E001 - ELECTRICAL - LEGENDS-SYMBOLS-DRAWING INDEX.pdf
PDF 322 KB Posted
- Attached to
- Y1DA--508-22-105 | 6th Floor CLC 16-Bed Bldg. C
- Solicitation number
- 36C24725R0029
About this file
This document is an electrical legends, symbols, and drawing index sheet for a VA Medical Center renovation project. The file details electrical symbols, abbreviations, and drawing conventions for a 16-bed Short Stay Clinical Logistics Center (CLC) renovation on the 6th floor of Building C at the VA Medical Center located in Decatur, Georgia. The project number is 508-22-105, with construction documents issued at 100% completion on 9/21/2023 by Charlotte Engineers for the Department of Veterans Affairs.
The drawing index includes 10 electrical-related sheets covering legends, symbols, special system details, riser diagrams, panel schedules, demolition plans, and new work drawings for lighting, power, and special systems on the 6th floor. Key technical notes include requirements for electrical materials (all to be listed and labeled by a nationally recognized testing agency), power outage coordination, demolition procedures, and compliance with electrical energy codes such as ASHRAE 90.1 and the National Electrical Code (NEC).
View the file
Other files
Show all 27
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
( NOTE: SYMBOLS WITHIN THIS SCHEDULE ARE REPRESENTATIVE OF THOSE TYPICALLY FOUND ON THE DRAWINGS. ALL SYMBOLS MAY NOT APPEAR ON THIS SET OF DRAWINGS. )ELECTRICAL SYMBOLS
DIMENSION INDICATES HEIGHT, AFF, AT WHICH DEVICE IS TO BE MOUNTED.
ON CENTER.
ABOVE FINISHED FLOOR TO CENTERLINE OF DEVICE.
TELEPHONE TERMINAL BOARD.
EMPTY CONDUIT.
ABBREVIATIONS
AFF
EC
OC
TTB
+60"
NIGHT LIGHTING, 24 HOUR, OPERATION. WIRE AHEAD OF ALL LOCAL SWITCHES.NL
LED LIGHTING FIXTURE, WALL MOUNTED OR UNDER CABINET, CONNECTED TO NORMAL POWER.
LED LIGHTING FIXTURE, CEILING OR WALL MOUNTED,
POLE MOUNTED LIGHTING FIXTURE. SEE SCHEDULE FOR TYPE (*).
DRAWINGS. SEE SCHEDULE FOR TYPE (*).
CEILING OR WALL MOUNTED EXIT SIGN. PROVIDE NUMBER OF FACES AND CHEVRONS AS INDICATED ON
EMERGENCY LIGHTING FIXTURE, CEILING-MOUNTED OR WALL-MOUNTED AT 7'-6" AFF UNLESS NOTED
OTHERWISE. CONNECT UNSWITCHED.
LIGHTING
LED LIGHTING WALLWASH FIXTURE, CEILING MOUNTED.
TRACK LIGHTING FIXTURE. SEE PLANS/SCHEDULE FOR TRACK LENGTH AND NUMBER OF TRACK HEADS.
EQUIPMENT IDENTIFICATION
HORSEPOWER RATING
MOTOR CONNECTION. SPECIAL VOLTAGES AS SHOWN ON DRAWING.
ENCLOSED CIRCUIT BREAKER. NUMERAL INDICATES TRIP AMPERE RATING.
FUSED SAFETY SWITCH. NUMERAL INDICATES FUSE RATING.
NON-FUSIBLE SAFETY SWITCH. NUMERAL INDICATES AMPERE RATING.
SIZE AND BOTTOM NUMERAL INDICATES NEMA STARTER SIZE.
COMBINATION MOTOR STARTER WITH CIRCUIT BREAKER. TOP NUMERAL INDICATES CIRCUIT BREAKER
MOTOR STARTER. NUMERAL INDICATES NEMA SIZE.
AMPACITY. SEE FEEDER SCHEDULE.
ON RISERS, DESIGNATION DENOTES QUANTITY OF CURRENT CARRYING CONDUCTORS AND FEEDER
WIRING SYSTEM CONCEALED IN OR ABOVE CEILING OR IN WALL.
