17-323113 - CHAIN LINK FENCES AND GATES.pdf
PDF 149 KB Posted
- Attached to
- Oakbrook Center for Early Education
- Solicitation number
- US.252787
- Issued by
- Berks County, Reese CDP, Pennsylvania
About this file
Summary
This document is a technical specification section (Section 323113) for chain-link fences and gates prepared for the Operations Center Expansion project by the City of Lancaster Department of Public Works (RGS 2025992-044). The specification establishes comprehensive requirements for the design, materials, installation, and testing of chain-link fence systems, including fabric, framework, fittings, barbed tape accessories, and grounding systems. The specification requires submission of product data, shop drawings, samples, and delegated-design documentation from a qualified professional engineer. Key material requirements include 0.148-inch diameter galvanized steel wire fabric with 2-inch mesh size, posts and rails complying with ASTM F 1043, and barbed tape conforming to ASTM F 1910 specifications. Installation must comply with ASTM F 567 standards, with line posts spaced uniformly at 10-foot centers, fabric tied to posts at maximum 12-inch intervals, and proper concrete setting of all posts. The specification establishes a 5-year warranty period from the date of substantial completion for all materials and workmanship.
The grounding and bonding system represents a critical component of the installation, with maximum grounding intervals of 1,500 feet for general applications and 750 feet for fences within 100 feet of buildings, structures, walkways, and roadways. Grounding rods must achieve a maximum resistance-to-ground value of 25 ohms under normal dry conditions, with connections utilizing copper conductors and complying with UL 467 standards. All grounding-resistance testing must be performed by a qualified testing agency certified by NETA or an NRTL, with testing conducted using megger tests at least two full days after precipitation and documented through certified test reports. The specification requires a preinstallation conference at the project site and field quality-control reports documenting all testing results and observations affecting test validity.
View the file
Other files
Show 40 more
Latest 50 of 63 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Operations Center Expansion RGS 2025992-044
City of Lancaster - Department of Public Works
CHAIN LINK FENCES AND GATES 323113
SECTION 323113 - CHAIN LINK FENCES AND GATES
PART 1 - GENERAL
1.1 RELATED DOCUMENTS
A. Drawings and general provisions of the Contract, including General and Supplementary
Conditions and Division 01 Specification Sections, apply to this Section.
1.2 SUMMARY
A. Section Includes:
1. Chain-link fences.
B. Related Sections:
1. Section 033000 "Cast-in-Place Concrete" for cast-in-place concrete controls and post footings.
1.3 PERFORMANCE REQUIREMENTS
A. Delegated Design: Engage a qualified professional engineer, to design chain-link fence framework.
B. Structural Performance: Chain-link fence shall withstand the effects of gravity loads and the following loads and stresses within limits and under conditions indicated according to
ASCE/SEI 7:
C. Lightning Protection System: Maximum resistance-to-ground value of 25 ohms at each grounding location along fence under normal dry conditions.
1.4 ACTION SUBMITTALS
A. Product Data: For each type of product.
1. Fence posts, rails, and fittings.
2. Chain-link fabric, reinforcements, and attachments.
3. Accessories: Razor Wire
B. Shop Drawings: Include plans, elevations, sections, details, and attachments to other work.
Show accessories, hardware, and operational clearances.
C. Samples for Initial Selection: For components with factory-applied color finishes.
D. Samples for Verification: Prepared on Samples of size indicated below:
1. Galvanized Components: In 6-inch lengths for components and on full-sized units for accessories.
E. Delegated-Design Submittal: For chain-link fences to comply with performance requirements and design criteria, including analysis data signed and sealed by the qualified professional engineer responsible for their preparation.
1.5 INFORMATIONAL SUBMITTALS
A. Product Certificates: For each type of chain-link fence from manufacturer.
B. Product Test Reports: For framing strength according to ASTM F 1043, for tests performed by a qualified testing agency.
C. Field quality-control reports.
1.6 QUALITY ASSURANCE
A. Testing Agency Qualifications: For testing fence grounding. Member company of NETA or an
NRTL.
1. Testing Agency's Field Supervisor: Currently certified by NETA to supervise on-site testing.
B. Preinstallation Conference: Conduct conference at Project Site.
1.7 FIELD CONDITIONS
A. Field Measurements: Verify layout information for chain-link fences shown on Drawings in relation to property survey and existing structures. Verify dimensions by field measurements.
