589A7-21-132 Wichita Bid Drawings 08_Electrical 2 of 2.pdf

PDF 9 MB Posted

Attached to
Z2DA--589A7-21-132 Construct Centralized Emergency Power System
Solicitation number
36C25526R0125
Issued by

About this file

This document is a set of bid documents containing electrical design drawings and specifications for a Centralized Emergency Power System project at Robert J. Dole VA Medical Center in Wichita, Kansas (Project No. 0499-0162). The drawings are prepared by Miller-Remick LLC as the Professional Engineer of Record, with associated consultants including IMEG Corp (Civil/Site Utility Engineering), Stanton Engineering Services LLC (Fire & Life Safety), Mabbett & Associates Inc. (Hazardous Materials), Oculus Inc. (Architectural), and Professional Engineering Consultants PA (Structural).

The project involves installation of three 3MW, 12,470-volt generators with associated paralleling switchgear, transformers, and automatic transfer switches (ATS) to replace existing distributed generators across multiple buildings. Key infrastructure includes a new generator building (Building 37), concrete-encased underground ductbanks for medium and low voltage distribution, pad-mounted transformers replacing existing generators in Buildings 2, 5, 13, 21, 26, 31, 31A, 34, and 62, and new electrical distribution systems throughout the facility. The work encompasses signal plans, electrical enlarged plans for multiple buildings, conduit and equipment mounting details, grounding and lightning protection systems, fire-rated penetration details, emergency lighting controls, card access systems, equipment nameplate schedules, and single-line diagrams for both the new switchgear and campus normal and emergency power loops. All electrical equipment shown is either existing to remain unless otherwise noted, or marked as new work. The drawings are fully sprinklered and dated March 26, 2026.

View the file

Other files

File Type Posted
589A7-21-132 Wichita Bid Drawings 01_General_Complete.pdf PDF
589A7-21-132 Wichita Bid Drawings 03_Civil 3 of 10.pdf PDF
589A7-21-132 Wichita Bid Drawings 03_Civil 4 of 10.pdf PDF
589A7-21-132 Wichita Bid Drawings 03_Civil 10 of 10.pdf PDF
02_Structural.pdf PDF
589A7-21-132 Wichita Bid Drawings 03_Civil 2 of 10.pdf PDF
589A7-21-132 Wichita Bid Drawings 03_Civil 6 of 10.pdf PDF
589A7-21-132 Wichita Bid Drawings 07_Mechanical 1 of 2.pdf PDF
589A7-21-132 Wichita Bid Drawings 06_Fire Protection_Complete.pdf PDF
589A7-21-132 Wichita EPS_Bid Docs - Specifications - Volume I.pdf PDF
589A7-21-132 Wichita Bid Drawings 07_Mechanical 2 of 2.pdf PDF
589A7-21-132 Wichita Bid Drawings 03_Civil 9 of 10.pdf PDF
04_Fire Protection and Fire Alarm Narrative.pdf PDF
589A7-21-132 Wichita Bid Drawings 02_HazMat_Complete.pdf PDF
589A7-21-132 Wichita EPS_Bid Docs - Specifications - Volume II.pdf PDF
589A7-21-132 Wichita Bid Drawings 08_Electrical 1 of 2.pdf PDF
36C25526R0125_1.docx DOCX document
852.219-75 VA Notice of Limitations on Subcontracting General Construction.pdf PDF
589A7-21-132 Wichita Bid Drawings 09_Fire Alarm_Complete.pdf PDF
05_Mechanical Narrative.pdf PDF
589A7-21-132 Wichita Bid Drawings 03_Civil 1 of 10.pdf PDF
589A7-21-132 Wichita Bid Drawings 03_Civil 5 of 10.pdf PDF
589A7-21-132 Wichita Bid Drawings 05_Architectural Complete.pdf PDF
01_Civil Narrative.pdf PDF
589A7-21-132 Wichita Bid Drawings 03_Civil 8 of 10.pdf PDF
589A7-21-132 Wichita Bid Drawings 03_Civil 7 of 10.pdf PDF
06_Electrical.pdf PDF
03_Architectural Narrative.pdf PDF
589A7-21-132 Wichita Bid Drawings 04_Structural_Complete.pdf PDF
APPENDIX 2- PRICE BREAKDOWN AND CALCULATION OF SELF-PERFORMED and SUBCONTRACTED WORK.docx DOCX document
Show all 30

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

CR

CR

CR

W +W

CRCR

CR

2 31 4

A

B

C

LOCKABLE

TELECOMMUNICATIONS

ENCLOSURE

GENERATOR

ROOM

FIRE RISER

ROOM

TIE CARD READER TO

ROLL-UP DOOR

OPERATOR

PANORAMIC MULTI-

SENSOR EXTERIOR

CAMERA

(TYPICAL FOR 4

EXTERIOR CAMERAS)

TIE CARD READER TO

ROLL-UP DOOR

OPERATOR

SWITCHGEAR

ROOM

SECURITY PANEL

SECURITY GATE

OPERATOR

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

CONSULTANTS

321 4 5 6 7 8 9 10

NO. DESCRIPTION DATE

PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE

WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE

PROFESSIONAL ENGINEER

o n e e ig h th i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e i n c h o n e f o o t o n e a n d o n e h a lf i n c h e s o n e f o o t th re e i n c h e s o n e f o o t

MILLER-REMICK LLC

PROFESSIONAL ENGINEER

NORTH

ENGINEER OF RECORD

M-R PROJECT NO:

Civil:

IMEG, CORP.

Fire & Life Safety:

STANTON ENGINEERING SERVICES, LLC

Hazardous Materials:

MABBETT & ASSOCIATES, INC.

Architectural:

OCULUS, INC.

Structural:

PROFESSIONAL ENGINEERING

CONSULTANTS, PA (PEC)

A u to d e s k D o c s /W ic h it a

C e n tr a liz e d E m e rg e n c y P o w e r/

-0

W ic h it a C e n tr a liz e d

E m e rg e n c y P o w e r-

M E

P -R

.r v t

/2

/2

:3

:0

A

M

EY111

ELECTRICAL

SIGNAL PLAN

GROUND FLOOR

CONSTRUCT CENTRALIZED

EMERGENCY POWER SYSTEM

589A7-21-132

Project Director

2026-03-26 TFO MJR

BID DOCUMENTS

FULLY SPRINKLERED

ROBERT J. DOLE VA MEDICAL CENTER

WICHITA, KANSAS

0499-0162

SCALE: 1/4" = 1'-0"1 SIGNAL PLAN - GROUND FLOOR

GENERAL SHEET NOTES:

1. REFER TO SHEETS E-001 & E-002 FOR SYMBOLS, ABBREVIATIONS AND NOTES.

2. ALL DEVICES SHOWN SHALL BE NEW, UNLESS OTHERWISE NOTED.

3. ALL TELE/DATA DEVICE WIRING SHALL BE RUN BACK TO THE NEW

TELECOMMUNICATIONS ENCLOSURE LOCATED.

SHEET KEYNOTES:

1 BASIS OF DESIGN: RLH INDUSTRIES, INC FIBER OPTIC LINK DUAL-DOOR TELECOM

ENSCLOSURE.

(E) ATS-3

208V, 400A

CAT

(D) GENERATOR "31"

242kW, 208-VOLT

(E) ATS-2FP

208V

(E) ATS-1FP

208V

(D) U.G. FUEL TANK

(D) GENERATOR "31A"

242kW, 240-VOLT

(D) REMOTE RADIATOR

(E) ATS-4

240V, 400A

CAT

(E) ATS-1

208V, 400A

CAT

(E) ATS-2

208V, 400A

CAT

FIRE PUMP BUILDING

GENERATOR BUILDING

(E) ATS-6

480V, 600A

CUMMINS

(E) ATS-5

480V, 225A

CUMMINS

(E) ATS-BUILDING 5

208V

CAT

(E) ATS-3

208V, 400A

CAT

(E) ATS-2FP

208V

(E) ATS-1FP

208V

(E) ATS-4

240V, 400A

CAT

(E) ATS-1

208V, 400A

CAT

(E) ATS-2

208V, 400A

CAT

(N) TRANSFORMER "31"

300kVA, 12,470V-208V

(N) LOOP FEED SWITCHES

(N) TRANSFORMER "31A"

300kVA, 12,470V-240V

(N) LOOP FEED SWITCHES

FIRE PUMP BUILDING

NO. DESCRIPTION DATE

MILLER-REMICK LLC

PROFESSIONAL ENGINEER

PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE

WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE

PROFESSIONAL ENGINEER.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

BID DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

Phase

ENGINEER OF RECORDCONSULTANT CONSTRUCT CENTRALIZED

EMERGENCY POWER SYSTEM

589A7-21-132

Project Director

2026-03-26

321 4 5 6 7 8 9 10

A

B

C

D

E

F

21 4 5 6 7 8 9 10

A

C

D

E

F

M-R PROJECT NO: 0499-0162

ROBERT J. DOLE VA MEDICAL CENTER

WICHITA, KANSAS

Civil / Site Utility Engineering:Hazardous Materials:

MABBETT & ASSOCIATES, INC.

