Reno VAMC-Building 1 Section C - Damper Inspection Report 2024.pdf

PDF 7 MB Posted

Attached to
H212--Fire Protection Testing, Inspection, and Maintenance/Repair
Solicitation number
36C26126Q0018
Issued by

About this file

This document is a Damper Inspection Report for the Reno Veterans Affairs Medical Center (VAMC), Building 1, Section C, conducted by Life Safety Services, LLC from August 15-21, 2024. The comprehensive inspection covered 126 combination fire and smoke dampers across six floors, with technician Greg Pena performing the assessment in accordance with National Fire Protection Association (NFPA) Standards 80 and 105.

The inspection results reveal significant findings: 56.35% of dampers passed inspection, 26.98% failed, and 16.67% were non-accessible. Failure reasons included inoperable actuators, dampers not fully opening or closing, actuators not properly installed, and lack of access. Specific issues were identified on multiple floors, such as dampers with power but disconnected switches, metal obstructing blade closure, and dampers found in closed positions. The report includes detailed documentation for each damper, including location, type, and photographic evidence, which suggests the need for comprehensive maintenance and repair of the facility's fire and smoke damper systems.

View the file

Other files

File Type Posted
36C26126Q0018 0002.docx DOCX document
Floor Plans - Fire and Smoke Dampers - Working.pdf PDF
975 Kirman Pre action 5 yr 7-20.pdf PDF
ANNUAL FWP 231130.pdf PDF
Semi-annual FM200 4-28-2025.pdf PDF
Reno VAMC-Area G - Damper Inspection Report 2025.pdf PDF
975 Kirman Ave. Reno Nv FSD 1.30.24.pdf PDF
VA Bldg. 12 Preaction 10-22-2024.pdf PDF
Reno VAMC-Building 1D - Damper Inspection Report 2025.pdf PDF
Semi-annual Ansul Testing Canteen 05-15-24.pdf PDF
QTRLY flow and tamper blank document.xlsx XLSX spreadsheet
Area D Fire Damper Inspection.xlsx XLSX spreadsheet
Semi-annual Ansul Testing NFS 05-15-24.pdf PDF
VA Bldg. 12 Preaction 1-6-2025.pdf PDF
36C26126Q0018 0001.docx DOCX document
2- Floor Plans - Fire and Smoke Dampers Bldg 1 1A 1D 5 6 10 12.pdf PDF
VA Bldg. 12 Preaction 4-28-2025.pdf PDF
Reno VAMC-Building 5 Section K - Damper Inspection Report 2024.pdf PDF
Attachment 1 - Drawings.pdf PDF
Reno VAMC-Building 12 - Damper Inspection Report 2025.pdf PDF
Bldg Sprinkler Inspections.pdf PDF
Reno VAMC-Building 6 - Damper Inspection Report 2025.pdf PDF
VA FSD Inspection Bldg 10 FD 5B-Fail 5.9.24.pdf PDF
Semi-annual FM200 10-22-2024.pdf PDF
Site Visit Information.docx DOCX document
36C26126Q0018.docx DOCX document
Show all 26

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

908 South 8th Street Louisville, KY. 40203

888.675.4519 info@LifeSafetyServices.com

Damper Inspection Report Reno VAMC - Building 1 Section C

08/15/2024 - 08/21/2024 www.LifeSafetyServices.com

DAMPER INSPECTION REPORT

Corporate Office 908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519

Facility: Reno VAMC Inspection Date: 08/15/2024 - 08/21/2024 Inspected By: Greg Pena Job ID: DR-040524-C11-DIS

FIRE & SMOKE DAMPER INSPECTION SERVICES

LSS Life Safety Services, LLC, in accordance with The National Fire Protection Association’s (NFPA) Standard 80 Chapter 19 and 105 Chapter 7 inspected fire and smoke dampers located in Building 1 Section C during the period of 08/15/2024 - 08/21/2024.

The following report and digital pictures provide the result of the inspection for the dampers that were inspected.

This report is intended to describe the location and operability of the dampers for the date in which LSS Life Safety Services’ representatives performed the inspection of the dampers, and is not intended to constitute any warranty as to the continued operation of any damper.

Thank you for contracting LSS Life Safety Services for this project and we look forward to the opportunity of working with you in the future on additional projects.

Technician Signature

908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519

Project Summary Building Fire Smoke Combination Pass Fail Non-Accessible

Building #1 0 0 126 71 34 21

GRAND TOTAL 0 0 126 71 34 21

Statistics Test Result % of Dampers

Pass 56.35%

Fail 26.98%

Non-Accessible 16.67%

Type Total % of Dampers

Fire 0 0.00%

Smoke 0 0.00%

Combination 126 100.00%

908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519

Facility: Reno VAMC Inspection Date: 08/15/2024 Inspected By: Greg Pena

All Dampers Date Floor Damper Number Damper

Type Damper Location

Inspection Result

Reason for Failure or Inaccessibility

08/15/2024 6 6-FSD-C6317-1 CombinationInside room C6317 above door Pass

08/15/2024 6 6-FSD-C6317-4 Combination Inside room, C6317 above whiteboard Pass

08/15/2024 6 6-FSD-C6319-5 Combination Outside of door, C6319 above door Pass

08/15/2024 6 6-FSD-C6329-6 Combination

Inside room, C6327 above computer desk, right hand corner back wall

Pass

08/15/2024 6 6-FSD-C6326-7 Combination Inside office

C6326 back wall left-hand corner

Fail Inoperable actuator

08/15/2024 6 6-FSD-C6357-8 Combination Outside storage door C6357 above door

Fail Inoperable actuator

08/15/2024 6 6-FSD-C6361-9 Combination Inside staff lounge room C6355 Non-Accessible No access door, access door install not authorized

08/15/2024 6 6-FSD-C6361-10 Combination

Inside office C6361 left side beside the door inside the office in between the walls

Pass

08/15/2024 6 6-FSD-C6365-12 Combination Inside exam room C6365 left-hand front corner by patient exam bed

Pass

08/15/2024 6 6-FSD-C6367-13 Combination Inside exam room C6367 left-hand wall corner above the sink

Pass

08/15/2024 6 6-FSD-C6360-11 CombinationInside room C6360 above the door Pass

08/15/2024 5 5-FSD-C5319-3 Combination Outside office C5319 above the door Pass

908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519

Facility: Reno VAMC Inspection Date: 08/16/2024 Inspected By: Greg Pena

All Dampers Date Floor Damper Number Damper

Type Damper Location

Inspection Result

Reason for Failure or Inaccessibility

08/16/2024 5 5-FSD-C5309-4 CombinationInside office c5309 left-hand corner Pass

08/16/2024 5 5-FSD-C5309-6 Combination Inside office number C 5309 outside door above door Pass