1.8 WARRANTY
A. Special Warranty: Manufacturer's standard form in which Installer agrees to repair or replace components of chain-link fences that fail in materials or workmanship within specified warranty period.
1. Failures include, but are not limited to, the following:
a. Failure to comply with performance requirements.
b. Deterioration of metals, metal finishes, and other materials beyond normal weathering.
2. Warranty Period: 5 years from date of Substantial Completion.
PART 2 - PRODUCTS
2.1 CHAIN-LINK FENCE FABRIC
A. General: Provide fabric in one-piece heights measured between top and bottom of outer edge of selvage knuckle or twist. Comply with CLFMI Product Manual and with requirements indicated below:
1. Fabric Height: As indicated on Drawings.
2. Steel Wire Fabric: Wire with a diameter of 0.148 inch.
a. Mesh Size: 2 inches.
b. Galvanized Fabric
c. Coat selvage ends of fabric that is metallic coated before the weaving process with manufacturer's standard clear protective coating.
3. Selvage: Knuckled at both selvages.
2.2 FENCE FRAMEWORK
A. Posts and Rails: Comply with ASTM F 1043 for framing, including rails, braces, and line;
terminal; and corner posts. Provide members with minimum dimensions and wall thickness according to ASTM F 1043 based on the following:
1. Fence Height: As indicated on Drawings.
2. Horizontal Framework Members: Intermediate, top, and bottom rails complying with
ASTM F 1043.
a. Top Rail: As shown on Drawings.
3. Metallic Coating for Steel Framing:
a. Type A, consisting of not less than minimum 2.0-oz./sq. ft. average zinc coating per ASTM A 123/A 123M or 4.0-oz./sq. ft. zinc coating per
ASTM A 653/A 653M.
b. Type C, Zn-5-Al-MM alloy, consisting of not less than 1.8-oz./sq. ft. coating.
c. Coatings: Any coating above.
2.3 FITTINGS
A. General: Comply with ASTM F 626.
B. Post Caps: Provide for each post.
1. Provide line post caps with loop to receive tension wire or top rail.
C. Rail and Brace Ends: For each gate, corner, pull, and end post.
D. Rail Fittings: Provide the following:
1. Top Rail Sleeves: Pressed-steel or round-steel tubing not less than 6 inches long.
2. Rail Clamps: Line and corner boulevard clamps for connecting intermediate and bottom rails in the fence line-to-line posts.
E. Tension and Brace Bands: Per manufacturer recommendation.
F. Tension Bars: Steel length not less than 2 inches shorter than full height of chain-link fabric.
Provide one bar for each gate and end post, and two for each corner and pull post, unless fabric is integrally woven into post.
G. Truss Rod Assemblies: Steel, hot-dip galvanized after threading rod and turnbuckle or other means of adjustment.
H. Tie Wires, Clips, and Fasteners: According to ASTM F 626.
1. Standard Round Wire Ties: For attaching chain-link fabric to posts, rails, and frames, complying with the following:
a. Hot-Dip Galvanized Steel: 0.148-inch diameter wire; galvanized coating thickness matching coating thickness of chain-link fence fabric.
I. Finish:
1. Metallic Coating for Pressed Steel or Cast Iron: Not less than 1.2 oz. /sq. ft. zinc.
2.4 BARBED TAPE
A. Wire-Reinforced Tape: ASTM F 1910; with four-point, needle-sharp barbs permanently cold clenched around a core wire.
1. Core Wire: High-tensile-strength, zinc-coated steel.
B. Clips: Stainless steel, 0.065 inch thick by 0.375 inch wide, capable of withstanding a minimum
150-lbf pull load to limit extension of coil, resulting in a concertina pattern when deployed.
1. Configuration: Single coil.
2. Style: Concertina pattern.
3. Coil Diameter(s): BTO-12
4. Coil Loop Spacing(s): Manufacturer's standard
5. Barb Length Medium, 0.4-inch.
6. Barb Spacing: 4 inches
7. Barb Set: Manufacturer's standard.
2.5 GROUT AND ANCHORING CEMENT
A. Nonshrink, Nonmetallic Grout: Premixed, factory-packaged, nonstaining, noncorrosive, nongaseous grout complying with ASTM C 1107. Provide grout, recommended in writing by manufacturer, for exterior applications.
