This document is a technical specification section for post-frame building systems prepared for the City of Lancaster Department of Public Works Operations Facilities Expansion project (BH 25-061). The specification establishes comprehensive requirements for the design, fabrication, and installation of engineered wood-framed structures including factory-engineered wall columns, roof trusses, roof and wall sheathing, metal roof and wall panels, and associated prefinished metal trim items and accessories. The project requires a complete integrated post-frame building system capable of withstanding structural loads, thermal movements, and weather exposure without water infiltration. The specification designates Conestoga Buildings as the basis-of-design post-frame structure manufacturer, with Lester Buildings and Pioneer Pole Buildings, Inc. identified as approved equals, while ATAS International, Inc. is specified for metal roof and wall panels (Belvedere Grand R Panel Model BWG390), with pre-engineered metal building companies and Fabral identified as approved alternatives. All manufacturers must demonstrate a minimum of five years of experience and appropriate accreditations, with design and engineering responsibility assigned to a registered professional engineer licensed in the project jurisdiction.

The specification requires metal panels in 26-gauge aluminum with 70% PVDF finish and 30-year finish warranty, with roof and wall colors to be selected by the architect. Wood framing must comply with AWPA U1 use category standards for preservative treatment, with UC3B treatment for exterior construction not in contact with ground and UC4A for exterior construction in contact with ground. The specification mandates compliance with multiple ASTM standards for structural performance, fire resistance, air infiltration, and water penetration, including deflection limits of L/360 for primary framing under snow and wind loads and L/150 for secondary framing. Warranties include a two-year manufacturer's warranty on treated materials and metal panel systems from the date of substantial completion, along with a 30-year paint finish warranty on metal panels. The document establishes detailed requirements for shop drawings, delegated design submittals, quality assurance standards, fabrication tolerances, installation procedures, and field inspection protocols to ensure compliance with NFBA standards and applicable building codes.

View the file

Other files

File Type Posted
34-25061 - Addendum 3 Arch-struct-MEP summary.pdf PDF
3-C05 - Site Civil Specifications Combined.pdf PDF
15-2026-10-06 - ES Addendum 1.pdf PDF
35-25061 - Addendum 3 Arch-struct-MEP summary.pdf PDF
10-C08 - Construction Plan.pdf PDF
Demolition.dwg DWG drawing
17-323113 - CHAIN LINK FENCES AND GATES.pdf PDF
321723 - PAVEMENT MARKINGS.pdf PDF
6-C10 - Geotechnical Report.pdf PDF
42-312000 - EARTH MOVING.pdf PDF
PG.dwg DWG drawing
EG.dwg DWG drawing
49-B861-26-01 BidTabulationReport.xlsx XLSX spreadsheet
24-2026-10-14 - CD Addendum 2.pdf PDF
25-061_Pitney Rd Warehouse_Arch-Structural-MEP Drawings_Addendum 3.pdf PDF
28-312000 - EARTH MOVING.pdf PDF
12-25061 - Addendum 1.pdf PDF
48-CD-18 UTILITY PLAN.pdf PDF
9-C06 - Pitney Rd Warehouse Arch-Structural-MEP Bid Set.pdf PDF
32-25-061 Pitney Rd Warehouse Arch-Structural-MEP Drawings Addendum 3.pdf PDF
22-B861-26-01 ADDENDUM 2 - MULTIPRIME Operations Facility Expansion Project.docx DOCX document
25-2026-10-14 - ES Addendum 2.pdf PDF
18-329113 - SOIL PREPARATION.pdf PDF
41-2026-10-29 - ES Addendum 4.pdf PDF
ES.dwg DWG drawing
29-321723 - PAVEMENT MARKINGS.pdf PDF
25061 - Addendum 3_ Arch-struct-MEP summary.pdf PDF
44-B861-26-01 ADDENDUM 4 - MULTIPRIME Operations Facility Expansion Project.docx DOCX document
30-2026-10-23 - ES Addendum 3.pdf PDF
Easements.dwg DWG drawing
Landscape.dwg DWG drawing
16-25-061 Pitney Rd Warehouse Arch-Structural-MEP Addendum 1.pdf PDF
20-City of Lancaster 150 Pitney Road Phase 1 ESA Sept2026.pdf PDF
33-Addendum 03 Arch Front End Specs.pdf PDF
13-133419-RIB- Pre-Engineered Metal Building Systems-09-17-2026.pdf PDF
11-B861-26-01 FINAL - MULTIPRIME Operations Facility Expansion Project.docx DOCX document
26-Pre-Bid Attendees Ops Center Expansion 10072026.pdf PDF
40-2026-10-29 - CD Addendum 4.pdf PDF
38-25061 - Addendum 4 Arch-struct-MEP summary.pdf PDF
2026-10-23 - ES Addendum 3.pdf PDF
Addendum 03_Arch & Front End Specs.pdf PDF
39-25-061 Pitney Rd Warehouse Arch-Structural-MEP Drawings Addendum 4.pdf PDF
45-FINAL QA Report.pdf PDF
2026-10-23 - CD Addendum 3.pdf PDF
47-CD-17 UTILITY PLAN.pdf PDF
7-C09 - Fill Assessment Summary.pdf PDF
31-2026-10-23 - CD Addendum 3.pdf PDF
5-C03 - Operations Facilities Expansion - Bid Specs - Vol I.pdf PDF
312000 - EARTH MOVING.pdf PDF
46-CD-16 UTILITY PLAN.pdf PDF
Show 40 more

Latest 50 of 63 listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Operations Facilities Expansion BH 25-061 City of Lancaster - Department of Public Works

POST FRAME BUILDING SYSTEMS 133418 - 1

SECTION 133418 - POST FRAME BUILDING SYSTEMS

PART 1 GENERAL

1.1 SUMMARY

A. Section Includes:

1. Engineered wood-framed structures consisting of the following components:

a. Factory-engineered wall columns.

b. Factory-engineered roof trusses.

c. Roof sheathing.

d. Factory-engineered metal roof and wall panels.

e. Prefinished metal trim items.

f. Prefinished ridge vents and soffits.

