589A7-21-132 Wichita Bid Drawings 07_Mechanical 1 of 2.pdf
PDF 6 MB Posted
- Solicitation number
- 36C25526R0125
About this file
These are mechanical design drawings for a Centralized Emergency Power System construction project at Robert J. Dole VA Medical Center in Wichita, Kansas (Project Number 589A7-21-132, Building 37). The drawings are bid documents issued with an effective date of March 26, 2026, prepared by Miller-Remick LLC as the Professional Engineer of Record, with consulting engineers including IMEG Corp (Civil), Stanton Engineering Services LLC (Fire & Life Safety), Oculus Inc (Architectural), and Professional Engineering Consultants PA (Structural).
The project involves construction of a new generator building containing three diesel generators with associated fuel oil storage, piping, ductwork, and controls systems. Key mechanical infrastructure includes two 40,000-gallon double-wall fiberglass underground fuel oil tanks with secondary containment, new precast concrete trenches for steam and fuel oil piping connections to existing building utilities, new 20-inch diameter generator exhaust ducts extending to roof level with sound attenuation and control dampers, combustion air intake louvers rated for extreme impact, and associated HVAC equipment including roof-mounted condensing units, steam unit heaters, and exhaust fans. The drawings specify piping materials (HPS for hot pipes, PC for condensate, MPS/MPR for mechanical piping), equipment scheduling requirements, control damper installations with BAS integration, and coordinate extensively with existing site utilities including steam tunnels, solar panel structures, and underground utilities. Contractor responsibilities include utility locating, equipment installation with flexible connections, leak monitoring sensors on tank sumps and interstitial spaces connected to BAS, and comprehensive coordination with existing facility infrastructure during construction.
View the file
Other files
Show all 30
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
MECHANICAL
ABBREVIATIONS, NOTES & SYMBOLS
M-001
GDSDC
NO. DESCRIPTION DATE
MILLER-REMICK LLC
PROFESSIONAL ENGINEER
PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE
WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE
PROFESSIONAL ENGINEER.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
BID DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
Phase
ENGINEER OF RECORDCONSULTANT CONSTRUCT CENTRALIZED
EMERGENCY POWER SYSTEM
589A7-21-132
Project Director
2026-03-26
321 4 5 6 7 8 9 10
A
B
C
D
E
F
21 4 5 6 7 8 9 10
A
C
D
E
F
M-R PROJECT NO: 0499-0162
ROBERT J. DOLE VA MEDICAL CENTER
WICHITA, KANSAS
Civil / Site Utility Engineering:Hazardous Materials:
MABBETT & ASSOCIATES, INC.
Fire & Life Safety:
STANTON ENGINEERING SERVICES, LLC
Architectural:
OCULUS, INC.
Structural:
PROFESSIONAL ENGINEERING
CONSULTANTS, PA (PEC)
IMEG, CORP. 37
MECHANICAL
NOTES
M-002
GDSDC
NO. DESCRIPTION DATE
MILLER-REMICK LLC
PROFESSIONAL ENGINEER
PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE
WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE
PROFESSIONAL ENGINEER.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
BID DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
Phase
ENGINEER OF RECORDCONSULTANT CONSTRUCT CENTRALIZED
EMERGENCY POWER SYSTEM
589A7-21-132
Project Director
2026-03-26
321 4 5 6 7 8 9 10
A
B
C
D
E
F
21 4 5 6 7 8 9 10
A
C
D
E
F
M-R PROJECT NO: 0499-0162
ROBERT J. DOLE VA MEDICAL CENTER
WICHITA, KANSAS
Civil / Site Utility Engineering:Hazardous Materials:
MABBETT & ASSOCIATES, INC.
Fire & Life Safety:
STANTON ENGINEERING SERVICES, LLC
Architectural:
OCULUS, INC.
Structural:
PROFESSIONAL ENGINEERING
CONSULTANTS, PA (PEC)
IMEG, CORP. 37
NEW 40,000 GALLON
DOUBLE WALL FIBERGLASS
UNDERGROUND TANK
NEW 40,000 GALLON
DOUBLE WALL FIBERGLASS
UNDERGROUND TANK
REFER TO DRAWING
MP111 FOR CONTINUATION
REFER TO DRAWING MS102
FOR ENLARGED PLAN OF THE FUEL OIL PIPING
4" TANK VENT
REFER TO DRAWING MP601
FOR ALL PIPE SIZES
TANK 1 TANK 2
4" TANK VENT
2" HPS
1-1/2" PC
EXISTING STEAM TUNNEL
EXISTING STEAM VAULT
NEW PRECAST CONCRETE TRENCH
STEAM UTILITIES
BASIS OF DESIGN: TRENWA, INC
MODEL BHC3024-120 WITH LHC30-120 LID
REFER TO DRAWING
MP111 FOR CONTINUATION
2" HPS
1-1/2" PC
BUILDING 37
PROPOSED NEW
GENERATOR BUILDING
CONTRACTOR SHALL COORDINATE
THE ROUTING OF THE NEW STEAM TRENCH
WITH THE EXISTING SOLAR PANEL STRUCTURES
OVER THE PARKING LOTS
EXISTING SOLAR PANEL
STRUCTURE OVER PARKING AREA.
(TYP.)
CONCRETE PAD
(TYP.)
PIPE SUPPORT
PIPE SUPORT TRENCH JOINT
SUMP
MANHOLE COVER
PIPING HIGH POINT
PIPE MITER
SLOPE HPS TOWARDS NEW BUILDING
WATER SERVICE TO
NEW GEN BLDG.
STEAM TRAP
ASSEMBLY
NO. DESCRIPTION DATE
PLAN
NORTH
MILLER-REMICK LLC
PROFESSIONAL ENGINEER
PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE
WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE
PROFESSIONAL ENGINEER.
KEYPLAN
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
BID DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
Phase
ENGINEER OF RECORDCONSULTANT CONSTRUCT CENTRALIZED
EMERGENCY POWER SYSTEM
589A7-21-132
Project Director
2026-03-26
321 4 5 6 7 8 9 10
A
B
C
D
E
F
21 4 5 6 7 8 9 10
A
C
D
E
F
M-R PROJECT NO: 0499-0162
ROBERT J. DOLE VA MEDICAL CENTER
WICHITA, KANSAS
Civil / Site Utility Engineering:Hazardous Materials:
MABBETT & ASSOCIATES, INC.
Fire & Life Safety:
STANTON ENGINEERING SERVICES, LLC
Architectural:
OCULUS, INC.
Structural:
PROFESSIONAL ENGINEERING
CONSULTANTS, PA (PEC)
IMEG, CORP. 37
20 12
34, 34A
1B
2A
5B
1A
35A
7A
1C
5A
3A
MECHANICAL
OVERALL SITE PLAN
MS101
GDSDC
1. REFER TO CIVIL DRAWINGS FOR ADDITIONAL INFORMATION ON THE UNDERGROUND
UTILITIES SHOWN ON THIS DRAWING.
2. PRIOR TO ANY EXCAVATION, THE CONTRACTOR IS RESPONSIBLE TO LOCATE AND
IDENTIFY THE LOCATION OF ALL PRIVATE UNDERGROUND UTILITIES AND
SUBSTRUCTURES THAT MAY BE EXPOSED OR COULD BE IMPACTED BY THE WORK
AND ARE WITHIN AND ADJACENT TO ANY EXCAVATIONS OR UNDERGROUND WORK.