B. Erosion-Resistant Anchoring Cement: Factory-packaged, nonshrink, nonstaining, hydraulic-controlled expansion cement formulation for mixing with potable water at Project site to create pourable anchoring, patching, and grouting compound. Provide formulation that is resistant to erosion from water exposure without needing protection by a sealer or waterproof coating and that is recommended in writing by manufacturer, for exterior applications.
2.6 FENCE GROUNDING
A. Conductors: Bare, solid wire for No. 6 AWG and smaller; stranded wire for No. 4 AWG and larger.
1. Material above Finished Grade: Copper
2. Material on or below Finished Grade: Copper.
3. Bonding Jumpers: Braided copper tape, 1 inch wide, woven of No. 30 AWG bare copper wire, terminated with copper ferrules.
B. Connectors and Grounding Rods: Comply with UL 467.
1. Connectors for Below-Grade Use: Exothermic welded type.
2. Grounding Rods: Copper-clad steel, 5/8 by 96 inches
PART 3 - EXECUTION
3.1 EXAMINATION
A. Examine areas and conditions, with Installer present, for compliance with requirements for site clearing, earthwork, pavement work, and other conditions affecting performance of the Work.
1. Do not begin installation before final grading is completed unless otherwise permitted by
Landscape Architect.
B. Proceed with installation only after unsatisfactory conditions have been corrected.
3.2 PREPARATION
A. Stake locations of fence lines, gates, and terminal posts. Do not exceed intervals of 500 feet or line of sight between stakes. Indicate locations of utilities, lawn sprinkler system, underground structures, benchmarks, and property monuments.
3.3 CHAIN-LINK FENCE INSTALLATION
A. Install chain-link fencing to comply with ASTM F 567 and more stringent requirements indicated in locations as noted on plans.
B. Post Excavation: Drill or hand-excavate holes for posts to diameters and spacings indicated, in firm, undisturbed soil.
C. Post Setting: Set posts in concrete at indicated spacing into firm, undisturbed soil.
1. Verify that posts are set plumb, aligned, and at correct height and spacing, and hold in position during setting with concrete or mechanical devices.
2. Concrete Fill: Place concrete around posts to dimensions indicated and vibrate or tamp for consolidation. Protect aboveground portion of posts from concrete splatter.
a. Concealed Concrete: Top 2 inches below grade to allow covering with surface material.
b. Posts Set into Concrete in Sleeves: Use steel pipe sleeves preset and anchored into concrete for installing posts. After posts have been inserted into sleeves, fill annular space between post and sleeve with nonshrink, nonmetallic grout, mixed and placed to comply with anchoring material manufacturer's written instructions, and finished sloped to drain water away from post.
D. Terminal Posts: Locate terminal end and corner posts per ASTM F 567 and terminal pull posts at changes in horizontal or vertical alignment of 15 degrees or more. For runs exceeding 500 feet, space pull posts an equal distance between corner or end posts.
E. Line Posts: Space line posts uniformly at 10 feet o.c.
F. Post Bracing and Intermediate Rails: Install according to ASTM F 567, maintaining plumb position and alignment of fencing. Diagonally brace terminal posts to adjacent line posts with truss rods and turnbuckles. Install braces at end and at both sides of corner and pull posts.
1. Locate horizontal braces at midheight of fabric 72 inches or higher, on fences with top rail and at two-third fabric height on fences without top rail. Install so posts are plumb when diagonal rod is under proper tension.
G. Top Rail: Install according to ASTM F 567, maintaining plumb position and alignment of fencing. Run rail continuously through line post caps, bending to radius for curved runs and terminating into rail end attached to posts or post caps fabricated to receive rail at terminal posts. Provide expansion couplings as recommended in writing by fencing manufacturer.
H. Intermediate and Bottom Rails: Install and secure to posts with fittings.
I. Chain-Link Fabric: Apply fabric to outside of enclosing framework. Leave 2 inches between finish grade or surface and bottom selvage unless otherwise indicated. Pull fabric taut and tie to posts, rails, and tension wires. Anchor to framework so fabric remains under tension after pulling force is released.
J. Tension or Stretcher Bars: Thread through fabric and secure to end, corner, and pull with tension bands spaced not more than 15 inches o.c.
K. Tie Wires: Use wire of proper length to firmly secure fabric to line posts and rails. Attach wire at one end to chain-link fabric, wrap wire around post a minimum of 180 degrees, and attach other end to chain-link fabric per ASTM F 626. Bend ends of wire to minimize hazard to individuals and clothing.
