This document contains a site analysis report and related federal contract opportunity notice. The site analysis report evaluates existing bathroom facilities in Building 116 at the Hampton VA Medical Center and proposes upgrades to improve ADA compliance. Bathrooms 100B, 115 and 118 could meet ADA requirements with minor modifications, while Bathroom 100C would require combining with 100B to create accessible male and female restrooms. The federal contract opportunity is a solicitation notice seeking bids for bathroom upgrade projects at the Hampton VAMC campus. The upgrades will include architectural, interior finishes and MEP work throughout the facility. The estimated construction value is between $2-5 million. The solicitation is a total SDVOSB set-aside and interested vendors must register on the website to receive amendments. The point of contact is listed for any questions, though phone inquiries will not be accepted. The solicitation number is 36C24621R0018 and is issued by the VA Veterans Health Administration VISN 6.
View the file
Other files for this federal contract opportunity
Show all 38
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
VAMC - HAMPTON
BATHROOM UPGRADES
Project No. ADG18003.00
BUILDING 116
OVERALL
ROOM 100B
ROOM 100C
ROOM 115
ROOM 118
SUMMARY
February 01, 2019
AD
G
3.
BATHROOM UPGRADES| HAMPTON, VIRGINIA
02.01.19
BUILDING 116
3.
EXISTING
3.
PROPOSED
REMOVAL OF
2ND STALL DOES
BRING THE ROOM
CLOSER TO BEING
ADA COMPLIANT
BUT OFFSETS THE
BUILDING CODE
FIXTURE COUNTS.
3.
3.
3.
MANEUVERING CLEARANCE
IS NOT ADA COMPLIANT.
ENTIRE BATHROOM WOULD
NEED TO BE WIDENED TO
MAKE IT ADA ACCESSIBLE.
3.
3.
3.
3’-0” DOOR TO BE
PROVIDED TO MAKE SPACE
ADA COMPLIANT
REMOVAL OF 2ND
URINAL DOES
BRING THE ROOM
CLOSER TO BEING
ADA COMPLIANT
BUT OFFSETS THE
BUILDING CODE
FIXTURE COUNTS.
SHIFTING SINKS WILL
PROVIDE ADEQUATE SPACE
FOR CLEAR FLOOR AREA AT
DOORWAY
3.
3.
3.
3’-0” DOOR TO
BE PROVIDED TO
MAKE SPACE ADA
COMPLIANT
REORIENTING FIXTURES
BRINGS SPACE CLOSER
TO ADA COMPLIANCE. THIS
DOES ELIMINATE A STALL
WHICH OFFSETS THE
BUILDING CODE FIXTURE
COUNTS
3.
3.
BUILDING 116 SUMMARY
ROOM 100B*, 115*, 118*
The clearances do meet ADA Requirements.
* Although proposed layout meets ADA requirements, the building code fixture count is offset.
ROOM 100C
The clearances do not meet ADA Requirements
Recommendation to combine 100B & 100C to provide a Male & Female accessible restroom
AS DIRECTED BY THE VA, BATHROOMS THAT CANNOT MEET
ACCESSIBILITY REQUIREMENTS WILL ONLY RECEIVE NEW
FINISHES AND FIXTURES