THIS ELECTRICAL EQUIPMENT LINEUP.
E521 PROVIDE RELAY PROTECTION ELEMENTS REQUIRED BY
UTILITY AND MULTIPLE GENERATOR AND PV MONITORING
AND CONTROL SYSTEM MANUFACTURER. INTEGRATE SEL
RELAY AND PROGRAMMING INTO MULTIPLE GENERATOR
AND PV MONITORING SYSTEM AND CIRCUIT BREAKER.
PROVIDE AND PROGRAM PROTECTION ELEMENT SET POINTS
AND LOGIC WITHIN THE RELAY. REFER TO SEL-751 DETAIL
FOR ADDITIONAL INFORMATION.
SCALE: NOT TO SCALE1 ONE LINE DIAGRAM - SES-B, 1 OF 2
50-3 3#6 + 1#10 G, 3/4" C 50-3V1 3#2 + 1#4 G, 1 1/4" C 80 4#3 + 1#8 G, 1 1/4" C 80-3 3#3 + 1#8 G, 1 1/4" C A125 4#2/0 + 1#6 G, 2" C
A225 4#300KCMIL + 1#2 G, 2 1/2" C
A225V1 4#400KCMIL + 1#1/0 G, 2 1/2" C
A250 4#350KCMIL + 1#2 G, 2 1/2" C
A300 4#500KCMIL + 1#2 G, 3" C
A300V1 4#600KCMIL + 1#1 G, 3" C
A400 2 SETS OF 4#250KCMIL + 1#1 G, (2) 2 1/2" C
A1000 3 SETS OF 4#600KCMIL + 1#4/0 G, (3) 3 1/2" C
T45N 45KVA TRANSFORMER, 480-208Y/120V, 3PH
PRIMARY FEEDER: 3#3 + 1#8 G, 1 1/4" C
SECONDARY FEEDER: 3#1/0, 1#4/0 N + 1#6 G, 2" C
BONDING JUMPERS & GROUNDING ELECTRODE
CONDUCTOR: #6
T75 75KVA TRANSFORMER, 480-208Y/120V, 3PH
PRIMARY FEEDER: 3#1/0 + 1#6 G, 1 1/2" C
SECONDARY FEEDER: 4#4/0 + 1#2 G, 2 1/2" C
BONDING JUMPERS & GROUNDING ELECTRODE
CONDUCTOR: #2
T75N 75KVA TRANSFORMER, 480-208Y/120V, 3PH
PRIMARY FEEDER: 3#1/0 + 1#6 G, 1 1/2" C
SECONDARY FEEDER: 3#4/0, 1#500KCMIL N + 1#2
G, 2 1/2" C
BONDING JUMPERS & GROUNDING ELECTRODE
CONDUCTOR: #2
T112 112.5KVA TRANSFORMER, 480-208Y/120V, 3PH
PRIMARY FEEDER: 3#3/0 + 1#6 G, 2" C
SECONDARY FEEDER: 2 SETS OF 4#3/0 + 1#2 G, (2)
2" C
BONDING JUMPERS & GROUNDING ELECTRODE
CONDUCTOR: #2
"A" DENOTES ALUMINUM CONDUCTORS, ALL OTHER CONDUCTORS SHALL BE COPPER
FINAL CONSTRUCTION DOCUMENTS 05MAR26
BID ADDENDUM-A 16APR26
A
LS
IG
/3
EN
L
BC
BPE2CHD
225A
FTL
SPD
LS
I
5/
BPE2CHE
225A
MLO
SPD
BPE2CHA
150A
MLO
BPE2CLA
125A
MCB
LS
I
0/
BPE2CLB
125A
MCB
BPE2CHB
150A
MLO
BPE2CLC
125A
MCB
LS
I
0/
BPE2CLD
125A
MCB
BPE1CHD
125A
MLO
SPD
BPE1CHE
125A
MLO
SPD
BPE1CLA
125A
MCB
BPE1CHA
150A
MLO
BPE1CLB
125A
MCB
BPE1CLD
125A
MCB
BPE1CHB
150A
MLO
BPE1CLC
125A
MCB
LS
IG
/3
EN
L
BD
LS
I
0/
LS
I
5/
LS
I
5/
LS
I
0/
LS
I
5/
LS
I
5/
BPE2CLE
125A
MCB
BPE2CLF
125A
MCB
LS
I
5/
LS
I
/3
VFD
LS
I
0/
VFD
LS
I
/3
VFD
LS
I
0/
VFD
LS
I
0/
LS
IG
0/
PVX
LS
IG
0/
EN
L
BE
LS
I
0/
LS
I
0/
BPE2EHA
400A
MLO
BPE1EHA
225A
MLO
BPE2EHB
400A
MLO
BPE1EHB
225A
MLO
BPE1ELA
150A
MCB
BPE1ELB
150A
MCB
LS
I
0/
LS
I
0/
LS
I
0/
UA1 BP1 UB1
LS
I
/3
M M M M
M
M
M M M M M
M M M M M
M M M M M M M M
A.
B.
C.
D.
E.
F.
G.
H.
I.
J.
K.
L.
BASE BUILD SCOPE SHALL ONLY INCLUDE EMPTY CONDUITS
OF FEEDERS SHOWN ON THIS SHEET WITH FEEDER TAGS.
ADD ALTERNATE SCOPE SHALL INCLUDE PV PANELS,
CARPORTS, DC CONDUCTORS, INVERTERS, AC CONDUCTORS,
AC COMBINER BOXES, PV DISTRIBUTION BOARDS.
SEE DRAWING E0.1 FOR ABBREVIATIONS, SYMBOLS, GENERAL
NOTES.
THE CONTRACTOR SHALL COORDINATE EXACT LOCATION OF
EQUIPMENT POWER CONNECTIONS WITH EQUIPMENT
INSTALLER PRIOR TO ROUGH-IN.
