589A7-21-132 Wichita Bid Drawings 05_Architectural Complete.pdf
PDF 8 MB Posted
- Solicitation number
- 36C25526R0125
About this file
This document is a comprehensive architectural drawing set for a centralized emergency power system construction project at Robert J. Dole VA Medical Center in Wichita, Kansas.
The project involves constructing a new 5,420 square-foot building (Building 37) to house three generator units, switchgear, fuel storage, and associated equipment. The structure is classified as Type II-B non-combustible construction with an F1 (moderate hazard industrial) occupancy designation. Key building features include a 4,202 square-foot generator room (Room 101), a 593 square-foot switchgear room (Room 103), and a 143 square-foot fire riser room (Room 102), plus equipment access areas. The building must withstand extreme impact pressures from a design-level explosive threat (W2) at 50 feet standoff distance, requiring 12-inch extreme impact-rated concrete masonry unit (CMU) exterior walls, extreme impact-rated doors and overhead doors with magnetic locks and dual authentication access controls, and minimal windows constructed of extreme impact-resistant frames with laminate glazing. The structure features a fully-adhered TPO membrane roof system on rigid insulation over a concrete-filled metal deck, cast stone parapet caps and datum bands, and face brick veneer matching existing site standards. All occupants must be restricted to authorized personnel only, and the building is fully sprinklered. Interior finishes include concrete floors with sealed surfaces and interior CMU walls painted with Sherwin Williams Light French Gray (SW 0055). The architectural drawings provide detailed specifications for wall sections, door and window schedules, roof details, site wall extensions, and comprehensive signage requirements including fire equipment identification, high voltage warnings, noise warnings, allowable floor loading signs, and exit signage with LED backlighting.
View the file
Other files
Show all 30
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
PULL
PULL
RADIOLOGY
RECORDS
RECOVERY
RECEPTION
M
MAINT
MECH
MACH MACHINE ROOM
MALE
MAINTENANCE
RECD
RECP
RECOV
RAD
ROOM
STAFF
REHABILITATION
SHOWER
SUPPLY
STAFF TOILET
SOILED UTILITY
SECRETARY
STAIRS
SUPPORT
STATION
STERILIZER
SERVICE
SWITCHGEAR
SUPERVISOR
SURGERY/ ICAL
STORAGE
MGR
MED
MRI
OFF
OR
ORTHO
OH
OB/GYN
OPERATING ROOM
MANAGER
OFFICE
MEDICATION/ MEDICAL
ORTHOPEDICS
OBSTETRICS/ GYNECOLOGY
ORAL HYGIENIST
MAGNETIC RESONANCE
IMAGING
SWGR
ST
STA
RM
S TLT
SVCE
SHR
S
STOR
SUPVR
SPRT
SPLY
SOIL
SECY
REHAB
STER
SURG
MECHANIC(AL)
EDUCATION
ELEVATOR
ELECTRIC(AL)
ED
ELEV
EMG
ELEC
ADMIN
ASSY
AUD
AMB
ASSEMBLY
ADMINISTRATION(OR)
AMBULATORY
AUDIOLOGY
"DN"
S
SIMILARSIM
SPEC
SF
SOUTH/ SINK
SQUARE FEET/ STOREFRONT
(NON - NCS ABBREVIATIONS ARE SHOWN
UNDERLINED) EXAMPLE:
ENDOSCOPY
EQUIPMENT
EXECUTIVE
ENDO
ENT
EQUIP
EXEC
FREEZER
FEMALE
FRZ
F
BALCONYBALC
CHEMICALCHEM
CHGN
CLASSCL
CHIRO CHIROPRACTOR
CHARGE NURSE
GENERAL
GYMNASIUM
GEN
GYM
HEAD
HOUSEKEEPINGHSKPG
HD
ICCU
HAZ MAT
CLERICAL
CLN
CLER
CLOSETCLO
CLRM CLASSROOM
CLEAN (ING)/ CLEAN UTILITY
COMM
CONF
CORRIDORCORR
COPY
COMMUNICATIONS
CONFERENCE
COPY/ WORK ROOM
COMMANDER/ COMMANDCMD
SQUARESQ
SST
STEEL
STC
STL
TREADT
THROUGHTHRU
TEMP
SOUND TRANSMISSION CLASS
STAINLESS STEEL
TEMPERATURE/ TEMPORARY
TOP OF
TOC
TO
TOF
TOM
TYPICALTYP
U
UC
TOS
HEAT TRANSFER COEFFICIENT
TOP OF FOOTING
TOP OF CONCRETE (CURB)
UNDERCUT
TOP OF MASONRY
TOP OF STEEL
SPECIFICATION(S)
HAZARDOUS MATERIALS
EAR NOSE THROAT
ELECTROMYOGRAPHY
INTENSIVE CARDIAC CARE UNIT
TECHNICIAN
TELEPHONE
TOILET
URINAL
TREATMENT
WAITING
WAREHOUSE
WATER CLOSET
WEIGHTS AND MEASURES
WEIGHT
WORK STATION, WORK ROOM
EXECUTIVE OFFICER
VESTIBULE
P
PHAR
PHYS
PEDS
PO
PSRDM
PRIN
PREP
POST OFFICE
PRINCIPAL
PHARMACY
PATIENT
PREPARATION
PEDIATRICS
PHYSICAL
PHYSICAL SECURITY RISK MITIGATION DESIGN
PROCTO
PROC
PUB
PT/OT
PULMO
PUBLIC
PHYSICAL / OCCUPATIONAL
THERAPY
PROCTOLOGY
PROCEDURE
PULMONARY
PARKINGPRKG
WT
WHSE
WAIT
VEST
UR
WORK
TRT
TECH
XO
WC
W & M
TEL
TLT
INFORMATION
ISOLATION
INJECTION
INFO
ICU
ISO
INJ
JANITOR
KITCHEN
JAN
JC
KIT
CSR
CT
CONTROLCTRL
CENTRAL STERILE ROOM
CAT SCAN
DRESSING
DEPT
D
DIRECTOR
DICTATION
DIR
DICT
DEPARTMENT
LAUNDRY
LABORATORY
LAU
LAB
LDRP
LCPO
LIBRARY
LOCKER
LIT/ FORMS
LIB
LPO
LKR
L/W
L/F
DOCTORDR
DOR
DRK
DTR
DARKROOM
DENTAL TREATMENT ROOM
DENTAL OPERATORY ROOM
DISP DISPENSING
UL
U/C/B
VACUUMV
U0N
VARIESVAR
VCT
VERTICAL
VTR
VERT
VENT THRU ROOF
UNLESS OTHERWISE NOTED
UNDERWRITERS LABORATORY
VINYL COMPOSITION TILE
UNDER COUNTER BASE
W
WITHW/
W
WITHOUT
WOOD
W/0
WD
WEIGHTWT
WP
WH WALL HUNG/ WATER HEATER
WEST /WATT
WATERPROOF / WORKING POINT
WIDTH /WIDE FLANGE
VWC VINYL WALL COVERING
WWF WELDED WIRE FABRIC
JANITOR'S CLOSET
LABOR DELIVERY RECOVERY POST PARTUM
LEADING CHIEF PETTY OFFICER
LEADING PETTY OFFICER
LITTER WHEELCHAIR
INTENSIVE CARE UNIT
KILOPASCAL
POUND
ANGLE
KPA
L
LB
EACH
ELEVATION
EACH END
EXPANSION JOINT
EA
EJ
EL
EE
AND&
DOLLAR (USD)
@ AT
NUMBER / POUND
NATIONAL CAD STANDARD ABBREVIATIONS
LINEAR FEET
METERS
MAXIMUM
LF
M
MAX
MINIMUM
MILLIMETERS
MISCELLANEOUS
MASONRY OPENING
MIN
MM
MISC
MO
ET CETERA
EQUAL
EYE WASH STATION
ELECTRIC WATER COOLER
EXISTING
FILLER
NORTH
NOT APPLICABLE
NUMBER
NOT IN CONTRACT
NA
N
NO
NIC
NOT TO SCALE
OXYGEN
ON CENTER
NTS
OC
O
NOMINALNOM
FACSIMILE
FIRE EXTINGUISHER
FINISHED FLOOR
FIRE EXTINGUISHER CABINET
FLOOR
FACE OF
FIBERGLASS REINFORCED POLYMER
FACE OF SLAB (STUD)
FIRE HOSE CABINET
EQ
F
A/C
A/E
ADA
ACT
AHJ
AHU
AFF
ALUM
AUTHORITY HAVING JURISDICTION
AMERICANS WITH DISABILITY ACT
ACOUSTICAL CEILING TILE
ABOVE FINISHED FLOOR
AIR HANDLING UNIT
ALUMINUM
ARCHITECT-ENGINEER
AIR CONDITIONED
FE
FF
FLR
FO
FRP
BEAM
BLDG
BM
BOS
BO
CG
CCT
CL
CJ
BUILDING
BOTTOM OF STEEL
CENTER LINE
CONTROL/ CONSTRUCTION JOINT
CORNER GUARD
BY OWNER/ BOTTOM OF
CUBICLE CURTAIN TRACK
FOS
FAX
EWS
ETC
FEC
FHC
EXIST
EWC
OPPOSITE HAND
OUTSIDE DIAMETER
PLATE
OPENING
OPH
OD
PL
OPNG
PAIR
PLASTIC LAMINATEPLAM
PR
PSI
PSF
GAS
GRAB BAR
GALVANIZED
GAGE
HIGH
GYPSUM BOARD
GENERAL CONTRACTOR
QUANTITY
PTS
QTY
RISER/RADIUS
REQUIRED
ROUGH OPENING
REFER
R
RAL
RO
REQ
REHARDWARE
HOUR
HOLLOW METAL
INTERCOM
INTRAVENOUS
INCH(ES)
INSIDE DIAMETER
PT
HANDICAP
G
GB
GA
GC
H
CLL
CLG
CM
CMU
CLR CLEAR
CONC
CO2
CONT
CTJ
CENTIMETER
CONCRETE
COLUMN LINE
CONTINUED (OUS)
CONCRETE MASONRY UNIT
CEILING
CONTRACTION JOINT
CARBON DIOXIDE
HM
HR
ID
IC
IV
INCTR
DBA
D
DEG
DIA
DR
DWG
DN DOWN
DEGREE
UNIT OF SOUND
CENTER
DEEP/ DEPTH
DIAMETER
DOOR/
DRAWING(S)
COORDINATECOORD
HC
HDW
GALV
GYP BD
ROICC
JOINTJT
DWR DRAWER
PAINT
POUNDS/SQUARE FOOT
POUNDS/SQUARE INCH
RESIDENT OFFICER IN CHARGE
OF CONST
FEDERAL COLOR PALETTE
PNEUMATIC TUBE STATION VOL VOLUNTEER
ASSISTANTAST
COMPUTERCOMP
COORD COORDINATOR
CLIN CLINIC (AL)
PERSONNELPERS
MANAGEMENTMGNT
ANALYSISTANLST
COMPR COMPTROLLER
CUBICLESCBCL
DEGREE(S)°
AIR
A
/ DIVIDE BY, PER
EQUALS, EQUAL TO
' FOOT, FEET
> GREATER THAN
> GREATER THAN OR EQUAL TO
INCH(ES)"
MINUS, NEGATIVE
< LESS THAN
LESS THAN OR EQUAL TO
MULTIPLY BY, BYX
% PERCENT
PLUS
+/- PLUS OR MINUS
NATIONAL CAD STANDARD ROOM NAME ABBREVIATIONS
"DN"
(NON - NCS ABBREVIATIONS ARE SHOWN
UNDERLINED) EXAMPLE:
FOOT/FEETFT
TELEVISIONT.V.
