A2-1f BP1_DWG2026-0416_15_ELECTRICAL_IHS-Whiteriver-Hospital_BID-ADD-A.pdf

PDF 8 MB Posted

Attached to
Whiteriver Hospital Construction
Solicitation number
75H70126R00016
Issued by

About this file

This document is a comprehensive electrical design drawing set for the IHS Whiteriver Hospital project located in Whiteriver, Arizona. The project is identified as IHS Project #131445 under IHS Contract #75H70123R00008, with an award date of February 2, 2024. The drawings are based on a Program of Requirements dated March 26, 2022, with amendments dated February 3, 2025, and schematic approvals dated November 19, 2024.

The electrical design encompasses multiple building systems including HVAC mechanical equipment distribution, power distribution across five electrical service areas (labeled A through E), uninterruptible power supply (UPS) configuration, and an alternate scope solar photovoltaic (PV) system with carports. Key electrical infrastructure includes five main switchboards and distribution panels, automatic transfer switches rated at 4-pole with bypass isolation, transformers (primarily 45kVA and 75-112.5kVA units), variable frequency drives (VFDs) for mechanical equipment, and surge protection devices on all life safety and lighting panelboards. The design specifies copper conductors, minimum #10 AWG branch circuit wiring, dedicated neutral conductors, voltage drop limitations of 3% for branch circuits and 2% for feeders, and compliance with UL891 standards for switchboards and UL1558 for generator paralleling gear. Mechanical systems are distributed across five zones with associated boilers (B-1 through B-5), air-cooled chillers (ACCH-1 through ACCH-3), heat pumps, and circulation pumps. The alternate scope solar PV system includes 625 kilowatts of capacity across six carports with multiple 62.5kW inverters, string combiner boxes, and DC/AC conductor routing to integration points within the main electrical distribution system.

View the file

Other files

File Type Posted
A10-1b 0_SPEC2026-0618_Specifications_IHS-Whiteriver-Hospital_BID-ADD-H.pdf PDF
A10-1f BP1_DWG2026-0618_16_ICT_IHS-Whiteriver-Hospital_BID-ADD-H.pdf PDF
A10-1d BP1_DWG2026-0618_08_ARCHITECTURAL_IHS-Whiteriver-Hospital_BID-ADD-H.pdf PDF
A10-3a Attachment J12a AZ FORM 5000HC_TPT HEALTHCARE EXEMPTION CERTIFICATE.pdf PDF
A10-1c BP1_DWG2026-0618_06_LANDSCAPE_IHS-Whiteriver-Hospital_BID-ADD-H.pdf PDF
A10-1i BP2_DWG2026-0618_08_ARCHITECTURAL_IHS-Whiteriver-WWTP_BID-ADD-H.PDF PDF
A10-1a 0_MEM2026-0618_IHS-Whiteriver-Hospital_BID-Addendum-H.pdf PDF
A10-4 WR Pre-Proposal_RFIs 001 - 163.xlsx XLSX spreadsheet
Amend10 - WR Construction - 24 Jun 2026.pdf PDF
A10-1h BP2_DWG2026-0618_05_CIVIL_IHS-Whiteriver-UC_BID-ADD-H.pdf PDF
A10-1e BP1_DWG2026-0618_15_ELECTRICAL_IHS-Whiteriver-Hospital_BID-H.pdf PDF
A10-5 For RFI 154 - Geotech Reports.pdf PDF
A10-1g BP1_EXH2026-0618_10_MED-EQUIP_IHS-Whiteriver-Hospital_BID-ADD-H.pdf PDF
A10-3 Attachment J12 AZ State Tax Exemption Letter- Phoenix Area IHS.pdf PDF
A10-2 Section B.pdf PDF
A10-1j BP3_DWG2026-0618_05_CIVIL_IHS-Hon-Dah-UC_BID-ADD-H.pdf PDF
A9-1a MEM2026-0612_IHS-Whiteriver-Hospital_BID-Addendum-G.pdf PDF
A9-2 WR Pre-Proposal_RFIs 001 - 163.xlsx XLSX spreadsheet
A9-1b BP1_DWG2026-0612_15_ELECTRICAL_IHS-Whiteriver-Hospital_BID-ADD-G.pdf PDF
Amend9 - WR Construction - 17 Jun 2026.pdf PDF
A8-1a 0_MEM2026-0609_IHS-Whiteriver-Hospital_BID-Addendum-F.pdf PDF
A8-1e BP1_DWG2026-0609_16_ICT_IHS-Whiteriver-Hospital_BID-ADD-F.pdf PDF
A8-1b 0_SPEC2026-0609_Specifications_IHS-Whiteriver-Hospital_BID-ADD-F.pdf PDF
A8-2 Section B.pdf PDF
Amend8 - WR Construction - 11 Jun 2026.pdf PDF
A8-1d BP1_DWG2026-0609_08_ARCHITECTURAL_IHS-Whiteriver-Hospital_BID-ADD-F.pdf PDF
A8-3 WR Pre-Proposal_RFIs 001 - 132.xlsx XLSX spreadsheet
A8-1c BP1_DWG2026-0609_06_LANDSCAPE_IHS-Whiteriver-Hospital_BID-ADD-F.pdf PDF
A7-1h BP4_DWG2026-0528_16_ICT_IHS-Whiteriver-Pump-House_BID-ADD-E.pdf PDF
A7-1c BP1_DWG2026-0528_08_ARCHITECTURAL_IHS-Whiteriver-Hospital_BID-ADD-E.pdf PDF
A7-1a 0_MEM2026-0528_IHS-Whiteriver-Hospital_BID-Addendum-E.pdf PDF
A7-2b Contact list Service Unit - RFI 109.xlsx XLSX spreadsheet
A7-1d BP1_DWG2026-0528_15_ELECTRICAL_IHS-Whiteriver-Hospital_BID-ADD-E.pdf PDF
A7-1g BP3_DWG2026-0528_16_ICT_IHS-Hondah-WWTP_BID-ADD-E.pdf PDF
A7-1f BP2_DWG2026-0528_16_ICT_IHS-Whiteriver-WWTP_BID-ADD-E.pdf PDF
A7-1e BP1_DWG2026-0528_16_ICT_IHS-Whiteriver-Hospital_BID-ADD-E.pdf PDF
A7-3 WR Standard Form 1442.pdf PDF
Amend7 - WR Construction - 29 May 2026.pdf PDF
A7-1b 00_SPEC2026-0528_Specifications_IHS-Whiteriver-Hospital_BID-ADD-E.pdf PDF
A7-2a WR Pre-Proposal_RFIs 001 - 121.xlsx XLSX spreadsheet
A6-1c BP1_DWG2026-0520_05_CIVIL_IHS-Whiteriver-ADOT-PLANS_BID-ADD-D.pdf PDF
A6-1a 0_MEM2026-0520_IHS-Whiteriver-Hospital_BID-Addendum-D.pdf PDF
A6-3b Attachment J06b - Highway AZ20260033 rev-0518.pdf PDF
A6-1e BP1_DWG2026-0520_08_ARCHITECTURAL_IHS-Whiteriver-Hospital_BID-ADD-D.pdf PDF
A6-1b SPEC2026-0520_Specifications_IHS-Whiteriver-Hospital_BID-ADD-D.pdf PDF
A6-3c Attachment J06c - Heavy AZ20260054 rev-0518.pdf PDF
A6-2 WR Pre-Proposal_RFIs 001 - 121.xlsx XLSX spreadsheet
A6-1d BP1_DWG2026-0521_06_LANDSCAPE_IHS-Whiteriver-Hospital_BID-ADD-D.pdf PDF
A6-3a Attachment J06a - Building AZ20260027 rev-0518.pdf PDF
A6-1f BP1_DWG2026-0520_16_ICT_IHS-Whiteriver-Hospital_BID-ADD-D.pdf PDF
Show 40 more

