This federal contract opportunity solicitation seeks offers to complete renovation of the Base Maintenance Building at the Mike Monroney Aeronautical Center. The successful offeror will provide all labor, supplies, equipment, material and equipment to complete the renovation in accordance with the specifications and drawings included in solicitation number 6973GH-20-R-00062. The Department of Transportation Federal Aviation Administration Non-Franchise Acquisition Services is the contracting agency. Offerors should respond in accordance with the requirements, terms, and conditions set forth in the solicitation.
View the file
Other files for this federal contract opportunity
Show all 26
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Owner Architect
Set Number _________
RENOVATION OF BMB-15
(BASE MAINTENANCE BUILDING)
FEDERAL AVIATION ADMINISTRATION
6125 SW 68TH ST, OKLAHOMA CITY, OK
VOLUME 2 OF 2
FEDERAL AVIATION
ADMINISTRATION
A&E DIVISION, AMP-400
(405) 954-7552
LWPB ARCHITECTURE
5909 NW EXPRESSWAY, STE 600
OKLAHOMA CITY, OK 73132
(405) 722-7270 Job Number: 16-1335-G230E
Date: 12/20/19
MEP ENGINEER
CIVIL ENGINEER
BURNS & MCDONNELL
615 N HUDSON, STE 200
OKLAHOMA CITY, OK 73102
(405) 200-0306
KFC ENGINEERING
525 CENTRAL PARK DRIVE, STE 202
OKLAHOMA CITY, OK 73105
(405) 528-4596
MACARTHUR ASSOCIATED CONSULTANTS
25 NW 146TH ST
EDMOND, OK 73013
(405) 848-2471
STRUCTURAL ENGINEER
12/20/19
MATERIALS LEGEND SYMBOLS LEGEND ABBREVIATIONS
COMPLETE LISTING OF MATERIALS ON THE JOB.
STANDARD AND ARE NOT INTENDED AS A
NOTE: ABOVE MATERIAL INDICATIONS ARE
( DISCONTINUOUS MEMBER )
( CONTINUOUS MEMBER )
MISCELLANEOUS METAL
RIGID INSULATION BOARD
EARTH FILL
BATT INSULATION
ALUMINUM
FINISH WOOD
WOOD BLOCKING
WOOD FRAMING
INSULATED PANEL
PLYWOOD
LARGER SCALE DETAIL MARK
WALL SECTION CUT MARK
BUILDING SECTION CUT MARK
STRUCTURAL GRID COORDINATES
DOOR NUMBER
SQUARE CONCRETE COLUMN
WIDE FLANGE STEEL COLUMN
SQUARE STEEL COLUMN
ROUND STEEL COLUMN
FRAME PARTITION ( METAL STUD )
CONCRETE BLOCK
FOR PLANS AND DETAILS
GYPSUM BOARD
CONCRETE
FACE BRICK
EXISTING BUILDING TO BE MODIFIED
EXISTING BUILDING TO BE REMOVED
EXISTING BUILDING TO REMAIN
BENCHMARK / SPOT ELEVATION
FINISH GRADE CONTOUR
EXISTING TREE TO BE PROTECTED
EXISTING GRADE CONTOUR
EXISTING TREE TO BE REMOVED
PROPERTY LINE
PAVING ( CONCRETE )
PAVING ( ASPHALT )
CONCRETE WALK
TEST HOLE
NEW BUILDING
FENCE X X
15' OAK
18' ELM
EXISTING SPOT ELEVATION
FINISH SPOT ELEVATION
100.25
X
FRAME ELEVATION
PARTITION TYPE
ROOM NAME AND NUMBER
INTERIOR
ELEVATION REF.
1 SIM
A102 A103
DETAIL SECTION CUT MARK
Room name
1t
NORTH ARROW SYMBOLS
PLAN
NORTH
TRUE
NORTH
FOR DETAILS
SHEET WHERE
ELEV IS DRAWN
ELEV INDICATED
A5.1
EXTERIOR
ELEVATION REF.SHEET WHERE
ELEV IS DRAWN
ELEV INDICATED
A5.1
REF. CASEWORK
SECTION SHEETS
CASEWORK
SECTION
IDENTIFICATION
NUMBER512
1i
AB ABOVE
ADJ ADJUSTABLE
AFF ABOVE FINISH FLOOR
ALUM ALUMINUM
APPROX, APP APPROXIMATELY
ATFP, AT/FP ANTI-TERRORISM/FORCE PROTECTION
AWC ACOUSTICAL WALL COVERING
BLDG BUILDING
BM BENCH MARK
BRG BEARING
BTM BOTTOM
C CENTERLINE
CJ CONTROL JOINT
CLG CEILING
CMU CONCRETE MASONRY UNIT
COL COLUMN
CONC CONCRETE
CONT CONTINUOUS
DF DRINKING FOUNTAIN
DIA DIAMETER
DIM DIMENSION
DN DOWN
DTL DETAIL
DWR DRAWER
EJ, EXP JT EXPANSION JOINT
ELEC ELECTRICAL
ELEV ELEVATION
EQ EQUAL
EWC ELECTRIC WATER COOLER
EXIST, EXSTG EXISTING
EXT, EXTR EXTERIOR
FD FLOOR DRAIN
FE FIRE EXTINGUISHER
FEB FIRE EXTINGUISHER BRACKET
FEC FIRE EXTINGUISHER CABINET
FF, FIN FLR FINISH FLOOR
FH FIRE HYDRANT
FHC FIRE HOSE CABINET
FIO FOR INFORMATION ONLY
F FLOW LINE
GA GAUGE
GI GALVANIZED IRON
GWB, GYP BD GYPSUM BOARD
HC, HDCP HANDICAPPED (ACCESSIBLE)
HD HEAD
HDWR HARDWARE
HM HOLLOW METAL
HORIZ HORIZONTAL
HT HEIGHT
INSUL INSULATION
INT, INTR INTERIOR
JST JOIST
JT JOINT
LAM LAMINATE
LAV LAVATORY
LP LIGHT POLE
MATL MATERIAL
MAX MAXIMUM
MB MARKER BOARD
MECH MECHANICAL
MFR, MFG MANUFACTURER
MIN MINIMUM
MISC MISCELLANEOUS
MO MASONRY OPENING
NIC NOT IN CONTRACT
NO NUMBER
NTS NOT TO SCALE
OC ON CENTER
OPNG OPENING
OPP OPPOSITE
PL PLATE
PLYWD PLYWOOD
R RADIUS OR RISER
RE:, REF REFER
REINF REINFORCING / REINFORCED
REQD REQUIRED
RI ROUGH IN
RM ROOM
RO ROUGH OPENING
SB SMART BOARD
SC SOLID CORE
SCHED SCHEDULE / SCHEDULED
SIM SIMILAR
SJ SCORED JOINT
SPECS SPECIFICATIONS
SQ SQUARE
SS STAINLESS STEEL
STL STEEL
STRUCT STRUCTURAL
T TREAD
TB TACK BOARD
TOC TOP OF CURB
TOM TOP OF MASONRY
TOS TOP OF STEEL
TOW TOP OF WALL
TYP TYPICAL
UNO UNLESS NOTED OTHERWISE
VERT VERTICAL
WC WATER CLOSET
WD WOOD
L
L
SHEET WHERE DETAIL IS
DRAWN
DETAIL INDICATED
SHEET WHERE DETAIL
IS FIRST REFERENCED
EXISTING WALL
GYPSUM SHEATHING
SIM
A102A108
SIM
A102A108
SIM
A102A108
SIM
A102A108
NOTE: ADDITIONAL SYMBOLS/ABBREVIATIONS NOT SHOWN OR DEFINED WITHIN THIS SHEET MAY OCCUR AND ARE DEFINED ON OTHER DRAWINGS.
-/--- SHEET WHERE
VIEW IS DRAWN
VIEW INDICATED
3-DIMENSIONAL
ISOMETRIC VIEW REF.
3-DIMENSIONAL CAMERA/
PERSPECTIVE VIEW REF.
GENERAL
DIRECTION OF
VIEW
SHEET WHERE
VIEW IS DRAWN
VIEW INDICATED
GENERAL
DIRECTION OF
VIEW
3-DIMENSIONAL
ISOMETRIC NORTH
ARROW SYMBOL
PLAN
NORTH
REVIEWED BY
DRAWN BY:
DESIGNED BY:
PLOT SCALE:
DRAWING NO. AMP-400-E-
OF
LO
C
AL
F
IL
E:
PL
O
T D
AT
E:
LW
PB
J O
B N
O
C
EN
TR
AL
F
IL
E:
SIGNATURES AFFIXED BELOW INDICATE OFFICIAL
RECOMMENDATION AND APPROVAL OF ALL
DRAWINGS IN THIS SET AS INDEXED ON THIS SHEET
REVIEWED BY:
APPROVED BY:
TITLE: CHIEF, DESIGN BRANCH
TITLE: CHIEF, ENGR & CONST DIV. DATE: 382
A
B
C
D
E
F
G
A
B
C
D
E
F
G
TE
M
PL
AT
E:
SENSITIVE SECURITY INFORMATION WARNING: This record contains Sensitive Security Information that is controlled under 49 CFR parts 15 and 1520, except with written permission of the Secretary of Transportation. Unauthorized release may result in civil penalty or other action. For U.S. government agencies, public disclosure is governed by 5 U.S.C. 552 and 49 CFR 15 and 1520.
DEPARTMENT OF TRANSPORTATION
FEDERAL AVIATION ADMINISTRATION
MIKE MONRONEY AERONAUTICAL CENTER - OKLAHOMA CITY, OKLAHOMA
DATE:
APPROVED BY:
ISSUED BY
OFFICE OF:
FACILITY
MANAGEMENT
AMP-400
PROJECT MANAGER:
WORK REQUEST NO:
BASE MAINTENANCE BUILDING
PLOT DATE:
12/20/19
12" = 1'-0"
BI
M
FA
A M
M
AC
B as e M ai nt en an ce B ui ld in g/
M M
AC
-B
M B
R en ov at io n
Ty pe
B -A rc h.
rv t
1/
/2
:4 5:
P
M
1/24/2020 12:45:43 PM
RENOVATION OF BMB-15
(BASE MAINTENANCE BUILDING)
6125 SW 68TH ST, OKLAHOMA CITY, OK
VOLUME 2 DRAWINGS INDEX,
SYMBOLS AND ABBREVIATIONS
G−001BW
BW
2014-004363
-1
5-
G
0E
\\l w pb -fi le sr vr \F ed er al
FA
A\
FA
A
ID
IQ
\T O
B M
B R en ov at io n Ty pe B
\0
D w gs \0
Ar ch M
M
AC
-B M
B R en ov at io n Ty pe B
7.
rv t
LW
PB
0 1
6.