Fire & Life Safety:

STANTON ENGINEERING SERVICES, LLC

Architectural:

OCULUS, INC.

Structural:

PROFESSIONAL ENGINEERING

CONSULTANTS, PA (PEC)

IMEG, CORP. 37

1. REFER TO SHEETS E-001 AND E-002 FOR SYMBOLS, ABBREVIATIONS AND

NOTES.

2. ALL ELECTRICAL EQUIPMENT SHOWN ON THIS DRAWING SHALL BE EXISTING

TO REMAIN, UNLESS OTHERWISE NOTED.

GENERAL SHEET NOTES:

SHEET KEYNOTES:

1. REMOVE EXISTING ATS SIGNALLING WIRE FROM EXISTING ATS TO

DEMOLISHED GENERATOR. CONDUIT PATHWAY SHALL BE EXISTING TO

REMAIN. EXISTING CONDUIT SHALL BE EXTENDED TO NEW LOW VOLTAGE

DUCTBANK, WHICH WILL BE INSTALLED DURING PHASE 1 OF THE PROJECT.

ELECTRICAL CONTRACTOR SHALL PROVIDE TWO (2) NEW #10 TWISTED PAIR

STRANDED CONTROL WIRES BETWEEN EXISTING ATS AND NEW MEDIUM

VOLTAGE GENERATORS. NEW CONTROL WIRES SHALL BE RUN IN THE NEW

LOW VOLTAGE DUCTBANK. REFER TO ES102 AND CIVIL DRAWINGS FOR

FURTHER INFORMATION ON DUCTBANK ROUTING.

ELECTRICAL

ENLARGED PLANS

BUILDINGS 1, 2, 5 & 36

EP401

MJRTO

SCALE: 1/8" = 1'-0"

SCALE: 1/8" = 1'-0"

SCALE: 1/8" = 1'-0"

EQUIPMENT

ROOM

GENERATOR

ROOM

CORRIDOR

TRANSFORMER

I.T. ROOM

ELECTRICAL

OFFICE

SECURITY

HAC

CONTROL

ROOM

BOILER

ROOM

PASSAGE

TOILET

LOCKER

ROOM

EQUIPMENT

TOILET

SHOWER

ROOM

CONTRACTOR

TOUCHDOWN

BREAK

AREA

FE

CT-5

FE FE

FE

(E) ATS-9

208V, 400A

CUMMINS

(E) ATS-8

240V, 225A

CUMMINS

(E) BUILDING 13-EMDP

(N) POWER CONDUIT PATHWAY

TO NEW BUILDING 37. CONDUIT

SHALL RUN TIGHT TO WALL. E.C.

SHALL FIELD VERIFY ROUTING.

AFTER EXITING BUILDING, CONDUIT

SHALL TURN DOWN INTO CONCRETE

ENCASED DUCTBANK. SEE CIVIL

DRAWINGS FOR CONTINUATION.

TELECOM

ROOM

103B

MEZZANINE

200-20200-20

(E) TELE/DATA RACK

(E) FIBER NETWORK

BOX

(E) TYCO SECURITY

PANELS

(N) 2" CORE THROUGH

SLAB. FIRE SEAL

OPENING AS REQUIRED.

(E) ATS-10

208V, 400A

CUMMINS

(E) INFILL PROJECT ATS

ASCO 7000 SERIES

(E) ATS-11

480V, 225A

CUMMINS

NEW GENERATOR

30KVA

(E) ATS-22

480V, 100A

CUMMINS

(E) ATS-21

480V, 225A

CUMMINS

(E) ATS-20

480V, 225A

CUMMINS

(E) ATS-23

480V, 100A

CUMMINS

(D) GENERATOR "62"

480V, 352kW

(E) ATS-22

480V, 100A

CUMMINS

(E) ATS-21

480V, 225A

CUMMINS

(E) ATS-20

480V, 225A

CUMMINS

(E) ATS-23

480V, 100A

CUMMINS

(N) TRANSFORMER "62"

300kVA, 12,470V-480V

(N) LOOP FEED SWITCHES

AFTER EXITING BUILDING, CONDUIT

SHALL TURN DOWN INTO CONCRETE

ENCASED DUCTBANK. SEE CIVIL

DRAWINGS FOR CONTINUATION.

UP TO IT ROOM ABOVE

VIA NEW CORE.

NO. DESCRIPTION DATE

MILLER-REMICK LLC

PROFESSIONAL ENGINEER

PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE

WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE

PROFESSIONAL ENGINEER.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

BID DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

Phase

ENGINEER OF RECORDCONSULTANT CONSTRUCT CENTRALIZED

EMERGENCY POWER SYSTEM

589A7-21-132

Project Director

2026-03-26

321 4 5 6 7 8 9 10

A

B

C

D

E

F

21 4 5 6 7 8 9 10

A

C

D

E

F

M-R PROJECT NO: 0499-0162

ROBERT J. DOLE VA MEDICAL CENTER

WICHITA, KANSAS

Civil / Site Utility Engineering:Hazardous Materials:

MABBETT & ASSOCIATES, INC.

Fire & Life Safety:

STANTON ENGINEERING SERVICES, LLC

Architectural:

OCULUS, INC.

Structural:

PROFESSIONAL ENGINEERING

CONSULTANTS, PA (PEC)

IMEG, CORP. 37

1. REFER TO SHEETS E-001 AND E-002 FOR SYMBOLS, ABBREVIATIONS AND

NOTES.

2. ALL ELECTRICAL EQUIPMENT SHOWN ON THIS DRAWING SHALL BE EXISTING

TO REMAIN, UNLESS OTHERWISE NOTED.

GENERAL SHEET NOTES:

SHEET KEYNOTES:

1. REMOVE EXISTING ATS SIGNALLING WIRE FROM EXISTING ATS TO

DEMOLISHED GENERATOR. CONDUIT PATHWAY SHALL BE EXISTING TO

REMAIN. EXISTING CONDUIT SHALL BE EXTENDED TO NEW LOW VOLTAGE

DUCTBANK, WHICH WILL BE INSTALLED DURING PHASE 1 OF THE PROJECT.

ELECTRICAL CONTRACTOR SHALL PROVIDE TWO (2) NEW #10 TWISTED PAIR

STRANDED CONTROL WIRES BETWEEN EXISTING ATS AND NEW MEDIUM

VOLTAGE GENERATORS. NEW CONTROL WIRES SHALL BE RUN IN THE NEW

LOW VOLTAGE DUCTBANK. REFER TO ES102 AND CIVIL DRAWINGS FOR

FURTHER INFORMATION ON DUCTBANK ROUTING.

2. PROVIDE 12-PAIR SINGLE MODE FIBER (OM4) IN INNERDUCT IN 2" CONDUIT

FROM EXISTING FIBER NETWORK BOX TO NEW GENERATOR BUILDING 37.

ELECTRICAL

ENLARGED PLANS

BUILDINGS 13, 20, 26, 29 & 62

EP402

MJRTO

SCALE: 1/8" = 1'-0"

SCALE: 1/8" = 1'-0"

SCALE: 1/8" = 1'-0"

SCALE: 1/8" = 1'-0"

SCALE: 1/8" = 1'-0"SCALE: 1/8" = 1'-0"

SPS

DIRTY

ELEVATOR

EQUIP.

INVENTORY

MANAGEMENT

ELECT.

RM

CORRIDOR

VESTIBULE

RM

E

ELEVATOR

MECHANICAL

(E) ATS-15

480V, 600A

ZENITH

EXISTING

ELEVATOR

HALL

STAIRS

ELECTRICAL

GENERATOR

ROOM

ELECTRICAL

(E) ATS-13

480V, 400A

CAT

(E) ATS-16

480V, 225A

CAT

(E) ATS-14

480V, 400A

CAT

(E) ATS-12

480V, 600A

CAT

(D) GENERATOR "34"

800kW, 480-VOLT

(E) ATS-18

208V, 150A

CUMMINS

(E) ATS-17

208V, 225A

CUMMINS

W A

IT

IN

G

A

C

LA

S S R O O M

A

B R E A K

B

C

LA

S S R O O M

B

CORRIDOR

001-2

COFFEE

C

LA

S S R O O M

A

C

LA

S S R O O M

A

C

LA

S S R O O M

B

C

LA

S S R O O M

B

ELEC

001B

STOR.

