589A7-21-132 Wichita Bid Drawings 06_Fire Protection_Complete.pdf
PDF 1 MB Posted
- Solicitation number
- 36C25526R0125
About this file
This is a Fire Suppression System design drawing and specification document for a federal construction project at the Robert J. Dole VA Medical Center in Wichita, Kansas. The document provides comprehensive technical requirements, abbreviations, legends, general notes, and detailed plans for the installation of a new automatic dry-pipe fire suppression sprinkler system for the entire new building.
The project requires a complete, automatic dry-type sprinkler system designed and installed in accordance with NFPA 13 (2022), NFPA 101 (2021), IBC 2024, and VA-PG-18-10 Fire Protection Design Manual (November 2023). The system must be designed to cover all building areas with maximum coverage of 130 square feet per head for ordinary hazard occupancies and 100 square feet for extra hazard occupancies. Design criteria specify light hazard at 0.10 GPM/SF over 1,500 SF, ordinary hazard group-1 at 0.15 GPM/SF, ordinary hazard group-2 at 0.20 GPM/SF, and extra hazard group-1 at 0.30 GPM/SF over 2,500 SF. Pipe sizes 2 inches and smaller must be black steel schedule 40 with threaded connections; sizes 2.5 inches and larger must be black steel schedule 10 with grooved connections. All components must be UL-listed and FM-approved. The contractor is responsible for performing water flow tests, developing hydraulic calculations, preparing scaled working drawings, and commissioning the system in accordance with manufacturer and NFPA requirements. All work must be coordinated with other trades to avoid obstructions and maintain proper coverage, with the contractor bearing responsibility for adding heads as needed at no additional cost to the owner. The project includes detailed specifications for seismic bracing, pipe penetrations, hanger installation, and system testing and inspection requirements.
View the file
Other files
Show all 30
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
SPRINKLER PIPE
ELBOW
TEE
CHECK VALVE
CONTROL VALVE
WATERFLOW INDICATOR
BACKFLOW PREVENTER
RISER CHECK VALVE
ORDINARY HAZARD GROUP 1
ORDINARY HAZARD GROUP 2
EXTRA HAZARD GROUP 1
UPRIGHT SPRINKLER HEAD
FIRE DEPARTMENT CONNECTION
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
CONSULTANTS
321 4 5 6 7 8 9 10
NO. DESCRIPTION DATE
PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE
WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE
PROFESSIONAL ENGINEER
o n e e ig h th i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e i n c h o n e f o o t o n e a n d o n e h a lf i n c h e s o n e f o o t th re e i n c h e s o n e f o o t
STANTON ENGINEERING SERVICES
PROFESSIONAL ENGINEERENGINEER OF RECORD
M-R PROJECT NO:
Civil / Site Utility Engineering:
IMEG, CORP.
Fire & Life Safety:
STANTON ENGINEERING SERVICES
Hazardous Materials:
MABBETT & ASSOCIATES, INC.
Architect:
OCULUS, INC.
Structural:
PROFESSIONAL ENGINEERING
CONSULTANTS, PA (PEC)
A u to d e s k D o c s /W ic h it a
C e n tr a liz e d E m e rg e n c y P o w e r/
-1
-K
S
W ic h it a V
A M
C O
C U
L U
S C
E N
T R
A L -F
IR
E
-R
.r v t
/2
/2
:1
:0
P
M
FX001
CONSTRUCT CENTRALIZED
EMERGENCY POWER SYSTEM
589A7-21-132
Project Director
2026-03-26 KD AL
BID DOCUMENTS
FULLY SPRINKLERED
ROBERT J. DOLE VA MEDICAL CENTER
WICHITA, KANSAS
0499-0162
FIRE SUPPRESSION
ABBREVIATIONS, LEGEND
AND GENERAL NOTES
FIRE SUPPRESSION ABBREVIATIONS FIRE SUPPRESSION LEGEND
1. THE FIRE PROTECTION SCOPE OF WORK INVOLVES THE INSTALLATION OF A NEW, DRY-PIPE FIRE SUPPRESSION AUTOMATIC SPRINKLER SYSTEM FOR THE ENTIRE NEW BUILDING.
