E001 - ELECTRICAL - LEGENDS-SYMBOLS-DRAWING INDEX.pdf

PDF 322 KB Posted

Attached to
Y1DA--508-22-105 | 6th Floor CLC 16-Bed Bldg. C
Solicitation number
36C24725R0029
Issued by

About this file

This document is an electrical legends, symbols, and drawing index sheet for a VA Medical Center renovation project. The file details electrical symbols, abbreviations, and drawing conventions for a 16-bed Short Stay Clinical Logistics Center (CLC) renovation on the 6th floor of Building C at the VA Medical Center located in Decatur, Georgia. The project number is 508-22-105, with construction documents issued at 100% completion on 9/21/2023 by Charlotte Engineers for the Department of Veterans Affairs.

The drawing index includes 10 electrical-related sheets covering legends, symbols, special system details, riser diagrams, panel schedules, demolition plans, and new work drawings for lighting, power, and special systems on the 6th floor. Key technical notes include requirements for electrical materials (all to be listed and labeled by a nationally recognized testing agency), power outage coordination, demolition procedures, and compliance with electrical energy codes such as ASHRAE 90.1 and the National Electrical Code (NEC).

View the file

Other files

File Type Posted
ES100 - ELECTRICAL - LEVEL 06 - NEW WORK - SPECIAL SYSTEMS.pdf PDF
E005 - ELECTRICAL - SPECIAL SYSTEM DETAILS.pdf PDF
E006 - ELECTRICAL - PARTIAL RISER DIAGRAMS.pdf PDF
Images.pdf PDF
01 01 45 35 - Special Inspections Worksheet.xlsx XLSX spreadsheet
36C24725R0029 0005.docx DOCX document
01 45 35 - Special Inspections.docx DOCX document
ED100 - ELECTRICAL - LEVEL 06 - DEMOLITION.pdf PDF
E007 - ELECTRCIAL - PANEL SCHEDULES.pdf PDF
RFI Responses.xlsx XLSX spreadsheet
36C24725R0029 0004.docx DOCX document
RFI Response Renovate 6th Floor CLC Bldg C.pdf PDF
DBA Wages 2-7-2025.pdf PDF
RFI ATTACHMENTS.zip ZIP file
36C24725R0029 0003.pdf PDF
36C24725R0029 0002.pdf PDF
Site Visit Attendance Sheet 508-22-105.pdf PDF
36C24725R0029 0001.docx DOCX document
Attachment 4 - Itemized Cost Breakdown.xlsx XLSX spreadsheet
Attachment 7 - Construction Drawings 508-22-105.pdf PDF
Attachment 1 - Experience Modification Rate Form.pdf PDF
36C24725R0029 Solicitation.docx DOCX document
Attachment 2 - VAAR 852.219-75 VA Notice of Limitations on Subcontracting Jan 2023 Dev.pdf PDF
Attachment 8 - Specs 508-22-105.pdf PDF
Attachment 3 - Past Performance Questionnaire -PPQ.docx DOCX document
Attachment 6 - Invoicing.docx DOCX document
Attachment 5 - DBA Wages GA20250305 01-03-2025.pdf PDF
Show all 27

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

( NOTE: SYMBOLS WITHIN THIS SCHEDULE ARE REPRESENTATIVE OF THOSE TYPICALLY FOUND ON THE DRAWINGS. ALL SYMBOLS MAY NOT APPEAR ON THIS SET OF DRAWINGS. )ELECTRICAL SYMBOLS

DIMENSION INDICATES HEIGHT, AFF, AT WHICH DEVICE IS TO BE MOUNTED.

ON CENTER.

ABOVE FINISHED FLOOR TO CENTERLINE OF DEVICE.

TELEPHONE TERMINAL BOARD.

EMPTY CONDUIT.

ABBREVIATIONS

AFF

EC

OC

TTB

+60"

NIGHT LIGHTING, 24 HOUR, OPERATION. WIRE AHEAD OF ALL LOCAL SWITCHES.NL

LED LIGHTING FIXTURE, WALL MOUNTED OR UNDER CABINET, CONNECTED TO NORMAL POWER.

LED LIGHTING FIXTURE, CEILING OR WALL MOUNTED,

POLE MOUNTED LIGHTING FIXTURE. SEE SCHEDULE FOR TYPE (*).

DRAWINGS. SEE SCHEDULE FOR TYPE (*).

