Attachment 169B EP.401T.pdf
PDF 276 KB Posted
- Attached to
- Z1DA-- Renovate OR for Hybrid Installation
- Solicitation number
- 36C26126R0009
About this file
This is an electrical one-line diagram for temporary operating room (OR) trailers at the Veterans Affairs facility located at 10535 Hospital Way, Mather, California 95655. The diagram illustrates the power distribution system for three hybrid temporary trailers, each containing critical, equipment, and normal electrical panels rated at 200 amps at 208Y/120 volts, three-phase, four-wire configuration.
The electrical system incorporates multiple distribution boards and automatic transfer switches (ATS) to manage power flow between normal utility supply and backup generator systems. Key components include existing emergency distribution boards (EHS1001A, EHS1001B, NSH1001A, NSH1001B) with ratings up to 4,000 amps at 480Y/277 volts, switchboards (SWB-NORM, SWB-CRIT, SWB-EQ) rated at 600-1,200 amps, and step-down transformers (CRT, EQT, NT) each rated at 112.5 kilovolt-amperes converting 480 volts to 208Y/120 volts. The work scope includes providing and installing new breakers within existing distribution boards, routing feeders overhead from the electrical room to trailer panelboards, and establishing generator start signal connections. Feeder conductor specifications are detailed in six categories using copper conductors ranging from 3/0 to 500 kilocircular mil sizes with conduit runs from 2 to 3.5 inches. The document is dated September 30, 2025, and was prepared by AESUS design group for the U.S. Department of Veterans Affairs Office of Construction and Facilities Management.
View the file
Other files
Show 40 more
50 files listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
4000 AT
4000 AF
100%
(E) EHS1001A
4,000A, 480Y/277V
3PH, 4W, SCCR=65KA
600 AT
800 AF
100%
(E) NSH1001A
4,000A, 480Y/277V
3PH, 4W, SCCR=65KA
600 AT
800 AF
100%
(E) ATS-NCHILL
(E) ATS-NHD654A
800 AT
800 AF
100%
(E) ATS-WCCH-1
400 AT
400 AF
100%
(E) ATS-WCCH-2
400 AT
400 AF
100%
(E) ATS-NHD51A
400 AT
400 AF
100%
600 AT
600 AF
100%
600 AT
600 AF
100%
400 AT
400 AF
100%
800 AT
800 AF
100%
1200 AT
1200 AF
100%
800 AT
800 AF
100%
800 AT
800 AF
100%
225 AT
250 AF
100%
600 AT
600 AF
100%
150 AT
250 AF
100%
1200 AT
1200 AF
100%
4000 AT
4000 AF
100%
(E) B647 N (E) PANEL N (E) XFMR AC-1(E) SPARE (E) CATS1001E (E) QATS1001D(E) QATS1001A (E) CATS1001B(E) SATS1001A(E) QATS1001C (E) EATS-1 (646) (E) SPARE
(E) TIE
600 AT
600 AF
100%
600 AT
600 AF
100%
400 AT
400 AF
100%
800 AT
800 AF
100%
804 AT
1200 AF
100%
800 AT
800 AF
100%
800 AT
800 AF
100%
600 AT
800 AF
100%
600 AT
800 AF
100%
200 AT
250 AF
100%
400 AT
400 AF
100%
250 AT
250 AF
100%
(E) ATS AC (E) ATS AC-E(E) NHD51A (E) ATS-WCCH-1(E) NHD645A (E) N CHILL(E) NSB11B (E) SPARE(E) NSB12B (E) PANEL MDP (E) 1N4MP12(E) PV SYS
4000 AT
4000 AF
100%
4000 AT
4000 AF
100%
TO FPINCOMING
800 AT
800 AF
100%
(E) ATS-WCCH-2
SWB-NORM
1,200A, 480Y/277V
3PH, 4W, SCCR=65KA
1200 AT
1200 AF
LSI,
100%
600 AT
600 AF
LSI,
80%
ATS-CR
600A, 4P, 480Y/277V WCR=65kA
CRL
400 A 208Y/120V
3PH, 4W
#1/0(CU)
600 AT
600 AF
LSI,
80%
ATS-EQ