001C

(E) ATS-19

208V, 200A

ZENITH

(E) PANEL ELL-G

208-VOLT

25,27,29 - 70A SPARE

AFTER EXITING BUILDING, CONDUIT SHALL

TURN DOWN INTO UNDERGROUND SITE

CONDUIT TO GATE. SEE ES102 CIVIL DRAWINGS

(CU100 & CU105) FOR CONTINUATION.

1" CONDUIT FOR GATE POWER

ABOVE ACCESSIBLE CEILING

(E) SELECTOR SWITCH "61"

(E) 1000kVA TRANSFORMER

(E) 16-DOOR

PACS PANEL

CAT-6A WIRE IN

3/4" C. TO

SECURITY GATE

AFTER EXITING BUILDING, CONDUIT SHALL

TURN DOWN INTO UNDERGROUND SITE

CONDUIT TO GATE. SEE ES102 CIVIL DRAWINGS

(CU100 & CU105) FOR CONTINUATION.

EXISTING

ELEVATOR

HALL

STAIRS

ELECTRICAL

GENERATOR

ROOM

ELECTRICAL

(E) ATS-13

480V, 400A

CAT

(E) ATS-16

480V, 225A

CAT

(E) ATS-14

480V, 400A

CAT

(E) ATS-12

480V, 600A

CAT

(N) TRANSFORMER "34"

1000kVA, 12,470V-480V

(N) LOOP FEED SWITCHES

NO. DESCRIPTION DATE

MILLER-REMICK LLC

PROFESSIONAL ENGINEER

PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE

WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE

PROFESSIONAL ENGINEER.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

BID DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

Phase

ENGINEER OF RECORDCONSULTANT CONSTRUCT CENTRALIZED

EMERGENCY POWER SYSTEM

589A7-21-132

Project Director

2026-03-26

321 4 5 6 7 8 9 10

A

B

C

D

E

F

21 4 5 6 7 8 9 10

A

C

D

E

F

M-R PROJECT NO: 0499-0162

ROBERT J. DOLE VA MEDICAL CENTER

WICHITA, KANSAS

Civil / Site Utility Engineering:Hazardous Materials:

MABBETT & ASSOCIATES, INC.

Fire & Life Safety:

STANTON ENGINEERING SERVICES, LLC

Architectural:

OCULUS, INC.

Structural:

PROFESSIONAL ENGINEERING

CONSULTANTS, PA (PEC)

IMEG, CORP. 37

1. REFER TO SHEETS E-001 AND E-002 FOR SYMBOLS, ABBREVIATIONS AND

NOTES.

2. ALL ELECTRICAL EQUIPMENT SHOWN ON THIS DRAWING SHALL BE EXISTING

TO REMAIN, UNLESS OTHERWISE NOTED.

GENERAL SHEET NOTES:

SHEET KEYNOTES:

ELECTRICAL

ENLARGED PLANS

BUILDINGS 34, 60 & 61

EP403

MJRTO

SCALE: 1/8" = 1'-0"

SCALE: 1/8" = 1'-0"

SCALE: 1/8" = 1'-0"

SCALE: 1/8" = 1'-0"

SCALE: 1/8" = 1'-0"

SCALE: 1/8" = 1'-0"

1. REMOVE EXISTING ATS SIGNALLING WIRE FROM EXISTING ATS TO

DEMOLISHED GENERATOR. CONDUIT PATHWAY SHALL BE EXISTING TO

REMAIN. EXISTING CONDUIT SHALL BE EXTENDED TO NEW LOW VOLTAGE

DUCTBANK, WHICH WILL BE INSTALLED DURING PHASE 1 OF THE PROJECT.

ELECTRICAL CONTRACTOR SHALL PROVIDE TWO (2) NEW #10 TWISTED PAIR

STRANDED CONTROL WIRES BETWEEN EXISTING ATS AND NEW MEDIUM

VOLTAGE GENERATORS. NEW CONTROL WIRES SHALL BE RUN IN THE NEW

LOW VOLTAGE DUCTBANK. REFER TO ES102 AND CIVIL DRAWINGS FOR

FURTHER INFORMATION ON DUCTBANK ROUTING.

2. PROVIDE ADDITIONAL DOOR CONTROL MODULE AS REQUIRED AS AN

EXTENSION OF THE EXISTING WICHITA VA STANDARD SOFTWARE HOUSE

C-CURE 9000 SYSTEM.

NO. DESCRIPTION DATE

MILLER-REMICK LLC

PROFESSIONAL ENGINEER

PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE

WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE

PROFESSIONAL ENGINEER.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

BID DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

Phase

ENGINEER OF RECORDCONSULTANT CONSTRUCT CENTRALIZED

EMERGENCY POWER SYSTEM

589A7-21-132

Project Director

2026-03-26

321 4 5 6 7 8 9 10

A

B

C

D

E

F

21 4 5 6 7 8 9 10

A

C

D

E

F

M-R PROJECT NO: 0499-0162

ROBERT J. DOLE VA MEDICAL CENTER

WICHITA, KANSAS

Civil / Site Utility Engineering:Hazardous Materials:

MABBETT & ASSOCIATES, INC.

Fire & Life Safety:

STANTON ENGINEERING SERVICES, LLC

Architectural:

OCULUS, INC.

Structural:

PROFESSIONAL ENGINEERING

CONSULTANTS, PA (PEC)

IMEG, CORP. 37

ELECTRICAL

DETAILS

E-501

MJRTO

EMT HOME

RUN

"SEALTITE"

CONN. TO

MOTOR

CEILING

SLAB

RIGID

STEEL

ELBOW

RIGID STEEL

CONDUIT

CLAMP

T-CONDUIT

FLOOR

SLAB

FLOOR FLANGE

SCALE:

CONDUIT - OVERHEAD DROP DETAIL

NTS

3M FIRE BARRIER FS-195

WRAP/STRIP IS BUTTED

SECURELY AGAINST THE

WALLBOARD

3M FIRE BARRIER RC-1

RESTRICTING COLLAR

STEEL HOSE

CLAMP

STUD

WALL

1-2 HR. FIRE RATED

GYPSUM WALL BOARD

3M FIRE BARRIER CP

25 CAULK OR MP

MOLDABLE PUTTY

STEEL HOLLOW WALL

SCREW ANCHORS (OR

EQUIVALENT) 3/16"x1-1/2"

LONG, MIN., WITH 1-1/4"

FENDER WASHERS

INSULATED METAL

PIPE/CONDUIT

FIBERGLASS

INSULATION

3/

M A

X . A

N N

U

LA

R

S P

A C

E

SCALE:

FIRE STOP FOR CONDUIT PENETRATION THROUGH

GYPSUM BOARD

NTS

3'-0" MAX

PROVIDE 5" OF SLACK AT MIDPOINT BETWEEN

TWO END OF FLEXIBLE GALVANIZED STEEL

CONDUIT. PROVIDE GREEN INSULATED

COPPER EQUIPMENT GROUNDING

CONDUCTOR WITH FLEXIBLE CONDUIT.

FLOOR OR ROOF STRUCTURE. FIELD

VERIFY ACTUAL CONDITIONS, TYP.

CONDUIT TRAPEZE SEE

DETAIL #1, DWG. #E-501.

CONDUIT, TYP.

SEISMIC OR EXPANSION JOINT.

FIELD VERIFY ACTUAL

CONDITIONS & LOCATIONS.

STRUCTURAL MEMBER

(BEAM, JOIST, ETC.), TYP.

STEEL EXPANSION

ANCHOR

INTEGRAL GALVANIZED LIPPED

STEEL MOUNTING CHANNEL

JUNCTION BOX

(SIZE AS REQUIRED)

CONDUIT

COMPRESSION FITTING

SPRING NUT

BEAM CLAMP, TYP.

SCALE:

CONDUIT - JOINT CROSSING DETAIL

NTS

PROVIDE EXTRA CABLE TO MAKE COMPLETE

LOOP AROUND BOX PERIMETER

GENERAL NOTE:

1. DETAIL IS APPLICABLE ONLY FOR CONDUIT SMALLER THAN 76mm (3").

NOTES

1. INTEGRAL GALVANIZED LIPPED STEEL MOUNTING

CHANNEL LONGER THAN 36" SHALL BE INSTALLED WITH A

CENTER SUPPORT ROD.

