Reno VAMC-Building 1 Section C - Damper Inspection Report 2024.pdf
PDF 7 MB Posted
- Solicitation number
- 36C26126Q0018
About this file
This document is a Damper Inspection Report for the Reno Veterans Affairs Medical Center (VAMC), Building 1, Section C, conducted by Life Safety Services, LLC from August 15-21, 2024. The comprehensive inspection covered 126 combination fire and smoke dampers across six floors, with technician Greg Pena performing the assessment in accordance with National Fire Protection Association (NFPA) Standards 80 and 105.
The inspection results reveal significant findings: 56.35% of dampers passed inspection, 26.98% failed, and 16.67% were non-accessible. Failure reasons included inoperable actuators, dampers not fully opening or closing, actuators not properly installed, and lack of access. Specific issues were identified on multiple floors, such as dampers with power but disconnected switches, metal obstructing blade closure, and dampers found in closed positions. The report includes detailed documentation for each damper, including location, type, and photographic evidence, which suggests the need for comprehensive maintenance and repair of the facility's fire and smoke damper systems.
View the file
Other files
Show all 26
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
908 South 8th Street Louisville, KY. 40203
888.675.4519 info@LifeSafetyServices.com
Damper Inspection Report Reno VAMC - Building 1 Section C
08/15/2024 - 08/21/2024 www.LifeSafetyServices.com
DAMPER INSPECTION REPORT
Corporate Office 908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519
Facility: Reno VAMC Inspection Date: 08/15/2024 - 08/21/2024 Inspected By: Greg Pena Job ID: DR-040524-C11-DIS
FIRE & SMOKE DAMPER INSPECTION SERVICES
LSS Life Safety Services, LLC, in accordance with The National Fire Protection Association’s (NFPA) Standard 80 Chapter 19 and 105 Chapter 7 inspected fire and smoke dampers located in Building 1 Section C during the period of 08/15/2024 - 08/21/2024.
The following report and digital pictures provide the result of the inspection for the dampers that were inspected.
This report is intended to describe the location and operability of the dampers for the date in which LSS Life Safety Services’ representatives performed the inspection of the dampers, and is not intended to constitute any warranty as to the continued operation of any damper.
Thank you for contracting LSS Life Safety Services for this project and we look forward to the opportunity of working with you in the future on additional projects.
Technician Signature
908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519
Project Summary Building Fire Smoke Combination Pass Fail Non-Accessible
Building #1 0 0 126 71 34 21
GRAND TOTAL 0 0 126 71 34 21
Statistics Test Result % of Dampers
Pass 56.35%
Fail 26.98%
Non-Accessible 16.67%
Type Total % of Dampers
Fire 0 0.00%
Smoke 0 0.00%
Combination 126 100.00%
908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519
Facility: Reno VAMC Inspection Date: 08/15/2024 Inspected By: Greg Pena
All Dampers Date Floor Damper Number Damper
Type Damper Location
Inspection Result
Reason for Failure or Inaccessibility
08/15/2024 6 6-FSD-C6317-1 CombinationInside room C6317 above door Pass
08/15/2024 6 6-FSD-C6317-4 Combination Inside room, C6317 above whiteboard Pass
08/15/2024 6 6-FSD-C6319-5 Combination Outside of door, C6319 above door Pass
08/15/2024 6 6-FSD-C6329-6 Combination
Inside room, C6327 above computer desk, right hand corner back wall
Pass
08/15/2024 6 6-FSD-C6326-7 Combination Inside office
C6326 back wall left-hand corner
Fail Inoperable actuator
08/15/2024 6 6-FSD-C6357-8 Combination Outside storage door C6357 above door
Fail Inoperable actuator
08/15/2024 6 6-FSD-C6361-9 Combination Inside staff lounge room C6355 Non-Accessible No access door, access door install not authorized
08/15/2024 6 6-FSD-C6361-10 Combination
Inside office C6361 left side beside the door inside the office in between the walls
Pass
08/15/2024 6 6-FSD-C6365-12 Combination Inside exam room C6365 left-hand front corner by patient exam bed
Pass
08/15/2024 6 6-FSD-C6367-13 Combination Inside exam room C6367 left-hand wall corner above the sink
Pass
08/15/2024 6 6-FSD-C6360-11 CombinationInside room C6360 above the door Pass
08/15/2024 5 5-FSD-C5319-3 Combination Outside office C5319 above the door Pass
908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519
Facility: Reno VAMC Inspection Date: 08/16/2024 Inspected By: Greg Pena
All Dampers Date Floor Damper Number Damper
Type Damper Location
Inspection Result
Reason for Failure or Inaccessibility
08/16/2024 5 5-FSD-C5309-4 CombinationInside office c5309 left-hand corner Pass
08/16/2024 5 5-FSD-C5309-6 Combination Inside office number C 5309 outside door above door Pass
08/16/2024 5 5-FSD-C5307-1 Combination Inside office C 5307 plain side wall above boxes Pass
08/16/2024 5 5-FSD-C5307-2 Combination Inside office c
5307 left-hand side above key box
Non-Accessible No access door, access door install not authorized
08/16/2024 5 5-FSD-C5317-1 Combination Inside office C 5317 above door Pass
08/16/2024 5 5-FSD-C5317-2 Combination Inside office C
5317 right hand side corner above key boxes Pass
08/16/2024 5 5-FSD-C5327-4 Combination Inside office C
5327 right hand corner above chair
Pass
08/16/2024 5 5-FSD-C5324-5 Combination Inside office C 5324 back wall Pass
08/16/2024 5 5-FSD-C5358-11 Combination
Inside room C 5358 above refrigerator back right hand corner of the staff lounge
Non-Accessible No access door, access door install not authorized
08/16/2024 5 5-FSD-C5355-7 Combination Outside office C 5355 Fail Inoperable actuator
08/16/2024 5 5-FSD-C5353-6 Combination Outside door C 5353 in hallway Fail Inoperable actuator
08/16/2024 5 5-FSD-C5365-10 Combination Inside office, c 5365 directly in front of door front wall
Pass
08/16/2024 5 5-FSD-C5373-1 Combination Inside office C 5373 Pass
08/16/2024 5 5-FSD-C5373-2 Combination Outside office C
5373 directly above the door
Fail Inoperable actuator
08/16/2024 5 5-FSD-C5379-4 Combination Inside office C 5379 above door Pass
908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519
Date Floor Damper Number Damper Type
Damper Location
Inspection Result
Reason for Failure or Inaccessibility
08/16/2024 5 5-FSD-C5380-5 Combination
Inside conference room c5380 next to back storage door above key box on wall
Fail Inoperable actuator
08/16/2024 5 5-FSD-C5359-8 Combination
Inside office C5359 left-hand front corner of office above key boxes
Pass
08/16/2024 5 5-FSD-C5359-9 Combination Inside office, c5359 left-hand front corner by key boxes Pass
08/16/2024 4 4-FSD-C4307-1 Combination
In hallway across from storage C
