This document includes a site analysis report and related federal contract opportunity for bathroom upgrades at a Veterans Affairs medical center. The site analysis report provides existing and proposed layouts for 40 bathrooms in Building 110 at the Hampton, VA VA center, identifying ADA compliance issues. Clearances meet requirements in some rooms, while others require fixture reconfiguration or cannot be made accessible. The related federal contract opportunity is a solicitation for project 590-19-106 Bathroom Upgrades with an estimated value between $2-5 million. It is a total SDVOSB set-aside to provide all labor, materials, and associated work to upgrade bathrooms throughout the facility per drawings and specifications. The solicitation is posted on the website and any amendments will also be posted there. Interested vendors must register on the site and have active SAM and VetBiz registrations to be eligible for award. Questions must be emailed to the point of contact by the unspecified due date.
View the file
Other files for this federal contract opportunity
Show all 38
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
VAMC - HAMPTON
BATHROOM UPGRADES
Project No. ADG18003.00
BUILDING 110
February 28, 2019
ROOM BG16B ROOM B433 ROOM C503
ROOM BG16N1 ROOM C401A ROOM C505
ROOM BG19 ROOM C401B ROOM C602
ROOM DG01C ROOM D402A
ROOM DG05C.1 ROOM D403A
ROOM DG5D.1 ROOM D404A
ROOM DG05E ROOM D411A
ROOM DG05H.1 ROOM D412A1
ROOM DG05J.1 ROOM D414A
ROOM DG20A ROOM D415A1
ROOM B201 ROOM D415B1
ROOM B205A ROOM D416A
ROOM B216 ROOM D418A
ROOM B219 ROOM D419A1
ROOM B230A ROOM D419B1
ROOM D203A ROOM D420A
ROOM D207A ROOM D422A
ROOM B412 ROOM D423A1
ROOM B413 ROOM D423B1
ROOM B417A1 ROOM D428A
ROOM B417B1 ROOM D429A
ROOM B423A ROOM D430A
AD
G
3.
BATHROOM UPGRADES| HAMPTON, VIRGINIA
02.28.19
BUILDING 110
3.
BATHROOM UPGRADES| HAMPTON, VIRGINIA
02.28.19
BUILDING 110
EXISTING
REMOVAL OF 3RD
TOILET ALLOWS
THE SPACE TO BE
ADA COMPLIANT
BUT OFFSETS THE
BUILDING CODE
FIXTURE COUNT
3.
BATHROOM UPGRADES| HAMPTON, VIRGINIA
02.28.19
BUILDING 110
PROPOSED
MANEUVERING
DOOR IS NOT ADA
COMPLIANT
3.
BATHROOM UPGRADES| HAMPTON, VIRGINIA
3.
BATHROOM UPGRADES| HAMPTON, VIRGINIA
02.28.19
EXISTING
3.
BATHROOM UPGRADES| HAMPTON, VIRGINIA
02.28.19
BUILDING 110
PROPOSED
MANEUVERING
CLEARANCE FOR
THIS SPACE IS NOT
ADA COMPLIANT
3.
BATHROOM UPGRADES| HAMPTON, VIRGINIA
3.
BATHROOM UPGRADES| HAMPTON, VIRGINIA
02.28.19
3.
BATHROOM UPGRADES| HAMPTON, VIRGINIA
02.28.19
PROPOSED
3.
BATHROOM UPGRADES| HAMPTON, VIRGINIA
3.
BATHROOM UPGRADES| HAMPTON, VIRGINIA
02.28.19
BUILDING 110
EXISTING
DOOR TO BE
WIDENED TO 3’-0”
3.
BATHROOM UPGRADES| HAMPTON, VIRGINIA
02.28.19
BUILDING 110
PROPOSED
MANEUVERING
CLEARANCE FOR
SINK IS NOT ADA
COMPLIANT
WALL TO BE WIDENED
TO ACCOMODATE
GRAB BAR
3.
BATHROOM UPGRADES| HAMPTON, VIRGINIA
3.