WIRING SYSTEM BELOW FLOOR OR BELOW GRADE.
DESIGNATION DENOTES PANEL BOARD, SWITCHBOARD, MOTOR CONTROL CENTER, ETC., AND OVERCURRENT BRANCH OR FEEDER CIRCUIT HOMERUN TO PANEL BOARD, SWITCHBOARD, MOTOR CONTROL CENTER, ETC.
WIRING SYSTEM TURNED UP.
WIRING SYSTEM TURNED DOWN.
WIRING SYSTEM EXPOSED.
PROTECTION DEVICE NUMBER.
DRY TYPE TRANSFORMER.
NEC REQUIRED GROUND.
EF-1, 10 HP.460V, 3∅
208V, 3∅
120V, 1∅
MOTOR RATED SWITCH.
CONNECTION TO WALL MOUNTED FILM ILLUMINATOR. PROVIDE RECEPTACLE IN FLUSH OUTLET BOX AT
LOWER RIGHT HAND CORNER OF UNIT IF SURFACE MOUNTED. HARD WIRE IF RECESSED.
JUNCTION BOX AND CONNECTION TO EQUIPMENT OR TERMINAL STRIPS.
CEILING FAN 120V. MANUFACTURER (HUNTER#21252 GREEN FINISH W/ INTEGRATED 240W LIGHT FIXTURE)
CONNECTION TO HEADWALL UNIT. ONE NORMAL POWER CIRCUIT. ONE CRITICAL POWER CIRCUIT, CONNECTION TO FAN COIL UNIT. COORDINATE EXACT LOCATION WITH MECHANICAL CONTRACTOR.
AND ONE DEDICATED CRITICAL POWER CIRCUIT FOR VENTILATOR.
CONNECTION TO EXHAUST FAN. COORDINATE EXACT LOCATION WITH MECHANICAL CONTRACTOR.
PANELBOARD SURFACE MOUNTED.
REMOTE ALARM PANEL FOR ISOLATED POWER PANEL BOARD WALL MOUNTED AT 5'-0" AFF.
GENERATOR REMOTE ALARM ANNUNCIATOR. WALL MOUNTED AT 5'-0" AFF.
PANELBOARD FLUSH MOUNTED.
JUNCTION OR PULL BOX. W = WEATHERPROOF.
CONDUIT STUBBED INTO ACCESSIBLE CEILING SPACE.
HARDWIRE CONNECTION FROM FLUSH MOUNTED JUNCTION BOX WITH APPROPRIATE COVERPLATE AND 3/4" LIQUID TIGHT FLEXIBLE METALLIC WHIP TO PRE-WIRED FURNITURE. COORDINATE EXACT REQUIREMENTS AND LOCATION WITH EQUIPMENT SUPPLIER/INSTALLER. EIGHT(8) WIRE SYSTEM PROVIDES FOUR(4) CIRCUITS.
POWER
SURFACE MOUNTED MULTIOUTLET ASSEMBLY. 46" AFF OR 8" ABOVE COUNTER
TV = TELEVISION, SEE DETAIL.
G = GROUND FAULT CIRCUIT INTERRUPTER.
EWC = ELECTRIC WATER COOLER POWER CONNECTION, PROVIDE GROUND FAULT CIRCUIT INTERRUPTER
P = PEDESTAL
WP = WEATHERPROOF "IN-USE" COVER, PROVIDE GROUND FAULT CIRCUIT INTERRUPTER DEVICE.
DUPLEX RECEPTACLE, MOUNTED 18" AFF TO CENTER OF DEVICE. NEMA 5-20R UNLESS OTHERWISE
OR 2" ABOVE BACKSPLASH. SHADED AREA INDICATES RECEPTACLE.
DUPLEX RECEPTACLE IN FLUSH POKE-THRU DEVICE. 3-1/16" HOLE SIZE. BRUSHED ALUMINUM FUNISH.
