E006 - ELECTRICAL - PARTIAL RISER DIAGRAMS.pdf

PDF 309 KB Posted

Attached to
Y1DA--508-22-105 | 6th Floor CLC 16-Bed Bldg. C
Solicitation number
36C24725R0029
Issued by

About this file

This is an electrical partial riser diagram for a renovation project at the VA Medical Center in Decatur, Georgia. The document details electrical system modifications for the 6th floor of Building C, involving the replacement and demolition of existing electrical panels, transformers, and associated equipment across multiple levels. The project scope specifically focuses on Level 6, with notes indicating that electrical devices and equipment on levels 1-3, 7-12, the roof, and machine rooms are not part of this project. The diagram uses legends to distinguish between existing equipment to remain (EX/RM), equipment to be replaced (RPD/RP), and shows detailed electrical configurations including panel types, voltages, amperage, and interconnections between various electrical rooms and panels.

The project is part of a VA contract (508-22-105) for renovating the 6th floor to create a 16-bed Short Stay Clinical Logistics Center (CLC), with the electrical riser diagram prepared by Charlotte Engineers for the Department of Veterans Affairs. The document is marked as 100% Construction Documents, dated 9/21/2023, with an addendum noted for 05-06-2025. The electrical systems involve multiple transformers ranging from 45kVA to 112.5kVA, with various panel configurations at 208Y/120V and 480Y/277V, indicating a comprehensive electrical system upgrade to support the medical facility's renovation.

View the file

Other files

File Type Posted
E001 - ELECTRICAL - LEGENDS-SYMBOLS-DRAWING INDEX.pdf PDF
ES100 - ELECTRICAL - LEVEL 06 - NEW WORK - SPECIAL SYSTEMS.pdf PDF
E005 - ELECTRICAL - SPECIAL SYSTEM DETAILS.pdf PDF
Images.pdf PDF
01 01 45 35 - Special Inspections Worksheet.xlsx XLSX spreadsheet
36C24725R0029 0005.docx DOCX document
01 45 35 - Special Inspections.docx DOCX document
ED100 - ELECTRICAL - LEVEL 06 - DEMOLITION.pdf PDF
E007 - ELECTRCIAL - PANEL SCHEDULES.pdf PDF
RFI Responses.xlsx XLSX spreadsheet
36C24725R0029 0004.docx DOCX document
RFI Response Renovate 6th Floor CLC Bldg C.pdf PDF
DBA Wages 2-7-2025.pdf PDF
RFI ATTACHMENTS.zip ZIP file
36C24725R0029 0003.pdf PDF
36C24725R0029 0002.pdf PDF
Site Visit Attendance Sheet 508-22-105.pdf PDF
36C24725R0029 0001.docx DOCX document
Attachment 4 - Itemized Cost Breakdown.xlsx XLSX spreadsheet
Attachment 7 - Construction Drawings 508-22-105.pdf PDF
Attachment 1 - Experience Modification Rate Form.pdf PDF
36C24725R0029 Solicitation.docx DOCX document
Attachment 2 - VAAR 852.219-75 VA Notice of Limitations on Subcontracting Jan 2023 Dev.pdf PDF
Attachment 8 - Specs 508-22-105.pdf PDF
Attachment 3 - Past Performance Questionnaire -PPQ.docx DOCX document
Attachment 6 - Invoicing.docx DOCX document
Attachment 5 - DBA Wages GA20250305 01-03-2025.pdf PDF
Show all 27

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

XFMR CX-C6-2

(XC6-2)

480V-208Y/120V

(RM)

PANEL

NHL-C6-1

(HN6-1)

480Y/277V

3PH 4W

300A MCB

(RP)

PANEL

LN6-1

208Y/120V

3PH 4W

225A MCB

(RP)

PANEL

6HA

480Y/277V

3PH 4W

225A

(RP)

PANEL

6LA

208Y/120V

3PH 4W

225A

(RP)

PANEL

NHL-C6-2

(HN6-2)

480Y/277V

3PH 4W

300A MCB

(RP)

LEVEL 06

LEVEL 05

DEMOLITION RISER DIAGRAM LEGEND

DEMO - RP (EXISTING DEVICE; TO BE REPLACED WITH NEW)

EXISTING - RM (EXISTING DEVICE; TO REMAIN)