2. ALL AREAS ARE TO BE PROTECTED WITH AUTOMATIC SPRINKLER SYSTEMS UNLESS OTHERWISE NOTED.
3. SYSTEMS SHALL BE DESIGNED, INSTALLED AND TESTED IN ACCORDANCE WITH THE CONTRACT DOCUMENTS AS WELL AS THE FOLLOWING CODES AND STANDARDS:
A. CRITERIA IN VA-PG-18-10 FIRE PROTECTION DESIGN MANUAL (NOVEMBER 2023)
B. IBC - INTERNATIONAL BUILDING CODE, 2024
C. NFPA 13 - STANDARD FOR THE INSTALLATION OF SPRINKLER SYSTEMS, 2022 EDITION
D. NFPA 101 - LIFE SAFETY CODE, 2021 EDITION
E. NFPA 241 - STANDARD FOR SAFEGUARDING CONSTRUCTION, ALTERATION, AND DEMOLITION OPERATIONS, 2022 EDITION
4. PROVIDE A COMPLETE, AUTOMATIC DRY-TYPE SPRINKLER SYSTEM IN ACCORDANCE WITH NFPA 13 REQUIREMENTS AND VA STANDARDS IN ALL AREAS AS NOTED ON PLANS.
5. PROVIDE ALL EQUIPMENT, MATERIAL, LABOR, SUPERVISION, COSTS AND SERVICES REQUIRED TO INSTALL COMPLETE AND WORKING SYSTEMS INCLUDING ALL ITEMS AND APPURTENANCES NECESSARY, REASONABLY INCIDENTAL, OR CUSTOMERILY
INCLUDED, EVEN THOUGH EACH AND EVERY ITEM IS NOT SPECIFIED OR SHOWN.
6. PENETRATIONS OF WALLS OR FLOORS FOR SPRINKLER PIPING AND/OR EQUIPMENT SHALL BE PROPERLY SEALED AFTER INSTALLATIONS.
7. IN GENERAL, SPRINKLERS SHALL BE ARRANGED FOR A MAXIMUM COVERAGE NO GREATER THAN 130 SQUARE FEET PER HEAD FOR ORDINARY HAZARD OCCUPANCIES AND 100 SF FOR EXTRA HAZARD OCCUPANCIES. COORDINATE WITH OTHER DISCIPLINES TO
AVOID OBSTRUCTIONS SUCH AS LIGHTS, DIFFUSERS, ETC.
8. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO COORDINATE PIPING AND SPRINKLER HEADS FOR PROPER COVERAGE IN EACH AREA AND ADD ADDITIONAL HEADS TO OBTAIN PROPER COVERAGE AS REQUIRED BY VARIATIONS IN FIELD LOCATIONS AND OBSTRUCTIONS AT NO ADDITIONAL COST TO OWNER. OBTAIN FINAL APPROVED ARCHITECTURAL LAYOUTS BEFORE LAYING OUT WORKING DRAWINGS.
9. PAINT AND LABEL ALL NEW SPRINKLER PIPE IN ACCORDANCE WITH SPECIFICATION 21 13 13.
10. CONTRACTOR SHALL SEAL ALL PIPE WALL AND FLOOR PENETRATIONS IN FIRE RATED BARRIERS WITH A LISTED FIRE STOP SYSTEM. SEE ARCHITECTURAL LIFE SAFETY PLAN FOR LOCATIONS OF SMOKE AND FIRE RATED PARTITIONS AND BARRIERS.
11. COORDINATE SPRINKLER PIPE RUNS WITH DUCTWORK, PLUMBING PIPING, AND LIGHTS. MAINTAIN 4'' CLEAR ABOVE LIGHTS. DO NO INTERFERE WITH DUCT ACCESS DOORS.
