This document is a Request for Information (RFI) Form containing pre-proposal inquiries submitted by D Square Construction LLC regarding a federal construction solicitation. The inquiries were submitted on 02/13/26 by Dennis Driskill (520-748-9371) and address both solicitation evaluation factors and statement of work technical data.
The RFI covers nine substantive questions regarding project execution requirements: clarification on removal of existing roof penetrations and how far below the roof deck pipe and conduit terminations should extend; confirmation of crane location and dumpster placement in the Cantina parking lot; clarification on whether existing light packs and electrical outlets should be retained or replaced, with procedures for defective items discovered during construction; confirmation that the roof hatch on Building B647 cannot be used and approval of a temporary bridge design; requirements for protecting the eastside doors to Building B647 with a covered walkway during business hours; availability of temporary egress points for roof access; procedures for temporarily replacing mechanical or electrical equipment removed during business hours; and whether temporary HEPA covering or other measures are permitted for roofing work afterhours. All pre-proposal inquiries must be submitted via email to alex.arter@va.gov using an editable form, with telephone requests not accepted.
View the file
Other files
Show all 32
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Abandon pipes should be removed back to a main line, conduits should be removed back to a junction box, panel or disconnect.
A crane location to be determined If a light pack or electrical outlet is found to be defective after start of construction submit an RFI at that time.
Roof hatch on B647 cannot be used during construction. Submit on plans for temporary bridge to VA for review
Eastside doors cannot be blocked during business hours. Provide covered walkway.
Access will be provided after hours.
Any mechanical or electrical equipment that is required to be removed for roofing work during business hours must have temporary equipment installed.
No
VHAMACHaemmK Highlight
VHAMACHaemmK Highlight
VHAMACHaemmK Highlight
VHAMACHaemmK Highlight
VHAMACHaemmK Highlight
VHAMACHaemmK Highlight
VHAMACHaemmK Highlight
VHAMACHaemmK Highlight
VHAMACHaemmK Highlight
VHAMACHaemmK Highlight
VHAMACHaemmK Highlight
VHAMACHaemmK Highlight
VHAMACHaemmK Highlight
File details come from the government source that posted it. Updated .