CEILING OR WALL MOUNTED EXIT SIGN. PROVIDE NUMBER OF FACES AND CHEVRONS AS INDICATED ON

EMERGENCY LIGHTING FIXTURE, CEILING-MOUNTED OR WALL-MOUNTED AT 7'-6" AFF UNLESS NOTED

OTHERWISE. CONNECT UNSWITCHED.

LIGHTING

LED LIGHTING WALLWASH FIXTURE, CEILING MOUNTED.

TRACK LIGHTING FIXTURE. SEE PLANS/SCHEDULE FOR TRACK LENGTH AND NUMBER OF TRACK HEADS.

EQUIPMENT IDENTIFICATION

HORSEPOWER RATING

MOTOR CONNECTION. SPECIAL VOLTAGES AS SHOWN ON DRAWING.

ENCLOSED CIRCUIT BREAKER. NUMERAL INDICATES TRIP AMPERE RATING.

FUSED SAFETY SWITCH. NUMERAL INDICATES FUSE RATING.

NON-FUSIBLE SAFETY SWITCH. NUMERAL INDICATES AMPERE RATING.

SIZE AND BOTTOM NUMERAL INDICATES NEMA STARTER SIZE.

COMBINATION MOTOR STARTER WITH CIRCUIT BREAKER. TOP NUMERAL INDICATES CIRCUIT BREAKER

MOTOR STARTER. NUMERAL INDICATES NEMA SIZE.

AMPACITY. SEE FEEDER SCHEDULE.

ON RISERS, DESIGNATION DENOTES QUANTITY OF CURRENT CARRYING CONDUCTORS AND FEEDER

WIRING SYSTEM CONCEALED IN OR ABOVE CEILING OR IN WALL.

WIRING SYSTEM BELOW FLOOR OR BELOW GRADE.

DESIGNATION DENOTES PANEL BOARD, SWITCHBOARD, MOTOR CONTROL CENTER, ETC., AND OVERCURRENT BRANCH OR FEEDER CIRCUIT HOMERUN TO PANEL BOARD, SWITCHBOARD, MOTOR CONTROL CENTER, ETC.

WIRING SYSTEM TURNED UP.

WIRING SYSTEM TURNED DOWN.

WIRING SYSTEM EXPOSED.

PROTECTION DEVICE NUMBER.

DRY TYPE TRANSFORMER.

NEC REQUIRED GROUND.

EF-1, 10 HP.460V, 3∅

208V, 3∅

120V, 1∅

MOTOR RATED SWITCH.

CONNECTION TO WALL MOUNTED FILM ILLUMINATOR. PROVIDE RECEPTACLE IN FLUSH OUTLET BOX AT

LOWER RIGHT HAND CORNER OF UNIT IF SURFACE MOUNTED. HARD WIRE IF RECESSED.

JUNCTION BOX AND CONNECTION TO EQUIPMENT OR TERMINAL STRIPS.

CEILING FAN 120V. MANUFACTURER (HUNTER#21252 GREEN FINISH W/ INTEGRATED 240W LIGHT FIXTURE)

CONNECTION TO HEADWALL UNIT. ONE NORMAL POWER CIRCUIT. ONE CRITICAL POWER CIRCUIT, CONNECTION TO FAN COIL UNIT. COORDINATE EXACT LOCATION WITH MECHANICAL CONTRACTOR.

AND ONE DEDICATED CRITICAL POWER CIRCUIT FOR VENTILATOR.

CONNECTION TO EXHAUST FAN. COORDINATE EXACT LOCATION WITH MECHANICAL CONTRACTOR.

PANELBOARD SURFACE MOUNTED.

REMOTE ALARM PANEL FOR ISOLATED POWER PANEL BOARD WALL MOUNTED AT 5'-0" AFF.

GENERATOR REMOTE ALARM ANNUNCIATOR. WALL MOUNTED AT 5'-0" AFF.

PANELBOARD FLUSH MOUNTED.

JUNCTION OR PULL BOX. W = WEATHERPROOF.

CONDUIT STUBBED INTO ACCESSIBLE CEILING SPACE.

HARDWIRE CONNECTION FROM FLUSH MOUNTED JUNCTION BOX WITH APPROPRIATE COVERPLATE AND 3/4" LIQUID TIGHT FLEXIBLE METALLIC WHIP TO PRE-WIRED FURNITURE. COORDINATE EXACT REQUIREMENTS AND LOCATION WITH EQUIPMENT SUPPLIER/INSTALLER. EIGHT(8) WIRE SYSTEM PROVIDES FOUR(4) CIRCUITS.