P.T. PRESSURE TREATED
MOUNTEDMNTD
FIRE RETARDANTF.R.
SS STAINLESS STEEL
WHEELCHAIRW/C
FIRE TREATEDF.T.
ABA ARCHITECTURAL BARRIERS ACT
SAB SOUND ATTENUATION BATTS
EXPOSEDEXP
VERIFY IN FIELDVIF
VERIFY IN FIELDVIF
PYSCH PSYCHOLOGY
HOLLOW METAL FRAMEHMF
RENOVATE(TION)RENO
A101
SIM
A101
SIM
A101
SIM
BUILDING ELEVATION/SECTIONDetail No.
Sheet No.
Reference Label
Detail No.
Sheet No.
Reference Label
Detail No.
Sheet No.
Reference Label
Room No.
Room Area
Door/Room No.
Partition Configuration
Partition Configuration
Key Note No.
ALIGN
WALL SECTION
DETAIL SECTION/CALLOUT
ROOM TAG
DOOR TAG
PARTITION TAG
KEYNOTE
ALIGNED SURFACES
Room Name
Area
AREA TAG
Area NameArea Name
150 SF
WL
2S 86
SCOPE OF PROJECT
Project Limit Line
Grid No.
CENTERLINE
COLUMN GRID LINE
SPOT ELEVATIONSpot Elevation AFF
Level/Datum Elevation AFF
LEVEL MARKER
Level/Datum Name
Window Type WINDOW TYPE TAG01
CL
Highpoint @ Tail SLOPE INDICATOR
Starting Point @ Center DIMENSION CROSSHAIR
NORTH ARROW
Plan North Reference Label
Name Elevation
Revision Reference Number
Revision Cloud Depicting Area Revised
REVISION
CEILING TAG1'-0" Clg Height
? Finish FINISH TAG
Casework / Furniture
CASEWORK TAG1i
FURNITURE TAG
Room Wall Finish
Room Wall Base
Room Floor Finish
ROOM FINISH TAG
FIRE
EXTINGUISHER
WALL MOUNTED
CABINET
FIRE ALARM
PULL BOX
4'
M A
X
IM
U M
4'
M A
X
IM
U M
4'
M A
X
IM
U M
3'
FIRE
EXTINGUISHER
WALL HUNG
FIRE
EXTINGUISHER
IN RECESSED
CABINET
FIRE EXTINGUISHER
AND FIRE HOSE
VALVE IN RECESSED
CABINET
FIRE EXTINGUISHER,
FIRE HOSE VALVE
AND FIRE
DEPARTMENT VALVE
IN RECESSED
CABINET
FIRE DEPARTMENT
VALVE IN
RECESSED
CABINET
3'
FIREFIGHTERS
HANDSET
FH
0' - 10 1/2"
1'
3'
M A
X
8" 8"7
AUDIO/VISUAL
FIRE ALARM
EXIT SIGN WALL
SWITCH
WALL
PHONE
JACK
FIRE ALARM
PULL STATION
(GENERALLY
LOCATE UNDER
A/V ALARM)
W
IT
H O
W N
E R
C O
O R
D
IN
A T
E0' - 8"
COMBINATION
POWER/SIGNAL/OUTLET
FOR WALL MOUNTED
TELEVISION OR
MONITOR
CLOCK
(PLACED ON WALL
WITH NO VISUAL
BOARDS
MOUNTED BELOW)
DOUBLE-SIDED
PROJECTED
CLOCK
M
IN
C
E
IL
IN
G
H E
IG
H
T
U
.N .O
S
P A
C E
S W
IT
H
T.V./DATA/
PHONE
POWER
RECEPTACLES
LIGHT
SWITCHES
DOME
LIGHT
OCCUPANCY
SENSOR
CARD
READER
THERMOSTAT
POWER
DISCONNECT
REMOTE DOOR
RELEASE
D/V L
TV
D/V
TV E
E
ED/V
L L OS CR T DR
AREA OF
REFUGE
INTERCOM
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ENGINEER OF RECORD
321 4 5 6 7 8 9 10
NO. DESCRIPTION DATE
PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE
WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE
PROFESSIONAL ENGINEER
o n e e ig h th i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e i n c h o n e f o o t o n e a n d o n e h a lf i n c h e s o n e f o o t th re e i n c h e s o n e f o o t
OCULUS INCORPORATED
ARCHITECT OF RECORD
MR PROJECT NO: 0499-0162
CONSULTANTS
Civil / Site Utility Engineering:
IMEG, CORP.
Fire & Life Safety:
STANTON ENGINEERING SERVICES, LLC
Hazardous Materials:
MABBETT & ASSOCIATES, INC.
Architectural:
OCULUS, INC.
Structural:
PROFESSIONAL ENGINEERING
CONSULTANTS, PA (PEC)
O C
U L U
S P
R O
JE
C
T N
O
A u to d e sk D o cs
/W ic h ita
C e n tr a liz e d
E m e rg e n cy P o w e r/
-1
-K
S
W ic h ita V
A M
C
O C
U L
U S
A C
C C
E N
T R
A L .r vt
/2
/2
:5
:1
P
M
A-001
CONSTRUCT CENTRALIZED
EMERGENCY POWER SYSTEM
ROBERT J. DOLE VA MEDICAL CENTER
WICHITA, KANSAS
589A7-21-132
Project Director
2026-03-26 RAF MMT
BID DOCUMENTS
FULLY SPRINKLERED
NOTES, SYMBOLS, ABBREVIATIONS
ARCHITECTURAL
-K
S
ABBREVIATIONS PLAN SYMBOLS
FIRE PROTECTION EQUIPMENT
ELECTRICAL CONTROL DEVICES
F1
E1
Matthew Thole - Oculus
T
T
T
F F
F
F A
C
PF
A
A
PATH OF TRAVEL (FEET)
VOICE/ALARM SYSTEM THROUGHOUT
(COORDINATE W/ ELECTRICAL)
EXIT FLOW
PATH TAG
EXIT SIGN
(COORDINATE W/ ELECTRICAL)
PORTABLE FIRE EXTINGUISHER
DRY-CHEMICAL ABC CLASSIFICATION
(COORDINATE W/ FIRE MARSHAL)
TWO HOUR FIRE BARRIER
CONSTRUCTION
PATH
ID'S:
X# X# X# X#
FE
COMBINED OCCUPANT LOAD AT DOOR
TOTAL EXIT CAPACITY OF DOOR
5053 SF
SI - SPECIAL
INDUSTRIAL
SI - SPECIAL INDUSTRIAL
PATH
ID'S:
1A, 1B
FE
PATH
ID'S:
2A, 2B
PATH
ID'S:
1A, 2A
PATH
ID'S:
1B, 2B
FE
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ENGINEER OF RECORD
321 4 5 6 7 8 9 10
NO. DESCRIPTION DATE
PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE
WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE
PROFESSIONAL ENGINEER
o n e e ig h th i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e i n c h o n e f o o t o n e a n d o n e h a lf i n c h e s o n e f o o t th re e i n c h e s o n e f o o t
OCULUS INCORPORATED
ARCHITECT OF RECORD
MR PROJECT NO: 0499-0162
NORTHKEYPLAN
CONSULTANTS
Civil / Site Utility Engineering:
IMEG, CORP.
Fire & Life Safety:
STANTON ENGINEERING SERVICES, LLC
Hazardous Materials:
MABBETT & ASSOCIATES, INC.
Architectural:
OCULUS, INC.
Structural:
PROFESSIONAL ENGINEERING
CONSULTANTS, PA (PEC)
BUILDING 37
AREA OF WORK
O C
U L U
S P
R O
JE
C
T N
O
A u to d e sk D o cs
/W ic h ita
C e n tr a liz e d
E m e rg e n cy P o w e r/
-1
-K
S
W ic h ita V
A M
C
O C
U L
U S
A C
C C
E N
T R
A L .r vt
/2
/2
:5
:0
P
M
A-101
CONSTRUCT CENTRALIZED
EMERGENCY POWER SYSTEM
ROBERT J. DOLE VA MEDICAL CENTER
WICHITA, KANSAS
589A7-21-132
Project Director
2026-03-26 RAF MMT
BID DOCUMENTS
FULLY SPRINKLERED
LIFE SAFETY
ARCHITECTURAL
PLAN
-K
S
APPLICABLE CODES _________________
2024 INTERNATIONAL BUILDING CODE (IBC)(ONLY WHEN SPECIFICALLY REFERENCED IN VA DESIGN
DOCUMENTS)
2024 EDITION NFPA 101 LIFE SAFETY CODE
2023 VA FIRE PROTECTION DESIGN MANUAL 9TH EDITION
2024 NFPA NATIONAL FIRE CODE (EXCEPTION OF NFPA 5000 AND NFPA 900)
2023 NATIONAL ELECTRICAL CODE (NEC)
2024 INTERNATIONAL PLUMBING CODE (IPC)
ENERGY POLICY ACT OF 2005 (EPACT)
FEDERAL LEADERSHIP IN HIGH PERFORMANCE AND SUSTAINABLE BUILDINGS: MEMORANDUM OF
UNDERSTANDING (MOU)
EXECUTIVE ORDER 13423: STRENGTHENING FEDERAL ENVIRONMENTAL, ENERGY, AND TRANSPORTATION
MANAGEMENT
THE PROVISIONS FOR CONSTRUCTION AND SAFETY SIGNAGE
VENTILATION FOR ACCEPTABLE INDOOR AIR QUALITY - ASHRAE STANDARD 62.1 -2004
OCCUPATIONAL, SAFETY AND HEALTH ADMINISTRATION (OSHA) STANDARDS
ARCHITECTURAL BARRIERS ACT ACCESSIBILITY STANDARDS (ABAAS)
VA BARRIER FREE DESIGN STANDARDS PG-18-13
UNIFIED FACILITIES CRITERIA (UFC 3-540-01) ENGINE GENERATOR SYTSEMS FOR PRIME AND STANDBY
POWER APPLICATIONS
BUILDING HEIGHT AND AREA LIMITATIONS (IBC CHAPTER 5):
USE & OCCUPANCY CLASSIFICATION: F1 - MOD. HZD. INDUSTRIAL
TYPE OF CONSTRUCTION: II-B / TYPE-II (000)
ALLOWABLE HT IN FEET (TABLE 504.3): 75' (S)
ACTUAL HEIGHT ABOVE GRADE: 24'-0"
ALLOWABLE ST. ABOVE GRADE (TABLE 504.4): 3 (S)
ACTUAL STORIES ABOVE GRADE: 1
ALOWABLE AREA (TABLE 506.2): 62,000 sqft (S1)
ACTUAL AREA: 5,420 sqft
PER IBC CHAPTER 5: TYPE 2B NON COMBUSTIBLE, FULLY SPRINKLERED BUILDING WITH AN F1 MODERATE HAZARD INDUSTRIAL OCCUPANCY IS PERMITTED TO BE UP TO 75’ TALL, THREE STORIES, WITH 62,000 SQFT
OF ALLOWABLE AREA.