08/16/2024 5 5-FSD-C5307-1 Combination Inside office C 5307 plain side wall above boxes Pass

08/16/2024 5 5-FSD-C5307-2 Combination Inside office c

5307 left-hand side above key box

Non-Accessible No access door, access door install not authorized

08/16/2024 5 5-FSD-C5317-1 Combination Inside office C 5317 above door Pass

08/16/2024 5 5-FSD-C5317-2 Combination Inside office C

5317 right hand side corner above key boxes Pass

08/16/2024 5 5-FSD-C5327-4 Combination Inside office C

5327 right hand corner above chair

Pass

08/16/2024 5 5-FSD-C5324-5 Combination Inside office C 5324 back wall Pass

08/16/2024 5 5-FSD-C5358-11 Combination

Inside room C 5358 above refrigerator back right hand corner of the staff lounge

Non-Accessible No access door, access door install not authorized

08/16/2024 5 5-FSD-C5355-7 Combination Outside office C 5355 Fail Inoperable actuator

08/16/2024 5 5-FSD-C5353-6 Combination Outside door C 5353 in hallway Fail Inoperable actuator

08/16/2024 5 5-FSD-C5365-10 Combination Inside office, c 5365 directly in front of door front wall

Pass

08/16/2024 5 5-FSD-C5373-1 Combination Inside office C 5373 Pass

08/16/2024 5 5-FSD-C5373-2 Combination Outside office C

5373 directly above the door

Fail Inoperable actuator

08/16/2024 5 5-FSD-C5379-4 Combination Inside office C 5379 above door Pass

908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519

Date Floor Damper Number Damper Type

Damper Location

Inspection Result

Reason for Failure or Inaccessibility

08/16/2024 5 5-FSD-C5380-5 Combination

Inside conference room c5380 next to back storage door above key box on wall

Fail Inoperable actuator

08/16/2024 5 5-FSD-C5359-8 Combination

Inside office C5359 left-hand front corner of office above key boxes

Pass

08/16/2024 5 5-FSD-C5359-9 Combination Inside office, c5359 left-hand front corner by key boxes Pass

08/16/2024 4 4-FSD-C4307-1 Combination

In hallway across from storage C

4304 about 6 feet down the hallway through the right hand side across from HVAC room

Non-Accessible No access door, access door install not authorized

08/16/2024 4 4-FSD-C4307-3 Combination

Inside office C 4309 there’s another door C 4307 right hand side corner of C

4307 is the damper and access

Pass

08/16/2024 4 4-FSD-C4309-4 Combination Inside office C 4309 above door Fail Blades will not fully open

08/16/2024 4 4-FSD-C4307-2 Combination Outside room C 4309 above key box number tw

Pass

08/16/2024 4 4-FSD-C4313-5 Combination

Inside office C 4313 between door and front wall soon as you walk in middle of room

Pass

08/16/2024 4 4-FSD-C4295-7 Combination Inside storage room c 4295 left-hand front corner by vent Pass

08/16/2024 4 4-FSD-C4295-6 Combination Inside room C 4295 left-hand front corner by vent Fail Inoperable actuator

08/16/2024 4 4-FSD-C4290-9 CombinationInside room C4290 above door Pass

08/16/2024 4 4-FSD-C4286-10 Combination

Inside office area C 4286 left-hand side above desk workstation middle of office

Pass

08/16/2024 4 4-FSD-C4319-1 CombinationOutside door office C 4319 above door Fail Actuator needs to be bolted in place

08/16/2024 4 4-FSD-C4319-2 Combination Outside office number C 4319 above door

908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519

Date Floor Damper Number Damper Type

Damper Location

Inspection Result

Reason for Failure or Inaccessibility

08/16/2024 4 4-FSD-C4319-3 Combination Inside office C 4319 back wall Fail Blades will not fully close

08/16/2024 4 4-FSD-C4324-4 Combination Inside office

C4324 back left-hand corner above key box Fail Damper found in the closed position

08/16/2024 4 4-FSD-C4325-5 Combination Inside office number C4325 right hand back corner above desk

908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519

Facility: Reno VAMC Inspection Date: 08/17/2024 Inspected By: Greg Pena

All Dampers Date Floor Damper Number Damper

Type Damper Location

Inspection Result

Reason for Failure or Inaccessibility

08/17/2024 4 4-FSD-C4333-13 Combination Inside office

C4333 back left-hand corner above the key box Pass

08/17/2024 4 4-FSD-C4342-12 Combination

Go through EMS headquarters door number C4332 Pass

08/17/2024 4 4-FSD-C4353-6 Combination Outside room number C 4353 directly above the door Pass

08/17/2024 4 4-FSD-C4357-7 Combination Outside office number C 4357 directly above the door Fail Actuator has power but switch may not be connected

08/17/2024 4 4-FSD-C4357-8 Combination Inside office number C 4357 left-hand corner above key box

Pass

08/17/2024 4 4-FSD-C4357-9 Combination Inside office C

4357 right hand side front corner above key box

Pass

08/17/2024 4 4-FSD-C4356-10 Combination

Inside office number c good 4356 left-hand corner in the back above key box

Pass

08/17/2024 4 4-FSD-C4365-11 Combination Inside staff lounge C 4365 directly in front of the door

Pass

08/17/2024 4 4-FSD-C4373-1 Combination Outside office C 4373 Fail Inoperable actuator

08/17/2024 4 4-FSD-C4373-3 Combination

To the right-hand side of office C

4373 outside of the door above the key box labeled three

Fail Inoperable actuator

08/17/2024 4 4-FSD-C4373-2 Combination

Inside office C4373 right hand side through the doorway to the right again above the key box label to

Fail Damper blades will not close

08/17/2024 4 4-FSD-C4377-5 Combination

Outside office C 4377 in the hallway by the bulkhead above key box labeled five

908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519

Date Floor Damper Number Damper Type

Damper Location

Inspection Result

Reason for Failure or Inaccessibility

08/17/2024 4 4-FSD-C4381-6 Combination

Inside office C 4381 directly in front of the door above key box on the wall labeled six

Pass

08/17/2024 4 4-FSD-C4405-7 Combination Inside office C

4405 directly by door

Pass

08/17/2024 4 4-FSD-C4405-8 Combination Inside office C

4405 right hand back corner

Pass

08/17/2024 4 4-FSD-C4400-10 Combination Inside of C4400 above door Fail Inoperable actuator

08/17/2024 4 4-FSD-C4394-11 Combination Outside office C

4394 directly above the door

Fail Damper found in the closed position

08/17/2024 4 4-FSD-C4395-12 Combination

Inside office number C 4395 I’ll be against the left-hand side of the wall

Fail Inoperable actuator

08/17/2024 3 3-FSD-C3307-1 Combination

Inside men’s restroom C 3307 in front of the toilet stall door drywall hatch key box