1.2 REFERENCE STANDARDS

A. ASTM E84 - Standard Test Method for Surface Burning Characteristics of Building Materials;

2026a.

B. ASTM E96/E96M - Standard Test Methods for Gravimetric Determination of Water Vapor Transmission Rate of Materials; 2024a.

C. ASTM E108 - Standard Test Methods for Fire Tests of Roof Coverings; 2025.

D. ASTM E331 - Standard Test Method for Water Penetration of Exterior Windows, Skylights, Doors, and Curtain Walls by Uniform Static Air Pressure Difference; 2000 (Reapproved 2023).

E. ASTM E1592 - Standard Test Method for Structural Performance of Sheet Metal Roof and Siding Systems by Uniform Static Air Pressure Difference; 2025.

F. ASTM E1646 - Standard Test Method for Water Penetration of Exterior Metal Roof Panel Systems by Uniform Static Air Pressure Difference; 1995 (Reapproved 2024).

G. ASTM E1677 - Standard Specification for Air Barrier (AB) Material or Assemblies for Low- Rise Framed Building Walls; 2023.

H. ASTM E1680 - Standard Test Method for Rate of Air Leakage through Exterior Metal Roof Panel Systems; 2016 (Reapproved 2022).

I. ASTM E2178 - Standard Test Method for Determining Air Leakage Rate and Calculation of Air Permeance of Building Materials; 2021a.

J. AWPA U1 - Use Category System: User Specification for Treated Wood; 2025.

K. NFPA 285 - Standard Fire Test Method for Evaluation of Fire Propagation Characteristics of Exterior Wall Assemblies Containing Combustible Components; 2025.

L. SSPC-SP 2 - Hand Tool Cleaning; 2024.

POST FRAME BUILDING SYSTEMS 133418 - 2

M. SSPC-SP 3 - Power Tool Cleaning; 2024.

1.3 REFERENCES

A. Reference Standards:

1. Preservative Treated Lumber:

a. American Wood Preservers Association (AWPA).

2. Lumber grading rules and wood species:

a. National Design Specifications for Wood Construction, current edition.

b. Northeastern Lumber Manufacturer’s Association, Inc. (NELMA).

c. Southern Pine Inspection Bureau (SPIB): Southern Pine.

d. West Coast Lumber Inspection Bureau (WCLIB): Douglas Fir.

e. Western Wood Products Association (WWPA): Douglas Fir and Ponderosa Pine.

3. MSR Lumber Producers Council (MSR) for machine stress rated lumber.

4. National Design Specifications for Wood Construction.

5. National Design Standard for Metal Plate Connected Wood Truss Construction (TPI).

1.4 ACTION SUBMITTALS

A. Product Data: For each type of post-frame building system component. Include construction details, material descriptions, dimensions of individual components and profiles, and finishes for the following:

1. Wood-post-framing system.

2. Metal roof and wall panels.

3. Flashing and trim.

4. Accessories.

5. Include data for wood-preservative treatment from chemical treatment manufacturer and certification by treating plant that treated materials comply with requirements. Indicate type of preservative used and net amount of preservative retained.

6. For products receiving waterborne treatment, include statement that moisture content of treated materials was reduced to levels specified before shipment to truss manufacturer.

7. Include copies of warranties from chemical treatment manufacturers for each type of treatment.

B. Shop Drawings: Indicate components by others. Include full building plans, elevations, sections, details and attachments to other work.

1. Foundation Drawings: Show complete layout of manufacturer’s engineered foundation system, including cast-in-place footing pads or foundation and piers, concrete side walls designed to retain salt storage to an elevation 12'-0" above grade, pressure preservative treated wood posts, as required by Manufacturer. Indicate dimensions, and anchorages.

2. Structural-Framing Drawings: Show complete fabrication of primary and secondary framing; include provisions for openings. Indicate bolted connections, distinguishing between shop and field applications. Include transverse cross-sections.

3. Sizes, stress grades, and species of lumber.

4. Anchor-bolt layout.

POST FRAME BUILDING SYSTEMS 133418 - 3

5. Metal Roof and Wall Panel Layout Drawings: Show layouts of metal panels including methods of support. Include details of edge conditions, joints, panel profiles, corners, anchorages, trim, flashings, closures, and special details. Distinguish between factory and field-assembled work.

a. Show all roof-mounted items.

6. Accessory Drawings: Include details of the following items:

a. Flashing and trim.

b. Gutters.

c. Downspouts.

C. Samples for Initial Selection: For units with factory-applied finishes.

D. Delegated-Design Submittal: For post-frame building systems, indicated to comply with performance requirements and design criteria, including analysis data signed and sealed by the qualified professional engineer responsible for their preparation.

E. Certification verifying that the metal roof system has been tested and approved by Underwriter’s Laboratory as Class 90.