AS DEFINED BY TABLE 601 THE BUILDING ELEMENTS ARE REQUIRED TO CARRY THE FOLLOWING
FIRE RESISTANCE RATINGS IN TYPE II-B CONSTRUCTION:
PRIMARY STRUCTURAL FRAME: 0 HRS
EXTERIOR BEARING WALLS: 0 HRS
INTERIOR BEARING WALLS: 0 HRS
EXTERIOR NON-BEARING WALLS: 0 HRS
INTERIOR NON-BEARING WALLS: 0 HRS
FLOOR CONSTRUCTION AND
SECONDARY MEMBERS: 0 HRS
ROOF CONSTRUCTION AND
SECONDARY MEMBERS: 0 HRS
PER NFPA 5000 TABLE 7.4.1, A TYPE II, (000), FULLY SPRINKLERED, ORDINARY HAZARD INDUSTRIAL OCCUPANCY IS PERMITTED TO BE UP TO 75’ TALL, THREE STORIES, WITH 15,500 SQFT OF FOOTPRINT.
AS DEFINED BY TABLE 7.2.1.1, CONSTRUCTION ELEMENTS ARE REQUIRED TO CARRY THE
FOLLOWING FIRE RESISTANCE RATINGS IN TYPE-II (000) CONSTRUCTION:
EXTERIOR BEARING WALLS:
SUPPORTING MORE THAN ONE FLOOR: 0 HRS
SUPPORTING ONLY ONE FLOOR: 0 HRS
SUPPORTING ROOF ONLY: 0 HRS
INTERIOR BEARING WALLS:
SUPPORTING MORE THAN ONE FLOOR: 0 HRS
SUPPORTING ONLY ONE FLOOR: 0 HRS
SUPPORTING ROOF ONLY: 0 HRS
COLUMNS:
SUPPORTING MORE THAN ONE FLOOR: 0 HRS
SUPPORTING ONLY ONE FLOOR: 0 HRS
SUPPORTING ROOF ONLY: 0 HRS
BEAMS, GIRDERS, TRUSSES, AND ARCHES:
SUPPORTING MORE THAN ONE FLOOR: 0 HRS
SUPPORTING ONLY ONE FLOOR: 0 HRS
SUPPORTING ROOF ONLY: 0 HRS
FLOOR/CEILING ASSEMBLIES: 0 HRS
ROOF/CEILING ASSEMBLIES: 0 HRS
INTERIOR NON-BEARING WALLS: 0 HRS
EXTERIOR NON-BEARING WALLS: 0 HRS
NFPA 101 OCCUPANCY & ASSOCIATED CHAPTER
• GENERATOR FLOOR, MAIN LEVEL : INDUSTRIAL OCCUPANCY (NFPA 101 : 2024, CHAPTER 40)
• STORAGE UTILITY AREAS ASSUMED TO BE NON-SEPERATED, ANCILLARY FACILITIES PER PROVISIONS
OF (A.6.1.14.1.3)
40.2.5.3.1 INDUSTRIAL EQUIPMENT ACCESS DIMENSIONAL CRITERIA:
MINIMUM HORIZONTAL DIMENSION OF ANY WALKWAY: 22” CLEAR
MINIMUM STAIR OR RAMP WIDTH: 22” @ RAILS
MINIMUM TREAD WIDTH: 22” CLEAR
MINIMUM TREAD DEPTH: 10”
MAXIMUM RISER HEIGHT: 9”
MAX HT. BETWEEN LANDINGS: 12’-0”
MINIMUM HEADROOM: 6’-8”
MINIMUM WIDTH OF DOOR OPENINGS: 22”
ENERGY CONSERVATION / ENVELOPE THERMAL PERFORMANCE CRITERIA:
ZONE 4A - MASS CONSTRUCTION:
MINIMUM THERMAL RESISTANCE - WALL: R-13 C.I.
MINIMUM THERMAL RESISTANCE - ROOF: R-30 C.I.
LIFE SAFETY LEGEND
GENERAL SHEET NOTES
1. THE MINIMUM WIDTH OF EACH DOOR OPENING SHALL BE SUFFICIENT FOR THE OCCUPANT LOAD
THEREOF AND SHALL PROVIDE A CLEAR WIDTH OF NOT LESS THAN 32 INCHES. THE HEIGHT OF DOORS
SHALL NOT BE LESS THAN 80 INCHES.
2. EGRESS DOORS SHALL BE READILY OPERABLE FROM THE EGRESS SIDE WITHOUT THE USE OF A KEY OR ANY SPECIAL KNOWLEDGE OR EFFORT. ALL EGRESS DOORS TO HAVE PANIC HARDWARE. PANIC HARDWARE SHALL NOT REQUIRE TIGHT GRASPING, PINCHING, OR TWISTING OF THE WRIST. FORCE
REQUIRED TO ACTIVATE OPERABLE PARTS SHALL BE 5 POUNDS MAXIMUM.
3. THE MEANS OF EGRESS, AND EXIT DISCHARGE, SHALL BE ILLUMINATED AT ANY TIME THE BUILDING IS OCCUPIED WITH A LIGHT INTENSITY OF NOT LESS THAN 1 FOOT-CANDLE AT THE WALKING SURFACE
LEVEL.
4. THE EGRESS PATH SHALL REMAIN FREE AND CLEAR OF ALL OBSTRUCTIONS AT ALL TIMES. NO
STORAGE IS PERMITTED IN ANY EGRESS PATHS.
5. PER DIRECTION OF THE PROJECT CONTRACTING OFFICER , AND PER GUIDANCE OF ABAAS SCOPING
REQUIREMNTS (F203.6 MACHINERY SPACES) PORTIONS OF THE PLAN INCLUDING DEDICATED
MECHANICAL SPACES AND LOCKER AND BREAK ROOM FACILITIES ACCESSED ONLY BY PLANT
OPERATIONS PERSONNEL ARE NOT REQUIRED TO BE REACHABLE BY CONTINUOUS ACCESSIBLE
PATHS.
6. CONTRACTOR TO SUBMIT TEMPORARY LIFE SAFETY PLANS IN THE EVENT REQUIRED EXITS ARE
BLOCKED DURING CONSTRUCTION.
PROJECT CODE SUMMARY
PATH "1A"
COMMON
PATH
DISTANCE
ALLOWABLE
COMMON
PATH
ACTUAL
TRAVEL
DISTANCE
ALLOWABLE
TRAVEL
DISTANCE
29' - 5" 100'-0" 35' - 2" 400'-0"
TRAVEL DISTANCES:
OCCUPANT SCHEDULE
Name Area Area Per Occupant
OCCUPANT LOAD
PRESCRIBED CALCULATED
SI - SPECIAL
INDUSTRIAL
5053 SF 10 0
5053 SF 10 0
OCCUPANT LOAD (40.1.7):
• "THE OCCUPANT LOAD, IN NUMBER OF PERSONS FOR WHOM MEANS OF EGRESS AND OTHER
PROVISIONS ARE REQUIRED, SHALL BE DETERMINED ON THE BASIS OF THE OCCUPANT LOAD FACTORS OF TABLE 7.3.1.2 THAT ARE CHARACTERISTIC OF THE USE OF THE SPACE, OR SHALL BE DETERMINED AS
THE MAXIMUM PROBABLE POPULATION OF THE SPACE UNDER CONSIDERATION, WHICHEVER IS
GREATER."
• PER TABLE 7.3.1.2 - NO PRESCRIPTIVE OCCUPANCY CALCULATION BASED ON AREA:
• ASSUMED SPECIAL-PURPOSE INDUSTRIAL OCCUPANCY PER DIRECTION FROM END USER IS NO
GREATER THAN 10 OCCUPANTS.
TRAVEL DISTANCE (40.2.6.1) AND
COMMON PATH OF TRAVEL (40.2.5.1):
INDUSTRIAL (EXISTING):
MAX TRAVEL DISTANCE:
FULLY SPRINKLERED 400' - 0"
MAX COMMON PATH OF TRAVEL:
FULLY SPRINKLERED = 100' - 0"
1/8" = 1'-0"F3 FIRST FLOOR - OCCUPANCY AND EGRESS
OCCUPANCY LEGEND:
OCCUPANTS
PATH "1B"
COMMON
PATH
DISTANCE
ALLOWABLE
COMMON
PATH
ACTUAL
TRAVEL
DISTANCE
ALLOWABLE
TRAVEL
DISTANCE
29' - 5" 100'-0" 126' - 7" 400'-0"
PATH "2A"
COMMON
PATH
DISTANCE
ALLOWABLE
COMMON
PATH
ACTUAL
TRAVEL
DISTANCE
ALLOWABLE
TRAVEL
DISTANCE
47' - 10" 100'-0" 89' - 5" 400'-0"
PATH "2B"
COMMON
PATH
DISTANCE
ALLOWABLE
COMMON
PATH
ACTUAL
TRAVEL
DISTANCE
ALLOWABLE
TRAVEL
DISTANCE
47' - 10" 100'-0" 109' - 2" 400'-0"
T
T
1. BUILDING IS "CRITICAL" OPERATION - SCOPE TO INCLUDE NON LOAD BEARING
WALLS PROTECTED/EXTREME IMPACT RESISTANT SUPPORTING STRUCTURE,
DOORS, FENESTRATION, AND ROOF.