2. FASTEN THREADED ROD TO STRUCTURE BY APPROVED

METHOD PER SPECIFICATION 26 05 33, RACEWAYS AND

BOXES FOR ELECTRICAL SYSTEMS. FIELD VERIFY EXACT

CONDITIONS.

LENGTH AS REQUIRED

3/8" MIN.

GALVANIZED

THREADED ROD,

TYP.

LOCKING SQUARE

WASHER & LOCKNUT

INTEGRAL

GALVANIZED

LIPPED STEEL

MOUNTING

CHANNEL

WASHER &

LOCKNUT

REFER TO PLANS

FOR QUANTITY &

SIZE OF CONDUITS

CONDUIT CLAMP.

SIZE AS

REQUIRED

INTEGRAL

GALVANIZED

LIPPED STEEL

MOUNTING

CHANNEL

SCALE:

CONDUIT TRAPEZE MOUNTING DETAIL

NTS

GENERAL NOTES:

1. MAINTAIN A MINIMUM CLEARANCE OF 12" ON ALL SIDES OF ROOF

PENETRATION FROM WALLS, CURBS, AND OTHER PROJECTIONS TO

FACILITATE PROPER FLASHING.

2. FLANGES OF ADJACENT FLASHINGS SHALL NOT BE CUT OR OVERLAPPED.

3. VERIFY ROOF & STRUCTURAL SYSTEM WITH ARCHITECT.

4. COORDINATE FLASHING INSTALLATION WITH ROOFING CONTRACTOR TO

ENSURE PROPER METHODS & MATERIALS ARE USED TO MAINTAIN ROOF

WARRANTY.

STANDARD CLAMP, TYP.

PREFABRICATED RUBBER BOOT

CAP WITH GRADUATED STEPS &

WEATHER-POOF SEAL TO COLLAR

SEALANT AT PENETRATION

TO MEMBRANE JUNCTURE

BY ROOFING CONTRACTOR

ROOF

MEMBRANE

ROOF

WATER CUT-OFF MASTIC

COMPATIBLE WITH ROOF

MEMBRANE

CONDUIT CLAMP.

SIZE AS REQUIRED

SEAL-OFF FITTING TYP. CONDUIT TYP.

MULTIPLE MEMBRANE STRIPPING

PLIES FEATHERED AT FIELD OF ROOF

BY ROOFING CONTRACTOR. PRIME

FLANGE BEFORE STRIPPING.

PREFABRICATED FORMED .06" THICK

ALUMINUM FLASHING ROUND COLLAR WITH

MIN. 3" WIDE FLANGE. ATTACH TO ROOF

PER MANUFACTURER'S INSTRUCTIONS

BATT INSULATION

STEEL EXPANSION ANCHOR

3/8" MIN. GALVANIZED

THREADED ROD, TYP.

LOCKING SQUARE

WASHER &

LOCKNUT

INTEGRAL GALVANIZED LIPPED

STEEL MOUNTING CHANNEL

CONDUIT CLAMP.

SIZE AS REQUIRED

SCALE:

CONDUIT - ROOF PENETRATION DETAIL

NTS

1/2" x 12" POINT

BRONZE BONDING PLATE

BRONZE BONDING PLATE

SCALE:

TYPICAL LIGHTNING PROTECTION MECHANICAL

EQUIPMENT

NTS

UL

SOLID AIR TERMINAL TYP EVERY 20'

MAX. 2'-0"

FROM CORNER

APART

CONDUCTOR CABLE

CABLE FASTENER

FLAT ROOF POINT BASE

3' MAX.

3'-0" M

AX.

SCALE:

TYPICAL LIGHTNING

PROTECTION GLUE DOWN PERIMETER SYSTEM

NTS

SCALE:

TYPICAL LIGHTNING PROTECTION SYSTEM

CONNECTION DETAIL

NTS

CONTROL

CIRCUITRY

BLUEYELLOW

GRAY

PURPLE

BLACK

WHITE

EMERGENCY LIGHTING CONTROL DEVICE

NORMAL NEUTRAL

NORMAL HOT

EMERGENCY NEUTRAL

EMERGENCY HOT

WALL

SWITCH

SCALE:

UL 924 EMERGENCY LIGHT FIXTURE SWITCHING

CONTROL SCHEMATIC

NTS

Y

NOTES:

1. DEVICE SHALL BE MOUNTED ABOVE ACCESSIBLE CEILING AHEAD OF LIGHTING CONTROL DEVICE, I.E.

LIGHT SWITCH.

2. DEVICE IS RATED FOR AN 8-AMP CIRCUIT WHEN CONTROLLING LED FIXTURES.

TO NORMAL/EMERGENCY

LIGHTING NEUTRAL

TO NORMAL/EMERGENCY

LIGHTING HOT

TO NORMAL LIGHTING HOT

TO NORMAL LIGHTING NEUTRAL

SCALE:

GROUNDING BAR DETAIL

NTS

2"

4"

1" 1" 1"2"

1 1/2" TYP

1" 5/ 8"

5" 2"

MIN

1/4" DIA.

MOUNTING

HOLES TYP. OF

(4)3" DEEP FIBERGLASS

CHANNEL SAME

LENGTH AS CU BUSS

3/8" DIA. HOLE

TYP. OF (6)

1/2"DIA. x2"L. BOLT

TYP. OF (2)

1/2" NUT

1/2" LOCK WASHER

1/2" STANDARD WASHER

1/2" FENDER WASHERS (EACH SIDE)

1/4" THICK CU

BUSS

2'-0" MIN

1/4" DIA. HOLE

TYP OF (8)

NOTES

1. ALL HARDWARE SHOWN SHALL BE STAINLESS STEEL.

2. PROVIDE 1 MOUNTING POINT PER 12" OF BAR LENGTH.

3. HOLES MAY BE ADDED IF REQUIRED.

SECTION

STEEL EXPANSION

ANCHOR

SOLID AIR TERMINAL SECURELY

FASTENED TO PERIMETER WALLCOPING BONDING PLATE

20'-0" O.C. MAX SECONDARY CONDUCTOR

MAIN CONDUCTOR

PROVIDE WATERPROOF

CAULKING AS REQUIRED

ROOF

ROOF MFR APPROVED

THRU ROOF CONNECTOR

PROVIDE WATERPROOF

CAULKING AS REQUIRED

#4/0 BARE COPPER

DOWN CONDUCTOR

8" SQUARE BONDING PLATE

FASTENED TO STEEL WITH

STAINLESS STEEL NUTS & BOLTS

#4/0 BARE COPPER

DOWN CONDUCTOR

FLOOR

1" PVC

FOUNDATION WALL

NOTE:

1. ALL LIGHTNING PROTECTION

INSTALLATION SHALL BE IN

ACCORDANCE WITH NFPA 780

FOR CONNECTION TO BUILDING

SEE GROUNDING SYSTEM PLAN

AS SHOWN ON PLANS

GRADE

BUILDING WALL

4/0 COPPER MAIN LOOP

GROUNDING ELECTRODE SYSTEM

EXOTHERMIC WELD

SEAL CONDUIT WITH

APPROPRIATE SILICONE CAULK

TO A DEPTH OF 1" MINIMUM

3/4" DIA. X 10'-0" LONG

COPPERWELD GROUND ROD.

BUILDING STEEL

PARAPET OR SCREEN WALL

OR PERIMETER SYSTEM

METAL COPING

FASTENED

EVERY

3' MAX.

GENERAL NOTES:

1. INSTALL ALL MATERIALS IN ACCORDANCE WITH MANUFACTURER'S RECOMMENDATIONS.

LINK-SEAL OR EQUAL.

2. DETAIL APPLIES TO CONDUITS PENETRATING FOUNDATION WALL AND ROUTED TO THE

BUILDING EXTERIOR FOR SERVICES/SITE LIGHTING/HVAC EQUIPMENT CONNECTIONS.

3. REFER TO SPECIFICATION SECTION 079200.

SCALE:

EXTERIOR BUILDING CONDUIT PENETRATION DETAIL

NONE

PROFESSIONAL ENGINEER

PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE

WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE

PROFESSIONAL ENGINEER.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

BID DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

Phase

ENGINEER OF RECORDCONSULTANT CONSTRUCT CENTRALIZED

EMERGENCY POWER SYSTEM

589A7-21-132

Project Director

2026-03-26

321 4 5 6 7 8 9 10

A

B

C

D

E

F

21 4 5 6 7 8 9 10

A

C

D

E

F

M-R PROJECT NO: 0499-0162

ROBERT J. DOLE VA MEDICAL CENTER

WICHITA, KANSAS

Civil / Site Utility Engineering:Hazardous Materials:

MABBETT & ASSOCIATES, INC.

