Bldg Sprinkler Inspections.pdf

PDF 1008 KB Posted

Attached to
H212--Fire Protection Testing, Inspection, and Maintenance/Repair
Solicitation number
36C26126Q0018
Issued by

About this file

These documents are annual inspection reports for automatic sprinkler systems at the VA Sierra Nevada Health Care System, located at 975 Kirman Avenue in Reno, Nevada. The reports, completed by inspector Will Headley (and occasionally Dorothy Kunde) between October and December 2019, document detailed inspections of wet pipe sprinkler systems across multiple buildings (Buildings 1, 1A, 5, 6, 10, 12, and 1D/4).

The standardized NFPA (National Fire Protection Association) Form 6 inspection reports systematically assess various components including gauges, control valves, alarm valves, fire department connections, pressure reducing valves, sprinklers, and pipes. Each building's report indicates routine maintenance checks were completed, with most inspections finding no significant issues. A few notable comments include a leaky fire water riser drain line in one building, multiple escutcheons being adjusted, two dusty sprinkler heads being cleaned, and some main drain test results showing variations that were determined not to indicate systemic problems.

View the file

Other files

File Type Posted
36C26126Q0018 0002.docx DOCX document
Floor Plans - Fire and Smoke Dampers - Working.pdf PDF
Reno VAMC-Building 1 Section C - Damper Inspection Report 2024.pdf PDF
975 Kirman Pre action 5 yr 7-20.pdf PDF
ANNUAL FWP 231130.pdf PDF
Semi-annual FM200 4-28-2025.pdf PDF
Reno VAMC-Area G - Damper Inspection Report 2025.pdf PDF
975 Kirman Ave. Reno Nv FSD 1.30.24.pdf PDF
VA Bldg. 12 Preaction 10-22-2024.pdf PDF
Reno VAMC-Building 1D - Damper Inspection Report 2025.pdf PDF
Semi-annual Ansul Testing Canteen 05-15-24.pdf PDF
QTRLY flow and tamper blank document.xlsx XLSX spreadsheet
Area D Fire Damper Inspection.xlsx XLSX spreadsheet
Semi-annual Ansul Testing NFS 05-15-24.pdf PDF
VA Bldg. 12 Preaction 1-6-2025.pdf PDF
36C26126Q0018 0001.docx DOCX document
2- Floor Plans - Fire and Smoke Dampers Bldg 1 1A 1D 5 6 10 12.pdf PDF
VA Bldg. 12 Preaction 4-28-2025.pdf PDF
Reno VAMC-Building 5 Section K - Damper Inspection Report 2024.pdf PDF
Attachment 1 - Drawings.pdf PDF
Reno VAMC-Building 12 - Damper Inspection Report 2025.pdf PDF
Reno VAMC-Building 6 - Damper Inspection Report 2025.pdf PDF
VA FSD Inspection Bldg 10 FD 5B-Fail 5.9.24.pdf PDF
Semi-annual FM200 10-22-2024.pdf PDF
Site Visit Information.docx DOCX document
36C26126Q0018.docx DOCX document
Show all 26

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Inspector: Will Headley

Contract No.: Builind lA

Property Name: VA Sierra Nevada Health Care System

Property Address: 975 Kirman Avenue, Reno NV. 89502

Form 6

Automatic Sprinkler Systems Inspection, Testing, and Maintenance of Wet Pipe Sprinkler Systems