SIMPLEX RECEPTACLE MOUNTED 18" AFF TO CENTER OF DEVICE. NEMA 5-20R UNLESS OTHERWISE
TWO DUPLEX RECEPTACLES IN 2-GANG BOX, MOUNTED 48" AFF TO CENTER OF OUTLET
OR 2" FROM BOTTOM OF OUTLET TO TOP OF BACKSPLASH OR COUNTERTOP. SLASH INDICATES
OUTLET TO TOP OF BACKSPLASH OR COUNTERTOP. SLASH INDICATES CONNECTED TO THE EMERGENCY
DUPLEX RECEPTACLE, MOUNTED 48" AFF TO CENTER OF OUTLET OR 2" FROM BOTTOM OF
TWO DUPLEX RECEPTACLES IN 2-GANG BOX, MOUNTED 18" AFF TO CENTER OF DEVICE. SLASH
DUPLEX RECEPTACLE OUTLET. CEILING MOUNTED.
SPECIAL RECEPTACLE OUTLET. NEMA CONFIGURATION AS INDICATED.
MODIFIERS FOR RECEPTACLES:
SPECIAL RECEPTACLE OUTLET. FLUSH FLOOR MOUNTED. NEMA CONFIGURATION AS INDICATED.
LH2A-1
POWER POLE. DEVICE CONFIGURATION AND COLOR AS INDICATED.
M
RATING AND BOTTOM NUMERAL INDICATES NEMA STARTER SIZE.
COMBINATION MOTOR STARTER WITH FUSED SWITCH. TOP NUMERAL INDICATES FUSETRON AMPERE
LIGHTNING PROTECTION SYSTEM GROUND ROD.
75KVA
T
LIGHTNING PROTECTION SYSTEM AIR TERMINAL.
TR = TAMPER RESISTANT
3 = THREE WAY
MODIFIERS FOR SWITCHES:
SINGLE POLE SWITCH, MOUNTED 48" AFF TO CENTER OF DEVICE.
THREE SINGLE POLE SWITCHES IN A 3-GANG BOX, MOUNTED 48" AFF TO CENTER OF DEVICE.
PHOTO ELECTRIC CELL MOUNTED ON CONDUIT STUBBED 6" ABOVE ROOF, FACING NORTH.
SWITCHES
TWO SINGLE POLE SWITCHES IN A 2-GANG BOX, MOUNTED 48" AFF TO CENTER OF DEVICE.
PROVIDE DIVIDER FOR DIFFERENT VOLTAGES OR BRANCHES.
4 = FOUR WAY
D = DIMMER
DT = DOUBLE THROW
LV = LOW VOLTAGE
TWO SINGLE POLE SWITCHES IN A 2-GANG BOX, MOUNTED 48" AFF TO CENTER OF DEVICE, TO COMPLY WITH ENERGY CODE. EITHER SWITCH INBOARD AND OUTBOARD LAMPS SEPARATELY OR STEP-DIM BOTH
PROVIDE DIVIDER(S) FOR DIFFERENT VOLTAGES OR BRANCHES.
OS = OCCUPANCY SENSOR
TIME CLOCK. PROVIDE POWER CIRCUIT AND 3/4" CONDUIT TO ACCESSIBLE CEILING SPACE.
a,b,c = MULTIPLE SWITCH LEGS
T = TIMER
INDICATED.
INDICATED. SLASH INDICATES CONNECTED TO THE EMERGENCY POWER SYSTEM.
INDICATES CONNECTED TO THE EMERGENCY POWER SYSTEM.
CONNECTED TO NORMAL POWER. SEE SCHEDULE FOR TYPE (*). SEE ARCHITECTURAL RCP FOR EXACT
LUMINAIRE, CEILING MOUNTED, CONNECTED TO THE NORMAL POWER SYSTEM (UNLESS OTHERWISE NOTED).
SEE SCHEDULE FOR TYPE (*). SEE ARCHITECTURAL RCP FOR EXACT LOCATION AND CEILING TYPE.
LOCATION AND CEILING TYPE. SLASH INDICATES CONNECTED TO THE CRITICAL BRANCH.
SEE SCHEDULE FOR TYPE (*).
SEE SCHEDULE FOR TYPE (*).
REMOTE EMERGENCY EGRESS TWIN-LAMP UNIT.
