E005 - ELECTRICAL - SPECIAL SYSTEM DETAILS.pdf

PDF 279 KB Posted

Attached to
Y1DA--508-22-105 | 6th Floor CLC 16-Bed Bldg. C
Solicitation number
36C24725R0029
Issued by

About this file

This document is an electrical engineering detail drawing (E005) for a telecommunications rack elevation, specifically for a renovation project at the VA Medical Center in Decatur, Georgia. The drawing provides a detailed schematic of a telecommunications rack configuration, including key components such as:

  • A 45RU channel rack with 6" vertical wire managers
  • 2RU fiber enclosure with 12-strand fiber adapter panels
  • Multiple 2U CAT6A patch panels with T568B wiring
  • Power distribution infrastructure including:
    • Zone Power Distribution Unit (ZPDU): 30 amp, 3-phase with multiple outlet types
    • 5KW, 208V Uninterruptible Power Supply (UPS)
    • Rack Power Distribution Unit (RPDU): Vertical, monitored, with 30 C13 and 6 C19 outlets

The drawing is part of a 100% construction document set for renovating the 6th floor to create a 16-bed short stay Clinical Logistics Center (CLC), with the project located at 1670 Clairmont Rd, Decatur, GA. The document is dated 9/21/2023 and includes an addendum dated 05-06-2025.

View the file

Other files

File Type Posted
E001 - ELECTRICAL - LEGENDS-SYMBOLS-DRAWING INDEX.pdf PDF
ES100 - ELECTRICAL - LEVEL 06 - NEW WORK - SPECIAL SYSTEMS.pdf PDF
E006 - ELECTRICAL - PARTIAL RISER DIAGRAMS.pdf PDF
Images.pdf PDF
01 01 45 35 - Special Inspections Worksheet.xlsx XLSX spreadsheet
36C24725R0029 0005.docx DOCX document
01 45 35 - Special Inspections.docx DOCX document
ED100 - ELECTRICAL - LEVEL 06 - DEMOLITION.pdf PDF
E007 - ELECTRCIAL - PANEL SCHEDULES.pdf PDF
RFI Responses.xlsx XLSX spreadsheet
36C24725R0029 0004.docx DOCX document
RFI Response Renovate 6th Floor CLC Bldg C.pdf PDF
DBA Wages 2-7-2025.pdf PDF
RFI ATTACHMENTS.zip ZIP file
36C24725R0029 0003.pdf PDF
36C24725R0029 0002.pdf PDF
Site Visit Attendance Sheet 508-22-105.pdf PDF
36C24725R0029 0001.docx DOCX document
Attachment 4 - Itemized Cost Breakdown.xlsx XLSX spreadsheet
Attachment 7 - Construction Drawings 508-22-105.pdf PDF
Attachment 1 - Experience Modification Rate Form.pdf PDF
36C24725R0029 Solicitation.docx DOCX document
Attachment 2 - VAAR 852.219-75 VA Notice of Limitations on Subcontracting Jan 2023 Dev.pdf PDF
Attachment 8 - Specs 508-22-105.pdf PDF
Attachment 3 - Past Performance Questionnaire -PPQ.docx DOCX document
Attachment 6 - Invoicing.docx DOCX document
Attachment 5 - DBA Wages GA20250305 01-03-2025.pdf PDF
Show all 27

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

KEYED NOTES

1 EXISTING TELECOMMUNICATIONS 45RU CHANNEL RACK.

7'H, 30"D CHANNEL MINIMUM, EXISTING RAILS, #12-24

TAPPED EIA HOLE PATTERN. PROVIDED WITH 6"W

VERTICAL WIRE MANAGERS.

2RU FIBER ENCLOSURE. USE 12 STRAND FIBER ADAPTER

PANELS FOR EXISTING FIBER FROM MCR. PROVIDE WITH

RACK-MOUNTED, 2RU CLOSET CONNECTOR HOUSING

(CCH) FOR DUPLEX LC ADAPTERS.

2RU HORIZONTAL DOUBLE-SIDED WIRE MANAGER.

OIT CAT6A PATCH PANEL FOR HORIZONTAL DATA

CABLING WITH T568B WIRING FOR 110 STYLE IDC

TERMINATIONS.

