4-C04 - Operations Facilities Expansion - Bid Specs - Vol II.pdf

PDF 5 MB Posted

Attached to
Oakbrook Center for Early Education
Solicitation number
US.252787
Issued by
Berks County, Reese CDP, Pennsylvania

About this file

This document is a technical specifications volume for the Operations Facilities Expansion project at the City of Lancaster Department of Public Works, located at 150 Pitney Road, Lancaster, Pennsylvania. The specifications cover Divisions 21 through 28, addressing fire suppression systems, plumbing, heating, ventilating and air-conditioning (HVAC), electrical, communications, and electronic safety and security systems. The project number is BH 25-061, with specifications dated September 8, 2026. The document provides detailed technical requirements for materials, equipment, installation procedures, and quality assurance standards across multiple building systems, including sprinkler systems compliant with NFPA 13, domestic water piping systems, sanitary waste systems, HVAC equipment and ductwork, low-voltage electrical systems, structured cabling, access control, and fire detection and alarm systems.

The specifications establish comprehensive product standards, installation requirements, and testing procedures for all contracted work. Materials must comply with applicable ASTM, ASME, NSF, UL, and other industry standards, with particular emphasis on potable water system components meeting NSF 61 and NSF 372 certification requirements. The document mandates submittal of product data, shop drawings, and quality assurance documentation prior to installation. Testing, adjusting, and balancing procedures for HVAC systems must follow ASHRAE Standard 111, with final reports submitted in I-P units. Pipe hangers, supports, and hangers must comply with MSS SP-58 standards, and all work must achieve specified pressure ratings, temperature tolerances, and sealing requirements. The specifications include detailed execution sections requiring installation per manufacturer instructions, independent structural support systems, vibration isolation where applicable, and comprehensive identification and labeling protocols for all piping and equipment systems.

View the file

Other files

File Type Posted
34-25061 - Addendum 3 Arch-struct-MEP summary.pdf PDF
3-C05 - Site Civil Specifications Combined.pdf PDF
15-2026-10-06 - ES Addendum 1.pdf PDF
35-25061 - Addendum 3 Arch-struct-MEP summary.pdf PDF
10-C08 - Construction Plan.pdf PDF
Demolition.dwg DWG drawing
17-323113 - CHAIN LINK FENCES AND GATES.pdf PDF
321723 - PAVEMENT MARKINGS.pdf PDF
6-C10 - Geotechnical Report.pdf PDF
42-312000 - EARTH MOVING.pdf PDF
PG.dwg DWG drawing
EG.dwg DWG drawing
49-B861-26-01 BidTabulationReport.xlsx XLSX spreadsheet
24-2026-10-14 - CD Addendum 2.pdf PDF
25-061_Pitney Rd Warehouse_Arch-Structural-MEP Drawings_Addendum 3.pdf PDF
28-312000 - EARTH MOVING.pdf PDF
12-25061 - Addendum 1.pdf PDF
48-CD-18 UTILITY PLAN.pdf PDF
9-C06 - Pitney Rd Warehouse Arch-Structural-MEP Bid Set.pdf PDF
32-25-061 Pitney Rd Warehouse Arch-Structural-MEP Drawings Addendum 3.pdf PDF
37-133418-USER-Post Frame Building Systems-10-23-2026.pdf PDF
22-B861-26-01 ADDENDUM 2 - MULTIPRIME Operations Facility Expansion Project.docx DOCX document
25-2026-10-14 - ES Addendum 2.pdf PDF
18-329113 - SOIL PREPARATION.pdf PDF
41-2026-10-29 - ES Addendum 4.pdf PDF
ES.dwg DWG drawing
29-321723 - PAVEMENT MARKINGS.pdf PDF
25061 - Addendum 3_ Arch-struct-MEP summary.pdf PDF
44-B861-26-01 ADDENDUM 4 - MULTIPRIME Operations Facility Expansion Project.docx DOCX document
30-2026-10-23 - ES Addendum 3.pdf PDF
Easements.dwg DWG drawing
Landscape.dwg DWG drawing
16-25-061 Pitney Rd Warehouse Arch-Structural-MEP Addendum 1.pdf PDF
20-City of Lancaster 150 Pitney Road Phase 1 ESA Sept2026.pdf PDF
33-Addendum 03 Arch Front End Specs.pdf PDF
13-133419-RIB- Pre-Engineered Metal Building Systems-09-17-2026.pdf PDF
11-B861-26-01 FINAL - MULTIPRIME Operations Facility Expansion Project.docx DOCX document
26-Pre-Bid Attendees Ops Center Expansion 10072026.pdf PDF
40-2026-10-29 - CD Addendum 4.pdf PDF
38-25061 - Addendum 4 Arch-struct-MEP summary.pdf PDF
2026-10-23 - ES Addendum 3.pdf PDF
Addendum 03_Arch & Front End Specs.pdf PDF
39-25-061 Pitney Rd Warehouse Arch-Structural-MEP Drawings Addendum 4.pdf PDF
45-FINAL QA Report.pdf PDF
2026-10-23 - CD Addendum 3.pdf PDF
47-CD-17 UTILITY PLAN.pdf PDF
7-C09 - Fill Assessment Summary.pdf PDF
31-2026-10-23 - CD Addendum 3.pdf PDF
5-C03 - Operations Facilities Expansion - Bid Specs - Vol I.pdf PDF
312000 - EARTH MOVING.pdf PDF
Show 40 more

Latest 50 of 63 listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

250 Harrisburg Ave

Lancaster, PA 17603

OPERATIONS FACILITIES EXPANSION

CITY OF LANCASTER

DEPARTMENT OF PUBLIC WORKS

TECHNICAL SPECIFICATIONS

VOLUME II: DIVISIONS 21 - 28

OPERATIONS FACILITIES EXPANSION

150 PITNEY ROAD

LANCASTER, PA 17603

Project No. 25-061 September 8, 2026

Operations Facilities Expansion BH 25-061 City of Lancaster - Department of Public Works

TABLE OF CONTENTS - VOLUME II 000110 - 1

SECTION 000110 - TABLE OF CONTENTS - VOLUME II

PROCUREMENT AND CONTRACTING REQUIREMENTS

VOLUME II - SPECIFICATIONS

VOLUME II

DIVISION 21 -- FIRE SUPPRESSION

210500 - COMMON WORK RESULTS FOR FIRE SUPPRESSION

210523 - GENERAL-DUTY VALVES FOR WATER-BASED FIRE-SUPPRESSION PIPING

210553 - IDENTIFICATION FOR FIRE SUPPRESSION PIPING AND EQUIPMENT

210719 - FIRE SUPPRESSION PIPING INSULATION

211300 - FIRE-SUPPRESSION SPRINKLER SYSTEMS

DIVISION 22 -- PLUMBING

220513 - COMMON MOTOR REQUIREMENTS FOR PLUMBING EQUIPMENT

220517 - SLEEVES AND SLEEVE SEALS FOR PLUMBING PIPING

220519 - METERS AND GAUGES FOR PLUMBING PIPING

220523 - GENERAL-DUTY VALVES FOR PLUMBING PIPING

220529 - HANGERS AND SUPPORTS FOR PLUMBING PIPING AND EQUIPMENT

220553 - IDENTIFICATION FOR PLUMBING PIPING AND EQUIPMENT

220719 - PLUMBING PIPING INSULATION

221005 - PLUMBING PIPING

221119 - DOMESTIC WATER PIPING SPECIALTIES

221123 - DOMESTIC WATER PUMPS

221319 - SANITARY WASTE PIPING SPECIALTIES

221323 - SANITARY WASTE INTERCEPTORS

223000 - PLUMBING EQUIPMENT

224000 - PLUMBING FIXTURES

DIVISION 23 -- HEATING, VENTILATING, AND AIR-CONDITIONING (HVAC)