Fire & Life Safety:

STANTON ENGINEERING SERVICES, LLC

Architectural:

OCULUS, INC.

Structural:

PROFESSIONAL ENGINEERING

CONSULTANTS, PA (PEC)

IMEG, CORP. 37

ELECTRICAL

DETAILS

E-502

MJRTO

DOOR STRIKE

(PROVIDED BY GEN.

CONTR.)

CONDUIT

& WIRING

TO CARD

READER

PROXIMITY

CARD

READER

NOTE;

1. EC TO COORDINATE WITH DOOR VENDOR THE REQUIRED DOOR LOCKING HARDWARE.

2. CONDUIT AND WIRE SIZE AS RECOMMENDED BY MANUFACTURER

3. DOOR SHALL ADHERE TO NFPA 101 AND SHALL RELEASE UPON ONE OF SEVERAL

"EMERGENCY" CONDITIONS SUCH AS: LOSS OF POWER TO SENSOR, FIRE ALARM SIGNAL,

ETC.

(TYP) DOOR

CONTACT

SWITCH

TO FIRE ALARM PANEL

SECURE AREA CEILING LINE

FLOOR

SCALE:

CARD ACCESS SINGLE DOOR DETAIL

NTS

TYP. CONDUIT

& WIRING FROM

CONTROLLER FOR

DOOR RELEASE

PANEL-CIRCUIT#

AHU-X

AHU-X

480v, 3Ø

FED FROM "XXX"

480v, 3Ø

FED FROM "XXX"

1/2" HIGH LETTERING FOR EQUIPMENT NAME

1/4" HIGH LETTERING FOR REMAINING TEXT

EQUIPMENT NAME

EQUIPMENT VOLTAGE AND PHASE

EQUIPMENT SOURCE

120/208V, 3Ø 4W

FED FROM PANEL "XXX"

VIA "T-XXX"

PANEL "XXXXX"

PANEL "XXXXX"

277/480V, 3Ø, 4W

FED FROM "XXX"

TYPICAL 277/480V PANELBOARD

TYPICAL 120/208V PANELBOARD

1/16" THICK PLASTIC WITH COLORED

FACE PER SPECIFICATIONS

1/2" HIGH LETTERING FOR EQUIPMENT NAME

FASTEN WITH SELF TAPPING STAINLESS

STEEL SCREWS, EA SIDE

1/4" HIGH LETTERING FOR REMAINING TEXT

PANELBOARD NAME

FASTEN WITH SELF TAPPING STAINLESS

STEEL SCREWS, EA SIDE

PANELBOARD VOLTAGE

PANELBOARD SOURCE

FASTEN WITH SELF TAPPING STAINLESS STEEL

SCREWS, EA SIDE

FASTEN WITH SELF TAPPING STAINLESS STEEL

SCREWS, EA SIDE

1/16" HICK NAMEPLATES WITH COLORED

FACE PER SPECIFICATIONS

LABEL COLOR:

1. LABELS FOR EMERGENCY POWER SHALL BE RED WITH ENGRAVED WHITE LETTERS.

2. LABELS FOR NORMAL POWER SHALL BE BLACK WITH ENGRAVED WHITE LETTERS.

LABEL COLOR:

1. LABELS FOR EQUIPMENT FED BY EMERGENCY POWER SHALL BE RED WITH ENGRAVED WHITE LETTERS.

2. LABELS FOR EQUIPMENT FED BY NORMAL POWER SHALL BE BLACK WITH ENGRAVED WHITE LETTERS.

SCALE:

PANELBOARD NAMEPLATES

NONE SCALE:

EQUIPMENT NAMEPLATES

NONE

SCALE:

TYPICAL RECEPTACLE NAMEPLATE

NONE

GENERAL NOTE:

ALL RECEPTACLES WHETHER DUPLEX OR QUADRAPLEX OR

ANY OTHER NEMA CONFIGURATION SHALL BE LABELED.

CIRCUIT DESIGNATION LABEL. 3/8" HIGH

WHITE LETTERING ON RED BACKGROUND

FOR EMERGENCY, WHITE LETTERING ON

BLACK BACKGROUND FOR NORMAL. USE

PERMANENT ADHESIVE TO SECURE

NAMETAG. LABEL ALL RECEPTACLES IN

PROJECT.

DUPLEX RECEPTACLE

120V IN

24V TRANSFORMER

PACS CONTROLLER

CONDUIT AND WIRING TO

PACS CONTROL PANEL

(7)

(8) (9)

(3)

(4)

(11)

(12)

(10)

(5) (6)

REFERENCE NOTES:

1. CONCRETE HOUSEKEEPING PAD.

2. CONCRETE ANCHOR BOLT, 4

REQUIRED.

3. TRANSFORMER BASE CHANNEL.

4. 1/2"Ø NUT, BOLT, & LOCK WASHER,

6 REQUIRED.

5. GROUND CONNECTOR.

6. SECONDARY CONNECTION DETAIL,

PRIMARY - SIMILAR.

7. TRANSFORMER - MOUNT BOTTOM

SUPPORTS 6'-6" AFF.

8. NAMEPLATE - CONNECTION

DIAGRAM TO FACE CLOSET

ENTRANCE.

9. EXTERNAL COPPER BONDING

WIRE.

10. LIQUID TIGHT FLEXIBLE METAL

CONDUIT 18" MIN.

11. RIGID CONDUIT.

12. COMBINATION COUPLING. (2)

(1)

SAFETY CHAIN OR

CABLE PER EACH LUMINARE

TYPICAL ROOF TRUSS OR

MULTI HOLE CHANNEL.

INTERMEDIATE SPAN OF

12 GAGUE MINIMUM

1 5/8" x 1 5/8"

JUNCTION BOX

FLEX CORD

CONDUIT

RED LABEL WITH

1/4"(6.35MM) WHITE

ENGRAVED LETTERS

ADA COMPLIANT

POLYCARBONATE

PROTECTIVE HINGED

COVER

60MM DIAMETER, RED

MUSHROOM HEAD

PUSHBUTTON

OVERSIZED 302

STAINLESS STEEL WALL

PLATE

POWER

DEACTIVATION

SWITCH EMERGENCY

USE ONLY

WALL

OUTLET

BOX

CONTACT

BLOCKS

NOTES:

1. SEE POWER PLANS FOR LOCATION OF CONTRACTOR SUPPLIED EPO SWITCHES.

LOCK WASHER

DOUBLE NUTS

1/2" EYE BOLT MINIMUM

NUT

FLAT WASHER

AIRCRAFT CABLE (TYP)

HIGH BAY FIXTURE (TYP)

SCALE:

LUMINAIRE MOUNTING - HIGH BAY DETAIL

NONE

SCALE:

TRANSFORMER MOUNTING DETAIL - FLOOR

NONE SCALE:

EMERGENCY POWER OFF PUSHBUTTON - EPO

NONE

#6 MIN.

DOWN CONDUCTOR TYP.

#3/0 UNLESS NOTED

OTHERWISE

GENERATOR BUILDING

WALL MOUNTED COPPER

EQUIPMENT GROUND BUS BAR

(1/4" X 4")

TO

FIRE

ALARM

SYSTEM

GROUNDING

TO

TELEPHONE

SYSTEM

GROUNDING

TO A/V

SYSTEM

GROUNDING

#3/0 MIN.

GROUND RING

LIGHTNING

PROTECTION GROUND

ROD (TYPICAL)

AIR TERMINAL

"LIGHTNING ROD"

ROOF (TYPICAL)

EQUIPMENT

RACKS

BUILDING

STEEL

ALL SLEEVES

AND RACEWAYS

TYPICAL

EQUIPMENT

BONDED TO

GROUND BAR

#6 COPPER

BONDING

CONDUCTOR

(TYPICAL)

TO TYPICAL

BRANCH

CIRCUIT

NEUTRAL BUS

GROUNDING BUS

480-VOLT PANEL

(TYPICAL)

TRANSFORMER

(TYPICAL)

TO TYPICAL

BRANCH

CIRCUIT

120-VOLT PANEL

(TYPICAL)

1. ALL GROUNDING CONDUCTORS OUTSIDE OF AN ELECTRICAL EQUIPMENT

ENCLOSURE SHALL BE PROTECTED BY PROVIDING A RACEWAY.

