589A7-21-132 Wichita Bid Drawings 08_Electrical 2 of 2.pdf
PDF 9 MB Posted
- Solicitation number
- 36C25526R0125
About this file
This document is a set of bid documents containing electrical design drawings and specifications for a Centralized Emergency Power System project at Robert J. Dole VA Medical Center in Wichita, Kansas (Project No. 0499-0162). The drawings are prepared by Miller-Remick LLC as the Professional Engineer of Record, with associated consultants including IMEG Corp (Civil/Site Utility Engineering), Stanton Engineering Services LLC (Fire & Life Safety), Mabbett & Associates Inc. (Hazardous Materials), Oculus Inc. (Architectural), and Professional Engineering Consultants PA (Structural).
The project involves installation of three 3MW, 12,470-volt generators with associated paralleling switchgear, transformers, and automatic transfer switches (ATS) to replace existing distributed generators across multiple buildings. Key infrastructure includes a new generator building (Building 37), concrete-encased underground ductbanks for medium and low voltage distribution, pad-mounted transformers replacing existing generators in Buildings 2, 5, 13, 21, 26, 31, 31A, 34, and 62, and new electrical distribution systems throughout the facility. The work encompasses signal plans, electrical enlarged plans for multiple buildings, conduit and equipment mounting details, grounding and lightning protection systems, fire-rated penetration details, emergency lighting controls, card access systems, equipment nameplate schedules, and single-line diagrams for both the new switchgear and campus normal and emergency power loops. All electrical equipment shown is either existing to remain unless otherwise noted, or marked as new work. The drawings are fully sprinklered and dated March 26, 2026.
View the file
Other files
Show all 30
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
CR
CR
CR
W +W
CRCR
CR
2 31 4
A
B
C
LOCKABLE
TELECOMMUNICATIONS
ENCLOSURE
GENERATOR
ROOM
FIRE RISER
ROOM
TIE CARD READER TO
ROLL-UP DOOR
OPERATOR
PANORAMIC MULTI-
SENSOR EXTERIOR
CAMERA
(TYPICAL FOR 4
EXTERIOR CAMERAS)
TIE CARD READER TO
ROLL-UP DOOR
OPERATOR
SWITCHGEAR
ROOM
SECURITY PANEL
SECURITY GATE
OPERATOR
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
CONSULTANTS
321 4 5 6 7 8 9 10
NO. DESCRIPTION DATE
PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE
WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE
PROFESSIONAL ENGINEER
o n e e ig h th i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e i n c h o n e f o o t o n e a n d o n e h a lf i n c h e s o n e f o o t th re e i n c h e s o n e f o o t
MILLER-REMICK LLC
PROFESSIONAL ENGINEER
NORTH
ENGINEER OF RECORD
M-R PROJECT NO:
Civil:
IMEG, CORP.
Fire & Life Safety:
STANTON ENGINEERING SERVICES, LLC
Hazardous Materials:
MABBETT & ASSOCIATES, INC.
Architectural:
OCULUS, INC.
Structural:
PROFESSIONAL ENGINEERING
CONSULTANTS, PA (PEC)
A u to d e s k D o c s /W ic h it a
C e n tr a liz e d E m e rg e n c y P o w e r/
-0
W ic h it a C e n tr a liz e d
E m e rg e n c y P o w e r-
M E
P -R
.r v t
/2
/2
:3
:0
A
M
EY111
ELECTRICAL
SIGNAL PLAN
GROUND FLOOR
CONSTRUCT CENTRALIZED
EMERGENCY POWER SYSTEM
589A7-21-132
Project Director
2026-03-26 TFO MJR
BID DOCUMENTS
FULLY SPRINKLERED
ROBERT J. DOLE VA MEDICAL CENTER
WICHITA, KANSAS
0499-0162
SCALE: 1/4" = 1'-0"1 SIGNAL PLAN - GROUND FLOOR
GENERAL SHEET NOTES:
1. REFER TO SHEETS E-001 & E-002 FOR SYMBOLS, ABBREVIATIONS AND NOTES.
2. ALL DEVICES SHOWN SHALL BE NEW, UNLESS OTHERWISE NOTED.
3. ALL TELE/DATA DEVICE WIRING SHALL BE RUN BACK TO THE NEW
TELECOMMUNICATIONS ENCLOSURE LOCATED.
SHEET KEYNOTES:
1 BASIS OF DESIGN: RLH INDUSTRIES, INC FIBER OPTIC LINK DUAL-DOOR TELECOM
ENSCLOSURE.
(E) ATS-3
208V, 400A
CAT
(D) GENERATOR "31"
242kW, 208-VOLT
(E) ATS-2FP
208V
(E) ATS-1FP
208V
(D) U.G. FUEL TANK
(D) GENERATOR "31A"
242kW, 240-VOLT
(D) REMOTE RADIATOR
(E) ATS-4
240V, 400A
CAT
(E) ATS-1
208V, 400A
CAT
(E) ATS-2
208V, 400A
CAT
FIRE PUMP BUILDING
GENERATOR BUILDING
(E) ATS-6
480V, 600A
CUMMINS
(E) ATS-5
480V, 225A
CUMMINS
(E) ATS-BUILDING 5
208V
CAT
(E) ATS-3
208V, 400A
CAT
(E) ATS-2FP
208V
(E) ATS-1FP
208V
(E) ATS-4
240V, 400A
CAT
(E) ATS-1
208V, 400A
CAT
(E) ATS-2
208V, 400A
CAT
(N) TRANSFORMER "31"
300kVA, 12,470V-208V
(N) LOOP FEED SWITCHES
(N) TRANSFORMER "31A"
300kVA, 12,470V-240V
(N) LOOP FEED SWITCHES
FIRE PUMP BUILDING
NO. DESCRIPTION DATE
MILLER-REMICK LLC
PROFESSIONAL ENGINEER
PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE
WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE
PROFESSIONAL ENGINEER.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
BID DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
Phase
ENGINEER OF RECORDCONSULTANT CONSTRUCT CENTRALIZED
EMERGENCY POWER SYSTEM
589A7-21-132
Project Director
2026-03-26
321 4 5 6 7 8 9 10
A
B
C
D
E
F
21 4 5 6 7 8 9 10
A
C
D
E
F
M-R PROJECT NO: 0499-0162
ROBERT J. DOLE VA MEDICAL CENTER
WICHITA, KANSAS
Civil / Site Utility Engineering:Hazardous Materials:
MABBETT & ASSOCIATES, INC.
Fire & Life Safety:
STANTON ENGINEERING SERVICES, LLC
Architectural:
OCULUS, INC.
Structural:
PROFESSIONAL ENGINEERING
CONSULTANTS, PA (PEC)
IMEG, CORP. 37
1. REFER TO SHEETS E-001 AND E-002 FOR SYMBOLS, ABBREVIATIONS AND
NOTES.
2. ALL ELECTRICAL EQUIPMENT SHOWN ON THIS DRAWING SHALL BE EXISTING
TO REMAIN, UNLESS OTHERWISE NOTED.
GENERAL SHEET NOTES:
SHEET KEYNOTES:
1. REMOVE EXISTING ATS SIGNALLING WIRE FROM EXISTING ATS TO
DEMOLISHED GENERATOR. CONDUIT PATHWAY SHALL BE EXISTING TO
REMAIN. EXISTING CONDUIT SHALL BE EXTENDED TO NEW LOW VOLTAGE
DUCTBANK, WHICH WILL BE INSTALLED DURING PHASE 1 OF THE PROJECT.
ELECTRICAL CONTRACTOR SHALL PROVIDE TWO (2) NEW #10 TWISTED PAIR
STRANDED CONTROL WIRES BETWEEN EXISTING ATS AND NEW MEDIUM
VOLTAGE GENERATORS. NEW CONTROL WIRES SHALL BE RUN IN THE NEW
LOW VOLTAGE DUCTBANK. REFER TO ES102 AND CIVIL DRAWINGS FOR
FURTHER INFORMATION ON DUCTBANK ROUTING.