THE CONTRACTOR SHALL ENLIST THE ASSISTANCE OF THE VA COR OR APPOINTED
FACILITY PERSONNEL TO OBTAIN THEIR OPINION AS TO THE LOCATIONS OF
UNDERGROUND UTILITIES THAT MAY EXIST WITHIN THE CONSTRUCTION AREA AND
THAT MAY OR MAY NOT BE PRESENTED IN THE CONTRACT DOCUMENTS.
3. THE CONTRACTOR IS RESPONSIBLE FOR ANY DAMAGE TO EXISTING UTILITIES EVEN
IF THE UTILITIES ARE NOT SHOWN ON THE DRAWINGS. THE CONTRACTOR SHALL
REPAIR ALL DAMAGES AT THEIR OWN EXPENSE AND WILL BE RESPONSIBLE FOR ANY
ADDITIONAL DAMAGES CAUSED BY A SYSTEM BEING DOWN.
4. REFER TO DRAWING M-001 FOR MECHANICAL SYMBOLS, ABBREVIATIONS.
5. REFER TO DRAWING M-002 FOR MECHANICAL NOTES.
6. REFER TO DRAWING MS102 FOR AN ENLARGED PLAN OF THE FUEL OIL PIPING.
7. REFER TO DRAWINGS MP601 & MP602 FOR PIPING FLOW DIAGRAMS.
8. REFER TO M-700 SERIES DRAWINGS FOR EQUIPMENT SCHEDULES.
9. REFER TO DRAWINGS M-801 & M-802 FOR CONTROLS.
GENERAL SHEET NOTES:
SCALE: 1" = 10'-0"
NEW 40,000 GALLON
DOUBLE WALL FIBERGLASS
UNDERGROUND TANK
NEW 40,000 GALLON
DOUBLE WALL FIBERGLASS
UNDERGROUND TANK
REFER TO DRAWING
MP111 FOR CONTINUATION
4" TANK VENT
REFER TO DRAWING MP601
FOR ALL PIPE SIZES
TANK 1
TANK 2
4" TANK VENT
NEW CAST-IN PLACE
CONCRETE TRENCH
STEAM UTILITIES
REFER TO DRAWING
MP111 FOR CONTINUATION
2" HPS
1-1/2" PC
BUILDING #37
PROPOSED NEW
GENERATOR BUILDING
CONTRACTOR SHALL COORDINATE
THE ROUTING OF THE NEW STEAM TRENCH
WITH THE EXISTING SOLAR PANEL STRUCTURES
OVER THE PARKING LOTS
OVERHEAD DOOR
REFER TO DRAWING A-112
FOR ADDITIONAL INFORMATION
2-1/2" FOR
2-1/2" FOS
2-1/2" FOS
2-1/2" FOR
2-1/2" FOS
2-1/2" FOS
PIPE SUPORT
TRENCH JOINT
NEW PRECAST CONCRETE TRENCH
FUEL OIL PIPING
BASIS OF DESIGN: TRENWA, INC
MODEL BHC3024-120 WITH LHC30-120 LID
4" FILL PORT WITH
SPILL CONTAINER
(TYPICAL FOR EACH TANK)
FIBERGLASS DOUBLE-WALL
TANK SUMP (TYP.)
NO. DESCRIPTION DATE
PLAN
NORTH
MILLER-REMICK LLC
PROFESSIONAL ENGINEER
PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE
WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE
PROFESSIONAL ENGINEER.
KEYPLAN
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
BID DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
Phase
ENGINEER OF RECORDCONSULTANT CONSTRUCT CENTRALIZED
EMERGENCY POWER SYSTEM
589A7-21-132
Project Director
2026-03-26
321 4 5 6 7 8 9 10
A
B
C
D
E
F
21 4 5 6 7 8 9 10
A
C
D
E
F
M-R PROJECT NO: 0499-0162
ROBERT J. DOLE VA MEDICAL CENTER
WICHITA, KANSAS
Civil / Site Utility Engineering:Hazardous Materials:
MABBETT & ASSOCIATES, INC.
Fire & Life Safety:
STANTON ENGINEERING SERVICES, LLC
Architectural:
OCULUS, INC.
Structural:
PROFESSIONAL ENGINEERING
CONSULTANTS, PA (PEC)
IMEG, CORP. 37
20 12
34, 34A
1B
2A
5B
1A
35A
7A
1C
5A
3A
MECHANICAL
SITE PLAN - ENLRGED PLAN
TANKS & NEW TRENCHES
MS102
GDSDC
1. REFER TO CIVIL DRAWINGS FOR ADDITIONAL INFORMATION ON THE UNDERGROUND
UTILITIES SHOWN ON THIS DRAWING.
2. PRIOR TO ANY EXCAVATION, THE CONTRACTOR IS RESPONSIBLE TO LOCATE AND
IDENTIFY THE LOCATION OF ALL PRIVATE UNDERGROUND UTILITIES AND
SUBSTRUCTURES THAT MAY BE EXPOSED OR COULD BE IMPACTED BY THE WORK
AND ARE WITHIN AND ADJACENT TO ANY EXCAVATIONS OR UNDERGROUND WORK.
THE CONTRACTOR SHALL ENLIST THE ASSISTANCE OF THE VA COR OR APPOINTED
FACILITY PERSONNEL TO OBTAIN THEIR OPINION AS TO THE LOCATIONS OF
UNDERGROUND UTILITIES THAT MAY EXIST WITHIN THE CONSTRUCTION AREA AND
THAT MAY OR MAY NOT BE PRESENTED IN THE CONTRACT DOCUMENTS.
3. THE CONTRACTOR IS RESPONSIBLE FOR ANY DAMAGE TO EXISTING UTILITIES EVEN
IF THE UTILITIES ARE NOT SHOWN ON THE DRAWINGS. THE CONTRACTOR SHALL
REPAIR ALL DAMAGES AT THEIR OWN EXPENSE AND WILL BE RESPONSIBLE FOR ANY
ADDITIONAL DAMAGES CAUSED BY A SYSTEM BEING DOWN.
4. REFER TO DRAWING M-001 FOR MECHANICAL SYMBOLS, ABBREVIATIONS.
5. REFER TO DRAWING M-002 FOR MECHANICAL NOTES.
6. REFER TO DRAWING MS101 FOR OVERALL SITE PLAN.
7. REFER TO DRAWING MS103 FOR MECHANICAL SITE DETAILS.
8. REFER TO DRAWINGS MP601, MP602 & MP603 FOR PIPING FLOW DIAGRAMS.
9. REFER TO M-700 SERIES FOR EQUIPMENT SCHEDULES.
10. REFER TO M-800 SERIES DRAWINGS FOR CONTROLS.
GENERAL SHEET NOTES:
SCALE: 1/4" = 1'-0"
SHEET KEYNOTES:
1. EMCO 5-GALLON DOUBLE WALL SPILL CONTAINER , EVR WITH INTEGRAL
DRAIN VALVE, CAST IRON IRON RIM & LID. MUST BE PROVIDE FULL
CONTAINMENT WITH THE SECONDARY PIPE.