BATHROOM UPGRADES| HAMPTON, VIRGINIA
02.28.19
3.
BATHROOM UPGRADES| HAMPTON, VIRGINIA
02.28.19
BUILDING 110
PROPOSED
WALL WOULD NEED
TO BE REMOVED TO
MAKE THIS ROOM
ADA COMPLIANT -
THIS WOULD ALLOW
FOR APPROPRIATE
MANEUVERING
CLEARANCE
3.
BATHROOM UPGRADES| HAMPTON, VIRGINIA
3.
BATHROOM UPGRADES| HAMPTON, VIRGINIA
02.28.19
3.
BATHROOM UPGRADES| HAMPTON, VIRGINIA
02.28.19
3.
BATHROOM UPGRADES| HAMPTON, VIRGINIA
3.
BATHROOM UPGRADES| HAMPTON, VIRGINIA
02.28.19
3.
BATHROOM UPGRADES| HAMPTON, VIRGINIA
02.28.19
BUILDING 110
PROPOSED
MANEUVERING
CLEARANCE FOR
DOOR APPROACH IS
NOT ADA COMPLIANT
3.
BATHROOM UPGRADES| HAMPTON, VIRGINIA
3.
BATHROOM UPGRADES| HAMPTON, VIRGINIA
02.28.19
3.
BATHROOM UPGRADES| HAMPTON, VIRGINIA
02.28.19
BUILDING 110
PROPOSED
MANEUVERING
CLEARANCE FOR
SPACE IS NOT ADA
3.
BATHROOM UPGRADES| HAMPTON, VIRGINIA
3.
BATHROOM UPGRADES| HAMPTON, VIRGINIA
02.28.19
3.
BATHROOM UPGRADES| HAMPTON, VIRGINIA
02.28.19
BUILDING 110
PROPOSED
MANEUVERING
CLEARANCE FOR
SPACE IS NOT ADA
3.
BATHROOM UPGRADES| HAMPTON, VIRGINIA
3.
BATHROOM UPGRADES| HAMPTON, VIRGINIA
02.28.19
3.
BATHROOM UPGRADES| HAMPTON, VIRGINIA
02.28.19
BUILDING 110
PROPOSED
MANEUVERING
CLEARANCE FOR
SINK IS NOT ADA
COMPLIANT
MANEUVERING
CLEARANCE FOR
THIS SPACE IS NOT
ADA COMPLIANT
3.
BATHROOM UPGRADES| HAMPTON, VIRGINIA
3.
BATHROOM UPGRADES| HAMPTON, VIRGINIA
3.
BATHROOM UPGRADES| HAMPTON, VIRGINIA
3.
BATHROOM UPGRADES| HAMPTON, VIRGINIA
02.28.19
BUILDING 110
EXISTING
REMOVAL OF 2ND
TOILET WOULD
ALLOW THIS
SPACE TO BE ADA
COMPLIANT BUT
WOULD OFFSET
THE BUILDING CODE
FIXTURE COUNT
CAPPED PLUMBING
FIXTURE IN THIS
AREA. (SEE PICTURE)
3.
BATHROOM UPGRADES| HAMPTON, VIRGINIA
02.28.19
BUILDING 110
PROPOSED
DOOR TO SHIFT TO
ALLOW ROOM FOR
MANEUVERING
CLEARANCE
3.
BATHROOM UPGRADES| HAMPTON, VIRGINIA
02.28.19
BUILDING 110
THERE WAS 3
TOILETS IN THIS
SPACE BUT ONE
WAS REMOVED AND
CAPPED.
3.
BATHROOM UPGRADES| HAMPTON, VIRGINIA
02.28.19
3.
BATHROOM UPGRADES| HAMPTON, VIRGINIA
02.28.19
BUILDING 110
PROPOSED
THIS ROOM CANNOT
BE MADE ADA
ACCESSIBLE
3.
BATHROOM UPGRADES| HAMPTON, VIRGINIA
3.
BATHROOM UPGRADES| HAMPTON, VIRGINIA
02.28.19
3.