1.5 INFORMATIONAL SUBMITTALS

A. Qualification Data: For qualified erector, manufacturer, professional engineer, and land surveyor.

B. Post-Frame Building System Certificates: For post-frame building system, from manufacturer.

1. Letter of Design Certification: Signed and sealed by a qualified professional engineer.

Include the following:

a. Name and location of the Project.

b. Order number.

c. Name of manufacturer.

d. Name of Contractor.

e. Building dimensions including width, length, height, and roof slopes.

f. Indicate compliance with NFBA standards.

g. Governing building code and year of edition.

h. Design Loads: Include dead load, roof live load, collateral loads, roof snow load, deflection, wind loads/speeds and exposure, seismic design category or effective peak velocity-related acceleration/peak acceleration, and auxiliary loads (cranes).

i. Load Combinations: Indicate that loads were applied acting simultaneously with concentrated loads, according to governing building code.

j. Building-Use Category: Indicate category of building use and its effect on load importance factors.

2. Evaluation Reports: For the following, from ICC-ES:

a. Wood-preservative-treated wood.

b. Engineered wood products.

3. Warranties: Sample of special warranties.

POST FRAME BUILDING SYSTEMS 133418 - 4

1.6 CLOSEOUT SUBMITTALS

A. Maintenance data.

B. Warranties.

1.7 QUALITY ASSURANCE

A. Manufacturer Qualifications: A qualified manufacturer with a minimum of five (5) years of experience that is an Accredited Post-Frame Builder by NFBA.

1. Engineering Responsibility: Preparation of comprehensive engineering analysis and Shop Drawings by a professional engineer who is legally qualified to practice in jurisdiction where Project is located.

B. Erector Qualifications: An experienced erector with a minimum of five (5) years experience who specializes in erecting and installing work similar in material, design, and extent to that indicated for this Project and who is acceptable to manufacturer.

C. Design: Standard drawing and design analysis must bear the seal of a registered professional engineer. Design analysis must be on file and furnished by manufacturer upon request.

D. Source Limitations: Obtain engineered post frame building components, including primary and secondary framing and metal panel assemblies from single source from single manufacturer.

1.8 DELIVERY, STORAGE, AND HANDLING

A. Delivery and Acceptance Requirements: Deliver materials to site so as not to be damaged or deformed. Package metal panels for protection during transportation and handling.

1. Inspect trusses upon delivery to site and notify manufacturer immediately if members have damage from handling or show discoloration, corrosion, or other evidence of deterioration. Discard and replace trusses that are damaged or defective.

B. Storage and Handling Requirements:

1. Store and handle materials in accordance with manufacturer’s instructions.

2. Keep materials in manufacturer’s original, unopened containers and packaging until installation.

3. Do not store materials directly on ground.

4. Store materials on flat, level surface, raised above ground, with adequate support to prevent sagging.

5. Protect materials and finish during storage, handling, and installation to prevent damage.

C. Maintain environmental conditions (temperature, humidity, and ventilation) within limits recommended by manufacturer for optimum results. Do not install products under environmental conditions outside manufacturer's absolute limits.

POST FRAME BUILDING SYSTEMS 133418 - 5

1.9 COORDINATION

A. Coordinate sizes and locations of concrete foundations and casting of anchor-bolt inserts into foundation walls, precast walls, and footings.

B. Coordinate installation of roof penetrations.

C. Coordinate metal panel assemblies with roof drainage work, flashing, trim, and construction of supports and other adjoining work to provide a leakproof, secure, and noncorrosive installation.

1.10 WARRANTY

A. Manufacturer’s Special Warranty – Treated Material: Manufacturer agrees to repair, restore, or replace wood structural elements that fail in materials within the specified warranty period.

1. Warranty Period: Two year from date of Substantial Completion.

2. Manufacturer shall repair treated wood structural elements that fail because of insect damage or because of decay that occurs under normal conditions and proper use. If manufacturer is not able to repair wood structural elements to satisfaction of Architect and Owner, manufacturer shall replace damaged treated wood structural elements.

B. Warranty on Metal Panel Finishes:

1. Material and Workmanship Warranty: Manufacturer agrees to repair or replace components of metal panel systems that fail in materials or workmanship within specified warranty period.

a. Failures include, but are not limited to, the following:

1) Structural failures including rupturing, cracking, or puncturing.

2) Deterioration of metals and other materials beyond normal weathering.

b. Warranty Period: Two years from date of Substantial Completion.

2. Paint Finish Warranty from date of Substantial Completion: 30 years.

3. Installer’s Warranty: Submit installer’s warranty, signed by Installer, covering the Work of this Section, including all components of wall panels for the following warranty period:

a. Warranty Period: Two years from date of Substantial Completion.

PART 2 PRODUCTS

2.1 MANUFACTURERS

A. Post Frame Structure:

1. Basis-of-Design Product: Subject to compliance with requirements, provide custom designed and engineered buildings by Conestoga Buildings, or equal as approved by Architect before the Bid.

2. Approved Equals:

a. Lester Buildings.

b. Pioneer Pole Buildings, Inc.

B. Metal Roof Panels, Metal Wall Panels, and Accessories:

POST FRAME BUILDING SYSTEMS 133418 - 6

1. Basis-of-Design Product: Subject to compliance with requirements, provide Belvedere Grand R Panel Model BWG390 metal wall panels, metal roof panels, and required accessories by ATAS International, Inc., or equal as approved by Architect before the Bid.

a. Approved Equals:

1) Equivalent Product by Pre-Engineered Metal Building company.