COORDINATE FINAL LOCATION OF MECHANICAL EQUIPMENT
AND ASSOCIATED DISCONNECT SWITCHES, STARTERS, VFDS,
CONTROL POWER AND OTHER POWER REQUIREMENTS WITH
DIV 23 AND MECHANICAL DRAWINGS.
SEE MECHANICAL EQUIPMENT SCHEDULE FOR ASSOCIATED
OVERCURRENT DEVICES, DISCONNECT SWITCHES, STARTERS
AND WIRES.
VOLTAGE DROP SHALL BE LIMITED TO LESS THAN 3% FOR ALL
BRANCH CIRCUITS AND 2% FOR ALL FEEDERS.
CONTRACTOR SHALL COORDINATE AND FIELD VERIFY
REQUIREMENT OF NEUTRAL CONDUCTOR FOR ALL EQUIPMENT
AND PROVIDE NEUTRAL CONDUCTOR AS NECESSARY.
ALL LIFE SAFETY AND LIGHTING PANELBOARDS SHALL BE
EQUIPPED WITH TYPE 2 SPD.
ALL AUTOMATIC TRANSFER SWITCHES SHALL BE 4 POLE AND
EQUIPPED WITH BYPASS ISOLATION.
ALL UTILITY TRANSFORMERS DESCRIBED AS NAVOPACHE
TRANSFORMER TO BE COORDINATED WITH UTILITY AND
PROVIDED BY UTILITY. COORDINATE ALL FINAL REQUIREMENTS
AND AVAILABLE FAULT CURRENT CONTRIBUTIONS BASED ON
SUPPLIED EQUIPMENT. BASIS OF DESIGN 2500KVA, AND 5%Z.
ELECTRICAL EQUIPMENT SHALL BE CONFIGURED AS FOLLOWS:
-SERVICE ENTRANCE SECTIONS - UL891 REAR CONNECTED
SWITCHBOARD
-DISTRIBUTION SWITCHBOARDS WITH DRAWOUT CIRCUIT
BREAKERS - UL891 REAR CONNECTED SWITCHBOARD
-GENERATOR PARALLELING GEAR - UL1558 SWITCHGEAR
GENERAL SHEET NOTES
LEVEL 1
LEVEL 2
LEVEL 2
LEVEL 3
LEVEL 3
LEVEL 4
LEVEL 4
ROOF
CRITICAL
BDM2CH
1000A
480-277V
3PH/4W
ATS-BCA
1000A
4P
LTG
TBPE2CLA/B
75kVA
PWR PWR
EQUIPMENT
BDM2EHA
1600A
480-277V
3PH/4W
ATS-BEB
1600A
4P
PWR PWR
TBPE1CLA/B
75kVA
PWR
PWR
TBPE2CLC/D
75kVA
PWR
PWR
TBPE1CLC/D
75kVA
TBPE2CLE/F
75kVA
PWR
A1000
A1000
A150
T75D
A150V1
T75DV1 T75D
A225
T75D T75DV1
A150 A150V1 A125 A125
A225V1
A1600
A1600
1000-3
ACCH-2
CHWP-2
100-3
HHWP-2
30-3
CBWP-2
100-3
EH-2
PV BEQUIPMENT
BDM2EHB
600A
480-277V
3PH/4W
ATS-BEC
600A
4P
A600
A600
A400V1A400
A225
TBPE1ELA
45kVA
T45
TBPE1ELB
45kVA
T45
, E O
400 400 400
UPS A1
INPUT
UPS B1
INPUT
UPS A1/B1
BYPASS
1000-3
NON-COINCIDENT
LOAD
B-2
E519
SB4 SB5 SB6
DB8
DB9
DB10 DB12 DB14 DB19
DB11 DB13 DB15 DB17 DB18
DB16
DB20 DB21 DB22 DB23 DB24 DB25 DB26 DB27
SB7
MATCHLINE
MATCHLINE
300-3
A225
E530
A
SHEET NUMBER
PROJECT NUMBER
SEALS AND SIGNATURES
ISSUED FOR DATE
Pl ot
Da te:
IHS Whiteriver Hospital 200 W Hospital Drive Whiteriver, Arizona, 85941
IHS Project #: 131445 IHS Contract #: 75H70123R00008 IHS Award Date: 02/02/2024
455 NORTH THIRD STREET
SUITE 250
PHOENIX, AZ 85004
602.265.2200 smithgroup.com
Drawn By: Checked By:
BASED ON PROGRAM OF REQUIREMENTS DATED [ 03/26/22],
POR AMENDMENT DATED [ 02/03/25], AND ON SCHEMATIC
DRAWINGS APPROVED [11/19/24].
4/1 6/2
6 9
:57 :48
A M
ELECTRICAL ONE LINE
DIAGRAM - SES-B, 2 OF 2
E5.2.2CD
W hit tin gto n
14904.000 Whittington Baca
X FEEDER SCHEDULE
SHEET KEYNOTES
E519 PV CIRCUIT BREAKER SHALL BE LOCATED AT LAST BUSSED
SPACE. PROVIDE PERMANENT IDENTIFICATION PLAQUE
INDICATING THE FOLLOWING: PV POWER SOURCE - DO NOT
RELOCATE THIS CIRCUIT BREAKER
E530 PROVIDE SHUNT TRIP CIRCUIT BREAKER FOR INTERFACE
WITH BOILER EMERGENCY SHUTDOWN EPO SWITCHES.
REFER TO EMP2.2.G FOR ADDITIONAL INFORMATION.