BATHROOM UPGRADES| HAMPTON, VIRGINIA
02.28.19
BUILDING 110
PROPOSED
THIS ROOM CANNOT
3.
BATHROOM UPGRADES| HAMPTON, VIRGINIA
3.
BATHROOM UPGRADES| HAMPTON, VIRGINIA
02.28.19
3.
BATHROOM UPGRADES| HAMPTON, VIRGINIA
02.28.19
BUILDING 110
PROPOSED
NEW FIXTURE
LAYOUT ALLOWS FOR
SPACE TO BE ADA
3.
BATHROOM UPGRADES| HAMPTON, VIRGINIA
3.
BATHROOM UPGRADES| HAMPTON, VIRGINIA
02.28.19
3.
BATHROOM UPGRADES| HAMPTON, VIRGINIA
02.28.19
BUILDING 110
PROPOSED
THIS ROOM CANNOT
3.
BATHROOM UPGRADES| HAMPTON, VIRGINIA
3.
BATHROOM UPGRADES| HAMPTON, VIRGINIA
02.28.19
3.
BATHROOM UPGRADES| HAMPTON, VIRGINIA
02.28.19
BUILDING 110
PROPOSED
THIS ROOM CANNOT
3.
BATHROOM UPGRADES| HAMPTON, VIRGINIA
3.
BATHROOM UPGRADES| HAMPTON, VIRGINIA
3.
BATHROOM UPGRADES| HAMPTON, VIRGINIA
02.28.19
3.
BATHROOM UPGRADES| HAMPTON, VIRGINIA
02.28.19
BUILDING 110
PROPOSED
NEW FIXTURE
LAYOUT HELPS
SPACE BE ADA
3.
BATHROOM UPGRADES| HAMPTON, VIRGINIA
3.
BATHROOM UPGRADES| HAMPTON, VIRGINIA
02.28.19
3.
BATHROOM UPGRADES| HAMPTON, VIRGINIA
02.28.19
BUILDING 110
PROPOSED
THIS SPACE
CANNOT BE MADE
3.
BATHROOM UPGRADES| HAMPTON, VIRGINIA
3.
BATHROOM UPGRADES| HAMPTON, VIRGINIA
02.28.19
3.
BATHROOM UPGRADES| HAMPTON, VIRGINIA
02.28.19
BUILDING 110
PROPOSED
MANEUVERING
CLEARANCE FOR
DOOR APPROACH IS
NOT ADA COMPLIANT
3.
BATHROOM UPGRADES| HAMPTON, VIRGINIA
3.
BATHROOM UPGRADES| HAMPTON, VIRGINIA
02.28.19
3.
BATHROOM UPGRADES| HAMPTON, VIRGINIA
02.28.19
3.
BATHROOM UPGRADES| HAMPTON, VIRGINIA
3.
BATHROOM UPGRADES| HAMPTON, VIRGINIA
02.28.19
BUILDING 110
EXISTING
SHOWER WOULD
NEED TO BE
REMOVED IN ORDER
TO MAKE SPACE ADA
3.
BATHROOM UPGRADES| HAMPTON, VIRGINIA
02.28.19
3.
BATHROOM UPGRADES| HAMPTON, VIRGINIA
3.
BATHROOM UPGRADES| HAMPTON, VIRGINIA
02.28.19
3.
BATHROOM UPGRADES| HAMPTON, VIRGINIA
02.28.19
3.
BATHROOM UPGRADES| HAMPTON, VIRGINIA
3.
BATHROOM UPGRADES| HAMPTON, VIRGINIA
02.28.19
BUILDING 110
EXISTING
WALL TO BE
REMOVED
3.
BATHROOM UPGRADES| HAMPTON, VIRGINIA
02.28.19
BUILDING 110
PROPOSED
NEW FIXTURE
LAYOUT ALLOWS FOR
3.
BATHROOM UPGRADES| HAMPTON, VIRGINIA
3.
BATHROOM UPGRADES| HAMPTON, VIRGINIA
02.28.19
BUILDING 110
EXISTING
WALL TO BE
REMOVED
3.