2) Equivalent Product by Fabral.

2.2 POST FRAME BUILDING SYSTEM PERFORMANCE

A. Delegated Design: Design post-frame building system, including comprehensive engineering analysis by a qualified professional engineer licensed in the state the project is located, using performance requirements and design criteria indicated.

B. Structural Performance: Post-frame building systems shall withstand the effects of gravity loads and the following loads and stresses within limits and under conditions indicated according to procedures in NFBA’s “Post-Frame Building Design Manual”.

1. Deflection and Drift Limits: Design post-frame building system assemblies to withstand design loads with deflections no greater than the following:

a. Primary Framing:

1) L/360 for roof snow load.

2) L/360 for wind load.

b. Secondary Framing:

1) L/150 for roof dead load + roof snow load; but not less than that required to maintain positive drainage for the greater of dead load + ½ roof snow load or dead load + 5 psf.

2) L/150 for wind load on walls and roof.

3) L/180 for roof snow load (but not less than 20 psf) on sheathing.

c. Design secondary-framing system to accommodate deflection of primary framing and construction tolerances, and to maintain clearances at openings.

2. Metal panel assemblies shall withstand the effects of gravity loads and loads and stresses within limits and under conditions indicated according to ASTM E1592.

C. Seismic Performance: Metal building system shall withstand the effects of earthquake motions determined according to ASCE/SEI 7.

D. Thermal Movements: Allow for thermal movements resulting from the following maximum change (range) in ambient and surface temperatures by preventing buckling, opening of joints, overstressing of components, failure of joint sealants, failure of connections, and other detrimental effects. Base engineering calculations on surface temperatures of materials due to both solar heat gain and nighttime-sky heat loss.

1. Temperature Change: 120 deg F.

E. Structural Performance for Metal Roof and Wall Panels: Provide metal panel systems capable of withstanding the effects of the following loads, based on testing according to ASTM E1592:

1. Wind Loads: As indicated on Structural Drawing S001.

POST FRAME BUILDING SYSTEMS 133418 - 7

F. Air Infiltration for Metal Roof Panels: Air leakage of not more than 0.06 cfm/sq. ft. when tested according to ASTM E1680 at the following test-pressure difference:

1. Test-Pressure Difference: 1.57 lbf/sq. ft.

G. Air Infiltration for Metal Wall Panels: Air leakage of not more than 0.06 cfm/sq. ft. when tested according to ASTM E 283 at the following test-pressure difference:

1. Test-Pressure Difference: 1.57 lbf/sq. ft.

H. Water Penetration for Metal Roof Panels: No water penetration when tested according to ASTM E1646 at the following test-pressure difference:

1. Test-Pressure Difference: 2.86 lbf/sq. ft.

I. Water Penetration for Metal Wall Panels: No water penetration when tested according to ASTM E331 at the following test-pressure difference:

1. Test-Pressure Difference: 2.86 lbf/sq. ft.

J. Wind-Uplift Resistance: Provide metal roof panel assemblies that comply with ASTM E1592 for wind-uplift-resistance class indicated.

2.3 POST-FRAME BUILDING SYSTEMS

A. Description: Provide a complete, integrated set of mutually dependent components and assemblies that form a post-frame building system capable of withstanding structural and other loads, thermally induced movement, and exposure to weather without failure or infiltration of water into building interior.

1. Provide post-frame building system of size and with roof slopes and spans indicated.

B. Primary-Frame Type: Solid member, structural framing system without interior columns, except for those bearing on or adjacent to the precast wall system. Roof framing to be wood trusses or solid-member rafters to meet clearances and maximum and minimum dimensions shown on drawings.

C. End-Wall Framing: Manufacturer’s standard for buildings not required to be expandable, consisting of primary frame, capable of supporting one-half of a bay design load, and end-wall columns.

D. Secondary Framing: Manufacturer's standard secondary framing, including purlins, girts, and joists.

2.4 FOUNDATION SYSTEM

A. Foundation: Provide concrete foundation system, engineered and designed by post-frame manufacturer, or by associate firm approved by post-frame manufacturer, to accommodate loads of post-frame building system indicated.

POST FRAME BUILDING SYSTEMS 133418 - 8

B. Wood products used in foundations must be protected with pressure preservative chemical treatments to retention levels for Use Category UC4B or better per AWPA-UI.

2.5 POST-FRAME WOOD FRAMING

A. Primary Framing: Manufacturer’s standard primary-framing system, designed to withstand required loads and specified requirements. Primary framing includes transvers and lean-to frames; rafter, rake, and canopy beams; sidewall, intermediate, end-wall, and corner columns;

and wind bracing.

1. General: Provide frames with attachment plates, bearing plates, and splice members.

Factory drill for field-bolted assembly. Provide frame span and spacing indicated.

a. Slight variations in span and spacing may be acceptable if necessary to comply with manufacturer’s standard, as approved by Architect.

2. Posts: Wall posts shall be solid-sawn or laminated, structural wood products, identified in the American Wood Council’s (AWC) National Design Specification for Wood Construction.