HALF-SHADED INDICATES CONNECTED TO LIFE SAFETY BRANCH.
LAMPS TO 50%.
SLASH INDICATES CONNECTED TO THE CRITICAL BRANCH. HALF-SHADED INDICATES CONNECTED TO THE EMERGENCY OR LIFE SAFETY BRANCH; VIA EMERGENCY GENERATOR SET OR BATTERY BALLAST, SEE PLANS.
SLASH INDICATES CONNECTED TO THE CRITICAL BRANCH. SEE SCHEDULE FOR TYPE (*).
HEADWALL. SEE PLAN FOR NUMBER.HW#
POWER COLUMN. SEE PLAN FOR NUMBER.PC#
POWER SYSTEM.
CONNECTED TO THE EMERGENCY POWER SYSTEM.
LED STRIP LUMINAIRE. CEILING MOUNTED OR SUSPENDED 8'-0" AFF TO BOTTOM OF LUMINAIRE, CONNECTED TO NORMAL POWER. SLASH INDICATES CONNECTED TO THE CRITICAL BRANCH.
HALF-SHADED INDICATES CONNECTED TO THE EMERGENCY OR LIFE SAFETY BRANCH; VIA EMERGENCY
GENERATOR SET OR BATTERY BALLAST, SEE PLANS.
REMOTE LINE ISOLATION MONITOR.
VARIABLE SPEED DRIVEVSD
PNEUMATIC TUBE STATIONPTS
DEVICE. INSTALL DEVICE SO IT IS CONCEALED BEHIND ENCLOSURE, COORDINATE WITH PLUMBING.
SHOWN TO CLARIFY THAT DEVICES/LUMINAIRES ON THE SAME CIRCUIT ARE CONTROLLED SEPARATELY.
POLE MOUNTED LIGHTING FIXTURE. SEE SCHEDULE FOR TYPE (*).
SYMBOL LOCATION LEADER
4/350
LIM
RA
GA
J
E
C
M
H
F
P
P
S
P
J
TC
PE
SS
SSS
SS
S
DUAL TECHNOLOGY CEILING MOUNTED OCCUPANCY SENSOR. PROVIDE ONE POWER PACK FOR EACHOS
SENSOR. COORDINATE WIRING REQUIREMENTS WITH EQUIPMENT SUPPLIER PRIOR TO ROUGH-IN.
GENERAL PROJECT NOTESELECTRICAL ENERGY CODE SUMMARY
ELECTRICAL SUMMARY
ELECTRICAL SYSTEM AND EQUIPMENT
Method of Compliance:
Prescriptive Performance
Lighting schedule lamp type required in fixture number of lamps in fixture ballast type used in the fixture number of ballasts in fixture total wattage per fixture total interior wattage specified vs. allowed NO ADDITIONAL LIGHTING LOAD ADDED total exterior wattage specified vs. allowed N/A
Additional Efficiency Package Options
C406.2 More Efficient HVAC Equipment Performance
C406.3 Reduced Lighting Power Density
C406.4 Enhanced Digital Lighting Controls
C406.5 On-Site Renewable Energy
C406.6 Dedicated Outdoor Air System
Energy Code:
ASHRAE 90.1: Prescriptive Performance
C406.7 Reduced Energy Use in Service Water Heating
(When using the 2018 NCECC; not required for ASHRAE 90.1)
A. THE DRAWINGS SHALL NOT BE SCALED FOR CONSTRUCTION PURPOSES. THE SCALE, WHEN
INDICATED, IS INTENDED FOR REFERENCE PURPOSES ONLY.
B. ALL POWER OUTAGES SHALL BE COORDINATED AND APPROVED THROUGH THE OWNERS'
REPRESENTATIVE AND REQUIRE ADVANCE NOTICE OF AT LEAST TWO (2) WEEKS. AT THE
OWNER'S REPRESENTATIVE’S DISCRETION, THIS TIME LENGTH MAY BE INCREASED OR
DECREASED, DEPENDING ON THE SYSTEMS IMPACTED BY THE POWER OUTAGE.
C. CONSTRUCTION DEBRIS SHALL BE REMOVED DAILY, OR AT THE OWNER'S REPRESENTATIVE’S
DISCRETION.