230130.51 - HVAC AIR-DISTRIBUTION SYSTEM CLEANING

230513 - COMMON MOTOR REQUIREMENTS FOR HVAC EQUIPMENT

230529 - HANGERS AND SUPPORTS FOR HVAC PIPING AND EQUIPMENT

230548 - VIBRATION AND SEISMIC CONTROLS FOR HVAC - MASON

230553 - IDENTIFICATION FOR HVAC PIPING AND EQUIPMENT

230593 - TESTING, ADJUSTING, AND BALANCING FOR HVAC

230713 - DUCT INSULATION

230913 - INSTRUMENTATION AND CONTROL DEVICES FOR HVAC

232300 - REFRIGERANT PIPING

233100 - HVAC DUCTS AND CASINGS

233300 - AIR DUCT ACCESSORIES

233416 - CENTRIFUGAL HVAC FANS

233439 - HIGH-VOLUME, LOW-SPEED PROPELLER FANS

233700 - AIR OUTLETS AND INLETS

235533 - FUEL-FIRED UNIT HEATERS

TABLE OF CONTENTS - VOLUME II 000110 - 2

238126.13 - SMALL-CAPACITY SPLIT-SYSTEM AIR CONDITIONERS

DIVISION 26 -- ELECTRICAL

260519 - LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES

260526 - GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS

260529 - HANGERS AND SUPPORTS FOR ELECTRICAL SYSTEMS

260533.13 - CONDUIT FOR ELECTRICAL SYSTEMS

260533.16 - BOXES FOR ELECTRICAL SYSTEMS

260533.23 - SURFACE RACEWAYS FOR ELECTRICAL SYSTEMS

260553 - IDENTIFICATION FOR ELECTRICAL SYSTEMS

260923 - LIGHTING CONTROL DEVICES

262100 - LOW-VOLTAGE ELECTRICAL SERVICE ENTRANCE

262416 - PANELBOARDS

262726 - WIRING DEVICES

262816.13 - ENCLOSED CIRCUIT BREAKERS

262816.16 - ENCLOSED SWITCHES

263213 - ENGINE GENERATORS

263600 - TRANSFER SWITCHES

265100 - INTERIOR LIGHTING

265600 - EXTERIOR LIGHTING

DIVISION 27 -- COMMUNICATIONS

270529 - HANGERS AND SUPPORTS FOR COMMUNICATIONS SYSTEMS

270533.13 - CONDUIT FOR COMMUNICATIONS SYSTEMS

271000 - STRUCTURED CABLING

DIVISION 28 -- ELECTRONIC SAFETY AND SECURITY

281000 - ACCESS CONTROL

284600 - FIRE DETECTION AND ALARM

Common Work Results for Fire Suppression 210500 - 3

SECTION 210500

COMMON WORK RESULTS FOR FIRE SUPPRESSION

PART 1 GENERAL

1.1 SUBMITTALS

A. Product Data: Provide manufacturer's catalog information. Indicate valve data and ratings.

B. Shop Drawings: Indicate pipe materials used, jointing methods, supports, and floor and wall penetration seals. Indicate installation, layout, weights, mounting and support details, and piping connections.

1.2 WARRANTY

A. See Section 017800 - Closeout Submittals for additional warranty requirements.

PART 2 PRODUCTS

2.1 GENERAL REQUIREMENTS

A. Sprinkler-based System:

1. Comply with NFPA 13.

2. See Section 211300.

B. Welding Materials and Procedures: Comply with ASME BPVC-IX.

C. Provide system pipes, fittings, sleeves, escutcheons, seals, and other related accessories.

2.2 ABOVE GROUND PIPING

A. Steel Pipe: ASTM A795 Schedule 10, ASME B36.10M Schedule 5, ASTM A53 Schedule 40, ASTM A135/A135M Schedule 10, ASTM A135/A135M UL listed light wall type, or ASTM A795 Schedule 40, black.

1. Steel Fittings: ASME B16.9 wrought steel, buttwelded, ASME B16.25 buttweld ends, ASTM A234/A234M wrought carbon steel or alloy steel, ASME B16.5 steel flanges and fittings, or ASME B16.11 forged steel socket welded and threaded.

2. Malleable Iron Fittings: ASME B16.3, threaded fittings and ASTM A47/A47M.

3. Mechanical Grooved Couplings: Malleable iron housing clamps to engage and lock, "C" shaped elastomeric sealing gasket, steel bolts, nuts, and washers; galvanized for galvanized pipe.

4. Mechanical Formed Fittings: Carbon steel housing with integral pipe stop and O-ring pocked and O-ring, uniformly compressed into permanent mechanical engagement onto pipe.

B. Ductile Iron Pipe: AWWA C151/A21.51.

2.3 PIPE SLEEVES

A. Vertical Piping:

1. Sleeve Length: 1 inch (25 mm) above finished floor.

2. Provide sealant for watertight joint.

B. Plastic, Sheet Metal, or Moisture-Resistant Fiber: Pipe passing through interior walls, partitions, and floors, unless steel or brass sleeves are specified below.

2.4 PIPE SLEEVE-SEAL SYSTEMS

A. Mechanical Sleeve-Seals:

1. Modular, Interlocking Link Type: Elastomer-based interlocking links continuously fill annular space between individual pipe and wall-sleeve, wall, or casing opening. Provide with manufacturer's pressure plates and bolts.

Common Work Results for Fire Suppression 210500 - 3

2. Compression Ring Type: Elastomer-based compression ring continuously fills annular space between individual pipe and wall-sleeve, wall, or casing opening. Rings may be solid, split, or segmented. Provide manufacturer's compression plates and bolts.

3. Compression Disk Type: Elastomer-based, multi-opening compression disk for sealing groups of pipes; disk continuously fills annular space between pipes, wall-sleeve, wall, or casing opening. Provide manufacturer's compression plates and bolts.

4. Watertight seal between pipe and wall-sleeve, wall or casing opening.

5. Size and select seal component materials in accordance with service requirements.

6. Service Requirements:

a. Underground, buried, and wet conditions.

B. Wall Sleeve: PVC material with waterstop collar, and nailer end caps.

C. Sleeve-Forming Disk: Nonconductive plastic-based material, 3 inch (76.2 mm) thick.

D. Pipeline-Casing Seals:

1. End Seals: 1/8 inch (3.1 mm), pull-on type, rubber or synthetic rubber based.

2.5 ESCUTCHEONS

A. Material:

1. Metals and Finish: Comply with ASME A112.18.1.

B. Construction:

1. One-piece for mounting on chrome-plated tubing or pipe and one-piece or split-pattern type elsewhere.

2. Internal spring tension devices or setscrews to maintain a fixed position against a surface.

2.6 PIPE HANGERS AND SUPPORTS

A. Hangers for Pipe Sizes 1/2 to 1-1/2 inch (15 to 40 mm): Malleable iron, adjustable swivel, split ring.

B. Hangers for Pipe Sizes 2 inches (50 mm) and Over: Carbon steel, adjustable, clevis.

C. Nonmetallic Piping Hangers:

D. Wall Support for Pipe Sizes to 3 inches (80 mm): Cast iron hook.

2.7 EXPANSION JOINTS AND LOOPS - HOSE AND BRAID

A. Provide flexible loops with two flexible sections of hose and braid, two 90-degree elbows, and

180-degree return with support bracket and air release or drain plug.

2.8 MECHANICAL COUPLINGS

A. Rigid Mechanical Couplings for Grooved Joints:

1. Dimensions and Testing: Comply with AWWA C606.

2. Minimum Working Pressure: 300 psig (2065 kPa).

3. Housing Material: Fabricate of ductile iron complying with ASTM A536.

4. Housing Coating: Factory applied orange enamel.

5. Gasket Material: EPDM suitable for operating temperature range from minus 30 degrees

F (minus 34 degrees C) to 230 degrees F (110 degrees C).