4304 about 6 feet down the hallway through the right hand side across from HVAC room
Non-Accessible No access door, access door install not authorized
08/16/2024 4 4-FSD-C4307-3 Combination
Inside office C 4309 there’s another door C 4307 right hand side corner of C
4307 is the damper and access
Pass
08/16/2024 4 4-FSD-C4309-4 Combination Inside office C 4309 above door Fail Blades will not fully open
08/16/2024 4 4-FSD-C4307-2 Combination Outside room C 4309 above key box number tw
Pass
08/16/2024 4 4-FSD-C4313-5 Combination
Inside office C 4313 between door and front wall soon as you walk in middle of room
Pass
08/16/2024 4 4-FSD-C4295-7 Combination Inside storage room c 4295 left-hand front corner by vent Pass
08/16/2024 4 4-FSD-C4295-6 Combination Inside room C 4295 left-hand front corner by vent Fail Inoperable actuator
08/16/2024 4 4-FSD-C4290-9 CombinationInside room C4290 above door Pass
08/16/2024 4 4-FSD-C4286-10 Combination
Inside office area C 4286 left-hand side above desk workstation middle of office
Pass
08/16/2024 4 4-FSD-C4319-1 CombinationOutside door office C 4319 above door Fail Actuator needs to be bolted in place
08/16/2024 4 4-FSD-C4319-2 Combination Outside office number C 4319 above door
908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519
Date Floor Damper Number Damper Type
Damper Location
Inspection Result
Reason for Failure or Inaccessibility
08/16/2024 4 4-FSD-C4319-3 Combination Inside office C 4319 back wall Fail Blades will not fully close
08/16/2024 4 4-FSD-C4324-4 Combination Inside office
C4324 back left-hand corner above key box Fail Damper found in the closed position
08/16/2024 4 4-FSD-C4325-5 Combination Inside office number C4325 right hand back corner above desk
908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519
Facility: Reno VAMC Inspection Date: 08/17/2024 Inspected By: Greg Pena
All Dampers Date Floor Damper Number Damper
Type Damper Location
Inspection Result
Reason for Failure or Inaccessibility
08/17/2024 4 4-FSD-C4333-13 Combination Inside office
C4333 back left-hand corner above the key box Pass
08/17/2024 4 4-FSD-C4342-12 Combination
Go through EMS headquarters door number C4332 Pass
08/17/2024 4 4-FSD-C4353-6 Combination Outside room number C 4353 directly above the door Pass
08/17/2024 4 4-FSD-C4357-7 Combination Outside office number C 4357 directly above the door Fail Actuator has power but switch may not be connected
08/17/2024 4 4-FSD-C4357-8 Combination Inside office number C 4357 left-hand corner above key box
Pass
08/17/2024 4 4-FSD-C4357-9 Combination Inside office C
4357 right hand side front corner above key box
Pass
08/17/2024 4 4-FSD-C4356-10 Combination
Inside office number c good 4356 left-hand corner in the back above key box
Pass
08/17/2024 4 4-FSD-C4365-11 Combination Inside staff lounge C 4365 directly in front of the door
Pass
08/17/2024 4 4-FSD-C4373-1 Combination Outside office C 4373 Fail Inoperable actuator
08/17/2024 4 4-FSD-C4373-3 Combination
To the right-hand side of office C
4373 outside of the door above the key box labeled three
Fail Inoperable actuator
08/17/2024 4 4-FSD-C4373-2 Combination
Inside office C4373 right hand side through the doorway to the right again above the key box label to
Fail Damper blades will not close
08/17/2024 4 4-FSD-C4377-5 Combination
Outside office C 4377 in the hallway by the bulkhead above key box labeled five
908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519
Date Floor Damper Number Damper Type
Damper Location
Inspection Result
Reason for Failure or Inaccessibility
08/17/2024 4 4-FSD-C4381-6 Combination
Inside office C 4381 directly in front of the door above key box on the wall labeled six
Pass
08/17/2024 4 4-FSD-C4405-7 Combination Inside office C
4405 directly by door
Pass
08/17/2024 4 4-FSD-C4405-8 Combination Inside office C
4405 right hand back corner
Pass
08/17/2024 4 4-FSD-C4400-10 Combination Inside of C4400 above door Fail Inoperable actuator
08/17/2024 4 4-FSD-C4394-11 Combination Outside office C
4394 directly above the door
Fail Damper found in the closed position
08/17/2024 4 4-FSD-C4395-12 Combination
Inside office number C 4395 I’ll be against the left-hand side of the wall
Fail Inoperable actuator
08/17/2024 3 3-FSD-C3307-1 Combination
Inside men’s restroom C 3307 in front of the toilet stall door drywall hatch key box
Pass
08/17/2024 3 3-FSD-C3309-4 Combination Inside women’s restroom C 3309 to left-hand side of the door
Non-Accessible No access door, access door install not authorized
08/17/2024 3 3-FSD-C3309-2 Combination
Inside women’s restroom C 3309 to the left-hand side front corner drywall hatches right there above the mirror
Non-Accessible No access door, access door install not authorized
08/17/2024 3 3-FSD-C3309-3 Combination Inside men’s restroom C 3307 right hand corner wall above urinal
Pass
08/17/2024 3 3-FSD-C3313-5 Combination
Inside office C 3313 directly in front of the door above the key box on the wall label five
Non-Accessible No access door, access door install not authorized
08/17/2024 3 3-FSD-C3293-6 Combination Directly above reception desk, location, C3293
Fail Damper found in closed position
08/17/2024 3 3-FSD-C3293-7 Combination Behind reception desk area c3293 Pass
08/17/2024 3 3-FSD-C3290-9 Combination Outside office number, C3290 right above door
Fail Inoperable actuator
08/17/2024 3 3-FSD-C3284-10 Combination Inside exam room C 3284 above door Fail Inoperable actuator
908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519
Date Floor Damper Number Damper Type
Damper Location
Inspection Result
Reason for Failure or Inaccessibility
08/17/2024 3 3-FSD-C3285-11 Combination Directly in front of the door inside room, C3285 right hand corner
908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519
Facility: Reno VAMC
Inspection Date: 08/18/2024 Inspected By: Greg Pena
All Dampers Date Floor Damper Number Damper
Type Damper Location
Inspection Result
Reason for Failure or Inaccessibility
08/18/2024 3 3-FSD-C3353-5 Combination Outside office C3353 directly above door Pass
08/18/2024 3 3-FSD-C3357-6 Combination
Outside office number C 3357 directly above door key box number 6 is in between the doors
Pass
08/18/2024 3 3-FSD-C3357-7 Combination
Inside office C 3357 left-hand back corner by smoke detector and key box labeled seven
Pass
08/18/2024 3 3-FSD-C3357-8 Combination
Inside office C 3357 to the right front corner above key box labeled eight
Pass
08/18/2024 3 3-FSD-C3365-9 Combination
Inside office c3365 directly in front of the door there’s a wall with a key box. Label nine
Pass
08/18/2024 3 3-FSD-C3373-1 Combination Outside office C3373 directly above door Pass
08/18/2024 3 3-FSD-C3375-3 Combination
Go through office door see 3373 to the right hand side.