2. STRUCTURES SHALL BE CONSTRUCTED TO WITHSTAND THE PEAK PRESSURES
AND CORRESPONDING IMPULSES PRODUCED BY THE DESIGN LEVEL EXPLOSIVE
THREAT (W2) LOCATED AT THE MINIMUM STANDOFF DISTANCE OF 50 FEET.
STANDOFF DISTANCES PROVIDED IN EXCESS OF 50 FEET MAY NOT BE
ACCOUNTED FOR IN THE CALCULATION OF THE EXTREME IMPACT LOADING
ENVIRONMENT.
3. BUILDING IS TO BE RESTRICTED TO AUTHORIZED PERSONNEL ONLY, AN INTERIOR
W1 SATCHEL CHARGE IS NOT BEING MODELED.
4. SINGLE STORY, AND EXISTING BUILDINGS, ARE EXEMPT FROM PROGRESSIVE
COLLAPSE REQUIREMENTS PER PSRDM.
5. PROVIDE EXTERIOR WALL EXTREME IMPACT PROTECTION AS FOLLOWS:
A. NON-LOAD BEARING WALLS SHALL BE DESIGNED SUCH THAT
THEY HAVE SOME PERMANENT DEFORMATION BUT ARE
GENERALLY REPAIRABLE IN RESPONSE TO THE CALCULATED
PEAK PRESSURES AND IMPULSES RESULTING FROM THE DESIGN
LEVEL THREAT (W1) LOCATED AT THE MINIMUM STANDOFF
DISTANCE OF 50 FEET, BUT NO GREATER THAN GP2.
B. WALLS SHALL SPAN FROM SLAB TO SLAB AND SHALL NOT BE
ATTACHED DIRECTLY TO GRAVITY LOAD BEARING ELEMENTS
C. WALLS SHALL BE ABLE TO ACCEPT THE TRIBUTARY LOADS
TRANSFERRED FROM GLAZED FENESTRATION IN ADDITION TO
THE DESIGN LEVEL EXTREME IMPACT PRESSURES APPLIED
DIRECTLY TO THEIR SURFACE.
6. PROVIDE EXTREME IMPACT RATED DOORS AS FOLLOWS:
A. TYPE "C" EXTREME IMPACT RATED DOUBLE DOORS IN HEAVY
GUAGE (14 GA. MIN.) HOLLOW METAL FRAMES.
B. TYPE "A" EXTREME IMPACT RATED SINGLE DOORS IN HEAVY
GUAGE (14 GA. MIN.) HOLLOW METAL FRAMES.
C. EXTREME IMPACT RATED OVERHEAD DOORS WITH 120 SECOND
AUTOMATIC CLOSURE OPERATION
-OR--
D. STANDARD OVERHEAD DOORS WITH EXTREME IMPACT RATED
CATCHMENT SYSTEM
7. ARM DOORS WITH MAGNETIC LOCKS, DUAL AUTHENTICATION PIV/PIN CODE
ACCESS CONTROLS, AUTO-CLOSERS WITH ANTI-PROP ALARMS AND TIE SYSTEMS
TO SCC
8. WINDOWS WHERE PROVIDED TO BE MINIMAL IN QUANTITY AND CONSTRUCTED OF
EXTREME IMPACT RESISTANT FRAMES AND LAMINATE GLAZING PER PSRDM.
9. PROVIDE PERIMETER LIGHTING IN ACCORDANCE WITH PERFORMANCE
REQUIREMENTS OF SSTV SYSTEM.
10. REFERENCE PHYSICAL SECURITY NARRATIVE FOR ADDITIONAL DETAILS
REGARDING EXTREME IMPACT RESISTANCE
4202 SF
GENERATOR
ROOM
A-202 F4 A-201F4
A-202
C4
C4
A-301
F4
A-301
143 SF
FIRE RISER ROOM
F6
A-304
F3
A-305
F1
A-305
4'
8'
2' - 10" 24' - 9" 24' - 9" 21' - 6" 2' - 10"
100100
A-201
C4
F5
A-305
2'
0"
2'
0"
GENERATOR
GENERATOR
GENERATOR
S W
IT
C
H G
E A
R
S W
IT
C
H G
E A
R
S W
IT
C
H G
E A
R
S W
IT
C
H G
E A
R
S W
IT
C
H G
E A
R
S W
IT
C
H G
E A
R
S W
IT
C
H G
E A
R
S W
IT
C
H G
E A
R
1 2 3 4
A
C
8'
4'
2' - 10" 24' - 9" 24' - 9" 21' - 6" 2' - 10"
101B
D
102B
B
DAY
TANK
PUMP
SET
SKID
FUEL
FILTRATION
SKID
76' - 8"
101A
C
102A
108 108
F
IR
E A
L A
R M
C O
N T
R O
L P
A N
E L
TELEDATA
ENCLOSURE
SECURITY
CABINET
FIRE
EQUIPMENT
CLEARANCE
76' - 8"
5' - 3 5/8" 18' - 0" 6' - 0" 18' - 0" 6' - 0" 18' - 0" 5' - 4 3/8"
2'
0"
2'
0"
0' - 8" 0' - 8"
0'
0'
A-502 C5
5'
15' - 4"101
15' - 3 1/2"
9'
/8
34' - 4"
6' - 0" 6' - 0"
593 SF
SWITCHGEAR ROOM
A
B
135135
F1
A-301
103103
DAY
TANK
DAY
TANK
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ENGINEER OF RECORD
321 4 5 6 7 8 9 10
NO. DESCRIPTION DATE
PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE
WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE
PROFESSIONAL ENGINEER
o n e e ig h th i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e i n c h o n e f o o t o n e a n d o n e h a lf i n c h e s o n e f o o t th re e i n c h e s o n e f o o t
OCULUS INCORPORATED
ARCHITECT OF RECORD
MR PROJECT NO: 0499-0162
NORTHKEYPLAN
CONSULTANTS
Civil / Site Utility Engineering:
IMEG, CORP.
Fire & Life Safety:
STANTON ENGINEERING SERVICES, LLC
Hazardous Materials:
MABBETT & ASSOCIATES, INC.
Architectural:
OCULUS, INC.
Structural:
PROFESSIONAL ENGINEERING
CONSULTANTS, PA (PEC)
BUILDING 37
AREA OF WORK
O C
U L U
S P
R O
JE
C
T N
O
A u to d e sk D o cs
/W ic h ita
C e n tr a liz e d
E m e rg e n cy P o w e r/
-1
-K
S
W ic h ita V
A M
C
O C
U L
U S
A C
C C
E N
T R
A L .r vt
/2
/2
:5
:1
P
M
A-111
CONSTRUCT CENTRALIZED
EMERGENCY POWER SYSTEM
ROBERT J. DOLE VA MEDICAL CENTER
WICHITA, KANSAS
589A7-21-132
Project Director
2026-03-26 RAF MMT
BID DOCUMENTS
FULLY SPRINKLERED
FLOOR PLAN
ARCHITECTURAL
-K
S
GENERAL NOTES
KEYED NOTES
100 CONCRETE FLOOR; RE: STRUCTURAL
101 PIPE TRENCH WITH GALV. STL. GRATE COVERS, RE: STRUCT.
103 THREE-SIDED SECURITY ENCLOSURE, 8'-6" HT x X'-X" WD. x X'-X" DP. PROVIDE 3'-0" x 7'-0" SWINGING DOOR. SECURE ASSEMBLIES TO WALLS AND FLOOR PER
MANUF. RECOMMENDATION.
106 12" CMU WALL WITH FACE BRICK TO MATCH EXISTING SITE STANDARD. RE:
WALL SECTIONS, RE: STRUCTURAL
108 EXTREME IMPACT-RATED EXTERIOR OHD. RE DOOR SCHEDULE
135 FUEL LINE TRENCH/PIPE ENTRY.
136 STEAM LINE TRENCH/PIPE ENTRY.
155 ROOF ACCESS LADDER, SUPPORT FROM WALL/STRUCT. ABOVE.
1/4" = 1'-0"F3 GROUND FLOOR
1. BUILDING IS "CRITICAL" OPERATION - SCOPE TO INCLUDE NON LOAD BEARING
WALLS PROTECTED/EXTREME IMPACT RESISTANT SUPPORTING STRUCTURE,
DOORS, FENESTRATION, AND ROOF.
2. STRUCTURES SHALL BE CONSTRUCTED TO WITHSTAND THE PEAK PRESSURES
AND CORRESPONDING IMPULSES PRODUCED BY THE DESIGN LEVEL EXPLOSIVE
THREAT (W2) LOCATED AT THE MINIMUM STANDOFF DISTANCE OF 50 FEET.
STANDOFF DISTANCES PROVIDED IN EXCESS OF 50 FEET MAY NOT BE
ACCOUNTED FOR IN THE CALCULATION OF THE EXTREME IMPACT LOADING
ENVIRONMENT.
3. BUILDING IS TO BE RESTRICTED TO AUTHORIZED PERSONNEL ONLY, AN INTERIOR
W1 SATCHEL CHARGE IS NOT BEING MODELED.
4. SINGLE STORY, AND EXISTING BUILDINGS, ARE EXEMPT FROM PROGRESSIVE
COLLAPSE REQUIREMENTS PER PSRDM.
5. PROVIDE EXTERIOR WALL EXTREME IMPACT PROTECTION AS FOLLOWS:
A. NON-LOAD BEARING WALLS SHALL BE DESIGNED SUCH THAT
THEY HAVE SOME PERMANENT DEFORMATION BUT ARE
GENERALLY REPAIRABLE IN RESPONSE TO THE CALCULATED
PEAK PRESSURES AND IMPULSES RESULTING FROM THE DESIGN
LEVEL THREAT (W1) LOCATED AT THE MINIMUM STANDOFF
DISTANCE OF 50 FEET, BUT NO GREATER THAN GP2.
B. WALLS SHALL SPAN FROM SLAB TO SLAB AND SHALL NOT BE
ATTACHED DIRECTLY TO GRAVITY LOAD BEARING ELEMENTS
C. WALLS SHALL BE ABLE TO ACCEPT THE TRIBUTARY LOADS
TRANSFERRED FROM GLAZED FENESTRATION IN ADDITION TO
THE DESIGN LEVEL EXTREME IMPACT PRESSURES APPLIED
DIRECTLY TO THEIR SURFACE.