0 2
12/20/19
MONTE THURMAN,
AMP-400
2014-004363
MONTE THURMAN,
AMP-400
DRAWING INDEX - VOLUME 2
NUM NAME
TELECOMMUNICATIONS
T-001 COMMUNICATIONS & SECURITY LEGEND
T-101 COMMUNICATIONS FLOOR PLAN - BASEMENT - PHASE 1A
T-102 COMMUNICATION FLOOR PLAN - BASEMENT- PHASE 1B
T-103 COMMUNICATIONS FLOOR PLAN - BASEMENT- PHASE 2
T-113 COMMUNICATION FLOOR PLAN - FIRST FLOOR AREA C - PHASE 1A
T-117 COMMUNICATION FLOOR PLAN - FIRST FLOOR AREA B - PHASE 1B
T-118 COMMUNICATION FLOOR PLAN - FIRST FLOOR AREA C - PHASE 1B
T-119 COMMUNICATION FLOOR PLAN - FIRST FLOOR AREA D - PHASE 1B
T-121 COMMUNICATION FLOOR PLAN - FIRST FLOOR AREA A - PHASE 2
T-122 COMMUNICATION FLOOR PLAN - FIRST FLOOR AREA B - PHASE 2
T-401 ENLARGED COMMUNICATIONS PLANS
T-501 COMMUNICATIONS DETAILS
T-502 COMMUNICATIONS DETAILS
T-601 COMMUNICATIONS SCHEDULES
T-701 COMMUNICATIONS RISER
T-702 PUBLIC ADDRESS RISER
TY101 SECURITY FLOOR PLAN - BASEMENT- PHASE 1B
TY117 SECURITY FLOOR PLAN - FIRST FLOOR AREA B - PHASE 1B
TY118 SECURITY FLOOR PLAN - FIRST FLOOR AREA C - PHASE 1B
TY119 SECURITY FLOOR PLAN - FIRST FLOOR AREA D - PHASE 1B
TY121 SECURITY FLOOR PLAN - FIRST FLOOR AREA A - PHASE 2
TY122 SECURITY FLOOR PLAN - FIRST FLOOR AREA B - PHASE 2
TY201 SECURITY CONDUIT FLOOR PLAN - BASEMENT - PHASE 1B
TY217 SECURITY CONDUIT FLOOR PLAN - FIRST FLOOR AREA B - PHASE 1B
TY218 SECURITY CONDUIT FLOOR PLAN - FIRST FLOOR AREA C - PHASE 1B
TY219 SECURITY CONDUIT FLOOR PLAN - FIRST FLOOR AREA D - PHASE 1B
TY221 SECURITY CONDUIT FLOOR PLAN - FIRST FLOOR AREA A - PHASE 2
TY222 SECURITY CONDUIT FLOOR PLAN - FIRST FLOOR AREA B - PHASE 2
TY411 ENLARGED SECURITY PLANS - PHASE 1B
TY501 SECURITY DETAILS
TY502 SECURITY DETAILS
TY601 SECURITY SCHEDULES
DRAWING INDEX - VOLUME 2
NUM NAME
PL322 PLUMBING ROOF PLAN - AREA B - PHASE 2
ELECTRICAL
ES101 SITE LIGHTING PLAN
E-001 ELECTRICAL LEGEND
E-002 ELECTRICAL ABBREVIATIONS, AND GENERAL NOTES
E-100 OVERALL ELECTRICAL FLOOR PLAN
ED101 ELECTRICAL DEMOLITION FLOOR PLAN - BASEMENT - PHASE 1A
ED102 ELECTRICAL DEMOLITION FLOOR PLAN - BASEMENT - PHASE 1B
ED103 ELECTRICAL DEMOLITION FLOOR PLAN - BASEMENT - PHASE 2
ED113 ELEC DEMOLITION FLOOR PLAN - FIRST FLOOR AREA C - PHASE 1A
ED114 ELEC DEMOLITION FLOOR PLAN - FIRST FLOOR AREA D - PHASE 1A
ED117 ELEC DEMOLITION FLOOR PLAN - FIRST FLOOR AREA B - PHASE 1B
ED118 ELEC DEMOLITION FLOOR PLAN - FIRST FLOOR AREA C - PHASE 1B
ED119 ELEC DEMOLITION FLOOR PLAN - FIRST FLOOR AREA D - PHASE 1B
ED121 ELEC DEMOLITION FLOOR PLAN - FIRST FLOOR AREA A - PHASE 2
ED122 ELEC DEMOLITION FLOOR PLAN - FIRST FLOOR AREA B - PHASE 2
ED123 ELEC DEMOLITION FLOOR PLAN - FIRST FLOOR AREA C - PHASE 2
ED130 ELECTRICAL DEMOLITION FLOOR PLAN - ROOF - PHASE 1A
ED131 ELECTRICAL DEMOLITION FLOOR PLAN - ROOF - PHASE 1B
ED132 ELECTRICAL DEMOLITION FLOOR PLAN - ROOF - PHASE 2
ED600 DEMOLITION ELEC, MECH, & SHOP EQUIPMENT SCHEDULES
ED610 DEMOLITION ONE-LINE DIAGRAM - MCC - PHASE 1A
ED611 DEMOLITION ONE-LINE DIAGRAM - 600A AND 225A BUSWAY - PH 1A
ED612 DEMOLITION ONE-LINE DIAGRAM - MCC - PHASE 1B
ED613 DEMOLITION ONE-LINE DIAGRAM - 600A BUSWAY - PHASE 1B
ED621 DEMOLITION ONE-LINE DIAGRAM - MCC - PHASE 2
ED622 DEMOLITION ONE-LINE DIAGRAM - 600A BUSWAY - PHASE 2
ES101 SITE LIGHTING PLAN
EP101 POWER FLOOR PLAN - BASEMENT - PHASE 1A
EP102 POWER FLOOR PLAN - BASEMENT - PHASE 1B
EP103 POWER FLOOR PLAN - BASEMENT - PHASE 2
EP113 POWER FLOOR PLAN - FIRST FLOOR AREA C - PHASE 1A
EP114 POWER FLOOR PLAN - FIRST FLOOR AREA D - PHASE 1A
EP117 POWER FLOOR PLAN - FIRST FLOOR AREA B - PHASE 1B
EP118 POWER FLOOR PLAN - FIRST FLOOR AREA C - PHASE 1B
EP121 POWER FLOOR PLAN - FIRST FLOOR AREA A - PHASE 2
EP122 POWER FLOOR PLAN - FIRST FLOOR AREA B - PHASE 2
EP123 POWER FLOOR PLAN - FIRST FLOOR AREA C - PHASE 2
EP130 POWER FLOOR PLAN - ROOF - PHASE 1A
EP131 POWER FLOOR PLAN - ROOF - PHASE 1B
EP132 POWER FLOOR PLAN - ROOF - PHASE 2
EP411 ENLARGED POWER PLANS - PHASE 1B
EP412 ENLARGED POWER PLANS - PHASE 1B
EP413 ENLARGED POWER PLANS - PHASE 1B
EP421 ENLARGED POWER PLANS - PHASE 2
EP500 POWER DETAILS
EP600 MECHANICAL EQUIPMENT SCHEDULE
EP601 ELECTRICAL AND SHOP EQUIPMENT SCHEDULES
EP610 ELECTRICAL ONE-LINE DIAGRAM - MCC - PHASE 1A
EP611 ELECTRICAL ONE-LINE DIAGRAM - MSWB - PHASE 1A
EP612 ELECTRICAL ONE-LINE DIAGRAM - 600A BUSWAY - PHASE 1A
EP613 ELECTRICAL ONE-LINE DIAGRAM - 225A BUSWAY - PHASE 1A
EP614 ELECTRICAL ONE-LINE DIAGRAM - MCC - PHASE 1B
EP615 ELECTRICAL ONE-LINE DIAGRAM - MSWB - PHASE 1B
EP616 ELECTRICAL ONE-LINE DIAGRAM - 600A BUSWAY - PHASE 1B
EP621 ELECTRICAL ONE-LINE DIAGRAM - MSWB - PHASE 2
EP630 PANELBOARD SCHEDULES
EP631 PANELBOARD SCHEDULES
EP632 PANELBOARD SCHEDULES
EP633 PANELBOARD SCHEDULES
EG130 LIGHTNING PROTECTION & GROUNDING PLAN - PHASE 1B
EG131 LIGHTNING PROTECTION & GROUNDING PLAN - PHASE 2
EG500 GROUNDING DETAILS
EG501 GROUNDING DETAILS
EG701 GROUNDING RISER
EL101 LIGHTING FLOOR PLAN - BASEMENT - PHASE 1B
EL113 LIGHTING FLOOR PLAN - FIRST FLOOR AREA C - PHASE 1A
EL114 LIGHTING FLOOR PLAN - FIRST FLOOR AREA D - PHASE 1A
EL117 LIGHTING FLOOR PLAN - FIRST FLOOR AREA B - PHASE 1B
EL118 LIGHTING FLOOR PLAN - FIRST FLOOR AREA C - PHASE 1B
EL121 LIGHTING FLOOR PLAN - FIRST FLOOR AREA A - PHASE 2
EL122 LIGHTING FLOOR PLAN - FIRST FLOOR AREA B - PHASE 2
EL123 LIGHTING FLOOR PLAN - FIRST FLOOR AREA C - PHASE 2
EL600 LIGHTING FIXTURE SCHEDULE
EL610 LIGHTING SCHEDULES - PHASE 1A AND 1B
EL620 LIGHTING SCHEDULES - PHASE 2
DRAWING INDEX - VOLUME 2
NUM NAME
GENERAL
G−000 VOLUME 2 COVER SHEET
G−001 VOLUME 2 DRAWINGS INDEX, SYMBOLS AND ABBREVIATIONS
MECHANICAL
M-001 MECHANICAL NOTES, LEGEND, SYMBOLS & ABBREVIATIONS
M-300 MECHANICAL ENLARGED PLANS
M-301 MECHANICAL ENLARGED PLANS
M-400 CHILLED WATER FLOW DIAGRAM (MECHANICAL ROOM)
M-401 CHILLED WATER FLOW DIAGRAM (BUILDING)
M-402 HEATING WATER FLOW DIAGRAM (MECHANICAL ROOM)
M-403 HEATING WATER FLOW DIGRAM (BUILDING)
M-500 MECHANICAL DETAILS
M-501 MECHANICAL DETAILS
M-502 MECHANICAL DETAILS
M-503 MECHANICAL DETAILS
M-504 MECHANICAL DETAILS
M-600 MECHANICAL SCHEDULES
M-601 MECHANICAL SCHEDULES
M-602 MECHANICAL SCHEDULES
M-701 AHU-1 CONTROL SEQUENCE
M-702 AHU-2 CONTROL SEQUENCE
M-703 AHU-3 CONTROL SEQUENCE
M-704 VAV AND MAU CONTROLS SEQUENCE
M-705 CHILLED WATER CONTROL SEQUENCE
M-706 CHILLED WATER SYSTEM CONTROL POINTS LIST
M-707 CHILLER CONTROLLER- CONTROL POINTS LIST
M-708 HEATING WATER SYSTEM CONTROL SEQUENCE
MD101 MECHANICAL DEMOLITION FLOOR PLAN - BASEMENT - PHASE 1A
MD113 MECHANICAL DEMOLITION FLOOR PLAN - AREA C - PHASE 1A
MD114 MECHANICAL DEMOLITION FLOOR PLAN - AREA D - PHASE 1A
MD117 MECHANICAL DEMOLITION FLOOR PLAN - AREA B - PHASE 1B
MD118 MECHANICAL DEMOLITION FLOOR PLAN - AREA C - PHASE 1B
MD121 MECHANICAL DEMOLITION FLOOR PLAN - AREA A - PHASE 2
MD122 MECHANICAL DEMOLITION FLOOR PLAN - AREA B - PHASE 2
MD213 MECHANICAL DEMOLITION ROOF PLAN - AREA C - PHASE 1A
MD214 MECHANICAL DEMOLITION ROOF PLAN - AREA D - PHASE 1A
MD217 MECHANICAL DEMOLITION ROOF PLAN - AREA B - PHASE 1B
MD218 MECHANICAL DEMOLITION ROOF PLAN - AREA C - PHASE 1B