Pass

08/17/2024 3 3-FSD-C3309-4 Combination Inside women’s restroom C 3309 to left-hand side of the door

Non-Accessible No access door, access door install not authorized

08/17/2024 3 3-FSD-C3309-2 Combination

Inside women’s restroom C 3309 to the left-hand side front corner drywall hatches right there above the mirror

Non-Accessible No access door, access door install not authorized

08/17/2024 3 3-FSD-C3309-3 Combination Inside men’s restroom C 3307 right hand corner wall above urinal

Pass

08/17/2024 3 3-FSD-C3313-5 Combination

Inside office C 3313 directly in front of the door above the key box on the wall label five

Non-Accessible No access door, access door install not authorized

08/17/2024 3 3-FSD-C3293-6 Combination Directly above reception desk, location, C3293

Fail Damper found in closed position

08/17/2024 3 3-FSD-C3293-7 Combination Behind reception desk area c3293 Pass

08/17/2024 3 3-FSD-C3290-9 Combination Outside office number, C3290 right above door

Fail Inoperable actuator

08/17/2024 3 3-FSD-C3284-10 Combination Inside exam room C 3284 above door Fail Inoperable actuator

908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519

Date Floor Damper Number Damper Type

Damper Location

Inspection Result

Reason for Failure or Inaccessibility

08/17/2024 3 3-FSD-C3285-11 Combination Directly in front of the door inside room, C3285 right hand corner

908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519

Facility: Reno VAMC

Inspection Date: 08/18/2024 Inspected By: Greg Pena

All Dampers Date Floor Damper Number Damper

Type Damper Location

Inspection Result

Reason for Failure or Inaccessibility

08/18/2024 3 3-FSD-C3353-5 Combination Outside office C3353 directly above door Pass

08/18/2024 3 3-FSD-C3357-6 Combination

Outside office number C 3357 directly above door key box number 6 is in between the doors

Pass

08/18/2024 3 3-FSD-C3357-7 Combination

Inside office C 3357 left-hand back corner by smoke detector and key box labeled seven

Pass

08/18/2024 3 3-FSD-C3357-8 Combination

Inside office C 3357 to the right front corner above key box labeled eight

Pass

08/18/2024 3 3-FSD-C3365-9 Combination

Inside office c3365 directly in front of the door there’s a wall with a key box. Label nine

Pass

08/18/2024 3 3-FSD-C3373-1 Combination Outside office C3373 directly above door Pass

08/18/2024 3 3-FSD-C3375-3 Combination

Go through office door see 3373 to the right hand side.

There’s another door C 3375 in there right hand side corner.

There’s a box labeled three above the box is the damper.

Pass

08/18/2024 3 3-FSD-C3375-2 Combination Inside of this C 3375 directly above door

Pass

08/18/2024 3 3-FSD-C3377-4 Combination Outside office C 3377 above key box labeled four

Fail Inoperable actuator

08/18/2024 3 3-FSD-C3381-5 Combination

Inside of C 3381 directly in front of the door key box label five by the vent

Pass

08/18/2024 3 3-FSD-C3356-10 Combination Inside office C 3356 left-hand back corner above key box labeled 10

Fail Inoperable actuator

908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519

Facility: Reno VAMC Inspection Date: 08/19/2024

Inspected By: Greg Pena

All Dampers Date Floor Damper Number Damper

Type Damper Location

Inspection Result

Reason for Failure or Inaccessibility

08/19/2024 3 3-FSD-C3333-11 Combination

Outside of office C3333 directly above door key box is to the right label 11

Pass

08/19/2024 3 3-FSD-C3340-14 Combination Inside office c3340 left-hand side back wall above key box

Pass

08/19/2024 3 3-FSD-C3344-13 Combination

Inside office C 3344 in front of door there’s a wall with a key box label 13 it’s above that

Fail Blades will not fully open

08/19/2024 3 3-FSD-C3337-12 Combination Inside room C

3337 to the right there is a drywall hatch by the floor

Non-Accessible No access door, nowhere to install access door

08/19/2024 3 3-FSD-C3405-6 Combination Inside office C 3405 directly above the door Fail Inoperable actuator

08/19/2024 3 3-FSD-C3405-7 Combination Inside office C

3405 right hand side wall in the corner Pass

08/19/2024 3 3-FSD-C3400-8 Combination Inside office

C3400 directly above the door

Fail Inoperable actuator

08/19/2024 3 3-FSD-c3396-9 Combination Inside office

C3396 directly above door

Pass

08/19/2024 3 3-FSD-C3397-10 Combination Inside office C 3397 directly in front of door above key box

Fail Damper found in closed position

08/19/2024 2 2-FSD-C2379-3 Combination

Inside storage room C 2379 up against the left-hand wall above the key box

Fail Actuator not installed correctly and thermal link is not hooked up

08/19/2024 2 2-FSD-C2375-2 Combination Outside of office C

2375 directly above door

Fail Inoperable actuator

08/19/2024 2 2-FSD-C2383-4 Combination

Inside storage room c2383 directly in front of the door there’s a wall with a key box. The damper is right above it.

908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519

Date Floor Damper Number Damper Type

Damper Location

Inspection Result

Reason for Failure or Inaccessibility

08/19/2024 2 2-FSD-C2375-1 Combination

Inside office C2375 directly in front of the door, the back wall above the key box

Pass

08/19/2024 2 2-FSD-C2403-5 Combination Inside office C

2403 front left side above door

Pass

08/19/2024 2 2-FSD-C2403-6 Combination

Inside office c2403 key box on the wall opposite the door they will six damper above it

Pass

08/19/2024 2 2-FSD-C2400-7 Combination Inside office C

2400 above the door

Non-Accessible No access door, nowhere to install access door

08/19/2024 2 2-FSD-C2396-8 Combination Inside biohazard room C 2396 directly above door

Pass

08/19/2024 2 2-FSD-C2397-9 Combination Inside office

C2397 back right hand corner

Fail Damper failed to fully close

08/19/2024 2 2-FSD-C2365-5 Combination Inside office C

2365 left-hand wall above computer desk Pass

08/19/2024 2 2-FSD-C2359-3 Combination Outside of office C

2359 directly above door, the vent Pass

08/19/2024 2 2-FSD-C2357-1 Combination Outside of office C

2357 directly above door

Non-Accessible No access door, access door install not authorized

08/19/2024 2 2-FSD-C2357-2 Combination Inside office C

2357 the second tile from the window Pass

08/19/2024 2 2-FSD-C2360-4 Combination

Inside office C 2360 right hand corner above the key box and the refrigerator

Pass

08/19/2024 2 2-FSD-C2353-6 Combination Inside conference room C 2353 right hand front corner

