About this file

36C25519R0017 VOL 2_JC dwg Electrical.pdf

View the file

Other files

File Type Posted
36C25519R0017-0003000.docx DOCX document
36C25519R0017-0002005.pdf PDF
36C25519R0017-0002004.pdf PDF
36C25519R0017-0002000.docx DOCX document
36C25519R0017-0002003.pdf PDF
36C25519R0017-0002002.pdf PDF
36C25519R0017-0002001.jpg JPG image
36C25519R0017-0001000.docx DOCX document
36C25519R0017-0001001.pdf PDF
36C25519R0017-018.pdf PDF
36C25519R0017-000.docx DOCX document
36C25519R0017-007.pdf PDF
36C25519R0017-022.pdf PDF
36C25519R0017-005.pdf PDF
36C25519R0017-023.pdf PDF
36C25519R0017-010.pdf PDF
36C25519R0017-015.pdf PDF
36C25519R0017-024.pdf PDF
36C25519R0017-011.pdf PDF
36C25519R0017-012.pdf PDF
36C25519R0017-027.pdf PDF
36C25519R0017-028.pdf PDF
36C25519R0017-017.pdf PDF
36C25519R0017-026.pdf PDF
36C25519R0017-003.pdf PDF
36C25519R0017-001.pdf PDF
36C25519R0017-025.pdf PDF
36C25519R0017-016.pdf PDF
36C25519R0017-004.pdf PDF
36C25519R0017-020.pdf PDF
36C25519R0017-008.pdf PDF
36C25519R0017-002.pdf PDF
36C25519R0017-014.pdf PDF
36C25519R0017-019.pdf PDF
36C25519R0017-009.pdf PDF
36C25519R0017-021.pdf PDF
36C25519R0017-006.pdf PDF
36C25519R0017_3.docx DOCX document
36C25519R0017_2.docx DOCX document
36C25519R0017_1.docx DOCX document
Show all 40

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

26 28 16FDS-# FUSIBLE DISCONNECT SWITCH, REFER TO DISCONNECT AND

STARTER SCHEDULE

26 24 19MX-# MANUAL SWITCH, REFER TO DISCONNECT AND STARTER SCHEDULE

NEP-# FIRE ALARM - EXTENDER PANEL 28 31 00

R-# RELAY 26 09 39

REC-# RECEPTACLE - SPECIAL USE 26 27 26

ELECTRICAL EQUIPMENT TAGS

TAG: DESCRIPTION:

RELATED

SPECIFICATION

F# LUMINAIRE TYPE

FA-100 28 31 00 FIRE ALARM CONTROL PANEL

FA-200 28 31 00 FIRE ALARM VISUAL NOTIFICATION

DEVICE - WALL MOUNTED

V1 V3

V7 VH

FA-211 28 31 00 FIRE ALARM AUDIO/VISUAL NOTIFICATION

DEVICE - WALL MOUNTED

A1 A3

A7 AH

AS

FA-201 28 31 00 FIRE ALARM VISUAL NOTIFICATION

DEVICE - CEILING MOUNTED

V1 V3

V7 VH

FA-231 28 31 00 FIRE ALARM AUDIO/VISUAL NOTIFICATION

DEVICE - CEILING MOUNTED

A1 A3

A7 AH

FA-230 28 31 00 FIRE ALARM AUDIO NOTIFICATION

DEVICE - CEILING MOUNTED

A

SD FA-120 28 31 00 FIRE ALARM SMOKE DETECTOR - CEILING

MOUNTED

SD FA-122 28 31 00 FIRE ALARM DUCT SMOKE DETECTOR

FA-130 28 31 00 FIRE ALARM MANUAL PULL STATIONF

FA-161 28 31 00 FIRE ALARM ADDRESSABLE RELAYAR

FA-160 28 31 00 FIRE ALARM ADDRESSABLE MONITOR MODULEMM

FA-251 28 31 00 SMOKE OR FIRE DAMPER CONTROLLERARD

FA-260 28 31 00 FIRE ALARM FLOW SWITCH TO MONITOR FIRE

PROTECTION SYSTEM

FS

FA-261 28 31 00 FIRE ALARM MONITOR SWITCH TO

MONITOR FIRE PROTECTION SYSTEM

MS

FA-262 28 31 00 FIRE ALARM POST INDICATOR VALVE

CONNECTION

PIV

FA-270 28 31 00 FIRE ALARM ELECTROMAGNETIC DOOR

HOLD DEVICE

DH

VS

VS

SW-1P 26 09 33 SWITCH - SINGLE POLE

SW-OC SWITCH - OCCUPANCY SENSOR WALL SWITCH0

OC SW-OC-D OCCUPANCY SENSOR - DUAL TECHNOLOGY

D

26 09 33

26 09 33

F# LINEAR LUMINAIRES26 51 00

F# TROFFER

F# WALL SCONCE LUMINAIRE

F# DOWNLIGHT LUMINAIRE

F# AIMABLE OR WALL WASH LUMINAIRE

F# INDUSTRIAL LUMINAIRE

X# SINGLE FACE EXIT SIGN

X# DOUBLE FACE EXIT SIGN

XM# EMERGENCY UNIT

F# WALL BRACKET LUMINAIRE

26 51 00

26 51 00

26 51 00

26 51 00

26 51 00

26 51 00

26 51 00

26 51 00

26 51 00

DS-# 26 28 16 DISCONNECT

AS

SW-D-LED DIMMER - LED26 09 33

ELECTRICAL SYMBOL LIST

SYMBOL: TAG:

SPEC

SECTION:

DESCRIPTION:

ELECTRICAL SYMBOL LIST

SYMBOL: TAG:

SPEC

SECTION:

DESCRIPTION:

JB 26 05 33 JUNCTION BOX

J

J

ECONN 26 05 33 ELECTRICAL CONNECTION

E

E

RI-TECH 26 05 33 TECHNOLOGY ROUGH-IN

RI

RI-TECH-W 26 05 33 TECHNOLOGY ROUGH-IN, MOUNTED +54" AFF

RI

PANEL '###' EXISTING PANELBOARD - SURFACE MOUNT

PANEL '###' EXISTING PANELBOARD - RECESS MOUNT

MX-#/MS-#/FCS-# 26 24 19 MANUAL SWITCH / STARTER / COMBINATION

STARTER

REC-DUP 26 27 26 DUPLEX RECEPTACLE, 125V

REC-DUP-GFI 26 27 26 DUPLEX GFI RECEPTACLE, 125V

ELECTRICAL SYMBOL LIST

SYMBOL: TAG:

SPEC

SECTION:

DESCRIPTION:

26 51 00

1. EXISTING CONDITIONS ARE SHOWN BASED ON INFORMATION OBTAINED FROM FIELD

SURVEYS, EXISTING BUILDING DOCUMENTS, AND STAFF. VERIFY EXISTING CONDITIONS AND

REPORT ANY CONFLICTS BEFORE PROCEEDING.

2. NOT ALL EXISTING EQUIPMENT, LUMINAIRES, AND CONDUIT ARE SHOWN. VERIFY EXISTING

CONDITIONS AND REPORT ANY CONFLICTS WITH NEW WORK BEFORE STARTING WORK.

3. FIELD VERIFY THE AVAILABLE CLEARANCES FOR CABLE TRAY, BUSWAY AND CONDUITS

BEFORE FABRICATION. RISES AND DROPS MAY BE NECESSARY BECAUSE OF EXISTING

FIELD CONDITIONS.

4. EACH CONTRACTOR SHALL FIELD VERIFY ACCESSIBILITY TO THE AREA OF HIS/HER WORK

AND SHALL NOTIFY THE GENERAL CONTRACTOR PRIOR TO BIDDING IF OTHER UTILITIES ARE

REQUIRED TO BE REMOVED OR RELOCATED TO ALLOW ACCESS TO HIS/HER AREA OF

WORK.

5. EACH CONTRACTOR SHALL CUT AND PATCH ROOFS, WALLS, AND FLOORS ASSOCIATED

WITH HIS/HER WORK.

6. THE GENERAL CONTRACTOR IS RESPONSIBLE FOR REMOVAL AND REPLACEMENT OF

CEILINGS, CEILING TILES, AND CEILING GRIDS ASSOCIATED WITH AREAS OF WORK BY ALL

CONTRACTORS. NOTIFY THE GENERAL CONTRACTOR OF AFFECTED AREAS PRIOR TO

BIDDING.

7. WHERE EXISTING ELECTRICAL SYSTEMS ARE LOCATED IN AREAS THAT CONFLICT WITH NEW

EQUIPMENT, PIPING, OR DUCTWORK TO BE INSTALLED, EACH CONTRACTOR SHALL EITHER

ARRANGE NEW EQUIPMENT, CONDUIT, OR DUCTWORK IN SUCH A FASHION THAT IT DOES

NOT CONFLICT WITH EXISTING SYSTEMS, OR REWORK EXISTING ELECTRICAL SYSTEMS TO

ALLOW FOR INSTALLATION OF NEW EQUIPMENT, PIPING, OR DUCTWORK.

ELECTRICAL RENOVATION NOTES:

THESE NOTES APPLY TO ALL ELECTRICAL SHEETS AND TRADES, INCLUDING BUT NOT LIMITED

TO, LIGHTING, POWER, AND SYSTEMS.

1. ##-### INDICATES ELECTRICAL EQUIPMENT DEFINED IN ELECTRICAL SCHEDULES OR

SPECIFICATION. REFER TO DRAWINGS CONTAINING ELECTRICAL SCHEDULES. PERMANENT

NAMEPLATE SHALL MATCH FINAL EQUIPMENT NOMENCLATURE, NOT ELECTRICAL

EQUIPMENT TAG NAME, REFER TO SPECIFICATIONS.

2. {L###} INDICATES THE LIGHTING SEQUENCE OF OPERATION FOR THE SPACE. REFER TO THE

LIGHTING SEQUENCE OF OPERATION MATRIX ON LIGHTING SHEETS.

3. "NL" INDICATES LUMINAIRE IS UNSWITCHED FOR NIGHT LIGHT.

4. "SE" INDICATES LUMINAIRE IS SWITCHED/CONTROLLED DURING NORMAL OPERATION AND

OPERATES FROM EMERGENCY CIRCUIT UPON LOSS OF POWER.

5. SHADED LUMINAIRE OR DEVICE INDICATES LUMINAIRE OR DEVICE IS CONNECTED TO AN

EMERGENCY CIRCUIT.