There’s another door C 3375 in there right hand side corner.
There’s a box labeled three above the box is the damper.
Pass
08/18/2024 3 3-FSD-C3375-2 Combination Inside of this C 3375 directly above door
Pass
08/18/2024 3 3-FSD-C3377-4 Combination Outside office C 3377 above key box labeled four
Fail Inoperable actuator
08/18/2024 3 3-FSD-C3381-5 Combination
Inside of C 3381 directly in front of the door key box label five by the vent
Pass
08/18/2024 3 3-FSD-C3356-10 Combination Inside office C 3356 left-hand back corner above key box labeled 10
Fail Inoperable actuator
908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519
Facility: Reno VAMC Inspection Date: 08/19/2024
Inspected By: Greg Pena
All Dampers Date Floor Damper Number Damper
Type Damper Location
Inspection Result
Reason for Failure or Inaccessibility
08/19/2024 3 3-FSD-C3333-11 Combination
Outside of office C3333 directly above door key box is to the right label 11
Pass
08/19/2024 3 3-FSD-C3340-14 Combination Inside office c3340 left-hand side back wall above key box
Pass
08/19/2024 3 3-FSD-C3344-13 Combination
Inside office C 3344 in front of door there’s a wall with a key box label 13 it’s above that
Fail Blades will not fully open
08/19/2024 3 3-FSD-C3337-12 Combination Inside room C
3337 to the right there is a drywall hatch by the floor
Non-Accessible No access door, nowhere to install access door
08/19/2024 3 3-FSD-C3405-6 Combination Inside office C 3405 directly above the door Fail Inoperable actuator
08/19/2024 3 3-FSD-C3405-7 Combination Inside office C
3405 right hand side wall in the corner Pass
08/19/2024 3 3-FSD-C3400-8 Combination Inside office
C3400 directly above the door
Fail Inoperable actuator
08/19/2024 3 3-FSD-c3396-9 Combination Inside office
C3396 directly above door
Pass
08/19/2024 3 3-FSD-C3397-10 Combination Inside office C 3397 directly in front of door above key box
Fail Damper found in closed position
08/19/2024 2 2-FSD-C2379-3 Combination
Inside storage room C 2379 up against the left-hand wall above the key box
Fail Actuator not installed correctly and thermal link is not hooked up
08/19/2024 2 2-FSD-C2375-2 Combination Outside of office C
2375 directly above door
Fail Inoperable actuator
08/19/2024 2 2-FSD-C2383-4 Combination
Inside storage room c2383 directly in front of the door there’s a wall with a key box. The damper is right above it.
908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519
Date Floor Damper Number Damper Type
Damper Location
Inspection Result
Reason for Failure or Inaccessibility
08/19/2024 2 2-FSD-C2375-1 Combination
Inside office C2375 directly in front of the door, the back wall above the key box
Pass
08/19/2024 2 2-FSD-C2403-5 Combination Inside office C
2403 front left side above door
Pass
08/19/2024 2 2-FSD-C2403-6 Combination
Inside office c2403 key box on the wall opposite the door they will six damper above it
Pass
08/19/2024 2 2-FSD-C2400-7 Combination Inside office C
2400 above the door
Non-Accessible No access door, nowhere to install access door
08/19/2024 2 2-FSD-C2396-8 Combination Inside biohazard room C 2396 directly above door
Pass
08/19/2024 2 2-FSD-C2397-9 Combination Inside office
C2397 back right hand corner
Fail Damper failed to fully close
08/19/2024 2 2-FSD-C2365-5 Combination Inside office C
2365 left-hand wall above computer desk Pass
08/19/2024 2 2-FSD-C2359-3 Combination Outside of office C
2359 directly above door, the vent Pass
08/19/2024 2 2-FSD-C2357-1 Combination Outside of office C
2357 directly above door
Non-Accessible No access door, access door install not authorized
08/19/2024 2 2-FSD-C2357-2 Combination Inside office C
2357 the second tile from the window Pass
08/19/2024 2 2-FSD-C2360-4 Combination
Inside office C 2360 right hand corner above the key box and the refrigerator
Pass
08/19/2024 2 2-FSD-C2353-6 Combination Inside conference room C 2353 right hand front corner
Fail Inoperable actuator
908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519
Facility: Reno VAMC Inspection Date: 08/20/2024 Inspected By: Greg Pena
All Dampers Date Floor Damper Number Damper
Type Damper Location
Inspection Result
Reason for Failure or Inaccessibility
08/20/2024 2 2-FSD-C2335A-8 Combination Inside office
C2335A directly above the door
Non-Accessible No access door, nowhere to install access door
908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519
Facility: Reno VAMC Inspection Date: 08/21/2024 Inspected By: Greg Pena
All Dampers Date Floor Damper Number Damper
Type Damper Location
Inspection Result
Reason for Failure or Inaccessibility
08/21/2024 2 2-FSD-C2301-1 Combination Inside lab office
C 2301 back wall above vent
Non-Accessible No access door, access door install not authorized
08/21/2024 2 2-FSD-C2300-2 Combination
Inside lab C 2300 second-floor for right hand back corner above biological safety cabinet
Non-Accessible No access door, nowhere to install access door
08/21/2024 2 2-FSD-C2307-3 Combination Inside women’s restroom C2307 Pass
08/21/2024 1 1-FSD-C1379-1 Combination Inside warehouse C1379 back left-hand corner above the duct work
Non-Accessible No access door, access door install not authorized
08/21/2024 1 1-FSD-C1377-2 Combination Inside office
C1377 back right hand corner
Non-Accessible No access door, access door install not authorized
08/21/2024 1 1-FSD-C1379-3 Combination Inside the hallway above the double doors going to warehouse C1379
Non-Accessible No access door, access door install not authorized
08/21/2024 1 1-FSD-C1379-4 Combination
Inside hallway going towards warehouse see 1379. It’s above the double doors.