2. CONDUITS ATTACHED TO ELECTRICAL EQUIPMENT ENCLOSURES SHALL BE

SECURELY BONDED TO THOSE ENCLOSURES WITH GROUND FITTINGS.

3. ALL CABLE CONNECTIONS TO BE MADE BY A 12-TON COMPRESSION TOOL OR

EXOTHERMIC WELDING, EXCEPT TO GROUND LUGS ON BUS BARS AND

BLOCKS.

4. ALL BUSBARS SHALL BE 1/4" X 4" X 24" PRE-DRILLED TIN-PLATED COPPER.

MOUNT ON WALL WITH 2" STANDOFF INSULATORS.

5. ALL CABLE CONNECTIONS TO GROUND BAR SHALL BE TWO HOLE TONGUE

COMPRESSION LUGS.

6. ALL GROUNDING CONDUCTORS SHALL BE COPPER CONDUCTORS WITH GREEN

INSULATION OR DISTINCTIVE GREEN MARKING.

SCALE:

GROUNDING DIAGRAM

NTS

NEW/TEMPORARY

WORK

M1

(E) XFMR

1000 KVA

480-12470V

(E) SOLAR SYSTEM

SPACE SPACE

NO. DESCRIPTION DATE

MILLER-REMICK LLC

PROFESSIONAL ENGINEER

PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE

WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE

PROFESSIONAL ENGINEER.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

BID DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

Phase

ENGINEER OF RECORDCONSULTANT CONSTRUCT CENTRALIZED

EMERGENCY POWER SYSTEM

589A7-21-132

Project Director

2026-03-26

321 4 5 6 7 8 9 10

A

B

C

D

E

F

21 4 5 6 7 8 9 10

A

C

D

E

F

M-R PROJECT NO: 0499-0162

ROBERT J. DOLE VA MEDICAL CENTER

WICHITA, KANSAS

Civil / Site Utility Engineering:Hazardous Materials:

MABBETT & ASSOCIATES, INC.

Fire & Life Safety:

STANTON ENGINEERING SERVICES, LLC

Architectural:

OCULUS, INC.

Structural:

PROFESSIONAL ENGINEERING

CONSULTANTS, PA (PEC)

IMEG, CORP. 37

1. REFER TO SHEETS E-001 AND E-002 FOR SYMBOLS, ABBREVIATIONS AND

NOTES.

2. REFER TO SHEET ES102 FOR LOCATION OF ALL NEW AND EXISTING

DUCTBANKS AND MANHOLES.

3. REFER TO SPECIFICATION 262315 EMERGENCY POWER SEQUENCE OF

OPERATION FOR INFORMATION ON THE OPERATIONAL SWITCHING INTENT OF

THE CAMPUS EMERGENCY SYSTEM.

4. GENERATORS SHALL BE MONITORED BY EXISTING CAMPUS SIEMENS BAS

SYSTEM. CONTRACTOR SHALL HARDWIRE ALL NEW ELECTRICAL

COMPONENTS TO BE MONITORED TO THE NEW BUILDING 37 BAS PANEL.

5. PROVIDE AN ADDITIONAL I/O CARD WITH EACH GENERATOR TO ACCOUNT FOR

AN INCREASED ALARM COUNT (LOW OIL PRESSURE, HIGH COOLANT ALARM,

BASIN RUPTURE, NOT IN AUTO, BATTERY CHARGER, LOW FUEL, LOW

COOLANT, ETC)

6. PARALLELING SWITCHGEAR SHALL PROVIDE A REPORT COVERING

GENERATOR RUNTIME VIA THE LOW VOLTAGE CAT 6A CONNECTION TO THE

BAS SYSTEM PANEL.

GENERAL SHEET NOTES: SHEET KEYNOTES:

1. NEW FEEDER SHALL BE 3-#4/0 MV-105 (15KV RATED) PULLED THROUGH

EXISTING UNDERGROUND DUCTBANK TO (E) MANHOLE MH-2B.

2. PROVIDE NEW METALCLAD SWITCHGEAR SECTION TO MATCH EXISTING TYPE

(SQUARE D MASTERCLAD) AND AIC RATING. EXTEND EXISTING BUSSING INTO

NEW SWITCHGEAR SECTION.

3. NEW EMERGENCY POWER LOOP: 3-#350KCMIL (15KV RATED) IN 5" SCHEDULE

40 PVC CONDUIT + (1) SPARE 5" SCHEDULE 40 PVC CONDUIT WITHIN NEW

CONCRETE ENCASED DUCTBANK.

4. GENERATOR LOAD BANK IS A PERMANENTLY INSTALLED PIECE OF

EQUIPMENT. BASIS OF DESIGN FOR THE LOAD BANK SHALL BE AVTRON

MODEL 9810. 480-VOLT LOAD BANK AND ASSOCIATED STEPDOWN

TRANSFORMER ARE SKID MOUNTED ON RAILS AND SET ON A HOUSEKEEPING

PAD. PRIMARY RATING SHALL BE 12,470-VOLT, 1-MW.

5. 12,470-VOLT NEMA 3R, 300-AMP RATED GENERATOR TAP BOX WITH CAMLOCK

CONNECTORS

6. ELECTRONIC POWER DEMAND (EPDM) METERING: BASIS OF DESIGN SHALL BE

SCHNEIDER ELECTRIC/SQUARE D TO MATCH EXISTING SYSTEM. PROVIDE

EPDM METER INTEGRATED TO PARALLELING SWITCHGEAR. EPDM METER

SHALL RECORD, STORE AND TREND VOLTAGE, CURRENT, kW, kWH, kVA, kVAR, POWER FACTOR AS WELL AS TOTAL HARMONIC DISTORTION. PROVIDE

CAPABILITY OF COMMUNICATION WITH THE EXISTING CENTRALIZED VA

MONITORING SYSTEM VIA THE BAS SYSTEM. PROVIDE CAT 6A DATA CABLES

IN 3/4" C. FROM EDPM METER TO NEW BAS PANEL IN BUILDING 37.

ELECTRICAL

NEW WORK SWITCHGEAR

SINGLE LINE DIAGRAM

E-601

MJRTO

DEMOLITION

EXISTING TO

REMAIN

(E) MAIN SWITCHGEAR 35, BUILDING 35A

12470V, 3Ø, 4W, 34KA MOMENTARY BRACING

TIE BREAKER

PAWNEE

LINE 12-12

M1

EASTBOROUGH

LINE 12-34

3MW, 12,470-VOLT

GENERATOR

(N) PARALLELING SWITCHGEAR

12470-VOLT, 1200-AMP BUS, 3Ø, 3W, 34KAIC

BASIS OF DESIGN: ASCO

3MW, 12,470-VOLT

GENERATOR

3MW, 12,470-VOLT

GENERATOR

NORMAL POWER BACKUP FEEDERS TO EXISTING CAMPUS SWITCHGEAR

3-#350KCMIL (15kV RATED) IN 5" SCHEDULE 40 PVC CONDUIT + (1) SPARE 5"

SCHEDULE 40 PVC CONDUIT WITHIN NEW CONCRETE ENCASED DUCTBANKNEW GENERATOR BUILDING

SEE DRAWING E-602 FOR EXISTING CAMPUS NORMAL

LOOP DUCTBANK CONTINUATION

SEE DRAWING E-602 FOR NEW CAMPUS NORMAL LOOP

DUCTBANK CONTINUATION

SEE DRAWING E-603 FOR NEW CAMPUS

EMERGENCY LOOP DUCTBANK CONTINUATION

1200A

1200A 1200A

1200A

1200A1200A 1200A 1200A

1200A

1200A 1200A 1200A

1200A1200A

NEUTRAL

GROUND

RESISTOR

NEUTRAL GROUND

RESISTOR

NEUTRAL

GROUND

RESISTOR

PERMANENTLY

INSTALLED

LOAD BANK

3-#2 (15kV RATED) IN 5" SCHEDULE 40 PVC

CONDUIT + (1) SPARE 5" SCHEDULE 40 PVC

CONDUIT WITHIN NEW CONCRETE

ENCASED DUCTBANK

3-#350KCMIL (15kV RATED)

IN 5" C.

SEE DRAWING E-603 FOR NEW CAMPUS

EMERGENCY LOOP DUCTBANK CONTINUATION

3-#350KCMIL

(15kV RATED)

IN 5" C.