Fail Inoperable actuator

908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519

Facility: Reno VAMC Inspection Date: 08/20/2024 Inspected By: Greg Pena

All Dampers Date Floor Damper Number Damper

Type Damper Location

Inspection Result

Reason for Failure or Inaccessibility

08/20/2024 2 2-FSD-C2335A-8 Combination Inside office

C2335A directly above the door

Non-Accessible No access door, nowhere to install access door

908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519

Facility: Reno VAMC Inspection Date: 08/21/2024 Inspected By: Greg Pena

All Dampers Date Floor Damper Number Damper

Type Damper Location

Inspection Result

Reason for Failure or Inaccessibility

08/21/2024 2 2-FSD-C2301-1 Combination Inside lab office

C 2301 back wall above vent

Non-Accessible No access door, access door install not authorized

08/21/2024 2 2-FSD-C2300-2 Combination

Inside lab C 2300 second-floor for right hand back corner above biological safety cabinet

Non-Accessible No access door, nowhere to install access door

08/21/2024 2 2-FSD-C2307-3 Combination Inside women’s restroom C2307 Pass

08/21/2024 1 1-FSD-C1379-1 Combination Inside warehouse C1379 back left-hand corner above the duct work

Non-Accessible No access door, access door install not authorized

08/21/2024 1 1-FSD-C1377-2 Combination Inside office

C1377 back right hand corner

Non-Accessible No access door, access door install not authorized

08/21/2024 1 1-FSD-C1379-3 Combination Inside the hallway above the double doors going to warehouse C1379

Non-Accessible No access door, access door install not authorized

08/21/2024 1 1-FSD-C1379-4 Combination

Inside hallway going towards warehouse see 1379. It’s above the double doors.

Non-Accessible No access door, access door install not authorized

08/21/2024 1 1-FSD-C1365-5 Combination

Inside storage room C 1365 directly in front of the door on the wall above the key fob

Fail Damper will not fully open

08/21/2024 1 1-FSD-C1359-6 Combination Inside office

C1359 above the door by the key fob

Fail Inoperable actuator

08/21/2024 1 1-FSD-C1357-7 Combination Above door office C1357 Pass

08/21/2024 1 1-FSD-C1357-8 Combination Inside office

C1357 by the window

Fail Metal stuck between damper and blades preventing closure

08/21/2024 1 1-FSD-C1318-9 Combination

Inside kitchen C 1318 above prep space where the key fob is to the right of the door

Non-Accessible No access door, access door install not authorized

08/21/2024 1 1-FSD-C1318-10 Combination

Inside kept to dining area directly in front of sliding door across from courtyard

Non-Accessible No access door, access door install not authorized

908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519

Date Floor Damper Number Damper Type

Damper Location

Inspection Result

Reason for Failure or Inaccessibility

08/21/2024 1 1-FSD-C1318-10 Combination

Inside cafeteria dining area back door through prep number C 1318 is across from kiosk in the middle of dining area

Non-Accessible No access door, access door install not authorized

08/21/2024 1 1-FSD-C1318-12 Combination Above store kiosk where they sell hats by dining area Non-Accessible No access door, access door install not authorized

08/21/2024 1 1-FSD-C1332-13 Combination

Through second floor kitchen to the back staircase, going downstairs to the right of the stairs storage room C1332 inside to the left above the door

Pass

08/21/2024 1 1-FSD-C1342-14 Combination

Through kitchen on second floor, back staircase, going down to first floor, corridor across from staircase ,in front of refrigerator

C1342 above the door

Pass

08/21/2024 1 1-FSD-C1335-15 Combination

For the kitchen on the second floor, down the back staircase, to the right at the bottom of the staircase, inside storage room, C1335 above the door

908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519

Location Description: Inside room C6317 above door

Tag: 6-FSD-C6317-1

Type: Combination

Floor: 6

Status: Pass

Open Photo Closed Photo https://www.gocanvas.com/values/20310091043 https://www.gocanvas.com/values/20310091043 https://www.gocanvas.com/values/20310091046 https://www.gocanvas.com/values/20310091046

908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519

Location Description: Inside room C6317 above whiteboard

Tag: 6-FSD-C6317-4

Type: Combination

Floor: 6

Status: Pass

Open Photo Closed Photo https://www.gocanvas.com/values/20310091240 https://www.gocanvas.com/values/20310091240 https://www.gocanvas.com/values/20310091243 https://www.gocanvas.com/values/20310091243

908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519

Location Description: Outside of door C6319

Tag: 6-FSD-C6319-5

Type: Combination

Floor: 6

Status: Pass

Open Photo Closed Photo https://www.gocanvas.com/values/20310091601 https://www.gocanvas.com/values/20310091601 https://www.gocanvas.com/values/20310091602 https://www.gocanvas.com/values/20310091602

908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519

Location Description: Inside room C6327 above computer desk, right hand corner back wall

Tag: 6-FSD-C6329-6

Type: Combination

Floor: 6

Status: Pass

Open Photo Closed Photo

Location Description: Inside office c6326 back wall left-hand corner

Tag: 6-FSD-c6326-7

Type: Combination

Floor: 6

Status: Fail

Reason for Failure or Inaccessibility: Inoperable actuator

Open Photo Closed Photo Actuator Photo https://www.gocanvas.com/values/20310091676 https://www.gocanvas.com/values/20310091676 https://www.gocanvas.com/values/20310091677 https://www.gocanvas.com/values/20310091677 https://www.gocanvas.com/values/20310091786 https://www.gocanvas.com/values/20310091786 https://www.gocanvas.com/values/20310091787 https://www.gocanvas.com/values/20310091787 https://www.gocanvas.com/values/20310091788 https://www.gocanvas.com/values/20310091788

908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519

Location Description: Outside storage door C6357 above door

Tag: 6-FSD-C6357-8

Type: Combination

Floor: 6

Status: Fail

Reason for Failure or Inaccessibility: Inoperable actuator

Open Photo Closed Photo Actuator Photo https://www.gocanvas.com/values/20310091861 https://www.gocanvas.com/values/20310091861 https://www.gocanvas.com/values/20310091862 https://www.gocanvas.com/values/20310091862 https://www.gocanvas.com/values/20310091863 https://www.gocanvas.com/values/20310091863

908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519

Location Description: Inside staff lounge room C6355

Tag: 6-FSD-c6361-9

Type: Combination

Floor: 6

Status: Non-Accessible

Reason for Failure or Inaccessibility: No access door, access door install not authorized