Latest 50 of 107 listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

M

M

M

M

M

J

M

M

M

M

J

J

J

J

J

J

M

L

M

N

O

P

Q

R

10 11 12 13

14 15 16 17 18

S

MAP-2-02

EWH-9

CP-5

WT-3

AAP-2-03

FCU-2188

CUH-2PCS

CUH-2PCM

CRAC-2153

CRAC-2045

FCU-2046

CUH-2019

CUH-2PCN

CUH-2040

FCU-2034

CRAC-2200

FCU-2029

FSD

FSD

FSD

FSD

E247

APW2LLA- 35

FSD-2-E1

APW2LLA- 37

FSD-2-C1

E247

TYP

E248

BPE2EHA- 17

BPE2EHA- 15

BPE2EHA- 13VAV-2-C1

VAV-2-C2

VAV-2-C3

CORRIDOR

COR-2038

CORRIDOR

COR-2048

WATER TRMT

PUB-2055

STAFF LOCKERS

MSP-2367

STAIR 2

STR-2020

EVS

EVS-2243

SOILED WORKROOM

SUR-2244

ELEVATOR LOBBY

ELV-2033

CORRIDOR

COR-2047

CORRIDOR

COR-2019

SHAFT

SHF-2043

OFFICE, CLINICAL ENGINEERING

CLE-2230

SHOP

CLE-2229

STORAGE, PARTS

CLE-2229C

STORAGE, DIALYSIS

CLE-2227

DIALYSIS WORKROOM

CLE-2226

WORKSTATION, TECH

CLE-2229A

CONFERENCE, SMALL

TCC-2196

QUIET ROOM

EFS-2148

ALCOVE, NOURISHMENT

TCC-2192

STAFF ENTRY VESTIBULE

VST-2039

CONFERENCE, TRAINING

TCC-2193

CONFERENCE, MEDIUM

TCC-2194

ELEVATOR VESTIBULE

ELV-2027

CORRIDOR

COR-2019

WAITING

PFS-2236B

PREP/PACU STAGE 1

SUR-2240

PREP/PACU STAGE 1

SUR-2239

PREP/PACU STAGE 1

SUR-2241

EVS

EVS-2365

SOILED INTAKE

MSP-2366

PREP/PACU STAGE 1

SUR-2242

TOILET, STAFF

OEH-2210A

WAITING

OEH-2210

HUDDLE ROOM

OEH-2214

DRAFTING AREA

OEH-2214A

OFFICE, EH SUPERVISOR

OEH-2219

WORKSTATION, EH OFF

OEH-2220

WORKSTATION, GIS

OEH-2215

OFFICE, ENG SUPERVISOR

OEH-2218

WORKSTATION, ENG

OEH-2216

WORKSTATION, ENG TECH

OEH-2217

ALCOVE, STAFF NOURISHMENT

OEH-2213

WORKSTATION, FLEX

OEH-2211B

RECEPTION

OEH-2212

PLUMBING CHASE

PUB-2235

LACTATION/WELLNESS

EFS-2149

ALCOVE, LOCKERS

ITS-2199A

WORKROOM

ITS-2200

OFFICE, CHIEF INFORMATION OFFICER

ITS-2206

OFFICE, DEPUTY CIO

ITS-2203

OFFICE, INFO SYSTEM SEC

ITS-2205

OFFICE, SHARED, SYSTEMS ADMIN

ITS-2209

OFFICE, SHARED, NETWORK SERV STAFF

ITS-2207

EQUIPMENT STORAGE

ITS-2202

UNIT SUPPLY & FILING

ITS-2208

DECOMMISSION STORAGE

ITS-2204

OFFICE, RMSTP

OEH-2226

STORAGE, RMSTP

OEH-2225

ALCOVE, PLOTTER

OEH-2211A

OFFICE, DIRECTOR

SEC-2143

OFFICE, ASSISTANT DIRECTOR

SEC-2145

WORK AREA

SEC-2147

CONTROL ROOM

SEC-2146

ALCOVE, STAFF NOURISHMENT

SEC-2142A

EQUIPMENT STORAGE

SEC-2147A

LOST & FOUND STORAGE

EFS-2150

WORKSTATIONS

FAC-2160

WORKSTATIONS

FAC-2158

ADMIN SUPPORT

FAC-2157

TOILET/SHOWER, STAFF

CUP-2368A

MAINTENANCE SHOP

FAC-2151

OFFICE, FOREMAN

FAC-2162

OFFICE, GEN ENGINEERING

FAC-2161

STORAGE

FAC-2165

CORRIDOR

FAC-2159

CORRIDOR

SEC-2142B

OFFICE, SHARED

ITS-2201

CONFERENCE, SMALL

TCC-2195

CORRIDOR

FAC-2154

UPS

UPS-2029

STORAGE, BEDS

CLE-2232

TOILET, STAFF

FAC-2152A

EVS

EVS-2197

STORAGE, SIM LAB

LAB-2191A

SIM LAB

LAB-2191

SIM LAB MONITORING

LAB-2190

PUBLIC TOILET, FEMALE

PFS-2234

PUBLIC TOILET, MALE

PFS-2233

CSPD WATER

PUB-2056

CORRIDOR

ITS-2199

CORRIDOR

OEH-2211

CONTROL STATION

SUR-2247

ALCOVE, SCALE

SUR-2248

MED PREP

SUR-2238C

PTS

COR-2065A

ANESTHESIA WORK

SUR-2245

STERILE SUPPLY STORAGE

SUR-2281

OR

SUR-2267

ALCOVE, CRASH CART

SUR-2249

SHAFT

SHF-2050

PICKUP/DROP OFF

MSP-2359

OFFICE, SUPERVISOR

MSP-2355

TOILET/SHOWER, STAFF

MSP-2367A

HIGH LEVEL DISINFECTION

MSP-2357

EVS

EVS-2361

SUPPLY BREAKDOWN

MSP-2354

CASE CART STORAGE

MSP-2353C

CASE CART COMPLETION

MSP-2353D

CORRIDOR

COR-2066

OR

SUR-2268

CORRIDOR

COR-2052

ALCOVE, GURNEY

SUR-2266

ALCOVE, PPE

SUR-2246

IDF

IDF-2045

ELECTRICAL

ELC-2046

ELECTRICAL

ELC-2034

CORRIDOR

COR-2049

PUBLIC ELEV 3A

ELV-2023A

ELEVATOR VESTIBULE

ELV-2022

PUBLIC ELEV 4B

ELV-2028B

STAIR 3

STR-2030

VESTIBULE

VST-2040

CORRIDOR

COR-2032

WORKROOM

SEC-2144

OFFICE, SUPERVISOR

FAC-2163

EQUIPMENT STORAGE

CLE-2231

WORKSTATION, TECH

CLE-2229B

CORRIDOR

CLE-2228

WORKSTATION, EH TECH

OEH-2221

WORKSTATIONS

CUP-2369C

CORRIDOR

CUP-2369

STORAGE

FAC-2164

STORAGE

FAC-2166

ALCOVE, STAFF NOURISHMENT

FAC-2155

PUBLIC ELEV 4A

ELV-2028A

PUBLIC ELEV 3B

ELV-2023B

STORAGE

OEH-2224

EVS

EVS-2222

CORRIDOR

COR-2051

DAS

FAC-2153

WORKROOM, DECONTAM

MSP-2364

HIGH LEVEL DISINFECTION

MSP-2358

WAITING

PFS-2236A

EMPLOYEE LOCKER, FEMALE

EFS-2176

STAFF LOUNGE

EFS-2189

LACTATION/WELLNESS

EFS-2168

EXERCISE CENTER

EFS-2188

TOILETS, FEMALE

EFS-2172

CIRCULATION

EFS-2171

SINKS

EFS-2171A

SHW ROOM

EFS-2173 ACC SHW ROOM

EFS-2175

EVS

EVS-2169

SHAFT

SHF-2044

STAFF LOCKERS

FAC-2152

WORKSTATION, TECH

COR-1002B

WORKSTATION, TECH

COR-1002C

DETERGENT/RODI

COR-2085

CART WASH

COR-1002G

STORAGE, FILES

FAC-2156

SECURITY STATION

PFS-2236C

ALCOVE, LOCKERS

OEH-2211C

GURNEY STORAGE

SUR-2268B

ALCOVE, SCRUB

SUR-2267A

CORRIDOR

CLE-2233NOURISHMENT ALCOVE

CLE-2234

CORRIDOR

COR-2064

CIRCULATION

EFS-2170

SHW ROOM

EFS-2174

CIRCULATION

EFS-2177

SINKS

EFS-2191

ALCOVE

EFS-2192

TOILETS, MALE

EFS-2193

SHW ROOM

EFS-2194

SHW ROOM

EFS-2195

ACC SHW ROOM

EFS-2196

EMPLOYEE LOCKER, MALE

EFS-2198

PTS

SCC-4256

FREIGHT ELEV 5

ELV-2035

MV-5

WM-IHW-1

WM-ICW-1

WM-RODI-1

EP2ELA- 33

E280

EP2ELA- 33

A

A.

B.

C.

D.

E.

F.

G.

H.

I.

J.

K.

L.

M.

N.

O.

P.

Q.

R.

S.

T.

SEE DRAWING E0.1 FOR ABBREVIATIONS, SYMBOLS, GENERAL

NOTES AND DEVICE MOUNTING HEIGHT OF WALL MOUNTED

DEVICES, UON.

ALL BRANCH CIRCUIT WIRING SHALL BE A MINIMUM SIZE OF #10

AWG. REFER TO SHEET E0.2 FOR ADDITIONAL SIZING

INFORMATION.

THE CONTRACTOR SHALL COORDINATE EXACT LOCATION OF

EQUIPMENT POWER CONNECTIONS WITH EQUIPMENT

INSTALLER PRIOR TO ROUGH-IN.

SEE MECHANICAL EQUIPMENT SCHEDULE FOR ASSOCIATED

OVERCURRENT DEVICES, DISCONNECT SWITCHES, STARTERS

AND WIRES.

CONTRACTOR SHALL COORDINATE AND FIELD VERIFY

REQUIREMENT OF NEUTRAL CONDUCTOR FOR ALL EQUIPMENT

AND PROVIDE NEUTRAL CONDUCTOR AS NECESSARY.

ALL CIRCUITS SHALL BE EQUIPPED WITH A DEDICATED

NEUTRAL CONDUCTOR, UNLESS NOTED OTHERWISE.

ALL CONDUCTORS SHALL BE COPPER, UNLESS NOTED OR

SCHEDULED OTHERWISE.

TRIPPING OF GFCI RECEPTACLES SHALL NOT AFFECT THE

DOWNSTREAM RECEPTACLES.

NO MORE THAN 3 CIRCUITS MAY SHARE A HOMERUN.

FOR ALL MECHANICAL EQUIPMENT, PROVIDE ADDITIONAL 120V

CONNECTIONS REQUIRED BY MANUFACTURER.

FOR EACH AIR HANDLING UNIT, PROVIDE (1)120V CONNECTION

FOR LIGHTING AND RECEPTACLES. CIRCUIT TO MECHANICAL

PANEL WITHIN THE SPACE.

PROVIDE 120V CIRCUITS FOR CONTROL PANELS AS REQUIRED

BY CONTROL VENDOR. CIRCUIT TO MECHANICAL PANEL WITHIN

THE SPACE.

ALL UNUSED WALL OUTLETS TO BE COVERED WITH BLANK

PLATE. ALL BLANK PLATE COLORS TO MATCH WALL COLOR.

REFER TO 'T' SERIES PLANS FOR LOW VOLTAGE BACK BOX AND

RACEWAY REQUIREMENTS.

ALL CONDUIT ROUTED WITHIN SLAB SHALL COMPLY WITH

GUIDELINES LISTED IN STRUCTURAL DRAWINGS.

COORDINATE FINAL LOCATION OF MECHANICAL AND PLUMBING

EQUIPMENT AND ASSOCIATED DISCONNECT SWITCHES,

STARTERS, VFDS, CONTROL POWER AND OTHER POWER

REQUIREMENTS WITH DIV 22 AND 23.

CONTRACTOR IS RESPONSIBLE FOR ALL WIRING FROM VFDs

AND DISCONNECTS SHOWN IN DRAWINGS TO THE EQUIPMENT

AND IS TO COORDINATE WITH EQUIPMENT MANUFACTURER

AND INSTALLATION INSTRUCTIONS.

CONTRACTOR SHALL PROVIDE VFD CABLE FOR LINE AND LOAD

SIDE VFD CONNECTIONS.

CONTRACTOR SHALL PROVIDE RUN PERMISSIVE INTERLOCK

BETWEEN VFD AND LOAD SIDE EQUIPMENT DISCONNECT

SWITCH. DISCONNECT SWITCH SHALL BE EQUIPPED WITH

AUXILIARY CONTACT.

CHILLED BEAM MECHANICAL EQUIPMENT DOES NOT REQUIRE

POWER SOURCE CIRCUITING. SHOWN FOR REFERENCE ONLY.

EXTEND LINE SIDE OF NEAREST 120V GENERAL RECEPTACLE

POWER CIRCUIT TO ELECTRONIC PLUMBING VALVES.

COORDINATE ELECTRONIC PLUMBING VALVE INFRASTRUCTURE

REQUIREMENTS AND LOCATION WITH PLUMBING CONTRACTOR

AND EQUIPMENT MANUFACTURER PRIOR TO COMMENCING

WORK. INSTALL PER EQUIPMENT MANUFACTURERS

SPECIFICATIONS.

GENERAL SHEET NOTES

NORTH

SHEET NUMBER

PROJECT NUMBER

KEYPLAN

SEALS AND SIGNATURES

ISSUED FOR DATE

Pl ot

Da te:

C

IHS Whiteriver Hospital 200 W Hospital Drive Whiteriver, Arizona, 85941

IHS Project #: 131445 IHS Contract #: 75H70123R00008 IHS Award Date: 02/02/2024

455 NORTH THIRD STREET

SUITE 250

PHOENIX, AZ 85004

602.265.2200 smithgroup.com

Drawn By: Checked By:

BASED ON PROGRAM OF REQUIREMENTS DATED [ 03/26/22],

POR AMENDMENT DATED [ 02/03/25], AND ON SCHEMATIC

DRAWINGS APPROVED [11/19/24].

4/1 6/2

6 9

:57 :24

A M

LEVEL 2 (UPPER GROUND)

HVAC PLAN AREA C

EMP2.2.CCD

W hit tin gto n

14904.000 Whittington Baca

SHEET KEYNOTES

GRAPHIC SCALE: 1/8" = 1'-0"

8' 8' 16'0'4'

PROJECT NORTH

E247 CONNECT ALL FIRE SMOKE DAMPERS IN THIS AREA TO

CIRCUIT SHOWN.

E248 CONNECT ALL VAV TRANSFORMERS INSTALLED IN THIS AREA

TO CIRCUITS SHOWN. DEVICE TAGS ARE STRUCTURED

BASED ON LEVEL AND AREA. BMS CONTRACTOR TO PROVIDE

(1) 24V TRANSFORMER TO AN AVERAGE OF (4) VAV'S PER

TRANSFORMER. REFERENCE BMS CONTRACTOR SHOP

DRAWINGS FOR TRANSFORMER LOCATIONS.

E280 PROVIDE WALL MOUNTED EMERGENCY POWER OFF (EPO)

SWITCH ASSEMBLY WITH RED MOMENTARY PUSH BUTTON,

YELLOW BODY, CLEAR FLIP COVER AND CUSTOM LABELING

AS FOLLOWS: "BOILER EMERGENCY SHUTDOWN",

MANUFACTURED BY STI #SS2-2-2-ZA-EN, OR EQUIVALENT.

ACTIVATION OF EPO SHALL SHUNT TRIP ALL CIRCUIT

BREAKERS SERVING BOILERS.

SCALE: 1/8" = 1'-0"1 LEVEL 2 (UPPER GROUND) - HVAC PLAN AREA C

FINAL CONSTRUCTION DOCUMENTS 05MAR26

BID ADDENDUM-A 16APR26

A

04-16-26

6-30-28

J

M

M

M

J

M

J

M

3 54 6 7 8 9 i

K

J

ET-1

BP-1

C H

W P-

C H

W P-

C H

W P-

C H

W P-

C H

W P-

H H

W P-

H H

W P-

H H

W P-

H H

W P-

H H

W P-

B-1 B-2

ACCH-2

ACCH-1

ACCH-3

ASHP-1

ASHP-2

C

BW

P-

C

BW

P-

C

BW

P-

B-4B-3

MAP-2-01

CU-2075A CU-2075B CU-1337 CU-1179

CU-2350

CHWP-1 CHWP-2 CHWP-3 CHWP-4 CHWP-5

VFD- VFD- VFD- VFD- VFD- VFD- VFD- VFD-

CBWP-1 CBWP-2 CBWP-3

VFD-

VFD-

VFD-

VFD-

VFD-

HHWP-1 HHWP-2 HHWP-3 HHWP-4 HHWP-5

EWH-5 EWH-4 EWH-3 EWH-2 EWH-1B-5

FCU-2373

FCU-2370

BCU-2374

BCU-2368

TOILET/SHOWER, STAFF

CUP-2368A

OFFICE, FOREMAN

CUP-2369A

CENTRAL PLANT

CUP-2368

WORKSTATIONS

CUP-2369C

CORRIDOR

CUP-2369

STORAGE, PLANS

CUP-2369B

MAIN ELECTRICAL ROOM

CUP-2371

MAIN NORMAL ELECTRICAL

CUP-2374

CUP ELECTRICAL

CUP-2373

FIRE PUMP

CUP-2370

MEP YARD

CUP-2368B

O2 TANKS YARD

CUP-2368C

WM-HW-1

WM-CW-1

WM-RW-2

WM-CW-4

WM-CW-3

E256

EP2ELA- 29

N

SC

-1 C

P-

C P-

WT-2

WT-1

MV-1

SM

W

P-

VFD-

GF-1

SMWP-1

BCU-2371

E280 TYP

OF 8

EP2ELA- 33

EP2ELA- 33

EP2ELA- 33

EP2ELA- 33

EP2ELA- 33

EP2ELA- 33

EP2ELA- 33 EP2ELA- 33

A

AAA

A

A

A

A.

B.

C.

D.

E.

F.

G.

H.

I.

J.

K.

L.

M.

N.

O.

P.

Q.

R.

S.

T.

SEE DRAWING E0.1 FOR ABBREVIATIONS, SYMBOLS, GENERAL

NOTES AND DEVICE MOUNTING HEIGHT OF WALL MOUNTED

DEVICES, UON.

ALL BRANCH CIRCUIT WIRING SHALL BE A MINIMUM SIZE OF #10

AWG. REFER TO SHEET E0.2 FOR ADDITIONAL SIZING

INFORMATION.

THE CONTRACTOR SHALL COORDINATE EXACT LOCATION OF

EQUIPMENT POWER CONNECTIONS WITH EQUIPMENT

INSTALLER PRIOR TO ROUGH-IN.

SEE MECHANICAL EQUIPMENT SCHEDULE FOR ASSOCIATED

OVERCURRENT DEVICES, DISCONNECT SWITCHES, STARTERS

AND WIRES.