Non-Accessible No access door, access door install not authorized
08/21/2024 1 1-FSD-C1365-5 Combination
Inside storage room C 1365 directly in front of the door on the wall above the key fob
Fail Damper will not fully open
08/21/2024 1 1-FSD-C1359-6 Combination Inside office
C1359 above the door by the key fob
Fail Inoperable actuator
08/21/2024 1 1-FSD-C1357-7 Combination Above door office C1357 Pass
08/21/2024 1 1-FSD-C1357-8 Combination Inside office
C1357 by the window
Fail Metal stuck between damper and blades preventing closure
08/21/2024 1 1-FSD-C1318-9 Combination
Inside kitchen C 1318 above prep space where the key fob is to the right of the door
Non-Accessible No access door, access door install not authorized
08/21/2024 1 1-FSD-C1318-10 Combination
Inside kept to dining area directly in front of sliding door across from courtyard
Non-Accessible No access door, access door install not authorized
908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519
Date Floor Damper Number Damper Type
Damper Location
Inspection Result
Reason for Failure or Inaccessibility
08/21/2024 1 1-FSD-C1318-10 Combination
Inside cafeteria dining area back door through prep number C 1318 is across from kiosk in the middle of dining area
Non-Accessible No access door, access door install not authorized
08/21/2024 1 1-FSD-C1318-12 Combination Above store kiosk where they sell hats by dining area Non-Accessible No access door, access door install not authorized
08/21/2024 1 1-FSD-C1332-13 Combination
Through second floor kitchen to the back staircase, going downstairs to the right of the stairs storage room C1332 inside to the left above the door
Pass
08/21/2024 1 1-FSD-C1342-14 Combination
Through kitchen on second floor, back staircase, going down to first floor, corridor across from staircase ,in front of refrigerator
C1342 above the door
Pass
08/21/2024 1 1-FSD-C1335-15 Combination
For the kitchen on the second floor, down the back staircase, to the right at the bottom of the staircase, inside storage room, C1335 above the door
908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519
Location Description: Inside room C6317 above door
Tag: 6-FSD-C6317-1
Type: Combination
Floor: 6
Status: Pass
Open Photo Closed Photo https://www.gocanvas.com/values/20310091043 https://www.gocanvas.com/values/20310091043 https://www.gocanvas.com/values/20310091046 https://www.gocanvas.com/values/20310091046
908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519
Location Description: Inside room C6317 above whiteboard
Tag: 6-FSD-C6317-4
Type: Combination
Floor: 6
Status: Pass
Open Photo Closed Photo https://www.gocanvas.com/values/20310091240 https://www.gocanvas.com/values/20310091240 https://www.gocanvas.com/values/20310091243 https://www.gocanvas.com/values/20310091243
908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519
Location Description: Outside of door C6319
Tag: 6-FSD-C6319-5
Type: Combination
Floor: 6
Status: Pass
Open Photo Closed Photo https://www.gocanvas.com/values/20310091601 https://www.gocanvas.com/values/20310091601 https://www.gocanvas.com/values/20310091602 https://www.gocanvas.com/values/20310091602
908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519
Location Description: Inside room C6327 above computer desk, right hand corner back wall
Tag: 6-FSD-C6329-6
Type: Combination
Floor: 6
Status: Pass
Open Photo Closed Photo
Location Description: Inside office c6326 back wall left-hand corner
Tag: 6-FSD-c6326-7
Type: Combination
Floor: 6
Status: Fail
Reason for Failure or Inaccessibility: Inoperable actuator
Open Photo Closed Photo Actuator Photo https://www.gocanvas.com/values/20310091676 https://www.gocanvas.com/values/20310091676 https://www.gocanvas.com/values/20310091677 https://www.gocanvas.com/values/20310091677 https://www.gocanvas.com/values/20310091786 https://www.gocanvas.com/values/20310091786 https://www.gocanvas.com/values/20310091787 https://www.gocanvas.com/values/20310091787 https://www.gocanvas.com/values/20310091788 https://www.gocanvas.com/values/20310091788
908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519
Location Description: Outside storage door C6357 above door
Tag: 6-FSD-C6357-8
Type: Combination
Floor: 6
Status: Fail
Reason for Failure or Inaccessibility: Inoperable actuator
Open Photo Closed Photo Actuator Photo https://www.gocanvas.com/values/20310091861 https://www.gocanvas.com/values/20310091861 https://www.gocanvas.com/values/20310091862 https://www.gocanvas.com/values/20310091862 https://www.gocanvas.com/values/20310091863 https://www.gocanvas.com/values/20310091863
908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519
Location Description: Inside staff lounge room C6355
Tag: 6-FSD-c6361-9
Type: Combination
Floor: 6
Status: Non-Accessible
Reason for Failure or Inaccessibility: No access door, access door install not authorized
Open Photo Closed Photo
Location Description: Inside office C6361 left side beside the door inside the office in between the walls
Tag: 6-FSD-C6361-10
Type: Combination
Floor: 6
Status: Pass
Open Photo Closed Photo https://www.gocanvas.com/values/20310091994 https://www.gocanvas.com/values/20310091994 https://www.gocanvas.com/values/20310091995 https://www.gocanvas.com/values/20310091995 https://www.gocanvas.com/values/20310092109 https://www.gocanvas.com/values/20310092109 https://www.gocanvas.com/values/20310092113 https://www.gocanvas.com/values/20310092113
908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519
Location Description: Inside exam room C6365 left-hand front corner by patient exam bed
Tag: 6-FSD-C6365-12
Type: Combination
Floor: 6
Status: Pass
Open Photo Closed Photo
Location Description: Inside exam room C6367 left-hand wall corner above the sink
Tag: 6-FSD-C6367-13
Type: Combination
Floor: 6
Status: Pass
Open Photo Closed Photo https://www.gocanvas.com/values/20310092370 https://www.gocanvas.com/values/20310092370 https://www.gocanvas.com/values/20310092373 https://www.gocanvas.com/values/20310092373 https://www.gocanvas.com/values/20310092481 https://www.gocanvas.com/values/20310092481 https://www.gocanvas.com/values/20310092482 https://www.gocanvas.com/values/20310092482
908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519
Location Description: Inside room C6360 above the door