6. Bolts and Nuts: Hot-dipped-galvanized or zinc-electroplated steel.

2.9 PIPING SPECIALTIES

A. Wet Pipe Sprinkler Alarm Valve: Check type valve with divided seat ring, rubber-faced clapper to automatically actuate water motor alarm, pressure retard chamber and variable pressure trim with the following additional capabilities and features:

1. Activate electric alarm.

Common Work Results for Fire Suppression 210500 - 3

2. Test and drain valve.

3. Replaceable internal components without removing valve from installed position.

B. Preaction Valve:

C. Auxiliary Drains: Condensate collection drain for each section of trapped pipe in preaction or dry fire protection system.

D. Air Venting Valves:

E. Backflow Preventer: Reduced-pressure principle valve assembly backflow preventer with drain and OS & Y gate valve on each end.

F. Water Motor Alarm: Hydraulically operated impeller type alarm with aluminum alloy chrome-plated gong and motor housing, nylon bearings, and inlet strainer.

G. Water Flow Switch: Vane-type switch for mounting horizontally or vertically, with two contacts; rated 10 A at 125 VAC and 2.5 A at 24 VDC.

H. Fire Department Connections:

1. Type: Free standing made of corrosion-resistant metal complying with UL 405.

a. Sleeve: Brass, 18-inch (460 mm) height.

2.10 PRESSURE GAUGES

A. Pressure Gauges: ASME B40.100, UL 393 drawn steel case, phosphor bronze bourdon tube, rotary brass movement, brass socket, with front recalibration adjustment, black scale on white background.

PART 3 EXECUTION

3.1 INSTALLATION

A. Install sprinkler system and service main piping, hangers, and supports in accordance with

NFPA 13.

B. Route piping in orderly manner, plumb and parallel to building structure. Maintain gradient.

C. Pipe Hangers and Supports:

1. Install hangers to provide minimum 1/2 inch (15 mm) space between finished covering and adjacent work.

END OF SECTION

General-Duty Valves for Water-Based Fire-Suppression Piping 210523 - 1

SECTION 210523

GENERAL-DUTY VALVES FOR WATER-BASED FIRE-SUPPRESSION PIPING

PART 1 GENERAL

1.1 SUBMITTALS

A. Product Data: Provide data on valves including manufacturers catalog information. Submit performance ratings, rough-in details, weights, support requirements, and piping connections.

PART 2 PRODUCTS

2.1 GENERAL REQUIREMENTS

A. Valve-End Connections:

1. Flanges on Iron Valves: ASME B16.1 or ASME B16.42.

2. Threaded Ends: ASME B1.20.1.

3. Grooved Ends: AWWA C606.

B. Valve Pressure Ratings: Not less than minimum pressure rating indicated or higher as required.

C. Valve Sizes: Same as upstream piping unless otherwise indicated.

2.2 SWING CHECK VALVES

A. UL 312 and FM 1210 listed.

B. Minimum Pressure Rating: 175 psig (1200 kPa).

C. Body Material: Cast or ductile iron.

D. Clapper: Bronze, EPDM-coated ductile iron, or stainless steel.

E. Seat: Bronze or EPDM-coated bronze.

F. End Connections: Flanged.

PART 3 EXECUTION

3.1 INSTALLATION

A. Install valves in accessible locations to allow for operation, inspections, tests, and maintenance.

B. Install listed valves in accordance with their listing.

C. Install valves in accordance with manufacturer's instructions.

D. Support valves independently of adjacent piping.

E. Install valves in horizontal piping with stem at or above pipe center.

F. Position valves to allow full actuator movement.

G. Install OS&Y valves with full clearance for rising stem. Install surrounding components so they do not interfere with nor are they impacted by full extension of rising stem.

H. Install supervised shutoff valves in supervised-open position.

I. Install permanent identification signs indicating portion of system controlled by each shutoff valve.

J. Install threaded-end valves with unions upstream and downstream.

Identification for Fire Suppression Piping and Equipment 210553 - 1

SECTION 210553

IDENTIFICATION FOR FIRE SUPPRESSION PIPING AND EQUIPMENT

PART 2 PRODUCTS

1.1 IDENTIFICATION APPLICATIONS

A. Automatic Controls: Tags.

B. Control Panels: Nameplates.

C. Valves: Nameplates and ceiling tacks where above lay-in ceilings.

1.2 NAMEPLATES

A. Description: Laminated three-layer plastic with engraved letters.

1.3 TAGS

A. Plastic Tags: Laminated three-layer plastic with engraved black letters on light contrasting background color. Tag size minimum 1-1/2 inch (40 mm) diameter.

B. Metal Tags: Brass with stamped letters; tag size minimum 1-1/2 inch (40 mm) diameter with smooth edges.

1.4 CEILING TACKS

A. Description: Steel with 3/4 inch (20 mm) diameter color coded head.

PART 3 EXECUTION

2.1 INSTALLATION

A. Install nameplates with corrosive-resistant mechanical fasteners, or adhesive. Apply with sufficient adhesive to ensure permanent adhesion and seal with clear lacquer.

B. Install tags with corrosion resistant chain.

Fire Suppression Piping Insulation 210719 - 1

SECTION 210719

FIRE SUPPRESSION PIPING INSULATION

PART 2 PRODUCTS

1.1 REGULATORY REQUIREMENTS

A. Surface Burning Characteristics: Flame spread index/Smoke developed index of 25/50, maximum, when tested in accordance with ASTM E84 or UL 723.

1.2 GLASS FIBER

A. Insulation: ASTM C547 and ASTM C795; rigid, preformed pipe insulation, noncombustible.

1. K (Ksi) Value: 0.24 at 75 degrees F (0.035 at 24 degrees C).

2. Maximum Service Temperature: 850 degrees F (454 degrees C).

3. Maximum Moisture Absorption: 0.2 percent by volume.

1.3 FLEXIBLE ELASTOMERIC CELLULAR INSULATION

A. Insulation: Preformed flexible elastomeric cellular rubber insulation complying with ASTM

C534/C534M, Grade 1; use molded tubular material wherever possible.

1. Minimum Service Temperature: Minus 40 degrees F (Minus 40 degrees C).

2. Maximum Service Temperature: 220 degrees F (104 degrees C).

3. Connection: Waterproof vapor barrier adhesive.

PART 3 EXECUTION

2.1 INSTALLATION

A. Install in accordance with manufacturer's instructions.

B. Exposed Piping: Locate insulation and cover seams in least visible locations.

Fire-Suppression Sprinkler Systems 211300 - 2

SECTION 211300

FIRE-SUPPRESSION SPRINKLER SYSTEMS

PART 1 GENERAL

1.1 SUBMITTALS

A. Product Data: Provide data on sprinklers, valves, and specialties, including manufacturers catalog information. Submit performance ratings, rough-in details, weights, support requirements, and piping connections.

B. Shop Drawings:

1. Indicate hydraulic calculations, detailed pipe layout, hangers and supports, sprinklers, components, and accessories. Indicate system controls.

C. Designer's qualification statement.

1.2 QUALITY ASSURANCE

A. Comply with FM (AG) requirements.

PART 2 PRODUCTS

2.1 SPRINKLER SYSTEM

A. Sprinkler System: Provide coverage for entire building.

B. Occupancy: Light hazard; comply with NFPA 13.

C. Water Supply: Determine volume and pressure from water flow test data.

D. Storage Cabinet for Spare Sprinklers and Tools: Install adjacent to alarm valve.

2.2 SPRINKLERS

A. Suspended Ceiling Type: Semi-recessed pendant type with matching push on escutcheon plate.

1. Response Type: Quick.

2. Coverage Type: Standard.

3. Fusible Link: Fusible solder link type temperature rated for specific area hazard.

B. Sidewall Type: Semi-recessed horizontal sidewall type with matching push on escutcheon plate.

1. Response Type: Quick.

2. Coverage Type: Standard.

3. Fusible Link: Fusible solder link type temperature rated for specific area hazard.

C. Storage Sprinklers: Pendant type with guard.

1. Response Type: Standard.

2. Coverage Type: Standard.

3. Fusible Link: Fusible solder link type temperature rated for specific area hazard.

D. Guards: Finish to match sprinkler finish.

E. Spray Nozzles: Brass with solid cone discharge, 30 degrees of arc with blow-off dust cap.

F. Spare Sprinkler Cabinets:

1. General: Provide wall-mounted cabinet; size as required to house spare sprinklers and sprinkler wrenches in types and quanitities in accordance with NFPA 13.