POWER

SURFACE MOUNTED MULTIOUTLET ASSEMBLY. 46" AFF OR 8" ABOVE COUNTER

TV = TELEVISION, SEE DETAIL.

G = GROUND FAULT CIRCUIT INTERRUPTER.

EWC = ELECTRIC WATER COOLER POWER CONNECTION, PROVIDE GROUND FAULT CIRCUIT INTERRUPTER

P = PEDESTAL

WP = WEATHERPROOF "IN-USE" COVER, PROVIDE GROUND FAULT CIRCUIT INTERRUPTER DEVICE.

DUPLEX RECEPTACLE, MOUNTED 18" AFF TO CENTER OF DEVICE. NEMA 5-20R UNLESS OTHERWISE

OR 2" ABOVE BACKSPLASH. SHADED AREA INDICATES RECEPTACLE.

DUPLEX RECEPTACLE IN FLUSH POKE-THRU DEVICE. 3-1/16" HOLE SIZE. BRUSHED ALUMINUM FUNISH.

SIMPLEX RECEPTACLE MOUNTED 18" AFF TO CENTER OF DEVICE. NEMA 5-20R UNLESS OTHERWISE

TWO DUPLEX RECEPTACLES IN 2-GANG BOX, MOUNTED 48" AFF TO CENTER OF OUTLET

OR 2" FROM BOTTOM OF OUTLET TO TOP OF BACKSPLASH OR COUNTERTOP. SLASH INDICATES

OUTLET TO TOP OF BACKSPLASH OR COUNTERTOP. SLASH INDICATES CONNECTED TO THE EMERGENCY

DUPLEX RECEPTACLE, MOUNTED 48" AFF TO CENTER OF OUTLET OR 2" FROM BOTTOM OF

TWO DUPLEX RECEPTACLES IN 2-GANG BOX, MOUNTED 18" AFF TO CENTER OF DEVICE. SLASH

DUPLEX RECEPTACLE OUTLET. CEILING MOUNTED.

SPECIAL RECEPTACLE OUTLET. NEMA CONFIGURATION AS INDICATED.

MODIFIERS FOR RECEPTACLES:

SPECIAL RECEPTACLE OUTLET. FLUSH FLOOR MOUNTED. NEMA CONFIGURATION AS INDICATED.

LH2A-1

POWER POLE. DEVICE CONFIGURATION AND COLOR AS INDICATED.

M

RATING AND BOTTOM NUMERAL INDICATES NEMA STARTER SIZE.

COMBINATION MOTOR STARTER WITH FUSED SWITCH. TOP NUMERAL INDICATES FUSETRON AMPERE

LIGHTNING PROTECTION SYSTEM GROUND ROD.

75KVA

T

LIGHTNING PROTECTION SYSTEM AIR TERMINAL.

TR = TAMPER RESISTANT

3 = THREE WAY

MODIFIERS FOR SWITCHES:

SINGLE POLE SWITCH, MOUNTED 48" AFF TO CENTER OF DEVICE.

THREE SINGLE POLE SWITCHES IN A 3-GANG BOX, MOUNTED 48" AFF TO CENTER OF DEVICE.

PHOTO ELECTRIC CELL MOUNTED ON CONDUIT STUBBED 6" ABOVE ROOF, FACING NORTH.

SWITCHES

TWO SINGLE POLE SWITCHES IN A 2-GANG BOX, MOUNTED 48" AFF TO CENTER OF DEVICE.

PROVIDE DIVIDER FOR DIFFERENT VOLTAGES OR BRANCHES.

4 = FOUR WAY

D = DIMMER

DT = DOUBLE THROW

LV = LOW VOLTAGE

TWO SINGLE POLE SWITCHES IN A 2-GANG BOX, MOUNTED 48" AFF TO CENTER OF DEVICE, TO COMPLY WITH ENERGY CODE. EITHER SWITCH INBOARD AND OUTBOARD LAMPS SEPARATELY OR STEP-DIM BOTH

PROVIDE DIVIDER(S) FOR DIFFERENT VOLTAGES OR BRANCHES.