12. PIPE SIZES 2” AND SMALLER SHALL BE BLACK STEEL SCHEDULE 40 WITH THREADED END CONNECTIONS. PIPE SIZES 2.5” AND LARGER SHALL BE BLACK STEEL SCHEDULE 10 WITH GROOVED CONNECTIONS. GROOVES IN SCHEDULE 10 PIPING SHALL BE ROLLED GROOVED ONLY. HANGERS SHALL BE IN ACCORDANCE WITH NFPA 13. SPRINKLERS IN AREAS WITHOUT CEILINGS SHALL HAVE ROUGH BRASS OR FACTORY STANDARD FINISH. ALL COMPONENTS SHALL BE UL LISTED AND FM APPROVED.
13. FLUSH, TEST, AND INSPECT WATER SUPPLY AND SPRINKLER SYSTEM IN ACCORDANCE WITH NFPA 13 AND 25. COMMISSION SYSTEM IN ACCORDANCE WITH MANUFACTURER, NFPA 13, COR, AND COMMISSIONING AGENT REQUIREMENTS. PROVIDE COPIES OF O&M MANUALS, CORRECTED SUBMITTALS, AS-BUILT SHOP DRAWINGS, AND TWO COPIES OF NFPA 25 TO OWNER, PROVIDE SYSTEM MAINTENANCE AND OPERATION INSTRUCTIONS TO OWNER'S PERSONNEL. SCHEDULE ACCEPTANCE TESTING TO BE WITNESSED BY CONTRACTING OFFICER'S REPRESENTATIVE (COR). PROVIDE CONTRACTOR'S CERTIFICATION AND TESTING PAPERWORK PER NFPA 13 AND 25.
14. HYDRAULICALLY DESIGN SYSTEM PER NFPA 13 AND IN ACCORDANCE WITH PROJECT SPECIFICATIONS AND VA FIRE PROTECTION DESIGN MANUAL. CALCULATED DEMAND INCLUDING HOSE STREAM REQUIREMENTS SHALL FALL NO LESS THAN 10 PERCENT BELOW THE AVAILABLE WATER SUPPLY CURVE. PROVIDE A NEW FLOW TEST IN ACCORDANCE WITH NFPA 13 AND NFPA 291 PROCEDURES. SUBMIT HYDRAULIC CALCULATIONS TO CONTRACTING OFFICER'S REPRESENTATIVE (COR).
15. PREPARE SCALED WORKING DRAWINGS IN ACCORDANCE WITH NFPA 13 SHOWING LAYOUT AND DETAILS OF SPRINKLER SYSTEM. SUBMIT DRAWINGS SHOWING LAYOUT TO CONTRACTING OFFICER'S REPRESENTATIVE (COR).
16. THE DESIGN CRITERIA FOR THE SPRINKLER SYSTEM SHALL BE IN ACCORDANCE WITH NFPA 13:
A. LIGHT HAZARD CLASSIFICATION: 0.10 GPM/SF DENSITY OVER 1500 SF FIRE AREA.
B. ORDINARY HAZARD GROUP-1 CLASSIFICATION: 0.15 GPM/SF DENSITY OVER 1500 SF FIRE AREA.
C. ORDINARY HAZARD GROUP-2 CLASSIFICATION: 0.20 GPM/SF DENSITY OVER 1500 SF FIRE AREA.
D. EXTRA HAZARD GROUP-1 CLASSIFICATION: 0.30 GPM/SF DENSITY OVER 2500 SF FIRE AREA.
17. WHERE STATIC PRESSURES EXCEED 100 PSI, SPRINKLERS IN A PENDENT POSITION SHALL HAVE A CUMULATIVE HORIZONTAL LENGTH OF UNSUPPORTED ARM OVERS, BRANCHLINE ENDS, OR SPRINKLER DROP SHALL NOT EXCEED 12 INCHES. IN ADDITION, EACH HANGER CLOSEST TO THE SPRINKLER SHALL BE OF A TYPE THAT PREVENTS UPWARD MOVEMENT OF PIPING.