SCALE: NOT TO SCALE1 ONE LINE DIAGRAM - SES-B, 2 OF 2
30-3 3#10 + 1#10 G, 3/4" C 100-3 3#1 + 1#8 G, 1 1/2" C
300-3 3#350KCMIL + 1#4 G, 3" C
400 2 SETS OF 4#3/0 + 1#3 G, (2) 2" C
1000-3 3 SETS OF 3#400KCMIL + 1#2/0 G, (3) 3" C
A125 4#2/0 + 1#6 G, 2" C A150 4#3/0 + 1#4 G, 2" C
A150V1 4#400KCMIL + 1#1/0 G, 2-1/2" C
A225 4#300KCMIL + 1#2 G, 2 1/2" C
A225V1 4#400KCMIL + 1#1/0 G, 2 1/2" C
A400 2 SETS OF 4#250KCMIL + 1#1 G, (2) 2 1/2" C
A400V1 2 SETS OF 4#500KCMIL + 1#2/0 G, (2) 3" C
A600 2 SETS OF 4#500KCMIL + 1#2/0 G, (2) 3" C
A1000 3 SETS OF 4#600KCMIL + 1#4/0 G, (3) 3 1/2" C
A1600 5 SETS OF 4#600KCMIL + 1#350KCMIL G, (5) 3 1/2" C
T45 45KVA TRANSFORMER, 480-208Y/120V, 3PH
PRIMARY FEEDER: 3#3 + 1#8 G, 1 1/4" C
SECONDARY FEEDER: 4#1/0 + 1#6 G, 2" C
BONDING JUMPERS & GROUNDING ELECTRODE
CONDUCTOR: #6
T75D 75KVA TRANSFORMER, 480-208Y/120V, 3PH
PRIMARY FEEDER: 3#1/0 + 1#6 G, 1 1/2" C
SECONDARY FEEDERS: 4#1/0 + 1#2 G, 2" C TO
EACH PANEL
BONDING JUMPERS & GROUNDING ELECTRODE
CONDUCTOR: #2
T75DV1 75KVA TRANSFORMER, 480-208Y/120V, 3PH
PRIMARY FEEDER: 3#3/0 + 1#4 G, 2" C
SECONDARY FEEDERS: 4#1/0 + 1#2 G, 2" C TO
EACH PANEL
BONDING JUMPERS & GROUNDING ELECTRODE
CONDUCTOR: #2
"A" DENOTES ALUMINUM CONDUCTORS, ALL OTHER CONDUCTORS SHALL BE COPPER
FINAL CONSTRUCTION DOCUMENTS 05MAR26
BID ADDENDUM-A 16APR26
A
A
LS
IG
/3
EN
L
CA
CPW3SHD
225A
FTL
SPD
LS
I
5/
CPW3SHE
225A
MLO
SPD
CPW3SHA
300A
FTL
CPW3SLA
400A
MCB/FTL
LS
I
0/
CPW3SLB
400A
MLO
CPW3SHB
300A
FTL
CPW3SLC
400A
MCB/FTL
LS
I
0/
CPW3SLD
400A
MLO
CPW3SHC
300A
FTL
CPW3SLE
400A
MCB/FTL
LS
I
0/
CPW3SLF
400A
MLO
CPW4SHD
125A
MLO
SPD
CPW4SHE
125A
MLO
SPD
CPW4SLA
225A
FTL
CPW4SHA
300A
MLO
CPW4SLB
225A
MLO
CPW4SLC
225A
FTL
CPW4SHB
300A
MLO
CPW4SLD
225A
MLO
CPW4SLE
400A
MCB/FTL
CPW4SHC
300A
MLO
CPW4SLF
400A
MLO
LS
IG
/3
CPT1SLA
150A
MCB
LS
I
5/
CPT2SLA
225A
MCB
CPT3SLA
80A
MLO
CPT4SLA
80A
MLO
LS
I
/3
M
M
M
M M M M
M
LS
I
5/
CP2SHA
125A
MLO
M
CP2SLA
150A
MCB
LS
I
5/
CPF2SHA
225A
MLO
M
CPF2SHA
225A
MCB
SPD
A.
B.
C.
D.
E.
F.
G.
H.
I.
J.
K.
L.
BASE BUILD SCOPE SHALL ONLY INCLUDE EMPTY CONDUITS
OF FEEDERS SHOWN ON THIS SHEET WITH FEEDER TAGS.
ADD ALTERNATE SCOPE SHALL INCLUDE PV PANELS,
CARPORTS, DC CONDUCTORS, INVERTERS, AC CONDUCTORS,
AC COMBINER BOXES, PV DISTRIBUTION BOARDS.
SEE DRAWING E0.1 FOR ABBREVIATIONS, SYMBOLS, GENERAL
NOTES.
THE CONTRACTOR SHALL COORDINATE EXACT LOCATION OF
EQUIPMENT POWER CONNECTIONS WITH EQUIPMENT
INSTALLER PRIOR TO ROUGH-IN.
COORDINATE FINAL LOCATION OF MECHANICAL EQUIPMENT
AND ASSOCIATED DISCONNECT SWITCHES, STARTERS, VFDS,
CONTROL POWER AND OTHER POWER REQUIREMENTS WITH
DIV 23 AND MECHANICAL DRAWINGS.
SEE MECHANICAL EQUIPMENT SCHEDULE FOR ASSOCIATED
OVERCURRENT DEVICES, DISCONNECT SWITCHES, STARTERS
AND WIRES.
VOLTAGE DROP SHALL BE LIMITED TO LESS THAN 3% FOR ALL
BRANCH CIRCUITS AND 2% FOR ALL FEEDERS.
CONTRACTOR SHALL COORDINATE AND FIELD VERIFY
REQUIREMENT OF NEUTRAL CONDUCTOR FOR ALL EQUIPMENT
AND PROVIDE NEUTRAL CONDUCTOR AS NECESSARY.
ALL LIFE SAFETY AND LIGHTING PANELBOARDS SHALL BE
EQUIPPED WITH TYPE 2 SPD.