BATHROOM UPGRADES| HAMPTON, VIRGINIA
02.28.19
BUILDING 110
PROPOSED
NEW FIXTURE
LAYOUT ALLOWS FOR
3.
BATHROOM UPGRADES| HAMPTON, VIRGINIA
3.
BATHROOM UPGRADES| HAMPTON, VIRGINIA
02.28.19
3.
BATHROOM UPGRADES| HAMPTON, VIRGINIA
02.28.19
BUILDING 110
PROPOSED
MANEUVERING
CLEARANCE FOR
DOOR APPROACH IS
NOT ADA COMPLIANT
THIS ROOM CANNOT
ACCESSIBLE.
3.
BATHROOM UPGRADES| HAMPTON, VIRGINIA
3.
BATHROOM UPGRADES| HAMPTON, VIRGINIA
02.28.19
3.
BATHROOM UPGRADES| HAMPTON, VIRGINIA
02.28.19
BUILDING 110
PROPOSED
MANEUVERING
CLEARANCE FOR
THIS SPACE IS NOT
ADA COMPLIANT
THIS ROOM CANNOT
BE MADE ADA
ACCESSIBLE.
4’-0” DOOR
TO MEET VA
BARRIER FREE
DESIGN
3.
BATHROOM UPGRADES| HAMPTON, VIRGINIA
02.28.19
3.
BATHROOM UPGRADES| HAMPTON, VIRGINIA
02.28.19
BUILDING 110
PROPOSED
MANEUVERING
CLEARANCE FOR
DOOR APPROACH IS
NOT ADA COMPLIANT
THIS ROOM CANNOT
BE MADE ADA
ACCESSIBLE.
4’-0” DOOR
TO MEET VA
3.
BATHROOM UPGRADES| HAMPTON, VIRGINIA
3.
BATHROOM UPGRADES| HAMPTON, VIRGINIA
02.28.19
3.
BATHROOM UPGRADES| HAMPTON, VIRGINIA
02.28.19
BUILDING 110
PROPOSED
MANEUVERING
CLEARANCE IS NOT
ADA COMPLIANT
THIS ROOM CANNOT
BE MADE ADA
ACCESSIBLE.
4’-0” DOOR
TO MEET VA
3.
BATHROOM UPGRADES| HAMPTON, VIRGINIA
3.
BATHROOM UPGRADES| HAMPTON, VIRGINIA
02.28.19
3.
BATHROOM UPGRADES| HAMPTON, VIRGINIA
02.28.19
BUILDING 110
PROPOSED
THIS ROOM CANNOT
ACCESSIBLE.
3.
BATHROOM UPGRADES| HAMPTON, VIRGINIA
3.
BATHROOM UPGRADES| HAMPTON, VIRGINIA
02.28.19
3.
BATHROOM UPGRADES| HAMPTON, VIRGINIA
02.28.19
BUILDING 110
PROPOSED
THIS ROOM CANNOT
BE MADE ADA
ACCESSIBLE.
MANEUVERING
CLEARANCE IS NOT
ADA COMPLIANT
4’-0” DOOR
TO MEET VA
3.
BATHROOM UPGRADES| HAMPTON, VIRGINIA
3.
BATHROOM UPGRADES| HAMPTON, VIRGINIA
02.28.19
3.
BATHROOM UPGRADES| HAMPTON, VIRGINIA
02.28.19
BUILDING 110
PROPOSED
THIS ROOM CANNOT
BE MADE ADA
ACCESSIBLE.
MANEUVERING
CLEARANCE IS NOT
ADA COMPLIANT
4’-0” DOOR
TO MEET VA
3.
BATHROOM UPGRADES| HAMPTON, VIRGINIA
3.
BATHROOM UPGRADES| HAMPTON, VIRGINIA
02.28.19
3.
BATHROOM UPGRADES| HAMPTON, VIRGINIA
02.28.19
BUILDING 110
THIS ROOM CANNOT
BE MADE ADA
ACCESSIBLE.