PANEL

CLP-C6-2

(LC6-2)

208Y/120V

3PH 4W

150A MCB

(RP)

PANEL

CHL-C5-1

(HC5-1)

480Y/277V

3PH 4W

(RM)

XFMR CX-C6-1

(XC6-1)

45 KVA

480V-208Y/120V

(RM)

ATS5-1

300A

(RM)

N E

L

DHC3-1

PANEL

LC6-1

208Y/120V

3PH 4W

150A MCB

(RP)

PANEL

6LXA

208Y/120V

3PH 4W

225A

(RP)

(RL)

PANEL

6HXA

480Y/277V

3PH 4W

100A

(RP)

(RL)

ATS5-2

300A

(RM)

N E

L

DHC3-1

PANEL

CHL-C5-2

(HC5-2)

480Y/277V

3PH 4W

300A MCB

(RM)

PANEL

NHL-C5-1

(HN5-1)

480Y/277V

3PH 4W

(RM)

XFMR XN5-1

45kVA

480V-208Y/120V

(RM)

PANEL

5PLA

208Y/120V

3PH 4W

(RM)

XFMR NX-C6-7

(T-6LB1)

75kVA

480V-208Y/120V

(RM)

ELEC ROOM 131

(ROOM 6C132)

XFMR CX-C5-3

(XC5-1)

45 kVA

480V-208Y-120V

(RM)

PANEL

LC5-1

208Y/120V

3PH 4W

150A MCB

(RM)

ELEC ROOM 129

(ROOM 6C132A)

ATS8-5

(RM)

PANEL

NLP-C6-2

(LN6-2)

208Y/120V

3PH 4W

225A MCB

(RP)

PANEL

ELP-C6-2

(6LXB)

208Y/120V

3PH 4W

225A MLO

(RP)

ELEC ROOM 114

(ROOM 6C175)

ELEC ROOM 113

(ROOM 3C174)

ELECTRICAL DEVICES AND EQUIPMENT ON LEVELS ONE THROUGH THREE ARE NOT WITHIN THE SCOPE OF THIS PROJECT.

LEVEL 04

PANEL

CHL-C6-2

(6HXB)

480Y/277V

3PH 4W

225A MLO

(RP)

PANEL

NLP-C6-8

(6LB2)

208Y/120V

3PH 4W

100A MCB

(RP)

PANEL

NLP-C6-7

(6LB1)

208Y/120V

3PH 4W

150A MCB

(RP)

PANEL

NLP-C5-4

(5PLB)

208Y/120V

3PH 4W

(RM)

PANEL

NLP-C6-4

(6LB)

208Y/120V

3PH 4W

MLO

(RP)

ELECTRICAL DEVICES AND EQUIPMENT ON LEVELS SEVEN THROUGH TWELVE ARE NOT WITHIN THE SCOPE OF THIS PRJECT.

ELECTRICAL DEVICES AND EQUIPMENT ON THE ROOF AND IN THE MACHINE ROOMS ARE NOT WITHIN THE SCOPE OF THIS PROJECT.

PANEL

NHL-C6-4

(6HB)

480Y/277V

3PH 4W

225A MLO

(RP)

DISCONNECT

12XLA

(RM)

PANEL

NHL-C5-2

(LC5-2)

208Y/120V

3PH 4W

(RM)

PANEL

NHL-C4-2

(HN4-2)

480Y/277V

3PH 4W

(RM)

XFMR NX-C4-1

(XN4-2)

(RM)

XFMR CX-C5-2

(XC5-2)

480V-208Y/120V

(RM)

TO

ROOF

PANEL

NHL-C5-1

(HN4-1)

480Y/277V

3PH 4W

(RM)

FED FROM

PANEL DHN3

PANEL

5HA

480Y/277V

3PH 4W

(RM)

XFMR

112.5 kVA

480V-208Y/120V

(RM)

N

L

E

DISCONNECT

T-6LB1

(RV)

PANEL

NHL-C5-2

(HN5-2)

480Y/277V

3PH 4W

(RM)

FED FROM

PANEL DHN3

PANEL

(5HB)

480Y/277V

3PH 4W

(RM)

XFMR CX-C5-2

112.5kVA

480V-208Y/120V

(RM)

BUSDUCT

BUSDUCT

ELECTRICAL DEVICES AND EQUIPMENT ON THE GROUND LEVEL ARE NOT WITHIN THE SCOPE OF THIS PROJECT.