Open Photo Closed Photo

Location Description: Inside office C6361 left side beside the door inside the office in between the walls

Tag: 6-FSD-C6361-10

Type: Combination

Floor: 6

Status: Pass

Open Photo Closed Photo https://www.gocanvas.com/values/20310091994 https://www.gocanvas.com/values/20310091994 https://www.gocanvas.com/values/20310091995 https://www.gocanvas.com/values/20310091995 https://www.gocanvas.com/values/20310092109 https://www.gocanvas.com/values/20310092109 https://www.gocanvas.com/values/20310092113 https://www.gocanvas.com/values/20310092113

908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519

Location Description: Inside exam room C6365 left-hand front corner by patient exam bed

Tag: 6-FSD-C6365-12

Type: Combination

Floor: 6

Status: Pass

Open Photo Closed Photo

Location Description: Inside exam room C6367 left-hand wall corner above the sink

Tag: 6-FSD-C6367-13

Type: Combination

Floor: 6

Status: Pass

Open Photo Closed Photo https://www.gocanvas.com/values/20310092370 https://www.gocanvas.com/values/20310092370 https://www.gocanvas.com/values/20310092373 https://www.gocanvas.com/values/20310092373 https://www.gocanvas.com/values/20310092481 https://www.gocanvas.com/values/20310092481 https://www.gocanvas.com/values/20310092482 https://www.gocanvas.com/values/20310092482

908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519

Location Description: Inside room C6360 above the door

Tag: 6-FSD-C6360-11

Type: Combination

Floor: 6

Status: Pass

Closed PhotoOpen Photo

Location Description: Outside office C5319 above the door

Tag: 5-FSD-C5319-3

Type: Combination

Floor: 5

Status: Pass

Open Photo Closed Photo https://www.gocanvas.com/values/20310092556 https://www.gocanvas.com/values/20310092556 https://www.gocanvas.com/values/20310092557 https://www.gocanvas.com/values/20310092557 https://www.gocanvas.com/values/20310092631 https://www.gocanvas.com/values/20310092631 https://www.gocanvas.com/values/20310092632 https://www.gocanvas.com/values/20310092632

908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519

Location Description: Inside office C5309 left-hand corner

Tag: 5-FSD-C5309-4

Type: Combination

Floor: 5

Status: Pass

Open Photo Closed Photo https://www.gocanvas.com/values/20319970088 https://www.gocanvas.com/values/20319970088 https://www.gocanvas.com/values/20319970091 https://www.gocanvas.com/values/20319970091

908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519

Location Description: Inside office number C 5309 outside door above door

Tag: 5-FSD-C5309-6

Type: Combination

Floor: 5

Status: Pass

Open Photo Closed Photo https://www.gocanvas.com/values/20319970245 https://www.gocanvas.com/values/20319970245 https://www.gocanvas.com/values/20319970247 https://www.gocanvas.com/values/20319970247

908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519

Location Description: Inside office C 5307 plain side wall above boxes

Tag: 5-FSD-C5307-1

Type: Combination

Floor: 5

Status: Pass

Open Photo Closed Photo https://www.gocanvas.com/values/20319970335 https://www.gocanvas.com/values/20319970335 https://www.gocanvas.com/values/20319970336 https://www.gocanvas.com/values/20319970336

908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519

Location Description: Inside office C5307 left-hand side above key box

Tag: 5-FSD-C5307-2

Type: Combination

Floor: 5

Status: Non-Accessible

Reason for Failure or Inaccessibility: No access door, access door install not authorized

Open Photo Closed Photo

Location Description: Inside office C 5317 above door

Tag: 5-FSD-c5317-1

Type: Combination

Floor: 5

Status: Pass

Open Photo Closed Photo https://www.gocanvas.com/values/20319970418 https://www.gocanvas.com/values/20319970418 https://www.gocanvas.com/values/20319970419 https://www.gocanvas.com/values/20319970419 https://www.gocanvas.com/values/20319970493 https://www.gocanvas.com/values/20319970493 https://www.gocanvas.com/values/20319970494 https://www.gocanvas.com/values/20319970494

908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519

Location Description: Inside office C 5317 right hand side corner above key boxes

Tag: 5-FSD-C5317-2

Type: Combination

Floor: 5

Status: Pass

Open Photo Closed Photo

Location Description: Inside office C 5327 right hand corner above chair

Tag: 5-FSD-C5327-4

Type: Combination

Floor: 5

Status: Pass

Open Photo Closed Photo https://www.gocanvas.com/values/20319970571 https://www.gocanvas.com/values/20319970571 https://www.gocanvas.com/values/20319970573 https://www.gocanvas.com/values/20319970573 https://www.gocanvas.com/values/20319970699 https://www.gocanvas.com/values/20319970699 https://www.gocanvas.com/values/20319970701 https://www.gocanvas.com/values/20319970701

908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519

Location Description: Inside office C 5324 back wall

Tag: 5-FSD-C5324-5

Type: Combination

Floor: 5

Status: Pass

Open Photo Closed Photo https://www.gocanvas.com/values/20319970855 https://www.gocanvas.com/values/20319970855 https://www.gocanvas.com/values/20319970858 https://www.gocanvas.com/values/20319970858

908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519

Location Description: Inside room C 5358 above refrigerator back right hand corner of the staff lounge

Tag: 5-FSD-C5358-11

Type: Combination

Floor: 5

Status: Non-Accessible

Reason for Failure or Inaccessibility: No access door, access door install not authorized

Open Photo

Closed Photo https://www.gocanvas.com/values/20319970997 https://www.gocanvas.com/values/20319970997 https://www.gocanvas.com/values/20319970999 https://www.gocanvas.com/values/20319970999

908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519

Location Description: Outside office C 5355

Tag: 5-FSD-C5355-7

Type: Combination

Floor: 5

Status: Fail

Reason for Failure or Inaccessibility: Inoperable actuator

Open Photo Closed Photo Actuator Photo https://www.gocanvas.com/values/20319971138 https://www.gocanvas.com/values/20319971138 https://www.gocanvas.com/values/20319971141 https://www.gocanvas.com/values/20319971141 https://www.gocanvas.com/values/20319971143 https://www.gocanvas.com/values/20319971143

908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519

Location Description: Outside door C 5353 in hallway

Tag: 5-FSD-C5353-6

Type: Combination

Floor: 5

Status: Fail

Reason for Failure or Inaccessibility: Inoperable actuator

Open Photo Closed Photo Actuator Photo

Location Description: Inside office, c 5365 directly in front of door front wall

Tag: 5-FSD-c5365-10

Type: Combination

Floor: 5

Status: Pass

Open Photo Closed Photo https://www.gocanvas.com/values/20319971219 https://www.gocanvas.com/values/20319971219 https://www.gocanvas.com/values/20319971220 https://www.gocanvas.com/values/20319971220 https://www.gocanvas.com/values/20319971221 https://www.gocanvas.com/values/20319971221 https://www.gocanvas.com/values/20319971299 https://www.gocanvas.com/values/20319971299 https://www.gocanvas.com/values/20319971300 https://www.gocanvas.com/values/20319971300