LUMINAIRE KEY:

DEVICE KEY:

ELECTRICAL MOUNTING SUBSCRIPT KEY:

A MOUNT AT +6" TO CENTERLINE ABOVE COUNTER OR BACKSPLASH

C MOUNT AT CEILING

H MOUNT ORIENTED HORIZONTALLY

L MOUNT IN CASEWORK

M MOUNT IN MODULAR FURNITURE

R MOUNT IN SURFACE RACEWAY

ELECTRICAL GENERAL NOTES:

LUMINAIRE

F1 = FIXTURE TAG

1 = CIRCUIT NUMBER

a = SWITCH DESIGNATION

NL = SUBSCRIPT (IF APPLICABLE)

*IF LABEL IS ORIENTED HORIZONTALLY A SLASH WILL SEPARATE THIS

INFORMATION. EX: F1 / 1 / a / NL

DEVICE

A = MOUNTING (IF APPLICABLE)

1 = CIRCUIT NUMBER

*IF LABEL IS ORIENTED HORIZONTALLY A SLASH WILL SEPARATE THIS

INFORMATION. EX: A / 1

1. THE COMPLETE INSTALLATION SHALL BE IN ACCORDANCE WITH THE ABAAS STANDARDS

FOR ACCESSIBLE DESIGN. REFER TO THE ABAAS GUIDELINES FOR ALL CONFIGURATION

DETAILS ON THIS PAGE FOR ADDITIONAL INFORMATION.

2. CIRCUIT NUMBERS ARE SHOWN FOR CIRCUIT IDENTIFICATION. CIRCUITING SHALL AGREE

WITH NUMBERING ON THE PANEL PROVIDED. COMMON NEUTRALS MAY NOT BE USED FOR

BRANCH CIRCUITS. BALANCE THE LOAD ON PANEL AS EVENLY AS POSSIBLE BETWEEN

EACH PHASE.

3. CIRCUITS SERVING EMERGENCY AND EXIT LUMINAIRES WILL BE RUN IN A SEPARATE

RACEWAY FROM ALL OTHER CIRCUITS.

4. FLUSH MOUNT ALL LIGHTING CONTROL DEVICES AT +42" FROM FLOOR (CENTERLINE

DIMENSION), EXCEPT WHERE OTHERWISE NOTED. DEVICES MAY BE SURFACE MOUNTED

WHEN CONDUIT IS SPECIFIED EXPOSED.

5. FLUSH MOUNT ALL DUPLEX RECEPTACLES AND TECHNOLOGY OUTLETS AT +18" FROM

FLOOR (CENTERLINE DIMENSION), EXCEPT WHERE OTHERWISE NOTED. RECEPTACLES AND

OUTLETS MAY BE SURFACE MOUNTED WHEN CONDUIT IS SPECIFIED EXPOSED.

6. ALL MATERIALS USED TO SEAL PENETRATIONS OF FIRE RATED WALLS AND FLOORS SHALL

BE TESTED AND CERTIFIED AS A SYSTEM PER ASTM E814 STANDARDS FOR FIRE TESTS OF

THROUGH-PENETRATION FIRESTOPS. REFER TO DIVISION 7 FOR ADDITIONAL INFORMATION

AND REQUIREMENTS SPECIFIC TO FIRESTOPPING.

7. MOUNT ALL FIRE ALARM PULL STATIONS AT +42" FROM FLOOR (CENTERLINE DIMENSION)

EXCEPT WHERE OTHERWISE NOTED.

8. INSTALL ALL WALL MOUNTED FIRE ALARM NOTIFICATION DEVICES AT 90" ABOVE FINISHED

FLOOR OR 6" BELOW THE CEILING, WHICHEVER IS LOWER, EXCEPT WHERE OTHERWISE

NOTED. HEIGHT SHALL BE MEASURED TO THE TOP OF THE DEVICE.

9. CONTRACTOR SHALL COORDINATE THE LOCATION OF ALL CEILING MOUNTED DEVICES AND

EQUIPMENT WITH LUMINAIRES, SPRINKLER, AND CEILING DIFFUSERS. CENTER ALL DEVICES

IN CEILING TILE PATTERN. SMOKE DETECTORS AND OCCUPANCY/VACANCY SENSORS

SHALL BE LOCATED NO CLOSER THAN 3 FEET TO AN AIR SUPPLY DIFFUSER OR RETURN

GRILLE.

10. CONTRACTOR SHALL VERIFY ALL EQUIPMENT LOCATIONS WITH ARCHITECTURAL PLANS,

ELEVATIONS, AND REVIEWED SHOP DRAWINGS. PRIOR TO MAKING THE ACTUAL

ELECTRICAL INSTALLATION, THIS CONTRACTOR SHALL ADJUST RECEPTACLES, OUTLETS,

OR CONNECTION LOCATIONS TO ACCOMMODATE FURNITURE AND/OR EQUIPMENT.

11. ELECTRICAL AND TECHNOLOGY EQUIPMENT SHALL BE MOUNTED TO AVOID IMPEDANCE OF,

OPERATION OF, AND/OR ACCESS TO ELECTRICAL AND MECHANICAL EQUIPMENT. ALL

MOUNTING OF ELECTRICAL AND TELECOMMUNICATIONS EQUIPMENT, ON EQUIPMENT

SUPPLIED BY ANOTHER CONTRACTOR, SHALL BE APPROVED IN ADVANCE BY THE OTHER

CONTRACTOR.

12. CONTRACTOR SHALL BE RESPONSIBLE FOR ALL OPENINGS REQUIRED IN WALLS. ALL

OPENINGS SHALL BE REPAIRED TO MATCH EXISTING BY A QUALIFIED CONTRACTOR AT THE

EXPENSE OF THIS CONTRACTOR. ALL CONDUITS THROUGH WALLS SHALL BE GROUTED OR

SEALED INTO OPENINGS.

13. ALL WELDING SHALL BE ACCORDING TO AMERICAN WELDING SOCIETY STANDARDS.

CONTRACTOR SHALL FURNISH TO THE ARCHITECT/ENGINEER CERTIFICATES QUALIFYING

EACH WELDER, PRIOR TO START OF WORK. THE ARCHITECT/ENGINEER RESERVES THE

RIGHT TO REQUIRE QUALIFYING DEMONSTRATION, AT THE CONTRACTOR'S EXPENSE, OF

ANY WELDERS ASSIGNED TO THE JOB.

14. CONTRACTOR SHALL REMOVE AND REINSTALL ALL CEILING TILES AS REQUIRED FOR THE

EXECUTION OF ELECTRICAL WORK. CONTRACTOR SHALL REPLACE CEILING TILES WITH

IDENTICAL MATERIAL WHERE DAMAGED BY THIS CONTRACTOR.

15. REFER TO ARCHITECTURAL REFLECTED CEILING PLAN, ELECTRICAL, TECHNOLOGY

AUDIO/VISUAL, AND OTHER ELECTRICAL PLANS FOR EXACT LOCATIONS OF ALL CEILING

MOUNTED DEVICES, OTHER THAN SPRINKLERS.

16. E.C. TO PROVIDE POWER TO WAYFINDING KIOSKS. EXTEND POWER FROM NEAREST

NORMAL POWER CIRCUIT, INSTALL CONDUIT AND CONDUCTORS TO THE KIOSK LOCATION,

AND PROVIDE RECEPTACLE. REFER TO WAYFINDING DOCUMENTS FOR LOCATIONS AND

INFORMATION. WAYFINDING KIOSKS ARE TO BE LOCATED AT VAJC BUILDING 1 ON LEVELS 1

&3.

ELECTRICAL INSTALLATION NOTES:

ELECTRICAL ABBREVIATION KEY

AFF ABOVE FINISHED FLOOR

N.C. NORMALLY CLOSED

NIC NOT IN CONTRACT

N.O. NORMALLY OPEN

SV SOLENOID VALVE

ABBR: DESCRIPTION:

TYP TYPICAL

C CONDUIT

UNO UNLESS NOTED OTHERWISE

GFI GROUND FAULT INTERRUPTER

NORMAL BRANCH LUMINAIRE

CRITICAL BRANCH LUMINAIRE

EMERGENCY LIFE SAFETY BRANCH LUMINAIRE

LUMINAIRE SYMBOL KEY

SYMBOL: DESCRIPTION:

PLAN OR DETAIL NUMBER

PLAN OR DETAIL NAME

PLAN OR DETAIL SCALE

DETAIL REFERRED TO BY SECTION CUT

SHEET DETAIL IS LOCATED ON

NAME

VIEW NAME

1/8" = 1'-0"

M101

T101

SIM

DETAIL REFERRED TO BY ELEVATION

SHEET DETAIL IS LOCATED ON

INDICATES SIMILAR DETAIL

REFERENCED IN MULTIPLE LOCATIONS

SIM

INDICATES SIMILAR DETAIL

REFERENCED IN MULTIPLE LOCATIONS

LEVEL NAME

10' - 0" HEIGHT ABOVE

PROJECT 0' - 0"

1 INDICATES NOTE USED TO DESCRIBE

ADDITIONAL INFORMATION ABOUT

WORK REQUIRED, SPECIFIC TO THE

SHEET AND/OR DETAIL

N

O R HT

INDICATES DIRECTION OF TRUE NORTH

VIEW KEY

NEW WORK BY THIS CONTRACTOR

(DARK SOLID LINE)

NEW WORK UNDERFLOOR OR UNDERGROUND BY THIS CONTRACTOR

(DARK LONG DASHED LINE)

NEW WORK BY OTHERS AND/OR EXISTING TO REMAIN

(LIGHT SOLID LINE)

LINE TYPE KEY:

TEMPERATURE CONTROLS CONTRACTORT.C.C.

SECURITY CONTRACTORS.C.

AUDIO/VISUAL CONTRACTORA.V.C.

NURSE CALL CONTRACTORN.C.C.

CIVIL CONTRACTORC.C.

FIRE PROTECTION CONTRACTORF.P.C.

PLUMBING CONTRACTORP.C.

GENERAL CONTRACTORG.C.

MECHANICAL CONTRACTORM.C.

ELECTRICAL CONTRACTORE.C.

CONTRACTOR ABBREVIATION KEY

ABBR: DESCRIPTION:

TECHNOLOGY CONTRACTORT.C.

CONSTRUCTION MANAGERC.M.