Tag: 6-FSD-C6360-11
Type: Combination
Floor: 6
Status: Pass
Closed PhotoOpen Photo
Location Description: Outside office C5319 above the door
Tag: 5-FSD-C5319-3
Type: Combination
Floor: 5
Status: Pass
Open Photo Closed Photo https://www.gocanvas.com/values/20310092556 https://www.gocanvas.com/values/20310092556 https://www.gocanvas.com/values/20310092557 https://www.gocanvas.com/values/20310092557 https://www.gocanvas.com/values/20310092631 https://www.gocanvas.com/values/20310092631 https://www.gocanvas.com/values/20310092632 https://www.gocanvas.com/values/20310092632
908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519
Location Description: Inside office C5309 left-hand corner
Tag: 5-FSD-C5309-4
Type: Combination
Floor: 5
Status: Pass
Open Photo Closed Photo https://www.gocanvas.com/values/20319970088 https://www.gocanvas.com/values/20319970088 https://www.gocanvas.com/values/20319970091 https://www.gocanvas.com/values/20319970091
908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519
Location Description: Inside office number C 5309 outside door above door
Tag: 5-FSD-C5309-6
Type: Combination
Floor: 5
Status: Pass
Open Photo Closed Photo https://www.gocanvas.com/values/20319970245 https://www.gocanvas.com/values/20319970245 https://www.gocanvas.com/values/20319970247 https://www.gocanvas.com/values/20319970247
908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519
Location Description: Inside office C 5307 plain side wall above boxes
Tag: 5-FSD-C5307-1
Type: Combination
Floor: 5
Status: Pass
Open Photo Closed Photo https://www.gocanvas.com/values/20319970335 https://www.gocanvas.com/values/20319970335 https://www.gocanvas.com/values/20319970336 https://www.gocanvas.com/values/20319970336
908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519
Location Description: Inside office C5307 left-hand side above key box
Tag: 5-FSD-C5307-2
Type: Combination
Floor: 5
Status: Non-Accessible
Reason for Failure or Inaccessibility: No access door, access door install not authorized
Open Photo Closed Photo
Location Description: Inside office C 5317 above door
Tag: 5-FSD-c5317-1
Type: Combination
Floor: 5
Status: Pass
Open Photo Closed Photo https://www.gocanvas.com/values/20319970418 https://www.gocanvas.com/values/20319970418 https://www.gocanvas.com/values/20319970419 https://www.gocanvas.com/values/20319970419 https://www.gocanvas.com/values/20319970493 https://www.gocanvas.com/values/20319970493 https://www.gocanvas.com/values/20319970494 https://www.gocanvas.com/values/20319970494
908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519
Location Description: Inside office C 5317 right hand side corner above key boxes
Tag: 5-FSD-C5317-2
Type: Combination
Floor: 5
Status: Pass
Open Photo Closed Photo
Location Description: Inside office C 5327 right hand corner above chair
Tag: 5-FSD-C5327-4
Type: Combination
Floor: 5
Status: Pass
Open Photo Closed Photo https://www.gocanvas.com/values/20319970571 https://www.gocanvas.com/values/20319970571 https://www.gocanvas.com/values/20319970573 https://www.gocanvas.com/values/20319970573 https://www.gocanvas.com/values/20319970699 https://www.gocanvas.com/values/20319970699 https://www.gocanvas.com/values/20319970701 https://www.gocanvas.com/values/20319970701
908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519
Location Description: Inside office C 5324 back wall
Tag: 5-FSD-C5324-5
Type: Combination
Floor: 5
Status: Pass
Open Photo Closed Photo https://www.gocanvas.com/values/20319970855 https://www.gocanvas.com/values/20319970855 https://www.gocanvas.com/values/20319970858 https://www.gocanvas.com/values/20319970858
908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519
Location Description: Inside room C 5358 above refrigerator back right hand corner of the staff lounge
Tag: 5-FSD-C5358-11
Type: Combination
Floor: 5
Status: Non-Accessible
Reason for Failure or Inaccessibility: No access door, access door install not authorized
Open Photo
Closed Photo https://www.gocanvas.com/values/20319970997 https://www.gocanvas.com/values/20319970997 https://www.gocanvas.com/values/20319970999 https://www.gocanvas.com/values/20319970999
908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519
Location Description: Outside office C 5355
Tag: 5-FSD-C5355-7
Type: Combination
Floor: 5
Status: Fail
Reason for Failure or Inaccessibility: Inoperable actuator
Open Photo Closed Photo Actuator Photo https://www.gocanvas.com/values/20319971138 https://www.gocanvas.com/values/20319971138 https://www.gocanvas.com/values/20319971141 https://www.gocanvas.com/values/20319971141 https://www.gocanvas.com/values/20319971143 https://www.gocanvas.com/values/20319971143
908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519
Location Description: Outside door C 5353 in hallway
Tag: 5-FSD-C5353-6
Type: Combination
Floor: 5
Status: Fail
Reason for Failure or Inaccessibility: Inoperable actuator
Open Photo Closed Photo Actuator Photo
Location Description: Inside office, c 5365 directly in front of door front wall
Tag: 5-FSD-c5365-10
Type: Combination
Floor: 5
Status: Pass
Open Photo Closed Photo https://www.gocanvas.com/values/20319971219 https://www.gocanvas.com/values/20319971219 https://www.gocanvas.com/values/20319971220 https://www.gocanvas.com/values/20319971220 https://www.gocanvas.com/values/20319971221 https://www.gocanvas.com/values/20319971221 https://www.gocanvas.com/values/20319971299 https://www.gocanvas.com/values/20319971299 https://www.gocanvas.com/values/20319971300 https://www.gocanvas.com/values/20319971300
908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519
Location Description: Inside office C 5373
Tag: 5-FSD-C5373-1
Type: Combination
Floor: 5
Status: Pass
Open Photo Closed Photo https://www.gocanvas.com/values/20319971416 https://www.gocanvas.com/values/20319971416 https://www.gocanvas.com/values/20319971418 https://www.gocanvas.com/values/20319971418
908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519
Location Description: Outside office C 5373 directly above the door
Tag: 5-FSD-C5373-2
Type: Combination
Floor: 5
Status: Fail
Reason for Failure or Inaccessibility: Inoperable actuator
Open Photo Closed Photo Actuator Photo
Location Description: Inside office C 5379 above door
Tag: 5-FSD-c5379-4
Type: Combination