1. Maximum Spacing: Tie fabric to line posts at 12 inches o.c. and to braces at 24 inches o.c.
L. Barbed Tape: Comply with ASTM F 1911. Install barbed tape uniformly in configurations indicated and fasten securely to prevent movement or displacement.
3.4 GROUNDING AND BONDING
A. Fence Grounding: Install at maximum intervals of 1500 feet except as follows:
1. Fences within 100 Feet of Buildings, Structures, Walkways, and Roadways: Ground at maximum intervals of 750 feet.
a. Other Fence Openings: Ground fence on each side of opening.
1) Bond metal gates to gate posts.
2) Bond across openings, with and without gates, except openings indicated as intentional fence discontinuities. Use No. 2 AWG wire and bury it at least
18 inches below finished grade.
B. Protection at Crossings of Overhead Electrical Power Lines: Ground fence at location of crossing and at a maximum distance of 150 feet on each side of crossing.
C. Grounding Method: At each grounding location, drive a grounding rod vertically until the top is
6 inches below finished grade. Connect rod to fence with No. 6 AWG conductor. Connect conductor to each fence component at the grounding location, including the following:
1. Make grounding connections to each barbed wire strand with wire-to-wire connectors designed for this purpose.
2. Make grounding connections to each barbed tape coil with connectors designed for this purpose.
D. Connections: Make connections to minimize possibility of galvanic action or electrolysis. Select connectors, connection hardware, conductors, and connection methods so metals in direct contact will be galvanically compatible.
1. Use electroplated or hot-tin-coated materials to ensure high conductivity and to make contact points closer in order of galvanic series.
2. Make connections with clean, bare metal at points of contact.
3. Make aluminum-to-steel connections with stainless-steel separators and mechanical clamps.
4. Make aluminum-to-galvanized-steel connections with tin-plated copper jumpers and mechanical clamps.
5. Coat and seal connections having dissimilar metals with inert material to prevent future penetration of moisture to contact surfaces.
E. Bonding to Lightning Protection System: If fence terminates at lightning-protected building or structure, ground the fence and bond the fence grounding conductor to lightning protection down conductor or lightning protection grounding conductor complying with NFPA 780.
3.5 FIELD QUALITY CONTROL
A. Grounding-Resistance Testing: Engage a qualified testing agency to perform tests and inspections.
1. Grounding-Resistance Tests: Subject completed grounding system to a megger test at each grounding location. Measure grounding resistance no fewer than two full days after last trace of precipitation, without soil having been moistened by any means other than natural drainage or seepage and without chemical treatment or other artificial means of reducing natural grounding resistance. Perform tests by two-point method according to
IEEE 81.
2. Excessive Grounding Resistance: If resistance to grounding exceeds specified value, notify Architect promptly. Include recommendations for reducing grounding resistance and a proposal to accomplish recommended work.
3. Report: Prepare test reports certified by a testing agency of grounding resistance at each test location. Include observations of weather and other phenomena that may affect test results.
END OF SECTION 323113
| PART 1 - GENERAL |
| 1.1 RELATED DOCUMENTS |
| A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section. |
| 1.2 SUMMARY |
| A. Section Includes: |
| 1. Chain-link fences. |
| B. Related Sections: |
| 1. Section 033000 "Cast-in-Place Concrete" for cast-in-place concrete controls and post footings. |
| 1.3 PERFORMANCE REQUIREMENTS |
| A. Delegated Design: Engage a qualified professional engineer, to design chain-link fence framework. |
| B. Structural Performance: Chain-link fence shall withstand the effects of gravity loads and the following loads and stresses within limits and under conditions indicated according to ASCE/SEI 7: |
| C. Lightning Protection System: Maximum resistance-to-ground value of 25 ohms at each grounding location along fence under normal dry conditions. |
| 1.4 ACTION SUBMITTALS |
| A. Product Data: For each type of product. |
| 1. Fence posts, rails, and fittings. |
| 2. Chain-link fabric, reinforcements, and attachments. |
| 3. Accessories: Razor Wire |
| B. Shop Drawings: Include plans, elevations, sections, details, and attachments to other work. Show accessories, hardware, and operational clearances. |
| C. Samples for Initial Selection: For components with factory-applied color finishes. |
| D. Samples for Verification: Prepared on Samples of size indicated below: |
| 1. Galvanized Components: In 6-inch lengths for components and on full-sized units for accessories. |
E. Delegated-Design Submittal: For chain-link fences to comply with performance requirements and design criteria, including analysis data signed and sealed by the qualified professional engineer responsible for their preparation.