D. ALL ELECTRICAL MATERIAL, DEVICES, APPLIANCES, AND FIXED EQUIPMENT PROVIDED SHALL
BE LISTED AND LABELED BY A NATIONALLY RECOGNIZED AND STATE APPROVED THIRD PARTY
TESTING AGENCY. FACTORY LISTED COMPONENTS ASSEMBLED TOGETHER SHALL BE
REVIEWED AND LABELED AS AN ASSEMBLY BY THE STATE APPROVED TESTING AGENCY.
E. FIRE ALARM APPLIANCES AND DEVICES SHOWN IN AN AREA INDICATE TO PROVIDE COVERAGE
IN THAT AREA. ELECTRICAL CONTRACTOR SHALL PROVIDE APPLIANCES AND DEVICES AS
REQUIRED BY THE LATEST EDITION OF NFPA 72 AND THE BUILDING CODE. NO CHANGE ORDERS
WILL BE ALLOWED FOR APPLIANCES AND DEVICES REQUIRED BY NFPA 72 AND THE BUILDING
CODE.
F. CONTRACTOR SHALL COORDINATE WITH THE FACILITY'S INFECTION CONTROL OFFICER TO
VERIFY THAT APPROPRIATE SAFEGUARDS ARE BEING TAKEN TO PROTECT WORKERS
INVOLVED IN DEMOLITION ACTIVITIES.
G. CONTRACTOR SHALL COORDINATE WITH THE FACILITY'S INFECTION CONTROL OFFICER TO
VERIFY THAT APPROPRIATE PRECAUTIONS ARE BEING TAKEN TO PROTECT FACILITY STAFF
AND PATIENTS DURING THE CONSTRUCTION ACTIVITIES.
H. ASBESTOS CONTAINING MATERIALS (IF PRESENT) WILL BE IDENTIFIED BY THE OWNER AND WILL BE REMOVED FROM AHU'S, PIPING INSULATION, DUCT INSULATION, ETC. (IF REQUIRED)
PRIOR TO CONTRACTOR BEGINNING ANY WORK ON THE SITE. COORDINATE WITH THE OWNER.
I. ELECTRICAL WORK SHALL BE COMPLETED ACCORDING TO THE TRUE INTENT AND MEANING AS
INDICATED IN THE CONTRACT DOCUMENTS. ANYTHING NOT ENTIRELY CLEAR SHALL BE
EXPLAINED IF SUBMITTED TO THE ARCHITECT/ENGINEER IN WRITING.
J. CONNECTIONS OF FEEDERS AND BRANCH CIRCUITS TO SWITCHBOARDS/PANELBOARDS SHALL
BE DONE IN A MANNER AS TO LIMIT THE OUTAGES TO AN ABSOLUTE MINIMUM.
K. ALL TERMINATIONS, CONDUCTORS, AND DEVICES SHALL BE 75 DEGREE CELSIUS RATED, TO
THE EXTENT FEASIBLE; OTHERWISE COMPLY WITH NEC ARTICLE 110.14(C)(1).
L. ELECTRICAL CONTRACTOR SHALL NOT ROUTE WIRING CONNECTED TO THE LIFE SAFETY
BRANCH OR THE CRITICAL BRANCH IN FLEXIBLE METAL RACEWAYS OR METAL SHEATHED
CABLE ASSEMBLIES, EXCEPT AS ALLOWED BY NEC ARTICLE 517.31(C)(3)(3).
M. ELECTRICAL CONTRACTOR SHALL PROVIDE RACEWAYS, JUNCTION BOXES, CABINETS, ETC., IN
ORDER TO SEPARATE THE LIFE SAFETY BRANCH AND/OR THE CRITICAL BRANCH CIRCUIT
WIRING FROM THE WIRING AND EQUIPMENT SERVED BY ANY OTHER BRANCHES OF POWER.
N. UNLESS OTHERWISE NOTED FOR MEDICAL EQUIPMENT, ELECTRICAL CONTRACTOR SHALL
INSTALL ALL RACEWAY, BOXES, AND CABLES. THE CABLES, UNLESS OTHERWISE NOTED, SHALL
BE PROVIDED BY THE MEDICAL EQUIPMENT VENDOR.