Floor: 5
Status: Pass
Open Photo Closed Photo https://www.gocanvas.com/values/20319971542 https://www.gocanvas.com/values/20319971542 https://www.gocanvas.com/values/20319971544 https://www.gocanvas.com/values/20319971544 https://www.gocanvas.com/values/20319971545 https://www.gocanvas.com/values/20319971545 https://www.gocanvas.com/values/20319971618 https://www.gocanvas.com/values/20319971618 https://www.gocanvas.com/values/20319971619 https://www.gocanvas.com/values/20319971619
908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519
Location Description: Inside conference room c5380 next to back storage door above key box on wall
Tag: 5-FSD-C5380-5
Type: Combination
Floor: 5
Status: Fail
Reason for Failure or Inaccessibility: Inoperable actuator
Open Photo
Closed Photo Actuator Photo
Location Description: Inside office C5359 left-hand front corner of office above key boxes
Tag: 5-FSD-c5359-8
Type: Combination
Floor: 5
Status: Pass
Open Photo Closed Photo https://www.gocanvas.com/values/20319971693 https://www.gocanvas.com/values/20319971693 https://www.gocanvas.com/values/20319971694 https://www.gocanvas.com/values/20319971694 https://www.gocanvas.com/values/20319971695 https://www.gocanvas.com/values/20319971695 https://www.gocanvas.com/values/20319971768 https://www.gocanvas.com/values/20319971768 https://www.gocanvas.com/values/20319971769 https://www.gocanvas.com/values/20319971769
908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519
Location Description: Inside office C5359 left-hand front corner by key boxes
Tag: 5-FSD-C5359-9
Type: Combination
Floor: 5
Status: Pass
Open Photo Closed Photo
Location Description: In hallway across from storage C 4304 about 6 feet down the hallway through the right hand side across from HVAC room
Tag: 4-FSD-C4307-1
Type: Combination Floor: 5
Status: Non-Accessible
Reason for Failure or Inaccessibility: No access door, access door install not authorized
Open Photo Closed Photo https://www.gocanvas.com/values/20319971843 https://www.gocanvas.com/values/20319971843 https://www.gocanvas.com/values/20319971844 https://www.gocanvas.com/values/20319971844 https://www.gocanvas.com/values/20319972018 https://www.gocanvas.com/values/20319972018 https://www.gocanvas.com/values/20319972020 https://www.gocanvas.com/values/20319972020
908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519
Location Description: Inside office C 4309 there’s another door C 4307 right hand side corner of C 4307 is the damper and access
Tag: 4-FSD-C4307-3
Type: Combination
Floor: 4
Status: Pass
Open Photo Closed Photo
Location Description: Inside office C 4309 above door
Tag: 4-FSD-C4309-4
Type: Combination
Floor: 4
Status: Fail
Reason for Failure or Inaccessibility: Blades will not fully open
Open Photo Closed Photo Actuator Photo https://www.gocanvas.com/values/20319972114 https://www.gocanvas.com/values/20319972114 https://www.gocanvas.com/values/20319972116 https://www.gocanvas.com/values/20319972116 https://www.gocanvas.com/values/20319972228 https://www.gocanvas.com/values/20319972228 https://www.gocanvas.com/values/20319972229 https://www.gocanvas.com/values/20319972229 https://www.gocanvas.com/values/20319972230 https://www.gocanvas.com/values/20319972230
908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519
Location Description: Outside room C 4309 above key box number 2
Tag: 4-FSD-C4307-2
Type: Combination
Floor: 4
Status: Pass
Open Photo Closed Photo
Location Description: Inside office C 4313 between door and front wall soon as you walk in middle of room
Tag: 4-FSD-c4313-5
Type: Combination
Floor: 4
Status: Pass
Open Photo Closed Photo https://www.gocanvas.com/values/20319972326 https://www.gocanvas.com/values/20319972326 https://www.gocanvas.com/values/20319972329 https://www.gocanvas.com/values/20319972329 https://www.gocanvas.com/values/20319972491 https://www.gocanvas.com/values/20319972491 https://www.gocanvas.com/values/20319972492 https://www.gocanvas.com/values/20319972492
908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519
Location Description: Inside storage room C4295 left-hand front corner by vent
Tag: 4-FSD-C4295-6
Type: Combination
Floor: 4
Status: Pass
Open Photo
Closed Photo https://www.gocanvas.com/values/20319972566 https://www.gocanvas.com/values/20319972566 https://www.gocanvas.com/values/20319972567 https://www.gocanvas.com/values/20319972567
908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519
Location Description: Inside room C 4295 left-hand front corner by vent
Tag: 4-FSD-C4295-7
Type: Combination
Floor: 4
Status: Fail
Reason for Failure or Inaccessibility: Inoperable actuator
Open Photo
Closed Photo
Actuator Photo
Location Description: Inside room C4290 above door
Tag: 4-FSD-c4290-9
Type: Combination
Floor: 4
Status: Pass
Open Photo Closed Photo https://www.gocanvas.com/values/20319972646 https://www.gocanvas.com/values/20319972646 https://www.gocanvas.com/values/20319972648 https://www.gocanvas.com/values/20319972648 https://www.gocanvas.com/values/20319972651 https://www.gocanvas.com/values/20319972651 https://www.gocanvas.com/values/20319972764 https://www.gocanvas.com/values/20319972764 https://www.gocanvas.com/values/20319972765 https://www.gocanvas.com/values/20319972765
908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519
Location Description: Inside office area C 4286 left-hand side above desk workstation middle of office
Tag: 4-FSD-C4286-10
Type: Combination
Floor: 4
Status: Pass
Open Photo
Closed Photo https://www.gocanvas.com/values/20319972839 https://www.gocanvas.com/values/20319972839 https://www.gocanvas.com/values/20319972840 https://www.gocanvas.com/values/20319972840
908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519
Location Description: Outside door office C 4319 above door
Tag: 4-FSD-C4319-1
Type: Combination
Floor: 4
Status: Fail
Reason for Failure or Inaccessibility: Actuator needs to be bolted in place
Open Photo Closed Photo
Actuator Photo https://www.gocanvas.com/values/20319972921 https://www.gocanvas.com/values/20319972921 https://www.gocanvas.com/values/20319972923 https://www.gocanvas.com/values/20319972923 https://www.gocanvas.com/values/20319972925 https://www.gocanvas.com/values/20319972925
908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519