18. CONTRACTOR TO ENSURE THAT ALL FIXED OBSTRUCTIONS OVER 4 FT IN WIDTH ARE PROVIDED WITH SPRINKLER PROTECTION UNDERNEATH IN ACCORDANCE WITH NFPA 13, 9.5.5.3.1. CONTRACTOR SHALL BE AWARE THAT THE BUILDING HAS EXTENSIVE UTILITY OBSTRUCTIONS THROUGHOUT AND THESE OBSTRUCTIONS MAY NOT ALL BE INDICATED ON THE PLANS HEREIN.
19. OPEN GRATE FLOORING OVER 4 FT IN WIDTH SHALL REQUIRE SPRINKLER PROTECTION BELOW THE GRATING IN ACCORDANCE WITH NFPA 13, 9.5.5.3.1.1.
20. CONTRACTOR SHALL BE RESPONSIBLE FOR PERFORMING A NEW WATER FLOW TEST PRIOR TO DEVELOPMENT OF SHOP DRAWINGS. CONTRACTOR'S HYDRAULIC CALCULATIONS SHALL INDICATE ALL HYDRAULIC NODES BACK TO THE TEST HYDRANT IN
ACCORDANCE WITH NFPA 13.
21. BUILDING WILL UTILIZE SEISMIC DESIGN CATEGORY C. FOLLOW NFPA 13 FOR SEISMIC BRACING REQUIREMENTS.
FIRE SUPPRESSION GENERAL NOTES
AAR
AHU
ALV
AS
BFP
BOR
CHV
CIS
CLG
COR
CV
DACT
DBA
DC
DD
DIA
DIM
DN
DT
EA
EAR
EB
EF
EH
EL
EMER
EQUIP
EST
ETR
EXIST
FA
FD
FDC
FE
FEC
FFE
FH
FHV
FLR
FM
FS
FT
GA
GC
GPM
GR
GF
HGT
HL
AUTOMATIC AIR RELEASE
AIR HANDLING UNIT
ALARM CHECK VALVE
AUTOMATIC SPRINKLER
BACK FLOW PREVENTER
BOTTOM OF RISER
CHECK VALVE
COMMON INTELLIGIBILITY SCORE
CEILING
CONTRACTING OFFICER'S REPRESENTATIVE
CONTROL VALVE
DIGITAL ALRM COMMUNICATOR TRANSMITTER
DECIBEL A-WEIGHTED
DIRECT CURRENT
DUCT SMOKE DETECTOR
DIAMETER
DIMENSION
DOWN/DROP NIPPLE
DRY PIPE VALVE TEMPERATURE
EACH
ELEVATOR ALTERNATE FLOOR RECALL
ELECTRIC BELL
EXHAUST FAN
EXTRA HAZARD
ELEVATION
EMERGENCY
EQUIPMENT
ELEVATOR SHUNT TRIP
EXISTING TO REMAIN
EXISTING
FIRE ALARM
FLOOR DRAIN
FIRE DEPARTMENT CONNECTION
FIRE EXTINGUISHER
FIRE EXTINGUISHER CABINET
FINISHED FLOOR ELEVATION
FIRE HAT
FIRE HOSE VALVE
FLOOR
FACTORY MUTUAL
FLOW SWITCH
FEET
GAUGE
GENERAL CONTRACTOR
GALLONS PER MINUTE
GENERATOR RUNNING
GENERATOR FAULT
HEIGHT
HI/LOW AIR SUPERVISORY
HT
ID
LH
LOC
MNS
OD
OH
PS
PSI
R
RCV
REQ
RM
RN
RPZ
S
SBV
SCHED
SCV
SD
SDC
SGV
SIM
SP
SPEC
SPKR
SP/ST
SQ
SR
SSI
ST
STOR
STS
SYST
TEMP
TOR
TS
TYP
UL
VAC
W/
WMG
W/O
WP
WS
ZCA
HEAT TRACING
INSIDE DIAMETER
LIGHT HAZARD
LOCAL OPERATING CONSOLE
MASS NOTIFICATION SYSTEM
OUTSIDE DIAMETER
ORDINARY HAZARD
PRESSURE SWITCH