O. ELECTRICAL WORK SHALL BE COMPLETED ACCORDING TO THE PHASES SHOWN ON THE
ARCHITECTURAL PLANS OR AS ESTABLISHED IN THE "GENERAL CONDITIONS".
P. THE EQUIPMENT GROUNDING TERMINAL BUSES OF THE NORMAL AND THE ESSENTIAL
ELECTRICAL SYSTEM BRANCH-CIRCUIT PANELBOARDS, SERVING THE SAME INDIVIDUAL
PATIENT CARE VICINITY, SHALL BE BONDED TOGETHER WITH A CONTINUOUS, INSULATED
COPPER GROUNDING CONDUCTOR NOT SMALLER THAN 10 AWG.
Q. A MAXIMUM OF THREE (3) 20 AMPERE, 1 POLE BRANCH CIRCUITS MAY BE COMBINED IN A
COMMON HOMERUN SHARING A COMMON GROUNDED (NEUTRAL) OR WITH DEDICATED
SEPARATE NEUTRALS (GROUNDED CONDUCTORS), FOR A TOTAL OF SIX CURRENT CARRYING
CONDUCTORS. ALL BRANCH CIRCUITS LARGER THAN 20A SHALL BE SEPARATELY HOMERUN TO
THE PANELBOARD.
R. ALL CONDUCTORS SHALL BE COPPER, RATED AT NOT LESS THAN 600 VOLTS. MINIMUM SIZE
SHALL BE NO. 12 AWG, UNLESS OTHERWISE NOTED ON THE DRAWINGS. ALL CONDUCTORS #8
AWG AND LARGER SHALL BE STRANDED. #10 THRU #12 AWG CONDUCTORS SHALL BE SOLID.
ALL INSULATION TYPES SHALL BE THWN OR THHN, UNLESS OTHERWISE NOTED.
S. ELECTRICAL CONTRACTOR SHALL USE MULTI-POLE CIRCUIT BREAKERS FOR ALL BRANCH
CIRCUITS WITH SHARED NEUTRALS (GROUNDED CONDUCTORS) PER NEC ARTICLE 210.4(B) OR
PROVIDE SEPARATE NEUTRALS (GROUNDED CONDUCTORS) FOR EACH BRANCH CIRCUIT.
PANELBOARD SCHEDULES SHALL INDICATE IF MULTI-POLE OR SINGLE-POLE CIRCUIT
BREAKERS WERE USED.
T. ALL WORK ASSOCIATED WITH VOICE, DATA, CCTV, CATV, NURSE CALL, WI-FI, PUBLIC ADDRESS, SECURITY ACCESS, TO BE PROVIDED UNDER THIS CONTRACT. THE ELECTRICAL CONTRACTOR
SHALL PROVIDE BACK BOXES AND CONDUIT STUBBED-UP, TO ACCESSIBLE CORRIDOR CEILING
SPACE, WITH PULL WIRE.
U. ALL 20 AMPERE SINGLE PHASE BRANCH CIRCUIT WIRING, TO PREVENT A VOLTAGE DROP
EXCEEDING 3%, SHALL BE IN ACCORDANCE WITH THE FOLLOWING TABLE:
V. A SHORT-CIRCUIT/ARC FLASH AND SELECTIVE COORDINATION STUDY SHALL BE PREPARED
FOR THE ELECTRICAL OVERCURRENT DEVICES BEING INSTALLED FOR THIS PROJECT. FINAL
FIELD SETTINGS AND MODIFICATIONS OF THE OVERCURRENT PROTECTIVE DEVICES SHALL BE
MADE TO CONFIRM WITH THE STUDY, WITHOUT ADDITIONAL COST OR TIME TO THE OWNER.
W. ALL BREAKERS 600 AMPERES AND ABOVE SHALL BE SOLID-STATE TYPE. SELECT ELECTRONIC
TRIP FUNCTIONS FOR LOW-VOLTAGE CIRCUIT BREAKERS SO AS TO ACHIEVE SELECTIVE
COORDINATION AS REQUIRED BY NFPA 70 (NEC).