2. REFER TO DETAIL 4 ON DRAWING MP502 FOR TANK CONNECTIONS.
3. CONTRACTOR SHALL COORDINATE THE TANK SUMPS WITH THE FIBERGLASS
TANK MANUFACTURER, PIPING, CONDUITS, ETC. CONTRACTOR SHALL
COORDINATE THE SUMP HEIGHT WITH THE FIELD CONDITIONS. TYPICAL FOR
BOTH TANKS.
DOUBLE-WALL TANK SUMP BASIS OF DESIGN: FRANKLIN FUELING SYSTEMS.
4. CONTRACTOR SHALL PROVIDE DOUBLE-WALL RIGID ENTRY BOOTS FOR PIPE
PENETRATIONS THROUGH THE TANK SUMP.
5. THE TANK INTERSTITIAL SPACE SHALL HAVE LEAKING MONITORING THAT IS
CONNECTED TO THE BAS SYSTEM.
6. THE TANK SUMPS SHALL HAVE LEAK MONITORING THAT IS CONNECTED TO
THE BAS SYSTEM.
2'-11 1/2"2'-0"
2'-6"6 3/4" 6 3/4"
5"
3'-7 1/2"
3'-2"
6 1/2"
1'-4"
1'-3 1/4"
1'-2"
LHC30-120
T.O.S.
2'-11 1/2"2'-0"
2'-6"6 3/4" 6 3/4"
5"
6 1/2"
1'-3"
LHC30-120
NEOPRENE
BEARING PAD
(INSTALL BEFORE
LID PLACEMENT)
2" HPS
1-1/2" PC
2'-11 1/2"2'-0"
2'-6"6 3/4" 6 3/4"
5"
6 1/2"
1'-1 3/4"8"8"
1'-3"
18 GA PRE-GALV
STEEL IMPACT CHANNEL
LHC30-120
NEOPRENE
BEARING PAD
(INSTALL BEFORE
LID PLACEMENT)
MECHANICAL
SITE DETAILS
MS103
GDSDC
NO. DESCRIPTION DATE
MILLER-REMICK LLC
PROFESSIONAL ENGINEER
PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE
WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE
PROFESSIONAL ENGINEER.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
BID DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
Phase
ENGINEER OF RECORDCONSULTANT CONSTRUCT CENTRALIZED
EMERGENCY POWER SYSTEM
589A7-21-132
Project Director
2026-03-26
321 4 5 6 7 8 9 10
A
B
C
D
E
F
21 4 5 6 7 8 9 10
A
C
D
E
F
M-R PROJECT NO: 0499-0162
ROBERT J. DOLE VA MEDICAL CENTER
WICHITA, KANSAS
Civil / Site Utility Engineering:Hazardous Materials:
MABBETT & ASSOCIATES, INC.
Fire & Life Safety:
STANTON ENGINEERING SERVICES, LLC
Architectural:
OCULUS, INC.
Structural:
PROFESSIONAL ENGINEERING
CONSULTANTS, PA (PEC)
IMEG, CORP. 37
SCALE:
STEAM & CONDENSATE - CONNECTION AT EXISTING STEAM VAULT - DEMOLITION
NTS
FROM
BUILDING 13
BOILER PLANT
(E) 6" HPS
(E) 3" PC
EXISTING
STEAM VAULT
EXISTING STEAM TUNNEL
EXISTING STEAM TUNNEL
SCALE:
STEAM & CONDENSATE - CONNECTION AT EXISTING STEAM VAULT - NEW WORK
NTS
TO NEW BUILDING 37
(N) 2" HPS
(N) 1-1/2" PC
REFER TO DRAWING MS101
FOR CONTINUATION
EXISTING
STEAM VAULT
EXISTING STEAM TUNNEL
EXISTING STEAM TUNNEL
NEW PRECAST
CONCRETE TRENCH
SEE DRAWING MS101
FOR BASIS OF DESIGN INFO
FROM
BUILDING 13
BOILER PLANT
(E) 6" HPS
(E) 3" PC
EXISTING STEAM TUNNEL
EXISTING STEAM TUNNEL
(E)SUMP
(E)ACCESS LADDER
(E)ACCESS LADDER
1. REFER TO CIVIL DRAWINGS FOR ADDITIONAL INFORMATION ON THE UNDERGROUND
UTILITIES SHOWN ON THIS DRAWING.
2. PRIOR TO ANY EXCAVATION, THE CONTRACTOR IS RESPONSIBLE TO LOCATE AND
IDENTIFY THE LOCATION OF ALL PRIVATE UNDERGROUND UTILITIES AND
SUBSTRUCTURES THAT MAY BE EXPOSED OR COULD BE IMPACTED BY THE WORK
AND ARE WITHIN AND ADJACENT TO ANY EXCAVATIONS OR UNDERGROUND WORK.
THE CONTRACTOR SHALL ENLIST THE ASSISTANCE OF THE VA COR OR APPOINTED
FACILITY PERSONNEL TO OBTAIN THEIR OPINION AS TO THE LOCATIONS OF
UNDERGROUND UTILITIES THAT MAY EXIST WITHIN THE CONSTRUCTION AREA AND
THAT MAY OR MAY NOT BE PRESENTED IN THE CONTRACT DOCUMENTS.
3. THE CONTRACTOR IS RESPONSIBLE FOR ANY DAMAGE TO EXISTING UTILITIES EVEN
IF THE UTILITIES ARE NOT SHOWN ON THE DRAWINGS. THE CONTRACTOR SHALL
REPAIR ALL DAMAGES AT THEIR OWN EXPENSE AND WILL BE RESPONSIBLE FOR ANY
ADDITIONAL DAMAGES CAUSED BY A SYSTEM BEING DOWN.
4. REFER TO DRAWING M-001 FOR MECHANICAL SYMBOLS, ABBREVIATIONS.
5. REFER TO DRAWING M-002 FOR MECHANICAL NOTES.
6. REFER TO DRAWING MS101 FOR THE MECHANICAL SITE.
7. REFER TO DRAWING MS102 FOR AN ENLARGED PLAN FOR THE TANKS AND
THE FUEL OIL PIPING.
8. REFER TO DRAWINGS MP601 & MP602 FOR PIPING FLOW DIAGRAMS.
9. REFER TO M-700 SERIES DRAWINGS FOR EQUIPMENT SCHEDULES.
10. REFER TO DRAWINGS M-801 & M-802 FOR CONTROLS.
GENERAL SHEET NOTES:
SHEET KEYNOTES
:1. CONTRACTOR SHALL CUT AND REMOVE THE EXISTING HPS BACK TO THE TEE
OFF THE 6" HPS MAIN.
2. CONTRACTOR SHALL REMOVE THE EXISTING BLIND FLANGE ON THE EXISTING
PC VALVE AND CONNECT NEW PIPE.
3. NEW CORED PIPE PENETRATIONS THROUGH THE EXISTING VAULT WALL.
4. CONTRACTOR SHALL COORDINATE THE ROUTING OF THE PIPING, SUCH TO
NOT BLOCK ACCESS TO ANY DEVICES, LADDER, SUMP, ETC.
5. CONTRACTOR SHALL INSTALL 4"Ø PIPE FROM THE BOTTOM OF THE NEW
TRENCH INTO THE EXISTING VAULT FOR TRENCH DRAINAGE.