MD221 MECHANICAL DEMOLITION ROOF PLAN - AREA A - PHASE 2
MD222 MECHANICAL DEMOLITION ROOF PLAN - AREA B - PHASE 2
MH101 HVAC FLOOR PLAN - BASEMENT - PHASE 1A
MH113 HVAC FLOOR PLAN - AREA C - PHASE 1A
MH114 HVAC FLOOR PLAN - AREA D - PHASE 1A
MH117 HVAC FLOOR PLAN - AREA B - PHASE 1B
MH118 HVAC FLOOR PLAN - AREA C - PHASE 1B
MH121 HVAC FLOOR PLAN - AREA A - PHASE 2
MH122 HVAC FLOOR PLAN - AREA B - PHASE 2
MH213 MECHANICAL ROOF PLAN - AREA C - PHASE 1A
MH214 MECHANICAL ROOF PLAN - AREA D - PHASE 1A
MH218 MECHANICAL ROOF PLAN - AREA C - PHASE 1B
MH222 MECHANICAL ROOF PLAN - AREA B - PHASE 2
MP101 MECHANICAL PIPING FLOOR PLAN - BASEMENT - PHASE 1A
MP113 MECHANICAL PIPING FLOOR PLAN - AREA C - PHASE 1A
MP114 MECHANICAL PIPING FLOOR PLAN - AREA D - PHASE 1A
MP117 MECHANICAL PIPING FLOOR PLAN - AREA B - PHASE 1B
MP118 MECHANICAL PIPING FLOOR PLAN - AREA C - PHASE 1B
MP121 MECHANICAL PIPING FLOOR PLAN - AREA A - PHASE 2
MP122 MECHANICAL PIPING FLOOR PLAN - AREA B - PHASE 2
PLUMBING
P-001 PLUMBING NOTES, LEGEND, SYMBOLS & ABBREVIATIONS
P-400 PLUMBING ENLARGED PLANS
P-500 PLUMBING DETAILS
P-501 PLUMBING DETAILS
P-600 PLUMBING SCHEDULES
P-700 DOMESTIC WATER RISER DIAGRAMS
P-701 SANITARY/VENT RISER DIAGRAMS
PD101 PLUMBING DEMOLITION FLOOR PLAN - BASEMENT - PHASE 1A
PD113 PLUMBING DEMOLITION FLOOR PLAN - AREA C - PHASE 1A
PD114 PLUMBING DEMOLITION FLOOR PLAN - AREA D - PHASE 1A
PD118 PLUMBING DEMOLITION FLOOR PLAN - AREA C - PHASE 1B
PD121 PLUMBING DEMOLITION FLOOR PLAN - AREA A - PHASE 2
PL117 PLUMBING UNDERGROUND PLAN - AREA B - PHASE 1B
PL118 PLUMBING UNDERGROUND PLAN - AREA C - PHASE 1B
PL121 PLUMBING UNDERGROUND PLAN - AREA A - PHASE 2
PL122 PLUMBING UNDERGROUND PLAN - AREA B - PHASE 2
PL201 PLUMBING FLOOR PLAN - BASEMENT - PHASE 1B
PL217 PLUMBING FLOOR PLAN - AREA B - PHASE 1B
PL218 PLUMBING FLOOR PLAN - AREA C - PHASE 1B
PL221 PLUMBING FLOOR PLAN - AREA A - PHASE 2
PL222 PLUMBING FLOOR PLAN - AREA B - PHASE 2
PL317 PLUMBING ROOF PLAN - AREA B - PHASE 1B
PL318 PLUMBING ROOF PLAN - AREA C - PHASE 1B
PL321 PLUMBING ROOF PLAN - AREA A - PHASE 2
FA001 FIRE ALARM NOTES, LEGEND AND ABBREVIATIONS
FA100 FIRE ALARM BASEMENT - AREA C
FA111 FIRE ALARM - AREA A
FA112 FIRE ALARM - AREA B
FA113 FIRE ALARM - AREA C
FA114 FIRE ALARM - AREA D
FA200 FIRE ALARM NOTIFICATION PLAN - BASEMENT
FA201 FIRE ALARM NOTIFICATION PLAN - AREA A
FA202 FIRE ALARM NOTIFICATION PLAN - AREA B
FA203 FIRE ALARM NOTIFICATION PLAN - AREA C
FA204 FIRE ALARM NOTIFICATION PLAN - AREA D
FA501 FIRE ALARM DETAILS
FA601A FIRE ALARM RISER
FA601B FIRE ALARM MATRIX
FX001 FIRE SUPPRESSION NOTES, LEGEND AND ABBREVIATIONS
FX100 FIRE SUPPRESSION BASEMENT - AREA C
FX111 FIRE SUPPRESSION - AREA A
FX112 FIRE SUPPRESSION - AREA B
FX113 FIRE SUPPRESSION - AREA C
FX114 FIRE SUPPRESSION - AREA D
FX115 FIRE SUPPRESSION - EXISTING LAYOUT
FX601 FIRE SUPPRESSION ONE LINE DIAGRAM
FIRE PROTECTION
SYMBOL DESCRIPTION DATE APPR
PIPE SYMBOLS
PIPE ELBOW
PIPE DOWN
PIPE UP
PIPE CONTINUATION
HVAC LEGEND
M
CONTROL DAMPER, MOTOR
OPERATED
MANUAL BALANCE DAMPER
BD
BACKDRAFT DAMPER
AD
AD
ACCESS DOOR (AD)
ACCESS PANEL (AP)
S
AD
S
DAMPERS:
FIRE (F) -
SMOKE (S) -
FIRE SMOKE (F/S) -
AD
SECURITY BARS
FLEXIBLE DUCT CONNECTION
RECTANGLUAR ELBOW WITH
TURNING VANES
RECTANGULAR TEE WITH
TURNING VANES
RECTANGULAR RADIUS ELBOW
R RISE IN RESPECT TO AIR-FLOW
D DROP IN RESPECT TO AIR-FLOW
SQUARE OR RECTANGULAR TO
ROUND TRANSITION
SUPPLY AIR OR OUTSIDE AIR
RECTANGULAR DUCT SECTION
RETURN AIR RECTANGULAR
DUCT SECTION
EXHAUST AIR RECTANGULAR
DUCT SECTION
ROUND FLEXIBLE DUCT
(5'-0" MAX LENGTH)
SQUARE OR RECTANGULAR
SUPPLY DIFFUSER
RETURN AIR DIFFUSER
EXHAUST AIR DIFFUSER
T THERMOSTAT
CO2 CARBON DIOXIDE SENSOR
H HUMIDISTAT
LINEAR SLOT DIFFUSER
VAV-
VARIABLE AIR VOLUME
TERMINAL BOX
(3'-0") FINNED TUBE RADIATION.
LENGTH OF ELEMENT SHOWN
IN PARENTHESIS
ESS EMERGENCY SHUT-OFF SWITCH
M MOTOR
FCP FAN CONTROL PANEL
AIRFLOW ARROW
BA BREATHING AIR DROP
CA COMPRESSED AIR DROP
SUPPLY AIR OR OUTSIDE AIR
ROUND DUCT SECTION
RETURN AIR ROUND DUCT
SECTION
EXHAUST AIR ROUND DUCT
SECTION
DP DIFFERENTIAL PRESSURE
SENSOR
S STATIC PRESSURE SENSOR
OCC OCCUPANCY SENSOR
ROUND & RECTANGULAR DUCT
TAKEOFF
CO CARBON MONOXIDE SENSOR
PIPE LINE ACCESSORIES
3-WAY VALVE
2-WAY VALVE
ANGLE VALVE
AV
AUTOMATIC AIR VENT
ASSEMBLY
BFP
BACKFLOW PREVENTION
ASSEMBLY
BALANCING VALVE / CIRCUIT
SETTER
BALL VALVE
BLIND FLANGE
BUTTERFLY VALVE
CHECK VALVE
FLEX CONNECTION
FLOW ARROW
FM FLOW METER
GATE VALVE
GLOBE VALVE
HOSE GATE DRAIN VALVE
IF
INSULATING FLANGE
MV
MANUAL AIR VENT ASSEMBLY
- SEE SPECIFICATIONS FOR
APPROPRIATE VALVE TYPE
M METER
M MOTORIZED CONTROL VALVE
OS&Y OUTSIDE SCREW & YOKE VALVE
PIPE WITH HEAT TRACE
PLUG VALVE
PRESSURE GUAGE
SELF CONTAINED PRESSURE
REDUCING (REGULATING)
VALVE
PUMP
REDUCER (CONCENTRIC)
RELIEF, SAFETY OR THERMAL
RELIEF VALVE
REMOVABLE CAP
REMOVABLE PLUG
S STRAINER
SUCTION DIFFUSER
TEST CONNECTION
THERMOMETER
UNION
Y-TYPE STRAINER
SRC SPRING RETURN CLOSED BALL
VALVE
PIPELINE ABBREVIATIONS
MECHANICAL ABBREVIATIONS GENERAL NOTES:
DETAIL / ENLARGED
CALLOUT SYMBOL
A
M-001
INDICATES
LIMITS OF
DETAIL/SECTION
DETAIL/SECTION
DESIGNATOR
SHEET WHERE
DETAIL/SECTION IS
SHOWN
DETAIL/SECTION TITLE
TITLE
A1
LOCATION WHERE
DETAIL / SECTION
IS SHOWN ON
SHEET
SECTION CUT SYMBOL
A
M-001
INDICATES PERSPECTIVE
AND LIMITS OF SECTION
SECTION
DESIGNATOR
DRAWING WHERE
SECTION IS SHOWN
CONSTRUCTION INTERFACE
DEMOLITION
EXISTING
NEW
EXISTING
EXISTING
NEW
DEMOLITION
AIR DISTRIBUTION DEVICE
IDENTIFICATION
AIR FLOW NECK SIZE
QUANTITY
SYSTEM TYPE SPEC. TYPE
SA-
(2)175-8Ø
1. LEGEND IS GENERAL IN NATURE AND MAY INDICATE MORE INFORMATION THAN IS APPLICABLE TO PROJECT. SEE
PLANS FOR SPECIFIC SYMBOLS AND ABBREVIATIONS.
2. PROVIDE ALL MATERIALS, VALVES, HANGERS, ETC. AND EQUIPMENT AND PERFORM ALL LABOR REQUIRED TO INSTALL COMPLETE AND OPERABLE MECHANICAL SYSTEMS AS INDICATED ON THE DRAWINGS, AS SPECIFIED, AND
AS REQUIRED BY CODE.
3. INSTALL ALL MECHANICAL EQUIPMENT AND APPURTENANCES IN ACCORDANCE WITH MANUFACTURERS
RECOMMENDATIONS, CONTRACT DOCUMENTS, AND APPLICABLE CODES AND REGULATIONS.
4. COORDINATE CONSTRUCTION OF ALL MECHANICAL WORK WITH STRUCTURAL, CIVIL, ELECTRICAL WORK, ETC., SHOWN ON OTHER CONTRACT DOCUMENT DRAWINGS.
5. UNLESS OTHERWISE INDICATED MAINTAIN A MINIMUM OF 6'-8" CLEARANCE TO UNDERSIDE OF PIPES, CONDUITS, ETC., THROUGHOUT ACCESS ROUTES AND IN MECHANICAL ROOMS.
6. LOCATE ALL MECHANICAL EQUIPMENT FOR UNOBSTRUCTED ACCESS TO UNIT ACCESS PANELS, CONTROLS, AND
VALVING; COORDINATE WITH OTHER TRADES AS NECESSARY.
7. VERIFY DIMENSIONS AND CONNECTION SIZE WITH FURNISHED EQUIPMENT.
8. ALL ELEVATIONS ARE ABOVE FINISHED FLOOR TO BOTTOM OF DUCT, PIPE, OR PIPE INSULATION UNLESS NOTED
OTHERWISE.
9. DUCT DIMENSIONS INDICATED REFER TO SHEET METAL DIMENSIONS. SHEET METAL SIZE SHALL BE AIR OPENING DIMENSION PLUS THE THICKNESS OF ACOUSTICAL LINER WHERE LINER IS INSTALLED. WHERE LINER IS NOT
INSTALLED, AIR OPENING SIZE AND SHEET METAL SIZE SHALL BE THE SAME.