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

VA FORM 08-6231

ARCHITECTS Drawing Title Project Title

Location

Date Checked Drawn

Project Number

Building Number

Drawing Number

CONSULTANTS

Dwg: Of:

657-18-110CORRECT WORKPLACE & LIFE SAFETY

ISSUES, ABATE ASBESTOS, & IMPROVE

WAYFINDING

SEPTEMBER 12, 2018

Building Name

JOHN COCHRAN DIVISION -

Revisions: Date:

3705 North 200th Street Elkhorn, Nebraska 68022

(402) 291-6941

15 Sunnen Drive Suite 104 St. Louis, MO 64143

(314) 645-1132

8802 South 135th Street, Suite 100 Omaha, NE 68138

(402) 861-4445

BID DOCUMENTS

FULLY SPRINKLERED

VETERANS

HEALTH

ADMINISTRATION

/1

/2

:3 :5

P

M

E-001

ELECTRICAL COVER SHEET

ST. LOUIS, MO - VA JOHN COCHRAN

IMEG

62 79

BUILDING 1

STEWIE

BLDG 7 - NOT FULLY SPRINKLERED

BLDG 1 - FULLY SPRINKLERED

A. DEDUCT ALT #1: ALL WORK IN BASE BID WITH THE FOLLOWING EXCEPTIONS / DEDUCTIONS:

1. WORK JOHN COCHRAN BUILDING 7 DELETE

BID ALTERNATE

A. DEDUCT ALT #1: ALL WORK IN BASE BID WITH THE FOLLOWING EXCEPTIONS / DEDUCTIONS:

1. WORK JOHN COCHRAN BUILDING 7 DELETE

BID ALTERNATE

CORRIDOR

H202

FILM VIEW

A216

RADIOGRAPHIC

AND

FLUOROSCOPIC

A217

TOILET

A218

RADIOGRAPHIC

A219

X-RAY

A220

CONTROL

A221

RADIOGRAPHIC

AND

FLUOROSCOPIC

A215

TOILET

A216C

CONTROL

A217AEQUIPMENT

STORAGE

A218C

TOILET

A219E

CONTROL

A219D

DUMB WAITER

LOBBY

A219A

ELEC. CLOSET

A220A

CONTROL

A215A

CHASE

CH-A-7

7 6 5 3489

D D

A

B

C

PANEL 2C-R

PANEL 2C-L

A1 th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

VA FORM 08-6231

ARCHITECTS Drawing Title Project Title

Location

Date Checked Drawn

Project Number

Building Number

Drawing Number

CONSULTANTS

Dwg: Of:

657-18-110CORRECT WORKPLACE & LIFE SAFETY

ISSUES, ABATE ASBESTOS, & IMPROVE

WAYFINDING

SEPTEMBER 12, 2018

Building Name

JOHN COCHRAN DIVISION -

Revisions: Date:

3705 North 200th Street Elkhorn, Nebraska 68022

(402) 291-6941

15 Sunnen Drive Suite 104 St. Louis, MO 64143

(314) 645-1132

8802 South 135th Street, Suite 100 Omaha, NE 68138

(402) 861-4445

BID DOCUMENTS

FULLY SPRINKLERED

VETERANS

HEALTH

ADMINISTRATION

/1

/2

:3 :3

P

M

1-2-ED-101A

SECOND FLOOR - ELECTRICAL DEMOLITION PLAN

ST. LOUIS, MO - VA JOHN COCHRAN

IMEG

63 79

BUILDING 1

STEWIE

N O R

HT

1/4" = 1'-0"1

SECOND FLOOR - ELECTRICAL DEMOLITION PLAN

GENERAL NOTES :

1. REFER TO SHEET E001 FOR ELECTRICAL

SYMBOLS, APPLICABLE CODES, GENERAL

NOTES, RENOVATION NOTES AND

INSTALLATION NOTES.

KEYNOTES:

1. REMOVE LIGHT FIXTURE AND RECEPTACLE.

PROTECT CIRCUIT IN PLACE TO BE REUSED IN

NEW WORK.

E

E

E

E

E

LOUNGE

A601

OFFICE

A602

HAC

A603

NURSE

MANAGER

A604

MED. PREP.

A605

NURSE STATION

A606

NOUR.

A607

GI PROCEDURE

ROOM

A608

PROCEDURE

RM.

A609 PROCEDURE

RM.

A610

SCOPE

A610A

PROCEDURE

RM.

A611

PROCEDURE

RM.

A612

SCOPE

CLEANING

A613B

CLEAN

A614

SOILED

A615

ANTE RM.

A613A

CLEAN UTILITY

A611A

SCOPE

CLEANING

DIRTY SIDE

A613

CORRIDOR

H601

NURSE BREAK

RM.

A616

STORAGE

A617

TOILET

A616AWORKSTATION

A624

CLOSET

A623D

ELEC. CLOSET

A623C

STORAGE

A623B

STAIRWELL NO.

S602

TOILET

A623A

TOILET

A626A

OFFICE

A629

TOILET

A627A

TOILET

A628

OI&T

A629B

OI&T

A629C

OFFICE

A631

OFFICE

A632

BED RM.

A626

STORAGE

H606C OFFICE

A671

STAIRWELL NO.

S601

F.E. CLOSET

H606B

ELEC. CLOSET

A629A

CHASE

CH-A-6

CHASE

CH-A-7

CHASE

CH-A-8

CHASE

CH-A-9

CHASE

CH-A-10

CHASE

CH-A-12

CHASE

CH-A-11

CHASE

CH-A-13

CHASE

CH-A-16

CHASE

CH-A-17

CHASE

CH-A-18

CHASE

CH-A-19

F.E. CLOSET

H602A

7 6 5 2 13

48910

K

J

J

I

H H

G

F

E

D

EXISTING PANEL 6A

EXISTING PANEL E6C

EXISTING EC6A

EXISTING CONDUITS TO

BE RELOCATED

EXISTING CONDUITS

TO BE RELOCATED

EXISTING PANEL 6C

EXISTING ELS61

AREA OF WORK ON 7TH

FLOOR AND 8TH FLOORS.

EXISTING CONDUIT AND

LIGHT FIXTURES TO BE

RELOCATED ON 7TH AND

8TH FLOORS TO MAKE

ROOM FOR NEW DUCT

CHASE. CORRDINATE

WORK WITH OWNER.

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

VA FORM 08-6231

ARCHITECTS Drawing Title Project Title

Location

Date Checked Drawn

Project Number

Building Number

Drawing Number

CONSULTANTS

Dwg: Of:

657-18-110CORRECT WORKPLACE & LIFE SAFETY

ISSUES, ABATE ASBESTOS, & IMPROVE

WAYFINDING

SEPTEMBER 12, 2018

Building Name

JOHN COCHRAN DIVISION -

Revisions: Date:

3705 North 200th Street Elkhorn, Nebraska 68022

(402) 291-6941

15 Sunnen Drive Suite 104 St. Louis, MO 64143

(314) 645-1132

8802 South 135th Street, Suite 100 Omaha, NE 68138

(402) 861-4445

BID DOCUMENTS

FULLY SPRINKLERED

VETERANS

HEALTH

ADMINISTRATION

/1

/2

:3 :4

P

M

1-6-ED-101A

SIXTH FLOOR - ELECTRICAL DEMOLITION PLAN

ST. LOUIS, MO - VA JOHN COCHRAN

IMEG

64 79

BUILDING 1

STEWIE

N

O R HT

3/16" = 1'-0"1

SIXTH FLOOR - ELECTRICAL DEMOLITION PLAN

GENERAL NOTES :

1. REFER TO SHEET E001 FOR ELECTRICAL

SYMBOLS, APPLICABLE CODES, GENERAL

NOTES, RENOVATION NOTES AND

INSTALLATION NOTES.

2. EXISTING FIRE ALARM AND NURSE CALL

DEVICES TO REMAIN PROTECT IN PLACE

DURING DEMOLITION.

KEYNOTES:

1. DISCONNECT EXISTING HVAC UNITS THAT ARE

TO BE REMOVED. REMOVE CONDUIT AND

CONDUCTORS BACK TO SOURCE IN H606C.

2. RELOCATE APPROXIMATELY 12 CONDUITS TO

ALLOW FOR DUCTWORK INSTALLATION.

EXISTING CONDUITS SPAN 38" FROM THE

NORTH WALL TO 74" FROM THE NORTH WALL

AT 8' 10" AFF. EXTEND CONDUIT AND

CONDUCTORS MATCHING THE EXISTING SIZE

AND RATING. FINAL INSTALLATION LOCATIONS

ARE REQUIRED TO BE COORDINATED WITH

THE MECHANICAL CONTRACTOR. THE

CONDUIT WILL NEED TO BE CONDENSED BY

STACKING AND REDUCING THE SPACE

BETWEEN INDIVIDUAL CONDUITS.

FILM VIEW

A216

RADIOGRAPHIC

AND

FLUOROSCOPIC

A217

TOILET

A218

RADIOGRAPHIC

A219

X-RAY

A220

CONTROL

A221

RADIOGRAPHIC

AND

FLUOROSCOPIC

A215

TOILET

A216C

CONTROL

A217AEQUIPMENT

STORAGE

A218C

TOILET

A219E

CONTROL

A219D

LASER PRINT

A219B

FILM STORAGE

A219C

DUMB WAITER

LOBBY

A219A

ELEC. CLOSET

A220A

CONTROL

A215A

CHASE

CH-A-7

7 6 5 3489

D D

A

B

C

PANEL 2C-R

PANEL 2C-L

F2

O th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

VA FORM 08-6231

ARCHITECTS Drawing Title Project Title

Location

Date Checked Drawn

Project Number

Building Number

Drawing Number

CONSULTANTS

Dwg: Of:

657-18-110CORRECT WORKPLACE & LIFE SAFETY

ISSUES, ABATE ASBESTOS, & IMPROVE

WAYFINDING

SEPTEMBER 12, 2018

Building Name

JOHN COCHRAN DIVISION -

Revisions: Date:

3705 North 200th Street Elkhorn, Nebraska 68022

(402) 291-6941

15 Sunnen Drive Suite 104 St. Louis, MO 64143

(314) 645-1132

8802 South 135th Street, Suite 100 Omaha, NE 68138

(402) 861-4445

BID DOCUMENTS

FULLY SPRINKLERED

VETERANS

HEALTH

ADMINISTRATION

/1

/2

:3 :3

P

M

1-2-EL-101A

SECOND FLOOR - ELECTRICAL LIGHTING RENOVATION PLAN

ST. LOUIS, MO - VA JOHN COCHRAN

IMEG

65 79

BUILDING 1

STEWIE

N O R

HT

1/4" = 1'-0"1

SECOND FLOOR - ELECTRICAL LIGHTING RENOVATION PLAN

GENERAL NOTES :

1. REFER TO SHEET E001 FOR ELECTRICAL

SYMBOLS, APPLICABLE CODES, GENERAL

NOTES, RENOVATION NOTES AND

INSTALLATION NOTES.

2. LUMINAIRE SCHEDULE INCLUDES

INFORMATION FOR FIXTURES ON SECOND AND

SIXTH FLOORS.