2. Material: Steel.

3. Finish: Red enamel, inside and out.

Fire-Suppression Sprinkler Systems 211300 - 2

2.3 PIPING SPECIALTIES

A. Wet Pipe Sprinkler Alarm Valve: Check type valve with divided seat ring, rubber-faced clapper to automatically actuate water motor alarm, pressure retard chamber and variable pressure trim with the following additional capabilities and features:

B. Flooding Deluge Valve: Gate type valve with rubber faced disc actuated manually with water motor alarm and electric alarm, with alarm testing trim.

C. Preaction Valve:

1. Operated by detection system listed for releasing service and independent of building fire alarm system with provisions for local, manual, and indicated remote releases.

D. Backflow Preventer: Reduced pressure principle valve assembly backflow preventer with drain and OS & Y gate valve on each end.

E. Test Connections:

1. Inspector's Test Connection for Preaction Systems:

a. Provide test connections approximately 6 ft (2 m) above floor for each or portion of each sprinkler system equipped with an alarm device, located at the most remote part of each system.

2. Backflow Preventer Test Connection:

F. Water Motor Alarm: Hydraulically operated impeller type alarm with aluminum alloy chrome plated gong and motor housing, nylon bearings, and inlet strainer.

G. Electric Alarm: Electrically operated chrome plated gong with pressure alarm switch.

H. Water Flow Switch: Vane type switch for mounting horizontal or vertical, with two contacts;

rated 10 amp at 125 volt AC and 2.5 amp at 24 volt DC.

I. Fire Department Connections:

1. Type: Free standing made of corrosion resistant metal complying with UL 405.

a. Sleeve: Brass, 18 inches (460 mm) height.

2.4 PREACTION VALVE CONTROL PANEL

A. Provide a modular type control panel for electrically operated detection and extinguishing systems for each preaction valve.

PART 3 EXECUTION

3.1 INSTALLATION

A. Install in accordance with referenced NFPA design and installation standard.

B. Install equipment in accordance with manufacturer's instructions.

C. Flush entire piping system of foreign matter.

D. Hydrostatically test entire system.

E. Require test be witnessed by Fire Marshal.

Common Motor Requirements for Plumbing Equipment 220513 - 1

SECTION 220513

COMMON MOTOR REQUIREMENTS FOR PLUMBING EQUIPMENT

PART 1 GENERAL

1.1 SUBMITTALS

A. Product Data: Provide wiring diagrams with electrical characteristics and connection requirements.

1.2 QUALITY ASSURANCE

A. Comply with NFPA 70.

B. Products Requiring Electrical Connection: Listed and classified by Underwriters Laboratories

Inc. as suitable for the purpose specified and indicated.

1.3 WARRANTY

A. See Section 017800 - Closeout Submittals for additional warranty requirements.

PART 2 PRODUCTS

2.1 GENERAL CONSTRUCTION AND REQUIREMENTS

A. Electrical Service:

1. Motors 1/2 HP and Smaller: 115 volts, single phase, 60 Hz.

B. Construction:

1. Open drip-proof type except where specifically noted otherwise.

2. Design for continuous operation in 104 degrees F (40 degrees C) environment.

3. Design for temperature rise in accordance with NEMA MG 00001 limits for insulation class, service factor, and motor enclosure type.

C. Visible Nameplate: Indicating motor horsepower, voltage, phase, cycles, RPM, full load amps, locked rotor amps, frame size, manufacturer's name and model number, service factor, power factor, efficiency.

D. Wiring Terminations:

1. Provide terminal lugs to match branch circuit conductor quantities, sizes, and materials indicated. Enclose terminal lugs in terminal box sized to NFPA 70, threaded for conduit.

2. For fractional horsepower motors where connection is made directly, provide threaded conduit connection in end frame.

2.2 APPLICATIONS

Sleeves and Sleeve Seals for Plumbing Piping 220517 - 2

SECTION 220517

SLEEVES AND SLEEVE SEALS FOR PLUMBING PIPING

PART 1 GENERAL

1.1 SUBMITTALS

A. Shop Drawings: Indicate pipe materials used, jointing methods, supports, floor and wall penetration seals. Indicate installation, layout, weights, mounting and support details, and piping connections.

1.2 QUALITY ASSURANCE

1.3 WARRANTY

A. See Section 017800 - Closeout Submittals, for additional warranty requirements.

PART 2 PRODUCTS

2.1 PIPE SLEEVES

A. Vertical Piping:

1. Sleeve Length: 1 inch (25 mm) above finished floor.

2. Provide sealant for watertight joint.

3. Drilled Penetrations: Provide 1-1/2 inch (40 mm) angle ring or square set in silicone adhesive around penetration.

B. Plastic or Sheet Metal: Pipe passing through interior walls, partitions, and floors, unless steel or brass sleeves are specified below.

C. Penetrations in concrete beam flanges are permitted but are prohibited through ribs or beams without prior approval from the Architect.

D. Clearances:

1. Provide allowance for insulated piping.

2. Wall, Floor, Partitions, and Beam Flanges: 1 inch (25 mm) greater than external pipe diameter.

3. All Rated Openings: Caulked tight with fire stopping material complying with ASTM

E814 in accordance with Section 078400 to prevent the spread of fire, smoke, and gases.

2.2 PIPE-SLEEVE SEALS

A. Modular Mechanical Sleeve-Seal:

1. Elastomer-based interlocking links continuously fill annular space between pipe and wall-sleeve, wall or casing opening.

2. Watertight seal between pipe and wall-sleeve, wall or casing opening.

3. Size and select seal component materials in accordance with service requirements.

4. Glass-reinforced plastic pressure end plates.

B. Sealing Compounds:

1. Provide packing and sealing compound to fill pipe to sleeve thickness.

2. Combined packing and sealing compounding to match partition fire-resistance hourly rating.

C. Pipe Sleeve Material:

1. Bearing Walls: Steel, cast iron, or terra-cotta pipe.

2. Masonry Structures: Sheet metal or fiber.

D. Wall Sleeve: PVC material with waterstop collar, and nailer end-caps.

Sleeves and Sleeve Seals for Plumbing Piping 220517 - 2

PART 3 EXECUTION

3.1 INSTALLATION

A. Route piping in orderly manner, plumb and parallel to building structure. Maintain gradient.

B. Install piping to conserve building space, to not interfere with use of space and other work.

C. Install piping and pipe sleeves to allow for expansion and contraction without stressing pipe, joints, or connected equipment.

Meters and Gauges for Plumbing Piping 220519 - 1

SECTION 220519

METERS AND GAUGES FOR PLUMBING PIPING

PART 1 GENERAL

1.1 SUBMITTALS

A. Product Data: Provide red-marked product data sheets for each furnished item with associated components and accessories.

PART 2 PRODUCTS

2.1 GAS METERS

A. Diaphragm Gas Meters:

1. Maximum Operating Line Pressure: 10 psi (0.7 bar).

2. Gas Flow Rate: Propane with flow rate as indicated on drawings.

3. Rangeability and Accuracy: 100 to 1 at plus or minus 1 percent.

4. Temperature Compensation: -30 to 140 degrees F (-34 to 60 degrees C).

5. B109.1/B109.2 of AGA/ANSI B109 Set, coated aluminum case with security seals, female threaded piping connection, and hermetically sealed register.

2.2 THERMOMETERS

A. General:

1. Product Compliance: ASTM E1.

2. Lens: Clear glass, except where stated.

3. Accuracy: One percent, when tested in accordance with ASTM E77, except where stated.

4. Scale: Black markings depicting single scale in degrees F where expected process value falls half-span of standard temperature range.

