Reno VAMC-Building 5 Section K - Damper Inspection Report 2024.pdf

PDF 3 MB Posted

Attached to
H212--Fire Protection Testing, Inspection, and Maintenance/Repair
Solicitation number
36C26126Q0018
Issued by

About this file

This is a Damper Inspection Report from Life Safety Services (LSS) for the Reno Veterans Affairs Medical Center (VAMC), specifically for Building 5 Section K. The inspection was conducted on August 20-22, 2024, by technician Greg Pena (Job ID: DR-040524-C11-DIS), in accordance with National Fire Protection Association (NFPA) Standard 80 Chapter 19 and 105 Chapter 7. The inspection covered three dampers on the second floor of the storage room K2770, with two fire dampers and one combination damper.

The inspection results show that two dampers (2-FD-K2770-2 and 2-FD-K2770-3) passed the inspection, while one damper (2-FD-K2770-1) was marked as non-accessible due to being longer than arm's reach and lacking authorization for an access door installation. The project summary indicates a 66.67% pass rate, with 100% of the dampers being fire dampers. The report includes open and closed photos of each damper, providing visual documentation of the inspection findings.

View the file

Other files

File Type Posted
36C26126Q0018 0002.docx DOCX document
Floor Plans - Fire and Smoke Dampers - Working.pdf PDF
Reno VAMC-Building 1 Section C - Damper Inspection Report 2024.pdf PDF
975 Kirman Pre action 5 yr 7-20.pdf PDF
ANNUAL FWP 231130.pdf PDF
Semi-annual FM200 4-28-2025.pdf PDF
Reno VAMC-Area G - Damper Inspection Report 2025.pdf PDF
975 Kirman Ave. Reno Nv FSD 1.30.24.pdf PDF
VA Bldg. 12 Preaction 10-22-2024.pdf PDF
Reno VAMC-Building 1D - Damper Inspection Report 2025.pdf PDF
Semi-annual Ansul Testing Canteen 05-15-24.pdf PDF
QTRLY flow and tamper blank document.xlsx XLSX spreadsheet
Area D Fire Damper Inspection.xlsx XLSX spreadsheet
Semi-annual Ansul Testing NFS 05-15-24.pdf PDF
VA Bldg. 12 Preaction 1-6-2025.pdf PDF
36C26126Q0018 0001.docx DOCX document
2- Floor Plans - Fire and Smoke Dampers Bldg 1 1A 1D 5 6 10 12.pdf PDF
VA Bldg. 12 Preaction 4-28-2025.pdf PDF
Attachment 1 - Drawings.pdf PDF
Reno VAMC-Building 12 - Damper Inspection Report 2025.pdf PDF
Bldg Sprinkler Inspections.pdf PDF
Reno VAMC-Building 6 - Damper Inspection Report 2025.pdf PDF
VA FSD Inspection Bldg 10 FD 5B-Fail 5.9.24.pdf PDF
Semi-annual FM200 10-22-2024.pdf PDF
Site Visit Information.docx DOCX document
36C26126Q0018.docx DOCX document
Show all 26

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

908 South 8th Street Louisville, KY. 40203

888.675.4519 info@LifeSafetyServices.com

Damper Inspection Report Reno VAMC - Building Section K

08/20/2024 - 08/22/2024 www.LifeSafetyServices.com

DAMPER INSPECTION REPORT

Corporate Office 908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519

Facility: Reno VAMC Inspection Date: 08/20/2024 - 08/22/2024 Inspected By: Greg Pena Job ID: DR-040524-C11-DIS

FIRE & SMOKE DAMPER INSPECTION SERVICES

LSS Life Safety Services, LLC, in accordance with The National Fire Protection Association’s (NFPA) Standard 80 Chapter 19 and 105 Chapter 7 inspected fire and smoke dampers located in Building 5 Section K during the period of 08/20/2024 - 08/22/2024.

The following report and digital pictures provide the result of the inspection for the dampers that were inspected.

This report is intended to describe the location and operability of the dampers for the date in which LSS Life Safety Services’ representatives performed the inspection of the dampers, and is not intended to constitute any warranty as to the continued operation of any damper.

Thank you for contracting LSS Life Safety Services for this project and we look forward to the opportunity of working with you in the future on additional projects.

Technician Signature

908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519

Project Summary Building Fire Smoke Combination Pass Fail Non-Accessible

Building 5 Section K 3 0 0 2 0 1

GRAND TOTAL 3 0 0 2 0 1

Statistics Test Result % of Dampers

Pass 66.67%

Fail 23.33%

Non-Accessible 100.00%

Type Total % of Dampers

Fire 3 100.00%

Smoke 0 0.00%

Combination 0 0.00%

Floor Total

2 3

908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519

Facility: Reno VAMC Inspection Date: 08/20/2024 Inspected By: Greg Pena

All Dampers Date Floor Damper Number Damper

Type Damper Location

Inspection Result

Reason for Failure or Inaccessibility

08/20/2024 2 2-FD-K2770-1 Fire Inside storage room K2770 2nd floor left-hand corner by light

Non-Accessible Longer than arm’s reach, access door install not authorized

908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519

Facility: Reno VAMC Inspection Date: 08/22/2024 Inspected By: Greg Pena

All Dampers Date Floor Damper Number Damper

Type Damper Location

Inspection Result

Reason for Failure or Inaccessibility

08/22/2024 2 2-FD-K2770-2 Fire Building 5 section

K second-floor storage room

K2770 Pass

08/22/2024 2 2-FD-K2770-3 Combination

Building 5 section K second floor storage room

K2770 right hand corner above the sprinkler

Pass

908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519

Location Description: Inside storage room K2770 2nd floor left-hand corner by light

Tag: 2-FD-K2770-1

Type: Fire

Floor: 2

Status: Non-Accessible

Reason for Failure or Inaccessibility: Longer than arm’s reach, access door install not authorized

Open Photo

Closed Photo https://www.gocanvas.com/values/20350099501 https://www.gocanvas.com/values/20350099501 https://www.gocanvas.com/values/20350099502 https://www.gocanvas.com/values/20350099502

908 South 8th Street 500 Louisville, KY 40203 www.LifeSafetyServices.com 888-675-4519

Location Description: Building 5 section K second-floor storage room K2770

Tag: 2-FD-K2770-2

Type: Fire

Floor: 2

Status: Pass

Open Photo

Closed Photo

Location Description: Building5 section K second floor storage room K2770 right hand corner above the sprinkler

Tag: 2-FD-K2770-3

Type: Combination

Floor: 2

Status: Pass

Open Photo Closed Photo https://www.gocanvas.com/values/20366627655 https://www.gocanvas.com/values/20366627655 https://www.gocanvas.com/values/20366627660 https://www.gocanvas.com/values/20366627660 https://www.gocanvas.com/values/20366628008 https://www.gocanvas.com/values/20366628008 https://www.gocanvas.com/values/20366628012 https://www.gocanvas.com/values/20366628012

908 South 8th Street Louisville, KY. 40203

888.675.4519 info@LifeSafetyServices.com

Damper Inspection Report Reno VAMC - Building 5 Section K

08/22/2024 www.LifeSafetyServices.com

08_20_2024_5_section_k_DR_040524_C11_DIS_Damper_Inspection.pdf
2
08_22_2024_Building_k_outpatient_mental_health_DR_0_Damper_Inspection.pdf
1