OS = OCCUPANCY SENSOR

TIME CLOCK. PROVIDE POWER CIRCUIT AND 3/4" CONDUIT TO ACCESSIBLE CEILING SPACE.

a,b,c = MULTIPLE SWITCH LEGS

T = TIMER

INDICATED.

INDICATED. SLASH INDICATES CONNECTED TO THE EMERGENCY POWER SYSTEM.

INDICATES CONNECTED TO THE EMERGENCY POWER SYSTEM.

CONNECTED TO NORMAL POWER. SEE SCHEDULE FOR TYPE (*). SEE ARCHITECTURAL RCP FOR EXACT

LUMINAIRE, CEILING MOUNTED, CONNECTED TO THE NORMAL POWER SYSTEM (UNLESS OTHERWISE NOTED).

SEE SCHEDULE FOR TYPE (*). SEE ARCHITECTURAL RCP FOR EXACT LOCATION AND CEILING TYPE.

LOCATION AND CEILING TYPE. SLASH INDICATES CONNECTED TO THE CRITICAL BRANCH.

SEE SCHEDULE FOR TYPE (*).

SEE SCHEDULE FOR TYPE (*).

REMOTE EMERGENCY EGRESS TWIN-LAMP UNIT.

HALF-SHADED INDICATES CONNECTED TO LIFE SAFETY BRANCH.

LAMPS TO 50%.

SLASH INDICATES CONNECTED TO THE CRITICAL BRANCH. HALF-SHADED INDICATES CONNECTED TO THE EMERGENCY OR LIFE SAFETY BRANCH; VIA EMERGENCY GENERATOR SET OR BATTERY BALLAST, SEE PLANS.

SLASH INDICATES CONNECTED TO THE CRITICAL BRANCH. SEE SCHEDULE FOR TYPE (*).

HEADWALL. SEE PLAN FOR NUMBER.HW#

POWER COLUMN. SEE PLAN FOR NUMBER.PC#

POWER SYSTEM.

CONNECTED TO THE EMERGENCY POWER SYSTEM.

LED STRIP LUMINAIRE. CEILING MOUNTED OR SUSPENDED 8'-0" AFF TO BOTTOM OF LUMINAIRE, CONNECTED TO NORMAL POWER. SLASH INDICATES CONNECTED TO THE CRITICAL BRANCH.

HALF-SHADED INDICATES CONNECTED TO THE EMERGENCY OR LIFE SAFETY BRANCH; VIA EMERGENCY

GENERATOR SET OR BATTERY BALLAST, SEE PLANS.

REMOTE LINE ISOLATION MONITOR.

VARIABLE SPEED DRIVEVSD

PNEUMATIC TUBE STATIONPTS

DEVICE. INSTALL DEVICE SO IT IS CONCEALED BEHIND ENCLOSURE, COORDINATE WITH PLUMBING.

SHOWN TO CLARIFY THAT DEVICES/LUMINAIRES ON THE SAME CIRCUIT ARE CONTROLLED SEPARATELY.

POLE MOUNTED LIGHTING FIXTURE. SEE SCHEDULE FOR TYPE (*).

SYMBOL LOCATION LEADER

4/350

LIM

RA

GA

J

E

C

M

H

F

P

P

S

P

J

TC

PE

SS

SSS

SS

S

DUAL TECHNOLOGY CEILING MOUNTED OCCUPANCY SENSOR. PROVIDE ONE POWER PACK FOR EACHOS

SENSOR. COORDINATE WIRING REQUIREMENTS WITH EQUIPMENT SUPPLIER PRIOR TO ROUGH-IN.

GENERAL PROJECT NOTESELECTRICAL ENERGY CODE SUMMARY

ELECTRICAL SUMMARY

ELECTRICAL SYSTEM AND EQUIPMENT

Method of Compliance:

Prescriptive Performance

Lighting schedule lamp type required in fixture number of lamps in fixture ballast type used in the fixture number of ballasts in fixture total wattage per fixture total interior wattage specified vs. allowed NO ADDITIONAL LIGHTING LOAD ADDED total exterior wattage specified vs. allowed N/A

Additional Efficiency Package Options

C406.2 More Efficient HVAC Equipment Performance

C406.3 Reduced Lighting Power Density

C406.4 Enhanced Digital Lighting Controls

C406.5 On-Site Renewable Energy

C406.6 Dedicated Outdoor Air System

Energy Code:

ASHRAE 90.1: Prescriptive Performance

C406.7 Reduced Energy Use in Service Water Heating

(When using the 2018 NCECC; not required for ASHRAE 90.1)

A. THE DRAWINGS SHALL NOT BE SCALED FOR CONSTRUCTION PURPOSES. THE SCALE, WHEN

INDICATED, IS INTENDED FOR REFERENCE PURPOSES ONLY.