ELECTRICAL
ENLARGED PLANS
BUILDINGS 1, 2, 5 & 36
EP401
MJRTO
SCALE: 1/8" = 1'-0"
SCALE: 1/8" = 1'-0"
SCALE: 1/8" = 1'-0"
EQUIPMENT
ROOM
GENERATOR
ROOM
CORRIDOR
TRANSFORMER
I.T. ROOM
ELECTRICAL
OFFICE
SECURITY
HAC
CONTROL
ROOM
BOILER
ROOM
PASSAGE
TOILET
LOCKER
ROOM
EQUIPMENT
TOILET
SHOWER
ROOM
CONTRACTOR
TOUCHDOWN
BREAK
AREA
FE
CT-5
FE FE
FE
(E) ATS-9
208V, 400A
CUMMINS
(E) ATS-8
240V, 225A
CUMMINS
(E) BUILDING 13-EMDP
(N) POWER CONDUIT PATHWAY
TO NEW BUILDING 37. CONDUIT
SHALL RUN TIGHT TO WALL. E.C.
SHALL FIELD VERIFY ROUTING.
AFTER EXITING BUILDING, CONDUIT
SHALL TURN DOWN INTO CONCRETE
ENCASED DUCTBANK. SEE CIVIL
DRAWINGS FOR CONTINUATION.
TELECOM
ROOM
103B
MEZZANINE
200-20200-20
(E) TELE/DATA RACK
(E) FIBER NETWORK
BOX
(E) TYCO SECURITY
PANELS
(N) 2" CORE THROUGH
SLAB. FIRE SEAL
OPENING AS REQUIRED.
(E) ATS-10
208V, 400A
CUMMINS
(E) INFILL PROJECT ATS
ASCO 7000 SERIES
(E) ATS-11
480V, 225A
CUMMINS
NEW GENERATOR
30KVA
(E) ATS-22
480V, 100A
CUMMINS
(E) ATS-21
480V, 225A
CUMMINS
(E) ATS-20
480V, 225A
CUMMINS
(E) ATS-23
480V, 100A
CUMMINS
(D) GENERATOR "62"
480V, 352kW
(E) ATS-22
480V, 100A
CUMMINS
(E) ATS-21
480V, 225A
CUMMINS
(E) ATS-20
480V, 225A
CUMMINS
(E) ATS-23
480V, 100A
CUMMINS
(N) TRANSFORMER "62"
300kVA, 12,470V-480V
(N) LOOP FEED SWITCHES
AFTER EXITING BUILDING, CONDUIT
SHALL TURN DOWN INTO CONCRETE
ENCASED DUCTBANK. SEE CIVIL
DRAWINGS FOR CONTINUATION.
UP TO IT ROOM ABOVE
VIA NEW CORE.
NO. DESCRIPTION DATE
MILLER-REMICK LLC
PROFESSIONAL ENGINEER
PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE
WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE
PROFESSIONAL ENGINEER.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
BID DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
Phase
ENGINEER OF RECORDCONSULTANT CONSTRUCT CENTRALIZED
EMERGENCY POWER SYSTEM
589A7-21-132
Project Director
2026-03-26
321 4 5 6 7 8 9 10
A
B
C
D
E
F
21 4 5 6 7 8 9 10
A
C
D
E
F
M-R PROJECT NO: 0499-0162
ROBERT J. DOLE VA MEDICAL CENTER
WICHITA, KANSAS
Civil / Site Utility Engineering:Hazardous Materials:
MABBETT & ASSOCIATES, INC.
Fire & Life Safety:
STANTON ENGINEERING SERVICES, LLC
Architectural:
OCULUS, INC.
Structural:
PROFESSIONAL ENGINEERING
CONSULTANTS, PA (PEC)
IMEG, CORP. 37
1. REFER TO SHEETS E-001 AND E-002 FOR SYMBOLS, ABBREVIATIONS AND
NOTES.
2. ALL ELECTRICAL EQUIPMENT SHOWN ON THIS DRAWING SHALL BE EXISTING
TO REMAIN, UNLESS OTHERWISE NOTED.
GENERAL SHEET NOTES:
SHEET KEYNOTES:
1. REMOVE EXISTING ATS SIGNALLING WIRE FROM EXISTING ATS TO
DEMOLISHED GENERATOR. CONDUIT PATHWAY SHALL BE EXISTING TO
REMAIN. EXISTING CONDUIT SHALL BE EXTENDED TO NEW LOW VOLTAGE
DUCTBANK, WHICH WILL BE INSTALLED DURING PHASE 1 OF THE PROJECT.
ELECTRICAL CONTRACTOR SHALL PROVIDE TWO (2) NEW #10 TWISTED PAIR
STRANDED CONTROL WIRES BETWEEN EXISTING ATS AND NEW MEDIUM
VOLTAGE GENERATORS. NEW CONTROL WIRES SHALL BE RUN IN THE NEW
LOW VOLTAGE DUCTBANK. REFER TO ES102 AND CIVIL DRAWINGS FOR
FURTHER INFORMATION ON DUCTBANK ROUTING.
2. PROVIDE 12-PAIR SINGLE MODE FIBER (OM4) IN INNERDUCT IN 2" CONDUIT
FROM EXISTING FIBER NETWORK BOX TO NEW GENERATOR BUILDING 37.
ELECTRICAL
ENLARGED PLANS
BUILDINGS 13, 20, 26, 29 & 62
EP402
MJRTO
SCALE: 1/8" = 1'-0"
SCALE: 1/8" = 1'-0"
SCALE: 1/8" = 1'-0"
SCALE: 1/8" = 1'-0"
SCALE: 1/8" = 1'-0"SCALE: 1/8" = 1'-0"
SPS
DIRTY
ELEVATOR
EQUIP.
INVENTORY
MANAGEMENT
ELECT.
RM
CORRIDOR
VESTIBULE
RM
E
ELEVATOR
MECHANICAL
(E) ATS-15
480V, 600A
ZENITH
EXISTING
ELEVATOR
HALL
STAIRS
ELECTRICAL
GENERATOR
ROOM
ELECTRICAL
(E) ATS-13
480V, 400A
CAT
(E) ATS-16
480V, 225A
CAT
(E) ATS-14
480V, 400A
CAT
(E) ATS-12
480V, 600A
CAT
(D) GENERATOR "34"
800kW, 480-VOLT
(E) ATS-18
208V, 150A
CUMMINS
(E) ATS-17
208V, 225A
CUMMINS
W A
IT
IN
G
A
C
LA
S S R O O M
A
B R E A K
B
C
LA
S S R O O M
B
CORRIDOR
001-2
COFFEE
C
LA
S S R O O M
A
C
LA
S S R O O M
A
C
LA
S S R O O M
B
C
LA
S S R O O M
B
ELEC
001B
STOR.
001C
(E) ATS-19
208V, 200A
ZENITH
(E) PANEL ELL-G
208-VOLT
25,27,29 - 70A SPARE
AFTER EXITING BUILDING, CONDUIT SHALL
TURN DOWN INTO UNDERGROUND SITE
CONDUIT TO GATE. SEE ES102 CIVIL DRAWINGS
(CU100 & CU105) FOR CONTINUATION.
1" CONDUIT FOR GATE POWER
ABOVE ACCESSIBLE CEILING
(E) SELECTOR SWITCH "61"
(E) 1000kVA TRANSFORMER
(E) 16-DOOR
PACS PANEL
CAT-6A WIRE IN
3/4" C. TO
SECURITY GATE
AFTER EXITING BUILDING, CONDUIT SHALL
TURN DOWN INTO UNDERGROUND SITE
CONDUIT TO GATE. SEE ES102 CIVIL DRAWINGS
(CU100 & CU105) FOR CONTINUATION.
EXISTING
ELEVATOR
HALL
STAIRS
ELECTRICAL
GENERATOR
ROOM
ELECTRICAL
(E) ATS-13
480V, 400A
CAT
(E) ATS-16
480V, 225A
CAT
(E) ATS-14
480V, 400A
CAT
(E) ATS-12
480V, 600A
CAT
(N) TRANSFORMER "34"
1000kVA, 12,470V-480V
(N) LOOP FEED SWITCHES
NO. DESCRIPTION DATE
MILLER-REMICK LLC
PROFESSIONAL ENGINEER
PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE
WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE
PROFESSIONAL ENGINEER.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
BID DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
Phase
ENGINEER OF RECORDCONSULTANT CONSTRUCT CENTRALIZED
EMERGENCY POWER SYSTEM
589A7-21-132
Project Director
2026-03-26
321 4 5 6 7 8 9 10
A
B
C
D
E
F
21 4 5 6 7 8 9 10
A
C
D
E
F
M-R PROJECT NO: 0499-0162
ROBERT J. DOLE VA MEDICAL CENTER
WICHITA, KANSAS
Civil / Site Utility Engineering:Hazardous Materials:
MABBETT & ASSOCIATES, INC.