6. PROVIDE EXTREME IMPACT RATED DOORS AS FOLLOWS:
A. TYPE "C" EXTREME IMPACT RATED DOUBLE DOORS IN HEAVY
GUAGE (14 GA. MIN.) HOLLOW METAL FRAMES.
B. TYPE "A" EXTREME IMPACT RATED SINGLE DOORS IN HEAVY
GUAGE (14 GA. MIN.) HOLLOW METAL FRAMES.
C. EXTREME IMPACT RATED OVERHEAD DOORS WITH 120 SECOND
AUTOMATIC CLOSURE OPERATION
-OR--
D. STANDARD OVERHEAD DOORS WITH EXTREME IMPACT RATED
CATCHMENT SYSTEM
7. ARM DOORS WITH MAGNETIC LOCKS, DUAL AUTHENTICATION PIV/PIN CODE
ACCESS CONTROLS, AUTO-CLOSERS WITH ANTI-PROP ALARMS AND TIE SYSTEMS
TO SCC
8. WINDOWS WHERE PROVIDED TO BE MINIMAL IN QUANTITY AND CONSTRUCTED OF
EXTREME IMPACT RESISTANT FRAMES AND LAMINATE GLAZING PER PSRDM.
9. PROVIDE PERIMETER LIGHTING IN ACCORDANCE WITH PERFORMANCE
REQUIREMENTS OF SSTV SYSTEM.
10. REFERENCE PHYSICAL SECURITY NARRATIVE FOR ADDITIONAL DETAILS
REGARDING EXTREME IMPACT RESISTANCE
C4
A-301
F4
A-301
F6
A-304
F3
A-305
F1
A-305
F5
A-305
1 2 3 4
A
C
B
F1
A-301
787 SF
EQUIPMENT ACCESS
12'-4"
23' - 8 3/8" 34' - 4" 15' - 4 3/8"
8'
6'
/2
1'
/8
6' - 1 1/2" 16' - 2" 7' - 9 1/4" 6' - 1 1/2"
7'
12'-4"
12'-4"
20' - 4" 4' - 0" 10' - 0"
2' - 10" 24' - 9" 24' - 9" 21' - 6" 2' - 10"
5' - 3 5/8" 18' - 0" 6' - 0" 18' - 0" 6' - 0" 18' - 0" 5' - 4 3/8"
76' - 8"
1'
0"
3'
4'
3'
3'
4'
3'
4'
3'
4'
3'
5'
0"
2'
0"
2'
0"
3' - 10" 3' - 4" 3' - 4" 3' - 4" 3' - 4" 3' - 4" 4' - 3" 1' - 9" 3' - 4" 4' - 0" 3' - 4" 4' - 0" 3' - 4" 5' - 0" 1' - 0" 3' - 4" 3' - 4" 3' - 4" 3' - 4" 3' - 4" 3' - 10"
2' - 10" 24' - 9" 24' - 9" 21' - 6" 2' - 10"
76' - 8"
3'
4'
3'
4'
3'
4'
3'
5'
0"
2'
0"
2'
0"
3'
0"
3'
3'
3'
144144
145145
145145
149149 149
154154154 154154154154154
155156
D
D
D
D D
D
D
D
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ENGINEER OF RECORD
321 4 5 6 7 8 9 10
NO. DESCRIPTION DATE
PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE
WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE
PROFESSIONAL ENGINEER
o n e e ig h th i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e i n c h o n e f o o t o n e a n d o n e h a lf i n c h e s o n e f o o t th re e i n c h e s o n e f o o t
OCULUS INCORPORATED
ARCHITECT OF RECORD
MR PROJECT NO: 0499-0162
NORTHKEYPLAN
CONSULTANTS
Civil / Site Utility Engineering:
IMEG, CORP.
Fire & Life Safety:
STANTON ENGINEERING SERVICES, LLC
Hazardous Materials:
MABBETT & ASSOCIATES, INC.
Architectural:
OCULUS, INC.
Structural:
PROFESSIONAL ENGINEERING
CONSULTANTS, PA (PEC)
BUILDING 37
AREA OF WORK
O C
U L U
S P
R O
JE
C
T N
O
A u to d e sk D o cs
/W ic h ita
C e n tr a liz e d
E m e rg e n cy P o w e r/
-1
-K
S
W ic h ita V
A M
C
O C
U L
U S
A C
C C
E N
T R
A L .r vt
/2
/2
:5
:1
P
M
A-112
CONSTRUCT CENTRALIZED
EMERGENCY POWER SYSTEM
ROBERT J. DOLE VA MEDICAL CENTER
WICHITA, KANSAS
589A7-21-132
Project Director
2026-03-26 RAF MMT
BID DOCUMENTS
FULLY SPRINKLERED
FLOOR PLAN
ARCHITECTURAL
-K
S
GENERAL NOTES
KEYED NOTES
1/4" = 1'-0"F3 CATWALK LEVEL
144 LIGHTWEIGHT CONC. DECK AT EQUIP. ACCESS PLATFORM. RE STRUCT. FOR
DETAILS.
145 EQUIPMENT ACCESS CATWALK. REFER TO STRUCTURAL FOR FRAMING /
DETAILS.
146 MATCH ELEVATION TO TOP OF DECK (+/- 3/8") MAX.
147 42" UTILITY GUARDRAIL AND KICKPLATE AT PLATFORM/CATWALK PERIMETER -
RE: STRUCT. FOR ATTACHMENT DETAILS.
148 BREAK RAIL AT STRUCTURAL SUPPORT VERTICALS, MAX 2" GAP TO STRUCT.
STEEL.
149 PROVIDE GUARDRAIL SECTIONS AT CATWALK BETWEEN LOUVERS/DAMPERS
154 INTAKE LOUVER / DAMPER ASSEMBLY (TYP. 13 LOCATIONS, RE: MECH.)
155 ROOF ACCESS LADDER, SUPPORT FROM WALL/STRUCT. ABOVE.
156 SPRINKLER PIPING ABOVE, REFER TO FIRE SUPRESSION DRAWING.
1. BUILDING IS "CRITICAL" OPERATION - SCOPE TO INCLUDE NON LOAD BEARING
WALLS PROTECTED/EXTREME IMPACT RESISTANT SUPPORTING STRUCTURE,
DOORS, FENESTRATION, AND ROOF.
2. STRUCTURES SHALL BE CONSTRUCTED TO WITHSTAND THE PEAK PRESSURES
AND CORRESPONDING IMPULSES PRODUCED BY THE DESIGN LEVEL EXPLOSIVE
THREAT (W2) LOCATED AT THE MINIMUM STANDOFF DISTANCE OF 50 FEET.
STANDOFF DISTANCES PROVIDED IN EXCESS OF 50 FEET MAY NOT BE
ACCOUNTED FOR IN THE CALCULATION OF THE EXTREME IMPACT LOADING
ENVIRONMENT.
3. BUILDING IS TO BE RESTRICTED TO AUTHORIZED PERSONNEL ONLY, AN INTERIOR
W1 SATCHEL CHARGE IS NOT BEING MODELED.
4. SINGLE STORY, AND EXISTING BUILDINGS, ARE EXEMPT FROM PROGRESSIVE
COLLAPSE REQUIREMENTS PER PSRDM.
5. PROVIDE EXTERIOR WALL EXTREME IMPACT PROTECTION AS FOLLOWS:
A. NON-LOAD BEARING WALLS SHALL BE DESIGNED SUCH THAT
THEY HAVE SOME PERMANENT DEFORMATION BUT ARE
GENERALLY REPAIRABLE IN RESPONSE TO THE CALCULATED
PEAK PRESSURES AND IMPULSES RESULTING FROM THE DESIGN
LEVEL THREAT (W1) LOCATED AT THE MINIMUM STANDOFF
DISTANCE OF 50 FEET, BUT NO GREATER THAN GP2.
B. WALLS SHALL SPAN FROM SLAB TO SLAB AND SHALL NOT BE
ATTACHED DIRECTLY TO GRAVITY LOAD BEARING ELEMENTS
C. WALLS SHALL BE ABLE TO ACCEPT THE TRIBUTARY LOADS
TRANSFERRED FROM GLAZED FENESTRATION IN ADDITION TO
THE DESIGN LEVEL EXTREME IMPACT PRESSURES APPLIED
DIRECTLY TO THEIR SURFACE.
6. PROVIDE EXTREME IMPACT RATED DOORS AS FOLLOWS:
A. TYPE "C" EXTREME IMPACT RATED DOUBLE DOORS IN HEAVY
GUAGE (14 GA. MIN.) HOLLOW METAL FRAMES.
B. TYPE "A" EXTREME IMPACT RATED SINGLE DOORS IN HEAVY
GUAGE (14 GA. MIN.) HOLLOW METAL FRAMES.
C. EXTREME IMPACT RATED OVERHEAD DOORS WITH 120 SECOND
AUTOMATIC CLOSURE OPERATION
-OR--
D. STANDARD OVERHEAD DOORS WITH EXTREME IMPACT RATED
CATCHMENT SYSTEM
7. ARM DOORS WITH MAGNETIC LOCKS, DUAL AUTHENTICATION PIV/PIN CODE
ACCESS CONTROLS, AUTO-CLOSERS WITH ANTI-PROP ALARMS AND TIE SYSTEMS
TO SCC
8. WINDOWS WHERE PROVIDED TO BE MINIMAL IN QUANTITY AND CONSTRUCTED OF
EXTREME IMPACT RESISTANT FRAMES AND LAMINATE GLAZING PER PSRDM.
9. PROVIDE PERIMETER LIGHTING IN ACCORDANCE WITH PERFORMANCE
REQUIREMENTS OF SSTV SYSTEM.