X. LIGHTING LAYOUTS ARE BASED ON LIGHTING LEVELS RECOMMENDED BY THE IESNA
(ILLUMINATING ENGINEERING SOCIETY OF NORTH AMERICA). LIGHT LEVELS ARE AFFECTED BY
ENVIRONMENTAL CONDITIONS SUCH AS THE COLOR OF FINISHES (CEILINGS, WALLS, FLOORS,
ETC.), WINDOW TREATMENTS, FURNISHINGS, AND FINAL LUMINAIRE SELECTIONS. ALL
ENVIRONMENTAL CONDITIONS MAY NOT BE ESTABLISHED DURING DESIGN, WHICH MAY IMPACT
THE LIGHTING LEVELS UPON THE COMPLETION OF CONSTRUCTION. BASIS OF DESIGN LIGHTING
CALCULATIONS FOR SPECIFIC AREAS ARE AVAILABLE UPON REQUEST.
VOLTS DISTANCE TO FIRST
OUTLET
HOMERUN REMAINDER OF CIRCUIT
120V
208V
277V
480V
0'-55'
55'-95'
95'-145'
145'-230'
0'-95'
95'-160'
160'-250'
0'-125'
125'-220'
220'-335'
0'-225'
225'-380'
380'-585'
#12
#10
#8
#6
#12
#10
#8
#12
#10
#8
#12
#10
#8
#12
#12
#12
#12
#12
#12
#12
#12
#12
#12
#12
#12
#12
Y. ALL DEMOLITION WORK SHALL BE COORDINATED WITH THE OWNER PRIOR TO BEGINNING
THE WORK.
Z. ALL ELECTRICAL DEVICES, LUMINAIRES, WIRING, AND RACEWAYS IN WALLS AND IN
CEILINGS BEING DEMOLISHED SHALL BE REMOVED, UNLESS OTHERWISE NOTED.
RECONNECT EXISTING DEVICES AND LUMINIRES DOWNSTREAM OF THOSE BEING
REMOVED. WIRING AND RACEWAYS SHALL BE REMOVED BACK TO THEIR SOURCE OF
POWER, UNLESS OTHERWISE NOTED.
AA. EXISTING ELECTRICAL WORK SHOWN TO REMAIN, BUT INTERFERES WITH THE NEW WORK,
SHALL BE REWORKED AND RELOCATED TO AVOID ANY INTERFERENCE.
BB. ELECTRICAL DEMOLITION WORK SHALL BE PHASED. THE ELECTRICAL CONTRACTOR SHALL
DEVELOP A PHASING PLAN THAT WILL WORK WITH THE ARCHITECT’S OVERALL PHASING
PLAN, THE WORK TO BE PERFORMED BY OTHER TRADES, AND TO MAINTAIN THE OWNER’S
OPERATIONS.
CC. ELECTRICAL CONTRACTOR SHALL PROVIDE TEMPORARY POWER TO MAINTAIN THE
OWNER’S OPERATIONS, AT NO EXTRA COST OR TIME TO THE OWNER, IN ORDER TO KEEP
THE BUILDING IN OPERATION DURING EACH PHASE OF THE PROJECT.
DD. REMOVE EXISTING ELECTRICAL GEAR AS SHOWN. DEMOLITION OF FEEDERS AND BRANCH
CIRCUITS OR TRANSFERRING FEEDERS AND BRANCH CIRCUITS TO NEW PANELBOARDS,
SHALL BE PERFORMED IN A MANNER AS TO KEEP DOWNTIME AND OUTAGES TO AN
ABSOLUTE MINIMUM.