Fire & Life Safety:
STANTON ENGINEERING SERVICES, LLC
Architectural:
OCULUS, INC.
Structural:
PROFESSIONAL ENGINEERING
CONSULTANTS, PA (PEC)
IMEG, CORP. 37
1. REFER TO SHEETS E-001 AND E-002 FOR SYMBOLS, ABBREVIATIONS AND
NOTES.
2. ALL ELECTRICAL EQUIPMENT SHOWN ON THIS DRAWING SHALL BE EXISTING
TO REMAIN, UNLESS OTHERWISE NOTED.
GENERAL SHEET NOTES:
SHEET KEYNOTES:
ELECTRICAL
ENLARGED PLANS
BUILDINGS 34, 60 & 61
EP403
MJRTO
SCALE: 1/8" = 1'-0"
SCALE: 1/8" = 1'-0"
SCALE: 1/8" = 1'-0"
SCALE: 1/8" = 1'-0"
SCALE: 1/8" = 1'-0"
SCALE: 1/8" = 1'-0"
1. REMOVE EXISTING ATS SIGNALLING WIRE FROM EXISTING ATS TO
DEMOLISHED GENERATOR. CONDUIT PATHWAY SHALL BE EXISTING TO
REMAIN. EXISTING CONDUIT SHALL BE EXTENDED TO NEW LOW VOLTAGE
DUCTBANK, WHICH WILL BE INSTALLED DURING PHASE 1 OF THE PROJECT.
ELECTRICAL CONTRACTOR SHALL PROVIDE TWO (2) NEW #10 TWISTED PAIR
STRANDED CONTROL WIRES BETWEEN EXISTING ATS AND NEW MEDIUM
VOLTAGE GENERATORS. NEW CONTROL WIRES SHALL BE RUN IN THE NEW
LOW VOLTAGE DUCTBANK. REFER TO ES102 AND CIVIL DRAWINGS FOR
FURTHER INFORMATION ON DUCTBANK ROUTING.
2. PROVIDE ADDITIONAL DOOR CONTROL MODULE AS REQUIRED AS AN
EXTENSION OF THE EXISTING WICHITA VA STANDARD SOFTWARE HOUSE
C-CURE 9000 SYSTEM.
NO. DESCRIPTION DATE
MILLER-REMICK LLC
PROFESSIONAL ENGINEER
PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE
WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE
PROFESSIONAL ENGINEER.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
BID DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
Phase
ENGINEER OF RECORDCONSULTANT CONSTRUCT CENTRALIZED
EMERGENCY POWER SYSTEM
589A7-21-132
Project Director
2026-03-26
321 4 5 6 7 8 9 10
A
B
C
D
E
F
21 4 5 6 7 8 9 10
A
C
D
E
F
M-R PROJECT NO: 0499-0162
ROBERT J. DOLE VA MEDICAL CENTER
WICHITA, KANSAS
Civil / Site Utility Engineering:Hazardous Materials:
MABBETT & ASSOCIATES, INC.
Fire & Life Safety:
STANTON ENGINEERING SERVICES, LLC
Architectural:
OCULUS, INC.
Structural:
PROFESSIONAL ENGINEERING
CONSULTANTS, PA (PEC)
IMEG, CORP. 37
ELECTRICAL
DETAILS
E-501
MJRTO
EMT HOME
RUN
"SEALTITE"
CONN. TO
MOTOR
CEILING
SLAB
RIGID
STEEL
ELBOW
RIGID STEEL
CONDUIT
CLAMP
T-CONDUIT
FLOOR
SLAB
FLOOR FLANGE
SCALE:
CONDUIT - OVERHEAD DROP DETAIL
NTS
3M FIRE BARRIER FS-195
WRAP/STRIP IS BUTTED
SECURELY AGAINST THE
WALLBOARD
3M FIRE BARRIER RC-1
RESTRICTING COLLAR
STEEL HOSE
CLAMP
STUD
WALL
1-2 HR. FIRE RATED
GYPSUM WALL BOARD
3M FIRE BARRIER CP
25 CAULK OR MP
MOLDABLE PUTTY
STEEL HOLLOW WALL
SCREW ANCHORS (OR
EQUIVALENT) 3/16"x1-1/2"
LONG, MIN., WITH 1-1/4"
FENDER WASHERS
INSULATED METAL
PIPE/CONDUIT
FIBERGLASS
INSULATION
3/
M A
X . A
N N
U
LA
R
S P
A C
E
SCALE:
FIRE STOP FOR CONDUIT PENETRATION THROUGH
GYPSUM BOARD
NTS
3'-0" MAX
PROVIDE 5" OF SLACK AT MIDPOINT BETWEEN
TWO END OF FLEXIBLE GALVANIZED STEEL
CONDUIT. PROVIDE GREEN INSULATED
COPPER EQUIPMENT GROUNDING
CONDUCTOR WITH FLEXIBLE CONDUIT.
FLOOR OR ROOF STRUCTURE. FIELD
VERIFY ACTUAL CONDITIONS, TYP.
CONDUIT TRAPEZE SEE
DETAIL #1, DWG. #E-501.
CONDUIT, TYP.
SEISMIC OR EXPANSION JOINT.
FIELD VERIFY ACTUAL
CONDITIONS & LOCATIONS.
STRUCTURAL MEMBER
(BEAM, JOIST, ETC.), TYP.
STEEL EXPANSION
ANCHOR
INTEGRAL GALVANIZED LIPPED
STEEL MOUNTING CHANNEL
JUNCTION BOX
(SIZE AS REQUIRED)
CONDUIT
COMPRESSION FITTING
SPRING NUT
BEAM CLAMP, TYP.
SCALE:
CONDUIT - JOINT CROSSING DETAIL
NTS
PROVIDE EXTRA CABLE TO MAKE COMPLETE
LOOP AROUND BOX PERIMETER
GENERAL NOTE:
1. DETAIL IS APPLICABLE ONLY FOR CONDUIT SMALLER THAN 76mm (3").
NOTES
1. INTEGRAL GALVANIZED LIPPED STEEL MOUNTING
CHANNEL LONGER THAN 36" SHALL BE INSTALLED WITH A
CENTER SUPPORT ROD.
2. FASTEN THREADED ROD TO STRUCTURE BY APPROVED
METHOD PER SPECIFICATION 26 05 33, RACEWAYS AND
BOXES FOR ELECTRICAL SYSTEMS. FIELD VERIFY EXACT
CONDITIONS.
LENGTH AS REQUIRED
3/8" MIN.
GALVANIZED
THREADED ROD,
TYP.
LOCKING SQUARE
WASHER & LOCKNUT
INTEGRAL
GALVANIZED
LIPPED STEEL
MOUNTING
CHANNEL
WASHER &
LOCKNUT
REFER TO PLANS
FOR QUANTITY &
SIZE OF CONDUITS
CONDUIT CLAMP.
SIZE AS
REQUIRED
INTEGRAL
GALVANIZED
LIPPED STEEL
MOUNTING
CHANNEL
SCALE:
CONDUIT TRAPEZE MOUNTING DETAIL
NTS
GENERAL NOTES:
1. MAINTAIN A MINIMUM CLEARANCE OF 12" ON ALL SIDES OF ROOF
PENETRATION FROM WALLS, CURBS, AND OTHER PROJECTIONS TO
FACILITATE PROPER FLASHING.
2. FLANGES OF ADJACENT FLASHINGS SHALL NOT BE CUT OR OVERLAPPED.
3. VERIFY ROOF & STRUCTURAL SYSTEM WITH ARCHITECT.
4. COORDINATE FLASHING INSTALLATION WITH ROOFING CONTRACTOR TO
ENSURE PROPER METHODS & MATERIALS ARE USED TO MAINTAIN ROOF
WARRANTY.