10. REFERENCE PHYSICAL SECURITY NARRATIVE FOR ADDITIONAL DETAILS
REGARDING EXTREME IMPACT RESISTANCE
A-202 F4 A-201F4
A-202
C4
C4
A-301
F4
A-301
F6
A-304
F3
A-305
F1
A-305
A-201
C4
F5
A-305
1 2 3 4
A
C
2'
0"
2'
0"
2' - 10" 24' - 9" 24' - 9" 21' - 6" 2' - 10"
B
/4
105 153153153
153 153 153
122 122 122
76' - 8"
/2
202202
202 202
1/ 2"
1/2" / 12" 1/ 2"
1/2" / 12"
F1
A-301
/2
" 1
/2 " / 1
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ENGINEER OF RECORD
321 4 5 6 7 8 9 10
NO. DESCRIPTION DATE
PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE
WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE
PROFESSIONAL ENGINEER
o n e e ig h th i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e i n c h o n e f o o t o n e a n d o n e h a lf i n c h e s o n e f o o t th re e i n c h e s o n e f o o t
OCULUS INCORPORATED
ARCHITECT OF RECORD
MR PROJECT NO: 0499-0162
NORTHKEYPLAN
CONSULTANTS
Civil / Site Utility Engineering:
IMEG, CORP.
Fire & Life Safety:
STANTON ENGINEERING SERVICES, LLC
Hazardous Materials:
MABBETT & ASSOCIATES, INC.
Architectural:
OCULUS, INC.
Structural:
PROFESSIONAL ENGINEERING
CONSULTANTS, PA (PEC)
BUILDING 37
AREA OF WORK
O C
U L U
S P
R O
JE
C
T N
O
A u to d e sk D o cs
/W ic h ita
C e n tr a liz e d
E m e rg e n cy P o w e r/
-1
-K
S
W ic h ita V
A M
C
O C
U L
U S
A C
C C
E N
T R
A L .r vt
/2
/2
:5
:1
P
M
A-114
CONSTRUCT CENTRALIZED
EMERGENCY POWER SYSTEM
ROBERT J. DOLE VA MEDICAL CENTER
WICHITA, KANSAS
589A7-21-132
Project Director
2026-03-26 RAF MMT
BID DOCUMENTS
FULLY SPRINKLERED
ROOF PLAN
ARCHITECTURAL
-K
S
GENERAL NOTES
KEYED NOTES
1/4" = 1'-0"F3 ROOF PLAN
105 ROOF HATCH; REF. PREMANUF. CURB DETAILS (A-503)
120 WHITE TPO MEMBRANE ROOF - REF. SPECIFICATIONS
122 NEW ROOF VENTILATION HOOD; REF. MECHANICAL
126 NEW EXHAUST FAN. RE: MECHANICAL.
127 NEW CONDENSING UNIT, RE: MECHANICAL.
152 TIE-DOWN ROOF ANCHOR; REF. STRUCTURAL
153 MEMBRANE WALKWAY PADS. PROVIDE SLIP RESISTANT SURFACE. FINAL
LOCATION TO BE COORDINATED WITH FINAL EQUIPMENT LOCATION
202 PRE-FINISHED STAINLESS STEEL CONDUCTOR HEAD AND DOWNSPOUT
208 MANUF. CAST STONE COPING
T
T
1 2 3 4
A
C
B
1.07.011.07.01
1.07.01
1.07.011.07.01
1.06
11.04 11.04
20.00 20.00
11.04
20.00
1.02
1.02
01.XX 01.XX
01.XX 01.XX
01.21 01.21
01.21 01.21
4202 SF
GENERATOR ROOM
CMU/P-1
N/A
C-1
593 SF
SWITCHGEAR ROOM
CMU/P-1
N/A
C-1
143 SF
FIRE RISER ROOM
CMU/P-1
N/A
C-1
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ENGINEER OF RECORD
321 4 5 6 7 8 9 10
NO. DESCRIPTION DATE
PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE
WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE
PROFESSIONAL ENGINEER
o n e e ig h th i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e i n c h o n e f o o t o n e a n d o n e h a lf i n c h e s o n e f o o t th re e i n c h e s o n e f o o t
OCULUS INCORPORATED
ARCHITECT OF RECORD
MR PROJECT NO: 0499-0162
NORTHKEYPLAN
CONSULTANTS
Civil / Site Utility Engineering:
IMEG, CORP.
Fire & Life Safety:
STANTON ENGINEERING SERVICES, LLC
Hazardous Materials:
MABBETT & ASSOCIATES, INC.
Architectural:
OCULUS, INC.
Structural:
PROFESSIONAL ENGINEERING
CONSULTANTS, PA (PEC)
BUILDING 37
AREA OF WORK
O C
U L U
S P
R O
JE
C
T N
O
A u to d e sk D o cs
/W ic h ita
C e n tr a liz e d
E m e rg e n cy P o w e r/
-1
-K
S
W ic h ita V
A M
C
O C
U L
U S
A C
C C
E N
T R
A L .r vt
/2
/2
:5
:3
P
M
AI111
CONSTRUCT CENTRALIZED
EMERGENCY POWER SYSTEM
ROBERT J. DOLE VA MEDICAL CENTER
WICHITA, KANSAS
589A7-21-132
Project Director
2026-03-26 RAF MMT
BID DOCUMENTS
FULLY SPRINKLERED
INTERIORS
ARCHITECTURAL
FLOOR PLAN
-K
S
GENERAL NOTES
1/4" = 1'-0"F3 GROUND FLOOR SIGNAGE/FINISHES PLAN
1. REFER TO SHEET AF-601 FOR SIGNAGE TYPES AND SCHEDULE.
2. REFER TO PROJECT GENERAL NOTES.
3. REFER TO SPECIFICATIONS, FINISH LEGEND, AND FINISH PLAN FOR ADDITIONAL
FINISH INFORMATION.
4. EXAMINE AND CONFIRM ALL SUBSTRATE CONDITIONS WHERE NEW MATERIALS
ARE APPLIED. SUBSTRATE SHALL BE SMOOTH, FREE OF DEFECTS AND SHALL
CONFORM TO THE REQUIREMENTS OF THE FINISHED MATERIAL
MANUFACTURERS’ RECOMMENDATIONS.
5. ADHERE TO MANUFACTURE'S SPECIFICATION FOR INSTALLATION INSTRUCTIONS
ON ALL SPECIFIED FINISHES.
1 2 3 4
A
C
B
01.YY
01.YY
01.YY
01.YY
787 SF
EQUIPMENT ACCESS
CMU/P-1
N/A
C-1
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ENGINEER OF RECORD
321 4 5 6 7 8 9 10
NO. DESCRIPTION DATE
PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE
WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE
PROFESSIONAL ENGINEER
o n e e ig h th i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e i n c h o n e f o o t o n e a n d o n e h a lf i n c h e s o n e f o o t th re e i n c h e s o n e f o o t
OCULUS INCORPORATED
ARCHITECT OF RECORD
MR PROJECT NO: 0499-0162
NORTHKEYPLAN
CONSULTANTS
Civil / Site Utility Engineering:
IMEG, CORP.
Fire & Life Safety:
STANTON ENGINEERING SERVICES, LLC
Hazardous Materials:
MABBETT & ASSOCIATES, INC.
Architectural:
OCULUS, INC.
Structural:
PROFESSIONAL ENGINEERING
CONSULTANTS, PA (PEC)
BUILDING 37
AREA OF WORK
O C
U L U
S P
R O
JE
C
T N
O
A u to d e sk D o cs
/W ic h ita
C e n tr a liz e d
E m e rg e n cy P o w e r/
-1
-K
S
W ic h ita V
A M
C
O C
U L
U S
A C
C C
E N
T R
A L .r vt
/2
/2
:5
:3
P
M
AI112
CONSTRUCT CENTRALIZED
EMERGENCY POWER SYSTEM
ROBERT J. DOLE VA MEDICAL CENTER
WICHITA, KANSAS
589A7-21-132
Project Director
2026-03-26 RAF MMT
BID DOCUMENTS
FULLY SPRINKLERED
INTERIORS
ARCHITECTURAL
FLOOR PLAN
-K
S
GENERAL NOTES
1. REFER TO SHEET AF-601 FOR SIGNAGE TYPES AND SCHEDULE.
2. REFER TO PROJECT GENERAL NOTES.
3. REFER TO SPECIFICATIONS, FINISH LEGEND, AND FINISH PLAN FOR ADDITIONAL
FINISH INFORMATION.
4. EXAMINE AND CONFIRM ALL SUBSTRATE CONDITIONS WHERE NEW MATERIALS
ARE APPLIED. SUBSTRATE SHALL BE SMOOTH, FREE OF DEFECTS AND SHALL
CONFORM TO THE REQUIREMENTS OF THE FINISHED MATERIAL
MANUFACTURERS’ RECOMMENDATIONS.
5. ADHERE TO MANUFACTURE'S SPECIFICATION FOR INSTALLATION INSTRUCTIONS
ON ALL SPECIFIED FINISHES.
1/4" = 1'-0"F3 CATWALK LEVEL SIGNAGE/FINISHES PLAN
GROUND FLOOR
0"
C4
A-301
F1
A-305
ROOF
19'-6"
AC B
TOP OF BOND BEAM
24'-0"
D D D D
101C102A 101A
209209
209209
110110
CATWALK LEVEL
12'-4"
216216 216216 216216
GROUND FLOOR
0"
F4
A-301
F5
A-305
ROOF
19'-6"
1 2 3 4
TOP OF BOND BEAM
24'-0"
110 110 110 110 110 110 110 110 110
209209
209209
215 215
215 215
122 122 122
CATWALK LEVEL
12'-4"
F1
A-301
216216 216216 216216 216216 216216 216216
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ENGINEER OF RECORD
321 4 5 6 7 8 9 10
NO. DESCRIPTION DATE
PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE
WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE
PROFESSIONAL ENGINEER
o n e e ig h th i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e i n c h o n e f o o t o n e a n d o n e h a lf i n c h e s o n e f o o t th re e i n c h e s o n e f o o t
OCULUS INCORPORATED
ARCHITECT OF RECORD
MR PROJECT NO: 0499-0162
CONSULTANTS
Civil / Site Utility Engineering:
IMEG, CORP.
Fire & Life Safety:
STANTON ENGINEERING SERVICES, LLC
Hazardous Materials:
MABBETT & ASSOCIATES, INC.
Architectural:
OCULUS, INC.