(E) 6" HPS
(E) 3" PC
SCALE:
TYPICAL STEAM TRENCH SECTION - PIPE GUIDES
3/4" = 1'-0"
SCALE:
TYPICAL STEAM TRENCH SECTION - ROLLERS
3/4" = 1'-0"
SCALE:
TYPICAL FUEL OIL - PIPE SUPPORT
3/4" = 1'-0"
(E)SUMP WITH PUMP
T
T
T
A
M-302
37-DT-3
37-DT-2
37-DT-1
37-FOP-1
37-FOF-1
GENERATOR #1
3'-0"W x 12"D TRENCH
FUEL OIL PIPE TRENCH WITH GRATING COVER
REFER TO STRUCTURAL DRAWINGS
A
M-301
2 31 4
A
B
C
GENERATOR RADIATOR
EXHAUST LOUVER
(EXTREME IMPACT RATED)
(216"W x 156"H) (TYP.3)
GENERATOR #2 GENERATOR #3
4'-0"W x 8'-0"H
CONTROL DAMPER
(TYP. 6)
B
M-301
ELECTRICAL
EQUIPMENT (TYP.)
OVERHEAD DOOR
OVERHEAD DOOR
4" THICK CONCRETE
HOUSEKEEPING PAD (TYP.)
GEM-1
GEM-2
GEM-3
(GENERATOR EXHAUST
MUFFLER)
(GENERATOR EXHAUST
MUFFLER)
(GENERATOR EXHAUST
MUFFLER)
MOUNT 8 FT. AFF
4'-0"W x 8'-0"H
CONTROL DAMPER
(TYP. 6)
INSULATED SHEETMETAL
GENERATOR RADIATOR
EXHAUST PLENUM.
TYP. 3
SOUND ATTENUATOR
(216"W x 156"H x 36"L) (TYP.3)
GENERATOR RADIATOR
CONTROL DAMPER
(216"W x 156"H) (TYP. 3)
EXHAUST AIR
(TYP.3)
37-CRU-1 37-HP-1B
37-FT-1
MOUNT 8'-0" AFF
(SUH-1)
(37-HP-1B)
(37-RTU-1)
37-SUH-1
GENERATOR
ROOM
SWITCHGEAR
ROOM
FIRE RISER
ROOM
37-HP-1A/B 1
(ON SWITCHGEAR LID)
REFER TO STRUCTURAL
DRAWING S-101 FOR
ADDITIONAL DETAILS FOR
MOUNTING LOUVER
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
CONSULTANTS
321 4 5 6 7 8 9 10
NO. DESCRIPTION DATE
PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE
WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE
PROFESSIONAL ENGINEER
o n e e ig h th i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e i n c h o n e f o o t o n e a n d o n e h a lf i n c h e s o n e f o o t th re e i n c h e s o n e f o o t
MILLER-REMICK LLC
PROFESSIONAL ENGINEER
NORTH
ENGINEER OF RECORD
M-R PROJECT NO:
Civil:
IMEG, CORP.
Fire & Life Safety:
STANTON ENGINEERING SERVICES, LLC
Hazardous Materials:
MABBETT & ASSOCIATES, INC.
Architectural:
OCULUS, INC.
Structural:
PROFESSIONAL ENGINEERING
CONSULTANTS, PA (PEC)
A u to d e s k D o c s /W ic h it a
C e n tr a liz e d E m e rg e n c y P o w e r/
-0
W ic h it a C e n tr a liz e d
E m e rg e n c y P o w e r-
M E
P -R
.r v t
/2
/2
:5
:5
A
M
MQ111
MECHANICAL
EQUIPMENT PLAN
GROUND FLOOR
CONSTRUCT CENTRALIZED
EMERGENCY POWER SYSTEM
589A7-21-132
Project Director
2026-03-26 DC GDS
BID DOCUMENTS
FULLY SPRINKLERED
ROBERT J. DOLE VA MEDICAL CENTER
WICHITA, KANSAS
0499-0162
SCALE: 1/4" = 1'-0"1 EQUIPMENT PLAN - GROUND FLOOR
GENERAL SHEET NOTES:
1. REFER TO DRAWING M-001 FOR SYMBOLS AND ABBRVIATIONS.
2. REFER TO DRAWINGS M-600 SERIES FOR FLOW DIAGRAMS
3. REFER TO DRAWINGS M-700 SERIES FOR EQUIPMENT SCHEDULES.
4. REFER TO DRAWINGS M-800 FOR CONTROLS.
5. DO NOT SCALE THE DRAWINGS FOR EXACT DIMENSIONS. VERIFY ALL FIGURES,
CONDITIONS, DIMENSIONS, ETC. AT THE JOB SITE.
1 CONTRACTOR SHALL PROVIDE EQUIPMENT RAILS FOR UNIT. UNIT LOCATED ON THE
LID OF THE SWITCHGEAR ROOM. PROVIDE REFRIGERANT LIQUID AND SUCTION
LINES BETWEEN CONDENSING UNIT AND INDOOR UNIT. SEAL OPENINGS THROUGH
ALL RATED ASSEMBLIES. INSTALL REFRIGEERANT LINES PER MANUFACTURER'S
WRITTEN INSTRUCTIONS.
2 CONTRACTOR SHALL INSTALL CONDENSATE PUMP AND ROUTE PIPING TO THE
EXTERIOR AND PROVIDE SPLASH BLOCK. REFER TO SCHEDULE DRAWING FOR
ADDITIONAL INFORMATION. COORDINATE WITH ALL TRADES.
SHEET KEYNOTES:
A
M-301
2 31 4
A
B
C
37-EF-1
(70"W x 144"L) (70"W x 144"L) (70"W x 144"L)
37-GIH-1 37-GIH-2 37-GIH-3
ROOF ACCESS
HATCH
B
M-301
PROVIDE EQUIPMENT RAILS FOR 37-CU-1
REFER TO THE EQUIPMENT SCHEDULE FOR
ADDITIONAL INFORMATION
37-CU-1
37-RTU-1
37-EF-2
PROVIDE EQUIPMENT CURB FOR 37-RTU-1
REFER TO THE EQUIPMENT SCHEDULE FOR
ADDITIONAL INFORMATION
OUTDOOR AIR
INTAKE HOOD
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
CONSULTANTS
321 4 5 6 7 8 9 10
NO. DESCRIPTION DATE
PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE
WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE
PROFESSIONAL ENGINEER
o n e e ig h th i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e i n c h o n e f o o t o n e a n d o n e h a lf i n c h e s o n e f o o t th re e i n c h e s o n e f o o t
MILLER-REMICK LLC
PROFESSIONAL ENGINEER
NORTH
ENGINEER OF RECORD
M-R PROJECT NO:
Civil:
IMEG, CORP.
Fire & Life Safety:
STANTON ENGINEERING SERVICES, LLC
Hazardous Materials:
MABBETT & ASSOCIATES, INC.
Architectural:
OCULUS, INC.