ALL AUTOMATIC TRANSFER SWITCHES SHALL BE 4 POLE AND
EQUIPPED WITH BYPASS ISOLATION.
ALL UTILITY TRANSFORMERS DESCRIBED AS NAVOPACHE
TRANSFORMER TO BE COORDINATED WITH UTILITY AND
PROVIDED BY UTILITY. COORDINATE ALL FINAL REQUIREMENTS
AND AVAILABLE FAULT CURRENT CONTRIBUTIONS BASED ON
SUPPLIED EQUIPMENT. BASIS OF DESIGN 2500KVA, AND 5%Z.
ELECTRICAL EQUIPMENT SHALL BE CONFIGURED AS FOLLOWS:
-SERVICE ENTRANCE SECTIONS - UL891 REAR CONNECTED
SWITCHBOARD
-DISTRIBUTION SWITCHBOARDS WITH DRAWOUT CIRCUIT
BREAKERS - UL891 REAR CONNECTED SWITCHBOARD
-GENERATOR PARALLELING GEAR - UL1558 SWITCHGEAR
GENERAL SHEET NOTES
OPTIONAL
STANDBYE505
E502
M
NAVOPACHE
TRANSFORMER
CDM2SH
1000A
480-277V
3PH/4W
LEVEL 1
LEVEL 2
LEVEL 2
LEVEL 3
LEVEL 3
LEVEL 4
SES-C
3200A BUS
PER NEC 705.12(B)
480-277V/3PH/4W
ATS-CSA
1000A
4P
LTG
TCPW3SLA/B
112.5kVA
PWR
TCPW3SLC/D
112.5kVA
TCPW3SLE/F
112.5kVA
PWR PWR
LEVEL 4
ROOF
A300 A225
A225
A400
T112
A300
A300 A225
A225
A400
T112
A300
A300
A400
A400
T112
A300 A225
A225
A125 A125
A1000
A1000
TCPT2SLA
75kVA K13 T75V1
TCPT1SLA
45kVA K13 T45V1
IDF
MDF
E501
MAIN
SC1
DC1
SC2
DC2 DC3 DC4 DC6
DC5
MATCHLINE
MATCHLINE
(3)
E521
TCPW4SLE/F
112.5kVA
T112
DC7
TCP2SLA
45kVA
T45
PWR
A300
TCPT2SLA
400A/225AF
TCPT1SLA
200A/150AF
SEL-751
(3)(3)
DC7
TCPF2SHA
75kVA
T75
MOBILE CLINICS
& EVSE
(FAC BLDG)
A225
A225
CPF2SHA
400A/225AF
#2
A
SHEET NUMBER
PROJECT NUMBER
SEALS AND SIGNATURES
ISSUED FOR DATE
Pl ot
Da te:
IHS Whiteriver Hospital 200 W Hospital Drive Whiteriver, Arizona, 85941
IHS Project #: 131445 IHS Contract #: 75H70123R00008 IHS Award Date: 02/02/2024
455 NORTH THIRD STREET
SUITE 250
PHOENIX, AZ 85004
602.265.2200 smithgroup.com
Drawn By: Checked By:
BASED ON PROGRAM OF REQUIREMENTS DATED [ 03/26/22],
POR AMENDMENT DATED [ 02/03/25], AND ON SCHEMATIC
DRAWINGS APPROVED [11/19/24].
4/1 6/2
6 9
:57 :54
A M
ELECTRICAL ONE LINE
DIAGRAM - SES-C, 1 OF 2
E5.3.1CD
W hit tin gto n
14904.000 Whittington Baca
X FEEDER SCHEDULE
SHEET KEYNOTES
E501 NAVOPACHE UTILITY METER. METER SHALL BE EQUIPPED
WITH CAPABILITY TO INTERFACE WITH BMS. ELECTRICAL
CONTRACTOR SHALL PROVIDE REQUIRED CONDUIT AND
COMMUNICATION WIRING FROM METER TO POINT OF
INTERFACE WITH BMS.
E502 COMPLIANCE WITH "NEC 240.87 ARC ENERGY REDUCTION"
REQUIRED. REDUCTION METHOD SHALL ALLOW FOR
REQUIRED SELECTIVE DEVICE COORDINATION AND ARC
FLASH REQUIREMENTS. REFER TO ELECTRICAL
SPECIFICATIONS FOR ADDITIONAL INFORMATION.
E505 PROVIDE PERMANENT IDENTIFICATION PLAQUE INDICATING
THE FOLLOWING: ELECTRICAL SERVICE #3 OF 5.
GENERATORS LOCATED IN ELECTRICAL EQUIPMENT YARD,
GENERATOR DISCONNECTS LOCATED IN ADJACENT
ELECTRICAL ROOM IN GMDB. PV DISCONNECT LOCATED AT
END OF THIS ELECTRICAL EQUIPMENT LINEUP.
E521 PROVIDE RELAY PROTECTION ELEMENTS REQUIRED BY
UTILITY AND MULTIPLE GENERATOR AND PV MONITORING
AND CONTROL SYSTEM MANUFACTURER. INTEGRATE SEL
RELAY AND PROGRAMMING INTO MULTIPLE GENERATOR
AND PV MONITORING SYSTEM AND CIRCUIT BREAKER.
PROVIDE AND PROGRAM PROTECTION ELEMENT SET POINTS
AND LOGIC WITHIN THE RELAY. REFER TO SEL-751 DETAIL
FOR ADDITIONAL INFORMATION.