B. Secondary Framing: Manufacturer's standard secondary framing, including purlins, girts, eave struts, flange bracing, base members, gable angles, clips, headers, jambs, and other miscellaneous structural members. Unless otherwise indicated, fabricate framing from either cold-formed, structural-steel sheet or roll-formed, metallic-coated steel sheet, prepainted with coil coating, to comply with the following:

1. Purlins and Girts: Provide roof purlins and wall girts of solid sawn structural wood products.

2. Framing for Openings: Provide secondary posts, headers, and sills as required for indicated layout of doors and windows. Frame head and jamb of door openings and head, jamb, and sill of other openings.

3. Miscellaneous Structural Members: Manufacturer's standard, solid sawn 2x lumber sections.

C. Bracing: Provide adjustable wind bracing as required by manufacturer or by manufacturer’s engineer on record, custom-engineered and designed for conditions indicated.

D. Bolts: Provide hot-dip galvanized bolts for structural-framing components that are galvanized.

2.6 SHEATHING

A. Plywood Roof and Wall Sheathing: Exterior, Structural I sheathing.

1. Span Rating: Not less than 24/0.

2. Nominal Thickness: As indicated on the Drawings; not less than 5/8 inch for roof and 1/2 inch for walls.

2.7 FACTORY WOOD TREATMENT (ADDENDUM #3)

POST FRAME BUILDING SYSTEMS 133418 - 9

A. Treated Lumber and Plywood: Comply with requirements of AWPA U1 - Use Category System for wood treatments determined by use categories, expected service conditions, and specific applications.

1. Treat as follows:

a. Category UC3b for exterior construction not in contact with ground.

b. Category UC4a for exterior construction in contact with ground.

2. Preservative-Treated Wood: Provide lumber and plywood marked or stamped by an ALSC-accredited testing agency, certifying level and type of treatment in accordance with AWPA standards.

3. Treatment shall not promote corrosion of metal fasteners.

4. Design Value Adjustment Factors: Treated lumber shall be tested according to

ASTM D5664, and design value adjustment factors shall be calculated according to

ASTM D 6841.

B. Preservative Treatment:

1. Preservative Pressure Treatment of Lumber Above Grade: AWPA U1, Use Category UC3B, Commodity Specification A using waterborne preservative.

a. Treat the following items

1) Treat wood cants, nailers, curbs, equipment support bases, blocking, stripping, and similar members.

2) Treat lumber and sheathing exposed to weather.

3) Treat lumber and sheathing in contact with roofing, flashing, waterproofing, or vapor barriers.

4) Treat lumber and sheathing in contact with masonry or concrete.

5) Treat lumber and sheathing less than 18 inches (450 mm) above grade.

2.8 METAL ROOF & WALL PANELS

A. Basis-of-Design Product: Belvedere Grand R Panel Model BWG390 aluminum panels with exposed fasteners as manufactured by ATAS International, Inc., or equal approved by before the Bid.

1. Thickness: 26 gauge.

B. Panel Finish: 70% PVDF, with a 30-year finish warranty.

C. Colors:

1. Roof: As selected by Architect from manufacturer's full range of colors.

2. Wall: As selected by Architect from manufacturer's full range of colors.

2.9 TRANSLUCENT PANEL SYSTEM

A. Translucent Panels: See Section 133419 - Pre-Engineered Metal Building Systems.

1. Provide translucent panel system approved by the metal wall panel manufacturer. If panel profile does not match adjacent panels, provide connecting trim components recommended by manufacturer.

POST FRAME BUILDING SYSTEMS 133418 - 10

2.10 ACCESSORIES

A. General: Provide accessories as standard with metal panel system manufacturer and as specified. Fabricate and finish accessories at the factory to greatest extent possible, by manufacturer's standard procedures and processes. Comply with indicated profiles and with dimensional and structural requirements.

1. Form exposed sheet metal accessories that are without excessive oil-canning, buckling, and tool marks and that are true to line and levels indicated, with exposed edges folded back to form hems.

B. Roof Panel Accessories: Provide components required for a complete metal roof panel assembly including copings, fasciae, corner units, ridge closures, clips, sealants, gaskets, fillers, closure strips, and similar items. Match material and finish of metal roof panels unless otherwise indicated.

C. Ridge Vents: As manufactured or approved by post frame building manufacturer, with vent openings do not permit direct water or weather entry; flanged to receive shingles.

1. Net Free Ventilation Area: 12 square inches per linear foot minimum.

D. Wall Panel Accessories: Provide components required for a complete metal wall panel assembly including copings, fasciae, mullions, sills, corner units, clips, sealants, gaskets, fillers, closure strips, and similar items. Match material and finish of metal wall panels unless otherwise indicated.

E. Flashing and Trim: Zinc-coated (galvanized) or aluminum-zinc alloy-coated steel sheet, 0.018-inch nominal uncoated steel thickness, prepainted with coil coating; finished to match adjacent metal panels.

F. Gutters: Zinc-coated (galvanized) or aluminum-zinc alloy-coated steel sheet, 0.018-inch nominal uncoated steel thickness, prepainted with coil coating; finished to match roof fascia and rake trim. Match profile of gable trim, complete with end pieces, outlet tubes, and other special pieces as required. Fabricate in minimum 96-inch long sections, sized according to SMACNA's "Architectural Sheet Metal Manual."

1. Gutter Supports: Fabricated from same material and finish as gutters.

2. Strainers: Bronze, copper, or aluminum wire ball type at outlets.

G. Downspouts: Zinc-coated (galvanized) or aluminum-zinc alloy-coated steel sheet, 0.018-inch nominal uncoated steel thickness, prepainted with coil coating; finished to match metal wall panels. Fabricate in minimum 10-foot long sections, complete with formed elbows and offsets.