B. Thermometers - Dial Type:

1. Fixed: 5 inch (125 mm) diameter dial with black pointer, stainless steel case, silicone damping bimetal element, hermetically sealed lens, recalibrating screw, and 2-1/2 inch (63.5 mm) NPT stem.

PART 3 EXECUTION

3.1 INSTALLATION

A. Install water meters with inlet and outlet isolation valves in compliance with AWWA M6.

B. Install thermometers as follows:

1. Hot Water Heaters: Place upstream and downstream of heater. Add one on the inlet end when using steam as the water heating medium.

General-Duty Valves for Plumbing Piping 220523 - 3

SECTION 220523

GENERAL-DUTY VALVES FOR PLUMBING PIPING

PART 1 GENERAL

1.1 SUBMITTALS

A. Product Data: Provide data on valves including manufacturers catalog information. Submit performance ratings, rough-in details, weights, support requirements, and piping connections.

PART 2 PRODUCTS

2.1 APPLICATIONS

A. See drawings for specific valve locations.

B. Listed pipe sizes shown using nominal pipe sizes (NPS) and nominal diameter (DN).

C. Provide the following valves for the applications if not indicated on drawings:

1. Shutoff: Ball, butterfly, gate.

2. Swing Check (Pump Outlet):

a. 2 inch (50 mm, DN) and Smaller: Bronze swing check valves with bronze or nonmetallic disc.

D. Domestic, Hot and Cold Water Valves:

1. 2 inch (50 mm, DN) and Smaller:

a. Ball: One piece, full port, brass with brass trim.

2. 2-1/2 inch (65 mm, DN) and Larger:

a. Iron, 2-1/2 inch (65 mm, DN) to 4 inch (100 mm, DN): Provide with threaded ends.

b. Iron Ball: Class 150.

c. Iron Swing Check: Class 125, metal seats.

2.2 GENERAL REQUIREMENTS

A. Valve Pressure and Temperature Ratings: No less than rating indicated; as required for system pressures and temperatures.

B. Valve Sizes: Match upstream piping unless otherwise indicated.

C. Valve Actuator Types:

1. Hand Lever: Quarter-turn valves 6 inch (150 mm, DN) and smaller except plug valves.

D. Insulated Piping Valves: With 2 inch (50 mm, DN) stem extensions and the following features:

1. Ball Valves: Extended operating handle of non-thermal-conductive material, and protective sleeve that allows operation of valve without breaking the vapor seal or disturbing insulation.

E. Valve-End Connections:

1. Threaded End Valves: ASME B1.20.1.

2. Pipe Flanges and Flanged Fittings 1/2 inch (15 mm, DN) through 24 inch (600 mm, DN):

ASME B16.5.

F. General ASME Compliance:

1. Ferrous Valve Dimensions and Design Criteria: ASME B16.10 and ASME B16.34.

G. Potable Water Use:

1. Certified: Approved for use in compliance with NSF 61 and NSF 372.

2. Lead-Free Certified: Wetted surface material includes less than 0.25 percent lead content.

2.3 BRASS, BALL VALVES

A. One Piece, Full Port with Brass Trim and Push-to-fit or Threaded Connections:

General-Duty Valves for Plumbing Piping 220523 - 3

1. Comply with MSS SP-110.

2. CWP Rating: 200 psi (1379 kPa).

3. Body: Forged brass.

4. Seats: PTFE.

5. Stem: Brass.

6. Ball: Chrome-plated brass.

7. Operator: Handle.

2.4 IRON, BALL VALVES

A. Class 125, Full Port, Stainless Steel Trim:

1. Comply with MSS SP-72.

2. CWP Rating: 200 psi (1380 kPa).

3. Body: ASTM A536 Grade 65-45-12, ductile iron.

4. End Connections: Flanged.

5. Seats: PTFE.

6. Operator: Lever with locking handle.

2.5 BRASS, INLINE CHECK VALVES

A. Class 150:

1. WOG Rating: 200 psi (1380 kPa).

2. Maximum Service Temperature: 250 degrees F (121.1 degrees C).

3. Body: Forged brass.

4. Disc: Forged brass.

5. Seal: PTFE, bubble-tight.

6. End Connections: Press.

2.6 BRONZE, SWING CHECK VALVES

A. General:

1. Fabricate from dezincification resistant material.

2. Copper alloys containing more than 15 percent zinc are not permitted.

B. Class 125:

1. Pressure and Temperature Rating: MSS SP-80, Type 3.

2. Design: Y-pattern, horizontal or vertical flow.

3. WOG Rating: 200 psi (1380 kPa).

4. Body: Bronze, ASTM B62.

5. End Connections: Threaded.

6. Disc: Bronze.

2.7 IRON, HORIZONTAL SWING CHECK VALVES

A. Class 125:

1. Pressure and Temperature Rating: MSS SP-71, Type I.

2. Design: T-body style for clear or full waterways.

3. WOG Rating: 200 psi (1380 kPa).

4. Body: ASTM A126, gray cast iron with bolted bonnet.

5. End Connections: Flanged.

6. Trim: Composition.

7. Seat Ring and Disc Holder: Bronze.

8. Disc: PTFE.

9. Gasket: Asbestos free.

General-Duty Valves for Plumbing Piping 220523 - 3

PART 3 EXECUTION

3.1 INSTALLATION

A. Provide unions or flanges with valves to facilitate equipment removal and maintenance while maintaining system operation and full accessibility for servicing.

B. Provide separate valve support as required and locate valve with stem at or above center of piping, maintaining unimpeded stem movement.

Hangers and Supports for Plumbing Piping and Equipment 220529 - 3

SECTION 220529

HANGERS AND SUPPORTS FOR PLUMBING PIPING AND EQUIPMENT

PART 2 PRODUCTS

1.1 GENERAL REQUIREMENTS

A. Provide required hardware to hang or support piping, equipment, or fixtures with related accessories as necessary to complete installation of plumbing work.

B. Provide hardware products listed, classified, and labeled as suitable for intended purpose.

C. Materials for Metal Fabricated Supports: Comply with Section 055000.

1. Zinc-Plated Steel: Electroplated in accordance with ASTM B633 unless stated otherwise.

2. Galvanized Steel: Hot-dip galvanized in accordance with ASTM A123/A123M or ASTM

A153/A153M unless stated otherwise.

D. Corrosion Resistance: Use corrosion-resistant metal-based materials fully compatible with exposed piping materials and suitable for the environment where installed.

1. Indoor Dry Locations: Use zinc-plated steel or approved equivalent unless otherwise indicated.

1.2 STRUT SYSTEMS FOR PIPE OR EQUIPMENT SUPPORT

A. Strut Channels:

1. ASTM A653/A653M galvanized steel bracket with clamps for surface mounting of piping or plumbing equipment support.

2. Channel or Bracket Kits: Include rods, brackets, end-fixed fittings, covers, clips, and other related hardware required to complete sectional trapeze section for piping or other support.

B. Hanger Rods:

1. Threaded zinc-plated steel unless otherwise indicated.

2. Minimum Size, Unless Otherwise Indicated or Required:

a. Piping up to 1 inch (25 mm, DN): 1/4 inch (6 mm, DN) diameter.

b. Piping larger than 1 inch (25 mm, DN): 3/8 inch (10 mm, DN) diameter.

C. Channel Nuts:

1. Provide carbon steel channel nut with epoxy copper or zinc finish and long, regular, or short spring as indicated on drawings.

1.3 BEAM CLAMPS

A. MSS SP-58 types 19 through 23, 25 or 27 through 30 based on required load.

B. C-Clamp: MSS SP-58 type 23, malleable iron and steel with plain, stainless steel, and zinc finish.

C. Provide clamps with hardened steel cup-point set screws and lock-nuts for anchoring in place.

D. Material: ASTM A395/A395M ductile iron, ASTM A36/A36M carbon steel, ASTM

A47/A47M malleable iron, ASTM A181/A181M forged steel, or ASTM A283/A283M steel.