(RM)

(RM)

(RM)

(RM)

(RM)

(RM)

(RM)

(RM)

(RM)

(RM)

(RP)

(RM) (RM)

(RM)

(RM)

(RM)

(RM)

(RM) (RP) (RM)

(RM)

(RM)

(RM)

(RM)

(RM)

(RM)

(RM)

(RM)

(RM)

(RM)

(RM) (RM)

(RM)

(RM)

(RM)

(RM)

(RM)

(RM)

J

(RV)

(RM)

NEW WORK RISER DIAGRAM LEGEND

NEW - RPD (EXISTING DEVICED REPLACED WITH NEW)

EXISTING - EX (EXISTING DEVICE)

XFMR CX-C6-2

(XC6-2)

480V-208Y/120V

(EX)

PANEL

NHL-C6-1

(HN6-1)

480Y/277V

3PH 4W

300A MCB

(RPD)

PANEL

LN6-1

208Y/120V

3PH 4W

225A MCB

(RPD)

PANEL

6HA

480Y/277V

3PH 4W

225A

(RPD)

PANEL

6LA

208Y/120V

3PH 4W

225A

(RPD)

PANEL

NHL-C6-2

(HN6-2)

480Y/277V

3PH 4W

300A MCB

(RPD)

LEVEL 06

LEVEL 05

PANEL

CLP-C6-2

(LC6-2)

208Y/120V

3PH 4W

150A MCB

(RPD)

PANEL

CHL-C5-1

(HC5-1)

480Y/277V

3PH 4W

(EX)

XFMR CX-C6-1

(XC6-1)

45 KVA

480V-208Y/120V

(EX)

ATS5-1

300A

(EX)

N E

L

DHC3-1

PANEL

LC6-1

208Y/120V

3PH 4W

150A MCB

(RPD)

PANEL

6LXA

208Y/120V

3PH 4W

225A

(RPD)

(RLD)

PANEL

6HXA

480Y/277V

3PH 4W

100A

(RPD)

(RLD)

ATS5-2

300A

(EX)

N E

L

DHC3-1

PANEL

CHL-C5-2

(HC5-2)

480Y/277V

3PH 4W

300A MCB

(EX)

PANEL

NHL-C5-1

(HN5-1)

480Y/277V

3PH 4W

(EX)

XFMR XN5-1

45kVA

480V-208Y/120V

(EX)

PANEL

5PLA

208Y/120V

3PH 4W

(EX)

XFMR NX-C6-7

(T-6LB1)

75kVA

480V-208Y/120V

(EX)

ELEC ROOM 131

(ROOM 6C132)

XFMR CX-C5-3

(XC5-1)

45 kVA

480V-208Y-120V

(EX)

PANEL

LC5-1

208Y/120V

3PH 4W

150A MCB

(EX)

ELEC

ROOM 129

(ROOM

6C132A)

ATS8-5

(EX)

PANEL

NLP-C6-2

(LN6-2)

208Y/120V

3PH 4W

225A MCB

(RPD)

PANEL

ELP-C6-2

(6LXB)

208Y/120V

3PH 4W

225A MLO

(RPD)

ELEC ROOM 114

(ROOM 6C175)

ELEC ROOM 113

(ROOM 3C174)

ELECTRICAL DEVICES AND EQUIPMENT ON LEVELS ONE THROUGH THREE ARE NOT WITHIN THE SCOPE OF THIS PROJECT.

LEVEL 04

PANEL

CHL-C6-2

(6HXB)

480Y/277V

3PH 4W

225A MLO

(RPD)

PANEL

NLP-C6-8

(6LB2)

208Y/120V

3PH 4W

100A MCB

(RPD)

PANEL

NLP-C6-7

(6LB1)

208Y/120V

3PH 4W

150A MCB

(RPD)

PANEL

NLP-C5-4

(5PLB)

208Y/120V

3PH 4W

(EX)

PANEL

NLP-C6-4

(6LB)

208Y/120V

3PH 4W

MLO

(RPD)

ELECTRICAL DEVICES AND EQUIPMENT ON LEVELS SEVEN THROUGH TWELVE ARE NOT WITHIN THE SCOPE OF THIS PRJECT.

