E006 - ELECTRICAL - PARTIAL RISER DIAGRAMS.pdf
PDF 309 KB Posted
- Attached to
- Y1DA--508-22-105 | 6th Floor CLC 16-Bed Bldg. C
- Solicitation number
- 36C24725R0029
About this file
This is an electrical partial riser diagram for a renovation project at the VA Medical Center in Decatur, Georgia. The document details electrical system modifications for the 6th floor of Building C, involving the replacement and demolition of existing electrical panels, transformers, and associated equipment across multiple levels. The project scope specifically focuses on Level 6, with notes indicating that electrical devices and equipment on levels 1-3, 7-12, the roof, and machine rooms are not part of this project. The diagram uses legends to distinguish between existing equipment to remain (EX/RM), equipment to be replaced (RPD/RP), and shows detailed electrical configurations including panel types, voltages, amperage, and interconnections between various electrical rooms and panels.
The project is part of a VA contract (508-22-105) for renovating the 6th floor to create a 16-bed Short Stay Clinical Logistics Center (CLC), with the electrical riser diagram prepared by Charlotte Engineers for the Department of Veterans Affairs. The document is marked as 100% Construction Documents, dated 9/21/2023, with an addendum noted for 05-06-2025. The electrical systems involve multiple transformers ranging from 45kVA to 112.5kVA, with various panel configurations at 208Y/120V and 480Y/277V, indicating a comprehensive electrical system upgrade to support the medical facility's renovation.
View the file
Other files
Show all 27
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
XFMR CX-C6-2
(XC6-2)
480V-208Y/120V
(RM)
PANEL
NHL-C6-1
(HN6-1)
480Y/277V
3PH 4W
300A MCB
(RP)
PANEL
LN6-1
208Y/120V
3PH 4W
225A MCB
(RP)
PANEL
6HA
480Y/277V
3PH 4W
225A
(RP)
PANEL
6LA
208Y/120V
3PH 4W
225A
(RP)
PANEL
NHL-C6-2
(HN6-2)
480Y/277V
3PH 4W
300A MCB
(RP)
LEVEL 06
LEVEL 05
DEMOLITION RISER DIAGRAM LEGEND
DEMO - RP (EXISTING DEVICE; TO BE REPLACED WITH NEW)
EXISTING - RM (EXISTING DEVICE; TO REMAIN)
PANEL
CLP-C6-2
(LC6-2)
208Y/120V
3PH 4W
150A MCB
(RP)
PANEL
CHL-C5-1
(HC5-1)
480Y/277V
3PH 4W
(RM)
XFMR CX-C6-1
(XC6-1)
45 KVA
480V-208Y/120V
(RM)
ATS5-1
300A
(RM)
N E
L
DHC3-1
PANEL
LC6-1
208Y/120V
3PH 4W
150A MCB
(RP)
PANEL
6LXA
208Y/120V
3PH 4W
225A
(RP)
(RL)
PANEL
6HXA
480Y/277V
3PH 4W
100A
(RP)
(RL)
ATS5-2
300A
(RM)
N E
L
DHC3-1
PANEL
CHL-C5-2
(HC5-2)
480Y/277V
3PH 4W
300A MCB
(RM)
PANEL
NHL-C5-1
(HN5-1)
480Y/277V
3PH 4W
(RM)
XFMR XN5-1
45kVA
480V-208Y/120V
(RM)
PANEL
5PLA
208Y/120V
3PH 4W
(RM)
XFMR NX-C6-7
(T-6LB1)
75kVA
480V-208Y/120V
(RM)
ELEC ROOM 131
(ROOM 6C132)
XFMR CX-C5-3
(XC5-1)
45 kVA
480V-208Y-120V
(RM)
PANEL
LC5-1
208Y/120V
3PH 4W
150A MCB
(RM)
ELEC ROOM 129
(ROOM 6C132A)
ATS8-5
(RM)
PANEL
NLP-C6-2
(LN6-2)
208Y/120V
3PH 4W
225A MCB
(RP)
PANEL
ELP-C6-2
(6LXB)
208Y/120V
3PH 4W
225A MLO
(RP)
ELEC ROOM 114
(ROOM 6C175)
ELEC ROOM 113
(ROOM 3C174)
ELECTRICAL DEVICES AND EQUIPMENT ON LEVELS ONE THROUGH THREE ARE NOT WITHIN THE SCOPE OF THIS PROJECT.
LEVEL 04
PANEL
CHL-C6-2
(6HXB)
480Y/277V
3PH 4W
225A MLO
(RP)
PANEL
NLP-C6-8
(6LB2)
208Y/120V
3PH 4W
100A MCB
(RP)
PANEL
NLP-C6-7
(6LB1)
208Y/120V
3PH 4W
150A MCB
(RP)
PANEL
NLP-C5-4
(5PLB)
208Y/120V
3PH 4W
(RM)
PANEL
NLP-C6-4
(6LB)
208Y/120V
3PH 4W
MLO
(RP)
ELECTRICAL DEVICES AND EQUIPMENT ON LEVELS SEVEN THROUGH TWELVE ARE NOT WITHIN THE SCOPE OF THIS PRJECT.