SCALE: NOT TO SCALE1 ONE LINE DIAGRAM - SES-C, 1 OF 2
80 4#3 + 1#8 G, 1 1/4" C A125 4#2/0 + 1#6 G, 2" C
A225 4#300KCMIL + 1#2 G, 2 1/2" C
A300 4#500KCMIL + 1#2 G, 3" C
A400 2 SETS OF 4#250KCMIL + 1#1 G, (2) 2 1/2" C
A1000 3 SETS OF 4#600KCMIL + 1#4/0 G, (3) 3 1/2" C
T45 45KVA TRANSFORMER, 480-208Y/120V, 3PH
PRIMARY FEEDER: 3#3 + 1#8 G, 1 1/4" C
SECONDARY FEEDER: 4#1/0 + 1#6 G, 2" C
BONDING JUMPERS & GROUNDING ELECTRODE
CONDUCTOR: #6
T45V1 45KVA TRANSFORMER, 480-208Y/120V, 3PH
PRIMARY FEEDER: 3#1 + 1#4 G, 1 1/2" C
SECONDARY FEEDER: 4#1/0 + 1#6 G, 2" C
BONDING JUMPERS & GROUNDING ELECTRODE
CONDUCTOR: #6
T75 75KVA TRANSFORMER, 480-208Y/120V, 3PH
PRIMARY FEEDER: 3#1/0 + 1#6 G, 1 1/2" C
SECONDARY FEEDER: 4#4/0 + 1#2 G, 2 1/2" C
BONDING JUMPERS & GROUNDING ELECTRODE
CONDUCTOR: #2
T75V1 75KVA TRANSFORMER, 480-208Y/120V, 3PH
PRIMARY FEEDER: 3#3/0 + 1#4 G, 2" C
SECONDARY FEEDER: 4#4/0 + 1#2 G, 2 1/2" C
BONDING JUMPERS & GROUNDING ELECTRODE
CONDUCTOR: #2
T112 112.5KVA TRANSFORMER, 480-208Y/120V, 3PH
PRIMARY FEEDER: 3#3/0 + 1#6 G, 2" C
SECONDARY FEEDER: 2 SETS OF 4#3/0 + 1#2 G, (2)
2" C
BONDING JUMPERS & GROUNDING ELECTRODE
CONDUCTOR: #2
"A" DENOTES ALUMINUM CONDUCTORS, ALL OTHER CONDUCTORS SHALL BE COPPER
FINAL CONSTRUCTION DOCUMENTS 05MAR26
BID ADDENDUM-A 16APR26
A
/3
EN
L
CB
CPW3CHD
225A
MLO/FTL
SPD
LS
I
5/
CPW3CHE
225A
MLO
SPD
CPW3CHA
150A
MLO
CPW3CLA
125A
MCB
LS
I
0/
CPW3CLB
125A
MCB
CPW3CHB
150A
MLO
CPW3CLC
125A
MCB
LS
I
0/
CPW3CLD
125A
MCB
CPW3CHC
150A
MLO
CPW3CLE
125A
MCB
LS
I
0/
CPW3CLF
125A
MCB
CPW4CHD
125A
MLO
SPD
CPW4CHE
125A
MLO
SPD
CPW4CLA
125A
MCB
CPW4CHA
150A
MLO
CPW4CLB
125A
MCB
CPW4CLD
125A
MCB
CPW4CHB
150A
MLO
CPW4CLC
125A
MCB
CPW4CLF
125A
MCB
CPW4CHC
150A
MLO
CPW4CLE
125A
MCB
LS
IG
/3
EN
L
CC
LS
I
5/
LS
I
5/
LS
I
5/
LS
I
0/
LS
I
5/
LS
I
0/
LS
I
0/
LS
I
5/
LS
I
5/
LS
I
/3
VFD
LS
I
0/
VFD
LS
I
/3
VFD
LS
I
0/
VFD
LS
I
0/
LS
I
5/
/1
IPP2A
10kVA 125A
MCB
IPP2B
10kVA 125A
MCB
P1
IPP2C
10kVA 125A
MCB
/1
/1
P2
/1
P3
/2
IPPLE
25kVA 150A
MCB
LS
IG
0/
EN
L
CD
LS
I
0/
LS
I
0/
CPW3EHA
400A
MLO
CPW4EHA
225A
MLO
CPW3EHB
250A
MLO
CPW4EHB
150A
MLO
LS
I
5/
LS
I
5/
LS
I
5/
BP2 UA2 UB2
LS
I
/3
M
M M M
M M
M M M M M M M M M M M M M
M M M M M
M M M M M M M M
SPD
CPW4ELB
150A
MCB
CPW4ELA
150A
MCB
CPW3ELA
150A
MCB
CPW3ELB
150A
MCB
CPW1EHD
500A
MCB
CPW1EHC
500A
MCB
LS
I
0/
LS
I
0/
M M
LS
I
LS
IG
0/
PVY
M
A.
B.
C.
D.
E.
F.
G.
H.
I.
J.
K.
L.
BASE BUILD SCOPE SHALL ONLY INCLUDE EMPTY CONDUITS
OF FEEDERS SHOWN ON THIS SHEET WITH FEEDER TAGS.
ADD ALTERNATE SCOPE SHALL INCLUDE PV PANELS,
CARPORTS, DC CONDUCTORS, INVERTERS, AC CONDUCTORS,
AC COMBINER BOXES, PV DISTRIBUTION BOARDS.
SEE DRAWING E0.1 FOR ABBREVIATIONS, SYMBOLS, GENERAL
NOTES.
THE CONTRACTOR SHALL COORDINATE EXACT LOCATION OF
EQUIPMENT POWER CONNECTIONS WITH EQUIPMENT
INSTALLER PRIOR TO ROUGH-IN.
COORDINATE FINAL LOCATION OF MECHANICAL EQUIPMENT
AND ASSOCIATED DISCONNECT SWITCHES, STARTERS, VFDS,
CONTROL POWER AND OTHER POWER REQUIREMENTS WITH
DIV 23 AND MECHANICAL DRAWINGS.
