ANNUAL FWP 231130.pdf

PDF 2 MB Posted

Attached to
H212--Fire Protection Testing, Inspection, and Maintenance/Repair
Solicitation number
36C26126Q0018
Issued by

About this file

This document is an electric fire pump test report for the VA Hospital in Reno, Nevada, conducted by Delta Fire Systems, Inc. on November 30, 2023. The test involved an AC Fire Pump Model 8100 (Serial # 11-060249-01-01), a HSC type pump with a Marathon electric motor, rated at 1,000 GPM, 69 PSI, and 3550 RPM. The report includes detailed annual fire pump test results for 2021, 2022, and 2023, documenting pressure readings, RPM, discharge coefficients, and individual outlet pitot readings. The test was performed using liquid-filled calibrated gauges and 2.5" hose monsters with internal pitot, following NFPA 25 2020 Edition procedures. The performance curve graph shows the pump's performance across different flow rates and pressures, with the pump appearing to perform as intended according to the inspector's notes.

View the file

Other files

File Type Posted
36C26126Q0018 0002.docx DOCX document
Floor Plans - Fire and Smoke Dampers - Working.pdf PDF
Reno VAMC-Building 1 Section C - Damper Inspection Report 2024.pdf PDF
975 Kirman Pre action 5 yr 7-20.pdf PDF
Semi-annual FM200 4-28-2025.pdf PDF
Reno VAMC-Area G - Damper Inspection Report 2025.pdf PDF
975 Kirman Ave. Reno Nv FSD 1.30.24.pdf PDF
VA Bldg. 12 Preaction 10-22-2024.pdf PDF
Reno VAMC-Building 1D - Damper Inspection Report 2025.pdf PDF
Semi-annual Ansul Testing Canteen 05-15-24.pdf PDF
QTRLY flow and tamper blank document.xlsx XLSX spreadsheet
Area D Fire Damper Inspection.xlsx XLSX spreadsheet
Semi-annual Ansul Testing NFS 05-15-24.pdf PDF
VA Bldg. 12 Preaction 1-6-2025.pdf PDF
36C26126Q0018 0001.docx DOCX document
2- Floor Plans - Fire and Smoke Dampers Bldg 1 1A 1D 5 6 10 12.pdf PDF
VA Bldg. 12 Preaction 4-28-2025.pdf PDF
Reno VAMC-Building 5 Section K - Damper Inspection Report 2024.pdf PDF
Attachment 1 - Drawings.pdf PDF
Reno VAMC-Building 12 - Damper Inspection Report 2025.pdf PDF
Bldg Sprinkler Inspections.pdf PDF
Reno VAMC-Building 6 - Damper Inspection Report 2025.pdf PDF
VA FSD Inspection Bldg 10 FD 5B-Fail 5.9.24.pdf PDF
Semi-annual FM200 10-22-2024.pdf PDF
Site Visit Information.docx DOCX document
36C26126Q0018.docx DOCX document
Show all 26

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Electric pump test

Company: VA Hospital 975 Kirman Ave. Reno, NV Inspector: Danny Pellegrino

Delta Fire Systems, Inc 1655 Marietta Way Sparks, NV 89431

(775) 359-0396

Location: Pipe Shop Bldg1/C0330 Date of Current Test: November 30, 2023

Pump Manufacturer & Model #: AC Fire Pump Model: 8100 Pump Serial # 11-060249-01-01 Pump Type: HSC

Electric Motor Manufacturer & Model Marathon Model: KB324TSTDP400BEL Electric Motor Serial # C0066751-01/14-02

GPM PSI RPM BHP Max Churn Pressure Max BHP Max Suction Pressure Impeller Diameter Rated Voltage Full Load Amps 1,000 69 3550 69 56.9 100 7.2 400 135

Controller Manufacturer and Model:rtron Model: MP300-50-208C MT Type Starting: Automatic H.P. 50 Flow Test Device Used: Hose monster with internal pitot and calibrated gauges

NFPA Limits Test Points Factory Certified Test Curve Field Certified Test Curve

GPM PSI GPM PSI GPM PSI 2023: 5 seconds for automatic transfer switch to operate 14 seconds to restore peak load to water flow. Referenced NFPA 25 2020 Edition chapter 8, table 8.1.1.2 for all test and inspection procedures. Used liquid filled calibrated gauges and 2.5” hose monsters with internal pitot. Pump appears to be performing as intended.

Start: 140 Start: 165 Churn 0 84 Stop: 160 Stop: 175 Rated 1000 69 Casing Relief Valve OK; Yes 150% 1500 47 Main Relief Valve Setting: N/A

Stuffing Box Adjusted: No Bearings Checked: Greased

Annual Fire Pump Test for year: 2021 Actual Flowing Condition 2021 Adjusted for RPM Auto or Manual Stop: Automatic Pressure Readings RPM

Reading Discharge Coefficient

Outlet Diameter Individual Outlet Pitot Readings Total gpm Adjusted GPM Adjusted

PSI

Adjusted

RPM

Measured Voltage

Measured Amps

Suction PSIG Discharge

PSIG

Net PSIG Leg 1 Leg 2 Leg 3

88 172 84 3572 0 0 83 3550 206 90 90 94 54 126 72 3554 0.97 2.50 40 1143.76025405923 1142 72 3550 204 136 142 147 38 106 68 3556 0.97 2.50 19 19 1576.56471026555 1574 68 3550 205 136 140 150

0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0

Annual Fire Pump Test for year: 2022 Actual Flowing Condition 2022 Adjusted for RPM Pressure Readings RPM

Reading Discharge Coefficient

Outlet Diameter Individual Outlet Pitot Readings Total gpm Adjusted GPM Adjusted

PSI

Adjusted

RPM

Measured Voltage

Measured Amps

Suction PSIG Discharge

PSIG

Net PSIG Leg 1 Leg 2 Leg 3

84 170 86 3573 0 0 85 3550 204 87 92 96 38 106 68 3555 0.97 2.50 35 1069.88975082479 1068 68 3550 203 138 143 152 24 88 64 3538 0.97 2.50 20 20 1617.52126339385 1623 64 3550 203 135 147 150

0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0

Annual Fire Pump Test for year: 2023 Actual Flowing Condition 2023 Adjusted for RPM Pressure Readings RPM

Reading Discharge Coefficient

Outlet Diameter Individual Outlet Pitot Readings Total gpm Adjusted GPM Adjusted

PSI

Adjusted

RPM

Measured Voltage

Measured Amps

Suction PSIG Discharge

PSIG

Net PSIG Leg 1 Leg 2 Leg 3

83 168 85 3573 0 0 84 3550 205 91 90 93 38 104 66 3554 0.97 2.50 23 10 1439.1792814684 1438 66 3550 206 136 140 146 28 90 62 3549 0.97 2.50 19 18 1555.54005854443 1556 62 3550 205 138 142 152

0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0

Electric Fire Pump Performance Curve pump #1

PS

I

GPM

0 450 900 1350 1800

NFPA Limits Test Points Factory Certified Test Curve Field Certified Test Curve 2021 Actual Flowing Condition 2021 Adjusted for RPM 2022 Actual Flowing Condition 2022 Adjusted for RPM 2023 Actual Flowing Condition 2023 Adjusted for RPM

Job Name:

VA Hospital Reno, NV

Date: 11/30/23

File details come from the government source that posted it. Updated .