Structural:
PROFESSIONAL ENGINEERING
CONSULTANTS, PA (PEC)
A u to d e s k D o c s /W ic h it a
C e n tr a liz e d E m e rg e n c y P o w e r/
-0
W ic h it a C e n tr a liz e d
E m e rg e n c y P o w e r-
M E
P -R
.r v t
/2
/2
:5
:5
A
M
MQ131
MECHANICAL
EQUIPMENT PLAN
ROOF
CONSTRUCT CENTRALIZED
EMERGENCY POWER SYSTEM
589A7-21-132
Project Director
2026-03-26 DC GDS
BID DOCUMENTS
FULLY SPRINKLERED
ROBERT J. DOLE VA MEDICAL CENTER
WICHITA, KANSAS
0499-0162
GENERAL SHEET NOTES:
1. REFER TO DRAWING M-001 FOR MECHANICAL ABBREVIATIONS & SYMBOLS.
2. REFER TO DRAWINGS MP600 SERIES FOR FLOW DIAGRAMS
3. REFER TO DRAWINGS M-700 SERIES FOR EQUIPMENT SCHEDULES.
4. DO NOT SCALE THE DRAWINGS FOR EXACT DIMENSIONS. VERIFY ALL FIGURES,
CONDITIONS, DIMENSIONS, ETC. AT THE JOB SITE.
SCALE: 1/4" = 1'-0"1 EQUIPMENT PLAN - ROOF
T
T
A
M-302
A
M-301
37-DT-1
37-DT-3
37-DT-2
37-FOF-1
37-FOP-1
2 31 4
A
B
C
GENERATOR RADIATOR
EXHAUST LOUVER
(EXTREME IMPACT RATED)
(216"W x 156"H) (TYP.3)
VENTILATION/COMBUSTION AIR
INTAKE LOUVERS
EXTREME IMPACT RATED (TYP. 13)
REFER TO WALL SECTION F5 ON DRAWING A-305
FOR ADDITIONAL INFORMATION
37-GEN-1 37-GEN-2 37-GEN-3
FUEL OIL
PIPE TRENCH
C
M-301
20" I.D. GENERATOR
EXHAUST DUCT
UP THRU. ROOF.
4'-0"W x 8'-0"H
CONTROL DAMPER
(TYP. 6)
B
M-301
20" I.D. GENERATOR
EXHAUST DUCT
UP THRU. ROOF.
20" I.D. GENERATOR
EXHAUST DUCT
UP THRU. ROOF.
GEM-3GEM-2GEM-1
70"W x 144"H DUCT
DOWN FROM ROOF
70"W x 144"H DUCT
DOWN FROM ROOF
70"W x 144"H DUCT
DOWN FROM ROOF. OVERHEAD DOOR
OVERHEAD DOOR
(RTU-1)
(SUH-1)
16x16 EXH. DUCT
UP TO 37-EF-1
ON THE ROOF
PROVIDE WIRE SCREEN
INSULATED SHEETMETAL
GENERATOR RADIATOR
EXHAUST PLENUM.
TYP. 3
SOUND ATTENUATOR
(216"W x 156"H) (TYP.3)
GENERATOR RADIATOR
CONTROL DAMPER
(216"W x 156"H) (TYP. 3)
3'-4"W x 6'-0"H
SOUND ATTENUATOR (TYP.)
CONTROL DAMPER (TYP.)
EXHAUST AIR
(TYP.3)
COMBUSTION/VENTILATION
AIR IN (TYP.)
24x16 SA
24x16 SA
57x9 SA DOWN
FROM 37-RTU-1
TRANSITION TO 24x30
37-FT-1
37-CRU-1
37-HP-1B
(37-HP-1A)
(37-RTU-1)
37-SUH-1
16x16 EXH. DUCT
UP TO 37-EF-2
ON THE ROOF
PROVIDE WIRE SCREEN
MOD-1A MOD-2A MOD-3A
D-3B
D-3C
D-2B
D-2C
D-1B
D-1C
WALL SLEEVE
(TYP.)
GENERATOR
ROOM
SWITCHGEAR
ROOM
FIRE RISER
ROOM
16x12 SA
16x12 SA
SG-1
800 CFM
SG-1
800 CFM
SG-1
800 CFM
SG-1
800 CFM
SG-1
800 CFM
SG-1
800 CFM
SG-1
815 CFM
SG-1
800 CFM
MOD-3A
MOD-3M
37-HP-1A/B 2
BAS PANEL
(37-SA-1A) (37-SA-1B) (37-SA-1C)
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
CONSULTANTS
321 4 5 6 7 8 9 10
NO. DESCRIPTION DATE
PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE
WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE
PROFESSIONAL ENGINEER
o n e e ig h th i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e i n c h o n e f o o t o n e a n d o n e h a lf i n c h e s o n e f o o t th re e i n c h e s o n e f o o t
MILLER-REMICK LLC
PROFESSIONAL ENGINEER
NORTH
ENGINEER OF RECORD
M-R PROJECT NO:
Civil:
IMEG, CORP.
Fire & Life Safety:
STANTON ENGINEERING SERVICES, LLC
Hazardous Materials:
MABBETT & ASSOCIATES, INC.
Architectural:
OCULUS, INC.
Structural:
PROFESSIONAL ENGINEERING
CONSULTANTS, PA (PEC)
A u to d e s k D o c s /W ic h it a
C e n tr a liz e d E m e rg e n c y P o w e r/
-0
W ic h it a C e n tr a liz e d
E m e rg e n c y P o w e r-
M E
P -R
.r v t
/2
/2
:0
:0
A
M
MH111
MECHANICAL
DUCTWORK PLAN
GROUND FLOOR
CONSTRUCT CENTRALIZED
EMERGENCY POWER SYSTEM
589A7-21-132
Project Director
2026-03-26 JK GDS
BID DOCUMENTS
FULLY SPRINKLERED
ROBERT J. DOLE VA MEDICAL CENTER
WICHITA, KANSAS
0499-0162
SCALE: 1/4" = 1'-0"1 DUCTWORK PLAN - GROUND FLOOR
GENERAL SHEET NOTES:
1. REFER TO DRAWING M-001 FOR MECHANICAL ABBREVIATIONS & SYMBOLS.
2. REFER TO DRAWING M-002 FOR MECHANICAL NOTES.
3. REFER TO DRAWINGS MP600 SERIES FOR FLOW DIAGRAMS
4. REFER TO DRAWINGS M-700 SERIES FOR EQUIPMENT SCHEDULES.
5. REFER TO DRAWINGS M-801 & M-802 FOR CONTROLS.
6. DO NOT SCALE THE DRAWINGS FOR EXACT DIMENSIONS. VERIFY ALL FIGURES,
CONDITIONS, DIMENSIONS, ETC. AT THE JOB SITE.
1 INSTALL 70"W x 144"H CONTROL DAMPER. MOUNT TO THE BOTTOM OF THE SOUND
ATTENUATOR. SEE SECTION A ON DRAWING M-302. REFER TO DRAWING M-802 FOR
CONTROLS INFORMATION.
2 CONTRACTOR SHALL PROVIDE EQUIPMENT RAILS FOR UNIT. UNIT LOCATED ON THE
LID OF THE SWITCHGEAR ROOM. PROVIDE REFRIGERANT LIQUID AND SUCTION
LINES BETWEEN CONDENSING UNIT AND INDOOR UNIT. SEAL OPENINGS THROUGH
ALL RATED ASSEMBLIES. INSTALL REFRIGEERANT LINES PER MANUFACTURER'S
WRITTEN INSTRUCTIONS.
3 CONTROL DAMPERS. REFER TO DETAIL 1 ON DRAWING M-802 FOR CONTROLS
INFORMATION.