SEE MECHANICAL EQUIPMENT SCHEDULE FOR ASSOCIATED
OVERCURRENT DEVICES, DISCONNECT SWITCHES, STARTERS
AND WIRES.
VOLTAGE DROP SHALL BE LIMITED TO LESS THAN 3% FOR ALL
BRANCH CIRCUITS AND 2% FOR ALL FEEDERS.
CONTRACTOR SHALL COORDINATE AND FIELD VERIFY
REQUIREMENT OF NEUTRAL CONDUCTOR FOR ALL EQUIPMENT
AND PROVIDE NEUTRAL CONDUCTOR AS NECESSARY.
ALL LIFE SAFETY AND LIGHTING PANELBOARDS SHALL BE
EQUIPPED WITH TYPE 2 SPD.
ALL AUTOMATIC TRANSFER SWITCHES SHALL BE 4 POLE AND
EQUIPPED WITH BYPASS ISOLATION.
ALL UTILITY TRANSFORMERS DESCRIBED AS NAVOPACHE
TRANSFORMER TO BE COORDINATED WITH UTILITY AND
PROVIDED BY UTILITY. COORDINATE ALL FINAL REQUIREMENTS
AND AVAILABLE FAULT CURRENT CONTRIBUTIONS BASED ON
SUPPLIED EQUIPMENT. BASIS OF DESIGN 2500KVA, AND 5%Z.
ELECTRICAL EQUIPMENT SHALL BE CONFIGURED AS FOLLOWS:
-SERVICE ENTRANCE SECTIONS - UL891 REAR CONNECTED
SWITCHBOARD
-DISTRIBUTION SWITCHBOARDS WITH DRAWOUT CIRCUIT
BREAKERS - UL891 REAR CONNECTED SWITCHBOARD
-GENERATOR PARALLELING GEAR - UL1558 SWITCHGEAR
GENERAL SHEET NOTES
CRITICAL
CDM2CH
1000A
480-277V
3PH/4W
ATS-CCA
1000A
4P
LTG
TCPW3CLA/B
75kVA
PWR PWR PWR
EQUIPMENT
CDM2EHA
1600A
480-277V
3PH/4W
ATS-CEA
1600A
4P
PWR
TCPW3CLC/D
75kVA
PWR
TCPW3CLE/F
75kVA
PWR
TCPW4CLA/B
75kVA
TCPW4CLC/D
75kVA
TCPW4CLE/F
75kVA
PWR PWR PWR PWRPWR PWR
A1000
A1000
A1600
A1600
A150 T75D
T75D
A150 A150 T75D
T75D
A150 A150 T75D
T75D
A150 A225
A225
A125 A125
1000-3
ACCH-3
CHWP-3
100-3
HHWP-3
30-3
CBWP-3
100-3
EWH-3
OR PWR
FESS-1
80kVA
INPUT
OUTPUT
CDSUR1
400A 480V
3PH/4W
50-2
SUR-2268
50-2 50-2 50-2 80-2
OR LASER
EQUIPMENT
IPP3B
SUR-2267
225-3
EQUIPMENT
CDM2EHB
600A
480-277V
3PH/4W
ATS-CEB
600A
4P
A600
A600
A250A300
A225 A150
IPP1B
SUR-2272
225V1 225V1 225V1
UPS B2
INPUT
UPS A2/B2
BYPASS
UPS A2
INPUT
1000-3
NON-COINCIDENT
LOAD
B-3
SC3
DC22 DC18 DC19
SC4 SC5
DC7 DC8 DC9 DC10 DC11 DC12 DC13 DC14 DC15 DC20 DC21
DC16 DC17
DC23 DC24 DC25 DC26 DC27
DC28 DC29 DC30 DC31 DC32 DC33 DC34 DC35
MATCHLINE
MATCHLINE
TCPW4ELB
45kVA
T45
TCPW4ELA
45kVA
T45
TCPW4ELA
45kVA
T45
TCPW3ELB
45kVA
T45
300-3
TCPW1EHD
150kVA K-13
ISO XFMR
TCPW1EHC
150kVA K-13
ISO XFMR
IMAGING IMAGING
T150NT150N
DC36 DC37
PV C
, E O
E519
SC6
LEVEL 1
LEVEL 2
LEVEL 2
LEVEL 3
LEVEL 3
LEVEL 4
LEVEL 4
ROOF
E530
A
SHEET NUMBER
PROJECT NUMBER
SEALS AND SIGNATURES
ISSUED FOR DATE
Pl ot
Da te:
IHS Whiteriver Hospital 200 W Hospital Drive Whiteriver, Arizona, 85941
IHS Project #: 131445 IHS Contract #: 75H70123R00008 IHS Award Date: 02/02/2024
455 NORTH THIRD STREET
SUITE 250
PHOENIX, AZ 85004
602.265.2200 smithgroup.com
Drawn By: Checked By:
BASED ON PROGRAM OF REQUIREMENTS DATED [ 03/26/22],
POR AMENDMENT DATED [ 02/03/25], AND ON SCHEMATIC
DRAWINGS APPROVED [11/19/24].
4/1 6/2
6 9
:58 :00
A M
ELECTRICAL ONE LINE
DIAGRAM - SES-C, 2 OF 2
E5.3.2CD
W hit tin gto n
14904.000 Whittington Baca
X FEEDER SCHEDULE
SHEET KEYNOTES
E519 PV CIRCUIT BREAKER SHALL BE LOCATED AT LAST BUSSED
SPACE. PROVIDE PERMANENT IDENTIFICATION PLAQUE
INDICATING THE FOLLOWING: PV POWER SOURCE - DO NOT
RELOCATE THIS CIRCUIT BREAKER
E530 PROVIDE SHUNT TRIP CIRCUIT BREAKER FOR INTERFACE
WITH BOILER EMERGENCY SHUTDOWN EPO SWITCHES.