1. Mounting Straps: Fabricated from same material and finish as gutters.

H. Roof Curbs: Zinc-coated (galvanized) or aluminum-zinc alloy-coated steel sheet, 0.048-inch nominal uncoated steel thickness prepainted with coil coating; finished to match metal roof panels; with welded top box and bottom skirt, and integral full-length cricket; capable of withstanding loads of size and height indicated.

I. Pipe Flashing: Premolded, EPDM pipe collar with flexible aluminum ring bonded to base.

POST FRAME BUILDING SYSTEMS 133418 - 11

J. Water-Repellent Preservative: NWWDA-tested and -accepted formulation containing 3-iodo-2-propynyl butyl carbamate, combined with an insecticide containing chloropyrifos as its active ingredient.

K. Underlayment for Metal Roofing Installation on Sheathing: Synthetic non-asphaltic sheet, intended by manufacturer for installation under metal panel roof materials.

1. Basis-of-Design Product: Provide DuPont Tyvek Roof Protector as manufactured by Dupont, or equal as approved by the Architect.

2. Type: Four-layer syntheic underlayment.

3. Thickness: 10 mils.

4. Flammability: Minimum of Class A, in accordance with ASTM E108 test method.

5. Water Vapor Permeance: 0.05 perms, maximum, when tested in accordance with ASTM

E96/E96M, Desiccant Method A.

6. UV Exposure: Up to 90 days.

L. Weather Barrier for Metal Wall Panels on Sheathing:

1. Building Wrap: ASTM E1677, Type I air barrier; with flame-spread and smoke-developed indexes of less than 25 and 450, respectively, when tested according to ASTM E84; UV stabilized; and acceptable to authorities having jurisdiction.

a. Basis-of-Design Product: Provide DuPont Tyvek CommercialWrap, or equal.

b. Water-Vapor Transmission: 23 perms maximum, when tested in accordance with

ASTM E96, Method A.

c. Air Permeance: Not more than 0.001 cfm/sq. ft. at 1.57 psf when tested according to

ASTM E2178.

d. Allowable UV Exposure Time: Not less than nine months.

e. Flame Propagation Test: Materials and construction shall be as tested according to

NFPA 285.

f. Surface Burning Characteristics: Class A, when tested in accordance with ASTM

E84.

M. Draftstopping and Fire Blocking: Provide draftstopping at trusses and fireblocking where required by building code.

2.11 FABRICATION

A. General: Design components and field connections required for erection to permit easy assembly.

1. Mark each piece and part of the assembly to correspond with previously prepared erection drawings, diagrams, and instruction manuals.

2. Fabricate structural framing to produce clean, smooth cuts and bends. Punch holes of proper size, shape, and location. Members shall be free of cracks, tears, and ruptures.

B. Tolerances: Comply with NFBA's "Accepted Practices for Post-Frame Building Construction:

Framing Tolerances" and “Accepted Practices for Post-Frame Building Construction: Metal Panel and Trim Installation Tolerances” for fabrication and erection tolerances.

POST FRAME BUILDING SYSTEMS 133418 - 12

C. Primary and Secondary Framing: Shop fabricate framing components to indicated size and section, with baseplates, bearing plates, stiffeners, and other items required for erection. Cut, form, punch, drill, and weld framing for bolted field assembly.

D. Metal Panels: Fabricate and finish metal panels at the factory to greatest extent possible, by manufacturer's standard procedures and processes, as necessary to fulfill indicated performance requirements. Comply with indicated profiles and with dimensional and structural requirements.

1. Provide panel profile, including major ribs and intermediate stiffening ribs, if any, for full length of metal panel.

PART 3 EXECUTION

3.1 EXAMINATION

A. Examine substrates, areas, and conditions, with erector present, for compliance with requirements for installation tolerances and other conditions affecting performance of the Work.

B. Verify that the work of this section may be installed in accordance with all applicable codes and regulations, and with original design as shown and indicated on the shop drawings as approved by the designer of record.

C. Proceed with erection only after unsatisfactory conditions have been corrected.

3.2 PREPARATION

A. Clean and prepare surfaces to be painted according to manufacturer's written instructions for each particular substrate condition.

B. Provide temporary shores, guys, braces, and other supports during erection to keep structural framing secure, plumb, and in alignment against temporary construction loads and loads equal in intensity to design loads. Remove temporary supports when permanent structural framing, connections, and bracing are in place unless otherwise indicated.

3.3 INSTALLATION OF FOUNDATIONS

A. Install all foundations, concrete foundation piers, and associated foundation elements as shown in the approved design shop drawings or in component supplier installation instruction sheets.

3.4 ERECTION OF STRUCTURAL FRAMING

A. Erect post-frame building system according to manufacturer's written erection instructions and shop drawings.

B. Do not field cut, drill, or alter structural members without written approval from post-frame building system manufacturer's professional engineer.

POST FRAME BUILDING SYSTEMS 133418 - 13

C. Set structural framing accurately in locations and to elevations indicated, according to NFBA specifications referenced in this Section. Maintain structural stability of frame during erection.

D. Align and adjust structural framing before permanently fastening. Before assembly, clean bearing surfaces and other surfaces that will be in permanent contact with framing. Perform necessary adjustments to compensate for discrepancies in elevations and alignment.

1. Level and plumb individual members of structure.

2. Make allowances for difference between temperature at time of erection and mean temperature when structure will be completed and in service.