1.4 PIPE HANGERS

A. Band Hangers, Adjustable:

1. MSS SP-58 type 7 or 9, zinc-plated ASTM A1011/A1011M steel or ASTM A653/A653M carbon steel.

B. Clevis Hangers, Adjustable:

1. Light-Duty: MSS SP-58 type 1, zinc-colored, epoxy plated.

2. Standard-Duty: MSS SP-58 type 1, zinc-colored, epoxy plated.

Hangers and Supports for Plumbing Piping and Equipment 220529 - 3

1.5 PIPE CLAMPS

A. Riser Clamps:

1. For insulated pipe runs, provide two bolt-type clamps designed for installation under insulation.

2. MSS SP-58 type 1 or 8, carbon steel or steel with epoxy plated, plain, stainless steel, or zinc plated finish.

3. Copper Tube Pipe Clamp: MSS SP-58 type 8, epoxy plated copper.

4. UL (DIR) listed: Pipe sizes 1/2 to 8 inch (15 to 200 mm, DN).

B. Insulation Coupling:

1. Two bolt-type clamps designed for installation under insulation.

2. Material: Carbon steel with epoxy copper or zinc finish.

1.6 PIPE SUPPORTS, GUIDES, SHIELDS, AND SADDLES

A. Dielectric Barriers: Provide between metallic supports and metallic piping and associated items of dissimilar type; acceptable dielectric barriers include rubber or plastic sheets or coatings attached securely to pipe or item.

B. Pipe Shields for Insulated Piping:

1. MSS SP-58 type 40, ASTM A1011/A1011M steel or ASTM A653/A653M carbon steel.

2. General Construction and Requirements:

a. Surface Burning Characteristics: Comply with ASTM E84 or UL 723.

b. Shields Material: UV-resistant polypropylene with glass fill.

c. Maximum Insulated Pipe Outer Diameter: 12-5/8 inch (321 mm).

d. Service Temperature: Minus 40 to 178 degrees F (Minus 40 to 81 degrees C).

e. Pipe shields to be provided at hanger, support, and guide locations on pipe requiring insulation or additional support.

C. Pipe Supports:

1. Material: ASTM A395/A395M ductile iron, ASTM A36/A36M carbon steel, ASTM A47/A47M malleable iron, ASTM A181/A181M forged steel, or ASTM A283/A283M steel.

2. Liquid Temperatures Up to 122 degrees F (50 degrees C):

a. Overhead Support: MSS SP-58 types 1, 3 through 12 clamps.

b. Support From Below: MSS SP-58 types 35 through 38.

3. Operating Temperatures from 122 to 446 degrees F (50 to 230 degrees C):

a. Overhead Support: MSS SP-58 type 1 or 3 through 12 clamps with appropriate saddle of MSS SP-58 type 40 for insulated pipe.

b. Roller Chair: MSS SP-58 types 41 or 43 through 46 roller chair support with appropriate saddle of MSS SP-58 type 39 for insulated pipe.

c. Sliding Support: MSS SP-58 types 35 through 38.

D. Pipe Supports, Thermal Insulated:

1. General Requirements:

a. Insulated pipe supports to be provided at hanger, support, and guide locations on pipe requiring insulation or additional support.

b. Surface Burning Characteristics: Flame spread index/smoke developed index of 5/30, maximum, when tested in accordance with ASTM E84 or UL 723.

c. Provide pipe supports for 1/2 to 30 inch (15 to 750 mm, DN) iron pipes.

d. Insulation inserts to consist of rigid phenolic foam insulation surrounded by 360 degree, PVC jacketing.

2. PVC Jacket:

Hangers and Supports for Plumbing Piping and Equipment 220529 - 3

a. Pipe insulation protection shields to be provided with ball bearing hinge and locking seam.

b. Moisture Vapor Transmission: 0.0071 perm inch (0.0092 ng/Pa s m), when tested in accordance with ASTM E96/E96M.

c. Minimum Thickness: 60 mil, 0.06 inch (1.524 mm).

1.7 ANCHORS AND FASTENERS

A. Unless otherwise indicated and where not otherwise restricted, use the anchor and fastener types indicated for the specified applications.

B. Concrete: Use preset concrete inserts, expansion anchors, or screw anchors.

C. Solid or Grout-Filled Masonry: Use expansion anchors or screw anchors.

D. Hollow Stud Walls: Use toggle bolts.

E. Steel: Use beam ceiling clamps, beam clamps, machine bolts, or welded threaded studs.

F. Preset Concrete Inserts: Continuous metal strut channel and spot inserts specifically designed to be cast in concrete ceilings, walls, and floors.

1. Channel Material: Use galvanized steel.

2. Manufacturer: Same as manufacturer of metal strut channel framing system.

PART 3 EXECUTION

2.1 INSTALLATION

A. Install products in accordance with manufacturer's instructions.

B. Provide independent support from building structure. Do not provide support from piping, ductwork, conduit, or other systems.

C. Unless specifically indicated or approved by Architect, do not provide support from suspended ceiling support system or ceiling grid.

D. Unless specifically indicated or approved by Architect, do not provide support from roof deck.

E. Do not penetrate or otherwise notch or cut structural members without approval of Structural

Engineer.

F. Provide thermal insulated pipe supports complete with hangers and accessories. Install thermal insulated pipe supports during the installation of the piping system.

G. Equipment Support and Attachment:

1. Use metal fabricated supports or supports assembled from metal channel (strut) to support equipment as required.

2. Use metal channel (strut) secured to studs to support equipment surface-mounted on hollow stud walls when wall strength is not sufficient to resist pull-out.

3. Use metal channel (strut) to support surface-mounted equipment in wet or damp locations to provide space between equipment and mounting surface.

4. Securely fasten floor-mounted equipment. Do not install equipment such that it relies on its own weight for support.

Identification for Plumbing Piping and Equipment 220553 - 2

SECTION 220553

IDENTIFICATION FOR PLUMBING PIPING AND EQUIPMENT

PART 1 GENERAL

1.1 SUBMITTALS

A. Product Data: Provide manufacturers catalog literature for each product required.

PART 2 PRODUCTS

2.1 PLUMBING COMPONENT IDENTIFICATION GUIDELINE

A. Nameplates:

1. Control panels, transducers, and other related control equipment products.

2. Pumps, tanks, filters, water treatment devices, and other plumbing equipment products.

B. Tags:

1. Piping: 3/4 inch (20 mm) diameter and smaller.

C. Pipe Markers: 3/4 inch (20 mm) diameter and higher.

2.2 NAMEPLATES

A. Description: Laminated piece with up to three lines of text.

1. Letter Color: White.

2. Letter Height: 1/4 inch (6 mm).

2.3 TAGS

A. Flexible: Vinyl with engraved black letters on light contrasting background color with up to three lines of text. Minimum tag size 1-1/2 inch (40 mm) in diameter.

B. Valve Tag Chart: Typewritten 12-point letter size list in anodized aluminum frame.

2.4 STENCILS

A. Pipe: Stencil size required per external insulated or uninsulated pipe diameter.

1. 3/4 to 1-1/4 inch (20 to 30 mm) Range: 1/2 inch (15 mm) text over 8 inch (200 mm) long background.

B. Stencil Paint: As specified in Section 099123, semi-gloss enamel, colors complying with

ASME A13.1.

2.5 PIPE MARKERS

A. Comply with ASME A13.1.

B. Flexible Marker: Factory fabricated, semi-rigid, preformed to fit around pipe or pipe covering;

minimum information indicating flow direction arrow and identification of fluid conveyed.

C. Flexible Tape Marker: Flexible, vinyl film tape with pressure-sensitive adhesive backing and printed markings.

D. Identification Scheme, ASME A13.1:

1. Primary: External Pipe Diameter, Uninsulated or Insulated.

a. 3/4 to 1-1/4 inches (19 to 32 mm): Use 8 inch (203 mm) field-length with 1/2 inch

(13 mm) text height.

b. 1-1/2 to 2 inches (38 to 51 mm): Use 8 inch (203 mm) field-length with 3/4 inch (19

mm) text height.