CONTRACTOR SHALL COORDINATE AND FIELD VERIFY

REQUIREMENT OF NEUTRAL CONDUCTOR FOR ALL EQUIPMENT

AND PROVIDE NEUTRAL CONDUCTOR AS NECESSARY.

ALL CIRCUITS SHALL BE EQUIPPED WITH A DEDICATED

NEUTRAL CONDUCTOR, UNLESS NOTED OTHERWISE.

ALL CONDUCTORS SHALL BE COPPER, UNLESS NOTED OR

SCHEDULED OTHERWISE.

TRIPPING OF GFCI RECEPTACLES SHALL NOT AFFECT THE

DOWNSTREAM RECEPTACLES.

NO MORE THAN 3 CIRCUITS MAY SHARE A HOMERUN.

FOR ALL MECHANICAL EQUIPMENT, PROVIDE ADDITIONAL 120V

CONNECTIONS REQUIRED BY MANUFACTURER.

FOR EACH AIR HANDLING UNIT, PROVIDE (1)120V CONNECTION

FOR LIGHTING AND RECEPTACLES. CIRCUIT TO MECHANICAL

PANEL WITHIN THE SPACE.

PROVIDE 120V CIRCUITS FOR CONTROL PANELS AS REQUIRED

BY CONTROL VENDOR. CIRCUIT TO MECHANICAL PANEL WITHIN

THE SPACE.

ALL UNUSED WALL OUTLETS TO BE COVERED WITH BLANK

PLATE. ALL BLANK PLATE COLORS TO MATCH WALL COLOR.

REFER TO 'T' SERIES PLANS FOR LOW VOLTAGE BACK BOX AND

RACEWAY REQUIREMENTS.

ALL CONDUIT ROUTED WITHIN SLAB SHALL COMPLY WITH

GUIDELINES LISTED IN STRUCTURAL DRAWINGS.

COORDINATE FINAL LOCATION OF MECHANICAL AND PLUMBING

EQUIPMENT AND ASSOCIATED DISCONNECT SWITCHES,

STARTERS, VFDS, CONTROL POWER AND OTHER POWER

REQUIREMENTS WITH DIV 22 AND 23.

CONTRACTOR IS RESPONSIBLE FOR ALL WIRING FROM VFDs

AND DISCONNECTS SHOWN IN DRAWINGS TO THE EQUIPMENT

AND IS TO COORDINATE WITH EQUIPMENT MANUFACTURER

AND INSTALLATION INSTRUCTIONS.

CONTRACTOR SHALL PROVIDE VFD CABLE FOR LINE AND LOAD

SIDE VFD CONNECTIONS.

CONTRACTOR SHALL PROVIDE RUN PERMISSIVE INTERLOCK

BETWEEN VFD AND LOAD SIDE EQUIPMENT DISCONNECT

SWITCH. DISCONNECT SWITCH SHALL BE EQUIPPED WITH

AUXILIARY CONTACT.

CHILLED BEAM MECHANICAL EQUIPMENT DOES NOT REQUIRE

POWER SOURCE CIRCUITING. SHOWN FOR REFERENCE ONLY.

EXTEND LINE SIDE OF NEAREST 120V GENERAL RECEPTACLE

POWER CIRCUIT TO ELECTRONIC PLUMBING VALVES.

COORDINATE ELECTRONIC PLUMBING VALVE INFRASTRUCTURE

REQUIREMENTS AND LOCATION WITH PLUMBING CONTRACTOR

AND EQUIPMENT MANUFACTURER PRIOR TO COMMENCING

WORK. INSTALL PER EQUIPMENT MANUFACTURERS

SPECIFICATIONS.

GENERAL SHEET NOTES

NORTH

SHEET NUMBER

PROJECT NUMBER

KEYPLAN

SEALS AND SIGNATURES

ISSUED FOR DATE

Pl ot

Da te:

G

IHS Whiteriver Hospital 200 W Hospital Drive Whiteriver, Arizona, 85941

IHS Project #: 131445 IHS Contract #: 75H70123R00008 IHS Award Date: 02/02/2024

455 NORTH THIRD STREET

SUITE 250

PHOENIX, AZ 85004

602.265.2200 smithgroup.com

Drawn By: Checked By:

BASED ON PROGRAM OF REQUIREMENTS DATED [ 03/26/22],

POR AMENDMENT DATED [ 02/03/25], AND ON SCHEMATIC

DRAWINGS APPROVED [11/19/24].

4/1 6/2

6 9

:57 :27

A M

LEVEL 2 (UPPER GROUND)

HVAC PLAN AREA G

EMP2.2.GCD

W hit tin gto n

14904.000 Whittington Baca

SHEET KEYNOTES

GRAPHIC SCALE: 1/8" = 1'-0"

8' 8' 16'0'4'

PROJECT NORTH

E256 PROVIDE 120V BRANCH CIRCUIT FOR ENERGY AND WATER

FLOW METER CONNECTIONS IN THIS AREA. COORDINATE

LOCATIONS WITH PLUMBING.

E280 PROVIDE WALL MOUNTED EMERGENCY POWER OFF (EPO)

SWITCH ASSEMBLY WITH RED MOMENTARY PUSH BUTTON,

YELLOW BODY, CLEAR FLIP COVER AND CUSTOM LABELING

AS FOLLOWS: "BOILER EMERGENCY SHUTDOWN",

MANUFACTURED BY STI #SS2-2-2-ZA-EN, OR EQUIVALENT.

ACTIVATION OF EPO SHALL SHUNT TRIP ALL CIRCUIT

BREAKERS SERVING BOILERS.

SCALE: 1/8" = 1'-0"1 LEVEL 2 (UPPER GROUND) - HVAC PLAN AREA G

FINAL CONSTRUCTION DOCUMENTS 23JAN26

BID ADDENDUM-A 16APR26

A

LSIG

2500/3

LS

IG

/3

EN

L

AB

LS

IG

0/

EN

L

AA

APW2LHA

225A

MLO

SPD

APW2LLA

150A

MCB

SPD

APW3LHA

80A

MLO

SPD

APW3LLA

60A

MLO

SPD

APW4LHA

80A

MLO

SPD

APW4LLA

60A

MLO

SPD

APW2SHD

225A

FTL

SPD

LS

I

5/

APW2SHE

225A

MLO

SPD

APW2SHA

300A

FTL

APW2SLA

400A

MCB/FTL

LS

I

0/

APW2SLB

400A

MLO

APW2SHB

300A

FTL

APW2SLC

400A

MCB/FTL

LS

I

0/

APW2SLD

400A

MLO

APW2SHC

300A

FTL

APW2SLE

400A

MCB/FTL

LS

I

0/

APW2SLF

400A

MLO

APW1LHA

80A

MLO

SPD

APW1LLA

60A

MLO

SPD

APW1SHD

125A

MLO

SPD

APW1SHE

125A

MLO

SPD

APW1SLA

225A

FTL

APW1SHA

300A

MLO

APW1SLB

225A

MLO

APW1SLC

225A

FTL

APW1SHB

300A

MLO

APW1SLD

225A

MLO

APW1SLE

225A

FTL

APW1SHC

300A

MLO

APW1SLF

225A

MLO

LS

IG

/3

EN

L

AC

APW2CHA

150A

MLO

LS

I

0/

APW1CHA

150A

MLO

LS

I

0/

LS

I

0/

APW1SLH

400A

MCB

APW1SLJ

225A

MLO

5/

M M M M

MM M

M

M

M M60 /3

APA2LHA

100A

MLO

SPD

APA2LLA

60A

MCB

SPD

APA2SHA

200A

MCB

LS

I

0/

M

APA2SLA

150A

MCB/FTL

APA1SLA

150A

MLO

AP2LLA

60A

MCB

SPD

/3

SPD

A.

B.

C.

D.

E.

F.

G.

H.

I.

J.

K.

L.

BASE BUILD SCOPE SHALL ONLY INCLUDE EMPTY CONDUITS

OF FEEDERS SHOWN ON THIS SHEET WITH FEEDER TAGS.

ADD ALTERNATE SCOPE SHALL INCLUDE PV PANELS,

CARPORTS, DC CONDUCTORS, INVERTERS, AC CONDUCTORS,

AC COMBINER BOXES, PV DISTRIBUTION BOARDS.

SEE DRAWING E0.1 FOR ABBREVIATIONS, SYMBOLS, GENERAL

NOTES.

THE CONTRACTOR SHALL COORDINATE EXACT LOCATION OF

EQUIPMENT POWER CONNECTIONS WITH EQUIPMENT

INSTALLER PRIOR TO ROUGH-IN.

COORDINATE FINAL LOCATION OF MECHANICAL EQUIPMENT

AND ASSOCIATED DISCONNECT SWITCHES, STARTERS, VFDS,

CONTROL POWER AND OTHER POWER REQUIREMENTS WITH

DIV 23 AND MECHANICAL DRAWINGS.

SEE MECHANICAL EQUIPMENT SCHEDULE FOR ASSOCIATED

OVERCURRENT DEVICES, DISCONNECT SWITCHES, STARTERS

AND WIRES.

VOLTAGE DROP SHALL BE LIMITED TO LESS THAN 3% FOR ALL

BRANCH CIRCUITS AND 2% FOR ALL FEEDERS.

CONTRACTOR SHALL COORDINATE AND FIELD VERIFY

REQUIREMENT OF NEUTRAL CONDUCTOR FOR ALL EQUIPMENT

AND PROVIDE NEUTRAL CONDUCTOR AS NECESSARY.

ALL LIFE SAFETY AND LIGHTING PANELBOARDS SHALL BE

EQUIPPED WITH TYPE 2 SPD.

ALL AUTOMATIC TRANSFER SWITCHES SHALL BE 4 POLE AND

EQUIPPED WITH BYPASS ISOLATION.

ALL UTILITY TRANSFORMERS DESCRIBED AS NAVOPACHE

TRANSFORMER TO BE COORDINATED WITH UTILITY AND

PROVIDED BY UTILITY. COORDINATE ALL FINAL REQUIREMENTS

AND AVAILABLE FAULT CURRENT CONTRIBUTIONS BASED ON

SUPPLIED EQUIPMENT. BASIS OF DESIGN 2500KVA, AND 5%Z.

ELECTRICAL EQUIPMENT SHALL BE CONFIGURED AS FOLLOWS:

-SERVICE ENTRANCE SECTIONS - UL891 REAR CONNECTED

SWITCHBOARD

-DISTRIBUTION SWITCHBOARDS WITH DRAWOUT CIRCUIT

BREAKERS - UL891 REAR CONNECTED SWITCHBOARD

-GENERATOR PARALLELING GEAR - UL1558 SWITCHGEAR

GENERAL SHEET NOTES

OPTIONAL

STANDBYE503

E502

M

NAVOPACHE

TRANSFORMER

ADM2SH

1000A

480-277V

3PH/4W

LIFE

SAFETY

ATS-ALA

250A

4P

LEVEL 1

LEVEL 2

LEVEL 2

LEVEL 3

TAPW2LLA

45kVA

LEVEL 3

LEVEL 4

ATS-ASA

1000A

4P

LTG

TAPW2SLA/B

112.5kVA

PWR

TAPW2SLC/D

112.5kVA

TAPW2SLE/F

112.5kVA

PWR PWR

CRITICAL

ADM2CH

1000A

480-277V

3PH/4W

ATS-ACA

1000A

4P

PWR

PWR

LEVEL 4

ROOF

A1000

A250 A1000

T112T112T112T45

A300

A400

A300 A225

A225

A300

A300 A225

A225

A400

A300

A300 A225

A225

A400

A225

A125 A125

A225

A150

A1000

A1000

A150

E501

TAPW1SLH/J

112.5kVA

A225

LAB PWR

ADM2LH

250A 480-277V

3PH/4W

A225

MAIN

SA1

SA2 SA3 SA4

DA1 DA2 DA3 DA4 DA7

DA5 DA8

A250

TAPA2LLA

15kVA

60V1

T15

EMS PWR

A200V1

EMS BLDG

TAPA2SLA

45kVA

T45

A150

DA6

MATCHLINE

MATCHLINE

TAP2LLA

15kVA T15

T112

SES-A

3200A BUS

PER NEC 705.12(B)

480-277V/3PH/4W (3)

E521

SEL-751

(3)(3)

A

SHEET NUMBER

PROJECT NUMBER

SEALS AND SIGNATURES

ISSUED FOR DATE

Pl ot

Da te:

IHS Whiteriver Hospital 200 W Hospital Drive Whiteriver, Arizona, 85941

IHS Project #: 131445 IHS Contract #: 75H70123R00008 IHS Award Date: 02/02/2024

455 NORTH THIRD STREET

SUITE 250

PHOENIX, AZ 85004

602.265.2200 smithgroup.com

Drawn By: Checked By:

BASED ON PROGRAM OF REQUIREMENTS DATED [ 03/26/22],

POR AMENDMENT DATED [ 02/03/25], AND ON SCHEMATIC

DRAWINGS APPROVED [11/19/24].

4/1 6/2

6 9

:57 :32

A M

ELECTRICAL ONE LINE

DIAGRAM - SES-A, 1 OF 2

E5.1.1CD

W hit tin gto n

14904.000 Whittington Baca

X FEEDER SCHEDULE

SHEET KEYNOTES

E501 NAVOPACHE UTILITY METER. METER SHALL BE EQUIPPED

WITH CAPABILITY TO INTERFACE WITH BMS. ELECTRICAL

CONTRACTOR SHALL PROVIDE REQUIRED CONDUIT AND

COMMUNICATION WIRING FROM METER TO POINT OF

INTERFACE WITH BMS.