MANEUVERING
CLEARANCE IS NOT
ADA COMPLIANT
4’-0” DOOR
TO MEET VA
3.
BATHROOM UPGRADES| HAMPTON, VIRGINIA
3.
BATHROOM UPGRADES| HAMPTON, VIRGINIA
02.28.19
3.
BATHROOM UPGRADES| HAMPTON, VIRGINIA
02.28.19
BUILDING 110
THIS ROOM CANNOT
BE MADE ADA
ACCESSIBLE.
MANEUVERING
CLEARANCE IS NOT
ADA COMPLIANT
4’-0” DOOR
TO MEET VA
3.
BATHROOM UPGRADES| HAMPTON, VIRGINIA
02.28.19
3.
BATHROOM UPGRADES| HAMPTON, VIRGINIA
02.28.19
BUILDING 110
THIS ROOM CANNOT
BE MADE ADA
ACCESSIBLE.
MANEUVERING
CLEARANCE IS NOT
ADA COMPLIANT
4’-0” DOOR
TO MEET VA
3.
BATHROOM UPGRADES| HAMPTON, VIRGINIA
3.
BATHROOM UPGRADES| HAMPTON, VIRGINIA
02.28.19
3.
BATHROOM UPGRADES| HAMPTON, VIRGINIA
02.28.19
BUILDING 110
THIS ROOM CANNOT
BE MADE ADA
ACCESSIBLE.
MANEUVERING
CLEARANCES
OVERLAP IN THIS
ROOM
4’-0” DOOR
TO MEET VA
3.
BATHROOM UPGRADES| HAMPTON, VIRGINIA
3.
BATHROOM UPGRADES| HAMPTON, VIRGINIA
02.28.19
3.
BATHROOM UPGRADES| HAMPTON, VIRGINIA
02.28.19
BUILDING 110
MANEUVERING
CLEARANCES
OVERLAP IN THIS
ROOM
THIS ROOM CANNOT
BE MADE ADA
ACCESSIBLE.
4’-0” DOOR
TO MEET VA
3.
BATHROOM UPGRADES| HAMPTON, VIRGINIA
3.
BATHROOM UPGRADES| HAMPTON, VIRGINIA
02.28.19
3.
BATHROOM UPGRADES| HAMPTON, VIRGINIA
02.28.19
BUILDING 110
THIS ROOM CANNOT
BE MADE ADA
ACCESSIBLE.
MANEUVERING
CLEARANCES
OVERLAP IN THIS
ROOM
4’-0” DOOR
TO MEET VA
3.
BATHROOM UPGRADES| HAMPTON, VIRGINIA
3.
BATHROOM UPGRADES| HAMPTON, VIRGINIA
02.28.19
3.
BATHROOM UPGRADES| HAMPTON, VIRGINIA
02.28.19
BUILDING 110
THIS ROOM CANNOT
BE MADE ADA
ACCESSIBLE.
MANEUVERING
CLEARANCES
OVERLAP IN THIS
ROOM
4’-0” DOOR
TO MEET VA
3.
BATHROOM UPGRADES| HAMPTON, VIRGINIA
3.
BATHROOM UPGRADES| HAMPTON, VIRGINIA
02.28.19
3.
BATHROOM UPGRADES| HAMPTON, VIRGINIA
02.28.19
BUILDING 110
PROPOSED
THIS ROOM CANNOT
BE MADE ADA
ACCESSIBLE.
MANEUVERING
CLEARANCES
OVERLAP IN THIS
ROOM
4’-0” DOOR
TO MEET VA
3.
BATHROOM UPGRADES| HAMPTON, VIRGINIA
02.28.19
3.
BATHROOM UPGRADES| HAMPTON, VIRGINIA
02.28.19
BUILDING 110
THIS ROOM CANNOT
BE MADE ADA
ACCESSIBLE.
MANEUVERING
CLEARANCES
OVERLAP IN THIS
ROOM
4’-0” DOOR
TO MEET VA
3.
BATHROOM UPGRADES| HAMPTON, VIRGINIA
3.