10. DUCT STATIC PRESSURE CLASSIFICATION: UNLESS OTHERWISE INDICATED, CONSTRUCT DUCTS ON THE DISCHARGE SIDE OF FANS AND VAV BOXES TO HAVE 1.0 IN. W.C. POSITIVE PRESSURE AND DUCTS ON THE INLET SIDE OF EQUIPMENT TO HAVE 1.0 IN. W.C. NEGATIVE PRESSURE CLASSIFICATIONS. DUCTS ON OUTLET SIDE OF
AHU'S SHALL HAVE 3.0 INCH POSITIVE PRESSURE CLASS DUCT.
11. LOCATE TRANSFER AIR DUCTS AND OPENINGS 24" ABOVE HIGHEST CEILING ELEVATION UNLESS OTHERWISE
NOTED.
12. COORDINATE ALL WALL AND ROOF PENETRATIONS WITH STRUCTURAL AND ARCHITECTURAL PLANS.
13. INSTALL TEMPERATURE CONTROLS AT 48" ABOVE FINISHED FLOOR; COORDINATE WITH THE FDA COR TO
ACCOMODATE SYSTEMS FURNITURE TO BE CONTRACTED SEPARATELY.
14. OCCUPANCY SENSORS SHALL BE PROVIDED BY DIVISION 26. WIRE OCCUPANCY SENSOR BACK TO CORRESPONDING VAV BOX AS SCHEDULED FOR VENTILATION CONTROL. WIRE CO2 SENSORS SHALL BE PROVIDED BY DIVISION 23. CO2 SENSOR BACK TO EMCS PANEL FOR ALARM. OCCUPANCY SENSORS SHALL NOT BE CLUSTERED TOGETHER. ARRANGE SENSORS AS NEEDED TO SERVE THEIR INTENDED PURPOSE. COORDINATE WITH
THE FAA COR.
15. PROVIDE STRUCTURAL EQUIPMENT PADS IN ACCORDANCE WITH STRUCTURAL DRAWINGS AND SPECIFICATIONS.
16. ALL EXISTING DUCTWORK SHOWN ON DRAWINGS IS SCHEMATIC AND ARE BASED ON EXISTING RECORD DRAWINGS PROVIDED BY THE OWNER AND DO NOT REFLECT EXACT EXISTING CONDITIONS. CONTRACTOR SHALL FIELD VERIFY ALL ACTUAL CONDITIONS ON JOB SITE. CONTRACTOR SHALL REROUTE NEW WORK TO ACCOMMODATE EXACT
LOCATIONS OF EXISTING UTILITIES, STUBOUTS, AND/OR CONNECTIONS.
17. CONTRACTOR SHALL AIR BALANCE ALL GRILLES TO CFM'S SHOWN ON PLANS.
18. MOUNT ALL OVERHEAD MECHANICAL EQUIPMENT AND FIXTURES WEIGHING 31 POUNDS OR MORE TO SUPPORTS THAT SHALL RESIST FORCES OF 0.5 TIMES THE EQUIPMENT WEIGHT IN ANY HORIZONTAL DIRECTION AND 1.5 TIMES
THE EQUIPMENT WEIGHT IN THE DOWNWARD DIRECTION.
19 PROVIDE FIRE STOPPING ON ALL PIPING PENETRATIONS OF FIRE RATED PARTITIONS. REFER TO ARCHITECTURAL
PLANS FOR WALL TYPES AND LOCATIONS.
BLWDN BLOWDOWN
CD CONDENSATE DRAIN
CHR CHILLED WATER RETURN
CHS CHILLED WATER SUPPLY
CR CONDENSATE RETURN
CT CHEMICAL TREATMENT
CTB COOLING TOWER BLOWDOWN
CWR CONDENSER WATER RETURN
CWS CONDENSER WATER SUPPLY
D DRAIN
DI DEIONIZED WATER
FOR FUEL OIL RETURN
FOS FUEL OIL SUPPLY
HPS HIGH PRESSURE STEAM
HWR HOT WATER RETURN
HWS HOT WATER SUPPLY
LPS LOW PRESSURE STEAM
MPS MEDIUM PRESSURE STEAM
MW MAKEUP WATER (AFTER
BACKFLOW PREVENTER)
N NITROGEN
NG NATURAL GAS
O OXYGEN
PCR PUMPED CONDENSATE RETURN
V VACUUM
IA INSTRUMENT AIR
IH INFRARED HEATER
IN. W.C INCHES WATER COLUMN
L LOUVER
LAT LEAVING AIR TEMPERATURE
LR LONG RADIUS
LWT LEAVING WATER TEMPERATURE
MA MIXED AIR
MAT MIXED AIR TEMPERATURE
MAU MAKEUP AIR UNIT
MFR MANUFACTURER
MJ MECHANICAL JOINT
MW MAKE-UP WATER (AFTER BACKFLOW
PREVENTER)
NC NORMALLY CLOSED (FAIL POSITION)
NG NATURAL GAS
NO NORMALLY OPEN (FAIL POSITION)
OA OUTSIDE AIR
OB OPPOSED BLADE
OD OVERFLOW DRAIN
PB PARALLEL BLADE
PCW PROCESS COLD WATER
PFX PLATE AND FRAME HEAT EXCHANGER
PSIA POUNDS PER SQUARE INCH ABSOLUTE
PSIG POUNDS PER SQUARE INCH GAUGE
RA RETURN AIR
RED REDUCER-REDUCING
RG REFRIGERANT HOT GAS DISCHARGE
RL REFRIGERANT LIQUID
RMJ RESTRAINED MECHANICAL JOINT
RS REFRIGERANT SUCTION
SA SUPPLY AIR
SCH SCHEDULE
SCR SPRING RETURN CLOSED
SHR SHORT RADIUS
SP STATIC PRESSURE SENSOR
SR SUPPLY REGISTER
ST STEAM TRAP
STM STEAM
SW SOCKET WELD
TA TRANSFER AIR
TOA TREATED OUTSIDE AIR
TOC TOP OF CONCRETE
TOD TOP OF DUCT
TOS TOP OF STEEL
UH UNIT HEATER
V VENT
VAV VARIABLE AIR VOLUME
VFD VARIABLE FREQUENCY DRIVE
VRF VARIABLE REFRIGERANT FLOW
WB WET BULB
WE WELD END
WN WELD NECK
12"Ø ROUND DUCT DIMENSION
24x12 RECTANGULAR DUCT DIMENSION
(INCHES)
ACU AIR CONDITIONING UNIT
AFF ABOVE FINISHED FLOOR
AFMS AIR FLOW MEASURING STATION
AHU AIR HANDLING UNIT
ARF ABOVE RAISED FLOOR
AS AIR SEPARATOR
BBO BOILER BLOW-OFF
BOD BOTTOM OF DUCT
BOP BOTTOM OF PIPE
BP BOOSTER PUMP
BS BRANCH SELECTOR (VRF SYSTEM)
CF CEILING FAN
CFM CUBIC FEET PER MINUTE
CHR CHILLED WATER RETURN
CHS CHILLED WATER SUPPLY
CL CENTER LINE OF PIPE ELEVATION
CONC CONCENTRIC
COND COOLING COIL CONDENSATE DRAIN
CRAC COMPUTER ROOM AIR CONDITIONER
CU CONDENSING UNIT
CUH CABINET UNIT HEATER
CV CONTROL VALVE
DB DRY BULB
DH DEHUMIDIFIER
DN DOWN
DRG DIFFUSER, REGISTER, GRILLE
EA EXHAUST AIR
EAT ENTERING AIR TEMPERATURE
EF EXHAUST FAN
EG EXHAUST GRILLE
EL ELEVATION
ELL ELBOW
EMCS ENERGY MANAGEMENT CONTROL
SYSTEM
ER EXHAUST REGISTER
ESP EXTERNAL STATIC PRESSURE
ET EXPANSION TANK
EWT ENTERING WATER TEMPERATURE
EXIST EXISTING
FCU FAN COIL UNIT
FD FEEDWATER
FF FLAT FACED
FO FLAT OVAL
FOB FLAT ON BOTTOM
FOT FLAT ON TOP
HWB HEATING HOT WATER BOILER
HWP HEATING HOT WATER PUMP
HWR HEATING HOT WATER RETURN
HWS HEATING HOT WATER SUPPLY
I.E. INVERT ELEVATION
REVIEWED BY
DRAWN BY:
DESIGNED BY:
PLOT DATE: PLOT SCALE:
DRAWING NO. AMP-400-E-
OF
P L O
T D
A T
E
C E
N T
R A
L F
IL
E
A
B
C
D
E
F
G
A
B
C
D
E
F
G
SENSITIVE SECURITY INFORMATION WARNING: This record contains Sensitive Security Information that is controlled under 49 CFR parts 15 and 1520, except with written permission of the Secretary of Transportation. Unauthorized release may result in civil penalty or other action. For U.S. government agencies, public disclosure is governed by 5 U.S.C. 552 and 49 CFR 15 and 1520.
DEPARTMENT OF TRANSPORTATION
FEDERAL AVIATION ADMINISTRATION
MIKE MONRONEY AERONAUTICAL CENTER - OKLAHOMA CITY, OKLAHOMA
DATE:
APPROVED BY:
ISSUED BY
OFFICE OF:
FACILITY
MANAGEMENT
AMP-400
PROJECT MANAGER:
WORK REQUEST NO:
BASE MAINTENANCE BUILDING
C O
P Y
R
IG
H T
B U
R N
S
M c D
O N
N E
L L
E N
G
IN
E E
R
IN
G C
O M
P A
N Y
IN
C
1/16/2020 8:48:22 AM
/1
/2
:4
:2
A
M
RENOVATION OF BMB-15
(BASE MAINTENANCE BUILDING)
6125 SW 68TH ST, OKLAHOMA CITY, OK
MECHANICAL NOTES, LEGEND,
SYMBOLS & ABBREVIATIONS
M-001A. SHUPE
C. BOALDIN
2014-004363
M M
A C
-B M
B R e n o v a tio n T y p e B
-M e c h
.r v t
12/20/2019
MONTE THURMAN,
AMP-400
2014-004363
MONTE THURMAN,
AMP-400
176 382
A B
A.5
4.7
5.4
3.7
MH101
M-301
M-300 ø
O A
B O
D E
L
10ø OA 13' - 0" BOD EL 6ø OA
13' - 8" BOD EL
32x16 OA
12' - 6" BOD EL
x R
A
B O
D E
L
48x18 RA
11' - 9" BOD EL
32x16 OA
8' - 4" BOD EL
x R
A
B O
D E
L
AHU-1
8ø EA
10' - 0" BOD EL
C H
W R
U P
6" CHWR UP
HWSP-01 HWSP-02 CHWP-01
CHWP-02
CHWSP-01
CHWSP-02
B-2 B-1
VAV-B1
x S
A
B O
D E
L x S
A
B O
D E
L ø
S A
B O
D E
L
3/4" HWR UP
3/4" HWS UP
4" HWR UP
4" HWS UP
6" CHWS UP
C H
W R
U P
M-300
AUX. CHW
CONNECTIONS
ET-02
3' - 5"
C H
W S
U P
60x28 RA
11' - 4" BOD EL
M-301 ø
O A
6ø OA
6ø OA
8ø EA
FIRST FLOOR -
FINISH FLOOR
100'-0"
Avg. B.O. Footing - Level 1
91'-6"
BASEMENT -
FINISH FLOOR
84'-0"
LEVEL 1
100' - 0"
BASEMENT - FINISH FLOOR
84' - 0"
LEVEL 1
100' - 0"
BASEMENT - FINISH FLOOR
84' - 0"
AUXILIARY CHWR
CONNECTION
AUXILIARY CHWS
CONNECTION
6" VICTAULIC
GROOVED PIPE
CONNECTIONS
6" ISOLATION
VALVE
60x28 RA
11' - 4" BOD EL
6" CHWS UP
FIRST FLOOR -
FINISH FLOOR
100'-0"
Avg. B.O. Footing - Level 1
91'-6"
A
BASEMENT -
FINISH FLOOR
84'-0"
LEVEL 1
100' - 0"
BASEMENT - FINISH FLOOR
84' - 0"
AA
LEVEL 1
100' - 0"
BASEMENT - FINISH FLOOR
84' - 0"
A
MH101
REVIEWED BY
DRAWN BY:
DESIGNED BY:
PLOT DATE: PLOT SCALE:
DRAWING NO. AMP-400-E-
OF
P L O
T D
A T
E
C E
N T
R A
L F
IL
A
B
C
D
E
F
G
A
B
C
D
E
F
G
SENSITIVE SECURITY INFORMATION WARNING: This record contains Sensitive Security Information that is controlled under 49 CFR parts 15 and 1520, except with written permission of the Secretary of Transportation. Unauthorized release may result in civil penalty or other action. For U.S. government agencies, public disclosure is governed by 5 U.S.C. 552 and 49 CFR 15 and 1520.