Phone Number: 775-784-3957 Date: 3/27/2020

Inspections Monthly

Ej Yes 0 No 0 N/A Gauges—normal water pressure maintained

Control Valves

El Yes 0 No 0 N/A In the correct (open or closed) position

El Yes 0 No 0 N/A Sealed, locked, or supervised

El Yes ID No 1=1 N/A Accessible

El Yes 0 No 1=1 N/A Free from damage or leaks

El Yes 1=1 No 1=1 N/A Proper signage

Alarm Valves

El Yes 1=1 No 0 N/A Free of damage

El Yes 1=1 No 0 N/A Accessible

El Yes 1=1 No 1=1 N/A Retard chamber/alarm drains not leaking

Quarterly

El Yes 1=1 No 1=1 N/A Alarm devices—free of damage

Z Yes 0 No 1=1 N/A Hydraulic data nameplate—securely attached to riser/legible

Fire Department Connections

El Yes 0 No 0 N/A Visible and accessible

El Yes 1=1 No El N/A Coupling/swivels operate correctly

E Yes 1=1 No I=1 N/A Plugs/caps are in place

El Yes 0 No I=1 N/A Gaskets are not damaged

El Yes 0 No 1=1 N/A Identification signs are in place

Z Yes 1=1 No 1=1 N/A Ball drip valve is functional

Pressure Reducing Valve

El Yes 1=1 No 0 N/A In the open position/not leaking

Z Yes 1=1 No 1=1 N/A Maintaining downstream pressure

NFPA° NFPA Water-Based Fire Protection Systems Forms 1 of 3

This Report Covers: El Monthly 1=1 Quarterly Annual

Three-Year 1=1 Five-Year

Form 6

El Yes

Annual

0 No 0 N/A In good condition

Sprinklers (visible)

El Yes 11 No 0 N/A No damage or leaks

El Yes 11 No 11 N/A Free of corrosion, foreign material, or paint

El Yes 0 No 11 N/A Installed in proper orientation

0 Yes 11 No 11 N/A Fluid in glass bulbs

LEI Yes E No 11 N/A Spare sprinklers—proper number and type. Complete with wrench?

El Yes 11 No 11 N/A Hangers and seismic bracing—not damaged or loose

Pipes and Fittings (visible)

El Yes 11 No 11 N/A In good condition/no external corrosion

ISI Yes 11 No 0 N/A No leaks or mechanical damage

[El Yes 0 No 11 N/A Correct alignment—no external loads

CI Yes 11 No Z N/A Hose racks—inspected per NFPA 1962

CI Yes 0 No Z N/A Building—wet piping not exposed to freezing temperatures

Five-Year

El Yes El No 11 N/A Alarm valve interior including strainers, filters, and restriction orifice

El Yes 11 No 0 N/A Check valve—internal moves freely, in good condition

IZ Yes 11 No 11 N/A Obstruction inspection—no foreign or obstructing material found

Test

CI Yes 11 No El N/A Alarm devices—water motor gong

CI Yes 0 No El N/A Main drain test—if the sole supply is through a backflow preventer

Static psi Residual psi

CI Yes 11 No Z N/A Do results differ by more than 10% from previous test?

Semi-annual

Z Yes 11 No 0 N/A Supervisory switch functions

Z Yes 11 No 0 N/A Alarm devices—inspectors test or bypass opened/obstructed waterflow

Annual

Z Yes Ei No 0 N/A Main drain test Static 171 Residual 130

CI Yes Z No 11 N/A Do results differ by more than 10% from previous test?

Z Yes CI No 0 N/A All control valves operated through full range of motion and returned to normal position.

El Yes 11 No 0 N/A Specific gravity or anti-freeze system (if present)

Z Yes 11 No El N/A Backflow preventer—test

El Yes 0 No 11 N/A Backflow preventer—flow test

NFPX NFPA Water-Based Fire Protection Systems Forms 2 of 3

Three-Year

El Yes 1=1 No

Five-Year

El Yes U No

LI Yes LI No

[s] N/A Hose has been tested in accordance with NFPA 1962

N/A Gauges tested or replaced

El N/A Pressure reducing valve—flow test and comparable to previous results

Routine Maintenance

El Yes 0 No 0 N/A Sprinklers tested or replaced per appropriate testing schedule

Comments

5 year gauge replacement completed 9/28/2018. Referenced for annual main drain comparisons.

Signature:

Date:

License/Certification No.:

NFPA Water-Based Fire Protection Systems Forms 3 of 3

Automatic Sprinkler Systems Inspection, Testing, and Maintenance of Wet Pipe Sprinkler Systems