KEYNOTES:

1. CONNECT NEW F2 LIGHT FIXTURE TO EXISTING

CIRCUIT PROTECTED AT DEMOLITION.

SURFACE MOUNT F2 FIXTURE TO CEILING.

ALL LAMPS FOR THIS PROJECT SHALL BE FURNISHED AND INSTALLED BY THE ELECTRICAL CONTRACTOR UNLESS OTHERWISE NOTED.

CORRELATED COLOR TEMPERATURE 3500°.

LED LAMP COLOR RENDERING INDEX (CRI) AT OR ABOVE 85 FOR INTERIOR APPLICATIONS.

CATALOG NUMBER SHALL NOT BE CONSIDERED COMPLETE AND MATERIAL SHALL NOT BE ORDERED BY MANUFACTURER AND CATALOG NUMBER ONLY. THE COMPLETE DESCRIPTION AND THE SPECIFICATION SHALL BE COORDINATED WITH THE CATALOG NUMBER TO DETERMINE THE EXACT MATERIAL AND ACCESSORIES TO BE ORDERED. THE

FIRST MANUFACTURER LISTED IS THE BASIS FOR DESIGN.

REFER TO SPECIFICATION SECTIONS LIGHTING 26 51 00 FOR ADDITIONAL INFORMATION AND REQUIREMENTS.

HP - HIGH PERFORMANCE / LBF PRS - ELECTRONIC PROGRAM RAPID START BALLAST

ML - MULTI-LEVEL SWITCHING MV - MULTI-VOLTAGE ELECTRONIC 120V-277V

CSA - FINISH SELECTION BY ARCHITECT HL - HIGH / LOW LEVEL BALLAST DALI - DIGITAL DIMMING BALLAST

PAF - PAINT AFTER FABRICATION DIM10 - 0-10V DIMMING BALLAST EM - EMERGENCY BATTERY / BALLAST

FINISH: DIM07 - LINE DIMMING BALLAST EB - ELECTRONIC BALLAST

(TYPE) BALLAST: (TYPE) BALLAST:

RS - REGRESSED STEEL

RA - REGRESSED ALUMINUM O - OTHER (SEE DESCRIPTION)

FS - FLAT STEEL XLP - EXTENDED LIFE & OUTPUT R - HIGH IMPACT OR ACRYLIC

FA - FLAT ALUMINUM XL - EXTENDED LIFE N - NONE

DOOR: O - OTHER (SEE DESCRIPTION L - LOW IRIDESCENT SPECULAR ALUM.

CMH - CERAMIC METAL HALIDE K19 - KSH19 .156" ACRYLIC

O - OTHER (SEE DESCRIPTION) PSMH - PULSE START METAL HALIDE K - KSH12 .125" ACRYLIC

FR - FLANGED RECESSED SMH - SUPER METAL HALIDE P - POLYCARBONATE

PL - POLE MH - METAL HALIDE H - WALL WASHER

CV - COVE HS - HIGH PRESSURE SODIUM G - TEMPERED GLASS

UC - UNDER CABINET LED - LIGHT EMITTING DIODE F - FRESNEL

WL - WALL IN - INCANDESCENT D - PARABOLIC

CL - CEILING SURFACE HL - HALOGEN C - CLEAR ALZAK

SP - SUSPENDED CF - COMPACT FLUORESCENT B - BLACK BAFFLE

RE - RECESSED FL - FLUORESCENT A - .125 ACRYLIC

(MTG) MOUNTING: (TYPE) LAMP TECHNOLOGY: (L/L) LENS / LOUVER:

LUMINAIRE SCHEDULE

ITEM DESCRIPTION

DIMENSIONS

MTG

LAMPS BALLAST

L/L

APPROVED

MANUFACTURERL W H DIA. TYPE QTY MODEL VOLTS TYPE

F1 FLAT PANEL LED FIXTURE 4'-0" 2'-0" 2" RE LED 1 MAX 40

WATTS

MINIMUM 4000

LUMENS

120 V DIM10 K METALUX 24FP LED

LITHONIA PANEL LED

PHILIPS FLUX PANEL

LED

F1E SAME AS F1 WITH EMERGENCY BACK UP 4'-0" 2'-0" 2" RE LED 1 MAX 40

WATTS

MINIMUM 4000

LUMENS

120 V DIM10 K METALUX 24FP LED

LITHONIA PANEL LED

PHILIPS FLUX PANEL

LED

F2 FLAT PANEL LED FIXTURE 4'-0" 1'-0" 2" RE LED 1 MAX 40

WATTS

MINIMUM 4000

LUMENS

120 V EB K METALUX 14FP LED

LITHONIA PANEL LED

PHILIPS FLUX PANEL

LED

F3 SHALLOW HEIGHT RECESSED LED DOWN

LIGHT.

7 1/2" 4" RE LED 1 MAX 20 WATT

MINIMUM 1200

LUMENS

120 V DIM10 O LITON

CH6SHL-18-UE-D10-CR6

SHL22WW-T35

OR APPROVED EQUAL

FILM VIEW

A216

RADIOGRAPHIC

AND

FLUOROSCOPIC

A217

TOILET

A218

RADIOGRAPHIC

A219

X-RAY

A220

CONTROL

A221

RADIOGRAPHIC

AND

FLUOROSCOPIC

A215

TOILET

A216C

CONTROL

A217AEQUIPMENT

STORAGE

A218C

TOILET

A219E

CONTROL

A219D

LASER PRINT

A219B

FILM STORAGE

A219C

DUMB WAITER

LOBBY

A219A

ELEC. CLOSET

A220A

CONTROL

A215A

CHASE

CH-A-7

7 6 5 3489

D D

A

B

C

2CL-10

PANEL 2C-R

PANEL 2C-L

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

VA FORM 08-6231

ARCHITECTS Drawing Title Project Title

Location

Date Checked Drawn

Project Number

Building Number

Drawing Number

CONSULTANTS

Dwg: Of:

657-18-110CORRECT WORKPLACE & LIFE SAFETY

ISSUES, ABATE ASBESTOS, & IMPROVE

WAYFINDING

SEPTEMBER 12, 2018

Building Name

JOHN COCHRAN DIVISION -

Revisions: Date:

3705 North 200th Street Elkhorn, Nebraska 68022

(402) 291-6941

15 Sunnen Drive Suite 104 St. Louis, MO 64143

(314) 645-1132

8802 South 135th Street, Suite 100 Omaha, NE 68138

(402) 861-4445

BID DOCUMENTS

FULLY SPRINKLERED

VETERANS

HEALTH

ADMINISTRATION

/1

/2

:3 :4

P

M

1-2-EP-101A

SECOND FLOOR - ELECTRICAL RENOVATION PLAN

ST. LOUIS, MO - VA JOHN COCHRAN

IMEG

66 79

BUILDING 1

STEWIE

N

O R HT

1/4" = 1'-0"1

SECOND FLOOR - ELECTRICAL RENOVATION PLAN

GENERAL NOTES :

1. REFER TO SHEET E001 FOR ELECTRICAL

SYMBOLS, APPLICABLE CODES, GENERAL

NOTES, RENOVATION NOTES AND

INSTALLATION NOTES.

KEYNOTES:

1. CONNECT NEW RECEPTACLE TO EXISTING

CIRCUIT PROTECTED AT DEMOLITION.

{LD1}

{LS1}

{LD1}

{LS1}

{LS1}

{LD1}

{LD1}

{LD1}

{LS1}

{LS1}

F

G

F

E

D

HH

I

J

J

K

LOUNGE

A601

OFFICE

A602

HAC

A603

NURSE

MANAGER

A604

MED. PREP.

A605

NURSE STATION

A606

NOUR.

A607

GI PROCEDURE

ROOM

A608

PROCEDURE

RM.

A609 PROCEDURE

RM.

A610

SCOPE

A610A

PROCEDURE

RM.

A611

PROCEDURE

RM.

A612

SCOPE

CLEANING

A613B

CLEAN

A614

SOILED

A615

ANTE RM.

A613A

CLEAN UTILITY

A611A

SCOPE

CLEANING

DIRTY SIDE

A613

CORRIDOR

H601

NURSE BREAK

RM.

A616

STORAGE

A617

TOILET

A616AWORKSTATION

A624

ELEC. CLOSET

A623C

STORAGE

A623B

STAIRWELL NO.

S602

TOILET

A623A

TOILET

A626A

OFFICE

A629

TOILET

A627A

TOILET

A628

OI&T

A629B

OI&T

A629C

OFFICE

A631

OFFICE

A632

BED RM.

A626

STORAGE

H606C

CORRIDOR

H603

OFFICE

A671

STAIRWELL NO.

S601

F.E. CLOSET

H606B

ELEC. CLOSET

A629A

ELEVATOR NO.

E5

CHASE

CH-A-6

CHASE

CH-A-7

CHASE

CH-A-8

CHASE

CH-A-9

CHASE

CH-A-10

CHASE

CH-A-12

CHASE

CH-A-11

CHASE

CH-A-13

CHASE

CH-A-16

CHASE

CH-A-17

CHASE

CH-A-18

CHASE

CH-A-19

F.E. CLOSET

H602A

EXISTING EC6A

EXISTING PANEL 6A

F1E/a

F1/a

F3/b F2

F1E/a

F1/a

F2

F1 a

F1E a

F1 a

F1 a

F3/b F3/b a b

F1E a

F1 a

F1 a

F1 a

F3/b F3/b

F3/b

F3/b

F3/b

F2

F1E/a

F1/a

F3/b

F3/b

F2

F1E

F1 a bab a bab

EXISTING PANEL E6C

EXISTING PANEL 6C

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

VA FORM 08-6231

ARCHITECTS Drawing Title Project Title

Location

Date Checked Drawn

Project Number

Building Number

Drawing Number

CONSULTANTS

Dwg: Of:

657-18-110CORRECT WORKPLACE & LIFE SAFETY

ISSUES, ABATE ASBESTOS, & IMPROVE

WAYFINDING

SEPTEMBER 12, 2018

Building Name

JOHN COCHRAN DIVISION -

Revisions: Date:

3705 North 200th Street Elkhorn, Nebraska 68022

(402) 291-6941

15 Sunnen Drive Suite 104 St. Louis, MO 64143

(314) 645-1132

8802 South 135th Street, Suite 100 Omaha, NE 68138

(402) 861-4445

BID DOCUMENTS

FULLY SPRINKLERED

VETERANS

HEALTH

ADMINISTRATION

/1

/2

:3 :4

P

M

1-6-EL-101A

SIXTH FLOOR - ELECTRICAL LIGHTING RENOVATION PLAN

ST. LOUIS, MO - VA JOHN COCHRAN

IMEG

67 79

BUILDING 1

STEWIE

N O R

HT

3/16" = 1'-0"1

SIXTH FLOOR - ELECTRICAL LIGHTING RENOVATION PLAN

GENERAL NOTES :

1. REFER TO SHEET E001 FOR ELECTRICAL

SYMBOLS, APPLICABLE CODES, GENERAL

NOTES, RENOVATION NOTES AND

INSTALLATION NOTES.

