This document is a Pre-Action/Deluge Fire Sprinkler System Inspection Report for the VA Sierra NV Health Care facility located at 975 Kirman Ave in Reno, Nevada. The semi-annual inspection was conducted by Western States Fire Protection on 4/28/2025, with inspector Daniel I Pellegrino (License C-4525) performing the assessment. The inspection covered a pre-action system in Building 12, verifying air compressor operation and recording water pressure at 147 psi and air pressure at 32 psi. No deficiencies were reported during the inspection, which was performed in accordance with NFPA 25 2023 Edition standards. The releasing panel is a Siemens FHA2056-U1R1 model with 22 smoke detection devices that release via solenoid, and the last internal pipe inspection was conducted in 7/2020.
View the file
Other files
Show all 26
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Pre-Action/Deluge Fire Sprinkler System Inspection
Report
Location Code: IZJKQQS
Contact: Owner or Manager
Contact Address: 975 KIRMAN AVE
RENO, NV 89502-0993
Phone: 775-384-3958
Email:
Property Evaluated: VA SIERRA NV HEALTH CARE
(Assembly)
975 KIRMAN AVE
RENO, NV 89502-0993
Description: Pre/Del (Preaction Bldg. 12)
Work Order: Sv2504011140@@1
Company: Western States Fire Protection
Address: 1655 Marietta Way, Suite 105
Sparks, NV 89431-6000
Company Phone: 775-359-0396
Company Fax: 775-418-5171
Inspector: Daniel I Pellegrino
C-4525
Date of Work: 4/28/2025
Frequency: Semi-Annual
Tag: NA
Deficiency Summary
There are no reported deficiencies for this submission
General Comments
These items are outside the regular scope of the required inspection and are not the result of an engineering review. This information is not intended to be all-inclusive but rather a list of items discovered as a by-product of the required inspection.
Performed semi-annual inspection and tests of Preaction system in accordance with NFPA 25 2023 Edition Table 13.1.1.2 and section 13.4
Air compressor operation verified.
147 psi water
32 psi air
Western States Fire Protection, 1655 Marietta Way, Suite 105, Sparks, NV, 89431-6000 Phone: 775-359-0396 Page 1 of 3
Western States Fire Protection 1655 Marietta Way, Suite 105 Sparks, NV 89431-6000 Phone: 775-359-0396
Pre-Action/Deluge Fire Sprinkler System Inspection
Report
Tag NA Inspection Frequency: Semi-Annual Property Being Evaluated:
VA SIERRA NV HEALTH CARE (Assembly) Owner:
Owner or Manager Owner's Phone Number:
775-384-3958 Property Address:
975 KIRMAN AVE, RENO, NV, 89502-0993
1. General A. (To be filled out by the Owner or Owner's Representative) Has the Owners section been answered on another inspection report that will be submitted with this inspection report? Yes No Owner not Available
Answers to the following questions should be for all fire and life safety systems and not limited to the scope of the present inspection form.
1. Has the occupancy, machinery, or operations remained the same since the last inspection? Yes No
2. Has the system(s) remained in service without modifications or repairs since the last inspection? Yes No
3. If a fire has occurred since the last inspection, have all damaged sprinkler system components been replaced? Yes No N/A
4. Have fire pumps had a curve test completed in the past 12 months? Yes No N/A
5. Are gravity, surface, or pressure tanks protected from freezing? Yes No N/A
6. Are any sprinkler heads or other sprinkler system components exposed to harsh conditions (ie.
Corrosive atmospheres, extreme temperatures, etc.) Yes No N/A
7. Do any systems contain low-point drains, excluding wet systems? (Please note - It's the owner's responsibility to ensure Low Point Drains are emptied of condensation on a regular basis)
Yes No N/A
7a. How many low point drains? NA 7b. What are the general locations of low point drains? NA
8. Does the valve room have adequate heat to maintain a minimum of 40 F? Yes No N/A The above answers are verified as accurate and current by the undersigned Owner or Owner’s Representative for all fire and life safety systems.