Property Name: VA Sierra Nevada Health Care System

Property Address: 975 Kirman Avenue, Reno NV. 89502

Phone Number: 775-784-3957

Inspector: Will Headley

Contract No.: Building 1

Date: 10/21-22/2019

This Report Covers: El Monthly Li Quarterly Annual

0 Three-Year Li Five-Year

Inspections Monthly

Yes

Yes

Ei Yes

Yes

Yes

El Yes

0 No

0 No

0 No

0 No

1=1 No

0 No

N/A

0 N/A

0 N/A

0 N/A

0 N/A

0 N/A

Gauges—normal water pressure maintained

Control Valves

In the correct (open or closed) position

Sealed, locked, or supervised

Accessible

Free from damage or leaks

Proper signage

Alarm Valves

Z Yes El No Cl N/A Free of damage

Z Yes El No CI N/A Accessible

Z Yes 1:1 No CI N/A Retard chamber/alarm drains not leaking

El Yes El No 0 N/A Alarm devices—free of damage

Z Yes 1:1 No CI N/A Hydraulic data nameplate—securely attached to riser/legible

Z Yes ID No 1:1 N/A Visible and accessible

0 Yes 0 No CI N/A Coupling/swivels operate correctly

Z Yes 1=1 No EI N/A Plugs/caps are in place

Z Yes CI No 1=1 N/A Gaskets are not damaged

Z Yes 1:1 No ID N/A Identification signs are in place

Z Yes ID No El N/A Ball drip valve is functional

Yes CI No CI N/A In the open position/not leaking

Yes 1=1 No CI N/A Maintaining downstream pressure

NFAV NFPA Water-Based Fire Protection Systems Forms

1 o13

IZI Yes 0 No 0 N/A In good condition •

Sprinklers (visible)

Z Yes 1=1 No 1=1 N/A No damage or leaks

El Yes 1=1 No 1=1 N/A Free of corrosion, foreign material, or paint

Z Yes I=1 No 1=1 N/A Installed in proper orientation

Z Yes 1=1 No ID N/A Fluid in glass bulbs

El Yes El No 1=1 N/A Spare sprinklers—proper number and type. Complete with wrench?

El Yes El No 1=I N/A Hangers and seismic bracing—not damaged or loose

El Yes lj No 1=1 N/A In good condition/no external corrosion

El Yes 1=1 No ID N/A No leaks or mechanical damage

El Yes ID No 1=1 N/A Correct alignment—no external loads

1=1 Yes 1=1 No liEl N/A Hose racks—inspected per NFPA 1962

Z Yes El No I=1 N/A Building—wet piping not exposed to freezing temperatures

El Yes El No 1=1 N/A Alarm valve interior including strainers, filters, and restriction orifice

El Yes El No 1=1 N/A Check valve—internal moves freely, in good condition

El Yes 1=1 No 1=1 N/A Obstruction inspection—no foreign or obstructing material found

1=1 Yes El No Z N/A Alarm devices—water motor gong

1=1 Yes 1=1 No Z N/A Main drain test—if the sole supply is through a backflow preventer

El Yes El No Z N/A Do results differ by more than 10% from previous test?

El Yes El No El N/A Supervisory switch functions

El Yes I=1 No 1=1 N/A Alarm devices—inspectors test or bypass opened/obstructed waterflow

Z Yes El No I:I N/A Main drain test Static 174 Residual 150

0 Yes El No 11 N/A Do results differ by more than 10% from previous test?

El Yes 1=1 No 1=1 N/A All control valves operated through full range of motion and returned to normal position.

Z Yes 1=1 No 1=1 N/A Specific gravity or anti-freeze system (if present)

El Yes El No 1=1 N/A Backflow preventer—test

Z Yes 1=1 No 1=1 N/A Backflow preventer—flow test rn 0.11 NFPA NFPA Water-Based Fire Protection Systems Forms 2 of 3

Form 6

Three-Year

Yes No El N/A Hose has been tested in accordance with NFPA 1962

El Yes El No El N/A Gauges tested or replaced

Yes No E N/A Pressure reducing valve—flow test and comparable to previous results

Routine Maintenance

El Yes 0 No 0 N/A Sprinklers tested or replaced per appropriate testing schedule

Comments

Leaky Fire Water Riser Drain Line North Stairwell (P190918-002).

Date: 7

WPM NFPA Water-Based Fire Protection Systems Forms 3 of 3

Property Name: Inspector: Will Headley VA Sierra Nevada Health Care System

Contract No.: Building 1D/4

Date: 12/15, 16/2019

Property Address: 975 Kirman Avenue, Reno NV. 89502

Phone Number: 775-784-3957

Annual Quarterly

Five-Year

O Monthly

1:1 Three-Year

This Report Covers:

Inspections

Monthly

Form 6

Automatic Sprinkler Systems Inspection, Testing, and Maintenance of Wet Pipe Sprinkler Systems