POUNDS PER SQUARE INCH
RISER
RISER CONTROL VALVE
REQUIRED
ROOM
RISER NIPPLE
REDUCED PRESSURE ZONE
SUPPLY
SUPERVISED BUTTERFLY VALVE
SCHEDULE
SUPERVISED CONTROL VALVE
SMOKE DETECTOR
SMOKE DAMPER CONTROL
SUPERVISED GATE VALVE
SIMILAR
SPEAKER
SPECIFICATION
SPRINKLER
SPEAKER/STROBE
SQUARE
SLEEPING ROOM
SECURITY SYSTEM INTERFACE
STROBE
STORAGE
SHUNT TRIP SUPERVISION
SYSTEM
TEMPERATURE
TOP OF RISER
TAMPER SWITCH
TYPICAL
UNDERWRITERS' LABORATORY
VOLT, ALTERNATING CURRENT
WITH
WATER MOTOR GONG
WITHOUT
WEATHERPROOF
WET SYSTEM
ZONE CONTROL ASSEMBLY
1 2 3 4
A
C
B
GENERATOR
ROOM
FIRE RISER ROOM
FDC
6" INCOMING
WATER SERVICE
6"
6"
6"
6"
F7
FX101
BACKFLOW
PREVENTER
NITROGEN
GENERATOR
SWITCHGEAR
ROOM
GROUND FLOOR
0"
ROOF
19'-6"
6"
6"
6"
BACKFLOW
PREVENTER
DRY PIPE
VALVE
FIRE
DEPARTMENT
CONNECTION
INCOMING
SERVICE LINE
CHECK VALVE
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
CONSULTANTS
321 4 5 6 7 8 9 10
NO. DESCRIPTION DATE
PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE
WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE
PROFESSIONAL ENGINEER
o n e e ig h th i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e i n c h o n e f o o t o n e a n d o n e h a lf i n c h e s o n e f o o t th re e i n c h e s o n e f o o t
STANTON ENGINEERING SERVICES
PROFESSIONAL ENGINEER
NORTH
ENGINEER OF RECORD
M-R PROJECT NO:
Civil / Site Utility Engineering:
IMEG, CORP.
Fire & Life Safety:
STANTON ENGINEERING SERVICES
Hazardous Materials:
MABBETT & ASSOCIATES, INC.
Architect:
OCULUS, INC.
Structural:
PROFESSIONAL ENGINEERING
CONSULTANTS, PA (PEC)
A u to d e s k D o c s /W ic h it a
C e n tr a liz e d E m e rg e n c y P o w e r/
-1
-K
S
W ic h it a V
A M
C O
C U
L U
S C
E N
T R
A L -F
IR
E
-R
.r v t
/2
/2
:1
:2
P
M
FX101
CONSTRUCT CENTRALIZED
EMERGENCY POWER SYSTEM
589A7-21-132
Project Director
2026-03-26 KD AL
BID DOCUMENTS
FULLY SPRINKLERED
ROBERT J. DOLE VA MEDICAL CENTER
WICHITA, KANSAS
0499-0162
FIRE SUPPRESSION
GROUND FLOOR PLAN
GENERAL NOTES
A. PROVIDE FM APPROVED QUICK RESPONSE SPRINKLERS IN THE
FIRE RISER ROOM AND SWITCH GEAR ROOM, AND STANDARD
RESPONSE SPRINKLERS IN ALL OTHER AREAS.