2. CONNECT F1E FIXTURES TO LIFE SAFETY

CIRCUIT FROM EXISTING PANEL ELS61.

3. CONNECT F1, F2, & F3 FIXTURES TO EXISTING

PANEL 6C CIRCUIT #20.

ALL LAMPS FOR THIS PROJECT SHALL BE FURNISHED AND INSTALLED BY THE ELECTRICAL CONTRACTOR UNLESS OTHERWISE NOTED.

CORRELATED COLOR TEMPERATURE 3500°.

LED LAMP COLOR RENDERING INDEX (CRI) AT OR ABOVE 85 FOR INTERIOR APPLICATIONS.

CATALOG NUMBER SHALL NOT BE CONSIDERED COMPLETE AND MATERIAL SHALL NOT BE ORDERED BY MANUFACTURER AND CATALOG NUMBER ONLY. THE COMPLETE DESCRIPTION AND THE SPECIFICATION SHALL BE COORDINATED WITH THE CATALOG NUMBER TO DETERMINE THE EXACT MATERIAL AND ACCESSORIES TO BE ORDERED. THE

FIRST MANUFACTURER LISTED IS THE BASIS FOR DESIGN.

REFER TO SPECIFICATION SECTIONS LIGHTING 26 51 00 FOR ADDITIONAL INFORMATION AND REQUIREMENTS.

HP - HIGH PERFORMANCE / LBF PRS - ELECTRONIC PROGRAM RAPID START BALLAST

ML - MULTI-LEVEL SWITCHING MV - MULTI-VOLTAGE ELECTRONIC 120V-277V

CSA - FINISH SELECTION BY ARCHITECT HL - HIGH / LOW LEVEL BALLAST DALI - DIGITAL DIMMING BALLAST

PAF - PAINT AFTER FABRICATION DIM10 - 0-10V DIMMING BALLAST EM - EMERGENCY BATTERY / BALLAST

FINISH: DIM07 - LINE DIMMING BALLAST EB - ELECTRONIC BALLAST

(TYPE) BALLAST: (TYPE) BALLAST:

RS - REGRESSED STEEL

RA - REGRESSED ALUMINUM O - OTHER (SEE DESCRIPTION)

FS - FLAT STEEL XLP - EXTENDED LIFE & OUTPUT R - HIGH IMPACT OR ACRYLIC

FA - FLAT ALUMINUM XL - EXTENDED LIFE N - NONE

DOOR: O - OTHER (SEE DESCRIPTION L - LOW IRIDESCENT SPECULAR ALUM.

CMH - CERAMIC METAL HALIDE K19 - KSH19 .156" ACRYLIC

O - OTHER (SEE DESCRIPTION) PSMH - PULSE START METAL HALIDE K - KSH12 .125" ACRYLIC

FR - FLANGED RECESSED SMH - SUPER METAL HALIDE P - POLYCARBONATE

PL - POLE MH - METAL HALIDE H - WALL WASHER

CV - COVE HS - HIGH PRESSURE SODIUM G - TEMPERED GLASS

UC - UNDER CABINET LED - LIGHT EMITTING DIODE F - FRESNEL

WL - WALL IN - INCANDESCENT D - PARABOLIC

CL - CEILING SURFACE HL - HALOGEN C - CLEAR ALZAK

SP - SUSPENDED CF - COMPACT FLUORESCENT B - BLACK BAFFLE

RE - RECESSED FL - FLUORESCENT A - .125 ACRYLIC

(MTG) MOUNTING: (TYPE) LAMP TECHNOLOGY: (L/L) LENS / LOUVER:

LUMINAIRE SCHEDULE

ITEM DESCRIPTION

DIMENSIONS

MTG

LAMPS BALLAST

L/L

APPROVED

MANUFACTURERL W H DIA. TYPE QTY MODEL VOLTS TYPE

F1 FLAT PANEL LED FIXTURE 4'-0" 2'-0" 2" RE LED 1 MAX 40

WATTS

MINIMUM 4000

LUMENS

120 V DIM10 K METALUX 24FP LED

LITHONIA PANEL LED

PHILIPS FLUX PANEL

LED

F1E SAME AS F1 WITH EMERGENCY BACK UP 4'-0" 2'-0" 2" RE LED 1 MAX 40

WATTS

MINIMUM 4000

LUMENS

120 V DIM10 K METALUX 24FP LED

LITHONIA PANEL LED

PHILIPS FLUX PANEL

LED

F2 FLAT PANEL LED FIXTURE 4'-0" 1'-0" 2" RE LED 1 MAX 40

WATTS

MINIMUM 4000

LUMENS

120 V EB K METALUX 14FP LED

LITHONIA PANEL LED

PHILIPS FLUX PANEL

LED

F3 SHALLOW HEIGHT RECESSED LED DOWN

LIGHT.

7 1/2" 4" RE LED 1 MAX 20 WATT

MINIMUM 1200

LUMENS

120 V DIM10 O LITON

CH6SHL-18-UE-D10-CR6

SHL22WW-T35

OR APPROVED EQUAL

LIGHTING SEQUENCE OF OPERATION

PLAN ID LIGHTING SWITCHED

{LD1} Sequence: Dimmed lights are controlled in this space.

ON: The lights turned on using a wall control.

ADJUST: The lights are raised / lowered using a wall controller.

OFF: The lights turned off using a wall controller.

{LS1} Sequence: Switched lights are controlled in this space.

ON: The lights turn on using switches.

OFF: The lights turn off using switches.

E

E

A R

D

SD

SD

SD

SD

SD

A R

D

E

EE

E

SD

F

G

F

E

D

HH

I

J

J

K

LOUNGE

A601

OFFICE

A602

HAC

A603

NURSE

MANAGER

A604

MED. PREP.

A605

NURSE STATION

A606

NOUR.

A607

GI PROCEDURE

ROOM

A608

PROCEDURE

RM.

A609 PROCEDURE

RM.

A610

SCOPE

A610A

PROCEDURE

RM.

A611

PROCEDURE

RM.

A612

SCOPE

CLEANING

A613B

CLEAN

A614

SOILED

A615

ANTE RM.

A613A

CLEAN UTILITY

A611A

SCOPE

CLEANING

DIRTY SIDE

A613

CORRIDOR

H601

NURSE BREAK

RM.

A616

STORAGE

A617

TOILET

A616AWORKSTATION

A624

ELEC. CLOSET

A623C

STORAGE

A623B

STAIRWELL NO.

S602

TOILET

A623A

TOILET

A626A

OFFICE

A629

TOILET

A627A

TOILET

A628

OI&T

A629B

OI&T

A629C

OFFICE

A631

OFFICE

A632

BED RM.

A626

STORAGE

H606C

CORRIDOR

H603

OFFICE

A671

STAIRWELL NO.

S601

F.E. CLOSET

H606B

ELEC. CLOSET

A629A

ELEVATOR NO.

E5

CHASE

CH-A-6

CHASE

CH-A-7

CHASE

CH-A-8

CHASE

CH-A-9

CHASE

CH-A-10

CHASE

CH-A-12

CHASE

CH-A-11

CHASE

CH-A-13

CHASE

CH-A-16

CHASE

CH-A-17

CHASE

CH-A-18

CHASE

CH-A-19

F.E. CLOSET

H602A

EXISTING EC6A

EXISTING PANEL 6A

REHEAT COIL

1-TU-6-8

6CA -20,22,24

REHEAT COIL

1-TU-6-7

6CA -19,21,23

REHEAT COIL

1-TU-6-6

6CA -14

REHEAT COIL

1-TU-6-5

6CA -13,15,17

REHEAT COIL

1-TU-6-4

6CA -8,10,12

REHEAT COIL

1-TU-6-3

6CA -7,9,11

REHEAT COIL

1-TU-6-2

6CA -2,4,6

REHEAT COIL

1-TU-6-1

6CA -1,3,5

FDS-30

FDS-30 FDS-30

FDS-60

FDS-60

MX-1FDS-30

FDS-30

EXISTING PANEL E6C

EXISTING PANEL 6C

1PANEL 6CA

BRANCH CIRCUIT WIRING KEY

WIRE

ID 2 WIRE 3 WIRE 4 WIRE

THHW/THWN COPPER

CONDUCTORS

EQUIPMENT

GROUNDING

CONDUCTOR CONDUIT

A# 2#12 3#12 4#12 1#12 3/4"

B# 2#10 3#10 4#10 1#10 3/4"

C# 2#8 3#8 4#8 1#10 3/4"

D# 2#6 3#6 4#6 1#10 1"

E# 2#4 3#4 4#4 1#8 1 1/4"

G# 2#2 3#2 4#2 1#8 1 1/4"

H# 2#1 3#1 4#1 1#6 1 1/2"

J# 2#1/0 3#1/0 4#1/0 1#6 2"

ALL BRANCH CIRCUITS SHALL INCLUDE THE EQUIPMENT GROUND

CONDUCTOR

F# 2#3 3#3 4#3 1#8 1 1/4" th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

VA FORM 08-6231

ARCHITECTS Drawing Title Project Title

Location

Date Checked Drawn

Project Number

Building Number

Drawing Number

CONSULTANTS

Dwg: Of:

657-18-110CORRECT WORKPLACE & LIFE SAFETY

ISSUES, ABATE ASBESTOS, & IMPROVE

WAYFINDING

SEPTEMBER 12, 2018

Building Name

JOHN COCHRAN DIVISION -

Revisions: Date:

3705 North 200th Street Elkhorn, Nebraska 68022

(402) 291-6941

15 Sunnen Drive Suite 104 St. Louis, MO 64143

(314) 645-1132

8802 South 135th Street, Suite 100 Omaha, NE 68138

(402) 861-4445

BID DOCUMENTS

FULLY SPRINKLERED

VETERANS

HEALTH

ADMINISTRATION

/1

/2

:3 :4

P

M

1-6-EP-101A

SIXTH FLOOR - ELECTRICAL RENOVATION PLAN

ST. LOUIS, MO - VA JOHN COCHRAN

IMEG

68 79

BUILDING 1

STEWIE

N O R

HT

3/16" = 1'-0"1

SIXTH FLOOR - ELECTRICAL RENOVATION PLAN

GENERAL NOTES :

1. REFER TO SHEET E001 FOR ELECTRICAL

SYMBOLS, APPLICABLE CODES, GENERAL

NOTES, RENOVATION NOTES AND

INSTALLATION NOTES.