STANDARD CLAMP, TYP.
PREFABRICATED RUBBER BOOT
CAP WITH GRADUATED STEPS &
WEATHER-POOF SEAL TO COLLAR
SEALANT AT PENETRATION
TO MEMBRANE JUNCTURE
BY ROOFING CONTRACTOR
ROOF
MEMBRANE
ROOF
WATER CUT-OFF MASTIC
COMPATIBLE WITH ROOF
MEMBRANE
CONDUIT CLAMP.
SIZE AS REQUIRED
SEAL-OFF FITTING TYP. CONDUIT TYP.
MULTIPLE MEMBRANE STRIPPING
PLIES FEATHERED AT FIELD OF ROOF
BY ROOFING CONTRACTOR. PRIME
FLANGE BEFORE STRIPPING.
PREFABRICATED FORMED .06" THICK
ALUMINUM FLASHING ROUND COLLAR WITH
MIN. 3" WIDE FLANGE. ATTACH TO ROOF
PER MANUFACTURER'S INSTRUCTIONS
BATT INSULATION
STEEL EXPANSION ANCHOR
3/8" MIN. GALVANIZED
THREADED ROD, TYP.
LOCKING SQUARE
WASHER &
LOCKNUT
INTEGRAL GALVANIZED LIPPED
STEEL MOUNTING CHANNEL
CONDUIT CLAMP.
SIZE AS REQUIRED
SCALE:
CONDUIT - ROOF PENETRATION DETAIL
NTS
1/2" x 12" POINT
BRONZE BONDING PLATE
BRONZE BONDING PLATE
SCALE:
TYPICAL LIGHTNING PROTECTION MECHANICAL
EQUIPMENT
NTS
UL
SOLID AIR TERMINAL TYP EVERY 20'
MAX. 2'-0"
FROM CORNER
APART
CONDUCTOR CABLE
CABLE FASTENER
FLAT ROOF POINT BASE
3' MAX.
3'-0" M
AX.
SCALE:
TYPICAL LIGHTNING
PROTECTION GLUE DOWN PERIMETER SYSTEM
NTS
SCALE:
TYPICAL LIGHTNING PROTECTION SYSTEM
CONNECTION DETAIL
NTS
CONTROL
CIRCUITRY
BLUEYELLOW
GRAY
PURPLE
BLACK
WHITE
EMERGENCY LIGHTING CONTROL DEVICE
NORMAL NEUTRAL
NORMAL HOT
EMERGENCY NEUTRAL
EMERGENCY HOT
WALL
SWITCH
SCALE:
UL 924 EMERGENCY LIGHT FIXTURE SWITCHING
CONTROL SCHEMATIC
NTS
Y
NOTES:
1. DEVICE SHALL BE MOUNTED ABOVE ACCESSIBLE CEILING AHEAD OF LIGHTING CONTROL DEVICE, I.E.
LIGHT SWITCH.
2. DEVICE IS RATED FOR AN 8-AMP CIRCUIT WHEN CONTROLLING LED FIXTURES.
TO NORMAL/EMERGENCY
LIGHTING NEUTRAL
TO NORMAL/EMERGENCY
LIGHTING HOT
TO NORMAL LIGHTING HOT
TO NORMAL LIGHTING NEUTRAL
SCALE:
GROUNDING BAR DETAIL
NTS
2"
4"
1" 1" 1"2"
1 1/2" TYP
1" 5/ 8"
5" 2"
MIN
1/4" DIA.
MOUNTING
HOLES TYP. OF
(4)3" DEEP FIBERGLASS
CHANNEL SAME
LENGTH AS CU BUSS
3/8" DIA. HOLE
TYP. OF (6)
1/2"DIA. x2"L. BOLT
TYP. OF (2)
1/2" NUT
1/2" LOCK WASHER
1/2" STANDARD WASHER
1/2" FENDER WASHERS (EACH SIDE)
1/4" THICK CU
BUSS
2'-0" MIN
1/4" DIA. HOLE
TYP OF (8)
NOTES
1. ALL HARDWARE SHOWN SHALL BE STAINLESS STEEL.
2. PROVIDE 1 MOUNTING POINT PER 12" OF BAR LENGTH.
3. HOLES MAY BE ADDED IF REQUIRED.
SECTION
STEEL EXPANSION
ANCHOR
SOLID AIR TERMINAL SECURELY
FASTENED TO PERIMETER WALLCOPING BONDING PLATE
20'-0" O.C. MAX SECONDARY CONDUCTOR
MAIN CONDUCTOR
PROVIDE WATERPROOF
CAULKING AS REQUIRED
ROOF
ROOF MFR APPROVED
THRU ROOF CONNECTOR
PROVIDE WATERPROOF
CAULKING AS REQUIRED
#4/0 BARE COPPER
DOWN CONDUCTOR
8" SQUARE BONDING PLATE
FASTENED TO STEEL WITH
STAINLESS STEEL NUTS & BOLTS
#4/0 BARE COPPER
DOWN CONDUCTOR
FLOOR
1" PVC
FOUNDATION WALL
NOTE:
1. ALL LIGHTNING PROTECTION
INSTALLATION SHALL BE IN
ACCORDANCE WITH NFPA 780
FOR CONNECTION TO BUILDING
SEE GROUNDING SYSTEM PLAN
AS SHOWN ON PLANS
GRADE
BUILDING WALL
4/0 COPPER MAIN LOOP
GROUNDING ELECTRODE SYSTEM
EXOTHERMIC WELD
SEAL CONDUIT WITH
APPROPRIATE SILICONE CAULK
TO A DEPTH OF 1" MINIMUM
3/4" DIA. X 10'-0" LONG
COPPERWELD GROUND ROD.
BUILDING STEEL
PARAPET OR SCREEN WALL
OR PERIMETER SYSTEM
METAL COPING
FASTENED
EVERY
3' MAX.
GENERAL NOTES:
1. INSTALL ALL MATERIALS IN ACCORDANCE WITH MANUFACTURER'S RECOMMENDATIONS.
LINK-SEAL OR EQUAL.
2. DETAIL APPLIES TO CONDUITS PENETRATING FOUNDATION WALL AND ROUTED TO THE
BUILDING EXTERIOR FOR SERVICES/SITE LIGHTING/HVAC EQUIPMENT CONNECTIONS.
3. REFER TO SPECIFICATION SECTION 079200.
SCALE:
EXTERIOR BUILDING CONDUIT PENETRATION DETAIL
NONE
PROFESSIONAL ENGINEER
PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE
WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE
PROFESSIONAL ENGINEER.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
BID DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
Phase
ENGINEER OF RECORDCONSULTANT CONSTRUCT CENTRALIZED
EMERGENCY POWER SYSTEM
589A7-21-132
Project Director
2026-03-26
321 4 5 6 7 8 9 10
A
B
C
D
E
F
21 4 5 6 7 8 9 10
A
C
D
E
F
M-R PROJECT NO: 0499-0162
ROBERT J. DOLE VA MEDICAL CENTER
WICHITA, KANSAS
Civil / Site Utility Engineering:Hazardous Materials:
MABBETT & ASSOCIATES, INC.
Fire & Life Safety:
STANTON ENGINEERING SERVICES, LLC
Architectural:
OCULUS, INC.
Structural:
PROFESSIONAL ENGINEERING
CONSULTANTS, PA (PEC)
IMEG, CORP. 37
ELECTRICAL
DETAILS
E-502
MJRTO
DOOR STRIKE
(PROVIDED BY GEN.
CONTR.)
CONDUIT
& WIRING
TO CARD
READER
PROXIMITY
CARD
READER
NOTE;
1. EC TO COORDINATE WITH DOOR VENDOR THE REQUIRED DOOR LOCKING HARDWARE.
2. CONDUIT AND WIRE SIZE AS RECOMMENDED BY MANUFACTURER
3. DOOR SHALL ADHERE TO NFPA 101 AND SHALL RELEASE UPON ONE OF SEVERAL
"EMERGENCY" CONDITIONS SUCH AS: LOSS OF POWER TO SENSOR, FIRE ALARM SIGNAL,
ETC.
