Reno VAMC-Building 6 - Damper Inspection Report 2025.pdf
PDF 3 MB Posted
- Solicitation number
- 36C26126Q0018
About this file
This document is a Damper Inspection Report for the Reno VAMC (Veterans Affairs Medical Center) Building 6, conducted by Life Safety Services (LSS) on 04/01/2025. The inspection was performed in accordance with the National Fire Protection Association's (NFPA) Standard 80 Chapter 19 and 105 Chapter 7, focusing on fire and smoke dampers.
The inspection covered 6 total fire dampers across two floors (3 dampers on each floor), with 5 dampers passing inspection and 1 damper marked as non-accessible due to an immovable object blocking the work area. Specifically, 5 dampers (83.33%) passed inspection, while 1 damper (16.67%) was non-accessible, located in the F2476 closet on the first floor. The dampers were located in various rooms including locker rooms, hallways, exam rooms, dressing rooms, and closets. The report includes detailed photographic documentation of each damper's open and closed states, along with specific location and tag information.
View the file
Other files
Show all 26
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
908 South 8th Street Louisville, KY. 40203
888.675.4519 info@LifeSafetyServices.com
Damper Inspection Report Reno VAMC - Building 6
04/01/2025 www.LifeSafetyServices.com
DAMPER INSPECTION REPORT
Corporate Office 908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519
Facility: Reno VAMC Inspection Date: 04/01/2025 Inspected By: Willie Leonard Job ID: DR-040524-C11-DIS
FIRE & SMOKE DAMPER INSPECTION SERVICES
LSS Life Safety Services, LLC, in accordance with The National Fire Protection Association’s (NFPA) Standard 80 Chapter 19 and 105 Chapter 7 inspected fire and smoke dampers located in Building 6 during the period of 04/01/2025.
The following report and digital pictures provide the result of the inspection for the dampers that were inspected.
This report is intended to describe the location and operability of the dampers for the date in which LSS Life Safety Services’ representatives performed the inspection of the dampers, and is not intended to constitute any warranty as to the continued operation of any damper.
Thank you for contracting LSS Life Safety Services for this project and we look forward to the opportunity of working with you in the future on additional projects.
Technician Signature
908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519
Project Summary Building Fire Smoke Combination Pass Fail Non-Accessible
6 6 0 0 5 0 1
GRAND TOTAL 6 0 0 5 0 1
Statistics Test Result % of Dampers
Pass 83.33%
Fail 0.00%
Non-Accessible 16.67%
Type Total % of Dampers
Fire 6 100.00%
Smoke 0 0.00%
Combination 0 0.00%
Floor Total
1 3
2 3
908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519
Facility: VA medical Reno Inspection Date: 04/01/2025 Inspected By: Willie Leonard
All Dampers Date Floor Damper Number Damper
Type Damper Location
Inspection Result
Reason for Failure or Inaccessibility
04/01/2025 2 2-F2FD Fire Inside locker room F2532 Pass
04/01/2025 2 3-F2FD Fire Inside locker room F2532 Pass
04/01/2025 2 1-F2FD Fire In hallway across from exam room
F2480 Pass
04/01/2025 1 4-F2FD Fire Inside room F2520 Pass
04/01/2025 1 5-FDFD Fire Inside dressing room F2503 Pass
04/01/2025 1 6-F2FD Fire Inside F2476 closet Non-Accessible Immovable object blocking work area
908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519
Location Description: Inside locker room F2532
Tag: 2-F2FD
Type: Fire
Floor: 2
Status: Pass
Open Photo Closed Photo https://www.gocanvas.com/values/22103926084 https://www.gocanvas.com/values/22103926084 https://www.gocanvas.com/values/22103926085 https://www.gocanvas.com/values/22103926085
908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519
Location Description: Inside locker room F2532
Tag: 3-F2FD
Type: Fire
Floor: 2
Status: Pass
Open Photo Closed Photo https://www.gocanvas.com/values/22103926255 https://www.gocanvas.com/values/22103926255 https://www.gocanvas.com/values/22103926256 https://www.gocanvas.com/values/22103926256
908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519
Location Description: In hallway across from exam room F2480
Tag: 1-F2FD
Type: Fire
Floor: 2
Status: Pass
Open Photo Closed Photo https://www.gocanvas.com/values/22103926383 https://www.gocanvas.com/values/22103926383 https://www.gocanvas.com/values/22103926386 https://www.gocanvas.com/values/22103926386
908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519
Location Description: Inside room F2520
Tag: 4-F2FD
Type: Fire
Floor: 1
Status: Pass
Open Photo Closed Photo https://www.gocanvas.com/values/22103926461 https://www.gocanvas.com/values/22103926461 https://www.gocanvas.com/values/22103926462 https://www.gocanvas.com/values/22103926462
908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519
Location Description: Inside dressing room F2503
Tag: 5-FDFD
Type: Fire
Floor: 1
Status: Pass
Open Photo
Closed Photo https://www.gocanvas.com/values/22103926672 https://www.gocanvas.com/values/22103926672 https://www.gocanvas.com/values/22103926674 https://www.gocanvas.com/values/22103926674
908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519
Location Description: Inside F2476 closet
Tag: 6-F2FD
Type: Fire
Floor: 1
Status: Non-Accessible
Reason for Failure or Inaccessibility: Immovable object blocking work area
Open Photo Closed Photo https://www.gocanvas.com/values/22103926779 https://www.gocanvas.com/values/22103926779 https://www.gocanvas.com/values/22103926781 https://www.gocanvas.com/values/22103926781