908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519

Location Description: Inside office C 5373

Tag: 5-FSD-C5373-1

Type: Combination

Floor: 5

Status: Pass

Open Photo Closed Photo https://www.gocanvas.com/values/20319971416 https://www.gocanvas.com/values/20319971416 https://www.gocanvas.com/values/20319971418 https://www.gocanvas.com/values/20319971418

908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519

Location Description: Outside office C 5373 directly above the door

Tag: 5-FSD-C5373-2

Type: Combination

Floor: 5

Status: Fail

Reason for Failure or Inaccessibility: Inoperable actuator

Open Photo Closed Photo Actuator Photo

Location Description: Inside office C 5379 above door

Tag: 5-FSD-c5379-4

Type: Combination

Floor: 5

Status: Pass

Open Photo Closed Photo https://www.gocanvas.com/values/20319971542 https://www.gocanvas.com/values/20319971542 https://www.gocanvas.com/values/20319971544 https://www.gocanvas.com/values/20319971544 https://www.gocanvas.com/values/20319971545 https://www.gocanvas.com/values/20319971545 https://www.gocanvas.com/values/20319971618 https://www.gocanvas.com/values/20319971618 https://www.gocanvas.com/values/20319971619 https://www.gocanvas.com/values/20319971619

908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519

Location Description: Inside conference room c5380 next to back storage door above key box on wall

Tag: 5-FSD-C5380-5

Type: Combination

Floor: 5

Status: Fail

Reason for Failure or Inaccessibility: Inoperable actuator

Open Photo

Closed Photo Actuator Photo

Location Description: Inside office C5359 left-hand front corner of office above key boxes

Tag: 5-FSD-c5359-8

Type: Combination

Floor: 5

Status: Pass

Open Photo Closed Photo https://www.gocanvas.com/values/20319971693 https://www.gocanvas.com/values/20319971693 https://www.gocanvas.com/values/20319971694 https://www.gocanvas.com/values/20319971694 https://www.gocanvas.com/values/20319971695 https://www.gocanvas.com/values/20319971695 https://www.gocanvas.com/values/20319971768 https://www.gocanvas.com/values/20319971768 https://www.gocanvas.com/values/20319971769 https://www.gocanvas.com/values/20319971769

908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519

Location Description: Inside office C5359 left-hand front corner by key boxes

Tag: 5-FSD-C5359-9

Type: Combination

Floor: 5

Status: Pass

Open Photo Closed Photo

Location Description: In hallway across from storage C 4304 about 6 feet down the hallway through the right hand side across from HVAC room

Tag: 4-FSD-C4307-1

Type: Combination Floor: 5

Status: Non-Accessible

Reason for Failure or Inaccessibility: No access door, access door install not authorized

Open Photo Closed Photo https://www.gocanvas.com/values/20319971843 https://www.gocanvas.com/values/20319971843 https://www.gocanvas.com/values/20319971844 https://www.gocanvas.com/values/20319971844 https://www.gocanvas.com/values/20319972018 https://www.gocanvas.com/values/20319972018 https://www.gocanvas.com/values/20319972020 https://www.gocanvas.com/values/20319972020

908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519

Location Description: Inside office C 4309 there’s another door C 4307 right hand side corner of C 4307 is the damper and access

Tag: 4-FSD-C4307-3

Type: Combination

Floor: 4

Status: Pass

Open Photo Closed Photo

Location Description: Inside office C 4309 above door

Tag: 4-FSD-C4309-4

Type: Combination

Floor: 4

Status: Fail

Reason for Failure or Inaccessibility: Blades will not fully open

Open Photo Closed Photo Actuator Photo https://www.gocanvas.com/values/20319972114 https://www.gocanvas.com/values/20319972114 https://www.gocanvas.com/values/20319972116 https://www.gocanvas.com/values/20319972116 https://www.gocanvas.com/values/20319972228 https://www.gocanvas.com/values/20319972228 https://www.gocanvas.com/values/20319972229 https://www.gocanvas.com/values/20319972229 https://www.gocanvas.com/values/20319972230 https://www.gocanvas.com/values/20319972230

908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519

Location Description: Outside room C 4309 above key box number 2

Tag: 4-FSD-C4307-2

Type: Combination

Floor: 4

Status: Pass

Open Photo Closed Photo

Location Description: Inside office C 4313 between door and front wall soon as you walk in middle of room

Tag: 4-FSD-c4313-5

Type: Combination

Floor: 4

Status: Pass

Open Photo Closed Photo https://www.gocanvas.com/values/20319972326 https://www.gocanvas.com/values/20319972326 https://www.gocanvas.com/values/20319972329 https://www.gocanvas.com/values/20319972329 https://www.gocanvas.com/values/20319972491 https://www.gocanvas.com/values/20319972491 https://www.gocanvas.com/values/20319972492 https://www.gocanvas.com/values/20319972492

908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519

Location Description: Inside storage room C4295 left-hand front corner by vent

Tag: 4-FSD-C4295-6

Type: Combination

Floor: 4

Status: Pass

Open Photo

Closed Photo https://www.gocanvas.com/values/20319972566 https://www.gocanvas.com/values/20319972566 https://www.gocanvas.com/values/20319972567 https://www.gocanvas.com/values/20319972567

908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519

Location Description: Inside room C 4295 left-hand front corner by vent

Tag: 4-FSD-C4295-7

Type: Combination

Floor: 4

Status: Fail

Reason for Failure or Inaccessibility: Inoperable actuator

Open Photo

Closed Photo

Actuator Photo

Location Description: Inside room C4290 above door

Tag: 4-FSD-c4290-9

Type: Combination

Floor: 4

Status: Pass

Open Photo Closed Photo https://www.gocanvas.com/values/20319972646 https://www.gocanvas.com/values/20319972646 https://www.gocanvas.com/values/20319972648 https://www.gocanvas.com/values/20319972648 https://www.gocanvas.com/values/20319972651 https://www.gocanvas.com/values/20319972651 https://www.gocanvas.com/values/20319972764 https://www.gocanvas.com/values/20319972764 https://www.gocanvas.com/values/20319972765 https://www.gocanvas.com/values/20319972765

908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519

Location Description: Inside office area C 4286 left-hand side above desk workstation middle of office