E502 COMPLIANCE WITH "NEC 240.87 ARC ENERGY REDUCTION"

REQUIRED. REDUCTION METHOD SHALL ALLOW FOR

REQUIRED SELECTIVE DEVICE COORDINATION AND ARC

FLASH REQUIREMENTS. REFER TO ELECTRICAL

SPECIFICATIONS FOR ADDITIONAL INFORMATION.

E503 PROVIDE PERMANENT IDENTIFICATION PLAQUE INDICATING

THE FOLLOWING: ELECTRICAL SERVICE #1 OF 5.

GENERATORS LOCATED IN ELECTRICAL EQUIPMENT YARD,

GENERATOR DISCONNECTS LOCATED IN ADJACENT

ELECTRICAL ROOM IN GMDB. PV DISCONNECT LOCATED AT

END OF THIS ELECTRICAL EQUIPMENT LINEUP.

E521 PROVIDE RELAY PROTECTION ELEMENTS REQUIRED BY

UTILITY AND MULTIPLE GENERATOR AND PV MONITORING

AND CONTROL SYSTEM MANUFACTURER. INTEGRATE SEL

RELAY AND PROGRAMMING INTO MULTIPLE GENERATOR

AND PV MONITORING SYSTEM AND CIRCUIT BREAKER.

PROVIDE AND PROGRAM PROTECTION ELEMENT SET POINTS

AND LOGIC WITHIN THE RELAY. REFER TO SEL-751 DETAIL

FOR ADDITIONAL INFORMATION.

SCALE: NOT TO SCALE1 ONE LINE DIAGRAM - SES-A, 1 OF 2

60 4#4 + 1#10 G, 1 1/4" C 60V1 4#1 + 1#6 G, 1 1/2" C 80 4#3 + 1#8 G, 1 1/4" C A125 4#2/0 + 1#6 G, 2" C A150 4#3/0 + 1#4 G, 2" C

A200V1 4#400KCMIL + 1#1 G, 2 1/2" C

A225 4#300KCMIL + 1#2 G, 2 1/2" C

A250 4#350KCMIL + 1#2 G, 2 1/2" C

A300 4#500KCMIL + 1#2 G, 3" C

A400 2 SETS OF 4#250KCMIL + 1#1 G, (2) 2 1/2" C

A1000 3 SETS OF 4#600KCMIL + 1#4/0 G, (3) 3 1/2" C

T15 15KVA TRANSFORMER, 480-208Y/120V, 3PH

PRIMARY FEEDER: 3#10 + 1#10 G, 3/4" C

SECONDARY FEEDER: 4#4 + 1#8 G, 1 1/4" C

BONDING JUMPERS & GROUNDING ELECTRODE

CONDUCTOR: #8

T45 45KVA TRANSFORMER, 480-208Y/120V, 3PH

PRIMARY FEEDER: 3#3 + 1#8 G, 1 1/4" C

SECONDARY FEEDER: 4#1/0 + 1#6 G, 2" C

BONDING JUMPERS & GROUNDING ELECTRODE

CONDUCTOR: #6

T112 112.5KVA TRANSFORMER, 480-208Y/120V, 3PH

PRIMARY FEEDER: 3#3/0 + 1#6 G, 2" C

SECONDARY FEEDER: 2 SETS OF 4#3/0 + 1#2 G, (2)

2" C

BONDING JUMPERS & GROUNDING ELECTRODE

CONDUCTOR: #2

"A" DENOTES ALUMINUM CONDUCTORS, ALL OTHER CONDUCTORS SHALL BE COPPER

FINAL CONSTRUCTION DOCUMENTS 05MAR26

BID ADDENDUM-A 16APR26

AA

APW2CHD

225A

MLO/FTL

SPD

LS

I

5/

APW2CHE

225A

MLO

SPD

APW2CLA

125A

MCB

APW2CLB

125A

MCB

APW2CHB

150A

MLO

APW2CLC

125A

MCB

LS

I

0/

APW2CLD

125A

MCB

APW2CHC

150A

MLO

APW2CLE

125A

MCB

LS

I

0/

APW2CLF

125A

MCB

APW1CHD

125A

MLO

SPD

APW1CHE

125A

MLO

SPD

APW1CLA

125A

MCB

APW1CHA

150A

MLO

APW1CLB

125A

MCB

APW1CLD

125A

MCB

APW1CHB

150A

MLO

APW1CLC

125A

MCB

APW1CLF

125A

MCB

APW1CHC

150A

MLO

APW1CLE

125A

MCB

LS

IG

/3

EN

L

AD

LS

I

0/

LS

I

5/

LS

I

5/

LS

I

0/

LS

I

5/

LS

I

5/

LS

I

5/

LS

I

0/

LS

I

5/

LS

I

/3

VFD

LS

I

0/

VFD

LS

I

/3

VFD

LS

I

0/

VFD

LS

IG

0/

PVW

LS

I

0/

LS

IG

0/

EN

L

AE

LS

I

0/

LS

I

0/

APW2EHA

300A

MLO

APW1EHA

150A

MLO

APW2EHB

250A

MLO

APW1EHB

150A

MLO

APW1ELA

150A

MCB

APW1ELB

150A

MCB

LS

I

/3

M M

M M M M M M M M M M M M M M

M M M M M M

M

APA1CLA

60A

MCB

APW2ELA

150A

MCB

APW2ELB

150A

MCB

A.

B.

C.

D.

E.

F.

G.

H.

I.

J.

K.

L.

BASE BUILD SCOPE SHALL ONLY INCLUDE EMPTY CONDUITS

OF FEEDERS SHOWN ON THIS SHEET WITH FEEDER TAGS.

ADD ALTERNATE SCOPE SHALL INCLUDE PV PANELS,

CARPORTS, DC CONDUCTORS, INVERTERS, AC CONDUCTORS,

AC COMBINER BOXES, PV DISTRIBUTION BOARDS.

SEE DRAWING E0.1 FOR ABBREVIATIONS, SYMBOLS, GENERAL

NOTES.

THE CONTRACTOR SHALL COORDINATE EXACT LOCATION OF

EQUIPMENT POWER CONNECTIONS WITH EQUIPMENT

INSTALLER PRIOR TO ROUGH-IN.

COORDINATE FINAL LOCATION OF MECHANICAL EQUIPMENT

AND ASSOCIATED DISCONNECT SWITCHES, STARTERS, VFDS,

CONTROL POWER AND OTHER POWER REQUIREMENTS WITH

DIV 23 AND MECHANICAL DRAWINGS.

SEE MECHANICAL EQUIPMENT SCHEDULE FOR ASSOCIATED

OVERCURRENT DEVICES, DISCONNECT SWITCHES, STARTERS

AND WIRES.

VOLTAGE DROP SHALL BE LIMITED TO LESS THAN 3% FOR ALL

BRANCH CIRCUITS AND 2% FOR ALL FEEDERS.

CONTRACTOR SHALL COORDINATE AND FIELD VERIFY

REQUIREMENT OF NEUTRAL CONDUCTOR FOR ALL EQUIPMENT

AND PROVIDE NEUTRAL CONDUCTOR AS NECESSARY.

ALL LIFE SAFETY AND LIGHTING PANELBOARDS SHALL BE

EQUIPPED WITH TYPE 2 SPD.

ALL AUTOMATIC TRANSFER SWITCHES SHALL BE 4 POLE AND

EQUIPPED WITH BYPASS ISOLATION.

ALL UTILITY TRANSFORMERS DESCRIBED AS NAVOPACHE

TRANSFORMER TO BE COORDINATED WITH UTILITY AND

PROVIDED BY UTILITY. COORDINATE ALL FINAL REQUIREMENTS

AND AVAILABLE FAULT CURRENT CONTRIBUTIONS BASED ON

SUPPLIED EQUIPMENT. BASIS OF DESIGN 2500KVA, AND 5%Z.

ELECTRICAL EQUIPMENT SHALL BE CONFIGURED AS FOLLOWS:

-SERVICE ENTRANCE SECTIONS - UL891 REAR CONNECTED

SWITCHBOARD

-DISTRIBUTION SWITCHBOARDS WITH DRAWOUT CIRCUIT

BREAKERS - UL891 REAR CONNECTED SWITCHBOARD

-GENERATOR PARALLELING GEAR - UL1558 SWITCHGEAR

GENERAL SHEET NOTES

LTG

TAPW2CLA/B

75kVA

PWR PWR

EQUIPMENT

ADM2EHA

1600A

480-277V

3PH/4W

ATS-AEA

1600A

4P

LEVEL 1

LEVEL 2

LEVEL 2

LEVEL 3

LEVEL 3

LEVEL 4

PWR PWR

TAPW1CLA/B

75kVA

PWR

PWR

TAPW2CLC/D

75kVA

PWR

PWR

TAPW1CLC/D

75kVA

TAPW2CLE/F

75kVA

PWR

PWR PWR

TAPW1CLE/F

75kVA

LEVEL 4

ROOF

T75D T75D

T75DT75DT75D A150 A150 A225

A225

A150 A150 A150 A125 A125

A1600

A1600

1000-3

ACCH-1

CHWP-1

100-3

HHWP-1

30-3

CBWP-1

100-3

PV A

EH-1

EQUIPMENT

ADM2EHB

600A

480-277V

3PH/4W

ATS-AEB

600A

4P

A600

A600

A250A300

A150 T75D

300-3

TAPW1ELA

45kVA

T45

TAPW1ELB

45kVA

T45

, E O

1000-3

B-1

NON-COINCIDENT

LOAD

SA5 SA6

DA9 DA11 DA13 DA15 DA17 DA19 DA20 DA21 DA22 DA23 DA24 DA25 DA26 DA29

DA8 DA10 DA12 DA14 DA16 DA18

E519

60V1

EMS BLDG

SA7

MATCHLINE

TAPW2ELA

45kVA

T45

TAPW2ELB

45kVA

T45

A150

MATCHLINE

NON-COINCIDENT

LOAD

E530

A

SHEET NUMBER

PROJECT NUMBER

SEALS AND SIGNATURES

ISSUED FOR DATE

Pl ot

Da te:

IHS Whiteriver Hospital 200 W Hospital Drive Whiteriver, Arizona, 85941

IHS Project #: 131445 IHS Contract #: 75H70123R00008 IHS Award Date: 02/02/2024

455 NORTH THIRD STREET

SUITE 250

PHOENIX, AZ 85004

602.265.2200 smithgroup.com

Drawn By: Checked By:

BASED ON PROGRAM OF REQUIREMENTS DATED [ 03/26/22],

POR AMENDMENT DATED [ 02/03/25], AND ON SCHEMATIC

DRAWINGS APPROVED [11/19/24].

4/1 6/2

6 9

:57 :37

A M

ELECTRICAL ONE LINE

DIAGRAM - SES-A, 2 OF 2

E5.1.2CD

W hit tin gto n

14904.000 Whittington Baca

X FEEDER SCHEDULE

SHEET KEYNOTES

E519 PV CIRCUIT BREAKER SHALL BE LOCATED AT LAST BUSSED

SPACE. PROVIDE PERMANENT IDENTIFICATION PLAQUE

INDICATING THE FOLLOWING: PV POWER SOURCE - DO NOT

RELOCATE THIS CIRCUIT BREAKER

E530 PROVIDE SHUNT TRIP CIRCUIT BREAKER FOR INTERFACE

WITH BOILER EMERGENCY SHUTDOWN EPO SWITCHES.

REFER TO EMP2.2.G FOR ADDITIONAL INFORMATION.

SCALE: NOT TO SCALE1 ONE LINE DIAGRAM - SES-A, 2 OF 2

30-3 3#10 + 1#10 G, 3/4" C 60V1 4#1 + 1#6 G, 1 1/2" C 100-3 3#1 + 1#8 G, 1 1/2" C

300-3 3#350KCMIL + 1#4 G, 3" C

1000-3 3 SETS OF 3#400KCMIL + 1#2/0 G, (3) 3" C

A125 4#2/0 + 1#6 G, 2" C A150 4#3/0 + 1#4 G, 2" C

A225 4#300KCMIL + 1#2 G, 2 1/2" C

A250 4#350KCMIL + 1#2 G, 2 1/2" C

A300 4#500KCMIL + 1#2 G, 3" C

A600 2 SETS OF 4#500KCMIL + 1#2/0 G, (2) 3" C

A1600 5 SETS OF 4#600KCMIL + 1#350KCMIL G, (5) 3 1/2" C

T45 45KVA TRANSFORMER, 480-208Y/120V, 3PH

PRIMARY FEEDER: 3#3 + 1#8 G, 1 1/4" C

SECONDARY FEEDER: 4#1/0 + 1#6 G, 2" C

BONDING JUMPERS & GROUNDING ELECTRODE

CONDUCTOR: #6

T75D 75KVA TRANSFORMER, 480-208Y/120V, 3PH

PRIMARY FEEDER: 3#1/0 + 1#6 G, 1 1/2" C

SECONDARY FEEDERS: 4#1/0 + 1#2 G, 2" C TO EACH PANEL

BONDING JUMPERS & GROUNDING ELECTRODE

CONDUCTOR: #2

"A" DENOTES ALUMINUM CONDUCTORS, ALL OTHER CONDUCTORS SHALL BE COPPER

FINAL CONSTRUCTION DOCUMENTS 05MAR26

BID ADDENDUM-A 16APR26

A

A

LS

IG

/3

EN

L

BB

LS

IG

0/

EN

L

BA

BPE2SHD

225A

FTL

SPD

LS

I

5/

BPE2SHE

225A

MLO

SPD

BPE2SHA

300A

FTL

BPE2SLA

400A

MCB/FTL

LS

I

0/

BPE2SLB

400A

MLO

BPE2SHB

300A

FTL

BPE2SLC

225A

MCB/FTL

LS

I

0/

BPE2SLD

225A

MLO

BPE1SHD

125A

MLO

SPD

BPE1SHE

125A

MLO

SPD

BPE1SLA

225A

FTL

BPE1SHA

300A

MLO

BPE1SLB

225A

MLO

BPE1SLC

225A

FTL

BPE1SHB

300A

MLO

BPE1SLD

225A

MLO

/3

/3

/3

/3

/3

LS

IG

/3

LS

I

/3

BPT2SLA

150A

MCB

BPT2SLB

225A

MCB

LS

I

5/

BPT1SLA

80A

MLO

BPT3SLA

80A

MLO

BPT4SLA

80A

MLO

BPT2SLC

225A

MCB

LS

I

5/

BPT1SLB

80A

MLO

BPT3SLB

80A

MLO

BPT4SLB

80A

MLO

BPF2SHA

250A

MLO

BPF2SLA

225A

MCB

LS

I

0/

M

M M

M M M M M M M

SPD

A.