EXISTING FIBER.

CABLE TRAY MOUNTED AS SHOWN IN PLANS AND

DETAILS.

CABLE TRAY ELEVATION BRACKETS WITH A 6" STAND-OFF

FROM THE TOP OF THE EQUIPMENT RACK

ZONE POWER DISTRIBUTION UNIT, ZPDU. 30 AMP 3-

PHASE – REAR CIRCUITS WITH FOUR L21-20R AND SIX

NEMA 5-20 OUTLETS AND TWO 10' POWER CORDS

TERMINATING IN L21-30P

RACK MOUNTED 5KW, 208V UNINTERRUPTIBLE POWER

SUPPLY (UPS) WITH NEMA 20A L21-20P INPUT AND L21-20R

OUTPUT.

RACK POWER DISTRIBUTION UNIT (RPDU), VERTICAL;

MONITORED; L21-20 PLUG; THREE PHASE; 120/208V INPUT;

20A; (30) C13 (6) C19 OUTLETS; 208V OUTPUT; 3 X 2P 20A

HYDRAULIC MAGNETIC BREAKERS; LCD; ETHERNET, USB,

AND ENVIRONMENTAL SENSOR PORTS; IP AND SERIAL

MONITORING; IP CONSOLIDATION (PDU LINKING); TOOL-

LESS MOUNTING.

EXISTING RACEWAY.

FIBER ENCLOSURE

TELECOMMUNICATIONS RACK ELEVATION 1

2U FIBER ENCLOSURE

2U WIRE MANAGER

2U CAT 6A PATCH PANEL

2U WIRE MANAGER

2U CAT 6A PATCH PANEL

2U WIRE MANAGER

2U CAT 6A PATCH PANEL

2U WIRE MANAGER

2U CAT 6A PATCH PANEL

2U WIRE MANAGER

2U CAT 6A PATCH PANEL

2U WIRE MANAGER

2U CAT 6A PATCH PANEL

2U WIRE MANAGER

NTS

ZONE PDU

5 KW UPS

V E

R T

IC

A

L P

D U

S

ID

E A

V E

R T

IC

A

L P

D U

S

ID

E B

(TYP)

(TYP)

(TYP)

(TYP)

(TYP)

MAIN IT ROOM

TR ROOM 11

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

Engineering Discipline:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Consultant:

U D

B e n d e r\ L o c a l R e v it F ile s \2

\4

V A

M C

A tl a n ta th f l\

C E

C e n tr a l M o d e l.

rv t

/5 /2

:1

:2

P M

E005

ELECTRICAL - SPECIAL SYSTEM

DETAILSCHARLOTTE ENGINEERS

5838 MONROE ROAD, SUITE 100

CHARLOTTE, NC 28212

704.531.3000

GUIDON

1221 N. PENNSYLVANIA STREET

INDIANAPOLIS STREET

317.800.6388

RENOVATE 6TH FLOOR FOR 16

BED STORT STAY CLC

1670 CLAIRMONT RD, DECATUR, GA

508-22-105

C

9/21/2023 JCE NMG

100% CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

Revisions: Date:

Addendum 2 05-06-2025

NOT A CERTIFIED DOCUMENT AS TO THE ORIGINAL DOCUMENT

BUT ONLY AS TO THE REVISION - THIS DOCUMENT ORIGINALLY

ISSUED AND SEALED BY JOHN C. EDWARDS, JR. 050482, 09-21-23

THIS DOCUMENT IS ONLY CERTIFIED AS TO THE REVISIONS.

Sheets
E001 - ELECTRICAL - LEGENDS, SYMBOLS, AND DRAWING INDEX
E004 - ELECTRICAL - SPECIAL SYSTEM DETAILS
E005 - ELECTRICAL - SPECIAL SYSTEM DETAILS
E006 - ELECTRICAL - PARTIAL RISER DIAGRAMS
E007 - ELECTRCIAL - PANEL SCHEDULES
ED100 - ELECTRICAL - LEVEL 06 - DEMOLITION
ES100 - ELECTRICAL - LEVEL 06 - NEW WORK - SPECIAL SYSTEMS
2025-05-05T16:36:02-0400
Nicholas Esposito

File details come from the government source that posted it. Updated .