3-#350KCMIL

(15kV RATED)

IN 5" C.

3-#350KCMIL

(15kV RATED)

IN 5" C.

MASTER

CONTROLS

(E)

SELECTOR

SWITCH 2

(E) XFMR

500 KVA

12470-480/2770V

CATH LAB

BLDG 2

(H1)

BLDG 19

(E)

SELECTOR

SWITCH 19

(E) XFMR

500 KVA

12470-480/2770V

(E)

SELECTOR

SWITCH 34

(E) XFMR

1000 KVA

12470-480/2770V

(SWGR 34A)

BLDG 34

(E)

SELECTOR

SWITCH 41

(E) XFMR 41

225 KVA

12470-480/2770V

(ML4B)

BLDG 4

(E)

SELECTOR

SWITCH 49

(E)

SELECTOR

SWITCH 42

(E) XFMR

500 KVA

12470-480/2770V

(SWGR 61)

BLDG 5,6,7

(E)

SELECTOR

SWITCH 60

(E) XFMR

300 KVA

12470-208/120V

(SWGR 61)

BLDG 60

(E) SELECTOR

SWITCH 53

NEAR BLDG 11

(SWGR 53)

NEAR BLDG 11

(SWGR 49)

BLDG 1

NEW/TEMPORARY

WORK

(E)

SELECTOR

SWITCH 61

(E) XFMR

1000 KVA

12470-480/2770V

(SWGR 61)

BLDG 61

(E)

SELECTOR

SWITCH 55

(SWGR 55)

BLDGS 3 & 26

NO. DESCRIPTION DATE

MILLER-REMICK LLC

PROFESSIONAL ENGINEER

PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE

WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE

PROFESSIONAL ENGINEER.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

BID DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

Phase

ENGINEER OF RECORDCONSULTANT CONSTRUCT CENTRALIZED

EMERGENCY POWER SYSTEM

589A7-21-132

Project Director

2026-03-26

321 4 5 6 7 8 9 10

A

B

C

D

E

F

21 4 5 6 7 8 9 10

A

C

D

E

F

M-R PROJECT NO: 0499-0162

ROBERT J. DOLE VA MEDICAL CENTER

WICHITA, KANSAS

Civil / Site Utility Engineering:Hazardous Materials:

MABBETT & ASSOCIATES, INC.

Fire & Life Safety:

STANTON ENGINEERING SERVICES, LLC

Architectural:

OCULUS, INC.

Structural:

PROFESSIONAL ENGINEERING

CONSULTANTS, PA (PEC)

IMEG, CORP. 37

1. REFER TO SHEETS E-001 AND E-002 FOR SYMBOLS, ABBREVIATIONS AND

NOTES.

2. REFER TO SHEET ES102 FOR LOCATION OF ALL NEW AND EXISTING

DUCTBANKS AND MANHOLES. REFER TO DETAILS ON CIVIL DRAWINGS FOR

FURTHER INFORMATION ON DUCTBANK AND MANHOLES CONSTRUCTION.

GENERAL SHEET NOTES:

SHEET KEYNOTES:

1. NEW FEEDER SHALL BE 3-#4/0 MV-105 (15KV RATED), 1-#6 G. PULLED THROUGH

EXISTING UNDERGROUND DUCTBANK.

2. NEW FEEDER SHALL BE 3-#4/0 MV-105 (15KV RATED), 1-#6 G. PULLED THROUGH

NEW CONCRETE ENCASED DUCTBANK.

ELECTRICAL

NEW WORK CAMPUS NORMAL LOOP

SINGLE LINE DIAGRAM

E-602

MJRTO

SCALE: NTS

DEMOLITION

EXISTING TO

REMAIN

TO SECTION 6

SEE E-601 FOR

CONTINUATION

TO SECTION 7

SEE E-601 FOR

CONTINUATION

TO SECTION 7

SEE E-601 FOR

CONTINUATION

TO SECTION 2

SEE E-601 FOR

CONTINUATION

TO SECTION 2

SEE E-601 FOR

CONTINUATION

TO SECTION 3

SEE E-601 FOR

CONTINUATION

NEW/TEMPORARY

WORK

NO. DESCRIPTION DATE

MILLER-REMICK LLC

PROFESSIONAL ENGINEER

PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE

WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE

PROFESSIONAL ENGINEER.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

BID DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

Phase

ENGINEER OF RECORDCONSULTANT CONSTRUCT CENTRALIZED

EMERGENCY POWER SYSTEM

589A7-21-132

Project Director

2026-03-26

321 4 5 6 7 8 9 10

A

B

C

D

E

F

21 4 5 6 7 8 9 10

A

C

D

E

F

M-R PROJECT NO: 0499-0162

ROBERT J. DOLE VA MEDICAL CENTER

WICHITA, KANSAS

Civil / Site Utility Engineering:Hazardous Materials:

MABBETT & ASSOCIATES, INC.

Fire & Life Safety:

STANTON ENGINEERING SERVICES, LLC

Architectural:

OCULUS, INC.

Structural:

PROFESSIONAL ENGINEERING

CONSULTANTS, PA (PEC)

IMEG, CORP. 37

1. REFER TO SHEETS E-001 AND E-002 FOR SYMBOLS, ABBREVIATIONS AND

NOTES.

2. REFER TO SHEET ES102 FOR LOCATION OF ALL NEW AND EXISTING

DUCTBANKS AND MANHOLES.

GENERAL SHEET NOTES:

SHEET KEYNOTES:

ELECTRICAL

NEW WORK CAMPUS EMERGENCY

LOOP SINGLE LINE DIAGRAM

E-603

MJRTO

DEMOLITION

EXISTING TO

REMAIN

(N) PAD MOUNTED XFMR-26

REPLACING GENERATOR "26"

500-KVA

12470V-208V

GEC: #3/0

EXISTING BLDG EMERGENCY

DISTRIBUTION SYSTEM

SEE DETAIL 2/ED602.

TO NEW PARALLELING SWITCHGEAR SECTION 2

SEE DRAWING E-601 FOR CONTINUATION

1. NEW EMERGENCY LOOP WITHIN NEW CONCRETE ENCASED UNDERGROUND

DUCTBANK. SEE DRAWING E-601 FOR FEEDER SIZES.

2. SPLICE AND EXTEND EXISTING GENERATOR FEEDER IN EXISTING CONDUIT AS

REQUIRED FOR CONNECTION TO NEW TRANSFORMER.

3. PROVIDE NEW 2" CONDUIT FROM NEW ATS-21 TO NEW UNDERGROUND

CONCRETE ENCASED LOW VOLTAGE DUCTBANK FOR SIGNALING WIRE

ROUTING TO NEW GENERATOR BUILDING. NEW LOW VOLTAGE CONTROL

WIRING (TWO SETS OF #10 TWISTED PAIR) BETWEEN NEW ATS-21 AND NEW

MEDIUM VOLTAGE GENERATORS SHALL BE RUN IN THIS PATHWAY.

4. NEW UNDERGROUND CONCRETE ENCASED DUCTBANK CONDUITS SHALL BE

EXTENDED AS REQUIRED FOR LOOP FEEDER TERMINATION SUNDER THE

EXISTING GENERATOR CONCRETE PAD AT THE LOCATION OF EACH OF THE

TWO (2) LOOP FEED SWITCHES.

EXISTING BLDG EMERGENCY

DISTRIBUTION SYSTEM

SEE DETAIL 3/ED602.

EXISTING BLDG EMERGENCY

DISTRIBUTION SYSTEM

SEE DETAIL 4/ED602.

(N) PAD MOUNTED XFMR-2

REPLACING GENERATOR "1B & 2"

750-KVA

12470V-480V

GEC: #3/0

(N) PAD MOUNTED XFMR-34

REPLACING GENERATOR "34"

1000-KVA

12470V-480V

GEC: #3/0

30A

200A

50A

200A

60A

200A

EXISTING BLDG EMERGENCY

DISTRIBUTION SYSTEM

SEE DETAIL 1/ED602.

(N) PAD MOUNTED XFMR-62

REPLACING GENERATOR "62"

300-KVA

12470V-480V

GEC: #1/0

20A

200A

EXISTING BLDG EMERGENCY

DISTRIBUTION SYSTEM

SEE DETAIL 5/ED602.

(N) PAD MOUNTED XFMR-31

REPLACING GENERATOR "31"

300-KVA

12470V-208V

GEC: #3/0

20A

200A

EXISTING BLDG EMERGENCY

DISTRIBUTION SYSTEM

SEE DETAIL 6/ED602.