B.

C.

D.

E.

F.

G.

H.

I.

J.

K.

L.

BASE BUILD SCOPE SHALL ONLY INCLUDE EMPTY CONDUITS

OF FEEDERS SHOWN ON THIS SHEET WITH FEEDER TAGS.

ADD ALTERNATE SCOPE SHALL INCLUDE PV PANELS,

CARPORTS, DC CONDUCTORS, INVERTERS, AC CONDUCTORS,

AC COMBINER BOXES, PV DISTRIBUTION BOARDS.

SEE DRAWING E0.1 FOR ABBREVIATIONS, SYMBOLS, GENERAL

NOTES.

THE CONTRACTOR SHALL COORDINATE EXACT LOCATION OF

EQUIPMENT POWER CONNECTIONS WITH EQUIPMENT

INSTALLER PRIOR TO ROUGH-IN.

COORDINATE FINAL LOCATION OF MECHANICAL EQUIPMENT

AND ASSOCIATED DISCONNECT SWITCHES, STARTERS, VFDS,

CONTROL POWER AND OTHER POWER REQUIREMENTS WITH

DIV 23 AND MECHANICAL DRAWINGS.

SEE MECHANICAL EQUIPMENT SCHEDULE FOR ASSOCIATED

OVERCURRENT DEVICES, DISCONNECT SWITCHES, STARTERS

AND WIRES.

VOLTAGE DROP SHALL BE LIMITED TO LESS THAN 3% FOR ALL

BRANCH CIRCUITS AND 2% FOR ALL FEEDERS.

CONTRACTOR SHALL COORDINATE AND FIELD VERIFY

REQUIREMENT OF NEUTRAL CONDUCTOR FOR ALL EQUIPMENT

AND PROVIDE NEUTRAL CONDUCTOR AS NECESSARY.

ALL LIFE SAFETY AND LIGHTING PANELBOARDS SHALL BE

EQUIPPED WITH TYPE 2 SPD.

ALL AUTOMATIC TRANSFER SWITCHES SHALL BE 4 POLE AND

EQUIPPED WITH BYPASS ISOLATION.

ALL UTILITY TRANSFORMERS DESCRIBED AS NAVOPACHE

TRANSFORMER TO BE COORDINATED WITH UTILITY AND

PROVIDED BY UTILITY. COORDINATE ALL FINAL REQUIREMENTS

AND AVAILABLE FAULT CURRENT CONTRIBUTIONS BASED ON

SUPPLIED EQUIPMENT. BASIS OF DESIGN 2500KVA, AND 5%Z.

ELECTRICAL EQUIPMENT SHALL BE CONFIGURED AS FOLLOWS:

-SERVICE ENTRANCE SECTIONS - UL891 REAR CONNECTED

SWITCHBOARD

-DISTRIBUTION SWITCHBOARDS WITH DRAWOUT CIRCUIT

BREAKERS - UL891 REAR CONNECTED SWITCHBOARD

-GENERATOR PARALLELING GEAR - UL1558 SWITCHGEAR

GENERAL SHEET NOTES

E504

E502

M

NAVOPACHE

TRANSFORMER

LEVEL 1

LEVEL 2

LEVEL 2

LEVEL 3

LEVEL 3

LEVEL 4

LEVEL 4

ROOF

OPTIONAL

STANDBY

BDM2SH

1000A

480-277V

3PH/4W

EQUIPMENT

(ELEVATORS)

ATS-BEA

400A

4P

ATS-BSA

1000A

4P

LTG

TBPE2SLA/B

112.5kVA

TBPE2SLC/D

75kVA

CNTRL

PNL

STAFF/PATIENT

ELEV 1B

CNTRL

PNL

STAFF/PATIENT

ELEV 1A

CNTRL

PNL

FREIGHT ELEV 5

CNTRL

PNL

PUBLIC ELEV 4B

CNTRL

PNL

PUBLIC ELEV 4A

BDW4EH

400A 480-277V

3PH/4W

ATS-BCA

1000A

4P

PWR PWR

A400

A400

A1000

A1000

A300 A300V1 A225

T112 T75

A300 A225

A225

A400

A300

A225

A225

A125 A125

A225V1

TBPT2SLA

45kVA K13

TBPT2SLB

75kVA K13

TBPT2SLC

75kVA K13

T45N T75N T75N

80 80

80 80

80 80

MDF IDF IDF

E501

50-3 50-3 80-3 50-3V1 50-3V1

FAC BLDG

TBPF2SLA

75kVA

MAIN

SB1

SB2 SB3

DB1 DB2 DB3 DB4 DB5 DB6 DB7

MATCHLINE

MATCHLINE

T75

A250

A250

TBPT2SLA

200A/150AF

BPF2SHA

400A/250AF

TBPE1SLC/D

75kVA

T75

TBPT2SLB

400A/225AF

TBPT2SLC

400A/225AF

#2

SES-B

3200A BUS

PER NEC 705.12(B)

480-277V/3PH/4W (3)

E521

SEL-751

(3)(3)

A

SHEET NUMBER

PROJECT NUMBER

SEALS AND SIGNATURES

ISSUED FOR DATE

Pl ot

Da te:

IHS Whiteriver Hospital 200 W Hospital Drive Whiteriver, Arizona, 85941

IHS Project #: 131445 IHS Contract #: 75H70123R00008 IHS Award Date: 02/02/2024

455 NORTH THIRD STREET

SUITE 250

PHOENIX, AZ 85004

602.265.2200 smithgroup.com

Drawn By: Checked By:

BASED ON PROGRAM OF REQUIREMENTS DATED [ 03/26/22],

POR AMENDMENT DATED [ 02/03/25], AND ON SCHEMATIC

DRAWINGS APPROVED [11/19/24].

4/1 6/2

6 9

:57 :43

A M

ELECTRICAL ONE LINE

DIAGRAM - SES-B, 1 OF 2

E5.2.1CD

W hit tin gto n

14904.000 Whittington Baca

X FEEDER SCHEDULE

SHEET KEYNOTES

E501 NAVOPACHE UTILITY METER. METER SHALL BE EQUIPPED

WITH CAPABILITY TO INTERFACE WITH BMS. ELECTRICAL

CONTRACTOR SHALL PROVIDE REQUIRED CONDUIT AND

COMMUNICATION WIRING FROM METER TO POINT OF

INTERFACE WITH BMS.

E502 COMPLIANCE WITH "NEC 240.87 ARC ENERGY REDUCTION"

REQUIRED. REDUCTION METHOD SHALL ALLOW FOR

REQUIRED SELECTIVE DEVICE COORDINATION AND ARC

FLASH REQUIREMENTS. REFER TO ELECTRICAL

SPECIFICATIONS FOR ADDITIONAL INFORMATION.

E504 PROVIDE PERMANENT IDENTIFICATION PLAQUE INDICATING

THE FOLLOWING: ELECTRICAL SERVICE #2 OF 5.

GENERATORS LOCATED IN ELECTRICAL EQUIPMENT YARD,

GENERATOR DISCONNECTS LOCATED IN ADJACENT

ELECTRICAL ROOM IN GMDB. PV DISCONNECT LOCATED AT

END OF THIS ELECTRICAL EQUIPMENT LINEUP.

E521 PROVIDE RELAY PROTECTION ELEMENTS REQUIRED BY

UTILITY AND MULTIPLE GENERATOR AND PV MONITORING

AND CONTROL SYSTEM MANUFACTURER. INTEGRATE SEL

RELAY AND PROGRAMMING INTO MULTIPLE GENERATOR

AND PV MONITORING SYSTEM AND CIRCUIT BREAKER.

PROVIDE AND PROGRAM PROTECTION ELEMENT SET POINTS

AND LOGIC WITHIN THE RELAY. REFER TO SEL-751 DETAIL

FOR ADDITIONAL INFORMATION.

SCALE: NOT TO SCALE1 ONE LINE DIAGRAM - SES-B, 1 OF 2

50-3 3#6 + 1#10 G, 3/4" C 50-3V1 3#2 + 1#4 G, 1 1/4" C 80 4#3 + 1#8 G, 1 1/4" C 80-3 3#3 + 1#8 G, 1 1/4" C A125 4#2/0 + 1#6 G, 2" C

A225 4#300KCMIL + 1#2 G, 2 1/2" C

A225V1 4#400KCMIL + 1#1/0 G, 2 1/2" C

A250 4#350KCMIL + 1#2 G, 2 1/2" C

A300 4#500KCMIL + 1#2 G, 3" C

A300V1 4#600KCMIL + 1#1 G, 3" C

A400 2 SETS OF 4#250KCMIL + 1#1 G, (2) 2 1/2" C

A1000 3 SETS OF 4#600KCMIL + 1#4/0 G, (3) 3 1/2" C

T45N 45KVA TRANSFORMER, 480-208Y/120V, 3PH

PRIMARY FEEDER: 3#3 + 1#8 G, 1 1/4" C

SECONDARY FEEDER: 3#1/0, 1#4/0 N + 1#6 G, 2" C

BONDING JUMPERS & GROUNDING ELECTRODE

CONDUCTOR: #6

T75 75KVA TRANSFORMER, 480-208Y/120V, 3PH

PRIMARY FEEDER: 3#1/0 + 1#6 G, 1 1/2" C

SECONDARY FEEDER: 4#4/0 + 1#2 G, 2 1/2" C

BONDING JUMPERS & GROUNDING ELECTRODE

CONDUCTOR: #2

T75N 75KVA TRANSFORMER, 480-208Y/120V, 3PH

PRIMARY FEEDER: 3#1/0 + 1#6 G, 1 1/2" C

SECONDARY FEEDER: 3#4/0, 1#500KCMIL N + 1#2

G, 2 1/2" C

BONDING JUMPERS & GROUNDING ELECTRODE

CONDUCTOR: #2

T112 112.5KVA TRANSFORMER, 480-208Y/120V, 3PH

PRIMARY FEEDER: 3#3/0 + 1#6 G, 2" C

SECONDARY FEEDER: 2 SETS OF 4#3/0 + 1#2 G, (2)

2" C

BONDING JUMPERS & GROUNDING ELECTRODE

CONDUCTOR: #2

"A" DENOTES ALUMINUM CONDUCTORS, ALL OTHER CONDUCTORS SHALL BE COPPER

FINAL CONSTRUCTION DOCUMENTS 05MAR26

BID ADDENDUM-A 16APR26

A

LS

IG

/3

EN

L

BC

BPE2CHD

225A

FTL

SPD

LS

I

5/

BPE2CHE

225A

MLO

SPD

BPE2CHA

150A

MLO

BPE2CLA

125A

MCB

LS

I

0/

BPE2CLB

125A

MCB

BPE2CHB

150A

MLO

BPE2CLC

125A

MCB

LS

I

0/

BPE2CLD

125A

MCB

BPE1CHD

125A

MLO

SPD

BPE1CHE

125A

MLO

SPD

BPE1CLA

125A

MCB

BPE1CHA

150A

MLO

BPE1CLB

125A

MCB

BPE1CLD

125A

MCB

BPE1CHB

150A

MLO

BPE1CLC

125A

MCB

LS

IG

/3

EN

L

BD

LS

I

0/

LS

I

5/

LS

I

5/

LS

I

0/

LS

I

5/

LS

I

5/

BPE2CLE

125A

MCB

BPE2CLF

125A

MCB

LS

I

5/

LS

I

/3

VFD

LS

I

0/

VFD

LS

I

/3

VFD

LS

I

0/

VFD

LS

I

0/

LS

IG

0/

PVX

LS

IG

0/

EN

L

BE

LS

I

0/

LS

I

0/

BPE2EHA

400A

MLO

BPE1EHA

225A

MLO

BPE2EHB

400A

MLO

BPE1EHB

225A

MLO

BPE1ELA

150A

MCB

BPE1ELB

150A

MCB

LS

I

0/

LS

I

0/

LS

I

0/

UA1 BP1 UB1

LS

I

/3

M M M M

M

M

M M M M M

M M M M M

M M M M M M M M

A.

B.

C.

D.

E.

F.

G.

H.

I.

J.

K.