| 1.5 INFORMATIONAL SUBMITTALS |
| A. Product Certificates: For each type of chain-link fence from manufacturer. |
| B. Product Test Reports: For framing strength according to ASTM F 1043, for tests performed by a qualified testing agency. |
| C. Field quality-control reports. |
| 1.6 QUALITY ASSURANCE |
| A. Testing Agency Qualifications: For testing fence grounding. Member company of NETA or an NRTL. |
| 1. Testing Agency's Field Supervisor: Currently certified by NETA to supervise on-site testing. |
B. Preinstallation Conference: Conduct conference at Project Site.
| 1.7 FIELD CONDITIONS |
| A. Field Measurements: Verify layout information for chain-link fences shown on Drawings in relation to property survey and existing structures. Verify dimensions by field measurements. |
| 1.8 WARRANTY |
| A. Special Warranty: Manufacturer's standard form in which Installer agrees to repair or replace components of chain-link fences that fail in materials or workmanship within specified warranty period. |
| 1. Failures include, but are not limited to, the following: |
| a. Failure to comply with performance requirements. |
| b. Deterioration of metals, metal finishes, and other materials beyond normal weathering. |
2. Warranty Period: 5 years from date of Substantial Completion.
| PART 2 - PRODUCTS |
| 2.1 CHAIN-LINK FENCE FABRIC |
| A. General: Provide fabric in one-piece heights measured between top and bottom of outer edge of selvage knuckle or twist. Comply with CLFMI Product Manual and with requirements indicated below: |
| 1. Fabric Height: As indicated on Drawings. |
| 2. Steel Wire Fabric: Wire with a diameter of 0.148 inch. |
| a. Mesh Size: 2 inches. |
| b. Galvanized Fabric |
| c. Coat selvage ends of fabric that is metallic coated before the weaving process with manufacturer's standard clear protective coating. |
3. Selvage: Knuckled at both selvages.
| 2.2 FENCE FRAMEWORK |
| A. Posts and Rails: Comply with ASTM F 1043 for framing, including rails, braces, and line; terminal; and corner posts. Provide members with minimum dimensions and wall thickness according to ASTM F 1043 based on the following: |
| 1. Fence Height: As indicated on Drawings. |
| 2. Horizontal Framework Members: Intermediate, top, and bottom rails complying with ASTM F 1043. |
| a. Top Rail: As shown on Drawings. |
| 3. Metallic Coating for Steel Framing: |
| a. Type A, consisting of not less than minimum 2.0-oz./sq. ft. average zinc coating per ASTM A 123/A 123M or 4.0-oz./sq. ft. zinc coating per ASTM A 653/A 653M. |
| b. Type C, Zn-5-Al-MM alloy, consisting of not less than 1.8-oz./sq. ft. coating. |
| c. Coatings: Any coating above. |
| 2.3 FITTINGS |
| A. General: Comply with ASTM F 626. |
| B. Post Caps: Provide for each post. |
| 1. Provide line post caps with loop to receive tension wire or top rail. |
| C. Rail and Brace Ends: For each gate, corner, pull, and end post. |
| D. Rail Fittings: Provide the following: |
| 1. Top Rail Sleeves: Pressed-steel or round-steel tubing not less than 6 inches long. |
| 2. Rail Clamps: Line and corner boulevard clamps for connecting intermediate and bottom rails in the fence line-to-line posts. |
| E. Tension and Brace Bands: Per manufacturer recommendation. |
| F. Tension Bars: Steel length not less than 2 inches shorter than full height of chain-link fabric. Provide one bar for each gate and end post, and two for each corner and pull post, unless fabric is integrally woven into post. |
| G. Truss Rod Assemblies: Steel, hot-dip galvanized after threading rod and turnbuckle or other means of adjustment. |
| H. Tie Wires, Clips, and Fasteners: According to ASTM F 626. |
| 1. Standard Round Wire Ties: For attaching chain-link fabric to posts, rails, and frames, complying with the following: |
| a. Hot-Dip Galvanized Steel: 0.148-inch diameter wire; galvanized coating thickness matching coating thickness of chain-link fence fabric. |
| I. Finish: |
| 1. Metallic Coating for Pressed Steel or Cast Iron: Not less than 1.2 oz. /sq. ft. zinc. |
| 2.4 BARBED TAPE |
| A. Wire-Reinforced Tape: ASTM F 1910; with four-point, needle-sharp barbs permanently cold clenched around a core wire. |
| 1. Core Wire: High-tensile-strength, zinc-coated steel. |