(TYP) DOOR
CONTACT
SWITCH
TO FIRE ALARM PANEL
SECURE AREA CEILING LINE
FLOOR
SCALE:
CARD ACCESS SINGLE DOOR DETAIL
NTS
TYP. CONDUIT
& WIRING FROM
CONTROLLER FOR
DOOR RELEASE
PANEL-CIRCUIT#
AHU-X
AHU-X
480v, 3Ø
FED FROM "XXX"
480v, 3Ø
FED FROM "XXX"
1/2" HIGH LETTERING FOR EQUIPMENT NAME
1/4" HIGH LETTERING FOR REMAINING TEXT
EQUIPMENT NAME
EQUIPMENT VOLTAGE AND PHASE
EQUIPMENT SOURCE
120/208V, 3Ø 4W
FED FROM PANEL "XXX"
VIA "T-XXX"
PANEL "XXXXX"
PANEL "XXXXX"
277/480V, 3Ø, 4W
FED FROM "XXX"
TYPICAL 277/480V PANELBOARD
TYPICAL 120/208V PANELBOARD
1/16" THICK PLASTIC WITH COLORED
FACE PER SPECIFICATIONS
1/2" HIGH LETTERING FOR EQUIPMENT NAME
FASTEN WITH SELF TAPPING STAINLESS
STEEL SCREWS, EA SIDE
1/4" HIGH LETTERING FOR REMAINING TEXT
PANELBOARD NAME
FASTEN WITH SELF TAPPING STAINLESS
STEEL SCREWS, EA SIDE
PANELBOARD VOLTAGE
PANELBOARD SOURCE
FASTEN WITH SELF TAPPING STAINLESS STEEL
SCREWS, EA SIDE
FASTEN WITH SELF TAPPING STAINLESS STEEL
SCREWS, EA SIDE
1/16" HICK NAMEPLATES WITH COLORED
FACE PER SPECIFICATIONS
LABEL COLOR:
1. LABELS FOR EMERGENCY POWER SHALL BE RED WITH ENGRAVED WHITE LETTERS.
2. LABELS FOR NORMAL POWER SHALL BE BLACK WITH ENGRAVED WHITE LETTERS.
LABEL COLOR:
1. LABELS FOR EQUIPMENT FED BY EMERGENCY POWER SHALL BE RED WITH ENGRAVED WHITE LETTERS.
2. LABELS FOR EQUIPMENT FED BY NORMAL POWER SHALL BE BLACK WITH ENGRAVED WHITE LETTERS.
SCALE:
PANELBOARD NAMEPLATES
NONE SCALE:
EQUIPMENT NAMEPLATES
NONE
SCALE:
TYPICAL RECEPTACLE NAMEPLATE
NONE
GENERAL NOTE:
ALL RECEPTACLES WHETHER DUPLEX OR QUADRAPLEX OR
ANY OTHER NEMA CONFIGURATION SHALL BE LABELED.
CIRCUIT DESIGNATION LABEL. 3/8" HIGH
WHITE LETTERING ON RED BACKGROUND
FOR EMERGENCY, WHITE LETTERING ON
BLACK BACKGROUND FOR NORMAL. USE
PERMANENT ADHESIVE TO SECURE
NAMETAG. LABEL ALL RECEPTACLES IN
PROJECT.
DUPLEX RECEPTACLE
120V IN
24V TRANSFORMER
PACS CONTROLLER
CONDUIT AND WIRING TO
PACS CONTROL PANEL
(7)
(8) (9)
(3)
(4)
(11)
(12)
(10)
(5) (6)
REFERENCE NOTES:
1. CONCRETE HOUSEKEEPING PAD.
2. CONCRETE ANCHOR BOLT, 4
REQUIRED.
3. TRANSFORMER BASE CHANNEL.
4. 1/2"Ø NUT, BOLT, & LOCK WASHER,
6 REQUIRED.
5. GROUND CONNECTOR.
6. SECONDARY CONNECTION DETAIL,
PRIMARY - SIMILAR.
7. TRANSFORMER - MOUNT BOTTOM
SUPPORTS 6'-6" AFF.
8. NAMEPLATE - CONNECTION
DIAGRAM TO FACE CLOSET
ENTRANCE.
9. EXTERNAL COPPER BONDING
WIRE.
10. LIQUID TIGHT FLEXIBLE METAL
CONDUIT 18" MIN.
11. RIGID CONDUIT.
12. COMBINATION COUPLING. (2)
(1)
SAFETY CHAIN OR
CABLE PER EACH LUMINARE
TYPICAL ROOF TRUSS OR
MULTI HOLE CHANNEL.
INTERMEDIATE SPAN OF
12 GAGUE MINIMUM
1 5/8" x 1 5/8"
JUNCTION BOX
FLEX CORD
CONDUIT
RED LABEL WITH
1/4"(6.35MM) WHITE
ENGRAVED LETTERS
ADA COMPLIANT
POLYCARBONATE
PROTECTIVE HINGED
COVER
60MM DIAMETER, RED
MUSHROOM HEAD
PUSHBUTTON
OVERSIZED 302
STAINLESS STEEL WALL
PLATE
POWER
DEACTIVATION
SWITCH EMERGENCY
USE ONLY
WALL
OUTLET
BOX
CONTACT
BLOCKS
NOTES:
1. SEE POWER PLANS FOR LOCATION OF CONTRACTOR SUPPLIED EPO SWITCHES.
LOCK WASHER
DOUBLE NUTS
1/2" EYE BOLT MINIMUM
NUT
FLAT WASHER
AIRCRAFT CABLE (TYP)
HIGH BAY FIXTURE (TYP)
SCALE:
LUMINAIRE MOUNTING - HIGH BAY DETAIL
NONE
SCALE:
TRANSFORMER MOUNTING DETAIL - FLOOR
NONE SCALE:
EMERGENCY POWER OFF PUSHBUTTON - EPO
NONE
#6 MIN.
DOWN CONDUCTOR TYP.
#3/0 UNLESS NOTED
OTHERWISE
GENERATOR BUILDING
WALL MOUNTED COPPER
EQUIPMENT GROUND BUS BAR
(1/4" X 4")
TO
FIRE
ALARM
SYSTEM
GROUNDING
TO
TELEPHONE
SYSTEM
GROUNDING
TO A/V
SYSTEM
GROUNDING
#3/0 MIN.
GROUND RING
LIGHTNING
PROTECTION GROUND
ROD (TYPICAL)
AIR TERMINAL
"LIGHTNING ROD"
ROOF (TYPICAL)
EQUIPMENT
RACKS
BUILDING
STEEL
ALL SLEEVES
AND RACEWAYS
TYPICAL
EQUIPMENT
BONDED TO
GROUND BAR
#6 COPPER
BONDING
CONDUCTOR
(TYPICAL)
TO TYPICAL
BRANCH
CIRCUIT
NEUTRAL BUS
GROUNDING BUS
480-VOLT PANEL
(TYPICAL)
TRANSFORMER
(TYPICAL)
TO TYPICAL
BRANCH
CIRCUIT
120-VOLT PANEL
(TYPICAL)
1. ALL GROUNDING CONDUCTORS OUTSIDE OF AN ELECTRICAL EQUIPMENT
ENCLOSURE SHALL BE PROTECTED BY PROVIDING A RACEWAY.
2. CONDUITS ATTACHED TO ELECTRICAL EQUIPMENT ENCLOSURES SHALL BE
SECURELY BONDED TO THOSE ENCLOSURES WITH GROUND FITTINGS.
3. ALL CABLE CONNECTIONS TO BE MADE BY A 12-TON COMPRESSION TOOL OR
EXOTHERMIC WELDING, EXCEPT TO GROUND LUGS ON BUS BARS AND
BLOCKS.
4. ALL BUSBARS SHALL BE 1/4" X 4" X 24" PRE-DRILLED TIN-PLATED COPPER.
MOUNT ON WALL WITH 2" STANDOFF INSULATORS.
5. ALL CABLE CONNECTIONS TO GROUND BAR SHALL BE TWO HOLE TONGUE
COMPRESSION LUGS.
6. ALL GROUNDING CONDUCTORS SHALL BE COPPER CONDUCTORS WITH GREEN
INSULATION OR DISTINCTIVE GREEN MARKING.
