E007 - ELECTRCIAL - PANEL SCHEDULES.pdf

PDF 340 KB Posted

Attached to
Y1DA--508-22-105 | 6th Floor CLC 16-Bed Bldg. C
Solicitation number
36C24725R0029
Issued by

About this file

The document is an Electrical - Panel Schedules drawing for a VA Medical Center renovation project located at 1670 Clairmont Rd, Decatur, GA. The drawing details electrical panel configurations for the 6th floor renovation of a 16-bed short stay Clinical Logistics Center (CLC), specifically showing six branch panels (6HA, 6HXA, 6HXB, 6LA, 6LB, and 6HB) with comprehensive circuit-level electrical load information. The panels are designed to support various hospital functional areas including patient rooms, corridors, medical spaces, recreational rooms, kitchens, dining areas, and support spaces, with each panel providing detailed information on circuit assignments, wire sizes, amperage, and load classifications.

The technical drawing, prepared by Charlotte Engineers and dated 09/21/2023, is part of 100% Construction Documents for a fully sprinklered facility. The electrical infrastructure includes multiple panels with varying voltage configurations (480/277 Wye and 120/208 Wye), main breaker ratings between 100-225 amps, and total estimated demands ranging from 0 to 72 amps across different panels. The project is associated with VA solicitation number 508-22-105 and involves renovation of the 6th floor to create a 16-bed short stay Clinical Logistics Center, with the electrical design accommodating existing loads to be transferred to new panels and providing spare circuit capacity for future expansion.

View the file

Other files

File Type Posted
E001 - ELECTRICAL - LEGENDS-SYMBOLS-DRAWING INDEX.pdf PDF
ES100 - ELECTRICAL - LEVEL 06 - NEW WORK - SPECIAL SYSTEMS.pdf PDF
E005 - ELECTRICAL - SPECIAL SYSTEM DETAILS.pdf PDF
E006 - ELECTRICAL - PARTIAL RISER DIAGRAMS.pdf PDF
Images.pdf PDF
01 01 45 35 - Special Inspections Worksheet.xlsx XLSX spreadsheet
36C24725R0029 0005.docx DOCX document
01 45 35 - Special Inspections.docx DOCX document
ED100 - ELECTRICAL - LEVEL 06 - DEMOLITION.pdf PDF
RFI Responses.xlsx XLSX spreadsheet
36C24725R0029 0004.docx DOCX document
RFI Response Renovate 6th Floor CLC Bldg C.pdf PDF
DBA Wages 2-7-2025.pdf PDF
RFI ATTACHMENTS.zip ZIP file
36C24725R0029 0003.pdf PDF
36C24725R0029 0002.pdf PDF
Site Visit Attendance Sheet 508-22-105.pdf PDF
36C24725R0029 0001.docx DOCX document
Attachment 4 - Itemized Cost Breakdown.xlsx XLSX spreadsheet
Attachment 7 - Construction Drawings 508-22-105.pdf PDF
Attachment 1 - Experience Modification Rate Form.pdf PDF
36C24725R0029 Solicitation.docx DOCX document
Attachment 2 - VAAR 852.219-75 VA Notice of Limitations on Subcontracting Jan 2023 Dev.pdf PDF
Attachment 8 - Specs 508-22-105.pdf PDF
Attachment 3 - Past Performance Questionnaire -PPQ.docx DOCX document
Attachment 6 - Invoicing.docx DOCX document
Attachment 5 - DBA Wages GA20250305 01-03-2025.pdf PDF
Show all 27

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

Engineering Discipline:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Consultant:

U D

B e n d e r\ L o c a l R e v it F ile s \2

\4

V A

M C

A tl a n ta th f l\

C E

C e n tr a l M o d e l.

rv t

/5 /2

:1

:2

P M

E007

ELECTRCIAL - PANEL SCHEDULES

CHARLOTTE ENGINEERS

5838 MONROE ROAD, SUITE 100

CHARLOTTE, NC 28212

704.531.3000

GUIDON

1221 N. PENNSYLVANIA STREET

INDIANAPOLIS STREET

317.800.6388

RENOVATE 6TH FLOOR FOR 16

BED STORT STAY CLC

1670 CLAIRMONT RD, DECATUR, GA

508-22-105

C

9/21/2023 JCE NMG

100% CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

Notes:

Total Est. Demand: 12 A

Total Conn.: 10 A

Other 0 VA 0.00% 0 VA Total Est. Demand: 10181 VA

Lighting - Dwelling Unit 48 VA 100.00% 48 VA Total Conn. Load: 8154 VA

Lighting 8108 VA 125.00% 10135 VA

Load Classification Connected Load Demand Factor Estimated Demand Panel Totals

TOTAL AMPS: 15 A 13 A 4 A

TOTAL LOAD: 3.9 kVA 3.2 kVA 1.1 kVA

PHASE A PHASE B PHASE C

41 SPARE -- 1 20 0.0 0.0 20 1 -- SPARE 42

39 SPARE -- 1 20 0.0 0.0 20 1 -- SPARE 40

37 SPARE -- 1 20 0.0 0.0 20 1 -- SPARE 38

35 SPARE -- 1 20 0.0 0.0 20 1 -- SPARE 36

33 SPARE -- 1 20 0.0 0.0 20 1 -- SPARE 34

31 SPARE -- 1 20 0.0 0.0 20 1 -- SPARE 32

29 SPARE -- 1 20 0.0 0.0 20 1 -- SPARE 30

27 SPARE -- 1 20 0.0 0.0 20 1 -- SPARE 28

25 SPARE -- 1 20 0.0 0.0 20 1 -- SPARE 26

23 SPARE -- 1 20 0.0 0.0 20 1 -- SPARE 24

21 SPARE -- 1 20 0.0 0.0 20 1 -- SPARE 22

19 SPARE -- 1 20 0.0 0.0 20 1 -- SPARE 20

17 SPARE -- 1 20 0.0 0.0 20 1 -- SPARE 18

15 Lighting CHART 602 1-#12, 1-#12, 1-#12 1 20 0.4 0.0 20 1 -- SPARE 16

13 Lighting CORRIDOR 6C60 1-#12, 1-#12, 1-#12 1 20 0.4 0.0 20 1 -- SPARE 14

11 Lighting PATIENT 13-1 628-1 1-#12, 1-#12, 1-#12 1 20 0.4 0.1 20 1 1-#12, 1-#12, 1-#12 Lighting TLT683, ELEV. 681 12

9 Lighting EQUIP. 689 1-#12, 1-#12, 1-#12 1 20 0.5 0.6 20 1 1-#12, 1-#12, 1-#12 Lighting Space 45 10

7 Lighting LIVING 70 1-#12, 1-#12, 1-#12 1 20 0.2 2.1 20 1 1-#12, 1-#12, 1-#12 Lighting SOILED PANT. 118 8

5 Lighting DINING 15 1-#12, 1-#12, 1-#12 1 20 0.4 0.2 20 1 1-#12, 1-#12, 1-#12 Lighting PATIENT 7 144 6

3 Lighting HUDDLE 41 1-#12, 1-#12, 1-#12 1 20 1.4 0.3 20 1 1-#12, 1-#12, 1-#12 Lighting Patient 1 9 4

1 Lighting GYM 5 1-#12, 1-#12, 1-#12 1 20 1.0 0.2 20 1 1-#12, 1-#12, 1-#12 Lighting PATIENT 5 142 2

CIR DESCRIPTION NOTE SIZE (HOT, N, G) C P AMP A B C A B C AMP P C SIZE (HOT, N, G) NOTE DESCRIPTION CIR

Enclosure: Type 1

Mounting: Surface Wires: 4 Mains Rating: 225 A

Supply From: NHL-C6-1 Phases: 3 Mains Type: MLO

Location: ELEC. 660 Volts: 480/277 Wye A.I.C. Rating: 22,000A

Branch Panel: NHL-C6-3 (6HA)

1. EXISTING LOADS TO BE TRANSFERED TO NEW PANEL.

Notes:

Total Est. Demand: 0 A

Total Conn.: 0 A

Total Est. Demand: 0 VA

Total Conn. Load: 0 VA

Load Classification Connected Load Demand Factor Estimated Demand Panel Totals

TOTAL AMPS: 0 A 0 A 0 A

TOTAL LOAD: 0.0 kVA 0.0 kVA 0.0 kVA

PHASE A PHASE B PHASE C

17 SPARE -- 1 20 0.0 0.0 20 1 -- SPARE 18

15 SPARE -- 1 20 0.0 0.0 20 1 -- SPARE 16

13 SPARE -- 1 20 0.0 0.0 20 1 -- SPARE 14

11 SPARE -- 1 20 0.0 0.0 20 1 -- SPARE 12

9 SPARE -- 1 20 0.0 0.0 20 1 -- SPARE 10

7 (EX) LOAD 1 -- 1 20 0.0 0.0 20 1 -- 1 (EX) LOAD 8

5 (EX) LOAD 1 -- 1 20 0.0 0.0 20 1 -- 1 (EX) LOAD 6

3 (EX) LOAD 1 -- 1 20 0.0 0.0 20 1 -- 1 (EX) LOAD 4

1 (EX) LOAD 1 -- 1 20 0.0 0.0 20 1 -- 1 (EX) LOAD 2

CIR DESCRIPTION NOTE SIZE (HOT, N, G) C P AMP A B C A B C AMP P C SIZE (HOT, N, G) NOTE DESCRIPTION CIR

Enclosure: Type 1

Mounting: Surface Wires: 4 Mains Rating: 100 A

Supply From: CHL-C5-1 Phases: 3 Mains Type: MLO

Location: ELEC. 660 Volts: 480/277 Wye A.I.C. Rating: 22,000A

Branch Panel: CHL-C6-1 (6HXA)

3. LOCK-ON CIRCUIT BREAKER DEVICE.

2. PANELBOARD HAS A 30A/3P SUBFEED CIRCUIT BREAKER.

1. EXISTING LOADS TO BE TRANSFERED TO NEW PANEL.

Notes:

Total Est. Demand: 0 A

Total Conn.: 0 A

Total Est. Demand: 0 VA

Total Conn. Load: 0 VA

Load Classification Connected Load Demand Factor Estimated Demand Panel Totals

TOTAL AMPS: 0 A 0 A 0 A

TOTAL LOAD: 0.0 kVA 0.0 kVA 0.0 kVA

PHASE A PHASE B PHASE C

41 SPARE -- 1 20 0.0 0.0 20 1 -- SPARE 42

39 SPARE -- 1 20 0.0 0.0 20 1 -- SPARE 40

37 SPARE -- 1 20 0.0 0.0 20 1 -- SPARE 38

35 SPARE -- 1 20 0.0 0.0 20 1 -- SPARE 36

33 SPARE -- 1 20 0.0 0.0 20 1 -- SPARE 34

31 SPARE -- 1 20 0.0 0.0 20 1 -- SPARE 32

29 SPARE -- 1 20 0.0 0.0 20 1 -- SPARE 30

27 SPARE -- 1 20 0.0 0.0 20 1 -- SPARE 28

25 SPARE -- 1 20 0.0 0.0 20 1 -- SPARE 26

23 SPARE -- 1 20 0.0 0.0 20 1 -- SPARE 24

21 SPARE -- 1 20 0.0 0.0 20 1 -- SPARE 22

19 EXISTING TO REMAIN 3 -- 1 20 0.0 0.0 20 1 -- SPARE 20

17 EXISTING TO REMAIN 3 -- 1 20 0.0 0.0 20 1 -- SPARE 18

15 EM LTG GROUND FL 1 -- 1 20 0.0 0.0 20 1 -- SPARE 16

13 EM LTG 1ST FL 1 -- 1 20 0.0 0.0 20 1 3 -- EXISTING TO REMAIN 14

11 EXISTING TO REMAIN 3 -- 1 20 0.0 0.0 20 1 1 -- EM LTG 10TH FL E&D SEC 12

9 EM LTG 4TH FL 1 -- 1 20 0.0 0.0 20 1 1 -- EM LTG 10TH FL E&D SEC 10

7 EM LTG 5,6 FL 1 -- 1 20 0.0 0.0 20 1 1 -- EM LTG 2ND FL 8

5 EM LTG 7,8 FL 1 -- 1 20 0.0 0.0 20 1 1 -- EM LTG 8,9,10,11 FL 6

3 EM LTG 9,10 FL 1 -- 1 20 0.0 0.0 20 1 1 -- EM LTG STAIR 3,4,5,6,7 FL 4

1 SPARE -- 1 20 0.0 0.0 20 1 -- SPARE 2

CIR DESCRIPTION NOTE SIZE (HOT, N, G) C P AMP A B C A B C AMP P C SIZE (HOT, N, G) NOTE DESCRIPTION CIR

Enclosure: Type 1

Mounting: Surface Wires: 4 Mains Rating: 225 A

Supply From: CHL-C5-2 Phases: 3 Mains Type: MLO

Location: ELEC 680 Volts: 480/277 Wye A.I.C. Rating: 22,000A

Branch Panel: CHL-C6-2 (6HXB)