REFER TO EMP2.2.G FOR ADDITIONAL INFORMATION.
30-3 3#10 + 1#10 G, 3/4" C 50-2 2#6 + 1#10 G, 3/4" C 80-2 2#3 + 1#8 G, 1 1/4" C 100-3 3#1 + 1#8 G, 1 1/2" C 225-3 3#4/0 + 1#4 G, 2" C
225V1 4#250KCMIL + 1#3 G, 2 1/2" C
300-3 3#350KCMIL + 1#4 G, 3" C
400 2 SETS OF 4#3/0 + 1#3 G, (2) 2" C
1000-3 3 SETS OF 3#400KCMIL + 1#2/0 G, (3) 3" C
A125 4#2/0 + 1#6 G, 2" C A150 4#3/0 + 1#4 G, 2" C
A225 4#300KCMIL + 1#2 G, 2 1/2" C
A250 4#350KCMIL + 1#2 G, 2 1/2" C
A300 4#500KCMIL + 1#2 G, 3" C
A600 2 SETS OF 4#500KCMIL + 1#2/0 G, (2) 3" C
A1000 3 SETS OF 4#600KCMIL + 1#4/0 G, (3) 3 1/2" C
A1600 5 SETS OF 4#600KCMIL + 1#350KCMIL G, (5) 3 1/2" C
T45 45KVA TRANSFORMER, 480-208Y/120V, 3PH
PRIMARY FEEDER: 3#3 + 1#8 G, 1 1/4" C
SECONDARY FEEDER: 4#1/0 + 1#6 G, 2" C
BONDING JUMPERS & GROUNDING ELECTRODE
CONDUCTOR: #6
T75D 75KVA TRANSFORMER, 480-208Y/120V, 3PH
PRIMARY FEEDER: 3#1/0 + 1#6 G, 1 1/2" C
SECONDARY FEEDERS: 4#1/0 + 1#2 G, 2" C TO
EACH PANEL
BONDING JUMPERS & GROUNDING ELECTRODE
CONDUCTOR: #2
T150N 150KVA TRANSFORMER, 480-208Y/120V, 3PH
PRIMARY FEEDER: 3#250KCMIL + 1#4 G, 2 1/2" C
SECONDARY FEEDER: 2 SETS OF 3#250KCMIL,
1#500KCMIL N + 1/0 G, (2) 3" C
BONDING JUMPERS & GROUNDING ELECTRODE
CONDUCTOR: #1/0
SCALE: NOT TO SCALE1 ONE LINE DIAGRAM - SES-C, 2 OF 2
"A" DENOTES ALUMINUM CONDUCTORS, ALL OTHER CONDUCTORS SHALL BE COPPER
FINAL CONSTRUCTION DOCUMENTS 05MAR26
BID ADDENDUM-A 16APR26
A
A
0/
EN
L
DA
DPE1LHA
60A
MLO
SPD
DPE1LLA
60A
MLO
SPD
DPE2LHA
80A
MLO
SPD
DPE2LLA
60A
MCB
SPD
DPE3LHA
225A
MLO
SPD
DPE3LLA
60A
MCB
SPD
DPE4LHA
60A
MLO
SPD
DPE4LLA
60A
MLO
SPD
LSIG
2500/3
LS
IG
/3
EN
L
DB
DPE3SHC
225A
FTL
SPD
LS
I
5/
DPE3SHD
225A
MLO
SPD
DPE3SHA
300A
FTL
DPE3SLA
400A
MCB/FTL
LS
I
0/
DPE3SLB
400A
MLO
DPE3SHB
300A
FTL
DPE3SLC
400A
MCB/FTL
LS
I
0/
DPE3SLD
400A
MLO
DPE4SHC
125A
MLO
SPD
DPE4SHD
125A
MLO
SPD
DPE4SLA
400A
MCB/FTL
DPE4SHA
300A
MLO
DPE4SLB
400A
MLO
DPE4SLC
400A
MCB/FTL
DPE4SHB
300A
MLO
DPE4SLD
400A
MLO
LS
IG
/3
M
M M
M M M
DPF2LHA
200A
MLO
SPD
0/
DPF2LLA
100A
MCB
SPD
5/
SPD
A.
B.
C.
D.
E.
F.
G.
H.
I.
J.
K.
L.
BASE BUILD SCOPE SHALL ONLY INCLUDE EMPTY CONDUITS
OF FEEDERS SHOWN ON THIS SHEET WITH FEEDER TAGS.
ADD ALTERNATE SCOPE SHALL INCLUDE PV PANELS,
CARPORTS, DC CONDUCTORS, INVERTERS, AC CONDUCTORS,
AC COMBINER BOXES, PV DISTRIBUTION BOARDS.
SEE DRAWING E0.1 FOR ABBREVIATIONS, SYMBOLS, GENERAL
NOTES.
THE CONTRACTOR SHALL COORDINATE EXACT LOCATION OF
EQUIPMENT POWER CONNECTIONS WITH EQUIPMENT
INSTALLER PRIOR TO ROUGH-IN.
COORDINATE FINAL LOCATION OF MECHANICAL EQUIPMENT
AND ASSOCIATED DISCONNECT SWITCHES, STARTERS, VFDS,
CONTROL POWER AND OTHER POWER REQUIREMENTS WITH
DIV 23 AND MECHANICAL DRAWINGS.
SEE MECHANICAL EQUIPMENT SCHEDULE FOR ASSOCIATED
OVERCURRENT DEVICES, DISCONNECT SWITCHES, STARTERS
AND WIRES.
VOLTAGE DROP SHALL BE LIMITED TO LESS THAN 3% FOR ALL
BRANCH CIRCUITS AND 2% FOR ALL FEEDERS.