4 THERMOSTAT CONTROLS DAMPERS: D-1B/C, D-2B/C AND D-3B/C. REFER TO DETAIL
1 ON DRAWING M-802 FOR CONTROLS INFORMATION.
M-302
A
M-301
2 31 4
A
B
C
37-EF-1
37-GIH-337-GIH-237-GIH-1
(GRAVITY INTAKE HOOD) (GRAVITY INTAKE HOOD) (GRAVITY INTAKE HOOD)
20" I.D. GENERATOR
EXHAUST DUCT UP FROM
BELOW. EXTEND UP TO
20 FT. ABOVE ROOF
20" I.D. GENERATOR
EXHAUST DUCT UP
FROM BELOW. EXTEND UP TO
20 FT. ABOVE THE ROOF
70"L x 144"L DUCT DOWN
TO 12" BELOW ROOF.
PROVIDE BIRD SCREEN.
TYP. 3
ROOF ACCESS
HATCH
B
M-301
PROVIDE ROOF CURB
REFER TO DRAWING M-701
FOR ADDITIONAL INFORMATION
(TYP.)
PROVIDE ROOF CURB
REFER TO DRAWING M-701
FOR ADDITIONAL INFORMATION (TYP.)
37-RTU-1
37-CU-1
57x9 SA DUCT DOWN
RE: DWG MH111
37-EF-2
REFER TO DETAIL 3 ON
DRAWING M-502
(TYP.)
PROVIDE EQUIPMENT RAILS FOR 37-CU-1
REFER TO THE EQUIPMENT SCHEDULE FOR
ADDITIONAL INFORMATION
PROVIDE EQUIPMENT CURB FOR 37-RTU-1
REFER TO THE EQUIPMENT SCHEDULE FOR
ADDITIONAL INFORMATION
OUTDOOR AIR
INTAKE HOOD
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
CONSULTANTS
321 4 5 6 7 8 9 10
NO. DESCRIPTION DATE
PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE
WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE
PROFESSIONAL ENGINEER
o n e e ig h th i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e i n c h o n e f o o t o n e a n d o n e h a lf i n c h e s o n e f o o t th re e i n c h e s o n e f o o t
MILLER-REMICK LLC
PROFESSIONAL ENGINEER
NORTH
ENGINEER OF RECORD
M-R PROJECT NO:
Civil:
IMEG, CORP.
Fire & Life Safety:
STANTON ENGINEERING SERVICES, LLC
Hazardous Materials:
MABBETT & ASSOCIATES, INC.
Architectural:
OCULUS, INC.
Structural:
PROFESSIONAL ENGINEERING
CONSULTANTS, PA (PEC)
A u to d e s k D o c s /W ic h it a
C e n tr a liz e d E m e rg e n c y P o w e r/
-0
W ic h it a C e n tr a liz e d
E m e rg e n c y P o w e r-
M E
P -R
.r v t
/2
/2
:5
:5
A
M
MH131
MECHANICAL
DUCTWORK PLAN
ROOF
CONSTRUCT CENTRALIZED
EMERGENCY POWER SYSTEM
589A7-21-132
Project Director
2026-03-26 JK GDS
BID DOCUMENTS
FULLY SPRINKLERED
ROBERT J. DOLE VA MEDICAL CENTER
WICHITA, KANSAS
0499-0162
SCALE: 1/4" = 1'-0"1 DUCTWORK PLAN - ROOF
GENERAL SHEET NOTES:
1. REFER TO DRAWING M-001 FOR MECHANICAL ABBREVIATIONS & SYMBOLS.
2. REFER TO DRAWING M-002 FOR MECHANICAL NOTES.
3. REFER TO DRAWINGS MP600 SERIES FOR FLOW DIAGRAMS
4. REFER TO DRAWINGS M-700 SERIES FOR EQUIPMENT SCHEDULES.
5. DO NOT SCALE THE DRAWINGS FOR EXACT DIMENSIONS. VERIFY ALL FIGURES,
T
T
A
M-302
A
M-301
2 31 4
A
B
C
37-FOF-1
37-DT-2
37-FOP-1
37-DT-3
37-DT-1
GENERATOR #1 GENERATOR #2 GENERATOR #3
C
M-301
B
M-301
(N)2" FOR
(N)2" FOS
(N)2" FOR
(N)2" FOS
(N)2" FOR
(N)2" FOS
(N)2" FOS
(N)2" FOS
(N)2" FOR
(N)2" FOS
(N)2" FOS (N)2" FOS
(N)2" FOR
(N)2 1/2" FOR
(N)2 1/2" FOS
(N)2 1/2" FOR
(N)2 1/2" FOR
(N)2 1/2" FOR
FUEL OIL
PIPE TRENCH
4" THICK CONCRETE
HOUSEKEEPING PAD
REFER TO STRUCTURAL DRAWINGS
OVERHEAD
DOOR
OVERHEAD DOOR
GENERATOR RADIATOR
EXHAUST PLENUM
REFER TO DRAWING MH111
FOR ADDTIONAL INFORMATION.
TYPICAL FOR EACH GENERATOR
PIPE RISE
UP OUT OF
TRENCH (TYP.)
REFER TO DRAWINGS MS101 & MS102
FOR CONTINUATION
REFER TO THE EQUIPMENT
SCHEDULES FOR MOUNTING HEIGHTS
(N)2 1/2" FOR
PRECAST CONCRETE TRENCH
REFER TO DRAWING MS102 FOR
INFORMATION
(N)1 1/2" MPS
1-1/2" MPS
UP TO ROOF
RE: DWG: MP131
37-PRV-1
2" HPS
UP FROM PIT
DRIP LEG AT BOTTOM.
1-1/2" PC
DOWN IN PIT
REFER TO DRAWING
MS101 FOR
CONTINUATION
37-CRU-1
37-FT-1
2-1/2" VTR
2" DAY TANK VENT
2-1/2" VTR
PIPING PIT
REFER TO STRUCTURAL
DRAWING S
37-HP-1B
37-RTU-1
37-SUH-1
2"SV UP FROM 37-SV-1
UP THRU ROOF
(N)1 1/2" MPR
1-1/4" MPR DOWN
FROM 37-RTU-1
RE: DWG. MP131
(N)1 1/2" MPR
(N)3/4" MPS
37-SUH-1
(N)3/4" MPS
(N)3/4" MPR
GENERATOR
ROOM
SWITCHGEAR
ROOM
FIRE RISER
ROOM
37-HP-1A/B
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
CONSULTANTS
321 4 5 6 7 8 9 10
NO. DESCRIPTION DATE
PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE
WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE
PROFESSIONAL ENGINEER
o n e e ig h th i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e i n c h o n e f o o t o n e a n d o n e h a lf i n c h e s o n e f o o t th re e i n c h e s o n e f o o t
MILLER-REMICK LLC
PROFESSIONAL ENGINEER
NORTH
ENGINEER OF RECORD
M-R PROJECT NO:
Civil:
IMEG, CORP.
Fire & Life Safety:
STANTON ENGINEERING SERVICES, LLC
Hazardous Materials:
MABBETT & ASSOCIATES, INC.
Architectural:
OCULUS, INC.