Structural:
PROFESSIONAL ENGINEERING
CONSULTANTS, PA (PEC)
O C
U L U
S P
R O
JE
C
T N
O
A u to d e sk D o cs
/W ic h ita
C e n tr a liz e d
E m e rg e n cy P o w e r/
-1
-K
S
W ic h ita V
A M
C
O C
U L
U S
A C
C C
E N
T R
A L .r vt
/2
/2
:5
:1
P
M
A-201
CONSTRUCT CENTRALIZED
EMERGENCY POWER SYSTEM
ROBERT J. DOLE VA MEDICAL CENTER
WICHITA, KANSAS
589A7-21-132
Project Director
2026-03-26 RAF MMT
BID DOCUMENTS
FULLY SPRINKLERED
EXTERIOR ELEVATIONS
ARCHITECTURAL
-K
S
KEYED NOTES
108 EXTREME IMPACT-RATED EXTERIOR OHD. RE DOOR SCHEDULE
110 EXTREME IMPACT-RATED LOUVER.
122 NEW ROOF VENTILATION HOOD; REF. MECHANICAL
125 GENERATOR EXHAUST STACK, RE: MECHANICAL.
208 MANUF. CAST STONE COPING
209 FACE BRICK-MATCH EXISTING SITE STANDARD.
215 MASONRY CONTROL JOINT WITH BACKER ROD. COLOR TO
MATCH MASONRY, REF. STRUCTURAL
216 CONTINUE MASONRY CONTROL JOINT THRU CAST STONE
DATUM BAND AND CAP STONE.
224 GRADE LINE; REF. CIVIL DWGS
229 MANUF. CAST STONE BAND
230 NEW LIGHT FIXTURE; REF. ELEC. DWGS
237 GENERATOR TAP BOX, RE: ELECT.
1/4" = 1'-0"F4 EAST ELEVATION
1/4" = 1'-0"C4 SOUTH ELEVATION1
F4
A-301
F6
A-304
ROOF
19'-6"
TOP OF BOND BEAM
24'-0"
209209
215 215 215 215 215 215
110 110 110
CATWALK LEVEL
12'-4"
125 125 125
216216 216216 216216 216216 216216 216216
GROUND FLOOR
0"
C4
A-301
F3
A-305
ROOF
19'-6"
A CB
TOP OF BOND BEAM
24'-0"
F1
A-305
D D D D
101B 101D
209209
209209
215 215 215
110 110
CATWALK LEVEL
12'-4"
216216 216216 216216
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ENGINEER OF RECORD
321 4 5 6 7 8 9 10
NO. DESCRIPTION DATE
PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE
WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE
PROFESSIONAL ENGINEER
o n e e ig h th i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e i n c h o n e f o o t o n e a n d o n e h a lf i n c h e s o n e f o o t th re e i n c h e s o n e f o o t
OCULUS INCORPORATED
ARCHITECT OF RECORD
MR PROJECT NO: 0499-0162
CONSULTANTS
Civil / Site Utility Engineering:
IMEG, CORP.
Fire & Life Safety:
STANTON ENGINEERING SERVICES, LLC
Hazardous Materials:
MABBETT & ASSOCIATES, INC.
Architectural:
OCULUS, INC.
Structural:
PROFESSIONAL ENGINEERING
CONSULTANTS, PA (PEC)
O C
U L U
S P
R O
JE
C
T N
O
A u to d e sk D o cs
/W ic h ita
C e n tr a liz e d
E m e rg e n cy P o w e r/
-1
-K
S
W ic h ita V
A M
C
O C
U L
U S
A C
C C
E N
T R
A L .r vt
/2
/2
:5
:2
P
M
A-202
CONSTRUCT CENTRALIZED
EMERGENCY POWER SYSTEM
ROBERT J. DOLE VA MEDICAL CENTER
WICHITA, KANSAS
589A7-21-132
Project Director
2026-03-26 RAF MMT
BID DOCUMENTS
FULLY SPRINKLERED
EXTERIOR ELEVATIONS
ARCHITECTURAL
-K
S
KEYED NOTES
108 EXTREME IMPACT-RATED EXTERIOR OHD. RE DOOR SCHEDULE
110 EXTREME IMPACT-RATED LOUVER.
122 NEW ROOF VENTILATION HOOD; REF. MECHANICAL
125 GENERATOR EXHAUST STACK, RE: MECHANICAL.
126 NEW EXHAUST FAN. RE: MECHANICAL.
208 MANUF. CAST STONE COPING
209 FACE BRICK-MATCH EXISTING SITE STANDARD.
215 MASONRY CONTROL JOINT WITH BACKER ROD. COLOR TO
MATCH MASONRY, REF. STRUCTURAL
216 CONTINUE MASONRY CONTROL JOINT THRU CAST STONE
DATUM BAND AND CAP STONE.
224 GRADE LINE; REF. CIVIL DWGS
229 MANUF. CAST STONE BAND
230 NEW LIGHT FIXTURE; REF. ELEC. DWGS
1/4" = 1'-0"C4 NORTH ELEVATION
1/4" = 1'-0"F4 WEST ELEVATION
F4
A-301
4202 SF
GENERATOR ROOM
CMU/P-1
N/A
C-1
A-304 F4
F5
A-305
ROOF
19'-6"
TOP OF BOND BEAM
24'-0"
A-304 F4
SIM.
SECURITY
CABINET
TELEDATA
ENCLOSURE
DAY
TANK
FUEL
FILTRATION
SKID
PUMP
SET
SKID
CATWALK LEVEL
12'-4"
F1
A-301
C4
A-301
4202 SF
GENERATOR ROOM
CMU/P-1
N/A
C-1
143 SF
FIRE RISER ROOM
CMU/P-1
N/A
C-1
A-303 F6
F3
A-305 AC
GENERATOR
A-303 F4
B
FIRE
EQUIPMENT
CLEARANCE
B
GROUND FLOOR
0"
ROOF
19'-6"
C
TOP OF BOND BEAM
24'-0"
CATWALK LEVEL
12'-4"
B
593 SF
SWITCHGEAR ROOM
CMU/P-1
N/A
C-14202 SF
GENERATOR ROOM
CMU/P-1
N/A
C-1 1 C
A-503 F5
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ENGINEER OF RECORD
321 4 5 6 7 8 9 10
NO. DESCRIPTION DATE
PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE
WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE
PROFESSIONAL ENGINEER
o n e e ig h th i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e i n c h o n e f o o t o n e a n d o n e h a lf i n c h e s o n e f o o t th re e i n c h e s o n e f o o t
OCULUS INCORPORATED
ARCHITECT OF RECORD
MR PROJECT NO: 0499-0162
CONSULTANTS
Civil / Site Utility Engineering:
IMEG, CORP.
Fire & Life Safety:
STANTON ENGINEERING SERVICES, LLC
Hazardous Materials:
MABBETT & ASSOCIATES, INC.
Architectural:
OCULUS, INC.
Structural:
PROFESSIONAL ENGINEERING
CONSULTANTS, PA (PEC)
O C
U L U
S P
R O
JE
C
T N
O
A u to d e sk D o cs
/W ic h ita
C e n tr a liz e d
E m e rg e n cy P o w e r/
-1
-K
S
W ic h ita V
A M
C
O C
U L
U S
A C
C C
E N
T R
A L .r vt
/2
/2
:5
:2
P
M
A-301
CONSTRUCT CENTRALIZED
EMERGENCY POWER SYSTEM
ROBERT J. DOLE VA MEDICAL CENTER
WICHITA, KANSAS
589A7-21-132
Project Director
2026-03-26 RAF MMT
BID DOCUMENTS
FULLY SPRINKLERED
BUILDING SECTIONS
ARCHITECTURAL
-K
S
1/4" = 1'-0"C4 BUILDING SECTION
KEYED NOTES
1/4" = 1'-0"F4 BUILDING SECTION
102 2 HOUR RATED CMU WALL ASSEMBLY - UL U906.
103 THREE-SIDED SECURITY ENCLOSURE, 8'-6" HT x X'-X" WD. x X'-X" DP. PROVIDE 3'-0" x 7'-0" SWINGING DOOR. SECURE ASSEMBLIES TO WALLS AND FLOOR PER
MANUF. RECOMMENDATION.
104 2 HOUR RATED FLOOR CEILING ASSEMBLY - UL D907
1/4" = 1'-0"F1 SWITCHGEAR ROOM SECTION
CONCRETE GRADE BEAM.
RE STRUCTURAL
PROTECTION BOARD AND DRAINAGE MAT
PERF PERIMETER DRAIN TILE. RE CIVIL
GROUT CAVITY SOLID MIN . 12"
ABOVE FINISH GRADE.
GENERATOR EXHAUST LOUVER.
RE: MECH
ROOF
19'-6"
A
TOP OF BOND BEAM
24'-0"
CAST STONE PARAPET CAP
ROOF SYSTEM: FULLY-ADHERED TPO
MEMBRANE ON ROOF COVERBOARD WITH
RIGID INSULATION OVER CONC. FILLED
METAL ROOF DECK
STEEL FRAMING. RE STRUCTURAL
CAST-STONE BAND
4'
1'
MASONRY TIES @ 24" OC VERT
SOLDIER COURSE BRICK AT HEAD
BOND BEAM AT HEAD. RE STRUCTURAL
STEEL LINTEL. RE STRUCTURAL
12" EXTREME IMPACT-RATED CMU
EXTERIOR WALL. RE STRUCTURAL
FACE BRICK - MATCH SITE STANDARD
COURSEWORK AND COLOR
R-13 C.I. IN 4 3/8" CAVITY
2'
2'
CAST STONE SILL. REF. DTL.
F9/A-701
2' - 10"
1' - 2 3/8" 1' - 7 5/8"
A-501 C7
A-502 B1
A-502 D1
A-501 F7
CATWALK LEVEL
12'-4"
GROUND FLOOR
0"
C
TOP OF BOND BEAM
24'-0"
CONCRETE GRADE BEAM. RE
STRUCTURAL
PROTECTION BOARD AND
DRAINAGE MAT
PERF PERIMETER DRAIN TILE. RE CIVIL
GROUT CAVITY SOLID MIN .
12" ABOVE FINISH GRADE.
CAST STONE PARAPET CAP
ROOF SYSTEM: FULLY-ADHERED TPO
MEMBRANE ON ROOF COVERBOARD WITH
RIGID INSULATION OVER CONC. FILLED
METAL ROOF DECK
CAST-STONE BAND
12" EXTREME IMPACT-RATED CMU
EXTERIOR WALL. RE STRUCTURAL
MASONRY TIES @ 16" OC VERT
FACE BRICK - MATCH SITE STANDARD
COURSEWORK AND COLOR
R-13 C.I. IN 4 3/8" CAVITY
4'
3'
1'
5'
1' - 7 5/8" 1' - 2 3/8"
A-501 F7
Sim
A-502 F5
CONCRETE PIER BEYOND
CONC. SLAB RE: STRUCT.