CONTRACTOR SHALL COORDINATE AND FIELD VERIFY
REQUIREMENT OF NEUTRAL CONDUCTOR FOR ALL EQUIPMENT
AND PROVIDE NEUTRAL CONDUCTOR AS NECESSARY.
ALL LIFE SAFETY AND LIGHTING PANELBOARDS SHALL BE
EQUIPPED WITH TYPE 2 SPD.
ALL AUTOMATIC TRANSFER SWITCHES SHALL BE 4 POLE AND
EQUIPPED WITH BYPASS ISOLATION.
ALL UTILITY TRANSFORMERS DESCRIBED AS NAVOPACHE
TRANSFORMER TO BE COORDINATED WITH UTILITY AND
PROVIDED BY UTILITY. COORDINATE ALL FINAL REQUIREMENTS
AND AVAILABLE FAULT CURRENT CONTRIBUTIONS BASED ON
SUPPLIED EQUIPMENT. BASIS OF DESIGN 2500KVA, AND 5%Z.
ELECTRICAL EQUIPMENT SHALL BE CONFIGURED AS FOLLOWS:
-SERVICE ENTRANCE SECTIONS - UL891 REAR CONNECTED
SWITCHBOARD
-DISTRIBUTION SWITCHBOARDS WITH DRAWOUT CIRCUIT
BREAKERS - UL891 REAR CONNECTED SWITCHBOARD
-GENERATOR PARALLELING GEAR - UL1558 SWITCHGEAR
GENERAL SHEET NOTES
LIFE
SAFETY
ATS-DLA
400A
4P
TDPE2LLA
15kVA
OPTIONAL
STANDBYE506
E502
M
NAVOPACHE
TRANSFORMER
DDM2SH
1000A
480-277V
3PH/4W
LEVEL 1
LEVEL 2
LEVEL 2
LEVEL 3
LEVEL 3
LEVEL 4
ATS-DSA
1000A
4P
LTG
TDPE3SLA/B
112.5kVA
PWR
TDPE3SLC/D
112.5kVA
PWR
ATS-DCA
1000A
4P
LEVEL 4
ROOF
A400
T15
A225V2
A1000
A1000 A1000
A400
A400
T112
A300V1
A300
A400
A400
T112
A300V2 A225V1
A225
A125 A1256060
E501
MAIN
SD1
SD2 SD3
DD1 DD2 DD3
MATCHLINE
MATCHLINE
TDPF2LLA
30kVA
T30
FAC BLDG
A200
A200
DDM2LH
400A 480-277V
3PH/4W
A400
A300
TDPE4SLA/B
112.5kVA
T112
#2
DPF2LHA
200A/200AF
TDPE3LLA
15kVA
T15
TDPE4SLC/D
112.5kVA
T112
SES-D
3200A BUS
PER NEC 705.12(B)
480-277V/3PH/4W (3)
E521
SEL-751
(3)(3)
A
SHEET NUMBER
PROJECT NUMBER
SEALS AND SIGNATURES
ISSUED FOR DATE
Pl ot
Da te:
IHS Whiteriver Hospital 200 W Hospital Drive Whiteriver, Arizona, 85941
IHS Project #: 131445 IHS Contract #: 75H70123R00008 IHS Award Date: 02/02/2024
455 NORTH THIRD STREET
SUITE 250
PHOENIX, AZ 85004
602.265.2200 smithgroup.com
Drawn By: Checked By:
BASED ON PROGRAM OF REQUIREMENTS DATED [ 03/26/22],
POR AMENDMENT DATED [ 02/03/25], AND ON SCHEMATIC
DRAWINGS APPROVED [11/19/24].
4/1 6/2
6 9
:58 :05
A M
ELECTRICAL ONE LINE
DIAGRAM - SES-D, 1 OF 2
E5.4.1CD
W hit tin gto n
14904.000 Whittington Baca
X FEEDER SCHEDULE
SHEET KEYNOTES
E501 NAVOPACHE UTILITY METER. METER SHALL BE EQUIPPED
WITH CAPABILITY TO INTERFACE WITH BMS. ELECTRICAL
CONTRACTOR SHALL PROVIDE REQUIRED CONDUIT AND
COMMUNICATION WIRING FROM METER TO POINT OF
INTERFACE WITH BMS.
E502 COMPLIANCE WITH "NEC 240.87 ARC ENERGY REDUCTION"
REQUIRED. REDUCTION METHOD SHALL ALLOW FOR
REQUIRED SELECTIVE DEVICE COORDINATION AND ARC
FLASH REQUIREMENTS. REFER TO ELECTRICAL
SPECIFICATIONS FOR ADDITIONAL INFORMATION.
E506 PROVIDE PERMANENT IDENTIFICATION PLAQUE INDICATING
THE FOLLOWING: ELECTRICAL SERVICE #4 OF 5.
GENERATORS LOCATED IN ELECTRICAL EQUIPMENT YARD,
GENERATOR DISCONNECTS LOCATED IN ADJACENT
ELECTRICAL ROOM IN GMDB. PV DISCONNECT LOCATED AT
END OF THIS ELECTRICAL EQUIPMENT LINEUP.
E521 PROVIDE RELAY PROTECTION ELEMENTS REQUIRED BY
UTILITY AND MULTIPLE GENERATOR AND PV MONITORING
AND CONTROL SYSTEM MANUFACTURER. INTEGRATE SEL
RELAY AND PROGRAMMING INTO MULTIPLE GENERATOR
AND PV MONITORING SYSTEM AND CIRCUIT BREAKER.
PROVIDE AND PROGRAM PROTECTION ELEMENT SET POINTS
AND LOGIC WITHIN THE RELAY. REFER TO SEL-751 DETAIL
FOR ADDITIONAL INFORMATION.
SCALE: NOT TO SCALE1 ONE LINE…