Notes:

Total Est. Demand: 55 A

Total Conn.: 78 A

MISCELLANEOUS 1000 VA 100.00% 1000 VA Total Est. Demand: 19694 VA

REC 26988 VA 68.53% 18494 VA Total Conn. Load: 28188 VA

Power 200 VA 100.00% 200 VA

Load Classification Connected Load Demand Factor Estimated Demand Panel Totals

TOTAL AMPS: 64 A 79 A 96 A

TOTAL LOAD: 7.7 kVA 9.3 kVA 11.3 kVA

PHASE A PHASE B PHASE C

41 SPARE -- 1 20 0.0 0.0 20 1 -- SPARE 42

39 SPARE -- 1 20 0.0 0.0 20 1 -- SPARE 40

37 RCP-1 - LAUNDRY 647 1-#12, 1-#12, 1-#12 1 20 0.2 0.0 20 1 -- SPARE 38

35 REC ROOM... 1-#12, 1-#12, 1-#12 1 20 1.0 1.2 20 1 1-#10, 1-#10, 1-#10 REC CORRIDOR 6C60/6C61 36

33 REC CORRIDOR 6C60/ 6C67 1-#12, 1-#12, 1-#12 1 20 0.8 0.6 20 1 1-#12, 1-#12, 1-#12 REC LAUNDRY 647 34

31 -- -- -- -- 1.3 0.2 20 1 1-#12, 1-#12, 1-#12 REC LAUNDRY 647 - WASHER 32

29 -- -- -- -- 1.3 1.3 -- -- -- -- 30

27 REC LAUNDRY 647 - DRYER 3-#12, 1-#12, 1-#12 3 20 1.3 1.3 -- -- -- -- 28

25 REC LAUNDRY 647 - WASHER 1-#12, 1-#12, 1-#12 1 20 0.2 1.3 20 3 3-#12, 1-#12, 1-#12 REC LAUNDRY 647 - DRYER 26

23 REC BREAK 643 1-#12, 1-#12, 1-#12 1 20 1.0 1.0 20 1 1-#12, 1-#12, 1-#12 REC TLT. 645/646 & LOCKER... 24

21 REC BREAK 643 - REF 1-#12, 1-#12, 1-#12 1 20 1.0 0.2 20 1 1-#12, 1-#12, 1-#12 REC BREAK 643 -... 22

19 REC BREAK 643 - COFFEE 1-#12, 1-#12, 1-#12 1 20 0.2 0.2 20 1 1-#12, 1-#12, 1-#12 REC BREAK 643 20

17 REC CONFERENCE 642 1-#12, 1-#12, 1-#12 1 20 1.0 0.6 20 1 1-#12, 1-#12, 1-#12 REC CONFERENCE 642 18

15 REC OFFICE 641 1-#12, 1-#12, 1-#12 1 20 0.6 0.6 20 1 1-#12, 1-#12, 1-#12 REC OFFICE 641 16

13 REC ROOM 634-2 1-#12, 1-#12, 1-#12 1 20 0.8 0.4 20 1 1-#12, 1-#12, 1-#12 REC ROOM 634-2 14

11 REC ROOM 639 1-#12, 1-#12, 1-#12 1 20 0.8 0.6 20 1 1-#12, 1-#12, 1-#12 REC ROOM 639 12

9 REC Room 637, 638 1-#12, 1-#12, 1-#12 1 20 0.6 0.8 20 1 1-#12, 1-#12, 1-#12 REC PROOM 638 10

7 REC ROOM 635 1-#12, 1-#12, 1-#12 1 20 0.6 0.8 20 1 1-#12, 1-#12, 1-#12 REC ROOM 635 8

5 REC ROOM 609-2 1-#12, 1-#12, 1-#12 1 20 0.8 0.6 20 1 1-#12, 1-#12, 1-#12 REC ROOM 609-2 6

3 REC ROOM 608 1-#12, 1-#12, 1-#12 1 20 0.6 0.8 20 1 1-#12, 1-#12, 1-#12 REC ROOM 608 4

1 REC ROOM 605 1-#12, 1-#12, 1-#12 1 20 0.8 0.6 20 1 1-#12, 1-#12, 1-#12 REC ROOM 605 2

CIR DESCRIPTION NOTE SIZE (HOT, N, G) C P AMP A B C A B C AMP P C SIZE (HOT, N, G) NOTE DESCRIPTION CIR

Enclosure: Type 1

Mounting: Surface Wires: 4 Mains Rating: 225 A

Supply From: NLP-C5-3 VIA XFMR SHARED W/... Phases: 3 Mains Type: MLO

Location: ELEC. 660 Volts: 120/208 Wye A.I.C. Rating:

Branch Panel: NLP-C6-3 (6LA)

Notes:

Total Est. Demand: 72 A

Total Conn.: 106 A

Total Est. Demand: 26090 VA

MISCELLANEOUS 4000 VA 100.00% 4000 VA Total Conn. Load: 38180 VA

REC 34180 VA 64.63% 22090 VA

Load Classification Connected Load Demand Factor Estimated Demand Panel Totals

TOTAL AMPS: 83 A 129 A 114 A

TOTAL LOAD: 10.0 kVA 15.0 kVA 13.2 kVA

PHASE A PHASE B PHASE C

41 SPARE -- 1 20 0.0 0.0 20 1 -- SPARE 42

39 SPARE -- 1 20 0.0 0.0 20 1 -- SPARE 40

37 REC - DATA 682 1-#12, 1-#12, 1-#12 1 20 0.6 0.6 20 1 1-#12, 1-#12, 1-#12 REC - DATA 682 38

35 REC DINING 611/675 1-#12, 1-#12, 1-#12 1 20 0.8 5.0 -- -- -- -- 36

33 REC KITCHEN 678 1-#12, 1-#12, 1-#12 1 20 1.6 5.0 30 2 2-#8, 1-#8, 1-#8 DOUBLE WALL OVEN -... 34

31 REC KITCHEN 678 - MICRO 1-#12, 1-#12, 1-#12 1 20 1.0 0.0 20 1 -- SPARE 32

29 REC KITCHEN 678 - REF 1-#12, 1-#12, 1-#12 1 20 1.0 0.0 20 1 -- SPARE 30

27 REC REC ROOM 631/ 630-2 1-#12, 1-#12, 1-#12 1 20 1.2 1.0 20 1 1-#12, 1-#12, 1-#12 REC KITCHEN 678 - MICRO 28

25 REC ROOM 684/686/685/683 1-#12, 1-#12, 1-#12 1 20 0.8 1.0 20 1 1-#12, 1-#12, 1-#12 REC KITCHEN 678 - REF 26

23 REC MED. 688 1-#12, 1-#12, 1-#12 1 20 0.8 1.2 20 1 1-#12, 1-#12, 1-#12 REC ELEV. LOBBY 681/ 691 24

21 REC CORRIDOR 6C66 1-#10, 1-#10, 1-#10 1 20 1.2 0.6 20 1 1-#12, 1-#12, 1-#12 REC MED. 688 22

19 REC ROOM 628-2 1-#12, 1-#12, 1-#12 1 20 0.6 0.8 20 1 1-#12, 1-#12, 1-#12 REC MED. 688 20

17 REC ROOM 75 1-#12, 1-#12, 1-#12 1 20 0.6 1.2 20 1 1-#10, 1-#10, 1-#10 REC CORRIDOR 6C63-2 18

15 REC ROOM 624 1-#12, 1-#12, 1-#12 1 20 0.6 0.8 20 1 1-#12, 1-#12, 1-#12 REC ROOM 628-2 16

13 REC ROOM 624 1-#12, 1-#12, 1-#12 1 20 0.8 0.8 20 1 1-#12, 1-#12, 1-#12 REC ROOM 75 14

11 REC ROOM 623 1-#12, 1-#12, 1-#12 1 20 0.6 0.6 20 1 1-#12, 1-#12, 1-#12 REC ROOM 623 12

9 REC ROOM 612-2 1-#12, 1-#12, 1-#12 1 20 0.6 0.8 20 1 1-#12, 1-#12, 1-#12 REC ROOM 612-2 10

7 REC ROOM 614 1-#12, 1-#12, 1-#12 1 20 0.8 0.6 20 1 1-#12, 1-#12, 1-#12 REC ROOM 614 8

5 REC ROOM 616-3 1-#12, 1-#12, 1-#12 1 20 0.6 0.8 20 1 1-#12, 1-#12, 1-#12 REC ROOM 616-3 6

3 REC ROOM 619-2 1-#12, 1-#12, 1-#12 1 20 0.8 0.8 20 1 1-#12, 1-#12, 1-#12 REC ROOM 619-2 4

1 REC ROOM 620-4 1-#12, 1-#12, 1-#12 1 20 0.8 0.8 20 1 1-#12, 1-#12, 1-#12 REC ROOM 620-4 2

CIR DESCRIPTION NOTE SIZE (HOT, N, G) C P AMP A B C A B C AMP P C SIZE (HOT, N, G) NOTE DESCRIPTION CIR