El Yes 0 No 0 N/A Gauges—normal water pressure maintained

[ZI Yes D No 0 N/A In the correct (open or closed) position

IZ Yes 0 No 0 N/A Sealed, locked, or supervised

[Z Yes 0 No 0 N/A Accessible

El Yes 0 No 0 N/A Free from damage or leaks

El Yes 0 No 0 N/A Proper signage lEl Yes 0 No 0 N/A Free of damage

El Yes 0 No 0 N/A Accessible

El Yes 0 No 0 N/A Retard chamber/alarm drains not leaking

El Yes 0 No 0 N/A Alarm devices—free of damage

El Yes El No 0 N/A Hydraulic data nameplate—securely attached to riser/legible

El Yes 0 No 0 N/A Visible and accessible

El Yes 0 No 0 N/A Coupling/swivels operate correctly

El Yes 0 No 0 N/A Plugs/caps are in place

El Yes 0 No 0 N/A Gaskets are not damaged

El Yes 0 No 0 N/A Identification signs are in place

El Yes 0 No 0 N/A Ball drip valve is functional

El Yes 0 No 0 N/A In the open position/not leaking

El Yes 0 No 0 N/A Maintaining downstream pressure

WPAz NFPA Water-Based Fire Protection Systems Forms 1 of 3

E Yes 0 No 0 N/A In good condition

1:31 Yes 1=1 No I=1 N/A No damage or leaks

E Yes 1=1 No 1=1 N/A Free of corrosion, foreign material, or paint

El Yes 1=I No I=1 N/A Installed in proper orientation

[Z] Yes I=1 No I:I N/A Fluid in glass bulbs

[Z] Yes I:I No El N/A Spare sprinklers—proper number and type. Complete with wrench?

El Yes I=1 No ID N/A Hangers and seismic bracing—not damaged or loose

El Yes 1=1 No El N/A In good condition/no external corrosion

El Yes 1=1 No El N/A No leaks or mechanical damage

El Yes 1=1 No 1=1 N/A Correct alignment—no external loads

I=1 Yes 1=1 No IZI N/A Hose racks—inspected per NFPA 1962 l=I Yes ID No [Z] N/A Building—wet piping not exposed to freezing temperatures

El Yes 1=I No El N/A Alarm valve interior including strainers, filters, and restriction orifice

El Yes El No 1=1 N/A Check valve—internal moves freely, in good condition

[ZI Yes I=1 No 1=1 N/A Obstruction inspection—no foreign or obstructing material found

0 Yes El No El N/A Alarm devices—water motor gong

ID Yes 1:1 No [S] N/A Main drain test—if the sole supply is through a backflow preventer

I=1 Yes El No El N/A Do results differ by more than 10% from previous test?

El Yes El No LI N/A Supervisory switch functions

El Yes El No El N/A Alarm devices—inspectors test or bypass opened/obstructed waterflow

El Yes El No I=1 N/A Main drain test Static 179 Residual 165

0 Yes El No I:I N/A Do results differ by more than 10% from previous test?

Z Yes I=1 No I=1 N/A All control valves operated through full range of motion and returned to normal position.

IZI Yes ID No 1=1 N/A Specific gravity or anti-freeze system (if present)

Z Yes 1=1 No I=1 N/A Backflow preventer—test

El Yes El No 1=1 N/A Backflow preventer—flow test

NFPX NFPA Water-Based Fire Protection Systems Forms 2 of 3

Form 6

Three-Year

El Yes El No Z N/A Hose has been tested in accordance with NFPA 1962

Z Yes El No El N/A Gauges tested or replaced

El Yes 1:1 No Z N/A Pressure reducing valve—flow test and comparable to previous results

Routine Maintenance

EI Yes 0 No 0 N/A Sprinklers tested or replaced per appropriate testing schedule

Comments

Multiple escutcheons were adjusted on the spot. Two dusty heads were cleaned on the spot.

[71) NFPX NFPA Water-Based Fire Protection Systems Forms 3 of 3

Inspector: Will Headley

Contract No.: Building 10

Property Name: VA Sierra Nevada Health Care System

Property Address: 975 Kirman Avenue, Reno NV. 89502

Phone Number: 775-784-3957 Date: 12/18/2019

Annual This Report Covers:

Inspections Monthly

1=1 Monthly 0 Quarterly

0 Three-Year 0 Five-Year

Form 6

Automatic Sprinkler Systems Inspection, Testing, and Maintenance of Wet Pipe Sprinkler Systems