ELECTRICAL DEVICES AND EQUIPMENT ON THE ROOF AND IN THE MACHINE ROOMS ARE NOT WITHIN THE SCOPE OF THIS PROJECT.
PANEL
NHL-C6-4
(6HB)
480Y/277V
3PH 4W
225A MLO
(RP)
DISCONNECT
12XLA
(RM)
PANEL
NHL-C5-2
(LC5-2)
208Y/120V
3PH 4W
(RM)
PANEL
NHL-C4-2
(HN4-2)
480Y/277V
3PH 4W
(RM)
XFMR NX-C4-1
(XN4-2)
(RM)
XFMR CX-C5-2
(XC5-2)
480V-208Y/120V
(RM)
TO
ROOF
PANEL
NHL-C5-1
(HN4-1)
480Y/277V
3PH 4W
(RM)
FED FROM
PANEL DHN3
PANEL
5HA
480Y/277V
3PH 4W
(RM)
XFMR
112.5 kVA
480V-208Y/120V
(RM)
N
L
E
DISCONNECT
T-6LB1
(RV)
PANEL
NHL-C5-2
(HN5-2)
480Y/277V
3PH 4W
(RM)
FED FROM
PANEL DHN3
PANEL
(5HB)
480Y/277V
3PH 4W
(RM)
XFMR CX-C5-2
112.5kVA
480V-208Y/120V
(RM)
BUSDUCT
BUSDUCT
ELECTRICAL DEVICES AND EQUIPMENT ON THE GROUND LEVEL ARE NOT WITHIN THE SCOPE OF THIS PROJECT.
(RM)
(RM)
(RM)
(RM)
(RM)
(RM)
(RM)
(RM)
(RM)
(RM)
(RP)
(RM) (RM)
(RM)
(RM)
(RM)
(RM)
(RM) (RP) (RM)
(RM)
(RM)
(RM)
(RM)
(RM)
(RM)
(RM)
(RM)
(RM)
(RM)
(RM) (RM)
(RM)
(RM)
(RM)
(RM)
(RM)
(RM)
J
(RV)
(RM)
NEW WORK RISER DIAGRAM LEGEND
NEW - RPD (EXISTING DEVICED REPLACED WITH NEW)
EXISTING - EX (EXISTING DEVICE)
XFMR CX-C6-2
(XC6-2)
480V-208Y/120V
(EX)
PANEL
NHL-C6-1
(HN6-1)
480Y/277V
3PH 4W
300A MCB
(RPD)
PANEL
LN6-1
208Y/120V
3PH 4W
225A MCB
(RPD)
PANEL
6HA
480Y/277V
3PH 4W
225A
(RPD)
PANEL
6LA
208Y/120V
3PH 4W
225A
(RPD)
PANEL
NHL-C6-2
(HN6-2)
480Y/277V
3PH 4W
300A MCB
(RPD)
LEVEL 06
LEVEL 05
PANEL
CLP-C6-2
(LC6-2)
208Y/120V
3PH 4W
150A MCB
(RPD)
PANEL
CHL-C5-1
(HC5-1)
480Y/277V
3PH 4W
(EX)
XFMR CX-C6-1
(XC6-1)
45 KVA
480V-208Y/120V
(EX)
ATS5-1
300A
(EX)
N E
L
DHC3-1
PANEL
LC6-1
208Y/120V
3PH 4W
150A MCB
(RPD)
PANEL
6LXA
208Y/120V
3PH 4W
225A
(RPD)
(RLD)
PANEL
6HXA
480Y/277V
3PH 4W
100A
(RPD)
(RLD)
ATS5-2
300A
(EX)
N E
L
DHC3-1
PANEL
CHL-C5-2
(HC5-2)
480Y/277V
3PH 4W
300A MCB
(EX)
PANEL
NHL-C5-1
(HN5-1)
480Y/277V
3PH 4W
(EX)
XFMR XN5-1
45kVA
480V-208Y/120V
(EX)
PANEL
5PLA
208Y/120V
3PH 4W
(EX)
XFMR NX-C6-7
(T-6LB1)
75kVA
480V-208Y/120V
(EX)
ELEC ROOM 131
(ROOM 6C132)
XFMR CX-C5-3
(XC5-1)
45 kVA
480V-208Y-120V
(EX)
PANEL
LC5-1
208Y/120V
3PH 4W
150A MCB
(EX)
ELEC
ROOM 129
(ROOM
6C132A)
ATS8-5
(EX)
PANEL
NLP-C6-2
(LN6-2)
208Y/120V
3PH 4W
225A MCB
(RPD)
PANEL
ELP-C6-2
(6LXB)
208Y/120V
3PH 4W
225A MLO
(RPD)
ELEC ROOM 114
(ROOM 6C175)
ELEC ROOM 113
(ROOM 3C174)
ELECTRICAL DEVICES AND EQUIPMENT ON LEVELS ONE THROUGH THREE ARE NOT WITHIN THE SCOPE OF THIS PROJECT.