DEPARTMENT OF TRANSPORTATION
FEDERAL AVIATION ADMINISTRATION
MIKE MONRONEY AERONAUTICAL CENTER - OKLAHOMA CITY, OKLAHOMA
DATE:
APPROVED BY:
ISSUED BY
OFFICE OF:
FACILITY
MANAGEMENT
AMP-400
PROJECT MANAGER:
WORK REQUEST NO:
BASE MAINTENANCE BUILDING
C O
P Y
R
IG
H T
B U
R N
S
M c D
O N
N E
L L
E N
G
IN
E E
R
IN
G C
O M
P A
N Y
IN
C
A
B
C D
KEYPLAN
1/4" = 1'-0"1/16/2020 8:48:27 AM
/1
/2
:4
:2
A
M
RENOVATION OF BMB-15
(BASE MAINTENANCE BUILDING)
6125 SW 68TH ST, OKLAHOMA CITY, OK
MECHANICAL ENLARGED PLANS
M-300A. SHUPE
C. BOALDIN
2014-004363
M M
A C
-B M
B R e n o v a tio n T y p e B
-M e c h
.r v t
12/20/2019
MONTE THURMAN,
AMP-400
2014-004363
MONTE THURMAN,
AMP-400
SCALE: 1/4" = 1'-0"MP101 M-300
MECHANICAL ENLARGED PLAN (BASEMENT
MECHANICAL ROOM) - PHASE 1B
SCALE: 1/4" = 1'-0"M-300 M-300
2 AUXILIARY CHW CONNECTIONS
GENERAL NOTES:
1. REFER TO MECHANICAL GENERAL NOTES ON SHEET M-001.
2. REFER TO DIFFUSER SCHEDULE FOR ALL INDIVIDUAL RUNOUTS.
3. REFER TO MECHANICAL PIPING DRAWINGS FOR THERMOSTAT
LOCATIONS.
4. REFER TO MP101 AND MH101 FOR CONTINUATION OF BASEMENT
FLOOR PLAN.
KEYED NOTES:
INSTALL NEW AUXILIARY CHILLED WATER RETURN AND SUPPLY
CONNECTIONS WITH ISOLATION VALVES AND VICTAULIC GROOVE
PIPE CONNECTIONS.
SYMBOL DESCRIPTION DATE APPR
177 382
SCALE: 1/4" = 1'-0"M-300 M-300
3 OUTDOOR AIR INTAKE DUCTS
A.5
5.4
M-301
B-2 B-1
HWP-2 HWP-1
HWSP-01 HWSP-02
ET-02
AS-02
6ø OA
12' - 3" BOD EL
6ø OA
12' - 3" BOD EL
FIRST FLOOR -
FINISH FLOOR
100'-0"
Avg. B.O. Footing - Level 1
91'-6"
5.4
BASEMENT -
FINISH FLOOR
84'-0"
LEVEL 1
100' - 0"
BASEMENT - FINISH FLOOR
84' - 0"
5.4
LEVEL 1
100' - 0"
BASEMENT - FINISH FLOOR
84' - 0"
HWP-2
ELEC.
SHUTOFF
ø
E A
10ø EA
AS-02
B-2
REVIEWED BY
DRAWN BY:
DESIGNED BY:
PLOT DATE: PLOT SCALE:
DRAWING NO. AMP-400-E-
OF
P L O
T D
A T
E
C E
N T
R A
L F
IL
A
B
C
D
E
F
G
A
B
C
D
E
F
G
SENSITIVE SECURITY INFORMATION WARNING: This record contains Sensitive Security Information that is controlled under 49 CFR parts 15 and 1520, except with written permission of the Secretary of Transportation. Unauthorized release may result in civil penalty or other action. For U.S. government agencies, public disclosure is governed by 5 U.S.C. 552 and 49 CFR 15 and 1520.
DEPARTMENT OF TRANSPORTATION
FEDERAL AVIATION ADMINISTRATION
MIKE MONRONEY AERONAUTICAL CENTER - OKLAHOMA CITY, OKLAHOMA
DATE:
APPROVED BY:
ISSUED BY
OFFICE OF:
FACILITY
MANAGEMENT
AMP-400
PROJECT MANAGER:
WORK REQUEST NO:
BASE MAINTENANCE BUILDING
C O
P Y
R
IG
H T
B U
R N
S
M c D
O N
N E
L L
E N
G
IN
E E
R
IN
G C
O M
P A
N Y
IN
C
1/16/2020 8:48:32 AM
/1
/2
:4
:3
A
M
RENOVATION OF BMB-15
(BASE MAINTENANCE BUILDING)
6125 SW 68TH ST, OKLAHOMA CITY, OK
MECHANICAL ENLARGED PLANS
M-301A. SHUPE
C. BOALDIN
2014-004363
M M
A C
-B M
B R e n o v a tio n T y p e B
-M e c h
.r v t
12/20/2019
MONTE THURMAN,
AMP-400
2014-004363
MONTE THURMAN,
AMP-400
178 382
SYMBOL DESCRIPTION DATE APPR
SCALE: 1/2" = 1'-0"M-300 M-301
1 BASEMENT - HEATING HW PIPING - Callout 1
GENERAL NOTES:
1. REFER TO MECHANICAL GENERAL NOTES ON SHEET M-001.
2. REFER TO DIFFUSER SCHEDULE FOR ALL INDIVIDUAL RUNOUTS.
3. REFER TO MECHANICAL PIPING DRAWINGS FOR THERMOSTAT
LOCATIONS.
4. REFER TO M300 FOR ENLARGED BASEMENT MECHANICAL ROOM
PLAN.
5. REFER TO MP101 AND MH101 FOR CONTINUATION OF BASEMENT
FLOOR PLAN.
SCALE: 1/2" = 1'-0"M-300 M-301
2 Section 84
DOM. HW HEATER
COMBUSTION AIR
INTAKE VENT
FD
AV
1" DRAIN
NC
RELIEF VALVE
SET AT 100 PSIG
1"
DIAPHRAGM TYPE
EXPANSION TANK
1"
1"
NO
6" CHWR
6" CHWS
AV
ET-01
FM
FLOW
METER
STRAIGHT PIPE MINIMUM
10 PIPE DIAMETERS (TYP)
1" NPW SEE PLUMBING
DRAWING PL201 FOR
CONTINUATION
PRESSURE REDUCING
FILL VALVE SET AT
15 PSIG (ADJ)
C H
W R
PLUMBING
CONTRACTOR
MECHANICAL
CONTRACTOR
POT
FEEDER
6" CHWS
AS-01
M
F C
V
CHWSP-01
CHWSP-02
3"
3"
3"
3"
A V
SUCTION
DIFFUSER (TYP)
CH-1
CHWSP-1
CH-2
CHWSP-2
B Y
P A
S S
STRAIGHT PIPE MINIMUM
10 PIPE DIAMETERS (TYP)
MANUAL SHUT
OFF VALVE
C H
W R3
C H
W R
M
C H
W P
-0
C H
W P
-0
6" CHWR
BFP
BACKFLOW PREVENTOR
3/4"
3/4"
STRAIGHT PIPE MINIMUM
5 PIPE DIAMETERS (TYP)
ALARM ON FLOW
C H
W R
T
B
U
IL
D
IN
G
C H
W S
U
IL
D
IN
G
S H
E E
T M
-4
S H
E E
T M
-4
REVIEWED BY
DRAWN BY:
DESIGNED BY:
PLOT DATE: PLOT SCALE:
DRAWING NO. AMP-400-E-
OF
P L O
T D
A T
E
C E
N T
R A
L F
IL
A
B
C
D
E
F
G
A
B
C
D
E
F
G
SENSITIVE SECURITY INFORMATION WARNING: This record contains Sensitive Security Information that is controlled under 49 CFR parts 15 and 1520, except with written permission of the Secretary of Transportation. Unauthorized release may result in civil penalty or other action. For U.S. government agencies, public disclosure is governed by 5 U.S.C. 552 and 49 CFR 15 and 1520.
DEPARTMENT OF TRANSPORTATION
FEDERAL AVIATION ADMINISTRATION
MIKE MONRONEY AERONAUTICAL CENTER - OKLAHOMA CITY, OKLAHOMA
DATE:
APPROVED BY:
ISSUED BY
OFFICE OF:
FACILITY
MANAGEMENT
AMP-400
PROJECT MANAGER:
WORK REQUEST NO:
BASE MAINTENANCE BUILDING
C O
P Y
R
IG
H T
B U
R N
S
M c D
O N
N E
L L
E N
G
IN
E E
R
IN
G C
O M
P A
N Y
IN
C
1/16/2020 8:48:33 AM
/1
/2
:4
:3
A
M
RENOVATION OF BMB-15
(BASE MAINTENANCE BUILDING)
6125 SW 68TH ST, OKLAHOMA CITY, OK
CHILLED WATER FLOW DIAGRAM
(MECHANICAL ROOM)
M-400A. SHUPE
C. BOALDIN
2014-004363
M M
A C
-B M
B R e n o v a tio n T y p e B
-M e c h
.r v t
12/20/2019
MONTE THURMAN,
AMP-400
2014-004363
MONTE THURMAN,
AMP-400
NTSSCALE:1
CHILLED WATER FLOW DIAGRAM (MECHANICAL ROOM)
179 382
AHU-01
172.2 GPM
/4
C
H W
S
/4
C
H W
R
MAU-01
9 GPM
AHU-02
41.8 GPM
AHU-03
134.2 GPM
C H
W R
C H
W S
C H
W R
A S
E M
E N
T
C H
W S
F R
M
A S
E M
E N
T
6" CHWR
6" CHWS
3" CHWR
3" CHWS
/2
C H
W R
/2
C H
W S
C H
W R
C H
W S
C H
W S
C H
W R
1 1/2" CHWS
1 1/2" CHWR
3/4" CHWS
3/4" CHWR
3" CHWR
3" CHWS
DP
DP
S H
E E
T M
-4
S H
E E
T M
-4
M
MM
M
REVIEWED BY
DRAWN BY:
DESIGNED BY:
PLOT DATE: PLOT SCALE:
DRAWING NO. AMP-400-E-
OF
P L O
T D
A T
E
C E
N T
R A
L F
IL
A
B
C
D
E
F
G
A
B
C
D
E
F
G
SENSITIVE SECURITY INFORMATION WARNING: This record contains Sensitive Security Information that is controlled under 49 CFR parts 15 and 1520, except with written permission of the Secretary of Transportation. Unauthorized release may result in civil penalty or other action. For U.S. government agencies, public disclosure is governed by 5 U.S.C. 552 and 49 CFR 15 and 1520.