2. REFER TO 1-10-EP-101A FOR DISCONNECT

SCHEDULE.

KEYNOTES:

1. INSTALL 150A 3P CIRCUIT BREAKER INTO

EXISTING PANEL 6C TO FEED PANEL 6CA.

UTILIZE 4# 1/0 & 1#6 GND IN 1 1/2" C FOR

CONNECTION.

2. CONNECT FIRE SMOKE DAMPERS TO PANEL

E6C CIRCUIT #9. UTILIZE 2#12 & 1#12 GND IN 3/4"

C FOR CONNECTION.

[Key*:]

Total Amps: 126.67 116.67 116.67

Total Load: 15.2 kVA 14 kVA 14 kVA

29 SPACE -- -- -- 0 0 -- -- -- SPACE 30

27 SPACE -- -- -- 0 0 -- -- -- SPACE 28

25 SPACE -- -- -- 0 0 -- -- -- SPACE 26

23 -- -- -- -- 1.5 2.5 -- -- -- -- 24

21 -- -- -- -- 1.5 2.5 -- -- -- -- 22

19 REHEAT COIL 1-TU-6-7 20 A 3 A4 1.5 2.5 A4 3 20 A REHEAT COIL 1-TU-6-8 20

17 -- -- -- -- 2.67 0 1 20 A SPARE 18

15 -- -- -- -- 2.67 0 1 20 A SPARE 16

13 REHEAT COIL 1-TU-6-5 30 A 3 B4 2.67 1.2 A2 1 20 A REHEAT COIL 1-TU-6-6 14

11 -- -- -- -- 0.67 3 -- -- -- -- 12

9 -- -- -- -- 0.67 3 -- -- -- -- 10

7 REHEAT COIL 1-TU-6-3 20 A 3 A4 0.67 3 C4 3 35 A REHEAT COIL 1-TU-6-4 8

5 -- -- -- -- 2.17 1.5 -- -- -- -- 6

3 -- -- -- -- 2.17 1.5 -- -- -- -- 4

1 REHEAT COIL 1-TU-6-1 25 A 3 B4 2.17 1.5 A4 3 20 A REHEAT COIL 1-TU-6-2 2

CKT NO. LOAD DESCRIPTION

OVERCURRENT

PROTECTION

AMPS P

WIRE

ID

A B C

WIRE

ID

OVERCURRENT

PROTECTION

P AMPS LOAD DESCRIPTION CKT NO.

Panel Notes:

LOCATION: ELEC. CLOSET A623C DEMAND: 43.2 kVA

SCCR: 10,000 WIRE: 4

FED FROM: EXISTING PANEL E6C GROUND BUS PHASE: 3

MOUNTING: SURFACE SOLID NEUTRAL VOLTS: 120/208 Wye

TYPE: BOLT-ON MAIN: 225 A/MLO

PANEL NAME: 6CA CONNECTED 43.2 kVA

SD

SD

SD

ARAR

E

E

F

G

F

E

H H

I

STAIRWELL NO.

S901

OFFICE

A920

OFFICE

A919

OFFICE

A914

STORAGE

CLOSET

A915

CLOSET

A912B

LAB

A912

CLOSET

A913

LAB

A911

STAIRWELL NO.

S902

F.E. CLOSET

H901A

CORRIDOR

H901

LAB

A905

LAB

A906

OFFICE

A903

LAB

A902

STORAGE

A912A

ELEC PANELS

A904

CHASE

CH-A-1

CHASE

CH-A-4

CHASE

CH-A-5

1-RTU-1

RTU

RETURN

RTU

RETURN

RTU

SUPPLY1

4 4

1-SH1 HUMIDIFIER

FDS-100RH

FDS-400R

W

VFD-5VFD-5

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

VA FORM 08-6231

ARCHITECTS Drawing Title Project Title

Location

Date Checked Drawn

Project Number

Building Number

Drawing Number

CONSULTANTS

Dwg: Of:

657-18-110CORRECT WORKPLACE & LIFE SAFETY

ISSUES, ABATE ASBESTOS, & IMPROVE

WAYFINDING

SEPTEMBER 12, 2018

Building Name

JOHN COCHRAN DIVISION -

Revisions: Date:

3705 North 200th Street Elkhorn, Nebraska 68022

(402) 291-6941

15 Sunnen Drive Suite 104 St. Louis, MO 64143

(314) 645-1132

8802 South 135th Street, Suite 100 Omaha, NE 68138

(402) 861-4445

BID DOCUMENTS

FULLY SPRINKLERED

VETERANS

HEALTH

ADMINISTRATION

/1

/2

:3 :5

P

M

1-9-EP-101A

NINTH FLOOR - ELECTRICAL RENOVATION PLAN

ST. LOUIS, MO - VA JOHN COCHRAN

IMEG

69 79

BUILDING 1

STEWIE

N

O R HT

1/4" = 1'-0"1

NINTH FLOOR - ELECTRICAL RENOVATION PLAN

GENERAL NOTES :

1. REFER TO SHEET E001 FOR ELECTRICAL

SYMBOLS, APPLICABLE CODES, GENERAL

NOTES, RENOVATION NOTES AND

INSTALLATION NOTES.

2. INSTALL LIGHTNING PROTECTION FOR RTU.

PROVIDE AIR TERMINALS EVERY 25' AND AT

EACH CORNER OF EQUIPMENT. CONNECT

GROUND CONDUCTOR TO EXISTING SYSTEM.

ALL ADDITIONS FOR LIGHTNING PROTECTION

SHALL BE TIED INTO THE EXISTING BUILDING

LIGHTNING PROTECTION SYSTEM. REFER TO

SPECIFICATION 26 41 00.

KEYNOTES:

1. DUCT TYPE SMOKE DETECTOR SUPPLY AND

RETURN FOR RTU SHUT DOWN.

2. MOUNT ADDRESSIBLE RELAY WITHIN 3' OF

CONTROLLER FOR RTU SHUT DOWN.

3. PROVIDE 120V POWER TO RTU FOR CONTROLS

AND COMPONENTS. COORDINATE FINAL

LOCATIONS WITH MECHANICAL CONTRACTOR.

UTILIZE SPARE 20A CIRCUIT FROM EXISTING

PANEL IN ROOM A928 WITH 2#10 & 1#10GND IN

3/4" C.

4. RAILING MOUNTED LIGHTNING PROTECTION

AIR TERMINAL.

5. EQUIPMENT MOUNTED LIGHTNING

PROTECTION AIR TERMINAL.

6. FEED -SH-1 HUMIDIFIER FROM 5MCC1

LOCATED IN 5TH FLOOR INTERSTIAL SPACE RM

D505. UTILIZE SPACE IN 5MCC1 TO CONNECT

TO BUSS, INSTALL FDS-100H DISCONNECT AT

5MCC1, UTILIZE 4#1 & 1#6 GND IN 1 1/2" C FOR

CONNECTION. STRUT MOUNT FDS-100RH AT

THE UNIT ON THE ROOF PROTECT WITH 90A

FUSE. REFER TO 1-10-EP101A FOR

DISCONNECT SCHEDULE.

7. FEED 1-RTU-1 FROM MCC-10 LOCATED IN 10TH

FLOOR MECHANICAL PENTHOUSE. UTILIZE

SPACE IN MCC-10, INSTALL A FDS-400 AND TWO

FDS-30 DISCONNECTS AT MCC-10 TO

CONNNECT TO BUSS FOR 208V THREE PHASE

POWER FOR MAIN CONNECTION TO 1-RTU-1,

THE SUPPLY FAN, AND THE RETURN FAN.

UTILIZE 4#500KCMIL & 1#3 GND IN 3" C FOR

MAIN CONNECTION, UTILIZE 4#10 & 1#10 GND IN

3/4" C FOR SUPPLY FAN, UTILIZE 4#10 & 1#10

GND IN 3/4" C FOR RETURN FAN. STRUT MOUNT

FDS-400R AND BOTH VFD-5 AT THE UNIT ON

THE ROOF PROTECT FDS-400R WITH 350A

FUSE. REFER TO 1-10-EP101A FOR

DISCONNECT SCHEDULE AND VFD SCHEDULE.

COORDINATE FINAL LOCATIONS OF POWER

CONNECTIONS TO 1-RTU-1 WITH MECHANICAL

CONTRACTOR.

8. INSTALL WEATHERPROOF RECEPTACLE STRUT

MOUNTED. UTILIZE SPARE 20A CIRCUIT

BREAKER FROM EXISTING PANEL IN ROOM

A928 WITH 2#10 & 1#10 GND IN 3/4" C.

STAIRWELL NO.

SP02

9 6

I

10 8

1-EF1

FDS-30R

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

VA FORM 08-6231

ARCHITECTS Drawing Title Project Title

Location

Date Checked Drawn

Project Number

Building Number

Drawing Number

CONSULTANTS

Dwg: Of:

657-18-110CORRECT WORKPLACE & LIFE SAFETY

ISSUES, ABATE ASBESTOS, & IMPROVE

WAYFINDING

SEPTEMBER 12, 2018

Building Name

JOHN COCHRAN DIVISION -

Revisions: Date:

3705 North 200th Street Elkhorn, Nebraska 68022

(402) 291-6941

15 Sunnen Drive Suite 104 St. Louis, MO 64143

(314) 645-1132

8802 South 135th Street, Suite 100 Omaha, NE 68138

(402) 861-4445

BID DOCUMENTS

FULLY SPRINKLERED

VETERANS

HEALTH

ADMINISTRATION

/1

/2

:3 :5

P

M

1-10-EP-101A

TENTH FLOOR - ELECTRICAL RENOVATION PLAN

ST. LOUIS, MO - VA JOHN COCHRAN

IMEG

70 79

BUILDING 1

STEWIE

N

O R HT

1/8" = 1'-0"1

TENTH FLOOR - ELECTRICAL RENOVATION PLAN

GENERAL NOTES :

1. REFER TO SHEET E001 FOR ELECTRICAL

SYMBOLS, APPLICABLE CODES, GENERAL

NOTES, RENOVATION NOTES AND

INSTALLATION NOTES.