E Yes 0 No 0 N/A Gauges—normal water pressure maintained

Yes 0 No 0 N/A In the correct (open or closed) position

Yes 0 No 0 N/A Sealed, locked, or supervised

Yes 0 No U N/A Accessible

Yes 0 No LI N/A Free from damage or leaks

Yes U No 0 N/A Proper signage

El Yes 0 No 0 N/A Free of damage

El Yes 0 No 0 N/A Accessible

Yes 0 No 0 N/A Retard chamber/alarm drains not leaking

Yes No 0 N/A Alarm devices—free of damage

El Yes No 0 N/A Hydraulic data nameplate—securely attached to riser/legible

Yes No 0 N/A Visible and accessible

Yes No 0 N/A Coupling/swivels operate correctly

Yes No U N/A Plugs/caps are in place

El Yes No 0 N/A Gaskets are not damaged

Yes No 0 N/A Identification signs are in place

Yes No 1=1 N/A Ball drip valve is functional

Yes No 0 N/A In the open position/not leaking

Yes No 0 N/A Maintaining downstream pressure

NEPA' NFPA Water-Based Fire Protection Systems Forms 1 of 3 lE1 Yes

Annual

0 No 0 N/A In good condition

Sprinklers (visible)

IZ1 Yes 1=1 No I=1 N/A No damage or leaks

Z Yes 11 No 11 N/A Free of corrosion, foreign material, or paint

Z Yes El No I=1 N/A Installed in proper orientation

Z Yes 1=1 No 0 N/A Fluid in glass bulbs

El Yes 1:1 No El N/A Spare sprinklers—proper number and type. Complete with wrench?

EZ1 Yes El No El N/A Hangers and seismic bracing—not damaged or loose

El Yes El No ID N/A In good condition/no external corrosion

El Yes 1=1 No El N/A No leaks or mechanical damage

Z Yes El No El N/A Correct alignment—no external loads

I=1 Yes El No El N/A Hose racks—inspected per NFPA 1962

1=1 Yes 1=1 No Z N/A Building—wet piping not exposed to freezing temperatures

[ZI Yes 1=1 No 1=1 N/A Alarm valve interior including strainers, filters, and restriction orifice

[ZI Yes I=1 No I=1 N/A Check valve—internal moves freely, in good condition

Z Yes 1=1 No 1=1 N/A Obstruction inspection—no foreign or obstructing material found

LI Yes LI No El N/A Alarm devices—water motor gong

1=I Yes ID No Z N/A Main drain test—if the sole supply is through a backflow preventer

El Yes El No El N/A Do results differ by more than 10% from previous test?

El Yes I=1 No El N/A Supervisory switch functions

El Yes 1:1 No I=1 N/A Alarm devices—inspectors test or bypass opened/obstructed waterflow

[E] Yes ID No 0 N/A Main drain test Static 172 Residual 100

Z Yes El No 1:1 N/A Do results differ by more than 10% from previous test?

El Yes I=1 No 1=1 N/A All control valves operated through full range of motion and returned to normal position.

El Yes El No 1=1 N/A Specific gravity or anti-freeze system (if present)

El Yes I=1 No I=1 N/A Backflow preventer—test

Z Yes 1=1 No El N/A Backflow preventer—flow test

Date: / Signature:

Form 6

Three-Year

LI Yes LI No N/A Hose has been tested in accordance with NFPA 1962

Five-Year

P Yes I=1 No N/A Gauges tested or replaced

1=I Yes El No El N/A Pressure reducing valve—flow test and comparable to previous results

Routine Maintenance

El Yes p No 0 N/A Sprinklers tested or replaced per appropriate testing schedule

Comments

Additional connbustable load (filter storage) was accepted by Safety in L1885.

Main Drain results differerred by >10%. Piping alignment was verified. No negative findings identified.

