This document is an architectural drawing for electrical work at a Veterans Affairs facility. The drawing, designated EP.201T, provides enlarged electrical floor plans for Building 650 (the Electrical Room) at the VA Hospital located at 10535 Hospital Way, Mather, California 95655. The project is titled "Hybrid Temporary Trailers" with project number 612A4-25-004, and this represents a 100% submittal dated September 30, 2025, with an expiration date of September 30, 2025. The drawing was prepared by AESUS design group (Architecture, Engineering, AESUS and Sustainable Design) located in Tempe, Arizona.
The drawing illustrates both existing and proposed electrical configurations, with keynotes providing specific installation and relocation requirements. Key work items include: relocating fixtures and devices to available wall space outside new electrical equipment footprints while extending existing circuits as needed; relocating fire alarm infrastructure with circuit extensions; connecting to the nearest critical lighting circuit; and providing a new 20-ampere single-phase circuit breaker in existing panelboard space matching existing type and AIC rating. The design basis utilizes a Siemens 3000-ampere distribution board, with coordination required between the electrical and mechanical contractors for thermostat relocation. The drawing is presented at two scales (1¼" = 1'-0" and 2¼" = 1'-0") and includes both demo (existing) and proposed electrical floor plan views.
View the file
Other files
Show 40 more
50 files listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
F
F
(E) NSH1001A(E) NSH1001B
(E) TIE BREAKER
(E) EHS1001A
DB-CR
DB-EQ
SWB-NORM
ATS-CR
ATS-EQ
(E) EHS1001A (SECTION PULL)
EHS1001B (SECTION PULL)
EHS1001B
(E) PARALLELING SWBD EHS1031A
(E) 701-ATS-12-EM
(E) 701-ATS-10-CHL3
(E) 701-ATS-08-CHL2
(E) 701-ATS-07-CHL1
(E) 701-ATS-11-5A028
(E) 701-ATS-09-EQ
(R)
(R)(R) THERMOSTAT
(R)
E1
QL656A-16
(E) QL656A
(E) QTX656A
(E) NSH1001A(E) NSH1001B
(E) TIE BREAKER
(E) EHS1001A
(E) EHS1001A (SECTION PULL)
(X) XFMR TNA
(E) PARALLELING SWBD EHS1031A
(E) 701-ATS-12-EM
(E) 701-ATS-10-CHL3
(E) 701-ATS-08-CHL2
(E) 701-ATS-07-CHL1
(E) 701-ATS-11-5A028
(E) 701-ATS-09-EQ
(R)
(R)
(R) THERMOSTAT
2 (R)
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Architecture, Engineering, and, Sustainable DesignAESUS 1050 E. Southern Ave, Suite #D, Tempe, Arizona 85282, (480) 454-2861 design group
A u to d e s k D o c s /A
E S
U S
P ro je c ts
/1
V
A T e m p -O
R
E L
E C
U
P G
R A
D E
D .r v t
/1
/2
:4
:1
A
M
EP.201T
ENLARGED ELECTRICAL FLOOR
PLANS - B650 ELECTRICAL ROOM
10535 HOSPITAL WAY MATHER, CA 95655
612A4-25-004
N/A
SEPT. 30, 2025 AESUS AESUS
HYBRID TEMPORARY TRAILERS100% Submittal
Revisions: Date:
1/4" = 1'-0"2
ENLARGED ELECTRICAL FLOOR PLAN - BUILDING 650 ELECTRICAL ROOM
1/4" = 1'-0"1
ENLARGED DEMO ELECTRICAL FLOOR PLAN - BUILDING 650 ELECTRICAL ROOM
1. SIEMENS 3000A DISTRIBUTION BOARD AND PULL SECTION USED AS BASIS OF DESIGN FOR
EQUIPMENT SIZES. EXISTING 3000A DISTRIBUTION BOARD (E) EHS1001A MANUFACTURED BY
SIEMENS.
2. RELOCATE FIXTURE/DEVICE TO AVAILABLE WALL SPACE OUTSIDE OF NEW ELECTRICAL
EQUIPMENT FOOTPRINT. FOR (R) THERMOSTAT, COORDINATE ADDITIONAL REQUIREMENTS WITH
MECHANICAL CONTRACTOR PRIOR TO RELOCATION. EXTEND EXISTING CIRCUITS AS NEEDED TO
REACH NEW LOCATIONS.
3. RELOCATE ANY EXISTING FIRE ALARM INFRASTRUCTURE AS NEEDED IN ROOM TO AVAILABLE WALL SPACE OUTSIDE OF NEW ELECTRICAL EQUIPMENT FOOTPRINT. EXTEND EXISTING CIRCUITS
AS NEEDED TO REACH NEW LOCATIONS.
4. CONNECT TO NEAREST CRITICAL LIGHTING CIRCUIT IN AREA.
5. PROVIDE NEW 20A/1P CIRCUIT BREAKER IN EXISTING SPACE ON PANELBOARD. MATCH EXISTING
TYPE AND AIC RATING.
KEYNOTES
02/11/2026
Expires 9/30/2025
| Sheets |
| EP.201T - ENLARGED ELECTRICAL FLOOR PLANS - B650 ELECTRICAL ROOM |
| EP.401T - ELECTRICAL ONE-LINE DIAGRAM - TEMP OR TRAILER |