SCALE:
GROUNDING DIAGRAM
NTS
NEW/TEMPORARY
WORK
M1
(E) XFMR
1000 KVA
480-12470V
(E) SOLAR SYSTEM
SPACE SPACE
NO. DESCRIPTION DATE
MILLER-REMICK LLC
PROFESSIONAL ENGINEER
PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE
WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE
PROFESSIONAL ENGINEER.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
BID DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
Phase
ENGINEER OF RECORDCONSULTANT CONSTRUCT CENTRALIZED
EMERGENCY POWER SYSTEM
589A7-21-132
Project Director
2026-03-26
321 4 5 6 7 8 9 10
A
B
C
D
E
F
21 4 5 6 7 8 9 10
A
C
D
E
F
M-R PROJECT NO: 0499-0162
ROBERT J. DOLE VA MEDICAL CENTER
WICHITA, KANSAS
Civil / Site Utility Engineering:Hazardous Materials:
MABBETT & ASSOCIATES, INC.
Fire & Life Safety:
STANTON ENGINEERING SERVICES, LLC
Architectural:
OCULUS, INC.
Structural:
PROFESSIONAL ENGINEERING
CONSULTANTS, PA (PEC)
IMEG, CORP. 37
1. REFER TO SHEETS E-001 AND E-002 FOR SYMBOLS, ABBREVIATIONS AND
NOTES.
2. REFER TO SHEET ES102 FOR LOCATION OF ALL NEW AND EXISTING
DUCTBANKS AND MANHOLES.
3. REFER TO SPECIFICATION 262315 EMERGENCY POWER SEQUENCE OF
OPERATION FOR INFORMATION ON THE OPERATIONAL SWITCHING INTENT OF
THE CAMPUS EMERGENCY SYSTEM.
4. GENERATORS SHALL BE MONITORED BY EXISTING CAMPUS SIEMENS BAS
SYSTEM. CONTRACTOR SHALL HARDWIRE ALL NEW ELECTRICAL
COMPONENTS TO BE MONITORED TO THE NEW BUILDING 37 BAS PANEL.
5. PROVIDE AN ADDITIONAL I/O CARD WITH EACH GENERATOR TO ACCOUNT FOR
AN INCREASED ALARM COUNT (LOW OIL PRESSURE, HIGH COOLANT ALARM,
BASIN RUPTURE, NOT IN AUTO, BATTERY CHARGER, LOW FUEL, LOW
COOLANT, ETC)
6. PARALLELING SWITCHGEAR SHALL PROVIDE A REPORT COVERING
GENERATOR RUNTIME VIA THE LOW VOLTAGE CAT 6A CONNECTION TO THE
BAS SYSTEM PANEL.
GENERAL SHEET NOTES: SHEET KEYNOTES:
1. NEW FEEDER SHALL BE 3-#4/0 MV-105 (15KV RATED) PULLED THROUGH
EXISTING UNDERGROUND DUCTBANK TO (E) MANHOLE MH-2B.
2. PROVIDE NEW METALCLAD SWITCHGEAR SECTION TO MATCH EXISTING TYPE
(SQUARE D MASTERCLAD) AND AIC RATING. EXTEND EXISTING BUSSING INTO
NEW SWITCHGEAR SECTION.
3. NEW EMERGENCY POWER LOOP: 3-#350KCMIL (15KV RATED) IN 5" SCHEDULE
40 PVC CONDUIT + (1) SPARE 5" SCHEDULE 40 PVC CONDUIT WITHIN NEW
CONCRETE ENCASED DUCTBANK.
4. GENERATOR LOAD BANK IS A PERMANENTLY INSTALLED PIECE OF
EQUIPMENT. BASIS OF DESIGN FOR THE LOAD BANK SHALL BE AVTRON
MODEL 9810. 480-VOLT LOAD BANK AND ASSOCIATED STEPDOWN
TRANSFORMER ARE SKID MOUNTED ON RAILS AND SET ON A HOUSEKEEPING
PAD. PRIMARY RATING SHALL BE 12,470-VOLT, 1-MW.
5. 12,470-VOLT NEMA 3R, 300-AMP RATED GENERATOR TAP BOX WITH CAMLOCK
CONNECTORS
6. ELECTRONIC POWER DEMAND (EPDM) METERING: BASIS OF DESIGN SHALL BE
SCHNEIDER ELECTRIC/SQUARE D TO MATCH EXISTING SYSTEM. PROVIDE
EPDM METER INTEGRATED TO PARALLELING SWITCHGEAR. EPDM METER
SHALL RECORD, STORE AND TREND VOLTAGE, CURRENT, kW, kWH, kVA, kVAR, POWER FACTOR AS WELL AS TOTAL HARMONIC DISTORTION. PROVIDE
CAPABILITY OF COMMUNICATION WITH THE EXISTING CENTRALIZED VA
MONITORING SYSTEM VIA THE BAS SYSTEM. PROVIDE CAT 6A DATA CABLES
IN 3/4" C. FROM EDPM METER TO NEW BAS PANEL IN BUILDING 37.
ELECTRICAL
NEW WORK SWITCHGEAR
SINGLE LINE DIAGRAM
E-601
MJRTO
DEMOLITION
EXISTING TO
REMAIN
(E) MAIN SWITCHGEAR 35, BUILDING 35A
12470V, 3Ø, 4W, 34KA MOMENTARY BRACING
TIE BREAKER
PAWNEE
LINE 12-12
M1
EASTBOROUGH
LINE 12-34
3MW, 12,470-VOLT
GENERATOR
(N) PARALLELING SWITCHGEAR
12470-VOLT, 1200-AMP BUS, 3Ø, 3W, 34KAIC
BASIS OF DESIGN: ASCO
3MW, 12,470-VOLT
GENERATOR
3MW, 12,470-VOLT
GENERATOR
NORMAL POWER BACKUP FEEDERS TO EXISTING CAMPUS SWITCHGEAR
3-#350KCMIL (15kV RATED) IN 5" SCHEDULE 40 PVC CONDUIT + (1) SPARE 5"
SCHEDULE 40 PVC CONDUIT WITHIN NEW CONCRETE ENCASED DUCTBANKNEW GENERATOR BUILDING
SEE DRAWING E-602 FOR EXISTING CAMPUS NORMAL
LOOP DUCTBANK CONTINUATION
SEE DRAWING E-602 FOR NEW CAMPUS NORMAL LOOP
DUCTBANK CONTINUATION
SEE DRAWING E-603 FOR NEW CAMPUS
EMERGENCY LOOP DUCTBANK CONTINUATION
1200A
1200A 1200A
1200A
1200A1200A 1200A 1200A
1200A
1200A 1200A 1200A
1200A1200A
NEUTRAL
GROUND
RESISTOR
NEUTRAL GROUND
RESISTOR
NEUTRAL
GROUND
RESISTOR
PERMANENTLY
INSTALLED
LOAD BANK
3-#2 (15kV RATED) IN 5" SCHEDULE 40 PVC
CONDUIT + (1) SPARE 5" SCHEDULE 40 PVC
CONDUIT WITHIN NEW CONCRETE
ENCASED DUCTBANK
3-#350KCMIL (15kV RATED)
IN 5" C.
SEE DRAWING E-603 FOR NEW CAMPUS
EMERGENCY LOOP DUCTBANK CONTINUATION
3-#350KCMIL
(15kV RATED)
IN 5" C.
3-#350KCMIL
(15kV RATED)
IN 5" C.
3-#350KCMIL
(15kV RATED)
IN 5" C.