Location Description: Outside office number C 4319 above door
Tag: 4-FSD-C4319-2
Type: Combination
Floor: 4
Status: Pass
Open Photo
Closed Photo https://www.gocanvas.com/values/20319973049 https://www.gocanvas.com/values/20319973049 https://www.gocanvas.com/values/20319973051 https://www.gocanvas.com/values/20319973051
908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519
Location Description: Inside office C 4319 back wall
Tag: 4-FSD-C4319-3
Type: Combination
Floor: 4
Status: Fail
Reason for Failure or Inaccessibility: Damper blades will not close
Open Photo Closed Photo
Actuator Photo https://www.gocanvas.com/values/20319973167 https://www.gocanvas.com/values/20319973167 https://www.gocanvas.com/values/20319973168 https://www.gocanvas.com/values/20319973168 https://www.gocanvas.com/values/20319973169 https://www.gocanvas.com/values/20319973169
908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519
Location Description: Inside office C4324 back left-hand corner above key box
Tag: 4-FSD-C4324-4
Type: Combination
Floor: 4
Status: Fail
Reason for Failure or Inaccessibility: Damper found in the closed position
Open Photo Closed Photo Actuator Photo
Location Description: Inside office number C4325 right hand back corner above desk
Tag: 4-FSD-C4325-5
Type: Combination
Floor: 4
Status: Pass
Open Photo Closed Photo https://www.gocanvas.com/values/20319973242 https://www.gocanvas.com/values/20319973242 https://www.gocanvas.com/values/20319973243 https://www.gocanvas.com/values/20319973243 https://www.gocanvas.com/values/20319973244 https://www.gocanvas.com/values/20319973244 https://www.gocanvas.com/values/20319973343 https://www.gocanvas.com/values/20319973343 https://www.gocanvas.com/values/20319973345 https://www.gocanvas.com/values/20319973345
908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519
Location Description: Inside office C4333 back left-hand corner above the key box
Tag: 4-FSD-C4333-13
Type: Combination
Floor: 4
Status: Pass
Open Photo Closed Photo
Location Description: Go through EMS headquarters door number C4332 Tag: 4-FSD-C4342-12 Type: Combination Floor: 4
Status: Pass
Open Photo Closed Photo https://www.gocanvas.com/values/20323997618 https://www.gocanvas.com/values/20323997618 https://www.gocanvas.com/values/20323997619 https://www.gocanvas.com/values/20323997619 https://www.gocanvas.com/values/20323997708 https://www.gocanvas.com/values/20323997708 https://www.gocanvas.com/values/20323997710 https://www.gocanvas.com/values/20323997710
908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519
Location Description: Outside room number C 4353 directly above the door
Tag: 4-FSD-C4353-6
Type: Combination
Floor: 4
Status: Pass
Open Photo Closed Photo
Location Description: Outside office number C 4357 directly above the door
Tag: 4-FSD-C4357-7
Type: Combination
Floor: 4
Status: Fail
Reason for Failure or Inaccessibility: Actuator has power but switch is not connected
Open Photo Closed Photo Actuator Photo https://www.gocanvas.com/values/20323997844 https://www.gocanvas.com/values/20323997844 https://www.gocanvas.com/values/20323997846 https://www.gocanvas.com/values/20323997846 https://www.gocanvas.com/values/20323997980 https://www.gocanvas.com/values/20323997980 https://www.gocanvas.com/values/20323997982 https://www.gocanvas.com/values/20323997982 https://www.gocanvas.com/values/20323997984 https://www.gocanvas.com/values/20323997984
908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519
Location Description: Inside office number C 4357 left-hand corner above key box
Tag: 4-FSD-C4357-8
Type: Combination
Floor: 4
Status: Pass
Open Photo Closed Photo https://www.gocanvas.com/values/20323998078 https://www.gocanvas.com/values/20323998078 https://www.gocanvas.com/values/20323998079 https://www.gocanvas.com/values/20323998079
908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519
Location Description: Inside office C 4357 right hand side front corner above key box
Tag: 4-FSD-C4357-9
Type: Combination
Floor: 4
Status: Pass
Open Photo Closed Photo https://www.gocanvas.com/values/20323998158 https://www.gocanvas.com/values/20323998158 https://www.gocanvas.com/values/20323998159 https://www.gocanvas.com/values/20323998159
908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519
Location Description: Inside office number c good 4356 left-hand corner in the back above key box
Tag: 4-FSD-C4356-10
Type: Combination
Floor: 4
Status: Pass
Open Photo Closed Photo
Location Description: Inside staff lounge C 4365 directly in front of the door
Tag: 4-FSD-C4365-11
Type: Combination
Floor: 4
Status: Pass
Open Photo Closed Photo https://www.gocanvas.com/values/20323998233 https://www.gocanvas.com/values/20323998233 https://www.gocanvas.com/values/20323998234 https://www.gocanvas.com/values/20323998234 https://www.gocanvas.com/values/20323998308 https://www.gocanvas.com/values/20323998308 https://www.gocanvas.com/values/20323998309 https://www.gocanvas.com/values/20323998309
908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519
Location Description: Outside office C 4373
Tag: 4-FSD-C4373-1
Type: Combination
Floor: 4
Status: Fail
Reason for Failure or Inaccessibility: Inoperable actuator
Open Photo Closed Photo Actuator Photo
Location Description: To the right-hand side of office C 4373 outside of the door above the key box labeled three
Tag: 4-FSD-C4373-3
Type: Combination
Floor: 4
Status: Fail
Reason for Failure or Inaccessibility: Inoperable actuator
Open Photo Closed Photo Actuator Photo https://www.gocanvas.com/values/20323998383 https://www.gocanvas.com/values/20323998383 https://www.gocanvas.com/values/20323998384 https://www.gocanvas.com/values/20323998384 https://www.gocanvas.com/values/20323998385 https://www.gocanvas.com/values/20323998385 https://www.gocanvas.com/values/20323998458 https://www.gocanvas.com/values/20323998458 https://www.gocanvas.com/values/20323998459 https://www.gocanvas.com/values/20323998459 https://www.gocanvas.com/values/20323998460 https://www.gocanvas.com/values/20323998460
908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519
Location Description: Inside office C4373 right hand side through the doorway to the right again above the key box label two
Tag: 4-FSD-C4373-2
Type: Combination
Floor: 4
Status: Fail