Structural:
PROFESSIONAL ENGINEERING
CONSULTANTS, PA (PEC)
A u to d e s k D o c s /W ic h it a
C e n tr a liz e d E m e rg e n c y P o w e r/
-0
W ic h it a C e n tr a liz e d
E m e rg e n c y P o w e r-
M E
P -R
.r v t
/2
/2
:5
:5
A
M
MP111
MECHANICAL
PIPING PLAN
GROUND FLOOR
CONSTRUCT CENTRALIZED
EMERGENCY POWER SYSTEM
589A7-21-132
Project Director
2026-03-26 JK GDS
BID DOCUMENTS
FULLY SPRINKLERED
ROBERT J. DOLE VA MEDICAL CENTER
WICHITA, KANSAS
0499-0162
SCALE: 1/4" = 1'-0"1 PIPING PLAN - GROUND FLOOR
GENERAL SHEET NOTES:
1. REFER TO DRAWING M-001 FOR MECHANICAL ABBREVIATIONS & SYMBOLS.
2. REFER TO DRAWING M-002 FOR MECHANICAL NOTES.
3. REFER TO DRAWINGS MP600 SERIES FOR FLOW DIAGRAMS
4. REFER TO DRAWINGS M-700 SERIES FOR EQUIPMENT SCHEDULES.
5. REFER TO DRAWINGS M-801 & M-802 FOR CONTROLS.
6. DO NOT SCALE THE DRAWINGS FOR EXACT DIMENSIONS. VERIFY ALL FIGURES,
CONDITIONS, DIMENSIONS, ETC. AT THE JOB SITE.
1 CONTRACTOR SHALL PROVIDE FLEXIBLE CONNECTION BETWEEN STEEL PIPING
AND THE GENERATOR FUEL OIL CONNECTIONS.
2 CONTRACTOR SHALL INSTALL A WATER SENSOR IN THE BOTTOM OF THE PIT.
SENSOR TO BE MONITORED BY THE BAS. IF SENSOR DETECTS WATER, IT SHALL
SEND AN ALARM TO THE BAS.
M-302
A
M-301
2 31 4
A
B
C
B
M-301
1-1/2" MPS
UP FROM BELOW
RE: DWG MP111
37-RTU-1
37-CU-1
2-1/2" V UP
FROM FLASH TANK
2-1/2" V UP
FROM 37-CRU-1
OA INTAKE
HOOD
37-EF-1
2"SV UP
FROM 37-SV-1
1-1/4" MPR DOWN
TO BELOW
RE: DWG. MP111
37-EF-2
7/8" RL
1-5/8" RS
ROOF ACCESS
HATCH
PIPE
SUPPORT
(TYP.)
1-1/4" COND. COIL DRAIN
SLOPE 1/8" = 1'-0"
REFER TO DETAIL 8 ON
DRAWING MP502
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
CONSULTANTS
321 4 5 6 7 8 9 10
NO. DESCRIPTION DATE
PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE
WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE
PROFESSIONAL ENGINEER
o n e e ig h th i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e i n c h o n e f o o t o n e a n d o n e h a lf i n c h e s o n e f o o t th re e i n c h e s o n e f o o t
MILLER-REMICK LLC
PROFESSIONAL ENGINEER
NORTH
ENGINEER OF RECORD
M-R PROJECT NO:
Civil:
IMEG, CORP.
Fire & Life Safety:
STANTON ENGINEERING SERVICES, LLC
Hazardous Materials:
MABBETT & ASSOCIATES, INC.
Architectural:
OCULUS, INC.
Structural:
PROFESSIONAL ENGINEERING
CONSULTANTS, PA (PEC)
A u to d e s k D o c s /W ic h it a
C e n tr a liz e d E m e rg e n c y P o w e r/
-0
W ic h it a C e n tr a liz e d
E m e rg e n c y P o w e r-
M E
P -R
.r v t
/2
/2
:5
:5
A
M
MP131
MECHANICAL
PIPING PLAN
ROOF
CONSTRUCT CENTRALIZED
EMERGENCY POWER SYSTEM
589A7-21-132
Project Director
2026-03-26 Checker Author
BID DOCUMENTS
FULLY SPRINKLERED
ROBERT J. DOLE VA MEDICAL CENTER
WICHITA, KANSAS
0499-0162
GENERAL SHEET NOTES:
1. REFER TO DRAWING M-001 FOR MECHANICAL ABBREVIATIONS, NOTES & SYMBOLS.
2. DO NOT SCALE THE DRAWINGS FOR EXACT DIMENSIONS. VERIFY ALL FIGURES,
SCALE: 1/4" = 1'-0"1 PIPING PLAN - ROOF
GROUND FLOOR
0' - 0"
A
M-302
COMBUSTION/VENTILATION AIR
EXTREME IMPACT INTAKE LOUVER (TYP.)
2 31 4
C
M-301
ROOF
19' - 6"
B
M-301
FUEL OIL PIPING
REFER TO DRAWINGS MS101
AND MP111 FOR ADDITIONAL INFORMATION
CATWALK LEVEL
12' - 4"
GROUND FLOOR
0' - 0"
ABC
ROOF
19' - 6"
20" I.D. GENERATOR
EXHAUST DUCT
37-GIH-1
(GRAVITY INTAKE HOOD)
GENERATOR
EXHAUST MUFFLER
GENERATOR
37-DT-337-DT-2
FUEL OIL
PIPING IN TRENCH
37-FOF-1
4'-0"W x 8'-0"H
CONTROL DAMPER
INSULATED GENERATOR RADIATOR
EXHAUST PLENUM
GENERATOR
ROOM
EXTREME IMPACT
LOUVER
SOUND ATTENUATOR
CONTROL DAMPERS 37-FOP-1
FUEL OIL PIPING
TO UNDERGROUND TANKS
REFER TO DRAWING MS101
FOR CONTINUATION
ROOF CURB
REFER TO DRAWING M-701
FOR ADDITONAL INFORMATION
70"W x 144"L
CONTROL DAMPER
REFER TO DETAIL 3
ON DRAWING MP502
GENERATOR RADIATOR
EXHAUST LOUVER
(EXTREME IMPACT RATED)
(216"W x 156"H)
GENERATOR RADIATOR
EXHAUST AIR
GENERATOR MUFFLER
EXHAUST AIR
216"W x 156"H
CONTROL DAMPER
70"W x 144"L x 3'-0"L
SOUND ATTENUATOR
CATWALK LEVEL
12' - 4"
37-FT-1
16x12 SA
(N)1 1/2" MPS
(N)1 1/2" MPR
REFER TO DRAWINGS
MP601 & MP602 FOR PIPING LAYOUT
(N)3/4" MPR
(N)3/4" MPS
(N)1 1/2" PC
(N)2 1/2" V
(N)2 1/2" V
TO ALLOW FOR EXPANSION THE
GENERATOR EXHAUST STACK
MUST NOT BE ATTACHED TO
THE SUPPORT STRUCTURE
REFER TO DETAIL 3
ON DRAWING MP502
SUPPORT CURB
REFER TO STRUCTURAL DWGS.
REFER TO
STRUCTURAL DETAIL
1 ON DRAWING S-513
FOR STACK SUPPORT
STRUCTURE
GROUND FLOOR
0' - 0"
C
ROOF
19' - 6"
CONTROL DAMPER
SOUND ATTENUATOR
EXTREME IMPACT
LOUVER
ACCESS PLATFORM
CATWALK LEVEL
12' - 4"
GALVANIZED SHEET METAL
WALL SLEEVE
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
CONSULTANTS
321 4 5 6 7 8 9 10
NO. DESCRIPTION DATE
PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE
WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE
PROFESSIONAL ENGINEER
o n e e ig h th i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e i n c h o n e f o o t o n e a n d o n e h a lf i n c h e s o n e f o o t th re e i n c h e s o n e f o o t
MILLER-REMICK LLC
PROFESSIONAL ENGINEERENGINEER OF RECORD
M-R PROJECT NO:
Civil:
IMEG, CORP.