L.

BASE BUILD SCOPE SHALL ONLY INCLUDE EMPTY CONDUITS

OF FEEDERS SHOWN ON THIS SHEET WITH FEEDER TAGS.

ADD ALTERNATE SCOPE SHALL INCLUDE PV PANELS,

CARPORTS, DC CONDUCTORS, INVERTERS, AC CONDUCTORS,

AC COMBINER BOXES, PV DISTRIBUTION BOARDS.

SEE DRAWING E0.1 FOR ABBREVIATIONS, SYMBOLS, GENERAL

NOTES.

THE CONTRACTOR SHALL COORDINATE EXACT LOCATION OF

EQUIPMENT POWER CONNECTIONS WITH EQUIPMENT

INSTALLER PRIOR TO ROUGH-IN.

COORDINATE FINAL LOCATION OF MECHANICAL EQUIPMENT

AND ASSOCIATED DISCONNECT SWITCHES, STARTERS, VFDS,

CONTROL POWER AND OTHER POWER REQUIREMENTS WITH

DIV 23 AND MECHANICAL DRAWINGS.

SEE MECHANICAL EQUIPMENT SCHEDULE FOR ASSOCIATED

OVERCURRENT DEVICES, DISCONNECT SWITCHES, STARTERS

AND WIRES.

VOLTAGE DROP SHALL BE LIMITED TO LESS THAN 3% FOR ALL

BRANCH CIRCUITS AND 2% FOR ALL FEEDERS.

CONTRACTOR SHALL COORDINATE AND FIELD VERIFY

REQUIREMENT OF NEUTRAL CONDUCTOR FOR ALL EQUIPMENT

AND PROVIDE NEUTRAL CONDUCTOR AS NECESSARY.

ALL LIFE SAFETY AND LIGHTING PANELBOARDS SHALL BE

EQUIPPED WITH TYPE 2 SPD.

ALL AUTOMATIC TRANSFER SWITCHES SHALL BE 4 POLE AND

EQUIPPED WITH BYPASS ISOLATION.

ALL UTILITY TRANSFORMERS DESCRIBED AS NAVOPACHE

TRANSFORMER TO BE COORDINATED WITH UTILITY AND

PROVIDED BY UTILITY. COORDINATE ALL FINAL REQUIREMENTS

AND AVAILABLE FAULT CURRENT CONTRIBUTIONS BASED ON

SUPPLIED EQUIPMENT. BASIS OF DESIGN 2500KVA, AND 5%Z.

ELECTRICAL EQUIPMENT SHALL BE CONFIGURED AS FOLLOWS:

-SERVICE ENTRANCE SECTIONS - UL891 REAR CONNECTED

SWITCHBOARD

-DISTRIBUTION SWITCHBOARDS WITH DRAWOUT CIRCUIT

BREAKERS - UL891 REAR CONNECTED SWITCHBOARD

-GENERATOR PARALLELING GEAR - UL1558 SWITCHGEAR

GENERAL SHEET NOTES

LEVEL 1

LEVEL 2

LEVEL 2

LEVEL 3

LEVEL 3

LEVEL 4

LEVEL 4

ROOF

CRITICAL

BDM2CH

1000A

480-277V

3PH/4W

ATS-BCA

1000A

4P

LTG

TBPE2CLA/B

75kVA

PWR PWR

EQUIPMENT

BDM2EHA

1600A

480-277V

3PH/4W

ATS-BEB

1600A

4P

PWR PWR

TBPE1CLA/B

75kVA

PWR

PWR

TBPE2CLC/D

75kVA

PWR

PWR

TBPE1CLC/D

75kVA

TBPE2CLE/F

75kVA

PWR

A1000

A1000

A150

T75D

A150V1

T75DV1 T75D

A225

T75D T75DV1

A150 A150V1 A125 A125

A225V1

A1600

A1600

1000-3

ACCH-2

CHWP-2

100-3

HHWP-2

30-3

CBWP-2

100-3

EH-2

PV BEQUIPMENT

BDM2EHB

600A

480-277V

3PH/4W

ATS-BEC

600A

4P

A600

A600

A400V1A400

A225

TBPE1ELA

45kVA

T45

TBPE1ELB

45kVA

T45

, E O

400 400 400

UPS A1

INPUT

UPS B1

INPUT

UPS A1/B1

BYPASS

1000-3

NON-COINCIDENT

LOAD

B-2

E519

SB4 SB5 SB6

DB8

DB9

DB10 DB12 DB14 DB19

DB11 DB13 DB15 DB17 DB18

DB16

DB20 DB21 DB22 DB23 DB24 DB25 DB26 DB27

SB7

MATCHLINE

MATCHLINE

300-3

A225

E530

A

SHEET NUMBER

PROJECT NUMBER

SEALS AND SIGNATURES

ISSUED FOR DATE

Pl ot

Da te:

IHS Whiteriver Hospital 200 W Hospital Drive Whiteriver, Arizona, 85941

IHS Project #: 131445 IHS Contract #: 75H70123R00008 IHS Award Date: 02/02/2024

455 NORTH THIRD STREET

SUITE 250

PHOENIX, AZ 85004

602.265.2200 smithgroup.com

Drawn By: Checked By:

BASED ON PROGRAM OF REQUIREMENTS DATED [ 03/26/22],

POR AMENDMENT DATED [ 02/03/25], AND ON SCHEMATIC

DRAWINGS APPROVED [11/19/24].

4/1 6/2

6 9

:57 :48

A M

ELECTRICAL ONE LINE

DIAGRAM - SES-B, 2 OF 2

E5.2.2CD

W hit tin gto n

14904.000 Whittington Baca

X FEEDER SCHEDULE

SHEET KEYNOTES

E519 PV CIRCUIT BREAKER SHALL BE LOCATED AT LAST BUSSED

SPACE. PROVIDE PERMANENT IDENTIFICATION PLAQUE

INDICATING THE FOLLOWING: PV POWER SOURCE - DO NOT

RELOCATE THIS CIRCUIT BREAKER

E530 PROVIDE SHUNT TRIP CIRCUIT BREAKER FOR INTERFACE

WITH BOILER EMERGENCY SHUTDOWN EPO SWITCHES.

REFER TO EMP2.2.G FOR ADDITIONAL INFORMATION.

SCALE: NOT TO SCALE1 ONE LINE DIAGRAM - SES-B, 2 OF 2

30-3 3#10 + 1#10 G, 3/4" C 100-3 3#1 + 1#8 G, 1 1/2" C

300-3 3#350KCMIL + 1#4 G, 3" C

400 2 SETS OF 4#3/0 + 1#3 G, (2) 2" C

1000-3 3 SETS OF 3#400KCMIL + 1#2/0 G, (3) 3" C

A125 4#2/0 + 1#6 G, 2" C A150 4#3/0 + 1#4 G, 2" C

A150V1 4#400KCMIL + 1#1/0 G, 2-1/2" C

A225 4#300KCMIL + 1#2 G, 2 1/2" C

A225V1 4#400KCMIL + 1#1/0 G, 2 1/2" C

A400 2 SETS OF 4#250KCMIL + 1#1 G, (2) 2 1/2" C

A400V1 2 SETS OF 4#500KCMIL + 1#2/0 G, (2) 3" C

A600 2 SETS OF 4#500KCMIL + 1#2/0 G, (2) 3" C

A1000 3 SETS OF 4#600KCMIL + 1#4/0 G, (3) 3 1/2" C

A1600 5 SETS OF 4#600KCMIL + 1#350KCMIL G, (5) 3 1/2" C

T45 45KVA TRANSFORMER, 480-208Y/120V, 3PH

PRIMARY FEEDER: 3#3 + 1#8 G, 1 1/4" C

SECONDARY FEEDER: 4#1/0 + 1#6 G, 2" C

BONDING JUMPERS & GROUNDING ELECTRODE

CONDUCTOR: #6

T75D 75KVA TRANSFORMER, 480-208Y/120V, 3PH

PRIMARY FEEDER: 3#1/0 + 1#6 G, 1 1/2" C

SECONDARY FEEDERS: 4#1/0 + 1#2 G, 2" C TO

EACH PANEL

BONDING JUMPERS & GROUNDING ELECTRODE

CONDUCTOR: #2

T75DV1 75KVA TRANSFORMER, 480-208Y/120V, 3PH

PRIMARY FEEDER: 3#3/0 + 1#4 G, 2" C

SECONDARY FEEDERS: 4#1/0 + 1#2 G, 2" C TO

EACH PANEL

BONDING JUMPERS & GROUNDING ELECTRODE

CONDUCTOR: #2

"A" DENOTES ALUMINUM CONDUCTORS, ALL OTHER CONDUCTORS SHALL BE COPPER

FINAL CONSTRUCTION DOCUMENTS 05MAR26

BID ADDENDUM-A 16APR26

A

A

LS

IG

/3

EN

L

CA

CPW3SHD

225A

FTL

SPD

LS

I

5/

CPW3SHE

225A

MLO

SPD

CPW3SHA

300A

FTL

CPW3SLA

400A

MCB/FTL

LS

I

0/

CPW3SLB

400A

MLO

CPW3SHB

300A

FTL

CPW3SLC

400A

MCB/FTL

LS

I

0/

CPW3SLD

400A

MLO

CPW3SHC

300A

FTL

CPW3SLE

400A

MCB/FTL

LS

I

0/

CPW3SLF

400A

MLO

CPW4SHD

125A

MLO

SPD

CPW4SHE

125A

MLO

SPD

CPW4SLA

225A

FTL

CPW4SHA

300A

MLO

CPW4SLB

225A

MLO

CPW4SLC

225A

FTL

CPW4SHB

300A

MLO

CPW4SLD

225A

MLO

CPW4SLE

400A

MCB/FTL

CPW4SHC

300A

MLO

CPW4SLF

400A

MLO

LS

IG

/3

CPT1SLA

150A

MCB

LS

I

5/

CPT2SLA

225A

MCB

CPT3SLA

80A

MLO

CPT4SLA

80A

MLO

LS

I

/3

M

M

M

M M M M

M

LS

I

5/

CP2SHA

125A

MLO

M

CP2SLA

150A

MCB

LS

I

5/

CPF2SHA

225A

MLO

M

CPF2SHA

225A

MCB

SPD

A.

B.

C.

D.

E.

F.

G.

H.

I.

J.

K.

L.

BASE BUILD SCOPE SHALL ONLY INCLUDE EMPTY CONDUITS

OF FEEDERS SHOWN ON THIS SHEET WITH FEEDER TAGS.

ADD ALTERNATE SCOPE SHALL INCLUDE PV PANELS,

CARPORTS, DC CONDUCTORS, INVERTERS, AC CONDUCTORS,

AC COMBINER BOXES, PV DISTRIBUTION BOARDS.

SEE DRAWING E0.1 FOR ABBREVIATIONS, SYMBOLS, GENERAL

NOTES.

THE CONTRACTOR SHALL COORDINATE EXACT LOCATION OF

EQUIPMENT POWER CONNECTIONS WITH EQUIPMENT

INSTALLER PRIOR TO ROUGH-IN.

COORDINATE FINAL LOCATION OF MECHANICAL EQUIPMENT

AND ASSOCIATED DISCONNECT SWITCHES, STARTERS, VFDS,

CONTROL POWER AND OTHER POWER REQUIREMENTS WITH

DIV 23 AND MECHANICAL DRAWINGS.

SEE MECHANICAL EQUIPMENT SCHEDULE FOR ASSOCIATED

OVERCURRENT DEVICES, DISCONNECT SWITCHES, STARTERS

AND WIRES.

VOLTAGE DROP SHALL BE LIMITED TO LESS THAN 3% FOR ALL

BRANCH CIRCUITS AND 2% FOR ALL FEEDERS.

CONTRACTOR SHALL COORDINATE AND FIELD VERIFY

REQUIREMENT OF NEUTRAL CONDUCTOR FOR ALL EQUIPMENT

AND PROVIDE NEUTRAL CONDUCTOR AS NECESSARY.

ALL LIFE SAFETY AND LIGHTING PANELBOARDS SHALL BE

EQUIPPED WITH TYPE 2 SPD.

ALL AUTOMATIC TRANSFER SWITCHES SHALL BE 4 POLE AND

EQUIPPED WITH BYPASS ISOLATION.

ALL UTILITY TRANSFORMERS DESCRIBED AS NAVOPACHE

TRANSFORMER TO BE COORDINATED WITH UTILITY AND

PROVIDED BY UTILITY. COORDINATE ALL FINAL REQUIREMENTS

AND AVAILABLE FAULT CURRENT CONTRIBUTIONS BASED ON

SUPPLIED EQUIPMENT. BASIS OF DESIGN 2500KVA, AND 5%Z.