B. ALL POWER OUTAGES SHALL BE COORDINATED AND APPROVED THROUGH THE OWNERS'

REPRESENTATIVE AND REQUIRE ADVANCE NOTICE OF AT LEAST TWO (2) WEEKS. AT THE

OWNER'S REPRESENTATIVE’S DISCRETION, THIS TIME LENGTH MAY BE INCREASED OR

DECREASED, DEPENDING ON THE SYSTEMS IMPACTED BY THE POWER OUTAGE.

C. CONSTRUCTION DEBRIS SHALL BE REMOVED DAILY, OR AT THE OWNER'S REPRESENTATIVE’S

DISCRETION.

D. ALL ELECTRICAL MATERIAL, DEVICES, APPLIANCES, AND FIXED EQUIPMENT PROVIDED SHALL

BE LISTED AND LABELED BY A NATIONALLY RECOGNIZED AND STATE APPROVED THIRD PARTY

TESTING AGENCY. FACTORY LISTED COMPONENTS ASSEMBLED TOGETHER SHALL BE

REVIEWED AND LABELED AS AN ASSEMBLY BY THE STATE APPROVED TESTING AGENCY.

E. FIRE ALARM APPLIANCES AND DEVICES SHOWN IN AN AREA INDICATE TO PROVIDE COVERAGE

IN THAT AREA. ELECTRICAL CONTRACTOR SHALL PROVIDE APPLIANCES AND DEVICES AS

REQUIRED BY THE LATEST EDITION OF NFPA 72 AND THE BUILDING CODE. NO CHANGE ORDERS

WILL BE ALLOWED FOR APPLIANCES AND DEVICES REQUIRED BY NFPA 72 AND THE BUILDING

CODE.

F. CONTRACTOR SHALL COORDINATE WITH THE FACILITY'S INFECTION CONTROL OFFICER TO

VERIFY THAT APPROPRIATE SAFEGUARDS ARE BEING TAKEN TO PROTECT WORKERS

INVOLVED IN DEMOLITION ACTIVITIES.

G. CONTRACTOR SHALL COORDINATE WITH THE FACILITY'S INFECTION CONTROL OFFICER TO

VERIFY THAT APPROPRIATE PRECAUTIONS ARE BEING TAKEN TO PROTECT FACILITY STAFF

AND PATIENTS DURING THE CONSTRUCTION ACTIVITIES.

H. ASBESTOS CONTAINING MATERIALS (IF PRESENT) WILL BE IDENTIFIED BY THE OWNER AND WILL BE REMOVED FROM AHU'S, PIPING INSULATION, DUCT INSULATION, ETC. (IF REQUIRED)

PRIOR TO CONTRACTOR BEGINNING ANY WORK ON THE SITE. COORDINATE WITH THE OWNER.

I. ELECTRICAL WORK SHALL BE COMPLETED ACCORDING TO THE TRUE INTENT AND MEANING AS

INDICATED IN THE CONTRACT DOCUMENTS. ANYTHING NOT ENTIRELY CLEAR SHALL BE

EXPLAINED IF SUBMITTED TO THE ARCHITECT/ENGINEER IN WRITING.

J. CONNECTIONS OF FEEDERS AND BRANCH CIRCUITS TO SWITCHBOARDS/PANELBOARDS SHALL

BE DONE IN A MANNER AS TO LIMIT THE OUTAGES TO AN ABSOLUTE MINIMUM.

K. ALL TERMINATIONS, CONDUCTORS, AND DEVICES SHALL BE 75 DEGREE CELSIUS RATED, TO

THE EXTENT FEASIBLE; OTHERWISE COMPLY WITH NEC ARTICLE 110.14(C)(1).

L. ELECTRICAL CONTRACTOR SHALL NOT ROUTE WIRING CONNECTED TO THE LIFE SAFETY

BRANCH OR THE CRITICAL BRANCH IN FLEXIBLE METAL RACEWAYS OR METAL SHEATHED

CABLE ASSEMBLIES, EXCEPT AS ALLOWED BY NEC ARTICLE 517.31(C)(3)(3).