2. Secondary: Color scheme per fluid service.

a. Water; Potable, Cooling, Boiler Feed, and Other: White text on green background.

Identification for Plumbing Piping and Equipment 220553 - 2

PART 3 EXECUTION

3.1 INSTALLATION

A. Install flexible nameplates with corrosive-resistant mechanical fasteners, or adhesive. Apply with sufficient adhesive to ensure permanent adhesion and seal with clear lacquer.

B. Install tags in clear view and align with axis of piping C. Apply stencil painted identification in compliance with Section 099123 requirements. Identify unit with assigned id-number and area being served using pipe marking rules.

Plumbing Piping Insulation 220719 - 2

SECTION 220719

PLUMBING PIPING INSULATION

PART 1 GENERAL

1.1 SUBMITTALS

A. Product Data: Provide product description, thermal characteristics, list of materials and thickness for each service, and locations.

PART 2 PRODUCTS

2.1 REGULATORY REQUIREMENTS

A. Surface Burning Characteristics: Flame spread index/Smoke developed index of 25/50, maximum, when tested in accordance with ASTM E84 or UL 723.

2.2 GLASS FIBER INSULATION

A. Insulation: ASTM C547 and ASTM C795; rigid molded, noncombustible.

B. Vapor Barrier Jacket: White Kraft paper with glass fiber yarn, bonded to aluminized film;

moisture vapor transmission when tested in accordance with ASTM E96/E96M of 0.02 perm (0.029 ng/(Pa s m)).

C. Tie Wire: 0.048 inch (1.22 mm) stainless steel with twisted ends on maximum 12 inch (300

mm) centers.

D. Vapor Barrier Lap Adhesive: Compatible with insulation.

E. Fibrous Glass Fabric:

F. Indoor Vapor Barrier Finish:

2.3 CELLULAR GLASS INSULATION

A. Insulation: ASTM C552, Type II, Grade 6.

1. K (Ksi) Value: 0.35 (0.050) at 100 degrees F (38 degrees C).

2. Service Temperature Range: From 250 degrees F (121 degrees C) to 800 degrees F (427 degrees C).

3. Water Vapor Permeability: 0.005 perm inch (0.007 ng/(Pa s m)) maximum per inch.

4. Water Absorption: 0.5 percent by volume, maximum.

2.4 FLEXIBLE ELASTOMERIC CELLULAR INSULATION

A. Insulation: Preformed flexible elastomeric cellular rubber insulation complying with ASTM

C534/C534M Grade 1; use molded tubular material wherever possible.

1. Minimum Service Temperature: Minus 40 degrees F (Minus 40 degrees C).

2. Maximum Service Temperature: 220 degrees F (104 degrees C).

3. Connection: Waterproof vapor barrier adhesive.

B. Elastomeric Foam Adhesive: Air dried, contact adhesive, compatible with insulation.

PART 3 EXECUTION

3.1 INSTALLATION

A. Glass fiber insulated pipes conveying fluids below ambient temperature:

1. Provide vapor barrier jackets, factory-applied or field-applied. Secure with self-sealing longitudinal laps and butt strips with pressure-sensitive adhesive. Secure with outward clinch expanding staples and vapor barrier mastic.

2. Insulate fittings, joints, and valves with molded insulation of like material and thickness as adjacent pipe. Finish with glass cloth and vapor barrier adhesive or PVC fitting covers.

Plumbing Piping Insulation 220719 - 2

B. Glass fiber insulated pipes conveying fluids above ambient temperature:

1. Provide standard jackets, with or without vapor barrier, factory-applied or field-applied.

Secure with self-sealing longitudinal laps and butt strips with pressure-sensitive adhesive.

Secure with outward clinch expanding staples.

2. Insulate fittings, joints, and valves with insulation of like material and thickness as adjoining pipe. Finish with glass cloth and adhesive or PVC fitting covers.

C. Pipe Exposed in Mechanical Equipment Rooms or Finished Spaces (less than 10 feet (3 meters) above finished floor): Finish with canvas jacket sized for finish painting.

Plumbing Piping 221005 - 3

SECTION 221005

PLUMBING PIPING

PART 1 GENERAL

1.1 SUBMITTALS

A. Product Data: Provide data on pipe materials, pipe fittings, valves, and accessories. Provide manufacturers catalog information. Indicate valve data and ratings.

1.2 QUALITY ASSURANCE

A. Perform work in accordance with applicable codes.

B. Valves: Manufacturer's name and pressure rating marked on valve body.

C. Identify pipe with marking including size, ASTM material classification, ASTM specification, potable water certification, water pressure rating.

PART 2 PRODUCTS

2.1 GENERAL REQUIREMENTS

A. Potable Water Supply Systems: Provide piping, pipe fittings, solder, and flux (if used), complying with NSF 61 and NSF 372; label pipe and fittings.

2.2 SANITARY WASTE PIPING, BURIED WITHIN 5 FEET (1500 MM) OF BUILDING

A. ABS Pipe: ASTM D2661.

1. Fittings: ABS.

2. Joints: Solvent welded with ASTM D2235 cement.

B. PVC Pipe: ASTM D2665 or ASTM D3034.

1. Fittings: PVC.

2. Joints: Solvent welded, with ASTM D2564 solvent cement.

2.3 SANITARY WASTE PIPING, ABOVE GRADE

A. PVC Pipe: ASTM D2665.

1. Fittings: PVC.

2. Joints: Solvent welded, with ASTM D2564 solvent cement.

2.4 DOMESTIC WATER PIPING, BURIED WITHIN 5 FEET (1500 MM) OF BUILDING

A. Copper Pipe: ASTM B88 (ASTM B88M), Type L (Type B), drawn temper.

B. Cross-Linked Polyethylene (PEX) Pipe: ASTM F876 or ASTM F877.

1. PPI TR-4 Pressure Design Basis:

a. 80 psig (551 kPa) at maximum 200 degrees F (93 degrees C).

2. Fittings: Brass and engineered polymer (EP) ASTM F1960.

3. Joints: ASTM F1960 cold-expansion fittings.

2.5 DOMESTIC WATER PIPING, ABOVE GRADE

A. Copper Pipe: ASTM B88 (ASTM B88M), Type L (Type B), drawn temper.

1. Fittings: ASME B16.18, cast copper, or ASME B16.22, wrought copper.

2. Joints: ASTM B32 solder.

3. Mechanical Press Sealed Fittings: ASME B16.51 or IAPMO/ANSI/CAN Z1117, ICC

(IPC), and IAPMO (UPC) approved, NSF 61 and NSF 372 certified, with EPDM seals.

B. Cross-Linked Polyethylene (PEX) Pipe: ASTM F876 or ASTM F877.

1. PPI TR-4 Pressure Design Basis:

a. 80 psig (551 kPa) at maximum 200 degrees F (93 degrees C).

Plumbing Piping 221005 - 3

2. Fittings: Brass and copper.

3. Fittings: Brass and engineered polymer (EP) ASTM F1960.

4. Joints: ASTM F1960 cold-expansion fittings.

2.6 NATURAL GAS PIPING, BURIED WITHIN 5 FEET (1500 MM) OF BUILDING

A. Steel Pipe: ASTM A53/A53M, Grade B, Type F, Schedule 40 black.

1. Fittings: ASTM A234/A234M, wrought steel welding type.

2. Joints: ASME B31.1, welded.

3. Jacket: AWWA C105/A21.5 polyethylene jacket or double layer, half-lapped 10 mil

(0.25 mm) polyethylene tape.