Lo..1 pew NFPA Water-Based Fire Protection Systems Forms 3 of 3 •

Inspection, Testing, and Maintenance of Wet Pipe Sprinkler Systems

Property Name: VA Sierra Nevada Health Care System

Property Address: 975 Kirman Avenue, Reno NV. 89502

Phone Number: 775-784-3957

Inspector: Will Headley

Contract No.: Building 12

Date: 12/20, 23, 24/2019

This Report Covers: D Monthly

Three-Year

Quarterly

Five-Year

Annual

Inspections Monthly

El Yes 0 No 0 N/A Gauges—normal water pressure maintained

Control Valves

El Yes 0 No 0 N/A In the correct (open or closed) position

El Yes 0 No 0 N/A Sealed, locked, or supervised

• Yes D No 1:1 N/A Accessible

• Yes U No 0 N/A Free from damage or leaks

• Yes D No 0 N/A Proper signage

El Yes D No 0 N/A

El Yes ID No 0 N/A

Z Yes 0 No 0 N/A

Quarterly

Z Yes D No DI N/A

El Yes 0 No 0 N/A

El Yes D No 0 N/A

[2] Yes 0 No 0 N/A

El Yes 0 No 0 N/A

El Yes 0 No 0 N/A

El Yes LI No 0 N/A

IZI Yes D No D N/A

Alarm Valves

Free of damage

Accessible

Retard chamber/alarm drains not leaking

Alarm devices—free of damage

Hydraulic data nameplate—securely attached to riser/legible

Fire Department Connections

Visible and accessible

Coupling/swivels operate correctly

Plugs/caps are in place

Gaskets are not damaged

Identification signs are in place

Ball drip valve is functional

Pressure Reducing Valve

• Yes 0 No 0 N/A In the open position/not leaking

• Yes U No D N/A Maintaining downstream pressure fl NFPR NFPA Water-Based Fire Protection Systems Forms 1 of 3

Ei Yes 0 No 0 N/A In good condition

El Yes I=1 No 1=I N/A No damage or leaks

Z Yes El No 1=I N/A Free of corrosion, foreign material, or paint

El Yes DI No I=1 N/A Installed in proper orientation

El Yes El No El N/A Fluid in glass bulbs

Z Yes 1=I No El N/A Spare sprinklers—proper number and type. Complete with wrench?

El Yes 11 No I=1 N/A Hangers and seismic bracing—not damaged or loose

El Yes El No I=1 N/A In good condition/no external corrosion

E Yes ID No I=1 N/A No leaks or mechanical damage

Z Yes 1:1 No I=1 N/A Correct alignment—no external loads

El Yes ID No Z N/A Hose racks—inspected per NFPA 1962

1:1 Yes I=1 No Z N/A Building—wet piping not exposed to freezing temperatures

Z Yes IEI No El N/A Alarm valve interior including strainers, filters, and restriction orifice

El Yes lj No El N/A Check valve—internal moves freely, in good condition

El Yes 1=I No El N/A Obstruction inspection—no foreign or obstructing material found

0 Yes El No El N/A Alarm devices—water motor gong

0 Yes I=1 No El N/A Main drain test—if the sole supply is through a backflow preventer

El Yes El No El N/A Do results differ by more than 10% from previous test?

El Yes ID No I=1 N/A Supervisory switch functions

Z Yes I=1 No El N/A Alarm devices—inspectors test or bypass opened/obstructed waterflow

El Yes 0 No 0 N/A Main drain test Static 182 Residual 150

0 Yes El No I=1 N/A Do results differ by more than 10% from previous test?

Z Yes I=1 No El N/A All control valves operated through full range of motion and returned to normal position.

Z Yes ID No 1:1 N/A Specific gravity or anti-freeze system (if present)

El Yes 11 No El N/A Backflow preventer—test

El Yes 1=1 No I=1 N/A Backflow preventer—flow test

CnO NPPAz NFPA Water-Based Fire Protection Systems Forms 2 of 3

Form 6

Three-Year

1:1 Yes I= No N/A Hose has been tested in accordance with NFPA 1962

LI Yes Ei No N/A Gauges tested or replaced

LI Yes 1:1 No Z N/A Pressure reducing valve—flow test and comparable to previous results

Routine Maintenance

[3] Yes 0 No 0 N/A Sprinklers tested or replaced per appropriate testing schedule

Comments

NFPA Water-Based Fire Protection Systems Forms 3 of 3

No N/A

0 No

No

No

No

No

N/A

N/A

N/A

N/A

N/A

No N/A

UI No N/A

No N/A

Form 6

Automatic Sprinkler Systems Inspection, Testing, and Maintenance of Wet Pipe Sprinkler Systems