M. ELECTRICAL CONTRACTOR SHALL PROVIDE RACEWAYS, JUNCTION BOXES, CABINETS, ETC., IN

ORDER TO SEPARATE THE LIFE SAFETY BRANCH AND/OR THE CRITICAL BRANCH CIRCUIT

WIRING FROM THE WIRING AND EQUIPMENT SERVED BY ANY OTHER BRANCHES OF POWER.

N. UNLESS OTHERWISE NOTED FOR MEDICAL EQUIPMENT, ELECTRICAL CONTRACTOR SHALL

INSTALL ALL RACEWAY, BOXES, AND CABLES. THE CABLES, UNLESS OTHERWISE NOTED, SHALL

BE PROVIDED BY THE MEDICAL EQUIPMENT VENDOR.

O. ELECTRICAL WORK SHALL BE COMPLETED ACCORDING TO THE PHASES SHOWN ON THE

ARCHITECTURAL PLANS OR AS ESTABLISHED IN THE "GENERAL CONDITIONS".

P. THE EQUIPMENT GROUNDING TERMINAL BUSES OF THE NORMAL AND THE ESSENTIAL

ELECTRICAL SYSTEM BRANCH-CIRCUIT PANELBOARDS, SERVING THE SAME INDIVIDUAL

PATIENT CARE VICINITY, SHALL BE BONDED TOGETHER WITH A CONTINUOUS, INSULATED

COPPER GROUNDING CONDUCTOR NOT SMALLER THAN 10 AWG.

Q. A MAXIMUM OF THREE (3) 20 AMPERE, 1 POLE BRANCH CIRCUITS MAY BE COMBINED IN A

COMMON HOMERUN SHARING A COMMON GROUNDED (NEUTRAL) OR WITH DEDICATED

SEPARATE NEUTRALS (GROUNDED CONDUCTORS), FOR A TOTAL OF SIX CURRENT CARRYING

CONDUCTORS. ALL BRANCH CIRCUITS LARGER THAN 20A SHALL BE SEPARATELY HOMERUN TO

THE PANELBOARD.

R. ALL CONDUCTORS SHALL BE COPPER, RATED AT NOT LESS THAN 600 VOLTS. MINIMUM SIZE

SHALL BE NO. 12 AWG, UNLESS OTHERWISE NOTED ON THE DRAWINGS. ALL CONDUCTORS #8

AWG AND LARGER SHALL BE STRANDED. #10 THRU #12 AWG CONDUCTORS SHALL BE SOLID.

ALL INSULATION TYPES SHALL BE THWN OR THHN, UNLESS OTHERWISE NOTED.

S. ELECTRICAL CONTRACTOR SHALL USE MULTI-POLE CIRCUIT BREAKERS FOR ALL BRANCH

CIRCUITS WITH SHARED NEUTRALS (GROUNDED CONDUCTORS) PER NEC ARTICLE 210.4(B) OR

PROVIDE SEPARATE NEUTRALS (GROUNDED CONDUCTORS) FOR EACH BRANCH CIRCUIT.

PANELBOARD SCHEDULES SHALL INDICATE IF MULTI-POLE OR SINGLE-POLE CIRCUIT

BREAKERS WERE USED.

T. ALL WORK ASSOCIATED WITH VOICE, DATA, CCTV, CATV, NURSE CALL, WI-FI, PUBLIC ADDRESS, SECURITY ACCESS, TO BE PROVIDED UNDER THIS CONTRACT. THE ELECTRICAL CONTRACTOR

SHALL PROVIDE BACK BOXES AND CONDUIT STUBBED-UP, TO ACCESSIBLE CORRIDOR CEILING

SPACE, WITH PULL WIRE.

U. ALL 20 AMPERE SINGLE PHASE BRANCH CIRCUIT WIRING, TO PREVENT A VOLTAGE DROP

EXCEEDING 3%, SHALL BE IN ACCORDANCE WITH THE FOLLOWING TABLE:

V. A SHORT-CIRCUIT/ARC FLASH AND SELECTIVE COORDINATION STUDY SHALL BE PREPARED

FOR THE ELECTRICAL OVERCURRENT DEVICES BEING INSTALLED FOR THIS PROJECT. FINAL

FIELD SETTINGS AND MODIFICATIONS OF THE OVERCURRENT PROTECTIVE DEVICES SHALL BE

MADE TO CONFIRM WITH THE STUDY, WITHOUT ADDITIONAL COST OR TIME TO THE OWNER.