| B. Clips: Stainless steel, 0.065 inch thick by 0.375 inch wide, capable of withstanding a minimum 150-lbf pull load to limit extension of coil, resulting in a concertina pattern when deployed. |
| 1. Configuration: Single coil. |
| 2. Style: Concertina pattern. |
| 3. Coil Diameter(s): BTO-12 |
| 4. Coil Loop Spacing(s): Manufacturer's standard |
| 5. Barb Length Medium, 0.4-inch. |
| 6. Barb Spacing: 4 inches |
| 7. Barb Set: Manufacturer's standard. |
| 2.5 GROUT AND ANCHORING CEMENT |
| A. Nonshrink, Nonmetallic Grout: Premixed, factory-packaged, nonstaining, noncorrosive, nongaseous grout complying with ASTM C 1107. Provide grout, recommended in writing by manufacturer, for exterior applications. |
| B. Erosion-Resistant Anchoring Cement: Factory-packaged, nonshrink, nonstaining, hydraulic-controlled expansion cement formulation for mixing with potable water at Project site to create pourable anchoring, patching, and grouting compound. Provide for... |
| 2.6 FENCE GROUNDING |
| A. Conductors: Bare, solid wire for No. 6 AWG and smaller; stranded wire for No. 4 AWG and larger. |
| 1. Material above Finished Grade: Copper |
| 2. Material on or below Finished Grade: Copper. |
| 3. Bonding Jumpers: Braided copper tape, 1 inch wide, woven of No. 30 AWG bare copper wire, terminated with copper ferrules. |
| B. Connectors and Grounding Rods: Comply with UL 467. |
| 1. Connectors for Below-Grade Use: Exothermic welded type. |
| 2. Grounding Rods: Copper-clad steel, 5/8 by 96 inches |
| PART 3 - EXECUTION |
| 3.1 EXAMINATION |
| A. Examine areas and conditions, with Installer present, for compliance with requirements for site clearing, earthwork, pavement work, and other conditions affecting performance of the Work. |
| 1. Do not begin installation before final grading is completed unless otherwise permitted by Landscape Architect. |
B. Proceed with installation only after unsatisfactory conditions have been corrected.
| 3.2 PREPARATION |
| A. Stake locations of fence lines, gates, and terminal posts. Do not exceed intervals of 500 feet or line of sight between stakes. Indicate locations of utilities, lawn sprinkler system, underground structures, benchmarks, and property monuments. |
| 3.3 CHAIN-LINK FENCE INSTALLATION |
| A. Install chain-link fencing to comply with ASTM F 567 and more stringent requirements indicated in locations as noted on plans. |
| B. Post Excavation: Drill or hand-excavate holes for posts to diameters and spacings indicated, in firm, undisturbed soil. |
| C. Post Setting: Set posts in concrete at indicated spacing into firm, undisturbed soil. |
| 1. Verify that posts are set plumb, aligned, and at correct height and spacing, and hold in position during setting with concrete or mechanical devices. |
| 2. Concrete Fill: Place concrete around posts to dimensions indicated and vibrate or tamp for consolidation. Protect aboveground portion of posts from concrete splatter. |
| a. Concealed Concrete: Top 2 inches below grade to allow covering with surface material. |
| b. Posts Set into Concrete in Sleeves: Use steel pipe sleeves preset and anchored into concrete for installing posts. After posts have been inserted into sleeves, fill annular space between post and sleeve with nonshrink, nonmetallic grout, mixed and ... |
| D. Terminal Posts: Locate terminal end and corner posts per ASTM F 567 and terminal pull posts at changes in horizontal or vertical alignment of 15 degrees or more. For runs exceeding 500 feet, space pull posts an equal distance between corner or end ... |
| E. Line Posts: Space line posts uniformly at 10 feet o.c. |
| F. Post Bracing and Intermediate Rails: Install according to ASTM F 567, maintaining plumb position and alignment of fencing. Diagonally brace terminal posts to adjacent line posts with truss rods and turnbuckles. Install braces at end and at both sid... |
| 1. Locate horizontal braces at midheight of fabric 72 inches or higher, on fences with top rail and at two-third fabric height on fences without top rail. Install so posts are plumb when diagonal rod is under proper tension. |
| G. Top Rail: Install according to ASTM F 567, maintaining plumb position and alignment of fencing. Run rail continuously through line post caps, bending to radius for curved runs and terminating into rail end attached to posts or post caps fabricated ... |