2. INSTALL LIGHTNING PROTECTION FOR 1-EF1

AND ASSOCIATED DUCT STACK. PROVIDE AIR

TERMINALS AT THE EXHAUST FAN AND THE

TOP OF THE DUCT STACK. CONNECT GROUND

CONDUCTOR TO EXISTING SYSTEM. ALL

ADDITIONS FOR LIGHTNING PROTECTION

SHALL BE TIED INTO THE EXISTING BUILDING

LIGHTNING PROTECTION SYSTEM. REFER TO

SPECIFICATION 26 41 00.

FS - FUSED SWITCH

MX - MANUAL SWITCH

MS - MANUAL STARTER

SS - SOLID STATE

RV - REDUCED VOLTAGE AUTOXFMR

SW - 2 SPEED, 1 WINDING

TW - 2 SPEED, 2 WINDING

RE - REVERSING HL - HANDLE PADLOCK HASP

YD - WYE - DELTA S/N - INSULATED NEUTRAL ASSEMBLY SS - START-STOP PUSHBUTTON IN DOOR

FV - FULL VOLTAGE *TA - TWO CONVERTIBLE AUXILIARY CONTACTS EI - ELECTRICAL INTERLOCK (2)-N.O. & (2)-N.C.

STARTER TYPE: *RP - RED (RUN) PILOT LIGHT IN DOOR FA - 4-CONVERTIBLE AUXILIARY CONTACTS

*HA - HAND-OFF-AUTO IN DOOR GP - GREEN (OFF) PILOT LIGHT IN DOOR

CB - CIRCUIT BREAKER *EO - ELECTRONIC OVERLOAD (3 PHASE MOTORS) TS - 2 SPEED SELECTOR SWITCH IN DOOR

NF - NON-FUSED *CT - CONTROL TRANSFORMER, FUSED 120V TO - MELTING THERMAL OVERLOADS (1 PHASE)

FU - FUSED SA - STANDARD ACCESSORIES (INCLUDES * ITEMS) PF - PHASE LOSS PROTECTION (5 HP OR GREATER...

DISCONNECT TYPE: REMARKS:

NOTE: ALL DISCONNECTS (EXCEPT MANUAL STARTERS) SHALL BE HEAVY DUTY TYPE.

E - DISCONNECT AND STARTER SCHEDULE

ITEM

DISCONNECT TYPE &

RATING CIRCUIT

VOLTAGE POLES

STARTER NEMA

ENCLOSURE REMARKS APPROVED MANUFACTURERSTYPE RATING NEMA SIZE TYPE

FDS-30 FU 30 A 208 V 3 1 FUSED TO MATCH OCPD AT

PANEL

MINIMUM 20A FUSE

SA

SQUARE D 3110

EATON TYPE DH

GENERAL ELECTRIC TYPE TH

SIEMENS TYPE HF

FDS-30R FU 30 A 208 V 3 3R REFER TO KEYNOTE FOR

FUSE SIZE

SA

SQUARE D 3110

EATON TYPE DH

GENERAL ELECTRIC TYPE TH

SIEMENS TYPE HF

FDS-60 FU 60 A 208 V 3 1 FUSED TO MATCH OCPD AT

PANEL

SA

SQUARE D 3110

EATON TYPE DH

GENERAL ELECTRIC TYPE TH

SIEMENS TYPE HF

FDS-100H FU 100 A 480 V 3 1 REFER TO KEYNOTE FOR

FUSE SIZE

SA

SQUARE D 3110

EATON TYPE DH

GENERAL ELECTRIC TYPE TH

SIEMENS TYPE HF

FDS-100RH FU 100 A 480 V 3 3R REFER TO KEYNOTE FOR

FUSE SIZE

SA

SQUARE D 3110

EATON TYPE DH

GENERAL ELECTRIC TYPE TH

SIEMENS TYPE HF

FDS-400 FU 400 A 208 V 3 1 REFER TO KEYNOTE FOR

FUSE SIZE

SA

SQUARE D 3110

EATON TYPE DH

GENERAL ELECTRIC TYPE TH

SIEMENS TYPE HF

FDS-400R FU 400 A 208 V 3 3R REFER TO KEYNOTE FOR

FUSE SIZE

SQUARE D 3110

EATON TYPE DH

GENERAL ELECTRIC TYPE TH

SIEMENS TYPE HF

MX-1 NF 30 A 120 V 1 0 MX 1 RP, TA, TO SQUARE D 2510 KG1

EATON TYPE B2

GENERAL ELECTRIC TYPE TC

SIEMENS TYPE MMS

KEYNOTES:

1. EQUIPMENT MOUNTED LIGHTNING

PROTECTION AIR TERMINAL.

2. FEED 1-EF1 FROM MCC-10 LOCATED IN 10TH

FLOOR MECHANICAL PENTHOUSE. UTILIZE

SPACE IN MCC-10, INSTALL FDS-30

DISCONNECT AT MCC-10 TO CONNNECT TO

BUSS, UTILIZE 4#12 & 1#12 GND IN 3/4" C FOR

CONNECTION. STRUT MOUNT FDS-30R AT THE

UNIT ON THE ROOF PROTECT WITH 20A FUSE.

REFER TO 1-10-EP101A FOR DISCONNECT

SCHEDULE.

420 - 4-20mA FOLLOWER

PN - 3-15 PSI TRANSDUCER

CONTROL: MOL - MULTIPLE MOTOR OVERLOADS HAR - PASSIVE HARMONIC FILTER

CB - CIRCUIT BREAKER TO - MELTING THERMAL OVERLOADS LR - INPUT LINE REACTOR

FDS - FUSED DISCONNECT SWITCH *HA - HAND-OFF-AUTO DOOR SWITCH RFT - REMOTE FAULT TRIP

DS - DISCONNECT SWITCH *CT - CONTROL TRANSFORMER, FUSED, 120V RDR - REMOTE DRIVE RUN

LINE DISCONNECT: *ET - ELECTRONIC THERMAL OVERLOADS RSS - REMOTE START-STOP

18PWM - 18 PULSE PWM *MA - MANUAL SPEED ADJUSTMENT *SHZ - SKIP FREQUENCY CAPABILITY

12PWM - 12 PULSE PWM (INCLUDES * ITEMS) ISO - ISOLATION TRANSFORMER

PWM - PULSE WIDTH MODULATED SA - STANDARD ACCESSORIES TA - TWO CONVERTIBLE AUXILIARY CONTACTS

STARTER TYPE: REMARKS:

VARIABLE FREQUENCY DRIVE SCHEDULE

ITEM LINE DISC.

DRIVE

BYPASS CONTROL

VOLTAGE DRIVE

NEMA ENCLOSURE REMARKS

APPROVED

MANUFACTURERSINPUT OUTPUT PH.

H.P.

RATING TYPE

VFD-5 FDS 3

CONTACT

420 208 V 208 V 3 7.5 PWM 3R SA LR

VARIABLE

TORQUE

TOSHIBA Q9 SERIES

ABB ACH 550 SERIES

ALLEN BRADLEY POWERFLEX

40 SERIES

DANFOSS VLT6000 SERIES

G.E. AF300 P11 SERIES

SQUARE D E-FLEX

CUTLER-HAMMER ECS HVX

SERIES

YASKAWA E7

B

C

D

E

F

G

A

2 1

PANEL PP-F

MAIN DIST PANEL

PANEL LP-A

EMER. DISC.

W

W

P

P

FACP

+48"

A A

+48"

+48"

+48"

PANEL PP-C

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

VA FORM 08-6231

ARCHITECTS Drawing Title Project Title

Location

Date Checked Drawn

Project Number

Building Number

Drawing Number

CONSULTANTS

Dwg: Of:

657-18-110CORRECT WORKPLACE & LIFE SAFETY

ISSUES, ABATE ASBESTOS, & IMPROVE

WAYFINDING

SEPTEMBER 12, 2018

Building Name

JOHN COCHRAN DIVISION -

Revisions: Date:

3705 North 200th Street Elkhorn, Nebraska 68022

(402) 291-6941

15 Sunnen Drive Suite 104 St. Louis, MO 64143

(314) 645-1132

8802 South 135th Street, Suite 100 Omaha, NE 68138

(402) 861-4445

BID DOCUMENTS

VETERANS

HEALTH

ADMINISTRATION

/1

/2

:3 :5

P

M

7-1-ED-101A

FIRST FLOOR - ELECTRICAL DEMOLITION PLAN

ST. LOUIS MO - JOHN COCHRAN

IMEG

71 79

BUILDING 7

STEWIE

N

O R HT

1/8" = 1'-0"1

FIRST FLOOR - ELECTRICAL DEMOLITION PLAN

GENERAL NOTES :

1. REFER TO SHEET E001 FOR ELECTRICAL

SYMBOLS, APPLICABLE CODES, GENERAL

NOTES, RENOVATION NOTES AND

INSTALLATION NOTES.

KEYNOTES:

1. DISCONNECT COLD ROOM AND FREEZER

ROOM CONDENSER UNITS. REMOVE CONDUIT

AND CONDUCTORS BACK TO SOURCE.

DEDUCT ALTERNATE

OC

OC

OC

{LS1}

{LS1}

{LS1}

B

C

D

E

F

G

A

2 1

PANEL PP-F

MAIN DIST PANEL

PANEL LP-A

FACP

F1E

F1

F1E/5

F1/5

F2

D

D

D

PANEL PP-C

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

VA FORM 08-6231

ARCHITECTS Drawing Title Project Title

Location

Date Checked Drawn

Project Number

Building Number

Drawing Number

CONSULTANTS

Dwg: Of:

657-18-110CORRECT WORKPLACE & LIFE SAFETY

ISSUES, ABATE ASBESTOS, & IMPROVE

WAYFINDING

SEPTEMBER 12, 2018

Building Name

JOHN COCHRAN DIVISION -

Revisions: Date:

3705 North 200th Street Elkhorn, Nebraska 68022

(402) 291-6941

15 Sunnen Drive Suite 104 St. Louis, MO 64143

(314) 645-1132

8802 South 135th Street, Suite 100 Omaha, NE 68138

(402) 861-4445

BID DOCUMENTS

VETERANS

HEALTH

ADMINISTRATION

/1

/2

:3 :5

P

M

7-1-EL-101A

FIRST FLOOR - ELECTRICAL LIGHTING RENOVATION PLAN

ST. LOUIS MO - JOHN COCHRAN

IMEG

72 79

BUILDING 7

STEWIE

N

O R HT

1/8" = 1'-0"1

FIRST FLOOR - ELECTRICAL LIGHTING RENOVATION PLAN

ALL LAMPS FOR THIS PROJECT SHALL BE FURNISHED AND INSTALLED BY THE ELECTRICAL CONTRACTOR UNLESS OTHERWISE NOTED.

CORRELATED COLOR TEMPERATURE 3500°.