Enclosure: Type 1

Mounting: Surface Wires: 4 Mains Rating: 225 A

Supply From: NLP-C5-4 VIA XFMR SHARED W/... Phases: 3 Mains Type: MLO

Location: ELEC 680 Volts: 120/208 Wye A.I.C. Rating: 10,000A

Branch Panel: NLB-C6-4 (6LB)

6HA

6HXB 6LA 6LB

6HB 6HXA

2. REFER TO POWER RISER DIAGRAM FOR CONDUCTOR AND RACEWAY SIZES AND QUANTITY.

1. EXISTING LOADS TO BE TRANSFERED TO NEW PANEL.

Notes:

Total Est. Demand: 0 A

Total Conn.: 0 A

Total Est. Demand: 0 VA

Total Conn. Load: 0 VA

Load Classification Connected Load Demand Factor Estimated Demand Panel Totals

TOTAL AMPS: 0 A 0 A 0 A

TOTAL LOAD: 0.0 kVA 0.0 kVA 0.0 kVA

PHASE A PHASE B PHASE C

23 SPARE -- 1 20 0.0 0.0 -- -- -- -- 24

21 SPARE -- 1 20 0.0 0.0 -- -- -- -- 22

19 SPARE -- 1 20 0.0 0.0 100 3 -- XFMR NX-C6-7 (T-6LB1) 20

17 SPARE -- 1 20 0.0 0.0 20 1 -- SPARE 18

15 SPARE -- 1 20 0.0 0.0 20 1 -- SPARE 16

13 SPARE -- 1 20 0.0 0.0 20 1 -- SPARE 14

11 SPARE -- 1 20 0.0 0.0 20 1 -- 1 EX) LOAD 12

9 SPARE -- 1 20 0.0 0.0 20 1 -- 1 EX) LOAD 10

7 SPARE -- 1 20 0.0 0.0 20 1 -- 1 EX) LOAD 8

5 (EX) LTS 6C101, 102, 103, 17... 1 -- 1 20 0.0 0.0 20 1 -- 1 (EX) LTS CORRIDOR 6

3 (EX) LTS 6C162,164,165 1 -- 1 20 0.0 0.0 20 1 -- 1 (EX) LTS 6C105,110,115 4

1 (EX) LTS 6C158-160 1 -- 1 20 0.0 0.0 20 1 -- 1 (EX) LTS 6C116-119 2

CIR DESCRIPTION NOTE SIZE (HOT, N, G) C P AMP A B C A B C AMP P C SIZE (HOT, N, G) NOTE DESCRIPTION CIR

Enclosure: Type 1

Mounting: Surface Wires: 4 Mains Rating: 225 A

Supply From: NHL-C6-2 Phases: 3 Mains Type: MLO

Location: ELEC 680 Volts: 480/277 Wye A.I.C. Rating: 22,000A

Branch Panel: NHL-C6-4 (6HB)

Revisions: Date:

Addendum 2 05-06-2025

NOT A CERTIFIED DOCUMENT AS TO THE ORIGINAL DOCUMENT

BUT ONLY AS TO THE REVISION - THIS DOCUMENT ORIGINALLY

ISSUED AND SEALED BY JOHN C. EDWARDS, JR. 050482, 09-21-23

THIS DOCUMENT IS ONLY CERTIFIED AS TO THE REVISIONS.

Sheets
E001 - ELECTRICAL - LEGENDS, SYMBOLS, AND DRAWING INDEX
E004 - ELECTRICAL - SPECIAL SYSTEM DETAILS
E005 - ELECTRICAL - SPECIAL SYSTEM DETAILS
E006 - ELECTRICAL - PARTIAL RISER DIAGRAMS
E007 - ELECTRCIAL - PANEL SCHEDULES
ED100 - ELECTRICAL - LEVEL 06 - DEMOLITION
ES100 - ELECTRICAL - LEVEL 06 - NEW WORK - SPECIAL SYSTEMS
2025-05-05T16:40:56-0400
Nicholas Esposito

File details come from the government source that posted it. Updated .