| H. Intermediate and Bottom Rails: Install and secure to posts with fittings. |
| I. Chain-Link Fabric: Apply fabric to outside of enclosing framework. Leave 2 inches between finish grade or surface and bottom selvage unless otherwise indicated. Pull fabric taut and tie to posts, rails, and tension wires. Anchor to framework so fab... |
| J. Tension or Stretcher Bars: Thread through fabric and secure to end, corner, and pull with tension bands spaced not more than 15 inches o.c. |
| K. Tie Wires: Use wire of proper length to firmly secure fabric to line posts and rails. Attach wire at one end to chain-link fabric, wrap wire around post a minimum of 180 degrees, and attach other end to chain-link fabric per ASTM F 626. Bend ends o... |
| 1. Maximum Spacing: Tie fabric to line posts at 12 inches o.c. and to braces at 24 inches o.c. |
L. Barbed Tape: Comply with ASTM F 1911. Install barbed tape uniformly in configurations indicated and fasten securely to prevent movement or displacement.
| 3.4 GROUNDING AND BONDING |
| A. Fence Grounding: Install at maximum intervals of 1500 feet except as follows: |
| 1. Fences within 100 Feet of Buildings, Structures, Walkways, and Roadways: Ground at maximum intervals of 750 feet. |
| a. Other Fence Openings: Ground fence on each side of opening. |
| 1) Bond metal gates to gate posts. |
| 2) Bond across openings, with and without gates, except openings indicated as intentional fence discontinuities. Use No. 2 AWG wire and bury it at least 18 inches below finished grade. |
| B. Protection at Crossings of Overhead Electrical Power Lines: Ground fence at location of crossing and at a maximum distance of 150 feet on each side of crossing. |
| C. Grounding Method: At each grounding location, drive a grounding rod vertically until the top is 6 inches below finished grade. Connect rod to fence with No. 6 AWG conductor. Connect conductor to each fence component at the grounding location, inclu... |
| 1. Make grounding connections to each barbed wire strand with wire-to-wire connectors designed for this purpose. |
| 2. Make grounding connections to each barbed tape coil with connectors designed for this purpose. |
| D. Connections: Make connections to minimize possibility of galvanic action or electrolysis. Select connectors, connection hardware, conductors, and connection methods so metals in direct contact will be galvanically compatible. |
| 1. Use electroplated or hot-tin-coated materials to ensure high conductivity and to make contact points closer in order of galvanic series. |
| 2. Make connections with clean, bare metal at points of contact. |
| 3. Make aluminum-to-steel connections with stainless-steel separators and mechanical clamps. |
| 4. Make aluminum-to-galvanized-steel connections with tin-plated copper jumpers and mechanical clamps. |
| 5. Coat and seal connections having dissimilar metals with inert material to prevent future penetration of moisture to contact surfaces. |
E. Bonding to Lightning Protection System: If fence terminates at lightning-protected building or structure, ground the fence and bond the fence grounding conductor to lightning protection down conductor or lightning protection grounding conductor com...
| 3.5 FIELD QUALITY CONTROL |
| A. Grounding-Resistance Testing: Engage a qualified testing agency to perform tests and inspections. |
| 1. Grounding-Resistance Tests: Subject completed grounding system to a megger test at each grounding location. Measure grounding resistance no fewer than two full days after last trace of precipitation, without soil having been moistened by any means ... |
| 2. Excessive Grounding Resistance: If resistance to grounding exceeds specified value, notify Architect promptly. Include recommendations for reducing grounding resistance and a proposal to accomplish recommended work. |
| 3. Report: Prepare test reports certified by a testing agency of grounding resistance at each test location. Include observations of weather and other phenomena that may affect test results. |
File details come from the government source that posted it. Updated .