MASTER
CONTROLS
(E)
SELECTOR
SWITCH 2
(E) XFMR
500 KVA
12470-480/2770V
CATH LAB
BLDG 2
(H1)
BLDG 19
(E)
SELECTOR
SWITCH 19
(E) XFMR
500 KVA
12470-480/2770V
(E)
SELECTOR
SWITCH 34
(E) XFMR
1000 KVA
12470-480/2770V
(SWGR 34A)
BLDG 34
(E)
SELECTOR
SWITCH 41
(E) XFMR 41
225 KVA
12470-480/2770V
(ML4B)
BLDG 4
(E)
SELECTOR
SWITCH 49
(E)
SELECTOR
SWITCH 42
(E) XFMR
500 KVA
12470-480/2770V
(SWGR 61)
BLDG 5,6,7
(E)
SELECTOR
SWITCH 60
(E) XFMR
300 KVA
12470-208/120V
(SWGR 61)
BLDG 60
(E) SELECTOR
SWITCH 53
NEAR BLDG 11
(SWGR 53)
NEAR BLDG 11
(SWGR 49)
BLDG 1
NEW/TEMPORARY
WORK
(E)
SELECTOR
SWITCH 61
(E) XFMR
1000 KVA
12470-480/2770V
(SWGR 61)
BLDG 61
(E)
SELECTOR
SWITCH 55
(SWGR 55)
BLDGS 3 & 26
NO. DESCRIPTION DATE
MILLER-REMICK LLC
PROFESSIONAL ENGINEER
PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE
WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE
PROFESSIONAL ENGINEER.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
BID DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
Phase
ENGINEER OF RECORDCONSULTANT CONSTRUCT CENTRALIZED
EMERGENCY POWER SYSTEM
589A7-21-132
Project Director
2026-03-26
321 4 5 6 7 8 9 10
A
B
C
D
E
F
21 4 5 6 7 8 9 10
A
C
D
E
F
M-R PROJECT NO: 0499-0162
ROBERT J. DOLE VA MEDICAL CENTER
WICHITA, KANSAS
Civil / Site Utility Engineering:Hazardous Materials:
MABBETT & ASSOCIATES, INC.
Fire & Life Safety:
STANTON ENGINEERING SERVICES, LLC
Architectural:
OCULUS, INC.
Structural:
PROFESSIONAL ENGINEERING
CONSULTANTS, PA (PEC)
IMEG, CORP. 37
1. REFER TO SHEETS E-001 AND E-002 FOR SYMBOLS, ABBREVIATIONS AND
NOTES.
2. REFER TO SHEET ES102 FOR LOCATION OF ALL NEW AND EXISTING
DUCTBANKS AND MANHOLES. REFER TO DETAILS ON CIVIL DRAWINGS FOR
FURTHER INFORMATION ON DUCTBANK AND MANHOLES CONSTRUCTION.
GENERAL SHEET NOTES:
SHEET KEYNOTES:
1. NEW FEEDER SHALL BE 3-#4/0 MV-105 (15KV RATED), 1-#6 G. PULLED THROUGH
EXISTING UNDERGROUND DUCTBANK.
2. NEW FEEDER SHALL BE 3-#4/0 MV-105 (15KV RATED), 1-#6 G. PULLED THROUGH
NEW CONCRETE ENCASED DUCTBANK.
ELECTRICAL
NEW WORK CAMPUS NORMAL LOOP
SINGLE LINE DIAGRAM
E-602
MJRTO
SCALE: NTS
DEMOLITION
EXISTING TO
REMAIN
TO SECTION 6
SEE E-601 FOR
CONTINUATION
TO SECTION 7
SEE E-601 FOR
CONTINUATION
TO SECTION 7
SEE E-601 FOR
CONTINUATION
TO SECTION 2
SEE E-601 FOR
CONTINUATION
TO SECTION 2
SEE E-601 FOR
CONTINUATION
TO SECTION 3
SEE E-601 FOR
CONTINUATION
NEW/TEMPORARY
WORK
NO. DESCRIPTION DATE
MILLER-REMICK LLC
PROFESSIONAL ENGINEER
PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE
WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE
PROFESSIONAL ENGINEER.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
BID DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
Phase
ENGINEER OF RECORDCONSULTANT CONSTRUCT CENTRALIZED
EMERGENCY POWER SYSTEM
589A7-21-132
Project Director
2026-03-26
321 4 5 6 7 8 9 10
A
B
C
D
E
F
21 4 5 6 7 8 9 10
A
C
D
E
F
M-R PROJECT NO: 0499-0162
ROBERT J. DOLE VA MEDICAL CENTER
WICHITA, KANSAS
Civil / Site Utility Engineering:Hazardous Materials:
MABBETT & ASSOCIATES, INC.
Fire & Life Safety:
STANTON ENGINEERING SERVICES, LLC
Architectural:
OCULUS, INC.
Structural:
PROFESSIONAL ENGINEERING
CONSULTANTS, PA (PEC)
IMEG, CORP. 37
1. REFER TO SHEETS E-001 AND E-002 FOR SYMBOLS, ABBREVIATIONS AND
NOTES.
2. REFER TO SHEET ES102 FOR LOCATION OF ALL NEW AND EXISTING
DUCTBANKS AND MANHOLES.
GENERAL SHEET NOTES:
SHEET KEYNOTES:
ELECTRICAL
NEW WORK CAMPUS EMERGENCY
LOOP SINGLE LINE DIAGRAM
E-603
MJRTO
DEMOLITION
EXISTING TO
REMAIN
(N) PAD MOUNTED XFMR-26
REPLACING GENERATOR "26"
500-KVA
12470V-208V
GEC: #3/0
EXISTING BLDG EMERGENCY
DISTRIBUTION SYSTEM
SEE DETAIL 2/ED602.
TO NEW PARALLELING SWITCHGEAR SECTION 2
SEE DRAWING E-601 FOR CONTINUATION
1. NEW EMERGENCY LOOP WITHIN NEW CONCRETE ENCASED UNDERGROUND
DUCTBANK. SEE DRAWING E-601 FOR FEEDER SIZES.
2. SPLICE AND EXTEND EXISTING GENERATOR FEEDER IN EXISTING CONDUIT AS
REQUIRED FOR CONNECTION TO NEW TRANSFORMER.
3. PROVIDE NEW 2" CONDUIT FROM NEW ATS-21 TO NEW UNDERGROUND
CONCRETE ENCASED LOW VOLTAGE DUCTBANK FOR SIGNALING WIRE
ROUTING TO NEW GENERATOR BUILDING. NEW LOW VOLTAGE CONTROL
WIRING (TWO SETS OF #10 TWISTED PAIR) BETWEEN NEW ATS-21 AND NEW
MEDIUM VOLTAGE GENERATORS SHALL BE RUN IN THIS PATHWAY.
4. NEW UNDERGROUND CONCRETE ENCASED DUCTBANK CONDUITS SHALL BE
EXTENDED AS REQUIRED FOR LOOP FEEDER TERMINATION SUNDER THE
EXISTING GENERATOR CONCRETE PAD AT THE LOCATION OF EACH OF THE
TWO (2) LOOP FEED SWITCHES.
EXISTING BLDG EMERGENCY
DISTRIBUTION SYSTEM
SEE DETAIL 3/ED602.
EXISTING BLDG EMERGENCY
DISTRIBUTION SYSTEM
SEE DETAIL 4/ED602.
(N) PAD MOUNTED XFMR-2
REPLACING GENERATOR "1B & 2"
750-KVA
12470V-480V
GEC: #3/0
(N) PAD MOUNTED XFMR-34
REPLACING GENERATOR "34"
1000-KVA
12470V-480V
GEC: #3/0
30A
200A
50A
200A
60A
200A
EXISTING BLDG EMERGENCY
DISTRIBUTION SYSTEM
SEE DETAIL 1/ED602.
(N) PAD MOUNTED XFMR-62
REPLACING GENERATOR "62"
300-KVA
12470V-480V
GEC: #1/0
20A
200A
EXISTING BLDG EMERGENCY
DISTRIBUTION SYSTEM
SEE DETAIL 5/ED602.
(N) PAD MOUNTED XFMR-31
REPLACING GENERATOR "31"
300-KVA
12470V-208V
GEC: #3/0
20A
200A
EXISTING BLDG EMERGENCY
DISTRIBUTION SYSTEM
SEE DETAIL 6/ED602.
(N) PAD MOUNTED XFMR-31A
REPLACING GENERATOR "31A"
300-KVA
12470V-240V
GEC: #3/0
20A
200A
EXISTING BLDG EMERGENCY
DISTRIBUTION SYSTEM
SEE DETAIL 7/ED602.
(N) PAD MOUNTED XFMR-5
REPLACING GENERATOR "5"
112.5-KVA
12470V-208V
GEC: #1/0
10A
200A
EXISTING BLDG EMERGENCY
DISTRIBUTION SYSTEM
SEE DETAIL 8/ED602.