LED LAMP COLOR RENDERING INDEX (CRI) AT OR ABOVE 85 FOR INTERIOR APPLICATIONS.

CATALOG NUMBER SHALL NOT BE CONSIDERED COMPLETE AND MATERIAL SHALL NOT BE ORDERED BY MANUFACTURER AND CATALOG NUMBER ONLY. THE COMPLETE DESCRIPTION AND THE SPECIFICATION SHALL BE COORDINATED WITH THE CATALOG NUMBER TO DETERMINE THE EXACT MATERIAL AND ACCESSORIES TO BE ORDERED. THE

FIRST MANUFACTURER LISTED IS THE BASIS FOR DESIGN.

REFER TO SPECIFICATION SECTIONS LIGHTING 26 51 00 FOR ADDITIONAL INFORMATION AND REQUIREMENTS.

HP - HIGH PERFORMANCE / LBF PRS - ELECTRONIC PROGRAM RAPID START BALLAST

ML - MULTI-LEVEL SWITCHING MV - MULTI-VOLTAGE ELECTRONIC 120V-277V

CSA - FINISH SELECTION BY ARCHITECT HL - HIGH / LOW LEVEL BALLAST DALI - DIGITAL DIMMING BALLAST

PAF - PAINT AFTER FABRICATION DIM10 - 0-10V DIMMING BALLAST EM - EMERGENCY BATTERY / BALLAST

FINISH: DIM07 - LINE DIMMING BALLAST EB - ELECTRONIC BALLAST

(TYPE) BALLAST: (TYPE) BALLAST:

RS - REGRESSED STEEL

RA - REGRESSED ALUMINUM O - OTHER (SEE DESCRIPTION)

FS - FLAT STEEL XLP - EXTENDED LIFE & OUTPUT R - HIGH IMPACT OR ACRYLIC

FA - FLAT ALUMINUM XL - EXTENDED LIFE N - NONE

DOOR: O - OTHER (SEE DESCRIPTION L - LOW IRIDESCENT SPECULAR ALUM.

CMH - CERAMIC METAL HALIDE K19 - KSH19 .156" ACRYLIC

O - OTHER (SEE DESCRIPTION) PSMH - PULSE START METAL HALIDE K - KSH12 .125" ACRYLIC

FR - FLANGED RECESSED SMH - SUPER METAL HALIDE P - POLYCARBONATE

PL - POLE MH - METAL HALIDE H - WALL WASHER

CV - COVE HS - HIGH PRESSURE SODIUM G - TEMPERED GLASS

UC - UNDER CABINET LED - LIGHT EMITTING DIODE F - FRESNEL

WL - WALL IN - INCANDESCENT D - PARABOLIC

CL - CEILING SURFACE HL - HALOGEN C - CLEAR ALZAK

SP - SUSPENDED CF - COMPACT FLUORESCENT B - BLACK BAFFLE

RE - RECESSED FL - FLUORESCENT A - .125 ACRYLIC

(MTG) MOUNTING: (TYPE) LAMP TECHNOLOGY: (L/L) LENS / LOUVER:

LUMINAIRE SCHEDULE

ITEM DESCRIPTION

DIMENSIONS

MTG

LAMPS BALLAST

L/L

APPROVED

MANUFACTURERL W H DIA. TYPE QTY MODEL VOLTS TYPE

F1 FLAT PANEL LED FIXTURE 4'-0" 2'-0" 2" RE LED 1 MAX 40

WATTS

MINIMUM 4000

LUMENS

120 V EB K METALUX 24FP LED

LITHONIA PANEL LED

PHILIPS FLUX PANEL

LED

F1E SAME AS F1 WITH BATTERY BACK UP 4'-0" 2'-0" 2" RE LED 1 MAX 40

WATTS

MINIMUM 4000

LUMENS

120 V EM K METALUX 24FP LED

LITHONIA PANEL LED

PHILIPS FLUX PANEL

LED

F2 FLAT PANEL LED FIXTURE 4'-0" 1'-0" 2" RE LED 1 MAX 40

WATTS

MINIMUM 4000

LUMENS

120 V EB K METALUX 14FP LED

LITHONIA PANEL LED

PHILIPS FLUX PANEL

LED

GENERAL NOTES :

1. REFER TO SHEET E001 FOR ELECTRICAL

SYMBOLS, APPLICABLE CODES, GENERAL

NOTES, RENOVATION NOTES AND

INSTALLATION NOTES.

2. ALL LIGHTING SHALL BE FED FROM EXISTING

PANEL PP-C UNLESS NOTED OTHERWISE.

REFER TO 7-1-EP-101 FOR PANEL SCHEDULE.

DEDUCT ALTERNATE

LIGHTING SEQUENCE OF OPERATION

PLAN ID LIGHTING SWITCHED

{LS1} Sequence: Switched lights are controlled in this space.

ON: The lights are turn on by occupancy sensor.

OFF: After the space has been vacant for 15 minutes, the lights will automatically turn off.

ADDITIONAL CONTROL: This space will have contact closure outputs available for HVAC unoccupied control.

A1 V1

V1

SD

SD

SD

CALL CENTER

CALL CENTER

SAFETY &

OCCUPATIONAL

HEALTH MGR.

CALL CENTER

OFFICE

5A

OFFICE

3A

INDUSTRIAL

HYGIENIST

EMERGENCY

MANAGEMENT

OFFICE

OFFICE

1A

OFFICE

2A

OFFICE

CONTROLLED

TEMP. RM.

SAFETY &

OCCUPATIONAL

HEALTH

EQUIPMENT RM.

ELEC. CLOSET

OI&T

CONTROLLED

TEMP. RM.

18A

MECH. RM.

ACCESS

OFFICE

HAC

TOILET, MALE

TOILET, FEMALE

BREAK ROOM

STORAGE

CORRIDOR

C101

OFFICE

MECH. RM.

ACCESS

OFFICE

OI&T

1B

B

C

D

E

F

G

A

8 SF

CHASE

CH-1

1-EF2

PP-C-11

LOCATED

ON ROOF

PANEL PP-F

MAIN DIST PANEL

PANEL LP-A

EMER. DISC.

FACP

PANEL PP-C

PP-C-12

PP-C-12

MX-1

th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e e ig h th in c h o n e fo o t

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

VA FORM 08-6231

ARCHITECTS Drawing Title Project Title

Location

Date Checked Drawn

Project Number

Building Number

Drawing Number

CONSULTANTS

Dwg: Of:

657-18-110CORRECT WORKPLACE & LIFE SAFETY

ISSUES, ABATE ASBESTOS, & IMPROVE

WAYFINDING

SEPTEMBER 12, 2018

Building Name

JOHN COCHRAN DIVISION -

Revisions: Date:

3705 North 200th Street Elkhorn, Nebraska 68022

(402) 291-6941

15 Sunnen Drive Suite 104 St. Louis, MO 64143

(314) 645-1132

8802 South 135th Street, Suite 100 Omaha, NE 68138

(402) 861-4445

BID DOCUMENTS

VETERANS

HEALTH

ADMINISTRATION

/1

/2

:3 :5

P

M

7-1-EP-101A

FIRST FLOOR - ELECTRICAL RENOVATION PLAN

ST. LOUIS MO - JOHN COCHRAN

IMEG

73 79

BUILDING 7

STEWIE

N

O R HT

1/8" = 1'-0"1

FIRST FLOOR - ELECTRICAL RENOVATION PLAN

GENERAL NOTES :

1. REFER TO SHEET E001 FOR ELECTRICAL

SYMBOLS, APPLICABLE CODES, GENERAL

NOTES, RENOVATION NOTES AND

INSTALLATION NOTES.

KEYNOTES:

1. EXISTING FIRE ALARM MANUFACTURER:

HONEYWELL NOTIFIER. ANY ADDITIONS TO THE

EXISTING FIRE ALARM SYSTEM MUST BE

COMPATIBLE AND ALLOW FULL OPERATION.

2. PROVIDE ELECTRICAL CONNECTION TO EF-1

LOCATED ON ROOF. PROVIDE ADDITIONAL

RELAYS IN RESTROOM OCCUPANCY SENSORS

FOR SIGNAL TO EF-1. COORDINATE FINAL

CONNECTIONS WITH MECHANICAL

CONTRACTOR. INSTALL 120V SINGLE PHASE

LOCAL DISCONNECT AT EXHAUST FAN,

SQUARE D 2510 KG1 OR APPROVED EQUAL, IN

NEMA 3R ENCLOSURE.

1.06 kVA TOTAL KVA

17 EXISTING LOAD 0 kVA 2 30 A

16 EXISTING LOAD 0 kVA 3 30 A

15 EXISTING LOAD 0 kVA 2 30 A

14 EXISTING LOAD 0 kVA 3 30 A

13 SPACE 0 kVA -- -- -- --

12 RECEPTACLES 0.36 kVA 1 20 A

11 1-EF2 0.5 kVA 1 20 A

10 EXISTING LOAD 0 kVA 1 20 A

9 EXISTING LOAD 0 kVA 1 20 A

8 EXISTING LOAD 0 kVA 1 20 A

7 EXISTING LOAD 0 kVA 1 20 A

6 EXISTING LOAD 0 kVA 1 20 A

5 LIGHTING 0.2 kVA 1 20 A

4 EXISTING LOAD 0 kVA 2 20 A

3 EXISTING LOAD 0 kVA 3 70 A

2 EXISTING LOAD 0 kVA 3 20 A

1 EXISTING LOAD 0 kVA 3 20 A

CKT LOAD DESCRIPTION

ADDED

LOAD KVA POLES

TRIP

RATING TYPE ACCESSORIES

Notes: UTLIZE EXISTING CIRCUIT BREAKERS FOR NEW LOADS

CB - CIRCUIT BREAKER

CLB - CURRENT LIMITING BREAKER

ECB - ELECTRONIC TRIP BREAKER ZI - ZONE INTERLOCK

MCB - MOLDED CASE BREAKER ST - SHUNT TRIP (120V COIL)

BPS - BOLTED PRESSURE SWITCH GFI - GROUND FAULT PROTECTION

FS - HEAVY DUTY FUSED SWITCH DPM - DIGITAL POWER METER

DISCONNECT TYPE: ACCESSORIES:

SCCR: EXISTING

LOCATION: RM 17 WIRE: 4

FED FROM: MDF PHASE: 3

MOUNTING: SURFACE GROUND BUS VOLTS: 120/208 Wye

TYPE: BOLT-ON SOLID NEUTRAL MAIN: 225 A

EXISTING PANEL: PP-C

DEDUCT ALTERNATE

CB

CB

CB

CB

CB

CB

CB

CB

CB

CB

CB

CB

CB

CB

CB

CB