ELECTRICAL EQUIPMENT SHALL BE CONFIGURED AS FOLLOWS:

-SERVICE ENTRANCE SECTIONS - UL891 REAR CONNECTED

SWITCHBOARD

-DISTRIBUTION SWITCHBOARDS WITH DRAWOUT CIRCUIT

BREAKERS - UL891 REAR CONNECTED SWITCHBOARD

-GENERATOR PARALLELING GEAR - UL1558 SWITCHGEAR

GENERAL SHEET NOTES

OPTIONAL

STANDBYE505

E502

M

NAVOPACHE

TRANSFORMER

CDM2SH

1000A

480-277V

3PH/4W

LEVEL 1

LEVEL 2

LEVEL 2

LEVEL 3

LEVEL 3

LEVEL 4

SES-C

3200A BUS

PER NEC 705.12(B)

480-277V/3PH/4W

ATS-CSA

1000A

4P

LTG

TCPW3SLA/B

112.5kVA

PWR

TCPW3SLC/D

112.5kVA

TCPW3SLE/F

112.5kVA

PWR PWR

LEVEL 4

ROOF

A300 A225

A225

A400

T112

A300

A300 A225

A225

A400

T112

A300

A300

A400

A400

T112

A300 A225

A225

A125 A125

A1000

A1000

TCPT2SLA

75kVA K13 T75V1

TCPT1SLA

45kVA K13 T45V1

IDF

MDF

E501

MAIN

SC1

DC1

SC2

DC2 DC3 DC4 DC6

DC5

MATCHLINE

MATCHLINE

(3)

E521

TCPW4SLE/F

112.5kVA

T112

DC7

TCP2SLA

45kVA

T45

PWR

A300

TCPT2SLA

400A/225AF

TCPT1SLA

200A/150AF

SEL-751

(3)(3)

DC7

TCPF2SHA

75kVA

T75

MOBILE CLINICS

& EVSE

(FAC BLDG)

A225

A225

CPF2SHA

400A/225AF

#2

A

SHEET NUMBER

PROJECT NUMBER

SEALS AND SIGNATURES

ISSUED FOR DATE

Pl ot

Da te:

IHS Whiteriver Hospital 200 W Hospital Drive Whiteriver, Arizona, 85941

IHS Project #: 131445 IHS Contract #: 75H70123R00008 IHS Award Date: 02/02/2024

455 NORTH THIRD STREET

SUITE 250

PHOENIX, AZ 85004

602.265.2200 smithgroup.com

Drawn By: Checked By:

BASED ON PROGRAM OF REQUIREMENTS DATED [ 03/26/22],

POR AMENDMENT DATED [ 02/03/25], AND ON SCHEMATIC

DRAWINGS APPROVED [11/19/24].

4/1 6/2

6 9

:57 :54

A M

ELECTRICAL ONE LINE

DIAGRAM - SES-C, 1 OF 2

E5.3.1CD

W hit tin gto n

14904.000 Whittington Baca

X FEEDER SCHEDULE

SHEET KEYNOTES

E501 NAVOPACHE UTILITY METER. METER SHALL BE EQUIPPED

WITH CAPABILITY TO INTERFACE WITH BMS. ELECTRICAL

CONTRACTOR SHALL PROVIDE REQUIRED CONDUIT AND

COMMUNICATION WIRING FROM METER TO POINT OF

INTERFACE WITH BMS.

E502 COMPLIANCE WITH "NEC 240.87 ARC ENERGY REDUCTION"

REQUIRED. REDUCTION METHOD SHALL ALLOW FOR

REQUIRED SELECTIVE DEVICE COORDINATION AND ARC

FLASH REQUIREMENTS. REFER TO ELECTRICAL

SPECIFICATIONS FOR ADDITIONAL INFORMATION.

E505 PROVIDE PERMANENT IDENTIFICATION PLAQUE INDICATING

THE FOLLOWING: ELECTRICAL SERVICE #3 OF 5.

GENERATORS LOCATED IN ELECTRICAL EQUIPMENT YARD,

GENERATOR DISCONNECTS LOCATED IN ADJACENT

ELECTRICAL ROOM IN GMDB. PV DISCONNECT LOCATED AT

END OF THIS ELECTRICAL EQUIPMENT LINEUP.

E521 PROVIDE RELAY PROTECTION ELEMENTS REQUIRED BY

UTILITY AND MULTIPLE GENERATOR AND PV MONITORING

AND CONTROL SYSTEM MANUFACTURER. INTEGRATE SEL

RELAY AND PROGRAMMING INTO MULTIPLE GENERATOR

AND PV MONITORING SYSTEM AND CIRCUIT BREAKER.

PROVIDE AND PROGRAM PROTECTION ELEMENT SET POINTS

AND LOGIC WITHIN THE RELAY. REFER TO SEL-751 DETAIL

FOR ADDITIONAL INFORMATION.

SCALE: NOT TO SCALE1 ONE LINE DIAGRAM - SES-C, 1 OF 2

80 4#3 + 1#8 G, 1 1/4" C A125 4#2/0 + 1#6 G, 2" C

A225 4#300KCMIL + 1#2 G, 2 1/2" C

A300 4#500KCMIL + 1#2 G, 3" C

A400 2 SETS OF 4#250KCMIL + 1#1 G, (2) 2 1/2" C

A1000 3 SETS OF 4#600KCMIL + 1#4/0 G, (3) 3 1/2" C

T45 45KVA TRANSFORMER, 480-208Y/120V, 3PH

PRIMARY FEEDER: 3#3 + 1#8 G, 1 1/4" C

SECONDARY FEEDER: 4#1/0 + 1#6 G, 2" C

BONDING JUMPERS & GROUNDING ELECTRODE

CONDUCTOR: #6

T45V1 45KVA TRANSFORMER, 480-208Y/120V, 3PH

PRIMARY FEEDER: 3#1 + 1#4 G, 1 1/2" C

SECONDARY FEEDER: 4#1/0 + 1#6 G, 2" C

BONDING JUMPERS & GROUNDING ELECTRODE

CONDUCTOR: #6

T75 75KVA TRANSFORMER, 480-208Y/120V, 3PH

PRIMARY FEEDER: 3#1/0 + 1#6 G, 1 1/2" C

SECONDARY FEEDER: 4#4/0 + 1#2 G, 2 1/2" C

BONDING JUMPERS & GROUNDING ELECTRODE

CONDUCTOR: #2

T75V1 75KVA TRANSFORMER, 480-208Y/120V, 3PH

PRIMARY FEEDER: 3#3/0 + 1#4 G, 2" C

SECONDARY FEEDER: 4#4/0 + 1#2 G, 2 1/2" C

BONDING JUMPERS & GROUNDING ELECTRODE

CONDUCTOR: #2

T112 112.5KVA TRANSFORMER, 480-208Y/120V, 3PH

PRIMARY FEEDER: 3#3/0 + 1#6 G, 2" C

SECONDARY FEEDER: 2 SETS OF 4#3/0 + 1#2 G, (2)

2" C

BONDING JUMPERS & GROUNDING ELECTRODE

CONDUCTOR: #2

"A" DENOTES ALUMINUM CONDUCTORS, ALL OTHER CONDUCTORS SHALL BE COPPER

FINAL CONSTRUCTION DOCUMENTS 05MAR26

BID ADDENDUM-A 16APR26

A

/3

EN

L

CB

CPW3CHD

225A

MLO/FTL

SPD

LS

I

5/

CPW3CHE

225A

MLO

SPD

CPW3CHA

150A

MLO

CPW3CLA

125A

MCB

LS

I

0/

CPW3CLB

125A

MCB

CPW3CHB

150A

MLO

CPW3CLC

125A

MCB

LS

I

0/

CPW3CLD

125A

MCB

CPW3CHC

150A

MLO

CPW3CLE

125A

MCB

LS

I

0/

CPW3CLF

125A

MCB

CPW4CHD

125A

MLO

SPD

CPW4CHE

125A

MLO

SPD

CPW4CLA

125A

MCB

CPW4CHA

150A

MLO

CPW4CLB

125A

MCB

CPW4CLD

125A

MCB

CPW4CHB

150A

MLO

CPW4CLC

125A

MCB

CPW4CLF

125A

MCB

CPW4CHC

150A

MLO

CPW4CLE

125A

MCB

LS

IG

/3

EN

L

CC

LS

I

5/

LS

I

5/

LS

I

5/

LS

I

0/

LS

I

5/

LS

I

0/

LS

I

0/

LS

I

5/

LS

I

5/

LS

I

/3

VFD

LS

I

0/

VFD

LS

I

/3

VFD

LS

I

0/

VFD

LS

I

0/

LS

I

5/

/1

IPP2A

10kVA 125A

MCB

IPP2B

10kVA 125A

MCB

P1

IPP2C

10kVA 125A

MCB

/1

/1

P2

/1

P3

/2

IPPLE

25kVA 150A

MCB

LS

IG

0/

EN

L

CD

LS

I

0/

LS

I

0/

CPW3EHA

400A

MLO

CPW4EHA

225A

MLO

CPW3EHB

250A

MLO

CPW4EHB

150A

MLO

LS

I

5/

LS

I

5/

LS

I

5/

BP2 UA2 UB2

LS

I

/3

M

M M M

M M

M M M M M M M M M M M M M

M M M M M

M M M M M M M M

SPD

CPW4ELB

150A

MCB

CPW4ELA

150A

MCB

CPW3ELA

150A

MCB

CPW3ELB

150A

MCB

CPW1EHD

500A

MCB

CPW1EHC

500A

MCB

LS

I

0/

LS

I

0/

M M

LS

I

LS

IG

0/

PVY

M

A.

B.

C.

D.

E.

F.

G.

H.

I.

J.

K.

L.

BASE BUILD SCOPE SHALL ONLY INCLUDE EMPTY CONDUITS

OF FEEDERS SHOWN ON THIS SHEET WITH FEEDER TAGS.

ADD ALTERNATE SCOPE SHALL INCLUDE PV PANELS,

CARPORTS, DC CONDUCTORS, INVERTERS, AC CONDUCTORS,

AC COMBINER BOXES, PV DISTRIBUTION BOARDS.

SEE DRAWING E0.1 FOR ABBREVIATIONS, SYMBOLS, GENERAL

NOTES.

THE CONTRACTOR SHALL COORDINATE EXACT LOCATION OF

EQUIPMENT POWER CONNECTIONS WITH EQUIPMENT

INSTALLER PRIOR TO ROUGH-IN.

COORDINATE FINAL LOCATION OF MECHANICAL EQUIPMENT

AND ASSOCIATED DISCONNECT SWITCHES, STARTERS, VFDS,

CONTROL POWER AND OTHER POWER REQUIREMENTS WITH

DIV 23 AND MECHANICAL DRAWINGS.

SEE MECHANICAL EQUIPMENT SCHEDULE FOR ASSOCIATED

OVERCURRENT DEVICES, DISCONNECT SWITCHES, STARTERS

AND WIRES.

VOLTAGE DROP SHALL BE LIMITED TO LESS THAN 3% FOR ALL

BRANCH CIRCUITS AND 2% FOR ALL FEEDERS.

CONTRACTOR SHALL COORDINATE AND FIELD VERIFY

REQUIREMENT OF NEUTRAL CONDUCTOR FOR ALL EQUIPMENT

AND PROVIDE NEUTRAL CONDUCTOR AS NECESSARY.

ALL LIFE SAFETY AND LIGHTING PANELBOARDS SHALL BE

EQUIPPED WITH TYPE 2 SPD.

ALL AUTOMATIC TRANSFER SWITCHES SHALL BE 4 POLE AND

EQUIPPED WITH BYPASS ISOLATION.

ALL UTILITY TRANSFORMERS DESCRIBED AS NAVOPACHE

TRANSFORMER TO BE COORDINATED WITH UTILITY AND

PROVIDED BY UTILITY. COORDINATE ALL FINAL REQUIREMENTS

AND AVAILABLE FAULT CURRENT CONTRIBUTIONS BASED ON

SUPPLIED EQUIPMENT. BASIS OF DESIGN 2500KVA, AND 5%Z.

ELECTRICAL EQUIPMENT SHALL BE CONFIGURED AS FOLLOWS:

-SERVICE ENTRANCE SECTIONS - UL891 REAR CONNECTED

SWITCHBOARD

-DISTRIBUTION SWITCHBOARDS WITH DRAWOUT CIRCUIT

BREAKERS - UL891 REAR CONNECTED SWITCHBOARD

-GENERATOR PARALLELING GEAR - UL1558 SWITCHGEAR

GENERAL SHEET NOTES

CRITICAL

CDM2CH

1000A

480-277V

3PH/4W

ATS-CCA

1000A

4P

LTG

TCPW3CLA/B

75kVA

PWR PWR PWR

EQUIPMENT

CDM2EHA

1600A

480-277V

3PH/4W

ATS-CEA

1600A

4P

PWR

TCPW3CLC/D

75kVA

PWR

TCPW3CLE/F

75kVA

PWR

TCPW4CLA/B

75kVA

TCPW4CLC/D

75kVA

TCPW4CLE/F

75kVA

PWR PWR PWR PWRPWR PWR

A1000

A1000

A1600

A1600

A150 T75D

T75D

A150 A150 T75D

T75D

A150 A150 T75D

T75D

A150 A225

A225

A125 A125

1000-3

ACCH-3

CHWP-3

100-3

HHWP-3

30-3

CBWP-3

100-3

EWH-3

OR PWR

FESS-1

80kVA

INPUT

OUTPUT

CDSUR1

400A 480V

3PH/4W

50-2

SUR-2268

50-2 50-2 50-2 80-2

OR LASER

EQUIPMENT

IPP3B

SUR-2267

225-3

EQUIPMENT

CDM2EHB

600A

480-277V

3PH/4W

ATS-CEB

600A

4P

A600

A600

A250A300

A225 A150

IPP1B

SUR-2272

225V1 225V1 225V1

UPS B2

INPUT

UPS A2/B2

BYPASS

UPS A2

INPUT

1000-3

NON-COINCIDENT

LOAD

B-3

SC3

DC22 DC18 DC19

SC4 SC5

DC7 DC8 DC9 DC10 DC11 DC12 DC13 DC14 DC15 DC20 DC21

DC16 DC17

DC23 DC24 DC25 DC26 DC27

DC28 DC29 DC30 DC31 DC32 DC33 DC34 DC35

MATCHLINE

MATCHLINE

TCPW4ELB

45kVA

T45

TCPW4ELA

45kVA

T45

TCPW4ELA

45kVA

T45

TCPW3ELB

45kVA

T45

300-3

TCPW1EHD

150kVA K-13

ISO XFMR

TCPW1EHC

150kVA K-13

ISO XFMR

IMAGING IMAGING

T150NT150N

DC36 DC37

PV C

, E O

E519

SC6

LEVEL 1

LEVEL 2

LEVEL 2

LEVEL 3

LEVEL 3

LEVEL 4

LEVEL 4

ROOF

E530

A

SHEET NUMBER

PROJECT NUMBER

SEALS AND SIGNATURES

ISSUED FOR DATE

Pl ot

Da te:

IHS Whiteriver Hospital 200 W Hospital Drive Whiteriver, Arizona, 85941

IHS Project #: 131445 IHS Contract #: 75H70123R00008 IHS Award Date: 02/02/2024

455 NORTH THIRD STREET

SUITE 250

PHOENIX, AZ 85004

602.265.2200 smithgroup.com

Drawn By: Checked By:

BASED ON PROGRAM OF REQUIREMENTS DATED [ 03/26/22],

POR AMENDMENT DATED [ 02/03/25], AND ON SCHEMATIC

DRAWINGS APPROVED [11/19/24].