Tag: 4-FSD-C4286-10

Type: Combination

Floor: 4

Status: Pass

Open Photo

Closed Photo https://www.gocanvas.com/values/20319972839 https://www.gocanvas.com/values/20319972839 https://www.gocanvas.com/values/20319972840 https://www.gocanvas.com/values/20319972840

908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519

Location Description: Outside door office C 4319 above door

Tag: 4-FSD-C4319-1

Type: Combination

Floor: 4

Status: Fail

Reason for Failure or Inaccessibility: Actuator needs to be bolted in place

Open Photo Closed Photo

Actuator Photo https://www.gocanvas.com/values/20319972921 https://www.gocanvas.com/values/20319972921 https://www.gocanvas.com/values/20319972923 https://www.gocanvas.com/values/20319972923 https://www.gocanvas.com/values/20319972925 https://www.gocanvas.com/values/20319972925

908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519

Location Description: Outside office number C 4319 above door

Tag: 4-FSD-C4319-2

Type: Combination

Floor: 4

Status: Pass

Open Photo

Closed Photo https://www.gocanvas.com/values/20319973049 https://www.gocanvas.com/values/20319973049 https://www.gocanvas.com/values/20319973051 https://www.gocanvas.com/values/20319973051

908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519

Location Description: Inside office C 4319 back wall

Tag: 4-FSD-C4319-3

Type: Combination

Floor: 4

Status: Fail

Reason for Failure or Inaccessibility: Damper blades will not close

Open Photo Closed Photo

Actuator Photo https://www.gocanvas.com/values/20319973167 https://www.gocanvas.com/values/20319973167 https://www.gocanvas.com/values/20319973168 https://www.gocanvas.com/values/20319973168 https://www.gocanvas.com/values/20319973169 https://www.gocanvas.com/values/20319973169

908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519

Location Description: Inside office C4324 back left-hand corner above key box

Tag: 4-FSD-C4324-4

Type: Combination

Floor: 4

Status: Fail

Reason for Failure or Inaccessibility: Damper found in the closed position

Open Photo Closed Photo Actuator Photo

Location Description: Inside office number C4325 right hand back corner above desk

Tag: 4-FSD-C4325-5

Type: Combination

Floor: 4

Status: Pass

Open Photo Closed Photo https://www.gocanvas.com/values/20319973242 https://www.gocanvas.com/values/20319973242 https://www.gocanvas.com/values/20319973243 https://www.gocanvas.com/values/20319973243 https://www.gocanvas.com/values/20319973244 https://www.gocanvas.com/values/20319973244 https://www.gocanvas.com/values/20319973343 https://www.gocanvas.com/values/20319973343 https://www.gocanvas.com/values/20319973345 https://www.gocanvas.com/values/20319973345

908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519

Location Description: Inside office C4333 back left-hand corner above the key box

Tag: 4-FSD-C4333-13

Type: Combination

Floor: 4

Status: Pass

Open Photo Closed Photo

Location Description: Go through EMS headquarters door number C4332 Tag: 4-FSD-C4342-12 Type: Combination Floor: 4

Status: Pass

Open Photo Closed Photo https://www.gocanvas.com/values/20323997618 https://www.gocanvas.com/values/20323997618 https://www.gocanvas.com/values/20323997619 https://www.gocanvas.com/values/20323997619 https://www.gocanvas.com/values/20323997708 https://www.gocanvas.com/values/20323997708 https://www.gocanvas.com/values/20323997710 https://www.gocanvas.com/values/20323997710

908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519

Location Description: Outside room number C 4353 directly above the door

Tag: 4-FSD-C4353-6

Type: Combination

Floor: 4

Status: Pass

Open Photo Closed Photo

Location Description: Outside office number C 4357 directly above the door

Tag: 4-FSD-C4357-7

Type: Combination

Floor: 4

Status: Fail

Reason for Failure or Inaccessibility: Actuator has power but switch is not connected

Open Photo Closed Photo Actuator Photo https://www.gocanvas.com/values/20323997844 https://www.gocanvas.com/values/20323997844 https://www.gocanvas.com/values/20323997846 https://www.gocanvas.com/values/20323997846 https://www.gocanvas.com/values/20323997980 https://www.gocanvas.com/values/20323997980 https://www.gocanvas.com/values/20323997982 https://www.gocanvas.com/values/20323997982 https://www.gocanvas.com/values/20323997984 https://www.gocanvas.com/values/20323997984

908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519

Location Description: Inside office number C 4357 left-hand corner above key box

Tag: 4-FSD-C4357-8

Type: Combination

Floor: 4

Status: Pass

Open Photo Closed Photo https://www.gocanvas.com/values/20323998078 https://www.gocanvas.com/values/20323998078 https://www.gocanvas.com/values/20323998079 https://www.gocanvas.com/values/20323998079

908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519

Location Description: Inside office C 4357 right hand side front corner above key box

Tag: 4-FSD-C4357-9

Type: Combination

Floor: 4

Status: Pass

Open Photo Closed Photo https://www.gocanvas.com/values/20323998158 https://www.gocanvas.com/values/20323998158 https://www.gocanvas.com/values/20323998159 https://www.gocanvas.com/values/20323998159

908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519

Location Description: Inside office number c good 4356 left-hand corner in the back above key box

Tag: 4-FSD-C4356-10

Type: Combination

Floor: 4

Status: Pass

Open Photo Closed Photo

Location Description: Inside staff lounge C 4365 directly in front of the door

Tag: 4-FSD-C4365-11

Type: Combination

Floor: 4

Status: Pass

Open Photo Closed Photo https://www.gocanvas.com/values/20323998233 https://www.gocanvas.com/values/20323998233 https://www.gocanvas.com/values/20323998234 https://www.gocanvas.com/values/20323998234 https://www.gocanvas.com/values/20323998308 https://www.gocanvas.com/values/20323998308 https://www.gocanvas.com/values/20323998309 https://www.gocanvas.com/values/20323998309

908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519

Location Description: Outside office C 4373

Tag: 4-FSD-C4373-1

Type: Combination

Floor: 4

Status: Fail

Reason for Failure or Inaccessibility: Inoperable actuator

Open Photo Closed Photo Actuator Photo

Location Description: To the right-hand side of office C 4373 outside of the door above the key box labeled three

Tag: 4-FSD-C4373-3

Type: Combination

Floor: 4

Status: Fail

Reason for Failure or Inaccessibility: Inoperable actuator

Open Photo Closed Photo Actuator Photo https://www.gocanvas.com/values/20323998383 https://www.gocanvas.com/values/20323998383 https://www.gocanvas.com/values/20323998384 https://www.gocanvas.com/values/20323998384 https://www.gocanvas.com/values/20323998385 https://www.gocanvas.com/values/20323998385 https://www.gocanvas.com/values/20323998458 https://www.gocanvas.com/values/20323998458 https://www.gocanvas.com/values/20323998459 https://www.gocanvas.com/values/20323998459 https://www.gocanvas.com/values/20323998460 https://www.gocanvas.com/values/20323998460