Owner Signature
Printed Ricky Robinson Title Date 4/28/2025 B. (To be answered by the inspector)
a. Is System in service upon arrival? Yes No
b. Was the alarm panel free of alarm and trouble signals upon arrival? (If no, please explain in comments) Yes No N/A
c. Does there appear to be proper clearance between the top of all storage and the sprinkler deflector? Yes No
2. Control Valves
a. Do Control Valves appear to be free of damage/leaks? Yes No
Control Valves:
No. of Valves:
Type: Additional Info:
Easily Accessible?
Signs? Valve in proper position?
Secured? Supervision Operational?
System 1 BFV Yes No Yes No N/A Yes No Yes No
N/A Yes No N/A
3. Water Supplies
a. Water Supply Source City Private
Pressure Fire Pump & Tank Pressure Fire Pump & City Pressure Fire Pump & Pond
Western States Fire Protection, 1655 Marietta Way, Suite 105, Sparks, NV, 89431-6000 Phone: 775-359-0396 Page 2 of 3
Western States Fire Protection 1655 Marietta Way, Suite 105 Sparks, NV 89431-6000 Phone: 775-359-0396
4. Tanks, Pumps, Fire Dept. Connections
a. Appears that the F.D.C. is in satisfactory condition, couplings free, caps or plugs in place and check valves tight? Yes No N/A
b. Are fire department connections visible, accessible, and identification sign(s) in place? Yes No N/A
c. Has the five years hydrostatic test been performed on piping from the fire department connection to the fire department check valve? Yes No N/A
d. Date: 7/2020
5. Pre-Action and Deluge Systems
a. No. of Pre-Action Systems 1
b. No. of Deluge Systems 0
c. Are the air and priming water pressures adequate? Yes No N/A
d. Does Valve and Trim appear to be free of damage/leaks and in good condition? Yes No N/A
e. Does Valve and Trim appear to be in its appropriate open or closed positions at time of inspection? Yes No N/A
f. Have all control valves been fully operated and returned to normal their position? Yes No N/A
g. Did the supervisory devices operate properly during testing? Yes No N/A
h. Has there been an air leakage test of the system(s) within the last 3 years? Yes No N/A
Appears to be due for an air leakage test Leakage Test Date Unknown
6. Trip Test Not applicable
7. After Tests Not applicable
8. Alarms
a. Did the water motor(s) and gong(s) test satisfactory? Yes No N/A
b. Did the electric alarm(s) test satisfactory? Yes No N/A
c. Did the supervisory alarms operate during testing? Yes No N/A
d. Was the alarm panel clear of alarm and trouble signals upon departure? (If no, please explain in comments) Yes No N/A
9. Releasing Panel Information
Manufacturer Model Device Type Number of Devices How Does Panel Release? Additional Notes
Siemens FHA2056-U1R1 Smoke 22 Solenoid
10. Systems, Sprinklers, and Piping (inspected from the ground level)
a. Is the hydraulic design information sign provided, legible, and attached securely to the sprinkler riser? Yes No N/A
b. Has there been an internal inspection of the piping within the last 5 years? Yes No N/A
c. Date last checked (Checking is recommended at least every 5 years) 7/2020
d. Do all gauges appear to be in good condition and read within normal range? Yes No N/A
e. Are all of the gauges dated within 5 years or compared to a calibrated gauge? Yes No N/A
f. Does the hand hose valve(s) on the sprinkler system appear to be in satisfactory condition? Yes No N/A Not applicable
11. Observations These items are outside the regular scope of the required inspection and are not the result of an engineering review. This information is not intended to be all-inclusive but rather a list of items discovered as a by-product of the required inspection.
Please see the summary section at the top of the form for the comments.
12. Adjustments or Corrections Made:
13. List Changes in the Occupancy Hazard or Fire Protection Equipment, as Advised by the Owner in Section 1A
14. Inspector Information:
Test Verification:
Inspected By Daniel I Pellegrino Inspector Signature
Inspector License: C-4525 Date of Work 4/28/2025 Inspection Notes
Western States Fire Protection, 1655 Marietta Way, Suite 105, Sparks, NV, 89431-6000 Phone: 775-359-0396 Page 3 of 3