E. Primary Framing and End Walls: Erect framing level, plumb, rigid, secure, and true to line.

Level baseplates to a true even plane with full bearing to supporting structures, set with doublenutted anchor bolts. Use grout to obtain uniform bearing and to maintain a level base-line elevation. Moist-cure grout for not less than seven days after placement.

F. Secondary Framing: Erect framing level, plumb, rigid, secure, and true to line. Field bolt secondary framing to clips attached to primary framing.

1. Provide rake or gable purlins with tight-fitting closure channels and fasciae.

2. Locate and space wall girts to suit openings such as doors and windows.

3. Provide supplemental framing at entire perimeter of openings, including doors, windows, louvers, ventilators, and other penetrations of roof and walls.

G. Bracing: Install bracing as required by manufacturer where indicated on shop drawings.

H. Roof Sheathing: Secure panels with long dimension perpendicular to framing members, with ends staggered and over firm bearing.

1. Nail or screw to wood framing. Apply a continuous bead of glue to framing members at edges of wall sheathing panels.

2. Space panels 1/8 inch (3 mm) apart at edges and ends.

I. Framing for Openings: Provide framing of proper design and size to reinforce openings and to carry loads and vibrations imposed, including equipment furnished under mechanical and electrical work. Securely attach to structural framing.

J. Erection Tolerances: Install all framing to within tolerances indicated in the NFBA Framing Tolerances standard, “Accepted Practices for Post Frame Building Construction: Framing Tolerances.”

3.5 METAL PANEL INSTALLATION, GENERAL

A. Examination: Examine primary and secondary framing to verify that structural-panel support members and anchorages have been installed within alignment tolerances required by manufacturer.

1. Examine roughing-in for components and systems penetrating metal panels, to verify actual locations of penetrations relative to seams before metal panel installation.

POST FRAME BUILDING SYSTEMS 133418 - 14

B. General: Anchor metal panels and other components of the Work securely in place, with provisions for thermal and structural movement.

1. Field cut metal panels as required for doors, windows, and other openings. Cut openings as small as possible, neatly to size required, and without damage to adjacent metal panel finishes.

a. Field cutting of metal panels by torch is not permitted unless approved in writing by manufacturer.

2. Install metal panels perpendicular to structural supports unless otherwise indicated.

3. Flash and seal metal panels with weather closures at perimeter of openings and similar elements. Fasten with self-tapping screws.

4. Locate and space fastenings in uniform vertical and horizontal alignment.

5. Locate metal panel splices over structural supports with end laps in alignment.

6. Lap metal flashing over metal panels to allow moisture to run over and off the material.

C. Lap-Seam Metal Panels: Install screw fasteners using power tools with controlled torque adjusted to compress EPDM washers tightly without damage to washers, screw threads, or metal panels. Install screws in predrilled holes.

1. Arrange and nest side-lap joints so prevailing winds blow over, not into, lapped joints.

Lap ribbed or fluted sheets one full rib corrugation. Apply metal panels and associated items for neat and weathertight enclosure. Avoid "panel creep" or application not true to line.

D. Metal Protection: Where dissimilar metals contact each other or corrosive substrates, protect against galvanic action by painting contact surfaces with corrosion-resistant coating, by applying rubberized-asphalt underlayment to each contact surface, or by other permanent separation as recommended by metal roof panel manufacturer.

E. Joint Sealers: Install gaskets, joint fillers, and sealants where indicated and where required for weatherproof performance of metal panel assemblies. Provide types of gaskets, fillers, and sealants indicated; or, if not indicated, provide types recommended by metal panel manufacturer.

1. Seal metal panel end laps with double beads of tape or sealant the full width of panel. Seal side joints where recommended by metal panel manufacturer.

2. Prepare joints and apply sealants to comply with requirements in Section 079200 "Joint Sealants."

F. Metal Panel Installation Tolerances: Comply with tolerances recommended in NFBA’s Cladding Tolerances standard, “Accepted Practices for Post-Frame Building Construction:

Metal Panel and Trim Installation Tolerances.”

3.6 METAL ROOF PANEL INSTALLATION

A. General: Provide metal roof panels of full length from eave to ridge unless otherwise indicated or restricted by shipping limitations.

1. Install ridge caps as metal roof panel work proceeds.

2. Flash and seal metal roof panels with weather closures at eaves and rakes. Fasten with self-tapping screws.

POST FRAME BUILDING SYSTEMS 133418 - 15

3. Flash and seal all penetrations through roof panels with manufacturer’s standard flashing.

B. Lap-Seam Metal Roof Panels: Fasten metal roof panels to supports with exposed fasteners at each lapped joint, at location and spacing recommended by manufacturer.

1. Provide metal-backed sealing washers under heads of exposed fasteners bearing on weather side of metal roof panels.

2. Provide sealant tape at lapped joints of metal roof panels and between panels and protruding equipment, vents, and accessories.

3. Apply a continuous ribbon of sealant tape to weather-side surface of fastenings on end laps and on side laps of nesting-type metal panels, on side laps of ribbed or fluted metal panels, and elsewhere as needed to make metal panels weatherproof to driving rains.

4. At metal panel splices, nest panels with minimum 6-inch end lap, sealed with butyl rubber sealant and fastened together by interlocking clamping plates.

C. Metal Fascia Panels: Align bottom of metal panels and fasten with blind rivets, bolts, or self-drilling or self-tapping screws. Flash and seal metal panels with weather closures where fasciae meet soffits, along lower panel edges, and at perimeter of all openings.