Reason for Failure or Inaccessibility: Damper blades will not close
Open Photo Closed Photo Actuator Photo
Location Description: Outside office C 4377 in the hallway by the bulkhead above key box labeled five
Tag: 4-FSD-C4377-5
Type: Combination
Floor: 4
Status: Pass
Open Photo Closed Photo https://www.gocanvas.com/values/20323998549 https://www.gocanvas.com/values/20323998549 https://www.gocanvas.com/values/20323998550 https://www.gocanvas.com/values/20323998550 https://www.gocanvas.com/values/20323998551 https://www.gocanvas.com/values/20323998551 https://www.gocanvas.com/values/20323998624 https://www.gocanvas.com/values/20323998624 https://www.gocanvas.com/values/20323998625 https://www.gocanvas.com/values/20323998625
908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519
Location Description: Inside office C 4381 directly in front of the door above key box on the wall labeled six
Tag: 4-FSD-C4381-6
Type: Combination
Floor: 4
Status: Pass
Open Photo Closed Photo https://www.gocanvas.com/values/20323998749 https://www.gocanvas.com/values/20323998749 https://www.gocanvas.com/values/20323998751 https://www.gocanvas.com/values/20323998751
908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519
Location Description: Inside office C 4405 directly by door
Tag: 4-FSD-C4405-7
Type: Combination
Floor: 4
Status: Pass
Open Photo Closed Photo
Location Description: Inside office C 4405 right hand back corner
Tag: 4-FSD-C4405-8
Type: Combination
Floor: 4
Status: Pass
Open Photo Closed Photo https://www.gocanvas.com/values/20323998907 https://www.gocanvas.com/values/20323998907 https://www.gocanvas.com/values/20323998910 https://www.gocanvas.com/values/20323998910 https://www.gocanvas.com/values/20323999066 https://www.gocanvas.com/values/20323999066 https://www.gocanvas.com/values/20323999068 https://www.gocanvas.com/values/20323999068
908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519
Location Description: Inside of C4400 above door
Tag: 4-FSD-C4400-10
Type: Combination
Floor: 4
Status: Fail
Reason for Failure or Inaccessibility: Inoperable actuator
Open Photo Closed Photo Actuator Photo
Location Description: Outside office C 4394 directly above the door
Tag: 4-FSD-C4394-11
Type: Combination
Floor: 4
Status: Fail
Reason for Failure or Inaccessibility: Damper found in closed position
Open Photo Closed Photo Actuator Photo https://www.gocanvas.com/values/20323999241 https://www.gocanvas.com/values/20323999241 https://www.gocanvas.com/values/20323999243 https://www.gocanvas.com/values/20323999243 https://www.gocanvas.com/values/20323999245 https://www.gocanvas.com/values/20323999245 https://www.gocanvas.com/values/20323999400 https://www.gocanvas.com/values/20323999400 https://www.gocanvas.com/values/20323999403 https://www.gocanvas.com/values/20323999403 https://www.gocanvas.com/values/20323999405 https://www.gocanvas.com/values/20323999405
908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519
Location Description: Inside office number C 4395 I’ll be against the left-hand side of the wall
Tag: 4-FSD-C4395-12
Type: Combination
Floor: 4
Status: Fail
Reason for Failure or Inaccessibility: Inoperable actuator
Open Photo Closed Photo Actuator Photo
Location Description: Inside men’s restroom C 3307 in front of the toilet stall door drywall hatch key box
Tag: 3-FSD-C3307-1
Type: Combination
Floor: 3
Status: Pass
Open Photo Closed Photo https://www.gocanvas.com/values/20323999478 https://www.gocanvas.com/values/20323999478 https://www.gocanvas.com/values/20323999479 https://www.gocanvas.com/values/20323999479 https://www.gocanvas.com/values/20323999480 https://www.gocanvas.com/values/20323999480 https://www.gocanvas.com/values/20323999558 https://www.gocanvas.com/values/20323999558 https://www.gocanvas.com/values/20323999559 https://www.gocanvas.com/values/20323999559
908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519
Location Description: Inside women’s restroom C 3309 to left-hand side of the door
Tag: 3-FSD-C3309-4
Type: Combination
Floor: 3
Status: Non-Accessible
Reason for Failure or Inaccessibility: No access door, access door install not authorized
Open Photo Closed Photo https://www.gocanvas.com/values/20323999633 https://www.gocanvas.com/values/20323999633 https://www.gocanvas.com/values/20323999634 https://www.gocanvas.com/values/20323999634
908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519
Location Description: Inside women’s restroom C 3309 to the left-hand side front corner drywall hatches right there above the mirror
Tag: 3-FSD-C3309-2
Type: Combination
Floor: 3
Status: Non-Accessible
Reason for Failure or Inaccessibility: No access door, access door install not authorized
Open Photo
Closed Photo https://www.gocanvas.com/values/20323999708 https://www.gocanvas.com/values/20323999708 https://www.gocanvas.com/values/20323999709 https://www.gocanvas.com/values/20323999709
908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519
Location Description: Inside men’s restroom C 3307 right hand corner wall above urinal
Tag: 3-FSD-C3309-3
Type: Combination
Floor: 3
Status: Pass
Open Photo Closed Photo https://www.gocanvas.com/values/20323999783 https://www.gocanvas.com/values/20323999783 https://www.gocanvas.com/values/20323999784 https://www.gocanvas.com/values/20323999784
908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519
Location Description: Inside office C 3313 directly in front of the door above the key box on the wall label five
Tag: 3-FSD-C3313-5
Type: Combination
Floor: 3
Status: Non-Accessible
Reason for Failure or Inaccessibility: No access door, access door install not authorized
Open Photo Closed Photo https://www.gocanvas.com/values/20323999858 https://www.gocanvas.com/values/20323999858 https://www.gocanvas.com/values/20323999859 https://www.gocanvas.com/values/20323999859
908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519
Location Description: Directly above reception desk C3293
Tag: 3-FSD-C3293-6
Type: Combination
Floor: 3
Status: Fail
Reason for Failure or Inaccessibility: Damper found in closed position
Open Photo Closed Photo Actuator Photo https://www.gocanvas.com/values/20323999933 https://www.gocanvas.com/values/20323999933 https://www.gocanvas.com/values/20323999934…
This is the start of the file's text. The full file is on GovTribe.