DEPARTMENT OF TRANSPORTATION
FEDERAL AVIATION ADMINISTRATION
MIKE MONRONEY AERONAUTICAL CENTER - OKLAHOMA CITY, OKLAHOMA
DATE:
APPROVED BY:
ISSUED BY
OFFICE OF:
FACILITY
MANAGEMENT
AMP-400
PROJECT MANAGER:
WORK REQUEST NO:
BASE MAINTENANCE BUILDING
C O
P Y
R
IG
H T
B U
R N
S
M c D
O N
N E
L L
E N
G
IN
E E
R
IN
G C
O M
P A
N Y
IN
C
1/16/2020 8:48:33 AM
/1
/2
:4
:3
A
M
RENOVATION OF BMB-15
(BASE MAINTENANCE BUILDING)
6125 SW 68TH ST, OKLAHOMA CITY, OK
CHILLED WATER FLOW DIAGRAM
(BUILDING)
M-401A. SHUPE
C. BOALDIN
2014-004363
M M
A C
-B M
B R e n o v a tio n T y p e B
-M e c h
.r v t
12/20/2019
MONTE THURMAN,
AMP-400
2014-004363
MONTE THURMAN,
AMP-400
NTSSCALE:1
CHILLED WATER FLOW DIAGRAM - BUILDING
180 382
V
HWS
B-2
HWR
AIR SEPARATOR
DIAPHRAGM TYPE
EXPANSION TANK
AV
RELIEF VALVE
SET @ 100-PSIG
ET-02
NC
3/4" DRAIN VALVE
BY BOILER MANUFACTURER
TO EXISTING
FLOOR DRAIN
T
4" HWR 4" HWR
3"
3"
HWSP-01
3"
3"
HWSP-02
4" HWS TO FIRST FLOOR
H W
S
TO EXISTING
FLOOR DRAIN
H W
S
NG
NG
PRV
VENT THRU
ROOF
3/4" NPW
V E
N T
1000 MBH
M
GAS
TRAIN
V
HWS
B-1
HWR
1000 MBH
M
GAS
TRAIN
M
4" HWR FROM FIRST FLOOR
NG
AS-02
PDV
PDV
INTAKE
THRU WALL
IN
T
A K
E
BFP
BACKFLOW PREVENTOR
AHU-1
1 1/2" 1 1/2"
M
40.9 GPM
VAV-B3
M
3/4" 3/4"
6.5 GPM
VAV-B4
M
3/4" 3/4"
6.5 GPM
VAV-B1
M
3/4" 3/4"
4.2 GPM
VAV-B2
M
3/4" 3/4"
6.5 GPM
4"
4"
4" HWR
4" HWS
4" HWR
4" HWS
T
4" HWR
4" HWR
HWP-01
HWP-02
H W
Y P
A S
S
STRAIGHT PIPE LESS
THAN 4 PIPE DIAMETERS
SHEET M-403
SHEET M-403
SET @ 15" W.C.
SET @ 25-PSIG
BASEMENT
REVIEWED BY
DRAWN BY:
DESIGNED BY:
PLOT DATE: PLOT SCALE:
DRAWING NO. AMP-400-E-
OF
P L O
T D
A T
E
C E
N T
R A
L F
IL
A
B
C
D
E
F
G
A
B
C
D
E
F
G
SENSITIVE SECURITY INFORMATION WARNING: This record contains Sensitive Security Information that is controlled under 49 CFR parts 15 and 1520, except with written permission of the Secretary of Transportation. Unauthorized release may result in civil penalty or other action. For U.S. government agencies, public disclosure is governed by 5 U.S.C. 552 and 49 CFR 15 and 1520.
DEPARTMENT OF TRANSPORTATION
FEDERAL AVIATION ADMINISTRATION
MIKE MONRONEY AERONAUTICAL CENTER - OKLAHOMA CITY, OKLAHOMA
DATE:
APPROVED BY:
ISSUED BY
OFFICE OF:
FACILITY
MANAGEMENT
AMP-400
PROJECT MANAGER:
WORK REQUEST NO:
BASE MAINTENANCE BUILDING
C O
P Y
R
IG
H T
B U
R N
S
M c D
O N
N E
L L
E N
G
IN
E E
R
IN
G C
O M
P A
N Y
IN
C
1/16/2020 8:48:35 AM
/1
/2
:4
:3
A
M
RENOVATION OF BMB-15
(BASE MAINTENANCE BUILDING)
6125 SW 68TH ST, OKLAHOMA CITY, OK
HEATING WATER FLOW DIAGRAM
(MECHANICAL ROOM)
M-402A. SHUPE
C. BOALDIN
2014-004363
M M
A C
-B M
B R e n o v a tio n T y p e B
-M e c h
.r v t
12/20/2019
MONTE THURMAN,
AMP-400
2014-004363
MONTE THURMAN,
AMP-400
NTSSCALE:1
HEATING WATER FLOW DIAGRAM (MECHANICAL ROOM)
181 382
VAV-10
3/4" 3/4"
1.0 GPM
1 1/2"
1 1/2"
VAV-06
M
3/4" 3/4"
2.5 GPM
VAV-05
M
3/4" 3/4"
7.2 GPM
VAV-04
M
3/4" 3/4"
2.3 GPM
VAV-03
M
3/4" 3/4"
3.6 GPM
M
3/4" 3/4"
AHU-2
2" 2"
M
26 GPM VAV-02
M
3/4" 3/4"
1.9 GPM
MAU-1
3/4" 3/4"
M
6.3 GPM
VAV-13
2.7 GPM
VAV-15
M
3/4" 3/4"
3.4 GPM
AHU-3
1 1/2" 1 1/2"
M
42.3 GPM
VAV-07
M
3/4" 3/4"
9.8 GPM
VAV-08
M
3/4" 3/4"
5.6 GPM
VAV-09
M
3/4" 3/4"
5.6 GPM
3/4"
3/4"
M
3/4" 3/4"
M
3/4" 3/4"
VAV-16
1.3 GPM
M
3/4" 3/4"
VAV-17
M
3/4" 3/4"
6.7 GPM
VAV-21
1.9 GPM
VAV-22
3.8 GPM
1"
1"
M
3/4" 3/4"
M
3/4" 3/4"
VAV-20
M
3/4" 3/4"
3.4 GPM
VAV-23
M
3/4" 3/4"
1.7 GPM
VAV-42
5.6 GPM
VAV-41
5.6 GPM
1"
1"
M
3/4" 3/4"
M
3/4" 3/4"
VAV-28
M
3/4" 3/4"
3.5 GPM
VAV-39
5.4 GPM
VAV-40
3.3 GPM
1"
1"
M
3/4" 3/4"
M
3/4" 3/4"
3/4"
3/4"
VAV-33
M
3/4" 3/4"
1.6 GPM
VAV-34
M
3/4" 3/4"
3.4 GPM
VAV-35
M
3/4" 3/4"
1.3 GPM
2 1/2"
2 1/2"
1"
1"
2 1/2"
2 1/2"
1 1/2"
1 1/2"
3"
3"
2 1/2"
2 1/2"
VAV-18
9.8 GPM
1 1/4"
1 1/4"
M
3/4" 3/4"
M
3/4" 3/4"
1"
1"
1"
1"
2 1/2"
2 1/2"
2"
2"
2"
2"
1"
1"
VAV-14
M
3/4" 3/4"
4.5 GPM
VAV-27
M
3/4" 3/4"
4.4 GPM
4"
4"
VAV-11
5.3 GPM
VAV-01
M
3/4" 3/4"
1.3 GPM
VAV-12
7.6 GPM
VAV-19
6.0 GPM
VAV-26
M
3/4" 3/4"
6.3 GPM
VAV-24
M
3/4" 3/4"
2.5 GPM
M
3/4" 3/4"
VAV-32
1.2 GPM
3/4"
3/4"
VAV-30
M
3/4" 3/4"
5.4 GPM
VAV-29
M
3/4" 3/4"
1.6 GPM
VAV-31
M
3/4" 3/4"
4.6 GPM
1"
1"
VAV-36
M
3/4" 3/4"
7.6 GPM
VAV-38
M
3/4" 3/4"
3.5 GPM
VAV-37
M
3/4" 3/4"
3.5 GPM
DP
DP
3-WAY
VALVE
3-WAY
VALVE
3/4"
3/4"
2 1/2"
2 1/2"
2"
2"
2 1/2"
2 1/2"
4" HWS FROM BASEMENT
4" HWR TO BASEMENT
SHEET M-402
SHEET M-402
REVIEWED BY
DRAWN BY:
DESIGNED BY:
PLOT DATE: PLOT SCALE:
DRAWING NO. AMP-400-E-
OF
P L O
T D
A T
E
C E
N T
R A
L F
IL
A
B
C
D
E
F
G
A
B
C
D
E
F
G
SENSITIVE SECURITY INFORMATION WARNING: This record contains Sensitive Security Information that is controlled under 49 CFR parts 15 and 1520, except with written permission of the Secretary of Transportation. Unauthorized release may result in civil penalty or other action. For U.S. government agencies, public disclosure is governed by 5 U.S.C. 552 and 49 CFR 15 and 1520.
DEPARTMENT OF TRANSPORTATION
FEDERAL AVIATION ADMINISTRATION
MIKE MONRONEY AERONAUTICAL CENTER - OKLAHOMA CITY, OKLAHOMA
DATE:
APPROVED BY:
ISSUED BY
OFFICE OF:
FACILITY
MANAGEMENT
AMP-400
PROJECT MANAGER:
WORK REQUEST NO:
BASE MAINTENANCE BUILDING
C O
P Y
R
IG
H T
B U
R N
S
M c D
O N
N E
L L
E N
G
IN
E E
R
IN
G C
O M
P A
N Y
IN
C
1/16/2020 8:48:37 AM
/1
/2
:4
:3
A
M
RENOVATION OF BMB-15
(BASE MAINTENANCE BUILDING)
6125 SW 68TH ST, OKLAHOMA CITY, OK
HEATING WATER FLOW DIGRAM
(BUILDING)
M-403A. SHUPE
C. BOALDIN
2014-004363
M M
A C
-B M
B R e n o v a tio n T y p e B
-M e c h
.r v t
12/20/2019
MONTE THURMAN,
AMP-400
2014-004363
MONTE THURMAN,
AMP-400
NTSSCALE:1
HEATING WATER FLOW DIAGRAM (BUILDING)
182 382
STRAP HANGERS TRAPEZE HANGERS
60" MAX.
REINFORCEMENT MAY BE USED FOR
ATTACHMENT IF IT QUALIFIES FOR
BOTH DUTIES DO NOT EXCEEED
ALLOWABLE LOAD LIMITS
ONE HALF-ROUND MAY BE USED
IF DUCT SHAPE IS MAINTAINED.
24" DIA. MAX.50" DIA. MAX.
10" DIA. MAX.
LOAD RATED
FASTENERS
HANGER
STRAPS
HANGER RODS,
WIRES OR STRAPS
BAND OF SAME SIZE
AS HANGAR STRAP
NUTS
HANGERS
MUST NOT
DEFORM DUCT
SHAPE
UNLESS FOOT OF STRAP
IS PLACED UNDER A
BOTTOM REINFORCEMENT
SCREWS
SCREWS MAY
BE OMITTED
IF HANGER LOOPS
SECURE
WIRE
STRAP
ALTERNATE LOCATION
(VERIFY UPPER
TRAPEZE LOAD CAPACITY)
ANGLES
BAND
STRAP OR
ANGLE
ROD
SIZE BOLT (S)
FOR LOAD
1" MIN.
ROD
12" MAX.
SPACING
1" MIN.
STRAP HANGERS TRAPEZE HANGERS
75(3")
ROD
ANGLE
SIZE BOLT(S) FOR LOAD
HANGER
STRAPS
SCREWS
SPIN-IN FITTING OR 45° BOOT
AS INDICATED WITH DAMPER
SUPPLY DUCT
DRAW BAND
FLEX DUCT
MAX. 5'
LENGTH
INSULATED
DIFFUSER
PLENUM
SEE PLANS AND SCHEDULE
FOR LENGTH, NUMBER OF
SLOTS AND CONNECTION
SIZE.