(N) PAD MOUNTED XFMR-31A

REPLACING GENERATOR "31A"

300-KVA

12470V-240V

GEC: #3/0

20A

200A

EXISTING BLDG EMERGENCY

DISTRIBUTION SYSTEM

SEE DETAIL 7/ED602.

(N) PAD MOUNTED XFMR-5

REPLACING GENERATOR "5"

112.5-KVA

12470V-208V

GEC: #1/0

10A

200A

EXISTING BLDG EMERGENCY

DISTRIBUTION SYSTEM

SEE DETAIL 8/ED602.

(N) PAD MOUNTED XFMR-21

REPLACING GENERATOR "21"

75-KVA

12470V-208V

GEC: #2

10A

200A

EXISTING BLDG EMERGENCY

DISTRIBUTION SYSTEM

SEE DETAIL 9/ED602.

(N) PAD MOUNTED XFMR-13

REPLACING GENERATOR "13"

150-KVA

12470V-208V

GEC: #1/0

10A

200A

TO NEW PARALLELING SWITCHGEAR SECTION 7

SEE DRAWING E-601 FOR CONTINUATION

SCALE: NTS

(N) ATS-21

208-VOLT, 225-AMP

NEMA 3R RATED

RECONNECT TO EXISTING NORMAL

POWER FEEDER TO BUILDING 21

4-#4/0, 1-#4G IN 2 1/2" C.

PROFESSIONAL ENGINEER

PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE

WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE

PROFESSIONAL ENGINEER.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

BID DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

Phase

ENGINEER OF RECORDCONSULTANT CONSTRUCT CENTRALIZED

EMERGENCY POWER SYSTEM

589A7-21-132

Project Director

2026-03-26

321 4 5 6 7 8 9 10

A

B

C

D

E

F

21 4 5 6 7 8 9 10

A

C

D

E

F

M-R PROJECT NO: 0499-0162

ROBERT J. DOLE VA MEDICAL CENTER

WICHITA, KANSAS

Civil / Site Utility Engineering:Hazardous Materials:

MABBETT & ASSOCIATES, INC.

Fire & Life Safety:

STANTON ENGINEERING SERVICES, LLC

Architectural:

OCULUS, INC.

Structural:

PROFESSIONAL ENGINEERING

CONSULTANTS, PA (PEC)

IMEG, CORP. 37

ELECTRICAL

SCHEDULES &

BUILDING 37 SINGLE LINE DIAGRAM

E-701

MJRTO

(E) BUILDING 13-EMDP

480/277V, 600A, 3Ø, 4W, 42KAIC

SEE DETAIL 1/EP402 FOR LOCATION.

1 2 3 4

80A 3P

80A 3P

600A 3P

225A 3P

5 6

80A 3P

70A 3P

7 8

BOILER #1 BOILER #2

9 10

175A 3P

BOILER #3

FEED WATER

PUMPS (SKID)

100A 3P

70A 3P

60A 3P

150A 3P

BOILER

COMPRESSORS

(SKID)

200A 3P

QUICK

CONNECT BOX

-T

-E

LP

-T

-E

LD

P

SPD

(E) (E) (E) (E) (E) (E) (E) (E) (E) (N) (E)

SPD

SCALE: NTS

(E) (E) (E) (E) (E) (E) (E) (E)

A

GROUND

WIRE SIZE (AWG/KCMIL)

WIRE AND CONDUIT SIZING SCHEDULE

CONDUCTOR PHASE &

NEUTRAL

SINGLE LINE TAG: THIS

COLUMN COMBINED

WITH "A", "B", OR "C"

COLUMN

NO. OF WIRES & CONDUIT

SIZE IN INCHES

1. CONDUIT SIZES SHOWN ARE TYPICAL FOR CONDUCTOR SIZES AND QUANTITY. CONDUIT AND WIRE SIZE NOTED ON THE

ELECTRICAL FLOOR PLANS AND SINGLE LINE TAKE PRECEDENCE.

1PH, 2W+G 3PH, 3W+G 3PH, 4W+G

B C

EX EXISTING FEEDERS AND CONDUIT

3/41414 3/4 3/4

3/41212 3/4 3/4

3/41010 3/4 3/4

3/48 3/4 3/4

3/46 3/4 1

3/44 1

3/484

1 1/41

1/0 1 1/2

2/0 2

3/0 2 2

44/0

350 3

(2) 1 1/2(2) 3(2) 3/0

(2) 2(2) 4/0 (2) 2 (2) 2 1/2

(2) 250

(2) 350

(2) 500

(3) 300

(3) 400

(4) 350

(5) 400

(6) 400

(7) 500

(8) 500

(2) 2

(2) 1

(2) 1/0

(3) 1/0

(3) 2/0

(4) 3/0

(5) 4/0

(6) 250

(7) 350

(8) 400

2 1/2

2 1/2

(2) 2

(2) 2 1/2

(2) 3

(3) 2 1/2

(3) 3

(4) 2 1/2

(5) 3

(6) 3

(7) 3

(8) 3

(2) 2 1/2

(2) 3

(2) 3 1/2

(3) 3

(3) 3

(4) 3

(5) 3

(6) 3

(7) 3 1/2

(8) 3 1/2

1 1/4

1 1/4

1 1/2

1 1/2

1 1/2

1 1/4

1 1/4

1 1/4

1 1/4

1 1/4

1 1/4

1 1/4

1 1/2

1 1/2

1 1/2

2 1/2

2 1/2

2 1/2

1 6 1 1/4 1 1/4 1 1/2

(2) 2 (2) 2

500 33 2 1/2 3

32 (2) 350 (2) 2/0 (2) 2 1/2 (2) 3

EGC: #6

BUILDING 13 INTERIOR

BUILDING 13 EXTERIOR

ROUTED IN CONCRETE

ENCASED DUCTBANK.

SEE CIVIL DRAWINGS

FOR FURTHER DETAIL.

SPD

ROUTE ALONG INTERIOR OF BOILER

PLANT TO BUILDING WEST EXTERIOR

WALL. SEE DETAIL 1/EP402 FOR

FURTHER INFORMATION.

MAIN CIRCUIT BREAKER

SHALL BE SERVICE

ENTRANCE RATED.

NOTES:

1. ELECTRICAL CONTRACTOR SHALL REMOVE EXISTING 60-AMP/3-POLE CIRCUIT BREAKER

AND REPLACE WITH A NEW 150-AMP CIRCUIT BREAKER. NEW CIRCUIT BREAKER SHALL

MATCH EXISTING BREAKER'S TYPE (SCHNEIDER ELECTRIC) AND AIC RATING (42kA).

SEE NOTE 1.

BUILDING 37

TRANSFORMER T1

30kVA

(E)

PANEL

13-EMH1

(E)

PANEL

13-EMH2

(E)

PANEL

13-ELDP

SPD

(E)

PANEL

13-ELP3

E-001 - ELECTRICAL ABBREVIATIONS & SYMBOLS
E-002 - ELECTRICAL NOTES
ED602 - ELECTRICAL DEMOLITION BUILDING SINGLE LINE DIAGRAMS
ES101 - ELECTRICAL DEMOLITION SITE PLAN
ES102 - ELECTRICAL NEW WORK SITE PLAN
EP101 - ELECTRICAL POWER PLAN BUILDING 35A
EL111 - ELECTRICAL LIGHTING PLAN GROUND FLOOR
EP111 - ELECTRICAL POWER PLAN GROUND FLOOR
EP131 - ELECTRICAL POWER & LIGHTNING PROTECTION PLAN -ROOF
EY111 - ELECTRICAL SIGNAL PLAN GROUND FLOOR
EP401 - ELECTRICAL ENLARGED PLANS BUILDINGS 1, 2, 5 & 36
EP402 - ELECTRICAL ENLARGED PLANS BUILDINGS 13, 20, 26, 29 & 62
EP403 - ELECTRICAL ENLARGED PLANS BUILDINGS 34, 60 & 61
E-501 - ELECTRICAL DETAILS
E-502 - ELECTRICAL DETAILS
E-601 - ELECTRICAL NEW WORK SWITCHGEAR SINGLE LINE DIAGRAM
E-602 - ELECTRICAL NEW WORK CAMPUS NORMAL LOOP SINGLE LINE DIAGRAM
E-603 - ELECTRICAL NEW WORK CAMPUS EMERGENCY LOOP SINGLE LINE DIAGRAM
E-701 - ELECTRICAL SCHEDULES & BUILDING 37 SINGLE LINE DIAGRAM