908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519

Location Description: Inside office C4373 right hand side through the doorway to the right again above the key box label two

Tag: 4-FSD-C4373-2

Type: Combination

Floor: 4

Status: Fail

Reason for Failure or Inaccessibility: Damper blades will not close

Open Photo Closed Photo Actuator Photo

Location Description: Outside office C 4377 in the hallway by the bulkhead above key box labeled five

Tag: 4-FSD-C4377-5

Type: Combination

Floor: 4

Status: Pass

Open Photo Closed Photo https://www.gocanvas.com/values/20323998549 https://www.gocanvas.com/values/20323998549 https://www.gocanvas.com/values/20323998550 https://www.gocanvas.com/values/20323998550 https://www.gocanvas.com/values/20323998551 https://www.gocanvas.com/values/20323998551 https://www.gocanvas.com/values/20323998624 https://www.gocanvas.com/values/20323998624 https://www.gocanvas.com/values/20323998625 https://www.gocanvas.com/values/20323998625

908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519

Location Description: Inside office C 4381 directly in front of the door above key box on the wall labeled six

Tag: 4-FSD-C4381-6

Type: Combination

Floor: 4

Status: Pass

Open Photo Closed Photo https://www.gocanvas.com/values/20323998749 https://www.gocanvas.com/values/20323998749 https://www.gocanvas.com/values/20323998751 https://www.gocanvas.com/values/20323998751

908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519

Location Description: Inside office C 4405 directly by door

Tag: 4-FSD-C4405-7

Type: Combination

Floor: 4

Status: Pass

Open Photo Closed Photo

Location Description: Inside office C 4405 right hand back corner

Tag: 4-FSD-C4405-8

Type: Combination

Floor: 4

Status: Pass

Open Photo Closed Photo https://www.gocanvas.com/values/20323998907 https://www.gocanvas.com/values/20323998907 https://www.gocanvas.com/values/20323998910 https://www.gocanvas.com/values/20323998910 https://www.gocanvas.com/values/20323999066 https://www.gocanvas.com/values/20323999066 https://www.gocanvas.com/values/20323999068 https://www.gocanvas.com/values/20323999068

908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519

Location Description: Inside of C4400 above door

Tag: 4-FSD-C4400-10

Type: Combination

Floor: 4

Status: Fail

Reason for Failure or Inaccessibility: Inoperable actuator

Open Photo Closed Photo Actuator Photo

Location Description: Outside office C 4394 directly above the door

Tag: 4-FSD-C4394-11

Type: Combination

Floor: 4

Status: Fail

Reason for Failure or Inaccessibility: Damper found in closed position

Open Photo Closed Photo Actuator Photo https://www.gocanvas.com/values/20323999241 https://www.gocanvas.com/values/20323999241 https://www.gocanvas.com/values/20323999243 https://www.gocanvas.com/values/20323999243 https://www.gocanvas.com/values/20323999245 https://www.gocanvas.com/values/20323999245 https://www.gocanvas.com/values/20323999400 https://www.gocanvas.com/values/20323999400 https://www.gocanvas.com/values/20323999403 https://www.gocanvas.com/values/20323999403 https://www.gocanvas.com/values/20323999405 https://www.gocanvas.com/values/20323999405

908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519

Location Description: Inside office number C 4395 I’ll be against the left-hand side of the wall

Tag: 4-FSD-C4395-12

Type: Combination

Floor: 4

Status: Fail

Reason for Failure or Inaccessibility: Inoperable actuator

Open Photo Closed Photo Actuator Photo

Location Description: Inside men’s restroom C 3307 in front of the toilet stall door drywall hatch key box

Tag: 3-FSD-C3307-1

Type: Combination

Floor: 3

Status: Pass

Open Photo Closed Photo https://www.gocanvas.com/values/20323999478 https://www.gocanvas.com/values/20323999478 https://www.gocanvas.com/values/20323999479 https://www.gocanvas.com/values/20323999479 https://www.gocanvas.com/values/20323999480 https://www.gocanvas.com/values/20323999480 https://www.gocanvas.com/values/20323999558 https://www.gocanvas.com/values/20323999558 https://www.gocanvas.com/values/20323999559 https://www.gocanvas.com/values/20323999559

908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519

Location Description: Inside women’s restroom C 3309 to left-hand side of the door

Tag: 3-FSD-C3309-4

Type: Combination

Floor: 3

Status: Non-Accessible

Reason for Failure or Inaccessibility: No access door, access door install not authorized

Open Photo Closed Photo https://www.gocanvas.com/values/20323999633 https://www.gocanvas.com/values/20323999633 https://www.gocanvas.com/values/20323999634 https://www.gocanvas.com/values/20323999634

908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519

Location Description: Inside women’s restroom C 3309 to the left-hand side front corner drywall hatches right there above the mirror

Tag: 3-FSD-C3309-2

Type: Combination

Floor: 3

Status: Non-Accessible

Reason for Failure or Inaccessibility: No access door, access door install not authorized

Open Photo

Closed Photo https://www.gocanvas.com/values/20323999708 https://www.gocanvas.com/values/20323999708 https://www.gocanvas.com/values/20323999709 https://www.gocanvas.com/values/20323999709

908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519

Location Description: Inside men’s restroom C 3307 right hand corner wall above urinal

Tag: 3-FSD-C3309-3

Type: Combination

Floor: 3

Status: Pass

Open Photo Closed Photo https://www.gocanvas.com/values/20323999783 https://www.gocanvas.com/values/20323999783 https://www.gocanvas.com/values/20323999784 https://www.gocanvas.com/values/20323999784

908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519

Location Description: Inside office C 3313 directly in front of the door above the key box on the wall label five

Tag: 3-FSD-C3313-5

Type: Combination

Floor: 3

Status: Non-Accessible

Reason for Failure or Inaccessibility: No access door, access door install not authorized

Open Photo Closed Photo https://www.gocanvas.com/values/20323999858 https://www.gocanvas.com/values/20323999858 https://www.gocanvas.com/values/20323999859 https://www.gocanvas.com/values/20323999859

908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519

Location Description: Directly above reception desk C3293

Tag: 3-FSD-C3293-6

Type: Combination

Floor: 3

Status: Fail

Reason for Failure or Inaccessibility: Damper found in closed position

Open Photo Closed Photo Actuator Photo https://www.gocanvas.com/values/20323999933 https://www.gocanvas.com/values/20323999933 https://www.gocanvas.com/values/20323999934…