4/1 6/2

6 9

:58 :00

A M

ELECTRICAL ONE LINE

DIAGRAM - SES-C, 2 OF 2

E5.3.2CD

W hit tin gto n

14904.000 Whittington Baca

X FEEDER SCHEDULE

SHEET KEYNOTES

E519 PV CIRCUIT BREAKER SHALL BE LOCATED AT LAST BUSSED

SPACE. PROVIDE PERMANENT IDENTIFICATION PLAQUE

INDICATING THE FOLLOWING: PV POWER SOURCE - DO NOT

RELOCATE THIS CIRCUIT BREAKER

E530 PROVIDE SHUNT TRIP CIRCUIT BREAKER FOR INTERFACE

WITH BOILER EMERGENCY SHUTDOWN EPO SWITCHES.

REFER TO EMP2.2.G FOR ADDITIONAL INFORMATION.

30-3 3#10 + 1#10 G, 3/4" C 50-2 2#6 + 1#10 G, 3/4" C 80-2 2#3 + 1#8 G, 1 1/4" C 100-3 3#1 + 1#8 G, 1 1/2" C 225-3 3#4/0 + 1#4 G, 2" C

225V1 4#250KCMIL + 1#3 G, 2 1/2" C

300-3 3#350KCMIL + 1#4 G, 3" C

400 2 SETS OF 4#3/0 + 1#3 G, (2) 2" C

1000-3 3 SETS OF 3#400KCMIL + 1#2/0 G, (3) 3" C

A125 4#2/0 + 1#6 G, 2" C A150 4#3/0 + 1#4 G, 2" C

A225 4#300KCMIL + 1#2 G, 2 1/2" C

A250 4#350KCMIL + 1#2 G, 2 1/2" C

A300 4#500KCMIL + 1#2 G, 3" C

A600 2 SETS OF 4#500KCMIL + 1#2/0 G, (2) 3" C

A1000 3 SETS OF 4#600KCMIL + 1#4/0 G, (3) 3 1/2" C

A1600 5 SETS OF 4#600KCMIL + 1#350KCMIL G, (5) 3 1/2" C

T45 45KVA TRANSFORMER, 480-208Y/120V, 3PH

PRIMARY FEEDER: 3#3 + 1#8 G, 1 1/4" C

SECONDARY FEEDER: 4#1/0 + 1#6 G, 2" C

BONDING JUMPERS & GROUNDING ELECTRODE

CONDUCTOR: #6

T75D 75KVA TRANSFORMER, 480-208Y/120V, 3PH

PRIMARY FEEDER: 3#1/0 + 1#6 G, 1 1/2" C

SECONDARY FEEDERS: 4#1/0 + 1#2 G, 2" C TO

EACH PANEL

BONDING JUMPERS & GROUNDING ELECTRODE

CONDUCTOR: #2

T150N 150KVA TRANSFORMER, 480-208Y/120V, 3PH

PRIMARY FEEDER: 3#250KCMIL + 1#4 G, 2 1/2" C

SECONDARY FEEDER: 2 SETS OF 3#250KCMIL,

1#500KCMIL N + 1/0 G, (2) 3" C

BONDING JUMPERS & GROUNDING ELECTRODE

CONDUCTOR: #1/0

SCALE: NOT TO SCALE1 ONE LINE DIAGRAM - SES-C, 2 OF 2

"A" DENOTES ALUMINUM CONDUCTORS, ALL OTHER CONDUCTORS SHALL BE COPPER

FINAL CONSTRUCTION DOCUMENTS 05MAR26

BID ADDENDUM-A 16APR26

A

A

0/

EN

L

DA

DPE1LHA

60A

MLO

SPD

DPE1LLA

60A

MLO

SPD

DPE2LHA

80A

MLO

SPD

DPE2LLA

60A

MCB

SPD

DPE3LHA

225A

MLO

SPD

DPE3LLA

60A

MCB

SPD

DPE4LHA

60A

MLO

SPD

DPE4LLA

60A

MLO

SPD

LSIG

2500/3

LS

IG

/3

EN

L

DB

DPE3SHC

225A

FTL

SPD

LS

I

5/

DPE3SHD

225A

MLO

SPD

DPE3SHA

300A

FTL

DPE3SLA

400A

MCB/FTL

LS

I

0/

DPE3SLB

400A

MLO

DPE3SHB

300A

FTL

DPE3SLC

400A

MCB/FTL

LS

I

0/

DPE3SLD

400A

MLO

DPE4SHC

125A

MLO

SPD

DPE4SHD

125A

MLO

SPD

DPE4SLA

400A

MCB/FTL

DPE4SHA

300A

MLO

DPE4SLB

400A

MLO

DPE4SLC

400A

MCB/FTL

DPE4SHB

300A

MLO

DPE4SLD

400A

MLO

LS

IG

/3

M

M M

M M M

DPF2LHA

200A

MLO

SPD

0/

DPF2LLA

100A

MCB

SPD

5/

SPD

A.

B.

C.

D.

E.

F.

G.

H.

I.

J.

K.

L.

BASE BUILD SCOPE SHALL ONLY INCLUDE EMPTY CONDUITS

OF FEEDERS SHOWN ON THIS SHEET WITH FEEDER TAGS.

ADD ALTERNATE SCOPE SHALL INCLUDE PV PANELS,

CARPORTS, DC CONDUCTORS, INVERTERS, AC CONDUCTORS,

AC COMBINER BOXES, PV DISTRIBUTION BOARDS.

SEE DRAWING E0.1 FOR ABBREVIATIONS, SYMBOLS, GENERAL

NOTES.

THE CONTRACTOR SHALL COORDINATE EXACT LOCATION OF

EQUIPMENT POWER CONNECTIONS WITH EQUIPMENT

INSTALLER PRIOR TO ROUGH-IN.

COORDINATE FINAL LOCATION OF MECHANICAL EQUIPMENT

AND ASSOCIATED DISCONNECT SWITCHES, STARTERS, VFDS,

CONTROL POWER AND OTHER POWER REQUIREMENTS WITH

DIV 23 AND MECHANICAL DRAWINGS.

SEE MECHANICAL EQUIPMENT SCHEDULE FOR ASSOCIATED

OVERCURRENT DEVICES, DISCONNECT SWITCHES, STARTERS

AND WIRES.

VOLTAGE DROP SHALL BE LIMITED TO LESS THAN 3% FOR ALL

BRANCH CIRCUITS AND 2% FOR ALL FEEDERS.

CONTRACTOR SHALL COORDINATE AND FIELD VERIFY

REQUIREMENT OF NEUTRAL CONDUCTOR FOR ALL EQUIPMENT

AND PROVIDE NEUTRAL CONDUCTOR AS NECESSARY.

ALL LIFE SAFETY AND LIGHTING PANELBOARDS SHALL BE

EQUIPPED WITH TYPE 2 SPD.

ALL AUTOMATIC TRANSFER SWITCHES SHALL BE 4 POLE AND

EQUIPPED WITH BYPASS ISOLATION.

ALL UTILITY TRANSFORMERS DESCRIBED AS NAVOPACHE

TRANSFORMER TO BE COORDINATED WITH UTILITY AND

PROVIDED BY UTILITY. COORDINATE ALL FINAL REQUIREMENTS

AND AVAILABLE FAULT CURRENT CONTRIBUTIONS BASED ON

SUPPLIED EQUIPMENT. BASIS OF DESIGN 2500KVA, AND 5%Z.

ELECTRICAL EQUIPMENT SHALL BE CONFIGURED AS FOLLOWS:

-SERVICE ENTRANCE SECTIONS - UL891 REAR CONNECTED

SWITCHBOARD

-DISTRIBUTION SWITCHBOARDS WITH DRAWOUT CIRCUIT

BREAKERS - UL891 REAR CONNECTED SWITCHBOARD

-GENERATOR PARALLELING GEAR - UL1558 SWITCHGEAR

GENERAL SHEET NOTES

LIFE

SAFETY

ATS-DLA

400A

4P

TDPE2LLA

15kVA

OPTIONAL

STANDBYE506

E502

M

NAVOPACHE

TRANSFORMER

DDM2SH

1000A

480-277V

3PH/4W

LEVEL 1

LEVEL 2

LEVEL 2

LEVEL 3

LEVEL 3

LEVEL 4

ATS-DSA

1000A

4P

LTG

TDPE3SLA/B

112.5kVA

PWR

TDPE3SLC/D

112.5kVA

PWR

ATS-DCA

1000A

4P

LEVEL 4

ROOF

A400

T15

A225V2

A1000

A1000 A1000

A400

A400

T112

A300V1

A300

A400

A400

T112

A300V2 A225V1

A225

A125 A1256060

E501

MAIN

SD1

SD2 SD3

DD1 DD2 DD3

MATCHLINE

MATCHLINE

TDPF2LLA

30kVA

T30

FAC BLDG

A200

A200

DDM2LH

400A 480-277V

3PH/4W

A400

A300

TDPE4SLA/B

112.5kVA

T112

#2

DPF2LHA

200A/200AF

TDPE3LLA

15kVA

T15

TDPE4SLC/D

112.5kVA

T112

SES-D

3200A BUS

PER NEC 705.12(B)

480-277V/3PH/4W (3)

E521

SEL-751

(3)(3)

A

SHEET NUMBER

PROJECT NUMBER

SEALS AND SIGNATURES

ISSUED FOR DATE

Pl ot

Da te:

IHS Whiteriver Hospital 200 W Hospital Drive Whiteriver, Arizona, 85941

IHS Project #: 131445 IHS Contract #: 75H70123R00008 IHS Award Date: 02/02/2024

455 NORTH THIRD STREET

SUITE 250

PHOENIX, AZ 85004

602.265.2200 smithgroup.com

Drawn By: Checked By:

BASED ON PROGRAM OF REQUIREMENTS DATED [ 03/26/22],

POR AMENDMENT DATED [ 02/03/25], AND ON SCHEMATIC

DRAWINGS APPROVED [11/19/24].

4/1 6/2

6 9

:58 :05

A M

ELECTRICAL ONE LINE

DIAGRAM - SES-D, 1 OF 2

E5.4.1CD

W hit tin gto n

14904.000 Whittington Baca

X FEEDER SCHEDULE

SHEET KEYNOTES

E501 NAVOPACHE UTILITY METER. METER SHALL BE EQUIPPED

WITH CAPABILITY TO INTERFACE WITH BMS. ELECTRICAL

CONTRACTOR SHALL PROVIDE REQUIRED CONDUIT AND

COMMUNICATION WIRING FROM METER TO POINT OF

INTERFACE WITH BMS.

E502 COMPLIANCE WITH "NEC 240.87 ARC ENERGY REDUCTION"

REQUIRED. REDUCTION METHOD SHALL ALLOW FOR

REQUIRED SELECTIVE DEVICE COORDINATION AND ARC

FLASH REQUIREMENTS. REFER TO ELECTRICAL

SPECIFICATIONS FOR ADDITIONAL INFORMATION.

E506 PROVIDE PERMANENT IDENTIFICATION PLAQUE INDICATING

THE FOLLOWING: ELECTRICAL SERVICE #4 OF 5.

GENERATORS LOCATED IN ELECTRICAL EQUIPMENT YARD,

GENERATOR DISCONNECTS LOCATED IN ADJACENT

ELECTRICAL ROOM IN GMDB. PV DISCONNECT LOCATED AT

END OF THIS ELECTRICAL EQUIPMENT LINEUP.

E521 PROVIDE RELAY PROTECTION ELEMENTS REQUIRED BY

UTILITY AND MULTIPLE GENERATOR AND PV MONITORING

AND CONTROL SYSTEM MANUFACTURER. INTEGRATE SEL

RELAY AND PROGRAMMING INTO MULTIPLE GENERATOR

AND PV MONITORING SYSTEM AND CIRCUIT BREAKER.

PROVIDE AND PROGRAM PROTECTION ELEMENT SET POINTS

AND LOGIC WITHIN THE RELAY. REFER TO SEL-751 DETAIL

FOR ADDITIONAL INFORMATION.

SCALE: NOT TO SCALE1 ONE LINE…