BATHROOM UPGRADES| HAMPTON, VIRGINIA
02.28.19
3.
BATHROOM UPGRADES| HAMPTON, VIRGINIA
02.28.19
BUILDING 110
PROPOSED
THIS ROOM CANNOT
BE MADE ADA
ACCESSIBLE.
MANEUVERING
CLEARANCES
OVERLAP IN THIS
ROOM
4’-0” DOOR
TO MEET VA
3.
BATHROOM UPGRADES| HAMPTON, VIRGINIA
3.
BATHROOM UPGRADES| HAMPTON, VIRGINIA
02.28.19
3.
BATHROOM UPGRADES| HAMPTON, VIRGINIA
02.28.19
BUILDING 110
PROPOSED
THIS ROOM CANNOT
BE MADE ADA
ACCESSIBLE.
MANEUVERING
CLEARANCES
OVERLAP IN THIS
ROOM
4’-0” DOOR
TO MEET VA
3.
BATHROOM UPGRADES| HAMPTON, VIRGINIA
3.
BATHROOM UPGRADES| HAMPTON, VIRGINIA
02.28.19
3.
BATHROOM UPGRADES| HAMPTON, VIRGINIA
02.28.19
BUILDING 110
PROPOSED
THIS ROOM CANNOT
BE MADE ADA
ACCESSIBLE.
MANEUVERING
CLEARANCES
OVERLAP IN THIS
ROOM
4’-0” DOOR
TO MEET VA
3.
BATHROOM UPGRADES| HAMPTON, VIRGINIA
3.
BATHROOM UPGRADES| HAMPTON, VIRGINIA
3.
BATHROOM UPGRADES| HAMPTON, VIRGINIA
02.28.19
3.
BATHROOM UPGRADES| HAMPTON, VIRGINIA
02.28.19
3.
BATHROOM UPGRADES| HAMPTON, VIRGINIA
3.
BATHROOM UPGRADES| HAMPTON, VIRGINIA
02.28.19
3.
BATHROOM UPGRADES| HAMPTON, VIRGINIA
02.28.19
3.
BATHROOM UPGRADES| HAMPTON, VIRGINIA
3.
BATHROOM UPGRADES| HAMPTON, VIRGINIA
3.
BATHROOM UPGRADES| HAMPTON, VIRGINIA
02.28.19
BUILDING 110
EXISTING
STALL TO BE
REMOVED TO BE ADA
ACCESSIBLE
WALL TO BE
REMOVED TO MAKE
SPACE ACCESSIBLE
3.
BATHROOM UPGRADES| HAMPTON, VIRGINIA
02.28.19
BUILDING 110
PROPOSED
THIS ROOM CAN BE
MADE ACCESSIBLE IF
ADJACENT SPACE IS
ABLE TO BE USED TO
MAKE MORE ROOM
3’-0” DOOR
3.
BATHROOM UPGRADES| HAMPTON, VIRGINIA
3.
BATHROOM UPGRADES| HAMPTON, VIRGINIA
02.28.19
BUILDING 110
BUILDING 110 SUMMARY
ROOM BG16B, BG19, DG05D.1, *B201, B219, B412, B417B1, *B423A,
B433, C401A, C401B, C503, C505, C602, The clearances meet ADA Requirements
ROOM BG16N.1, DG10.C, DG05C.1, DG05E, DG05H.1, DG05J.1, DG20A,
B205A, B216, D203A, D207A, B413, B417A1, D402A, D403A, D404A, D411A, D412A1, D414A, D415A1, D415B1, D416A, D418A, D419A1, D419B1, D420A, D422A, D423A1, D423B1, D428A, D429A, D430A, The clearances do not meet ADA requirements.
AS DIRECTED BY THE VA, BATHROOMS THAT CANNOT MEET
ACCESSIBILITY REQUIREMENTS WILL ONLY RECEIVE NEW
FINISHES AND FIXTURES
*ROOM B201, B423A
In order to make these bathrooms accessible the fi xture count was reduced.