EE. ELECTRICAL CONTRACTOR SHALL PREPARE AN OUTAGE PLAN, INCLUDING PROVISIONS
FOR TEMPORARY POWER, AND SUBMIT IT WITH THEIR BID. THE OUTAGE PLAN SHALL
INCLUDE ALL OUTAGES REQUIRED TO PERFORM THE WORK SHOWN IN THE CONTRACT
DOCUMENTS. NO EXTRA COST OR TIME TO THE OWNER SHALL BE CONSIDERED FOR NOT
INCLUDING REQUIRED OUTAGES. ALL OUTAGES SHALL BE COORDINATED WITH, AND
APPROVED BY, THE OWNER AT LEAST TWO (2) WEEKS IN ADVANCE. AT THE OWNER’S
DISCRETION, THIS TIME MAY BE LONGER OR SHORTER FOR SOME SHUTDOWNS.
FF. ELECTRICAL CONTRACTOR SHALL REMOVE ALL ELECTRICAL ITEMS ASSOCIATED WITH
DEMOLITION WORK SHOWN ON THE ARCHITECTURAL, CIVIL, STRUCTURAL, INTERIOR,
PLUMBING, MECHANICAL, AND FIRE PROTECTION DRAWINGS.
GG. EXISTING ELECTRICAL CONDITIONS ARE BASED UPON SITE SURVEY INFORMATION AND
EXISTING RECORD/AS-BUILT DRAWINGS MADE AVAILABLE FROM THE OWNER. ELECTRICAL
WORK SHOWN CONVEYS THE GENERAL SCOPE OF THE DEMOLITION WORK TO BE
PERFORMED. THE ELECTRICAL CONTRACTOR SHALL VISIT THE SITE AND OBSERVE THE
EXISTING CONDITIONS PRIOR TO BIDDING. NO CHANGE ORDERS WILL BE CONSIDERED FOR
CONDITIONS EASILY VISIBLE DURING A SITE VISIT.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
Engineering Discipline:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Consultant:
U D
B e n d e r\ L o c a l R e v it F ile s \2
\4
V A
M C
A tl a n ta th f l\
C E
C e n tr a l M o d e l.
rv t
/5 /2
:3
:1
P M
E001
ELECTRICAL - LEGENDS,
SYMBOLS, AND DRAWING INDEX
CHARLOTTE ENGINEERS
5838 MONROE ROAD, SUITE 100
CHARLOTTE, NC 28212
704.531.3000
GUIDON
1221 N. PENNSYLVANIA STREET
INDIANAPOLIS STREET
317.800.6388
RENOVATE 6TH FLOOR FOR 16
BED STORT STAY CLC
1670 CLAIRMONT RD, DECATUR, GA
508-22-105
C
9/21/2023 JCE NMG
100% CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
ELECTRICAL - DRAWING INDEX
Sheet Number Sheet Name
E001 ELECTRICAL - LEGENDS, SYMBOLS, AND DRAWING INDEX
E002 ELECTRICAL - SPECIAL SYSTEMS SYMBOLS, AND NOTES
E003 ELECTRICAL - DETAILS & LUMINAIRE SCHEDULE
E004 ELECTRICAL - SPECIAL SYSTEM DETAILS
E005 ELECTRICAL - SPECIAL SYSTEM DETAILS
E006 ELECTRICAL - PARTIAL RISER DIAGRAMS
E007 ELECTRCIAL - PANEL SCHEDULES
E008 ELECTRICAL - PANEL SCHEDULES
E009 ELECTRICAL - PANEL SCHEDULES
ED100 ELECTRICAL - LEVEL 06 - DEMOLITION
EL100 ELECTRICAL - LEVEL 06 - NEW WORK - LIGHTING
EP100 ELECTRICAL - LEVEL 06 - NEW WORK - POWER
ES100 ELECTRICAL - LEVEL 06 - NEW WORK - SPECIAL SYSTEMS
Revisions: Date:
Addendum 2 05-06-2025
NOT A CERTIFIED DOCUMENT AS TO THE ORIGINAL DOCUMENT
BUT ONLY AS TO THE REVISION - THIS DOCUMENT ORIGINALLY
ISSUED AND SEALED BY JOHN C. EDWARDS, JR. 050482, 09-21-23
THIS DOCUMENT IS ONLY CERTIFIED AS TO THE REVISIONS.
| Sheets |
| E001 - ELECTRICAL - LEGENDS, SYMBOLS, AND DRAWING INDEX |
| 2025-05-05T16:41:41-0400 | |
| Nicholas Esposito |