Fire & Life Safety:
STANTON ENGINEERING SERVICES, LLC
Hazardous Materials:
MABBETT & ASSOCIATES, INC.
Architectural:
OCULUS, INC.
Structural:
PROFESSIONAL ENGINEERING
CONSULTANTS, PA (PEC)
A u to d e s k D o c s /W ic h it a
C e n tr a liz e d E m e rg e n c y P o w e r/
-0
W ic h it a C e n tr a liz e d
E m e rg e n c y P o w e r-
M E
P -R
.r v t
/2
/2
:5
:0
A
M
M-301
MECHANICAL
BUILDING ELEVATIONS AND SECTIONS
CONSTRUCT CENTRALIZED
EMERGENCY POWER SYSTEM
589A7-21-132
Project Director
2026-03-26 JK GDS
BID DOCUMENTS
FULLY SPRINKLERED
ROBERT J. DOLE VA MEDICAL CENTER
WICHITA, KANSAS
0499-0162
SCALE: 1/4" = 1'-0"A BUILDING ELEVATION - SOUTH
SCALE: 1/4" = 1'-0"B BUILDING SECTION AT GENERATOR
SCALE: 1/4" = 1'-0"C SECTION @ INTAKE LOUVER
1 CONTRACTOR SHALL SUPPORT THE GENERATOR RADIATOR EXHAUST PLENUM
INCLUDING DAMPERS FROM THE FLOOR. CONTRACTOR SHALL COORDINATION THE
DIMENSIONS OF THE PLENUM WITH THE APPROVED EQUIPMENT SUBMITTAL.
2 CONTRACTOR SHALL PROVIDE AND INSTALL PIPES/ELBOWS AND FLEXIBLE
CONNECTIONS AS REQUIRED FROM THE GENERATOR TO THE GENERATOR
MUFFLER. PIPES, ELBOWS AND FLEXIBLE CONNECTIONS TO BE INCLUDED FROM
THE MUFFLER MANUFACTURER.
SHEET KEY NOTES:
GENERAL SHEET NOTES:
1. REFER TO DRAWING M-001 FOR MECHANICAL ABBREVIATIONS & SYMBOLS.
2. REFER TO DRAWING M-002 FOR MECHANICAL NOTES.
3. REFER TO DRAWINGS MP600 SERIES FOR FLOW DIAGRAMS
4. REFER TO DRAWINGS M-700 SERIES FOR EQUIPMENT SCHEDULES.
5. REFER TO DRAWINGS M-801 & M-802 FOR CONTROLS.
6. DO NOT SCALE THE DRAWINGS FOR EXACT DIMENSIONS. VERIFY ALL FIGURES,
GROUND FLOOR
0' - 0"
ABC
ROOF
19' - 6"
GENERATOR EXHAUST MUFFLER
TYPICAL 3.
20" I.D. GENERATOR
EXHAUST DUCT
37-GIH-3
GENERATOR
FIRE RISER
ROOM
GENERATOR
ROOM
GENERATOR RADIATOR
EXHAUST LOUVER
(EXTREME IMPACT RATED)
(216"W x 156"H)
INSULATED GENERATOR RADIATOR
EXHAUST PLENUM
FUEL OIL PIPING
IN TRENCH.
RE: DRAWING MP111
GEM-3
VENTILATION/COMBUSTION AIR
INTAKE LOUVERS
EXTREME IMPACT RATED (TYP. 13)
216"W x 156"H
CONTROL DAMPER
REFER TO DETAIL 3
ON DRAWING MP502
M
IN
IM
U
M
ROOF CURB
REFER TO DRAWING M-701
FOR ADDITONAL INFORMATION
SOUND ATTENUATOR
CONTROL DAMPER
70"W x 144"L CONTROL DAMPER
4'-0"W x 8'-0"H
CONTROL DAMPER
70"W x 144"L x 3'-0"L
SOUND ATTENUATOR
CATWALK LEVEL
12' - 4"
16x12 SA
37-RTU-1
ROOF CURB
REFER TO SCHEDULE DRAWINGS
FOR ADDITIONAL INFORMATION
REFER TO DETAIL 3
ON DRAWING MP502
REFER TO DETAIL 3
FOR PIPING TO STEAM UNIT HEATER
SUPPORT CURB
REFER TO STRUCTURAL DWGS.
(N)3/4" MPS
(N)3/4" MPR
REFER TO DETAIL 1
ON STRUCTURAL
DRAWING S-513 FOR
STACK SUPPORT
STRUCTURE
MAIN BAS PANEL
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
CONSULTANTS
321 4 5 6 7 8 9 10
NO. DESCRIPTION DATE
PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE
WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE
PROFESSIONAL ENGINEER
o n e e ig h th i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e i n c h o n e f o o t o n e a n d o n e h a lf i n c h e s o n e f o o t th re e i n c h e s o n e f o o t
MILLER-REMICK LLC
PROFESSIONAL ENGINEERENGINEER OF RECORD
M-R PROJECT NO:
Civil:
IMEG, CORP.
Fire & Life Safety:
STANTON ENGINEERING SERVICES, LLC
Hazardous Materials:
MABBETT & ASSOCIATES, INC.
Architectural:
OCULUS, INC.
Structural:
PROFESSIONAL ENGINEERING
CONSULTANTS, PA (PEC)
A u to d e s k D o c s /W ic h it a
C e n tr a liz e d E m e rg e n c y P o w e r/
-0
W ic h it a C e n tr a liz e d
E m e rg e n c y P o w e r-
M E
P -R
.r v t
/2
/2
:5
:0
A
M
M-302
MECHANICAL - BUILDING SECTION CONSTRUCT CENTRALIZED
EMERGENCY POWER SYSTEM
589A7-21-132
Project Director
2026-03-26 JK GDS
BID DOCUMENTS
FULLY SPRINKLERED
ROBERT J. DOLE VA MEDICAL CENTER
WICHITA, KANSAS
0499-0162
SCALE: 1/4" = 1'-0"A BUILDING SECTION - GENERATOR EXHAUST
1 CONTRACTOR SHALL SUPPORT THE GENERATOR RADIATOR EXHAUST PLENUM
INCLUDING DAMPERS FROM THE FLOOR. CONTRACTOR SHALL COORDINATION THE
DIMENSIONS OF THE PLENUM WITH THE APPROVED EQUIPMENT SUBMITTAL.
SHEET KEY NOTES:
GENERAL SHEET NOTES:
1. REFER TO DRAWING M-001 FOR MECHANICAL ABBREVIATIONS & SYMBOLS.
2. REFER TO DRAWING M-002 FOR MECHANICAL NOTES.
3. REFER TO DRAWINGS MP600 SERIES FOR FLOW DIAGRAMS
4. REFER TO DRAWINGS M-700 SERIES FOR EQUIPMENT SCHEDULES.
5. REFER TO DRAWINGS M-801 & M-802 FOR CONTROLS.
6. DO NOT SCALE THE DRAWINGS FOR EXACT DIMENSIONS. VERIFY ALL FIGURES,
File details come from the government source that posted it. Updated .