Property Name: VA Sierra Nevada Health Care System

Property Address: 975 Kirman Avenue, Reno NV. 89502

Phone Number: 775-784-3957

Inspector: Will Headley

Contract No.: Building 5

Date: 10/9/2019

This Report Covers: El Monthly Quarterly 1E1 Annual

0 Three-Year Five-Year

Inspections Monthly

1E1 Yes

• Yes

IZ Yes

[Fl Yes

• Yes

• Yes

• Yes

El Yes

Yes

Quarterly

El Yes

• Yes

▪ Yes

• Yes

El Yes

El Yes

• Yes

• Yes

El Yes

▪ Yes

Gauges—normal water pressure maintained

Control Valves

In the correct (open or closed) position

Sealed, locked, or supervised

Accessible

Free from damage or leaks

Proper signage

Alarm Valves

Free of damage

Accessible

Retard chamber/alarm drains not leaking

No I=1 N/A Alarm devices—free of damage

No 0 N/A Hydraulic data nameplate—securely attached to riser/legible

Fire Department Connections

No 0 N/A Visible and accessible

No 0 N/A Coupling/swivels operate correctly

No 0 N/A Plugs/caps are in place

No 0 N/A Gaskets are not damaged

No 0 N/A Identification signs are in place

No 0 N/A Ball drip valve is functional

Pressure Reducing Valve

No 1=1 N/A In the open position/not leaking

No U N/A Maintaining downstream pressure

NFPX NFPA Water-Based Fire Protection Systems Forms

1=1

E

UI

1=1

E Yes 0 No 0 N/A In good condition

El Yes El No 1=1 N/A No damage or leaks

El Yes 1:1 No IEI N/A Free of corrosion, foreign material, or paint

El Yes El No ID N/A Installed in proper orientation

El Yes 1=1 No IEI N/A Fluid in glass bulbs

1:1 Yes El No ID N/A Spare sprinklers—proper number and type. Complete with wrench?

El Yes IEI No El N/A Hangers and seismic bracing—not damaged or loose

El Yes LI No 1=1 N/A In good condition/no external corrosion

El Yes I=1 No I=1 N/A No leaks or mechanical damage

El Yes I=1 No 1=1 N/A Correct alignment—no external loads

El Yes 1=1 No El N/A Hose racks—inspected per NFPA 1962

0 Yes El No El N/A Building—wet piping not exposed to freezing temperatures

El Yes 1=1 No El N/A Alarm valve interior including strainers, filters, and restriction orifice

El Yes El No ID N/A Check valve—internal moves freely, in good condition

El Yes El No 1=1 N/A Obstruction inspection—no foreign or obstructing material found

El Yes El No El N/A Alarm devices—water motor gong

1:1 Yes IEI No El N/A Main drain test—if the sole supply is through a backflow preventer

I=1 Yes El No El N/A Do results differ by more than 10% from previous test?

E Yes IEI No 1=1 N/A Supervisory switch functions

E Yes El No El N/A Alarm devices—inspectors test or bypass opened/obstructed waterflow

El Yes 11 No El N/A Main drain test Static 176 Residual 120

0 Yes 11 No E N/A Do results differ by more than 10% from previous test?

El Yes 1=1 No IEI N/A All control valves operated through full range of motion and returned to normal position.

Igl Yes El No 1=1 N/A Specific gravity or anti-freeze system (if present)

El Yes 1=1 No 1=1 N/A Backflow preventer—test

El Yes 1=1 No El N/A Backflow preventer—flow test

NFPA Water-Based Fire Protection Systems Forms 2 of 3

Three-Year

LI Yes 1=1 No N/A Hose has been tested in accordance with NFPA 1962

Five-Year

El Yes 1:1 No 1=1 N/A Gauges tested or replaced

CEI Yes 1=1 No N/A Pressure reducing valve—flow test and comparable to previous results

Routine Maintenance

El Yes 0 No 0 N/A Sprinklers tested or replaced per appropriate testing schedule

Comments

No negative findings.

Signature:

License/Certification No.:

NFPA NFPA Water-Based Fire Protection Systems Forms 3 of 3

Inspection, Testing, and Maintenance of Wet Pipe Sprinkler Systems

Property Name: VA Sierra Nevada Health Care System Inspector: Will Headley

Dorothy Kunde

Property Address:

Phone Number:

975 Kirman Avenue, Reno NV. 89502 Contract No.: Building 6

775-784-3957

Date: 10/21/2019

This Report Covers:

Inspections Monthly

LI Monthly

El Three-Year

0 Quarterly

EJ Five-Year

El Yes 0 No 0 N/A Gauges—normal water pressure maintained

IE Yes 0 No 0 N/A In the correct (open or closed) position

El Yes 0 No 0 N/A Sealed, locked, or supervised

Z Yes I=1 No 1=1 N/A Accessible

El Yes I=1 No El N/A Free from damage or leaks

El Yes I=1 No El N/A Proper signage

[ZI Yes El No El N/A Free of damage

Z Yes ID No El N/A Accessible

El Yes I=1 No 1=1 N/A Retard chamber/alarm drains not leaking

Z Yes 1=1 No 1=1 N/A Alarm devices—free of damage

El Yes ID No I=1 N/A Hydraulic data nameplate—securely attached to riser/legible

[Z1 Yes I=1 No El N/A Visible and accessible

El Yes LI No I=1 N/A Coupling/swivels operate correctly

El Yes 1=1 No I=1 N/A Plugs/caps are in place

El Yes 1=1 No I=1 N/A Gaskets are not damaged

El Yes El No 1=1 N/A Identification signs are in place

Z Yes El No I=1 N/A Ball drip valve is functional

El Yes I=1 No 1=1 N/A In the open position/not leaking

El Yes El No I=1 N/A Maintaining downstream pressure

NFPA Water-Based Fire Protection Systems Forms 1 of 3

El Yes

Annual

0 No 0 N/A In good condition

Sprinklers (visible)

El Yes ID No 1=1 N/A No damage or leaks

El Yes CI No CI N/A Free of corrosion, foreign material, or paint

El Yes CI No CI N/A Installed in proper orientation

Z Yes El No 1=1 N/A Fluid in glass bulbs

CI Yes [E] No CI N/A Spare sprinklers—proper number and type. Complete with wrench?

El Yes 1=1 No I=1 N/A Hangers and seismic bracing—not damaged or loose

El Yes 1:1 No 1=1 N/A In good condition/no external corrosion

Z Yes 1:1 No CI N/A No leaks or mechanical damage

Z Yes 1:1 No CI N/A Correct alignment—no external loads

CI Yes I=1 No El N/A Hose racks—inspected per NFPA 1962

CI Yes I=1 No E N/A Building—wet piping not exposed to freezing temperatures

El Yes 1:1 No El N/A Alarm valve interior including strainers, filters, and restriction orifice

Z Yes 1:1 No El N/A Check valve—internal moves freely, in good condition

El Yes 1:1 No El N/A Obstruction inspection—no foreign or obstructing material found

1:1 Yes 1=1 No El N/A Alarm devices—water motor gong

1:1 Yes 1=1 No El N/A Main drain test—if the sole supply is through a backflow preventer

CI Yes 1=1 No LSI N/A Do results differ by more than 10% from previous test?

El Yes CI No CI N/A Supervisory switch functions

El Yes CI No CI N/A Alarm devices—inspectors test or bypass opened/obstructed waterflow

El Yes 0 No El N/A Main drain test Static 178 Residual 120

El Yes 1:1 No El N/A Do results differ by more than 10% from previous test?

El Yes CI No CI N/A All control valves operated through full range of motion and returned to normal position.

El Yes 1:1 No CI N/A Specific gravity or anti-freeze system (if present)

El Yes 1=1 No CI N/A Backflow preventer—test

Z Yes I=1 No 1:1 N/A Backflow preventer—flow test

[7] qr:

2'7f Signature:

License/Certification No.:

Form 6

Three-Year

LI Yes LI No N/A Hose has been tested in accordance with NFPA 1962

El Yes El No EI N/A Gauges tested or replaced

LI Yes No EI N/A Pressure reducing valve—flow test and comparable to previous results

Routine Maintenance

E1 Yes 0 No 0 N/A Sprinklers tested or replaced per appropriate testing schedule

Comments

No negative findings. Although last year annual Main Drain results were greater than 10% the next quarter indicated within the 10% allowance. 2018-180/150, 2019-178/120, following quarter-175/145.

Assessment determined no change in piping conditions.

[71 tif

NFPX NFPA Water-Based Fire Protection Systems Forms 3 of 3

Page 1
Page 2
Page 3
Page 4
Page 5
Page 6
Page 7
Page 8
Page 9
Page 10
Page 11
Page 12
Page 13
Page 14
Page 15
Page 16
Page 17
Page 18
Page 19
Page 20
Page 21
Page 22
Page 23
Page 24
Page 25
Page 26
Page 27
Page 28

File details come from the government source that posted it. Updated .