(N) PAD MOUNTED XFMR-21
REPLACING GENERATOR "21"
75-KVA
12470V-208V
GEC: #2
10A
200A
EXISTING BLDG EMERGENCY
DISTRIBUTION SYSTEM
SEE DETAIL 9/ED602.
(N) PAD MOUNTED XFMR-13
REPLACING GENERATOR "13"
150-KVA
12470V-208V
GEC: #1/0
10A
200A
TO NEW PARALLELING SWITCHGEAR SECTION 7
SEE DRAWING E-601 FOR CONTINUATION
SCALE: NTS
(N) ATS-21
208-VOLT, 225-AMP
NEMA 3R RATED
RECONNECT TO EXISTING NORMAL
POWER FEEDER TO BUILDING 21
4-#4/0, 1-#4G IN 2 1/2" C.
PROFESSIONAL ENGINEER
PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE
WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE
PROFESSIONAL ENGINEER.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
BID DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
Phase
ENGINEER OF RECORDCONSULTANT CONSTRUCT CENTRALIZED
EMERGENCY POWER SYSTEM
589A7-21-132
Project Director
2026-03-26
321 4 5 6 7 8 9 10
A
B
C
D
E
F
21 4 5 6 7 8 9 10
A
C
D
E
F
M-R PROJECT NO: 0499-0162
ROBERT J. DOLE VA MEDICAL CENTER
WICHITA, KANSAS
Civil / Site Utility Engineering:Hazardous Materials:
MABBETT & ASSOCIATES, INC.
Fire & Life Safety:
STANTON ENGINEERING SERVICES, LLC
Architectural:
OCULUS, INC.
Structural:
PROFESSIONAL ENGINEERING
CONSULTANTS, PA (PEC)
IMEG, CORP. 37
ELECTRICAL
SCHEDULES &
BUILDING 37 SINGLE LINE DIAGRAM
E-701
MJRTO
(E) BUILDING 13-EMDP
480/277V, 600A, 3Ø, 4W, 42KAIC
SEE DETAIL 1/EP402 FOR LOCATION.
1 2 3 4
80A 3P
80A 3P
600A 3P
225A 3P
5 6
80A 3P
70A 3P
7 8
BOILER #1 BOILER #2
9 10
175A 3P
BOILER #3
FEED WATER
PUMPS (SKID)
100A 3P
70A 3P
60A 3P
150A 3P
BOILER
COMPRESSORS
(SKID)
200A 3P
QUICK
CONNECT BOX
-T
-E
LP
-T
-E
LD
P
SPD
(E) (E) (E) (E) (E) (E) (E) (E) (E) (N) (E)
SPD
SCALE: NTS
(E) (E) (E) (E) (E) (E) (E) (E)
A
GROUND
WIRE SIZE (AWG/KCMIL)
WIRE AND CONDUIT SIZING SCHEDULE
CONDUCTOR PHASE &
NEUTRAL
SINGLE LINE TAG: THIS
COLUMN COMBINED
WITH "A", "B", OR "C"
COLUMN
NO. OF WIRES & CONDUIT
SIZE IN INCHES
1. CONDUIT SIZES SHOWN ARE TYPICAL FOR CONDUCTOR SIZES AND QUANTITY. CONDUIT AND WIRE SIZE NOTED ON THE
ELECTRICAL FLOOR PLANS AND SINGLE LINE TAKE PRECEDENCE.
1PH, 2W+G 3PH, 3W+G 3PH, 4W+G
B C
EX EXISTING FEEDERS AND CONDUIT
3/41414 3/4 3/4
3/41212 3/4 3/4
3/41010 3/4 3/4
3/48 3/4 3/4
3/46 3/4 1
3/44 1
3/484
1 1/41
1/0 1 1/2
2/0 2
3/0 2 2
44/0
350 3
(2) 1 1/2(2) 3(2) 3/0
(2) 2(2) 4/0 (2) 2 (2) 2 1/2
(2) 250
(2) 350
(2) 500
(3) 300
(3) 400
(4) 350
(5) 400
(6) 400
(7) 500
(8) 500
(2) 2
(2) 1
(2) 1/0
(3) 1/0
(3) 2/0
(4) 3/0
(5) 4/0
(6) 250
(7) 350
(8) 400
2 1/2
2 1/2
(2) 2
(2) 2 1/2
(2) 3
(3) 2 1/2
(3) 3
(4) 2 1/2
(5) 3
(6) 3
(7) 3
(8) 3
(2) 2 1/2
(2) 3
(2) 3 1/2
(3) 3
(3) 3
(4) 3
(5) 3
(6) 3
(7) 3 1/2
(8) 3 1/2
1 1/4
1 1/4
1 1/2
1 1/2
1 1/2
1 1/4
1 1/4
1 1/4
1 1/4
1 1/4
1 1/4
1 1/4
1 1/2
1 1/2
1 1/2
2 1/2
2 1/2
2 1/2
1 6 1 1/4 1 1/4 1 1/2
(2) 2 (2) 2
500 33 2 1/2 3
32 (2) 350 (2) 2/0 (2) 2 1/2 (2) 3
EGC: #6
BUILDING 13 INTERIOR
BUILDING 13 EXTERIOR
ROUTED IN CONCRETE
ENCASED DUCTBANK.
SEE CIVIL DRAWINGS
FOR FURTHER DETAIL.
SPD
ROUTE ALONG INTERIOR OF BOILER
PLANT TO BUILDING WEST EXTERIOR
WALL. SEE DETAIL 1/EP402 FOR
FURTHER INFORMATION.
MAIN CIRCUIT BREAKER
SHALL BE SERVICE
ENTRANCE RATED.
NOTES:
1. ELECTRICAL CONTRACTOR SHALL REMOVE EXISTING 60-AMP/3-POLE CIRCUIT BREAKER
AND REPLACE WITH A NEW 150-AMP CIRCUIT BREAKER. NEW CIRCUIT BREAKER SHALL
MATCH EXISTING BREAKER'S TYPE (SCHNEIDER ELECTRIC) AND AIC RATING (42kA).
SEE NOTE 1.
BUILDING 37
TRANSFORMER T1
30kVA
(E)
PANEL
13-EMH1
(E)
PANEL
13-EMH2
(E)
PANEL
13-ELDP
SPD
(E)
PANEL
13-ELP3
| E-001 - ELECTRICAL ABBREVIATIONS & SYMBOLS |
| E-002 - ELECTRICAL NOTES |
| ED602 - ELECTRICAL DEMOLITION BUILDING SINGLE LINE DIAGRAMS |
| ES101 - ELECTRICAL DEMOLITION SITE PLAN |
| ES102 - ELECTRICAL NEW WORK SITE PLAN |
| EP101 - ELECTRICAL POWER PLAN BUILDING 35A |
| EL111 - ELECTRICAL LIGHTING PLAN GROUND FLOOR |
| EP111 - ELECTRICAL POWER PLAN GROUND FLOOR |
| EP131 - ELECTRICAL POWER & LIGHTNING PROTECTION PLAN -ROOF |
| EY111 - ELECTRICAL SIGNAL PLAN GROUND FLOOR |
| EP401 - ELECTRICAL ENLARGED PLANS BUILDINGS 1, 2, 5 & 36 |
| EP402 - ELECTRICAL ENLARGED PLANS BUILDINGS 13, 20, 26, 29 & 62 |
| EP403 - ELECTRICAL ENLARGED PLANS BUILDINGS 34, 60 & 61 |
| E-501 - ELECTRICAL DETAILS |
| E-502 - ELECTRICAL DETAILS |
| E-601 - ELECTRICAL NEW WORK SWITCHGEAR SINGLE LINE DIAGRAM |
| E-602 - ELECTRICAL NEW WORK CAMPUS NORMAL LOOP SINGLE LINE DIAGRAM |
| E-603 - ELECTRICAL NEW WORK CAMPUS EMERGENCY LOOP SINGLE LINE DIAGRAM |
| E-701 - ELECTRICAL SCHEDULES & BUILDING 37 SINGLE LINE DIAGRAM |
File details come from the government source that posted it. Updated .