CATWALK LEVEL
12'-4"
2' - 10"
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ENGINEER OF RECORD
321 4 5 6 7 8 9 10
NO. DESCRIPTION DATE
PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE
WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE
PROFESSIONAL ENGINEER
o n e e ig h th i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e i n c h o n e f o o t o n e a n d o n e h a lf i n c h e s o n e f o o t th re e i n c h e s o n e f o o t
OCULUS INCORPORATED
ARCHITECT OF RECORD
MR PROJECT NO: 0499-0162
CONSULTANTS
Civil / Site Utility Engineering:
IMEG, CORP.
Fire & Life Safety:
STANTON ENGINEERING SERVICES, LLC
Hazardous Materials:
MABBETT & ASSOCIATES, INC.
Architectural:
OCULUS, INC.
Structural:
PROFESSIONAL ENGINEERING
CONSULTANTS, PA (PEC)
O C
U L U
S P
R O
JE
C
T N
O
A u to d e sk D o cs
/W ic h ita
C e n tr a liz e d
E m e rg e n cy P o w e r/
-1
-K
S
W ic h ita V
A M
C
O C
U L
U S
A C
C C
E N
T R
A L .r vt
/2
/2
:5
:2
P
M
A-303
CONSTRUCT CENTRALIZED
EMERGENCY POWER SYSTEM
ROBERT J. DOLE VA MEDICAL CENTER
WICHITA, KANSAS
589A7-21-132
Project Director
2026-03-26 RAF MMT
BID DOCUMENTS
FULLY SPRINKLERED
WALL SECTIONS
ARCHITECTURAL
-K
S
1/2" = 1'-0"F6 WALL SECTION
1/2" = 1'-0"F4 WALL SECTION
4'
EXTREME IMPACT RATED OVERHEAD
DOOR.
EXTERIOR PAVING. SLOPE AWAY FROM
BUILDING. RE CIVIL
FIBEROUS EXPANSION JOINT FILLER
CONCRETE GRADE BEAM.
RE STRUCTURAL
FLUID APPLIED WATERPROOFING
PROTECTION BOARD AND DRAINAGE MAT
PERF PERIMETER DRAIN TILE. RE CIVIL
SOLDIER COURSE BRICK AT DOOR HEAD
BOND BEAM AT HEAD. RE STRUCTURAL
STEEL LINTEL. RE STRUCTURAL
TOP OF BOND BEAM
24'-0"
MASONRY TIES @ 24" OC VERT
FACE BRICK - MATCH SITE STANDARD
COURSEWORK AND COLOR
12" EXTREME IMPACT-RATED CMU
EXTERIOR WALL. RE STRUCTURAL
ROOF SYSTEM: FULLY-ADHERED TPO
MEMBRANE ON ROOF COVERBOARD WITH
RIGID INSULATION OVER CONC. FILLED
METAL ROOF DECK
R-13 C.I. IN 4 3/8" CAVITY
STEEL FRAMING. RE STRUCTURAL
CAST-STONE BAND
CAST STONE PARAPET CAP
0'
1"
4'
A-502 F8
Sim
A-501 C4
A-501 F4
CATWALK LEVEL
12'-4"
0'
6'
2' - 10"
1' - 7 5/8"
GROUND FLOOR
0"
0'
1"
4'
CONCRETE GRADE BEAM.
RE STRUCTURAL
FLUID APPLIED WATERPROOFING
PROTECTION BOARD AND DRAINAGE MAT
PERF PERIMETER DRAIN TILE. RE CIVIL
GROUT CAVITY SOLID MIN . 12"
ABOVE FINISH GRADE.
MORTAR NET, THRU WALL
FLASHING AND WEEPS.
A
TOP OF BOND BEAM
24'-0"
MASONRY TIES @ 24" OC VERT
FACE BRICK - MATCH SITE STANDARD
COURSEWORK AND COLOR
12" EXTREME IMPACT-RATED CMU
EXTERIOR WALL. RE STRUCTURAL
CAST STONE PARAPET CAP
ROOF SYSTEM: FULLY-ADHERED TPO
MEMBRANE ON ROOF COVERBOARD WITH
RIGID INSULATION OVER CONC. FILLED
METAL ROOF DECK
R-13 C.I. IN 4 3/8" CAVITY
STEEL FRAMING. RE STRUCTURAL
CAST-STONE BAND
2' - 10"
1' - 7 5/8"
A-501 C7
Sim
A-501 F7
Sim
CATWALK LEVEL
12'-4"
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ENGINEER OF RECORD
321 4 5 6 7 8 9 10
NO. DESCRIPTION DATE
PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE
WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE
PROFESSIONAL ENGINEER
o n e e ig h th i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e i n c h o n e f o o t o n e a n d o n e h a lf i n c h e s o n e f o o t th re e i n c h e s o n e f o o t
OCULUS INCORPORATED
ARCHITECT OF RECORD
MR PROJECT NO: 0499-0162
CONSULTANTS
Civil / Site Utility Engineering:
IMEG, CORP.
Fire & Life Safety:
STANTON ENGINEERING SERVICES, LLC
Hazardous Materials:
MABBETT & ASSOCIATES, INC.
Architectural:
OCULUS, INC.
Structural:
PROFESSIONAL ENGINEERING
CONSULTANTS, PA (PEC)
O C
U L U
S P
R O
JE
C
T N
O
A u to d e sk D o cs
/W ic h ita
C e n tr a liz e d
E m e rg e n cy P o w e r/
-1
-K
S
W ic h ita V
A M
C
O C
U L
U S
A C
C C
E N
T R
A L .r vt
/2
/2
:5
:2
P
M
A-304
CONSTRUCT CENTRALIZED
EMERGENCY POWER SYSTEM
ROBERT J. DOLE VA MEDICAL CENTER
WICHITA, KANSAS
589A7-21-132
Project Director
2026-03-26 RAF MMT
BID DOCUMENTS
FULLY SPRINKLERED
WALL SECTIONS
ARCHITECTURAL
-K
S
1/2" = 1'-0"F4 WALL SECTION
1/2" = 1'-0"F6 WALL SECTION
CONCRETEGRADE BEAM.
RE STRUCTURAL
PROTECTION BOARD AND DRAINAGE MAT
PERF PERIMETER DRAIN TILE. RE CIVIL
1'
4'
0'
1"
7'
MORTAR NET, THRU WALL
FLASHING AND WEEPS.
WALL PACK LIGHTING. PROVIDE
BLOCKING, COORD W/ ELECTRICAL
HMF DOOR AND FRAME AS SCHEDULED.
BOND BEAM AT DOOR HEAD.
RE STRUCTURAL
STEEL LINTEL. RE STRUCTURAL
EXTERIOR PAVING. SLOPE AWAY FROM
BUILDING. RE CIVIL
FIBEROUS EXPANSION JOINT FILLER
TOP OF BOND BEAM
24'-0"
12" EXTREME IMPACT-RATED CMU
EXTERIOR WALL. RE STRUCTURAL
CAST STONE PARAPET CAP
ROOF SYSTEM: FULLY-ADHERED TPO
MEMBRANE ON ROOF COVERBOARD WITH
RIGID INSULATION OVER CONC. FILLED
METAL ROOF DECK
STEEL FRAMING. RE STRUCTURAL
2' - 10"
1' - 2 3/8" 1' - 7 5/8"
A-501 F1
A-502 F8
A-502 B3
A-502 D3
A-501 C1
CATWALK LEVEL
12'-4"
MASONRY TIES @ 24" OC VERT
FACE BRICK - MATCH SITE STANDARD
COURSEWORK AND COLOR
SOLDIER COURSE BRICK AT DOOR HEAD
BOND BEAM AT HEAD. RE STRUCTURAL
STEEL LINTEL. RE STRUCTURAL
R-13 C.I. IN 4 3/8" CAVITY
5'
6'
GROUND FLOOR
0"
CONCRETE GRADE BEAM.
RE STRUCTURAL
PROTECTION BOARD AND DRAINAGE MAT
PERF PERIMETER DRAIN TILE. RE CIVIL
GROUT CAVITY SOLID MIN . 12"
ABOVE FINISH GRADE.
MORTAR NET, THRU WALL
FLASHING AND WEEPS.
6'
0'
5/ 8"
4'
TOP OF BOND BEAM
24'-0"
CAST STONE SILL. REF. DTL.
F9/A-701
CAST STONE PARAPET CAP
ROOF SYSTEM: FULLY-ADHERED TPO
MEMBRANE ON ROOF COVERBOARD WITH
RIGID INSULATION OVER CONC. FILLED
METAL ROOF DECK
STEEL FRAMING. RE STRUCTURAL
FACE BRICK - MATCH SITE STANDARD
COURSEWORK AND COLOR
R-13 C.I. IN 4 3/8" CAVITY
2' - 10"
1' - 7 5/8"1' - 2 3/8"
A-501 F7
Sim
A-502 F8
Sim
A-502 B3
Sim
A-502 D3
Sim
CATWALK LEVEL
12'-4"
MASONRY TIES @ 24" OC VERT
CAST-STONE BAND
BOND BEAM AT HEAD. RE STRUCTURAL
STEEL LINTEL. RE STRUCTURAL
GROUND FLOOR
0"
C
TOP OF BOND BEAM
24'-0"
CONCRETE GRADE BEAM.
RE STRUCTURAL
PROTECTION BOARD AND DRAINAGE MAT
PERF PERIMETER DRAIN TILE. RE CIVIL
GROUT CAVITY SOLID MIN . 12"
ABOVE FINISH GRADE.
MORTAR NET, THRU WALL
FLASHING AND WEEPS.
CAST STONE SILL. REF. DTL.
F9/A-701
12" EXTREME IMPACT-RATED CMU
EXTERIOR WALL. RE STRUCTURAL
ROOF SYSTEM: FULLY-ADHERED TPO
MEMBRANE ON ROOF COVERBOARD WITH
RIGID INSULATION OVER CONC. FILLED
METAL ROOF DECK
STEEL FRAMING. RE STRUCTURAL
4'
0'
1"
6'
1'
EXTREME IMPACT RESISTANT
INTAKE LOUVER :RE: MECH.
1' - 2 3/8" 1' - 7 5/8"
A-502 C8
A-501 F7
Sim
A-502 D1
Sim
CATWALK LEVEL
12'-4"
MASONRY TIES @ 24" OC VERT
FACE BRICK - MATCH SITE STANDARD
COURSEWORK AND COLOR
CAST-STONE BAND
BOND BEAM AT HEAD. RE STRUCTURAL
STEEL LINTEL. RE STRUCTURAL
R-13 C.I. IN 4 3/8" CAVITY
A-502
B1 Sim
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and…
This is the start of the file's text. The full file is on GovTribe.
File details come from the government source that posted it. Updated .