LEVEL 04
PANEL
CHL-C6-2
(6HXB)
480Y/277V
3PH 4W
225A MLO
(RPD)
PANEL
NLP-C6-8
(6LB2)
208Y/120V
3PH 4W
100A MCB
(RPD)
PANEL
NLP-C6-7
(6LB1)
208Y/120V
3PH 4W
150A MCB
(RPD)
PANEL
NLP-C5-4
(5PLB)
208Y/120V
3PH 4W
(EX)
PANEL
NLP-C6-4
(6LB)
208Y/120V
3PH 4W
MLO
(RPD)
ELECTRICAL DEVICES AND EQUIPMENT ON LEVELS SEVEN THROUGH TWELVE ARE NOT WITHIN THE SCOPE OF THIS PRJECT.
ELECTRICAL DEVICES AND EQUIPMENT ON THE ROOF AND IN THE MACHINE ROOMS ARE NOT WITHIN THE SCOPE OF THIS PROJECT.
PANEL
NHL-C6-4
(6HB)
480Y/277V
3PH 4W
225A MLO
(RPD)
DISCONNECT
12XLA
(EX)
PANEL
NHL-C5-2
(LC5-2)
208Y/120V
3PH 4W
(EX)
PANEL
NHL-C4-2
(HN4-2)
480Y/277V
3PH 4W
(EX)
XFMR NX-C4-1
(XN4-2)
(EX)
XFMR CX-C5-2
(XC5-2)
480V-208Y/120V
(EX)
TO
ROOF
PANEL
NHL-C5-1
(HN4-1)
480Y/277V
3PH 4W
(EX)
FED FROM
PANEL DHN3
PANEL
5HA
480Y/277V
3PH 4W
(EX)
XFMR
112.5 kVA
480V-208Y/120V
(EX)
N
L
E
PANEL
NHL-C5-2
(HN5-2)
480Y/277V
3PH 4W
(EX)
FED FROM
PANEL DHN3
PANEL
(5HB)
480Y/277V
3PH 4W
(EX)
XFMR CX-C5-2
112.5kVA
480V-208Y/120V
(EX)
BUSDUCT
ELECTRICAL DEVICES AND EQUIPMENT ON THE GROUND LEVEL ARE NOT WITHIN THE SCOPE OF THIS PROJECT.
(EX)
(EX)
(EX)
(EX)
(EX)
(EX)
(EX)
(EX) (EX)
(EX)
(4)#3/0, (1)#6, 2" C
(EX) (EX)
(EX)
(EX)
(EX)
(EX)
(EX)
(EX)
(EX)
(EX)
(EX)
(EX)
(EX)
(EX)
(EX)
(EX)
(EX)
(EX) (EX)
(EX)
(EX)
(EX)
(EX)
(EX)
J
BUSDUCT
J
SPLICE AND EXTEND
3#1, 1#6, 1 1/2"C
GENERAL NOTES
A. ALL PANELBOARDS AND DISCONNECTS FEEDING ELECTRICAL DEVICES
AND EQUIPMENT ON LEVEL 06 ARE TO BE DEMOLISHED AND REPLACED.
B. PANELBOARD AND DISCONNECT FEEDERS ARE EXISTING TO REMAIN,
UNLESS OTHERWISE NOTED.
C. ALL BRANCH CIRCUITS SUPPLYING DEVICES ON LEVEL 06 ARE TO BE
DEMOLISHED. SEE PANEL SCHEDULES FOR NEW BRANCH CIRCUITS.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
Engineering Discipline:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Consultant:
U D
B e n d e r\ L o c a l R e v it F ile s \2
\4
V A
M C
A tl a n ta th f l\
C E
C e n tr a l M o d e l.
rv t
/5 /2
:1
:3
P M
E006
ELECTRICAL - PARTIAL RISER
DIAGRAMSCHARLOTTE ENGINEERS
5838 MONROE ROAD, SUITE 100
CHARLOTTE, NC 28212
704.531.3000
GUIDON
1221 N. PENNSYLVANIA STREET
INDIANAPOLIS STREET
317.800.6388
RENOVATE 6TH FLOOR FOR 16
BED STORT STAY CLC
1670 CLAIRMONT RD, DECATUR, GA
508-22-105
C
9/21/2023 JCE NMG
100% CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
NOT TO SCALE
PARTIAL ELECTRICAL RISER DIAGRAM - DEMOLITION
NOT TO SCALE
PARTIAL ELECTRICAL RISER DIAGRAM - NEW WORK
Revisions: Date:
Addendum 2 05-06-2025
NOT A CERTIFIED DOCUMENT AS TO THE ORIGINAL DOCUMENT
BUT ONLY AS TO THE REVISION - THIS DOCUMENT ORIGINALLY
ISSUED AND SEALED BY JOHN C. EDWARDS, JR. 050482, 09-21-23
THIS DOCUMENT IS ONLY CERTIFIED AS TO THE REVISIONS.
| Sheets |
| E006 - ELECTRICAL - PARTIAL RISER DIAGRAMS |
| 2025-05-05T16:41:13-0400 | |
| Nicholas Esposito |
File details come from the government source that posted it. Updated .