B. IN UNFINISHED ROOMS WITH NO CEILING PROVIDE UPRIGHT TYPE
SPRINKLER HEADS. COORDINATE HEAD LOCATIONS WITH HVAC
CONTRACTOR TO MAINTAIN ADEQUATE COVERAGE ABOVE AND
BELOW LARGE DUCTWORK AND OTHER OBSTRUCTIONS AS
GOVERNED BY NFPA 13.
KEYED NOTES
1/4" = 1'-0"F1
FIRE SUPPRESSION GROUND FLOOR
3/8" = 1'-0"F7
FIRE RISER ROOM ELEVATION VIEW
1. PROVIDE SPRINKLER COVERAGE WITHIN THE ROOM AND SPACE
ABOVE THE ROOM AT CEILING LEVEL. SPRINKLER COVERAGE
ABOVE ROOM WILL BE CONSIDERED EXTRA HAZARD GROUP 1.
BEAM CLAMP HANGER
(FOR BAR JOIST)
I-BEAM CLAMP HANGER
ARMOVER SPRIG UP
I-BEAM CLAMP HANGER
1" PIPE
1" PIPE
BRANCH
LINE
BRANCH
LINE
REDUCING
COUPLING
REDUCING
COUPLING
CEILING
SPRINKLER
HEAD
SPRINKLER
HEAD
ALL THREAD ROD
ALL THREAD ROD
SPLIT RING
HANGER
SPLIT RING
HANGER
BEAM CLAMP
WITH LOCKNUT
BEAM CLAMP
WITH LOCKNUT
ALL THREAD ROD
SPLIT RING
HANGER
CONCRETE SLAB
DROP-IN
ANCHOR
LONITUDINAL BRACE (SIDE VIEW)
LATERAL BRACE (FRONT VIEW)
FOUR WAY RISER BRACE (TOP VIEW)
BRACE PIPE
BRACE PIPE
PIPE CLAMP FOR
SWAY BRACE
1" PIPE
REDUCING COUPLING
CEILING
SPRINKLER HEAD
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
CONSULTANTS
321 4 5 6 7 8 9 10
NO. DESCRIPTION DATE
PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE
WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE
PROFESSIONAL ENGINEER
o n e e ig h th i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e i n c h o n e f o o t o n e a n d o n e h a lf i n c h e s o n e f o o t th re e i n c h e s o n e f o o t
STANTON ENGINEERING SERVICES
PROFESSIONAL ENGINEERENGINEER OF RECORD
M-R PROJECT NO:
Civil / Site Utility Engineering:
IMEG, CORP.
Fire & Life Safety:
STANTON ENGINEERING SERVICES
Hazardous Materials:
MABBETT & ASSOCIATES, INC.
Architect:
OCULUS, INC.
Structural:
PROFESSIONAL ENGINEERING
CONSULTANTS, PA (PEC)
A u to d e s k D o c s /W ic h it a
C e n tr a liz e d E m e rg e n c y P o w e r/
-1
-K
S
W ic h it a V
A M
C O
C U
L U
S C
E N
T R
A L -F
IR
E
-R
.r v t
/2
/2
:1
:1
P
M
FX501
CONSTRUCT CENTRALIZED
EMERGENCY POWER SYSTEM
589A7-21-132
Project Director
2026-03-26 KD AL
BID DOCUMENTS
FULLY SPRINKLERED
ROBERT J. DOLE VA MEDICAL CENTER
WICHITA, KANSAS
0499-0162
FIRE SUPPRESSION
DETAILS
NTSF1
SPRINKLER ARMOVER, SPRIG, AND
HANGER DETAILS
NTSF4
SEISMIC/EARTHQUAKE
NTSD1
SEMI-RECESSED SPRINKLER HEAD
DETAIL
| FX001 - FIRE SUPPRESSION ABBREVIATIONS, LEGEND AND GENERAL NOTES |
| FX101 - FIRE SUPPRESSION GROUND FLOOR PLAN |
| FX501 - FIRE SUPPRESSION DETAILS |
File details come from the government source that posted it. Updated .