BALANCING DAMPER WITH
LOCKING QUADRANT. PROVIDE 2" DUCT
EXTENSION TO ALLOW OPERATION OF
DAMPER WITHOUT DAMAGE TO
INSULATION.
SPIN-IN FITTING OR 45° BOOT
WITH DAMPER, WHERE
INDICATED.
SUPPLY DUCT
INSULATED FLEXIBLE DUCT
(MAX LENGTH = 5 FEET)
DIFFUSER DAMPER SECTION
(WHERE SCHEDULED OR
SPECIFIED)
T-BAR
CEILING
SUPPLY DIFFUSER
90° SHEET METAL ELBOW
DRAW BAND
BALANCING DAMPER WITH
LOCKING QUADRANT. SEE NOTE 2.
EXTERNALLY
INSULATE ELBOW AND
DIFFUSER
INTERMEDIATE SUPPORT
SEE NOTE 1
PROVIDE INTERMEDIATE SUPPORT, WHERE REQUIRED, TO PREVENT SAGGING AND KINKS AND TO KEEP
FLEXIBLE DUCTWORK OFF SURROUNDING OBJECTS.
PROVIDE 2" DUCT EXTENSION TO ALLOW OPERATION OF DAMPER WITHOUT DAMAGE TO INSULATION.
1.
NOTES:
2.
RECTANGULAR SUPPLY
DUCT,
SEE PLANS FOR SIZE.
OPPOSED BLADE DAMPER
DOUBLE DEFLECTION SIDE
WALL DIFFUSER SEE PLANS FOR
SIZE
NOTES:
TAKEOFF ON BOTH SIDES OR SINGLE SIDE AS REQUIRED BY PLANS.
SEE SMACNA MANUAL FOR TAP-IN DETAILS.
4.
3.
2.
1.
X = 20° MAX.
J = 45°
W
L
L = 1/4 W, 4" MIN.
AIRFLOW
X
J
RECTANGULAR
DUCT,
SEE PLAN FOR SIZE.
ROUND DUCT, SEE
PLAN FOR SIZE.
WHEN FITTING HAS ONLY ONE SIDE SLOPED FOR A SINGLE
SIDE TAKE-OFF, THE TAP-IN SHALL BE INSTALLED IN SLOPED
SIDE.
CLINCH LOCK CONNECTION TO DUCT SHALL HAVE
CORNER
SEALS. (SEE SMACNA MANUAL)
BALANCING DAMPER WITH
LOCKING QUADRANT. PROVIDE 2" DUCT
EXTENSION TO ALLOW OPERATION OF
DAMPER WITHOUT DAMAGE TO
INSULATION.
WIDTH AS
NOTED
30" MIN
NOTE:
TYPICAL FOR ALL RETURN
GRILLES OR REGISTERS
WHICH ARE NOT DUCTED.
0.75 X
DEPTH
NOTED
SHEET METAL DUCT AND
ELBOW W/1" THICK LINER
R.A. REGISTER
OR GRILLE
REVIEWED BY
DRAWN BY:
DESIGNED BY:
PLOT DATE: PLOT SCALE:
DRAWING NO. AMP-400-E-
OF
P L
O T
D A
T E
C E
N T
R A
L F
IL
A
B
C
D
E
F
G
A
B
C
D
E
F
G
SENSITIVE SECURITY INFORMATION WARNING: This record contains Sensitive Security Information that is controlled under 49 CFR parts 15 and 1520, except with written permission of the Secretary of Transportation. Unauthorized release may result in civil penalty or other action. For U.S. government agencies, public disclosure is governed by 5 U.S.C. 552 and 49 CFR 15 and 1520.
DEPARTMENT OF TRANSPORTATION
FEDERAL AVIATION ADMINISTRATION
MIKE MONRONEY AERONAUTICAL CENTER - OKLAHOMA CITY, OKLAHOMA
DATE:
APPROVED BY:
ISSUED BY
OFFICE OF:
FACILITY
MANAGEMENT
AMP-400
PROJECT MANAGER:
WORK REQUEST NO:
BASE MAINTENANCE BUILDING
C O
P Y
R
IG
H T
B U
R N
S
M c D
O N
N E
L L
E N
G
IN
E E
R
IN
G C
O M
P A
N Y
IN
C
1/16/2020 8:48:39 AM
/1
/2
:4
:3
A
M
RENOVATION OF BMB-15
(BASE MAINTENANCE BUILDING)
6125 SW 68TH ST, OKLAHOMA CITY, OK
MECHANICAL DETAILS
M-500A. SHUPE
C. BOALDIN
2014-004363
M M
A C
-B M
B R e n o v a tio n T y p e B
-M e c h
.r v t
12/20/2019
MONTE THURMAN,
AMP-400
2014-004363
MONTE THURMAN,
AMP-400
NTSSCALE:1
DUCT & PIPE HANGERS
NTSSCALE:2
DUCT SUPPORT
NTSSCALE:3
LINEAR SLOT DIFFUSER
NTSSCALE:6
DUCT CONNECTION TO DIFFUSER
NTSSCALE:4
RECTANGULAR DUCT SIDEWALL DIFFUSER
NTSSCALE:5
ROUND BRANCH DUCT TAKE-OFF
NTSSCALE:7
SOUND TRAP
183 382
NOTES:
D
L = 1/4 D, 4" MIN.
L
Q
J = 45°
J
= 20° MAX.Q
AIR FLOW
1.
2.
3.
BALANCING DAMPER WITH
LOCKING QUADRANT. PROVIDE 2" DUCT
EXTENSION TO ALLOW OPERATION OF DAMPER
WITHOUT DAMAGE TO INSULATION.
SEE PLANS FOR
RECTANGULAR
DUCT SIZE
RECTANGULAR TAP-IN (NOTE 2 AND 3)
DIFFUSER CONNECTION
SIZE, SEE PLANS.
NOTE 1
DUCT TRANSITION
EXTRACTORS, SCOOPS, DEFLECTORS OR DAMPERS
THAT PROTRUDE INTO THE MAIN DUCT SHALL NOT BE
USED. BALANCING DAMPERS SHALL BE LOCATED TO
PREVENT PROTRUSION INTO THE MAIN DUCT AND TO
PROVIDE STABLE AIR FLOW AND MINIMAL NOISE WHEN
ADJUSTED.
CLINCH LOCK CONNECTION TO DUCT SHALL HAVE
CORNER SEALS (SEE SMACNA MANUAL).
TAKEOFF ON BOTH SIDES OR SINGLE SIDE AS
REQUIRED BY PLANS.
NOTES:
AIR FLOW
45°
4.
3.
2.
1.
SEE PLANS FOR
RECTANGULAR DUCT
SIZE
RECTANGULAR TAP-
IN
(NOTE 2 AND 4)
BALANCING DAMPER WITH
LOCKING QUADRANT. PROVIDE 2" DUCT
EXTENSION TO ALLOW OPERATION OF DAMPER
WITHOUT DAMAGE TO INSULATION.
SEE NOTE 1. SEE PLANS
FOR FLEX DUCT SIZE - MAX 5'-0"
DUCT TRANSITION
TAKEOFF ON BOTH SIDES OR SINGLE SIDE
AS
REQUIRED BY PLANS.
TAP-IN MAY BE RECTANGULAR OR ROUND. SEE
SMACNA MANUAL FOR DETAILS.
WHEN FITTING HAS ONLY ONE SIDE SLOPED FOR A
SINGLE SIDE TAKE-OFF, THE TAP-IN SHALL BE INSTALLED
IN SLOPED SIDE.
CLINCH LOCK CONNECTION TO DUCT SHALL
HAVE
CORNER SEALS (SEE SMACNA MANUAL).
NOTES:
X = 20° MAX.
J = 45°
W
L
L = 1/4 W, 4" MIN.
AIRFLOW
J
X
RECTANGULAR
DUCT,
SEE PLAN FOR SIZE.
TAKEOFF ON BOTH SIDES OR SINGLE SIDE AS REQUIRED
BY PLANS.
SEE SMACNA MANUAL FOR TAP-IN DETAILS.
WHEN FITTING HAS ONLY ONE SIDE SLOPED FOR A SINGLE SIDE
TAKE-OFF, THE TAP-IN SHALL BE INSTALLED IN SLOPED SIDE.
CLINCH LOCK CONNECTION TO DUCT SHALL HAVE CORNER
SEALS. (SEE SMACNA MANUAL).
EXTRACTORS, SCOOPS, DEFLECTORS OR DAMPERS THAT
PROTRUDE INTO THE MAIN DUCT SHALL NOT BE USED.
BALANCING DAMPERS SHALL BE LOCATED TO PREVENT
PROTRUSION INTO THE MAIN DUCT AND TO PROVIDE STABLE
AIR FLOW AND MINIMAL NOISE WHEN ADJUSTED.
1.
2.
3.
4.
5.
BRANCH
DUCT,
SEE PLAN FOR
SIZE.
BALANCING DAMPER WITH
LOCKING QUADRANT. PROVIDE 2" DUCT
EXTENSION TO ALLOW OPERATION OF
DAMPER WITHOUT DAMAGE TO
INSULATION.
NOTE:
RECTANGULAR TRANSITION RECTANGULAR TO
ROUND TRANSITION
TURNING VANES DETAIL
1" 1"
2" R
1" R
ROUND 90 ELBOW SQUARE 90 ELBOW
W
W
W
W
1.
TURNING VANES
MAX. SLOPE 1" IN 4"
ROUND DUCT
RECTANGULAR DUCT
MAX. SLOPE 1" IN 4"
1.5 x W
USE THIS DESIGN WHERE SQUARE 90°ELBOWS
ARE SHOWN ON DRAWINGS OR IF SPACE DOES
NOT PERMIT ROUND 90° ELBOWS.
C
B
D
C D
B
A
B
A C D
DDIMENSION IS EQUAL TO C +
DIMENSIONS, SEE PLANS FOR SIZES
(MAX)30°
AIRFLOW
15° (RECOMMENDED)
AIRFLOW
AIRFLOW
AIRFLOW
TURNING VANES @ 45° (TYP.)
TURNING VANES @ 45° (TYP.)
REVIEWED BY
DRAWN BY:
DESIGNED BY:
PLOT DATE: PLOT SCALE:
DRAWING NO. AMP-400-E-
OF
P L
O T
D A
T E
C E
N T
R A
L F
IL
A
B
C
D
E
F
G
A
B
C
D
E
F
G
SENSITIVE SECURITY INFORMATION WARNING: This record contains Sensitive Security Information that is controlled under 49 CFR parts 15 and 1520, except with written permission of the Secretary of Transportation. Unauthorized release may result in civil penalty or other action. For U.S. government agencies, public disclosure is governed by 5 U.S.C. 552 and 49 CFR 15 and 1520.
DEPARTMENT OF TRANSPORTATION
FEDERAL AVIATION ADMINISTRATION
MIKE MONRONEY AERONAUTICAL CENTER - OKLAHOMA CITY, OKLAHOMA
DATE:
APPROVED BY:
ISSUED BY
OFFICE OF:
FACILITY
MANAGEMENT
AMP-400
PROJECT MANAGER:
WORK REQUEST NO:
BASE MAINTENANCE BUILDING
C O
P Y
R
IG
H T
B U
R N
S
M c D
O N
N E
L L
E N
G
IN
E E
R
IN
G C
O M
P A
N Y
IN
C
1/16/2020 8:48:40 AM
/1
/2
:4
:4
A
M
RENOVATION OF BMB-15
(BASE MAINTENANCE BUILDING)
6125 SW 68TH ST, OKLAHOMA CITY, OK
MECHANICAL DETAILS
M-501A. SHUPE
C. BOALDIN
2014-004363
M M
A C
-B M
B R e n o v a tio n T y p e B
-M e c h
.r v t
12/20/2019
MONTE THURMAN,
AMP-400
2014-004363
MONTE THURMAN,
AMP-400
NTSSCALE:1
RECTANGULAR DUCT WITH 2 DIFFUSER TAKE-OFFS
NTSSCALE:2
DIFFUSER TAKE-OFF
NTSSCALE:4
RECTANGULAR BRANCH DUCT TAKE-OFF
NTSSCALE:3
LOW VELOCITY DUCT LAYOUT
NTSSCALE:5
LOW PRESSURE DUCT TEE FITTING
184 382
R S GA
SINGLE VANE SCH.