ELECTRICAL DEVICES AND EQUIPMENT ON THE ROOF AND IN THE MACHINE ROOMS ARE NOT WITHIN THE SCOPE OF THIS PROJECT.

PANEL

NHL-C6-4

(6HB)

480Y/277V

3PH 4W

225A MLO

(RPD)

DISCONNECT

12XLA

(EX)

PANEL

NHL-C5-2

(LC5-2)

208Y/120V

3PH 4W

(EX)

PANEL

NHL-C4-2

(HN4-2)

480Y/277V

3PH 4W

(EX)

XFMR NX-C4-1

(XN4-2)

(EX)

XFMR CX-C5-2

(XC5-2)

480V-208Y/120V

(EX)

TO

ROOF

PANEL

NHL-C5-1

(HN4-1)

480Y/277V

3PH 4W

(EX)

FED FROM

PANEL DHN3

PANEL

5HA

480Y/277V

3PH 4W

(EX)

XFMR

112.5 kVA

480V-208Y/120V

(EX)

N

L

E

PANEL

NHL-C5-2

(HN5-2)

480Y/277V

3PH 4W

(EX)

FED FROM

PANEL DHN3

PANEL

(5HB)

480Y/277V

3PH 4W

(EX)

XFMR CX-C5-2

112.5kVA

480V-208Y/120V

(EX)

BUSDUCT

ELECTRICAL DEVICES AND EQUIPMENT ON THE GROUND LEVEL ARE NOT WITHIN THE SCOPE OF THIS PROJECT.

(EX)

(EX)

(EX)

(EX)

(EX)

(EX)

(EX)

(EX) (EX)

(EX)

(4)#3/0, (1)#6, 2" C

(EX) (EX)

(EX)

(EX)

(EX)

(EX)

(EX)

(EX)

(EX)

(EX)

(EX)

(EX)

(EX)

(EX)

(EX)

(EX)

(EX)

(EX) (EX)

(EX)

(EX)

(EX)

(EX)

(EX)

J

BUSDUCT

J

SPLICE AND EXTEND

3#1, 1#6, 1 1/2"C

GENERAL NOTES

A. ALL PANELBOARDS AND DISCONNECTS FEEDING ELECTRICAL DEVICES

AND EQUIPMENT ON LEVEL 06 ARE TO BE DEMOLISHED AND REPLACED.

B. PANELBOARD AND DISCONNECT FEEDERS ARE EXISTING TO REMAIN,

UNLESS OTHERWISE NOTED.

C. ALL BRANCH CIRCUITS SUPPLYING DEVICES ON LEVEL 06 ARE TO BE

DEMOLISHED. SEE PANEL SCHEDULES FOR NEW BRANCH CIRCUITS.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

Engineering Discipline:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Consultant:

U D

B e n d e r\ L o c a l R e v it F ile s \2

\4

V A

M C

A tl a n ta th f l\

C E

C e n tr a l M o d e l.

rv t

/5 /2

:1

:3

P M

E006

ELECTRICAL - PARTIAL RISER

DIAGRAMSCHARLOTTE ENGINEERS

5838 MONROE ROAD, SUITE 100

CHARLOTTE, NC 28212

704.531.3000

GUIDON

1221 N. PENNSYLVANIA STREET

INDIANAPOLIS STREET

317.800.6388

RENOVATE 6TH FLOOR FOR 16

BED STORT STAY CLC

1670 CLAIRMONT RD, DECATUR, GA

508-22-105

C

9/21/2023 JCE NMG

100% CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

NOT TO SCALE

PARTIAL ELECTRICAL RISER DIAGRAM - DEMOLITION

NOT TO SCALE

PARTIAL ELECTRICAL RISER DIAGRAM - NEW WORK

Revisions: Date:

Addendum 2 05-06-2025

NOT A CERTIFIED DOCUMENT AS TO THE ORIGINAL DOCUMENT

BUT ONLY AS TO THE REVISION - THIS DOCUMENT ORIGINALLY

ISSUED AND SEALED BY JOHN C. EDWARDS, JR. 050482, 09-21-23

THIS DOCUMENT IS ONLY CERTIFIED AS TO THE REVISIONS.

Sheets
E006 - ELECTRICAL - PARTIAL RISER DIAGRAMS
2025-05-05T16:41:13-0400
Nicholas Esposito

File details come from the government source that posted it. Updated .