600A, 4P, 480Y/277V WCR=65kA
EQL
400 A 208Y/120V
3PH, 4W
#1/0(CU)
NL
400 A 208Y/120V
3PH, 4W
#1/0(CU)
CRT
112.5KVA
480V 208Y/120V
EQT
112.5KVA
480V 208Y/120V
NT
112.5KVA
480V 208Y/120V
TO EXISTING
GEN-BOARD
EHS1001B
3,000A, 480Y/277V
3PH, 4W, SCCR=22KA
600 AT
600 AF
LSI,
80%
CRITICAL
PANEL
200 A 208Y/120V
3PH, 4W
EQUIP
PANEL
200 A 208Y/120V
3PH, 4W
NORMAL
PANEL
200 A 208Y/120V
3PH, 4W
CRITICAL
PANEL
200 A 208Y/120V
3PH, 4W
EQUIP
PANEL
200 A 208Y/120V
3PH, 4W
NORMAL
PANEL
200 A 208Y/120V
3PH, 4W
CRITICAL
PANEL
200 A 208Y/120V
3PH, 4W
EQUIP
PANEL
200 A 208Y/120V
3PH, 4W
NORMAL
PANEL
200 A 208Y/120V
3PH, 4W
TRAILER #1
TRAILER #2
TRAILER #3
44TYPICAL
55 55
SPD
100KA
SPD
100KA
SPD
100KA
(3) #10, #10G, 3/4"C (3) #10, #10G, 3/4"C (3) #10, #10G, 3/4"C
BUS TAP
(4) 600 A SPACES 225 AT
225 AF N.C.,
0%
SWB-CRIT
600A, 480Y/277V
3PH, 4W, SCCR=42KA
225 AT
225 AF
LSI
80%
400 AT
400 AF
LSI
80%
225 AT
225 AF
LSI
80%
200 AT
200 AF
LSI
80%
SWB-EQ
600A, 480Y/277V
3PH, 4W, SCCR=42KA
225 AT
225 AF
LSI
80%
400 AT
400 AF
LSI
80%
225 AT
225 AF
LSI
80%
200 AT
200 AF
LSI
80%
600 AT
600 AF
LSI
80%
3 3 3 3
3 3
4 4 4
5 5 5
6 6 6 6 6 6 6 6 6
(E) NSH1001B
4000A, 480Y/277V
3PH, 4W
1200AT
1200AF
100%
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Architecture, Engineering, and, Sustainable DesignAESUS 1050 E. Southern Ave, Suite #D, Tempe, Arizona 85282, (480) 454-2861 design group
A u to d e s k D o c s /A
E S
U S
P ro je c ts
/1
V
A T e m p -O
R
E L
E C
U
P G
R A
D E
D .r v t
/1
/2
:4
:1
A
M
EP.401T
ELECTRICAL ONE-LINE DIAGRAM -
TEMP OR TRAILER
10535 HOSPITAL WAY MATHER, CA 95655
612A4-25-004
N/A
SEPT. 30, 2025 AESUS AESUS
HYBRID TEMPORARY TRAILERS100% Submittal
N.T.S.1 ELECTRICAL ONE-LINE DIAGRAM
Revisions: Date:
BIDDER RFIS 02/11/2026
1 PROVIDE AND INSTALL NEW BREAKER WITHIN EXISTING EMERGENCY
DISTRIBUTION BOARD. PROVIDE ANY REQUIRED BUS EXTENSIONS,
MOUNTING KITS OR SECTIONS REQUIRED TO ACCOMMODATE NEW BREAKER.
2 PROVIDE NEW CIRCUIT BREAKER IN AVAILABLE SPACE WITHIN EXISTING
DISTRIBUTION BOARD TO SERVE LOAD. CONFIRM TRIP SETTING IS SET TO
1200A.
3 TERMINATE FEEDER TO TRAILER PANELBOARD. PANELBOARD BY TRAILER
SUPPLIER. FAULT CURRENT AT TRAILER PANELBOARD IS LESS THAN 10KA.
4 FIELD ROUTE FROM ELECTRICAL ROOM TO TRAILER PANELBOARDS,
OVERHEAD. COORDINATE EXACT POINT OF CONNECTION WITHIN TRAILER
WITH TRAILER MANUFACTURER SHOP DRAWINGS. PRIOR TO INSTALLATION.
5 PROVIDE GENERATOR START SIGNAL BACK TO EXISTING EMERGENCY
DISTRIBUTION AND GENERATOR SYSTEM. CAT6A OR AS REQUIRED BY
MANUFACTURER.
KEYNOTES
1 8 SETS EACH OF [3#500KCM, 1#400 KCM N, 1#500KCM G, 3-1/2" C]
2 4 SETS EACH OF [3#350KCM, 1#350KCM N, 1#3/0 G, 3" C]
3 2 SETS EACH OF [3#350KCM, 1#350KCM N, 1#1 G, 3" C]
4 3#4/0, 1#4 G, 2" C
5 2 SETS EACH OF [3#3/0, 1#3/0 N, 1#2 G, 2-1/2" C]
6. 3#3/0, 1#3/0 N, 1#6 G, 2" C
FEEDER SIZES (CU)
*AFC VALUES TAKEN FROM ARC FLASH ANALYSIS REPORT (DATED 08/13/2021) PROVIDED BY VA
02/11/2026
Expires 9/30/2025
| Sheets |
| EP.201T - ENLARGED ELECTRICAL FLOOR PLANS - B650 ELECTRICAL ROOM |
| EP.401T - ELECTRICAL ONE-LINE DIAGRAM - TEMP OR TRAILER |
File details come from the government source that posted it. Updated .