SMALL
LARGE
51 38 24
114 83 22
45°45°
S
S S S S
L
LWW
D
S= D/6 (MIN.2")
W/S= NO. OF SPACES
R= 1 1/4 S
L= 3/4 S
R
BOLT, SCREW
OR
WELD TO DUCT
SCREW EVERY
SIXTH VANE
BLADES IN TRANSITION ELBOWS
SHALL
BE DETERMINED ACCORDING TO
SMALLEST WIDTH OF ELBOW.
EA
EXHAUST FAN
BACKDRAFT DAMPER
BIRDSCREEN
ROOF CURB, COORDINATE
W/EQUIPMENT FURNISHED
SEE ARCHITECTURAL
DWGS FOR FLASHING DETAILS
NOTE:
1. INSTALL NEW GRAVITY DAMPER INSIDE EXISTING
ROOF CURBS, MECHANICAL CONTRACTOR SHALL
COORDINATE WITH MANUFACTURER AND
EXISTING CONDITIONS.
MV
CWS
CHILLED WATER COIL
SEE NOTE 6
SEE NOTE 2
SEE NOTE 4
TWO WAY CONTROL VALVE
CWR
SEE NOTE 3
SEE NOTE 7
SEE NOTE 8
1. INDIVIDUAL PIPE SIZES SHALL BE THE SAME SIZE AS THE COIL TAPS.
2. LOCATE FLANGES AND UNIONS TO ALLOW FOR REMOVAL OF ALL COILS AND CONTROL
VALVES.
3. TYPE OF ISOLATION VALVE IS DEPENDENT UPON PIPING LINE SIZE. REFER TO
SPECIFICATIONS FOR SPECIFIC REQUIREMENTS. TYPICAL ALL ISOLATION VALVES THIS
DETAIL.
4. ALL COILS SHALL BE PIPED FOR COUNTERFLOW ARRANGEMENT; I.E. CHILLED WATER
ENTERS COIL NEAREST COIL FACE WHERE COLDEST AIR LEAVES.
5. PROVIDE 3/4" BALL OR GATE VALVE WITH 3/4" HOSE CONNECTION FOR DRAINING AND
FLUSHING.
6. ALL COIL DRAIN CONNECTIONS SHALL BE INSTALLED THROUGH HVAC UNIT CASING TO
PERMIT COMPLETE DRAINAGE OF COILS FROM UNIT EXTERIOR. TYPICAL ALL DRAIN AND
FLUSH CONNECTIONS.
7. PROVIDE STRAINER WITH 3/4" BALL OR GATE VALVE WITH 3/4" HOSE CONNECTION FOR
FLUSHING. TYPICAL ALL STRAINERS.
8. VENTS SHALL BE INSTALLED THROUGH HVAC UNIT CASING TO PERMIT COMPLETE VENTING
OF COILS FROM UNIT EXTERIOR. TYPICAL ALL VENT CONNECTIONS.
NOTES:
NOTES:
1. INDIVIDUAL PIPE SIZES SHALL BE THE SAME SIZE AS THE COIL TAPS.
2. LOCATE FLANGES AND UNIONS TO ALLOW FOR REMOVAL OF ALL COILS AND CONTROL
VALVES.
3. TYPE OF ISOLATION VALVE IS DEPENDENT UPON PIPING LINE SIZE. REFER TO
SPECIFICATIONS FOR SPECIFIC REQUIREMENTS. TYPICAL ALL ISOLATION VALVES THIS
DETAIL.
4. ALL COILS SHALL BE PIPED FOR COUNTERFLOW ARRANGEMENT; I.E. HOTTEST WATER ENTERS
COIL NEAREST COIL FACE WHERE HOTTEST AIR LEAVES.
5. PROVIDE 3/4" BALL OR GATE VALVE WITH 3/4" HOSE CONNECTION FOR DRAINING AND
FLUSHING.
6. ALL COIL DRAIN CONNECTIONS SHALL BE INSTALLED THROUGH HVAC UNIT CASING TO PERMIT
COMPLETE DRAINAGE OF COILS FROM UNIT EXTERIOR. TYPICAL ALL DRAIN AND FLUSH
CONNECTIONS.
7. PROVIDE STRAINER WITH 3/4" BALL OR GATE VALVE WITH 3/4" HOSE CONNECTION FOR
FLUSHING. TYPICAL ALL STRAINERS.
8. VENTS SHALL BE INSTALLED THROUGH HVAC UNIT CASING TO PERMIT COMPLETE VENTING OF
COILS FROM UNIT EXTERIOR. TYPICAL ALL VENT CONNECTIONS.
MV
HWS
HOT WATER COIL
SEE NOTE 6
SEE NOTE 2
SEE NOTE 5
TWO WAY CONTROL VALVE
HWR
SEE NOTE 3
SEE NOTE 7
SEE NOTE 8
AIR FLOW
AIR FLOW
VARIABLE AIR VOLUME
DAMPER
MIN. 2'-0" OF STRAIGHT DUCTWORK
BEFORE CONNECTION
PRIMARY AIR DUCT
HEATING COIL
SECTION
REVIEWED BY
DRAWN BY:
DESIGNED BY:
PLOT DATE: PLOT SCALE:
DRAWING NO. AMP-400-E-
OF
P L
O T
D A
T E
C E
N T
R A
L F
IL
A
B
C
D
E
F
G
A
B
C
D
E
F
G
SENSITIVE SECURITY INFORMATION WARNING: This record contains Sensitive Security Information that is controlled under 49 CFR parts 15 and 1520, except with written permission of the Secretary of Transportation. Unauthorized release may result in civil penalty or other action. For U.S. government agencies, public disclosure is governed by 5 U.S.C. 552 and 49 CFR 15 and 1520.
DEPARTMENT OF TRANSPORTATION
FEDERAL AVIATION ADMINISTRATION
MIKE MONRONEY AERONAUTICAL CENTER - OKLAHOMA CITY, OKLAHOMA
DATE:
APPROVED BY:
ISSUED BY
OFFICE OF:
FACILITY
MANAGEMENT
AMP-400
PROJECT MANAGER:
WORK REQUEST NO:
BASE MAINTENANCE BUILDING
C O
P Y
R
IG
H T
B U
R N
S
M c D
O N
N E
L L
E N
G
IN
E E
R
IN
G C
O M
P A
N Y
IN
C
1/16/2020 8:48:41 AM
/1
/2
:4
:4
A
M
RENOVATION OF BMB-15
(BASE MAINTENANCE BUILDING)
6125 SW 68TH ST, OKLAHOMA CITY, OK
MECHANICAL DETAILS
M-502A. SHUPE
C. BOALDIN
2014-004363
M M
A C
-B M
B R e n o v a tio n T y p e B
-M e c h
.r v t
12/20/2019
MONTE THURMAN,
AMP-400
2014-004363
MONTE THURMAN,
AMP-400
NTSSCALE:1
RECTANGULAR DUCT ELBOW TURNING VANES
NTSSCALE:2
CENTRIFUGAL ROOF EXHAUST FAN
NTSSCALE:4
CHILLED WATER, SINGLE COIL, 2-WAY CONTROL VALVE
NTSSCALE:5
HOT WATER, SINGLE COIL, 2-WAY CONTROL VALVE
NTSSCALE:3
VARIABLE AIR VOLUME BOX
NOTE: DETAIL FOR AHU & MAU COILS NOTE: DETAIL FOR AHU & MAU COILS
185 382
WELDED PIPING
ELEVATION
THREADED PIPING
ELEVATION
TYP. WATER PIPING
TYP. WATER PIPING
3/4" GATE VALVE
REDUCER, IF REQUIRED
ADAPTER TO 3/4" HOSE
THREAD, PROVIDE HOSE
CAP NUT 3/4" GATE VALVE
DRAIN ALL LOW POINTS AS INDICATED BELOW.
WHERE DIRT LEGS ARE SHOWN ON PIPE
RISER DIAGRAMS AND/OR PLANS LOCATE
DRAIN AT BOTTOM OF DIRT LEG.
1.
2.
ADAPTER TO 3/4" HOSE
THREAD, PROVIDE
HOSE CAP NUT
4"
MINIMUM
1.
NOTE:
WATER PIPING
REDUCER
3/4" BALL
VALVE
(TYP)
3/4"
3/8" O.D. COPPER TUBING TO
FLOOR DRAIN OR TO
ACCESSIBLE POINT FOR
DISCHARGE INTO A CONTAINER
VENT ALL HIGH
POINTS
AS INDICATED ABOVE.
BALL VALVE AT ACCESSIBLE
LOCATION FROM FLOOR
2" THREAD-O-LET
2"
2" CAP-THREADED
2"
2"-90 ELBOW-
THREADED
2" BALL
VALVE-THREADED
2. DIMENSION EQUAL TO MAXIMUM FAN OUTLET PRESSURE +1/2" (MIN.)
1. DIMENSION EQUAL TO 1/2" (MIN.)
NOTES:
BLOW THRU UNIT
UNIT
DRAIN
PAN
INTERNAL
OPERATING
POSITIVE STATIC
PRESSURE ("WG)
UNIT
DRAIN
PAN
INTERNAL
OPERATING
NEGATIVE
STATIC
PRESSURE ("WG)
2. DIMENSION EQUAL TO HALF OF (MIN.)
1. DIMENSION EQUAL TO MAXIMUM FAN INLET PRESSURE (INCH WC) +1" (MIN.)
NOTES:
DRAW THRU UNIT
A
FAN INLET PRESSURE
(NEGATIVE)
B
A
B
A
B A
B
A
HAND-TIGHT
CLEANOUT PLUG
FAN OUTLET
PRESSURE
AHU CABINET WALL
NPT DRAIN
CONNECTION
ADAPTER
PITCH (1/8" PER
FOOT) TYPW "M"
COPPER (TYP.)
2" MIN SIZE,
SLOPE TO
EQUIP DRAIN
HAND-TIGHT
CLEANOUT PLUG
RETURN BEND
(CLOSED)
PITCH(1/8" PER
FOOT) TYPE "M"
COPPER (TYP.)
AHU CABINET WALL
NPT DRAIN
CONNECTION
ADAPTER
2" MIN SIZE,
SLOPE TO
EQUIP DRAIN
RETURN BEND
(CLOSED)
3. INCREASE PAD THICKNESS AS REQUIRED TO ACHIEVE REQUIRED
TRAP DEPTH (4" MINIMUM)
C 3. INCREASE PAD THICKNESS AS REQUIRED TO ACHIEVE REQUIRED
TRAP DEPTH (4" MINIMUM)
C
C C
M
MANUAL AIR VENT
BALL VALVE (TYP.)
UNION (TYP.)
MANUAL VENT
BALANCING VALVE
DRAIN VALVE (TYP)
ISOLATION VALVE
2-WAY CONTROL VALVE
(MAX. P = 5 PSI)
VAV
REVIEWED BY
DRAWN BY:
DESIGNED BY:
PLOT DATE: PLOT SCALE:
DRAWING NO. AMP-400-E-
OF
P L
O T
D A
T E
C E
N T
R A
L F
IL
A
B
C
D
E
F
G
A
B
C
D
E
F
G
SENSITIVE SECURITY…