W. ALL BREAKERS 600 AMPERES AND ABOVE SHALL BE SOLID-STATE TYPE. SELECT ELECTRONIC

TRIP FUNCTIONS FOR LOW-VOLTAGE CIRCUIT BREAKERS SO AS TO ACHIEVE SELECTIVE

COORDINATION AS REQUIRED BY NFPA 70 (NEC).

X. LIGHTING LAYOUTS ARE BASED ON LIGHTING LEVELS RECOMMENDED BY THE IESNA

(ILLUMINATING ENGINEERING SOCIETY OF NORTH AMERICA). LIGHT LEVELS ARE AFFECTED BY

ENVIRONMENTAL CONDITIONS SUCH AS THE COLOR OF FINISHES (CEILINGS, WALLS, FLOORS,

ETC.), WINDOW TREATMENTS, FURNISHINGS, AND FINAL LUMINAIRE SELECTIONS. ALL

ENVIRONMENTAL CONDITIONS MAY NOT BE ESTABLISHED DURING DESIGN, WHICH MAY IMPACT

THE LIGHTING LEVELS UPON THE COMPLETION OF CONSTRUCTION. BASIS OF DESIGN LIGHTING

CALCULATIONS FOR SPECIFIC AREAS ARE AVAILABLE UPON REQUEST.

VOLTS DISTANCE TO FIRST

OUTLET

HOMERUN REMAINDER OF CIRCUIT

120V

208V

277V

480V

0'-55'

55'-95'

95'-145'

145'-230'

0'-95'

95'-160'

160'-250'

0'-125'

125'-220'

220'-335'

0'-225'

225'-380'

380'-585'

#12

#10

#8

#6

#12

#10

#8

#12

#10

#8

#12

#10

#8

#12

#12

#12

#12

#12

#12

#12

#12

#12

#12

#12

#12

#12

Y. ALL DEMOLITION WORK SHALL BE COORDINATED WITH THE OWNER PRIOR TO BEGINNING

THE WORK.

Z. ALL ELECTRICAL DEVICES, LUMINAIRES, WIRING, AND RACEWAYS IN WALLS AND IN

CEILINGS BEING DEMOLISHED SHALL BE REMOVED, UNLESS OTHERWISE NOTED.

RECONNECT EXISTING DEVICES AND LUMINIRES DOWNSTREAM OF THOSE BEING

REMOVED. WIRING AND RACEWAYS SHALL BE REMOVED BACK TO THEIR SOURCE OF

POWER, UNLESS OTHERWISE NOTED.

AA. EXISTING ELECTRICAL WORK SHOWN TO REMAIN, BUT INTERFERES WITH THE NEW WORK,

SHALL BE REWORKED AND RELOCATED TO AVOID ANY INTERFERENCE.

BB. ELECTRICAL DEMOLITION WORK SHALL BE PHASED. THE ELECTRICAL CONTRACTOR SHALL

DEVELOP A PHASING PLAN THAT WILL WORK WITH THE ARCHITECT’S OVERALL PHASING

PLAN, THE WORK TO BE PERFORMED BY OTHER TRADES, AND TO MAINTAIN THE OWNER’S

OPERATIONS.

CC. ELECTRICAL CONTRACTOR SHALL PROVIDE TEMPORARY POWER TO MAINTAIN THE

OWNER’S OPERATIONS, AT NO EXTRA COST OR TIME TO THE OWNER, IN ORDER TO KEEP

THE BUILDING IN OPERATION DURING EACH PHASE OF THE PROJECT.

DD. REMOVE EXISTING ELECTRICAL GEAR AS SHOWN. DEMOLITION OF FEEDERS AND BRANCH

CIRCUITS OR TRANSFERRING FEEDERS AND BRANCH CIRCUITS TO NEW PANELBOARDS,

SHALL BE PERFORMED IN A MANNER AS TO KEEP DOWNTIME AND OUTAGES TO AN

ABSOLUTE MINIMUM.