3.7 METAL WALL PANEL INSTALLATION

A. General: Install metal wall panels in orientation, sizes, and locations indicated on Drawings.

Install panels perpendicular to girts, extending full height of building, unless otherwise indicated. Anchor metal wall panels and other components of the Work securely in place, with provisions for thermal and structural movement.

1. Unless otherwise indicated, begin metal panel installation at corners with center of rib lined up with line of framing.

2. Shim or otherwise plumb substrates receiving metal wall panels.

3. When two rows of metal panels are required, lap panels 4 inches minimum.

4. When building height requires two rows of metal panels at gable ends, align lap of gable panels over metal wall panels at eave height.

5. Rigidly fasten base end of metal wall panels and allow eave end free movement for thermal expansion and contraction. Predrill panels.

6. Flash and seal metal wall panels with weather closures at eaves and rakes, and at perimeter of all openings. Fasten with self-tapping screws.

7. Install screw fasteners in predrilled holes.

8. Install flashing and trim as metal wall panel work proceeds.

9. Apply elastomeric sealant continuously between metal base channel (sill angle) and concrete, and elsewhere as indicated on Drawings; if not indicated, as necessary for waterproofing.

10. Align bottom of metal wall panels and fasten with blind rivets, bolts, or self-drilling or self-tapping screws.

11. Provide weatherproof escutcheons for pipe and conduit penetrating exterior walls.

B. Metal Wall Panels: Install metal wall panels on exterior side of girts. Attach metal wall panels to supports with fasteners as recommended by manufacturer.

POST FRAME BUILDING SYSTEMS 133418 - 16

3.8 ACCESSORY INSTALLATION

A. General: Install accessories with positive anchorage to building and weathertight mounting, and provide for thermal expansion. Coordinate installation with flashings and other components.

1. Install components required for a complete metal roof panel assembly, including trim, copings, ridge closures, seam covers, flashings, sealants, gaskets, fillers, closure strips, and similar items.

2. Install components for a complete metal wall panel assembly, including trim, copings, corners, seam covers, flashings, sealants, gaskets, fillers, closure strips, and similar items.

3. Where dissimilar metals contact each other or corrosive substrates, protect against galvanic action by painting contact surfaces with corrosion-resistant coating, by applying rubberized-asphalt underlayment to each contact surface, or by other permanent separation as recommended by manufacturer.

B. Flashing and Trim: Comply with performance requirements, manufacturer's written installation instructions, and SMACNA's "Architectural Sheet Metal Manual." Provide concealed fasteners where possible, and set units true to line and level. Install work with laps, joints, and seams that will be permanently watertight and weather resistant.

1. Install exposed flashing and trim that is without excessive oil-canning, buckling, and tool marks and that is true to line and levels indicated, with exposed edges folded back to form hems. Install sheet metal flashing and trim to fit substrates and to result in waterproof and weather-resistant performance.

2. Expansion Provisions: Provide for thermal expansion of exposed flashing and trim. Space movement joints at a maximum of 10 feet with no joints allowed within 24 inches of corner or intersection. Where lapped or bayonet-type expansion provisions cannot be used or would not be sufficiently weather resistant and waterproof, form expansion joints of intermeshing hooked flanges, not less than 1 inch deep, filled with mastic sealant (concealed within joints).

C. Gutters: Join sections with riveted-and-soldered or lapped-and-sealed joints. Attach gutters to eave with gutter hangers spaced as required for gutter size, but not more than 36 inches o.c.

using manufacturer's standard fasteners. Provide end closures and seal watertight with sealant.

Provide for thermal expansion.

D. Downspouts: Join sections with 1-1/2-inch telescoping joints. Provide fasteners designed to hold downspouts securely 1 inch away from walls; locate fasteners at top and bottom and at approximately 60 inches o.c. in between.

1. Provide elbows at base of downspouts to direct water away from building.

2. Tie downspouts to underground drainage system indicated on civil drawings.

E. Roof Curbs: Install curbs at locations indicated on Drawings. Install flashing around bases where they meet metal roof panels.

F. Pipe Flashing: Form flashing around pipe penetration and metal roof panels. Fasten and seal to panel as recommended by manufacturer.

G. Insulation System: Install in compliance with manufacturer's written instructions.

POST FRAME BUILDING SYSTEMS 133418 - 17

3.9 CLEANING AND PROTECTION

A. Repair damaged galvanized coatings on galvanized items with galvanized repair paint according to ASTM A 780 and manufacturer's written instructions.

B. Touchup Painting: After erection, promptly clean, prepare, and prime or reprime field connections, rust spots, and abraded surfaces of prime-painted structural framing, bearing plates, and accessories.

1. Clean and prepare surfaces by SSPC-SP 2, “Hand Tool Cleaning,” or by SSPC-SP 3, “Power Tool Cleaning.”

2. Apply a compatible primer of same type as shop primer used on adjacent surfaces.

C. Metal Panels: Remove temporary protective coverings and strippable films, if any, as metal panels are installed. On completion of metal panel installation, clean finished surfaces as recommended by metal panel manufacturer. Maintain in a clean condition during construction.

1. Replace metal panels that have been damaged or have deteriorated beyond successful repair by finish touchup or similar minor repair procedures.

END OF SECTION 133418

POST FRAME BUILDING SYSTEMS 133418 - 18

THIS PAGE INTENTIONALLY LEFT BLANK