2.7 NATURAL GAS PIPING, ABOVE GRADE

A. Steel Pipe: ASTM A53/A53M Schedule 40 black.

1. Fittings: ASME B16.3, malleable iron, or ASTM A234/A234M, wrought steel welding type.

2. Joints: Threaded or welded to ASME B31.1.

B. Flexible Gas Piping:

1. Corrugated Stainless Steel Tubing: Comply with ANSI LC 1/CSA 6.26.

2. Comply with ASTM E84.

3. Fittings: Provided by piping system manufacturer.

2.8 PIPE FLANGES, UNIONS, AND COUPLINGS

A. Unions for Pipe Sizes 3 inch (80 mm, DN) and Under:

1. Ferrous Pipe: Class 150 malleable iron threaded unions.

2. Copper Tube and Pipe: Class 150 bronze unions with soldered joints.

B. Flanges for Pipe Sizes Over 1 inch (25 mm, DN):

1. Ferrous Pipe: Class 150 malleable iron threaded or forged steel slip-on flanges;

preformed neoprene gaskets.

2. Copper Tube and Pipe: Class 150 slip-on bronze flanges; preformed neoprene gaskets.

C. Mechanical Couplings for Grooved and Shouldered Joints: Two or more curved housing segments with continuous key to engage pipe groove, circular C-profile gasket, and bolts to secure and compress gasket.

1. Dimensions and Testing: In accordance with AWWA C606.

2. Housing Material: Provide ASTM A47/A47M malleable iron or ductile iron, galvanized.

3. Bolts and Nuts: Hot dipped galvanized or zinc-electroplated steel.

4. When pipe is field grooved, provide coupling manufacturer's grooving tools.

D. Dielectric Connections: Union with galvanized or plated steel threaded end, copper solder end, water impervious isolation barrier.

2.9 PIPE HANGERS AND SUPPORTS

A. Provide hangers and supports that comply with MSS SP-58.

1. If type of hanger or support for a particular situation is not indicated, select appropriate type using MSS SP-58 recommendations.

2. Overhead Supports: Individual steel rod hangers attached to structure or to trapeze hangers.

3. Trapeze Hangers: Welded steel channel frames attached to structure.

4. Vertical Pipe Support: Steel riser clamp.

B. Plumbing Piping - Drain, Waste, and Vent:

Plumbing Piping 221005 - 3

1. Hangers for Pipe Sizes 1/2 to 1-1/2 inch (15 to 40 mm, DN): Malleable iron, adjustable swivel, split ring.

2. Hangers for Pipe Sizes 2 inch (50 mm, DN) and Over: Carbon steel, adjustable, clevis.

3. Wall Support for Pipe Sizes to 3 inch (80 mm, DN): Cast iron hook.

C. Plumbing Piping - Water:

1. Hangers for Pipe Sizes 1/2 to 1-1/2 inch (15 to 40 mm, DN): Malleable iron, adjustable swivel, split ring.

2. Hangers for Cold Pipe Sizes 2 inch (50 mm, DN) and Over: Carbon steel, adjustable, clevis.

3. Wall Support for Pipe Sizes Up to 3 inch (80 mm, DN): Cast iron hook.

D. Hanger Fasteners: Attach hangers to structure using appropriate fasteners, as follows:

2.10 BALL VALVES

A. Construction, 4 inch (100 mm, DN) and Smaller: MSS SP-110, Class 150, 400 psi (2760 kPa) CWP, bronze or ductile iron body, 304 stainless steel or chrome plated brass ball, regular port, teflon seats and stuffing box ring, blow-out proof stem, lever handle with balancing stops, threaded or grooved ends with union.

PART 3 EXECUTION

3.1 INSTALLATION

A. Install in accordance with manufacturer's instructions.

B. Provide non-conducting dielectric connections wherever jointing dissimilar metals.

C. Install piping to maintain headroom, conserve space, and not interfere with use of space.

D. Group piping whenever practical at common elevations.

E. Install piping to allow for expansion and contraction without stressing pipe, joints, or connected equipment. See Section 220516.

F. Provide clearance in hangers and from structure and other equipment for installation of insulation and access to valves and fittings.

G. Provide access where valves and fittings are not exposed.

1. Coordinate size and location of access doors with Section 083100.

H. Copper Pipe and Tube: Make soldered joints in accordance with ASTM B828, using specified solder, and flux meeting ASTM B813; in potable water systems use flux also complying with NSF 61 and NSF 372.

I. PVC Pipe: Make solvent-welded joints in accordance with ASTM D2855.

J. Pipe Hangers and Supports:

1. Install in accordance with ASME B31.9.

3.2 FIELD TESTS AND INSPECTIONS

A. Verify and inspect systems according to requirements by the Authority Having Jurisdiction. In the absence of specific test and inspection procedures proceed as indicated below.

B. Domestic Water Systems:

C. Gas Distribution Systems:

3.3 DISINFECTION OF DOMESTIC WATER PIPING SYSTEM

A. Disinfect water distribution system in accordance with Section 330110.58.

Domestic Water Piping Specialties 221119 - 2

SECTION 221119

DOMESTIC WATER PIPING SPECIALTIES

PART 1 GENERAL

1.1 SUBMITTALS

A. Product Data: Provide manufacturer's literature and data sheets for each product. Include information on materials of fabrication, assembly of components, dimensions, ratings, finishes, rough-in requirements, and installed accessories.

PART 2 PRODUCTS

2.1 GENERAL REQUIREMENTS

A. Specialties in Potable Water Supply Systems: Provide products complying with NSF 61 and

NSF 372.

B. Source Limitations: Furnish domestic water piping specialties of same kind by same manufacturer.

C. Provide brass-bodied domestic water piping specialties in DZR brass.

2.2 BACKFLOW PREVENTERS

A. Reduced-Pressure-Principle Backflow Preventers:

1. NPS 2 (DN 50) and Smaller:

a. Assembly: ASSE 1013 and AWWA C511.

b. Backflow Valve: Manufactured from bronze, copper silicon alloy, or stainless steel.

c. Isolation Valves: Ball valves on inlet and outlet.

d. Maximum Working Pressure: 175 psi (12.1 bar).

e. Working Temperature Range: 33 to 180 degrees F (0.5 to 82 degrees C).

2.3 WATER PRESSURE REDUCING VALVES

A. Direct-Acting Pressure Reducing Valves:

1. Valve: ASSE 1003, bronze or copper silicon alloy body, with spring-loaded diaphragm;

field-adjustable outlet pressure, and integral inlet screen strainer.

a. Diaphragm: EPDM or buna-nitrile.

b. Spring: Stainless steel.

2. Maximum Working Pressure: 300 psi (20.7 bar).

3. Outlet Pressure Range: 15 to 75 psi (100 to 515 kPa).

4. Working Temperature Range: 33 to 140 degrees F (0.5 to 60 degrees C).

2.4 MIXING VALVES

A. Thermostatic Master Mixing Valves:

1. Valve: ASSE 1017, brass body; thermostatic element; corrosion- and lime-resistant internal components; integral locking temperature adjustment.

B. Automatic Temperature Control Mixing Valves:

1. Valve: ASSE 1069, brass or bronze body; thermostatic element; corrosion- and lime-resistant internal components; integral locking temperature adjustment; integral check valves with strainer screens on inlets.

2. Accessories:

a. Shut-off valve on inlets and outlet.

C. Water Temperature Limiting Valves:

Domestic Water Piping Specialties 221119 - 2

1. Valve: ASSE 1070, brass or bronze body; thermostatic element; corrosion- and lime-resistant internal components; integral locking temperature adjustment with high-temperature limit stop; integral check valves with strainer screens on inlets.

2.5 OUTLET BOXES

A. Washing Machine Outlet Boxes:

1. Description: Plastic preformed rough-in box with brass quarter-turn ball valves or single lever valve, socket for 2-inch (50 mm) waste, and slip-in finishing cover.

B. Ice Maker Outlet Boxes:

1. Description: Plastic preformed square or round rough-in box with quarter-turn ball valve and slip-in finishing cover.

2.6 HOSE BIBBS

A. Hose Bibbs:

1. Valve: Bronze or brass body with mounting flange, replaceable seat, hose thread spout, and integral or add-on vacuum breaker complying with ASSE…

This is the start of the file's text. The full file is on GovTribe.