EE. ELECTRICAL CONTRACTOR SHALL PREPARE AN OUTAGE PLAN, INCLUDING PROVISIONS

FOR TEMPORARY POWER, AND SUBMIT IT WITH THEIR BID. THE OUTAGE PLAN SHALL

INCLUDE ALL OUTAGES REQUIRED TO PERFORM THE WORK SHOWN IN THE CONTRACT

DOCUMENTS. NO EXTRA COST OR TIME TO THE OWNER SHALL BE CONSIDERED FOR NOT

INCLUDING REQUIRED OUTAGES. ALL OUTAGES SHALL BE COORDINATED WITH, AND

APPROVED BY, THE OWNER AT LEAST TWO (2) WEEKS IN ADVANCE. AT THE OWNER’S

DISCRETION, THIS TIME MAY BE LONGER OR SHORTER FOR SOME SHUTDOWNS.

FF. ELECTRICAL CONTRACTOR SHALL REMOVE ALL ELECTRICAL ITEMS ASSOCIATED WITH

DEMOLITION WORK SHOWN ON THE ARCHITECTURAL, CIVIL, STRUCTURAL, INTERIOR,

PLUMBING, MECHANICAL, AND FIRE PROTECTION DRAWINGS.

GG. EXISTING ELECTRICAL CONDITIONS ARE BASED UPON SITE SURVEY INFORMATION AND

EXISTING RECORD/AS-BUILT DRAWINGS MADE AVAILABLE FROM THE OWNER. ELECTRICAL

WORK SHOWN CONVEYS THE GENERAL SCOPE OF THE DEMOLITION WORK TO BE

PERFORMED. THE ELECTRICAL CONTRACTOR SHALL VISIT THE SITE AND OBSERVE THE

EXISTING CONDITIONS PRIOR TO BIDDING. NO CHANGE ORDERS WILL BE CONSIDERED FOR

CONDITIONS EASILY VISIBLE DURING A SITE VISIT.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

Engineering Discipline:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Consultant:

U D

B e n d e r\ L o c a l R e v it F ile s \2

\4

V A

M C

A tl a n ta th f l\

C E

C e n tr a l M o d e l.

rv t

/5 /2

:3

:1

P M

E001

ELECTRICAL - LEGENDS,

SYMBOLS, AND DRAWING INDEX

CHARLOTTE ENGINEERS

5838 MONROE ROAD, SUITE 100

CHARLOTTE, NC 28212

704.531.3000

GUIDON

1221 N. PENNSYLVANIA STREET

INDIANAPOLIS STREET

317.800.6388

RENOVATE 6TH FLOOR FOR 16

BED STORT STAY CLC

1670 CLAIRMONT RD, DECATUR, GA

508-22-105

C

9/21/2023 JCE NMG

100% CONSTRUCTION

DOCUMENTS

FULLY SPRINKLERED

ELECTRICAL - DRAWING INDEX

Sheet Number Sheet Name

E001 ELECTRICAL - LEGENDS, SYMBOLS, AND DRAWING INDEX

E002 ELECTRICAL - SPECIAL SYSTEMS SYMBOLS, AND NOTES

E003 ELECTRICAL - DETAILS & LUMINAIRE SCHEDULE

E004 ELECTRICAL - SPECIAL SYSTEM DETAILS

E005 ELECTRICAL - SPECIAL SYSTEM DETAILS

E006 ELECTRICAL - PARTIAL RISER DIAGRAMS

E007 ELECTRCIAL - PANEL SCHEDULES

E008 ELECTRICAL - PANEL SCHEDULES

E009 ELECTRICAL - PANEL SCHEDULES

ED100 ELECTRICAL - LEVEL 06 - DEMOLITION

EL100 ELECTRICAL - LEVEL 06 - NEW WORK - LIGHTING

EP100 ELECTRICAL - LEVEL 06 - NEW WORK - POWER

ES100 ELECTRICAL - LEVEL 06 - NEW WORK - SPECIAL SYSTEMS

Revisions: Date:

Addendum 2 05-06-2025

NOT A CERTIFIED DOCUMENT AS TO THE ORIGINAL DOCUMENT

BUT ONLY AS TO THE REVISION - THIS DOCUMENT ORIGINALLY

ISSUED AND SEALED BY JOHN C. EDWARDS, JR. 050482, 09-21-23

THIS DOCUMENT IS ONLY CERTIFIED AS TO THE REVISIONS.

Sheets
E001 - ELECTRICAL - LEGENDS, SYMBOLS, AND DRAWING INDEX